Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Assembly Features: Removable Terminal Blue

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Switch Amplifier KFD2-SR2-Ex1.

Features Assembly

• 1-channel isolated barrier


• 24 V DC supply (Power Rail)
Front view
• Dry contact or NAMUR inputs
Removable terminal
• Relay contact output blue
• Line fault detection (LFD)
• Reversible mode of operation
1 2 3
4 5 6

• Up to SIL2 acc. to IEC 61508/IEC 61511 LED yellow: KFD2-SR2-Ex1.W


LED green:
Relay output Power supply
Function OUT CHK PWR

LED red: Switch S1


S1

This isolated barrier is used for intrinsic safety applications. It


LB/SC S2 (mode of operation)
S3

transfers digital signals (NAMUR sensors/mechanical I II


Switch S2
contacts) from a hazardous area to a safe area. (no functions)
The proximity sensor or switch controls a form C changeover 7 8 9

relay contact for the safe area load. The barrier output
10 11 12 Switch S3
13 14 15
(LB/SC-monitoring)
changes state when the input signal changes state. The
normal output state can be reversed using switch S1. Removable terminals
green
Switch S3 is used to enable or disable line fault detection of
the field circuit.
During an error condition, the relay reverts to its de-energized
state and the LEDs indicate the fault according to
NAMUR NE44.
A unique collective error messaging feature is available when
used with the Power Rail system.

Connection
132958_eng.xml

KFD2-SR2-Ex1.W

1+ 7
8
10 kΩ 2+ 9
10 kΩ
Date of issue 2014-08-19

3-
400 Ω ≤ R ≤ 2 kΩ
Release date 2014-08-19 09:56

14+
15-
24 V DC

Zone 0, 1, 2 ERR 24 V DC Zone 2


Div. 1, 2 Power Rail Div. 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data KFD2-SR2-Ex1.W

General specifications
Signal type Digital Input
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 20 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 30 mA
Power loss 0.7 W
Power consumption < 0.9 W
Input
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
Output
Connection terminals 7, 8, 9
Output signal ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency < 10 Hz
Electrical isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
132958_eng.xml

EC-Type Examination Certificate PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
Input [Ex ia] IIC, [Ex ia] IIIC
Voltage Uo 10.5 V
Current Io 13 mA
Date of issue 2014-08-19

Power Po 34 mW (linear characteristic)


Supply
Maximum safe voltage Um 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Release date 2014-08-19 09:56

Maximum safe voltage Um 253 V AC (Attention! The rated voltage can be lower.)
Error message output
Maximum safe voltage Um 40 V DC (Attention! Um is no rated voltage.)
Statement of conformity PF 08 CERT 0803
Group, category, type of protection ¬ II (3)G [Ex ic Gc] IIC
Input [Ex ic] IIC
Voltage Uo 10.5 V

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
2
Technical data KFD2-SR2-Ex1.W

Current Io 13 mA
Power Po 34 mW (linear characteristic)
Output
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Statement of conformity TÜV 99 ATEX 1493 X , observe statement of conformity
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4
temperature class
Output
Contact loading 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0035
CSA approval
Control drawing 116-0047
IECEx approval IECEx PTB 11.0034
Approved for [Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
132958_eng.xml
Date of issue 2014-08-19
Release date 2014-08-19 09:56

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
3
Technical data KFD2-SR2-Ex1.W

Configuration

Switch position
S Function Position
1 Mode of operation with high input current I
Output I (relay) with low input current II
energized
2 no function
1 2 3
4 5 6
3 Line fault detection ON I
OFF II
1
OUT CHK PWR

S1
1
S1
Operating status
1

S2 S2 2
2

S3
3

S3 Control circuit Input signal


3

7 8 9
10 11 12 Initiator high impedance/ low input current
13 14 15
I II contact opened
Initiator low impedance/ high input current
contact closed
Lead breakage, Line fault
lead short-circuit

Factory settings: switch 1, 2 and 3 in position I


132958_eng.xml
Date of issue 2014-08-19
Release date 2014-08-19 09:56

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
4
Technical data KFD2-SR2-Ex1.W

Maximum switching power of output contacts

Resistive load DC Resistive load AC

I (A)
4

2 Electrical life
max. 105 switching cycles
1

0.5 Electrical life


max. 2.5 x 105 switching cycles

0.2

20 40 100 200 U (V)


115 250

The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and
voltages are applied.

Accessories

Power feed module KFD2-EB2


The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.

Power Rail UPR-03


The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.

Profile Rail K-DUCT with Power Rail


The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.

Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
132958_eng.xml
Date of issue 2014-08-19
Release date 2014-08-19 09:56

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
5

You might also like