KCD2-SR-1.LB SW Amp PDF
KCD2-SR-1.LB SW Amp PDF
KCD2-SR-1.LB SW Amp PDF
LB
Features Assembly
S1
S2
system.
5 6
The proximity sensor or switch controls a form A normally 7 8
9 10 Place for labeling
open relay contact for the load. The normal output state is
reversed using switch S1. Switch S2 allows output II to be
switched between a signal output and an error message Removable terminals
output. Switch S3 enables or disables line fault detection of green
the field circuit.
During an error condition, relays revert to their de-energized
state and LEDs indicate the fault according to NAMUR NE44.
A unique collective error messaging feature is available when
used with the Power Rail system.
Due to its compact housing design and low heat dissipation,
this device is useful for detecting positions, end stops, and
switching states in space-critical applications.
Connection
Release date 2010-11-04 14:00 Date of issue 2010-11-04 216713_ENG.xml
KCD2-SR-1.LB
1+ 5
10 k I
2- 6
400 R 2 k
7
II
8
9+
10-
24 V DC
ERR 24 V DC
Power Rail
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 1
Technical data KCD2-SR-1.LB
General specifications
Signal type Digital input
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30 V DC
Ripple 10 %
Rated current 30 mA
Power loss 500 mW
Power consumption 500 mW
Input
Connection terminals 1+, 2-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA , short-circuit I 6.5 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
Connection output I: terminals 5, 6 ; output II: terminals 7, 8
Output I signal ; relay
Output II signal or error message ; relay
Contact loading 253 V AC/2 A/cos > 0.7; 126.5 V AC/4 A/cos > 0.7; 30 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay 20 ms / 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency 10 Hz
Electrical isolation
Input/Output reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
Indicators/settings
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 50178:1997
Conformity
Electromagnetic compatibility NE 21
Protection degree IEC 60529
Protection against electric shock IEC 61140
Ambient conditions
Ambient temperature -20 ... 60 C (-4 ... 140 F)
Mechanical specifications
Protection degree IP20
Mass approx. 100 g
Release date 2010-11-04 14:00 Date of issue 2010-11-04 216713_ENG.xml
Dimensions 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , housing type A2
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be
observed where applicable. For information see www.pepperl-fuchs.com.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 2
Technical data KCD2-SR-1.LB
Configuration
Switch position
S Function Position
1 Mode of operation with high input current I
Output I (relay) with low input current II
1 2 energized
3 4
2 Assignment switching state like relay I I
Output II (relay) fault signal output II
(de-energized if fault)
3 Line fault detection ON I
OFF II
1 4 no function
1
S
2 2
3
4
I II
3 Operating status
4
Control circuit Input signal
5
7
6
8
I II Initiator high impedance/ low input current
9 10 contact opened
Initiator low impedance/ high input current
contact closed
Lead breakage, Line fault
lead short-circuit
Accessories
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
Release date 2010-11-04 14:00 Date of issue 2010-11-04 216713_ENG.xml
Attention
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 3