Ksups: Solenoid Controlled Switch
Ksups: Solenoid Controlled Switch
Ksups: Solenoid Controlled Switch
Operation
The Castell KSUPS+ solenoid controlled switch is typically used in uninterruptable power supply control systems.
1 Key is trapped while power is on, 2 Solenoid is energised by external 3 Solenoid is energised, switch
solenoid is de-energised. signal. As the LED illuminates, key is locked out and key is free.
can be turned and released.
1. While the power is on and a machine is running, the key is trapped in the KSUPS+ unit.
2. To release the key, an external signal must be received to energise the solenoid. With the solenoid energised,
the LED will illuminate to confirm that the key can be removed ensuring the power is off.
3. The key can now be removed and taken to open the door lock and gain acces to the machine area.
The KSUPS+ can operate with a range of input voltages: 24, 110 or 240 VAC or VDC.
The KSUPS+ comes with 4 switch contacts as standard with contacts arrangements as 2NO/2NC or 4 Pole ON/OFF. Auxiliary
sets of contacts are available on request.
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
Usage
The KSUPS+ solenoid controlled switch is designed to be part of a safety system and is used to isolate the power releasing a
key which is then used to gain access to a hazardous area via an access interlock such as the AI, AIE or Salus.
The KSUPS+ solenoid controlled switch is not designed for security purposes.
Installation
The front of panel units should be mounted to a flat surface using 2 suitable M6 fixing screws. Holes should be drilled in the
panel to accept the lock mounting (please refer to drawing on page 4 for more details). The lock face should be sealed to the
panel for ingress protection.
The faceplate is pushed on and clips on to the lock portion.
Cables should be connected to the switch in accordance with the applicable wiring diagrams. Ensure that the unit is
bonded for earth continuity (see drawing on page 4 for more installation details).
IMPORTANT:
The interlock should be mounted using anti-tamper fasteners to prevent unauthorised removal.
The KSUPS+ range of solenoid controlled switches must be installed by a competent and qualified person who has read
and understood these instructions. Please retain this document in your technical file.
Installation not in accordance with these instructions may result in incorrect or unsafe operation.
Maintenance
Periodic visual checks should be carried out by the site manager / safety officer.
Do not lubricate lock barrel with oil or grease, use CK Dry Powder Graphite if necessary.
In case of defects being detected please contact your nearest Castell Support Department for further actions.
Please see Contact section for contact details.
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
Technical Data
Application
The key is released when the UPS system gives a signal to the KSUPS+ to
energise the solenoid when it is in a safe state to allow access.
The key can then be taken to gain access to the protected area. The UPS
cannot commence until the key is removed and taken to the KSUPS+.
EC-Declaration
We, the manufacturers, declare that the components, detailed herein and placed on the market, comply with all the essential
health and safety requirements applying to them.
Empowered signatory:
Dr T.C. Whelan
Managing Director
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
Drawing
KSUPS+
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
Wiring Diagram
T1 L
Solenoid
Rectifier Supply AC or DC
T2 N
T1
SOLENOID WIRING DIAGRAM (24V AC OR DC) T2
110-240V Input
or
24v AC/DC Input
T3 +
Solenoid
T3
T5
LED
Rectifier 24V AC or DC T4
T6
TERMINAL FOR SOLENOID POSITION MONITORING
T5
Normally Closed Contact. (Volt Free)
Max 0.5A @ 30V Contact Open when Solenoid
is energised.
T6
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
Order Information
Product Type 1 2 3 4 5 6
Part Number KSUPSP - - -
(1) FS - Lock type Q - Lock type Special construction available upon enquiry
Up to 3 characters Up to 6 characters
Contact Information
Castell Safety International Ltd. Castell Safety International Ltd. Castell Interlocks Inc. Castell Safety China
The Castell Building Oskar-Jäger-Strasse 137 Suite 800 Building 1, No. 123,
217 Kingsbury Road 50825 Köln 150 N Michigan Avenue, Lane 1165, Jindu Road,
London, England NW9 9PQ Germany Chicago, Illinois 60601 Minhang District,
USA Shanghai 201108, China.
t: +44 (0) 20 8200 1200 t: +49 (0) 221 1694 794 t: +1.312.360.1516 t: +86 21 61519023
f: +44 (0) 20 8905 9378 f: +49 (0) 221 1694 795 f: +1.312.268.5174 f: +86 21 61519030
e: uksales@castell.com e: vertrieb@castell.com e: ussales@castell.com e: chinasales@castell.com
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.