Technical data KFD0-RSH-1.4S.PS2
General specifications
Signal type Digital Output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
Supply
Rated voltage Ur loop powered
Power dissipation < 1.5 W
Power consumption < 1.5 W
Input
Connection side control side
Connection Input terminals 7, 8 ; test input terminals 10, 11, 12
Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
Test input see Functional Safety Manual
Signal level 0-signal: -3 ... 3 V DC
1-signal: 20 ... 26.5 V
Rated current Ir 45 ... 50 mA
Output
Connection side field side
Connection output I (ETS): terminals 2, 3
output II (DTS): terminals 4, 5, 6
output I and II (DPS): terminals 2, 3, 4, 5, 6
Contact loading 253 V AC/5 A/cos φ 0.7; 30 V DC/5 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay approx. 10 ms / approx. 5 ms
Mechanical life 5 x 106 switching cycles
Fuse rating 2.5 A (max. 5 A)
recommended maximum utilization of the fuse: 80 %
Transfer characteristics
Switching frequency < 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2012
Degree of protection IEC 60529:2013
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
224579_eng.xml
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For
information see www.pepperl-fuchs.com.
2
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFD0-RSH-1.4S.PS2
Derating
I I
(A) (A)
5 5
4 4
3 3
2 2
1 1
0 10 20 30 40 50 60 70 T 0 10 20 30 40 50 60 70 T
(°C) (°C)
≥ 10 mm ≥ 10 mm
fused 5 AT unfused
fused 5 AT, 10 mm unfused, 10 mm
Ui 26.5 V Ui 26.5 V
I I
(A) (A)
5 5
4 4
3 3
2 2
1 1
0 10 20 30 40 50 60 70 T 0 10 20 30 40 50 60 70 T
(°C) (°C)
≥ 10 mm ≥ 10 mm
fused 5 AT unfused
fused 5 AT, 10 mm unfused, 10 mm
Ui 26.5 V Ui 26.5 V
224579_eng.xml
Date of issue 2019-01-14
Release date 2019-01-14 10:15
3
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFD0-RSH-1.4S.PS2
I (A)
5
4
3
1
2
0.5 2
0.4
0.3
0.2
0.1
0 50 100 150 200 250 U (V)
Resistive load DC
Resistive load AC
1 max. 105 switching cycles
2 max. 3 x 104 switching cycles
224579_eng.xml
Date of issue 2019-01-14
Release date 2019-01-14 10:15
4
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com