Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Assembly Features: Removable Terminals Green

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Transmitter Power Supply/Converter KFU8-VCR-1

Features Assembly

• 1-channel signal conditioner


• Universal usage at different power supplies
Front view
• Input 2-wire and 3-wire transmitters, current and voltage Removable terminals
sources green
• Current and voltage output
1 2 3
4 5 6

Function
KFU8-VCR-1

This signal conditioner provides the isolation for non-


PWR
LED green:
intrinsically safe applications. Switch S1 S1 I II Power supply
Output 901
The device supplies 2-wire and 3-wire transmitters, and can

23
78
S2
456
also be used with current and voltage sources. Switch S2
The input ranges include 0/4 mA ... 20 mA or 0/2 V ... 10 V. Measuring range

At the output the signal is available as 0/4 mA ... 20 mA or 7 8 9

0/2 V ... 10 V.
10 11 12
13 14 15

Output and measuring range are selected by switches located


on the front of the device.
Removable terminals
green

Connection
211535_eng.xml

KFU8-VCR-1

1+ 7
Date of issue 2017-08-09

2- 8+ mA I
mA V
9-
3
10-
5- II
11+ V
V
Release date 2017-08-09 14:10

6+

14
15
AC/DC

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data KFU8-VCR-1

General specifications
Signal type Analog input
Supply
Connection terminals 14, 15
Rated voltage Ur 19 ... 90 V DC / 48 ... 253 V AC
Rated current Ir ≤ 110 mA DC / ≤ 75 mA AC
Power dissipation 1.3 W
Power consumption 2.1 W
Input
Connection side field side
Input I
Connection terminals 1+, 2-, 3
Input signal 0/4 ... 20 mA
Rated current 22 mA
Available voltage > 15 V at 20 mA , terminals 1+, 3-
Open circuit voltage/short-circuit 21 V / 26 mA , terminals 1+, 3-
current terminals 1+, 2- not short-circuit protected
Input resistance < 55 Ω , terminals 2-, 3+
Input II
Connection terminals 5-, 6+
Input signal 0/2 ... 10 V
Input resistance > 1 MΩ
Output
Connection side control side
Output I current output
Connection source: terminals 7(-), 8(+)
sink: terminals 7(+), 9(-)
Output signal 0/4 ... 20 mA
Source load 0 ... 750 Ω open circuit voltage < 21 V
Sink voltage across terminals 5 ... 30 V
Output II voltage output
Connection terminals 10-, 11+
Output signal 0/2 ... 10 V
Load ≥ 10 kΩ
Transfer characteristics
Deviation
Resolution/accuracy S1 in position I: 7 µA/40 µA (0.2 %)
S1 in position II: 3.5 mV/20 mV (0.2 %)
Influence of ambient temperature 0.01 % / K of output signal range
Reaction time 150 ms
Galvanic isolation
Input/Output functional insulation acc. to IEC 62103, rated insulation voltage 100 Vrms
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LED
Control elements DIP-switch
rotary switch
211535_eng.xml

Configuration via DIP switches


via rotary switch
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Date of issue 2017-08-09

Directive 2004/108/EC EN 61326-1:2006


Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529
Release date 2017-08-09 14:10

Protection against electrical shock IEC 61140


Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
2
Technical data KFU8-VCR-1

Mass approx. 150 g


Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For
information see www.pepperl-fuchs.com.
211535_eng.xml
Date of issue 2017-08-09
Release date 2017-08-09 14:10

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
3
Technical data KFU8-VCR-1

Configuration

Switch S1 (output)
Position Signal
I Current output
II Voltage output
1 2 3
4 5 6

Switch S2 (measuring range)


PWR

S1 I II Position Input Output I Output II


S1 I II
0 4 mA ... 20 mA 4 mA ... 20 mA 2 V ... 10 V
901 901 1 4 mA ... 20 mA 0 mA ... 20 mA 0 V ... 10 V
23
78

S2
23
78

S2 2 0 mA ... 20 mA 4 mA ... 20 mA 2 V ... 10 V


456
456
3 0 mA ... 20 mA 0 mA ... 20 mA 0 V ... 10 V
4 2 V ... 10 V 4 mA ... 20 mA 2 V ... 10 V
7 8 9 5 2 V ... 10 V 0 mA ... 20 mA 0 V ... 10 V
10 11 12
13 14 15 6 0 V ... 10 V 4 mA ... 20 mA 2 V ... 10 V
7 0 V ... 10 V 0 mA ... 20 mA 0 V ... 10 V
8 not used
9 not used

Factory settings: switch S1 in position I


switch S2 in position 3
211535_eng.xml
Date of issue 2017-08-09
Release date 2017-08-09 14:10

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
4