Assembly Features: Front View
Assembly Features: Front View
Assembly Features: Front View
Features Assembly
S1
This isolated barrier is used for intrinsic safety applications. It LED red: S2
S3
Switch S1
LB/SC channel I
transfers digital signals (NAMUR sensors/mechanical I II (Mode of operation channel I)
relay contact for the safe area load. The normal output state
10 11 12
13 14 15
LED red:
can be reversed using switches S1 and S2. Switch S3 is used
Switch S3
LB/SC channel II (LB/SC-monitoring)
to enable or disable line fault detection of the field circuit.
Removable terminals
During an error condition, the relays revert to their de- green
energized state and the LEDs indicate the fault according to
NAMUR NE44.
Connection
103373_eng.xml
KFA6-SR2-Ex2.W
1+ 7
8 I
I 10 kΩ 2+ 9
10 kΩ
Date of issue 2019-01-24
3-
400 Ω ≤ R ≤ 2 kΩ
4+ 10
11 II
II 10 kΩ 5+ 12
10 kΩ
6-
400 Ω ≤ R ≤ 2 kΩ
Release date 2019-01-24 13:56
14
15
230 V AC
Zone 0, 1, 2
Div. 1, 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
1
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFA6-SR2-Ex2.W
General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 14, 15
Rated voltage Ur 207 ... 253 V AC, 45 ... 65 Hz
Power dissipation 1.2 W
Power consumption ≤ 1.3 W
Input
Connection side field side
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
Output
Connection side control side
Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, II signal ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency ≤ 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
103373_eng.xml
Current Io 19.1 mA
Power Po 51 mW (linear characteristic)
Supply
Maximum safe voltage Um 253 V AC (Attention! Um is no rated voltage.)
Output
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
2
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFA6-SR2-Ex2.W
Maximum safe voltage Um 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/input not available
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
FM approval
Control drawing 116-0035
UL approval
Control drawing 116-0145
CSA approval
Control drawing 116-0047
IECEx approval IECEx PTB 11.0031
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For
information see www.pepperl-fuchs.com.
103373_eng.xml
Date of issue 2019-01-24
Release date 2019-01-24 13:56
3
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFA6-SR2-Ex2.W
Configuration
Switch position
S Function Position
1 Mode of operation with high input current I
Output I (relay) with low input current II
energized
2 Mode of operation with high input current I
1
4
2
5
3
6
Output II (relay) with low input current II
energized
1 3 Line fault detection ON I
OFF II
OUT CHK PWR
2
S1
1
S1
1
S2 S2
2
2
S3
Operating status
3
S3
3
7 8 9
10 11 12
13 14 15
I II Control circuit Input signal
Initiator high impedance/ low input current
contact opened
Initiator low impedance/ high input current
contact closed
Lead breakage, Line fault
lead short-circuit
4
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Technical data KFA6-SR2-Ex2.W
I (A)
4
2 Electrical life
max. 105 switching cycles
1
0.2
The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and
voltages are applied.
103373_eng.xml
Date of issue 2019-01-24
Release date 2019-01-24 13:56
5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com