KFD0 Ro Ex2
KFD0 Ro Ex2
Features Assembly
Removable terminal
green
Connection
038975_eng.xml
KFD0-RO-Ex2
1 7
I 3 I
2 V
Date of issue 2016-05-16
4 8 (+/-)
II II
6
9
5
Release date 2016-05-15 23:27
Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data KFD0-RO-Ex2
General specifications
Signal type Digital Output
Supply
Power dissipation 0.8 W
Input
Connection terminals 7, 8, 9
Input voltage 15 ... 30 V DC
Input current 21 mA per channel
Output
Safety note Attention! Combination of output Ex i with output not Ex i is not permitted.
If load voltage > 50 V, de-energize before removing the terminals.
Connection terminals 1, 2, 3; 4, 5, 6
Contact loading 230 V AC/2 A/cos > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay approx. 10 ms / approx. 5 ms
Mechanical life 5 x 106 switching cycles
Transfer characteristics
Switching frequency < 10 Hz
Electrical isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 65 C (-4 ... 149 F)
Mechanical specifications
Degree of protection IP20
Mass approx. 100 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate DMT 00 ATEX E 016
Group, category, type of protection II (1)GD [Ex ia] IIC , [Ex iaD] , I (M1) [Ex ia] I
Output Ex ia
Voltage Ui 60 V
Current Ii 2A
Input
Maximum safe voltage Um 40 V DC (Attention! Um is no rated voltage.)
Output
Contact loading 50 V AC/2 A ; 40 V DC/2 A (TV 00 ATEX 1621 X)
Statement of conformity TV 00 ATEX 1621 X
Group, category, type of protection, II 3G Ex nA nC IIC T4
038975_eng.xml
temperature class
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V
Date of issue 2016-05-16
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000
International approvals
CSA approval
Control drawing 116-0156
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Release date 2016-05-15 23:27
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
I (A)
4
2 Electrical life
max. 105 switching cycles
1
0.6
0.5
0.3
0.2
The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and
voltages are applied.
038975_eng.xml
Date of issue 2016-05-16
Release date 2016-05-15 23:27