KFD2 DWB Ex1.D
KFD2 DWB Ex1.D
KFD2 DWB Ex1.D
Features Assembly
Connection
231203_eng.xml
KFD2-DWB-Ex1.D
400 Ω ≤ R ≤ 2 kΩ 10
1+ 11 I
12
Date of issue 2017-09-12
10 kΩ 10 kΩ
16
3- 17 II
18
13+
14-
Release date 2017-09-12 15:15
23+
24-
24 V DC
General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage Ur 20 ... 30 V DC
Rated current Ir approx. 100 mA
Power dissipation/power consumption ≤ 1.8 W / 1.8 W
Input
Connection side field side
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Pulse duration > 50 µs
Input frequency 0.001 ... 5000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit 18 V / 5 mA
current
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Collective error message Power Rail
Transfer characteristics
Input I
Measurement range 0.001 ... 5000 Hz
Resolution 0.1 % of measured value , ≥ 0.001 Hz
Accuracy 0.1 % of measured value , > 0.001 Hz
Measuring time < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Start-up override/power supply and functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
collective error
Indicators/settings
Display elements LEDs , display
Control elements Control panel
231203_eng.xml
I (A)
4
3
1
1
0.5
231203_eng.xml
0.4
0.3
0.2
0.15
Date of issue 2017-09-12
0.1
Resistive load DC
Resistive load AC
1 max. 105 switching cycles
Release date 2017-09-12 15:15
Accessories
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
231203_eng.xml
Date of issue 2017-09-12
Release date 2017-09-12 15:15