12.1 Why Finned Tube Heat Exchangers?
12.1 Why Finned Tube Heat Exchangers?
12.1 Why Finned Tube Heat Exchangers?
Due to the poor outer heat transfer coefcient, the outer surface area should be larger than the inner
surface tube area by 8.5!
Advantages of nned tubes
higher heat load per m tube or per construction volume
smaller equipment dimensions/less tubes
smaller ow cross-section in the tubes/better heat transfer
less pressure loss
A distinction is made between the following types of nned tubes:
high-nned cross-nned tubes with nned heights of 10e16 mm
high-nned longitudinal-nned tubes with nned heights of 12.7e25 mm
low-nned cross-nned tubes with nned heights of 1.5e3 mm
The high-nned cross-nned tubes are used in air coolers and gas heat exchangers.
The longitudinal-nned tubes are used as vessel heater or in double pipe heat exchangers for high
viscous media, for instance oil or bitumen, becausedas opposed to the cross-nned tubesdthe distances
between the ns are much greater than the laminar boundary layer on the tube so that a ow between the
ns is possible.
For a face ow length of 10 mm, the following laminar boundary layer thickness results depending on
the Reynolds number Re at plates:
Re 100 j d 4:64 mm
Re 200 j d 3:28 mm
Re 500 j d 2:07 mm
The n spacing must be larger than the boundary layer thickness! Low-nned tubes are used to increase
the efciency in existing heat exchangers or to reduce the size of the equipment, for instance, for the
refrigerant evaporation and condensation or for the decrease of the construction heights of heating
bundles.
At convective heat transfer on the shell side, the Reynolds number should be >500.
Finned Tube Heat Exchangers 249
Figure 12.1 Outer tube surface area as a function of the n height for a core tube diameter of 20 mm.
Figure 12.2 Fin efciency hF as a function of the n height and the n material.
250 Heat Exchanger Design Guide
Figure 12.3 Fin efciency hF as a function of the n height for different outer heat transfer coefcients
of ao 40e800 W/m2 K.
The required tube length L for the heat duty Q 100 kW is determined for
different ao-values and nned tube types.
ao 50 W/m2 K ao 500 W/m2 K
Type 1: hF 16 mm dC 38 mm L 340 m L 145 m
Type 2: hF 10 mm dC 20 mm L 905 m L 313 m
Type 3: hF 1.5 mm dC 22.2 mm L 1695 m L 317 m
Plain tube L 4348 m L 623 m
25 ! 2
hF n height
dC core tube diameter
r
2 ! 40
X ! 0:01 0:7303
0:0003 ! 50
# $
40
XDF 0:7303 ! 1 0:35 ! ln 0:9075 tanh XDF 0:7199
20
tanh X 0:7199
hF 0:7933
X 0:9075
0:7933 ! 0:48 0:07
hW 0:82
0:55
1. ao 40 W/m2 K hF 0.7933
# # $$
0:48 %
aoW 40 ! 1 % 1 % 0:7933 ! 32:8 W m2 K
0:55
# $
1 1 0:55 0:002 1
! 0:0346
Uo 32:8 0:05 50 3000
% %
Ua 28:82 W m2 K Fo 0:55 m2 m tube
Qo 28:82 ! 30 ! 0:55 475:5 W=m tube
Conversion:
%
Ui Uo ! Ao =Ai 28:82 ! 11 317 W m2 K
Qi 317 ! 30 ! 0:05 475:5 W=m tube
Finned Tube Heat Exchangers 255
Example 10: Calculation of the temperature gradients for plain tube and nned
tube
Q 500 kW ao 800 W/m2 K ai 6000 W/m2 K
ro ri 0.00015 sW 1 mm lW 50 W/m K Dt 25 K
9632:5
Dtao 12:85 ( K
800 ! 0:9368
0:00015 ! 0632:5
Dtro 1:55 ( K
0:9368
9632:5
Dtai ! 3:27 5:25 ( K
6000
Dtri 0:00015 ! 9632:5 ! 3:27 4:72 ( K
0:001
DtW ! 9632:5 ! 3:27 0:63 ( K
50
Dtao temperature gradient for ao
Dtai temperature gradient for ai
Dtro temperature gradient for the outer fouling ro
Dtri temperature gradient for the inner fouling ri
DtW temperature gradient for the heat conductivity through the wall
Figure 12.4 Heat load (W/m K) as a function of the outer heat transfer coefcients.
Finned Tube Heat Exchangers 259
The advantage is seen with the high-nned tubes in the area of lower outer heat
transfer coefcients and also the possibilities for an increase of the efciency by the use
of low-nned tubes in the area of higher outer heat transfer coefcients.
Example 12: Heating bundle for the heating of a product in a storage tank with
10 m diameter without considering the fouling and the heat conduction
resistance of the tube wall
Q 200 kW ai 6000 W/m2 K ao 50 W/m2 K Dt 50 K
Tube data as in Example 11.
Example 13: Gas cooling in a cross ow bundle with cooling water in the tubes
ai 5000 W/m2 K in the tubes
Gas ow rate VShell 904,000 m3/h Q 8 Mio W Dt 40 K
Allowable pressure loss 3.8 mbar
Allowable bundle width 6 m
Properties of the gases: 9 0.885 kg/m3 l 0.0332 W/m K
n 25 mm2/s Pr 0.68
1. With plain tubes 38 ! 3.6 without fouling
Estimation of the required area A with U 90 W/m2 K:
Q 8 ! 106
A 2222 m2
U ! Dt 90 ! 40
Lreq 19;000 m 3166 tubes with L 6 m
Due to the low allowable pressure losses, an aligning arrangement with PC PL 2 ! da 76 mm is
chosen.
PC cross pitch of the tubes
PL longitudinal pitch of the tubes
Arrangement: 100 tubes one over the other, 6 m long, 36 tube rows one behind the other, aligned
arrangement
Free ow cross-sectional area Afree for the gas through the tube bundle:
PC % do 76 % 38
Afree !H!L ! 7:6 ! 6 22:8 m2
PC 76
904;000
wgas 11 m=s
22:8 ! 3600
wgas ! do 11 ! 0:038
Re 16; 720
n 25 ! 10%6
Pressure loss calculation according to Jakob (Section 11.3): z 0.189
w2 ! r 11 ! 0:88
DP ! nR ! z ! 36 ! 0:189 362 Pa
2 2
Heat transfer calculation according to Grimison (Section 11.3):
U 90.7 W/m2 K
Total tube length Ltot 153 ! 6 ! 5 4590 m tube Total surface area A 6885 m2
2 2
Abundle 7.6 ! 6 45.6 m fproj 0.03 m /m tube Afree 45.6 ! 6 ! 0.03 18 m2
904;000 13:95 ! 0:0254
w 13:95 m=s Re 14; 174
3600 ! 18 25 ! 10%6
Pressure loss calculation with z 0.8 from manufacturer data
13:952 ! 0:88
DP ! 5 ! 0:8 343 Pa
2
Calculation of the heat transfer coefcients according to manufacturer data:
Nu
0:37 ! Re0:553 ! fR 0:37 ! 14;1740:553 ! 1 73:1
Pr1=3
Nu 73:1 ! 0:680:33 64:4
64:4 ! 0:0332 %
ao 84:2 W m2 K
0:0254
Calculation of the n efciency:
r
2 ! 84:2
X 0:0159 ! 1:459 XDF 1:8735 hF 0:5092
50 ! 0:0004
0:5092 ! 1:46 0:04
hW 0:5222
1:5
%
aoW 0:5222 ! 84:2 44 W m2 K
Example 14: Double pipe oil cooler with an inner longitudinal-nned tube
Pipe shell with Di 77.9 mm Ao/Ai 5.5
Inner tube with longitudinal ns: do 48.2 mm, n height 12.7 mm, surface area 0.76 m2/m
Tube-side product: cooling water
REFERENCES
[1] D.Q. Kern, A.D. Kraus, Extended Surface Heat Transfer, McGraw-Hill, N.Y., 1972.
[2] Th.E. Schmidt, Kaltetechnik 18 (4) (1966) 135e138.
[3] W.M. Kays, A.L. London, Compact Heat Exchangers, McGraw-Hill, N.Y., 1964.
[4] G.P. Purohit, Thermal and hydraulic design of hairpin and nned-bundle exchangers, Chem. Eng., 90
(1983) 62e70.