Rotation Speed Monitor KFD2-DWB-Ex1.

Features Assembly

• 1-channel isolated barrier


• 24 V DC supply (Power Rail) Front view
• Dry contact or NAMUR inputs Removable terminal
blue
• Input frequency 1 mHz ... 5 kHz
• 2 relay contact outputs
• Start-up override
1 2 3 4 5 6
LED green:
LC display
• Configurable by keypad
Power supply KFD2-DWB-
Ex1.D

• Line fault detection (LFD)


1 PWR
IN/
LED yellow/red: CHK
1 2

• Up to SIL 2 acc. to IEC 61508/IEC 61511


Input pulses/ OUT

fault signal ESC

Function LED yellow: OK Keypad


Output I
LED yellow:
This isolated barrier is used for intrinsic safety applications. It Output II Place for labeling
monitors for an overspeed or underspeed condition of a digital 7 8 9
13 14 15
10 11 12
16 17 18
signal (NAMUR sensor/mechanical contact) from a hazardous 19 20 21 22 23 24

area by comparing the input frequency to the user Removable terminals


programmed reference frequency. green

An overspeed or underspeed condition is signaled via the


relay outputs. Line fault detection of the field circuit is indicated
by a red LED, Power Rail and relay. The start-up override
feature sets relay outputs to default conditions programmed
by the user for up to 1,000 seconds.
The unit is easily programmed by the use of a keypad located
on the front of the unit.
A unique collective error messaging feature is available when
used with the Power Rail system.
For additional information, refer to the manual and
www.pepperl-fuchs.com.
2

Connection
231203_eng.xml

KFD2-DWB-Ex1.D

400 Ω ≤ R ≤ 2 kΩ 10
1+ 11 I
12
Date of issue 2017-09-12

10 kΩ 10 kΩ
16
3- 17 II
18

13+
14-
Release date 2017-09-12 15:15

23+
24-
24 V DC

Zone 0, 1, 2 ERR 24 V DC Zone 2


Div. 1, 2 Power Rail Div. 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data KFD2-DWB-Ex1.D

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage Ur 20 ... 30 V DC
Rated current Ir approx. 100 mA
Power dissipation/power consumption ≤ 1.8 W / 1.8 W
Input
Connection side field side
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Pulse duration > 50 µs
Input frequency 0.001 ... 5000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit 18 V / 5 mA
current
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Collective error message Power Rail
Transfer characteristics
Input I
Measurement range 0.001 ... 5000 Hz
Resolution 0.1 % of measured value , ≥ 0.001 Hz
Accuracy 0.1 % of measured value , > 0.001 Hz
Measuring time < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Start-up override/power supply and functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
collective error
Indicators/settings
Display elements LEDs , display
Control elements Control panel
231203_eng.xml

Configuration via operating buttons


Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Date of issue 2017-09-12

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)


Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Release date 2017-09-12 15:15

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)


Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
2
Technical data KFD2-DWB-Ex1.D

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Data for application in connection
with hazardous areas
EU-Type Examination Certificate TÜV 99 ATEX 1408
Marking ¬ II (1)G [Ex ia Ga] IIC
¬ II (1)D [Ex ia Da] IIIC
¬ I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage Um 40 V DC (Attention! Um is no rated voltage.)
Input I terminals 1+, 3-: Ex ia
Voltage Uo 10.1 V
Current Io 13.5 mA
Power Po 34 mW (linear characteristic)
Input II terminals 13+, 14- non-intrinsically safe
Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.)
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)

Certificate TÜV 02 ATEX 1885 X


Marking ¬ II 3G Ex nA nC IIC T4 Gc
Output I, II
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation
Input I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 16-538FM-12
UL approval E223772
IECEx approval IECEx TUN 03.0000
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For
information see www.pepperl-fuchs.com.

Maximum Switching Power of Output Contacts

I (A)
4
3

1
1
0.5
231203_eng.xml

0.4
0.3

0.2
0.15
Date of issue 2017-09-12

0.1

0 50 100 150 200 250 U (V)

Resistive load DC
Resistive load AC
1 max. 105 switching cycles
Release date 2017-09-12 15:15

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
3
Technical data KFD2-DWB-Ex1.D

Accessories

Power feed module KFD2-EB2


The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.

Power Rail UPR-03


The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.

Profile Rail K-DUCT with Power Rail


The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.

Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
231203_eng.xml
Date of issue 2017-09-12
Release date 2017-09-12 15:15

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
4

You might also like