4007ES and 4007ES Hybrid Fire Alarm Systems: Programmer's Manual 579-1167 Rev. D
4007ES and 4007ES Hybrid Fire Alarm Systems: Programmer's Manual 579-1167 Rev. D
4007ES and 4007ES Hybrid Fire Alarm Systems: Programmer's Manual 579-1167 Rev. D
Programmer’s
Manual
579-1167
Rev. D
Copyright, Trademarks, Cautions, Warnings, and Regulatory Info
Cautions READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions
and must be followed to avoid damage to this product and associated equipment. Product operation and reliability
Warnings depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex
product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All
repairs should be performed by a representative or authorized agent of your local Simplex product supplier.
EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may
exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when
viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to comply with the limits for a Class A
digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be
tested in accordance with NFPA-72, after any programming operation or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
IMPORTANT: Verify FACP System Programmer, Executive, and Slave Software compatibility
when installing, or replacing system components. Refer to the Technical Support
Information and Downloads website for compatibility information.
i
Table of Content
Chapter 1 Getting Started ...................................................................... 1-1
Introduction .................................................................................................1-1
Requirements and Compatibility .................................................................1-1
Downloading the Software ..........................................................................1-1
Installing the Software .................................................................................1-2
Starting the Programmer .............................................................................1-2
iii
Table of Content
Adding the Additional IDNet Loops .............................................................5-3
Removing Hardware ...................................................................................5-3
Editing Properties ........................................................................................5-3
Annunciator Numbers .................................................................................5-4
Annunciator Number Sharing Rules ............................................................5-4
Editing Basic Card Properties .....................................................................5-5
iv
Table of Content
Chapter 8 Viewing, Adding, and Editing Lists ..................................... 8-1
Introduction .................................................................................................8-1
List Tab .......................................................................................................8-2
Sort Function ...............................................................................................8-2
Custom Label Spell Check ..........................................................................8-2
Managing Points .........................................................................................8-3
Turning Autogen Off and On from the General List Tab .............................8-3
Basic Operations .........................................................................................8-4
Adding a User-Defined List .........................................................................8-4
Editing an Existing User-Defined List ..........................................................8-4
Latching Supv Verification ...........................................................................8-5
WalkTest™ ..................................................................................................8-6
Elevator Recall List .....................................................................................8-9
Zone Lists ..................................................................................................8-10
v
Table of Content
Step 1. Defining Hazard Area ...................................................................9-27
Step 2. Specifying Initial Data and Options ...............................................9-28
Step 3. Specifying Abort Switch Operation ...............................................9-29
Step 4. Setting Timer Options ...................................................................9-30
Step 5. Specifying Hazard Area Points .....................................................9-31
Deleting Hazard Area ................................................................................9-34
Editing Existing Hazard Area ....................................................................9-34
Scheduling Options for Self-Test Wizard ..................................................9-35
Step 1. Creating a New Self-Test ..............................................................9-35
Step 2. Selecting Start Time and Frequency of the Self-Test ...................9-36
Step 3. Selecting Self-Test Triggering Point and Point List ......................9-37
.
Chapter 10 File Transfer ...................................................................... 10-1
Introduction ...............................................................................................10-1
USB File Transfer ..........................................................................................10-2
USB File Transfer ......................................................................................10-2
Files Transferred .......................................................................................10-3
IP File Transfer ...............................................................................................10-4
IP File Transfer ..........................................................................................10-4
File Transfer Connection to the PC ...........................................................10-4
Starting the IP File Transfer Utility ............................................................10-4
IP Communication Parameter Settings .....................................................10-5
Downloadable Files ...................................................................................10-5
Download Tab ...........................................................................................10-6
Upload/Reports Tab ..................................................................................10-8
Type of Transfer ........................................................................................10-9
vi
Table of Content
Chapter 13 Adding or Editing Network Information ......................... 13-1
Introduction ...............................................................................................13-1
Role of the Network Programmer ..............................................................13-1
Public Versus External Points ...................................................................13-1
General Network Programming Guidelines ...............................................13-1
4007ES Programmer Network tab ............................................................13-2
Gaining Access to the Network Information ..............................................13-3
Editing the Network Name and Node Number ..........................................13-4
Procedure to Declare Public Points ..........................................................13-5
Procedure to Declare External Points .......................................................13-5
Programming Network Alarm Silence .......................................................13-6
Programming Central Network Silence .....................................................13-7
Programming Distributed Network Silence ...............................................13-8
Programming Central Network Reset .......................................................13-9
Programming Distributed Network Reset ................................................13-10
Distributed Configuration .........................................................................13-11
vii
Chapter 1.
Getting Started
Introduction The 4007ES Panel Programmer is a software program designed to create “jobs” that are used
to configure and program the 4007ES and 4007ES Hybrid Fire Alarm Control Panel (FACP).
The 4007ES Panel Programmer must be installed on a computer that can be either physically
or remotely connected to the panel.
In this chapter Requirements and Compatibility .....1-1 Installing the Software .....................1-2
Downloading the Software ..............1-1 Starting the Programmer ..................1-2
Programmer Requirements:
To install and open the Programmer, the user must have the following:
• Internet access in order to download the software.
1-1
4007ES Panel Programmer Manual (579-1167)
Getting Started
1-2
Chapter 2.
User Interface
Introduction The user interface has menus, icons, tabs, sub-tabs, and a status bar that help the user navigate
through the programmer and create jobs.
The following sections detail the user interface and the options associated with each item.
Menus
Toolbar
Icons
Tabs
Sub-Tabs
Status Bar
Figure 2-1. 4007ES Programmer Interface
Menus The menus are located at the top of the ES Panel Programmer:
Consult the following tables for the description of the menu items.
Table 2-1. File Menu
Close Closes the current job. Restore Restores the previous saved version of
the job.
Save Saves the current job. Export Allows the user to:
• Export data to service sales tools
Save as Allows you to copy or rename the • Export user points to text file
current job. • Export XLG point data
Reports Generates a digital job report. Import Allow the importation of user points
from another file.
View report Brings up the latest report. DB Compare Compares the job to previous revisions
of itself.
Print set up Configures the hard copy print Current Job The name of the current job.
specifications.
Print Label Prints labels for the FACP cards. Exit Exits the current job.
2-1
4007ES Panel Programmer Manual (579-1167)
User Interface
Paste Inserts the previously cut or copied material into the selected area.
Revision History Allows the user to enter notes about the changes made for each revision.
*Tab List* Click on the option to open the corresponding tab. The choices are:
• Panel: Allows the user to access the following sub-tabs: General Info, System
Options, Access Levels, Passcode Assignments, and Feature.
• Hardware: Allows the user to add and remove components and configure their
properties.
• Point: Allows the user to edit TrueAlert devices.
• List: Allows the user to access the following sub-tabs: General List, Latching Supv
Verification, Alarm Verification, WalkTest, and Elevator Recall.
• Custom Control: Allows the components of the ES Panel FACP to be controlled
with user-definable custom control equations.
• TrueAlert Zone: Allows the user to view the points in each TrueAlert zone.
• Port Vectoring: Allows the user to program cards to output only specific groups of
events.
• AMON Pt Type: Allows the user to create custom point types.
• Zone Lists: Allows the user to view the lists sorted by zone.
Checklist Displays a mandatory and an optional checklist that lets the user know which steps
have been completed in the programming process.
Toolbar Click in the checkbox to make the tool bar icons visible.
Status Bar Click in the checkbox to make the status bar visible.
Notes Click to open a note pad where the user can type in notes about the job.
View Build Log Click to view the log of previous builds for this job.
2-2
4007ES Panel Programmer Manual (579-1167)
USB Transfer the job data from the computer to the USB key.
Serial Enable a serial connection between the FACP and the Perle Box. This option cannot be
used for panel serial downloads.
Network Enable a network connection between the computer and the panel.
About Programmer Click to access basic information, copyright of the programmer software, and the
revision of the programmer being used.
2-3
4007ES Panel Programmer Manual (579-1167)
Toolbar Icons The toolbar icons are shortcuts to popular programmer commands. Table 2-9 explains each
icon and the command it is attached to.
Table 2-9. Icons and Commands
Cut Click to cut the selected information from its current location.
About Click to access basic information and copyright of the programmer software.
2-4
4007ES Panel Programmer Manual (579-1167)
Tabs and Sub- Each tab represents a specific component or feature of the job that must be configured. The
Tabs tabs are placed in sequential order and should be completed in that order. Certain tabs are made
up of multiple sub-tabs that are found at the bottom of the page. All sub-tabs must be opened
and configured to complete the job.
Table 2-10. Tab list
AMON Point Type -NA- View the analog monitor (AMON) points.
Network • Network Information Add and edit the lists of public and external points.
• Network Points
Status bar The Status bar is found at the bottom of the Programmer window and indicates the:
• Programmer status
• Time
2-5
Chapter 3.
Working with Jobs
Introduction A job is a file that contains specific programming and configuration information for the FACP.
This chapter explains the basics surrounding creating and saving jobs, however, it is important
to consult the following chapter in this document, Panel Information and Configuration, for
crucial information on how to configure and program the job.
Creating Jobs When the programmer is opened on a computer for the first time, a prompt window appears
automatically requesting that the user create a job. If a job has been previously saved on the
programmer it automatically opens when the programmer is started.
To create a new job:
1. Start the ES Panel Programmer:
• If this is the first job saved for the FACP, the New Job window opens automatically.
• If a previous job opens, click on the New icon or select New from the File menu to
open the New Job window.
2. In the New Job window, select the job type:
- 4007 - for the addressable panel
- 4007H - for the Hybrid panel.
3. Enter the job number. The job name should be 8 characters long and start with a number.
• Year. This is a two-digit field. Use the last two digits of the current year to indicate the year
in which the job is programmed.
• Month. This is a single character field. Use the numbers and letters shown in the example
below to indicate the month in which the job is programmed. See Table 3-1.
• File Type. This field is a single letter, used to indicate the panel type. There is currently
only a single supported type.
• Number. This is a three-digit field used to track how many of a specific job type have been
programmed during the month. For example, if the File type is 4100ES, enter the number
of 4100ES jobs programmed during the month.
• Job Version. When archiving a job, you can use letters to differentiate the jobs once they
have been archived. For example, once job 103E123A is archived, new edits should be
saved to 103E123B.
3-1
4007ES Panel Programmer Manual (579-1167)
4. Select the path to the file in which the job will be stored.
Note: It is preferable that the default folder C:\4100UJOBS be used for job storage.
3-2
4007ES Panel Programmer Manual (579-1167)
Saving Jobs There are two saving options in the programmer, Save and Save As. The Save option is used to
save the job in progress, the Save As option is used to save the job with a new name.
To save a job with Save:
• Click on the Save icon.
• Open the Edit menu and click on the Save option.
Note: When you click on the save option, the programmer overwrites the previous information and there is
no way to backtrack to the previous job.
To save a job with Save As:
1. Open the File menu and click on the Save As option.
2. Select either the Copy option or the Rename option:
• Copy: This option saves a copy of the currently open job under a new name in a new
directory. This option allows you to open and reuse the previous version.
• Rename: This option saves the job under a new name and deletes the content of the
previous job folder. For example, if a user renames job 333 as job 444, a new job
folder named 444 appears and the job folder 333 is empty.
Note: Conventionally, performing a Save As > Copy is the first action a technician takes when opening an
existing job to create a new revision. This way, if complications arise, the technician can return to the
previously saved revision.
Building a Job A job needs to be “built” before it can be downloaded. This process transforms the .SDB file
into a CFIG file that is compatible with the FACP.
Note: All configuration options and panel information must be complete before building the job. Any errors
detected during the build will abort the process.
To build a job:
1. Open the job.
2. Make the programming changes.
3. Start the build by either clicking on the Build icon or by selecting the Build item from the
Build menu.
4. The Revision History window appears and the user must enter:
• Their name.
• A brief description of the edits that were made to the current revision.
Once the information has been entered click on OK.
5. The Job Builder window then appears and displays all the elements in the job and their build
status. Once the compilation is complete, the final dialogue in the window will read either:
• Build Complete: This means the build has been successful and the job is ready to be
downloaded to the FACP.
• Build Aborted: This means that errors were found while the job was being built and
that the job build was aborted. The errors that caused the job to abort are listed in the
Job Builder window.
3-3
4007ES Panel Programmer Manual (579-1167)
System Requirements
Archiving a Job Once a job is archived, it is saved as a read-only .SDA4100U file that can no longer be opened
for editing.
To archive a job:
1. Save the job.
2. Open the Edit menu and click on the Archive menu item.
3. The Programmer Archive Utility window opens and requests that the user name the file and
select the directory to which the file will be saved.
4. Click on Archive. A progress meter appears, showing the progress of the operation. When
this bar disappears, the archive operation is complete. The archived file is saved as
.SDA4100U.
To open an archived file:
1. Open the File menu and click on the Restore menu item.
2. The Programmer Restore Utility window opens. Use the Look In search box to locate the
archived file.
3. Once the file is located, click on it so that its name appears in the File Name box.
4. Click on Continue.
5. The Browse for Folder window appears and requires that the user select the directory and
file to which the file will be restored. It is recommended to use the 4100UJOB Folder.
6. If a file with that name already exists, the user will be prompted to:
• Overwrite the existing file
• Rename the file
• Cancel the operation: This will result in an error file and the programmer will return to
the last saved job.
7. The archived file will then open as a read-only job. To save the job as a different version in
the 4100U folder, the user must use the Save As function.
Backing Up a Job Backing up a job creates a compressed version of the job and stores it as a read/writable
.SDC4100U file on either a removable storage medium or a remote disk.
To back up a job:
1. Open the File menu and select the Backup menu item.
2. The Programmer Backup Utility window opens and requests that the user name the file and
select the directory to which the file will be saved.
3. Click on Backup. A progress meter appears, showing the progress of the operation. When
this bar disappears, the backup is complete.
To restore a Backup file:
1. Open the File menu and click on the Restore menu item.
2. The Programmer Restore Utility window opens. Use the Look In search box to locate the
backup file.
3. Once the file is located, click on it so that its name appears in the File Name box.
4. Click on Continue.
5. The Browse for Folder window appears and requires that the user select the directory and
file to which the file will be restored.
6. If a file with that name already exists, the user will be prompted to:
• Overwrite the existing file
• Rename the file
• Cancel the operation
7. The backup file will then open as normal job.
3-4
Chapter 4.
Panel Information and Configuration
Introduction This section focuses on items found in the Panel tab. Information in this section must be
completed and the options must be configured before the job is successfully built.
In this chapter
Notice to users, Installers, AHJ, and other
Panel Information .................................... 4-1
Involved Parties ........................................4-1
Passcode Configuration ............................4-8 System Options ........................................ 4-2
Features Configuration .............................4-8 User Access Level Configuration ............ 4-7
Notice to users, This product incorporates field programmable software. In order for the product to comply
Installers, AHJ, with the Standard for Control Units and Accessories for Fire alarm systems, UL864, certain
and other programming features or options must be limited to specific values or not used at all as
Involved Parties indicated in Table 4-1.
Table 4-1. Programming Features and Options
Panel Information Panel information provides identification reference for the technicians who created the jobs.
To enter the panel information:
1. Click on the Panel tab and select the General Information sub-tab.
2. Fill out the information requested on the page:
• Panel Information: This section requests information about the panel.
• Branch Information: This section requests information about the branch of the
company and other useful information.
Continued on next page
4-1
4007ES Panel Programmer Manual (579-1167)
Panel Information • Programmed by: This section requests information about the people who programmed
the FACP (branch, customer information).
• Hardware Edit Lock: When this option is checked, the user cannot add or remove any
hardware.
• Comment: Enter any comments about this specific FACP.
System Options ES Panel System Options are global attributes that allow the user to configure specific
application options as well as configure certain elements of the panel's display.
To access the System Options screen:
1. Click on the Panel tab and select the System Options sub-tab.
2. Configure the options that appear on the page. The following tables list and define the
different options.
Table 4-2. General System Options
Description
Option
(“dflt” indicates the default setting)
Date Format • Select MM-DD-YY dflt for the panel to display the date by month, day, and
year (example: January 4th 2013 = 01-04-13).
• Select DD-MM-YY for the panel to display the date by day, month, and year
(example: January 4th 2013 = 04-01-13).
Time Format • Select 12 Hour dflt for the panel to display the time as “a.m.” and “p.m.”
(example: 6:00 a.m., 6:00 p.m.)
• Select 24 Hour for the panel to display the time on a 24h clock (example:
6h00, 18h00.)
Unit Format • Select Fahrenheit dflt for the panel to display Imperial units.
(example: 96 oF, 6 ft)
• Select Centigrade for the panel to display Metric units.
(example: 36 oC, 1.83 m)
Acknowledge • Select Global acknowledgedfl to allow every point reporting the same alarm
Option state (alarm, trouble, priority 2, or supervisory condition) to be
acknowledged at once by pressing the according Acknowledge button.
(Example: If 5 Trouble conditions are present on the system and global
acknowledge is enabled, one press of the Trouble Ack button
acknowledges all five Troubles at the same time.)
• Select Individual Acknowledge to ensure that each point reporting an
alarm state must be acknowledged individually. (example: If five Trouble
conditions are present, acknowledge each one individually.)
4-2
4007ES Panel Programmer Manual (579-1167)
Description
Option
(“dflt” indicates the default setting)
Service Select Service Reset to allow an operator to reset the system even though
Reset the device causing the alarm has not restored to normal.
The typical application for this would be when a malfunctioning initiating
device (detector or sensor consisting of a base and removable head) causes
an alarm, but will not reset even though the off-normal condition is no longer
present. With this option enabled, the head can be removed and the system
(including the local energy masterbox, if provided) can be reset. Without this
option enabled, removing the head will cause the system to abort the reset
because it will not have seen the alarmed point/zone having restored to a
normal state, and it will not be possible to reset the local energy masterbox.
The default setting for this option is disabled.
Combined If checked, pressing the Reset button performs an alarm reset followed by a
Alarm and hardware reset. If this option is not selected, an alarm reset is performed if
Hardware there are fire alarms or supervisories in the system. Otherwise, a hardware
Reset reset is performed.
Display First When this option is selected, the display alternates between the summary
Alarm screen (with the number of active alarms, troubles, etc.) and the screen
showing detailed information on the first alarm received by the system.
If this option is not selected, the screen indicating the number of alarm
conditions on the system is displayed.
Non Steady When enabled, this option allows you to select the type of operation for Non
Audible Evac Steady Audible Evacuation Signals. The term Non Steady Audible Evacuation
Signal refers to any Notification Appliance capable of sounding a coded
signal. The default setting for this option is not enabled. Choices are:
• California Code 1. A coding pattern consisting of 12 beats within a
10 second span of time, followed by a 2 ½ second pause. This sequence
repeats four times (four rounds) and then terminates (i.e., the total coding
pattern lasts approximately one minute).
• California Code 3. Same coding pattern as California Code 1, however the
sequence repeats 12 times (12 rounds) and then terminates (i.e., the total
coding pattern lasts approximately three minutes).
• Fast March Time. A coded signal that uses 120 beats per minute. Each
beat consists of ¼ second pulse on, ¼ second off. Pattern repeats until
alarm silence.
• March Time. A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats until alarm
silence.
• Slow March Time. A coded signal that uses 20 beats per minute. Each beat
consists of 1.5 second pulse on, 1.5 second off. Pattern repeats until alarm
silence.
• Temporal 4. A CO gas warning that is a repeated sequence of four
cycles of 100 msec on with 100 msec off, followed by 5 seconds off.
• Temporal. A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence. Pattern repeats until alarm silence.
• On Steady.
Note: If the coding pattern selected here is not supported by the notification appliance,
it will be replaced by a default one.
4-3
4007ES Panel Programmer Manual (579-1167)
Non Steady When enabled, this option allows you to select the flash pattern output by Non
Visual Evac Steady Visual Signals. The term Non Steady Visual Signal refers to any Visual
Notification Appliance capable of emitting a pattern of flashes (such as
incandescent visuals). The default setting for this option is not enabled.
Choices are:
• March Time. A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off.
• Slow March Time. A coded signal that uses 20 beats per minute. Each beat
consists of 1½ second pulse on, 1½ second off.
• Temporal. A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence.
Note: This option cannot be used for public mode signaling as defined in Section 4-4 of
NFPA 72-99.
Alarm Cutout This option allows you to set a duration (up to 60 minutes) that specifies how
Timer long signals sound following an alarm. For example, with this option set at
2 minutes, building signals sound for two minutes and then automatically stop.
After the signals stop, the alarm condition remains active at the panel.
If Alarm Silence/Reset Inhibit option is active, it takes precedence over this
option. See description of Alarm Silence/Reset Inhibit below for more
information.
The range for this option is 60-3600 seconds. The default setting for this
option is not enabled. Set the point type for visual NACS to SVISUAL to have
them turn off at the same time as the audible signals.
Note: See Appendix A for ULC Programming requirements when using this feature for
ULC applications.
This option disables the Alarm Silence and System Reset buttons for a user-
definable duration that ranges from 1 to 60 minutes. The timer is activated
only by the first alarm (i.e., subsequent alarms do not reset the timer).
Alarm If this option and the Alarm Cutout Timer are both enabled, this option takes
Silence/ precedence. For example, if the Alarm Cutout Timer is set to one minute and
Reset Inhibit this option is set to 2 minutes, signals continue to sound after one minute.
The default setting is not enabled.
Note: This option must be enabled for Canadian jobs.
AC Failure Specifies the time delay (HH:MM) in reporting an AC failure trouble to the city
Delay circuit (if AC fail is the only trouble) or Central Station if an SDACT is installed.
The time and date that appeared on the panel before the CFIG DOWNLOAD
Auto Set
are automatically set after download is complete. This option will not work if
Panel Time
the time/date was not set prior to the download (i.e. system time/date invalid
and Date
trouble at the panel).
4-4
4007ES Panel Programmer Manual (579-1167)
Option Description
Fire The Fire Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared Alarm condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Pri2 The Pri2 Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared Priority 2 Alarm (security) condition exists at the panel,
thereby reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Supv The Supv Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared supervisory condition exists at the panel, thereby
reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Trbl The Trbl Reminder option programs the system to periodically sound the piezo
Reminder if an uncleared Trouble condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Local If there is a per point serial DACT in the system, this setting specifies whether
Annunciation the piezo on the local panel will sound. This option is useful in situations
where the panel is located in a public area (such as a lobby) and the occupant
does not want the piezo repeatedly sounding.
4-5
4007ES Panel Programmer Manual (579-1167)
General Description: These options stop a recurring trouble event from continuously dialing
the central station or from generating SafeLINC email events if the programmed criteria are
met (number of occurrences of that point in the trouble log within the specified elapsed time
frame).
Option Description
Number of times the point is found in the Trouble log (0=no filtering; default for
Occurrences pre-existing jobs upgraded to 12.06). Value is selectable from 0 and 2 to 10.
By default, it is set to 3.
General Description: This option allows System Options to be selected for TrueAlert ES
appliances that can be configured identically or independently through the ES Programmer
software.
To use the System Options to configure TrueAlert ES appliances:
• The appliance's jumpers and configuration switches must be set to the correct setting. For
example, if a specific candela value is selected in the system options, the device should be
set to FACP. On the other hand, if system option is set to “Hardware”, the candela flag at the
device should be set to any other position than FACP.
• The appliance's candela and coding type in the power supply's Point Editing tab in the
programmer must be set to "System Default".
When a specific candela value is selected, that value applies to all compatible appliances that
have their configuration switches set to FACP*.
When Hardware Specified is selected, it is the appliance's locally configured candela value that
is used.
*Note: When a specific candela value is selected, a warning window appears to notify the user that in the
event that an appliance cannot be set to the selected Preferred Default System Option, a
compatible default value is assigned to the device by the programmer.
For example: If the System Option is set to 20 cd and there is a UL Weatherproof device (that has
no 20 cd setting), the Programmer assigns a value of WP75 cd to the UL weatherproof device.
4-6
4007ES Panel Programmer Manual (579-1167)
System Options Table 4-5. Addressable Appliances Preferred Default System Options, Continued
Value for
Assigned Candela Value for Indoor Value for Weatherproof,
Weatherproof,
Value Appliances UL
ULC
15 cd 15 cd 15 cd 20 cd
20 cd 30 cd WP75 cd 20 cd
30 cd 30 cd WP75 cd 30 cd
75 cd 75 cd 75 cd 75 cd
WP75 cd 75 cd WP75 cd 75 cd
User Access Level User access levels can be configured on the programmer for display functions to determine
Configuration their access level.
Each access level automatically has access to the level below it. For example, a technician
authorized for level 1 is only able to access functions that are tagged as level 1. A technician
with a level 3 authorization level however, has access to functions tagged as levels 1, 2 and 3.
Note: Passcodes can be attributed to user levels 2, 3, and 4 to restrict the access to certain functions. For
more information consult the Passcode Configuration section.
To associate user levels with a display function:
1. Click on the Panel tab and select the Access Levels sub-tab.
2. Double click on the table entry to open its Object Properties window.
3. Select one of four user levels for the display function. Basic display functions, such as
System Reset and Change Time and Date, are usually assigned to user level 1. More
sensitive display functions, such as Remote Download, are typically assigned to user level 2,
3, or 4.
4. Click on OK to confirm the selection.
4-7
4007ES Panel Programmer Manual (579-1167)
Passcode Numeric passcodes can be created to grant specific access level to up to 20 different operators.
Configuration Each access level automatically has access to the level below it. For example, a technician
authorized for level 1 is only able to access functions that are tagged as level 1. A technician
with a level 3 authorization level however, has access to functions tagged as levels 1, 2, and 3.
To create a passcode:
1. Click on the Panel tab and select the Passcode Assignments sub-tab.
2. Double-click on a table entry to open Object Properties window.
3. Enter a passcode, composed of up to ten numbers.
4. Assign the access level to the passcode.
5. Click on OK to confirm the selection.
Features The Features sub-tab provides information on the functionalities of the ES Panel Programmer
Configuration which can be used with the software key currently plugged into the Programmer PC.
To configure the functionalities:
1. Click on the Panel tab and select the Features sub-tab.The usable features are listed in the
Programmer/Runtime Features window.
2. To enable the options under Programmer and Runtime on the left panel, enter the software
key provided by an authorized Simplex representative with the appropriate access codes.
3. Click on Update Access Codes to complete the action.
Note: This sub-tab also prompts the user to enter the CPU Number. To get the CPU number, from the
panel, press on Menu > System info > Panel Serial Number. Enter the number in the designated box.
4-8
Chapter 5.
Specifying Hardware Components
Introduction The hardware components that are part of the FACP must be entered into the programmer so
that the user can configure their properties according to the job requirements.
This chapter explains how to add and remove the hardware elements that are entered into the
programmer.
Hardware Tab The Hardware Tab Window uses a drag and drop interface, consisting of a palette of available
Overview icons on the right-hand side of the screen and a work area on the left-hand side of the screen.
There are two available views:
• Tree View: This view displays the hardware in a branch structure. The hardware
appears linked to the bay into which it is installed.
• Grid View: This view displays the hardware in a grid structure and groups the
hardware by type. This view also features search and sorting options for elements
already added to the FACP.
5-1
Chapter 5 Specifying Hardware Components
Icon Meaning
Panel Icon This icon permanently resides in the top left corner of the work area. The panel
icon represents all of the non-networked, RUI-linked components controlled by
a single CPU. A single panel may, for example, actually be multiple boxes,
some residing at one location and some at another location.
Highlighting this icon and hitting Shift-Right Arrow at the same time expands
the entire hardware tree.
Unit Icon The unit icon does not represent actual equipment. It corresponds to a location
at which the box resides.
Click on the + sign to expand the contents of a unit and see the box.
Box Icon The box icon typically represents a standard bay box. There is also an option
that represents a custom box.
Click on the + sign to expand the contents of the box.
Logical Card Logical cards are not hardware; instead they represent all of the analog pseudo
Icon points, digital pseudo points, or lists used on the system.
Double click on the card to access its properties.
Physical Physical cards are actual hardware, including: monitor, signal, relay,
Card Icon annunciator, display, interface, and power cards.
Double click on the card to access its properties.
LED Module This icon represents the fixed-48 LED Module. The module is installed directly
Icon in a recess of the dress panel.
Double click on the card to access its properties.
Adding Hardware There are two ways to add a hardware component to the programmer:
• Drag and drop
• Right click + add
To add a hardware component to the programmer using drag and drop:
1. Locate the hardware component that you want to add from the Available Hardware window
on the right of the programmer screen.
2. Click on the hardware and drag it into the Hardware Configuration window on the left of the
programmer screen, into the proper directory:
• Units must be placed in panel icons.
• Boxes must be placed in units.
• Cards must be placed in boxes.
3. When the component is in the proper place, release the mouse. If the component was
successfully added, it appears in the Hardware Configuration menu. If the component
cannot be added to the configuration, an error message appears with the problem diagnosis.
5-2
Chapter 5 Specifying Hardware Components
Adding Hardware To add a hardware component to the programmer using click + add:
1. Right click in the Hardware component window. An action list appears.
2. Select the type of hardware you want to add to the programmer from the action list:
• Add Unit: The Unit Properties box automatically opens.
• Add Box: The Add Box window opens and displays the available boxes.
• Add Card: The Add Card window opens. Use the drop-down menus to select the card
you want to add. If the card cannot be added to the configuration, an error message
appears with the problem diagnosis.
To add multiple boxes or cards at one time, use the right-click method. Specify the number of
boxes/cards to add in the Quantity field.
Adding the To add additional loops in the IDNet expansion loop card:
Additional IDNet 1. In the Hardware Configuration window, double click on IDNAC power supply, then double
Loops click on IDNet+ Multiloop.
2. Click on the Loop Editing tab.
3. Select the first unused card 2: loop B isolator.
4. Change the device type to Isolator/Expanded point capacity.
5. Repeat steps 3 and 4 with the second unused card 2: loop C isolator.
5-3
Chapter 5 Specifying Hardware Components
Annunciator Every card in a 4007ES Panel job must have an associated annunciator number, whether it is an
Numbers annunciator or not. Annunciator numbers are assigned in the following manner: when a new
unit is added to a job, the unit is assigned the next available annunciator number.
When the first annunciator card is added to such a unit, it also assumes the unit's annunciator
number.
As additional annunciators are added to the unit, there are several cases where the annunciators
share their annunciator numbers. Any additional annunciator cards of the same type added to
the same unit also shares this number.
When an additional annunciator card of a different type is added to the unit, that annunciator
card is given an annunciator number distinct from the number assigned to the earlier
annunciator type.
A card’s annunciator number is important for correct LED Switch operation. For example, a
lamp test switch only lights lamps/LED on cards with the same annunciator number.
Exception to the rules above:
• Internal and external LCD Annunciators require their own annunciator number and do
not share numbers even with their own kind.
5-4
Chapter 5 Specifying Hardware Components
Editing Basic All cards, regardless of whether they are the standard system cards (such as the system power
Card Properties supply) or an option card, include the basic properties. The basic card properties are listed
below.
• Card Address. A unique number used to identify the card within the system. This
number must correspond to the card address dip switch settings on the card.
- Address 001 IDNAC/NAC power supply
- Address 002 IDNet and multiloop
- Address 003 Color user interface
Note: It is usually easier to first add the card to the job with the programmer and then set the dip switches
with the address automatically assigned by the programmer.
• Card Custom Label. This field describes the card's function, location, or some other
descriptive text.
• Unit, Box, Bay, and Block (location). The values shown in the fields reflect the
location in which the card icon was placed when you added it with the programmer. It
is possible to change these values; however, the new values must reflect the new
physical location of the card.
To gain access to the Card Properties dialog, do either of the following:
• Double click on any card icon in the work area.
• Right click on any card in the work area. When the list of choices appears, click on
Properties.
A window similar to Figure 5-2 appears.
Figure 5-2. Card Properties Window - Color User Interface shown as example
5-5
Chapter 6.
Editing Standard Component Properties
Introduction 4007ES panels come equipped with a standard set of hardware components. This chapter
details the programming for those cards.
In this chapter Accessing Properties............................. 6-1 Editing the IDNET Multiloop........ 6-7
Editing the Unit Properties ................... 6-1 Editing the NAC Power Supply..... 6-9
Editing the CPU .................................... 6-1 Editing the Zone/Relay Card ....... 6-11
Editing the Serial DACT Card Per Point
Editing the Color User Interface ........... 6-3
..................................................... 6-13
Editing the IDNAC Power Supply........ 6-5 Editing the Event DACT Card..... 6-15
48-LED Module..................................6-17
Editing the Unit Each 4007ES panel set-up automatically requires a unit in the programmer.
Properties To edit the unit:
The Unit Window requests that the user enters the following information:
• Description: Enter a description that identifies the particular FACP.
• AC Breaker Location: Enter the location of the breaker that powers the unit’s power
supply.
Editing the CPU The 4007 CPU window has three main tabs to edit. The Card Properties tab, the Service Port
tab, and the Ethernet tab.
To edit the Card Properties tab (Figure 6-1):
Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
To edit the Service Port tab (used as an output for ExacTech and TrueInsight):
1. Configure the communication settings by selecting the Baud Rate, Parity, Data Bits, and
Stop Bits fields to the values required by the attached device. It is recommended that you
use the following default settings whenever possible.
• Baud Rate: 115,200
• Data Bits: 8
• Stop Bits: 1
• Parity: None
2. Click on the Port Data button. The RS323 Port Data Entry window opens (Figure 6-1).
Continued on next page
6-1
4007ES Panel Programmer Manual (579-1167)
Editing the CPU 3. Click the Gen. Info tab. Enter the
information requested. Click on
Apply and then OK to confirm the
selection (Figure 6-1).
• Device Type: For a CPU card
service port, this field is
permanently set to
COMMAND.
• Header Label: This field
specifies the first line of banner
text that appears at the top of the
CRT screen.
• Port ID Label: This field
specifies the second line of
banner text that appears at the
top of the CRT screen. It is
typically used to designate the
port connection. For example,
“Port 2, Command Center.”
Figure 6-1. 4007 CPU - Gen Info Tab
• Port Default SET Priority CPU Card Only: This is the system priority level assigned to
commands issued from the service port. The range is 2 to 15 and the default is 9.
4. Click on the Access Level tab
in the RS232 Port Data Entry
window (Figure 6-2). This tab
allows you to set the access
level for the various system
operations that can be carried
out via the service port.To set
an access level for one of the
service port operations, scroll
through the list of functions
and highlight the function. Use
this control to associate an
access level with the function.
Click on Apply and then OK
to confirm the selection.
Figure 6-2. 4007 CPU Access Levels and Port Options
Note: These access levels apply only to actions performed through the service port, not for operations
made at the panel display.
5. Click on the Port Options tab in the RS232 Port Data Entry window. This tab contains
options that apply to the way data appears on the display connected to the service port.
These are read-only fields. Click OK to return to the Service Port tab.
6. Click in the TrueInsight Remote Service Gateway box to enable the use of the Remote
Service Gateway.
6-2
4007ES Panel Programmer Manual (579-1167)
6-3
4007ES Panel Programmer Manual (579-1167)
Editing the Color To edit the Point Editing tab (Figure 6-4):
User Interface For each control key:
1. Select a switch mode
from the drop-down
list.
2. Enter a reference
address. Press F9 to
access the TagList
window.
3. Edit the point’s
custom label if
required. This label
should make the
point easily
identifiable.
4. Check the Invert
Pushbutton State box
to switch down the
point.
6-4
4007ES Panel Programmer Manual (579-1167)
Editing the Color To edit the Display Options tab (Figure 6-5): If
User Interface needed, check the Reverse Display of custom label and
status line. To use custom external files for the primary
and/or the alternate MsgLib:
1. Click on Import.
2. Browse to import the appropriate MsgLib.
3. Click on Open.
4. Edit the Name and Date fields.
By default, the System is Normal image is displayed. To
edit this image:
1. Check the Enable Custom Image check box.
2. Click on Import Image...
3. Browse to select the appropriate image.
4. Click on Open > Apply.
Figure 6-5. Color User Interface - Display Options
To edit the Access Levels tab:
Editing the IDNAC The IDNAC Power Supply is part of the 4007ES Hardware Configuration. It has five main tabs
Power Supply to edit. The Card Properties tab, the Data Entry tab, the AuxNAC tab, the Aux Relay tab, and
the Point Editing tab. For more information on the 4007ES Hybrid power supply, refer to the
Editing the NAC Power Supply section.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
6-5
4007ES Panel Programmer Manual (579-1167)
Editing the IDNAC To edit the Data Entry tab (Figure 6-7):
Power Supply 1. Configure the Depleted Battery Cutout
option. If selected, the power supply card
shuts itself off after detecting a depleted
battery condition when no AC power is
present. If this option is selected, a jumper
must be installed on the power supply (on
S527), for Canadian operation. It is
unselected by default.
2. Select the optional cards that are
connected to the power supply card. The
choices are:
• None
• City Connect
• Relay
Figure 6-7. IDNAC - Data Entry Tab
3. Click in the 25V Regulator box if a 25V regulator card, 4007-9802, is used with the FACP.
4. Click OK to confirm the selection.
6-6
4007ES Panel Programmer Manual (579-1167)
Editing the IDNET The IDNet Multiloop can contain up to 250 points. The card has three main tabs to edit. The
Multiloop Card Properties tab, the Point Editing tab, and the Loop Editing tab.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
2. Click in the box beside the following functions to activate them:
• Only activate TrueAlarm device LEDs
• Activate Signal IAM LEDs
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
• Total of configured points
• Total of available points
6-7
4007ES Panel Programmer Manual (579-1167)
6-8
4007ES Panel Programmer Manual (579-1167)
Editing the NAC The NAC Power Supply is part of the 4007ES Hybrid Hardware Configuration. The card has
Power Supply four main tabs to edit. The Card Properties tab, the Data Entry tab, the NACs tab, and the
AuxNAC tab.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
To edit the Data Entry tab (Figure 6-14):
1. Configure the Depleted Battery Cutout option. If selected, the power supply card shuts itself
off after detecting a depleted battery condition when no AC power is present. If this option is
selected, a jumper must be installed on the power supply (on S527), for Canadian operation.
It is unselected by default.
2. Select the optional cards that are connected to the power supply card. The choices are:
• None
• City Connect
• Relay
3. Select the NAC options for the wiring. The choices are:
• 4 Class B
• 4 Class A
4. Click in the Wheelock Devices (Code 3) box if ONLY Wheelock device are used with the
FACP.
5. Click in the 25V Regulator box if a 25V regulator card is used with the FACP.
6. Click Apply > OK to confirm the edits.
.
6-9
4007ES Panel Programmer Manual (579-1167)
6-10
4007ES Panel Programmer Manual (579-1167)
• MONB Class B
Monitoring Device
• Relay device
2. Select the point type.
3. Enter the card’s custom
label. This label should
make the card easily
identifiable.
4. Select the EOL resistance
from the EOL Resistance
drop-down list.
5. Click Apply > OK to
confirm the edits.
6-11
4007ES Panel Programmer Manual (579-1167)
6-12
4007ES Panel Programmer Manual (579-1167)
Editing the Serial The 4007-9806 serial DACT interface card can be programmed per point or by event.
DACT Card Per The 4007-9806 serial DACT per point has six main tabs to edit. The Card Properties tab, the
Point Basics tab, the Event Codes tab, the Local Points tab, the Point Types tab, and the Points tab.
To edit the Card Properties tab per point:
1. The panel assigns an address when a DACT card is added. Set the card address to match the
programmer assigned address.
2. Enter the card’s custom label. This label should make the card easily identifiable.
3. Select a card address, from 0 to 31.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Box number
• Bay number
• Location
To edit the Basics tab (Figure 6-19):
The Basics tab can be used to set up the basic communication information of the DACT to
DACR link. The following fields in the tab can be edited:
• Phone and Account Numbers
- Primary (1)#
- Secondary (2)#
- Account (1)#
- Account (2)#
• Central Station Line #
• Dial Mode
- Tone
- Pulse
- Tone else Pulse
• Miscellaneous
- Report AC Failure Delay
- Test Report Time
- Send Unmapped Points
- IP Communicator
Figure 6-19. DACT Card - Basics Tab
• Central Station Email Address. Check the box to enter an email address and the .CSV
file is automatically sent to Central Station. Automatic email can only be used with Per
Point DACTs and must be set up in advance with Central Station.
To edit the Event Codes tab (Figure 6-20):
The Event Codes tab allows you to edit the
event codes associated with each of the
4007ES Panel point types.
1. Click on the Point Types drop-down list box
and select the point type whose event codes
needs to be changed. (The Next and
Previous buttons allow you to scroll
through the list without clicking on the
drop-down list box.)
2. Click on the Enable Edit checkbox at the
top left of the window.
3. A warning window appears. Click on Yes.
Figure 6-20. DACT - Event Codes Tab
Note: Do not edit event codes without prior authorization and direction from the central station.
4. The non-editable fields remain grayed out. Define the appropriate event codes for both the
Event and the Restoral columns.
5. Click Apply > OK to confirm the edits.
6-13
4007ES Panel Programmer Manual (579-1167)
Editing the Serial To edit the Local Points tab (Figure 6-21):
DACT Card The Local Points tab allows you to edit the local points associated with each of the 4007ES
Panel point types.
1. Click on the Enable Edit checkbox at the
top right of the window.
2. A warning window appears. Click on Yes.
Note: Do not edit local points without prior
authorization and direction from the central
station.
3. The non-editable fields remain grayed out.
Define the appropriate local points for
both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
6-14
4007ES Panel Programmer Manual (579-1167)
Editing the Event The 4007-9806 DACT “per event” has five main tabs. To edit the Card Properties tab, the
DACT Card Basics tab, the Event Codes tab, the Local Points tab, and the Points tab.
To edit the Card Properties tab per event:
1. The panel assigns an address when a DACT card is added. Set the card address to match the
programmer assigned address.
2. Enter the card’s custom label. This label should make the card easily identifiable.
3. Select a card address, from 0 to 31.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Box number
• Bay number
• Location
6-15
4007ES Panel Programmer Manual (579-1167)
6-16
4007ES Panel Programmer Manual (579-1167)
Editing the Event The Local Points tab allows you to edit the local points associated with each of the 4007ES
DACT Card Panel point types.
To edit the Local Points tab (Figure 6-21):
1. Select the Enable Edit checkbox at the top right of the window.
2. A warning window appears. Click on Yes.
Note: Do not edit local points without prior authorization and direction from the central station.
3. Define the appropriate local points for both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
48-LED Module The 48-LED Module has two main tabs to configure. The Card Properties tab and the Point
Editing tab.
To edit the Card Properties tab:
1. Enter a card address for the 48-LED Module.
2. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
6-17
4007ES Panel Programmer Manual (579-1167)
6-18
4007ES Panel Programmer Manual (579-1167)
6-19
Chapter 7.
Editing TrueAlert Devices Properties
Introduction TrueAlert devices are edited through the Point Editing tab on the IDNAC Power Supply.
To access this tab:
1. Go to the Hardware Configuration window.
2. Double click on the IDNAC Power Supply icon.
3. Click on the Point Editing tab.
In this chapter TrueAlert ES AO Appliance Point Editing ...... 7-2 TrueAlert ES VO Appliances Point Editing .... 7-3
TrueAlert ES VO-H Appliances Point Editing 7-4 TrueAlert ES VO-L Appliances Point Editing 7-5
TrueAlert ES VO-LH Appliances Point Editing7-6 TrueAlert ES AV Appliance Point Editing ...... 7-7
TrueAlert ES AV-H Appliance Point Editing... 7-9 TrueAlert ES AV-L Appliance Point Editing. 7-11
TrueAlert ES AV-LH Appliance Point Editing7-13 ISO Options ................................................... 7-15
Repeater Options............................................ 7-15 DCAI Options ................................................ 7-16
TrueAlert STRB Appliances Point Editing .... 7-16 TrueAlert Horn Appliance Point Editing ....... 7-17
TrueAlert A/V Appliances Point Editing ....... 7-18
7-1
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AO Use this device type to edit TrueAlert ES Audible Only (AO) appliances.
Appliance Point The following editing options are available for this appliance:
Editing Table 7-1. TrueAlert ES AO Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
Available • Indoor
settings: • Weatherproof UL
• Weatherproof ULC
Tone BROADBAND BROADBAND, 250 HZ, BELL, SLOW WHOOP, SIREN, HILO,
CHIME, HARDWARE
Coding Type Select the Coding Type to set the cadence of the audible signal.
System This sets the coding to the value determined in the System Option
Default tab.
March 20 A coded signal that uses 20 beats per minute. Each beat consists of
1 ½ second pulse on, 1 ½ second off. Pattern repeats until alarm
silence.
March 60 A coded signal that uses 60 beats per minute. Each beat consists of
½ second pulse on, ½ second off. Pattern repeats until alarm
silence.
March 120 A coded signal that uses 120 beats per minute. Each beat consists
of ¼ second pulse on, ¼ second off. Pattern repeats until alarm
silence.
On Steady On steadily.
High To use this option the appliance's configuration control must be set
to Panel.
Low To use this option the appliance's configuration control must be set
to Panel.
Hardware Selecting this option sets the appliance to the setting indicated on
the appliance's configuration switch or jumper.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-2
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES VO Use this device type to edit TrueAlert ES Visual Only (VO) appliances.
Appliances Point The following editing options are available for this appliance:
Editing
Table 7-2. TrueAlert ES VO Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
135 candela
185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
• Weatherproof UL. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
75 candela
WP 75 candela
WP 185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
• Weatherproof ULC. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
20 candela
30 candela
75 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Mounting Select the mounting location of the appliance: wall-mounted or ceiling-mounted.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-3
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES Use this device type to edit TrueAlert ES Visual Only High Candela (VO-H) appliances.
VO-H Appliances The following editing options are available for this appliance:
Point Editing
Table 7-3. TrueAlert ES VO-H Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Selecting this option sets the candela value to
Available candela the one selected in the System Option tab.
options:
110 candela
135 candela
185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Mounting Only a ceiling-mounted appliance is allowed.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-4
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES VO-L Use this device type to edit TrueAlert ES Visual Only LED Strobe (VO-L) appliances.
Appliances Point The following editing options are available for this appliance:
Editing
Table 7-4. TrueAlert ES VO-L Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Selecting this option sets the candela value to
• Weatherproof UL/ the one selected in the System Option tab.
ULC. 15 candela
Available candela
options: 30 candela
75 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Mounting Only a wall-mounted appliance is allowed.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-5
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES Use this device type to edit TrueAlert ES Visual Only LED Strobe High Candela (VO-LH)
VO-LH appliances. The following editing options are available for this appliance:
Appliances Point
Editing Table 7-5. TrueAlert ES VO-LH Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Selecting this option sets the candela value to
• Weatherproof UL/ the one selected in the System Option tab.
ULC. 110 candela
Available candela
options: 135 candela
175 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Mounting Only a wall-mounted appliance is allowed.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-6
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV Use this device type to edit TrueAlert ES Audible/Visual (AV) appliances. The following
Appliance Point editing options are available for this appliance:
Editing
Table 7-6.TrueAlert ES AV Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
15 candela
30 candela
• Indoor. 75 candela
• Available candela 110 candela
options:
135 candela
185 candela
15 candela
20 candela
• Weatherproof
ULC. 30 candela
• Available candela
options: 75 candela
7-7
4007ES Panel Programmer Manual (579-1167)
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
7-8
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV-H Use this device type to edit TrueAlert ES Audible/Visual High Candela (AV-H) appliances. The
Appliance Point following editing options are available for this appliance:
Editing
Table 7-7.TrueAlert ES AV-H Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
110 candela
• Indoor.
135 candela
• Available candela
options: 185 candela
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
7-9
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV-H Table 7-7. TrueAlert ES AV-H Point Editing Options, Continued
Appliance Point
Option Description
Editing
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
March 20 A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
7-10
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV-L Use this device type to edit TrueAlert ES Audible/Visual LED Strobe (AV-L) appliances. The
Appliance Point following editing options are available for this appliance:
Editing
Table 7-8.TrueAlert ES AV-L Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. 15 candela
• Weatherproof UL/
ULC 30 candela
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Tone BROADBAND
7-11
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV-L Table 7-8. TrueAlert ES AV-L Appliance Point Editing, Continued
Appliance Point
Option Description
Editing
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
March 20 A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
7-12
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES Use this device type to edit TrueAlert ES Audible/Visual LED Strobe High Candela (AV-LH)
AV-LH Appliance appliances. The following editing options are available for this appliance:
Point Editing
Table 7-9.TrueAlert ES AV-LH Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Tone BROADBAND
7-13
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV- Table 7-9. TrueAlert ES AV-LH Appliance Point Editing, Continued
LH Appliance
Option Description
Point Editing
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
March 20 A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
7-14
4007ES Panel Programmer Manual (579-1167)
ISO Options Use this device type to edit TrueAlert Isolators. The following editing options are available for
this device:
Table 7-10.TrueAlert Isolator Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Depleted Battery When this option is selected the Repeater shuts itself off after detecting a depleted
Cutout battery condition when no AC power is present. This option is de-selected by default.
Repeater Select the option that corresponds to the Repeater’s wiring style.
Operation
• For local Class B Wiring select "Class B Spur"
7-15
4007ES Panel Programmer Manual (579-1167)
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Loop 2 Address This virtual address does not need to be adjacent to the loop 1 hardware address.
TrueAlert STRB Use this device type to edit TrueAlert Strobe (STRB) appliances. The following editing options
Appliances Point are available for this appliance:
Editing
Table 7-13. TrueAlert STRB Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-16
4007ES Panel Programmer Manual (579-1167)
TrueAlert Horn Use this device type to edit TrueAlert Horn appliances. The following editing options are
Appliance Point available for this appliance:
Editing
Table 7-14. TrueAlert Horn Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Coding Type Select the Coding Type to set the cadence of the audible signal.
System This sets the coding to the value determined in the System Option tab.
Default
March 60 A coded signal that uses 60 beats per minute. Each beat consists of ½
second pulse on, ½ second off. Pattern repeats until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat consists of
¼ second pulse on, ¼ second off. Pattern repeats until alarm silence.
On Steady On steadily.
High To use this option the appliance's configuration control must be set to
Panel.
Low To use this option the appliance's configuration control must be set to
Panel.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-17
4007ES Panel Programmer Manual (579-1167)
TrueAlert A/V Use this device type to edit TrueAlert Strobe Audible/Visual (A/V) appliances. The following
Appliances Point editing options are available for this appliance:
Editing
Table 7-15. TrueAlert AV Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
Operation The strobe and horn appliances is automatically associated respectively with the “ALL
VISUAL” and "ALL AUDIBLE" VNAC by default.
Coding Type Select the Coding Type to set the cadence of the audible signal.
System Default This sets the coding to the value determined in the System
Option tab.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-18
Chapter 8.
Viewing, Adding, and Editing Lists
Introduction A list is a group of similar points, sharing a common name, that can be monitored or
controlled as if they were a single point. For example, when you use a switch to turn on a list
populated with control points, all of the points in the list turn on.
The 4007ES FACP includes the following types of lists.
• Automatically Generated, Read-Only System Lists. These lists are created based
on the point type assigned to the point. Points cannot be manually added or deleted
from these lists.
• Automatically Generated, Editable System Lists. These are lists created based on
the point types you assign to the point. These lists are only editable after the automatic
list generation property is turned off for the list.
• User-Defined Lists. Switches, LEDs, and Custom Control equations all make use of
these types of lists. Switches typically control lists made up of control points (relays),
or standard NACs (horns/strobes). LEDs can be programmed to monitor a list and
turn ON when any point in the list activates. Custom Control equations typically use
lists of monitor points to indicate when a specific output action should occur, and the
points affected by the output action are typically specified in a user-defined list of
control points.
• Zone Lists. This option allows you to create up to 512 lists grouping together points
in one defined zone.
This chapter describes the programming of the four list categories, General Lists, WalkTest
Lists, Latching Supv Verification Lists, and Elevator Recall Lists, used by the Panel FACP.
Note: The Alarm Verification Tab can still be accessed through the List Tab, but it cannot be used.
For information on using lists for the Install Mode feature, consult the 4007ES Operator’s
Manual (579-1165).
8-1
4007ES Panel Programmer Manual (579-1167)
List Tab Select the List Tab to display the List Tab window. By default when you select the List Tab, the
General List subtab, located on the bottom left of the window, is selected. This window
contains an entry for every list in the system.
The subtabs running across the bottom of the window allow you to display only the lists
associated with a specific system category. For example, clicking on the alarm verification
subtab displays only the lists associated with alarm verification.
Sort Function The Sort function allows you to sort and display lists in ascending or descending order based
on list-specific criteria (the criteria shown in the Sort Dialog is different for each type of list).
To sort lists, do one of the following:
Custom Label Spell Check allows you to validate the spelling of custom labels. Using Spell Check,
Spell Check incorrectly spelled words can be automatically corrected or suggested alternatives can be
substituted.
1. Position the pointer in the point list and press the F7 button. (Alternatively, you can right-
click in the List window and select Spell Check when the list of options appears.)
2. Correct the misspelled word in any of the following ways. (Use the Ignore and Ignore All
buttons to ignore the misspelled word.)
• Click on the Change or Change All button to accept the suggested spelling in the
“Change to” field.
• Type the correct spelling in the “Change to” field and press the Change or Change All
button.
• Scroll through the Suggestions drop-down list, click on one of the entries, and then
click on the Change or Change All field.
The Search and Find functions allow you to specify a specific search criteria (such as a specific
custom label) and then search the List Window for the selected data.
1. Position the pointer in the List Window and press the CTRL + F key combination.
(Alternatively, you can right click in the List Window and select Search or Find from the list
that appears.)
2. Enter the Search text in the Search What field. Click on the Search in Column field and
select the column in which to search. Click on Search Next to start the search.
3. Press the F3 key to continue searching the List Window for another occurrence of the item
you are searching.
8-2
4007ES Panel Programmer Manual (579-1167)
Managing Points Default custom control programming within the system automatically adds points to system
lists based on their point type, a process known as auto list generation, or autogen. For
example, adding a signal point with the SSIGNAL point type automatically adds the point to
system list L8, Fire Alarm Points Off on Silence.
In some applications, however, you need to turn a system list's autogen property off, so that you
can manually move points into or out of the system list. This is particularly true when editing
WalkTest, Latching Supv Verification, and Elevator Recall groups.
Be aware that when working with the system lists, four icons are used to indicate the status of
the system list.
This symbol represents an auto-generated list with the autogen property turned on. When
autogen is turned on, points cannot be manually moved into or out of the list.
This symbol represents an auto-generated list whose autogen property cannot be altered.
The list is permanently set to autogen on and cannot be edited.
This symbol represents an auto-generated list with the autogen property turned off.
A system list's autogen property can be turned on and off in one of two places:
• General List Tab. Clicking on the General List tab displays all lists (system and user)
currently defined on the panel. Refer to “Turning Autogen Off and On from the
General List Tab” for specific information on doing this.
• WalkTest, Latching Supv Verification, Elevator Recall Tabs. Each of these tabs
displays a window that allows you to move points into the appropriate lists. Within
each window, you can toggle the autogen property to allow points to be moved into
and out of the lists. Refer to the specific section for information on turning off autogen
for Latching Supv Verification, WalkTest, or elevator recall.
Turning Autogen 1. Click on the List tab at the top of the programmer.
Off and On from 2. Click on the General List subtab at the bottom of the window.
the General List 3. Right click on the list whose autogen property you want to change. Select Properties from
Tab the list that appears. A dialog similar to Figure 8-2 appears.
8-3
4007ES Panel Programmer Manual (579-1167)
Basic Operations User-defined lists allow a range of points to be controlled (turned on or off, for example) by
turning a switch on, or via a Custom Control command. Lists associated with LEDs allow the
status of system attributes or components to be monitored.
Editing an To edit an existing list (i.e., add additional points or delete points from the list):
Existing User- 1. Open the list's Tag List by either right clicking on the list and selecting Tag List from the
Defined List menu that appears, or click on the list and press the F9 key.
2. When the tag list appears, click on the points you want to add or delete. Press the spacebar to
toggle whether the point is tagged (included in the list) or not. Tagged points are identified
by the “>>” to the left of the point name.
3. Click on OK to accept the changes.
4. Edit the List Label and the Alternate List Label.
5. Press OK.
8-4
4007ES Panel Programmer Manual (579-1167)
Type Operation
Retard Stage. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 15
seconds
Reset Stage. When the 15 second timer expires, the system attempts to reset
Canadian
the initiating device for five seconds.
Operation
Confirmation Stage. After the five second timer expires, the system
evaluates the state of the initiating device for 10 additional seconds. After 10
seconds, if the device is still in alarm, the system immediately annunciates the
alarm.
Retard Stage. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 30
seconds
Domestic
Reset Stage. When the timer expires, the system attempts to reset the
(US)
initiating device for five seconds.
Operation
Confirmation Stage. After the timer expires, the system evaluates the state
of the initiating device for up to 120 additional seconds. After this duration, if
the device is still in alarm, the system immediately annunciates the alarm.
To select Canadian or Domestic (US) operation (Figure 8-3), follow these steps:
1. Right click on one of the groups and select
Properties. The Alarm Verification Properties
dialog appears.
2. Click on the Alarm Verification tab.
3. Click on the drop-down list box and select
Canadian or Domestic operation.
Note: You only need to set the Verification Timer field
for one of the alarm verification groups. The
programmer sets this field to the same value for
all other groups.
8-5
4007ES Panel Programmer Manual (579-1167)
WalkTest™ WalkTest allows the function of the system's initiating devices and signals to be tested by a
single person. Conducting a WalkTest requires you to perform the following general steps.
• Step 1. Create WalkTest Groups. The ES Panel supports up to eight WalkTest groups.
This allows the building to be divided into small portions for the WalkTest, and allows
the rest of the building to be protected by the fire alarm panel. Each group has a list of
monitor points (initiating devices) and a list of the signal circuits that activate when
one of the monitor points within the group activates.
• Step 2. Enable WalkTest Options from Front Panel. These options include the
following:
- Which WalkTest Group is enabled.
- Whether the group's signals turn on when a monitor point in the same group
activates. Turn this option off to perform a silent WalkTest on the system.
- Whether logging of WalkTest information is enabled or not. (Enable this option to
perform a silent WalkTest. Refer to the 4007ES Operator's Manual (579-1165) for
information on setting these options.)
• Step 3. Manually Activate Initiating Devices in Each Group and Interpret Signals.
Individually activate each initiating device in the group, using the manufacturer’s
recommended test equipment. Make sure to proceed in a logical manner (i.e., start with
the lowest IDNet address and work toward the highest). Each time you activate an
initiating device, the system’s signals pulse a code that allows you to verify exactly
which initiating device triggered the signals. For hardwired monitor zones, the signal
code corresponds to the number of the zone. (For example, if the zone number is eight,
the signals pulse eight times to indicate zone eight.) For IDNet devices, the first set of
pulses from the signals correspond to the channel. The signals then pause momentarily
and the next set of pulses corresponds to the number of the device on the channel. For
example, if you activate an IDNet smoke detector with an address of M1-25, the
signals would sound once to indicate channel one, pause for a short duration, and then
sound two pulses followed by a pause and then five pulses to indicate device 25. In
some cases, immediately after verifying the function of an initiating device, you may
also want to verify its ability to generate a trouble condition. To do this, cause a trouble
on the device and then listen to the signals. The signals sound steady for 4 seconds to
indicate trouble conditions, and then reset.
8-6
4007ES Panel Programmer Manual (579-1167)
8-7
4007ES Panel Programmer Manual (579-1167)
Tab Properties
Setting the properties in this tab affects all WalkTest groups.
Monitor. A check in this box means monitor points are automatically inserted in
Group 1 - Monitor Zones. If you uncheck this box, you can move points from
one group to another. However, at a later point, if you recheck this box, the
points you previously moved to other groups will be moved back to Group 1.
WalkTest Control. A check in this box means control points (signals/relays) are
automatically inserted in Group 0 - Signals/Relays. If you uncheck this box, you
can move points from one group to another. However, at a later point, if you
recheck this box, the points you previously moved to other groups will be
moved back to Group 1.
On. Allows you to set the duration of each tone within the PNIS code.
Off. Allows you to set the duration of silence between tones of the PNIS code.
Setting the properties in this tab affects only the selected group.
Monitor. A counter that tracks the number of devices in the group.
Group Control. A counter that tracks the number of devices in the group.
Reset Delay. Allows you to shorten or lengthen the reset time used by the
monitor device. For example, increase the delay in cases where canned smoke
does not clear from a smoke detector quickly enough.
Description. Allows you to change the description of the group’s monitor or
List control lists. For example, you can change the name of the WalkTest Group 0 -
Signals/Relays to a more descriptive name, if necessary.
4. After making changes to the WalkTest Group properties, click on the Apply button to apply
the changes and then click on OK to close the window.
8-8
4007ES Panel Programmer Manual (579-1167)
Elevator Recall The Elevator Recall list is made up of five groups, each corresponding to an elevator shaft
List numbered from one to five. Each shaft group contains three lists - one for the primary recall
points, one for the alternate recall points, and one for the shutdown points.
The Elevator Shaft 1 group initially contains all of the system's monitor points and all relays
with the following point types - PRIMARY, ALTERN, and SHAFT (shutdown).
8-9
4007ES Panel Programmer Manual (579-1167)
Zone Lists The Zone List tab provides a way to group alarm conditions into zones (up to 512 zones).
When grouped into zones, when an alarm occurs, a list of affected zones is displayed on the
panel's touchscreen. It is then possible to touch the zone in alarm to display all the points that
are in alarm in that particular zone.
8-10
Chapter 9.
Custom Control
Introduction With Custom control the components of the ES Panel FACP—hardware points, pseudo points,
and lists—can be controlled with user-definable custom control “equations.”
This chapter describes using Custom Control to create custom programming applications for
the ES Panel FACP.
In this chapter
Custom Control Overview.........................................................9-1 Role of Lists and Pseudo Points .............................................. 9-2
Anatomy of a Custom Control Equation...................................9-2 Using a Ladder Logic Diagram to Evaluate an Equation ........ 9-3
Custom Control Window...........................................................9-5 Selecting User Program ........................................................... 9-6
Adding Input Statements...........................................................9-7 Adding Output Statements....................................................... 9-8
Floor Above/Floor Below Wizard.............................................9-8 Selecting Floor Tab.................................................................. 9-9
General Information................................................................9-10 Specifying Floor Names .........................................................9-11
Specifying Input and Static Points..........................................9-11 Using the Selective Signaling Wizard ................................... 9-12
Selecting Selective Signaling Wizard Tab..............................9-12 Setting General Options......................................................... 9-13
Setting Zone Names................................................................9-13 Linking Initiating and Notification Points............................. 9-14
Using the Sounder/Relay Base Wizard...................................9-15 Activating Base on Alarm ..................................................... 9-15
Common Ground Fault LED Control .................................... 9-17 Suppression Release Introduction...........................................9-18
Suppression Release General Capabilities..............................9-18 Suppression Release Device and Point Types........................9-20
Suppression Release Device and Point Types........................9-20 Suppression Release Use Cases.................................... .........9-22
Step 1. Defining Hazard Area................................................ 9-27 Step 2. Specifying Initial Data and Options...........................9-28
Step 3. Specifying Abort Switch Operation............................9-29 Step 4. Setting Timer Options................................................9-30
Step 5. Specifying Hazard Area Points...................................9-31 Deleting Hazard Area..............................................................9-34
Editing Existing Hazard Area ................................................ 9-34 Scheduling Options for Self-Test Wizard...............................9-35
Step 1. Creating a New Self-Test........................................... 9-35 Step 2. Selecting Start Time and Frequency of the Self-Test. 9-36
Step 3. Selecting Self-Test Triggering Point and Point List .. 9-37
Custom Control ES Panel Custom Control — which is a wizard-based application used to create Custom
Overview Control Equations — provides a way to override the ES Panel’s default operation and for the
ES Panel to function in a facility-specific way. Each Custom Control equation has a similar
form: one half of the equation, called the input side, is used to monitor the state of specific
system inputs (initiating devices, for example). The other half of the equation, called the
output side, is used to control specific system outputs (such as relays, notification appliances).
The output side executes only when the state of the input side is true. Another way to think
about Custom Control equations is to consider them as If/Then commands. If the input side of
the equation is true, then execute the output side.
The following examples help explain the way custom control is typically used with a ES Panel
FACP.
• Selective Signaling. Selective signaling replaces the system's general alarm NAC
operation — which activates all NACs in response to any alarm condition — with
selective NAC control. With this type of control you can program the system so that
only specific NACs respond to specific initiating devices.
• Fan and Damper Control following an Alarm. Controlling a building's HVAC
system following an alarm condition prevents supply fans from feeding a potential
fire and makes it possible for the HVAC system to exhaust smoke from the area in
alarm. In this case, custom control equations are used to monitor the initiating devices
in a given area and control the HVAC system’s dampers and air handling units to
provide the correct supply and exhaust pressurization.
9-1
4007ES Panel Programmer Manual (579-1167)
Custom Control
Role of Lists and Using lists and pseudo points (both user-defined and system) improves the efficiency of
Pseudo Points Custom Control equations and makes it possible for a range of facility-specific operations to be
programmed.
Anatomy of a As mentioned above, every Custom Control equation has an input side, consisting of input
Custom Control statements, and an output side, consisting of output statements.
Equation
Input Statements are typically used to monitor the status of a point or list, or perform an
action such as delay, cycle, compare two values, or save/recall values. Every input statement
begins with an Opcode, which is the action that the input is performing (for example, monitor
point status, recall memory register). The Custom Control wizard then displays a series of
opcode-specific dialogs. For example if the Opcode is Point Status, the dialogs prompt the user
for Qualifier about the condition (such as, alarm, trouble) and point being monitored.
9-2
4007ES Panel Programmer Manual (579-1167)
Anatomy of a Using Logical Operators (AND, OR, NOT) you can link multiple input statements to form
Custom Control logical expressions. Logical operators are only used with input statements and are not used
Equation with Output statements. ES Panel Custom Control uses the following logical operators.
• AND Operator. With the AND logical operator you can put a group of points in series
so that only the activation of all points at the same time causes the Output side of the
equation to occur. In the following example, Zone1 and Zone2 must both be in alarm
(FIRE) before the output (Hold ON SIG3) executes.
Using a Ladder A ladder logic diagram is a “sketch” of the equation used to evaluate (predict the outcome) of a
Logic Diagram to custom control equation before it is entered into the programmer. Use the following
Evaluate an conventions when creating ladder logic diagrams:
Equation
• Draw a solid, vertical line on the left side of the sketch to represent the starting point
for the equation. Use a vertical dashed line to divide the sketch into an input side and
an output side.
• Use two vertical, parallel lines to represent each input statement. Add text between the
lines to describe the input statement.
9-3
4007ES Panel Programmer Manual (579-1167)
Using a Ladder • Use a circle to represent each output statement. Add text within or beside the circle to
Logic Diagram to describe the output statement. In the following example, the output side of the equation
Evaluate an contains a single output statement, HOLD ON SIG 1. This action only occurs if the
Equation input side of the equation, which monitors point M 2-1 for the presence of a fire
condition, is true.
• Represent the OR logical operator by positioning inputs on top of one another as
shown in the example below. Represent the AND logical operator by positioning the
inputs beside one another.
Point Status
Position the M 2-1 for TBL
inputs on Point Status Point Status Relay
top of one M 2-2 for TBL M 2-4 for TBL
another to
Point Status
represent M 2-3 for TBL
the OR
Position the inputs beside
logical operator
one another to represent AND
logical operator
Figure 9-6. Logic Diagram
The example shown above can be interpreted as: If point M2-1 or M2-2 or M2-3 and M2-4 are
in a trouble state, hold on Relay 1. M2-4 is the key here. At least one of the three on the left
(M2-1, M2-2, and M2-3) must be in a trouble state AND M2-4 must also be in a trouble state.
9-4
4007ES Panel Programmer Manual (579-1167)
Custom Control Selecting the Custom Control tab from the main programmer window displays the Custom
Window Control Window shown in Figure 9-7. This window contains two halves.
• The left half lists user-defined and system-only (non-editable) programs. Click on the
+ sign to the left of an entry to expand the contents of that entry.
• The right half of the window is used for creating user-defined Custom Control
equations. With the Equation Comment text entry box you can enter descriptive text
explaining the operation of the equation. The Equations Area contains a text entry box
for creating and editing an equation’s input and output statements. The Add button
starts the Custom Control Wizard and is used to create new equations. The Edit button
is used to edit existing equations. The Taglist button starts a taglist that can be used for
selecting/deselecting points in an existing equation.
9-5
4007ES Panel Programmer Manual (579-1167)
Selecting User Note: You cannot write custom control on InfoAlarm switches and LEDs.
Program
The first step in defining a new custom control equation is to add the equation to a User
Programs.
To add a new custom control equation:
1. Right click on one of the user programs, located at the bottom of the program list, and select
Add Equation from the list of options.
The Equations section of the Custom Control window updates to include the [INPUTS],
[END INPUTS] etc, entries.
9-6
4007ES Panel Programmer Manual (579-1167)
Adding Input The second step in creating a new Custom Control equation is to add input statements to the
Statements equation. Repeat the steps in this section until all input statements in the equation have been
defined.
1. In the Equations box, position the cursor just to the right of [INPUTS].
9-7
4007ES Panel Programmer Manual (579-1167)
Adding Output The third step in creating a new Custom Control equation is to add output statements to the new
Statements equation. Repeat the steps in this section until all output statements in the equation have been
defined.
1. In the Equations box, position the cursor just to the right of [OUTPUTS].
2. Click on the Add button. The dialog shown in Figure 9-11 appears.
3. Click on the drop-down list box, select one of the output Opcodes, and click the Next button.
Opcode available: Select Item, Set/Reset Priority, Select Point.
4. The next dialogs displayed by the wizard depend on the Opcode you selected in Step 3.
Follow the Wizard’s windows to create the output for the equation.
5. The Finish button becomes available when all dialogs related to the output Opcode have
appeared. Click it to finish defining the output statement.
Floor Above/Floor This application limits the activation of NACs to the floor on which the activated initiating
Below Wizard device is located, referred to as the fire floor, and the floors immediately above and below the
fire floor.
In Figure 9-12, an activated smoke detector or pull station on Floor 3 activates the NACs on
Floors 2, 3, and 4.
9-8
4007ES Panel Programmer Manual (579-1167)
Selecting Floor 1. Start the Floor Above/Below Wizard by clicking on the Floor Above/Floor Below Wizard
Tab tab, which is located along the bottom left part of the Custom Control window.
2. Right click in the blank area above the tab. When the list of options appears, select Create
Floor Group. (The ES Panel refers to each set of floor above/below equations as a Floor
Group. This is the name of the group or area that the floor above/below program has control
over.) Enter a name for the Floor Group in the dialog that appears.
9-9
4007ES Panel Programmer Manual (579-1167)
General After you enter a name for the floor group, click Next. A dialog appears, with this dialog you
Information can specify general information about the application.
9-10
4007ES Panel Programmer Manual (579-1167)
Specifying Floor The Floor drop-down list box contains an entry for all floors (i.e., if you set number of floors to
Names 10 in the previous screen, there are 10 entries). To enter a floor's name, first click on the
drop-down list box to select the floor and then enter a descriptive label in the Floor Label text
box. Enter any comments in the Comment box at the bottom of the dialog.
Specifying Input Enter information for the other fields in this screen as follows:
and Static Points
• Alarm Points. Identifies the floor's input points (such as, detectors, pull stations).
• Non-Audio Points. Identifies the floor's non-audio (horns, strobes) notification points.
• Air ON Points. Identifies the pressurization fan and damper ON points.
• Exhaust ON Points. Identifies the exhaust fan and damper ON points.
• Air OFF Points. Identifies the pressurization fan and damper OFF points.
• Exhaust OFF Points. Identifies the exhaust fan and damper OFF points.
For each of these selections, when you click on the button, a taglist appears, with which you
can select specific points. Press the space bar to select a point. A “>>” symbol appears to the
left of the point to indicate that it is selected.
9-11
4007ES Panel Programmer Manual (579-1167)
Using the Selective Signaling is typically used to limit the activation of NACs to the area or floor on
Selective which an activated initiating devices is located. In the following example, an activated
Signaling Wizard initiating device on Floor 2 triggers only the NACs located on Floor 2.
Selecting Start the Selective Signaling Wizard by clicking on the Selective Signaling Wizard tab, which
Selective is located along the bottom left part of the Custom Control window.
Signaling Wizard Right click in the blank area above the tabs. When the list of options appears, select Create
Tab Group. (See Figure 9-19.)
9-12
4007ES Panel Programmer Manual (579-1167)
Setting General After you enter a name for the group, click the Next button. A dialog appears, with this dialog
Options you can specify general information about the application.
Setting Zone Click on the Zone drop-down list box and select the zone number. Enter a label for the zone in
Names the Signal Zone Label box. Click on Next to continue.
9-13
4007ES Panel Programmer Manual (579-1167)
Linking Initiating Using the screen shown below you can link initiating and notification points to one another. If
and Notification one of the specified initiating devices activates, only the notification appliances linked to the
Points initiating device activates.
Note: The user list is created starting from the first available user list and the number of list used depends
on the chosen configuration.
1. Click on the button labeled Alarm Points. A tag list appears. Use the up and down arrow
keys to move through the list. Use the spacebar to tag (select) a point. A “>>” symbol
appears to the left of the point when it is selected. Click OK to continue. The previous
screen appears.
2. In Notification Points in this Signal Zone, click the notification appliance you want to turn
on when the tagged initiating devices activate. The choices are: Visual Points, Audible
Points, TrueAlert Zones (Addressable), and TrueAlert Zones (Non-Addressable). A tag
list appears. Use the up and down arrow keys to move through the list. Use the spacebar to
tag (select) a point. A“>>” symbol appears to the left of the point when it is selected. Click
OK to continue. The previous screen appears.
3. You can also activate other notification signal zones when a tagged initiating device
activates. To do this, click on the Notification Zones button to the right of the Other Signal
Zones Notified label. A tag list appears. Use the up and down arrow keys to move through
the list. Use the spacebar to tag (select) a point. A “>>” symbol appears to the left of the
point when it is selected. Click OK to continue. The previous screen appears.
4. Click Next to continue. A screen showing the equations created by the wizard appears. Click
Finish.
9-14
4007ES Panel Programmer Manual (579-1167)
Using the Using the Sounder/Relay Base Wizard you can change the default operation of single station
Sounder/Relay smoke detectors. Note that the default operation—sounder activates when the alarm threshold
Base Wizard is passed and deactivates when the smoke level drops back below the threshold—is
programmed using the TPHOTO device type. To use the wizard to change the default
operation, you must assign a device type of SPHOTO or RPHOTO to the device.
1. Start the Sounder/Relay Base Wizard by clicking on the Sounder/Relay Base Operation Wiz-
ard tab, which is located along the bottom left part of the Custom Control window.
2. Right click in the blank area above the tabs. When the list of options appears, select Create
Point Group. A figure similar to appears.
Activating Base Activate base on Alarm configures the single station detectors to activate when the alarm
on Alarm threshold is reached and to turn off on either reset or silence.
1. To select this option, select the radio button labeled “Alarm—Activate Base on Alarm.”
2. If necessary, you can select a different Custom Control user program. To do this, click on the
control to the right of Program # and select the appropriate program number. Click Next to
continue.
9-15
4007ES Panel Programmer Manual (579-1167)
Activating Base 3. A dialog similar to the following appears. Select the operation for the device as either “Hold
on Alarm Device ON until Reset” (sounder or relay remains activated until reset) or “Hold Device on
until Silence” (sounder or relay remains activated until signal silence).
9-16
4007ES Panel Programmer Manual (579-1167)
Common Ground Select and utilize the LED Yellow point type for custom control ground fault LED trouble
Fault LED Control indications:
Program the Color User Interface, Point Editing Tab as follows:
HW Ref. Switch Mode Ref. Address Ref. Label HW Ref. LED Mode
Add the following custom control equation to the 4007ES IDNAC Addressable Panel:
[INPUTS]
STATUS ON
1-0-9 | CARDSTAT | CSP | POSTIVE EARTH
OR STATUS ON
1-0-10 | CARDSTAT | CSP | NEGATIVE EARTH
OR STATUS ON
1-0-27 | CARDSTAT | CSP | POSITIVE EARTH ON RUI
OR STATUS ON
1-0-28 | CARDSTAT | CSP | NEGATIVE EARTH ON RUI
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
Add the following custom control equation to the 4007ES Hybrid Panel:
[INPUTS]
STATUS ON
1-0-3 | CARDSTAT | CSP | POSITIVE EARTH GROUND
OR STATUS ON
1-0-4 | CARDSTAT | CSP | NEGATIVE EARTH GROUND
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
9-17
4007ES Panel Programmer Manual (579-1167)
Suppression This section describes how to configure Suppression Release Hazard Areas using the
Release programmer.
Introduction Suppression Release refers to the release of water or chemical agents in response to alarm
conditions. Suppression Release operation is limited to hazard areas, which are collections of
initiating devices, signaling appliances, and releasing peripherals, powered by NACs, that are
set up to respond to alarm conditions.
Suppression The 4007ES panel is capable of controlling either a preaction/deluge sprinkler system or an
Release General agent release extinguishing system.
Capabilities
• The number of hazard areas that the 4007ES panel is capable of monitoring is restricted by
the hardware and point capacity of the panel. Each hazard is defined as a separate area
containing its own 4090-9005 or -9006 releasing peripheral and solenoid.
• Table 9-1 lists the number of Notification Appliance Circuits required by each hazard area of
the 4007ES FACP.
Each hazard area requires three to five conventional or virtual NACs, depending on the use case and options selected. One
conventional NAC is required to power the Suppression Release Peripheral (SRP). The other outputs can either use conventional
NACs or Virtual Notification Appliance Circuits (VNACs). The information below describes the operation associated with the available
suppression release NAC/VNAC point types.
• The RELSIG circuit for audible notification typically consists of a horn and provides escalating cadence patterns to identify the
stage of events (i.e., first alarm, confirmed alarm, release).
• The RELWVIS circuit for visual notification is used to alert when the first stage of a cross-zoned releasing sequence occurs or when
a delayed action is used.
• The RELVIS circuit for visual notification is activated when the releasing output activates and remains on until System Reset. It can
be used in systems without cross-zoning and without a delay timer to indicate the release output activation. It can also be used in
systems with cross-zoning or a delay timer to provide a separate indication that the release output activation has occurred outside
entrances of the hazard area.
• The SUPRELS circuit controls the power to the SRP. This circuit must be a conventional NAC, not an addressable VNAC.
• The RELISIG circuit controls audible and visual notification appliances when the system is configured to have a NYC Abort
Investigation timer. Although an audible signal type, this NAC can connect sounders and strobes to the same circuit as required by
NYC requirements. The audible portion of these appliances activates on steady when the NYC investigation timer activates and
turn off when the investigation timer reaches zero. The NYC Abort option does not comply with UL 864.
• The releasing peripheral activates its output, which attaches to the solenoid, only when the
designated initiating devices and the NAC connected to the release peripheral are active at
the same time. This prevents a malfunctioning input from triggering a release.
9-18
4007ES Panel Programmer Manual (579-1167)
Suppression
Release General
Capabilities
9-19
4007ES Panel Programmer Manual (579-1167)
Suppression Suppression release device and point types are shown in the table below. Assign the applicable
Release Device device and point types to the suppression points before programming hazard area information.
and Point Types
Refer to section Programming Points inside the Online Help of the 4007ES Panel Programmer
for information on programming the points.
RELVIS Release visual SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A, L0 - Coding Group 0
circuit CHAN4B, PCHAN4A, PCHAN4B, SBZAM, L13 - Fire Alarm Visuals OFF on RESET
SAZAM, SIGIAM, NULLSIG, PS_SIGA, L49 - TrueAlert Zone OFF on RESET
PS_SIGB, MFIO_SIGA, MFIO_SIGB, L50 - Walk Test Group 0 - signals/relays
MSOUND, MSIGA, MSIGB, VNAC L139- Local Mode Operation Points
SSDUMP Shorted MONA, MONB, SMONA, SMONB, L18 - General Fire Alarm Monitor Zones
Suppression SCAN50, 4002MA, 4002MB, IAM, SECIAM, L30 - Alarm Verification Group 0
Agent Manual MAZAM, MBZAM, ADRPUL, CANPUL L61 - Coding Group 1 - Monitor Zones
Dump L139- Local Mode Operation Points
9-20
4007ES Panel Programmer Manual (579-1167)
Suppression
Release Device
and Point Types
SUPDET Suppression Agent MONA, MONB, SMONA, SMONB, L18 - General Fire Alarm Monitor Zones
Monitor Zone SCAN50, 4002MA, 4002MB, IAM, L30 - Alarm Verification Group 0
SECIAM, MAZAM, MBZAM, ADRDET, L61 - Coding Group 1 - Monitor Zones
GENIAM, NULLMON,500PSM, L139- Local Mode Operation Points
APM500, CM520, DM520, DMC520,
IHN135, IHN200, 500CMB, 500CMC,
500CMAB, 500CMAC, 500CMAD,
500CMAE, TFXCDM, 501CMB,
LPBD520, MD501, MD501EX, MD901,
MDR901,MDS901, MF401,
MF501,MF501HA, MF501EX, MF901,
MF901HA, MFR901HA,
MFS901HA,MER901, MFS901,
MR501, MR501EX, MR501T,
MR501TEX, MR901, MRR901,
MRS901, MS502EX, MU901, MU912,
S251, S252PLUS, All PHOTO Device
types, All ION Device types, all HEAT
Device types
SUPDUMP Suppression Agent MONA, MONB, SMONA, SMONB, L18 - General Fire Alarm Monitor Zones
Manual Dump SCAN50, 4002MA, 4002MB, IAM, L30 - Alarm Verification Group 0
SECIAM, MAZAM, MBZAM, ADRPUL, L61 - Coding Group 1 - Monitor Zones
CANPUL L139- Local Mode Operation Points
SUPPRES Suppression Agent MONA, MONB, SMONA, SMONB, L18 - General Fire Alarm Monitor Zones
Pressure Mon SCAN50, 4002MA, 4002MB, IAM, L30 - Alarm Verification Group 0
SECIAM, MAZAM, MBZAM L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points
9-21
4007ES Panel Programmer Manual (579-1167)
Suppression This section describes the responses of the suppression release signals.
Release Signal
Responses 1. Alarm Silence/System Reset
IDNet points:
• Manual release point: MBZAM with SSDUMP point type at address M1-11-0.
• Automatic Release Points: Two Smoke detector devices with SUPDET point types at
addresses at M1-18-0 and M1-19-0.
• Abort Switches: One IAM with point type SUPABRT at address M1-35-0.
• SRP: One SRP (RELEASE) with point type SUPRELS at address M1-36-0.
AuxNAC
• SIG3 set as SUPRELS point type.
9-22
4007ES Panel Programmer Manual (579-1167)
Timer Configurations
• Set Manual Release at 30 seconds and check the box.
• Set Detector Release Delay at 60 seconds and check box.
Specific Configuration
Abort Logic Window
• Set System Release after GREATER of Remaining Time Delay or 10 seconds.
Action Response
9-23
4007ES Panel Programmer Manual (579-1167)
Action Response
First detector is
RELISIG turns on steady.
triggered.
Specific Configuration
True Alert Zone
• SIG915 is configured as RELVIS (Releasing Visual Signal) and has at least one visual
device from the IDNAC channel.
9-24
4007ES Panel Programmer Manual (579-1167)
Action Response
First detector is
RELSIG turns on low cadence (Temporal). RELWVIS turns on.
triggered.
Abort switch is
No change.
pressed and held.
Second detector is
triggered while abort
switch is still pressed. • RELSIG goes on high cadence (March120). RELWVIS stays on.
Keep the abort switch • SRP output does not turn on including after Automatic Release Timer expires.
pressed for more than
one minute.
After 10 seconds or the remaining value of the release timer, whichever is greater,
RELSIG goes on steady. RELWVIS stays on. RELVIS goes on. SUPRELS NAC
goes on steady and SRP output goes on steady.
Notes:
• If a second alarm condition occurs while the Abort switch is still pressed, the
Abort switch is
automatic release timer resets to the value that has been configured for it. It
released
begins to count down and will stop at 10 seconds. When the abort switch is
released, the panel starts the release timer countdown at the value of the
countdown timer or at 10 seconds, whichever is greater.
• Pressing the abort switch again and releasing it, when a second alarm is
triggered, has no effect.
Specific Configuration
IDNET points
• Manual release point: MBZAM with SSDUMP point type at address M1-11-0.
• Automatic Release Points: One Smoke detector devices with SUPDET point types at
address at M1-18-0.
• SRP: One SRP (RELEASE) with point type SUPRELS at address M1-36-0.
AuxNAC
• SIG3 set as SUPRELS point type.
9-25
4007ES Panel Programmer Manual (579-1167)
Timer Configurations
• Uncheck Manual Release to set it a 0.
• Uncheck Detector Release Delay to set it at 0.
Action Response
First detector is RELSIG turns on steady. RELVIS turns on. SUPRELS NAC turns on steady and
triggered SRP output turns on steady.
9-26
4007ES Panel Programmer Manual (579-1167)
3. Right click on the blank area of the screen labeled Hazard Area.
4. Click on Create Hazard Area from the menu that appears. A screen similar to the one
shown below appears.
5. Enter a name for the hazard area in the Hazard Area Name field and enter any applicable
comments. Click Next to continue.
9-27
4007ES Panel Programmer Manual (579-1167)
Step 2. Specifying The next screen, shown in Figure 9-31, prompts you to specify the following information.
Initial Data and
Options • Custom Control Program Number. This is the program number under which the
suppression release custom control equations created by the wizard are stored. In the case of
a 4007ES FACP, Program # 3 is the only one that can be used.
• Cross Zone (Dual Detector). Check this box to enable cross-zoned (dual detector)
operation. Cross-zoned applications require that two automatic initiating devices in different
areas enter an alarm state before the releasing appliance can activate.
Note: To achieve true cross zoning, the initiating devices must be wired to either Monitor cards or ZAMs.
Dual detector operation, which requires two detectors to activate, can use TrueAlarm initiating
devices.
• First Stage Audible Notification. Click on the drop down list box and set the audible
notification appliance pattern used for the first stage of a cross-zone (dual detector) alarm.
Choices include Slow March Time, Temporal, or Fast March time*. When cross-zoned
(dual detector) is enabled, this is the audible NAC tone pattern plays following activation of
the first detector. When the second detector activates, the pattern is always Fast March. This
option is not applicable if Cross Zone (Dual Detector) check box is not selected.
* Note: Fast March time is not recommended, for example, there would be no change in pattern when
transitioning from the first stage alarm to the second stage alarm.
Click Next to continue programming when you have set these options to the appropriate
values.
9-28
4007ES Panel Programmer Manual (579-1167)
Step 3. Specifying Using the next screen you can specify the action that occurs when the abort switch is released.
Abort Switch
IMPORTANT: For all choices except the International Risk Insurers (IRI) Abort method,
Operation
pressing and holding the abort switch prevents agent release for as long as
the switch is held in, unless a Manual Release switch is operated, which
overrides the Abort Switch operation. For IRI Abort, the abort switch must
be pressed and held before the second alarm activation occurs to prevent
release.
9-29
4007ES Panel Programmer Manual (579-1167)
Step 3. Specifying • NYC Abort (Does not comply with UL 864). Pressing the Abort switch does the
Abort Switch following:
Operation • Warning bell and strobe turn on (NAC associated with RELISIG point type).
• Evacuation visuals turn off (NAC associated with RELWVIS point type).
• Evacuation audibles turn off (NAC associated with RELSIG point type).
• Automatic Release Timer countdown stops at its current value.
Releasing the Abort switch starts the 90-second Investigate Timer. When the
Investigative Timer expires, the following occurs:
• Warning bell and strobe turns off
• Evacuation visuals turn on
• Evacuation audibles turn on at 120 BPM
• Reload the Automatic Release Timer with the programmed value
If the abort switch is pressed and released after the second alarm while the investigation
timer is running, the investigation timer does not reset and continues to countdown until
it reaches zero. When the investigation timer reaches zero, the evacuation visuals and
audibles turn back on and the automatic release timer begins to countdown. If the abort
switch is pressed and released again while the automatic release timer is running, a new
full cycle of investigation and automatic release delay starts.
Step 4. Setting Using the next screen you can set values for the Manual Release, Detector Release, and the
Timer Options Releasing Cutout.
9-30
4007ES Panel Programmer Manual (579-1167)
Step 4. Setting Use the following guidelines when setting these values:
Timer Options • Manual Release. The Manual Release Time Delay is a programmable timer that specifies
the delay between the activation of a manual release switch and the activation of releasing
appliances. The default setting for this timer is 10 seconds. A setting of 0 causes the
releasing appliances to immediately activate after a manual release switch activates. This
delay is programmable from 0-30 seconds.
• Detector Release Delay. The Automatic Release Time Delay is a programmable timer that
delays the activation of the releasing appliance circuits. This timer starts immediately after
receiving a confirming alarm (cross zoned system) or a first alarm (single alarm system).
When the timer expires, the releasing appliances activate (assuming the abort switch is not
active). This delay is programmable from 0-60 seconds.This delay makes evacuation of the
protected space possible before the agent is released. Consider a delay timer when occupants
could be present in the protected space.
• Cross-Zoned System. The occupants receive a warning signal of the first alarm and
receive an evacuation signal on the second alarm. Implementing a warning signal
makes it possible to investigate the alarm before the second (confirmed) alarm.
Implementing a delay on the second alarm gives time for occupants to evacuate, and
where required, for the ventilation fans and dampers to shut down prior to the release
activation.
• Single Alarm System. A selection of “0” seconds activates the releasing circuit at the
same time as when the NACs signal an initial warning. A delay provides time for
occupants to evacuate, and where required, for the ventilation fans and dampers to shut
down prior to the release activation.
• Releasing Cutout. The Releasing Cutout Timer is a programmable timer that specifies the
length of time the output on the Suppression Release Peripheral is held on. When the timer
expires, the solenoid turns off (or cuts out), which stops the water flow or release of the
extinguishing agent. This option is typically used on Deluge systems and is not intended for
use with all releasing systems and releasing devices. A selection of “0” means the solenoid
does not “cut out” and remains on until the system is reset. The Countdown Timer is
programmable from 0-30 minutes.
Step 5. Specifying The next screen, shown in Figure 9-34, contains seven buttons, each corresponding to one of
Hazard Area the suppression-release system lists. Points are automatically assigned to the appropriate list
Points based on the suppression release point type assigned to the point.
9-31
4007ES Panel Programmer Manual (579-1167)
Step 5. Specifying Each button accesses a tag list, with this you can select (tag) the specific points to associate
Hazard Area with the hazard. Follow these steps to tag points:
Points
1. Click on the button corresponding to the type of suppression points you want to select. The
TagList screen shown in Figure 9-35 appears.
2. The TagList screen displays all points with the relevant suppression release point type. To
select a specific point for inclusion in the hazard area being programmed, click on the point
to highlight it and then press the space bar.
3. Click OK when you are finished selecting points. The screen containing the Tag List buttons
(Figure 9-34) reappears. Click Next when all points associated with this hazard area have
been chosen.
9-32
4007ES Panel Programmer Manual (579-1167)
Step 5. Specifying Review the options selected for the hazard area using the screen shown in Figure 9-36. Use the
Hazard Area scroll bar to check the selections for all options. If necessary, click Back to return to one of the
Points option selection screens to change a choice. When all of the options are set correctly, click
Finish.
When you click Finish, an icon and label appear in the list of hazard areas shown in Figure 9-
37.
9-33
4007ES Panel Programmer Manual (579-1167)
Editing Existing Existing hazard areas can be edited in the following ways:
Hazard Area
• Using the Wizard. Right-click the name of an existing equation (see Figure 9-37) and select
Edit Hazard Area. The wizard screens reappear in sequence. Reselect the options for the
hazard area as necessary.
• Properties. Right click on the name of an existing equation and select Properties. A
properties sheet, containing a series of tabs across the top, appears. Each tab corresponds to
one of the groups of suppression options. Click on each tab and reselect the options for the
hazard area as necessary.
• Custom Control Equations. Right click on the name of an existing equation and select
Manual Edit. Edit the Custom Control equations using Manual Edit, this eliminates the
ability to use the wizard to edit the equations. After selecting this option, click on Custom
Control subtab on the far left at the bottom of the Custom Control window. Select the
program containing the hazard area's equations.
9-34
4007ES Panel Programmer Manual (579-1167)
Scheduling Select the following options in the Self-Test Wizard to set up one or more schedules to run the
Options for scheduled self-tests:
Self-Test Wizard • Frequency
• Day
• Time
• Triggering pseudo point
Note: An automatic self-test can be launched from the TSW instead of the FACP. The pseudo point is a
trigger to execute the scheduled self-test. The triggering point is optional. The purpose is to select a
digital pseudo point to launch a scheduled self-test by overriding the usual date and time condition.
For example, a public TSW digital point can be added to the job as external point and used to trigger
a self-test. The user can run an automatic self-test at any time and on multiple panels at the same
time.
Important: The system pseudo point P503 RUN SCHEDULED SELF-TEST cannot be used
as a triggering point. Doing so will lead to unpredictable behavior.
After configuring the date and time select the following options:
• List of SIGs
• Volume
• Trouble on fault
9-35
4007ES Panel Programmer Manual (579-1167)
Step 1. Creating a 5. The next screen, shown in Figure 9-41, specifies the Custom Control Program Number.
New Self-Test This is the program number under which the self-test custom control equations created by
the wizard are stored. No specific program number is reserved for use by Self-Test
equations. Click Next.
Figure 9-42. Self-Test Time and Recurrence (Weekly Configuration Shown as an Example)
9-36
4007ES Panel Programmer Manual (579-1167)
Step 3. Selecting 1. In Self-Test Triggering Point, click Select Pseudo Point to choose a pseudo point that will
Self-Test be used to activate Self-Test (Figure 9-43).
Triggering Point
2. Inside Self-Test Options, click Select Point List to choose the points list for Self-Test.
and Point List
In Volume select whether horns on sounder devices will be disabled during Self-Test.
In Trouble on Fail select yes or no to choose if a trouble will be generated if self-test fails.
Click Next.
3. In the summary screen that appears, ensure that all of the settings are configured correctly
and click Finish to complete the Self-Test Wizard. Table 9-7 lists all the default values for
the Scheduled Self-Test Wizard.
Two options: Two options for the user to select Input validation required. A Self-Test
Yearly • First of January between the date or day of the schedule with the wizard will be
• First Sunday of January week. executed at least once a year.
Triggering Point and Triggering or point list not User cannot continue to next page if
Self-Test Options selected by default a point list is not selected.
Volume NORMAL
Trouble on Fail NO
9-37
9-38
Chapter 10.
File Transfer
Introduction There are two methods of performing file transfer in the 4007ES. The preferred method is to
use a USB portable storage device (also called thumb drive, key, memory stick, etc.) to
transfer files between the 4007ES USB port and the service PC. The secondary method is by
connecting a cable between the Ethernet port and the service PC. Both methods are explained
in this chapter.
For the 4606-Series Color Touchscreen LCD Annunciator, the preferred file transfer method is
also to use USB portable storage device. Partial file transfer can also be performed using the
RUI addressable connection to the panel, but the transfer speed is slower.
10-1
4007ES Panel Programmer Manual (579-1167)
Note: To check which Master BIN file is running in the panel, press the Menu button on the panel, then
browse to System Info and then to Software Revisions. The Master BIN file version appears on
the 4007ES panel display and it is different from the 4100ES and 4010ES.BIN files.
4. Save the job, build it, and then re-open it using the most recent version of the Programmer.
5. Click on the Transfer menu option and then on USB.
6. In the USB Transfer window (Figure 10-1), click CFIG, Panel Exec and Include Binary
Files checkboxes and make sure the files are attached.
Note: Selecting the Panel Exec and Include Binary Files makes it possible for the USB transfer to
select the correct panel bootloader, kernel, file system, panel UI slave and other listed slaves in the
compatibility file (on the USB key /bins/compatibility.xml).
10-2
4007ES Panel Programmer Manual (579-1167)
USB File Transfer 8. Disconnect the USB storage device from the PC and insert it into the USB port located on
the CPU board that is mounted on the inner door panel of the 4007ES. Files that need to be
updated are flagged for an upgrade on the panel display (Figure 10-2).
10. When prompted, press the button to take a snapshot of the existing panel software to
be able to go back to the original files, if necessary.
11. After the panel reboot, press on the System Upgrade button to verify that no software is
marked for an upgrade and disconnect the USB storage device by pressing the Eject USB
button located under the Mass Storage.
The panel has now been upgraded with a new job and the latest software.
Files Transferred The following is an example of the files that can be transferred using a USB storage device:
File Description
10-3
4007ES Panel Programmer Manual (579-1167)
IP File Transfer
IP File Transfer IP file transfer operates over the Ethernet service port, with files directly copied to the file
system and activated. New Slave Exec data is then downloaded by the master once it is
running.
File Transfer The Ethernet service port is located on the CPU board behind the inner door assembly
Connection to the (see Figure 10-3) and connects to the Service PC using a standard straight (non-crossover)
PC Ethernet Patch Cable. Service Mode Jumper P7 must be connected for this operation which
causes a Service Trouble condition. After, move the jumper to only one pin to disconnect and
retain the jumper for future use.
Service Mode
Jumper P7
Starting the IP This feature enables a download of the Fire Alarm Control Panel (FACP) software features
File Transfer (Panel Exec, Slave Exec, etc.). This provides a means for recovering previous configurations
Utility (via the File Transfer “History/Undo” tab). This also makes it possible for the FACP to
continue operating during file download operation. FACP down-time is minimal.
The ES Panel IP File Transfer utility can be started from within the ES Panel Programmer or
from the Windows Start menu. To start the File Transfer:
• From within the Programmer. While the programmer is running, click on the
Transfer icon, located along the menu bar at the top of the programmer window. When
the options appear, click on Local Panel.
When start-up procedure has been completed, the File Transfer Utility appears.
10-4
4007ES Panel Programmer Manual (579-1167)
IP Communication Click on the Settings button near the top of the IP File Transfer Window to access the Settings
Parameter Window. The settings window shows you the IP address the program is currently using, you to
Settings change it if necessary.
Downloadable The following types of files can be downloaded to the ES Panel FACP through its file transfer
Files utility.
• CFIG File. This is the built job file, consisting of all programming definitions in a
binary format, that the panel's CPU can execute.
• Slave Exec. Module-specific slave Exec files execute on intelligent slave modules
(listed below) and define the way in which the slave module operates. Occasionally,
changes to the functionality of a slave module may require you to download a new
slave Exec file. (For example, a change to the IDNet Slave Exec file may be necessary
to provide support for new, additional device types.) The following 4007ES modules
are “intelligent” slave devices that use a module-specific Slave Exec file.
• CFIG Text File. A panel with a missing or corrupt CFIG file can be restored to proper
operation by downloading a CFIG text file to the panel. The CFIG text file is
automatically built and placed in the same job directory as the “executable” CFIG file
(file ending in .CFG extension).
• Panel Exec (Master). The Panel Exec file is the “operating system” that runs on the
panel’s CPU module. It manages interactions between system components.
Occasionally, changes to the functionality of the operating system may require that a
new Panel Exec file be downloaded.
10-5
4007ES Panel Programmer Manual (579-1167)
Download Tab By default, the IP File Transfer window opens to the Download tab.
10-6
4007ES Panel Programmer Manual (579-1167)
Download Tab 1. To download a software feature, make sure the Service Mode (Jumper 7) is enabled.
Select the type of file you want to download by clicking on the radio button next to the file
you want to download. The options are:
• CFIG and all Execs
• CFIG
• Slave Exec
• Panel Exec
• CPU Bootloader
• Primary Msglib
• Alternate Msglib
IMPORTANT: Selecting the CFIG and All Execs option makes it possible for the
IP Transfer to download the correct panel bootloader, panel UI slave
and other slaves to the panel, in addition to the job.
2. Once the selection has been made, use the checkboxes to select the download options:
• Download to a running panel: Select this option to download the file to a running
panel. Once this option is selected, there are 3 ways in which the changes can be
applied:
- Automatically after the download. Select the "Apply download changes after
download" box to have the downloaded changes applied immediately after the
download. This is the program’s default setting.
- When the system reboots: If the "Apply download changes after download" button is
not selected, the downloaded changes will be saved and applied once the system is
rebooted.
• Exclude the recovery file. This box option can be used when downloading a CFIG, it
will result in a faster download.
• Preserve current Install mode list: Select this box to keep all the points you have
placed in install mode in install mode once downloaded changes have been applied.
This is highly recommended.
3. Use the File name box to select the file you want to download to the panel.
4. Click on the Download button to start the process.
The following are additional functions accessible from the Download tab:
• View Final Status of Last Panel Update: Click on this button to bring up the final status of
the last panel update.
10-7
4007ES Panel Programmer Manual (579-1167)
Upload/Reports The default option for this feature is to upload the job that is currently running in the FACP.
Tab The file that is uploaded is a compressed image of the programmer job file. Therefore, there is
no need for an “unbuild.” The file is uploaded to its default location.
(C:\4100UJOBS\JobName). This tab also has options for uploading all FACP reports. The
reports are uploaded to the “reports” subdirectory of the current job directory. The report file is
given a descriptive name, appended with the current date (e.g., AlarmLog_2010_3_11.txt).
10-8
4007ES Panel Programmer Manual (579-1167)
Type of Transfer In addition to the upload of the CFIG file, other types of information from the Panel can also be
uploaded to the ES Panel Programmer.
10-9
Chapter 11.
Port Vectoring
Introduction The term port vectoring refers to the way in which certain cards can be programmed to output
only specific groups of events. This section describes programming the ES Panel's port
vectoring option.
Note: User editing of the DACT port vectoring is not permitted in UL 864.
11-1
Chapter 12.
AMON Point Type
Introduction This chapter describes creating custom point types (referred to as AMON point types) for use
with analog monitor ZAMs. These point types allow descriptive text and device-specific
settings to be associated with a point name.
AMON Pt Type The AMON Pt Type tab (Figure 12-1) is for use only with IDNET analog monitor ZAMs. It
Tab allows you to create a custom point type that specifies how the ES Panel system should
interpret (i.e., react to) incoming analog data from the device attached to the ZAM. This point
type can then be assigned to the ZAM using the IDNET point editing screen, which is
accessible through either the Hardware or Point tab. For example, if you have an analog
device that measures the amount of liquid within a tank, you can use this tab to create a point
type that specifies what the unit of measurement is (gallons, for example) and what the
threshold values for an alarm should be (generate an alarm when the tank is half empty, for
example).
12-1
4007ES Panel Programmer Manual (579-1167)
Adding a Point The AMON Point Type Tab uses a wizard-style interface that guides you through the process
Type of creating an AMON point type.
1. To start this wizard, right click in the blank space just below the Point. When the menu
appears, click on Add. A dialog similar to the one shown in Figure 12-3 appears.
FIRE Causes the system to generate a fire alarm when the device crosses the
threshold.
Creates a latching supervisory condition when the device crosses the
LATSUPV threshold. This means that the supervisory condition on the panel does
not clear until the point restores to normal and a system reset is
performed.
MPR12 Generates a priority 2 alarm when the device crosses the threshold.
12-2
4007ES Panel Programmer Manual (579-1167)
Adding a Point 3. Click the Next button to view the dialog shown in Figure 12-3.
Type
Field Description
The “unit” (ppm, gal, psi, etc.) text that appears on the front panel display
Eng Unit Text when you display the current value of the device via the front panel. For
example, if a monitor device with a monitoring capability of parts per
million is attached to the ZAM, you might put ppm in this field.
4mA Value This is the lowest value that the device reports. When the device is at this
value, it draws 4mA of current from the ZAM.
20mA Value This is the highest value that the device reports. When the device is at
this value, it draws 20mA of current from the ZAM.
5. Click the Next button. A dialog similar to the one shown in Figure 12-4 appears.
12-3
4007ES Panel Programmer Manual (579-1167)
12-4
Chapter 13.
Adding or Editing Network Information
Introduction This chapter describes the following network-related procedures.
In this chapter Role of the Network Programmer .................. 13-1 Public Versus External Points ........................ 13-1
General Network Programming Guidelines... 13-1 4007ES Programmer Network tab................. 13-2
Gaining Access to the Network Information . 13-3 Editing the Network Name and Node Number13-4
Procedure to Declare Public Points................ 13-5 Procedure to Declare External Points ............ 13-5
Programming Network Alarm Silence........... 13-6 Programming Central Network Silence ......... 13-7
Programming Distributed Network Silence ... 13-8 Programming Central Network Reset............ 13-9
Programming Distributed Network Reset.... 13-10 Distributed Configuration ............................ 13-11
Role of the Programming a network of 4007ES FACPs requires the use of two programmers, as follows.
Network • Simplex New Network Programmer. Use this programmer to create a new network or edit
Programmer an existing network. Opening an existing network job with the network programmer
spawns the ES Panel programmer, which can then be used to declare the public and external
points for that node.
• ES Panel Programmer. The ES Panel programmer works along with the Simplex Network
Programmer. It allows you to specify the panel's public points, external points, and Node
numbers.
Public Versus A public point is a point connected to this panel that you want to be visible to other nodes on
External Points the network. In other words, when the status of the point changes, you want it to annunciate its
status on the other node. There is no limit to the quantity of public points for 4007ES network
panels.
An external point is a point on another node. Declaring it to be an external point allows its
status to be annunciated on this panel. The 4007ES supports up to 100 external points.
For example, when you want changes to the status of the panel’s points to report to a central
annunciator, such as a TSW, you would use the ES Panel programmer to declare the panel’s
points (or a subset of its points) public. Likewise, on the TSW, you would declare the panel’s
points as external.
13-1
4007ES Panel Programmer Manual (579-1167)
General Network • Do not make an NDU point Public above offset 1535. This only applies to the 4100+.
Programming • Never set the value of an External Analog Pseudo Point through the Network.
Guidelines
• Do not use P210, P211 or P212 at the same time for Network System Reset.
• Use P217 for Network Signal Silence.
• Avoid Version Mismatch. If you change a label or device type or point type on a point that is
EXTERNAL to other nodes, you must build and download all nodes that have an external
copy of the point. If you change the Job Title in the General Info screen, or the Network
Prefix in the Network Points in the Info Screen, you must build all nodes and download all
nodes.
4007ES The Network Tab provides access to the dialogs used to add and edit the lists of public and
Programmer external points. Click on the Network Tab to see the screen shown in Figure 13-1.
Network tab
13-2
4007ES Panel Programmer Manual (579-1167)
Gaining Access The network information fields are contained within the Panel tab. To access these fields, do
to the Network the following:
Information
1. Click on the Network tab, shown in the upper right corner of Figure 13-2.
2. Click on the Network Information subtab on the bottom left of the window.
13-3
4007ES Panel Programmer Manual (579-1167)
Editing the The Network Information tab includes the following fields. Use the guidelines outlined in the
Network Name table when setting these fields.
and Node Number
Field Guidelines
Advanced Network Click on the Advanced button and use the dialog that appears to change the network
Network to which the 4007ES panel is assigned.
Information
Node Click on the Advanced button and use the dialog that appears to change the node
number of the 4007ES panel.
Master Select to use this panel as the network’s master timekeeper. Only one master
Timekeeper timekeeper per network.
Annunciate Select if you wish to have other panel’s common trouble messages annunciated on
Common Troubles this panel.
Annunciate Network Select if you wish to have this panel’s Network messages sent to the system’s
Troubles annunciators.
Annunciate Extra The Annunciate Extra Node Option prevents a node from annunciating an Extra
Node Troubles Node Trouble following the addition of a new node. Guidelines for setting this option
are as follows:
• Unselect this option on nodes without a need to annunciate events from the new
node.
• Select this option on the node that functions as the network's central annunciator.
Auto Gen List When selected, this option adds the external points from other nodes to the system
Externals lists on this node. When it does this, it adds the points to the list based on the point
type of the point.
Miscellaneous Network Prefix Enter descriptive text in this field. This text appears when the more info. field is
Network selected on a TSW.
Information
Special Analog Checking this option prevents analog detectors from sending status on initialization if
Initialization the value is not an alarm or trouble condition. However, if the analog value indicates
an alarm or trouble condition exists, the detector will send its state.
If you select this option and you have Custom Control equations that contain the
Compare Opcode and Current Value qualifier, be aware that the equation will not
trigger on network initialization, but will trigger on subsequent value changes. Also, if
analog detectors have a numeric value on a GCC screen, the screen will not update
until the point's value changes after network initialization.
Note: To avoid Network Initialization troubles, all network nodes must be set the same
way.
Inhibit Priority-Only This option prevents network EQBs from being generated for status changes that
EQBs only affect priority and not the status of the point. For example, a Custom Control
equation triggers that modifies the priority of a public control point, putting the point to
the reset priority but not changing its state. If this option is selected, no EQB will be
generated. The side effect of choosing this option is that there will be a display
mismatch of the priority between the owner and the external node.
Inhibit Sounder- This option prevents TrueAlarm sounder/relay base (non-combo points) from
EQBs generating network EQBs when only the status of the sounder/relay changes. If the
sounder/relay is turned on or off without a threshold or logical state change on the
sensor portion of the device, no EQB will be generated to external nodes. Status
changes to the device that involve a logical status change (e.g. alarm, trouble), or a
sensor threshold level change will still report.
13-4
4007ES Panel Programmer Manual (579-1167)
Procedure to Use the following procedure to define the panel’s public points.
Declare Public
1. Click on the Network tab shown in the upper right corner of Figure 13-1.
Points
2. Right click on the Public Points folder and select the Edit Public choice. The tag list is
shown in Figure 13-3.
3. Position the highlight on a point and press the space bar to tag the point. A >> symbol is
shown to the left of the point to indicate that it is selected. (To remove this symbol and
deselect a point, highlight the point and press the space bar again.)
To select a contiguous group of points, click on the first point in the group, press the SHIFT
key and click on the last point in the group you want to select.
Procedure to Use the following procedure to define the panel’s external points.
Declare External
1. Right click on the External Points folder and select the Edit Externals choice. The dialog
Points
shown below appears. Click on the drop down list box and select the number of the node
containing the points you want to declare external.
13-5
4007ES Panel Programmer Manual (579-1167)
Procedure to 2. Click OK. The tag list shown in Figure 13-5 appears. This taglist contains all of the points
Declare External that are currently declared public on the node selected in Step 1 above.
Points
3. Position the highlight on a point and press the space bar to tag the point. A >> symbol is
shown to the left of the point to indicate that it is selected. (To remove this symbol and
deselect a point, highlight the point and press the space bar again.)
To select a contiguous group of points, click on the first point in the group, press the SHIFT
key and click on the last point in the group you want to select.
Programming The sections below describe programming Network Silence and Network Reset. These options
Network Alarm can be configured to work in either of the following ways:
Silence
• Central Network Silence and Reset. With this type of configuration, only one node
(known as the Central Network Silence/Reset Node) is capable of initiating a Network
Silence or Network Reset.
• Distributed Network Silence and Reset. This setup allows a Network Silence or Network
Reset to be initiated from any node on the network.
13-6
4007ES Panel Programmer Manual (579-1167)
Programming Any 4007ES node can be configured as the Central Network Silence Node. Programming
Central Network Central Network Silence does not invalidate inhibit and cutout timers on each node. Each node
Silence handles these functions locally. The figure below provides an overview of Central Network
Silence. In this figure, Node 1 serves as the Central Network Silence Node. Each node’s P217
pseudo has been declared external on Node 1 and L106 on this node has been edited to include
the external points.
Node 3
Public
P217
1. Open the network job, using the network programmer. Open the job for the node you have
designated as the Central Network Silence Node.
2. When the ES Panel programmer appears, click on the Network tab at the top of the
programmer. When the Network window appears, click on the Network Points subtab at the
bottom of the Network window.
3. Right click in the Network window. When the choices appear, click on Edit Externals. A
dialog similar to the following appears. Click on the drop down list box and choose one of
the nodes on the network.
13-7
4007ES Panel Programmer Manual (579-1167)
Programming 4. Click OK to close the dialog. When you do this, a tag list containing the public points from
Central Network the selected node appears. Click on P217 Network Signal Silence and press the space bar to
Silence select the point. Click OK to close the taglist.
5. Repeat Steps 3 and 4 for every node on the network.
6. Click on the List tab at the top of the programmer. When the List window appears, click on
the General List subtab at the bottom of the window. Scroll through the list, right click on
L106 - External Alarm Silence Points and select Tag List.
7. Click on the Filter icon at the top of the Tag List. When the list of choices appears, click on
the Network Externals check box. Click on the OK button. All of the External Points
appear.
8. Click on each entry for P217 - Network Signal Silence (each node on the network should
have an entry) and press the space bar to add the entry to L106. N:P217 represents the Node
Number.
Programming This setup allows a Network Silence to be initiated from any node on the network. The figure
Distributed below provides an overview of Distributed Network Silence. In this figure, each node's P217
Network Silence pseudo has been declared external on the other nodes and L106 on each node has been edited to
include the external points.
To configure Distributed Network Silence, follow the steps in section “Programming Central
Network Silence” of this chapter for each node. Repeat Steps 3 through 7 for every node on the
network.
13-8
4007ES Panel Programmer Manual (579-1167)
Programming Note: 1. Do not reset a Node using Central Network Reset if you cannot see all the alarms associated to
Central Network that node. When reset is pressed, P210 goes ON in every node it can reset. If the node where
reset is activated has no alarms, it immediately turns ON the P211 pseudos on all nodes. However
Reset
the system in alarm is not ready for this and latches.
2. If a TSW has a UT connected to it, put P210 of the UT into L0 to reset the UT.
Any 4007ES node can be configured as the Central Network Reset Node. Keep the following
in mind when programming Central Network Reset.
• This application performs separate internal Detector Reset and System Reset.
• All General Alarm Points must be monitored and SMPL-controlled by the Central Node.
• System Points involved:
- P210 Network Detector Reset/L103 External Detector Reset Points
- P211 Network System Reset/L104 External Control Reset Points
13-9
4007ES Panel Programmer Manual (579-1167)
Programming 11. Click on the Filter icon at the top of the Tag List. When the list of choices appears, click on
Central Network the Network Externals check box. All of the External Points appear.
Reset 12. Click on the entry for P211 and press the space bar.
13. Repeat Steps 10 through 12 for every node on the network.
13-10
4007ES Panel Programmer Manual (579-1167)
Programming 5. Click on the List tab at the top of the programmer. When the List window appears, click on
Distributed the General List subtab at the bottom of the window. Scroll through the list, right click on
Network Reset L105 and select Tag List.
6. Click on the Filter icon at the top of the Tag List. When the list of choices appears, click on
the Network Externals check box. All of the External Points appear.
7. Click on every entry for P212 and press the space bar to add the entry to L106.
8. Repeat Steps 3 through 7 for every node on the network.
Distributed The digital pseudo points P463 and P464 are used to raise a trouble when a CO sensor is within
Configuration 6 or 12 month of its expiration date. A transition from off to on of the digital pseudo point will
trigger a check on all CO sensors within the local panel. On site, where multiple panels are
linked together over the network, it is possible to synchronize the 2 digital pseudo points on
every node. To do so, the remote node must declare the local node’s P463 as External, since
P463 and P464 are always public by default. Once P463 is imported to the remote node’s job,
its L170 is automatically updated to include the imported digital pseudo point. The same
applies to P464 and L171. So when the remote node P463 is turned on, default SMPL equation
0-164 will turn the local node’s P463 to on. To declare an external point, refer to the section
“Procedure to Declare External Points” in this chapter.
Node 1
L170
2:P463
3:P463
4:P463
L171
2:P464
Node 4 3:P464 Node 2
L170 4:P464 L170
1:P463 1:P463
2:P463 3:P463
3:P463 Node 3 4:P463
L171 L170 L171
1:P464 1:P463 1:P464
2:P464 2:P463 3:P464
3:P464 4:P463 4:P464
L171
1:P464
2:P464
4:P464
13-11
Appendix A.
ULC Programming Requirements
Introduction This appendix describes ULC programming requirements.
In this chapter
Required Operations..............................................................................................A-2
Alarm Cutout Timer Feature.................................................................................A-4
Releasing Specific Controls and Indications.........................................................A-7
A-1
4007ES Panel Programmer Manual (579-1167)
Required Operations
Introduction To comply with ULC standards, there are indicators and a key that must be programmed and
labeled, as outlined in this section. The LED indicators required are for Manual Evacuation,
Ground Fault, and AC Power On. User Button 1 is designated as the Manual Evacuation key.
Procedure For ease of programming, there is a check box in the Card Properties section of the Color
User Interface properties. Follow the steps outlined below to program the ULC required
items.
1. Click the Hardware tab and expand the Unit 0, Box 1, Bay 1, and Block A icons to display
the Color User Interface icon, see Figure A-1. Click the + signs to the left of the Unit 0, Box
1, Bay 1, and Block A icons to expand them.)
2. Right click the Color User Interface icon (highlighted in Figure A-1) and select Properties.
3. Click check box S527 Operation, as shown in Figure A- 2.
4. Click OK to close the dialog box.
A-2
4007ES Panel Programmer Manual (579-1167)
Procedure
Figure A- 2. Color User Interface Properties with S527 Operation Check Box
Note: In compliance with ULC requirements, the slide-in label for LEDs on the user interface must be
labeled as shown in Figure A- 3.
A-3
4007ES Panel Programmer Manual (579-1167)
Introduction To comply with ULC standards when using the Alarm Cutout Timer feature, there must be a
yellow LED dedicated to indicate when the timer has expired.
Note: The LEDs adjacent to the LCD must be used for other ULC indication requirements, therefore the
inclusion of the Alarm Cutout Timer feature will require the additional LED Module (4007-9805).
Programming the Step 1: Assigning a digital pseudo point for the LED.
LED
1. Click the Point tab.
2. Scroll until the points with the Digital device type are visible. Select a point which has an
empty custom label field. (For purposes of demonstration, pseudo point P700 has been
selected.)
3. Right click on the point selected and select Properties.
4. Enter the description in the custom label field, as shown in Figure A- 4.
5. Click OK.
1. Review Chapter 8 of this manual for the process of creating Custom Control equations.
2. Create the equation shown below in Figure A-5, which turns the assigned pseudo point
ON when the Alarm Cutout Timer expires.
3. Create a second equation, shown in Figure A-6, which turns the assigned pseudo point
OFF when a subsequent alarm resounds the signaling devices and when the system is
reset.
A-4
4007ES Panel Programmer Manual (579-1167)
Programming the
LED
1. Review the section detailing how to program the LED module, see Chapter 6.
2. Select a YELLOW LED to program. Set the Mode to ON and set the Reference Address to
the pseudo assigned in Step 1, as shown in Figure A-7.
3. Click OK.
A-5
4007ES Panel Programmer Manual (579-1167)
Programming the
LED
A-6
4007ES Panel Programmer Manual (579-1167)
Introduction To comply with ULC standards when using the 4007ES for releasing service, program a Pre-
Discharge red LED, a Discharge red LED, and the abort switches to cause a system trouble
when activated (UL864 requires a system supervisory which is default). You may need to
program a Releasing Service Signal Silence button with yellow LED. If your releasing job
includes abort switches, you are required to program an abort trouble LED.
Notes: 1. Since the LEDs adjacent to the LCD must be used for other ULC indication requirements, the
inclusion of releasing service in the panel requires the additional LED Module (4007-9805).
2. If you have multiple Hazard Areas, repeat the steps below for each Hazard area as required.
Label the insert for the LEDs appropriately to identify the function and the hazard zone that is
being referred to.
Pre-Discharge A Pre-Discharge LED Programming (Red LED) is required for every Hazard Area.
LED The Pre-Discharge LED activates whenever the system is in the Pre-Discharge State. The LED
Programming will be off when the system has discharged.
(Red LED) An example program follows.
1. Open the suppression releasing wizard for that hazard and write down the list number
created for Manual Release Points and Automatic Release Points (L268 and L269 in this
example).
2. Pick any available digital pseudo point (P720 in this example) and program it to turn ON
whenever a point in the lists from step 1 are detected going active.
A-7
4007ES Panel Programmer Manual (579-1167)
Pre-Discharge 3. Write an equation to turn off the LED when the zone releases.
LED
Programming
(Red LED)
4. Write (or add to an existing equation) the equation to turn off the digital pseudo during
system startup or upon system reset.
5. Choose an available RED LED on the LED Module (under the Hardware tab in the
programmer) and set its mode as "ON" and set the reference address to the list that was
assigned.
A-8
4007ES Panel Programmer Manual (579-1167)
Discharge LED Discharge LED Programming (RED LED) is required for every Hazard Area.
Programming The Discharge LED activates when the suppression release device is in the released state
(RED LED) (solenoid is activated). The LED clears upon system reset or when the solenoid is deactivated.
Below is an example program.
1. Click the Custom Control tab.
2. Click the Suppression Release Wizard subtab.
3. Right-click the title (next to the wizard graphic) and select Properties to open the Hazard
Area.
4. Select the Points tab and write down the List assigned to Suppression Dump Points.
5. Choose an available RED LED on the LED Module located under the Hardware tab. Set its
mode as "ON" and set the reference address to the list that was assigned.
A-9
4007ES Panel Programmer Manual (579-1167)
Abort Switch Program a LED to display that an abort switch is active in a hazard area. The LED will be on
Active whenever an abort is activated in during a releasing service alarm. It will not turn on during
normal supervisory conditions.
1. Open the digital Pseudo Point list and look for a digital pseudo point created by the
Suppression Release Wizard called SupRel Abort Switch Activate- yourhazardname. It
should be towards the end of the list as the wizard just selects the next available digital
pseudo point.
2. Choose an available Yellow LED on the LED Module located under the Hardware tab. Set
its mode as "ON" and set the reference address to the digital pseudo point that was assigned.
Abort Switch This programs the panel such that an abort switch causes a trouble when activated during
Trouble during normal supervisory conditions. If the hazard area enters alarm while the abort switch is
Normal pressed, or the abort switch is activated while the hazard area is in alarm the abort switch will
Supervisory behave normally.
Conditions
In order to program the Abort Switch Trouble During Normal Supervisory
Conditions function, disable the Suppression Release Wizard in custom
IMPORTANT: control. The equations stay in custom control but you are not able to edit them
through the wizard. Any future changes to the hazard area will need to be
manual.
1. Change / Program the abort IAMs type from SUPABRT to a UTILITY point type in the
Hardware tab for the IDNet devices. These IAMs should have already been assigned to the
Hazard Area in the Suppression Release Wizard. If not, assign them now.
A-10
4007ES Panel Programmer Manual (579-1167)
Abort Switch 2. Configure three unused digital pseudo points to be used as two new troubles and a
Trouble during supervisory point. Label them as follows (change HAZNAME to the appropriate label for
Normal your hazard area):
Supervisory
Conditions
3. In the Suppression Release Wizard that you are working on, right click the title (next to
the wizard graphic) and select Properties to open the Hazard Area.
4. Select the points tab and write down the lists assigned to Abort Switches and Automatic
Release Points.
A-11
4007ES Panel Programmer Manual (579-1167)
Abort Switch 6. Click the List tab in the Programmer and right click the list for the abort switches made
Trouble during during step 3 and select where used to show all the custom control equations this list is
Normal referenced in.
Supervisory
Conditions
Find these equations in the custom control user equations and whenever the abort switches
list is referenced for status SUPV, change it to ABNORM. For example:
7. Add a HAZNAME - Abort Switch Trouble equation to annunciate troubles from this abort
switch as shown below when the hazard area is not in alarm. Use the lists you wrote down
from above as the input lists and the trouble digital pseudo point you created with the Abort
Active - No Alarm as the output.
8. Add a HAZNAME - Abort Switch Short Circuit equation to annunciate short troubles
from this abort switch as shown below. Use the abort list you wrote down from above as the
input lists and the trouble digital pseudo point you created the Abort Switch Short as the
output.
A-12
4007ES Panel Programmer Manual (579-1167)
Abort Switch 9. Add a HAZNAME - Abort Switch Supervisory equation to annunciate a supervisory when
Trouble during the abort switch is activated in alarm as shown below. Use the lists you wrote down from
Normal above as the input lists and the supervisory digital pseudo point you created the Abort
Supervisory Switch Active as the output.
Conditions
Releasing Service The Releasing Service Signal Silence button (and Yellow LED indicator) is used instead of a
Signal Silence silence for all systems that contain releasing and standard evacuation zones. The separate
Programming - silence LED is used to ensure that someone trying to silence the evac zone does not
Optional inadvertently silence a releasing zone thereby disabling the warning of a possible toxic release.
(Pushbutton and When this feature is used, the normal signal silence will not silence the special service NACs
Yellow LED) (such as, releasing warning NACs). The Releasing Service Signal Silence button should not
prevent the release, it only silences the warning NACs. Note that an escalation of the releasing
sequence (going from warning to released) will not re-sound the warning NACs.
An example program follows. In this example both the visual and audible Release Notification
NACs are silenced.
See the following for a program example:
In order to program the Releasing Service Signal Silence function, disable the
Suppression Release Wizard in Custom Control. The equations will stay in
IMPORTANT: Custom Control but you will not be able to edit them through the wizard. Any
future changes to the hazard area will need to be manual.
1. Program a button and a LED for Releasing Service Signal Silence (RSSS).
a. Move the power LED function to the 4010-9805 LED module because the panel defaults to the
bottom LED programmed as power when configured for ULC operation. This vacates a LED next
to the silence button.
b. If a second Hazard Zone is required, do the same for the ground fault trouble. To move the
functionality of the LED mimic the mode, reference address, point type and any custom labels to
an available LED.
c. Configure the switch as Mode PBT* and select an available digital pseudo point as a reference
address. The Custom Label appears on the display for the switch.
*Note: In this example, the lowest switch, next to the ground fault LED, is chosen.
d. Label it appropriately for the hazard area you are silencing.
e. Configure the LED to as Mode ON and have it track another available digital Pseudo.
A-13
4007ES Panel Programmer Manual (579-1167)
Releasing Service
Signal Silence
Programming -
Optional
(Pushbutton and
Yellow LED)
2. Check if there are any manual or automatic alarms in the system and if someone is
requesting to silence the NACs. The equation below checks this.
•If there is an alarm in the system AND someone is pressing the RSSS button (indicated by
the pseudo chosen for the button) the output holds the NACs off at a higher priority than
releasing would normally turn them on.
•If your job specific requirements specify that the releasing NACs turn on at a higher
priority you may need to adjust these numbers. The pseudo for the LED is also held on
indicating the releasing NACs are silenced.
3. Add to the reset equation for the pre-discharge LED above to reset the NACs and the LED
during a system reset or startup.
A-14
4007ES Panel Programmer Manual (579-1167)
Releasing Service
Signal Silence
Programming -
Optional
(Pushbutton and
Yellow LED)
4. Disable the Suppression Release Wizard to delete the default equation written by the
Suppression Release Wizard to silence the NACs on system silence. If it is not deleted it
will still silence the hazard area.
a. Right click the wizard for that hazard and select enable Manual Edit.
b. Click Yes in the confirmation box that follows.
c. Return to your custom control equations and find the equation that the Suppression Release
Wizard labeled On System Silence - yourhazardname
d. Right click and select Delete.
A-15
A-16
579-1167
Rev. D
© 2015-2016 Tyco Fire Protection Products. Specifications and other information were current as of publication and are subject to change without notice.