SG Frenic Lift en 1 8 0
SG Frenic Lift en 1 8 0
SG Frenic Lift en 1 8 0
FRENIC-Lift
Dedicated
Inverter for Lift
Applications
3 ph 400V 4.0 kW - 45 kW
3 ph 200V 5.5 kW - 22 kW
1 ph 200V 2.2 kW
SG_Lift_EN_1.8.0
Version Changes applied Date Written Checked Approved
0.1.0 Draft 10.05.2007 W. Zinke W. Zinke W. Zinke
st
1.0.0 1 Release 15.08.2007 A. Schader A. Schader A. Schader
1.0.1 Spelling corrections 16.08.2007 A. Schader A. Schader A. Schader
1.0.2 Recommendations according to Lutz 20.08.2007 A. Schader A. Schader A. Schader
1.0.3 Added cover mounting / dismounting 20.08.2007 A. Schader A. Schader A. Schader
1.0.4 Recover the lift 20.08.2007 A. Schader A. Schader A. Schader
1.0.5 Update for 4.0, 37 and 45 kW 24.10.2007 A. Schader A. Schader A. Schader
1.0.6 Update 2 for 4.0, 37 and 45 kW 31.10.2007 A. Schader A. Schader A. Schader
1.1.0 First English version 20.11.2007 D. Bedford D. Bedford D. Bedford
Spelling corrections
Most important functions in I/O terminal functions are added
1.2.0 in table 16 21.02.2007 J. Alonso D. Bedford D. Bedford
200 V technical data added
De-rating and over-rating added
1.2.1 Layout changes applied 27.02.2008 A. Schader D. Bedford D. Bedford
1.2.2 OS formula corrected 28.03.2008 J. Alonso D. Bedford D. Bedford
Caution added in chapter “conformity to European
1.2.3 07.04.2008 J. Alonso D. Bedford D. Bedford
standards”
“Maximum braking time” changed.
“Binary combination for speed selection” example modified.
“Signal timing diagram for travel using intermediate speeds”
updated.
“Correspondence of functions for each phase of the
1.3.0 14.07.2008 J. Alonso J. Català J. Català
sequence” table updated and general table added.
H64, H65 & L74 added in start & stop optimization table.
Figure 26 modified.
Rescue operation information modified.
Alarm codes updated.
L56 added to travel optimization table
1.3.1 Figures 8, 9, 10 and 11 modified slightly 15.07.2008 J. Català J. Català J. Català
Some information added to parameter F03
Specification tables revised
Figure on page 11, 12, 18, 19, 20 and 22, slightly modified
1.3.2 16.07.2008 J. Català J. Català J. Català
H67 definition improved on page 33
L56 definition added on page 39
Figure 23 modified
Table 11 modified
Title changed and text added on page 39 (soft start function)
1.3.3 16.07.2008 J. Alonso D. Bedford D. Bedford
Alarm messages table modified
Tables numbers corrected
Small text corrections
No-load current calculation formula is added
Table 12 is updated
Function L83 is added and a value is specified in functions
1.4.0 25.11.2008 J. Alonso D. Bedford D. Bedford
F20 and F25 in table 11.4
Chapter numbers are included
Small text corrections
ROM version is included
CE declaration is updated
EN954-1 Cat 3 is included
1.5.0 2,2kW -7 is included 25.01.2010 J. Alonso D. Bedford D. Bedford
Specifications and over-rating changed
Figure 26 is changed
Some text is added or modified
ROM version updated
L07, H98(bit2) and L99(bit6) functions included
1.6.0 24.12.2010 J. Alonso D. Bedford D. Bedford
Some text is added or modified
Specifications modified
Figure numbers are restructured
1.6.1 Figure 4 is modified 28.02.2011 J. Alonso D. Bedford D. Bedford
Chapter 3.1 is corrected
Information at 15 kHz of switching frequency is added in
chapter 3.3
OPL trip is included in chapter 17
Definition of parameters F03 and F04 is changed in chapters
1.6.2 12.03.2011 J. Alonso D. Bedford D. Bedford
11.2, 11.3 and 11.4
F09 is added in chapter 11.4
Some text is modified
Format of tables is changed and restructured
EN1 and EN2 terminals included
Safety standards updated
1.7.0 Mistake corrected in figure 11 04.01.2012 J. Alonso D. Bedford D. Bedford
Firmware version updated
ASR PI included on figure 29
Some information is added in Chapter 3 (safety standards)
Some values updated in table 1
1.7.1 12.07.2012 J. Alonso J. Català J. Català
Some trips are included in chapter 17
Logo is updated
Modifications regarding L80, H04. L76 added.
1.8.0 20.05.2014 J. Alonso J. Català J. Català
Some text is modified in chapter 3.1, 3.2 and 15
Dedicated to Mr. Wilfred Zinke
We would like to thank you for your valuable support and assistance in creating this Starting Guide, we are very grateful that you
dedicated your time for this.
FRENIC-Lift series inverter is specially designed for operation of induction and permanent magnet
synchronous motors used in lift applications. Also induction motors without encoder (open loop) can be
controlled obtaining good performance and high positioning accuracy at stop.
This starting guide includes the important information and explanations about the connection and
commissioning of FRENIC-Lift for elevator applications.
Inputs and outputs can be set to different functions using the corresponding functions. By
factory defaults these settings are already suitable for lift applications. In this manual only the
functions related to lift applications are described.
The factory default settings are suitable for induction motors (geared). In case of gearless
synchronous motors the corresponding functions have to be set. It is always possible revert
the function values to factory default.
When setting back to factory default the value of the encoder offset (function L04) is lost. In
this case it is recommended to write down this value before setting to default settings, to be
set back afterwards. This saves the time of making again the pole tuning procedure.
Special functions are not described which are only used in special applications. For questions
please contact our technical staff.
This starting guide is based on firmware version 1950 and 1951 or later. For other software
versions, please contact with Fuji Electric technical department.
Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or maintenance and inspection. Ensure you have
sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the inverter.
Safety precautions are classified into the following two categories in this manual.
Failure to heed the information indicated by this symbol may lead to dangerous conditions,
possibly resulting in death or serious bodily injuries.
Failure to heed the information indicated by this symbol may lead to dangerous conditions,
possibly resulting in minor or light bodily injuries and/or substantial property damage.
Failure to heed the information contained under the CAUTION title can also result in serious consequences. These safety precautions are
of utmost importance and must be observed at all times.
Application
• FRENIC-Lift is designed to drive a three-phase induction motor. Do not use it for single-phase motors or for other purposes.
Fire or an accident could occur.
• FRENIC-Lift may not be used for a life-support system or other purposes directly related to the human safety.
• Though FRENIC-Lift is manufactured under strict quality control, install safety devices for applications where serious accidents
or material losses are foreseen in relation to the failure of it.
An accident could occur.
Installation
• Do not support the inverter by its terminal block cover during transportation.
Doing so could cause a drop of the inverter and injuries.
• Prevent lint, paper fibres, sawdust, dust, metallic chips, or other foreign materials from getting into the inverter or from
accumulating on the heat sink.
Otherwise, a fire or an accident might result.
Wiring
• When wiring the inverter to the power supply, insert a recommended moulded case circuit breaker (MCCB) or
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection)
in the path of power lines. Use the devices within the recommended current range.
• Use wires of the specified size.
• When wiring the inverter to the power supply that is 500 kVA or more, be sure to connect an optional DC reactor
(DCR).
Otherwise, fire could occur.
• Do not use one multicore cable in order to connect several inverters with motors.
• Do not connect a surge killer to the inverter's output (secondary) circuit.
Doing so could cause fire.
• Ground the inverter in compliance with the national or local electric code.
Otherwise, electric shock could occur.
• Qualified electricians should carry out wiring.
• Disconnect power before wiring.
Otherwise, electric shock could occur.
• Install inverter before wiring.
Otherwise, electric shock or injuries could occur.
• Ensure that the number of input phases and the rated voltage of the product match the number of phases and the
voltage of the AC power supply to which the product is to be connected.
Otherwise fire or an accident could occur.
• Do not connect the power supply wires to output terminals (U, V, and W).
• Do not insert a braking resistor between terminals P (+) and N (-), P1 and N (-), P (+) and P1, DB and N (-), or P1 and
DB.
Doing so could cause fire or an accident.
• Generally, control signal wires are not reinforced insulation. If they accidentally touch any of live parts in the main
circuit, their insulation coat may break for any reasons. In such a case, ensure the signal control wire is protected from
making contact with any high voltage cables.
Doing so could cause an accident or electric shock.
• Be sure to install the terminal cover before turning the power ON. Do not remove the covers while power is applied.
Otherwise electric shock could occur.
• Do not operate switches with wet hands.
Doing so could cause electric shock.
• If the auto-reset function has been selected, the inverter may automatically restart and drive the motor depending on
the cause of tripping.
(Design the machinery or equipment so that human safety is ensured after restarting.)
• If the stall prevention function (current limiter), automatic deceleration, and overload prevention control have been
selected, the inverter may operate at an acceleration/deceleration time or frequency different from the commanded
ones. Design the machine so that safety is ensured even in such cases.
Otherwise an accident could occur.
• If an alarm reset is made with the Run command signal turned ON, the inverter may start immediately. Ensure that the
Run command signal is turned OFF in advance.
Otherwise an accident could occur.
• Ensure you have read and understood the manual before programming the inverter, incorrect parameter settings may
cause damage to the motor or machinery.
An accident or injuries could occur.
• Do not touch the inverter terminals while the power is applied to the inverter even if the inverter is in stop mode.
Doing so could cause electric shock.
• Do not turn the main circuit power (circuit breaker) ON or OFF in order to start or stop inverter operation.
Doing so could cause failure.
• Do not touch the heat sink and braking resistor because they become very hot.
Doing so could cause burns.
• Before setting the speeds (frequency) of the inverter, check the specifications of the machinery.
• The brake function of the inverter does not provide mechanical holding means.
Injuries could occur.
• Turn the power OFF and wait for at least five minutes before starting inspection. Further, check that the LED
monitor is unlit and that the DC link bus voltage between the P (+) and N (-) terminals is lower than 25 VDC.
Otherwise, electric shock could occur.
• Maintenance, inspection, and parts replacement should be made only by qualified persons.
• Take off the watch, rings and other metallic objects before starting work.
• Use insulated tools.
Otherwise, electric shock or injuries could occur.
Disposal
Others
The CE marking on Fuji Electric products indicates that they comply with the essential requirements of the Electromagnetic
Compatibility (EMC) Directive 2004/108/EC issued by the Council of the European Communities and the Low Voltage Directive
2006/95/EC.
Inverters with built-in EMC filter that bear a CE marking are in conformity with EMC directives. Inverters having no built-in EMC
filter can be in conformity with EMC directives if an optional EMC compliant filter is connected to them.
General purpose inverters are subject to the regulations set forth by the Low Voltage Directive in the EU. Fuji Electric declares the
inverters bearing a CE marking are compliant with the Low Voltage Directive.
FRENIC-Lift inverters are in accordance with the regulations of following council directives and their amendments:
EMC Directive 2004/108/EC (Electromagnetic Compatibility)
EN61800-5-1:2003
The FRENIC-Lift inverters are categorized as category C2 according to EN61800-3:2004. When you use these
products in the domestic environment, you may need to take appropriate countermeasures to reduce or eliminate
any noise emitted from these products.
Output ratings
Type: FRN□□□ LM1S-4□ 4.0 5.5 7.5 11 15 18.5 22 30 37 45
Rated voltage (V) 3-phase 380 to 480 V (Output voltage cannot be higher than input voltage)
Rated frequency (Hz) 50-60 Hz
Rated capacity at 440V (kVA) 6.8 10.2 14 18 24 29 34 45 57 69
Typical Motor capacity (kW) 4 5.5 7.5 11 15 18.5 22 30 37 45
*1
Rated current (A) 9 13.5 18.5 24.5 32 39 45 60 75 91
Overload current rating (A) 18 for 3 s 27 for 10 s 37 for 10 s 49 for 10 s 64 for 10 s 78 for 10 s 90 for 10 s 108 for 5 s 135 for 5 s 163 for 5 s
Overload capability (%) 200% for 3 s 200% for 10 s 180% for 5 s
Input values
Mains supply 3-phase 380 to 480 V; 50/60 Hz; Voltage: -15% to +10%; Frequency: -5% to +5%
1-phase 380 to 480V;
External control supply 1-phase 200 to 480 V; 50/60Hz
50/60 Hz
Input current with DC reactor (A) 7.5 10.6 14.4 21.1 28.8 35.5 42.2 57 68.5 83.2
Input current without DC reactor (A) 13 17.3 23.2 33 43.8 52.3 60.6 77.9 94.3 114
Required power supply capacity
5.2 7.4 10 15 20 25 30 40 48 58
(kVA)
Input values for battery operation
Battery operation voltage 48 VDC or higher
1-phase 380 to 480 V;
Auxiliary control power supply 1-phase 200 to 480 V; 50/60 Hz
50/60 Hz
Voltage/frequency variations Voltage: -15% to +10% (Voltage unbalance: 2% or less); Frequency: -5% to +5%
Braking resistor values
Maximum braking time (s) 60
Duty cycle (%ED) 50
Minimum resistor value ± 5% (Ω) 96 48 48 24 24 16 16 10 10 8
Options and Standards
DC reactor (DCRE) Optional
EMC – Filter Optional
Safety standards EN 61800-5-1, EN 61800-5-2 (SIL 2), EN ISO 13849-1 (Cat. 3, PL d) EN61800-5-1
Protection degree (IEC60529) IP20 IP00
Cooling Fan cooling
Mass (kg) 2.8 5.6 5.7 7.5 11.1 11.2 11.7 24.0 33.0 34.0
*1
For 10 kHz Switching frequency, 45 °C ambient temperature and 80%ED
Terminal block
cover
Front cover
"PULL" Mark
Figure 1: Removing the terminal block cover and the front cover
Front cover
Front cover
Hinge
Hole
Cover
fastening
Terminal Latch screw
block cover (terminal block
cover)
Terminal block
cover
Figure 2: Mounting the terminal block cover and the front cover
DC reactor 2 THR
PLC
1
EMC Filter R0
FRENIC-Lift
T0
2 Main contactors
L1 L1' L1 / R (L1/L) U
V 3ph.
L2 L2' L2 / S
400V
L3 L3' L3 / T (L2/N) W
Auxiliary supply for inverter control circuit. In case of FRN37LM1S-4 and FRN45LM1S-
R0, T0 4, those terminals supply also fans and MC contactor for charging circuit. In this case
380 V must be supplied. Only one terminal R0 and T0 must be supplied
Please connect the screen in both motor and inverter sides. Ensure that the screen is continued also
through the main contactors.
It is recommended to use a braking resistor with clixon and connect the fault signal to the controller and
also to the inverter, configuring a digital input with External alarm function. To do so, set the related
function (E01 to E08) to 9.
It is recommended the use of a thermal relay in the braking resistor circuit. This relay should be set up
that it only trips in the case that there is a short circuit in the braking transistor.
Filter L2/S
L3/T
This is only a schematic drawing. This is for information only and without responsibility.
The start of rescue operation, enable signal activation and main contactors control is handled by the lift
controller and is not in the range of the responsibility of the inverter.
P0
12
PA
11 Encoder
PB
Analog Inputs V2 12 to 15 VDC
PZ
C1
CM
11
PLC
Lift direction:
30B Relay output
Up FWD
for any alarm
Down REV
30C
CM
X1 to X3: Binary
X1
combination
inputs for speed
set points X2 Y5C
selection Brake control relay
(see Table below) Y5A
output
X3
Digital inputs and outputs and relay outputs can be configured for alternative functions.
The functions described in the schematic diagram are the factory settings of FRENIC-Lift
In case you want to use a different binary combination for a speed set point function it is possible by means of
changing binary speed coding functions (L11-L18).
a. Analog inputs
Using analog inputs the motor speed and the torque bias can be set without steps (stageless).
b. Digital Inputs
The digital inputs can operate using NPN or PNP logic. The selection of the logic is set using slide switch SW1
located on the control PCB. Factory setting is PNP (Source) Logic.
Connection example using PNP Logic:
FRENIC-Lift
Up
FWD
Speed 1
X1
Figure 6: Normal connection using free potential contacts of the lift controller.
FRENIC-Lift
+24 V
Up FWD
+24 V
Speed 1 X1
+24 V
CM
+ -
External power supply
d. Transistor outputs
Terminals Y1 to Y4 are configured from factory with the functions described in the table below. Other functions
can be set using functions E20 to E23.
Y1-Y4
Optocoupled outputs
or
Optocoupled inputs 24 V
CMY
Maximum connectable voltage is 27 VDC – inductive loads should not be connected directly (they should
be connected through a relay or optocoupler)
FRENIC-Lift has one RS485 port and one CAN port available for communication.
The RS485 port (through a RJ-45 connector) makes possible the connection of the FRENIC-Lift keypad, a PC or the
connection with a controller through DCP 3 communication. Only one communication is possible at the same time.
i. Keypad
The keypad can be remotely connected up to 20 m.
FRENIC-Lift
USB/RS485
Converter
EX9530
RJ45 1 2
USB
4 5
6. Hardware configuration
On the control board we can find 4 slide switches. With these switches different configurations can be set. From
factory (default) these switches are configured as follows.
It is not needed to set slide switch SW5 for standard encoders with supply voltages from 10
to 30 V.
By using the PTC input, the cut-off (stopping) function of the inverter does not fulfil EN81-1.
FRENIC-Lift control board includes the interface for the connection of an encoder for applications with induction
machines. The connection is done using screw terminals.
The output supply voltages 12 or 15 VDC are compatible with standard encoders HTL 10-30 VDC. Pulse
resolution from 360 to 6000 can be set using function L02.
Output signals
The signals from A phase and B phase are available as output signals on terminals PAO and PBO, to be used by
the lift controller.
The maximum connectable voltage is 27 VDC and the maximum allowed output current is 50 mA.
Supply voltage
The supply voltage of the encoders can be selected by setting the slide switch SW5 located in the inverter control
board. Factory setting is 12 V, which can be used for standard encoders with supply voltages from 10 to 30 VDC.
FRENIC-Lift
Term6
Built-in
HTL - Interface
Term1
PAO PBO PO CM PA PB PZ
Maximum 20 m cable length
The encoder cable must be always shielded. The shield must be connected in the inverter side and
the encoder side using the ground terminal or dedicated terminal.
7.2 Option card OPC-LM1-IL for induction motors (with or without gear)
Application:
For induction motors with or without gear
The feedback encoder of the motor is line driver TTL (differential signal + 5 VDC)
When the encoder signals are also connected (used by) the lift controller
FRENIC-Lift
OPC-LM1-IL
PO PO CM CM PA+ PA- PB+ PB- PZ+ PZ- PA+ PA- PB+ PB- PZ+ PZ-
Maximum cable length 20 m
Incremental
encoder
Application:
For permanent magnet synchronous motors (gearless)
For encoder Heidenhain type ECN1313 or ECN413 or ECN113 EnDat 2.1
FRENIC-Lift
OPC-LM1-PS1
PO PO CM CM CM PA+ PA- PB+ PB- CK+ CK- DT+ DT- CM FPA FPB
This option card is delivered in a separate box. An instruction manual is included in this box.
Prior to the commissioning the encoder resolution (pulses per revolution) has to be set always using
function L02.
For synchronous motors it is also necessary to set the encoder type in function L01.
Application:
For permanent magnet synchronous motors
For encoder Heidenhain type ERN1387 or ERN487 or compatible
FRENIC-Lift
OPC-LM1-PR
PO PO CM CM CM PA+ PA- PB+ PB- PC+ PC- PD+ PD- CM FPA FPB
This option card is delivered in a separate box. An instruction manual is included in this box.
Prior to the commissioning the encoder resolution (pulses per revolution) has to be set always using
function L02.
For synchronous motors it is also necessary to set the encoder type in function L01.
Also can be applied to induction motors (only PA and PB are used in this case, L01= 0)
Is not recommended to use this kind of encoders with pole motors > 24
8.1 Overview
To operate, commission and set up FRENIC-Lift inverter there are two possibilities: using inverter keypad TP-G1-ELS
or PC. For operation using a PC it is necessary to use the dedicated software Lift Loader. This software is free of
charge and can be downloaded from our website www.fujielectric-europe.com.
The keypad is connected to the inverter through the RJ-45 connector. This connection is also used for the connection
with the PC or the lift controller using DCP 3 protocol.
Use this key to move the cursor to the right in programming mode.
These 3 keys may not be used in lift application. In local mode with these keys the
motor can be started and/or stopped.
The complete menus list can be accessed by pressing PRG key. The LCD display shows the 4 first menus from the
complete list.
1. DATA SET
2. DATA CHECK
3. OPR MNTR
4. I/O CHECK
5. MAINTENANC
6. ALM INF
7. ALM CAUSE
8. DATA COPY
9. LOAD FCTR
Figure 16: Complete menus list
1. DATA SET
This is the important menu for commissioning. It displays the function codes list. Every function has a
number and name assigned. After selecting a function it can be checked and/or changed (edited) if
needed by pressing key.
2. DATA CHECK
Also using this menu functions codes can be changed. In this menu only function codes numbers are
shown (without the names) and the set values can be directly read. Changed function values from default
are indicated by a star on the right side of the parameter number. By pressing key the
selected function can be changed (edited).
00,00
Figure 17: DATA CHECK menu.
P01 4
Function changed P02* 11kW
and saved P03 20A
P04 0
In this menu different operating values can be shown in the LCD display. There are 4 different screens
showing 4 lines each, for example output frequency, output current, output voltage and calculated torque.
4. I/O CHECK
For checking, if FRENIC-Lift is receiving the correct control signals from the lift controller and the output
signals are issued correctly. Input and output signals are displayed in different screens.
5. MAINTENANC (MAINTENANCE)
Shows the inverter condition: runtime, main capacitors capacitance, firmware version.
In this menu the alarm memory is shown. After the selection of an alarm by pressing key the
most relevant information of this alarm is shown.
In this menu the possible alarm causes are shown. After the selection of an alarm by pressing
key a possible causes of this alarm is shown.
8. DATA COPY
With this menu complete inverter function set up can be transferred from one inverter to another. This
may be helpful to set up different installations with the same motor and same characteristics. Be aware
that function protection (F00) is no copied. Motor data and communication set are copied only between
inverters of same range.
In this menu the maximum current, the average current and the average braking torque during a preset
measuring time can be measured in the real application.
Figure 19: LCD display of the first 4 menus after Figure 20: Menu selection (in this figure
pressing key maintenance menu is selected)
00,00 00,00
1. DATA SET 2. DATA CHECK
2. DATA CHECK 3. OPR MNTR
3. OPR MNTR 4. I/O CHECK
4. I/O CHECK 5. MAINTENANC
Figure 21: Selection of Menu 1 Figure 22: Function code selection. In this figure
P03 Rated current from the P Group (Motor
functions)
00,00
00,00
1.DATA SET
2.DATA CHECK P01 M-POLES
3.OPR MNTR P02 M-CAP
4.I/O CHECK P03 M-Ir
P04 M-TUN
Figure 23: To edit (go inside) the function Figure 24: Changing the value of P03 (motor rated
current), in this example to 12.
00,00
00,00
P03 M-Ir
12 A Actual value P03 M-Ir
0.00~500.00 12 A
0.00~500.00
Setting range
After changing the value using the arrow keys, it can be saved by pressing key.
High speed
Creep speed
Stop speed
t1
Direction inputs
FWD or REV
Speed selection
inputs
Input X1
Input X2
Input X3
t2 t3
Mechanical brake
status
t t
Main contactors t t4
Sequence description
Start:
By activating FWD (UP) or REV (DOWN) terminal and EN1 and EN2 (enable) terminals, t1 and t2 times start
to run. During that time, terminals X1 to X3 (speed selection) can be activated.
After the completion of time t2 the output of brake control will be activated and the mechanical brake opens
(releases) after some time (delay time to the reaction of contactors, coil…). After completion of time t1, the
speed set point will be used and the lift will start to move accelerating to reach high speed (normal case).
Stop:
The terminal X3 will be deactivated by the lift controller (from the internal settings of the controller).
After finishing the deceleration the lift will reach creep speed (set point activated by inputs X1 and X2).
After reaching the floor level, also creep speed will be deactivated. After the deceleration the cabin will reach
zero speed. In this moment t3 begins to run. After time t3, the brake output is deactivated (and brake will be
applied).
To control the main contactors the transistor output Y1 can also be used. With this it is ensured that the
main contactors are opened always after the brake is closed.
Intermediate speed
Creep speed
Terminal X1
Intermediate speed 1
(Case 1) Terminal X2
Terminal X1
Intermediate speed 2 Terminal X2
(Case 2)
Terminal X3
Terminal X1
Intermediate speed 3 Terminal X2
(Case 3)
Terminal X3
Terminal X1
Intermediate speed 4 Terminal X2
(Case 4)
Terminal X3
11. Settings
11.1 Introduction
The set up of the inverter depending on the application is done using several inverter functions. Especially the motor
and speed profile related functions have to be adjusted depending on the application. All these functions must be set
up according to known motor and installation data before the first travel. The optimization of the travel is done after
that and after the complete assembly of the lift installation.
The first travel for checking if the motor control is good, SHOULD BE ALWAYS done by controlling the lift
from outside the cabin (typically RESCUE operation).
1. Ensure that the encoder is connected properly and that the encoder used is suitable for the motor used
(check also the chapters for Encoder and Connections). The screen of the encoder cable must be
connected to earth in BOTH, motor and inverter side.
2. Ensure that the motor cables are connected to U,V,W terminals and that the screen of the motor cable
must be connected to earth in BOTH, motor and inverter side.
3. Ensure that the protective earth of the installation is connected to the inverter and motor.
4. Ensure that the braking resistor is connected properly to the inverter and protective earth.
5. Ensure that the control signals FWD or REV; X2 and EN1 and EN2 become active by using rescue
operation (controlling the lift from outside the cabin). Ensure that the output signals for brake control on
terminal Y5C and –if main contactors are controlled by the inverter- the signal on terminal Y1 becomes
active. The status of the signals can be checked using the LCD display; for more information please
check the chapter related to Keypad operation.
6. Function settings (see following pages for induction motors and permanent magnet synchronous motors)
7. Perform auto tuning for induction motors or pole tuning for permanent magnet synchronous motors.
8. Optimization of the travel.
For induction motors auto tuning has to be performed before the first travel. The brake stays applied. To do so, the
parameters described in the table below must be set.
To perform the described procedure the enable (EN1&EN2) inputs must be active.
After that, please give RUN command from the lift controller (for example in INSPECTION), and check that motor is
turning without any problem. In negative case (for example inverter trips OC, OS or Ere) please exchange motor
phases connection to change rotation direction (for example U phase by V phase).
For permanent magnet synchronous motors pole tuning has to be performed before the first travel. The brake stays
applied. To do so, the parameters described in the table below must be set.
To perform the described procedure the enable (EN1&EN2) inputs must be active.
11.4 Specific settings for induction motors in open loop (geared motors without encoder)
For induction motors auto tuning has to be performed before the first travel. The brake stays applied. To do so, the
parameters described in the table below must be set.
To perform the described procedure the enable (EN1&EN2) inputs must be active.
The no-load current (function P06) defines the value of the current of the motor when no load is applied to the motor
(exciting current).
Typical values of the no-load current range from 30 % of P03 up to 70 % of P03. In the majority of the cases the
value calculated by the auto-tuning procedure will be correct (when P04=3). In some cases the auto-tuning procedure
cannot be finished correctly (due to special behaviour of the motor). In this later case the value of P03 must be set
2
manually. For calculate no-load current you can use the formula P06 P032 P02 *1000
1.47 * F05
Too low values in P03 will make that the motor does not have enough torque. Too high values will make that the
motor oscillates (this oscillation will cause a vibration in the motor that is transmitted to the cabin).
The slip frequency function defines the value of the slip frequency of the motor. Is the key function for a good slip
compensation by the inverter; this means that this function is very important in open loop control of induction motors
for a good landing accuracy because it will ensure that the rotating frequency of the motor is the same regardless of
the load condition of the motor.
In the majority of the cases the value measured by the auto-tuning procedure will be correct. In some cases the auto-
tuning procedure cannot be finished correctly (due to special behaviour of the motor). In this later case the value of
P12 must be set manually.
To set function P12 manually we can calculate it from the following formula:
speed
1 2 3 4 5 6 7 8 9 10 11
time
Speed profile sections 1 to 11
Table 22: Correspondence of functions for each phase of the sequence according with figures 22, 23 & 24.
Speed profile
Normal travel Case 1 Case 2 Case 3 Case 4 Case 5 Case 6
phase Meaning
(fig. 22) (fig. 23) (fig. 23) (fig. 23) (fig. 23) (fig. 23) (fig. 23)
(fig. 24)
st
1 S curve
1 L19 L19 L19 L19 L19 L19 L19
acceleration
Linear
2 E12 E10 F07 F07 E10 F07 E10
acceleration
nd
3 2 S curve acc. L24 L22 L20 L20 L22 L20 L22
4 Constant speed C11 C05 C08 C09 C10 C09 C10
st
1 S curve
5 L25 L23 L21 L21 L23 H57 H59
deceleration
6 Linear dec. E13 E11 F08 F08 E11 F08 F08
nd
7 2 S curve dec. L26 L26 L26 L26 L26 H58 H60
8 Creep speed C07 C07 C07 C07 C07 C05 C08
st
1 S curve
9 L28 L28 L28 L28 L28 L23 L21
deceleration
10 Linear dec. E14 E14 E14 E14 E14 E11 F08
11 2nd S curve dec. L28 L28 L28 L28 L28 L28 L28
Intermediate speeds are seldom used in standard lifts. These speeds will be used with high speed
lifts or between short floors
For creepless operation (direct to floor) phases 7, 8, 9 and 10 do not appear. The setting of the S
curve at stopping from creep speed to zero speed is set by function L28.
For other combinations, please see table below
Table 23: Correspondence of acceleration and deceleration ramps and S-curves.
ACCELERATION & DECELERATION RAMPS (S-CURVES)
AFTER CHANGE
STOP C04 C05 C06 C07 C08 C09 C10 C11
BEFORE CHANGE
-/F08
(- / -) F07 F07 F07 F07 F07 F07 F07 F07
STOP (H57 / H58) (H57 / H58) (- / -) (H57 / H58) (H57 / H58) (H57 / H58) (H57 / H58) (H57 / H58)
E16 F07 / F08 E10 F07 F07/ F08 F07 F07 E10 E12
C04 (H59 / H60) (- / -) (L19 / L22) (- / -) (H57 / H58) (L19 / L20) (L19 / L20) (L19 / L22) (L19 / L24)
E16 E11 F07 / F08 F07 / F08 E11 F07 / F08 F07 / F08 F07 / F08 F07/ F08
C05 (H59 / H60) (L23 / L28) (- / -) (- / -) (L23 / L26) (H59 / H60) (H59 / H60) (H57 / H58) (H57 / H58)
E16 F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08
C06 (- / -) (- / -) (- / -) (- / -) (- / -) (- / -) (- / -) (- / -) (- / -)
E15 E14 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08
C07 (L27) (L28) (H57 / H58) (- / -) (- / -) (H57 / H58) (H57 / H58) (H57 / H58) (H57 / H58)
E16 F08 F07 / F08 F07 / F08 F08 F07 / F08 F07 / F08 F07 / F08 F07 / F08
C08 (H59 / H60) (L21 / L28) (H57 / H58) (- / -) (L21 / L26) (- / -) (H57 / H58) (H57 / H58) (H57 / H58)
E16 F08 F07 / F08 F07 / F08 F08 F07/ F08 F07 / F08 F07 / F08 F07 / F08
C09 (H59 / H60) (L21 / L28) (H57 / H58) (- / -) (L21 / L26) (H59 / H60) (- / -) (H57 / H58) (H57 / H58)
E16 E11 F07 / F08 F07 / F08 E11 F07 / F08 E11 F07 / F08 F07 / F08
C10 (H59 / H60) (L23 / L28) (H59 / H60) (- / -) (L23 / L26) (H59 / H60) (L23 / L26) (- / -) (H57 / H58)
E16 E13 F07 / F08 F07 / F08 E13 F07 / F08 E13 F07 / F08 F07 / F08
C11 (H59 / H60) (L25 / L28) (H59 / H60) (- / -) (L25 / L26) (H59 / H60) (L25 / L26) (H59 / H60) (- / -)
In order to know which ramps and S-curves are used we have to enter in Table 12 from the left hand column in the
row of the speed that is settled before the change (ex. C08) and look up in the column pointing at the target speed
after the change (ex. C09). In the intersection of the row and the column we can find the ramps (ex. F07 / F08) and
the S-curves (in brackets, ex. H57/H58) used during the change. In the example the change uses F07 as acceleration
ramp or F08 in case of deceleration; for the S-curves H57 is used at the beginning of the speed change (close to
C08) and H58 is used at the end of the change (when the speed has reached C09).
Table 24: Guideline of acceleration, deceleration times and deceleration distances for different travelling speeds
Acc./Dec. S curve settings Acc./Dec.
Rated speed Creep speed
Times settings Times settings Deceleration
Functions distance
Function C11 Function C07
Function E13 L24,L25,L26 Function E14
0.6 m/s 0.05 m/s 1.6 s 25% 1.6 s 892 mm
0.8 m/s 0.10 m/s 1.7 s 25% 1.7 s 1193 mm
1.0 m/s 0.10 m/s 1.8 s 25% 1.0 s 1508 mm
1.2 m/s 0.10 m/s 2.0 s 25% 1.0 s 1962 mm
1.6 m/s 0.10 m/s 2.2 s 30% 1.0 s 2995 mm
2.0 m/s 0.15 m/s 2.4 s 30% 0.8 s 4109 mm
2.5 m/s 0.20 m/s 2.6 s 30% 0.7 s 5649 mm
The deceleration distance and therefore the starting point of the deceleration phase depends on the
function settings. The deceleration distance shown in the above table is the distance from the start of
the deceleration to the final floor landing position. The time during creep speed has been estimated for 1
s. This time depends on the real application.
Speed
E13: Acc./Dec.
time 6
E12: Acc./Dec.
time 5
L28: S-Curve 10
Creep speed C07
L26: S-Curve 8
Stop speed. F25 L28: S-Curve 10
Zero speed C04 L19: S-Curve 1
Time
E14: Acc./Dec. time 7
FWD ON
X1 (SS1) ON
X2 (SS2) ON
X3 (SS4) ON
SW52-2
Main
contactors ON
control
BRKS ON
Brake
control
L85 L83
L82 H67
F24 L56
L86
Factory setting of the speed units is rpm (defined by function C21). To set up all functions correctly
the rated speed of the motor must be known. If this speed is NOT known it can be calculated from the
formula below:
19,1 v r Where
nrated v: rated speed in m/s
Di r: Cabin suspension (1 for 1:1, 2 for 2:1, 4 for 4:1,…)
D: Pulley diameter in m
I : Gear ratio
Factory
Function Explanation Setting
setting
Speed loop controller P gain (ASR P) for high speeds.
Depends on the
L36 10.00 High values can lead to instability or noise in the motor for speeds
installation
higher than the value set in function L41.
Speed loop controller Integral time (ASR I) for high speeds. This
value normally does not need to be changed. Too high values can Depends on the
L37 0.100 s
cause over/undershoot at the end of acceleration and deceleration installation
phases from speeds higher than the value set in function L41.
Speed loop controller P gain (ASR P) for low speeds.
Depends on the
L38 10.00 Same effect as L36, effective for speeds under the value set in
installation
function L40.
Speed loop controller Integral time (ASR I) for low speeds.
Depends on the
L39 0.100 s Same effect as L37, effective for speeds under the value set in
installation
function L40.
Changing point of P and I values for small speeds. Under this speed Depends on the
L40 150 r/min
the values in functions L38 and L39 are effective. installation
Changing point of P and I values for high speeds. Over this speed the Depends on the
L41 300 r/min
values in functions L36 and L37 are effective. installation
Time for decreasing the current inside the motor at the stopping. This
Depends on the
L56 0.2 s time must be increased in case the demagnetization process in a
installation
synchronous motor makes noise.
Delay time for opening (releasing) the brake after operation command
Depends on the
L82 0.2 s (FWD or REV) has been activated. This time should be bigger than
installation
the time required for the motor current to settle.
Delay time for closing (applying) the brake after the speed is under
stop speed (F25). It is very important that EN1&EN2 (enable) signals Depends on the
L83 0.1 s
are deactivated and the main contactors are opened after the brake is installation
closed.
Delay time from closing the main contactors until the inverter starts Depends on the
L85 0.1s
giving current (voltage) at the output installation
Delay time from stopping giving current at the output until the inverter Depends on the
L86 0.1s
opens the main contactors installation
For most applications the factory default settings are enough for good comfort and low noise.
Speed
Time
F24 or H64
L66
ULC ASR at low speed Linear ASR at high speed Linear ASR at low speed
ASR PI (L68,L69) ASR PI (L38,L39) change ASR PI (L36,L37) change ASR PI (L38,L39)
APR PD (L73,L74) ACR P (L05) for ASR ACR P (L05) for ASR ACR P (L05)
ACR P (L76)
Figure 29. Time diagram with Unbalanced Load Compensation (ULC) active (L65 = 1).
Factory
Function Explanation Setting
setting
0: r/min
C21 0 r/min 1: m/min r/min
2: Hz
1500 r/min Y3 Output will become active, when the speed reaches the value set If used in the
E31
60 r/min in this function installation
15 Hysteresis under speed E31. When the actual speed is under (E31- If used in the
E32
0.6 E32) value the output Y3 will be deactivated. installation
0 Induction motor control with encoder (closed loop)
1 Permanent magnet synchronous motor control Depends on
F42
Induction motor control without encoder (open loop) the installation
2
(for 37 and 45kW Dynamic torque vector control is not available)
Value from 1
H04 0 This function sets the number of attempts of alarm Auto Reset.
to 10
Time between
H05 5s Delay time for executing alarm Auto Reset
0,5s and 20 s
Depends on
H98 81 Protection and maintenance function (Bitwise function, see table 18)
the installation
L07 0 Automatic pole tuning after first RUN command (after power ON) 1,3 or 4
1: Brake control by time (Standard setting)
L80 1 1
2: Brake control by output current
Depends on
L29 0.00 Hold time for short floor operation
the installation
Rated speed
L30 0.00 Speed limit for the classical short floor operation (time-speed control).
-10 %
When the main contactors are controlled by the inverter, this function
L86 0.1 s is the delay time for opening the main contactors after the inverter 0.1 s
stops giving current at the output
450 r/min If used in the
L87 Speed limit for anticipated door opening
18 r/min installation
Factory
Function Explanation Setting
setting
E01 0 X1-X8 digital inputs function: 0
0: bit 0 of binary code for speed selection inputs (SS1)
E02 1 1
1: bit 1 of binary code for speed selection inputs (SS2)
E03 2 2: bit 2 of binary code for speed selection inputs (SS4) 2
8: External reset for alarm messages (RST)
E04 8 9: Enable external alarm trip (THR) 8
10: Enable jogging operation (JOG)
E05 60 63: Battery operation enable (low voltage cancellation) (BATRY) --
E06 61 64: Start creepless operation (CRPLS) --
65: Check brake control (BRKE)
E07 62 69: Start magnetic pole position offset tuning (PPT) --
103: MC confirmation (CS-MC)
E08 63 63
E20 12 Y1-Y4 transistor output function: 12
E21 78 0: Inverter running (RUN) 78
E22 2 2: Speed detected (FDT) 2
12: Main contactors control mode 1(SW52-2)
57: Brake control (BRKS)
78: Door open (DOPEN)
99: Alarm output for any alarm (ALM)
107: During magnetic pole position offset tuning (DTUNE)
E23 57 109: Recommended running direction (RRD) 57
112: Input power limitation (IPL)
114: Main contactors control mode 2 (SW52-3)
115: Pole tuning done signal (PTD)
116: Detected speed direction signal (DSD)
E24 57 Y5A/C and 30A/B/C relay output function: 57
0: Inverter running (RUN)
2: Speed detected (FDT)
12: Main contactors control mode 1(SW52-2)
78: Door open (DOPEN)
99: Alarm output for any alarm (ALM)
E27 99 107: During magnetic pole position offset tuning (DTUNE) 99
109: Recommended running direction (RRD)
112: Input power limitation (IPL)
114: Main contactors control mode 2 (SW52-3)
115: Pole tuning done signal (PTD)
116: Detected speed direction signal (DSD)
If the distance between the two floors is shorter than the distance needed for acceleration and deceleration to/from
high speed FRENIC-Lift is able to perform the so called short floor operation. There are two alternatives of short floor
operation.
With this alternative the control is done by frequency and time. If the actual frequency is smaller than L30
value then the actual frequency (after interrupting the acceleration and reaching constant speed) will be held
for the time set in function L29.
Speed
L24: S-Curve 6
High speed
L30: Short floor
maximum speed L24: S-Curve 6
E13: Acc./Dec.
time 6
E12: Acc./Dec.
time 5 L25: S-curve 7
L26: S-Curve 8
Creep speed L28: S-Curve
10
Zero speed time
L19: S-Curve 1
L28: S-Curve 10
FWD ON
SS1 ON
SS2 ON
SS4 ON ON
With this alternative the inverter keeps the deceleration distance (from high speed to creep speed) regardless
of the actual speed and acceleration. The needed S-curves are calculated to fulfil this condition.
Speed
FWD ON
SS1 ON
SS2 ON
SS4 ON ON
Speed
S-Curve will be calculated from
Sdec
Creep speed
Sdec L28: S-Curve 10
Zero speed Time
L19: S-Curve 1
FWD ON
SS1 ON
SS2 ON
SS4 ON
This function is only available when accelerating from C04 to C09, C10 or C11, The inverter is
forced to decelerate to C07.
Functions L31 (linearization factor from linear to rotational speed) and L34 (travelling distance for creepless
operation) MUST be calculated and set before using creepless operation.
Creepless operation starts when all speed selection signals are removed during deceleration from High speed to
Creep speed (after removing the signals for High speed and before reaching Creep speed). For better landing
performance it is needed to set up properly functions L36 to L42 (ASR gains).
Speed
L24: S-Curve 6 L25: S-Curve 7
Theoretical start point od
High speed Creepless operatiion
(Calculated from remaining distance)
L28: S-Curve 10
Stop speed L19: S-Curve 1
Time
Zero speed Rated speed
active active
FWD ON
SS1 ON
SS2 ON
SS4 ON
Brake Open
Creepless
Figure 32. Creepless operation.
To recover the lift from speed limiter condition (cabin or counterweight are blocked), use inspection speed
(C06). The reason is that S curve is not effective (only linear acceleration/deceleration) when inspection
speed is used.
If the jerk is not enough to recover the lift, decrease the value of function F07 to increase the jerk against the speed
limiter condition.
To activate the rescue (battery operation) the signal BATRY must be activated (by default programmed to input X8).
The controller has to activate EN1 and EN2 (enable), FWD or REV (direction) and binary speed coding function L12
(speed) signals -like in normal operation- and the motor will start to move at C03 (battery speed). The ramps in that
case are E17 and S curves are disabled. If binary speed coding function selected is other than L12 the speed, ramps
and S-curves will be the specified in the standard table.
The torque in closed loop and gearless applications (for driving mode only) can be limited to avoid an overload during
battery operation. The torque limit level can be set in function C01. The time that the limiting value becomes effective
can be set in function C02. In order to make C01 effective during all travel, the setting value of C02 must be 0.0 s.
Digital outputs [Y1] to [Y4], [Y5A/C] and [30A/B/C] of the inverter can be programmed to RRD (Recommended
Running Direction) function (signal). This signal gives the recommended direction of travelling (motion) for rescue
operation.
Table 25. Function RRD setting
Set up value for E20 to E24
or E27
Assigned Function Symbol
Positive Inverse
Logic Logic
109 1109 Recommended running direction RRD
RRD signal informs the direction of regenerative operation. This signal is saved in case of mains loss until the next
travel.
In the case of open loop control, if the reference speed is smaller than 5% of the base speed, RRD is not judged.
Function E39 is the RRD detection level. Please use this function only for geared motors. Setting range: 0 to 100%
Setting procedure
1. Please confirm the reference torque during the nominal speed of the lift with balanced load condition.
2. Write down the value of the reference torque during up and down.
3. Please compare both values, and set the larger value to function E39.
In case of open loop control (F42=2) and rescue operation with batteries, use brake control
by output current (L80=2), otherwise brake could open anyway when batteries are
discharged.
The inverters keeps zero speed (C04) during the time set in function H64, after main contactors are closed. The
factory setting of H64 is 0.00 (not active) and the setting range is from 0.00 to 10.00 s. After this time, the motor starts
to turn at speed F23 during F24 time (using acceleration H65). This function may be used to obtain a soft start in lift
installations with high friction.
Speed
EN ON
FWD ON
SS1 ON
SS2 ON
SS4 ON
SW52-2
Main ON
contactors
control
BRKS ON
Brake
control
L85 L83
L82 H67
H64 L56
H65
L86
F24
Delay time after closing main contactors (L85) to start giving current to the motor
Delay time for releasing (opening) the brake (L82)
Hold time for zero speed (H64)
Time (H65) for soft start of start speed (F23)
Hold time for start speed (F24)
In case of using this function, rollback compensation (ULC) will be active as soon as H64 starts (and
L65=1).
Alarm
message Description Possible causes
Displayed
a) Check if the motor used in the
application has been selected properly
Motor overloaded:
b) Check if the inverter used in the
OC1= Overload during acceleration
O0c OC2= Overload during deceleration
application has been selected properly
c) Check if brake opens
OC3= Overload during constant speed
d) Has the pole tuning procedure been
completed successfully?
a) Braking resistor not connected or
Overvoltage in inverter DC link: defective
OU1= Overvoltage during acceleration b) Counterweight not counterbalanced
0u OU2= Overvoltage during deceleration c) Deceleration time too short
OU3= Overvoltage during constant speed d) Check connection
e) Check mains connection
a) Supply voltage too low
b) Mains supply failure
lu Undervoltage in inverter DC link c) Acceleration too fast
d) Load too high
e) Check connection of the input signal
a) Check inverters input protections
lin Input phase loss
b) Check input connections
a) Misconnection on inverters side
0pl Output phase loss b) Misconnection on motors side
c) Misconnection on main contactors
a) Inverter fan defective
0h1 Inverter heat sink temperature too high
b) Ambient temperature too high
Digital input programmed with value 9 (THR)
0h2 External Alarm
is not active.
Ambient temperature around inverter too
0h3 high
Check temperature inside electrical cabinet
a) Motor fan too small
Motor over temperature detected from
0h4 temperature sensor (PTC). See H26
b) Ambient temperature too high
c) Check setting of H26,H27
a) Check encoder cable
pg Encoder error b) Motor is blocked
c) Brake did not open
a) Check brake
b) Motor, car or counterweight blocked
0l1 Motor overload c) Inverter at current limit, possibly too
small
d) Check functions F10~F12
a) Over temperature in IGBT
b) Failure in the cooling system
0lu Inverter overload c) Switching frequency (function F26) too
high
d) Cabin load too high
er1 Save error Data has been lost
Keypad was removed while inverter in
er2 Keypad communication error
operation (RUN)
er3 CPU error Failure in the inverter CPU
A communication error occurred between the
option card and the inverter.
er4 Option card communication error
a) Check option card installation
b) Check cables and shield connection
A communication error occurred between the
option card and the encoder.
er5 Option card error
a) Check encoder
b) Check cables and shield connection
Alarm
message Description Possible causes
Displayed
a) Check function L11-L18: One/many
binary combinations are repeated
b) Check brake signal status if BRKE
function is used
c) Check MC signal status if CS-MC
function is used
er6 Operation error
d) Check function L84
e) Check function L80,L82,L83
f) If F42=1 and L04=0.00. Pole tuning not
done
g) EN81-1+A3 function is active but
another related function is missed
a) Connection between inverter and motor
interrupted during auto tuning procedure
(main contactors open?)
er7 Error during Auto Tuning / Pole tuning
b) Enable input interrupted
c) Check encoder cable
d) Check encoder
a) Cable is interrupted
er8 RS 485 Communications error
b) High noise level
a) Check brake
b) Motor, car or counterweight blocked
c) Check functions L90~L92
ere Speed error (disagreement)
d) Current limiter active
e) Has been completed successfully the
pole tuning procedure?
a) Option
b) Option card not correctly installed
erh Option card hardware error
c) Inverter software version not compatible
with option card
a) CAN bus disconnected from the inverter
ert CAN bus communication error
b) Electrical noise, connect cable shield
The inverter detects an error on the enable
ecf EN1 and EN2 terminals circuit error terminals circuit, and stops itself. Contact
with Fuji Electric.
a) Check encoder resolution setting in
L32xF 03 function L02
0s Motor speed greater than (rpm) b) Check value of function F03
100 c) Check value of function P01
d) Check value of function L32
Fault in the charging circuit of 37 and 45 kW
inverters.
pbf Charging circuit fault
Check power supply in R0/T0 terminals.
Contact with Fuji Electric.
Brake state differs from expected.
Brake status monitoring according to EN81-
bbe 1+A3
For additional information, please contact
Fuji Electric.
UK Branch
Fuji Electric Europe GmbH
Tel.: +44 (0) 7989 090 783
info.uk@fujielectric-europe.com
www.fujielectric-europe.com