Catalogue Absorption Chillers ENG F

Download as pdf or txt
Download as pdf or txt
You are on page 1of 80

LG HVAC SOLUTION

ABSORPTION
CHILLER
Nomenclature

Chiller heater
DH : Direct-fired double-effect H series
DN : Direct-fired double-effect N series Water working pressure:
DS : Direct-fired double-effect S series C: Chilled water: 5kgf/cm2G
DA : Direct-fired double-effect A series Cooling water: 5kgf/cm2G
W: Water
G: Chilled water: 8kgf/cm2G
Chiller Cooling water: 8kgf/cm2G
SH : Steam-fired double-effect H series K: Chilled water: 10kgf/cm2G
SS : Steam-fired double-effect S series Cooling water: 10kgf/cm2G
MH : Hot-water single-effect H series N: Chilled water: 12kgf/cm2G
MW : Hot-water single-effect W series Cooling water: 12kgf/cm2G
2H : Double-lift, low-temperature, R: Chilled water: 16kgf/cm2G
hot-water single-effect H series Cooling water: 16kgf/cm2G
U: Chilled water: 20kgf/cm2G
Heat pump Cooling water: 20kgf/cm2G
PX : First absorption heat pump X series

W C DH 024 S K 6 1
S: Standard
A: 1 step-up
heating capacity
B: 2 step-up
heating capacity 6: Leaving hot water
Nominal ton: C: 3 step-up temperature 60C
10RT 001 heating capacity 8: Leaving hot water Develop
100RT 010 R: Other type temperature 80C -ment
C: Chiller 1000RT 100 N: Cooling only N: Chiller sequence

Contents

02 Nomenclature
03 Line up
04 Absorption chiller application
05 Equipment overview
09 Options
10 Specification
29 Absorption chiller cycle
30 Specification
38 Thermal insulation
40 Piping diagram
43 Control diagram of cooling water inlet temperature
44 Standard of water quality
45 Fuel piping
46 Multi-Sectional shipment
48 Outline & Foundation
73 Schematic diagram
78 Interface diagram

02 | 2015 LG Absorption Chiller


Line up & Features Introduction

Line up
Direct fired absorption chiller & heater
Model 0 100 500 1,000 1,500 3,000

WCDH 100RT 1,500RT 3,000RT


(H Series)

WCDN 50RT 700RT 3,000RT


(N Series)

WCDS 100RT 1,500RT 3,000RT


(S Series)

WCDA 50~80RT
(A Series)

Absorption chiller
Model 0 100 500 1,000 1,500 4,000

WCSH 100RT 1,500RT 4,000RT


Steam fired

WCSS 100RT 1,500RT 4,000RT


Steam fired

WCMW 28RT 1,020RT 2,000RT


Hot water fired

WC2H 73RT 1,350RT 2,000RT


Hot water fired

WCMH 28RT 1,020RT 2,000RT


Hot water fired

Heat pump
Model 0 300 1,000 5,000 10,000 20,000 30,000

WCPX 349kW 30,218kW


Heat pump

* Available on request.

2015 LG HVAC Solution | 03


Features Absorption chiller application

Absorption chiller application


Model Selection
Energy Available (Example) Application
Efficiency Model Remark

LNG COP 1.51 WCDH World class high efficiency


LPG Commercial area
Gas or Oil Bio-Gas COP 1.34 WCDN Enhanced stability & reliability Multipurpose building
Exhaust gas Thermoelectric power plant
Oil COP 1.12 WCDS Steady best selling model
COP 1.50 World Class High Efficiency
WCSH Commercial area
Steam pressure Consumption (3.5 kg/hRT) Steam Pressure : 4 ~ 8kg/cm2
Chiller Steam Multipurpose building
4~8kg/cm2 COP 1.21 Steady Best Selling Model
WCSS Petroleum and Chemical Factory
Consumption (4.4 kg/hRT) Steam Pressure : 4 ~ 8kg/cm2
World Class High Efficiency
COP 0.80 WCMH
Inlet Outlet Temp. : 85 ~ 75C
Solar system
Hot Temperature Steady Best Selling Model
COP 0.72 WCMW District energy system
Water Standard 95C Outlet Temp. : 85 ~ 70C
Cogeneration
(130 ~85C) Low Temperature outlet
COP 0.74 WC2H
Outlet Temp. : 70 ~ 55C
Gas
Heat Waste heating World Class High Efficiency Combined Heat and Power
Steam COP 1.65~1.80 WCPX
pump Source Hot water Temp. : 55 ~ 90C Incinerator system
Hot water

With over 50% domestic market share, LG Electronics has provided heating,
ventilating and air conditioning total solution to industrial and commercial fields
over 40 years. Now the company, specialized in absorption, centrifugal & GHP,
now wants to share its leading technology with the global friends.
The LG Absorption Chillers have always been nations No.1 energy saving
chillers, since the company has considered R&D as frontier mover of all.

Features of LG absorption chillers


Beneficial where cooling/heating demands are all year around by using diversified energy sources as Gas, Steam and Hot water.
Reduces operation cost in where electrical costs are high.
Utilizing environmental safe, non chlorine mixture based refrigerant.
Reduces green house effect by less using hydrocarbon fuels as well as electricity.

Stainless steel tube lead to pitting corrosion.


Enhanced heat-transfer efficiency of stainless steel tube
Corrosion resistance

Generally, stainless steel tube has low heat transfer
In general, tubes of absorption chiller are corroded by pollutant
coefficient than copper.
in the cooling water.
LG has achieved same performance comparing to copper by
The type of corrosion is majority pitting corrosion. So many
improving low heat transfer efficiency of stainless steel with
maker recommend triennial cleaning tubes.
our unique knowhow
LG has applied to stainless steel tube and enhanced reliability,
Strength and hardness of stainless steel tube is higher than
maintenance of machine.
that of copper tube.
Main characteristic of corrosion in tube: pitting corrosion
If the pollutants is pasted at a tube surface, pollutants can be

04 | 2015 LG Absorption Chiller


Features Equipment overview

safety function when the chiller operation reached at abnormal


Thickness of corrosion(mm)
0.75 state.
Copper

Stainless Optimized dilution operation shortened stoppage time


0.5 steel
LG's newly designed microprocessor decides when to equalize
Copper : 0.4mm concentration of solution in every part of chiller by self diagnostic
0.25 STS : 0.002mm calculations. Also this led to saving dilution operation as well as
energy saving at auxiliary equipments, such as water pumps by
0 reducing idle time from 15 min to 5 min.
start up 1 year 2 year 3 year 4 year 5 year
Operating time(year)

High reliability & practical design


High performance of purging system
Copper Stainless steel
Newly designed injector typed, purging either at upper shell
Corrosion rate 2400% 100%
(mm/year) (0.1352700) (0.0056209) and lower shell, a new LG purging system, enabled less purging
Loss by weight 1500% 100% time and better purging performance.
(mg/year) (-0.0196) (-0.00013)

Marine hatch type water box


Reinforced user interface design No need to cut or dissemble for tube cleaning or maintenance
Over 40 years experience with successful delivery of 10,000 purposes, marine hatch typed water box allows an operator to
units. LG Absorption chiller has been focused on user interface clean tubes in less time.
and reliable convenient operations that to considered as a first
step of total HVAC solution.
Series flow
Easy control of absorbent circulation rate by load
High efficiency & high energy saving operation Reduce Facility installation cost by reduce cooling water flow
Inverter controlled solution pump enabled high part-load Enable absorbent circulation rate control and Pump Soft
efficiency with fast full-loaded operation Start/Stop by inverter pump
Optimized flow rate of solution is decided upon cooling demand Easy operation
and that to enable highly efficient energy saving operation at all No damage by local heating
operation range.
Outlet of
Cooling Water Condenser Low Temp.
Generator

LGs New PID Control


Cooling Capacity(%)

100 High Temp.


Inlet of Generator
Chilled/Hot Water

Conventional Control Evaporator Absorber


Air Burner Fuel
Outlet of
50 Cooling Water Low Temp. High Temp.
Heat Heat
Exchanger Exchanger
Inlet of
Cooling Water
Water(Liquid) Absorbent(High Concentrated)
Piping Diagram Water(Steam) Absorbent(Concentrated)
Exhaust Gas Absorbent(Diluted)

time

Reinforced safety operation


ON-OFF Controlfunction

LG's unique microprocessor keeps monitoring every part of


0.30
AS Consumption (N m 3/h. RT)

chiller so to0.25
prevent any damage could happen at abnormal
operation. The
0.20
machine can stop automatically by reinforced
P Control

2015 LG HVAC Solution | 05


0.15
LGs New PID Control
Features Equipment overview

High performance controller


Delicate Designed with PID Control Logic, a new Micro Processor
enables LG Chiller be always at optimum operation state

A new quick response PID control logic


A quick response, new LG designed PID algorithm enabled high
sensitive combustion control rate that to meet minimized
reaching time of demand temperature.
It also reduced the fluctuating temperature difference so that
to enable constant temperature control logic.

7 Color LCD with high resolution Real time operation status Time schedule

Evaporator & absorber Low temperature generator High temperature generator

all operational condition and keeps concentration level in


temp.(C)
optimum state by controlling a combustion rate.
Conventional Control
LGs New 2. A safety operation feature against cooling water temperature
PID Control (P Control)
9
Set Value 7
8 For stable operation, entering cooling water can be reset
6
Load Variation
based on remote temperature range of 19~34C as well
5
as responding its temperature at the micro processor by
90% controlling combustion rate.
Load 60%
3. Operation data storage/maintenance feature
time 20 years normal operation history data record
300 abnormal message history data record
10.6 day temperature sensing data record
A new Quick Response PID Control Logic
Based on all stored data, more accurate operational maintenance
is capable.
Self diagonistic safety operation 4. Self Diagnostics / Mal function Alarm feature
1. Anti-crystallization safety operation If any disturbing factor predicted while normal operation, a
A solution concentration is monitored at micro processor in chiller tests itself and determines whether it has to turn into
06 | 2015 LG Absorption Chiller
Features Equipment overview

safe mode operation or to stop. Cooling Tower


Interlock
Maintenance purpose
Chamber Cleaning: by monitoring exhaust gas temperature, Controller

operators can predict right time of cleaning a combustion


channel of HTG.(Option)
Chilled Water
Malfunction alarm feature Pump

Monitoring all sensors, of their conditions like temperatures Contr


and pressure state so that if any abnormal sign occurs it
shows abnormal reason on the display for easy operation.
Cooling Water Pump
Absorbent concentration control
Controller calculates Absorbent Concentration by Condenser Equip. Facility Diagram
and Low Temp. Generator, Controls Inlet Heat for Preventing
Absorbent Crystallization. Safety Device, Self Diagnosis
 Safety device and Sensor status with Self-diagnosis from Controller
Low temperator Concentration
when Start-up. Customer can prevent from abnormal operation
Generator 24% 34% 44% 54% 64% and safety accident.
Pressure (mmHg)

Condenser
temperature Cooling Tower
Interlock
ve
4%

ur
nc
~6

tio
54

Controller
iza
in

all
ta

st
ain

Input-energy control
ry
M

rc
LiB

Chilled Water Temperature (C)


Pump

Controller
Process during Power failure
Auto Self Diagnosis and Restart by Blackout Response Function.

Cooling Water Pump

Auto Dilution Manual Dilution Piping Diagram


Auto Restart
Auto Restart Manual Restart

Enhanced user interface designed micro processor


Blackout In In After Operation State Display
30Min. 1 Hour 1 Hour
Operation state is displayed either in text or as graph so to
enable better understanding
30min. 1hour Time
Printer(Option)
Stored operation normal/abnormal/ alarm history data can be
printed out from mounted printer
Flow Rate Indication(Option)
Maximize System Stability by Self Diagnosis
A flow rate of chilled/ cooling water flow rate can be indicated
Equipment Facility, Self Diagnosis
on the display. For this operation an additional transducer
Equipment Facility from Controller when Start-up (Chilled water /
should be applied on chilled/cooling water pipe line.
Cooling water pump, Cooling tower) with Self diagnosis, Customer
Annex System Control
can prevent from Crystallization and Frozen burst.
Pumps and cooling fan are in control with micro processor for
automated operation
Schedule Operation
Schedule operation can be done in days or at the desired any time

2015 LG HVAC Solution | 07


Features Equipment overview

Status Voltage Cooling


Display Run Heating
(LED display) Stop CHW/HW inlet temp. RS485
Multi-Drop
CHW/HW outlet temp. TCP/IP
Setting CW temp.
CHW/HW Inlet Temp. Value P value RS485
CHW/HW Outlet Temp. I value Serial to LAN Converter
converter
CW Inlet Temp. D calue
H.gen Temp.
Reading L.gen Temp.
Value Condensing Temp. Protocol Connecting to max 8 units
(LCD display) Remote Set Temp. converter
Control V/V Open(%) The chillers can be managed up to 255 units when using communication of RS485 or TCP/IP.
Libr Concentration Combustion signal
Inverter(Hz) Purge chamber
PID Value pressure
H. Gen level low Detailed diagrams of BMS
Run mode
Running time Control v/v mode
Operation Combustion time Abs pump #1 th. Relay
Time Ref. Pump run time Abs pump #2 th. Relay
(LCD display) Abs pump #1 run time Reading Chw/hw pump interlock
Abs pump #2 run time Value Cw pump interlock
(LCD display) H. Gen pressure
Chw flow rate
Cw flow rate
Running time Abs pump #1 m.
No. Of Combustion time Contactor
Run/stop Ref. Pump run time Abs pump #2 m.
(LCD display) Abs pump #1 run time Contactor
Abs pump #2 run time Purge pump m.
Contactor

Group unit system control


For intelligent buildings and huge factories
1. Communication protocol for Building Automation and Remote
monitoring control
Easily accessible to user's interface
RS485 communication processor installed
MODBUS is standard, BACnet, Lonwork are available as an option.
Operational data acquisition
Graphical display of monitoring & control status
Data editing and Report generation with MS EXCEL
Real-time graphical display of trend data
Various graphic display for analog data
Password protected
2. Optimized Operation
Integrated System Management
Integrated control of Chillers and Peripheral Equipment
which are connected to LG controller
Preventative Maintenance
Log data management
:D aily report generation of operation data, abnormal data
and etc.
Operational Cost Saving
Cost saving through centralized monitoring
Auxiliary Function
Control of peripheral equipment, load control

08 | 2015 LG Absorption Chiller


Options

Items Option

Refrigerant charging

Leaving chilled water temperature is available from 5C

Entering cooling water temperature is available from 22C

BACnet/Lonworks protocol converter module

Flexible Wiring

Dual Burner (LNG + Oil or LPG + Oil)

Factory completed thermal insulation

Factory performance test with witness

Sectional shipment

Wood Packing

Extended warranty

Solution Filter

Pump Inlet/Outlet shut-off valve

Auto purge system

Refrigerant temperature sensor

Companion flange

Special construction for hazardous-area installation

Outdoor installation construction (non-hazardous areas)

Enclosure protection upgrade(IP54)

2015 LG HVAC Solution | 09


Specification Direct fired absorption chiller & heater

WCDH Series
Model name 010 012 015 018 021 024 028 032 036 040 045 050
USRT 100 120 150 180 210 240 280 320 360 400 450 500
Cooling capacity
kW 352 422 527 633 738 844 985 1,125 1,266 1,407 1,582 1,758
kcal/h 253,000 253,000 303,600 379,500 455,400 531,300 607,200 708,400 809,600 910,800 1,012,000 1,138,500
Heating capacity
kW 294 294 353 441 530 618 706 824 941 1,059 1,177 1,324
Temperature C 12 7.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Chilled
water Pressure drop mAq 6.2 6.3 8.0 8.3 8.0 8.1 5.4 5.5 5.6 5.8 5.1 5.2
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 56.2 60.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Hot
water Pressure drop mAq 6.2 6.3 8.0 8.3 8.0 8.1 5.4 5.5 5.6 5.8 5.1 5.2
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 32.0 37.0
Water flow rate m3/h 100 120 150 180 210 240 280 320 360 400 450 500
Cooling
water Pressure drop mAq 3.9 4.2 6.1 6.9 6.1 6.6 8.3 8.8 7.4 8.0 8.8 9.7
data
A(mm) 125 125 125 125 150 150 200 200 200 200 250 250
Connection size
B(inch) 5 5 5 5 6 6 8 8 8 8 10 10
A(mm) 40 (at 4,000mmAq) 50 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 1 1/2 (at 4,000mmAq) 2 (at 4,000mmAq)
(Gas) Cooling 3
Nm /h 21.4 25.7 32.1 38.5 44.9 51.3 59.9 68.4 77.0 85.5 96.2 106.9
3
Heating Nm /h 27.5 27.5 33.0 41.2 49.4 57.7 65.9 76.9 87.9 98.9 109.9 123.6
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 12.2 12.2 15.6 15.6 16.8 16.8 23.9 23.9 23.9 26.9 26.9 26.9
Wire size mm2 4 4 4 4 4 4 6 6 10 10 10 10
Power kVA 8.2 9.1 10.6 11.2 12.1 12.1 15.9 17.9 19.8 19.8 17.7 17.7
Electrical
Absorbent pump no.1 kW(A) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3)
data
Absorbent pump no.2 kW(A) 0.4(1.6) 0.4(1.6) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Burner blower (gas) kW(A) 0.72(2.1) 0.72(2.1) 0.72(2.1) 1.5(3.3) 1.5(3.3) 1.5(3.3) 2.2(4.7) 2.2(4.7) 2.2(4.7) 3.7(7.7) 3.7(7.7) 3.7(7.7)
Length mm 2,895 2,895 3,745 3,745 3,795 3,795 4,815 4,815 4,890 4,890 4,900 4,900
Dimension Width mm 1,965 1,965 1,965 2,095 2,150 2,170 2,225 2225 2,430 2,515 2,765 2,855
Height mm 2,070 2,070 2,070 2,070 2,415 2,415 2,415 2,415 2,590 2,590 2,925 2,925
Operating ton 4.9 5.2 6.2 6.9 8.0 8.6 10.4 10.9 12.4 13.2 15.5 17.3
Rigging Max. shipping ton 4.7 4.9 5.8 6.4 7.3 7.9 9.5 10.0 11.1 11.9 13.9 15.6
Dry shipping ton 3.8 4.0 4.6 5.0 5.8 6.1 7.4 7.8 8.7 9.4 11.0 12.4
Flue connection size mm 340 x 320 340 x 320 340 x 320 340 x 320 340 x 320 380 x 430 380 x 430 380 x 430 380 x 430 450 x 430 450 x 430 520 x 550
Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

010 | 2015 LG Absorption Chiller


Specification Direct fired absorption chiller & heater

WCDH Series
Model name 056 063 070 080 090 100 110 120 130 140 150
USRT 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Cooling capacity
kW 1,969 2,215 2,461 2,813 3,165 3,516 3,868 4,220 4,571 4,923 5,274
kcal/h 1,265,000 1,416,800 1,593,900 1,771,000 2,024,000 2,277,000 2,530,000 2,783,000 3,036,000 3,289,000 3,542,000
Heating capacity
kW 1,471 1,647 1,853 2,059 2,353 2,648 2,942 3,236 3,530 3824 4,119
Temperature C 12 7.0
Water flow rate m3/h 338.7 381 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Chilled
water Pressure drop mAq 5.2 7.2 9.6 4.4 6.0 7.9 5.8 6.1 9.2 7.6 9.3
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 56.2 60.0
Water flow rate m3/h 338.7 381 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Hot
water Pressure drop mAq 5.2 7.2 9.6 4.4 6.0 7.9 5.8 6.1 9.2 7.6 9.3
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 32.0 37.0
Water flow rate m3/h 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Cooling
water Pressure drop mAq 8.9 11.9 15.3 6.9 9.3 12.3 9.2 11.7 14.6 11.4 13.9
data
A(mm) 300 300 300 350 350 350 400 400 400 400 400
Connection size
B(inch) 12 12 12 14 14 14 16 16 16 16 16
A(mm) 50 (at 4,000mmAq) 65 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 2 (at 4,000mmAq) 2 1/2 (at 4,000mmAq)
(Gas) Cooling Nm3/h 119.7 134.7 149.7 171.0 192.4 213.8 235.2 256.6 277.9 299.3 320.7
3
Heating Nm /h 137.4 153.8 173.1 192.3 219.8 247.2 274.7 302.2 329.6 357.1 384.6
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 35.7 35.7 35.7 44.4 49.4 55.9 73.7 73.7 73.7 73.7 73.7
Wire size mm2 16 16 16 16 25 35 35 35 35 35 35
Power kVA 23.5 23.5 23.5 29.2 32.5 36.8 48.5 48.5 48.5 48.5 48.5
Electrical
Absorbent pump no.1 kW(A) 6.6(16.2) 6.6(16.2) 6.6(16.2) 5.5(20.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0)
data
Absorbent pump no.2 kW(A) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5)
Burner blower (gas) kW(A) 5.5(10.6) 5.5(10.6) 5.5(10.6) 7.5(14.0) 7.5(14.0) 7.5(14.0) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5)
Length mm 5,310 5,520 6,010 5,610 6,200 6,700 6,200 6,700 7,200 6,850 7,350
Dimension Width mm 3,025 3,150 3,150 3,800 4,050 4,050 4,400 4,400 4,400 4,800 4,800
Height mm 3,295 3,295 3,295 3,550 3,600 3,600 3,800 3,800 3,800 3,900 3,900
Operating ton 21.2 24.4 27.2 31.6 33.9 37.1 40.4 44.1 48.1 52.1 55.9
Rigging Max. shipping ton 18.7 21.6 24.3 27.8 29.7 32.7 36.1 39.6 43.2 46.7 50.2
Dry shipping ton 15.0 17.5 19.5 21.0 22.5 24.0 26.0 28.0 30.0 32.0 34.0
Flue connection size mm 520 x 550 650 x 550 650 x 550 650 x 550 750 x 550 750 x 550 750 x 550 850 x 550 850 x 550 850 x 550 950 x 550
Clearance for tube removal mm 4,500 5,200 5,700 5,200 5,700 6,200 5,700 6,200 6,700 6,200 6,700

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 011


Specification Direct fired absorption chiller & heater

WCDN Series
Model name 005 006 007 008 010 012 015 018 021 024
USRT 50 60 70 80 100 120 150 180 210 240
Cooling capacity
kW 176 211 246 281 352 422 528 633 739 844
kcal/h 133,000 160,000 186,000 212,000 267,000 319,000 400,000 479,000 559,000 639,000
Heating capacity
kW 155 186 216 247 311 371 465 557 650 743
Temperature C 12 7.0
Water flow rate m3/h 30.3 36.3 42.4 48.4 60.5 72.6 90.7 108.9 127 145.2
Chilled
water Pressure drop mAq 4.6 4.8 4.7 4.5 9.1 9.0 12.0 12.0 12.0 12.0
data
A(mm) 80 80 80 80 100 100 100 100 125 125
Connection size
B(inch) 3 3 3 3 4 4 4 4 5 5
Temperature C 54 60.0 55.6 60.0
Water flow rate m3/h 30.3 36.3 42.4 48.4 60.5 72.6 90.7 108.9 127 145.2
Hot
water Pressure drop mAq 4.6 4.8 4.7 4.5 9.1 9.0 12.0 12.0 12.0 12.0
data
A(mm) 80 80 80 80 100 100 100 100 125 125
Connection size
B(inch) 3 3 3 3 4 4 4 4 5 5
Temperature C 32.0 37.2
Water flow rate m3/h 50 60 70 80 100 120 150 180 210 240
Cooling
water Pressure drop mAq 5.8 6.3 4.8 5.4 4.5 4.5 7.0 8.0 6.5 7.0
data
A(mm) 100 100 100 100 125 125 125 125 150 150
Connection size
B(inch) 4 4 4 4 5 5 5 5 6 6
A(mm) 25 (at 200mmAq) 40 (at 200mmAq) 40 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 25 (at 200mmAq) 1 1/2 (at 200mmAq) 1 1/2 (at 4,000mmAq)
(Gas) Cooling Nm3/h 12.0 14.4 16.8 19.2 24.0 28.8 36.0 43.3 50.5 57.7
3
Heating Nm /h 15.2 18.3 21.2 24.2 30.5 36.4 45.7 54.7 63.8 72.9
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.2 8.2 9.5 9.5 12.2 12.2 15.6 16.8 16.8 16.8
Wire size mm2 4 4 4 4 4 4 4 4 4 4
Power kVA 5.4 5.4 6.2 6.2 8.2 8.2 10.5 11.3 11.3 11.3
Electrical
Absorbent pump no.1 kW(A) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4)
data
Absorbent pump no.2 kW(A) N/A N/A N/A N/A 0.4(1.6) 0.4(1.6) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.2(4.0)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Burner blower (gas) kW(A) 0.37(1.0) 0.37(1.0) 0.74(2.3) 0.74(2.3) 0.72(2.1) 0.72(2.1) 0.72(2.1) 1.5(3.3) 1.5(3.3) 1.5(3.3)
Length mm 2,205 2,205 2,555 2,555 3,165 3,165 3,745 3,665 3,705 3,795
Dimension Width mm 1,685 1,685 1,860 1,860 2,000 2,045 2,095 2,095 2,150 2,170
Height mm 1,760 1,760 1,760 1,760 2,070 2,070 2,070 2,070 2,415 2,415
Operating ton 3.2 3.4 3.8 4.0 4.9 5.2 6.2 6.8 8.0 8.5
Rigging Max. shipping ton 2.3 2.5 2.7 2.9 4.6 4.9 5.8 6.4 7.3 7.7
Dry shipping ton 1.9 2.0 2.1 2.2 3.8 4.0 4.6 5.0 5.8 6.1
Flue connection size mm 190 x 100 190 x 100 270 x 150 270 x 150 280x210 280x210 280x210 280x210 310x310 310x310
Clearance for tube removal mm 1,700 1,700 2,200 2,200 2,400 2,400 3,400 3,400 3,400 3,400

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
( But, WCDN005~N008 : 5kg/G(490kPa) )
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

012 | 2015 LG Absorption Chiller


Specification Direct fired absorption chiller & heater

WCDN Series
Model name 028 032 036 040 045 050 056 063 070
USRT 280 320 360 400 450 500 560 630 700
Cooling capacity
kW 985 1,125 1,266 1,407 1,583 1,758 1,969 2,216 2,462
kcal/h 745,000 852,000 958,000 1,064,000 1,198,000 1,330,000 1,490,000 1,676,000 1,863,900
Heating capacity
kW 866 991 1,114 1,237 1,393 1,547 1,733 1,949 2,168
Temperature C 12 7.0
Water flow rate m3/h 169.3 193.5 217.7 241.9 272.2 302.4 338.7 381 423.4
Chilled
water Pressure drop mAq 7.5 8.0 8.0 8.5 7.5 7.5 7.5 10.5 13.5
data
A(mm) 150 150 150 150 200 200 200 200 200
Connection size
B(inch) 6 6 6 6 8 8 8 8 8
Temperature C 55.6 60.0
Water flow rate m3/h 169.3 193.5 217.7 241.9 272.2 302.4 338.7 381 423.4
Hot
water Pressure drop mAq 7.5 8.0 8.0 8.5 7.5 7.5 7.5 10.5 13.5
data
A(mm) 150 150 150 150 200 200 200 200 200
Connection size
B(inch) 6 6 6 6 8 8 8 8 8
Temperature C 32.0 37.2
Water flow rate m3/h 280 320 360 400 450 500 560 630 700
Cooling
water Pressure drop mAq 8.5 9.0 7.5 8.0 9.0 10.0 9.0 12.0 15.5
data
A(mm) 200 200 200 200 250 250 300 300 300
Connection size
B(inch) 8 8 8 8 10 10 12 12 12
A(mm) 40 (at 4,000mmAq) 50 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 1 1/2 (at 4,000mmAq) 2 (at 4,000mmAq)
(Gas) Cooling 3
Nm /h 67.3 76.9 86.5 96.1 108.1 120.2 134.6 151.4 168.2
3
Heating Nm /h 85.0 97.2 109.3 121.4 136.7 151.8 170.1 191.3 212.7
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 23.9 23.9 25.6 26.9 26.9 26.9 35.7 35.7 35.7
Wire size mm2 6 6 10 10 10 10 16 16 16
Power kVA 14.9 15.9 15.9 17.9 17.9 17.9 23.5 23.5 23.5
Electrical
Absorbent pump no.1 kW(A) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 6.6(16.2) 6.6(16.2) 6.6(16.2)
data
Absorbent pump no.2 kW(A) 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Burner blower (gas) kW(A) 2.2(4.7) 2.2(4.7) 3.0(7.7) 3.0(7.7) 3.0(7.7) 3.0(7.7) 5.5(10.6) 5.5(10.6) 5.5(10.6)
Length mm 4,725 4,725 4,890 4,890 4,900 5,205 5,050 5,495 6,005
Dimension Width mm 2,320 2,260 2,425 2,545 2,840 2,840 3,350 3,150 3,255
Height mm 2,415 2,415 2,590 2,590 2,925 2,925 3,295 3,295 3,295
Operating ton 10.2 10.9 12.4 13.3 15.6 17.4 21.3 24.5 27.6
Rigging Max. shipping ton 9.4 9.9 11.2 12.0 14.1 15.7 18.8 21.8 24.7
Dry shipping ton 7.4 7.8 8.7 9.4 11.0 12.4 15.0 17.5 19.5
Flue connection size mm 310x310 310x310 360x310 360x310 410x310 410x310 500x350 500x350 500x350
Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,500 4,500 4,500 5,200 5,700

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
( But, WCDN005~N008 : 5kg/G(490kPa) )
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 013


Specification Direct fired absorption chiller & heater

WCDS Series
Model name 010 012 015 018 021 024 028 032 036 040 045 050
USRT 100 120 150 180 210 240 280 320 360 400 450 500
Cooling capacity
kW 352 422 528 633 739 844 985 1,125 1,266 1,407 1,583 1,758
kcal/h 253,000 303,600 379,500 455,400 531,300 607,200 708,400 809,600 910,800 1,012,000 1,138,500 1,265,000
Heating capacity
kW 294 353 441 529 617 706 823 941 1,059 1,176 1,323 1,470
Temperature C 12 7.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127.0 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Chilled
water Pressure drop mAq 8.0 8.1 10.2 10.5 9.6 10.0 6.4 6.7 7.1 7.3 6.8 5.8
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 55.8 60.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127.0 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Hot
water Pressure drop mAq 6.5 6.6 8 8.3 7.5 7.9 5.1 5.5 5.8 6.1 5.2 5.5
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 32.0 37.5
Water flow rate m3/h 100 120 150 180 210 240 280 320 360 400 450 500
Cooling
water Pressure drop mAq 3.9 4.4 6.5 7.7 5.6 6.2 10.9 12.1 8.7 9.4 10.3 11.2
data
A(mm) 125 125 125 125 150 150 200 200 200 200 250 250
Connection size
B(inch) 5 5 5 5 6 6 8 8 8 8 10 10
A(mm) 40 (at 4,000mmAq) 50 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 1 1/2 (at 4,000mmAq) 2 (at 4,000mmAq)
(Gas) Cooling 3
Nm /h 28.9 34.6 43.3 52.0 60.6 69.3 80.8 92.4 103.9 115.5 129.9 144.4
3
Heating Nm /h 28.9 34.6 43.3 52.0 60.6 69.3 80.8 92.4 103.9 115.5 129.9 144.4
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 10.6 10.6 11.6 12.8 12.8 12.8 24.2 24.2 24.2 27.2 28.6 28.6
Wire size mm2 4 4 4 4 4 4 4 4 4 6 6 6
Power kVA 7.0 7.0 7.6 8.4 8.4 8.4 15.9 15.9 15.9 17.9 18.8 18.8
Electrical
Absorbent pump no.1 kW(A) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.7(12.0) 3.7(12.0)
data
Absorbent pump no.2 kW(A) n/a n/a n/a n/a n/a n/a 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Burner blower (gas) kW(A) 0.72(2.1) 0.72(2.1) 0.72(2.1) 1.5(3.3) 1.5(3.3) 1.5(3.3) 2.2(4.7) 2.2(4.7) 2.2(4.7) 3.7(7.7) 3.7(7.7) 3.7(7.7)
Length mm 2,700 2,700 3,720 3,720 3,740 3,740 4,780 4,780 4,890 4,890 4,870 4,870
Dimension Width mm 1,990 1,990 1,990 2,010 2,190 2,210 2,170 2,170 2,310 2,350 2,570 2,570
Height mm 2,030 2,030 2,030 2,030 2,300 2,300 2,300 2,300 2,540 2,540 2,765 2,765
Operating ton 4.8 5.1 6.1 6.7 7.9 8.2 9.2 9.8 12.3 12.7 16.4 17.4
Rigging Max. shipping ton 4.0 4.2 5.1 5.6 6.4 7.6 8.1 8.7 10.8 11.1 14.5 15.0
Dry shipping ton 3.2 3.3 3.9 4.2 4.9 6.0 6.1 6.6 8.3 8.5 10.2 10.6
Flue connection size mm 280x210 280x210 280x210 280x210 310 x 310 310 x 310 310 x 310 310 x 310 360 x 310 360 x 310 410 x 310 410 x 310
Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 8kg/G(785kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

014 | 2015 LG Absorption Chiller


Specification Direct fired absorption chiller & heater

WCDS Series
Model name 056 063 070 080 090 100S 110 120 130 140 150
USRT 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Cooling capacity
kW 1,969 2,216 2,462 2,813 3,165 3,517 3,869 4,220 4,572 4,924 5,275
kcal/h 1,416,800 1,593,900 1,771,000 2,024,000 2,277,000 2,530,000 2,783,000 3,036,000 3,289,000 3,542,000 3,795,000
Heating capacity
kW 1,647 1,852 2,058 2,352 2,646 2,940 3,234 3,529 3,823 4,117 4,411
Temperature C 12 7.0
Water flow rate m3/h 338.7 381 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Chilled
water Pressure drop mAq 6.6 9.1 12.1 6.1 8.3 10.9 8.3 10.6 13.1 10.7 13.1
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 55.8 60.0
Water flow rate m3/h 338.7 381 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Hot
water Pressure drop mAq 5.2 7.1 9.4 4.7 6.4 8.4 6.2 7.9 9.8 8.0 9.8
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 32.0 37.5
Water flow rate m3/h 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Cooling
water Pressure drop mAq 8 10.6 13.7 8.4 11.1 14.3 8.8 10.9 13.4 12.3 14.6
data
A(mm) 300 300 300 350 350 350 400 400 400 400 400
Connection size
B(inch) 12 12 12 14 14 14 16 16 16 16 16
A(mm) 50 (at 4,000mmAq) 65 (at 4,000mmAq)
Nozzle size
Fuel B(inch) 2 (at 4,000mmAq) 2 1/2 (at 4,000mmAq)
(Gas) Cooling Nm3/h 161.7 181.9 202.1 231 259.9 288.7 317.6 346.5 375.4 404.2 433.1
3
Heating Nm /h 161.7 181.9 202.1 231 259.9 288.7 317.6 346.5 375.4 404.2 433.1
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 35.7 35.7 35.7 44.4 49.4 49.4 73.7 73.7 73.7 73.7 73.7
Wire size mm2 16 16 16 16 25 25 35 35 35 35 35
Power kVA 23.5 23.5 23.5 29.2 32.5 32.5 48.5 48.5 48.5 48.5 48.5
Electrical
Absorbent pump no.1 kW(A) 6.6(16.2) 6.6(16.2) 6.6(16.2) 5.5(20.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0)
data
Absorbent pump no.2 kW(A) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5)
Burner blower (gas) kW(A) 5.5(10.6) 5.5(10.6) 5.5(10.6) 7.5(14.0) 7.5(14.0) 7.5(14.0) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5)
Length mm 5,060 5,600 6,100 5,740 6,240 6,760 6,170 6,690 7,190 6,850 7,350
Dimension Width mm 3,080 3,080 3,080 3,400 3,400 3,400 4,180 4,180 4,180 4,590 4,590
Height mm 3,066 3,066 3,066 3,600 3,600 3,600 3,600 3,600 3,600 3,800 3,800
Operating ton 21.2 22.9 24.7 33.5 36.1 38.9 44.3 47.6 50.6 55.5 58.5
Rigging Max. shipping ton 19.1 20.6 22.1 29.4 31.8 34.3 39.8 42.8 45.5 50.0 52.6
Dry shipping ton 15.7 16.6 17.8 23.7 25.5 27.4 31.4 33.6 35.5 38.8 40.6
Flue connection size mm 500 x 350 500 x 350 500 x 350 620 x 400 620 x 400 620 x 400 900 x 400 900 x 400 900 x 400 900 x 400 900 x 400
Clearance for tube removal mm 4,600 5,200 5,700 5,200 5,700 6,200 5,700 6,200 6,700 6,200 6,700

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 8kg/G(785kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 015


Specification Direct fired absorption chiller & heater

WCDA Series
Model name 005 006 007 008
USRT 50 60 70 80
Cooling capacity
kW 176 211 246 281
103kcal/h 182 218 254 291
Heating capacity
kW 212 253 295 338
Temperature C 12 7.0
Water flow rate m3/h 30.3 36.3 42.4 48.4
Chilled
water Pressure drop mAq 3 3.3 2.4 2.5
data
A(mm) 80 80 80 80
Connection size
B(inch) 3 3 3 3
Temperature C 54.0 60.0
Water flow rate m3/h 30.3 36.3 42.4 48.4
Hot
water Pressure drop mAq 3 3.3 2.4 2.5
data
A(mm) 80 80 80 80
Connection size
B(inch) 3 3 3 3
Temperature C 32.0 37.6
Water flow rate m3/h 50 60 70 80
Cooling
water Pressure drop mAq 4.4 5.2 3.9 4.2
data
A(mm) 100 100 100 100
Connection size
B(inch) 4 4 4 4
A(mm) 25 (at 200mmAq) 40 (at 200mmAq)
Nozzle size
Fuel B(inch) 1 (at 200mmAq) 1 1/2 (at 200mmAq)
(Gas) Cooling Nm3/h 15.3 18.4 21.5 24.5
3
Heating Nm /h 21.1 25.3 29.5 33.7
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.2 8.2 9.5 9.5
Wire size mm2 4 4 4 4

Electrical Power kVA 5.4 5.4 6.2 6.2


data Absorbent Pump kW(A) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1)
Refrigerant Pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Burner blower (gas) kW(A) 0.37(1.0) 0.37(1.0) 0.74(2.3) 0.74(2.3)
Length mm 1,976 1,976 2,480 2,480
Dimension Width mm 1,875 1,875 1,875 1,875
Height mm 1,852 1,852 1,852 1,852
Operating ton 3.2 3.4 3.8 4.0
Rigging Max. shipping ton 2.9 3.1 3.5 3.7
Dry shipping ton 2.3 2.5 2.7 2.9
Flue connection size mm 190 x 100 190 x 100 270 x 150 270 x 150
Clearance for tube removal mm 1,700 1,700 2,200 2,200

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 5kg/G(490kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific value : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

016 | 2015 LG Absorption Chiller


Specification Steam fired absorption chiller

WCSH Series
Model name 010 012 015 018 021 024 028 032 036 040 045 050
USRT 100 120 150 180 210 240 280 320 360 400 450 500
Cooling capacity
kW 352 422 528 633 739 844 985 1,125 1,266 1,407 1,583 1,758
Temperature C 12 7.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Chilled
water Pressure drop mAq 6.2 6.3 8.0 8.3 8.0 8.1 5.4 5.5 5.6 5.8 5.1 5.2
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 32.0 37.0
Water flow rate m3/h 100 120 150 180 210 240 280 320 360 400 450 500
Hot
water Pressure drop mAq 3.9 4.2 6.1 6.9 6.1 6.6 8.3 8.8 7.4 8.0 8.8 9.7
data
A(mm) 125 125 125 125 150 150 200 200 200 200 250 250
Connection size
B(inch) 5 5 5 5 6 6 8 8 8 8 10 10
Steam Flow rate kg/h 350 420 525 630 735 840 980 1,120 1,260 1,400 1,575 1,750
A(mm) 50 50 50 50 50 50 65 65 80 80 80 80
Steam Inlet Connection
B(inch) 2 2 2 2 2 2 2.5 2.5 3 3 3 3
Fuel A(mm) 25 25 25 25 25 25 25 25 40 40 40 40
Drain Outlet Connection
B(inch) 1 1 1 1 1 1 1 1 1.5 1.5 1.5 1.5
A(mm) 25 25 40 40 40 40 40 50 50 50 50 50
Steam Control Valve
B(inch) 1 1 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 10.1 10.1 13.5 13.5 13.5 13.5 19.2 19.2 19.2 19.2 18.9 18.9
2
Wire size mm 4 4 4 4 4 4 6 6 10 10 10 10

Electrical Power kVA 6.6 6.6 8.9 8.9 8.9 8.9 12.6 12.6 12.6 12.6 12.4 12.4
data Absorbent pump no.1 kW(A) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3)
Absorbent pump no.2 kW(A) 0.4(1.6) 0.4(1.6) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Length mm 2,730 2,730 3,720 3,720 3,720 3,720 4,740 4,740 4,800 4,800 4,815 4,815
Dimension Width mm 1,810 1,810 1,810 1,810 2,000 2,000 2,070 2,070 2,200 2,200 2,385 2,385
Height mm 2,065 2,065 2,070 2,110 2,415 2,415 2,415 2,415 2,590 2,590 2,950 2,950
Operating ton 4.5 5.0 6.0 6.5 7.6 8.1 9.8 10.3 11.9 13.1 15.3 16.8
Rigging Max. shipping ton 4.1 4.6 5.5 5.9 6.8 7.2 8.7 9.2 10.5 11.6 13.5 14.8
Dry shipping ton 3.5 3.9 4.6 4.9 5.7 5.9 7.1 7.6 8.6 9.6 11.3 12.5
Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 017


Specification Steam fired absorption chiller

WCSH Series
Model name 056 063 070 080 090 100S 110 120 130 140 150
USRT 560 630 700 800 900 1000 1100 1200 1300 1400 1500
Cooling capacity
kW 1,969 2,216 2,462 2,813 3,165 3,517 3,869 4,220 4,572 4,924 5,275
Temperature C 12 7.0
Water flow rate m3/h 338.7 381 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Chilled
water Pressure drop mAq 5.2 7.2 9.6 4.4 6.0 7.9 5.8 6.1 9.2 7.6 9.3
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 32.0 37.0
Water flow rate m3/h 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Hot
water Pressure drop mAq 8.9 11.9 15.3 6.9 9.3 12.3 9.2 11.7 14.6 11.4 13.9
data
A(mm) 300 300 300 350 350 350 400 400 400 400 400
Connection size
B(inch) 12 12 12 14 14 14 16 16 16 16 16
Steam Flow rate kg/h 1,960 2,205 2,450 2,800 3,150 3,500 3,850 4,200 4,550 4,900 5,250
A(mm) 100 100 100 125 125 125 150 150 150 150 150
Steam Inlet Connection
B(inch) 4 4 4 5 5 5 6 6 6 6 6
Fuel
A(mm) 50 50 50 65 65 65 80 80 80 80 80
(Gas) Drain Outlet Connection
B(inch) 2 2 2 2.5 2.5 2.5 3 3 3 3 3
A(mm) 65 65 65 65 80 80 80 80 80 100 100
Steam Control Valve
B(inch) 2.5 2.5 2.5 2.5 3 3 3 3 3 4 4
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 25.1 25.1 25.1 26.6 35.4 35.4 53.2 53.2 53.2 53.2 53.2
2
Wire size mm 16 16 16 16 25 35 35 35 35 35 35

Electrical Power kVA 16.5 16.5 16.5 17.5 23.3 23.3 35.0 35.0 35.0 35.0 35.0
data Absorbent pump no.1 kW(A) 6.6(16.2) 6.6(16.2) 6.6(16.2) 6.6(16.2) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0)
Absorbent pump no.2 kW(A) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5)
Length mm 5,030 5,520 6,010 5,635 6,130 6,590 6,060 6,580 7,080 6,640 7,140
Dimension Width mm 2,620 2,620 2,620 3,090 3,090 3,090 3,180 3,180 3,180 3,520 3,520
Height mm 3,300 3,300 3,300 3,550 3,550 3,550 3,820 3,820 3,820 3,840 3,840
Operating ton 20.2 23.8 26.8 30.9 32.9 35.8 38.8 42.2 45.8 49.4 52.8
Rigging Max. shipping ton 17.4 20.7 23.5 26.6 28.3 30.9 33.9 36.9 40.2 43.2 46.3
Dry shipping ton 14.8 17.6 19.9 21.3 22.7 24.1 26.0 27.8 29.7 31.5 33.4
Clearance for tube removal mm 4,500 5,200 5,700 5,200 5,700 6,200 5,700 6,200 6,700 6,200 6,700

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

018 | 2015 LG Absorption Chiller


Specification Steam fired absorption chiller

WCSS Series
Model name 010 012 015 018 021 024 028 032 036 040 045 050
USRT 100 120 150 180 210 240 280 320 360 400 450 500
Cooling capacity
kW 352 422 527 633 738 844 985 1,125 1,266 1,407 1,582 1,758
Temperature C 12 7.0
Water flow rate m3/h 60.5 72.6 90.7 108.9 127 145.2 169.3 193.5 217.7 241.9 272.2 302.4
Chilled
water Pressure drop mAq 8.0 8.1 10.2 10.5 9.6 10.0 6.4 6.7 7.1 7.3 6.8 5.8
data
A(mm) 100 100 100 100 125 125 150 150 150 150 200 200
Connection size
B(inch) 4 4 4 4 5 5 6 6 6 6 8 8
Temperature C 32.0 37.5
Water flow rate m3/h 100 120 150 180 210 240 280 320 360 400 450 500
Hot
water Pressure drop mAq 3.9 4.4 6.5 7.7 5.6 6.2 10.9 12.1 8.7 9.4 10.3 11.2
data
A(mm) 125 125 125 125 150 150 200 200 200 200 250 250
Connection size
B(inch) 5 5 5 5 6 6 8 8 8 8 10 10
Steam Flow rate kg/h 440 528 660 792 924 1,060 1,230 1,410 1,580 1,760 1,980 2,200
A(mm) 50 50 50 50 65 65 65 65 80 80 80 80
Steam Inlet Connection
B(inch) 2 2 2 2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 3
Fuel A(mm) 25 25 25 25 25 25 25 25 40 40 40 40
Drain Outlet Connection
B(inch) 1 1 1 1 1 1 1 1 1 1/2 1 1/2 1 1/2 1 1/2
A(mm) 25 40 40 40 40 40 50 50 50 50 65 65
Steam Control Valve
B(inch) 1 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.5 8.5 9.5 9.5 9.5 9.5 19.2 19.2 19.2 19.2 20.6 20.6
2
Wire size mm 4 4 4 4 4 4 4 4 4 4 4 4

Electrical Power kVA 5.6 5.6 6.3 6.3 6.3 6.3 12.6 12.6 12.6 12.6 13.6 13.6
data Absorbent pump no.1 kW(A) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.7(12.0) 3.7(12.0)
Absorbent pump no.2 kW(A) n/a n/a n/a n/a n/a n/a 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Length mm 2,650 2,650 3,670 3,670 3,730 3,730 4,750 4,750 4,850 4,850 4,850 4,850
Dimension Width mm 1,800 1,800 1,800 1,800 2,030 2,030 2,030 2,030 2,110 2,110 2,350 2,350
Height mm 2,150 2,150 2,150 2,150 2,450 2,450 2,450 2,450 2,650 2,650 2,900 2,900
Operating ton 4.6 4.8 6.0 6.2 7.4 7.8 9.0 9.6 11.6 12.0 14.2 14.8
Rigging Max. shipping ton 4.0 4.2 5.3 5.6 6.5 6.7 8.0 8.3 10.1 10.5 12.4 12.8
Dry shipping ton 3.2 3.3 4.1 4.2 5.0 5.1 6.0 6.2 7.6 7.9 9.3 9.5
Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 019


Specification Steam fired absorption chiller

WCSS Series
Model name 056 063 070 080 090 100S 110 120 130 140 150
USRT 560 630 700 800 900 1,000 1,100 1,120 1,300 1,400 1,500
Cooling capacity
kW 1,969 2,215 2,461 2,813 3,165 3,516 3,868 3,938 4,571 4,923 5,274
Temperature C 12 7.0
Water flow rate m3/h 338.7 381.0 423.4 483.8 544.3 604.8 665.3 725.8 786.2 846.7 907.2
Chilled
water Pressure drop mAq 6.6 9.1 12.1 6.1 8.3 10.9 8.3 10.6 13.1 10.7 13.1
data
A(mm) 200 200 200 250 250 250 300 300 300 350 350
Connection size
B(inch) 8 8 8 10 10 10 12 12 12 14 14
Temperature C 32.0 37.5
Water flow rate m3/h 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Hot
water Pressure drop mAq 8.0 10.6 13.7 8.4 11.1 14.3 8.8 10.9 13.4 12.3 14.6
data
A(mm) 300 300 300 350 350 350 400 400 400 400 400
Connection size
B(inch) 12 12 12 14 14 14 16 16 16 16 16
Steam Flow rate kg/h 2,470 2,780 3,080 3,520 3,960 4,400 4,840 5,280 5,720 6,160 6,600
A(mm) 100 100 100 125 125 125 150 150 150 150 150
Steam Inlet Connection
B(inch) 4 4 4 5 5 5 6 6 6 6 6
Fuel
A(mm) 50 50 50 65 65 65 80 80 80 80 80
(Gas) Drain Outlet Connection
B(inch) 2 2 2 2 1/2 2 1/2 2 1/2 3 3 3 3 3
A(mm) 65 65 80 80 80 80 100 100 100 100 100
Steam Control Valve
B(inch) 2 1/2 2 1/2 3 3 3 3 4 4 4 4 4
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 25.1 25.1 25.1 26.6 35.4 35.4 53.2 53.2 53.2 53.2 53.2
2
Wire size mm 6 6 6 10 16 16 25 25 25 25 25

Electrical Power kVA 16.5 16.5 16.5 17.5 23.3 23.3 35.0 35.0 35.0 35.0 35.0
data Absorbent pump no.1 kW(A) 6.6(16.2) 6.6(16.2) 6.6(16.2) 6.6(16.2) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0)
Absorbent pump no.2 kW(A) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5)
Length mm 5,060 5,600 6,100 5,710 6,210 6,730 6,170 6,690 7,180 6,830 7,330
Dimension Width mm 2,500 2,500 2,500 2,850 2,850 2,850 3,000 3,000 3,000 3,500 3,500
Height mm 3,255 3,255 3,255 3,580 3,580 3,580 3,750 3,750 3,750 3,950 3,950
Operating ton 19.6 21.4 23.0 29.4 31.6 34.0 37.8 40.4 42.8 47.2 50.0
Rigging Max. shipping ton 16.9 18.5 19.8 25.4 27.3 29.3 33.2 35.5 37.7 41.7 44.0
Dry shipping ton 13.3 14.3 15.3 19.7 21.0 22.4 24.8 26.3 27.7 30.5 32.1
Clearance for tube removal mm 4,600 5,200 5,700 5,200 5,700 6,200 5,800 6,300 6,800 6,300 6,800

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

020 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WCMH Series
Model name 008 009 011 014 016 018 021
USRT 75 90 110 135 155 180 210
Cooling capacity
kW 264 316 387 475 545 633 738
Temperature C 13.0 8.0
Water flow rate m3/h 45.4 54.4 66.5 81.6 93.7 108.9 127.0
Chilled
water Pressure drop mAq 6.8 7.0 5.8 6.0 6.2 6.5 8.6
data
A(mm) 80 80 100 100 125 125 125
Connection size
B(inch) 3 3 4 4 5 5 5
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 92.1 110.6 135.1 165.9 190.4 221.1 258.0
Water
Pressure drop mAq 5.4 5.9 5.7 6.2 4.7 5.4 7.7
Data
A(mm) 125 125 150 150 150 150 200
Connection size
B(inch) 5 5 6 6 6 6 8
Temperature C 95..0 72.0
Water Flow rate ton/h 12.2 14.6 17.9 21.9 25.2 29.2 34.1
Pressure Drop mAq 0.9 1.0 2.3 2.4 2.4 2.6 4.8
Fuel A(mm) 65 65 65 65 80 80 80
Connection size
B(inch) 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3

Connection size A(mm) 40 40 50 50 65 65 80


of Control valve B(inch) 1 1/2 1 1/2 2 2 2 1/2 2 1/2 3
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.3 8.3 8.3 8.3 8.3 8.3 8.6
2
Wire size mm 4 4 4 4 4 4 4
Power kVA 5.4 5.4 5.4 5.4 5.4 5.4 5.7
kW 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Absorbent pump no.1
Electrical A 5.2 5.2 5.2 5.2 5.2 5.2 5.2
data kW N/A N/A N/A N/A N/A N/A 1.5
Absorbent pump no.2
A N/A N/A N/A N/A N/A N/A 5.5
kW 0.2 0.2 0.2 0.2 0.2 0.2 0.4
Refrigerant pump
A 1.1 1.1 1.1 1.1 1.1 1.1 1.4
kW 0.4 0.4 0.4 0.4 0.4 0.4 0.4
Purge pump
A 1.45 1.45 1.45 1.45 1.45 1.45 1.45
Length mm 2,747 2,747 3,767 3,767 3,827 3,827 4,732
Dimension Width mm 1,355 1,355 1,355 1,355 1,526 1,526 2,265
Height mm 2,150 2,150 2,150 2,150 2,330 2,330 2,090
Operating ton 4.9 5.2 6.4 6.8 8.3 8.6 10.1
Rigging Max. shipping ton 4.2 4.4 5.5 5.9 7.1 7.3 8.5
Dry shipping ton 3.6 3.7 4.6 4.9 5.8 6.0 6.8
Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 021


Specification Hot water fired absorption chiller

WCMH Series
Model name 024 027 030 034 038 042
USRT 240 270 300 340 375 420
Cooling capacity
kW 844 949 1,055 1,196 1,319 1,477
Temperature C 13.0 8.0
Water flow rate m3/h 145.2 163.3 181.4 205.6 226.8 254.0
Chilled
water Pressure drop mAq 8.8 8.8 8.9 9.4 9.7 6.5
data
A(mm) 125 150 150 200 200 200
Connection size
B(inch) 5 6 6 8 8 8
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 294.9 331.7 368.6 417.7 460.7 516.0
Water
Pressure drop mAq 8.4 7.4 8.1 7.9 8.6 7.3
Data
A(mm) 200 250 250 250 250 300
Connection size
B(inch) 8 10 10 10 10 12
Temperature C 95..0 72.0
Water Flow rate ton/h 39.0 43.8 48.7 55.2 60.9 68.2
Pressure Drop mAq 4.7 4.8 4.8 4.8 4.8 2.2
Fuel A(mm) 80 80 80 100 100 100
Connection size
B(inch) 3 3 3 4 4 4

Connection size A(mm) 80 80 80 100 100 100


of Control valve B(inch) 3 3 3 4 4 4
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.9 8.9 8.9 8.9 8.9 19.9
2
Wire size mm 4 4 4 4 4 6
Power kVA 5.8 5.8 5.8 5.8 5.8 13.1
kW 2.2 2.2 2.2 2.2 2.2 3.0
Absorbent pump no.1
Electrical A 5.5 5.5 5.5 5.5 5.5 11.0
data kW 1.5 1.5 1.5 2.0 2.0 2.0
Absorbent pump no.2
A 5.5 5.5 5.5 5.2 5.2 5.2
kW 0.4 0.4 0.4 0.4 0.4 0.4
Refrigerant pump
A 1.4 1.4 1.4 1.4 1.4 1.4
kW 0.4 0.4 0.4 0.4 0.4 0.4
Purge pump
A 1.45 1.45 1.45 1.45 1.45 1.45
Length mm 4,732 4,850 4,850 4,910 4,910 4,995
Dimension Width mm 2,265 2,380 2,380 2,550 2,550 2,745
Height mm 2,090 2,340 2,340 2,615 2,615 2,940
Operating ton 10.7 13.0 13.6 16.1 16.8 23.2
Rigging Max. shipping ton 9.0 10.9 11.4 13.4 14.0 19.4
Dry shipping ton 7.2 8.9 9.2 10.9 11.4 16.1
Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,500 4,600

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

022 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WCMH Series
Model name 047 053 060 068 075 083
USRT 470 525 600 675 750 825
Cooling capacity
kW 1,653 1,846 2,110 2,373 2,637 2,901
Temperature C 13.0 8.0
Water flow rate m3/h 284.3 317.5 362.9 408.2 453.6 499.0
Chilled
water Pressure drop mAq 8.4 10.6 7.0 8.7 11.3 6.8
data
A(mm) 200 200 250 250 250 300
Connection size
B(inch) 8 8 10 10 10 12
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 577.4 645.0 737.2 829.3 921.5 1013.6
Water
Pressure drop mAq 9.2 10.7 6.8 9.3 12.2 7.2
Data
A(mm) 300 300 350 350 350 400
Connection size
B(inch) 12 12 14 14 14 16
Temperature C 95..0 72.0
Water Flow rate ton/h 76.3 85.2 97.4 109.6 121.7 133.9
Pressure Drop mAq 3.0 4.0 2.8 3.7 4.9 1.4
Fuel A(mm) 100 100 125 125 125 150
Connection size
B(inch) 4 4 5 5 5 6

Connection size A(mm) 100 125 125 125 125 150


of Control valve B(inch) 4 5 5 5 5 6
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 19.9 21.4 21.4 21.4 26.4 44.2
2
Wire size mm 6 6 6 6 10 16
Power kVA 13.1 14.1 14.1 14.1 17.3 29.1
kW 3.0 3.0 3.0 3.0 4.5 4.5
Absorbent pump no.1
Electrical A 11.0 11.0 11.0 11.0 16.0 16.0
data kW 2.0 2.2 2.2 2.2 2.2 5.5
Absorbent pump no.2
A 5.2 6.7 6.7 6.7 6.7 21.0
kW 0.4 0.4 0.4 0.4 0.4 1.5
Refrigerant pump
A 1.4 1.4 1.4 1.4 1.4 3.9
kW 0.4 0.4 0.4 0.4 0.4 0.75
Purge pump
A 1.45 1.45 1.45 1.45 1.45 2.5
Length mm 5,540 6,035 5,680 6,180 6,705 6,340
Dimension Width mm 2,745 2,745 3,235 3,235 3,235 3,800
Height mm 2,940 2,940 3,175 3,175 3,175 3,650
Operating ton 25.1 26.4 33.0 35.4 38.0 42.8
Rigging Max. shipping ton 21.1 22.2 27.2 29.3 31.7 36.1
Dry shipping ton 17.4 18.1 22.0 23.6 25.4 28.6
Clearance for tube removal mm 5,200 5,700 5,200 5,700 6,200 5,800

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 023


Specification Hot water fired absorption chiller

WCMH Series
Model name 090 098 105 113 120 135
USRT 900 975 1050 1125 1200 1350
Cooling capacity
kW 3,165 3,428 3,692 3,956 4,220 4,747
Temperature C 13.0 8.0
Water flow rate m3/h 544.3 589.7 635.0 680.4 725.8 816.5
Chilled
water Pressure drop mAq 8.5 10.4 7.0 8.8 8.3 10.9
data
A(mm) 300 300 300 300 350 350
Connection size
B(inch) 12 12 12 12 14 14
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 1105.7 1197.9 1290.0 1382.2 1474.3 1658.6
Water
Pressure drop mAq 9.3 12.0 11.1 13.1 11.6 13.9
Data
A(mm) 400 400 400 400 450 450
Connection size
B(inch) 16 16 16 16 18 18
Temperature C 95..0 72.0
Water Flow rate ton/h 146.1 158.3 170.4 182.6 194.8 219.1
Pressure Drop mAq 1.8 2.2 1.9 2.2 2.5 2.5
Fuel A(mm) 150 150 200 200 200 200
Connection size
B(inch) 6 6 8 8 8 8

Connection size A(mm) 150 150 150 150 200 200


of Control valve B(inch) 6 6 6 6 8 8
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 44.2 44.2 44.2 44.2 44.2 44.2
2
Wire size mm 16 16 16 16 16 16
Power kVA 29.1 29.1 29.1 29.1 29.1 29.1
kW 4.5 4.5 4.5 4.5 4.5 4.5
Absorbent pump no.1
Electrical A 16.0 16.0 16.0 16.0 16.0 16.0
data kW 5.5 5.5 5.5 5.5 5.5 5.5
Absorbent pump no.2
A 21.0 21.0 21.0 21.0 21.0 21.0
kW 1.5 1.5 1.5 1.5 1.5 1.5
Refrigerant pump
A 3.9 3.9 3.9 3.9 3.9 3.9
kW 0.75 0.75 0.75 0.75 0.75 0.75
Purge pump
A 2.5 2.5 2.5 2.5 2.5 2.5
Length mm 6,865 7,365 7,070 7,570 7,570 8,070
Dimension Width mm 3,800 3,800 4,000 4,000 4,200 4,200
Height mm 3,650 3,650 3,750 3,750 3,850 3,850
Operating ton 45.8 48.6 54.0 56.9 62.9 66.5
Rigging Max. shipping ton 38.8 41.0 45.4 47.8 47.8 47.8
Dry shipping ton 30.5 32.3 35.5 37.3 37.3 37.3
Clearance for tube removal mm 6,300 6,800 6,300 6,800 6,800 7,400

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

024 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WCMW Series
Model name 003 004 005 007 008 010 012
USRT 28 30 38 40 47 50 61 65 75 80 94 100 113 120
Cooling capacity
kW 98 105 134 141 165 176 214 229 264 281 331 352 397 422
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 17.1 18.1 22.8 24.2 28.5 30.2 37.0 39.3 45.6 48.4 57.0 60.5 68.3 72.6
Chilled
water Pressure drop mAq 2.6 3.0 3.5 4.0 6.4 7.2 7.8 8.8 8.0 9.1 7.0 7.8 7.0 7.8
data
A(mm) 65 65 65 65 65 65 80 80 80 80 100 100 100 100
Connection size
B(inch) 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 3 4 4 4 4
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 37.4 39.4 49.8 52.5 62.3 65.7 81.0 85.4 99.7 105.1 124.6 131.3 149.5 157.6
Water
Pressure drop mAq 2.5 2.8 3.6 4.0 6.3 7.0 2.3 2.6 2.8 3.1 4.3 4.8 5.1 5.7
Data
A(mm) 80 80 80 80 80 80 125 125 125 125 125 125 125 125
Connection size
B(inch) 3 3 3 3 3 3 5 5 5 5 5 5 5 5
Temperature C 95..0 80.0
Water Flow rate ton/h 8.0 8.4 10.7 11.2 13.4 14.0 17.4 18.2 21.4 22.4 26.7 28.0 32.0 33.6
Pressure Drop mAq 1.1 1.2 1.2 1.3 2.6 2.9 0.8 0.9 0.9 1.0 2.1 2.3 2.2 2.4
Fuel A(mm) 40 40 40 40 65 65 65 65 65 65 80 80 80 80
Connection size
B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 3

Connection size A(mm) 40 40 40 40 40 40 50 50 65 65 65 65 80 80


of Control valve B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 1/2 2 1/2 2 1/2 2 1/2 3 3
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 7.2 7.2 7.2 7.2 7.2 7.2 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3
2
Wire size mm 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Electrical Power kVA 4.7 4.7 4.7 4.7 4.7 4.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
data Absorbent pump no.1 kW(A) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2)
Absorbent pump no.2 kW(A) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Length mm 2,020 2,020 2,020 2,020 2,520 2,520 2,547 2,547 2,547 2,547 3,567 3,567 3,567 3,567
Dimension Width mm 1,394 1,394 1,396 1,396 1,396 1,396 1,355 1,355 1,355 1,355 1,355 1,355 1,355 1,355
Height mm 1,952 1,952 1,965 1,965 1,965 1,965 2,150 2,150 2,150 2,150 2,150 2,150 2,150 2,150
Operating ton 2.1 2.1 2.3 2.3 2.7 2.7 4.1 4.1 4.3 4.3 5.3 5.3 5.7 5.7
Rigging Max. shipping ton 1.7 1.7 1.8 1.8 2.2 2.2 3.5 3.5 3.7 3.7 4.6 4.6 4.9 4.9
Dry shipping ton 1.3 1.3 1.4 1.4 1.6 1.6 3.0 3.0 3.1 3.1 3.8 3.8 4.1 4.1
Clearance for tube removal mm 2,000 2,000 2,000 2,000 2,400 2,400 2,400 2,400 2,400 2,400 3,400 3,400 3,400 3,400

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit)
WCMW003~WCMW005 : 5kg/G(490kPa)
WCMW003~WCMW005 : 8kg/G(785kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 025


Specification Hot water fired absorption chiller

WCMW Series
Model name 014 016 019 021 024 027
USRT 132 140 151 160 179 190 198 210 226 240 254 270
Cooling capacity
kW 464 492 531 563 629 668 696 738 795 844 893 949
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 79.7 84.7 91.1 96.8 108.2 114.9 119.6 127.0 136.7 145.2 153.8 163.3
Chilled
water Pressure drop mAq 7.2 8.2 7.7 8.6 7.1 7.9 7.0 7.8 7.1 8.0 6.8 7.7
data
A(mm) 100 100 100 100 125 125 125 125 150 150 150 150
Connection size
B(inch) 4 4 4 4 5 5 5 5 6 6 6 6
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 174.4 183.9 199.4 210.2 236.8 249.6 261.7 275.8 299.1 315.2 336.4 354.6
Water
Pressure drop mAq 3.6 4.0 4.1 4.6 7.3 8.1 7.8 8.7 5.7 6.3 6.3 7.0
Data
A(mm) 150 150 150 150 200 200 200 200 200 200 200 200
Connection size
B(inch) 6 6 6 6 8 8 8 8 8 8 8 8
Temperature C 95..0 80.0
Water Flow rate ton/h 37.4 39.2 42.7 44.8 50.7 53.2 56.1 58.8 64.1 67.2 72.1 75.6
Pressure Drop mAq 2.2 2.4 2.4 2.6 4.4 4.8 4.3 4.7 4.4 4.8 4.4 4.8
Fuel A(mm) 80 80 80 80 100 100 100 100 100 100 100 100
Connection size
B(inch) 3 3 3 3 4 4 4 4 4 4 4 4

Connection size A(mm) 80 80 80 80 100 100 100 100 100 100 100 100
of Control valve B(inch) 3 3 3 3 4 4 4 4 4 4 4 4
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.3 8.3 8.3 8.3 8.6 8.6 8.9 8.9 8.9 8.9 8.9 8.9
2
Wire size mm 4 4 4 4 4 4 4 4 4 4 4 4

Electrical Power kVA 5.4 5.4 5.4 5.4 5.7 5.7 5.8 5.8 5.8 5.8 5.8 5.8
data Absorbent pump no.1 kW(A) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5)
Absorbent pump no.2 kW(A) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Length mm 3,627 3,627 3,627 3,627 4,630 4,630 4,630 4,630 4,784 4,784 4,784 4,784
Dimension Width mm 1,526 1,526 1,526 1,526 1,526 1,526 1,526 1,526 1,575 1,575 1,575 1,575
Height mm 2,330 2,330 2,330 2,330 2,330 2,330 2,330 2,330 2,630 2,630 2,630 2,630
Operating ton 6.9 6.9 7.2 7.2 8.4 8.4 8.9 8.9 10.8 10.8 11.3 11.3
Rigging Max. shipping ton 5.8 5.8 6.1 6.1 7.1 7.1 7.5 7.5 9.1 9.1 9.5 9.5
Dry shipping ton 4.8 4.8 5.0 5.0 5.7 5.7 6.0 6.0 7.4 7.4 7.7 7.7
Clearance for tube removal mm 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit)
WCMW003~WCMW005 : 5kg/G(490kPa)
WCMW003~WCMW005 : 8kg/G(785kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

026 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WCMW Series
Model name 031 034 038 043 048 054 060
USRT 292 310 320 340 358 380 405 430 452 480 509 540 565 600
Cooling capacity
kW 1,027 1,090 1,125 1,196 1,259 1,336 1,424 1,512 1,589 1,688 1,790 1,899 1,987 2,110
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 176.6 187.5 193.7 205.6 216.4 229.8 244.9 260.1 273.4 290.3 307.6 326.6 341.7 362.9
Chilled
water Pressure drop mAq 7.9 8.9 7.7 8.6 7.0 7.8 9.7 10.9 13.0 14.6 7.2 8.2 9.6 10.8
data
A(mm) 150 150 150 150 200 200 200 200 200 200 200 200 200 200
Connection size
B(inch) 6 6 6 6 8 8 8 8 8 8 8 8 8 8
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 386.3 407.2 423.7 446.6 473.5 499.1 535.8 564.8 598.1 630.5 672.9 709.3 747.6 788.1
Water
Pressure drop mAq 7.2 8.0 7.7 8.6 5.8 6.4 7.8 8.7 10.2 11.3 5.9 6.6 7.7 8.5
Data
A(mm) 250 250 250 250 300 300 300 300 300 300 350 350 350 350
Connection size
B(inch) 10 10 10 10 12 12 12 12 12 12 14 14 14 14
Temperature C 95..0 80.0
Water Flow rate ton/h 82.8 86.8 90.8 95.2 101.5 106.4 114.8 120.4 128.2 134.4 144.2 151.2 160.2 168.0
Pressure Drop mAq 4.4 4.8 4.4 4.8 2.0 2.2 2.7 3.0 3.6 4.0 2.5 2.8 3.4 3.7
Fuel A(mm) 125 125 125 125 150 150 150 150 150 150 200 200 200 200
Connection size
B(inch) 5 5 5 5 6 6 6 6 6 6 8 8 8 8

Connection size A(mm) 125 125 125 125 125 125 125 125 150 150 150 150 150 150
of Control valve B(inch) 5 5 5 5 5 5 5 5 6 6 6 6 6 6
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 8.9 8.9 8.9 8.9 19.9 19.9 19.9 19.9 21.4 21.4 21.4 21.4 21.4 21.4
2
Wire size mm 4 4 4 4 6 6 6 6 6 6 6 6 6 6

Electrical Power kVA 5.8 5.8 5.8 5.8 13.1 13.1 13.1 13.1 14.1 14.1 14.1 14.1 14.1 14.1
data Absorbent pump no.1 kW(A) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0)
Absorbent pump no.2 kW(A) n/a n/a n/a n/a 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45)
Length mm 4,789 4,789 4,789 4,789 4,931 4,931 5,473 5,473 5,971 5,971 5,616 5,616 6,114 6,114
Dimension Width mm 1,702 1,702 1,702 1,702 2,015 2,015 2,015 2,015 2,015 2,015 2,195 2,195 2,195 2,195
Height mm 2,886 2,886 2,886 2,886 3,260 3,260 3,260 3,260 3,260 3,260 3,680 3,680 3,680 3,680
Operating ton 13.4 13.4 14 14 19.3 19.3 20.9 20.9 22.0 22.0 27.5 27.5 29.5 29.5
Rigging Max. shipping ton 11.2 11.2 11.7 11.7 16.2 16.2 17.6 17.6 18.5 18.5 22.7 22.7 24.4 24.4
Dry shipping ton 9.1 9.1 9.5 9.5 13.4 13.4 14.5 14.5 15.1 15.1 18.3 18.3 19.7 19.7
Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,600 4,600 5,200 5,200 5,700 5,700 5,200 5,200 5,700 5,700

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit)
WCMW003~WCMW005 : 5kg/G(490kPa)
WCMW003~WCMW005 : 8kg/G(785kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 027


Specification Hot water fired absorption chiller

WCMW Series
Model name 067 074 081 088 095 102
USRT 631 670 697 740 763 810 829 880 895 950 961 1020
Cooling capacity
kW 2,219 2,356 2,451 2,602 2,683 2,848 2,915 3,094 3,147 3,340 3,379 3,587
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 381.6 405.2 421.5 447.6 461.4 489.9 501.2 532.2 541.1 574.6 581.0 616.9
Chilled
water Pressure drop mAq 12.7 14.3 9.5 10.7 12.1 13.7 15.0 16.9 12.2 13.8 15.2 17.2
data
A(mm) 200 200 250 250 250 250 250 250 300 300 300 300
Connection size
B(inch) 8 8 10 10 10 10 10 10 12 12 12 12
Temperature C 31.0 36.5
Cooling Water flow rate m3/h 834.9 880.0 922.1 972.0 1009.0 1064.0 1097.0 1156.0 1184.0 1248.0 1271.0 1340.0
Water
Pressure drop mAq 10.0 11.1 6.2 6.9 7.7 8.6 9.5 10.6 8.8 9.8 10.4 11.6
Data
A(mm) 350 350 400 400 400 400 400 400 400 400 400 400
Connection size
B(inch) 14 14 16 16 16 16 16 16 16 16 16 16
Temperature C 95..0 80.0
Water Flow rate ton/h 178.9 187.6 197.6 207.2 216.3 226.8 235.0 246.4 253.7 266.0 272.4 285.6
Pressure Drop mAq 4.5 4.9 1.3 1.4 1.6 1.8 2.0 2.2 1.7 1.9 2.0 2.2
Fuel A(mm) 200 200 200 200 200 200 200 200 200 200 200 200
Connection size
B(inch) 8 8 8 8 8 8 8 8 8 8 8 8

Connection size A(mm) 150 150 200 200 200 200 200 200 200 200 200 200
of Control valve B(inch) 6 6 8 8 8 8 8 8 8 8 8 8
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 26.4 26.4 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2
2
Wire size mm 10 10 16 16 16 16 16 16 16 16 16 16

Electrical Power kVA 17.3 17.3 29.1 29.1 29.1 29.1 29.1 29.1 29.1 29.1 29.1 29.1
data Absorbent pump no.1 kW(A) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0)
Absorbent pump no.2 kW(A) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9)
Purge pump kW(A) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5)
Length mm 6,639 6,639 6,346 6,346 6,871 6,871 7,371 7,371 7,070 7,070 7,570 7,570
Dimension Width mm 2,195 2,195 2,680 2,680 2,680 2,680 2,680 2,680 2,910 2,910 2,910 2,910
Height mm 3,680 3,680 3,920 3,920 3,920 3,920 3,920 3,920 4,040 4,040 4,040 4,040
Operating ton 31.7 31.7 35.7 35.7 38.2 38.2 40.5 40.5 45 45 47.4 47.4
Rigging Max. shipping ton 26.4 26.4 30.1 30.1 32.3 32.3 34.2 34.2 37.8 37.8 39.8 39.8
Dry shipping ton 21.2 21.2 23.8 23.8 25.4 25.4 26.9 26.9 29.6 29.6 31.1 31.1
Clearance for tube removal mm 6,200 6,200 5,800 5,800 6,300 6,300 6,800 6,800 6,300 6,300 6,800 6,800

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit)
WCMW003~WCMW005 : 5kg/G(490kPa)
WCMW003~WCMW005 : 8kg/G(785kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

028 | 2015 LG Absorption Chiller


Absorption chiller cycle WC2H

2015 LG HVAC Solution | 029


Specification Hot water fired absorption chiller

WC2H Series
Model name 008 009 011 014 016 018 021
USRT 73 75 88 90 107 110 132 135 151 155 176 180 205 210
Cooling capacity
kW 258 264 309 316 378 387 464 474 532 545 618 633 721 738
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 44.3 45.4 53.2 54.4 65.0 66.5 79.8 81.6 91.6 93.7 106.4 108.9 124.1 127.0
Chilled
water Pressure drop mAq 6.5 6.8 6.7 7.0 5.5 5.8 5.7 6.0 5.9 6.2 6.2 6.5 8.2 8.6
data
A(mm) 80 80 80 80 100 100 100 100 125 125 125 125 125 125
Connection size
B(inch) 3 3 3 3 4 4 4 4 5 5 5 5 5 5
Temperature C 31.0 36.5
Water flow rate m3/h 95 97 114 116 139 142 171 175 196 200 227 233 265 271
Cooling
Water Pressure drop mAq 5.7 6.0 6.2 6.5 6.0 6.3 6.6 6.9 5.0 5.2 5.7 6.0 8.1 8.5
Data
A(mm) 125 125 125 125 150 150 150 150 150 150 150 150 200 200
Connection size
B(inch) 5 5 5 5 6 6 6 6 6 6 6 6 8 8
Temperature C 95..0 55.0
Water Flow rate ton/h 7.5 7.7 9.0 9.2 11.0 11.2 13.5 13.8 15.5 15.8 18.0 18.4 21.0 21.5
Pressure Drop mAq 4.4 4.6 4.7 4.9 4.1 4.3 4.8 5.0 4.8 5.0 5.2 5.5 5.5 5.8
Pressure Drop(Valve) mAq 1.0 1.0 1.3 1.4 2.0 2.1 2.9 3.0 2.8 2.9 3.4 3.6 1.9 2.0
Fuel
A(mm) 65 65 65 65 65 65 65 65 80 80 80 80 80 80
Connection size
B(inch) 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 3 3 3

Connection size A(mm) 40 40 40 40 40 40 40 40 50 50 50 50 65 65


of Control valve B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 11.8 11.8 11.8 11.8 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 24.0 24.0
2
Wire size mm 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 5.5 5.5

Electrical Power kVA 7.7 7.7 7.7 7.7 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 15.8 15.8
data Absorbent pump no.1 kW(A) 2.8(6.3) 2.8(6.3) 2.8(6.3) 2.8(6.3) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 5.4(17.4) 5.4(17.4)
Absorbent pump no.2 kW(A) 0.6(2.4) 0.6(2.4) 0.6(2.4) 0.6(2.4) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(3.2) 0.8(3.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1)
Purge pump kW(A) 0.4(1.45)
Length mm 2,630 2,630 2,630 2,630 3,650 3,650 3,650 3,650 3,712 3,712 3,712 3,712 4,732 4,732
Dimension Width mm 1,750 1,750 1,750 1,750 1,750 1,750 1,750 1,750 1,865 1,865 1,865 1865 1,865 1,865
Height mm 2,400 2,400 2,400 2,400 2,400 2,400 2,690 2,690 2,690 2,690 2,690 2690 2,690 2,690
Operating ton 5.2 5.2 5.5 5.5 6.9 6.9 7.4 7.4 8.9 8.9 9.5 9.5 11.1 11.1
Rigging
Max. shipping ton 4.4 4.4 4.6 4.6 5.9 5.9 6.2 6.2 7.4 7.4 7.8 7.8 9.3 9.3
Clearance for tube removal mm 2,400 2,400 2,400 2,400 3,400 3,400 3,400 3,400 3,400 3,400 3,400 3,400 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

030 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WC2H Series
Model name 024 027 030 034 038 042
USRT 234 240 264 270 293 300 332 340 366 375 410 420
Cooling capacity
kW 824 843 927 949 1,030 1,054 1,167 1,195 1,288 1,318 1,442 1,476
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 141.8 145.2 159.5 163.3 177.3 181.4 200.9 205.6 221.6 226.8 248.2 254.0
Chilled
water Pressure drop mAq 8.4 8.8 8.4 8.8 8.5 8.9 9.0 9.4 9.3 9.7 6.2 6.5
data
A(mm) 125 125 150 150 150 150 200 200 200 200 200 200
Connection size
B(inch) 5 5 6 6 6 6 8 8 8 8 8 8
Temperature C 31.0 36.5
Water flow rate m3/h 303 310 341 349 379 388 429 440 474 485 530 543
Cooling
Water Pressure drop mAq 8.9 9.3 7.8 8.2 8.6 9.0 8.4 8.8 9.2 9.6 7.7 8.1
Data
A(mm) 200 200 250 250 250 250 250 250 250 250 300 300
Connection size
B(inch) 8 8 10 10 10 10 10 10 10 10 10 10
Temperature C 95..0 55.0
Water Flow rate ton/h 24.0 24.5 26.9 27.6 29.9 30.6 33.9 34.7 37.4 38.3 41.9 42.9
Pressure Drop mAq 6.0 6.3 5.5 5.8 5.7 6.0 5.4 5.7 5.7 6.0 5.3 5.6
Pressure Drop(Valve) mAq 2.5 2.6 3.1 3.2 1.5 1.6 1.9 2.0 2.4 2.5 2.9 3.0
Fuel
A(mm) 80 80 100 100 100 100 100 100 100 100 100 100
Connection size
B(inch) 3 3 4 4 4 4 4 4 4 4 4 4

Connection size A(mm) 65 65 80 80 80 80 80 80 80 80 80 80


of Control valve B(inch) 2 1/2 2 1/2 3 3 3 3 3 3 3 3 3 3
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 24.0 24.0 24.0 24.0 24.0 24.0 27.2 27.2 27.2 27.2 28.2 28.2
2
Wire size mm 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0

Electrical Power kVA 15.8 15.8 15.8 15.8 15.8 15.8 17.9 17.9 17.9 17.9 18.5 18.5
data Absorbent pump no.1 kW(A) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 6.4(19.0) 6.4(19.0) 6.4(19.0) 6.4(19.0) 6.7(20.0) 6.7(20.0)
Absorbent pump no.2 kW(A) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.45)
Length mm 4,732 4,732 4,850 4,850 4,850 4,850 4,910 4,910 4,910 4,910 4,995 4,995
Dimension Width mm 1,865 1,865 2,180 2,180 2,180 2,180 2,450 2,450 2,450 2,450 2,745 2,745
Height mm 2,690 2,690 2,740 2,740 2,740 2,740 2,920 2,920 2,920 2,920 3,140 3,140
Operating ton 11.8 11.8 14.9 14.9 16.0 16.0 18.8 18.8 19.8 19.8 26.3 26.3
Rigging
Max. shipping ton 9.8 9.8 12.4 12.4 13.3 13.3 15.7 15.7 16.5 16.5 21.9 21.9
Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 031


Specification Hot water fired absorption chiller

WC2H Series
Model name 047 053 060 068 075 083
USRT 459 470 513 525 586 600 659 675 732 750 806 825
Cooling capacity
kW 1,614 1,652 1,803 1,845 2,060 2,109 2,318 2,372 2,573 2,636 2,833 2,900
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 277.7 284.3 310.2 317.5 354.5 362.9 398.9 408.2 442.7 453.6 487.5 499.0
Chilled
water Pressure drop mAq 8.0 8.4 10.1 10.6 6.7 7.0 8.3 8.7 10.8 11.3 6.5 6.8
data
A(mm) 200 200 200 200 250 250 250 250 250 250 300 300
Connection size
B(inch) 8 8 8 8 10 10 10 10 10 10 12 12
Temperature C 31.0 36.5
Water flow rate m3/h 594 608 663 679 758 776 853 873 946 970 1,042 1,067
Cooling
Water Pressure drop mAq 9.7 10.2 11.4 11.9 7.3 7.6 9.8 10.3 12.9 13.5 7.6 8.0
Data
A(mm) 300 300 300 300 350 350 350 350 350 350 400 400
Connection size
B(inch) 12 12 12 12 14 14 14 14 14 14 16 16
Temperature C 95..0 55.0
Water Flow rate ton/h 46.9 48.0 52.4 53.6 59.9 61.3 67.4 69.0 74.8 76.6 82.3 84.3
Pressure Drop mAq 3.4 3.6 4.6 4.8 3.1 3.2 4.0 4.2 5.1 5.4 4.1 4.3
Pressure Drop(Valve) mAq 1.4 1.5 1.9 2.0 2.4 2.5 3.1 3.2 3.7 3.9 1.7 1.8
Fuel
A(mm) 100 100 100 100 125 125 125 125 125 125 125 125
Connection size
B(inch) 4 4 4 4 5 5 5 5 5 5 5 5

Connection size A(mm) 100 100 100 100 100 100 100 100 100 100 125 125
of Control valve B(inch) 4 4 4 4 4 4 4 4 4 4 5 5
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 28.2 28.2 40.4 40.4 40.4 40.4 46.9 46.9 46.9 46.9 56.1 56.1
2
Wire size mm 8.0 8.0 14.0 14.0 14.0 14.0 22.0 22.0 22.0 22.0 22.0 22.0

Electrical Power kVA 18.5 18.5 26.6 26.6 26.6 26.6 30.8 30.8 30.8 30.8 36.9 36.9
data Absorbent pump no.1 kW(A) 6.7(20.0) 6.7(20.0) 8.7(27.0) 8.7(27.0) 8.7(27.0) 8.7(27.0) 10.5(33.5) 10.5(33.5) 10.5(33.5) 10.5(33.5) 11.5(37.5) 11.5(37.5)
Absorbent pump no.2 kW(A) 1.2(4.8) 1.2(4.8) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 4.0(12.0) 4.0(12.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 4.0(12.0) 4.0(12.0)
Purge pump kW(A) 0.4(1.45) 0.75(2.2)
Length mm 5,540 5,540 6,035 6,035 5,680 5,680 6,180 6,180 6,705 6,705 6,340 6,340
Dimension Width mm 2,745 2,745 2,745 2,745 3,480 3,480 3,480 3,480 3,480 3,480 3,800 3,800
Height mm 3,140 3,140 3140 3,140 3,600 3,600 3,600 3,600 3,600 3,600 3,900 3,900
Operating ton 28.4 28.4 30.2 30.2 37.5 37.5 39.7 39.7 42.6 42.6 47.5 47.5
Rigging
Max. shipping ton 23.7 23.7 25.2 25.2 31.7 31.7 33.8 33.8 36.6 36.6 39.5 39.5
Clearance for tube removal mm 5,200 5,200 5,700 5,700 5,200 5,200 5,700 5,700 6,200 6,200 5,800 5,800

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

032 | 2015 LG Absorption Chiller


Specification Hot water fired absorption chiller

WC2H Series
Model name 090 098 105 113 120 135
USRT 879 900 952 975 1,026 1,050 1,099 1,125 1,172 1,200 1,319 1,350
Cooling capacity
kW 3,090 3,163 3,344 3,427 3,605 3,690 3,863 3,954 4,120 4,217 4,636 4,745
Temperature C 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
Water flow rate m3/h 531.8 544.3 575.5 589.7 620.4 635.0 664.8 680.4 709.1 725.8 797.7 816.5
Chilled
water Pressure drop mAq 8.1 8.5 9.9 10.4 6.7 7.0 8.4 8.8 7.9 8.3 10.4 10.9
data
A(mm) 300 300 300 300 300 300 300 300 350 350 350 350
Connection size
B(inch) 12 12 12 12 12 12 12 12 14 14 14 14
Temperature C 31.0 36.5
Water flow rate m3/h 1,137 1,164 1,230 1,260 1,326 1,357 1,421 1,454 1,516 1,551 1,705 1,745
Cooling
Water Pressure drop mAq 9.8 10.3 12.7 13.3 11.7 12.3 13.9 14.6 12.3 12.9 14.7 15.4
Data
A(mm) 400 400 400 400 400 400 400 400 450 450 450 450
Connection size
B(inch) 16 16 16 16 16 16 16 16 18 18 18 18
Temperature C 95..0 55.0
Water Flow rate ton/h 89.8 91.9 97.2 99.6 104.8 107.3 112.3 114.9 119.8 122.6 134.7 137.9
Pressure Drop mAq 5.1 5.3 6.0 6.3 4.4 4.6 5.3 5.6 4.6 4.8 5.7 6.0
Pressure Drop(Valve) mAq 2.1 2.2 2.4 2.5 2.8 2.9 3.2 3.4 1.6 1.7 2.1 2.2
Fuel
A(mm) 125 125 125 125 150 150 150 150 150 150 150 150
Connection size
B(inch) 5 5 5 5 6 6 6 6 6 6 6 6

Connection size A(mm) 125 125 125 125 125 125 125 125 150 150 150 150
of Control valve B(inch) 5 5 5 5 5 5 5 5 6 6 6 6
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 56.1 56.1 56.1 56.1 75.1 75.1 75.1 75.1 75.1 75.1 75.1 75.1
2
Wire size mm 22.0 22.0 22.0 22.0 38.0 38.0 38.0 38.0 38.0 38.0 38.0 38.0

Electrical Power kVA 36.9 36.9 36.9 36.9 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4
data Absorbent pump no.1 kW(A) 11.5(37.5) 11.5(37.5) 11.5(37.5) 11.5(37.5) 17.5(52.5) 17.5(52.5) 17.5(52.5) 17.5(52.5) 17.5(52.5) 17.5(52.5) 17.5(52.5) 17.5(52.5)
Absorbent pump no.2 kW(A) 4.0(12.0) 4.0(12.0) 4.0(12.0) 4.0(12.0) 6.0(16.0) 6.0(16.0) 6.0(16.0) 6.0(16.0) 6.0(16.0) 6.0(16.0) 6.0(16.0) 6.0(16.0)
Refrigerant pump kW(A) 1.5(3.9)
Purge pump kW(A) 0.75(2.2)
Length mm 6,865 6,865 7,365 7,365 6,890 6,890 7,390 7,390 7,490 7,490 8,490 8,490
Dimension Width mm 3,800 3,800 3,800 3,800 4,530 4,530 4,530 4,530 4,780 4,780 4,780 4,780
Height mm 3,900 3,900 3,900 3,900 4,150 4,150 4,150 4,150 4,300 4,300 4,300 4,300
Operating ton 49.4 49.4 52.5 52.5 58.4 58.4 62.6 62.6 64.8 64.8 71.3 71.3
Rigging
Max. shipping ton 41.0 41.0 43.6 43.6 47.8 47.8 51.4 51.4 52.6 52.6 58.2 58.2
Clearance for tube removal mm 6,300 6,300 6,800 6,800 6,300 6,300 6,800 6,800 6,400 6,400 7,400 7,400

Note:
1. 1usRT = 3,024kcal/h, 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Chiller & Cooling Water Circuit): 10kg/G(981kPa)
3. Currents & Electricity Consumptions are based on 3 380V 60Hz
4. Alternate cooling water temperaure range available upon request.
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 033


Specification Absorption heat pump (Steam 0.8 MPa)

WCPX absorption heat pump


Model name 003 007 010 015 020 026 033 040 052 066
4
Waste heat source capacity 10 kcal/h 13 31 44 67 89 116 147 178 231 293
kW 349 814 1,162 1,743 2,324 3,022 3,835 4,649 6,044 7,671
Hot water Capacity
104kcal/h 30 70 100 150 200 260 330 400 520 660
Temperature C 55.0 59.0

Hot Water Water flow rate m3/h 8.7 20.3 29.0 43.5 58.0 75.4 95.7 116.0 150.8 191.4
Data Pressure drop mAq 5.8 10.0 7.4 10.1 8.5 12.8 11.0 9.8 10.0 7.5
Connection size A(mm) 40 65 65 65 80 100 100 125 125 150
Temperature C 46.0 40.0

Waste heat Water flow rate m3/h 22.5 52.5 74.9 112.4 149.9 194.9 247.3 299.8 389.7 494.6
source system Pressure drop mAq 5.0 4.4 4.4 4.5 4.4 8.6 8.8 8.4 11.3 6.0
Connection size A(mm) 65 100 100 100 125 150 150 200 200 250
Steam Flow rate kg/h 316 738 1,055 1,582 2,110 2,742 3,481 4,219 5,485 6,962
Steam Inlet Connection A(mm) 40 50 65 65 80 100 100 125 150 200
Steam Data
Drain outlet Connection A(mm) 25 25 25 32 40 50 65 65 80 80
Steam Control Vavle A(mm) 40 40 40 50 65 65 80 80 100 150
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 7.6 8.9 8.9 9.9 9.9 14.3 14.3 16.0 20.2 20.1
2
Wire size mm 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 5.5 5.5
Electrical
Power kVA 5.0 5.9 5.9 6.5 6.5 9.4 9.4 10.5 13.3 13.2
data
Absorbent pump no.1 kW(A) 1.2(4.1) 1.5(5.4) 1.5(5.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.7(12.0) 6.6(16.2) 6.6(16.2)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Purge pump kW(A) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6)
Length mm 2,180 2,680 2,680 3,700 3,760 4,780 4,880 4,880 5,630 5,740
Dimension Width mm 1,400 1,460 1,460 1,460 1,630 1,630 1,680 1,810 2,120 2,300
Height mm 2,090 2,210 2,210 2,350 2,600 2,600 2,960 3,270 3,800 4,000
Operating ton 3.0 4.6 4.9 6.5 8.4 10.4 13.1 16.0 23.8 30.6
Rigging Max. shipping ton 2.8 4.2 4.4 5.8 7.5 9.2 11.6 14.1 20.9 26.5
Dry shipping ton 2.4 3.6 3.7 4.7 6.1 7.4 9.4 11.5 17.3 22.0

Note:
1. 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Waste heat soruce & Hot Water Circuit): 10kg/G(981kPa)
3. Max. steam pressure : 785kPa = 8kg/G
4. Currents & Electricity Consumptions are based on 3 380V 60Hz
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

Refrigerant vapor

Outlet of heat source


Outlet of
hot water
Inlet of heat source
(Steam, Hot water) Generator Condenser
Strong s
olution
Absorbent Refrigerant
Heat (Water)
Refrigerant vapor
exchanger
Waste heat source

Outlet of waste heat source Hot water

Refrigerant vapor

Heat source
Inlet of waste heat source
Absorber Evaporator Diluted solution
(Stream, Sewer)
Inlet of hot water Strong solution
Diluted solution

034 | 2015 LG Absorption Chiller


Specification Absorption heat pump (Steam 0.8 MPa)

WCPX absorption heat pump


Model name 082 098 115 130 147 163 196 230 260
4
Waste heat source capacity 10 kcal/h 364 436 511 578 653 724 871 1,022 1,156
kW 9,530 11,390 13,366 15,109 17,085 18,944 22,780 26,731 30,218
Hot water Capacity
104kcal/h 820 980 1,150 1,300 1,470 1,630 1,960 2,300 2,600
Temperature C 55.0 59.0

Hot Water Water flow rate m3/h 237.8 284.2 333.5 377.0 426.3 472.7 568.4 667.0 754.0
Data Pressure drop mAq 12.4 16.5 19.5 12.6 16.7 21.3 19.8 23.4 15.1
Connection size A(mm) 150 200 200 250 250 250 300 350 350
Temperature C 46.0 40.0

Waste heat Water flow rate m3/h 614.5 734.4 861.9 974.3 1101.7 1221.6 1468.9 1723.7 1948.5
source system Pressure drop mAq 10.7 10.3 10.5 2.3 3.1 4.1 12.4 12.6 3.2
Connection size A(mm) 250 300 350 400 400 400 400 450 500
Steam Flow rate kg/h 8,649 10,337 12,130 13,712 15,505 17,193 20,674 24,260 27,424
Steam Inlet Connection A(mm) 200 200 250 250 250 250 200 x 2 250 x 2 250 x 2
Steam Data
Drain outlet Connection A(mm) 80 100 100 125 125 125 100 x 2 100 x 2 125 x 2
Steam Control Vavle A(mm) 150 150 200 200 200 200 150 x 2 200 x 2 200 x 2
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 30.0 32.6 32.6 45.6 45.6 45.6 64.1 64.1 91.2
2
Wire size mm 8 8 8 14 14 14 30 30 50
Electrical
Power kVA 19.7 21.5 21.5 30 30 30.0 42.2 42.2 60
data
Absorbent pump no.1 kW(A) 7.5(25.0) 7.5(25.0) 7.5(25.0) 15(36.0) 15(36.0) 15(36.0) 7.5(25.0) x 2 7.5(25.0) x 2 15(36.0) x 2
Refrigerant pump kW(A) 0.4(1.4) 1.5(4.0) 1.5(4.0) 3(5.8) 3(5.8) 3(5.8) 1.5(4.0) x 2 1.5(4.0) x 2 3(5.8) x 2
Purge pump kW(A) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) x 2 0.75(2.5) x 2 0.75(2.5) x 2
Length mm 6,760 6,720 6,860 7,370 8,170 8,970 6,720 6,860 7,370
Dimension Width mm 2,300 2,780 3,010 3,240 3,240 3,240 5,460 5,920 6,380
Height mm 4,000 4,200 4,300 4,400 4,400 4,400 4,300 4,400 4,400
Operating ton 35.1 41.3 48.2 55.8 59.3 62.9 82.6 96.5 112
Rigging Max. shipping ton 30.5 36.5 42.7 49.5 52.3 55.0 73.0 85.4 99.0
Dry shipping ton 25.1 29.4 34.2 40.2 42.0 43.7 29.4 34.2 40.2

Note:
1. 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Waste heat soruce & Hot Water Circuit): 10kg/G(981kPa)
3. Max. steam pressure : 785kPa = 8kg/G
4. Currents & Electricity Consumptions are based on 3 380V 60Hz
5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
6. The specifications are subject to change without prior notice.
7. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 035


Specification Absorption heat pump (Direct fired)

WCPX absorption heat pump (Direct fired)


Model name 003 007 010 015 020 026
4
Waste heat source capacity 10 kcal/h 13 31 44 67 89 116
kW 349 814 1,162 1,743 2,324 3,022
Hot water Capacity
104kcal/h 30 70 100 150 200 260
Temperature C 55.0 59.0

Hot Water Water flow rate m3/h 8.7 20.3 29.0 43.5 58.0 75.4
Data Pressure drop mAq 5.8 10.0 7.4 10.1 8.5 12.8
Connection size A(mm) 40 65 65 65 80 100
Temperature C 46.0 40.0

Waste heat Water flow rate m3/h 22.5 52.5 74.9 112.4 149.9 194.9
source system Pressure drop mAq 5.0 4.4 4.4 4.5 4.4 8.6
Connection size A(mm) 65 100 100 100 125 150
Fuel consumption N/h 16.0 37.4 53.4 80.1 106.8 138.9
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 9.8 11.1 13.5 14.8 21.7 26.1
Wire size mm2 3.5 3.5 3.5 3.5 5.5 8.0

Electrical Power kVA 6.5 7.3 8.9 9.7 14.3 17.2


data Absorbent pump no.1 kW(A) 1.2(4.1) 1.5(5.4) 1.5(5.4) 2.4(6.4) 2.4(6.4) 3.4(10.3)
Refrigerant pump kW(A) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4)
Burner kW(A) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6)
Purge pump kW(A) 0.72(2.2) 0.75(2.2) 1.5(4.6) 2.2(4.9) 5.5(11.8) 5.5(11.8)
Length mm 2,620 3,120 3,120 3,990 4,020 4,820
Dimension Width mm 2,140 2,190 2,190 2,190 2,540 2,560
Height mm 2,030 2,060 2,060 2,120 2,390 2,610
Operating ton 4.5 5.6 6.0 7.9 10.1 12.8
Rigging Max. shipping ton 4.3 5.2 5.5 7.2 9.1 11.6
Dry shipping ton 3.6 4.3 4.4 5.7 7.3 9.3

Note:
1. 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Waste heat soruce & Hot Water Circuit): 10kg/G(981kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific power : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

036 | 2015 LG Absorption Chiller


Specification Absorption heat pump (Direct fired)

WCPX absorption heat pump (Direct fired)


Model name 033 040 052 066 082
4
Waste heat source capacity 10 kcal/h 147 178 231 293 364
kW 3,835 4,649 6,044 7,671 9,530
Hot water Capacity
104kcal/h 330 400 520 660 820
Temperature C 55.0 59.0

Hot Water Water flow rate m3/h 95.7 116.0 150.8 191.4 237.8
Data Pressure drop mAq 11.0 9.8 10.0 7.5 12.4
Connection size A(mm) 100 125 125 150 150
Temperature C 46.0 40.0

Waste heat Water flow rate m3/h 247.3 299.8 389.7 494.6 614.5
source system Pressure drop mAq 8.8 8.4 11.3 6.0 10.7
Connection size A(mm) 150 200 200 250 250
Fuel consumption N/h 176.3 213.7 277.8 352.6 438.0
Source V 3 220/380/440V, 50Hz/60Hz
Total current A 30.3 32.0 36.2 42.9 59.3
Wire size mm2 8.0 8.0 14.0 14.0 22.0

Electrical Power kVA 19.9 21.1 23.8 28.2 39.0


data Absorbent pump no.1 kW(A) 3.4(10.3) 3.7(12.0) 6.6(16.2) 6.6(16.2) 7.5(25.0)
Refrigerant pump kW(A) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4)
Burner kW(A) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.4(1.6) 0.75(2.5)
Purge pump kW(A) 7.5(16.0) 7.5(16.0) 7.5(16.0) 11.0(22.7) 15.0(29.3)
Length mm 4,940 5,080 6,080 6,710 7,810
Dimension Width mm 2,830 3,010 3,500 4,020 4,070
Height mm 3,030 3,030 3,650 3,650 3,680
Operating ton 16.3 19.9 29.8 39.3 55.9
Rigging Max. shipping ton 14.8 18.0 26.9 35.3 51.4
Dry shipping ton 11.9 14.5 21.9 28.7 42.8

Note:
1. 1kW = 860kcal/h
2. Standard Tube and Water Side Pressure(Waste heat soruce & Hot Water Circuit): 10kg/G(981kPa)
3. Standard gas prssure : 4,000mmAq
4. Standard low calorific power : 9,360 kcal/N
5. Currents & Electricity Consumptions are based on 3 380V 60Hz
6. Power supply wire size is based on the due of metal conduit and 40C of ambient temperatue.
7. The specifications are subject to change without prior notice.
8. Fouling factor of water side: 0.0001 m2 hr C/kcal

2015 LG HVAC Solution | 037


Thermal insulation

Direct Fired (WCD Series, H,N,S-TYPE)


Don`t insulate fusible plug.

REFRIGERANT PUMP
: Don`t insulate the motor of refrigerant pump

75mm FOR WARM SURFACE NOTE.


Material : Glass Wool, Galvanized Steel Plate,
25mm FOR WARM SURFACE Nitrile-Butadiene Rubber(NBR)
1. Use noncombustible insulation material.
19mm FOR COLD SURFACE 2. Do not insulate motor of refrigerant pump.
3. Insulation area includes piping.
REMOVAL PART 4. The Chiller is coated with a anticorrosive paint at the factory.
Finish painting is typically performed in the eld after insulating is complete.

Hot Surface (m2) Cold(m2)


Capacity(RT)
75mm 25mm 19mm
100 6.3 5.0 4.4
120 6.9 5.3 4.4
150 8.1 6.1 5.9
180 8.7 6.5 5.9
210 10.1 7.1 6.8
240 10.9 7.2 6.8
280 11.9 8.8 8.4
320 12.6 9.0 8.4
360 14.5 9.9 9.9
400 15.3 10.0 9.9
450 17.5 10.5 11.2
500 18.4 10.7 11.2
REFRIGERANT PUMP
560 20.0 : Don`t insulate the motor of refrigerant pump 11.8 13.9
630 21.3 12.6 15
700 22.4 13.3 16.1
800 75mm FOR WARM SURFACE 27.2 NOTE.
14.7 17.3
Material : Glass Wool, Galvanized Steel Plate,
900 25mm FOR WARM SURFACE 29.0 15.5 Nitrile-Butadiene Rubber(NBR) 19.5
1. Use noncombustible insulation material.
1,000 19mm FOR COLD SURFACE 30.8 16.3
2. Do not insulate motor of refrigerant pump. 19.9
1,100 36.7 3. Insulation
18.4 area includes piping. 12.7
REMOVAL PART 4. The Chiller is coated with a anticorrosive paint at the factory.
1,200 38.7 Finish
19.1painting is typically performed in the eld after insulating
13.3 is complete.
1,300 40.7 19.8 13.8
1,400 45.5 20.7 14.6
1,500 47.0 21.5 15.1

038 | 2015 LG Absorption Chiller


25mm FOR WARM SURFACE
1. Use noncombustible insulation material.
19mm FOR COLD SURFACE 2. Do not insulate motor of refrigerant pump.
3. Insulation area includes piping.
REMOVAL PART 4. The Chiller is coated with a anticorrosive paint at the factory.
Finish painting is typically performed in the eld after insulating is complete.

Thermal insulation

Steam Fired (WCS Series H,S-TYPE)

REFRIGERANT PUMP
: Don`t insulate the motor of refrigerant pump

75mm FOR WARM SURFACE NOTE.


Material : Glass Wool, Galvanized Steel Plate,
25mm FOR WARM SURFACE Nitrile-Butadiene Rubber(NBR)
1. Use noncombustible insulation material.
19mm FOR COLD SURFACE 2. Do not insulate motor of refrigerant pump.
3. Insulation area includes piping.
REMOVAL PART 4. The Chiller is coated with a anticorrosive paint at the factory.
Finish painting is typically performed in the eld after insulating is complete.

Hot Surface (m2) Cold(m2)


Capacity(RT)
75mm 25mm 19mm
100 5.3 3.0 4.4
120 5.3 3.4 4.4
150 7.5 3.7 5.9
180 7.5 4.2 5.9
210 8.4 4.7 6.8
240 8.4 4.8 6.8
280 11.2 5.8 8.4
320 11.2 6.0 8.4
360 12.7 6.5 9.9
400 12.7 6.7 9.9
450 13.4 6.9 11.2
500 13.4 7.2 11.2
560 16.1 8.8 13.9
630 18.1 9.3 15
700 19.9 9.7 16.1
800 21.2 10.7 17.3
900 23.3 11.2 19.5
1,000 25.4 11.7 19.9
1,100 27.2 13.5 12.7
1,200 29.6 13.9 13.3
1,300 31.9 14.3 13.8
1,400 31.3 15.2 14.6
1,500 33.8 15.5 15.1

2015 LG HVAC Solution | 039


Direct fired absorption chiller
Piping diagram (H,N,S Type)

040 | 2015 LG Absorption Chiller


Steam absorption chiller
Piping diagram (H,S Type)

2015 LG HVAC Solution | 041


Hot water fired absorption chiller
Piping diagram (H,W Type)

042 | 2015 LG Absorption Chiller


Control diagram of cooling water inlet temperature

Direct/Steam/Hot water fired absorption chiller


Ensure that the cooling water temperature does not fall more cooling water temperature does not fall below 22C. During
than 10C below the design temperature. For example, if starting, however, a lower temperature is permissible until the
the cooling water inlet temperature is 32C, ensure that the machine reaches the rated capacity.
2. Cooling water thermostat setting value

1. Be sure to start and stop the fan by means of the


25C and above ... on
22C and below ... off,
(When the cooling water inlet temp. is 32C)

cooling water thermostat.

2015 LG HVAC Solution | 043


Standard of water quality

Standard of water quality


The cooling water of an open-type recycling cooling tower be degraded. As the water and air always come in contact
lowers temperature of the cooling water using vaporized with each other in the cooling tower, sulfurous acidgas, dust,
latent-heat and is reused. In this case, the water is evaporated sand, etc. in the atmosphere will mix into the water, further
and dissolved salts, Hardness materials, sulfate ion, etc. in the degrading the water quality. in the cooling water system,
water will increase. Namely, condensation phenomena of such problems with water are caused by these factors.
materials occurs in the water, and water quality will gradually Typical problems are corrosion, scales and slimes.

Cooling Water Chilled Water Tendency


Model One-pass or Make-up Circulating
Make-up Corrosion Scale
Circulating water water
pH(25C) 6.5~8.0 6.5~8.0 6.5~8.0 6.5~8.0 O O
Electrical conductivity
Max.800 Max.200 Max.500 Max.200 O O
(25C s/cm)
Alkalinity (ppm) Max.100 Max.50 Max.100 Max.50 O
Total hardness (ppm) Max.200 Max.50 Max.100 Max.50 O
Chlorine ion (ppm) Max.200 Max.50 Max.100 Max.50 O
Sulfuric acid ion (ppm) Max.200 Max.50 Max.100 Max.50 O
Total ion (ppm) Max.1.0 Max.0.3 Max.1.0 Max.0.3 O
Sulfur ion (ppm) No trace No trace No trace No trace O
Ammonium ion (ppm) Max.1.0 Max.1.0 Max.0.5 Max.0.2 O
Silica (ppm) Max.50 Max.30 Max.50 Max.30 O
Free carbonic acid (ppm) ******* ***** Max.1.0 Max.1.0 O

044 | 2015 LG Absorption Chiller


Fuel piping Combustion

Combustion Sequence Diagram

GAS
PRESSURE : 200mmAq
GASGAS GAS PRESSURE : 900~4,000mmAq

GAS PRESSURE : 200mmAq GAS PRESSURE : 900~4,000mmAq

OIL
OIL

* The information is typical

* The information is typical

Flue and Stack Connection


INTER LINING
1. Local regulations regarding exhaust of direct-fired burners
must be adhered to. These instructions shown are typical and INTER LINING
DRAFT
are not meant to supersede local codes in any way. REGULATOR FLUE(INSULATED) STACK

2. The steel stack should be lined on the interior surface to DRAFT


FLUE(INSULATED)
protect the stack from corrosion due to moisture in the DAMPER
REGULATOR STACK

exhaust gas. CONDENSATE


DAMPER
3. The flue and stack must be heat insulated and provided with DRAIN
FIRE PROOF
a condensate drain. CONDENSATE MORTAR
DRAIN
4. Do not connect the flue to an incinerator stack. FIRE PROOF
MORTAR
5. Place the top of the stack within a sufficient distance from
the cooling towers to prevent contamination.
6. Provide a barometric draft regulator or damper if fluctuations or
CONDENSATE
downdraft in static pressure are expected inside the flue. Some DRAIN

means of controlling the flue draft may be necessary to insure CONDENSATE


DRAIN
that proper combustion efficiency is maintained at all times.
7. If a common stack is to be used, exhaust must be prevented
from floeing into the unit(s) that are not in operation.
8. The draft pressure at the flue flange should be designed for a
maximum negative pressure of-5mmH2O.

2015 LG HVAC Solution | 045


Multi-Sectional shipment

WCDH Series
Entrance dimension of 3-sectional shipment
Entrance dimension of total unit
Upper shell Lower Shell High temperature generator
Model
Length Width Height Weight Length Width Height Weight Length Width Height Weight Length Width Height Weight

mm mm mm ton mm mm mm ton mm mm mm ton mm mm mm ton

WCDH010S 3,095 2,035 2,110 3.8 2,965 1,180 530 0.7 2,965 1,520 2,010 1.9 1,590 760 1,930 1.2

WCDH012S 3,095 2,035 2,110 4.0 2,965 1,180 530 0.8 2,965 1,520 2,010 2.1 1,590 760 1,930 1.2

WCDH015S 3,945 2,035 2,110 4.6 3,945 1,180 530 1.0 3,945 1,520 2,010 2.4 1,800 760 1,930 1.2

WCDH018S 3,945 2,165 2,110 5.0 3,945 1,180 530 1.0 3,945 1,520 2,010 2.6 1,950 880 1,930 1.4

WCDH021S 3,995 2,220 2,455 5.8 3,995 1,250 600 1.2 3,995 1,520 2,155 3.0 2,100 880 1,930 1.6

WCDH024S 3,995 2,240 2,455 6.1 3,995 1,250 600 1.2 3,995 1,520 2,155 3.1 2,270 900 2,110 1.7

WCDH028S 5,015 2,295 2,455 7.4 5,015 1,250 600 1.5 5,015 1,520 2,155 3.8 2,450 900 2,110 1.9

WCDH032S 5,015 2,295 2,455 7.8 5,015 1,250 600 1.6 5,015 1,520 2,155 4.0 2,750 910 2,130 2.0

WCDH036S 5,090 2,500 2,630 8.7 5,090 1,385 670 1.8 5,090 1,730 2,550 4.6 3,250 910 2,130 2.2

WCDH040S 5,090 2,585 2,630 9.4 5,090 1,385 670 2.0 5,090 1,730 2,550 5.0 3,000 1,000 2,370 2.4

WCDH045S 5,100 2,835 2,965 11.0 5,100 1,520 710 2.3 5,100 1,910 2,625 5.9 3,000 1,040 2,380 2.8

WCDH050S 5,100 2,925 2,965 12.4 5,100 1,520 710 2.4 5,100 1,910 2,625 6.1 3,190 1,130 2,600 3.4

WCDH056S 5,510 3,095 3,335 15.0 5,200 1,600 870 2.9 5,200 2,140 2,980 7.3 3,350 1,130 2,600 4.0

WCDH063S 5,720 3,220 3,335 17.5 5,720 1,600 870 3.3 5,720 2,140 2,980 8.6 3,230 1,370 3,080 4.5

WCDH070S 6,210 3,220 3,335 19.5 6,210 1,600 870 3.7 6,210 2,140 2,980 9.5 3,500 1,350 3,080 5.0

WCDH080S 5,810 3,870 3,590 21.0 5,835 1,770 1,090 4.0 5,835 2,570 2,840 10.3 3,650 1,400 3,600 6.0

WCDH090S 6,400 4,120 3,640 22.5 6,330 1,770 1,090 4.3 6,330 2,570 2,840 11.0 3,700 1,500 3,600 7.0

WCDH100S 6,900 4,120 3,640 24.0 6,790 1,770 1,090 4.6 6,790 2,570 2,840 11.8 3,900 1,500 3,600 8.0

WCDH110S 6,400 4,470 3,840 26.0 6,260 2,200 1,140 5.0 6,260 2,890 3,000 12.7 4,320 1,620 3,600 9.0

WCDH120S 6,900 4,470 3,840 28.0 6,780 2,200 1,140 5.3 6,780 2,890 3,000 13.7 4,620 1,620 3,600 10.0

WCDH130S 7,400 4,470 3,840 30.0 7,280 2,200 1,140 5.7 7,280 2,890 3,000 14.7 4,920 1,620 3,600 11.0

WCDH140S 7,050 4,870 3,940 32.0 6,840 2,300 1,170 6.1 6,840 3,500 3,000 15.7 4,940 1,870 3,800 12.0

WCDH150S 7,550 4,870 3,940 34.0 7,340 2,300 1,170 6.5 7,340 3,500 3,000 16.6 5,140 1,870 3,800 13.0

046 | 2015 LG Absorption Chiller


Multi-Sectional shipment

WCSH Series
Entrance dimension of 3-sectional shipment
Entrance dimension of total unit
Upper shell Lower Shell High temperature generator
Model
Length Width Height Weight Length Width Height Weight Length Width Height Weight Length Width Height Weight

mm mm mm ton mm mm mm ton mm mm mm ton mm mm mm ton

WCSH010 2,930 1,880 2,105 3.5 2,930 1,520 2,105 0.7 2,930 1,700 1,970 1.9 2,600 500 700 0.9

WCSH012 2,930 1,880 2,105 3.9 2,930 1,520 2,105 0.8 2,930 1,700 1,970 2.1 2,600 500 700 1.0

WCSH015 3,920 1,880 2,110 4.6 3,920 1,520 2,105 1.0 3,920 1,700 1,970 2.4 3,620 500 700 1.2

WCSH018 3,920 1,880 2,150 4.9 3,920 1,520 2,105 1.0 3,920 1,700 1,970 2.6 3,620 500 700 1.3

WCSH021 3,920 2,070 2,455 5.7 3,920 1,513 2,455 1.2 3,920 1,900 2,300 3.0 3,650 530 790 1.5

WCSH024 3,920 2,070 2,455 5.9 3,920 1,513 2,455 1.2 3,920 1900 2,300 3.1 3,650 530 790 1.6

WCSH028 4,940 2,140 2,455 7.1 4,940 1,513 2,455 1.5 4,940 1,900 2,300 3.8 4,680 530 790 1.9

WCSH032 4,940 2,140 2,455 7.6 4,940 1,513 2,455 1.6 4,940 1,900 2,300 4.0 4,680 530 790 2.0

WCSH036 5,000 2,270 2,630 8.6 5,000 1,730 2,630 1.8 5,000 2,000 2,510 4.6 4,730 630 850 2.3

WCSH040 5,000 2,270 2,630 9.6 5,000 1,730 2,630 2.0 5,000 2,000 2,510 5.1 4,730 630 850 2.6

WCSH045 5,015 2,455 2,990 11.3 5,015 1,910 2,965 2.1 5,015 2,100 2,590 5.4 4,860 720 920 3.8

WCSH050 5,015 2,455 2,990 12.5 5,015 1,910 2,965 2.4 5,015 2,100 2,590 6.1 4,860 720 920 4.1

WCSH056 5,230 2,690 3,340 14.8 5,230 2,140 3,335 2.9 5,230 2,290 2,940 7.3 4,900 770 1,070 4.6

WCSH063 5,720 2,690 3,340 17.6 5,720 2,140 3,335 3.3 5,720 2,290 2,940 8.6 5,450 770 1,070 5.7

WCSH070 6,210 2,690 3,340 19.9 6,210 2,140 3,335 3.7 6,210 2,290 2,940 9.5 5,940 770 1,070 6.7

WCSH080 5,835 3,160 3,590 21.3 5,835 2,570 3,590 4.0 5,835 3,090 2,810 10.3 5,600 1,000 1,230 7.1

WCSH090 6,330 3,160 3,590 22.7 6,330 2,570 3,590 4.3 6,330 3,090 2,810 11.0 6,000 1,000 1,230 7.4

WCSH100 6,790 3,160 3,590 24.1 6,790 2,570 3,590 4.6 6,790 3,090 2,810 11.8 6,530 1,000 1,230 7.8

WCSH110 6,260 3,250 3,860 26.0 6,260 3,370 3,820 5.0 6,260 2,870 2,850 12.7 6,000 930 1,230 8.3

WCSH120 6,780 3,250 3,860 27.8 6,780 3,370 3,820 5.3 6,780 2,870 2,850 13.7 6,990 930 1,230 8.8

WCSH130 7,280 3,250 3,860 29.7 7,280 3,370 3,820 5.7 7,280 2,870 2,850 14.7 6,000 930 1,230 9.3

WCSH140 6,840 3,590 3,880 31.5 6,840 3,500 3,880 6.1 6,840 3,000 2,950 15.7 6,540 950 1,310 9.8

WCSH150 7,340 3,590 3,880 33.4 7,340 3,500 3,880 6.5 7,340 3,000 2,950 16.6 7,040 950 1,310 10.3

2015 LG HVAC Solution | 047


Direct fired absorption chiller
Outline & Foundation & heater

WCDH
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance (mm)


Model
Length Width Height A B C D G
WCDH010S 2,895 1,965 2,070 5 4 4 5 2,400
WCDH012S 2,895 1,965 2,070 5 4 4 5 2,400
WCDH015S 3,745 1,965 2,070 5 4 4 5 3,400
WCDH018S 3,745 2,095 2,070 5 4 4 5 3,400
WCDH021S 3,795 2,150 2,415 6 5 5 6 3,400
WCDH024S 3,795 2,170 2,415 6 5 5 6 3,400
WCDH028S 4,815 2,225 2,415 8 6 6 8 4,500
WCDH032S 4,815 2,225 2,415 8 6 6 8 4,500
WCDH036S 4,890 2,430 2,590 8 6 6 8 4,500
WCDH040S 4,890 2,515 2,590 8 6 6 8 4,500
WCDH045S 4,900 2,765 2,925 10 8 8 10 4,500
WCDH050S 4,900 2,855 2,925 10 8 8 10 4,500
WCDH056S 5,310 3,025 3,295 12 8 8 12 4,500
WCDH063S 5,520 3,150 3,295 12 8 8 12 5,200
WCDH070S 6,010 3,150 3,295 12 8 8 12 5,700

048 | 2015 LG Absorption Chiller


Direct fired absorption chiller
Outline & Foundation & heater

WCDH
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance (mm)


Model
Length Width Height A B C D G
WCDH080S 5,635 3,800 3,550 14 10 10 14 5,200
WCDH090S 6,130 3,920 3,600 14 10 10 14 5,700
WCDH100S 6,590 3,920 3,600 14 10 10 14 6,200
WCDH110S 6,060 4,200 3,780 16 12 12 16 5,700
WCDH120S 6,580 4,300 3,780 16 12 12 16 6,200
WCDH130S 7,080 4,300 3,780 16 12 12 16 6,700
WCDH140S 6,640 4,700 3,840 16 14 14 16 6,200
WCDH150S 7,140 4,850 3,840 16 14 14 16 6,700

2015 LG HVAC Solution | 049


Direct fired absorption chiller
Outline & Foundation & heater

WCDH
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Nozzle connection (B)


Model
A B C D E Total
WCDH010S 2,500 2,000 1.7 0.7 0.9 5.0
WCDH012S 2,500 2,000 1.8 0.7 0.9 5.2
WCDH015S 3,500 2,000 2.3 0.7 0.9 6.2
WCDH018S 3,500 2,100 2.5 0.9 1.1 7.0
WCDH021S 3,500 2,150 3.0 1.0 1.2 8.2
WCDH024S 3,500 2,150 3.1 1.1 1.3 8.6
WCDH028S 4,500 2,250 4.0 1.2 1.4 10.6
WCDH032S 4,500 2,250 4.1 1.3 1.5 11.0
WCDH036S 4,500 2,500 4.7 1.4 1.6 12.4
WCDH040S 4,500 2,550 5.0 1.4 1.7 13.1
WCDH045S 4,500 2,900 5.9 1.7 2.0 15.5
WCDH050S 4,500 2,900 6.4 2.1 2.4 17.3
WCDH056S 4,500 3,100 8.0 2.4 2.8 21.2
WCDH063S 5,050 3,300 9.3 2.7 3.1 24.4
WCDH070S 5,550 3,300 10.4 3.0 3.4 27.2
WCDH080S 5,050 3,750 11.6 4.0 4.4 31.6
WCDH090S 5,550 4,000 12.0 4.7 5.2 33.9
WCDH100S 6,100 4,000 12.7 5.6 6.1 37.1
WCDH110S 5,150 4,150 13.5 6.4 7.0 40.4
WCDH120S 5,700 4,150 14.4 7.4 7.9 44.1
WCDH130S 6,200 4,150 15.5 8.3 8.8 48.1
WCDH140S 5,700 4,600 16.6 9.2 9.7 52.1
WCDH150S 6,200 4,600 17.5 10.1 10.8 55.9

050 | 2015 LG Absorption Chiller


Direct fired absorption chiller
Outline & Foundation & heater

WCDN
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance (mm)


Model
Length Width Height A B C D G
WCDN005 2,205 1,685 1,760 4 3 3 4 1,700
WCDN006 2,205 1,685 1,760 4 3 3 4 1,700
WCDN007 2,555 1,860 1,760 4 3 3 4 2,200
WCDN008 2,555 1,860 1,760 4 3 3 4 2,200
WCDN010 3,165 2,000 2,070 5 4 4 5 2,400
WCDN012 3,165 2,045 2,070 5 4 4 5 2,400
WCDN015 3,745 2,095 2,070 5 4 4 5 3,400
WCDN018 3,665 2,095 2,070 5 4 4 5 3,400
WCDN021 3,705 2,150 2,415 6 5 5 6 3,400
WCDN024 3,795 2,170 2,415 6 5 5 6 3,400
WCDN028 4,725 2,320 2,415 8 6 6 8 4,500
WCDN032 4,725 2,260 2,415 8 6 6 8 4,500
WCDN036 4,890 2,425 2,590 8 6 6 8 4,500
WCDN040 4,890 2,545 2,590 8 6 6 8 4,500
WCDN045 4,900 2,840 2,925 10 8 8 10 4,500
WCDN050 5,205 2,840 2,925 10 8 8 10 4,500
WCDN056 5,050 3,350 3,295 12 8 8 12 4,500
WCDN063 5,495 3,150 3,295 12 8 8 12 5,200
WCDN070 6,005 3,255 3,295 12 8 8 12 5,700

2015 LG HVAC Solution | 051


Direct fired absorption chiller
Outline & Foundation & heater

WCDN
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Weight (ton)


Model
A B C D E Total
WCDN005 1,868 1,333 1.2 0.5 0.3 3.2
WCDN006 1,868 1,333 1.3 0.5 0.3 3.4
WCDN007 2,318 1,480 1.5 0.5 0.3 3.8
WCDN008 2,318 1,480 1.5 0.6 0.4 4.0
WCDN010 2,300 2,000 1.6 0.8 1.0 4.9
WCDN012 2,300 2,100 1.8 0.8 1.0 5.2
WCDN015 3,300 2,100 2.1 0.9 1.1 6.2
WCDN018 3,300 2,100 2.4 1.0 1.2 6.8
WCDN021 3,300 2,150 2.7 1.2 1.4 8.0
WCDN024 3,300 2,150 2.9 1.2 1.4 8.5
WCDN028 4,500 2,250 3.8 1.2 1.4 10.2
WCDN032 4,500 2,250 4.0 1.3 1.5 10.9
WCDN036 4,500 2,650 4.4 1.6 2.0 12.4
WCDN040 4,500 2,650 4.8 1.7 2.1 13.3
WCDN045 4,500 3,000 5.6 2.0 2.4 15.6
WCDN050 4,500 3,000 6.4 2.1 2.5 17.4
WCDN056 4,500 3,300 7.7 2.7 3.1 21.3
WCDN063 5,500 3,300 9.1 3.0 3.4 24.5
WCDN070 5,500 3,300 10.3 3.3 3.7 27.6

052 | 2015 LG Absorption Chiller


Direct fired absorption chiller
Outline & Foundation & heater

WCDS
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance (mm)


Model
Length Width Height A B C D G
WCDS010S 2,700 1,990 2,030 5 4 4 5 2,400
WCDS012S 2,700 1,990 2,030 5 4 4 5 2,400
WCDS015S 3,720 1,990 2,030 5 4 4 5 3,400
WCDS018S 3,720 2,010 2,030 5 4 4 5 3,400
WCDS021S 3,740 2,190 2,300 6 5 5 6 3,400
WCDS024S 3,740 2,210 2,300 6 5 5 6 3,400
WCDS028S 4,780 2,170 2,300 8 6 6 8 4,500
WCDS032S 4,780 2,170 2,300 8 6 6 8 4,500
WCDS036S 4,890 2,310 2,540 8 6 6 8 4,500
WCDS040S 4,890 2,350 2,540 8 6 6 8 4,500
WCDS045S 4,870 2,570 2,765 10 8 8 10 4,500
WCDS050S 4,870 2,570 2,765 10 8 8 10 4,500
WCDS056S 5,060 3,080 3,255 12 8 8 12 4,600
WCDS063S 5,600 3,080 3,255 12 8 8 12 5,200
WCDS070S 6,100 3,080 3,255 12 8 8 12 5,700
WCDS080S 5,740 3,400 3,600 14 10 10 14 5,200
WCDS090S 6,240 3,400 3,600 14 10 10 14 5,700
WCDS100S 6,760 3,400 3,600 14 10 10 14 6,200

2015 LG HVAC Solution | 053


Direct fired absorption chiller
Outline & Foundation & heater

WCDS
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance (mm)


Model
Length Width Height A B C D G
WCDS110S 6,170 4,180 3,600 16 12 12 16 5,700
WCDS120S 6,690 4,180 3,600 16 12 12 16 6,200
WCDS130S 7,190 4,180 3,600 16 12 12 16 6,700
WCDS140S 6,850 4,590 3,800 16 14 14 16 6,200
WCDS150S 7,350 4,590 3,800 16 14 14 16 6,200

054 | 2015 LG Absorption Chiller


Direct fired absorption chiller
Outline & Foundation & heater

WCDS
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Weight (ton)


Model
A B C D E Total
WCDS010S 2,300 1,700 1.6 0.7 0.9 4.8
WCDS012S 2,300 1,700 1.7 0.8 0.9 5.1
WCDS015S 3,300 1,800 2.1 0.9 1.0 6.1
WCDS018S 3,300 1,800 2.3 1.0 1.1 6.7
WCDS021S 3,300 1,950 2.7 1.1 1.4 7.9
WCDS024S 3,300 1,950 2.8 1.2 1.4 8.2
WCDS028S 4,350 1,900 3.3 1.2 1.4 9.2
WCDS032S 4,350 1,900 3.5 1.3 1.5 9.8
WCDS036S 4,350 2,000 4.4 1.7 1.8 12.3
WCDS040S 4,350 2,000 4.5 1.8 1.9 12.7
WCDS045S 4,350 2,250 5.7 2.4 2.6 16.4
WCDS050S 4,350 2,250 5.8 2.8 3.0 17.4
WCDS056S 4,350 2,750 7.7 2.7 3.1 21.2
WCDS063S 4,900 2,750 8.3 3.0 3.3 22.9
WCDS070S 5,400 2,750 8.9 3.3 3.6 24.7
WCDS080S 4,900 3,100 12.4 4.1 4.6 33.5
WCDS090S 5,400 3,100 13.2 4.6 5.1 36.1
WCDS100S 5,900 3,100 14.1 5.2 5.5 38.9
WCDS110S 5,000 3,650 15.6 6.4 6.7 44.3
WCDS120S 5,500 3,650 16.7 6.9 7.3 47.6
WCDS130S 6,000 3,650 17.6 7.5 7.9 50.6
WCDS140S 5,500 4,000 19.3 8.3 8.6 55.5
WCDS150S 6,000 4,000 20.4 8.7 9.0 58.5

2015 LG HVAC Solution | 055


Hot water fired
Outline & Foundation absorption chiller

WCMW
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCMW003 2,020 1,394 1,952 3 2 1/2 2 1/2 1 1/2 3 1 1/2 2,000
WCMW004 2,020 1,396 1,965 3 2 1/2 2 1/2 1 1/2 3 1 1/2 2,000
WCMW005 2,520 1,396 1,965 3 2 1/2 2 1/2 2 1/2 3 2 1/2 2,400
WCMW007 2,547 1,355 2,150 5 3 3 2 1/2 5 2 1/2 2,400
WCMW008 2,547 1,355 2,150 5 3 3 2 1/2 5 2 1/2 2,400
WCMW010 3,567 1,355 2,150 5 4 4 3 5 3 3,400
WCMW012 3,567 1,355 2,150 5 4 4 3 5 3 3,400
WCMW014 3,627 1,526 2,330 6 4 4 3 6 3 3,400
WCMW016 3,627 1,526 2,330 6 4 4 3 6 3 3,400
WCMW019 4,630 1,526 2,330 8 5 5 4 8 4 4,500
WCMW021 4,630 1,526 2,330 8 5 5 4 8 4 4,500
WCMW024 4,784 1,575 2,630 8 6 6 4 8 4 4,500
WCMW027 4,784 1,575 2,630 8 6 6 4 8 4 4,500
WCMW031 4,789 1,702 2,886 10 6 6 5 10 5 4,500
WCMW034 4,789 1,702 2,886 10 6 6 5 10 5 4,500
WCMW038 4,931 1,702 3,260 12 8 8 6 12 6 4,600
WCMW043 5,473 2,015 3,260 12 8 8 6 12 6 5,200
WCMW048 5,971 2,015 3,260 12 8 8 6 12 6 5,700
WCMW054 5,616 2,195 3,680 14 8 8 8 14 8 5,200
WCMW060 6,114 2,195 3,680 14 8 8 8 14 8 5,700
WCMW067 6,639 2,195 3,680 14 8 8 8 14 8 6,200

056 | 2015 LG Absorption Chiller


Hot water fired
Outline & Foundation absorption chiller

WCMW003~WCMW021
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Weight(ton)
Model
A B C D E F G H W
WCMW003 1,471 900 1,120 195 110 95 1,020 97.5 1.10
WCMW004 1,471 900 1,120 195 110 95 1,020 97.5 1.15
WCMW005 1,971 900 1,120 195 110 95 1,020 97.5 1.35
WCMW007 1,926 820 1,120 245 150 145 1,020 125 2.05
WCMW008 1,926 820 1,120 245 150 145 1,020 125 2.15
WCMW010 2,946 820 1,120 245 150 145 1,020 125 2.65
WCMW012 2,946 820 1,120 245 150 145 1,020 125 2.85
WCMW014 2,816 980 1,280 370 150 270 1,180 185 3.45
WCMW016 2,816 980 1,280 370 150 270 1,180 185 3.60
WCMW019 3,836 980 1,280 370 150 270 1,180 185 4.20
WCMW021 3,836 980 1,280 370 150 270 1,180 185 4.45

2015 LG HVAC Solution | 057


Hot water fired
Outline & Foundation absorption chiller

WCMW
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCMW074 6,346 2,680 3,920 16 10 10 8 16 8 5,800
WCMW081 6,871 2,680 3,920 16 10 10 8 16 8 6,300
WCMW088 7,371 2,680 3,920 16 10 10 8 16 8 6,800
WCMW095 7,070 2,910 4,040 16 12 12 8 16 8 6,300
WCMW102 7,570 2,910 4,040 16 12 12 8 16 8 6,800

058 | 2015 LG Absorption Chiller


Hot water fired
Outline & Foundation absorption chiller

WCMW024~WCMW102
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Weight(ton)
Model
A B C D E F G H W
WCMW024 3,716 1,040 1,340 370 120 270 1,240 125 5.40
WCMW027 3,716 1,040 1,340 370 120 270 1,240 125 5.65
WCMW031 3,716 1,160 1,460 370 120 270 1,360 125 6.70
WCMW034 3,716 1,160 1,460 370 120 270 1,360 125 7.00
WCMW038 3,706 1,600 1,900 370 130 270 1,800 120 9.65
WCMW043 4,248 1,600 1,900 370 130 270 1,800 120 10.45
WCMW048 4,746 1,600 1,900 370 130 270 1,800 120 11.00
WCMW054 4,188 1,800 2,100 420 140 320 2,000 140 13.75
WCMW060 4,686 1,800 2,100 420 140 320 2,000 140 14.75
WCMW067 5,211 1,800 2,100 420 140 320 2,000 140 15.85
WCMW074 4,286 2,100 2,400 420 140 320 2,300 140 17.85
WCMW081 4,811 2,100 2,400 420 140 320 2,300 140 19.10
WCMW088 5,311 2,100 2,400 420 140 320 2,300 140 20.25
WCMW095 4,811 2,300 2,600 420 140 320 2,500 140 22.50
WCMW102 5,311 2,300 2,600 420 140 320 2,500 140 23.70

2015 LG HVAC Solution | 059


Outline & Foundation Steam fired absorption chiller

WCSS
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCSS010 2,650 1,800 2,150 5 4 4 5 1 2 2,400
WCSS012 2,650 1,800 2,150 5 4 4 5 1 2 2,400
WCSS015 3,670 1,800 2,150 5 4 4 5 1 2 3,400
WCSS018 3,670 1,800 2,150 5 4 4 5 1 2 3,400
WCSS021 3,730 2,030 2,450 6 5 5 6 1 2 1/2 3,400
WCSS024 3,730 2,030 2,450 6 5 5 6 1 2 1/2 3,400
WCSS028 4,750 2,030 2,450 8 6 6 8 1 2 1/2 4,500
WCSS032 4,750 2,030 2,450 8 6 6 8 1 2 1/2 4,500
WCSS036 4,850 2,110 2,650 8 6 6 8 1 1/2 3 4,500
WCSS040 4,850 2,110 2,650 8 6 6 8 1 1/2 3 4,500
WCSS045 4,850 2,350 2,900 10 8 8 10 1 1/2 3 4,500
WCSS050 4,850 2,350 2,900 10 8 8 10 1 1/2 3 4,500
WCSS056 5,060 2,500 3,255 12 8 8 12 2 4 4,600
WCSS063 5,600 2,500 3,255 12 8 8 12 2 4 5,200
WCSS070 6,100 2,500 3,255 12 8 8 12 2 4 5,700
WCSS080 5,710 2,850 3,580 14 10 10 14 2 1/2 5 5,200
WCSS090 6,210 2,850 3,580 14 10 10 14 2 1/2 5 5,700
WCSS100 6,730 2,850 3,580 14 10 10 14 2 1/2 5 6,200

060 | 2015 LG Absorption Chiller


Outline & Foundation Steam fired absorption chiller

WCSS010~WCSS032 WCSS010~WCSS032
WCSS036~WCSS150
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

WCSS036~WCSS150

Dimension(mm) Weight(ton)
Model
A B C D E F G H I J
WCSS010 210 210 420 1,160 960 1,360 220 1,846 2.3 2.3
WCSS012 210 210 420 1,160 960 1,360 220 1,846 2.4 2.4
WCSS015 210 210 420 1,160 960 1,360 220 2,866 3.0 3.0
WCSS018 210 210 420 1,160 960 1,360 220 2,866 3.1 3.1
WCSS021 235 235 470 1,460 1,260 1,660 270 2,816 3.7 3.7
WCSS024 235 235 470 1,460 1,260 1,660 270 2,816 3.9 3.9
WCSS028 235 235 470 1,460 1,260 1,660 270 3,836 4.5 4.5
WCSS032 235 235 470 1,460 1,260 1,660 270 3,836 4.8 4.8
WCSS036 470 270 1,760 1,560 1,360 3,716 120 175 5.8 5.8
WCSS040 470 270 1,760 1,560 1,360 3,716 120 175 6.0 6.0
WCSS045 470 270 1,860 1,660 1,460 3,716 120 175 7.1 7.1
WCSS050 470 270 1,860 1,660 1,460 3,716 120 175 7.4 7.4
WCSS056 470 270 2,060 1,860 1,660 3,706 130 170 9.8 9.8
WCSS063 470 270 2,060 1,860 1,660 4,248 130 170 10.7 10.7
WCSS070 470 270 2,060 1,860 1,660 4,746 130 170 11.5 11.5
WCSS080 520 320 2,300 2,100 1,900 4,188 140 190 14.7 14.7
WCSS090 520 320 2,300 2,100 1,900 4,686 140 190 15.8 15.8
WCSS100 520 320 2,300 2,100 1,900 5,211 140 190 17.0 17.0
WCSS110 520 320 2,500 2,300 2,100 4,286 140 190 18.9 18.9
WCSS120 520 320 2,500 2,300 2,100 4,811 140 190 20.2 20.2
WCSS130 520 320 2,500 2,300 2,100 5,311 140 190 21.4 21.4
WCSS140 520 320 2,700 2,500 2,300 4,811 140 190 23.6 23.6
WCSS150 520 320 2,700 2,500 2,300 5,311 140 190 25.0 25.0

2015 LG HVAC Solution | 061


Outline & Foundation Steam fired absorption chiller

WCSS
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCSS110 6,170 3,000 3,750 16 12 12 16 3 6 5,800
WCSS120 6,690 3,000 3,750 16 12 12 16 3 6 6,300
WCSS130 7,180 3,000 3,750 16 12 12 16 3 6 6,800
WCSS140 6,830 3,500 3,950 16 14 14 16 3 6 6,300
WCSS150 7,330 3,500 3,950 16 14 14 16 3 6 6,800

062 | 2015 LG Absorption Chiller


Outline & Foundation Steam fired absorption chiller

WCSH
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCSH010 2,730 1,810 2,065 5 4 4 5 1 2 2,400
WCSH012 2,730 1,810 2,065 5 4 4 5 1 2 2,400
WCSH015 3,720 1,810 2,070 5 4 4 5 1 2 3,400
WCSH018 3,720 1,810 2,110 5 4 4 5 1 2 3,400
WCSH021 3,720 2,000 2,415 6 5 5 6 1 2 3,400
WCSH024 3,720 2,000 2,415 6 5 5 6 1 2 3,400
WCSH028 4,740 2,070 2,415 8 6 6 8 1 2 1/2 4,500
WCSH032 4,740 2,070 2,415 8 6 6 8 1 2 1/2 4,500
WCSH036 4,800 2,200 2,590 8 6 6 8 1 1/2 2 4,500
WCSH040 4,800 2,200 2,590 8 6 6 8 1 1/2 2 4,500
WCSH045 4,815 2,385 2,950 10 8 8 10 1 1/2 2 4,500
WCSH050 4,815 2,385 2,950 10 8 8 10 1 1/2 2 4,500
WCSH056 5,030 2,620 3,300 12 8 8 12 2 4 4,500
WCSH063 5,520 2,620 3,300 12 8 8 12 2 4 5,200
WCSH070 6,010 2,620 3,300 12 8 8 12 2 4 5,700

2015 LG HVAC Solution | 063


Outline & Foundation Steam fired absorption chiller

WCSH
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

Dimension(mm) Nozzle connection (B) Clearance


Model (mm)
Length Width Height A B C D E F G
WCSH080 5,635 3,090 3,550 14 10 10 14 2 1/2 5 5,200
WCSH090 6,130 3,090 3,550 14 10 10 14 2 1/2 5 5,700
WCSH100 6,590 3,090 3,550 14 10 10 14 2 1/2 5 6,200
WCSH110 6,060 3,180 3,820 16 12 12 16 3 6 5,700
WCSH120 6,580 3,180 3,820 16 12 12 16 3 6 6,200
WCSH130 7,080 3,180 3,820 16 12 12 16 3 6 6,700
WCSH140 6,640 3,520 3,840 16 14 14 16 3 6 6,200
WCSH150 7,140 3,520 3,840 16 14 14 16 3 6 6,700

064 | 2015 LG Absorption Chiller


Outline & Foundation Steam fired absorption chiller

WCSH
1. The foundation and the floor must be sufficiently strong to
suport the unit weight.
2. Provide a flor drain near chiller foundation.
3. Only if foundation anchoring is is required, anchor bolts, nuts
and washers, shall be suplied together with chiller. Anchor bolts
must be fixed on the foundation prior to chiller installation.
4. Unit must be leveled before startup.
(Horizontal level must be below than 2mm/1,000mm)

Dimension(mm) Weight (ton)


Model
A B C D E F Total
WCSH010 2,466 1,326 570 1,500 2.3 2.2 4.5
WCSH012 2,466 1,326 570 1,500 2.5 2.5 5.0
WCSH015 3,486 2,346 570 1,500 3.0 3.0 6.0
WCSH018 3,486 2,346 570 1,500 3.3 3.2 6.5
WCSH021 3,486 2,346 570 1,800 3.8 3.8 7.6
WCSH024 3,486 2,346 570 1,800 4.1 4.0 8.1
WCSH028 4,506 3,366 570 1,800 4.9 4.9 9.8
WCSH032 4,506 3,366 570 1,800 5.2 5.1 10.3
WCSH036 4,506 3,166 670 1,900 6.0 5.9 11.9
WCSH040 4,506 3,166 670 1,900 6.6 6.5 13.1
WCSH045 4,506 3,166 670 2,000 7.7 7.6 15.3
WCSH050 4,506 3,166 670 2,000 8.4 8.4 16.8
WCSH056 4,506 3,166 670 2,300 10.1 10.1 20.2
WCSH063 5,048 3,708 670 2,300 11.9 11.9 23.8
WCSH070 5,546 4,206 670 2,300 13.4 13.4 26.8
WCSH080 5,048 3,608 720 2,660 15.4 15.4 30.9
WCSH090 5,546 4,106 720 2,660 16.5 16.4 32.9
WCSH100 6,071 4,631 720 2,660 17.9 17.9 35.8
WCSH110 5,546 4,106 720 2,780 19.4 19.4 38.8
WCSH120 6,071 4,631 720 2,780 21.1 21.1 42.2
WCSH130 6,571 5,131 720 2,780 22.9 22.9 45.8
WCSH140 6,071 4,631 720 3,020 24.7 24.7 49.4
WCSH150 6,571 5,131 720 3,020 26.4 26.4 52.8

2015 LG HVAC Solution | 065


Outline & Foundation Absorption heat pump - Steam

WCPX - Steam
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

A : Hot Water Inlet


B : Waste Heat Source Input
C : Waste Heat Source Ouput
D : Hot Water Outlet
F : Clearance

Hot Water Clearance


Dimension(mm) Nozzle connection (B) (mm)
Model Capacity
10^4 kcal/h Length Width Heght A B C D E F
WCPX003 30 2,180 1,400 2,090 40 65 65 40 40 2,000
WCPX007 70 2,680 1,460 2,210 65 100 100 65 50 2,400
WCPX010 100 2,680 1,460 2,210 65 100 100 65 65 2,400
WCPX015 150 3,700 1,460 2,350 65 100 100 65 65 3,400
WCPX020 200 3,760 1,630 2,600, 80 125 125 80 80 3,400
WCPX026 260 4,780 1,630 2,600 100 150 150 100 100 4,500
WCPX033 330 4,880 1,680 2,960 100 150 150 100 100 4,500
WCPX040 400 4,880 1,810 3,270 125 200 200 125 125 4,500
WCPX052 520 5,630 2,120 3,800 125 200 200 125 150 5,200
WCPX066 660 5,740 2,300 4,000 150 250 250 150 200 5,200
WCPX082 820 6,760 2,300 4,000 150 250 250 150 200 6,200

066 | 2015 LG Absorption Chiller


Outline & Foundation Absorption heat pump - Steam

WCPX - Steam
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

A : Hot Water Inlet


B : Waste Heat Source Input
C : Waste Heat Source Ouput
D : Hot Water Outlet
F : Clearance

Hot Water Clearance


Dimension(mm) Nozzle connection (B) (mm)
Model Capacity
10^4 kcal/h Length Width Heght A B C D E F
WCPX098 980 6,720 2,780 4,200 200 300 300 200 200 6,200
WCPX115 1,150 6,860 3,010 4,300 200 350 350 200 250 6,200
WCPX130 1,300 7,370 3,240 4,400 250 400 400 250 250 6,800
WCPX147 1,470 8,170 3,240 4,400 250 400 400 250 250 7,600
WCPX163 1,630 8,970 3,240 4,400 250 400 400 250 250 8,400

2015 LG HVAC Solution | 067


Outline & Foundation Absorption heat pump - Steam

WCPX - Steam
1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

A : Hot Water Inlet


B : Waste Heat Source Input
C : Waste Heat Source Ouput
D : Hot Water Outlet
F : Clearance

Hot Water Clearance


Dimension(mm) Nozzle connection (B) (mm)
Model Capacity
10^4 kcal/h Length Width Heght A B C D E F
WCPX196 1,960 6,720 5,460 4,300 300 400 400 300 200x2 6,200
WCPX230 2,300 6,860 5,920 4,400 350 450 450 350 250x2 6,200
WCPX260 2,600 7,370 6,380 4,400 350 500 500 350 250x2 6,800

068 | 2015 LG Absorption Chiller


Absorption heat pump
Outline & Foundation Direct Fired

WCPX - Direct Fired


1. All external water piing are to be provided with welded ANSI 150PSIG
RF flanges by the customer.
2. Installation and service clearance as folows :
Logitudinal distance - 1,000mm
Top - 200mm
Control panel side - 1,200mm
3. Please refer to the LG Electronics drawings for the piping direction

A : Hot Water Inlet


B : Waste Heat Source Input
C : Waste Heat Source Ouput
D : Hot Water Outlet
F : Clearance

Hot Water
Dimension(mm) Nozzle connection (B) Clearance (mm)
Model Capacity
10^4 kcal/h Length Width Heght A B C D F
WCPX003 30 2,620 2,140 2,030 40 65 65 40 2,000
WCPX007 70 3,120 2,190 2,060 65 100 100 65 2,400
WCPX010 100 3,120 2,190 2,060 65 100 100 65 2,400
WCPX015 150 3,990 2,190 2,120 65 100 100 65 3,400
WCPX020 200 4,020 2,540 2,390 80 125 125 80 3,400
WCPX026 260 4,820 2,560 2,610 100 150 150 100 4,500
WCPX033 330 4,940 2,830 3,030 100 150 150 100 4,500
WCPX040 400 5,080 3,010 3,030 125 200 200 125 4,500
WCPX052 520 6,080 3,500 3,650 125 200 200 125 5,200
WCPX066 660 6,710 4,020 3,650 150 250 250 150 5,200
WCPX082 820 7,810 4,070 3,680 150 250 250 150 6,200

2015 LG HVAC Solution | 069


Outline & Foundation Absorption heat pump - Steam

WCPX003~WCPX163

Hot Water
Dimension(mm)
Model Capacity
10^4 kcal/h A B C D E F G H W(ton)
WCPX003 30 1,470 820 1,140 295 160 95 940 147.5 1.5
WCPX007 70 1,926 820 1,220 345 200 145 1,020 172.5 2.3
WCPX010 100 1,926 820 1,220 345 200 145 1,020 172.5 2.5
WCPX015 150 2,946 820 1,220 345 200 145 1,020 172.5 3.2
WCPX020 200 2,816 980 1,380 470 200 270 1,180 235 4.2
WCPX026 260 3,836 980 1,380 470 200 270 1,180 235 5.2
WCPX033 330 3,836 1,040 1,440 470 200 270 1,240 235 6.5
WCPX040 400 3,836 1,160 1,560 470 200 270 1,360 235 8.0
WCPX052 520 4,378 1,600 2,000 470 200 270 1,800 235 11.9
WCPX066 660 4,328 1,800 2,200 520 200 320 2,000 260 15.3
WCPX082 820 5,351 1,800 2,200 520 200 320 2,000 260 17.5
WCPX098 980 4,951 2,100 2,500 520 200 320 2,300 260 20.7
WCPX115 1,150 4,951 2,300 2,700 520 200 320 2,500 260 24.1
WCPX130 1,300 5,461 2,500 2,900 520 200 320 2,700 260 27.9
WCPX147 1,470 6,261 2,500 2,900 520 200 320 2,700 260 29.7
WCPX163 1,630 7,061 2,500 2,900 520 200 320 2,700 260 31.5

070 | 2015 LG Absorption Chiller


Outline & Foundation Absorption heat pump - Steam

WCPX003 ~ WCPX163

Hot Water
Dimension(mm)
Model Capacity
10^4 kcal/h A B C D E F G H J W(ton)
WCPX196 1,960 4,951 2,100 5,000 520 200 320 2,300 260 200 20.7
WCPX230 2,300 4,951 2,300 5,400 520 200 320 2,500 260 200 24.1
WCPX260 2,600 5,461 2,500 5,800 520 200 320 2,700 260 200 27.9

2015 LG HVAC Solution | 071


Absorption heat pump
Outline & Foundation Direct Fired

WCPX003~WCPX082

Hot
Water Dimension(mm)
Model Capacity
10^4 S W
kcal/h A B C D E F G H I J K L M N O P Q R T
(Ton) (Ton)
WCPX003 30 1,470 820 1,140 295 160 95 940 147.5 258 220 970 698 100 100 200 540 160 220 340 0.8 1.45
WCPX007 70 1,926 820 1,220 345 200 145 1,020 172.5 577 300 1,330 425 130 160 330 750 225 300 440 0.9 1.90
WCPX010 100 1,926 820 1,220 345 200 145 1,020 172.5 547 350 1,350 440 170 185 370 750 200 350 550 0.9 2.10
WCPX015 150 2,946 820 1,220 345 200 145 1,020 172.5 559 350 1,850 672 170 185 370 750 200 350 550 1.3 2.65
WCPX020 200 2,816 980 1,380 470 200 270 1,180 235 549 460 1,954 716 220 210 420 820 185 460 620 1.6 3.45
WCPX026 260 3,836 980 1380 470 200 270 1,180 235 557 550 2,250 830 220 210 420 920 185 550 720 2.1 4.30
WCPX033 330 3,836 1,040 1,440 470 200 270 1,240 235 480 960 2,250 1,165 200 200 400 1,320 180 960 1,120 2.8 5.35
WCPX040 400 3,836 1,160 1,560 470 200 270 1,360 235 460 1,160 2,400 1,328 300 250 500 1,520 180 1,160 1,320 3.4 6.55
WCPX052 520 4,378 1,600 2,000 470 200 270 1,800 235 460 1,160 3,000 1,328 300 250 500 1,520 180 1,160 1,320 5.0 9.90
WCPX066 660 4,328 1,800 2,200 520 200 320 2,000 260 750 1,260 3,400 0 300 250 500 1,620 180 1,260 1,420 7.0 12.65
WCPX082 820 5,351 1,800 2,200 520 200 320 2,000 260 800 1,340 3,700 0 300 250 500 1,700 180 1,340 1,500 10.5 17.45

072 | 2015 LG Absorption Chiller


Schematic diagram Direct fired absorption chiller

Heating mode (60C)

2015 LG HVAC Solution | 073


Schematic diagram Direct fired absorption chiller

Heating mode (80C)

074 | 2015 LG Absorption Chiller


Schematic diagram Steam fired absorption chiller

2015 LG HVAC Solution | 075


Schematic diagram Hot water fired absorption chiller

WCMW003 ~ WCMW034

076 | 2015 LG Absorption Chiller


Schematic diagram Hot water fired absorption chiller

WCMW038~WCMW102

2015 LG HVAC Solution | 077


Interface diagram Direct fired absorption chiller & heater

078 | 2015 LG Absorption Chiller


Steam/Hot water
Interface diagram fired absorption chiller

2015 LG HVAC Solution | 079


Ver. 201504

LG Electronics, Home appliance & Air solution company


Two IFC, 10 Gukjegeumyung-ro, Yeongdeungpo-gu, Seoul, 150-945, Korea.

www.lg.com
www.lgeaircon.com

For continual product development, LG reserves the right to


change specifications or designs without notice.
Distributed by
2015 LG Electronics. Printed in Korea. April. 2015

You might also like