Eng
Eng
2O
Features Assembly
Function PWR
LED green:
Power supply
Application
Connection
122581_eng.xml
KFD2-STC4-Ex1.2O
1+ 7-
HART
I
HART
2- 8+
Date of issue 2014-12-01
9
mA 250
3
10-
5-
HART
II
11+
HART
12
Release date 2014-12-01 16:23
mA 250
6+ 14+
15-
24 V DC
Zone 0, 1, 2 24 V DC Zone 2
Div. 1, 2 Power Rail Div. 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data KFD2-STC4-Ex1.2O
General specifications
Signal type Analog input
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage UN 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.9 W
Power consumption 2.5 W
Input
Connection terminals 1+, 2-, 3 or 5-, 6+
Input signal 0/4 ... 20 mA
Voltage drop 2.4 V at 20 mA (terminals 5, 6)
Input resistance 76 terminals 2-, 3 ; 500 terminals 1+, 3 (250 load)
Available voltage 16 V at 20 mA terminals 1+, 3
Output
Connection terminals 7-, 8+,9; 10-, 11+,12
Load 0 ... 550
Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple 50 A rms
Transfer characteristics
Deviation at 20 C (68 F), 0/4 ... 20 mA
10 A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature 0.25 A/K
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Settling time 200 s
Rise time/fall time 20 s
Electrical isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Output/Output functional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -20 ... 60 C (-4 ... 140 F)
Mechanical specifications
Degree of protection IP20
Mass approx. 200 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
122581_eng.xml
Voltage Uo 25.4 V
Current Io 86.8 mA
Power Po 551 mW
Equipment terminals 2-, 3
Current Io/Current Ii 74 mA / 115 mA
Current Ii 115 mA
Voltage Uo 3.5 V
Release date 2014-12-01 16:23
Current Io 74 mA
Power Po 64 mW
Equipment terminals 1+, 2 / 3-
Voltage Ui 30 V
Current Ii 115 mA
Voltage Uo 25.4 V
Current Io 115 mA
Power Po 584 mW
Equipment terminals 5-, 6+
Voltage Ui 30 V
Current Ii 115 mA
Voltage Uo 8.7 V
Current Io 0 mA
Output
Maximum safe voltage Um 250 V (Attention! The rated voltage can be lower.)
EC-Type Examination Certificate DMT 01 ATEX E 133
Group, category, type of protection I (M1) [Ex ia] I
Statement of conformity TV 99 ATEX 1499 X , observe statement of conformity
Group, category, type of protection, II 3G Ex nA II T4 [device in zone 2]
temperature class
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
UL approval
Control drawing 116-0173 (cULus)
IECEx approval IECEx BAS 04.0016
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Note Both output loads must be connected to ensure complete and correct operation within the technical
specification.
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
Accessories
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
122581_eng.xml
Date of issue 2014-12-01
Release date 2014-12-01 16:23