Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Assembly Features: Front View

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Redundant Power Feed Module KFD2-EB2.R4A.

Features Assembly

• Interface for Power Rail


• Used for redundant configuration
Front view
• Supply current ≤ 4 A
• Replaceable fuse
• Relay contact output, reversible
• LED status indication
1 2 3
4 5 6

LED red:
Function Fault signal KFD2-EB2.R4A.B

Switch S1
ERR PWR mode of operation
The power feed module supplies the Power Rail with a voltage
S1 I II
LED green: Position I: NO
Power supply 5 AT
Position II: NC
of 24 V DC and a maximum current of 4 A. The device is
designed for applications requiring redundant power. !

In the event of a device fault or a wiring fault of any isolator on Fuse carrier
the Power Rail, the collective error messaging relay alerts the 7 8 9

controller via a binary I/O point. This relay can be configured 10 11 12


13 14 15

as normally-open or normally-closed.
A green LED on the front of the device indicates the power
state, and a red LED lights up during a fault condition. Removable terminals
green
Additionally, the bus implemented in the Power Rail is
forwarded to the terminals 13 and 15 for usage with the RS-
485 connection of the KFD2-WAC2-Ex1.D device.
Terminal 14 is only for test purposes.
In the sense of functional safety (SIL) the device provides no
dangerous failures. Thereby the safe condition of the supplied
isolators must be defined as the de-energized state. Thus the
device will not influence the safety calculation or the SIL value.
This device is compatible with all versions of the Power Rail
and provides group fusing.
Note: Redundant systems require 2 KFD2-EB.R4A.B
power feed modules.

Connection
189784_eng.xml

KFD2-EB2.R4A.B

10
Date of issue 2019-04-02

14 ERR
13
BUS
15

5 AT
8+
Release date 2019-04-02 15:54

11+
24 V DC
9-
12-

BUS ERR 24 V DC Zone 2


Power Rail

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

1
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFD2-EB2.R4A.B

Supply
Connection terminals 11+, 12-
terminals 8+, 9-
Rated voltage Ur 20 ... 30 V DC
The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded.
Fusing 5A
recommended maximum utilization of the fuse: 80 %
Power dissipation ≤ 2.4 W
Output
Connection Power Rail
Output rated operating current ≤4A
Output voltage 24 V DC
Fault signal relay output: NO contact
Contact loading 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Indicators/settings
Display elements LEDs
Control elements DIP-switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with hazardous areas
Certificate TÜV 00 ATEX 1618 X
Marking ¬ II 3G Ex nA nC IIC T4
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0160
IECEx approval IECEx UL 16.0051X
Approved for Ex nA nC IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For
information see www.pepperl-fuchs.com.
189784_eng.xml

Accessories
Optional accessories - universal power rail UPR-03(-M)(-S)
- universal power rail UPR-05(-S)
- profile rail K-DUCT-GY(-UPR-03)
- profile rail K-DUCT-GY(-UPR-05)
Date of issue 2019-04-02

- profile rail K-DUCT-BU(-UPR-03)


- profile rail K-DUCT-BU(-UPR-05)
Release date 2019-04-02 15:54

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

2
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

You might also like