Type M220 Communicating Measurement Centre: Features Application
Type M220 Communicating Measurement Centre: Features Application
Type M220 Communicating Measurement Centre: Features Application
Features Application
• Single phase or three-phase M220 applications include;
connection
• Accurate monitoring of
• Balanced or unbalanced load instantaneous and integrated
• True rms measurements values
• Active and reactive energy • Active energy measurement to
metering IEC 61036 class 1.0
• Two line LCD display • Replacement of separate energy
meters and instrumentation in
• Pulsed outputs available
cost-sensitive applications
• Four quadrant power
• Distributed monitoring using an
measurements
integrated system
• Setting of VT and CT ratios Figure 1: M220
The M220 is intended for use on
• MODBUS Communications over systems where energy monitoring
RS485 or RS232. and instrumentation are required,
• Power factor CosΦa, CosΦb,
• Demand values for current, providing volts, amps, watts, VArs,
CosΦc, CosΦt
active, reactive and apparent VA, power factor and frequency, as
power well as metering for active and • Phase voltage Ua, Ub,
reactive power. Demand values for Uc, U
• Real time clock with battery
current, active, reactive and
backup • Line voltage Uab, Ubc,
apparent power are also provided.
• Compact and rugged design Uca, U∆
In this application, the M220 can
provide a more cost-effective • Current Ia, Ib,
Introduction solution than using separate Ic, In
devices, saving on hole-punching • Frequency
The M220 Communicating
and wiring costs as well as the more
Measurement Centre uses numerical
obvious device cost and panel Demand values
technology to achieve high
space savings. The M220 can also • Total current
accuracy over a wide dynamic
enable system-level access for all
measuring range. It measures • Total active power
parameters and settings using
energy, demand and instantaneous
MODBUS RTU communications over • Total reactive power
values for single or three phase
either RS485 or RS232 connections.
systems, and can be linked into a • Total apparent power
system using the MODBUS protocol.
Housed in a DIN 144mm by Functions Demand calculation
144mm by 117mm (max) case, the The M220 is able to calculate
Instantaneous measurements
M220 is compact, rugged and ideal demand values using thermal, fixed
for panel mounting in power • Active power Pa, Pb, or sliding window algorithms.
distribution or power monitoring Pc, Pt
systems. Energy
• Reactive power Qa, Qb,
Qc, Qt • Active energy Whtotal
2
u v
1
11
U V 3
Load
A
K L
Figure 2: mode_1b
Typical diagram - single
phase connection
N
Notes: Connect two wire auxiliary supply terminals marked ‘supply’ if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.
u v u v
U V U V 3
2 5 8
Load
A
K L
Figure 3: mode_3b
Typical diagram - three phase, B
three wire balanced load
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.
u v 1
3 11
2
U V
Out 1 Out 2 Comms Supply
k l
Load
A
K L
Figure 4: mode_4b
Typical diagram - three phase, C
four wire balanced load
N
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.
3
u v u v
1 7
U V U V 3 9
2 5 8
Load
A
K L
k l
Figure 5: mode_3U B
Typical diagram - three phase,
three wire unbalanced load
C
K L
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.
u u u
11
x x x
1 4 7
X X X 3 6 9 11
2 5 8
U U U
k l
A
K L
k l
B
K L
Figure 6: mode_ 4U C
K L
Typical diagram - three
phase, four wire unbalanced N
load
Load
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.
Out
100ms
Figure 7:
Typical connections for pulse
24V DC R>100R
output
Power supply
Pulse receptor
0V
4
Pulsed outputs Technical data • Frequency
There are two pulsed outputs 0.05% of reading
available as an option, which are Voltage input
• Real time clock
set to correspond to the device • Nominal phase to neutral input ±30ppm
energy displays. The pulsed output voltage (Un) * For these values the accuracy is % of
rate can be set using the front panel 63.5V, 120V, 230V nominal for 0....100% of nominal
or remote communications link. (Other voltages in the range of 50V to and % of reading above nominal.
250V phase to neutral are available on **For voltage the accuracy is % of
Remote communications request). nominal for 10…100% of nominal
A rear communications port is and % of reading above nominal.
• Measuring range with separate
provided, which can be specified as
auxiliary supply For voltage range 0…10% Un the
either RS232 or RS485.
10...150% Un maximum error is 2% of nominal
The protocol used is MODBUS RTU. value.
• Burden with separate auxiliary
Configuration supply AC auxiliary supply
<0.1VA (if applicable)
Two password controlled access
levels are available. The following • Rated frequency • Input voltage (Ux – ac only)
settings are password protected; 50Hz/60Hz 63.5V, 120V, 230V
• CT ratio • Frequency range Other voltages in the range of 50V
45Hz to 65Hz to 250V available on request.
• VT primary
• VT secondary • Thermal withstand • Supply voltage range
1.5Un continuously 0.8...1.2 Ux
• System connection 2Un for 10s
• Burden
• Communications parameters
Current input <5VA
• Demand calculation mode
• Rated current (In) • Thermal withstand
• Demand period 1.2Ux continuously
1A or 5A
• Energy meter operation 1.5Ux for 10s
(communications only) • Measuring range
0…160%In • Frequency range
• Energy meter resetting 45Hz to 65Hz
• Burden
• Demand resetting
<0.1VA DC auxiliary supply
• Pulse output configuration (if applicable)
• Thermal withstand
• Clock settings 3In continuously • Input voltage (Ux – dc only)
25In for 3s 24...400V
Hardware description 50In for 1s
• Supply voltage range
The M220 is housed in a DIN case 20...440V
Accuracy
with maximum dimensions of
144mm by 144mm by 117mm. • Active energy • Burden
IEC 61036 Class 1.0 <5VA
Two variants of M220 are
available. For three phase three • Reactive energy Relay outputs
wire unbalanced two element IEC 61268 Class 2.0
• Maximum ac switching power
systems, a unique device is • Voltage 50VA
required. A second model caters for ±0.5% Un **
all other system configurations. • Maximum switching voltage
• Phase current 350V dc or peak ac
The front panel contains a 2 lines by ±0.5% In *
24 character liquid crystal display, • Maximum switching current
with a character size of 4.86mm by • Neutral current 1A
2.96mm. Four pushbuttons provide ±1% of 3 x In *
• Maximum number of pulses
access to the M220’s menu. • Power 4000 per hour
Measuring circuit connections on the ±0.5% *
• Pulse duration
rear are by means of individual M4 • Power factor 100ms
screw clamp terminals. ±0.005
Auxiliary, communications and • Isolation
pulsed output connections use M2.5 • MD values 4kV rms coil to contacts
terminal blocks. ±1% * 1.4kV across contacts
5
Communications port • Insulation resistance The following generic standards
RS485 variant were used to establish conformity.
IEC 60255-5: 1977
• Connection type >100M Ω. EN 50081-2: 1994
Multidrop (32 connections Generic Emission Standard
per link) Electrical environment Part 2: Industrial Environment.
• Cable type • High frequency disturbance
EN 50082-2: 1994
Screened twisted pair IEC 60255-22-1: 1988 Generic Emission Standard
• Cable length Class II and Class III Part 2: Industrial environment
1000m max 2.5kV peak applied between all • Product Safety
• Protocol circuits and earth (except
73/23/EEC
MODBUS RTU communication port).
1kV peak applied between the Compliance with European
RS232 variant Commission Low Voltage
communication port and earth.
• Connection type Directive.
1kV peak applied across the
Point to point EN 61010-1: 1993/A2: 1995
terminals of all circuits (except
• Cable type communication port) Compliance is demonstrated by
Screened multi-core reference to generic safety
• Fast transient disturbance standards.
• Cable length
IEC 61000-4-4: 1995 600V Installation category II,
15m max
Level IV pollution degree II
• Protocol
4kV, 2.5kHz applied directly 300V Installation category III,
MODBUS RTU
between all terminals and earth pollution degree II
High voltage withstand (except communications port)
• Dielectric withstand • Electrostatic discharge Environmental withstand
IEC 60255-5:1977 IEC 60255-22-2 : 1996 Atmospheric environment
Class II
2kV rms for 1 minute between all Temperature and humidity
terminals and earth. 8kV air discharge
JVF (DIN 40 040)
6kV contact discharge
2kV rms for 1 minute between
• Reference range of operation
terminals of independent circuits • AC ripple on dc supply
0°C to 50°C
including the output relay circuits. IEC 60255-11: 1979
• Nominal range of operation
1kV rms for 1 minute across open The unit will withstand 12% ripple –10°C to 60°C
contacts of output relays on the dc auxiliary supply
• Storage and transit
2kV rms for 1 minute between all • AC supply voltage dips and short –40°C to 70°C
pins of the communications port interruptions
wired together and all other • Humidity
terminals. EN 61000-4-11: 1994 to 95% non-condensing
• High voltage impulse The unit will withstand voltage • Enclosure protection
dips of 100%, 60% and 30% in IEC 50529: 1989
IEC 60255-5: 1977 the auxiliary power supply for a IP 52
Three positive and three negative duration of 10ms, under normal
impulses of 5kV peak, 1.2/50µs, operating conditions, without Construction
between all terminals of the same de-energising. • Case
circuit (except communication • EMC compliance Polycarbonate
port); between independent Compliance with UL 94 VO
circuits (except communication 89/336/EEC
• Dimensions
port); and between all terminals
Compliance with European 144 x 144 x 125mm
connected together and earth
Commission Directive on EMC, is
(except communication port) • Weight
claimed via the technical
0.8 kg
Three positive and three negative construction file route.
impulses of 1kV peak, 1.2/50µs,
between the communication port
and earth.
6
Case
41.5 8.0
138.0
square to pips
136.0
square 10.0 54.0 53.0
90.0
square
32.9
Panel cut-out to be 138.0 square
Terminal 1
13.1
32.9
13.1
M4 terminals
7
Information required with order
M 2 2 0
Numeric instrumentation
Measurement centre
Application
Measurement centre 2
Variant
Connection options
CT secondary rating
1A 1
5A 5
VT secondary rating
VT auxiliary rating
63.5V B
110V E
120V G
230V V
DC 6
Other (please specify on next page) Z
Frequency
50 – 60Hz X
Pulsed outputs
None 0
Two 2
RS232 2
RS485 4
8
Additional information Notes on ordering
required with order The standard devices on offer reflect
the new normalised European
Non-standard VT and/or voltage, eg. 230V L-N will work on
auxiliary voltages; a 220V or 240V system. Therefore,
if for example a 220V unit is
VT V L-L or requested, a nominal 230V unit will
be supplied.
V L-N Note: The unit of measurement
displayed changes according
Auxiliary V to the change in CT ratio.
The energy per pulse is
related to the displayed
value. See Table 1 below for
default settings.
Display
1Wh 10Wh 100Wh 1kWh 10kWh
resolution
230V L-N 5A 10A to 55A 60A to 550A 575A to 5500A 5750A to 20000A
63V L-N 5A to 20A 25A to 200A 205A to 2000A 2050A to 20000A
Table 1