Switch Amplifier KFA6-SR2-Ex1.W.LB: Function
Switch Amplifier KFA6-SR2-Ex1.W.LB: Function
Switch Amplifier KFA6-SR2-Ex1.W.LB: Function
KFA6-SR2-Ex1.W.LB
< 1-channel isolated barrier
< 230 V AC supply
< Dry contact or NAMUR inputs
< Relay contact output
< Fault relay contact output
< Line fault detection (LFD)
< Reversible mode of operation
< Up to SIL 2 acc. to IEC 61508/IEC 61511
Function
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous
area to a safe area.
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The normal output state can be reversed using
switch S1. Switch S2 allows output II to be switched between a signal output or an error message output. Switch S3 is used to enable or disable
line fault detection of the field circuit.
During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.
Connection
KFA6-SR2-Ex1.W.LB
1+ 7
8 I
10 k̀ 2+ 9
10 k̀
3-
400 Ω ≤ R ≤ 2 kΩ
10
11 II
12
14
15
230 V AC
Release date: 2022-01-10 Date of issue: 2022-01-10 Filename: 103375_eng.pdf
Zone 0, 1, 2
Div. 1, 2
Technical Data
General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 14, 15
Rated voltage Ur 207 ... 253 V AC, 45 ... 65 Hz
Power dissipation 1.2 W
Power consumption max. 1.3 W
Input
Assembly
Front view
Removable terminal
blue
1 2 3
4 5 6
I II
Switch S2
(output selection II)
7 8 9
Release date: 2022-01-10 Date of issue: 2022-01-10 Filename: 103375_eng.pdf
10 11 12
13 14 15
Switch S3
(LB/SC-monitoring)
Removable terminals
green
Configuration
1 2 3
4 5 6
1
OUT CHK PWR
S1
1
S1
1
S2 S2
2
2
S3
3
S3
3
7 8 9
10 11 12
13 14 15
I II
Switch position
S Function Position
1 Mode of operation output I (relay) energized with high input current I
with low input current II
2 Assignment output II (relay) Switching state like output I I
Fault indication output (de-energized if fault) II
3 Line fault detection ON I
OFF II
Operating states
Characteristic Curve
Maximum switching power of output contacts
5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Switch Amplifier KFA6-SR2-Ex1.W.LB
Resistive load DC Resistive load AC
I (A)
4
2 Electrical life
max. 105 switching cycles
1
0.2
The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and
voltages are applied.
Release date: 2022-01-10 Date of issue: 2022-01-10 Filename: 103375_eng.pdf