Ws Sinamics Gl150 en
Ws Sinamics Gl150 en
Ws Sinamics Gl150 en
Robust and reliable performance for high power and starting applications
siemens.com/sinamics-gl150
Portfolio
180 kVA10 MVA 430 MVA 110.1 MVA 3.45.8 MVA 6.313.7 MVA 1.4 - 19.4 MVA 2.918.8 MVA
(air-cooled) (water-cooled) (air-cooled) (air-cooled) (water-cooled) (air-cooled) (air-cooled)
524.4 MVA 024 MVA 4.640 MVA 685 MVA 1240 MVA
(water-cooled) (water-cooled) (water-cooled) (water-cooled) (water-cooled)
(higher power
on request)
Output voltage Output voltage Output voltage Output voltage Output voltage Output voltage Output voltage
2.311 kV 4.167.2 kV 2.34.16 kV 3.3 kV (IGCT & IGBT) 3.37.2 kV 1.410.3 kV 1.54 kV
4.16 kV (IGBT)
Multi-cell voltage Multi-cell voltage 3-level NPC voltage 3-level NPC voltage Customizable modular Load-Commutated Cycloconverter (CC)
source inverter (PH VSI) source inverter source inverter source inverter voltage source system inverter (LCI)
(M2C VSI) (DFE VSI) (AFE VSI) (VSI)
Air- and water-cooled Water-cooled Air- and water-cooled Air- and water-cooled Water-cooled Air- and water-cooled Air- and water-cooled
2
LCI drives
SINAMICS GL150 drives serve some of the most demanding applications all around the world in industries such as:
4
Features & Benefits
5
Reliability
SINAMICS GL150 air-cooled compact and innovative design Air-cooled version of SINAMICS GL150 power section
for high power rating
Perfect for high-speed synchronous motors with the Higher motor voltages can be achieved by using a high
highest ratings number of thyristors with a high blocking capability in
SINAMICS GL150 is admirably suited for directly driven a series circuit.
high-speed compressors and pumps. SIMOVERT S from The series thyristor circuits for the highest power ratings
Siemens the predecessor of the SINAMICS GL150 con- can be optionally configured corresponding to an n+1
trols the speed of the highest-rated high-speed compres- redundant design. This further increases the availability.
sor drive ever built. Frequently, SINAMICS GL150 is used One of the advantages of the patented arrangement of
as a starting converter to softly start large synchronous the DC link reactors is the insensitivity to a single ground
motors for instance, for blast furnace blowers. In this fault. The power unit as well as the closed-loop control
case, a SINAMICS GL150 brings the multi-megawatt can be redundantly configured as an option to achieve the
motors up to the line synchronous speed and then trans- highest availability.
fers them over to the line supply.
Over four decades of reliability LCI drives
The simple and rugged concept of LCIs from Siemens has
been ensuring maximum availability with a high degree of
cost-effectiveness for three decades now. The combina-
tion of extremely rugged thyristor technology in a fuseless
design, combined with an intelligent response to external
disturbances, makes these drive units extremely reliable
requiring little maintenance. The LCI concept is based on
a combination of synchronous motor and simple thyristor
bridges on the line and motor sides.
The two thyristor bridges are force-commutated and no
forced commutation circuitry is required. This makes the
power electronics extremely simple and rugged. Liquid-cooled version of the SINAMICS GL150 power unit
6
Redundancy
Leading-edge technology
that is easy to handle
7
Innovation
8
Innovation
9
Soft starting
Getting everything up
and running just right
Circuit-breaker
Motor-side
Synchronizing
thyristor converter control
Step-up transformer
Bypass circuit-breaker
High-voltage
synchronous motor
Block diagram of a starting
converter in this case, for
two synchronous motors Excitation equipment
10
Commissioning
11
Compatible motors
65-MW compressor motor running at 3,600 rpm Soon to be winging its way to site: A 24-MW One of the two 21-MW motors
for the first completely electric gas liquefaction motor for the West-to-East Pipeline in China for the main drive of a cruise ship
system in the world in Hammerfest/Norway
12
Compatible motors
The system partner on the motor side All of this together with the extremely high mechanical
more than just reliable strength and thermal endurance ensure an extremely long
Together with SINAMICS GL150, Siemens synchronous winding lifetime. The bearings also have extremely long
motors form a perfectly Integrated Drive System: lifetimes and require hardly any maintenance.
Whether for high-speed compressors with the highest Motors with integrated safety
power rating for transporting or liquefying gas, or large
Siemens synchronous motors are equipped as standard
extruders and water pumps or for main ships drives,
with bearing and winding monitoring devices to cope
these rugged synchronous motors are the foundation
with even the most extreme situations. It goes without
for maximum reliability.
saying that all of the synchronous motors are available in
The enclosure, bearings, active parts, ventilation and cool- explosion-protected versions: With pressurized enclosure
ing system are perfectly harmonized with one another. Ex p for gas explosion protection, Zone 1. For high-speed
The materials, components and production techniques synchronous motors, we also offer oil-lubricated sleeve
utilized have been carefully selected with this objective bearings or active magnetic bearings. When using mag-
in mind. netic bearings, an extremely wide speed control range can
be implemented for instance, 6006,300 rpm at 23 MW
The Micalastic insulating system that Siemens uses for
when fed from a SINAMICS GL150.
all our high-power high-voltage motors has proven itself
over many years of operation in applications all around
the world. An important component is the VPI insulation
technique (Vacuum Pressure Impregnation) which allows
the motor to be connected directly to the line supply and
MV drive. The insulation has a high switching and revers-
ing strength as a result of the high winding overhang
stiffness and excellent corona shielding.
35-MW motor running at 5,040 rpm for a 23-MW motor running at 6,300 rpm to pump 42-MW motor for the blast furnace
compressor station of a gas pipeline from gas south of Groningen/The Netherlands blower in the Anshan steelworks, China
Great Britain to Belgium
13
SINAMICS GL150 Technical data
Specifications
Power connection Closed-loop control
Line supply voltage Vector control with and without speed encoder
Air cooling: up to 5.4kV +/ 10% Separately excited synchronous motors can be connected
Water cooling: up to 12kV +/ 10% (excitation equipment is available separately)
Frequency: 50/60Hz +/ 3% Operation as starting converter
Line supply power factor: approx. 0.82 at rated speed and load Operation as continuous duty drive
Either from the top or bottom Speed accuracy: 0.1% without encoder,
Motor connection 0.01% with encoder
Motor voltage Torque accuracy: +/ 3%
Air cooling: up to 4.8kV Field-weakening operation
Water cooling: up to 11kV Starting converter: 1:8
Either from the top or bottom Continuous duty drive: 1:1.5
Auxiliary power supply Maximum output frequency: 125Hz
Air-cooled: 1
AC 230 V 10%, 50/60 Hz 3%
Standards
3 AC 400 V 10%, 50/60 Hz 3%
IEC, EN, CE
Water-cooled: 1 AC 230 V 10%, 50/60 Hz 3%
DIN EN 61800-3 / VDE 0160 T103 (IEC 61800-3)
Line-side rectifier
DIN EN 61800-4 / VDE 0160 T104 (IEC 61800-4)
LCI (Load-Commutated Inverter), DIN EN 61800-5-1 / VDE 0160 T105 (IEC 61800-5-1)
thyristor rectifier in a B6C-circuit, DIN EN 60146-1-1 / VDE 0558 T11 (IEC 60146-1-1)
6-pulse, 12-pulse or 24-pulse, regenerative feedback into the DIN EN 50178 / VDE 0160 (IEC 62103)
line supply DIN EN 60204-11 / VDE 0113 T11 (IEC 60204-11)
Motor-side inverter
LCI (Load-Commutated Inverter),
Standard features
thyristor inverter in a B6C-circuit, Flying restart
6-pulse or 12-pulse Automatic restart
Efficiency Operating hours counter for fans and circuit-breaker
> 99.0% at rated speed and load Maintenance functions
Cooling STARTER software for user-friendly commissioning and
Air cooling with top-mounted cabinet fan diagnostics with a PC
Water cooling using heat exchanger with redundant pumps as Control I/O
standard
Analog inputs: 2/4
Degrees of protection
Analog outputs: 0/4
Air cooling: IP20 (higher degree of protection on request)
Digital inputs: 6/6
Water cooling: IP41 (higher degree of protection on request)
Digital outputs: 4/16. Others through optional expansion modules
Ambient conditions
Speed encoder
Temperature:
+540C (41104F), up to 45C (113F) with power derating Communications: PROFIBUS-DP or PROFINET (other on request)
Installation altitude: Selection of additional options
1,000m above sea level: 100% load capability Increased degree of protection
> 1,000m to 3,000m above sea level: Current derating
Suitable for marine duty
> 2,000m to 3,000 m above sea level: Additional voltage derating
Teleservice module
Humidity: < 85% (condensation not permissible)
Anti-condensation heating
Safety functions (this is only a selection of those available)
Additional I/O modules
Short-circuit and ground fault monitoring
Overcurrent, overvoltage and undervoltage monitoring Output transformer (starting converter)
Line supply voltage failure monitoring Bypass control for up to 4 motors (starting converter)
Overtemperature monitoring (drive converter and motor) Demagnetizing equipment for the output transformer
(starting converter)
Overspeed protection, anti-stall protection (motor)
Redundant configurations (control and/or semiconductor
Cooling circuit monitoring
redundancy)
Self-diagnostics of the control and power unit
Grounding breaker at the input and output
Circuit-breaker at the converter output
Various versions of the heat exchanger
14
Rated output Output voltage Shaft output No. of No. of Article No.1 Configuration
current pulses, pulses,
A V kW hp line side motor side
1
Please contact your sales partner to complete the configuration
2
Available in new innovative air-cooled configuration
3
Values are referred to the data of a typical synchronous motor
4
Please inquire, modified frame size
15
Theres
Find outmore to it
more:
siemens.com/sinamics-gl150
Discover the
advantages of the
SINAMICS GL150
The advantages
of SINAMICS
GL150 at a
glance