Rel316 4 PDF
Rel316 4 PDF
Rel316 4 PDF
1MRK506013-Ben
Page 1
Issued: February 2002
Changed: since December 1999
Data subject to change without notice
Application The fully numerical protection terminal both systems increases significantly. The rea-
REL316*4 is a compact line terminal. It is son for this is the limited phase selection
designed to provide high-speed selective pro- within the reach.
tection in distribution, MV and HV transmis-
sion systems. It can be applied at all power Distance and longitudinal differential protec-
system voltages and in solidly earthed, low- tion combined in one terminal allows a better
impedance grounded or ungrounded systems protection concept. For example, distance
or in systems equipped with arc suppression protection as a backup in addition to the tradi-
(Petersen) coils. tional overcurrent backup in case of a com-
munication failure.
REL316*4 can be used on overhead lines and
cables, long feeders, short feeders, parallel Another application may be longitudinal dif-
circuit lines, heavily loaded lines, lines with ferential protection for transformer protection
weak infeeds and on short zone lines. It with distance protection as a backup.
detects all kinds of faults including close
three-phase faults, cross-country faults, REL316*4 also takes account of power
evolving faults and high-resistance ground swings and changes of energy direction. A
faults. switch-onto-fault condition is tripped instan-
taneously. The demands on c.t and v.t. perfor-
The distance function for high-voltage lines mance are moderate and the relays response
(<ZHV) essentially has identical starting and is uninfluenced by their characteristics.
measuring characteristics.
The distance protection function and the di-
The differences refer to their speciality for rectional comparison function for high-resis-
these lines. With regard to their settings this tance earth faults can communicate with the
is especially noticeable during phase selec- opposite end of the line by all the usual com-
tion and the adaption to source-to-line imped- munication media as well as by the integrated
ance conditions. The relay detects evolving direct optical connection used for the longitu-
faults and follow-up faults. Also at follow-up dinal differential protection. The communica-
faults between parallel lines, the probability tion between the terminals of the phase-seg-
of successful single-phase autoreclosure on ragated longitudinal differential protection
can be performed using the integrated or sep-
arate optical fibre link.
Example
Auto-reclosure for 1 breaker scheme
A B C
Fig. 1 Auto-reclosing for 1 breaker scheme (line - line diameter), three pole application
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 5
The promoted solution for 1 breaker scheme with three pole tripping and auto-reclosing is
shown in Figure 1.
- 21 Distance Protection: REL316*4 SN100
- 87 Line differential Protection: REL316*4 SP100
- 79/25 Autorecloser/Synchrocheck: REL316*4 SD050 or REC316*4.
A B C
Fig. 2 Auto-reclosing for 1 breaker scheme (line - line diameter), single pole application
The promoted solution for 1 breaker scheme with single pole tripping and auto-reclosing is
shown in Figure 2.
- 21 Distance Protection: REL316*4 SN100, T141
- 87 Line differential Protection: REL316*4 SP100, T129
- 79/25 Autorecloser/Synchrocheck: REL316*4 SD050, T142
or REC316*4, T142.
In these figures two lines are connected to The auto-reclosure functions used for the bus
one diameter. Each line is protected by two breakers A and C are set as Masters and the
REL316*4 relays. For the line on the left, the one for the centre breaker B as Follower. Co-
main relay is a distance protection relay ordination is required between the auto-rec-
(SN100), while the back-up relay is a line dif- losure functions. A synchrocheck function is
ferential relay (SP100). The line on the right also loaded in each relay to permit 3 pole
is protected with two distance protection re- auto-reclosing.
lays (SN100). The auto-reclosure functional-
ity is achieved by one RE.316*4 relay per Each line protection relay starts both bus and
breaker (e.g. REL316*4 SD050). centre breakers for the concerned line. After a
successful reclosure of the bus breaker, the
For a single-pole application, the distance centre breaker will be reclosed after a supple-
protection relay (SN100) is loaded with the mentary time delay. Should the bus CB auto-
supplementary FUPLA logic T141, the line recloser relay not be successful in its reclos-
differential relay (SP100) with the logic T129 ing attempt, the centre CB auto-recloser is
and the autorecloser (e.g. SD050) with the blocked. If the bus CB is open or its auto-
logic T142. recloser relay is not ready or out of service,
the centre CB auto-recloser will reclose the
centre breaker after its own dead time without
any supplementary time delay.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 6
Design The REL316*4 belongs to the generation of vice without failure and its total life, is most
fully numerical line protection terminals, i.e. certainly the most important characteristic re-
analogue to digital conversion of the input quired of protection equipment. As a conse-
variables takes place immediately after the quence of the continuous supervision of its
input transformers and all further processing functions, this quotient in the case of
of the resulting numerical signals is perfor- REL316*4 is typically always close to 1.
med by microprocessors and controlled by
programs. The menu-based HMI (human machine inter-
face) and the REL316*4 small size makes the
Standard interfaces enable REL316*4 to tasks of connection, configuration and setting
communicate with other control systems. simple. A maximum of FLEXIBILITY, i.e.
Provision is thus made for the exchange of the ability to adapt the protection for applica-
data such as reactionless reporting of binary tion in a particular power system or to coordi-
states, events, measurements and protection nate with, or replace units in an existing pro-
parameters or the activation of a different set tection scheme, is provided in REL316*4 by
of settings by higher level control systems. ancillary software functions and the assign-
ment of input and output signals via the HMI.
Because of its compact design, the very few
hardware units it needs, its modular software REL316*4s RELIABILITY, SELECTIV-
and the integrated continuous self-diagnosis ITY and STABILITY are backed by decades
and supervision functions, REL316*4 ideally of experience in the protection of lines and
fulfils the users expectations of a modern feeders in transmission and distribution sys-
protection terminal at a cost-effective price. tems. Numerical processing ensures consis-
The AVAILABILITY of a terminal, i.e. the tent ACCURACY and SENSITIVITY
ratio between its mean operating time in ser- throughout its operational life.
Hardware The hardware concept for the REL316*4 line input transformer unit can accommodate a
protection equipment comprises four differ- maximum of nine input transformers (volt-
ent plug-in units, a connecting mother PCB age-, protection current- or measuring trans-
and housing (Fig. 3): former).
analog input unit
Every analog variable is passed through a
central processing unit first order R/C low-pass filter on the main
1 to 4 binary input/output units CPU unit to eliminate what is referred to as
the aliasing effect and to suppress HF inter-
power supply unit ferences (Fig. 4). They are then sampled 12
connecting mother PCB times per period and converted to digital sig-
nals. The analog/digital conversion is per-
housing with connection terminals. formed by a 16 Bit converter.
In the analog input unit an input transformer A powerful digital signal processor (DSP)
provides the electrical and static isolation carries out part of the digital filtering and
between the analogue input variables and the makes sure that the data for the protection
internal electronic circuits and adjusts the sig- algorithms are available in the memory to the
nals to a suitable level for processing. The main processor.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 7
RX Tx DC
+5V
+15V
CPU -15V
Power
Supply
Remote I/O
A/D DSP 486 +24V
DC
Remote I/OTrip
DPM Outputs
Remote I/OTrip
A/D DSP Sign.
Outputs
TripOutputs
SW-Key Sign.
Outputs
Trip Bin.
Outputs
Outputs
Trip FLASH PCC Sign.Inputs
Trip EPROM Bin.
Outputs
Outputs Inputs
Trip Sign.
Outputs I/O IEC1375
I/O (MVB) Bin.
OutputsI / OPorts
Sign.
Outputs a
Sign.
Outputs Ports
I /Ports
O P Process bus Inputs
Sign.
Outputs Tranceiver
Bin.
Ports C
OutputsBin.
Inputs b
Bin.
Inputs M
Bin.
Inputs PCC
Inputs C
c
RAM I LON
A IEC1375
d
SCS
LED's
SMS
RS Serial RS Serial
232 Controller 232 Controller SPA / IEC870-5-103
HMI
The processor core essentially comprises the REL316*4 can have one to four binary I/O
main microprocessor (Intel 80486) for the units each. These units are available in three
protection algorithms and dual-ported memo- versions:
ries (DPMs) for communication between the
A/D converters and the main processor. The a) two tripping relays with two heavy-duty
main processor performs the protection algo- contacts, 8 opto-coupler inputs and 6
rithms and controls the local HMI and the in- signalling relays Type 316DB61.
terfaces to the station control system. Binary
signals from the main processor are relayed to b) two tripping relays with two heavy-duty
the corresponding inputs of the I/O unit and contacts, 4 opto-coupler inputs and 10 sig-
thus control the auxiliary output relays and nalling relays Type 316DB62.
the light emitting diode (LED) signals. The
c) 14 opto-coupler inputs and 8 signalling
main processor unit is equipped with an
RS232C serial interface via which among relays Type 316DB63.
other things the protection settings are made,
events are read and the data from the distur- When ordering REL316*4 with more than
bance recorder memory are transferred to a 2 I/O units casing size N2 must be selected.
local or remote PC.
According to whether one or two I/O units
On this main processor unit there are two are fitted, there are either 8 LED's or 16
PCC slots and one RS232C interface. These LEDs visible on the front of the REL316*4.
serial interfaces provide remote communica-
tion to the station monitoring system (SMS)
and station control system (SCS) as well as to
the remote I/Os.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 8
Software Both analogue and binary input signals are form, they are then separated by numerical
conditioned before being processed by the filters into real and apparent components
main processor: As described under hardware before being applied to the main processor.
above, the analogue signals pass through the Binary signals from the opto-coupler inputs
sequence input transformers, shunt, low-pass go straight to the main processor. The actual
filter (anti-aliasing filter), multiplexer and A/ processing of the signals in relation to the
D converter stages and DSP. In their digital protection algorithms and logic then takes place.
Example:
3
B_DRIVE
CL CL Q0_CL
OP OP Q0_OP
POK Q0_Q0_POK
4
& Q0_Q0_CLOSED
5 Q0_Q0_OPEN
&
SEL
DPMIN_Q0_CLOSED
RQON GON Q0_GUIDE_ON
DPMIN_Q0_OPEN
RQOF GOF Q0_GUIDE_OFF
GEX Q0_GUIDE_EXE
2
>=1 EXE Q0_EXE
1
&
SYNC GOON Q0_GOON_Q0
RQEX GOOF Q0_GOOFF_Q0
Q0_SEL_DRIVE_Q0
SYST Q0_Q0_SYST
GEN_REQUEST_ON
SREL DPMOUT_Q0_SEL_REL
GEN_REQUES_ON 30 T:SY 6
1 T:RT =1 Q0_SUP_SEL_REL_Q0
GEN_SYNC
Q1_Q1_OPEN
ALSY Q0_ALSY
Q2_Q2_OPEN
BKS Q0_BLOCK_SELECT
GEN_REQUEST_EXE
KDOF Q0_KDO_FAIL
Part of FUPLA application (Q0) : control and interlocking logic for three objects Q0,
Q1, Q2. B_DRIVE is a macro based on binary function blocks.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 10
Functions The library of function modules for A v.t. supervision function is also included
REL316*4 includes a variety of protection which monitors the zero-sequence component
and ancillary functions from which the user (U0 I0) and/or the negative-sequence compo-
can choose according to relay version (see nent (U2 I2), the latter being of advantage in
Ordering data). Within the constraints of ungrounded systems or systems with poor
the available processing capacity, the same grounding.
function may be included several times. Four
parameter sets may be selected via binary in- An independent overcurrent backup measure-
puts. The individual functions are described ment is provided which becomes a short-zone
below. scheme as soon as the feeder isolator is open-
ed. When the backup overcurrent measure-
Distance protection ment picks up, the distance relay is enabled in
The distance protection function can have spite of any blocking signals (e.g. v.t. super-
either overcurrent or underimpedance start- vision or power swing blocking) which may
ers. They are equally suitable for use in sol- be active. The power swing blocking feature
idly grounded, ungrounded or impedance included in the distance function is based on
grounded systems. In the case of ungrounded the evaluation of the variation of U cosj.
and impedance grounded systems, all the This principle of detecting power swings is
relays in the system have to have identically entirely independent of the operating charac-
set phase-preference logics to maintain selec- teristic and location of the distance relay. It
tivity for cross-country faults. The following covers the range 0.2 to 8 Hz.
phase-preference schemes are available:
Functions (contd) permissive overreaching transfer tripping The setting parameters for not effectively
(with echo tripping in the case of a weak earthed networks have been omitted and a
infeed and blocking logic for change of few new ones added, especially in connection
energy direction) with an improved phase selection.
blocking scheme (with blocking logic for
The operating times for the "HV distance"
change of energy direction).
function are shown in the form of isochrones.
The tripping logic provides access for the (see Section 'High-voltage distance protec-
user to disable or enable a variety of func- tion function operating times'). All other
tions such as the type communications chan- functions remain unchanged.
nel, the switch-onto-fault logic, the over-
Longitudinal differential protection
reaching zone, the v.t. supervision logic and The longitudinal differential protection func-
whether tripping by the function should be tion included with REL316*4 is suitable for
single or three-phase. the protection of
Distance protection for high-voltage lines overhead lines
The distance protection function (<ZHV) is
especially suited for 220 kV and 380 kV cables
lines. transformer feeders.
It operates according to the proven trans-
The "HV distance" function essentially has
former protection algorithm used in
identical starting and measuring characteris-
RET316*4 and exhibits the same outstanding
tics and the same setting parameters as the
characteristics with respect to through-fault
standard "distance" function.
stability and minimum c.t. performance.
I2
Functions (contd)
Fig. 7 Longitudinal differential protection with a power transformer in the protected zone
Tripping takes place should the comparison tion where they are evaluated in relation to
of the values in the terminal stations result in the local current signals. Similarly the cur-
a differential current ID above a given level rents measured and digitized in the remote
(see operating characteristic in Fig. 6). The station are transferred to the local station and
self-supervision function of the optical fibre evaluated. A digital signal processor (DSP)
link operates at such a speed that an additional ensures that the sampling and coordination of
enabling signal is not necessary. the signals in the two stations and also the
transmission between the stations is properly
Interposing c.ts are not needed where the synchronized. Thus there are two current sig-
protected unit includes a power transformer nals available for the longitudinal differential
(Fig. 7). The settings for the protection are comparison of each phase in both stations.
made using a convenient control program Comparison is performed in the main proces-
running on a personal computer. sor according to the proven algorithm men-
tioned above.
Provision is made for transmitting other sig-
nals via the optical fibre link in addition to As previously explained, the longitudinal dif-
those of the longitudinal differential function. ferential function operates in conjunction
These might be intertripping signals to the with an optical fibre link between the stations
remote station generated by other internal at the ends of the transmission line. The sig-
protection functions or applied to the termi- nals are transmitted by a LED diode with a
nals binary inputs by some other external ter- wavelength of 1300 nm and are coupled by a
minal. A ground fault comparison scheme Type FC optical connector. Depending on the
can thus operate via the same optical fibre attenuation of the of the optical cable used,
link. When the terminal equipment in one sta- distances of up to 28 km can be covered.
tion is being tested, the equipment in the Repeaters have to be used for longer dis-
other station can be remotely blocked. tances which in the case of FOX 6 Plus or
Fox 20 enable transmission over distances up
When the longitudinal protection function is to 120 km (Fig. 8).
in use, a maximum of six analogue inputs is
available, e.g. three current and three voltage In REL316*4 units for longitudinal differen-
measurements for main and backup protec- tial applications, the standard distance protec-
tions and for the disturbance recorder. Fol- tion function can also be activated. The ope-
lowing analogue to digital conversion, the ration for single-pole autoreclosure is fore-
signals branch in two directions. All six go to seen with the T129 logic. The other standard
the main processor for evaluation for the local software of the line protection terminal is un-
protection functions and the three correspon- influenced. Other optional functions from the
ding to the local phase currents are addition- software library are also provided (see table
ally converted to light signals by an optical of codes).
modem for transmission to the opposite sta-
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 13
Fig. 8 Optical fibre link (OFL) using communications system Type FOX with a data transfer rate of
2 MBit/s
Auto-reclosure Synchrocheck
The autoreclosure function included in The synchrocheck function determines the
REL316*4 permits up to four three-phase difference between the amplitudes, phase-
reclosure cycles to be carried out, each with angles and frequencies of two voltage vec-
an independently adjustable dead time for fast tors. Checks are also included to detect a dead
and slow autoreclosure. Where single-phase line or busbar.
reclosure is being applied, the first reclosure
is the single-phase one and the others are Thermal overload
three-phase. The thermal overload function can be used
for either cables or overhead lines. It is equip-
The autoreclosure function can also be loaded ped with alarm and tripping stages and has a
several times in the same parameter set. This wide setting range for adjusting the time con-
function also contains an integrated additio- stant to match that of the protected unit.
nal logic (FUPLA). This allows a customer-
specific AR functionality. Both these possi- Definite time voltage function
bilities have been used for the CH standard The voltage function can be set to operate on
AR. Two AR functions are loaded for this: overvoltage or undervoltage with a definite
the first function with additional logic serves time delay. Either single or three-phase mea-
as fast autoreclosure and the second function surements can be performed.
as slow autoreclosure.
Definite time current function
The integrated autoreclosure function for The current function can be set to operate on
high-voltage lines (REL316*4/SN300) is overcurrent or undercurrent with a definite
employed on lines without local protection time delay. Either single or three-phase mea-
redundancy. surements can be performed.
mined by its pre-disturbance history and the Any desired protection function can be selec-
duration of the disturbance itself. The total ted from the software library of all released
recording time is approximately 5 s. protection functions by means of the drag-
and-drop feature.
Human Machine Interface (HMI) - CAP2/316
For local communication with REL316*4,
there is the setting software CAP2/316 availa-
ble which is based on Windows. This soft-
ware runs under the following operating sys-
tems:
Windows NT 4.0
Windows 2000.
Remote communication
REL316*4 is able to communicate with a sta-
tion monitoring and evaluation system (SMS)
or a station control system (SCS) via an opti-
cal fibre link. The corresponding serial inter-
face permits events, measurements, distur-
bance recorder data and protection settings to
be read and sets of parameter settings to be
switched.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 16
Functions (contd) Using the LON bus permits in addition the The program execution itself is monitored by
exchange of binary information between the a watchdog function for each processor.
individual bay controllers, e.g. signals for sta-
tion interlocking. An important advantage of the extensive self-
diagnosis and supervision functions is that
Remote in- and outputs (RIO580) periodic routine maintenance and testing are
Using the process bus type MVB remote in- reduced.
and output units (500RIO11) can be connec-
ted to the RE.316*4 terminals. The input and The optical fibre link is also supervised on
output channels can be extended to a large terminal equipped with the longitudinal dif-
number by using RIO580 remote input/output ferential function. For this purpose test data
system. Installing 500RIO11 I/O close to the are transmitted in addition to the protection
process reduces the wiring dramatically, signals to test the integrity of the communica-
since they are accessible via fibre optic link tions channel. The supervision function also
from the RE.316*4 terminals. detects the failure of the auxiliary supply in
one terminal station. In the event that the
Analog signals can also be connected to the optical fibre link should fail, the back-up pro-
system via the 500AXM11 from the RIO580 tection functions remain operational.
family:
Supporting software
DC current 4...20 mA
The operator program facilitates configura-
0...20 mA tion and setting of the protection, listing para-
-20...20 mA meters, reading events and listing the various
DC voltage 0...10 V internal diagnostic data.
-10...10 V
The evaluation programs REVAL and WIN-
Temp. sensor Pt100, Pt250, Pt1000,
EVE (MS Windows/Windows NT) are avail-
Ni100, Ni250, Ni1000.
able for viewing and evaluating the disturban-
Self-diagnosis and supervision ces stored by the disturbance recorder. Where
RE.316*4s self-diagnosis and supervision the disturbance data are transferred via the
functions ensure maximum availability not communications system to the disturbance
only of the protection terminal itself, but also recorder evaluation station, the file transfer
of the power system it is protecting. Hard- program EVECOM (MS Windows/Windows
ware failures are immediately signalled by an NT) is also used.
alarm contact. In particular, the external and
internal auxiliary supplies are continuously The program XSCON is available for conver-
supervised. The correct function and toler- sion of the RE.316*4 disturbance recorder
ance of the A/D converter are tested by cycli- data to ABBs test set XS92b format. This
cally converting two reference voltages. Spe- offers reproduction of electrical quantities
cial algorithms regularly check the proces- recorded during a fault.
sors memories (background functions). A
watchdog supervises the execution of the pro-
grams.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 17
Technical data Table 10: Distance and high-voltage distance protection (21)
Functions All values of settings referred to the secondaries, every zone can be set independently of the others,
4 independent files for sets of settings.
Impedance measurement -300 to 300 W/ph in steps of 0.01 W/ph (IN = 1 A or 2 A)
-30 to 30 W/ph in steps of 0.001 W/ph (IN = 5 A)
Zero-sequence current compensation 0 to 8 in steps of 0.01,
-180 to +90 in steps of 1
Mutual impedance for parallel circuit lines 0 to 8 in steps of 0.01,
-90 to +90 in steps of 1
Time step setting range 0 to 10 s in steps of 0.01 s
Underimpedance starters -999 to 999 W/ph in steps of 0.1 W/ph (IN = 1 A or 2 A)
-99.9 to 99.9 W/ph in steps of 0.01 W/ph (IN = 5 A)
Overcurrent starters (not included in the high- 0.5 to 10 IN in steps of 0.01 IN
voltage distance protection function <ZHV)
Min. operating current 0.1 to 2 IN in steps of 0.01 IN
Back-up overcurrent 0 to 10 IN in steps of 0.01 IN
Neutral current criterion 0.1 to 2 IN in steps of 0.01 IN
Neutral voltage criterion 0 to 2 UN in steps of 0.01 UN
Low voltage criterion for detecting, for exam- 0 to 2 UN in steps of 0.01 UN
ple, a weak infeed
V.t. supervision
NPS/neutral voltage criterion 0.01 to 0.5 UN in steps of 0.01UN
NPS/neutral current criterion 0.01 to 0.5 IN in steps of 0.01 IN
Accuracy (applicable for current time con-
stants between 40 and 150 ms)
amplitude error 5% for U/UN >0.1
phase error 2 for U/UN >0.1
Supplementary error for
- frequency fluctuations of +10% 5%
- 10% third harmonic 10%
- 10% fifth harmonic 10%
Operating times of the high-voltage distance
protection function <ZHV (including tripping
relay)
minimum 21 ms
typical 25 ms
(see also isochrones)
all permitted additional functions activated 4 ms in addition
The operating times of the (standard-)
distance functions are higher by 5 to 10 ms
Typical reset time 30 ms
VT-MCB auxiliary contact requirements
Operating time <15 ms
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 22
Isochrones
ZF/ZL
ZF/ZL
22ms 0.2
0.2
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
0.8 0.8
0.6 0.6
ZF/ZL
ZF/ZL
0.2 0.2
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
SIR (ZS/ZL) SIR (ZS/ZL)
22ms
ZF/ZL
0.6 0.6
ZF/ZL
0.4 0.4
25ms
0.2 0.2
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
SIR (ZS/ZL) SIR (ZS/ZL)
Technical data Func- Table 11: Longitudinal differential protection function (87)
tions (contd) Three-phase measurement with current comparison per phase
Adaptive current characteristic
Provision for two-winding power transformer in protection zone
- compensation of group of connection
- compensation of differing c.t. ratios
- 2nd. harmonic inrush restraint
Settings:
Basic setting g = 0.1 to 0.5 IN in steps of 0.1 IN
Pick-up ratio v = 0.25 / 0.5
Restraint criterion b = 1.25 to 5 in steps of 0.25
Typical operating time (incl. tripping relay) 25 ms
Pick-up accuracy of g 5% IN (at fN)
Condition for resetting ID <0.8 setting for g
Communications link to the remote station Two optical fibre connectors for transmit (Tx) and
receive (Rx)
Data transfer rate 64 kBit/s
Optical fibre conductors multi-mode MM (50/25 mm)
single-mode SM (9/125 mm)
Max. attenuation of link MM 18 dB, SM 14 dB
Optical connectors Type FC
Operating wavelength 1300 nm
Max. permissible transmission time per direc- 11.5 ms at fN = 50 Hz
tion 9.5 ms at fN = 60 Hz
Range
MM <18 km (1 dB/km incl. splice)
SM <28 km (0.5 dB/km incl. splice)
Long distance range using FOX20 <87 km (0.5 dB/km incl. splice for SM, 1300 nm)
<124 km (0.35 dB/km incl. splice for SM, 1550 nm)
Technical data Func- Table 19: Inverse time ground fault overcurrent function (51N)
tions (contd) Neutral current measurement (derived externally or internally)
Stable response to transients
Inverse time characteristic t = k1 / ((I/IB)C - 1)
(acc. to B.S. 142 with extended setting range)
normal inverse c = 0.02
very inverse c=1
extremely inverse c=2
long time inverse c=1
or RXIDG characteristic t = 5.8 - 1.35 In (I/IB)
Settings:
Number of phases 1 or 3
Base current IB 0.04 to 2.5 IN in steps of 0.01 IN
Pick-up current Istart 1 to 4 IB in steps of 0.01 IB
Min. time setting tmin 0 to 10 s in steps of 0.1 s
k1 setting 0.01 to 200 s in steps of 0.01 s
Accuracy classes for the operating time
according to British Standard 142 E 5.0
RXIDG characteristic 4% (1 - I/80 IB)
Reset ratio >94%
Table 22: Directional ground fault function for ungrounded systems and systems with
Petersen coils (32N)
Determination of real or apparent power from neutral current and voltage
Settings:
Pick-up power 0.005 to 0.1 SN in steps of 0.001 SN
Reference value of the power SN 0.5 to 2.5 UN IN in steps of 0.001 UN IN
Characteristic angle -180 to +180 in steps of 0.01
Phase error compensation of current input -5 to +5 in steps of 0.01
Delay 0.05 to 60 s in steps of 0.01 s
Reset ratio 30 to 95% in steps of 1%
Accuracy of the pick-up setting 10% of setting or 2% UN IN
(for protection c.t.s)
3% of setting or 0.5% UN IN
(for core-balance c.t.s)
Max. operating time without intentional delay 70 ms
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 28
Technical data Func- Table 23: Directional ground fault function for grounded systems (67N)
tions (contd) Detection of high-resistance ground faults
Current enabling setting 3I0
Direction determined on basis of neutral variables (derived externally or internally)
Permissive or blocking directional comparison scheme
Echo logic for weak infeeds
Logic for change of energy direction
Settings:
Current pick-up setting 0.1 to 1.0 IN in steps of 0.01 IN
Voltage pick-up setting 0.003 to 1 UN in steps of 0.001 UN
Characteristic angle -90 to +90 in steps of 5
Delay 0 to 1 s in steps of 0.001 s
Accuracy of the current pick-up setting 10% of setting
Ancillary functions
Table 33: Accuracy of the metering function UIfPQ and three-phase measuring module
(including input voltage and input current c.t.)
Input variable Accuracy Conditions
Core balance c.t.s Protection c.t.s
with error compensation without error com-
pensation
Voltage 0.5% UN 1% UN 0.2 to 1.2 UN
f = fN
Current 0.5% IN 2% IN 0.2 to 1.2 IN
f = fN
Real power 0.5% SN 3% SN 0.2 to 1.2 SN
0.2 to 1.2 UN
0.2 to 1.2 IN
f = fN
Apparent power 0.5% SN 3% SN
Power factor 0.01 0.03 S = SN, f = fN
Frequency 0.1% fN 0.1% fN 0.9 to 1,1 fN
0.8 to 1,2 UN
SN = 3 UN IN (three-phase)
SN = 1/3 3 UN IN (single-phase)
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 32
Connection
diagram
CURRENT
AND VOLTAGE
INPUTS
(VALID FOR CODE K03)
SIGNALLING
COMMUNICATION
PORT
(LOCAL HMI) (PC))
SERIAL COMMUNI-
CATION WITH SUB-
STATION CONTROL
EARTHING SCREW
ON CASING
TRIP
OPTOCOUPLER
INPUTS
DC SUPPLY
Fig. 9 Typical wiring diagram of REL316*4 in size N1 casing with two input/output units 316DB62
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 33
Basic-SW
E/Fungnd
Long. diff
E/Fgnd
<ZHV
BST
AR
SC
<Z
A*B0U*K01E*I*F0J0 Q0V0R0W0Y*N*M* SA010 T*** X
A*B0U*K01E*I*F0J0 Q0V0R0W0Y*N*M* SA100 T*** X X
A*B0U*K03E*I*F*J* Q*V*R*W*Y* N*M* SE010 T*** X
A*B0U*K03E*I*F*J* Q*V*R*W*Y* N*M* SE100 T*** X X
A*B*U*K04E*I*F*J* Q*V*R*W*Y* N*M* SG100 T*** X X X
A*B*U*K04E*I*F*J* Q*V*R*W*Y* N*M* SH100 T*** X X X X
A*B*U*K09E*I*F*J* Q*V*R*W*Y* N*M* SH300 T*** X X X X X
A*B0U*K03E*I*F*J* Q*V*R*W*Y* N*M* SK100 T*** X X X
A*B0U*K05E*I*F*J* Q*V*R*W*Y* N*M* SK300 T*** X X X X
A*B0U*K05E*I*F*J* Q*V*R*W*Y* N*M* SL100 T*** X X X
HESG448750M0001
T0129 is to be ordered additionally in case that single-pole autoreclosure for line differential protection
is required.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 34
All the functions of the basic versions can be applied in any combination providing the maximum capacity of
the processor and the number of analogue channels is not exceeded.
The basic versions with the longitudinal differential function include the additional 316EA62 board and
another back plate.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 35
R- R0 none
R1 8 optocoupler 4. binary input/output unit see previous table
6 signal. relays Type 316DB61
2 command relays
R2 4 optocoupler 4. binary input/output unit
10 signal. relays Type 316DB62
2 command relays
R3 14 optocoupler 4. binary input/output unit
8 signal. relays Type 316DB63
W- W0 none
W3 82 to 312 V DC 4. binary input/output unit state
W4 36 to 75 V DC optocoupler input voltage
W5 18 to 36 V DC
W9 175 to 312 V DC
Y- Y0 no comm. protocol Interbay bus protocol
Y1 SPA
Y2 IEC 60870-5-103
Y3 LON
Y41) MVB (part of IEC 61375)
N- N1 casing width 225.2 mm see previous table
N2 casing width 271 mm
M- M1 Semi-flush mounting Order M1 and sepa-
M51) Surface mounting, standard ter- rate assembly kit for
minals 19" rack mounting
S- SA000 basic versions REL316*4 Different versions of func- see previous table
to without differential function tions
SO990
SP000 basic versions REL316*4
to with differential function
SQ990
SZ990 order not acc. to Data Sheet
T- T0000 without FUPLA logic Customer-specific logic Defined by
T0001x FUPLA logic x = version of the FUPLA ABB Switzerland Ltd
to logic
T9999x
T0129x Logic for single-phase
autoreclosure for line differ-
ential protection
T0141x Logic for single-phase
autoreclosure for the distance
protection with a 1-breaker
scheme
T0142x Logic for single-phase
autoreclosure for a reclosure unit
with a 1-breaker scheme
T0990x FUPLA logic written by others
1)
MVB interface (for interbay or process bus) not applicable for surface-mounted version.
The order number has been defined for the basic version as above and the required accessories
can be ordered according to the following Table.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 38
Ordering (contd)
1
A test kit Type 316TSS01 comprises:
- casing for semi-flush or surface mounting
- test socket block RTXP24.
PCC card interface
Type Protocol Connector Optical fibre* Gauge ** Order No.
For interbay bus:
PCCLON1 SET LON ST (bajonet) G/G 62,5/125 HESG 448614R0001
500PCC02 MVB ST (bajonet) G/G 62,5/125 HESG 448735R0231
For process bus:
500PCC02 MVB ST (bajonet) G/G 62,5/125 HESG 448735R0232
Dimensioned
drawings
Dimensioned draw-
ings (contd)
Fig. 12 Surface mounting, casing able to swing to the left, rear connections. Size N1 casing
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 42
Dimensioned draw-
ings (contd)
Fig. 13 Surface mounting, casing able to swing to the left, rear connections. Size N2 casing.
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 43
Distance protection function (Z starters Alternatively, the relay ID code may be given
with provision for all transfer tripping instead. In this case the order would be:
schemes)
1 REL316*4, A1B0U1K03E2I3F2
Auto-reclosure J3Y1N1M1SK100T0
Communication with the station control 1 mounting kit HESG324310P1
system (e.g. LON)
1 CD RE.216 / RE.316*4
Operator program on CD. 1MRB260030M0001
Example of a Numerical line protection terminal with ex- be transmitted via the same communications
specification tensive self-supervision of the internal func- channel. Provision shall be made for the com-
tions and A/D conversion of all input vari- bination with a distance protection scheme, a
ables. The terminal shall be suitable for the directional ground fault scheme and back-up
protection of single and double-circuit lines functions.
and cables in solidly or low-impedance
grounded systems, ungrounded systems and The protection functions shall be in the form
systems with Petersen coils. It shall be capa- of software such that additional or different
ble of detecting all kinds of power system functions, i.e. power swing blocking, sensi-
faults including close three-phase faults, tive ground fault, overcurrent, thermal over-
cross-country faults (in ungrounded systems load, single or three-phase auto-reclosure,
or systems with Petersen coils), evolving application-specific logics etc., can be readily
faults and high-resistance ground faults. Due implemented without changes to the existing
account shall be taken of power swings and hardware. All configuration and setting oper-
changes in the direction of energy flow. ations shall be made using a menu-based
operator program running on a PC connected
The distance protection terminal shall have at locally to the terminal for the purpose.
least three distance zones with independent
settings and in addition zones of measure- The assignment of input and output signals to
ment for all the usual transfer tripping sche- the protection functions shall be possible lar-
mes. Provision shall be made for compensat- gely without restrictions. An event recorder
ing the mutual impedance in the case of par- with fault locator function shall be provided.
allel circuit lines using the neutral current of
the parallel circuit to obtain a correct setting. The data exchange between the control sys-
The integrity of the v.t. circuit shall be super- tem and the station control system shall be
vised. ensured via a communication interface. The
data connection itself shall be able to be de-
The longitudinal differential protection termi- signed with fibre optic conductors.
nal shall measure the three phases indepen-
dently and permit other protection signals to
ABB Switzerland Ltd Numerical line protection REL316*4
Utility Automation
1MRK506013-Ben
Page 44
The operating instructions are available in English or German (please state when ordering).
www.abb.com/substationautomation