Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

GB Statys 100A Rack Installation and Operating Manual (IOMSTARA0910-GB)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 39

STATYS

63-100A Rack
Installation and operating manual GB
INDEX

1. Warranty certificate 1
2. Presentation 2
2. 1. Foreword 2
2. 2. The role of Statys 2
2. 3. Operating principle 2
3. Safety instructions 3
3. 1. Precautions 3
3. 2. Electrical risk 4
3. 3. Risk of power cut 4
4. Overview 5
5. Unpacking 6
5. 1. Precautions on delivery of the product 6
5. 2. General recommendations for installation 6
6. Installation 7
6. 1. Securing the rack cabinet 7
6. 2. Installing the rails 7
6. 3. Installing the base 7
6. 4. Installing the power rack 7
6. 5. Cooling 8
6. 6. Mechanical characteristics 8
6. 7. Environment 8
7. Connection 9
7. 1. Access to terminals 9
7. 2. Electrical environment 10
7. 3. Schematic diagram 10
7. 4. Cable sizing 11
7. 5. Earthing diagrams 11
7. 6. Connection kit TNC diagrams 11
7. 7. Cable routing 12
7. 8. Devices for protecting persons and property 13
7. 9. Cabling procedure 14

2 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


INDEX

8. Operating modes 15
7. 10. Manual transfer 15
7. 11. Automatic transfer 15
8. 1. Automatic restart function 17
8. 2. Overload operation 17

ENGLISH
9. Mimic panel 18
9. 1. LCD and LEDs 18
9. 2. Password management 19
9. 3. Keypad 20
9. 4. Display 21
9. 5. Operating modes 22
10. Commissioning 29
10. 1. Start conditions 29
10. 2. Activation of output conduction 29
10. 3. Selecting the preferred source 29
10. 4. Load supply 29
10. 5. Maintenance bypass 30
11. Communication interfaces facilities 31
12. Advanced diagnostics and parameters 31
13. Main features 32
13. 1. Electrical characteristics - inputs 32
13. 2. Electrical characteristics - output 32
13. 3. Mechanical characteristics 32
13. 4. Environment 32
14. Glossary 33
15. Appendices: 34
14. 1. Plan: diagram 34

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 3


4 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03
1. Warranty certificate

The warranty terms are stipulated in the offer, by default the following clauses apply.

The SOCOMEC UPS warranty is strictly limited to the product(s) and does not extend to equipment which may be

integrated with this(these) product(s), nor the performance of this equipment.

The manufacturer guarantees its material to be free from manufacturing faults and defects in design, material or

ENGLISH
workmanship, subject to the limits set forth below.

The manufacturer reserves the right to modify the delivery with a view to fulfilling these guarantees or to replace de-

fective parts. The manufacturer’s warranty does not apply in the following cases:

–– fault or defect in the design of parts added or supplied by the customer;

–– fault due to unforeseen circumstances or force majeure;

–– replacement or repair resulting from the normal wear of the modules or machinery;

–– damage caused by negligence, lack of proper maintenance or misuse of the products;

–– repair, modification, adjustment or replacement of parts performed by unqualified third parties or personnel

without the express agreement of SOCOMEC UPS.

The warranty period is twelve months commencing from the date of delivery of the product.

The repair, replacement or modification of the parts during the warranty period does not extend the warranty period.

In order to establish a valid warranty claim, the purchaser must notify the manufacturer in writing immediately after

the discovery of any defects which are attributed to the material and provide any and all supporting evidence of the

defects at the latest within eight days before the date of expiry of the warranty.

Defective parts which have been returned and replaced free of charge shall become the property of SOCOMEC UPS.

The warranty is void if the purchaser has undertaken modifications or repairs on the devices on his or her own initia-

tive and without the express consent of the manufacturer.

The manufacturer’s responsibility is strictly limited to the obligations defined in this warranty (repair and replacement)

excluding any other right to claim compensation or indemnity.

Any import tax, duty, fee or charge of any nature whatsoever imposed by European regulations or those of an import-

ing country or of a transit country shall be paid by the purchaser.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 1


2. Presentation

2. 1. Foreword
Thank you for choosing the STATYS Static Transfer System from SOCOMEC UPS.

This equipment complies with the IEC 62310-2 product standard concerning Static Transfer Systems (STS).

This equipment conforms to EC directives applicable to this type of product. This conformity is indicated by the CE
mark.

2. 2. The role of Statys


STATYS watches permanently both sources of supply and the output to insure the automatic transfer of the use on
the alternate source in case of failure of the priority source and to allow a return of the use on that source when she
will be exploitable.

STATYS is defined by the rating of the current which passes through it by phase (in Amps), irrespective of other elec-
trical characteristics. The power for a given rating is a function of the nominal voltage used.

2. 3. Operating principle
STATYS is an autonomous electrical device which permits the seamless transfer of the load between an alternate elec-
trical source S1 and another alternate source S2 (see schematic diagrams § 7.3).

Under normal operation, STATYS supplies the load from the priority source. The priority source is selected by the
user according to on-site restrictions.
Two transfer modes are possible:

–– manual transfer mode, controlled by the operator locally or remotely by means of a BMS or other communicating
system,
–– automatic transfer mode, which occurs when an out-of-tolerance voltage is detected on the priority source. The
break-before-make switching principle prevents source overlap.

NOTE: The priority source (source 1 or source 2) is selected using the keyboard and this selection is displayed on-screen.

2 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


3. Safety instructions

3. 1. Precautions
This document provides essential instructions regarding safety, handling and connections (see § 7)

Carefully read this manual before operating STATYS.


Keep this manual in a safe place for future reference.

ENGLISH
CAUTION

For optimal use, it is recommended to maintain the ambient temperature and humidity at the values specified by the
manufacturer.
Do not expose STATYS to rain or any other type of liquid. Do not introduce foreign bodies into the unit.

WARNING

SOCOMEC UPS maintains integral and exclusive ownership of its intellectual and industrial property rights regard-
ing this document. Use of this document is limited to personal use by the recipient for the application specified by
SOCOMEC UPS. Any reproduction, modification or distribution of this document, whether in whole or in part, by any
means whatsoever, is expressly prohibited without the prior written permission of SOCOMEC.

This document is not a specification. SOCOMEC UPS reserves the right to modify the content of this document
without notice.

This unit must be exclusively installed, commissioned and repaired by specialist technical personnel authorised by
SOCOMEC UPS.

The product which you have chosen taking into consideration its conditions of use, capacities and performance
limits, is designed for commercial and industrial use only.
For use with so-called “critical applications”, the product may be required to comply with legal and regulatory obliga-
tions as well as specific local standards, and be adapted based on the recommendations of SOCOMEC UPS. In all
cases where the equipment is to be used for critical applications, you are advised to contact SOCOMEC UPS in ad-
vance to confirm that the products are capable of meeting the required levels of safety, performance and reliability.
The term “critical applications” notably includes life support systems, medical applications, commercial transport,
nuclear installations or any other system or application where the failure of the product is likely to cause substantial
damage to persons or property.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 3


3. Safety instructions

3. 2. Electrical risk
WARNING
All operations and maintenance must be performed by authorised personnel who have undertaken suitable training.

Scrupulously follow the operating or maintenance instructions described in this manual.


Take maximum precautions and determine which parts are live:
- by following the load diagrams,
- by checking the presence of power with a voltmeter, for example.

DANGER

The cabinet is permanently powered by sources 1 and 2.

In normal operating conditions, there is no danger for personnel handling this equipment.

3. 3. Risk of power cut


WARNING
Scrupulously follow the operating instructions described in this manual to prevent inadvertent power cuts which may
pose a safety hazard to the user.

DANGER

Taking into account the presence of high leakage currents, it is essential to connect the ground cable
before connecting the upstream and load sources.

Hazardous voltage may be present within STATYS after it is switched off.

In fact, the power supply voltage remains present at the input of each static contactor

STATYS MUST be moved by at least two people. They MUST stand on either side of the unit according
to the direction of movement.

4 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


4. overvieW

«Used source» LED

ENGLISH
Simplified mimic panel
a
Communication

b
Bypass hatch

a
b
Backfeed fuses

Extensions

Relay terminal block

Incoming / outgoing cable connections

KEY:
A = Pull-out power rack with switching electronics,
B = Fixed base incorporating the connection and manual bypass components.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 5


5. Unpacking

5. 1. Precautions on delivery of the product


On delivery, check the condition of the packaging and ensure that the equipment casing is not damaged, dented or
warped.
If necessary, report any damage or defects on the delivery note.

Carefully remove STATYS from its box, please bear in mind that the weight of the unit is not evenly distributed.

5. 2. General recommendations for installation


STATYS must be installed in an interior room which is:
–– protected from humidity
–– free of obstacles which may prevent natural ventilation,
–– sufficiently ventilated to ensure a constant temperature to the equipment,
–– clean, dry and dust-free,
–– free of flammable vapour or corrosive smoke

Carefully read this manual before making the «source» input and «load» output connections.

This manual must be kept next to STATYS, so that the operator may refer to it at any time in case of need.

The electrical connection and all wiring operations must be performed by qualified personnel.

6 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


6. Installation

6. 1. Securing the rack cabinet


Since STATYS is a pull-out unit, the cabinet must be firmly secured to the floor!

6. 2. Installing the rails

ENGLISH
Fasten the 2 rails (supplied with the product) inside the rack cabinet in order to support the base.

6. 3. Installing the base


Slide the base onto the 2 rails previously mounted and use the 4 holes in the front panel to fix the base to the cabinet
using 4 screws.

6. 4. Installing the power rack


STATYS is equipped with a device to protect against incorrect handling; check that the switch (behind the bypass
cover) is set to position 0.
Slide the power rack onto the base and check that the rear section is squarely positioned against the base.

Fasten the front of the rack using 4 screws.

Power rack fixing points

Base fixing points

The rack cabinet must have a minimum depth of 800 mm

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 7


6. Installation

6. 5. Cooling
air is drawn in through the front and exits through the back of the unit

Check that the air flow is not obstructed

Rating 63A 100A


Type of cooling Forced cooling
Air flow (m3 / h) 26
Max. dissipation (W) 330 540

6. 6. Mechanical characteristics

Rating 63A 100A


Height 400 mm
Width 483 mm
Depth 648 mm without handle
Weight 58 Kg
Module 3+6

6. 7. Environment

Rating 63A 100A


Operating temperatures 0 to 40 °C
Storage temperatures -20 to 70 °C
Protection degree IP 30
Humidity 0 - 95%
Altitude < 1000 m a.s.l. without derating
Noise level 42 dB(A)

8 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


7. Connection

7. 1. Access to terminals

The cabinet must be accessible from the rear in order to connect STATYS

Remove the 4 screws on the connection panel at the rear of the unit.

ENGLISH
Remove the panel, thus providing access to the connection terminals of the incoming / outgoing power cables.

COM slot 1

COM slot 2

L1 L2
Relay terminal block

Source 1 input Source 2 input Output

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 9


7. Connection

7. 2. Electrical environment
7. 2.1. Electrical characteristics - inputs

Rating 63A 100A


Nominal voltages (source 1 / source 2) 208-220V/ 380-415V / 440V
Nominal voltage tolerance ± 10% of Un (standard setting)
Rated Frequency 50 or 60 Hz
Frequency tolerance ± 2.5 Hz (can be configured up to ± 5 Hz)
Current crest factor ≤3.5
7. 2.2. Electrical characteristics - output

Rating 63A 100A


Nominal voltages Same as input voltages
Nominal frequency Same as input frequencies
Current 63A 100A
Current crest factor ≤3.5
Overloads See § 8.4

7. 3. Schematic diagram

Description Load

Uamt BP PE Uamt BP PE X10 Source 1 input

X10 X20 X20 Source 2 input

X30 Load output


XJ400 XJ400 XJ400

Q30 Position 0 of Q50


F411 F421
Q50 Maintenance bypass
Iavl Iavl

CS1 CS2 F4xx* 315A UR fuses


Iavl
RACK CSx Switches
RACK

XJ400
* according to model
Q30
I II

Q50-I Q30 Q50-II

4p 4p 4p

EMBASE
X30
FIXED CONNECTOR

Uavl PE

10 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


7. Connection

7. 4. Cable sizing
The connection terminals are adapted for connection of copper cables. The connection terminals cannot receive tinned
conductors. These terminals are spaced at 30mm intervals, which prevents accidental contact between 1 strand and a
terminal

Phases Neutral Earth

ENGLISH
Connection M6 M6 3 x M6

Max diameter (mm?) 35 50 50

Tightening torque (Nm) 4.5 4.5 4.5

Failure to observe earthing procedures may lead to the risk of electric shock, or the risk of fire if aa
earth fault occurs.

Remember to connect the earth at the marked point

Earth connections must be in compliance with local regulations and applicable standards.

The neutral is not always wired and depends on the neutral condition of the installation.

Earth connections must be in compliance with local regulations and applicable standards.

7. 5. Earthing diagrams
The STATYS range is compatible with all earthing systems. Nevertheless you should ensure that you have a suitable
safety device (3-pole breaker or 4-pole breaker) installed.

7. 6. Connection kit TNC diagrams


Supplied on request, these 3 brackets enable the neutral
terminal of the sources and output to be connected to a
ground terminal directly on the connection terminals. N

TNC kit

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 11


7. Connection

7. 7. Cable routing

7.7-1 Correct installation. 7.7-2 Authorised installation.

Common Control
Common Control mains Load cables 1
mains Load cables 1
N N
N N

≥10 cm ≥10 cm

Control
Mains Aux mains Load cables 1 Control
Mains Aux mains Load cables 1
N N N
N N N

≥10 cm ≥10 cm ≥10 cm

Control cables1: connections between the cabinets and each unit, alarm messages, remote mimic panel, BMS con-
nection, emergency stop, connection to breaker components...

7.7-3 Incorrect installation.

N N

N N N

Power cables and control cables must never be installed in the same raceway

Power cables near to sensitive equipment must not be exposed to electromagnetic fields.

12 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


7. Connection

7. 8. Devices for protecting persons and property


7. 8.1. Backfeed protection
In order to comply with the IEC62310-1 & IEC62310-3 Standard, STATYS is fitted with a control for backfeed protection
devices. In case of default on one input, STATYS delivers a voltage signal on terminal block XB2 (see § 11) to triggers the
breaker component by means of a pulse-type shunt trip coil.

ENGLISH
It is a phase to phase voltage

Backfeed cabling is mandatory

The breaker components triggered by the shunt trip coils must be marked with a warning label

7. 8.2. Internal protective device


Depending on the STATYS model ordered, an internal protective device may be present:

If possible, replace using an identical model of the same brand.

In any case the neutral is not protected (never broken).

The internal protective does not provide external upstream protection.

7. 8.3. External upstream protection


These protective devices need to be selected and configured taking into account the size of the STATYS unit, the
installation and the diameter of cable used.

Neutral rating if the load is non-linear (x 1.7).

The installation’s short-circuit current must not exceed that permitted by STATYS (see § 8.4)

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 13


7. Connection

7. 9. Cabling procedure
7. 9.1. Preliminary checks
Ensure that STATYS is correctly installed in its final position.
Check that the installation is isolated.

Set all switches to position 0.

7. 9.2. Cabinet cabling


Remove the protective devices to gain access to the power connections.

Check that the ground connector is clamped in firm contact with ground.

Check that the other installation devices are securely attached to this ground.

The diameter of the cable must comply with table § 7.4.

Fit a cable linking the ground connector to the PE terminal block.

Wire the source 1 phases on terminal block X10. Pay attention to the direction of rotation of the phases.

Note : Whether or not the neutral is wired on terminal block X10 depends on your neutral condition.

Wire the source 2 phases on terminal block X20. Pay attention to the direction of rotation of the phases.

Note: Whether or not the neutral is wired on terminal block X20 depends on your neutral condition.

Wire the output on terminal block X30. Pay attention to the direction of rotation of the phases.

Note: Whether or not the neutral is wired on terminal block X30 depends on your neutral condition.

Refit the protective panels.

14 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


8. Operating modes

8. 1. Manual transfer
The user is able to control the transfer of the load from one source to another, both via the keypad and via commu-
nication (see «communication interface» § 11).

Manual transfer does not disturb the supply to the load.


If the synchronisation conditions are not met after 30 seconds (factory default setting), an asynchronous transfer oc-

ENGLISH
curs, if authorised, otherwise the request is cancelled.

If the transfer cannot take place (for example, 2nd source out of tolerance), the following icon appears:

Impossible transfer

Note: The alarm will shut off automatically when normal conditions are restored.

8. 2. Automatic transfer
Automatic transfer occurs in the event of a voltage drop, frequency drop or when the preferred source is unavailable.
It does not interrupt the supply to the load. Automatic transfer switches the supply from the preferred source to the
alternate source. Once the preferred source is re-established, the system automatically returns to this source after a
time delay, which can be configured by the user.

The parameters that define the quality thresholds of the source and the automatic return can be adjusted in program-
ming mode (see § 9.5.4)

To ensure totally secure transfer, STATYS continuously monitors the presence of the alternate source.
If the alternate source is unavailable (or if the voltage exceeds the preset tolerances), the transfer function is inhibited.
STATYS immediately raises an alarm to warn the operator that the transfer is no longer possible.

Automatic return from the alternate source back to the preferred source may also occur following a manual transfer.

In the event of a short circuit at the output of the supplied equipment, the transfer function is inhibited. This stops the
short circuit from being transmitted along the other track and thus prevents the other source from being interrupted.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 15


8. Operating modes

Two types of transfer may occur, synchronous or asynchronous, according to the source synchronisation status and
the hardware configuration.

Synchronous transfer
Synchronous transfer occurs automatically when the two sources S1 and S2 are deemed to be synchronised, e.g.
when their phase deviation is within the tolerance window (standard +/- 10°). In this case, switching the source does
not alter the phase.
If the phase deviation exceeds this tolerance window, synchronous transfer is inhibited and automatic changeover to
the other source will not be possible. However, the transfer may in any event be executed in these conditions if the
system is configured for synchronous/asynchronous transfer.

NOTE: STATYS is configured for synchronous/asynchronous transfer by default.


It may be configured to «synchronous only» transfer for applications which are sensitive to phase shifts (advanced
parameters, see §12).
Most information processing equipment, servers, computer... are impervious to significant phase variations.

Asynchronous transfer
Automatic asynchronous transfer occurs only if it is authorised by the software configuration (standard factory con-
figuration, advanced parameters see §12) and if the sources S1 and S2 are not synchronised, e.g. their phase de-
viation exceeds the tolerance window. In this case, switching the source may produce a significant phase variation
during the changeover.

This type of transfer allows for automatic load changeover between sources which are not permanently controlled,
or which are unusually out of phase, thereby maximising the security of the power supply.

16 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


8. Operating modes

8. 3. Automatic restart function

Following the total unavailability of both sources and if STATYS is in conduction state on one of the two sources, an
automatic restart and conduction occurs on the return to one of the 2 sources.

The supply is re transferred automatically onto the preferred source as soon as this source becomes available.

ENGLISH
The automatic restart function is configurable and is set to OFF by default.

8. 4. Overload operation

The STATYS overload control is based on the principle of filling a reservoir more or less rapidly, depending on the
measured load rate.
Each STATYS string has its own reservoir.
When STATYS is in overload, an «OVERLOAD ALARM» message appears and the «GENERAL ALARM» is triggered.

Typical overloads guide:

The increment follows the guide below:

Overload Time
110% 60 min
125% 10 min
150% 2 min
200% 20 seconds

Note: These values may vary as a function of the rating (in amperes), the protection index and the ambient temperature.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 17


9. mimic Panel

9. 1. LCD and LEDs


9. 1.1. Presentation
The mimic panel consists of:

– an LCD screen permitting:


• display of electrical magnitudes of an input or output (in AUT mode)
• activation of system controls (in CONTROL mode)
• display of maintenance codes (in TEST mode)
• programming of the device (in PROG mode)

– 13 LEDS indicating:
• the different operating states
• the mimic panel showing the power flow
• the system’s current mode

– 6 keys used for system management.

18 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


9. Mimic panel

9. 1.2. Meaning of leds

ON BLINKING OFF

Load supplied by STATYS Output shutdown imminent Output not supplied by STATYS

Output supplied directly by source 1 / /

ENGLISH
Output supplied directly by source 2 / /

General Alarm Critical alarm No alarm active

Source within tolerances Source outside tolerated range Source absent

Conduction path Path outside tolerated range No conduction

Transfer locked Switchback impossible Transfer possible

Selected mode Mode awaiting selection /

9. 2. Password management
Two levels of protection:
«User» password: provides access to control mode and user parameters settings (user access). Disabled by default
(set to _ _ _), it can be configured from 000 to 999 and _ _ _.
«System» password: provides access to user and system parameter settings. The default setting is 000, it may be
configured from 000 to 999.

When the device is in standby mode, the password is invalidated.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 19


9. Mimic panel

9. 3. Keypad

KEY FUNCTION

Accesses different menus (AUT, CONTROL, TEST and PROG)

Once in a menu, cancels an ongoing command

In CONTROL mode, activates source 1 conduction

Scrolls display, menu or digit

In CONTROL mode, stops conduction

Scrolls display, menu or digit

In CONTROL mode, activates source 2 conduction

Modifies the blinking value

In TEST mode, launches a full display test (LEDs, screen, buzzer)

Modifies the blinking value

Acknowledges alarm

Validate or store

The buzzer emits a short beep whenever a key is pressed

20 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


9. Mimic panel

9. 4. Display
The LCD screen displays:

The following icons (irrespective of which mode is selected):

or = indicates the preferred source

ENGLISH
Off = synchronous sources
Blinking = sliding sources
On = permanently asynchronous sources

= Password protection is ON

Electrical magnitudes:

Voltages and frequency of each source on 1 page marked with the number or to indicate the source in
question

Voltages and frequency (1 page), current (1 page), power (kW and kVA), power factor and crest factor (CF) (1 page)
and load rate (Lr and %) (1 page) of the output, marked with the icon

If there is no output load, the display switches alternately from source 1 to source 2.
If there is a load at the output, only the output pages are displayed.

An alarm message may appear if an alarm is raised (see «alarm» chapter).

This standard display may be temporarily fixed on one page using the buttons and

The display goes into standby mode (backlight OFF) after 5 minutes of keypad inactivity.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 21


9. Mimic panel

9. 5. Operating modes

there are 4 modes:


Whatever the mode selected, STATYS operation remains prioritised.
–– automatic (AUT)
–– control (CONTROL)
–– test (TEST)
–– programming (PROG)

Press the key to select the next mode (the corresponding LED will blink), press the key to enter the se-

lected mode.

If the keypad is not touched for 30 seconds, the system returns to automatic mode.

9. 5.1. Automatic mode


This is the default mode. In this mode the LCD screen displays the electrical magnitudes of the inputs or of the output
(see «display» chapter), as well as alarm messages (see «alarm» chapter).
The display can be fixed on one page using the keys and

9. 5.2. Control mode

This mode is accessed by entering the «user» password (if defined)

The display is identical to the automatic mode display (but cannot be fixed on one page). The device waits for the
conduction state to be changed manually:

Stop conduction press the (OFF) key, the «ld off» indicator blinks, press the key, then this sequence a

second time to validate this choice or press the key to cancel the command.

Activate source 1 conduction press the key (1), the message «use S1» blinks, press the key to validate this

choice or press the key to cancel the command.

22 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


9. Mimic panel

Activate source 2 conduction press the key (2), the message «use S2» blinks, press the key to validate

this choice or press the key to cancel the command.

These changeovers are performed whether the sources are synchronous or asynchronous, unless the

ENGLISH
factory setting of the device is changed to «synchronous only» mode (no asynchronous transfer, set-
tings accessible in advanced parameters, see §10).

If the sources are sliding, the appliance requests a «transfer on the fly»

Transfer on the fly


If, during a conduction activation request, the sources are sliding, a «fly» message blinks along with the phase shift
value.

The user can then:

–– wait for the transfer to occur automatically once the 2 sources become synchronous,

–– force the transfer (if the device configuration authorises an asynchronous transfer) by once more pressing the key for

the desired source. The message «frc trf» (force transfer) blinks on the last line («fly» no longer blinks), press the

key to validate the forced transfer request (cancel using the key and thereby return to the «fly» message),

To exit this mode, press the key for the source in conduction state once more. The message «esc» then appears.
Validate it using the key or cancel it using the key.

Stop automatic switchback when the device is waiting for phase synchronisation, press the key for the alternate

source ( or ).

The message «end asb» appears

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 23


9. Mimic panel

9. 5.3. Test mode


This mode enables maintenance codes to be displayed in the form of pages marked with a number
For each maintenance page the following information appears:

–– on the bottom line, the message «STS Code N° xxx» where xxx corresponds to the page n°,
–– on the top two lines, 4 hexadecimal digits corresponding to the maintenance code.

the page is changed using the keys and

Pressing on the key launches a complete mimic panel test by:

–– Switching on all LEDs,

–– Displaying all LCD segments,

–– Operating the buzzer.

This mode does not interrupt the normal operation of STATYS

9. 5.4. Programming mode

This mode is accessed by entering a password:

If the «user» password is inputted, only «user» parameters may be configured.


If the «system» password is inputted, all parameters could be modified.

24 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


9. Mimic panel

Choice of preferred source (user access)


Display: PS
Default value: S1
Possible choice: S1 or S2

Modbus link configuration (user access)

ENGLISH
Display: mod bus

Slave number
Display: sla nb
Default value: 1
Possible choice: 1 to 255

Link speed
Display: bds
Default value: 9600
Possible choice: 2400, 4800, 9600 or 19200

Link parity
Display: par
Default value: no
Possible choice: odd, eve (even) or no

Timestamp (user access)


Display: day time

Date
Display: day
Default value: today
Possible choice: day-month-year with day from 1 to 31, month from Jan to Dec and year from 00 to 99

Time
Display: time
Default value: current hour

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 25


9. Mimic panel

System configuration (System access)


Display: sys cfg

Password configuration
Display: pin code

User password
Display: usr pin (user pin)
Default value: _ _ _
Possible choice: 000 to 999 (000 = no password)

System password
Display: sys pin (system pin)
Default value: 000
Possible choice: 000 to 999

Remote control (System access)


Display: rem ctl (remote control)
Default value: en
Possible choice: en (enable) or dis (disable )

Sensitivity threshold* (System access)


Display: sen (sensitivity)
Default value: std
Possible choice: L for «low», std for «standard», H for «high» and cus for «custom» (configuration via PC link)

*Values used to carry out transfer (if authorised):


Low Sensitivity:
• the RMS voltage value exceeds the rated value by +/- 15%,
• The frequency exceeds the rated value by +/- 4 Hz,
• instantaneous voltage (1ms transient) drops to 40% below the RMS rated voltage.
High Sensitivity:
• the RMS voltage value exceeds the rated value by +/- 5%,
• The frequency exceeds the rated value by +/- 1 Hz,
• instantaneous voltage (1ms transient) drops to 15% below the RMS rated voltage.
Standard Sensitivity:
• the RMS voltage value exceeds the rated value by +/- 10%,
• The frequency exceeds the rated value by +/- 2 Hz,
• instantaneous voltage (1ms transient) drops to 25% below the RMS rated voltage.

26 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


9. Mimic panel

Automatic load resupply (System access)


Display: aut on (automatic on)

Use of automatic resupply


Display: aut on (automatic on)
Default value: no

ENGLISH
Possible choice: yes or no

Delay before automatic resupply


Display: dly (delay)
Default value: 0 seconds
Possible choice: 0 to 65535 (if aut on = yes)

Automatic retransfer to the preferred source (System access)


Display: aut sb (automatic switchback)

Use of automatic switchback


Display: aut sb (automatic switchback)
Default value: no
Possible choice: yes or no

Delay before automatic switchback


Display: dly (delay)
Default value: 3 seconds
Possible choice: 0 to 65535 (if aut sb = yes)

Nominal voltage (System access)1


Display: un (Un)
Default value: nominal value measured by the equipment
Possible choice: 100V to 499V

Nominal frequency (System access)1


Display: fn (F)
Default value: nominal value measured by the equipment
Possible choice: 50 or 60 Hz

Values used to calculated upper and lower limits.


1

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 27


9. Mimic panel

9. 5.5. Alarm management


When an alarm is triggered (see alarms table), a flashing message (and his number) appears on the screen regard-
less of which mode is in use. If the alarm is critical the LED flashes, otherwise it is lit continuously. In addition to the
message and the LED warning, a buzzer will sound.
When the key is pressed, the alarm is acknowledged and the buzzer is silenced, the display remains fixed (it
shows the display pages) but the LED remains ON
These different alarm displays will disappear when the alarm disappears.
In the case of multiple alarms, only the most important one will be displayed and the buzzer will sound until the last
alarm is acknowledged.

Name Message N° Meaning

Imminent stop imm stp 0 Imminent conduction shutdown

Output Isc detection Out isc 1 Output in short circuit

Manual By-pass mnt bp 2 Manual bypass on

Overload I max 3 Overload at the output

Consecutive detections Con det 5 Too many consecutive transfers

Switchback impossible sb imp 6 Impossible Switchback

Transfer impossible trf imp 7 Impossible Transfer

PowerPath 1 deteriorated pa1 at 9 Input 1 out of tolerance

PowerPath 1 in short circuit pa1 sc 10 Input 1 in short circuit

PowerPath 1 in failure pa1 out 11 Input 1 in failure

PowerPath 2 deteriorated pa2 at 13 Input 2 out of tolerance

PowerPath 2 in short circuit pa2 sc 14 Input 2 in short circuit

PowerPath 2 in failure pa2 out 15 Input 2 in failure

Backfeed S1 protection open bf opn 16 Source 1 protection open

Backfeed S2 protection open bf opn 17 Source 2 protection open

Ambient temperature max tmp max 18 Max temperature reached

Insufficient resources ins res 20 Insufficient resources

HMI hmi 27 Communication with screen lost

Electronic eln 28 Electronic problem

Custom input alarm cus in 29 Custom alarm

Preventive alarm pre alm 30 Preventive alarm

General Alarm gen alm 31 General Alarm

28 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


10. Commissioning

10. 1. Start conditions


The 3-way switch is set to position «0», Source 1 and Source 2 voltages are present, the mimic panel will then be
activated.

10. 2. Activation of output conduction

ENGLISH
According to the autorestart configuration (see § 9.5) conduction can then be activated on the output. The user can
then establish conduction from the alternate source, or stop conduction.

10. 3. Selecting the preferred source


Note: According to the factory default setting, the preferred source is source 1.
Under normal operation, the load is supplied by the preferred source.

REMINDER: automatic transfer switches the supply from the preferred source to the alternate source. It is therefore
important that the user defines the preferred source.

The preferred source is selected in «programming» mode (see § 9.5.4).

10. 4. Load supply


If conduction is not activated, the user may force the conduction (see § 9.5.2 Controls mode).

When STATYS is in conduction state, close switch Q30. The icon lights up.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 29


10. Commissioning

10. 5. Maintenance bypass


STATYS is equipped with two bypasses which enable it to directly supply the load from source 1 or 2 without inter-
rupting your application’s power supply
At that point, the power rack can be pulled out.

This function is entirely secure, the switches are equipped with mechanical and electronic locks to minimise the risk
of human error.
Nevertheless you should observe the follow instructions:

The bypass is initiated using a 3-way switch:

0
In position 0 = normal operation
1 2

the power rack cannot be pulled out (mechanical lock).

Activate bypass 1: Ensure that STATYS is on source 1

0 In position 1 = bypass to source 1

1 2
the load is directly supplied by source 1

the power rack can be pulled out.

Return to normal operation (position 0): Ensure that STATYS is on source 1

Activate bypass 2: Ensure that STATYS is on source 2

0
In position 2 = bypass to source 2

1 2
the load is directly supplied by source 2

the power rack can be pulled out.

Return to normal operation (position 0): Ensure that STATYS is on source 2

Do not change the position of the switch when the power rack is removed, as the critical load would
no longer be supported

30 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


11. Communication interfaces facilities

STATYS is equipped as standard with:


–– (on front panel) one Ethernet port which allows for ModBus TCP communication, use of the SNMP protocol, send-
ing of emails following alarm activation, and integrated Web page browsing
–– (on the rear panel), one terminal block giving access to:

ENGLISH
4 3 2 1

8 7 6 5 4 3 2 1

XB 1 XB 2

XB 1:
•• 1 inverter relay for the general alarm, terminal 1 = Normally Open, 2 = Common, 3 = Normally Closed,
•• 1 inverter relay for the preventive maintenance alarm, 4 = Normally Open, 5 = Common, 6 = Normally Closed,
•• 1 relay for an emergency stop button (not supplied), terminals 7 and 8, Normally Open (on request Normally Closed)

XB 2:
•• 1 relay for tripping of upstream protection (source 1), terminals 1 and 2,
•• 1 relay for tripping of upstream protection (source 2), terminals 3 and 4.

STATYS is also equipped with 2 spare slots (slot 1 and slot 2) which can each house one communication module:
–– 1 serial port module (JBus/ModBus or Profibus or DeviceNet) on slot 1 only,
–– 1 to 2 alarm relay modules (each module providing 3 inputs and 4 outputs).

12. Advanced diagnostics and parameters


STATYS is equipped with a diagnostic plug on the front panel, for connection of a maintenance computer. This link
can be used for adjusting the advanced parameters and other settings according to specific operational needs.
Maintenance personnel can also use this link to download the event log, statistics and comprehensive information
for rapid and complete diagnostics.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 31


13. Main features

13. 1. Electrical characteristics - inputs


Rating 63A 100A
Nominal voltages (source 1 / source 2) 208-220V/ 380-415V / 440V
Nominal voltage tolerance ± 10% of Un (standard setting)
Rated Frequency 50 or 60 Hz
Frequency tolerance ± 2.5 Hz (can be configured up to ± 5 Hz)
Current crest factor ≤3.5

13. 2. Electrical characteristics - output


Rating 63A 100A
Nominal voltages Same as input voltages
Rated Frequency Same as input frequencies
Current 63A 100A
Current crest factor ≤3.5
Overloads See § 8.4

13. 3. Mechanical characteristics


Rating 63A 100A
Height 400 mm
Width 483 mm
Depth 648 mm
Weight 58 Kg
Module 3+6

13. 4. Environment
Rating 63A 100A
Operating temperatures 0 to 40 °C
Storage temperatures -20 to 70 °C
Protection degree IP 30
Humidity 0 - 95%
Altitude < 1000 m a.s.l. without derating
Cooling Forced cooling
Noise level 42 dB(A)

32 STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


14. Glossary

STS: Static Transfer System

S1: Source 1 input


S2: Source 2 input

preferred source:

ENGLISH
source used as normal power supply to the load, generally set by the operator

alternate source:
source used as an alternative power supply to the load when the priority source fails or exceeds the permitted tole-
rances or is switched off for maintenance.

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03 33


34
m
m
COURANT MAXIMUM ADMISSIBLE

8
MAXIMUM CURRENT WITH STAND

68
10x8.2 mm
MODEL Volts X10 X20 X30
3STA 63A 380-415V 63A 63A 63A 359.95 mm
3STA 100A 380-415V 100A 100A 100A

X10 : ARRIVEE RESEAU SOURCE 1


MAINS INPUT SOURCE 1
X20 : ARRIVEE RESEAU SOURCE 2

266.7 mm
MAINS INPUT SOURCE 2
X30 : SORTIE UTILISATION
169.45 mm
LOAD OUTPUT
15. Appendices:

400.05 mm
SOURCE 1 SOURCE 2
14. 1. Plan: diagram

3Ph+N+PE PE 3Ph+N+PE PE
92.8 mm

STATYS 63-100A Rack - Ref.: IOMSTARA0910-GB_03


X10 X20 35.7 mm

133.35 mm
XJ400 XJ400 XJ400
483 mm

F411 F421

CS1 CS2

RACK
RACK
XJ400

IQ30
II

Q50-I Q30 Q50-II


SLOT1
4p 4p 4p
SLOT2
EMBASE X30
EMBASE

3Ph+N+PE PE X10 X20 X30

STATYS 100A
DATE REV. ETABLI MODIFICATIONS VERIFIE APPROUVE
Rack 19" Innovative Power Solutions
DATE REV. ISSUED BY MODIFICATIONS CHECKED BY APPROUVED BY
Socomec UPS
worldwide
IN EUROPE IN ASIA
BELGIUM PORTUGAL CHINA
Schaatsstraat, 30 rue du Patinage Rua Moinho do Cuco No.1 Yuanda Road Haidian District, Beijing, 100097
B - 1190 Bruxelles Bloco A Golden Resource Times Shopping Mall
Tel. +32 (0)2 340 02 34 Lj. Dta. - Paz No. 1001 section B the 2nd issue of business building
Fax +32 (0)2 346 16 69 2640-566 MAFRA Tel. +86 10 8889 2202
be.ups.sales@socomec.com Tel. +351 261 812 599 Fax +86 10 8889 2150
Fax +351 261 812 570 socomec@socomec.com.cn
FRANCE portugal@socomec.com
95, rue Pierre Grange INDIA
F - 94132 Fontenay-sous-Bois Cedex SLOVENIA B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate
Tel. +33 (0)1 45 14 63 90 Savlje 89 Guindy
Fax +33 (0)1 48 77 31 12 SI - 1000 Ljubljana Chennai – 600 032
ups.paris.dcm@socomec.com Tel. +386 1 5807 860 Tel. +91 44 3921 5400
Fax +386 1 5611 173 Fax +91 44 3921 5450 — 51
GERMANY si.ups.info@socomec.com sales@socomec-ups.co.in
Heppenheimerstraße 57
D - 68309 Mannheim SPAIN MALAYSIA
Tel. +49 (0) 621 71 68 40 C/Nord, 22 Pol. Ind. Buvisa 31 Jalan SS 25/41- Mayang Industrial Park
Fax +49 (0) 621 71 68 44 4 E - 08329 Teià (Barcelona) 47301 Petaling Jaya.- Selangor, Malaysia
de.ups.all@socomec.com Tel. +34 935 407 575 Tel. +603 7804 1153
Fax +34 935 407 576 Fax +603 7803 8901
ITALY info@socomec-aron.com sales@cspm.com.my
Via Leone Tolstoi, 73 - Zivido
20098 San Giuliano Milanese (MI) UNITED KINGDOM SINGAPORE
Tel. +39 02 98 242 942 Units 7-9 Lakeside Business Park 31 Ubi Road 1, Aztech Building
Fax +39 02 98 240 723 Broadway Lane - South Cerney # 01-00 (Annex) - SG - Singapore 408694
siconmi@socomec.com Cirencester - GL7 5XL Tel. +65 6745 7555
Tel. +44 (0)1285 863300 Fax +65 6458 7377
NETHERLANDS Fax +44 (0)1285 862304 sg.ups.sales@socomec.com
Bergveste 2F
uk.ups.sales@socomec.com
NL - 3992De Houten THAILAND
Tel. +31 (0)30 63 71 504 No.9 Soi Vibhavadirangsit 42
Fax +31 (0)30 63 72 166 Vibhavadirangsit Rd, Ladyao
info@socomec.nl Chatujak Bangkok 10900
Tel. +66 2 941-1644-7
POLAND Fax. +66 2 941-1650
Nowowiejska St 21/25 info@socomec-th.com
00-665 Warszawa
Tel. +48 (0)22 2345 223
Fax +48 (0)22 2345 223
ups.poland@socomec.com

HEAD OFFICE S ales , M arketing and


SOCOMEC GROUP S ervice M anagement
S.A. SOCOMEC capital 11 102 300 € - R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex SOCOMEC UPS paris
SOCOMEC UPS Strasbourg 95, rue Pierre Grange
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE F-94132 Fontenay-sous-Bois Cedex - FRANCE
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
ups.benfeld.admin@socomec.com ups.paris.dcm@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
Tel. +39 0444 598611 - Fax +39 0444 598622
info.it.ups@socomec.com

www.socomec.com
Non contractual document. © 2008, Socomec SA. All rights reserved.

Valid for France Valid for Italy


ООО "Энергетические и Телекоммуникационные Системы"
Тел./факс: (495) 981-13-66
http://www.entel.ru, E-Mail: sales@entel.ru

You might also like