Ufc 4 211 01 2017 c1
Ufc 4 211 01 2017 c1
Ufc 4 211 01 2017 c1
13 April 2017
Change 1, November 2017
AIRCRAFT MAINTENANCE
HANGARS
Any copyrighted material included in this UFC is identified at its point of use.
Use of the copyrighted material apart from this UFC requires the permission of the
copyright holder.
This UFC supersedes UFC 4-211-01N dated 25 October 2004 with Change 3, dated
16 December 2009.
UFC 4-211-01
13 April 2017
Change 1, November 2017
FOREWORD
The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides
planning, design, construction, sustainment, restoration, and modernization criteria, and applies
to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance
with USD (AT&L) Memorandum dated 29 May 2002. UFC will be used for all DoD projects and
work for other customers where appropriate. All construction outside of the United States is
also governed by Status of Forces Agreements (SOFA), Host Nation Funded Construction
Agreements (HNFA), and in some instances, Bilateral Infrastructure Agreements (BIA.)
Therefore, the acquisition team must ensure compliance with the most stringent of the UFC, the
SOFA, the HNFA, and the BIA, as applicable.
UFC are living documents and will be periodically reviewed, updated, and made available to
users as part of the Services’ responsibility for providing technical criteria for military
construction. Headquarters, U.S. Army Corps of Engineers (HQUSACE), Naval Facilities
Engineering Command (NAVFAC), and Air Force Civil Engineer Center (AFCEC) are
responsible for administration of the UFC system. Defense agencies should contact the
preparing service for document interpretation and improvements. Technical content of UFC is
the responsibility of the cognizant DoD working group. Recommended changes with supporting
rationale should be sent to the respective service proponent office by the following electronic
form: Criteria Change Request. The form is also accessible from the Internet sites listed below.
UFC are effective upon issuance and are distributed only in electronic media from the following
source:
• Whole Building Design Guide web site http://dod.wbdg.org/.
Refer to UFC 1-200-01, DoD Building Code (General Building Requirements), for
implementation of new issuances on projects.
AUTHORIZED BY:
Description: This UFC provides criteria for planning and design of Aircraft
Maintenance Hangars for the aircraft of the combined DoD United States Armed
Forces.
Reasons for Document: This is a new Joint Service document. This new document
represents another step in the Joint Services effort to bring uniformity to the planning,
design and construction of military facilities. The UFC was developed to provide design
requirements to accomplish the following:
Impact: The following will result from the publication of this UFC:
• This UFC creates a single source for common DoD Aircraft Maintenance
Hangar criteria and an accurate reference to individual Service-specific
documents.
• This UFC facilitates updates and revisions and promotes agreement and
uniformity of design and construction between the Services.
• The Navy included Functional Data Sheets (FDS) in this UFC. The Army
keeps their Room Data Sheets with the Army Standard and the Air Force
keeps these specific requirements with their Dynamic Prototypes.
• The Army and Navy perform fuel cell operations in the Aircraft
Maintenance Bay per operational guidelines. The Air Force has specific
construction criteria for the design of fuel cell maintenance hangars.
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Service differences in various subjects are noted in this UFC:
o Aircraft Clearance Tables
o Design of the Aircraft Maintenance Bay slab on ground
o Ordnance grounding
o Fire suppression and detection
o High intensity overhead radiant heaters in the Aircraft Maintenance
Bay
o Aircraft power distribution servicing aircraft
o Aircraft Maintenance Bay floor finish options
Previously, the UFC did not allow for slab on ground variable thickness in the hangar
bay for areas not subject to aircraft loading. Generally, the reasoning was that the
hangar bay may experience different aircraft during its lifespan due to change in mission
or during special circumstances such as airshows or storms where aircraft may be
“dense packed” into every available slab space or just to maintain future flexibility of
use. However, it was recognized that this could result in substantial savings in a very
large hangar bay. The governing rationale to revise was to continue to prohibit variable
thickness in multiple aircraft hangar bays since these hangars generally house smaller
aircraft and are less likely to maintain dedicated aircraft parking locations in perpetuity,
but to allow slab thickness variation for single aircraft hangar bays where a very large
aircraft dedicated to one single parking spot was envisioned. In any case, the designer
should validate the requirements with the user. For standard hangars, such as Navy
Type I, II, III, and IV, this is prohibited since the intention for these is to maintain hangar
bay flexibility in accommodating multiple aircraft platforms or repurposing the hangar.
i
UFC 4-211-01
13 April 2017
Change 1, November 2017
ii
UFC 4-211-01
13 April 2017
Change 1, November 2017
iii
UFC 4-211-01
13 April 2017
Change 1, November 2017
iv
UFC 4-211-01
13 April 2017
Change 1, November 2017
v
UFC 4-211-01
13 April 2017
Change 1, November 2017
vi
UFC 4-211-01
13 April 2017
Change 1, November 2017
vii
UFC 4-211-01
13 April 2017
Change 1, November 2017
viii
UFC 4-211-01
13 April 2017
Change 1, November 2017
ix
UFC 4-211-01
13 April 2017
Change 1, November 2017
x
UFC 4-211-01
13 April 2017
Change 1, November 2017
xi
UFC 4-211-01
13 April 2017
Change 1, November 2017
FIGURES
xii
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-5: Large Body Aircraft Hangar with Attached Shops and Office Space and
Sliding Doors ......................................................................................... 261
Figure E-6: Helicopter Hangar Bay with Sliding Doors, Sliding Door Tracks and
Overhead Cranes .................................................................................. 261
Figure E-7: Helicopter Hangar Bay with Converters, Pedestals and Safety Lane .... 262
Figure E-8: UAS/RPA Casket in Hangar Bay Ready for Assembly .......................... 262
Figure E-9: Overhead Bridge Crane with Cabled Controls within Hangar Bay ......... 263
Figure E-10: Hangar Bay with Bridge Cranes and Fall Arrest .................................... 263
Figure E-11: Overhead Bridge Crane within a Shop .................................................. 264
Figure E-12: Sliding Hangar Door Tracks ................................................................... 265
Figure E-13: Vertical Lift Fabric Door with Mullions and Multiple Sections and Fall
Arrest System ........................................................................................ 266
Figure E-14: Vertical Lift Fabric Door Mullion and Mullion Pit..................................... 266
Figure E-15: Floor Mounted 400 Hz Converter with Permanently Attached Cables ... 267
Figure E-16: Permanent Pedestals with 400 Hz, 120V, Communications and
Compressed Air ..................................................................................... 267
Figure E-17: Example of Fire Pan, for Acceptance Test of Optical ............................ 268
TABLES
xiii
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-20: Seat and Canopy Maintenance/AME Maintenance (Shop) (F-35 Only) . 190
Table 7-21: Airframe Hydraulic Clean Room (Shop) (MV-22 Only)........................... 191
xiv
UFC 4-211-01
13 April 2017
Change 1, November 2017
INTRODUCTION
This UFC provides requirements for Aircraft Maintenance Hangars. This UFC is not
intended as a substitution for thorough review during design by individual Program
Managers and Operations Staff in the appropriate Service.
Applicability
The information in this UFC applies to the design of all new construction projects, to
include additions, alterations, and renovation projects within the United States and its
territories and possessions and outside of the United States and its territories and
possessions.
References
This UFC is intended as a source of basic architectural and engineering information for
all individuals involved in the planning, design and construction of Aircraft Maintenance
Hangars.
Architects and Engineers (A/E) who will provide design services under the direction of
the individual Service design agencies.
Planning Personnel
Planning personnel will use this UFC for programming new or replacement facilities,
pre-design planning, or assessing the extent of improvements required in an existing
Aircraft Maintenance Hangar in order to achieve the standard established herein.
Additional Users
Additional users may include entities for operational or other purposes. The respective
users should refer to this UFC from their own policy documents as appropriate and may
include:
1
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Major Command (MAJCOM) Staff/Regions,
• Base, Installation and Garrison Commanders,
• Installation Facilities Management,
• Installation Technical Proponents.
Comply with UFC 1-200-01. UFC 1-200-01 provides applicability of model building
codes and government unique criteria for typical design disciplines and building
systems, as well as for accessibility, antiterrorism, security, high performance and
sustainability requirements, and safety. Use this UFC in addition to UFC 1-200-01 and
government criteria referenced therein.
FRDs are typically authored by the airframe manufacturer and contain many specific
details, are often quite voluminous and difficult to obtain. The FRD may have additional
technical facility requirements, special spaces, special clearances, special maintenance
procedures, systems, data or other items that may impact the hangar design. This UFC
is not a substitute for the FRD of the design airframe(s) being hangared.
SCOPE OF FACILITY
This UFC specifies requirements for aircraft hangars that support all types of fixed wing,
rotary wing, and hybrid aircraft of the Army, Air Force, Navy, Marine Corps, and
Reserves. The UFC additionally applies to hangars for select Unmanned Aircraft
Systems (UAS)/Remotely Piloted Aircraft (RPA).
This UFC focuses primarily on Aircraft Maintenance Hangars. However, it applies to all
hangars including other, specialized, hangar types. Additional study is required to
identify unique requirements, functional areas or systems based on mission or aircraft.
Some specialized hangars include but are not limited to depot, transient, special
operations, research, fuel-cell maintenance, and prototype hangars. For aircraft
corrosion control and paint facility hangar design requirements, refer to UFC 4-211-02
and this UFC where incorporated by specific reference. Maintenance hangars support
ongoing day to day functions of the aviation squadron, wing or brigade and facilitate
routine, preventative, basic aircraft upkeep to sustain aircraft operations. Maintenance
activities are generally short-term and minor in nature compared to those that might be
performed in more intensive intermediate maintenance level or depot-level hangars that
facilitate extensive breakdown and rebuilding of components. Maintenance hangars are
typically characterized by large obstruction-free hangar bays surrounded by various
configurations of supporting trade shop and administrative spaces. Extra value has
been placed on facility safety, continuity of mission operations, flexibility, maximizing
2
UFC 4-211-01
13 April 2017
Change 1, November 2017
hangar bay utilization, and minimizing life-cycle costs of materials and systems. For
these reasons, the UFC limits options on certain requirements, ranging from structural
systems and hangar doors, to proven systems for the expected large-scale aircraft and
operations common in military maintenance hangars. Exemptions to certain
requirements can be submitted for consideration where supported and warranted by the
mission requirements.
Refer to Chapters 5, 6, and 7 for Air Force, Army, and Navy, respectively, for Service-
specific information.
3
UFC 4-211-01
13 April 2017
Change 1, November 2017
4
UFC 4-211-01
13 April 2017
Change 1, November 2017
PLANNING AND LAYOUT
SITE ISSUES
The planning and design of an Aircraft Maintenance Hangar will emphasize AOA safety.
AOA safety includes unobstructed airspace and safe and efficient ground movements
per UFC 3-260-01.
The Airport Operations Area is any area of an airport, installation, or station used or
intended to be used for the landing, takeoff or surface maneuvering of aircraft. The AOA
includes such paved areas or unpaved areas that are used or intended to be used for
the unobstructed movement of aircraft in addition to its associated runway, taxiway or
aprons.
Safety Clearances
Apply all horizontal and vertical operational safety clearances to Aircraft Maintenance
Hangars that dictate the general arrangement and sizing of hangars and their
relationship to airfield and airside facilities. There are, however, general considerations
that apply in most cases, such as:
Regulatory requirements for security of assets can have a significant impact on the
planning and layout associated with aircraft, as well as the aircraft themselves, requiring
varying types and levels of protection. Operational security of the airfield is also a
consideration. Collocate maintenance buildings to inhibit or prevent unauthorized
access and enhance facility and airfield security.
Integrate protective features such as barriers, fences, lighting, access control, intrusion
detection, and assessment into the site and facility planning and design process to
minimize problems with aircraft operations and safety requirements. Include the
protective measures in the design, based on risk and threat analyses, with an
appropriate level of protection, and comply with security-related requirements.
If any new photovoltaic and glass-enclosed solar-hot water systems are proposed,
provide solar glare hazard analysis as required by FAA policy. Refer to Interim Policy,
FAA Review of Solar Energy System Projects on Federally Obligated Airports. FAA
policy on Glint/Glare Impacts on DoD Aviation Operations requires Glint/Glare analysis
of photovoltaic and glass-enclosed solar-hot water systems that are on military airfields
and within 2 miles of military airfield control towers, active runways thresholds, and
helicopter landing zones. FAA policy requires the use of FAA's Solar Glare Hazard
Analysis Tool (SGHAT) for Glint/Glare analysis found on website:
https://share.sandia.gov/phlux. This analysis is required for eliminating the potential for
ocular impact to pilots and/or air traffic control facilities due to glare from solar
photovoltaic (PV) and solar hot water (SHW) systems on airports.
To prevent mirror-like reflections from building surfaces to aircraft in flight, provide roofs
and other external surfaces with a specular reflectance compatible with the location of
the building on the airfield. If the building is located so that glare is an operational
hazard, provide surfaces of the building with a light reflectance of not more than 10,
6
UFC 4-211-01
13 April 2017
Change 1, November 2017
measured at an angle of 85 degrees in accordance with American Society of Testing
and Materials (ASTM) D523, Specular Gloss at critical surfaces of the building.
Maintenance hangars are required to provide weather-protected shelter for the servicing
and repair of aircraft at the organizational level.
Ground Level
The following spaces are typically provided on the ground level of a two story hangar.
Locate these rooms with consideration of the access requirements described in each
Paragraph, regardless of the number of levels in the hangar.
7
UFC 4-211-01
13 April 2017
Change 1, November 2017
2-2.1.5 Storage
Ground level storage includes spaces for storing and issuing parts and tools for the
maintenance of the aircraft. Direct access to both the Aircraft Maintenance Bay and to
the exterior are preferred, but direct access to the exterior is more important to allow for
deliveries.
Upper Level
The following spaces are typically provided on the upper level of a two story hangar.
Locate these rooms with consideration of the access requirements described in each
Paragraph, regardless of the number of levels in the hangar.
8
UFC 4-211-01
13 April 2017
Change 1, November 2017
2-2.2.3 Building Support
These spaces are often satellite rooms associated with ground level mechanical,
electrical and communication rooms. Provide a janitor closet near the restrooms.
Secure Spaces
Many hangars require some level of physical security for the protection of assets such
as classified materials, Sensitive Compartmented Information (SCI) or Special Access
Program (SAP) information. The requirements for the protection of assets is defined in
DoD and Service regulatory guidance or policy. The security requirements must be
coordinated with the supported command and their security representatives to ensure
the configuration will meet their operational (compartmented) and the regulatory and
policy based security requirements. When a hangar has more than one secure space,
serious consideration should be given to consolidate multiple secure spaces. Any
consolidation will reduce the initial and sustainment cost for infrastructure, electronic
security systems and the associated accrediting requirements. When required, integrate
the physical security protective measures into the site, building, room(s), or area(s) as
applicable.
Provide the minimum required clearances between the aircraft and adjacent horizontal
obstructions, vertical obstructions, and other aircraft in designing the Aircraft
Maintenance Bay as indicated in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances and Figure 2-1: Minimum Aircraft Maintenance Bay Clearances, Figure 2-2:
Alternate Corner Configuration, Figure 2-3: Vertical Hangar Clearances, Figure 2-4:
Vertical Hangar Clearances with Sloped Roofs. These clearances are essential to
ensure aircraft are protected from structural damage as they are moving in and out of
the hangar and to allow personnel and equipment to safely and efficiently maneuver
around the aircraft during aircraft maintenance activities.
Horizontal Obstructions
The nearest horizontal fixed obstructions include but are not limited to the inside face of
the wall, faces and jambs of hangar doors, structural columns or bracing, bollards, liner
panels, mechanical equipment or ductwork, plumbing equipment, valves and pipes,
electrical equipment such as power transformers or other permanent physical items.
Fixed obstructions do not include furniture, tables, desks, benches, cabinets, tools,
parts, carts or other movable objects. Clearances from rotary blade aircraft are from
rotor blade arcs, except where specifically noted otherwise in Table 2-1: Minimum
Aircraft Maintenance Bay Clearances.
Vertical Obstructions
The nearest fixed or mobile overhead obstructions include but are not limited to
structure, draft curtains, mechanical, electrical, and plumbing equipment such as
lighting, fans, heaters, ductwork, and fire protection systems, crane rails and crane
9
UFC 4-211-01
13 April 2017
Change 1, November 2017
bridges. Crane hoists and hooks are excluded if they can be maneuvered around tall
parts of the aircraft and can be stored out of the way during aircraft movement.
Additional Clearances
Maximize the unobstructed space in Aircraft Maintenance Bays where designs allow for
exceeding the minimum clearances determined from this section. Exceeding minimum
requirements for bay widths and depths, door heights, clear heights or crane hook
heights may provide the flexibility to accommodate a future aircraft type or a revised
aircraft parking layout without violating required clearances. For example, if for some
good reason the structure of an Aircraft Maintenance Bay roof is higher than necessary
to meet the minimum vertical clearance requirements, locate MEP systems and cranes
as high as possible rather than dropping them to the minimum clear height allowed.
The concept indicated in Figure 2-2: Alternate Corner Configuration is acceptable for
Aircraft Maintenance Hangars of any size where it may be desirable to re-distribute
large corner areas. The clearances indicated by Table 2-1: Minimum Aircraft
Maintenance Bay Clearances apply to all hangars, even if using the alternate corner
configuration. Where used in hangars with multiple aircraft parking positions the
alternate corner configuration is only acceptable at the end bays. Do not reduce the
square footage of the Aircraft Maintenance Bay. Distribute the area gained by the
corner configuration within the Aircraft Maintenance Bay.
This UFC allows encroaching on the space in front of the wings of aircraft with walls and
other fixed obstructions. However, it is the designer's responsibility to confirm
operational clearance requirements around the aircraft if introducing obstructions in
front of the wings of aircraft. Consult the users for any specific airframe or Service
requirements that limit the location of an alternative sidewall configuration. Provide
additional clearances where required by an approved document such as the design
aircraft's Facility Requirements Document (FRD) or a Service-specific standard design,
defined Service hangar type, or other approved criteria. For example, the FRD may
10
UFC 4-211-01
13 April 2017
Change 1, November 2017
require additional space in front of the wing of the aircraft to remove a wing-mounted
engine. Allow for alternate aircraft layouts that could be used in the future such as tail-in
parking. If future flexibility is a guiding concern, do not locate core spaces such as
elevators, utility rooms, restrooms or showers in the high bay space. Refer to Appendix
C-3.2: Considerations for Large Aircraft Maintenance Bays.
Notes:
3. Minimum clearances A and C are to a vertical plane at the face of the fixed
obstruction that extends furthest toward the aircraft.
4. The minimum clearance from the aircraft to the hangar door is to a vertical plane at
the interior face of the innermost panel of a sliding door, or to the interior face of a
vertical lift door panel or mullion. Fixed columns along the hangar door separating
bays are considered hangar door jambs for the purpose of determining clearances.
11
UFC 4-211-01
13 April 2017
Change 1, November 2017
5. Minimum clearance between aircraft is from any part of the aircraft. Depending on
the hangar configuration, the minimum clearance between aircraft is wingtip to
wingtip, nose to nose, tail to tail, nose to tail, or rotor blade arc to rotor blade arc. Do
not assume wingtips or rotor blades are folded. Do not determine minimum
clearances between aircraft based on specific stationary rotor blade positions.
6. Minimum horizontal clearances at hangar door jambs are from wingtip or rotor blade
to the edge of the clear width of the hangar door opening as the aircraft passes
through the door opening. Rotor blades are assumed to be fixed in the narrowest
configuration possible when entering and leaving the hangar. Do not assume
wingtips or rotor blades are folded. Fixed columns along the hangar door separating
bays are considered hangar door jambs for the purpose of determining clearances.
7. Refer to Figure 2-3: Vertical Hangar Clearances and Figure 2-4: Vertical Hangar
Clearances with Sloped Roofs.
8. Minimum vertical clearances are from the top of the aircraft to the bottom of the
nearest fixed or mobile overhead obstruction.
12
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 2-1: Minimum Aircraft Maintenance Bay Clearances
Note: Refer to Table 2-1: Minimum Aircraft Maintenance Bay Clearances for
dimensions A, B, C, D and E.
13
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 2-2: Alternate Corner Configuration
Note: Refer to 2-3.4: Alternate Corner Configuration and Table 2-1: Minimum Aircraft
Maintenance Bay Clearances for dimension A.
14
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 2-3: Vertical Hangar Clearances
Note: Refer to Table 2-1: Minimum Aircraft Maintenance Bay Clearances for
dimensions F, G, and H.
Note: Refer to Table 2-1: Minimum Aircraft Maintenance Bay Clearances for
dimensions F and G.
15
UFC 4-211-01
13 April 2017
Change 1, November 2017
NET TO GROSS AREA IN AIRCRAFT MAINTENANCE HANGARS
Planning personnel are encouraged to allow sufficient net-to-gross area for specific
spaces in Aircraft Maintenance Hangars. Aircraft Maintenance Bays require additional
square footage outside of the safety lane where structure and other utilities create
obstructions which cannot be specifically accounted for in paragraph 2-3: Minimum
Aircraft Maintenance Bay Clearances. Hangars require large mechanical rooms to
accommodate equipment such as air compressors. Hangar fire protection rooms are
larger than in typical buildings due to the foam suppression system required for the
Aircraft Maintenance Bay. Select Hangar doors based on the pros and cons of the
different types of doors and by the users/installation preferences.
The area required for different types of hangar doors varies, but is not intended to
govern the decision of the type of hangar door to use. Calculate the area inside the
exterior face of hangar doors in the closed position at 100% square footage. Calculate
the area inside the exterior face of door pockets at 100% square footage. Enclose all
door pockets. Do not include the area under the roof, outside of the hangar doors. Refer
to Figure 2-5: Space Requirements for Vertical Lift Fabric Doors and Figure 2-6: Space
Requirements for Sliding Steel Hangar Doors for clarification on calculating gross
square footage of different hangar doors.
16
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 2-6: Space Requirements for Sliding Steel Hangar Doors
Count the area inside the exterior face of the door as 100%
Square Footage (SF)
Do not count the area under roof and outside the exterior face
of the door
Count the area inside the exterior face of a door pocket as
100% SF
ACCESSIBILITY
It is the goal of the DoD to make its facilities accessible to persons with disabilities. In
accordance with UFC 1-200-01, follow the Architectural Barriers Act (ABA) Accessibility
Standard for Department of Defense Facilities.
SUSTAINABLE DESIGN
Design Aircraft Maintenance Hangars per the requirements of UFC 1-200-02. Refer to
Appendix C - Best Practices for discussion on sustainability strategies applicable to
Aircraft Maintenance Hangars.
HAZARDOUS MATERIALS
Background Information
The DoD, including the Department of the Navy, operates facilities which routinely
utilize, or have utilized in the past, hazardous materials and chemicals that contain lead,
cadmium and chromium, and other heavy metals. Operations and activities which can
create an unsafe condition with regards to worker protection, include (but are not limited
to): manual demolition, scraping, grinding, heat-gun applications, power tooling with
dust collection, application of corrosion control materials, spray paint with
lead/chromium (VI)/Cadmium-based paints, burning, power tooling without dust
17
UFC 4-211-01
13 April 2017
Change 1, November 2017
collection, rivet busting, cleanup activities with dry abrasives, movement/removal of
enclosures, abrasive blasting, welding, cutting and burning on steel structures. When
these operations occur, there are hazards associated with the generation of dust, debris
and fumes. The hazards and the controls required are dependent on the materials used.
Additionally, these operations, and utilization of these hazardous materials and
chemicals, are found in aviation facilities.
Comply with the Occupational Safety and Health Act (OSHA), American Conference of
Governmental Industrial Hygienist (ACGIH), and DoD regulations and guidelines for
facilities that will operate, or will continue to operate, utilizing hazardous materials
and/or chemicals. The requirements found in the OSHA regulations and the DoD
Instructions and Directives may affect facility design requirements, which may include
(but are not limited to): separate toilets and washing/bathing areas for workers who are
exposed to the hazard, change rooms, decontamination areas, break rooms, clothes
washing facilities, areas for controlled disposal of contaminated waste and work clothes,
both local and general high-efficiency particulate air (HEPA) ventilation systems and
filters, eyewash stations and deluge showers. Areas of facilities utilizing these
hazardous materials and/or chemicals must be designated as regulated areas
whenever exposure can be expected to be in excess of the permissible exposure
limit(s), and must be demarcated from the rest of the workplace in a manner that
adequately establishes and alerts building occupants of the boundaries of the regulated
area. Design facilities in a manner to allow the OSHA required air sampling and
monitoring that are required for the specific hazardous material in use. Design facilities
to control these hazards below the standards set in the stated regulations. Refer to
Appendix D, Questionnaire, for a list of questions the planner and designer should ask
the operators regarding their aircraft maintenance operations and activities.
Additionally, the DoD Instruction 6055.01, Appendix 4 lists additional requirements for
facilities which involve operations generating airborne dust, mist, debris, or aerosols
containing lead, chromium (VI), or cadmium. These requirements include (but are not
limited to): containment processes and methods to monitor effectiveness of
housekeeping procedures, decontamination procedures, and engineering controls
tailored to each facility.
18
UFC 4-211-01
13 April 2017
Change 1, November 2017
GENERAL HANGAR REQUIREMENTS
INTRODUCTION
Typical systems utilized in Aircraft Maintenance Hangars are described below. Refer to
Chapters 5, 6, and 7 for Air Force, Army, and Navy specific applicability and exceptions
to Chapter 3. Specific rooms where these systems are used are indicated later in this
UFC.
CIVIL
Siting
3-2.1.1 General
When siting the hangar, place emphasis on operation, function, energy efficiency,
safety, and Fire Department and Emergency vehicle access. Provide efficient access to
the flight line. Other factors to consider include topography, vegetative cover, existing
construction, weather elements, wind direction, soil conditions, flood hazards, natural
and man-made obstructions, adjacent land use, availability of usable airspace,
accessibility of utilities, taxiway and runway clearances, existing Control Tower sight
lines, and future expansion capability. When siting the Hangar, give careful
consideration to vehicular parking, pedestrian access, and traffic flow. Follow
UFC 3-260-01 and UFC 1-200-01.
3-2.1.2.1 Restrictions
Land use restrictions dealing with runway clearances, helipad planning, aircraft noise,
and use of airspace are to be applied to the site location with UFC 3-260-01 and
UFC 2-100-01.
19
UFC 4-211-01
13 April 2017
Change 1, November 2017
Vehicular and Pedestrian Circulation
Airfield Pavements
Design utilities in accordance with the appropriate UFC. Avoid installing utilities under
airfield pavements to the maximum extent possible. Obtain written approval for the need
of any utilities under the airfield pavement other than those directly supporting the apron
or parked aircraft, from NAVFAC Headquarters (HQ) Chief Engineer for Navy projects,
United States Army Corp of Engineers (USACE) Transportation Systems Center (TSC)
for Army projects, and AFCEC pavements engineer for Air Force projects.
20
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-2.4.1 Storm Drainage
Design storm drainage around hangars and aircraft movement areas in accordance with
UFC 1-200-01, and FAA AC 150/5320-5D. Design the storm drainage system, including
gutters, drains, inlets and culverts, to carry the anticipated runoff for the appropriate
level design storm event, including runoff from melting snow. Design of aboveground
storage of runoff tends to attract birds that are not recommended in the AOA.
ARCHITECTURAL
Provide hangar construction, life safety, and fire department access in accordance with
UFC 3-600-01 except where additional requirements are added by this UFC. Use
National Fire Protection Agency (NFPA) 409 only where explicitly noted. If there is a
conflict, this UFC supersedes UFC 3-600-01 and NFPA standards.
21
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Provide a 1-hour fire barrier between hangar bay and support areas such
as offices, maintenance shops, and storage areas including tools, parts,
and tires.
• Provide a 2-hour fire barrier between separate fire areas within the hangar
bay.
• Internal fire barriers are not required between adjacent aircraft servicing
areas unless required elsewhere in this UFC.
• Protect openings in fire barriers in accordance with NFPA 101, such as
doors and windows.
• Protect duct penetrations through fire barriers in accordance with UFC 3-
600-01.
22
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-1-1: Internal Fire Rated Separations
23
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-1-3: Internal Fire Rated Separations
24
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-3.1.7 Allowable Building Height and Stories
Where the building is constructed in accordance with this UFC, the allowable building
height is unlimited. The allowable number of stories is limited to the restrictions of the
IBC based on the construction type.
• For Air Force and Navy: Provide exits or exit access doors around the
entire perimeter of the hangar bay at a maximum spacing of 150 feet (ft.)
(45.7 meters (m.)). Unless otherwise noted in this UFC, travel distance
limitations do not apply in the hangar bay. Provide each exit access door
from the hangar bay, which passes through adjacent building areas, with a
continuous unobstructed path to an exit. Travel distance begins at the
hangar bay exit access, and is measured along the path of egress travel
to the exit. Refer to Figure 3-2: Air Force and Navy Hangar Bay Egress
for additional information.
• For Army: Provide exits on the exterior walls around the hangar bay
egressing directly to the exterior at a maximum spacing of 150 ft. (45.7 m).
Locate the first exit on the exterior wall no further than 75 ft. (22.9 m) from
the start of the hangar bay exterior wall. Apply the maximum travel
distance for General Industrial occupancy as defined by NFPA 101. Refer
to Figure 3-3: Army Hangar Bay Egress for additional information.
• Where hangar bay doors exceed 110 ft. (33.5 m), do not provide exits in
the hangar bay door to meet the maximum distance limitation between
exits. Provide exits within 20 ft. (6.1 m) of each end of the hangar bay door
opening.
• Personnel access doors may be provided through the hangar bay door;
however these doors are not considered exits for egress.
• Install an egress door in the structure between hangar bay doors, when
the structure is greater than 7 ft. (2.1 m) in width. Provide this door
regardless of whether the 110 ft. (33.5 m) limitation is exceeded.
• Provide each required exit or exit access door from the hangar bay with
panic hardware, and swing the door in the direction of egress travel.
25
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Support areas are not permitted to have their required egress through the
hangar bay with the exception of normally unoccupied rooms less than
100 sq. ft. (9.3 sq. m). This limitation is not inclusive of equipment
platforms as defined by IBC.
• Do not exceed a travel distance of 75 ft. (22.9 m) from the most remote
location on the mezzanine to an exit or exit access. Equipment platforms
as defined per IBC are not considered mezzanines.
Figure 3-2: Air Force and Navy Hangar Bay Egress
1. Normally unoccupied rooms less than 100 sq. ft. (9.3 sq. m) may have their sole
means of egress through the hangar bay.
2. Travel distance limitations begin at the door from the hangar bay.
3. Except where noted, do not exceed 150 ft. (45.7 m) between exits and exit access
doors along the hangar bay perimeter.
4. Do not exceed a cumulative total of 150 ft. (45.7 m) for the distance of A + B.
5. Except where noted, travel distance limitations do not apply within the hangar bay.
6. Do not exceed a travel distance of 75 ft. (22.9 m) from the most remote location on
the mezzanine to an exit or exit access.
26
UFC 4-211-01
13 April 2017
Change 1, November 2017
7. Where the hangar bay door opening exceeds 110 ft. (33.5 m), provide the first exit or
exit access within 20 ft. (6.1 m) of the hangar bay door opening.
8. Personnel doors are permitted in the hangar bay door, however they are not
considered exits for egress.
1. Normally unoccupied rooms less than 100 sq. ft. (9.3 sq. m) may have their sole
means of egress through the hangar bay.
2. Unless the wall separating the hangar bay from the support area is a horizontal exit
as defined by NFPA 101, the distance between exit access doors along this wall is
only limited by the travel distance.
3. Except where noted, do not exceed 150 ft. (45.7 m) between exits in the hangar bay
exterior wall.
4. Do not exceed 75 ft. (22.9 m) between the start of the hangar bay exterior wall and
the first exterior exit along the wall.
5. Travel distance limitations from the hangar bay are applicable until an exit is
reached.
6. Do not exceed a travel distance of 75 ft. (22.9 m) from the most remote location on
the mezzanine to an exit or exit access.
27
UFC 4-211-01
13 April 2017
Change 1, November 2017
7. Where hangar bay door exceeds 110 ft. (33.5 m), provide the first exit or exit access
within 20 ft. (6.1 m.) of the hangar bay door opening.
8. Personnel doors are permitted in the Aircraft Maintenance Bay door, however they
are not considered exits for egress.
• dmin = Hmax/8, or
• dmin = 4 ft. (1220 mm), and the draft curtain extends at least 1 ft. (305 mm)
below Hmin.
Where:
• dmin = Minimum depth of the draft curtain measured down from Hmax (ft.,
m).
• Hmax = Maximum roof height AFF where the draft curtain is installed (ft.,
m).
• Hmin = Minimum roof height AFF where the draft curtain is installed (ft., m).
Suitable access surfaces include ramps, aircraft parking aprons, automotive parking
areas, fire apparatus access roads, and stabilized landscaped areas. Where automotive
parking areas are used for fire department access, provide at least one aisle 20 ft. (6.1
m) wide with an adequate turning radius for fire department apparatus.
28
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-3.1.12 Interior Firefighting Accessibility
Exit and exit access doors from the hangar bay provide building access into the hangar
bay for normal structural firefighting operations.
Provide the ability to operate the hangar bay door under emergency conditions. Refer to
3-7.2: Hangar Bay Door Power for requirements.
Exterior Systems
Provide exterior materials appropriate for the environment at the project location.
3-3.2.4 Roof
Provide a roof system in accordance with UFC 3-110-03, except as modified in this
paragraph. Aggregate surfaces and vegetative roofs are not acceptable due to FOD
prevention concerns at airfields. Do not slope roof toward airfield unless rainwater will
be collected at the roof eave and taken below grade to stormwater drain system. Do not
direct rainwater above grade to the flight line side of the hangar. Slope roof away from
hangar doors and aircraft movement areas. Provide fall prevention and/or fall protection
in accordance with UFC 3-110-03. Most hangars do not have mechanical equipment on
29
UFC 4-211-01
13 April 2017
Change 1, November 2017
the Aircraft Maintenance Bay roofs but there may be other equipment such as antenna
platforms. Provide path and fall protection for access to all roof mounted lighting and
antenna platforms from interior roof access point. Refer to 2-1.6 Solar Glare Hazard
Analysis.
3-3.2.5 Windows
Provide exterior windows, skylights, and doors on inhabited portions of the building per
UFC 4-010-01. In addition, provide all interior windows and glazed doors exposed to the
Aircraft Maintenance Bay with laminated glass designed in accordance with UFC 4-010-
01 for the same blast effects as the most severely loaded exterior glazing system.
Provide materials appropriate for the environment at project location and warrant
material for expected lifespan of the building without any requirements for special
maintenance. Provide insect screens with any operable windows.
30
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Closers - ANSI/BHMA A156.4 tested to exceed at least 3 times the
number of cycles required for Grade 1.
• Overhead Stops - ANSI/BHMA A156.8.
• Protection Plates - ANSI/BHMA A156.6 - Kick Plates J102, Armor Plates
J101.
• Thresholds - ANSI/BHMA A156.21.
• Weatherstrip, Sweeps, Drip Caps - ANSI/BHMA A156.22.
Provide closers with heavy-duty arms at all exterior doors. Provide closers with integral
spring stop arms or provide separate heavy-duty overhead stops. Provide thresholds,
head and jamb weatherstrip (with astragals at pairs of doors without mullions), sweeps
with integral rain drips, and overhead rain drips at exterior doors. Provide kickplates at
hollow metal doors with closers, and at storage room doors with or without closers.
Armor plates are required at doors anticipated to encounter cart traffic.
Interior Systems
Durability is extremely important when specifying materials for interior construction and
finishes. Aircraft Maintenance Hangars are often occupied 24 hours per day, seven
days a week and heavy equipment is regularly handled throughout the facility. Provide
durable low maintenance finishes in a limited palette with good appearance retention.
Incorporate colors, patterns, and textures which successfully mask minor abrasions and
day-to-day soiling between cleaning. Provide finishes that are easily repairable if and
when necessary. Provide corner guards if using gypsum board in corridors and other
high traffic areas. Provide finishes to incorporate LEED criteria, with low and no VOC
adhesive and paint finishes, walk off mats for increased indoor air quality, with highest
recycled content as is feasible for the project, and other environmentally sensitive
features and benefits.
31
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Corridors
• Perimeter of toilet and locker room areas
• Offices and operational spaces where privacy issues are of significant
concern
• Flight planning
• Maintenance Shops
Refer to 3-3.3.3: Acoustics for additional requirements. Provide a wall base on all walls
in spaces with an applied floor finish.
3-3.3.3 Acoustics
Provide acoustics per UFC 3-101-01 unless superseded by other criteria or the STC
ratings listed in individual Functional Room Data Sheets as the basis for the sound
attenuation design of the partition, door and window assemblies for the facility.
Hangar maintenance bays and maintenance shops can be high noise areas. Prevent
sound from the exterior and sound from these and other noisy spaces such as corridors,
toilets, elevator, machine rooms, and mechanical rooms from having negative impact on
the adjacent spaces.
3-3.3.4 Floors
Provide floors per 3-4.2: Ground Floors.
3-3.3.5 Ceilings
The following spaces may have exposed ceiling structure:
• Hangar Bay
• Maintenance Shops
• Corridors (Ground Level) and Stairs
• Building Support Spaces
Provide finished ceilings in all other spaces. Refer to Finishes. Typical minimum finished
ceiling height to be 9 ft. (2.74 m) unless otherwise indicated. Coordinate minimum hook
heights for overhead cranes and hoists with MEP and Structural building systems when
setting floor to floor and floor to roof heights to ensure a safe working environment for
occupants in those spaces.
32
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-3.3.6.1 Interior Hollow Metal Doors and Frames
Interior hollow metal doors are to be Level 3 and Physical Performance Level A. Interior
hollow metal frames are to be welded Level 3. Interior hollow metal doors between
Aircraft Maintenance Bays and shop spaces and other areas subject to high abuse are
to be Level 4 and Physical Performance Level A, with Level 4 welded frames. Interior
hollow metal doors at administrative areas may be Level 2 and Physical Performance
Level B, with Level 3 frames. Refer to ANSI/SDI A250.8. Provide fire resistant
assemblies where required to meet fire ratings. Provide fire-rated glazing door vision
panels where required in this UFC. Meet ASTM E90 where acoustical door assemblies
are specified.
33
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Closers - ANSI/BHMA A156.4 tested to exceed at least 3 times the
number of cycles required for Grade 1.
• Protection Plates - ANSI/BHMA A156.6 Kick Plates J102, Armor Plates
J101.
Provide exit devices on door at rooms containing explosives (Paraloft, Flight Gear, and
Ordnance). Provide kickplates at all doors with closers and at all storage rooms with or
without closers. Armor plates are required at doors that are anticipated to encounter cart
traffic.
3-3.3.7 Casework
Specify Architectural Woodwork Institute (AWI) Premium or Custom for construction and
finishes per AWI Quality Standards Illustrated, Current Edition. Provide veneer panel
core casework, cabinet doors and drawer faces. Provide plastic laminate or better finish
on all exposed surfaces of the casework must. Provide solid composite plastics
countertops, unless otherwise indicated or requested.
3-3.3.8 Signage
Provide signage per UFC 3-120-01, in Aircraft Maintenance Bay to explain operation of
significant building features and limiting factors for hangar door operation. For example,
locate a sign near the controls of hangar doors explaining proper operation. Similarly,
provide signage near the maintenance control office to explain items such as maximum
slab loads, jacking loads, use of ventilation system, operation of the fire protection
system, and lighting controls. Develop a comprehensive signage package (both interior
and exterior) that addresses way-finding and definition of all spaces within the facility.
Provide signage to reflect and complement the environment through colors, images and
materials used.
Finishes
34
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-3.4.1.2 Maintenance Administration
Provide resilient flooring, painted walls, resilient base, and suspended acoustical ceiling
systems. Partitions separating administrative spaces may be gypsum board on metal
stud construction. Partitions may extend to above the ceiling for similar office types and
spaces where noise between offices is not an acoustical issue.
3-3.4.1.5 Storage
Provide sealed concrete floors, painted masonry or concrete walls, painted exposed
ceilings.
In support spaces such as break rooms provide resilient flooring or seamless resinous
flooring, painted gypsum board walls and suspended acoustical ceiling system.
3-3.4.1.8 Corridors
Provide flooring equal to the most durable finish provided in the spaces served by the
corridor. Provide 5-coat fuel resistive resinous flooring in corridors providing indirect
access to heavy maintenance shops. Provide resilient flooring or 3-Coat fuel resistive
resinous flooring in corridors serving light maintenance shops. Provide sealed concrete
or resilient flooring in corridors serving only personnel and building support spaces.
Provide painted concrete, masonry or impact resistant gypsum board walls, resilient
35
UFC 4-211-01
13 April 2017
Change 1, November 2017
base, and suspended acoustical ceiling systems. Provide full-height corner guards at all
exterior corners, including columns.
3-3.4.1.9 Stairs
In stairs, provide resilient flooring and stair accessories, painted concrete, masonry or
impact resistant gypsum wall board up to a minimum of 8 ft. (2.44 m) above stair level.
In support spaces such as break rooms provide resilient flooring or seamless resinous
flooring, resilient base, painted gypsum board walls and suspended acoustical ceiling
system.
3-3.4.2.4 Corridors
Provide resilient flooring or carpet tile, painted impact resistant gypsum board walls,
resilient base and suspended acoustical ceiling systems.
• Shop coat exposed exterior ferrous metal primary and secondary steel
framing per UFGS 09 97 13.27. Coat all other exposed exterior ferrous
metal per 09 90 00, Division 5: Exterior Metal, Ferrous and Non-Ferrous
Paint Table.
• Shop coat all exposed and non-exposed ferrous metal of hangar doors per
UFGS 09 97 13.27.
36
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Shop coat exposed interior ferrous metal primary and secondary steel
framing inside Aircraft Maintenance Bays per UFGS 09 97 13.27. Coat all
other exposed interior ferrous metal inside Aircraft Maintenance Bays per
UFGS 09 90 00, Division 5: Interior Metal, Ferrous and Non-ferrous Paint
Table.
• Coat exposed interior ferrous metal in spaces other than Aircraft
Maintenance Bays and Building Support spaces as defined in 3-3.4:
Finishes per UFGS 09 90 00, Division 5: Interior Metal, Ferrous and Non-
ferrous Paint Table.
• Coat exposed interior ferrous metal in Building Support spaces as defined
in 3-3.4: Finishes at a minimum with primer coat only per UFGS 09 90 00,
Division 5: Interior Metal, Ferrous and Non-ferrous Paint Table.
• Coat non-exposed interior ferrous metal at a minimum with a primer coat
only per UFGS 09 90 00, Division 5: Interior Metal, Ferrous and Non-
ferrous Paint Table.
• Coat other interior substrates such as gypsum board, concrete, masonry
and wood per UFGS 09 90 00.
• Provide 5-coat fuel resistive resinous flooring at the Aircraft Maintenance
Bay and heavy maintenance shops and associated corridors per UFGS 09
67 23.16. Provide striping of safety lanes, lead-in lines, nose gear stop
lines, grounding points, emergency eye wash fixtures, fire extinguishers
and other safety markings. Coordinate colors, striping and grit level with
the users. Provide grit to meet OSHA Requirements for wet floors. Refer
to Chapters 5, 6, and 7 for figures showing Service-specific striping
requirements. Follow recommendations in UFGS 09 67 23.16 to
coordinate with the structural engineer doing the slab design to provide a
below slab vapor barrier, and to design the slab to be as low vapor
emitting as possible. Do not use spray-on curing compounds. Specify the
manufacturer's Moisture Vapor Reducer coating and just don't use it if the
concrete test come in at acceptable vapor emissivity rates.
• Provide 3-coat fuel resistive resinous flooring at light maintenance shops
and associated corridors per UFGS 09 67 23.15. Provide striping safety
markings. Coordinate colors, striping and grit level with the users. Follow
recommendations in UFGS 09 67 23.15 to coordinate with the structural
engineer doing the slab design to provide a below slab vapor barrier, and
to design the slab to be as low vapor emitting as possible. Do not use
spray-on curing compounds. Specify the manufacturer's Moisture Vapor
Reducer coating and just don't use it if the concrete test come in at
acceptable vapor emissivity rates.
37
UFC 4-211-01
13 April 2017
Change 1, November 2017
Elevators
Coordinate accepted intrusion prevention measures with environmental office for host
facility. Design intrusion prevention systems to not restrict access to building systems.
Design all access required as removable panels that can be removed and replaced with
the normal means of access and tools used by maintenance personnel.
STRUCTURAL
Typical structural systems utilized in Aircraft Maintenance Hangars are described below.
Refer to Chapters 5, 6, and 7 for Air Force, Army, and Navy specific applicability and
exceptions to this section.
Aircraft Hangars are to be assigned Risk Category III unless the Authority Having
Jurisdiction approves a different Risk Category based on the following conditions:
• Aircraft Hangars housing aircraft which are not "high value equipment"
may be assigned to Risk Category II.
• Aircraft Hangars that house aircraft with a "mission critical" function, which
are required to remain operational, may be assigned to Risk Category IV.
Foundations
Foundations are not to utilize the slab on ground to resist lateral forces. Foundations are
to be separated from the slab on ground by an isolation joint. Hairpins or tie beams
within the slab on ground are not allowed. Tie beams are allowed if they are completely
independent of the slab on ground such as when the tie beams are located below the
slab on ground.
Ground Floors
Design ground floors for all loadings anticipated to be supported by the floor system.
These loads may include aircraft wheel loads, aircraft tug wheel loads, fire truck wheel
loads, fork truck wheel loads, jacking loads, wall loads, and point loads. \1\ Confirm with
using activity full range of intended aircraft to be housed within the hangar including
whether it is to be used for "dense packing" of multiple aircraft in non-standard use
during storms or other events. /1/
38
UFC 4-211-01
13 April 2017
Change 1, November 2017
structural slabs in accordance with the structural requirements and criteria of
UFC 3-301-01. In the Aircraft Maintenance Bay these structural slabs are also to be
designed for the aircraft loads stated in this UFC. Design the slab on ground in the three
different areas of the Aircraft Maintenance Hangar as follows:
The Aircraft Maintenance Bay floor will be above the exterior grade and the floor slope
will project beyond the face of the building to meet the exterior apron grade. Slope the
Aircraft Maintenance Bay floor a minimum of 0.5% (1/16" per foot) towards the flight line
door or trench drains (when provided). Additional cross-slopes may be necessary to
meet other drainage requirements. Do not slope floors more than 1.5% (3/16 inch per
foot).
40
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-4: Typical Aircraft Maintenance Bay Slab on Ground Cross-Section
41
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 3-1: Aircraft Maintenance Bay Slab on Ground Joint Spacing
205 (8) < T < 230 (9) 3.8 TO 4.6 (12.5 TO 15)
NONREINFORCED SLAB 230 (9) < T < 305 (12) 4.6 TO 6.1 (15 TO 20)
T > 305 (12) 6.1 (20) MAX
SLAB WITH ALL THICKNESSES 7.6 (25) MAX
REINFORCEMENT
(MINIMUM 0.05% STEEL IN
BOTH DIRECTIONS)
42
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-5: Concrete Slab on Ground Construction Joint
43
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-6: Concrete Slab on Ground Contraction Joint
44
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-7: Concrete Slab on Ground Expansion Joint
45
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-8: Joint Sealant Details for Concrete Slabs on Ground
46
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 3-2: Concrete Slab on Ground Dowel Size and Spacing
47
UFC 4-211-01
13 April 2017
Change 1, November 2017
floor tubing. Refer to ACI 360R-10, Chapter 13 for additional guidance on
under slab insulation.
• Coordinate closely with the in-floor radiant heat systems supplier on the
design of the hangar floor slab, location of insulation, location of radiant
tubing and radiant tubing manifolds within the slab on ground.
Superstructures
Design the aircraft maintenance hangar in accordance with UFC 4-010-01. Aircraft
Maintenance Hangars are generally considered "inhabited" buildings due to the
occupancy and population density within the administration and office areas. However,
the Aircraft Maintenance Bay may be considered "low occupancy" buildings if it meets
all the requirements of UFC 4-010-01.
48
UFC 4-211-01
13 April 2017
Change 1, November 2017
The framing system selected for the Administration and Shops area will provide areas
free from isolated columns. Structural bracing will be located so as not to impair
functionality of Administration and Shops areas. Exposed structural bracing will not be
permitted in office areas without prior approval.
Select exposed steel shapes to minimize their surface area. Design all exposed steel
connections to shed water. Design and detail exposed steel to permit the complete
inspection of all fasteners and welds. Seal Hollow Structural Sections (HSS) to keep
water from entering the section and animals from nesting inside.
Design the walls and partitions of the Aircraft Maintenance Bay to be non-load bearing
and not be considered as elements of the lateral load resisting system. The walls of the
office/shop portion of the facility may be designed as load-bearing if structurally isolated
from the Aircraft Maintenance Bay structure. Limit the use of interior load bearing walls
to allow for future reconfiguration of the spaces. Consider the relative stiffness of all wall
and partition systems and the main framing and provide for structural isolation as
required.
Roof framing system will be a galvanized structural steel roof deck on structural steel
members, open-web steel joists or light-gage "Z" purlins. The steel deck cannot be used
as a diaphragm for the principal building lateral force resisting system. Utilize horizontal
truss or other system for the principal building lateral force resisting system. The steel
deck can be utilized to brace secondary members, if the designer can show that there is
deflection compatibility between the deck serving as a brace, and the main lateral force
resisting system. Provide a positive load path from the steel deck to the structural
system, which does not rely on the joist seats or purlins to transfer lateral loads.
Properly brace roof framing members for stability during construction and for final
configuration.
Strength Requirements
Design for all the loads described in or incorporated by reference to UFC 3-301-01, and
for all loads imposed by bridge cranes, suspended work docs, personal fall arrest
systems, hangar doors or other specialty equipment supported by the structure. Show
all relevant design loading and stability assumptions on the construction drawings. Note
elements that function as stability bracing and the members that are laterally unstable
until the stability bracing is installed. All instances where the installation of multiple
secondary elements is required for the proper stability of a primary element or when a
bracing element in turn requires stability bracing.
Design to consider the effect of pattern loads resulting from multiple loaded crane hooks
and work docks. All crane hardware and lifted loads will be treated as live loads in the
load combinations defined in Chapter 16 of the IBC, except for patented tracks, tracks,
49
UFC 4-211-01
13 April 2017
Change 1, November 2017
supports, sway braces and similar elements which are immobile and may be defined as
dead loads.
Serviceability Requirements
Control deflections of structural elements to within the limits imposed by UFC 3-301-01
unless stricter control is necessary to support equipment, fascia or other
appurtenances. Design the Aircraft Maintenance Bay roof and wall structural elements
to meet a minimum deflection criteria of l/240. Design the office/shops area structural
elements to meet the deflection requirements appropriate to finish type.
Control lateral drift (side sway) of the structure to within the limits imposed by
UFC 3-301-01 unless stricter control is necessary for the serviceability of the structure
and all its components, including, but not limited to, exterior walls and cladding, partition
walls, hangar doors, bridge cranes, utilities and other appurtenances. If the Aircraft
Maintenance Bay and the office/shops area framing is constructed as a single frame,
design the structure to meet the most stringent requirements described above.
Thermal Requirements
In addition to the thermal loads of UFC 3-301-01, design to account for anticipated
differential thermal effects from solar heating (e.g., on long sun-exposed exterior steel
compared to shaded steel such as roof trusses, joists, or decking) or inside/outside
differences (particularly an "attic" effect in the hangar bay). Consider the local climate
conditions when selecting the final differential temperature range. Investigate the
deflections caused by differential thermal effects using unfactored loads. Some
architectural fascia elements and weather seals around hangar doors are particularly
vulnerable to detrimental deflections.
MECHANICAL
Comply with the requirements of UFC-3-410-01, UFC 3-410-02, UFC 3-410-04N and
other applicable UFCs. Additional criteria specific to aircraft hangar mechanical systems
is included herein.
Heating and cooling system design loads for the purpose of sizing systems, appliances
and equipment are determined in accordance with UFC 3-410-01. Include analysis of
UFC 1-200-02, ASHRAE 189.1, and ASHRAE 55 for thermal environmental conditions
for human occupancy in the HVAC design.
Size equipment and all system components to maintain the following indoor design
conditions. Provide design conditions, including temperature, humidity, filtration,
ventilation, and air changes required.
50
UFC 4-211-01
13 April 2017
Change 1, November 2017
in the space. During unoccupied hours, set temperatures no lower than
85ºF (29.4ºC).
• Administrative/ Office/Shop heating: 68ºF (20ºC) db. During unoccupied
hours, set temperatures no higher than 55ºF (12.8ºC).
• Aircraft Maintenance Bay heating: 55ºF (12.8ºC) db at 99% db outdoor
design temperature. During unoccupied hours, set temperature no higher
than 50ºF (10ºC) at 99% db outdoor design temperature. The appropriate
unoccupied setpoint temperature depends on the system selected and the
designer will take this into consideration when selecting the heating
system for the facility. Humidification is not authorized. Take into account
infiltration in the hangar bay heating loads.
• Locate HVAC air handling equipment serving administration and shop
spaces in dedicated mechanical rooms or on the roof. Locate air handling
systems(s) floor-mounted in the mechanical rooms and not within the
actual spaces served. Make mechanical room large enough to allow a
minimum of 2 ft. (610 mm) between the air-handling unit and the wall,
adequate coil pull space, and unobstructed access to replace air filters.
Provide additional access/maintenance space in accordance with
equipment manufacturer’s recommendations.
Heating
The type of heating system depends on the outdoor design temperatures. The options
are overhead radiant heat, in-floor radiant heat, or forced-air heat. Conduct a 40-year
life-cycle cost analysis to support selection from the heating system choices. Include an
analysis of the anticipated user occupancy schedule. Include these results in the design
analysis. If floor-type or forced-air heaters are installed, direct the discharged air to
cover the entire floor area to help reduce accumulation of combustible and flammable
vapors and arranged to draw warm air from the top of the hangar for distribution at
occupied level. Provide floor-type heater fans with not less than six air changes per hour
based on an artificial ceiling height of 15 ft. (4.6 m). Refer to 3-5.3: Ventilation for
ventilation requirements.
In climates where freezing temperatures occur, protect hangar door tracks or the bottom
edges of hangar doors with electric or hot water-glycol snow-melting coils in accordance
with NFPA 409. Ensure that non-toxic antifreeze is used, such as propylene glycol, to
avoid freezing and environmental spill concerns. Use a sump pump to inject the
antifreeze into the system. Provide ratio of antifreeze to water between 30 and 50%,
depending on the design temperature, to avoid freezing.
51
UFC 4-211-01
13 April 2017
Change 1, November 2017
the overhead gas-fired, radiant heating system. If the outside air temperature is below
40ºF (4.4ºC) operate the radiant heating system regardless of hangar door position.
For Air Force and Navy: High-intensity type radiant heaters with open flame or
glowing elements are not to be installed.
For Army: Refer to Chapter 6 - Army Specific Criteria for use of high-intensity type
radiant heaters in Army Aircraft Maintenance Bays.
3-5.2.3 Humidification
For administration and shop spaces, where the indoor relative humidity for comfort
heating is expected to fall below 20%, add humidification to increase the indoor relative
humidity to 30%. Coordinate with the architect to design the building envelope to
prevent condensation in the wall/roof systems during the time humidification is in
operation. Include in the design analysis a dew point analysis profile (ASHRAE
Fundamentals Chapter 23) for winter design conditions, showing condensation
boundaries. The dew point analysis will consider the effect of air movement into the
walls for buildings under positive pressurization relative to the outdoors.
Ventilation
Provide ventilation in shop administration spaces in accordance with the latest versions
of ASHRAE 62 and UFC 3-410-01. This is typically provided by a dedicated outdoor air
system (DOAS), which is separated from the space-cooling function. Include infiltration
into ventilation system design.
The use of high-volume, low-speed (HVLS) fans or high velocity focused destratification
fans can be considered for installation in hangar bays to provide air mixing and create
air movement for comfort at the floor level. These are not a replacement for the exhaust
system described below. These fans can redirect heat back down to the occupied level,
can improve comfort and efficiency, and provide a homogeneous volume of air to
reduce concentration of local vapors. Coordinate the installation of fans with overhead
radiant heaters, fall protection, high-expansion foam generators, lights, bird netting,
bridge cranes and sprinklers. Coordinate with sprinklers in accordance with the
requirements of NFPA 13.
52
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-5.3.1 Exhaust
Provide exhaust systems at the heat or contamination sources. Exhaust systems will
operate continuously while the building is occupied. Exhaust fans in spaces that are
infrequently occupied such as conference rooms and break rooms, can be provided with
occupancy sensors or manual switches for operation. Provide energy recovery from
exhaust systems in accordance with ASHRAE 189.1. Provide exhaust systems in
accordance with ASHRAE and NFPA 90A.
53
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-5.3.1.6 Repair and Maintenance Areas Exhaust
Provide general exhaust in weapons vault and non air-conditioned repair and
maintenance areas at a minimum rate of 0.5 cfm/square foot (2.54 liters/sec/ m2) for
purposes of odor and fume mitigation. Provide weapons vault with non-sparking
exhaust fans, and all exhaust ducted to the exterior of the building. Operate exhaust
systems continuously while the building is occupied. Direct exhaust outside through the
roof to eliminate possibility of creating nuisances/hazardous situations to personnel at
ground level. If Life Cycle Cost effective, include air quality monitoring to reduce the
ventilation when it is not otherwise required.
For Navy: 7-14.5: Functional Data Sheets for Navy Functional Data Sheets.
Comply with applicable OSHA standards and end user requirements where
maintenance operations include working with heavy metals, grinding, sanding, and
working with chemicals.
Air Conditioning
The following criteria applies to air conditioning of rooms within the maintenance hangar
facility:
• Do not air condition hangar bays unless required for certain aircraft and
their maintenance procedures. Verify and coordinate with end user and
Facilities Requirements Document (FRD).
• Certain UAS/RPA aircraft have internal avionics systems that are sensitive
to high temperatures and can alarm when the inside temperature gets up
to 110ºF (43.3ºC) while the aircraft is inside the hangar during
maintenance operations. These aircraft may also have fuel systems that
need to be maintained below a certain temperature. A conditioned hangar
bay can be provided for these aircraft in accordance with the requirements
of the aircraft. In dry, arid climates, evaporative cooling systems can meet
this requirement and should be evaluated in lieu of air conditioning.
• Provide air conditioning for all maintenance shops and for those functional
areas where it is required for quality control of equipment, material, and
task.
• Serve shop spaces with a separate air handling/air conditioning system
from the administration type spaces.
• Administrative and shop areas will have positive pressurization with
respect to the hangar bay area. Administrative areas will have positive
pressurization with respect to shop areas.
54
UFC 4-211-01
13 April 2017
Change 1, November 2017
Where the fire alarm equipment cannot be located in a normally occupied conditioned
space as required by UFC 3-600-01 and 3-6.19.2.2 Location of Releasing System
Components because this space does not exist (E.g. an Alert Shelter with minimal
support space), condition the room housing the fire alarm equipment to meet the
conditions defined in 3-6.19.2.2 Location of Releasing System Components.
The following air conditioning system design considerations apply to critical, high-
density heat load spaces, such as server rooms and computer rooms, which contain
critical equipment that is sensitive to high temperatures:
• Provide redundant cooling units. Ensure that if one cooling unit goes
down, the remaining unit(s) can provide cooling for at least 75% of the
load.
• Provide a high space temperature alarm that will notify the Energy
Management Control System (EMCS).
• Provide condensate pumps in the cooling units if the condensate from the
cooling units cannot gravity drain to a nearby drain.
• Depending on the outdoor design conditions, provide a humidifier in each
cooling unit for winter humidification of the space.
Plumbing
Provide a drainage system for hangar door mullion pits and sliding hangar door tracks.
For Air Force: Connect drainage system to sanitary or storm sewer based on
requirements for other building drainage system and as required by Base Environmental
Office.
For Army and Navy: Connect drainage system to industrial waste or storm or sanitary
sewer based on requirements for other building drainage systems as required by Base
Environmental Office.
55
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-5.5.2 Wall Hydrants and Hose Bibbs
Provide exterior wall hydrants on perimeter walls of building with a maximum spacing of
100 ft. (30.5 m). Provide freeze-proof exterior yard hydrant in mechanical yards
containing chillers, condensers, condensing unit, and cooling towers. Provide all
hydrants with a vacuum breaker to prevent back flow.
Provide a hose bibb in all mechanical rooms. Provide hose bibbs with a vacuum breaker
to prevent back flow.
Size domestic water piping per ASHRAE and international plumbing code. Size the
domestic water heating system with storage and recovery for delivery of hot water to
every fixture per ASHRAE and international plumbing code. Provide usage diversity
factor of one for the showers. Size water heater(s) based upon anticipated usage or this
diversity factor. Instantaneous water heaters are permissible for remote fixtures. Install
floor drains and cleanouts in accordance with the latest version of International
Plumbing Code and UFC 3-420-01. Provide floor drains near ice machines, in rooms
requiring HVAC condensate removal, restrooms, showers, and mechanical rooms.
Per Energy Independence Security Act (EISA) Section 523 and UFC 1-200-02, evaluate
the cost effectiveness of solar domestic hot water.
Since hazardous materials are used in the aircraft maintenance process, provide floor
drains in the hangar bay spaces or shops/storage rooms that are tied to the station
industrial sewer with outlet to an oil/water separator tied to a collection system that will
capture and hold these materials for proper disposal. Drainage from interior hangar door
trench drains may be included in this system. Design in accordance with all applicable
environmental codes. Coordination of the collection system is required with the Base or
Station to determine the size of the collection system based on the frequency of
evacuating it (such as weekly, bi-monthly, monthly), volume of potential liquid spill, and
the size of the site where it is to be located.
Design trench drain system for easy cleanout of oil or other residue. Convey waste to
an oil/water separator prior to discharge to the sanitary sewer system. Refer to 3-11.3:
Trench Drains.
For Air Force: Do not install floor drains or trench drains in the hangar bay except
where explicitly indicated in Chapter 5: Air Force Specific Criteria.
Process Systems
56
UFC 4-211-01
13 April 2017
Change 1, November 2017
drops, with lubricator on every wall at spacing of every 25 ft. (7.6 m). In hangar bays,
provide compressed air drops, with lubricator, along back wall and side walls at spacing
of every 50 ft. (15.2 m). Coordinate with users any requirements for compressed air
hose reels in shops and hangar bays.
For Navy: Refer to Chapter 7: Navy Specific Criteria, 7-14.5: Functional Data Sheets
for Functional Data Sheets for specific requirements. Size air compressor system to
accommodate all tool loads including fuel cell evacuation equipment.
For Army: In hangars, mount compressed air connections on utility pedestals located
inside the perimeter access aisle.
57
UFC 4-211-01
13 April 2017
Change 1, November 2017
• A long hangar with multiple aircraft bays can be installed with PCA
equipment on each end of the building to minimize PCA duct length and
minimize the time required to get the system to required temperature.
• Provide utility pits (PCA only) with an automatic or manual drain in the pit
to handle any condensate that might drain from the PCA system.
• Provide utility pits with a cover rated for aircraft loading. Provide a locking
device so the cover is locked in open position for safety reasons.
• Provide PCA connections in utility pits with explosion proof electric
actuators with push button controls and open/close indication at the pit.
Integrate the valve control with the PCA unit control panel such that valves
and PCA operations are coordinated, controlled and monitored by one
system.
• Provide a detachable connection at the underside of the utility pit lid which
allows the hose to be connected to the lid when not in use.
3-5.8.2.2 Preconditioned Air Unit Quantity
Design and provide system for total quantity of PCA units installed equal to number of
aircraft bays. Combine the discharge of at least every two PCA units in a manifold
arrangement. The Owner has the final authority on configuration of PCA units to be
installed. Control each PCA unit from the utility pit or PCA hose connection.
58
UFC 4-211-01
13 April 2017
Change 1, November 2017
systems based on the BACnet® protocol in accordance with ANSI/ASHRAE Standard
135 and UFGS 23 09 23.13 20.
For Army: LonWorks® protocol is the preferred control system architecture for
facilities. Design and construct facility HVAC control systems based on the LonWorks®
(American National Standards Institute/Consumer Electronics Association (ANSI/CEA)-
709.1 and related technologies) in accordance with UFC 3-410-02 and UFGS 23 09
23.01.
General
Provide a building and systems in accordance with UFC 3-600-01 except where
additional requirements are added by this UFC. Use NFPA 409 only where explicitly
noted. If there is a conflict, this UFC supersedes UFC 3-600-01 and NFPA standards.
59
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.1.2 UAV or RPA Aircraft
Where required by UFC 3-600-01, protect hangars housing Unmanned Aerial Vehicles
(UAV) or Remotely Pilot Aircraft (RPA) in accordance with this UFC.
Refer to 3-3.1: Construction, Life Safety, and Fire Fighter Access of this UFC for
additional construction, life safety, and fire fighter access requirements.
Fire Hydrants
Design the fire water supply to meet the following fire flow demands for the required
duration. When the existing fire water supply cannot meet the flow or duration
requirements, modify the system or provide an independent fire water supply to meet
the requirements.
60
UFC 4-211-01
13 April 2017
Change 1, November 2017
sprinkler system and foam/water fire suppression system for 45 minutes
(min.).
• For other suppression system(s) within the hangar bay, provide additional
water supply in accordance with NFPA 409.
• Include the demand of the outside hose stream allowance where supplied
from the same fire water supply.
• Include domestic and industrial demands where required by
UFC 3-600-01.
Where a fire pump house, station, or pump room supplies more than one hangar,
provide pumps of equal capacity meeting the total fire water demand of the most
demanding hangar, and a redundant pump meeting the size of the largest pump.
When starting the fire pump, do not exceed ten seconds before the pump is operating at
the design pressure.
61
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.4.2.1 Piping Materials
Black steel piping is not permitted for installation below grade.
When non-metallic piping is used, use pipe specifically listed for "Fire Service"
applications by a NRTL. Non-metallic piping used for fire water distribution such as High
Density Polyethylene (HDPE), Polyvinyl Chloride (PVC), and filament-wound fiberglass,
is not permitted to be routed above grade or exposed within the building.
62
UFC 4-211-01
13 April 2017
Change 1, November 2017
Surge Arrestors
Provide listed or approved surge arrestors for fire protection systems with a minimum
rated working pressure of 275 psi (1,895 kiloPascals (kPa)).
• 1,500 ft. for a system not exceeding a working pressure of 175 psi.
• 1,000 ft. for a system not exceeding a working pressure of 250 psi.
• 500 ft. for a system not exceeding a working pressure of 175 psi, and
plastic piping is used such as PVC or HDPE.
• 300. ft. for a system not exceeding a working pressure of 250 psi, and
plastic piping is used such as PVC or HDPE.
• Provide 10 gallons (gal) (38 liters (L)) of capacity for each dry pipe or
preaction riser located on the riser manifold supplying a hangar bay.
• Provide 25 gal (95 L) of capacity for each foam/water riser located on the
riser manifold supplying a hangar bay.
• For each riser room, combine the surge capacity of the risers in the room
into a single common surge arrestor. Where risers feed different fire
areas, only use the greatest combined surge capacity from one fire area.
Connect this common surge arrestor to the riser manifold immediately
upstream of the protected risers.
• Where the fire pump is not located in the same room as the risers it
serves, provide 100 gal (380 L) capacity surge arrestors for each fire
pump. Locate this surge arrestor immediately downstream of the isolation
valve on the discharge side of the fire pump.
• The cumulative minimum capacity of each required fire pump surge
arrestor may be combined into a single common surge arrestor. Connect
this common surge arrestor to the fire pump header immediately
downstream of the isolation valve on the discharge side of the most
remote fire pump.
• Where surge arrestors are 100 gal (380 L) or larger in capacity, provide
floor stands.
63
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.5.3 Surge Arrestor Installation
Provide each arrestor with an indicating isolation valve to separate it from the system.
Electrically supervise this valve in the normally open position. Provide a drain after the
isolation valve to relieve pressure from the surge arrestor during testing and
maintenance. When connecting the surge arrestor to the riser, the use of piping, fittings,
and valving smaller than the connecting orifice on the surge arrestor is not permitted.
After the surge arrestor is installed and pressurized in the field with nitrogen per the
manufacturer’s written directions, provide a permanent label indicating the set pressure
of the arrestor. Do not pressurize the surge arrestor during hydrostatic testing of the
system.
Backflow Prevention
Where backflow prevention is provided for cross connection control, provide piping and
fitting materials upstream of the backflow preventer listed for use with potable water
systems such as ductile iron, stainless steel, and galvanized steel. Where fire pumps
are supplied directly from the domestic water system, install backflow prevention on the
discharge side of the pump.
Exception: Backflow prevention may be installed on the inlet side of the fire pump when
the following conditions are met with fire pump(s) operating at 150% capacity. The
quantity of pumps used in this calculation is the number expected in normal operation to
meet the system demand.
• Not less than 20 psi residual pressure at the backflow preventer inlet.
• Not less than 5 psi residual pressure at the fire pump inlet.
• Use outside stem & yoke (OS&Y) valving in the backflow preventer
assembly and locate the assembly a minimum of 10 pipe diameters
upstream of the pump suction flange.
Locate foam concentrate tanks, pumping equipment, and riser control valves associated
with the protection of the hangar bay in a dedicated fire protection equipment room with
a minimum 1-hour fire barrier. Although not required, other fire suppression equipment
is permitted within this room such as the wet pipe system for the support area. Locate
fire protection equipment rooms housing fire pumps and/or the incoming fire water
service at grade with doors providing direct access to the exterior. Where secondary
foam proportioning rooms are provided to facilitate the hydraulic design, provide this
equipment in dedicated fire protection equipment rooms with minimum 1-hour fire
barriers.
Do not install piping below a concrete slab within the hangar building. Use concrete
trenching with steel grating for all piping located below the floor line.
65
UFC 4-211-01
13 April 2017
Change 1, November 2017
between the cup drain and the main drain. Drains from the AFFF or Hi-Ex Foam risers
will have the ability to be contained and collected.
Provide a wye or basket strainer and an isolation valve for maintenance in the piping
ahead of foam system risers. Provide strainer baskets with stainless steel mesh sized
no greater than 1/4 in (6.4 mm).
Provide a flow control valve with remote resetting capability for each foam/water
system. Provide flow control valve with automatic re-closing feature and adjustable
speed control. Where an inductor is used for foam/water proportioning, provided field
adjustable pressure reducing trim. Install the manual release for the flow control valve
no higher than 5 ft. (1524 mm) above finished floor. For hydraulic calculations, include
the manufacturer’s minimum pressure drop across flow control valve for the features
indicated.
Where AFFF concentrate is used, pipe the main drain from the flow control valve into
the retention trench.
For Army: Refer to Chapter 6: Army Specific Criteria for foam/water proportioning
system.
Provide a single foam inductor per foam/water riser meeting the requirements outlined
below. Where more than one foam inductor is used, they may take suction from a
common concentrate tank. Do not supply more than one fire area from a single inductor.
66
UFC 4-211-01
13 April 2017
Change 1, November 2017
height of a near empty concentrate tank. Off the shelf pre-tuned generic
model inductors are not permitted.
• Design the inductor to 115% of the nominal injection rate such as the
inductor for 3% AFFF would be designed for a 3.45% injection rate.
• Size inductor for the exact orifice of foam/water pipe.
• Fit concentrate suction line of the inductor with a low loss brass, bronze,
or stainless check valve assembly by the manufacturer that is included in
the device's hydraulic design.
• Provide a design that indicates the inductor's flow rate, inlet pressure,
back pressure, and concentrate lift height for a near empty concentrate
tank. Hydraulically calculate the back pressure for the inductor using the
Hazen-Williams equation with a C-factor of a 100 for all piping
downstream of the inductor.
• Potential manufacturers at the time of this publication include Fomtec,
Skum, Matre Maskin, Wilson Foam, Ansul, Chemguard, and Delta Fire.
• Inductors meeting the performance criteria within this UFC are approved.
Provide a 3/4 inch (19 mm) copper line with ball valve from the fire water supply, that is
used for flushing the concentrate line after use. Provide sign with the following
instructions, "Flush concentrate line after discharge or testing. Close concentrate tank
shutoff valve prior to opening this valve. After flushing, drain concentrate line through
test connection prior to re-opening concentrate tank shutoff valve." Refer to Figure 3-9:
Inductor and Concentrate Tank Installation.
67
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-9: Inductor and Concentrate Tank Installation
Provide a closed cell double wall polyethylene concentrate storage tank compatible with
the required concentrate. Provide a reverse float level gauge with minimum 50 gallon
increments permanently marked on the tank or gauge. Indicate on the tank or gauge the
empty, full, and minimum level required to operate the system. Do not include the
inaccessible portion of concentrate at the bottom of the tank that cannot be accessed by
the suction line, in the tank's capacity markings. Provide a closeable fill opening and
pressure/vacuum vent assembly. When an inductor is used, enter the tank only through
the top with no taps on the bottom or sides of the tank.
68
UFC 4-211-01
13 April 2017
Change 1, November 2017
For Army: Exception, provide a single wall closed cell polyethylene concentrate
storage tank.
For Army: Exception, provide secondary containment for the storage tank and
associated foam concentrate pump pad capable of capturing the entire volume from the
largest concentrate storage tank.
Provide listed/approved gaskets for dry pipe service on all foam/water solution piping.
69
UFC 4-211-01
13 April 2017
Change 1, November 2017
been damaged. Dry and paint damaged areas with two full coats of a cold galvanizing
primer containing a minimum of 95% zinc.
Route foam/water solution piping in trenches to trench nozzles. Routing piping across
the hangar floor is not permitted. Provide end caps tapped with a valve at the end each
of branchline in the trench nozzle system. Use these taps for the attachment of pressure
gages during testing, and drainage of the piping system after activation.
Provide a linear test header to meet the fire water demand of the foam/water system.
For Air Force: The foam/water test system header and fire pump test header (when
provided) may be combined. When a common test header is used, provide valving to
permit independent testing of each foam/water riser and each fire pump.
In geographic locations having a 99.6% dry bulb temperature less than 32ºF (0ºC) per
UFC 3-400-02 Engineering Weather Data, provide test header with automatic ball drip
routed to the exterior.
Hose Demand
70
UFC 4-211-01
13 April 2017
Change 1, November 2017
Overhead Sprinkler System for the Hangar Bay
Protect the hangar bay with water only closed head wet pipe, dry pipe, or preaction
sprinkler systems. Wet pipe automatic sprinkler systems are only permitted in the
hangar bay when the following conditions are met:
Design the sprinkler piping such that the majority or all of the system drains back to the
riser. Minimize or eliminate the requirement for remote drainage connections in the
hangar bay.
Where wet pipe systems are installed in areas with a 99.6% dry bulb temperature of
40ºF (4.4ºC) of less per UFC 3-400-02 Engineering Weather Data, adhere to the
following piping installation requirements:
• Locate the inspector’s test connections at the riser. Test stations are not
permitted in the hangar bay.
• Where drainage piping is required in the hangar bay, do not route the
portion of the drainage piping normally containing water and associated
drainage valve more than 5 ft. (1524 mm) below the level of the lowest
71
UFC 4-211-01
13 April 2017
Change 1, November 2017
sprinkler head in the hangar bay. Route the remaining normally empty
drainage piping to the building exterior.
3-6.15.3.1 Wet Pipe Sprinkler System Temperature Monitoring
In geographic locations having a 99.6% dry bulb temperature less than 40ºF (4.4ºC) per
UFC 3-400-02 Engineering Weather Data, provide temperature sensors in the hangar
bay. Provide listed/approved fixed temperature sensors set at 32ºF (0.0ºC). Locate
temperature sensors at the same level as the adjacent sprinkler head branchline.
Provide center to center spacing not exceeding 200 ft. (61.0 m), or spacing from the
wall not exceeding 100 ft. (30.5 m). Alarm low temperature conditions at the FACU as a
supervisory condition and the Energy Management Control System.
For Navy: Provide a hydraulically designed low level AFFF trench nozzle system for
hangar bays. Refer to Chapter 7: Navy Specific Criteria for additional requirements
regarding the trench nozzle system design.
Where more than one AFFF trench nozzle system is present within a fire area, design
the releasing system to only release the AFFF trench nozzle system associated with the
fire event. Such as where a hangar is subdivided by a non-rated wall into two bays with
independent AFFF trench nozzle systems or where a large hangar bay is provided with
multiple AFFF trench nozzle systems, zone the initiation devices to only release the
AFFF trench nozzle system associated with the fire event. Design the fire flow and
concentrate supply to allow for sufficient simultaneous operation of all AFFF trench
nozzle systems within the fire area that are wholly or partially within a 100 ft. (30.5 m)
horizontal radius of any point on the hangar bay floor.
72
UFC 4-211-01
13 April 2017
Change 1, November 2017
Hi-Ex Foam System
For Air Force and Army: Provide a hydraulically designed low level Hi-Ex foam
system for hangar bays. Refer to Chapters 5 and 6 for additional requirements
regarding the Hi-Ex system design.
Where more than one Hi-Ex foam system is present within a fire area, design the
releasing system to only release the Hi-Ex foam system associated with the fire event.
Such as where a hangar bay is subdivided by a non-rated wall into two bays with
independent Hi-Ex foam systems or where a large hangar bay is provided with multiple
Hi-Ex foam systems, zone the initiation devices to only release the Hi-Ex foam system
associated with the fire event. However, design the fire flow and concentrate supply to
allow for sufficient simultaneous operation of all Hi-Ex foam systems within the fire area.
Tap the generator foam/water supply piping with a valve to allow for the attachment of a
pressure gauge or sampling hose during testing.
73
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.17.4 Hi-Ex Foam Generator Location
Locate Hi-Ex generators to discharge within close proximity, but not directly upon the
aircraft or surrounding maintenance platforms. When mounting generators in the
horizontal position, take into account the throw pattern of the Hi-Ex foam discharge. Do
not locate the generator where the Hi-Ex foam discharge is obstructed by items such as
structural members, lighting fixtures, or bird screen or in areas that obstruct the use of
service equipment such as the crane travel path. Use the initial discharge from the foam
generators to protect under the aircraft fuselage and underwing area, prior to spreading
to the remaining hangar bay floor area.
Do not provide generators in locations where the developing foam blanket will block
exits from the hangar bay within the first minute of discharge. Blocked exits are defined
as an exit that is obstructed by a foam blanket exceeding 5 ft. (1.5 m) in depth. In small
hangar bays where the entire floor may be covered with foam within the first minute,
provide generator locations so exits are one of the last areas blocked.
Hydraulic Calculations
74
UFC 4-211-01
13 April 2017
Change 1, November 2017
o Time for the foam/water reach the each generator based on the
piping velocities in the hydraulic supply calculation.
o Time for the foam to reach the floor of the hangar bay after
discharging from the generator based on the height and orientation
of each generator.
o Time for the foam to spread across the floor based on the
manufacturer's foam spread diagrams, or at a rate not to exceed 1
ft. /sec.
• For AFFF trench nozzle systems, provide a calculation demonstrating the
most remote trench nozzle achieves the minimum discharge pressure
within 30 seconds. This calculation method is a reasonable approach to
demonstrate the design meets the performance requirements, but does
not take all aspects into consideration. This calculation method does not
remove the obligation to demonstrate system compliance during testing.
Include the following parameters in determining the 30 second limitation is
met:
o Time for the RSFACU to open the flow control valve after initiation
of the manual foam releasing station.
o Time for the foam/water reach the most remote trench nozzle
based on the piping velocities in the hydraulic supply calculation.
R = ([V/T] + RS) x CN x CL
Where:
75
UFC 4-211-01
13 April 2017
Change 1, November 2017
• CL = Provide a compensation for loss value of not less than 2.0 for hangar
bays less than 15,000 ft2 (1,394 m2), 2.5 for hangar bays between 15,000
and 30,000 ft2 (1,394 - 2,787 m2), and 3.0 for all other hangar bays.
Provide a separate FACU and RSFACU for each building. Where multiple releasing
systems are provided within a single building, they may be combined into a single
RSFACU.
Install the FACU and RSFACU in a location readily accessible to the emergency
responders and maintenance personnel.
76
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.19.2.3 Foam/Water and Preaction Supervised Solenoid Disconnect
Provide a key operated supervised disconnect switch to physically disable the solenoid
for each foam/water and preaction riser (if provided). Provide switch that disables the
releasing functions without the use of programming, while leaving all other functions of
the panel operational. Do not provide a trouble signal upon operation of the disconnect.
Monitor the disconnect switch at the RSFACU. Provide a supervisory signal to the
receiving station upon operation of the disconnect.
Locate the disconnect switch in the riser room, in a readily accessible location near the
solenoid. Provide a sign near the disconnect switch with a white background and a
minimum 1/2 inch wide blue border, with "DISABLE FOAM SYSTEM" or "DISABLE
PREACTION SYSTEM" in red lettering not less than 1 inch (25.4 mm) high. Provide
engraved labels on the disconnect switch indicating when the system is "ENABLED" or
"DISABLED". Do not install backboxes or route conduit in front of sign in a manner that
obstructs any lettering.
Provide notification from the fire alarm reporting system to the receiving station in
accordance with the FACU and RSFACU matrixes.
77
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 3-3: FACU Functional Matrix
78
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.19.4 FACU, RSFACU, Auxiliary Panels and Component Installation
Where panels are located in normally occupied areas, provide recessed panels and
combine miscellaneous components in common recessed enclosures to provide a clean
installation. Where an auxiliary battery supply is required and cannot be recessed within
the wall, locate it remotely in a normally unoccupied area.
Where panels, devices, and appliances are subjected to water spray/runoff under
normal operating conditions, provide National Electrical Manufacturers Association
(NEMA) 250 Type 4 enclosures and water tight conduit. Regardless of environmental
conditions, do not provide openings or conduit entry into the top of the RSFACU.
Route conduit into the bottom of the backbox for manual foam releasing stations, stop
stations, and flame detectors. Provide the low point of this conduit with a drain. Where
the conduit is in a hazardously classified area, provide breathers in isolated portions of
the conduit such as where sealed offs are provided. Rate drains and breathers for the
electrical hazard classification in which they are installed, but not be less than NEMA
250 Type 4.
79
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.19.8 Manual Foam Releasing Stations
Provide distinctively different NEMA 250 Type 4 manual foam releasing stations and
signage from the manual fire alarm pull stations. Provide station and tamper cover with
colored portions in yellow and lettering reading "FOAM"; the words "FIRE", "ALARM", or
"AGENT" are prohibited to appear on the cover or station. Provide locking type manual
foam releasing stations that when activated require a key to be reset. Provide
conventional manual foam releasing stations. Do not locate addressable monitor
modules for the manual foam releasing stations in the hangar bay.
Where foam/water systems are zoned per 3-6.16.1: AFFF System Performance or 3-
6.17: Hi-Ex Foam System Performance, provide manual foam releasing stations within
each zone for the release of that zone. Provide additional 1 inch (25 mm) high black
block lettering on the sign indicating which zone is served by the manual foam releasing
station.
For Army: Zoned manual foam release stations are not permitted. Program the foam
release stations to simultaneously release the foam/water discharge from all zones
viewable from the foam release station.
80
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.19.9.1 Manual Foam Stop Station Operation
Once depressed, and so long as the button is held down, design the system so the stop
station prevents/stops discharge of the foam/water system regardless of whether or not
the foam/water system was activated automatically or manually, and whether or not the
activation occurs prior to or after the stop station is pressed and held. Program the stop
stations to simultaneously stop the foam/water discharge from all zones viewable from
the depressed stop station. Unless the RSFACU has been reset and all activation
alarms (manual and automatic) have been cleared; restore the foam/water system
operation when the foam stop station button is released. Do not exceed 15 seconds to
fully close the flow control valve when the foam stop station button is depressed under
full flow. Where the foam/water system is still in alarm, do not exceed 5 seconds to fully
open the flow control valve upon release of the foam stop station button.
To the right of the stop button provide the following in minimum 1/2 inch (12 mm) high
black lettering "To stop foam system, press and continuously hold STOP button until
relieved by emergency responders. There may be up to a 30 second delay after
pressing the STOP button before the foam stops."
81
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-10: Start Foam System Signage
82
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-11: Stop Foam System Signage
83
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.19.11.2 Optical Flame Detector Location
Provide a sufficient number of optical flame detectors around the perimeter of the
hangar bay, such that all portions of the hangar bay are within the range and cone-of-
vision of at least three detectors. Exception: The area of the hangar bay within 5 ft. (1.5
m) of the perimeter wall is not required to be within the cone-of-vision of an optical flame
detector. No aircraft silhouette will be solely visible from optical flame detectors located
on one side of the fuselage. A minimum of two optical flame detectors covering the
aircraft silhouette are required on each side of the fuselage.
Angle detectors and provide blinds (field of view inhibitors) so the cone-of-vision is
contained within its designated suppression zone and does not extend more than 5 ft.
(1.5 m) outside the hangar bay, into another fire area such as through a normally open
roll-up fire door, or is within the view of hot sources such as radiant heaters. Locate
optical flame detectors at a sufficient distance per the manufacturer's recommendations
from sources that may cause false alarms such as welding, solar glare, radiant heaters,
aircraft engine exhaust, strobes, hot surfaces and other relevant sources.
84
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Linear thermistor (line-type electrical conductivity) fire detector having a
temperature setting of 170ºF (76ºC). Space detection lines with a
maximum spacing of 30 ft. (9.1 m). Use the manufacturer's approved
testing method to verify the detector's response setting after installation.
On curved roofs or roof exceeding a 2 in 12 pitch, install thermistor
detectors perpendicular to the slope or arc (along the axis of the curve).
3-6.19.12.2 Thermal Fire Detector Installation
Provide a fire detection zone for each corresponding preaction sprinkler system.
Activate the associated preaction valve for the floor area covered by the zone.
"May I have your attention. There is a fire emergency in the hangar bay. Please
leave the building by the nearest exit. Do not exit through the hangar bay."
<Pause 2 seconds>
Repeat
• Visual notification coverage is not required in the center of the hangar bay.
85
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Provide strobes not exceeding 110 cd around the perimeter of the hangar
bay, not including the hangar bay door opening, in accordance with the
room spacing requirements for wall-mounted visible appliances in
NFPA 72.
For Air Force and Army: Strobes not exceeding 177 cd are permitted.
Electrical or mechanical supervision is not required for normally closed control valves,
unless opening the valve is detrimental to the system operation. When supervision is
required on normally closed valves, provide electrical supervision such as cable type
monitoring.
Provide signs with white background and a minimum 1/2 inch wide blue border with red
lettering not less than 1 inch (25.4 mm) high. At a minimum, provide each sign with the
language "EMERGENCY FOAM SHUTDOWN PROCEDURE" and the order and action
to be performed such as "1 - CLOSE FOAM CONCENTRATE VALVE", "2 - CLOSE
FOAM/WATER RISER CONTROL VALVE". Continue the sequence as required for
shutdown.
86
UFC 4-211-01
13 April 2017
Change 1, November 2017
Testing
At a minimum, provide the testing and reports outlined in this section. Coordinate testing
personnel as required to demonstrate the coordination and communication of the fire
protection systems through full functional testing. Independent testing of each individual
fire protection system is not a substitute to the functional testing requirements. Such as
depressing the stop button and witnessing the de-energizing of the solenoid, does not
adequately demonstrate the flow control valve will stop the foam/water under full flow.
At a minimum, provide a factory authorized representative for the startup and/or testing
of the following systems as outlined below:
• Who will perform the testing and who will be the onsite factory authorized
representatives.
• What are the safety precautions taken during testing.
• How will the foam/water system be tested to demonstrate the performance
criteria has been met.
• How will the event be recorded for future review.
• What are the testing procedures to demonstrate the coordination and
communication of the fire protection systems associated with the
foam/water discharge.
• How will the hangar bay be protected during the discharge of foam.
• How will the foam be captured during the discharge and disposed.
87
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-6.20.3 Preliminary Testing
Provide acceptance testing for the fire suppression and fire alarm systems complying
with NFPA 11, 13, 20, 24, and 72 as applicable. At a minimum, provide the following
preliminary testing reports.
ELECTRICAL
89
UFC 4-211-01
13 April 2017
Change 1, November 2017
Hazardous (Classified) Locations
Design hazardous (classified) locations including the hangar bay and adjacent spaces
in accordance with NFPA 70 requirements for hazardous locations. At a minimum,
classify adjacent spaces that are not suitably cutoff as Class I Division 2 up to 18 inches
(460 mm) above the floor of the hangar bay adjacent to the space.
If a space is adjacent and communicates with a hazardous location, the term "suitably
cutoff" in NFPA 70 is defined as either of the following conditions as shown in Figure
3-12: Adjacent Space Electrical Hazardous Classifications:
90
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 3-12: Adjacent Space Electrical Hazardous Classifications
91
UFC 4-211-01
13 April 2017
Change 1, November 2017
Hangar Bay Door Power
Provide a separate and dedicated power supply from the facility transformer or ahead of
the main service disconnecting means. Provide power to the hangar bay door such that
the door remains energized when the main disconnect switches for general hangar
power are shut off.
Provide an electric door track heating system in accordance with heating requirements
listed in 3-5.2: Heating. A heated antifreeze system may be used in lieu of an electric
door track heating system. Coordinate which system is to be used with the mechanical
design.
Photovoltaic (PV) systems on flight line facilities are currently prohibited. If a glare
analysis has been previously approved for other facilities on the installation PV systems
on the flight line facilities may be considered when determined to be life cycle cost
effective and project funds are available.
Note: Renewable energy requirements for facilities are currently under development in
UFC 3-440-01.
Backup Power
92
UFC 4-211-01
13 April 2017
Change 1, November 2017
3-7.5.2 Backup Generator
Backup generators and Uninterruptible Power Supply (UPS) backup power systems are
not generally required for this facility type.
Backup generators may be considered for situations in which backup power is required
for the hangar door installation or for missions attached to the hangar. When authorized,
provide backup generator power in accordance with UFC 3-540-01. Refer to C-10.2 for
discussion on Vertical Lift Fabric Door operations.
Aircraft have specific power requirements, including unique voltages, frequencies, and
capacities. Review the aircraft requirements of the aircraft being maintained in the
hangar bay to determine the appropriate services. Provide appropriate services in
voltage, frequency, and capacity to service the aircraft.
93
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Provide wall-mounted cable storage racks for storage of the cable when
receptacles are installed. Mount receptacles above electrical hazardous
location. Provide floor-mounted cable protectors from the wall across the
service lane to the aircraft side of the service lane. Lay cables in the cable
protector to protect cable from cross traffic while the cables are extended
and in use.
• When approved, electrically or air driven reels may be provided. Install
electric motors above the electrical hazardous location. Provide reel
controls as part of the cable assembly. Coordinate motor size and type
with length and weight of cable provided.
• For Army and Navy: Cables connecting to the service point may or may
not be provided as part of the service.
• For Air Force: Refer to Chapter 5: Air Force Specific Criteria for
additional requirements.
3-7.6.1.2 Permanently-Mounted Pedestal
For Air Force and Navy: Permanently-mounted pedestals are not permitted.
For Army: Refer to Chapter 6: Army Specific Criteria for additional requirements.
Aircraft have specific power requirements, including unique voltages, frequencies, and
capacities. Review the requirements of the aircraft being maintained in the hangar bay
to determine the appropriate special power systems required. Provide the appropriate
aircraft power systems in voltage, frequency, and capacity to service the aircraft being
maintained.
94
UFC 4-211-01
13 April 2017
Change 1, November 2017
requirement at the aircraft point-of-service and to meet the requirements of the aircraft
power monitor.
For Army and Navy: The use of centralized systems servicing more than two aircraft
are prohibited.
400 Hz Equation
I = current in Amps.
X1 = Reactance
For Army and Navy: 400 Hz converters, cables, and connector are Real Property
Installed Equipment (RPIE) equipment. The use of centralized systems servicing more
than two aircraft are prohibited.
For Air Force: Refer to Chapter 5: Air Force Specific Criteria for additional
requirements.
Coordinate how the cables are being provided for the project with the users. The cables
may be part of the Military Construction (MILCON) or the cables may be equipment
provided by the user. If the cables are permanently affixed to the facility distribution
system, the cable is considered to be part of the MILCON. If the cables can be
disconnected from the facility distribution system, the cable is provided by the user.
For Army and Navy: 28VDC ground power units, cables and connector are RPIE
equipment. The use of centralized systems servicing more than two aircraft are
prohibited.
For Air Force: Refer to Chapter 5 - Air Force Specific Criteria for additional
requirements.
Coordinate how the cables are being provided for the project with the users. The cables
may be part of the Military Construction (MILCON) or the cables may be equipment
provided by the user. If the cables are permanently affixed to the equipment, the cable
is considered to be part of the MILCON. If the cables can be disconnected from the
facility distribution system, the cable is provided by the user.
For Air Force: Refer to Chapter 5: Air Force Specific Criteria for additional
requirements.
For Navy: Refer to Chapter 7: Navy Specific Criteria for additional requirements.
Coordinate how the cables are being provided for the project with the users. The cables
may be part of the Military Construction (MILCON) or the cables may be equipment
provided by the user. If the cables are permanently affixed to the equipment, the cable
96
UFC 4-211-01
13 April 2017
Change 1, November 2017
is considered to be part of the MILCON. If the cables can be disconnected from the
facility distribution system, the cable is provided by the user.
Coordinate the requirement for ordnance grounding with the users supported. Areas of
consideration may include, but is not limited to, the following:
For Army: Refer to Chapter 6: Army Specific Criteria for additional ordnance
grounding requirements.
For Navy: Refer to Chapter 7: Navy Specific Criteria for additional ordnance grounding
requirements.
Lightning Protection
For Navy: Refer to Chapter 7: Navy Specific Criteria for additional requirements.
97
UFC 4-211-01
13 April 2017
Change 1, November 2017
Industrial Controls
Coordinate industrial controls systems including, but not limited to, energy management
systems, building management systems, HVAC controls, mechanical controls systems,
crane controls systems, diverter valves, and plumbing control systems, with project
location existing systems. Provide the ability to connect industrial controls systems with
local site control systems as required, to report to installation-wide systems. Design
industrial control system in accordance with NFPA 70 and manufacturer's requirements
for each system.
Plan, design, acquire, execute and maintain all control systems (including systems
separate from an energy management control system) in accordance with DoD
Instruction 8500.01 and DoD Instruction 8510.01, and as required by individual Service
implementation.
Mission(s) associated with the aircraft may be incorporated into the maintenance
hangar. These missions may include but are not limited to the following:
• UAS/RPA operations
• Command Operations
• Medical Evacuation Operations
• Flight Operations
• North Atlantic Treaty Organization (NATO) Operations
• Training Operations
These mission(s) may have significant impact on the electrical system including:
98
UFC 4-211-01
13 April 2017
Change 1, November 2017
COMMUNICATIONS
Consider potential obstructions that may cause interference, including aircraft and
maintenance stands, when designing the wireless system.
Public Address
Provide a Public Address (PA) system with coverage to all areas of the facility. Provide
a complete and functioning integrated public address system. Coordinate the PA
system with the activities. Integrate the PA system with the MNS per UFC 4-021-01.
Interface the PA system with the telephone system such that the telephone system
provides access to the PA system.
99
UFC 4-211-01
13 April 2017
Change 1, November 2017
Cable Television (CATV) Systems
Audio/Visual System
A/V System infrastructure includes raceway systems and cabling only. Coordinate
cabling types and raceway size with the GFGI and GFCI equipment provided. Provide
power for A/V equipment per the A/V requirements.
• Coordinate the infrastructure size and location with the design of the
CCTV system.
• Provide power for CCTV equipment per the CCTV requirements.
Where specifically authorized to also provide CCTV equipment as follows.
• Provide cameras within the hangar bay and on the exterior of the building
to monitor the apron.
• Provide monitoring equipment in user identified locations.
Refer to 3-8.7: Electronic Security Systems for CCTV for security systems is covered
under Electronic Security Systems.
When required by the users and authorized, provide radio system antenna, cable and
raceways to support GFGI radio systems. Provide radio system drops in locations
identified by the users.
When required by the users and authorized, provide satellite system cable and
raceways to support GFGI satellite systems. Provide satellite system drops in locations
identified by the users.
100
UFC 4-211-01
13 April 2017
Change 1, November 2017
Electronic Security Systems
When required by the users and authorized, provide Electronic Security Systems (ESS)
in accordance with UFC 4-021-02.
• UAS/RPA operations
• Command Operations
• Medical Evacuation Operations
• Flight Operations
• NATO Operations
Provide all cranes in accordance with the relevant portions of the following standards:
101
UFC 4-211-01
13 April 2017
Change 1, November 2017
Crane Operating Envelope
The crane operating envelope, including clearances, will not have interferences with the
electrical, HVAC, or similar equipment, as specified by OSHA 29 Code of Federal
Regulations (CFR) 1910.179. Clearly identify the crane operating envelope on the floor
plans and building section drawings.
Provide overhead bridge crane with infinitely variable-speed electric motors and controls
for the bridge, trolley and hoist. Crane is to be operable from the floor. Provide a crane
disconnecting means for maintenance in a location that is accessible without the use of
lifts or ladders.
3-9.2.1 Controls
Provide crane control interfaces, which are accessible at floor level. Provide controls for
accessibility of the entire coverage area, horizontally and vertically.
Cranes may have wire connected controls or wireless controls. Coordinate the selection
of wire connected controls and wireless controls with the users. When wireless controls
are provided, coordinate the frequency of wireless controls with local frequency
manager.
HANGAR DOORS
Provide either a vertical lift fabric door system or horizontal sliding hangar doors.
Coordinate with the user to provide type of hangar door and controls required for
maintenance operations. Refer to C-10: HANGAR DOOR for guidance on best
practices for hangar door selection and design. Refer to 2-4: Net to Gross Area in
Aircraft Maintenance Hangars for requirements on calculating building gross square
footage at different types of hangar doors. Hangar doors are to be fully operational
when subjected to wind pressures up to a minimum of 15 psf. Include signage noting
operational wind speed at which doors should be closed and secured with wind lock
activation.
102
UFC 4-211-01
13 April 2017
Change 1, November 2017
Design hangar doors to resist the component and cladding wind pressures determined
in accordance with UFC 1-200-01. Consider the full deflection range and wind uplift to
design the interface between the superstructure and the door systems. Design hangar
doors in accordance with all provisions of UFC 4-010-01 where applicable.
3-10.1.1 Doors
Provide the vertical lift fabric doors, as a complete system from a single source
manufacturer for the purpose of closing a hangar maintenance bay space. Design the
Aircraft Maintenance Bay superstructure to support the doors vertically and laterally.
Design for the different load combinations imposed by open and closed door panels
resulting in eccentric wind loads or mechanical loads from the door and mullion hoisting
equipment. The mullions of the door system connect to pits at grade which serve to
restrain the mullions from motion perpendicular to the face of the doors. Design the pits
to resist the concentrated mullion loads and provide a means of draining water from the
pits.
Design VLFD hangar doors to be individually operated with an upward acting lightweight
framing system with polyvinyl fabric facing. Design doors in sections with lifting mullions
between door sections. Design features include electric operation, personnel exit doors,
and translucent fabric.
3-10.1.2 Safety
Provide an intrinsically safe electric safety edge on the bottom of the edge of each door,
continuous over the full length of the door.
Provide fabric doors with a wind lock to secure the door prior to extreme wind conditions
and to prevent door uplift. Provide the wind lock with a proximity switch to show proper
engagement of the wind lock for the operator's benefit. Design VLFDs in accordance
with UFGS 08.34.16.20.
3-10.1.3 Catwalk
Provide a catwalk for accessing the motors and other serviceable items of the fabric
door. Provide access to maintain vertical lift fabric door equipment, motors, limit
switches, and other serviceable door parts. Provide access to the catwalk from inside
the hangar.
Hangar doors are to be a series of insulated, horizontal sliding leaves with protected,
preformed metal or sheet-steel siding. Support each sliding door on hardened steel
wheels rolling on continuously supported recessed rails with guide rails at the top of the
doors. Hangar doors are to be of hot-rolled steel construction and designed and built to
the same standards as the main Aircraft Maintenance Bay superstructure. Provide hot-
rolled steel tension and compression bracing members. Hangar door frames will not
103
UFC 4-211-01
13 April 2017
Change 1, November 2017
depend on the metal or steel siding to provide diaphragm actions. Provide insulation
values equal to the minimum values required for the exterior walls of the Aircraft
Maintenance Bay. Provide waterproof weather stripping at all door system joints.
Support the hangar doors at grade with a concrete hangar door rail foundation. Design
the foundation to be compatible with the building foundation and consider the potential
for differential settlement. In the hangar door rail support foundation, provide for surface
drainage with intermediate drainage, at a maximum spacing of 10 ft. (3.0 m). In cold
climates provide a door track heating system. Design the hangar door rail foundation to
have contraction joints constructed in the top slab placement to prevent random
cracking of the surface of the hangar door rail foundation. Integrate the contraction
joints with the door rail drainage structures.
104
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 3-4: Sliding Hangar Door Pockets
Hangar door panels may be individually electric motor operated and controlled or may
be operated in groups. Coordinate with the user to provide hangar door controls as
required for maintenance operations. Individually operated panels are preferred
because they are the most flexible system. They allow any panel to be moved anywhere
in the door opening without moving any other panels. The least flexible operation is
anchored groups. The lead panel of an anchored group is motorized and all other
panels in the group are interconnected by a cable system anchored to the building,
typically in a door pocket. All panels in each anchored group start to move at the same
time and arrive at their fully-open or fully-closed positions simultaneously. Floating
groups are more flexible than anchored groups, but not as flexible as individually
operated panels. The panels on each end of a floating group are motorized and each
can collect the other doors of the group as they move in either direction. Floating groups
can be collected and stored anywhere on in the opening, or in a pocket, but operate as
a group. Design each drive unit with a release mechanism and provide a means of
movement in the event of power failure. The normal mode of operation will be an
electric drive and the minimum speed of door travel will be 60 feet per minute. Control
the doors with momentary contact-type push buttons located near the leading edge of
the door and limit switches on each door leaf. Install safety devices to prevent injury to
personnel and damage to equipment during movement of the door sections. Design
steel sliding hangar doors in accordance with UFGS 08 34 16.10.
For Navy: Refer to Chapter 7: Navy Specific Criteria for criteria for hangar door types,
operation and control.
105
UFC 4-211-01
13 April 2017
Change 1, November 2017
Hangar Door Power
Refer to 3-7.2: Hangar Bay Door Power for hangar door electrical requirements.
Floor Slope
Arrange floor elevations within the hangar bay to prevent fuel/liquid spills within the
hangar bay from flowing into adjacent shop/storage areas or from one aircraft to an
adjacent aircraft. The finished floor elevation of the remainder of the facility is required
to be above the highest floor elevation of the hangar bay. Coordinate hangar floor
elevations with the existing sanitary sewer elevation to avoid the need for ejection
pumps where feasible. Provide hangar floor sloping at a minimum 0.5% towards the
flight line door. Provide additional cross-slopes to keep liquid spills from flowing into
adjacent bays, or to direct flows towards trench drains, when provided.
Trench Drains
106
UFC 4-211-01
13 April 2017
Change 1, November 2017
FUEL CELL MAINTENANCE
For Navy: Refer to Chapter 7: Navy Specific Criteria for criteria for fuel cell
maintenance bays
For Air Force: Refer to Chapter 5: Air Force Specific Criteria for additional criteria for
fuel cell maintenance bays.
WASH BAY
General
If limited aircraft wash function is expected to be performed within a hangar bay provide
the features as described below. This function within the hangar bay is not intended to
replace the function of an outdoor wash rack or wash apron, nor is it intended for full
aircraft cleaning, dry media stripping or Painting/Chemical De-Paint operations. High
pressure washing is not allowed and not intended to be covered by these requirements.
Refer to UFC 4-211-02 for Aircraft Corrosion Control and Paint Facilities including wash
racks in hangar bays.
Architecture
Provide moisture resistant interior face of walls such as painted Concrete Masonry Unit
(CMU) up to 10 ft. (3.0 m) above finished floor elevation. Provide a moisture-resistant
interior face on the hangar door such as enameled metal panels up to 10 ft. (3.0 m)
above finished floor elevation.
Plumbing
Provide the following for any aircraft bay in the hangar used for limited aircraft wash:
Electrical
Provide the following for any aircraft bay in the hangar used for limited aircraft wash:
107
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Wet location light fixtures within 10 ft. (3.0 m) of the aircraft envelope.
Communications
Design the aircraft maintenance facility to eliminate fall hazards. If fall hazards cannot
be eliminated, ensure that a viable fall prevention and protection system is identified by
the user and provide where applicable. Provide path and fall protection system for all
roof-mounted lighting, equipment and platforms from the interior roof access platform.
These systems can be facility based systems such as horizontal life lines and
retractable life lines and non-facility based systems such as aircraft stands/platforms,
aircraft safety line attachments, or mobile cranes. Refer to APPENDIX C: BEST
PRACTICES, for further discussion.
108
UFC 4-211-01
13 April 2017
Change 1, November 2017
EMERGING AIRCRAFT
The F-35 Lightning II (F-35) is a 5th Generation fighter, combining advanced stealth
with fighter speed and agility, fully fused sensor information, network-enabled
operations and advanced sustainment. There are three variants to the F-35 that will
replace fighter aircraft of the US armed forces as well as at least 10 other countries. The
F-35A fixed-wing variant will replace the A-10 and F-16 for the US Air Force. The F-35B
VTOL variant will replace the AV-8B Harrier for the U.S. Marine Corps. The carrier
variant F-35C will replace the F/A-18 for the US Navy and the U.S. Marine Corps.
Architectural
For Navy: F-35 hangars may require a Special Access Program Facility (SAPF) space.
Refer to 2-2.3 - Secure Spaces for standards that apply to the construction of secure
spaces. Refer to Chapter 7: Navy Specific Criteria for additional Navy SAPF
requirements.
109
UFC 4-211-01
13 April 2017
Change 1, November 2017
Mechanical Systems
• Provide cooling air for the aircraft in the F-35 aircraft hangar bay.
Coordinate the service point locations with users. Coordinate the aircraft
PCA hose connection requirements with the 2015 FRD. Size the cooling
air system to support the aircraft. Provide one PCA unit per aircraft
parking position with a minimum of every two PCA units connected with a
common discharge manifold. The Owner has the final authority on
configuration of PCA units to be installed. One aircraft requires air to be
supplied at 46.6 pounds per minute at 35 to 55 degrees Fahrenheit at a
minimum pressure of 5.25 psig (-0.25/+0.50 psig) with maximum moisture
content of 0 to 55 grains per pound of dry air and particulates per pound of
air at 0.02 grams with maximum particle size of 50 microns. Thirty minutes
is the maximum time duration to deliver the required PCA temperature,
pressure and airflow at the aircraft connection from a steady state off
condition.
• PCA air quality specifications are based on the 2015 FRD and are
considered minimum requirements. Validate against the latest F-35 FRD
and use the most restrictive requirements. Maximum time duration noted
in this UFC to deliver the required PCA must not be increased regardless
of any circumstances.
Electrical Systems
Communication Systems
The F-35 system requires the Autonomic Logistics Information Systems (ALIS)
communication systems. Segregate the ALIS System from all other communication
systems within the maintenance hangar building.
Coordinate locations of ALIS and network connections with the user. The Navy requires
SAPF for all ALIS spaces. Air Force and Army may require a SAPF. Coordinate the
requirement for secured spaces with the project’s site security officer. Refer to 2-2.3:
Secure Spaces for additional information on secured spaces.
For Navy: Refer to Chapter 7: Navy Specific Criteria for additional requirements.
110
UFC 4-211-01
13 April 2017
Change 1, November 2017
UNMANNED AIRCRAFT SYSTEMS AND REMOTELY PILOTED
AIRCRAFT
New Unmanned Aircraft Systems (UAS) and Remotely Piloted Aircraft (RPA) are being
introduced at a relatively fast rate and may be considered emerging aircraft. Specific
requirements and direction are provided in previous Chapters.
For Air Force: Refer to Chapter 5: Air Force Specific Criteria for additional RPA
specific requirements.
For Army: Refer to Chapter 6: Army Specific Criteria for additional UAS specific
requirements.
For Navy: Refer to Chapter 7: Navy Specific Criteria for additional UAS specific
requirements.
111
UFC 4-211-01
13 April 2017
Change 1, November 2017
112
UFC 4-211-01
13 April 2017
Change 1, November 2017
AIR FORCE SPECIFIC CRITERIA
INTRODUCTION
Current US Air Force aircraft maintenance strategy indicates centralized services are
provided at an installation level for most maintenance functions performed on the
aircraft. Typical unit maintenance operations include removing and replacing
components within the hangar and transporting components to the centralized service
location for repair.
The US Air Force has the largest variety of aircraft of the three branches of the US
armed Services. Due to the variability of both type and size of the aircraft within the Air
Force, aircraft maintenance facilities are built specifically for each aircraft or similar type
of aircraft.
Refer to the US Air Force Dynamic Prototypes for Aircraft Maintenance Hangars for
functional program areas requirements and descriptions.
CIVIL
Design and layout all Airfield pavement markings for Air Force in accordance with ETL
04-2, AF1 32-1042 and UFC 3-260-04 (Draft) Standard Airfield Pavement Marking
Schemes.
Where a fuel spill capture trench drain is provided in the hangar bay, route the captured
fuel to an underground containment tank unless required otherwise by local
environmental regulations.
113
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-2.2.2 Capacity
Provide capacity to contain the maximum fuel spilled from the failure of a single fuel
tank/bladder on the anticipated aircraft(s) in the hangar bay. Do not provide less than
5,000 gallons of containment. Do not include any anticipated fire suppression discharge
in this containment volume. Design the containment system to accommodate the
anticipated fuel spill. Do not use the trenches or piping of the containment system to
contain any of the required volume.
Rate any devices, conduits, or electrical enclosures installed below grade for prolonged
submersion, minimum NEMA 250 Type 6P. Provide any devices, conduits, or electrical
enclosures within the tank for an electrical (hazard) classification of Class I Division 1.
ARCHITECTURAL
At a minimum, provide a 2-hour fire barrier between dissimilar hangar bay operations
including:
114
UFC 4-211-01
13 April 2017
Change 1, November 2017
Aircraft Maintenance Bay Striping Requirements
Provide striping in the aircraft maintenance bay per paragraph 3-3.4.3: Protective
Coatings and Figure 5-1: Aircraft Maintenance Bay Striping Requirements.
Striping Notes:
2. Aircraft position centerline & nose gear stop; 6 in (152 mm) wide stripe; color -
yellow.
115
UFC 4-211-01
13 April 2017
Change 1, November 2017
3. Aircraft clearance boundary line; 6 in (152 mm) wide stripe; color - yellow.
4. Safety eyewash/shower; color - green; provide 2 ft. (610 mm) clearance from safety
equipment.
5. Fire Extinguishers; color - red. Provide 2 ft. (610 mm) clearance from extinguishers.
STRUCTURAL
Air Force traffic loadings are designated in Table 3-1 of UFC 3-260-02 Pavement
Design for Airfields. Air Force hangar pavement thickness will be designed in
accordance with UFC 3-260-02, Chapter 3, paragraph 2c, titled Type C Traffic Areas.
Obtain approval for deviations of aircraft traffic mixes or deviation of airfield design type
(heavy, modified-heavy, medium, light) from the AFCEC pavements engineer.
MECHANICAL
Plumbing
Refer to 5-11: Floors and Trench Drains for trench drain criteria.
General
Classify all hangars as Group I in accordance with NFPA 409, unless specifically
permitted otherwise.
Where Group III hangars are provided, hydraulically design an overhead fire
suppression system to provide 0.3 gpm/sq. ft. (12.0 L/min/sq. m) over the hydraulically
most demanding 3,000 sq. ft. (278.7 sq. m). A Hi-Ex foam system is not required in the
hangar bay.
116
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-6.1.2 Group IV Hangars
Group IV hangars as defined by NFPA 409 (tension fabric structures on metal structural
frames) are permitted when sited and constructed in accordance with this UFC specific
to Group IV hangars.
Where Group IV hangars are provided, protect them in accordance with the
requirements of this UFC, including overhead sprinkler protection, Hi-Ex foam, fire
alarm and mass notification, and hangar bay egress.
Where Air Force Hangars are housing Navy/Marine Assets, provide fire suppression
and fire alarms in accordance with the Navy design standards in this UFC.
Only release the Hi-Ex foam system from a manual foam releasing station, or two
simultaneous votes from non-latching optical flame detectors in the releasing zone.
Refer to Table 5-1: Air Force RSFACU Functional Matrix for additional functional
requirements.
Where aircraft may taxi in and out of a hangar bay under their own power, such as an
alert shelter or drive through hangar, the Det-Tronics X3301 Multispectrum IR Flame
Detector is only permitted to use a low or medium setting.
117
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 5-1: Air Force RSFACU Functional Matrix
Notification Devices
Provide blue rotating beacons not less than 400 cd (208/120VAC) powered from a
dedicated emergency panel provided in accordance with UFC 3-520-01. Control the
beacon initiation through the RSFACU. A backup power supply or supervision of the
power supply supplying the beacons is not required when supplied from the dedicated
emergency panel. Mount beacons 20 - 30 ft. (6.1 - 9.1 m) above the floor of the hangar
bay. Provide a sign next to each blue beacon with a yellow or lime-yellow background
matching the manual foam releasing station signage, with "FOAM RELEASE WHEN
ILLUMINATED" in red lettering not less than 3 inches (76 millimeters) high. Blue
beacons are in addition to any general fire alarm notification such as the general fire
alarm strobes.
118
UFC 4-211-01
13 April 2017
Change 1, November 2017
Protective and Hardened/Semi-Hardened Aircraft Shelters (PAS and
HAS)
5-6.6.3 Siting/Separation
For PAS and HAS, increase the distance from other structures as required to comply
with the citing and separation requirements for munitions safety quantity/distance
criteria in the Air Force Manual (AFM) 91-201, Explosive Safety Standards. No
minimum fire separation distance is required between any combination of PAS/HAS
buildings where constructed in accordance with this UFC.
Do not provide a hangar bay overhead sprinkler system, Hi-Ex foam generators, interior
or exterior hose stations, or a fire department connection as required by this UFC.
Where personnel shelters, offices, or other similar structures are located within the
hangar bay they shall be protected in accordance with this UFC and UFC 3-600-01
including sprinklers and fire alarm systems.
119
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-6.6.6.1 Foam/Water Supply Systems
Provide either a pre-mixed or post-mixed system per this section. For a pre-mixed
system, provide a pressure tank filled with pre-mixed 3% AFFF foam/water solution
sufficient to maintain the application rate for at least 4 minutes. 4 minute duration is
based on actual system flow. Use nitrogen (or other stored gas) capable of discharging
the entire AFFF/water solution in the pressure tank. Provide secondary containment for
the foam/water storage tanks capable of capturing the entire volume from the largest
foam/water storage tank.
For a post-mixed system, provide a pressure tank filled with enough water to maintain
the application rate for at least 4 minutes. 4 minute duration is based on actual system
flow. Use nitrogen (or other stored gas) capable of discharging the entire water supply
in the pressure tank. Store 3% AFFF concentrate in an atmospheric tank, and use a
self-inducting inline proportioner to induct the concentrate into the water stream
discharged from the pressure tank. Provide a quantity of concentrate to support the
complete discharge of water from the pressure tank.
It is not necessary for the foam/water nozzle discharge pattern (throw) to cover the
entire aircraft servicing area, however it is required to cover the area under the aircraft
silhouette within one minute and the entire aircraft servicing area within 4 minutes.
Locate the foam/water nozzles to push the foam across the floor with minimal agitation.
Do not align nozzles to discharge foam/water solution either directly or indirectly onto
aircraft surfaces. Provide nozzles in locations to avoid anticipated obstructions to the
discharge pattern.
120
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-6.6.6.6 Foam System Location
Locate the foam system outside and adjacent to the building. Mount the supply on a
concrete surface and provide small arms ballistic and splinter protection. For third
generation and similarly sized PAS and HAS, it is permitted to locate the foam system
inside the building. Locate inside systems to minimize the impact to operational space.
Mount inside systems on the floor, mounting to the roof or wall is not permitted.
121
UFC 4-211-01
13 April 2017
Change 1, November 2017
Assessment of Existing Fire Protection Systems
This section provides criteria for assessing the improvement requirements of existing
fire protection systems in accordance with Section 1-2.2 Planning Personnel. Apply this
section to existing hangar bay fire protection systems that are wholly or partially
designed to criteria other than contained in this UFC.
122
UFC 4-211-01
13 April 2017
Change 1, November 2017
bladder system is used, replace the bladder in the existing storage tank. Where an
atmospheric storage tank is used, replace the storage tank with an atmospheric storage
tank in accordance with this UFC.
With water only, flush and drain the concentrate line from the storage tank to the
proportioner a minimum of three times. Collect and dispose of AFFF concentrate and
effluent using a high temperature incinerator. After refilling the concentrate storage tank
with C6 AFFF, permanently label and date the storage tank.
Where upgrades are made to the fire water supply per this section such as adding a fire
water booster pump, provide a foam/water flow control valve and manual foam stop
stations in accordance with this UFC. Where manual foam water stop stations are
provided, surge arrestors are required accordance with this UFC. Reconfigure the
bladder pressurization piping so the bladder is not under constant pressure, which may
include relocating the pressurization piping downstream of the deluge or flow control
valve.
ELECTRICAL
123
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-7.1.1 Aircraft Power Distribution Service Points
Distribute aircraft power from government furnished SE carts. Government-furnished SE
equipment is mobile and provides a flexible solution. The aircraft cables are typically
connected to the SE cart. The equipment is owned and maintained by the maintenance
mission and typically the equipment will be shared for hangar and on-ramp
maintenance. A storage area may also be required for the equipment.
The cables connecting to the aircraft power distribution service point may or may not be
provided as part of the service. Coordinate the provision of the cables with the mission
owner.
Provide ordnance grounding in accordance with Air Force Manual (AFMAN) 91-201.
Provide the design in accordance with specific details from NAVSEA OP-5.
The Air Force prohibits the use of Light Emitting Diode (LED) Obstruction Lighting.
COMMUNICATIONS
CATV Systems
Refer to the Air Force dynamic prototypes for required CATV locations.
124
UFC 4-211-01
13 April 2017
Change 1, November 2017
Audible Warning System
Where required and authorized, provide an audible warning horn and warning lights for
aircraft maintenance safety. Provide an audible warning system capable of being heard
or seen at any location in the hangar bay. Provide unique color warning lights and horn
tones to differentiate the system from other warning systems in the hangar bay.
Refer to Air Force dynamic prototypes for required overhead bridge cranes.
HANGAR DOORS
Trench Drains
Provide a fuel spill capture trench drain in the hangar bay to remove an inadvertent fuel
spill from a ruptured aircraft fuel tank/bladder. Exception: A fuel spill capture trench
drain is not required in a wash bay provided in accordance with this UFC.
125
UFC 4-211-01
13 April 2017
Change 1, November 2017
FUEL CELL MAINTENANCE HANGARS
General
The use of segregated repair facilities/areas for fuel systems repair is essential for safe
and efficient operations and is primarily an Air Force Hangar operation. The repair
facilities/areas described in this paragraph provide necessary protection for both the
aircraft and personnel from a variety of hazards. This paragraph is based on Chapter 3
of Technical Manual TO 1-1-3 Inspection and Repair of Aircraft Integral Tanks and Fuel
Cells
Facilities meeting the previous fire and safety requirements for fuel systems repair
facilities in accordance with Air Force guidelines are compliant if they meet the
requirements of ETL 98-8, Existing Aircraft Hangars.
Permitted Operations
Fuel systems repair facilities are intended to support the complete range of operations
normally restricted from being conducted inside other hangars and structures. Normally
restricted operations permitted in fuel systems repair facilities include, but are not
limited to: fuel cell repair, partial/complete defuel/refuel, fuel transfer, de-
puddling/purging of fuel tanks/cells and fuel systems components and fuel tank/cell
pressurization testing.
Definitions
Conduct open fuel tank/cell repair only in predesignated repair facilities/areas approved
by the appropriate using organization. The facilities and areas are defined as follows:
126
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-12.3.4 Fuel Foam/Cell Repair Room
A room separate from on-airframe maintenance activity areas (e.g., shelter, hangar),
when a fuel bladder/foam is removed from the aircraft, and where repair, maintenance,
and testing is expected to be performed on the removed item. When an alternate tank
repair "area" is required, provide the space with the same requirements as the primary
repair area.
127
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-12.4.3 Facility Design and Construction Standards
Fuel systems repair facilities are to be designed and constructed in accordance with this
UFC. Address facility design and construction standards or other technical support
questions to the AFCEC Reach Back Center at AFCEC.RBC@us.af.mil
NOTE: Due to changes in fuel cell maintenance hangar requirements, some related
references may be inaccurate/inadequate in mandating additional fume and sensing
alarms, and wash down drainage trenches. Fume Sensing and Alarm systems are not
installed as part of the facility project but are to be provided as equipment. Wash-down
drainage trenches are not to be provided in United States Air Force (USAF) fuel system
repair facilities.
Architectural
128
UFC 4-211-01
13 April 2017
Change 1, November 2017
5-12.5.6 Support Spaces
Provide office space, break room, support equipment/tool room, restrooms, and locker
rooms as required.
Mechanical
Heating, Ventilation and Air Conditioning (HVAC) Systems. Draw return air from the
aircraft servicing area above 10 ft. (3.0 m). Refer to UFC 3-410-01 for direction
regarding heating/cooling the hangar. In general, heating is required, and cooling is not
allowed unless required for the task.
5-12.6.1 Ventilation
Provide ventilation in accordance with this UFC, UFC 3-410-01, and UFC 3-410-04N.
The ability to vary the amount of outside air needs to be in the design. Locate outside
air intakes in areas free from contamination.
129
UFC 4-211-01
13 April 2017
Change 1, November 2017
Maintenance Hangar Bay Vapor exhaust requirements as outlined in
previous paragraph.
• Positive Pressure Ventilation. Provide office space, break room, and
support equipment/tool room with positive pressure ventilation to prevent
vapors and gases from migrating from the aircraft repair area.
• Negative/Neutral Pressure Ventilation. When appropriate, provide
negative pressure ventilation in restrooms and locker rooms. When these
spaces are located next to, and thus will pull air from, areas with fuel/toxic
vapors, provide sufficient supply air to allow this space to be at a neutral
pressure (to prevent fuel/toxic vapor infiltration.)
• Purge Ventilation System. Provide a system for purging the fuel line and
the tanks to fuel systems maintenance/repair facilities. Provide a system
to ventilate the aircraft fuel tank using filtered outside air. Exhaust air from
the fuel tank directly to the outdoors. Monitor the inside of the tanks being
worked on and maintain purge system exhaust below 600 ppm or 10% of
the Lower Explosive Limit (LEL) for JP-8 to ensure the space is
adequately ventilated prior to and during maintenance. The use of a
supply and exhaust fan is the preferred method, followed by exhaust only,
supply only and finally no ventilation if the vapors in the tank are shown to
remain within the limits above. Locate outside-air intakes at locations free
from contamination by the exhaust of other ventilation systems.
• Emergency Ventilation System. A separate emergency ventilation system
will be used to ventilate the hangar bay in the event of high fuel vapor
concentrations in the hangar. The emergency ventilation system will
energize to maintain the space at or below 14.4 ppm. The ventilation rate
should be based on providing a minimum of 20 air changes per hour
(ACH) at up to 2 ft. (610 mm) above the finished floor. In hangar bays with
lifts, landing gear pits and recessed inspection areas, locate an additional
detector in each below-floor area, and increase the emergency ventilation
rate to 30 ACH to ensure proper ventilation and removal of the vapors.
5-12.6.1.1 Exhaust Systems
Exhaust systems discharging to the exterior of the facility may draw air at any level
above the floor, but exhaust location should be selected to best remove fuel/toxic
vapors.
130
UFC 4-211-01
13 April 2017
Change 1, November 2017
air purifying system is not available, make provisions for fresh air inlet hoses to be
routed outside of the facility.
5-12.6.2 Plumbing
Emergency Eyewash/Shower. Provide privacy enclosures at emergency
eyewash/shower combinations to permit complete disrobing in the aircraft servicing
area. Provide water to emergency eyewash/showers through a thermostatic mixing
valve.
Scrub Sink and Showers. Provide hands-free type scrub sinks to permit the washing of
hands and arms to the shoulder. Provide water to scrub sinks and showers through a
thermostatic mixing valve.
5-12.6.2.1 Drainage
Wash-down drains and drainage trenches are not required in new USAF fuel system
repair facilities except where specifically noted in Chapter 5: Air Force Specific Criteria.
If existing drainage is provided, drainage trench ventilation is not required.
Electrical
Design the fuel bladder/cell repair room as a Class I Division 2 hazardous (classified)
location to the ceiling/deck in accordance with NFPA 70. At a minimum, classify
adjacent spaces that are not suitability cutoff as defined in 3-7.1: Hazardous
(Classified) Locations as Class I Division 2 up to 18 inches (460 mm) above the floor of
the fuel bladder/cell repair room. In the hangar bay, provide wall mounted outlets
designed for Class I Division 1 or 2 hazardous (classified) locations even though they
131
UFC 4-211-01
13 April 2017
Change 1, November 2017
may be outside the classified area. This is an aircraft maintenance (user) safety
requirement, and is intended to prohibit the use of unclassified tools or equipment in the
classified area around the aircraft.
WASH BAY
132
UFC 4-211-01
13 April 2017
Change 1, November 2017
ARMY SPECIFIC CRITERIA
INTRODUCTION
The Army Standard for the Aircraft Maintenance Hangar (HGR) Complex applies to the
planning, design, and construction of all active Army Tables of Organization and
Equipment (TOE) aircraft maintenance and repair requirements worldwide. The Army
Standard applies equally to Tables of Distribution and Allowance (TDA) hangars. While
the Army Standard is based on the Combat Aviation Brigade (CAB), the criteria are
applicable to all aircraft maintenance and repair facilities. The current version of the
Army Standard is maintained on the MILCON Requirements and Standardization
Integration (MRSI) website https://mrsi.erdc.dren.mil.
CIVIL
Design and layout Airfield Pavement Markings for Army Hangars in accordance with
ETL 1110-3-512.
133
UFC 4-211-01
13 April 2017
Change 1, November 2017
Containment of Fire Suppression Effluent
Route the wet pipe, dry pipe, preaction or foam/water system runoff from the hangar
bay to automatically discharge to an underground containment tank, unless required
otherwise by the local environmental regulations.
6-2.2.2 Capacity
Provide capacity to contain 15 minutes of the hydraulically calculated demand from the
overhead sprinkler system in the hangar bay, plus the hose stream demand. Do not
include the Hi-Ex foam system fire flow in the containment capacity. Design the
containment system to accommodate the entire calculated fire suppression effluent
discharge volume for the duration noted. Do not use the trenches or piping of the
containment system to contain any of the required volume.
Rate any devices, conduits, or electrical enclosures installed below grade or within the
containment tank for prolonged submersion, minimum NEMA 250 Type 6P.
ARCHITECTURAL
The Army Standard has established standard aircraft maintenance module sizes for
rotary wing aircraft and UAS aircraft. Refer to the USACE Centers of Standardization
website (https://mrsi.erdc.dren.mil/cos/ ) or via links on the National Institute of Building
Sciences (NIBS) Whole Building Design Guide (WBDG) site
(http://www.wbdg.org/references/pa_dod.php).
135
UFC 4-211-01
13 April 2017
Change 1, November 2017
Coordinate Interior Systems
Coordinate Interior Systems with the APPROVED Army Standard Design for Aircraft
Maintenance Hangar Complexes.
Provide one of the following floor finishes for the Aircraft Maintenance Bay and Heavy
Maintenance Shops consistent with the user requirements, facility purpose, and the
intended design life cycle of the facility:
Design and layout all Aircraft Maintenance Bay pavement markings in accordance with
ETL 1110-3-512 and Figure 6-2: Maintenance Bay Pavement Markings. All paint for
pavement markings to be in compliance with FS TT-P-1952, Paint, Traffic and Airfield
Marking, Waterborne.
136
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 6-1: Typical Maintenance Bay Configuration
137
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 6-2: Maintenance Bay Pavement Markings
1. Maintenance module boundary; 6 in. (152 mm) wide stripe; color - dark grey.
2. Maintenance module centerline & nose gear stop; 6 in. (152 mm) wide stripe;
color - dark grey.
3. Safety corridor; 5 ft. (1.5 m) wide; color - yellow.
4. Grounding receptacle; paint per UFC 3-575-01, figure 2-3.
5. Utility stand; 6 in. (152 mm) wide stripe; color - orange. Provide 2'-0" clearance
from utility stand equipment.
6. Safety eyewash/shower; color - green; provide 2 ft. (610 mm) clearance from
safety equipment.
7. Provide markings for required clear area on floor around electrical and life safety
features.
138
UFC 4-211-01
13 April 2017
Change 1, November 2017
STRUCTURAL
Design Army Aircraft Maintenance Bay slabs on ground in accordance with the
minimum following traffic requirements. Add project specific additional vehicles to the
mix as required. Make no reductions to these traffic mixes without the approval of the
USACE Transportation Systems Center (TSC).
MECHANICAL
Heating
139
UFC 4-211-01
13 April 2017
Change 1, November 2017
infrared radiant heat is not effective due to the mounting height required or where the
path of the radiation is obstructed, evaluate radiant floor heat in the life-cycle cost
analysis.
Ventilation may be used in economizer cycles for increased thermal comfort where
climatic conditions are appropriate. One example would be where diurnal temperature
variation allows night time cooling. Natural air movement through locating louvers and
dampers near the ceiling and floor should be evaluated for life cycle cost effectiveness
versus a fan powered economizer cycle. Evaporative cooling is not allowed in Army
hangar maintenance bays.
Plumbing
Mount hose bibbs and compressed air connections on at least one utility pedestal
located inside the perimeter access aisle.
General
Fire Pumps
Where fire pumps supply a single hangar, a redundant pump meeting the size of the
largest pump is required. Size all fire pumps with the same nominal pressure and flow.
In addition to pressure drop, start fire pumps automatically upon receiving a fire pump
start signal from the FACU.
Proportioning foam concentrate through the use of a ratio flow controller and bladder
tank, or a foam inductor is not permitted. Provide a foam concentrate pumping system,
with an atmospheric foam concentrate storage tank. Provide a foam concentrate
pumping system in compliance with NFPA 11, NFPA 20, and NFPA 409, except as
modified by UFC 3-600-01 and this UFC. Refer to Figure 6-3: Army Foam Pump Detail.
140
UFC 4-211-01
13 April 2017
Change 1, November 2017
6-6.3.1 Foam Concentrate Pumps
Provide positive displacement concentrate pumps with electric motor drivers, supplied
by a reliable power source. Use UFC 3-600-01 for reliable power requirements. Where
reliable power is not available, provide diesel driven concentrate pumps.
Provide a reserve foam concentrate pump of equal capacity. Automatically operate the
reserve pump upon failure of the primary pump. Arrange concentrate supply piping to
meet the foam concentrate demand from either the primary or reserve foam pump.
141
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 6-3: Army Foam Pump Detail
142
UFC 4-211-01
13 April 2017
Change 1, November 2017
6-6.3.6 Foam/Water Concentrate Proportioning Performance
Increase the capacity of the foam concentrate tanks and pumps, to compensate for
proportioner tolerance and the maximum anticipated fire water pressure. Calculate this
increase to enable the foam concentrate system to deliver foam for the required
discharge duration.
Provide waterflow detection devices to monitor the overhead wet pipe, dry pipe, or
preaction sprinkler systems in the hangar bay.
Only release the Hi-Ex foam system from a manual foam releasing station, or two
simultaneous votes from non-latching initiating devices in the releasing zone. These
initiating devices are required to be an optical flame detector in simultaneous operation
with either another optical flame detector or waterflow detection device within the same
releasing zone. Refer to Table 6-1: Army RSFACU Functional Matrix for additional
functional requirements.
Provide a key operated supervised disconnect switch to disable all optical flame
detectors in the hangar bay through programming at the RSFACU. Provide a switch that
disables the releasing and notification functions of the optical flame detectors, while
leaving all other functions of the RSFACU operational. Operation of the switch will not
create a trouble signal. Monitor the disconnect at the RSFACU. Provide a supervisory
signal to the receiving station upon operation of the disconnect. While the switch is in
the disable mode, the optical flame detectors will not retain any history of alarm
conditions such that when the switch is placed in the enable mode the RSFACU will not
immediately go into alarm.
Locate the disconnect switch in the hangar bay, in a readily accessible location near a
manual foam stop station. Provide a NEMA 250 Type 4 switch and backbox or house
the components in a NEMA 250 Type 4 enclosure. Provide a non-flashing or rotating
red indicating light not less than 400 cd (208/120VAC) powered from a dedicated
emergency panel provided in accordance with UFC 3-520-01. Control light initiation
through the RSFACU. A backup power supply or supervision of the power supply to the
light is not required when supplied from the dedicated emergency panel. Mount the light
above the disconnect switch. Provide a sign with a white background and a minimum
1/2 inch wide blue border, with "OPTICAL FLAME DETECTION DISABLED WHEN
143
UFC 4-211-01
13 April 2017
Change 1, November 2017
ILLUMINATED" in red lettering not less than 1 inch (25.4 mm) high. Provide engraved
labels on the disconnect switch indicating when the optical flame detectors are
"ENABLED" or "DISABLED". Do not install backboxes or route conduit in front of sign in
a manner that obstructs any lettering.
Notification Devices
Provide blue rotating beacons not less than 400 cd (208/120VAC) powered from a
dedicated emergency panel provided in accordance with UFC 3-520-01. Control beacon
initiation through the RSFACU. A backup power supply or supervision of the power
supply supplying the beacons is not required when supplied from the dedicated
emergency panel. Mount beacons 20 - 30 ft. (6.1 - 9.1 m) above the floor of the hangar
bay. Provide a sign next to each blue beacon with a yellow or lime-yellow background
matching the manual foam releasing station signage, with "FOAM RELEASE WHEN
ILLUMINATED" in red lettering not less than 3 inches (76 millimeters) high. Blue
beacons are in addition to any general fire alarm notification such as the fire alarm
strobes.
Supervision Devices
Provide a supervisory level alarm monitoring for foam concentrate. Indicate when the
foam concentrate in the storage tank is below the amount required to meet the
performance criteria.
144
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 6-1: Army RSFACU Functional Matrix
145
UFC 4-211-01
13 April 2017
Change 1, November 2017
ELECTRICAL
Special Power
Use Table 6-2: Aviation Platform Ground Service Baseline Requirements for Service
Baseline Requirements.
GROUND
SERVICE AHH- UH- UH/MH
AH-64D CH-47D DH/MH-47E, F, G OH-58D ARH
64A 60A/L -60M, X
34.4kV
A
28kW
400 Hz 93kVA 45KV
(35kV 45kVA 20kVA 40kVA 10kVA ?
200/115V (270A) A
A)
FOR
0.0
28VDC
NONE NONE NONE NONE NONE NONE 500-750A START 500-800A START
START
Integrate the system with the building power system and complete with all cables and
connectors required to interface with the aircraft. No ground power units (carts) are
allowed. Design system to provide access to each aircraft parking space without any
cables or equipment passing thru the five foot clear zone around the hangar bay floor.
146
UFC 4-211-01
13 April 2017
Change 1, November 2017
Grounding and Bonding
Provide ordnance grounding in accordance with Department of the Army Pamphlet (DA
PAM) 385-64.
Electrical Equipment
All electrical equipment in the hangar bay is required to be in a NEMA 250 Type 3R or
weather proof enclosure.
COMMUNICATIONS
CATV Systems
Refer to the Army Hangar Center of Standardization for required CATV locations.
Provide in accordance with 3-9: Overhead Bridge Cranes and the Army Standard for
Aircraft Maintenance Hangar Complex.
HANGAR DOORS
Trench Drains
Provide trench drains in the hangar bay to comply with NFPA 409 Floor Drainage
Requirements for the removal of hazardous fuels and fire suppression system
discharges.
Trench Covers
147
UFC 4-211-01
13 April 2017
Change 1, November 2017
FUEL CELL MAINTENANCE
WASH BAY
148
UFC 4-211-01
13 April 2017
Change 1, November 2017
NAVY SPECIFIC CRITERIA
INTRODUCTION
7-1.1.1 Applicability
Refer to 1-4: Scope of Facility. Additionally, this UFC applies to all new Navy or USMC
hangars including the defined Navy standard hangar Types I, II, III, and IV, variations of
the hangar Types, as well as any non-standard hangars. All new Navy and USMC
standard hangars must meet all hangar Type I-IV requirements for the respective
standard. In any case, design all hangars to accommodate the minimum safety
clearances shown in Table 2-1: Minimum Aircraft Maintenance Bay Clearances for the
design airframe(s). Clearances for non-standard hangars should be conservatively
selected by comparing the design airframe size to those found in the various standard
hangar Types.
Selective portions of this UFC apply only when renovating or re-purposing an existing
hangar. As a minimum, renovation projects must comply with all safety and life-safety
related criteria. This includes, but is not limited to, fire protection, egress, and aircraft
minimum clearances. Follow all other criteria of this UFC, including all standard hangar
Type requirements (Table 7-1: Standard Hangar Bay Module Dimensions and Crane
Capacities*), to the maximum extent practical for the renovation. The intent of meeting
all criteria in this UFC is to provide for future hangar flexibility to maintain alternate
aviation platforms. If meeting those additional standard hangar Type requirements is not
feasible or possible for a renovation project addressing a specific aircraft platform, then
it is only necessary to meet the mission requirements for that specific platform and all
safety and life-safety criteria as stated above. This is not an option for new hangars
which must meet this entire UFC including Table 7-1. It is important for the planner to
clarify the intent of the renovation scope on the 1391 planning document.
With these concepts in mind, flexibility of the hangar bay is critical and has been
incorporated into these criteria where reasonable. Specific areas of consideration
include hangar bay sizes, minimum slab design loading, maximization of door sizes,
bridge crane capacities, and elimination of fixed obstructions or other features on the
hangar bay floor that would impact revised aircraft layouts. The theory is that although
hangars are being designed and optimized for an initial airframe and layout, the Navy
and USMC are building multi-purpose hangars with reasonable flexibility that can be
utilized through their lifespan. Custom, non-standard, single purpose hangars should be
avoided when possible and special caution should be given where frequent airframe
changes are expected.
CIVIL
Orient hangar such that it is in compliance with all runway safety zones and imaginary
surface criteria of UFC 2-000-05N, UFC 3-260-01, and 3-2.1.2: Airfield Clearance
Criteria.
Airfield Pavements
Design and Layout all airfield pavements, including hangar access aprons, in
accordance UFC 2-000-05N, UFC 3-260-01, and 3-2.3: Airfield Pavements.
150
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airfield Pavement Markings
Design airfield pavement markings for Navy and Marine Corps facilities in accordance
with Naval Air Systems Command (NAVAIR) 51-50AAA-2.
AFFF Containment
Route the AFFF system runoff from the hangar bay to automatically discharge to an
underground containment system, unless required otherwise by local environmental
regulations.
7-2.4.2 Capacity
Provide capacity to contain 15 minutes of the hydraulically calculated demand from the
AFFF system. Design the containment system to accommodate the entire calculated
AFFF system effluent discharge volume for the duration noted. Do not use the trenches
or piping of the containment system to contain any of the required volume. No
allowance is required for the water only sprinkler systems or hose streams.
151
UFC 4-211-01
13 April 2017
Change 1, November 2017
beacon) that automatically illuminates when the valve position is "off normal" or
"closed", and remains illuminated until valve is restored to full the normal "open"
position. Locate diverter valve panel in the hangar bay adjacent to the containment
system monitoring panel. Provide an alarm to the FACU and Energy Management
Control System when the diverter valve is in the off normal position. Install the diverter
valve motorized operator above grade or list it for a submersible environment.
Rate any devices, conduits, or electrical enclosures installed below grade or within the
containment tank for prolonged submersion, minimum NEMA 250 Type 6P.
ARCHITECTURAL
Types of Hangars
7-3.1.1 General
Refer to 7-1.1.2: Hangar Design Philosophy for additional discussion on the Navy
Hangar Type concept. The Navy has established four (4) standard maintenance hangar
bays including Type I, Type II, Type III and Type IV to efficiently meet the needs of its
current aircraft inventory. Each Type is designed to accommodate commonly grouped
aircraft which are categorized by size and function and are further defined in paragraphs
below and in Table 7-1: Standard Hangar Bay Module Dimensions and Crane
Capacities*. These hangar Types are based on the controlling aircraft size, controlling
aircraft layout, additional maintenance clearance required (if any), and minimum
required aircraft clearances shown in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances. Do not reduce the minimum clearances for standard hangar Types below
the thresholds indicated. If necessary, increase the selected standard Hangar Type
dimensions to accommodate the specific design airframe(s) layout with adequate
clearances (Table 2-1: Minimum Aircraft Maintenance Bay Clearances) and any
additional maintenance clearance per the manufacturer's Facilities Requirements
Document (FRD). The intent is to prevent a situation where a new airframe or larger
variant is introduced prior to an update of Hangar Type standard definitions. Refer to
UFC 2-000-05N for hangar planning requirements, modular sizing, and square footage
guidance.
7-3.1.1.1 Organization
Navy aircraft hangars are comprised of three distinct areas; the hangar bay
Organizational Hangar (OH) space, the Shop and Maintenance Administration (O1
level); and the Operations, Training and Administration (O2 level). The levels are
designations from shipboard levels and are not specific to the hangar design. The
hangar bay provides sheltered space to primarily perform Organizational "O" level
maintenance to aircraft and limited additional levels as previously discussed in
152
UFC 4-211-01
13 April 2017
Change 1, November 2017
7-1.1.3: US Navy Aircraft Maintenance Strategy. Layout of this space is determined by
the planning documents for the module configuration identified. The net area of the
hangar bay is defined in the module layout and is considered a fixed area.
Provide one bridge crane per modules for all Type I hangars. When a single large
hangar includes more than one module, additional cranes are required.
153
UFC 4-211-01
13 April 2017
Change 1, November 2017
they be acquired by the Navy. For UAS other than Triton, planners may consider non-
standard hangars or other facility types as appropriate to meet the mission.
Table 7-1: Standard Hangar Bay Module Dimensions and Crane Capacities*
154
UFC 4-211-01
13 April 2017
Change 1, November 2017
Notes:
1. The Width and Depth of the hangar are defined as the respective net clear horizontal
dimension between the nearest fixed obstructions. Horizontal fixed obstructions
along back walls and side walls include, but are not limited to the inside face of the
wall, a structural column or bracing, bollard, liner panel, an open door extending into
the Aircraft Maintenance Bay, mechanical equipment or ductwork, plumbing
equipment, valves and pipes, electrical equipment (such as power transformers), or
other fixed items. Fixed obstructions do not include furniture, tables, desks, benches,
cabinets, tools, parts, carts or other movable objects. The depth at the hangar door
is to the interior face of the innermost panel of a rolling steel door, or to the interior
face of a vertical lift fabric door.
2. Dimensions for width, depth, and height are considered to be "standard." Variations
in hangar bay sizes are not permitted without authorization of the NAVFAC HQ Chief
Engineer. Additionally, Marine Corps hangar bay configurations may be modified by
Headquarters, USMC (LF).
3. Table includes required NET clear hangar dimensions that are also to be used for
square foot planning calculations. See UFC 2-000-05N for guidance and
requirements on Net to Gross planning calculations. See also paragraph 2-4: Net to
Gross Area in Aircraft Maintenance Hangars.
4. The clear height is the lowest obstruction including but not limited to, an overhead
structure, and MEP equipment such as lighting, fans, heaters, ductwork, and
sprinklers.
5. Hook height is to the saddle of the hook. Hook heights are minimum requirements.
Increase height where possible to maximize for available structure height. Refer to
crane requirements in Chapter 3: General Hangar Requirements and 7-9:
Overhead Bridge Cranes.
6. Refer to Figure 7-11: Section through Type II Hangar Crane Configuration and
Vertical Clearances to clarify minimum hangar crane coverage area for Type II
hangars. The bridge crane coverage must be designed to account for the possibility
of servicing a C-130 aircraft. Coordinate crane coverage with the user.
7. The elements at the edge of the hangar door opening determine the width of the
opening. Provide an opening not less than 3 ft. (1 m) less than the width of the
aircraft maintenance bay.
Provide striping in the aircraft maintenance bay per paragraph 3-3.4.3: Protective
Coatings and Figure 7-1: Aircraft Maintenance Bay Striping Requirements.
155
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-1: Aircraft Maintenance Bay Striping Requirements
Striping Notes:
Design Navy/USMC Aircraft Maintenance Bay slabs on ground in accordance with the
minimum following traffic requirements. Add project specific additional vehicles to the
mix as required. The mixes represent a 50-year traffic loading. These slab loadings
have been developed to maximize Aircraft Maintenance Bay use and flexibility. Make no
reductions to these traffic mixes or loadings without the approval of NAVFAC HQ Chief
Engineer.
\1\ For Navy and USMC standard hangar Types I, II, III, and IV or similar variations,
provide a slab on ground of uniform design and thickness throughout the hangar bay.
Do not reduce the slab thickness in areas not subject to the design aircraft loads. For
single aircraft non-standard hangar types, slab optimization is permitted by section 3-
4.2.3.1 Aircraft Maintenance Bay - Slab on Ground Design where applicable. /1/
7-4.1.2 Type II Hangar- Type B traffic area with the following minimum
traffic mix:
Use Type B traffic area with the following minimum traffic mix:
157
UFC 4-211-01
13 April 2017
Change 1, November 2017
7-4.1.4 Type IV Hangar
Use Type B traffic area with the following minimum traffic mix:
MECHANICAL
Plumbing
HVAC
Provide dedicated units for the Communications Room and Secure Office. Provide
heating only with a unit heater for the stairs when the climate makes it necessary.
General
158
UFC 4-211-01
13 April 2017
Change 1, November 2017
7-6.2.2.2 O1/O2 Levels within the Tension Fabric Structural Frame
Provide a minimum 1-hour fire barrier between the O1/O2 levels and the OH space,
inclusive of all sides exposed to the OH space such as side, top, and bottom.
Concentrate Piping
The use of brass piping with brazed or flanged joints is permitted. Provide flanges in the
brass piping for equipment and valve removal. The use of threaded connections is not
permitted, except at the connection to the inductor or concentrate storage tank.
Only release the AFFF trench nozzle system from a manual foam releasing station, or
two simultaneous votes from non-latching optical flame detectors in the releasing zone.
Refer to Table 7-2: Navy RSFACU Functional Matrix for additional functional
requirements.
159
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-2: Navy RSFACU Functional Matrix
ELECTRICAL
Coordinate all requirements with users and aircraft manufacturer and dedicate adequate
wall space for all equipment. The power service points may include:
160
UFC 4-211-01
13 April 2017
Change 1, November 2017
O1/O2 Level Spaces
Serve shop spaces by distinct panels dedicated to shop and equipment loads only. Do
not supply office spaces from shop circuits or panels. Supply loads located in the O1
space from panel boards located in the O1 space; supply loads located in the O2 space
from panel boards located in the O2 space.
Obstruction Lighting
COMMUNICATIONS
CATV Systems
Refer to the Navy functional data sheets for locations where CATV is required.
161
UFC 4-211-01
13 April 2017
Change 1, November 2017
Intercommunication System
• Rooms in the O1 and O2 level space, except corridors, locker and toilet
rooms, and storage rooms.
• Department heads and the Commanding Officer and Executive Officers of
the squadron.
• Officers' ready room and maintenance control.
• Administration office and maintenance administration.
The ALIS is required for all F-35 hangars. A SAPF area is required for the ALIS. Refer
to 2-2.3 - Secure Spaces for standards that apply to the construction of secure spaces.
Provide all cranes in accordance with Navy Crane Instruction 11450.2 Design of Navy
Shore Weight Handling Equipment. For bridge crane capacities and additional crane
requirements refer to Table 7-1: Standard Hangar Bay Module Dimensions and Crane
Capacities*.
All overhead bridge cranes to be under running girder electric cranes with under running
trolley hoist. Provide either single or double girder type, whichever minimizes the lowest
overall crane depth for the configuration. Support all bridge cranes from patented track
systems designed by the crane manufacturer.
Hook Height
The minimum hook clearance height, (measured from the finished floor elevation to the
saddle of the hook at full elevation) is as tabulated in Table 7-1: Standard Hangar Bay
Module Dimensions and Crane Capacities*. Increase crane hook height where possible
to take advantage of the available structure height.
Hook Coverage
Design bridge crane layout to provide loaded hook coverage to within 12 ft. (3.7 m) of
the inside face of all walls and to within 15 ft. (4.6 m) of the inside face of the hangar
doors, except for Type II hangars. Refer to Figure 7-11: Section through Type II Hangar
Crane Configuration and Vertical Clearances for Type II crane requirements. Where
multiple cranes are provided, fully loaded hooks must be capable of being located within
15 ft. (4.6 m) of each other.
162
UFC 4-211-01
13 April 2017
Change 1, November 2017
HANGAR DOORS
Hangar door widths to be determined by the elements at the edge of the door opening.
Design the width of the opening to be not be less than 3ft. less than the width of the
aircraft maintenance bay. Provide individually operated panels if the project includes
sliding steel hangar doors.
At a minimum, provide trenches and nozzles around the perimeter of the hangar bay to
enclose the aircraft silhouette and service area. For the purpose of the trench and
nozzle locations, the aircraft service area is defined by Table 2-1: Minimum Aircraft
Maintenance Bay Clearances. For example, in a Navy Type I Hangar, the aircraft
service area starts at 7'-6" from the inside face of the hangar bay door.
Trench Drains
Provide trench drains in the hangar bay to remove hazardous fuels, fire suppression
system discharge, and convey fire suppression system piping to the AFFF system
discharge devices. Trench drains may also be used to convey compressed air and
water service lines to support other operational functions of the maintenance hangar.
Provide nozzles that have been tested for obstruction to discharge such as aircraft tires,
55 gal. (208 L) barrels, 3/4 in. (19 mm) rubber hoses, construction materials, with little
effect on time of floor coverage. Design the system so the total nozzle obstructions do
not negatively impact the hydraulics of the distribution system or the foam induction
capabilities.
Install the low level AFFF trench nozzle system in a similar arrangement and with the
limitations indicated in Figure 7-2: Drive-Through Hangar and Figure 7-3: Pull-In
Hangar.
164
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-2: Drive-Through Hangar
1. Center to center nozzle spacing is approved for no less than 22.5 ft. (6.8 m.) and no
greater than 27.5 ft. (8.4 m.)
2. The maximum distance between the centerline of distribution trenches is 50 ft. (15.2
m).
3. Provide 180 degree nozzles around the perimeter of the aircraft servicing area.
5. Do not exceed a distance of 3 ft. (1 m) into the hangar bay from the face of the
hangar bay door jamb to the nearest parallel edge of the trench.
6. Do not exceed the tabular value in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances for the perpendicular distance from the centerline of the nozzles to the
inside face of the nearest hangar bay door.
165
UFC 4-211-01
13 April 2017
Change 1, November 2017
7. Do not exceed the tabular value in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances for the perpendicular distance from the centerline of the nozzles to the
nearest fixed obstruction along the side wall.
1. Center to center nozzle spacing is approved for no less than 22.5 ft. (6.8 m.) and no
greater than 27.5 ft. (8.4 m.)
2. The maximum distance between the centerline of distribution trenches is 50 ft. (15.2
m).
3. Provide 180 degree nozzles around the perimeter of the aircraft servicing area.
5. Do not exceed the tabular value in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances for the perpendicular distance from the centerline of the nozzles to the
nearest fixed obstruction along the back wall.
6. Do not exceed the tabular value in in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances for the perpendicular distance from the centerline of the nozzles to the
inside face of the nearest hangar bay door.
7. Do not exceed the tabular value in in Table 2-1: Minimum Aircraft Maintenance Bay
Clearances for the perpendicular distance from the centerline of the nozzles to the
nearest fixed obstruction along the side wall.
166
UFC 4-211-01
13 April 2017
Change 1, November 2017
FUEL CELL MAINTENANCE
WASH BAY
The Functional Data Sheets (FDS) and Space Types identify the functional spaces and
specific design needs for individual spaces within hangars. They are presented as a
guide for the designer, planner, or Request for Proposal (RFP) preparer. It is intended
that the information in the FDS are the minimum requirements for the respective rooms
and spaces. These minimum requirements apply in addition to all other requirements of
this UFC and other referenced documents. In the event of a mutually exclusive conflict
or where both requirements cannot be satisfied, the FDS take precedence. However, if
in the best judgment of the designer, a more restrictive requirement is appropriate, the
more restrictive requirement may be applied after consulting with the user. It should not
be assumed that these data sheets or space types reflect full requirements of the user
or the full requirements of any specific aircraft type. Refer to 7-14.1: FDS Format for
blank space references and additional minimum requirements.
FDS Format
Building design criteria are provided in a standard FDS table format that generally
follows the Uniformat II/Work Breakdown Structure (WBS). Note that blank spaces
found in the FDS indicate building components or systems should follow standard
guidance per UFC 1-200-01, as a minimum. The Built-In Equipment/Casework category
includes anything physically attached or plumbed to the building such as counters,
cabinets, casework, toilet accessories, window shades or blinds, heavy-duty pallet
racks, and recessed projection screens. The Furnishings, Fixtures &Equipment (FF&E)
category includes loose or moveable items such as desks, chairs, and shelving. Items
such as computers, printers, copiers, and flat screen monitors are "user-provided"
equipment and are not considered FF&E. Coordinate FF&E and user-provided
equipment with the building systems.
Applicability
All of the spaces listed in the following tables may not be applicable to all hangar types.
For example, Aviation Ordnance will not generally be provided in a hangar where the
aircraft do not have weapons or ejection seats. However, consider future flexibility and
future hangar use in the design of functional spaces. Additionally, not all required
spaces are listed in these tables, as there are too many variations and unique
requirements when considering the range of aircraft inventory. Many aircraft FRD may
167
UFC 4-211-01
13 April 2017
Change 1, November 2017
further define more specific requirements for these functional areas as well as define
other required hangar spaces. Building support spaces such as mechanical, pump
rooms, and electrical rooms must be provided as required and all spaces may not be
listed. Some data sheets and space types apply only to specific airframes as noted.
Each squadron occupying a hangar has different requirements based on the size of the
squadron, the type of aircraft, the type of hangar (see below), the type of squadron
(e.g., training, reserve) and various other factors. The functional areas required are
dependent on operational requirements and the functions required are determined by
the user during the planning/DD 1391 development phase. Designer or RFP preparer
must develop and coordinate project specific requirements with the user squadron,
based on this UFC, the specific design aircraft(s), respective FRD or equivalent
documents, and existing maintenance capabilities at each base.
168
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airframe Space Space Space Name Space Description Refer to Functional Data Sheet
Category Grouping (Reference Table Number)
General Shop O1 Avionics Space Maintains Aircraft electrical Refer to Table 7-7: Avionics
(Shop) systems. This shop also
provides storage for
specialized communication
equipment and may require
special secure storage
areas. Consider providing a
vault within the shop as
opposed to making the
entire shop a secure space.
A separate Avionics shop
may be required due to
different ratings of work or
required security level.
General Shop O1 Corrosion Provides maintenance shop Refer to Table 7-8: Corrosion
Control/Coating for corrosion control. Control/Coating Shop
(Shop) Includes Low Observability
(LO) Maintenance for F-35.
General Shop O1 Detachment (Shop) Standard shop for Refer to Table 7-9: Detachment
Squadrons employing
deployed aircraft. This is
generally a workspace
without any specific
requirements. Coordinate
requirements with a
squadron configured for
detachment components.
General Shop O1 Flight Gear/Paraloft This space is used to repair Refer to Table 7-10: Flight
(Shop) flight gear. It also provides Gear/Paraloft
the storage area for flight
gear. Also may be part of
AME shop or Flight
Equipment
General Shop O1 Flight Line Office Office for flight line shop None
General Shop O1 Hangar Storage Storage area adjacent to None
(Shop) hangar bay.
General Shop O1 Line Shack (Shop) Flightline personnel waiting None
area and storage area
General Shop O1 Night Vision This space provides for Refer to Table 7-12: Night Vision
Goggles (NVG) storage of night vision gear. Goggles (NVG) Storage
Storage (Shop)
General Shop O1 Phase Crew (Shop) Provides planned Refer to Table 7-13: Phase Crew
maintenance on aircraft
parts.
General Shop O1 Power Plant (Shop) Maintains Aircraft Engines. Refer to Table 7-14: Power Plant
General Shop O1 Seat Shop (Shop) Shop and storage area for Refer to Table 7-15: Seat Shop
seats and other
components that are part of
reconfigurable aircraft.
General Shop O1 Tool Room (Shop) Tool Storage and Issue Refer to Table 7-16: Tool Room
General Admin O1 1st Lieutenant This space provides for the None
storage of building
maintenance supplies and
office space for the 1st
Lieutenant.
General Admin O1 Bunk Room Sleeping Quarters for Duty None
Officer
169
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airframe Space Space Space Name Space Description Refer to Functional Data Sheet
Category Grouping (Reference Table Number)
General Admin O1 Chief's Mess Provides meeting space for None
Chief Petty Officers (CPO).
Coordinate requirement
with squadron.
General Admin O1 Division Office This space provides office Refer to Table 7-17: Division Office
space for the squadron
division officers.
General Admin O1 Lobby This space is located at the None
main personnel entrance to
the hangar. The space may
include the quarterdeck.
Verify requirement for
quarterdeck as not all
squadrons have personnel
available for manning.
General Admin O1 Maintenance This space provides for None
Administration administration of
maintenance activities. This
space is a general office
area.
General Admin O1 Maintenance Provides for separate or None
Administration - combined office for the
Private Offices Maintenance Officer (MO)
and the Assistant
Maintenance Officer
(AMO).
General Admin O1 Maintenance This space provides for Refer to Table 7-18: Maintenance
Control administration of squadron Control
maintenance. The space
also provides flight crews to
access the maintenance
records and flight data. This
space may also be used for
briefing of maintenance
personnel prior to beginning
of work day. Includes
consolidated printer
location and admin supply
storage.
General Admin O1 Maintenance Provides private office for None
Control Private the Maintenance Control
Office Officer in Charge (OIC).
General Admin O1 Material Control This space provides for None
maintenance record
storage. This area also
provides for receipt and
documentation of
deliveries.
General Admin O1 Quality Assurance This space provides office None
space and study space for
quality assurance activities.
This space also provides
for storage of aircraft
manuals. Manuals may be
provided on Compact Disk
(CD).
General Admin O1 Quarterdeck/Duty/S This space is located at the None
ecurity Office main personnel entrance to
the hangar. The space may
be separate from the lobby
or open to the lobby as
determined. Generally, this
space is occupied by one
person. Provides a
controlled entry to the
building.
General Admin O2 CO/XO Toilet Private Toilet for CO/XO None
170
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airframe Space Space Space Name Space Description Refer to Functional Data Sheet
Category Grouping (Reference Table Number)
General Admin O2 Exam Room Provides exam space for None
medical officer
General Admin O2 General Office General open office space None
(open) used for squadron
administration.
General Admin O2 Personnel Office General open office space None
used for squadron
administration.
General Admin O2 Private Office - Executive level private None
Commanding offices are generally
Officer, Executive adjacent to each other and
Officer are often interconnected
either by direct access or
by a vestibule. They may
share a toilet with shower if
requested. Generally, the
spaces are associated with
a waiting area and/or
clerk’s office. They may be
a part of a "command suite"
that includes the Command
Master Chief. Command
Suites may have secure
environments.
General Admin O2 Private Office - This type of office is None
General provided for various
administrative functions on
the O2 level. Offices may
include: Drug and Alcohol
Program Advisor (DAPA),
Command Master Chief,
Admin Officer, CPO, OIC,
CCD, Combat Control
Officer (CCO), SAFTO,
NATO, Legal, and
Contractor.
General Ops O2 Briefing Room This space provides for None
operational briefings
associated with flight
operations
General Ops O2 Chart Room Provides space for flight None
planning operations and
storage of charts.
General Ops O2 Conference Room Provides space for None
meetings and conferences.
May be a secure space and
may include Video
Teleconference Capabilities
(VTC).
General Ops O2 Operations Offices Office serves as the None
operations center for all
squadron flight operations.
This may include other
offices such as Intel or
Tactics
General Ops O2 Secure Provides head-in space for None
Communications SIPRNet
Office
General Ops O2 Training This space provides for None
Room/Classroom training of personnel. May
require training storage
space for table/chairs. May
include operable partitions
to create separate spaces.
General Ops O2 Ward Room (Ready Ready room for pilots and None
Room) flight crew.
171
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airframe Space Space Space Name Space Description Refer to Functional Data Sheet
Category Grouping (Reference Table Number)
General Support O1/O2 Men's Toilet Toilet facilities, locker and None
shower rooms.
General Support O1/O2 Break Provides space for vending None
Room/Vending machines and snack bar
operations. Coordinate
specific requirements with
the squadron. Multiple
break rooms may be
required.
General Support O1/O2 Building Systems Provides space for building None
Spaces systems including, but not
limited to: Mechanical, Fire
Protection, Fire Pump,
Electrical, and Elevator
Equipment.
General Support O1/O2 Communications Provides space for None
Room telecommunications and
Navy Marine Corp Intranet
(NMCI) head-in equipment
General Support O1/O2 Corridors Provides for horizontal None
circulation
General Support O1/O2 Elevator Elevator cab and shaft None
space
General Support O1/O2 Janitor Closet Provides for cleaning None
supply storage.
General Support O1/O2 Stairs Provides for vertical None
circulation
General Support O1/O2 Women's Toilet Toilet facilities, locker and None
shower rooms.
F-35 OH OH Hangar Bay (OH) Maintenance Hangar area Refer to Table 7-19: Hangar Bay
(F-35 Only) (OH) (F-35 Only)
F-35 Shop O1 Seat and Canopy Maintains ejection seats Refer to Table 7-20: Seat and
Maintenance/AME and canopies. Includes Canopy Maintenance/AME
(Shop) (F-35 Only) arming and de-arming with Maintenance (Shop) (F-35 Only)
storage of explosives.
Includes storage and
maintenance of other
Alternate Mission
Equipment (AME).
F-35 Ops O1/O2 SAPF ALIS Office None
Administration (F-35
Only)
F-35 Ops O1/O2 SAPF ALIS Office None
Maintenance (F-35
Only)
F-35 Ops O1/O2 SAPF ALIS OMS Office None
Operations (F-35
Only)
F-35 Ops O1/O2 SAPF Assistant Office None
Intel (F-35 Only)
172
UFC 4-211-01
13 April 2017
Change 1, November 2017
Airframe Space Space Space Name Space Description Refer to Functional Data Sheet
Category Grouping (Reference Table Number)
F-35 Ops O1/O2 SAPF Mission Office None
Planning (F-35
Only)
F-35 Ops O1/O2 SAPF Pilot Briefing Briefing None
(6) (F-35 Only)
173
UFC 4-211-01
13 April 2017
Change 1, November 2017
Functional Data Sheets
Minimum Ceiling Height Refer to mandatory height requirements based on hangar type.
Floors Fuel Resistive Resinous Flooring, 5-Coat System. Incorporate floor markings if
required.
Ceiling Exposed construction.
Interior Construction / Incorporate an approved Avian Intrusion Prevention System in the hangar bay.
Built-in Equipment
Furniture, Fixtures & Equipment Storage cabinets
(FF&E)
Plumbing Emergency Shower and Eyewash stations per Chapter 3. Compressed air drops on
walls - Compressed air source of 125 psi with a constant flow rate of 20 cfm. Each
service point with the following: One (1) 38 mm (1/2 in.) needle valve shutoff, One
(1) pneumatic tool filter, One (1) 861.8 kPa (125.0 psi) pressure regulator, One (1)
pneumatic tool lubricator, Two (2) pneumatic tool quick-connectors, One (1) wall-
mounted hose rack. Coordinate with users on number of compressed air drops
required and requirements for hose reels for water or air.
HVAC Provide per Chapter 3.
Specialized exhaust system(s) required. Exhaust directly outdoors
through roof. Thermostatic control switch activated by hangar door
to shutoff heating if OA temp is above 40ºF.
May require air conditioned hangar bay for certain aircraft in warmer climates.
May require overhead radiant heating.
May require hangar door track heating system in colder climates.
Fire Protection Provide per Chapter 3 and Chapter 7.
Lighting
Intercommunications Systems Provide per Chapter 3. Microphone and Auxiliary Jacks, Paging Speaker
System (Neoplanar Emitters), GPS Repeater Systems
Electrical Special Systems Provide per Chapter 3 and Chapter 7. 400 Hz Frequency Converters, Ground
and Devices Power Equipment Connections.
Security - CCTV Cameras, Access Control (if required by Government)
Special Requirements Provide Hangar Doors per Chapter 3 and Chapter 7.
Provide catwalks and ladders to provide service for Vertical Lift Fabric Doors.
Provide bridge crane(s) when required.
Acoustics Provide acoustical seals including automatic door bottoms and perimeter seals on
any doors provided between the O2 level and the hangar bay.
174
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-5: Air Frames (Shop)
Description / Usage Maintains air frames.
Floors Fuel Resistive Resinous Flooring, 5-Coat System. Incorporate floor markings
if required.
Ceiling Exposed construction.
Lighting
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide
a minimum of a pair of 3'0" x 7'-0" personnel doors opening onto the hangar
bay.
If a 4 ft. (1220 mm) wide opening is adequate, provide a single 4 ft. (1220 mm)
wide personnel door in lieu of double doors.
Acoustics
175
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-6: Aviation Ordnance (Shop)
Description / Usage Maintains aircraft weapons systems including weapons cleaning and storage.
Floors Fuel Resistive Resinous Flooring, 3-Coat System. Incorporate floor markings
if required.
Ceiling Exposed construction.
Power
Electrical Special Systems and 400 Hz Panelboard, 400 Hz Bench Connection, Test Bench Connections
Devices
Lighting
Special Requirements Provide direct access to the exterior for the Aviation Ordnance Shop. Provide
panic devices on all doors from the shop. May require a vault. Coordinate
with the squadron.
Special solvents may be used for cleaning - provide special exhaust if
required.
Coordinate explosive classification requirements with the users.
Acoustics
176
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-7: Avionics Space (Shop)
Description / Usage Maintains aircraft electrical systems. This shop also provides storage for
specialized communication equipment and may require special secure
storage areas. Consider providing a vault within the shop as opposed to
making the entire shop a secure space.
Minimum Ceiling Height
Finishes Walls Paint resilient base.
Furnishings Desks and chairs, bookcases, file cabinets, workbench with stools, aircraft parts
shelf, vice, storage cabinets, secure file cabinet if required.
Power
Lighting
Communication CATV Outlet
Special Requirements Sometimes this space may require a vault or secure file cabinets. Coordinate
requirement with squadron.
Acoustics
177
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-8: Corrosion Control/Coating Shop
Description / Usage Maintenance shop for corrosion control. Includes Low Observability (LO)
Maintenance for F-35.
Furniture, Fixtures & Equipment Desks and chairs, bookcases, file cabinets, workbench with stools, aircraft parts
(FF&E) shelf, vice, storage cabinets, hazmat lockers, and corrosive battery lockers.
Power
Lighting
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide a
minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the hangar bay.
If a 4 ft. (1220 mm) wide opening is adequate, provide a single 4 ft. (1220 mm)
wide personnel door in lieu of double doors.
Acoustics
178
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-9: Detachment (Shop)
Description / Usage Standard shop for Squadrons using deployed aircraft. Coordinate
requirements with a squadron configured for detachment components.
Minimum Ceiling Height
Floors Fuel Resistive Resinous Flooring, 3-Coat System. Incorporate floor markings if
required.
Ceiling Exposed construction.
Power
Lighting
Special Requirements
Acoustics
179
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-10: Flight Gear/Paraloft (Shop)
Description / Usage This space is used to repair and store flight gear.
Floors Resilient flooring or Fuel Resistive Resinous Flooring, 3-Coat System. May
require static dissipative flooring.
Ceiling Exposed construction.
HVAC Dryer vent required. Specialized exhaust system(s) required. Exhaust directly
outdoors through roof. Explosion-proof fan motors may be required.
Fire Protection Provide per Chapter 3 and Chapter 7
Lighting
Special Requirements Two (2) exits are required from this space. Swing door outward and provide panic
hardware.
Verify quantity of Class C/D1.4G explosive material within the space. Provide
protective construction if the allowable quantities of explosive material are
exceeded.
Space may need to be classified as a "Hazardous Occupancy" based on types
and quantity of pyrotechnical devices stored in the space. Verify quantity
(pounds) of material prior to establishing a special occupancy separation.
Acoustics
180
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-11: Flight Line (Shop)
Description / Usage Flight line personnel shop
Floors Sealed concrete is the minimum. Resilient flooring or Fuel Resistive Resinous
Flooring, 3-Coat System if requested by the squadron.
Ceiling Exposed construction. Paint exposed items such as structure, ductwork, conduit,
piping, devices.
Interior Construction /
Built-in Equipment
Furniture, Fixtures & Equipment Desks, desk chairs, tool storage cabinets, workbenches, stools, file cabinets, as
(FF&E) required.
Plumbing Service sink
Emergency eyewash per Chapter 3
HVAC
Power
Lighting
Special Requirements Due to the potentially large pieces of equipment brought into this space,
provide a minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the
hangar bay.
Provide a minimum 8 ft. (2.4 m) high motorized rolling service door to the
exterior.
Acoustics No special requirements
181
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-12: Night Vision Goggles (NVG) Storage (Shop)
Description / Usage This space serves as storage room of night vision gear.
HVAC
Power
Lighting
Communication
Special Requirements Provide metal door with a combination lock and deadbolt.
Acoustics
182
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-13: Phase Crew (Shop)
Description / Usage Shop for planned maintenance on aircraft parts.
Floors Fuel Resistive Resinous Flooring, 5-Coat System. Incorporate floor markings if
required.
Ceiling Exposed construction.
Power
Lighting
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide a
minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the hangar bay.
If a 4 ft. (1220 m) wide opening is adequate, provide a single 4 ft. (1220 mm) wide
personnel door in lieu of double doors.
Acoustics
183
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-14: Power Plant (Shop)
Description / Usage Maintains aircraft engines.
Floors Fuel Resistive Resinous Flooring, 5-Coat System. Incorporate required floor
markings
Furniture, Fixtures & Equipment Desks and chairs, bookcases, file cabinets, workbench with stools, aircraft parts
(FF&E) shelf, vice, storage cabinets.
Lighting
Intercommunications Systems Call-In and Volume Control Station. Connect all shops, maintenance control, tool
room and material control via intercommunication system.
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide a
minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the hangar bay.
If a 4 ft. (1220 mm) wide opening is adequate, provide a single 4 ft. (1220 mm) wide
personnel door in lieu of double doors.
Acoustics
184
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-15: Seat Shop (Shop)
Description / Usage Shop and storage area for seats and other components that are part
of reconfigurable aircraft.
Minimum Ceiling Height
Interior Construction / Marker Boards. May require heavy industrial shelving for seat storage.
Built-in Equipment
Furniture, Fixtures & Equipment Desks and chairs, bookcases, file cabinets.
(FF&E)
Plumbing
Power
Lighting
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide a
minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the hangar bay.
If direct access to the hangar bay is not provided, provide an exterior double
door.
Acoustics
185
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-16: Tool Room (Shop)
Description / Usage Tool storage and issue
Floors Sealed concrete resilient flooring or Fuel Resistive Resinous Flooring, 3-Coat
System.
Interior Construction / Stainless steel tool issue counter located within the tool room. Provide a stainless
Built-in Equipment steel service counter with overhead rolling service counter door if requested by the
users. Marker Boards and Peg Board
Furniture, Fixtures & Equipment Desks and chairs, bookcases file cabinets, workbench with stools, aircraft parts
(FF&E) shelf, vice, storage cabinets, parts storage bins.
Lighting
Communication
Intercommunications Systems Call-In and Volume Control Stations. Connect all shops, maintenance control, tool
room and material control via intercommunication system.
Special Requirements Due to the potentially large pieces of equipment brought into this shop, provide
a minimum of a pair of 3'-0" x 7'-0" personnel doors opening onto the hangar
bay.
If a 4 ft. (1220 mm) wide opening is adequate, provide a single 4 ft. (1220 mm)
wide personnel door in lieu of double doors.
Consider using modular rolling storage shelving units for large tool rooms.
Coordinate with structural slab for possible rail installation.
Acoustics
186
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-17: Division Office
Description / Usage This space provides office space for the squadron division office.
Finishes Walls Paint resilient base. Internal separation partitions may be gypsum board on
metal studs.
Floors Resilient flooring, minimum. Do not provide carpet.
HVAC
Power
Lighting
Special Requirements
Acoustics Provide a minimum STC rating of 39, for partition and door construction.
187
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-18: Maintenance Control
Description / Usage Squadron Maintenance Administration: The space also allows flight crews to
access the maintenance records and flight data. This space may also be used
for briefing of maintenance personnel prior to beginning of work day.
Minimum Ceiling Height
Floors Resilient flooring, minimum on office side; sealed concrete, epoxy coating
on the customer side. Do not provide carpet.
Interior Construction / Service Counter to provide for maintenance personnel to receive daily
Built-in Equipment assignments and provide a work space for review of records.
Counter for flight crew to enter flight records. Marker Board, TV Bracket.
Furniture, Fixtures & Equipment Desks and chairs, bookcases, lateral files, time zone clock. Flight planning boards,
(FF&E) if required.
Plumbing
HVAC
Power
Lighting
Communication Provide network and telephone per UFC 3-580-01, CATV Outlet, Conduits to Roof
Mounted Antenna Farm Platform, Base Radio Outlet
Intercommunications Systems Master Control Station. Connect all shops, maintenance control, tool room and
material control via intercommunication system.
Special Requirements User may request that this space be combined with Material Control.
Sometimes access to the exterior is provided if it is part of Material
control. CCTV monitoring and Pan, Tilt Zoom (PTZ) control of hangar
and apron cameras.
When this space has direct visual access to the hangar bay, provide fixed with fire
rated glass.
Acoustics
188
UFC 4-211-01
13 April 2017
Change 1, November 2017
7-14.5.1 F-35 Functional Data Sheets
Table 7-19: Hangar Bay (OH) (F-35 Only)
Description / Usage Maintenance Hangar area
Minimum Ceiling Height Refer to mandatory height requirements based on hangar type.
Finishes Walls Paint walls between O1/O2 and hangar bay
Floors Fuel Resistive Resinous Flooring, 5-Coat System. Incorporate floor
markings if required
Ceiling Exposed construction.
Interior Construction / Built-in Equipment Incorporate Avian Intrusion Prevention System in the hangar bay.
Furniture, Fixtures & Equipment (FF&E)
Plumbing Emergency Shower and Eyewash stations per Chapter 3. Compressed
air drops on walls - Compressed air source of 125 psi with a constant
flow rate of 20 cfm. Each service point with the following: One (1) 38 mm
(1/2 in.) needle valve shutoff, One (1) pneumatic tool filter, One (1) 861.8
kPa (125.0 psi) pressure regulator, One (1) pneumatic tool lubricator,
Two (2) pneumatic tool quick-connectors, One (1) wall-mounted hose
rack. Coordinate with users on number of compressed air drops required
and requirements for hose reels for water or air.
Provide catwalks and ladders to provide service for Vertical Lift Fabric
Doors
Provide Overhead Bridge Crane
Acoustics Provide doors between the O2 level and the hangar bay with acoustical
seals including automatic door bottoms and perimeter seals
189
UFC 4-211-01
13 April 2017
Change 1, November 2017
Table 7-20: Seat and Canopy Maintenance/AME Maintenance (Shop) (F-35 Only)
Description / Usage Maintains ejection seats and canopies. Includes arming and de-arming with storage
of explosives. Includes storage and maintenance of other Alternate Mission
Equipment (AME).
Minimum Ceiling Height
Finishes Walls Paint with resilient base.
Floors Sealed concrete is the minimum. Resilient flooring or Fuel Resistive Resinous
Flooring, 3-Coat System if requested by the squadron.
Ceiling Exposed construction.
Interior Construction / Built-in Marker Boards
Equipment
Furniture, Fixtures & Equipment Desks and chairs, bookcases, file cabinets, workbench with stools, aircraft parts
(FF&E) shelf, vice, storage cabinets.
Plumbing Compressed air drop: Compressed air source of 125 psi with a constant flow rate
of 20 cfm. Each service point with the following: One (1) 38 mm (1/2 in.) needle
valve shutoff, One (1) pneumatic tool filter, One (1) 861.8 kPa (125.0 psi) pressure
regulator, One (1) pneumatic tool lubricator, Two (2) pneumatic tool quick-
connectors, One (1) wall-mounted hose rack. Coordinate with user on quantity and
location and requirements for hose reels.
HVAC Specialized exhaust system(s) required. Exhaust directly outdoors through roof.
Thermostat/humidistat. Separately controlled zone
Humidifier/Dehumidifier may be required due to the presence of ordnance.
Explosion-proof fans and motors may be required for MK16E aircraft ejection seats.
Fire Protection Provide per Chapter 3 and Chapter 7. Deflagration venting may be required
depending upon the type and quantity of explosive stored.
Power
Grounding Systems Provide Ground Bus Bar per UFC 3-575-01 and Ordnance Grounding per NAVSEA
OP-5.
Electrical Special Systems and
Devices
Lighting Explosive proof
Communication CATV Outlet
Criteria for explosive classifications are based on Joint Technical Bulletin 700-2
Department of Defense Ammunition and Explosives Hazard Classification
Procedure
Provide doors wide enough to accommodate the seat dolly. Validate door size
adequate to accommodate Rotating Canopy Stand.
Acoustics
190
UFC 4-211-01
13 April 2017
Change 1, November 2017
7-14.5.2 MV-22 Functional Data Sheets
Table 7-21: Airframe Hydraulic Clean Room (Shop) (MV-22 Only)
Description / Usage This work center performs inspections and proper procedures on flight
control systems, hydraulic power systems and associated subsystems,
and Blade Fold Wing Stow (BFWS) systems
Power
Grounding Systems
Electrical Special Systems and Devices
Lighting
Communication Category (CAT) 5e Unshielded Twisted Pair (UTP) cable for all
connections involving the Portable Electronic Maintenance Aid (PEMA)
equipment.
Intercommunications Systems
Special Requirements The Hydraulic Particle Analyzer uses a Class 1 Laser, has a
rechargeable Nickel-Metal Hydride battery, an Alternating Current (A/C)
power cord, a sonic bath with A/C plug, and a compressed air connection
(60.0 to 110.0 psi, clean and dry). This unit is portable using Carbon
Dioxide (CO2) bottles for compressed air and rechargeable battery for
power.
Provide handling and storage (IAW) local codes and requirements due to
HAZMAT.
Acoustics
191
UFC 4-211-01
13 April 2017
Change 1, November 2017
NAVY ADJACENCY DRAWINGS
Drawings
The conceptual adjacency diagrams below illustrate functional relationships and are not
intended for use as standard designs.
192
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-4: OH/O1 Level Adjacency Diagram
193
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-5: O2 Level Adjacency Diagram
194
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-6: Type I & II OH/O1 Level Hangar Adjacency Diagram
195
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-7: Type I (F-35) O2 Level Adjacency Diagram
196
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-8: Type III OH/O1 Hangar Adjacency Diagram
197
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-9: Section Showing Header Truss
198
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure 7-11: Section through Type II Hangar Crane Configuration and Vertical
Clearances
199
UFC 4-211-01
13 April 2017
Change 1, November 2017
200
UFC 4-211-01
13 April 2017
Change 1, November 2017
APPENDIX A: REFERENCES
A-1 REFERENCES:
GOVERNMENT PUBLICATIONS
1. Department of Defense (DoD)
Washington Headquarters Service DoD Instruction 6055.01, DoD Safety and
Communications and Directives Directorate Occupation Health (SOH) Program, 14 October
http://www.whs.mil/ 2015
201
UFC 4-211-01
13 April 2017
Change 1, November 2017
GOVERNMENT PUBLICATIONS
UFC 3-260-01, Airfield and Heliport Planning
and Design
202
UFC 4-211-01
13 April 2017
Change 1, November 2017
GOVERNMENT PUBLICATIONS
UFC 3-535-01, Visual Air Navigation Facilities
203
UFC 4-211-01
13 April 2017
Change 1, November 2017
GOVERNMENT PUBLICATIONS
UFGS 09 67 23.16, Fuel Resistive Resinous
Flooring, 5-Coat System
204
UFC 4-211-01
13 April 2017
Change 1, November 2017
GOVERNMENT PUBLICATIONS
8. Occupational Safety & Health Standard 1910, Occupational Safety and Health
Administration (OSHA) Standards
www.OSHA.gov
OSHA 29 CFR 1910.179, Overhead and Gantry
Cranes Standard
10. Air Force Civil Engineer Center ETL 02-15, Fire Protection Engineering Criteria
http://www.afcec.af.mil/ for Aircraft Maintenance, Servicing and Storage
Facilities.
FED-STD-595B, Colors
205
UFC 4-211-01
13 April 2017
Change 1, November 2017
GOVERNMENT PUBLICATIONS
FS TT-P-1952 Paint, Traffic and Airfield
Marking, Waterborne.
NON-GOVERNMENT PUBLICATIONS
1. National Fire Protection Association NFPA 11, Standard for Low, Medium and
(NFPA) High-Expansion Foam
www.nfpa.org
NFPA 13, Standard for the Installation of
Sprinkler Systems
206
UFC 4-211-01
13 April 2017
Change 1, November 2017
NON-GOVERNMENT PUBLICATIONS
5. American Society of Civil Engineers ASCE 7, Minimum Design Loads for Buildings
www.asce.org and Other Structures
6. American Concrete Institute (ACI) ACI 302.2R-06, Guide for Concrete Slabs that
https://www.concrete.org/ Receive Moisture-Sensitive Flooring Materials
207
UFC 4-211-01
13 April 2017
Change 1, November 2017
NON-GOVERNMENT PUBLICATIONS
9. American Society for Testing and ASTM 523, Standard Test Methods for
Materials Specular Gloss
100 Barr Harbor Drive
PO Box C700 ASTM 1886, Standard Test Method for
West Conshohocken, PA Performance of Exterior Windows, Curtain
http://www.astm.org Walls, Doors, and Impact Protective Systems
Impacted by Missile(s) and Exposed to Cyclic
Pressure Differentials
208
UFC 4-211-01
13 April 2017
Change 1, November 2017
NON-GOVERNMENT PUBLICATIONS
10. Crane Manufacturing Association of CMAA 70, Specification for Top Running Bridge
America and Gantry Type Multiple Girder Electric
http://www.mhi.org/cmaa Overhead Traveling Cranes
209
UFC 4-211-01
13 April 2017
Change 1, November 2017
NON-GOVERNMENT PUBLICATIONS
210
UFC 4-211-01
13 April 2017
Change 1, November 2017
APPENDIX B: GLOSSARY
B-1 GLOSSARY
A Amps
AR Army Regulation
C Celsius
CAT Category
CD Compact Disc
cd Candela
CE Civil Engineering
cm centimeter(s)
db Dry Bulb
F Fahrenheit
FM Factory Mutual
ft. Feet
FW Fixed Wing
gal Gallon
HGR Hangar
Hi-Ex High-Expansion
HQ Headquarters
in inches
IR Infrared
IT Information Technology
kPA kiloPascals
kVA kilovolt-amperes
L Liters
lbs. Pounds
LF Logistics Facilities
max maximum
mg milligram
mm millimeter(s)
MO Maintenance Officer
MPa Megapascal
OH Organizational Hangar
PA Public Address
PV Photovoltaic
RF Radio Frequency
RW Rotary Wing
SE Service Equipment
sec Second
SF Square Footage
sq. Square
TBD To Be Determined
UL Underwriters Laboratory
US United States
UV Ultra-Violet
V Volt
220
UFC 4-211-01
13 April 2017
Change 1, November 2017
APPENDIX C: BEST PRACTICES
C-1 GENERAL
Best practices in Aircraft Maintenance Hangar design are contained in this appendix.
Design all Aircraft Maintenance Hangars to meet all applicable requirements found in
the following:
Incorporate AT/FP issues at the initial phase of the design. Formulate the basis for
design on UFC 4-010-01. Coordinate all protection features with the current standards
and any additional requirements in place at the time of the design. Ascertain the exact
requirements for protection based on a site-specific survey, or lacking one, provide the
minimum protection standards outlined in the standards. Coordinate all AT/FP issues
with the base that may be a part of another project or impact adjacent facilities such as
security fencing, parking.
221
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Highly reflective roof surfaces can reduce the heat island effect and
decrease solar heat gain to the building interior.
• Use whole building energy simulation and life cycle cost analysis to
evaluate high performance building envelope, mechanical and electrical
systems.
• Integrate automated controls with high-bay lighting, such as zoned
photometric sensors.
• Reflective (white or light colored) interior finishes help reduce the amount
of required lighting while ensuring direction to the work zone, instead of
absorption by walls and ceilings.
• Air compressor designs to include water cooled equipment strategically
located to provide the rejected heat for space heating, domestic hot water
pre-heating and tie into building heating systems.
• Solar air preheat for hangar bay area and combination preheating
domestic hot water.
C-2 CIVIL
C-2.1 Appearance
Locate HVAC equipment, meters, poles, transformers, vaults, pressure reducing station
piping and valving, and other utility items so that they do not detract from the building's
appearance. Design should also reduce the negative visual impact of utility items and
communication lines.
Consider the effect of local sun angles and wind conditions on the hangar.
C-2.3 Winds
In harsh climates, seacoasts and areas of consistently high or changing winds, design
hangar entry points (hangar bay, personnel entrance and windows, intake and exhaust
vents) to compensate for these adverse conditions, including snow. Consider prevailing
and seasonal wind conditions as well.
Limit the use of fencing to enclose and separate areas within the vicinity of the hangar
to those conditions requiring security or the protection of life, separation of a
construction site from operational facilities, isolation of a hazardous area, or as
stipulated by the Base Security Department.
222
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-2.5 Landscape Planting
Make use of low maintenance landscape plants that are indigenous to the area. Existing
mature trees and vegetation should be retained whenever practical. Landscape design
should avoid planting next to the hangar that would permit concealment in accordance
with criteria set forth in the Unified Facilities criteria for AT/FP. As hangars are generally
in industrial areas, limit landscaping to entrances and other public areas.
C-2.6 Utilities
Consider utilities that are essential to efficient operation and design of adequate size to
serve future requirements in the early planning stages. Specifically address the
adequacy of existing utilities support and include any additional needs. Plan utility lines
to minimize utility easements, capital investments, and maintenance and repair costs.
Locate underground utilities to minimize the cost and effort of performing maintenance.
Do not locate utility lines of any type under hangars except for those portions serving
the hangar. Minimize utility lines running under parking lots, sidewalks, and other paved
surfaces to minimize cost for maintenance of the systems. Locate all underground utility
lines, mains, and conduits at the minimum depth required in accordance with local code,
frost line and water table requirements, and, when possible, in common corridors to
allow for ready access and maintenance. Locate utilities to allow for future expansion of
the flightline.
C-3 ARCHITECTURAL
Military maintenance hangars are active workspaces and can be especially abusive
environments. An aircraft maintenance bay floor finish must be evaluated on a number
of performance characteristics.
• Proper Installation
• Chemical Resistance
• Impact Resistance
• Abrasion Resistance
• Reflectivity
223
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Slip Resistance
• Ease of Maintenance
• Replacement Timeline
• Life Cycle Cost
Coordinate floor finishes with the concrete design. For example UFGS Section 09 67
23.15 and UFGS Section 09 67 23.16 suggest a number of items for the concrete
designer to consider, such as types of admixtures, curing strategies, and below slab
vapor barriers to keep an epoxy finish from delaminating due to moisture emissivity
levels in the concrete. Refer to Figure 3-4: Typical Aircraft Maintenance Bay Slab on
Ground Cross-Section for guidance on location of the vapor barrier in the Aircraft
Maintenance Bay. Refer also to C-4.2.1: Floor Coatings and Vapor Retarder/Barrier.
Protect the floor from deterioration from harsh chemicals and solvents commonly used
in aircraft maintenance including jet fuel and Skydrol® fire resistant hydraulic fluids.
Concrete is porous and can easily be contaminated by spills. Dry shake floor hardeners
and polished floors increase resistance to absorption of chemicals, but true protection
requires a barrier. Consider Ultra-Violet (UV) resistance in hot climates that have high
levels of UV radiation.
Protect concrete from damage from dropped tools and parts. The urethane topcoats of
an epoxy system are less brittle and are more resistant to impact and abrasion wear
than hardeners or polishing. 5-coat epoxy is more resistant to chipping.
An abrasion resistant floor finish will protect concrete from damage incurred by carts,
stands and heavy wheels of aircraft and tugs. Sand and dirt left on the floor can become
an abrasive and dull the shine of many finishes.
C-3.1.1.5 Reflectivity
Reflectivity improves lighting conditions for maintenance operations under the fuselage
or wings and reduces the amount of lighting fixtures required. Provide translucent
windows to diffuse the natural light coming into a space with a reflective floor.
Provide a floor finish requiring fewer replacements over the life of the building.
Provide the finish most appropriate for the users’ requirements at the lowest life cycle
cost.
There are a number of floor finishes commonly used in aircraft maintenance bays. The
3-coat system is most common, but has an ongoing problem with low tolerance to
moisture emissivity in the slab. There are two floor finish options if the 3-coat system is
considered unacceptable and unreliable. You can use a non-coating system which may
cost less but provide significantly less protection than a coating system. The other
option is to provide the 5-coat system which has high performance ratings, but high
initial costs. However, the 5-coat system outperforms the 3-coat system in life cycle cost
analyses due to requiring fewer replacements over the life of the building.
• Sealed concrete
• Polished concrete
• Dry shake-on hardener
• 3-coat epoxy systems
• 5-coat epoxy systems
Concrete sealers are applied to concrete to protect it from surface damage, corrosion,
and staining. They either block the pores in the concrete to reduce absorption of water
and salts or form an impermeable layer which prevents such materials from passing.
This is basically the lowest initial cost solution but it provides almost no protection for
the concrete with regard to chemical and impact resistance. Performance:
225
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Cleanability depends on the texture of the concrete
• Low maintenance
• Needs to be resealed every couple of years
• Least expensive initial cost and least expensive life cycle cost
Polished concrete is a high-gloss finish attained by using special floor polishers fitted
with diamond-impregnated abrasive disks (similar to sandpaper) to grind down surfaces
to the desired degree of shine and smoothness. The resulting surface is relatively low
cost and low-maintenance but only provides slightly better performance than the sealed
concrete. Performance:
Mineral and metallic dry shake hardeners are hand spread and power-trowelled into the
wet concrete to provide additional abrasion resistance for high wear industrial concrete
floors. Performance:
Commonly known as a thin-film flooring system, this coating system has had
delamination problems in the past due to its intolerance to moisture emissivity in
concrete slabs. Current moisture vapor emissivity test requirements by the
manufacturers as well as the UFGS spec have minimized the installation of this system
on slabs where moisture rates are likely to cause delamination. Most manufacturers can
provide a moisture vapor barrier coating to reduce the emissivity to acceptable levels. A
3-coat system typically consists of 2 layers of epoxy with a urethane topcoat.
Performance:
This has an epoxy primer, a 1/4" to 3/8" trowelled on epoxy grout coat followed by 2
layers of epoxy and urethane top coat. Basically, the top 3 coats are the 3-coat system
bonded to a thick grout layer. Performance:
227
UFC 4-211-01
13 April 2017
Change 1, November 2017
manufacturer's moisture vapor barrier coating with a requirement to
deduct the associated cost if the concrete moisture tests determine this
coating is not necessary.
• High chemical resistance
• High impact resistance due to epoxy grout layer
• Abrasion resistance based on level of grit applied
• High reflectivity
• Slip resistance based on level of grit applied. There is a fine line between
slippery and hard to clean.
• Low maintenance - sweep regularly and scrub weekly. Higher grit levels
make cleaning more difficult.
• Needs to be patched and a new top coat applied every 8-10 years
• Most expensive initial cost, but lower life cycle cost than a 3-coat system
due to a less frequent re-coating schedule than the 3-coat system over the
life of the building.
Sealed concrete, polished concrete and dry shake-on hardeners are lower in cost than
the coating systems, but have significant reduced capabilities to protect the concrete
from the harsh environment of a military aircraft maintenance hangar. Life Cycle Cost
Analysis (LCCA) of the coating systems show the 3-coat system is less expensive
initially, but requires recoating more often than the 5-coat system, and therefore, has a
higher life cycle cost. The 5-coat system is tolerant of higher moisture vapor emissivity
rates and is less likely to require a moisture vapor barrier coating.
Consider the following issues when designing an Aircraft Maintenance Hangar for large
aircraft.
229
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure C-1: Considerations for Aircraft Maintenance Bays for Large Aircraft
230
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure C-2: Considerations for Aircraft Maintenance Bays for Large Aircraft
231
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-3.3 Interior Design - Furniture and Equipment
Furniture, Fixtures and Equipment (FF&E) should be "heavy duty" for shop spaces.
Verify FF&E to be furnished by user (not MILCON funded)." In addition, shops must be
easily reconfigurable by the users, so avoid the use of systems/panel furniture. Utilize a
freestanding desking systems for ease of configuration.
Office equipment such as printers, copiers, and fax machines are typically user-
provided equipment. However, these items should be located on furnishings plans and
coordination of supporting building systems such as power, data, and comm should be
included. Provide flush recessed floor power/data outlets as required by furnishings
layouts. Avoid or limit the use of power poles.
C-3.4 Acoustics
Acoustics around operational airfields pose significant questions about what to provide
in the way of acoustical enhancements on a hangar. The type of aircraft and the
projects proximity to the runways play a significant role in what might be expected on
the envelope of the project. At jet bases or other locations employing aircraft with
extremely high noise levels, it is important to consult with an acoustical consultant to
determine proper noise reduction requirements within various areas of the hangar. The
designer should carefully investigate the implications of providing specific acoustical
requirements for the envelope of the facility. In Design Build projects it is the
responsibility of the RFP preparer to determine the requirements and provide adequate
data to allow the Design-Build Contractor to adequately determine the cost for any
acoustical requirements.
C-3.4.2 Interior
Birds entering various openings within aircraft maintenance bay, roost in the available
flat areas of the superstructure. Accumulation of droppings, feathers, and other matter
pose a big problem. Bird droppings, accumulating on the aluminum skin of airplanes,
232
UFC 4-211-01
13 April 2017
Change 1, November 2017
can corrode the metal and eventually weaken the structure itself. Another concern is
that if droppings, feathers, and other matter get into the engines, clean critically
important parts as they could stall an engine during flight. Another concern is the
constant maintenance of the hangar floor and other surfaces due to bird inhabitants.
Bird-proofing methods vary from scaring devices, repellents such as screening mists
and sonic systems and full netting systems.
An inexpensive way to try and bird proof facilities is through the use of visual deterrents.
Iridescent reflective foil or flash tape can be easily strung around the superstructure and
turned into pennants. Inflatable balloons and stuffed bird predators are another
economical visual scare device. Their lifelike reflective predator eyes and markings drive
birds away by creating an "Optical Distraction Zone." Although inexpensive these devices
are usually a short term solution to the issue. The birds get use the scaring devices and
eventually ignore them.
Bird-misting systems are ideal for both humane and effective bird control. These bird
proofing systems work by releasing an ultra-fine mist that pest birds can't see and prefer
not to be around. The mist typically employs a chemical called methyl anthranilate, a
grape extract that naturally occurs in concord grapes. The extract has been widely used
for decades to deter a wide variety of pest birds including, sparrows, pigeons, starlings,
crows, blackbirds and geese. Yet it's safe for people, pets, plants and birds. The system
requires refilling and maintenance and too much misting can lead to residue on the
facility. Too little misting and you are not controlling the issue.
Another useful bird proofing repellent method is the electric-track bird repeller. Ideal for
ledges, rooftops, and flat or curved surfaces, these low-profile electrified tracks deliver a
non-lethal electric shock that discourages birds from landing or feeding. Some
manufacturers offer a flow-through design to keep water from damming up on rooftops
and other surfaces. These systems require maintenance and a constant electric source.
It is difficult to install this system on all surfaces of the superstructure birds would use
for nesting.
A bird slope is a simple solution ideal for many government buildings. Suitable for
eaves, ledges, beams and other 90-degree areas where pest birds tend to nest and
233
UFC 4-211-01
13 April 2017
Change 1, November 2017
roost, the angled, slippery PVC panels cause pest birds to simply slide off when they try
to land. For an even easier-to-install solution, there's bird gel. Birds hate this stuff
because it creates a sticky surface that birds find very annoying to land in. It's safe for
birds (except swallows) and a great way to keep birds from landing on ledges, I-beams,
parapet walls, conduit, pipes, and most flat or curved surfaces. It is difficult to install this
system on all surfaces of the superstructure birds would use for nesting.
A repellent method of bird spikes can be found on many military facilities. Bird spikes
are ideal for pigeons and other large birds. Some bird spikes are made of strong, rigid
unbreakable polycarbonate, others have stainless steel spikes. A cousin to the bird
spike is the bird spider. The spider arms wave with the breeze, keeping wild birds from
landing. Most come in a variety of diameters and install easily. And although they
appear menacing, spikes and spiders won't harm birds. Once installed these systems
require little maintenance besides fixing areas birds have found to next. It is difficult to
install this system on all surfaces of the superstructure birds would use for nesting.
To bird proof large areas such as the aircraft maintenance bay, bird netting creates an
impenetrable barrier for most birds. Some heavy-duty bird netting is made of
polyethylene fabric and is UV stabilized, flame resistant and rot and waterproof. Netting
comes in various mesh sizes to deter a wide range of birds. To seal out small openings,
there's copper mesh cloth. Available in rolls, it's easily stuffed into cracks or holes to let
air circulate but keep birds out. The system is quite noticeable in the aircraft
maintenance bay even if it is painted to match the superstructure. The net needs to be
located to not interfere with utilities such as fire protection, lighting and crane travel.
The net systems work well once they are installed and all the bird openings are
secured. These systems require monitoring to see if and where birds are getting
through the netting and getting them out. The netting may become an issue with
maintaining equipment located above the netting. Place the outlet of the high-expansion
foam fire protection system below the netting because the netting tends to disrupt the
foam flow.
C-4 STRUCTURAL
C-4.1 Foundations
Ground floors are typically slabs on ground. In some circumstances with particularly
poor geotechnical properties and schedules which do not allow for remediation, pile
supported slabs may be desirable. It is typical for the main structural frame to be built on
deep foundations while the ground floor slabs are soil supported. In this circumstance,
differential settlement is a potential risk to the serviceability of the facility. The designer
may consider careful detailing between the floor slabs and the surrounding structure or,
in the most severe circumstances, pile supporting the floor slab.
Floor coatings are moisture sensitive materials and care must be taken in construction
of the concrete slab. In the Aircraft Maintenance Bay, install the vapor retarder/barrier
as shown in Figure 3-4: Typical Aircraft Maintenance Bay Slab on Ground Cross-
Section.
For all other slabs on ground use ACI 302.2R-06 Guide for Concrete Slabs that Receive
Moisture-Sensitive Flooring Materials. In general, the flow chart in Figure 7-1: Aircraft
Maintenance Bay Striping Requirements of ACI 302.2R will be followed to ascertain the
location of the vapor Barrier/Retarder relative to the concrete slab and subgrade
materials. If the questions asked in the flow chart can’t be answered at the time of
design, then it is suggested that Figure 3-4: Typical Aircraft Maintenance Bay Slab on
Ground Cross-Section be used for locating the vapor retarder/barrier under the slab.
C-4.3 Superstructure
Single points of failure are undesirable in any facility but are historically common in long
span-steel structures. A single connection or member failure can result in catastrophic
collapse or failure of a large portion of the facility. Investigate secondary or back up load
paths for single points of failure and provide them where practical. If secondary or back
up load paths can’t practically be provided, then thoroughly design and review these
single points of failure.
While the structural engineer is typically advised to avoid interfering with the means and
methods of the construction professionals, he should have an understanding of the
consequences that accompany any chosen erection method. The design documents
should indicate if and when the structure is statically indeterminate. The designer of
record should consider the effect which various erection approaches may have on the
loads in an indeterminate structure and the documents must clearly indicate any
restrictions required on the erection to ensure a safe, serviceable building.
Some issues for the designer to be aware of include: The rigging and lift may impose
loads on a structural assembly that were not anticipated by the designer. Even if the
assembly is not damaged by the lift, it may undergo unexpected deformations that may
then be locked into the final structure once the last connections are made. The heavy lift
may place the large, overhead elements into place prior to the remainder of the facility's
framing being completed. This is often a physical requirement given the necessity of
getting equipment adjacent to the lift operations. The designer should give some
consideration early in the design as to the lateral stability of the building components
that support the major roof elements.
This approach is becoming increasingly uncommon with the general availability of large
cranes and the increased emphasis on avoiding fall injuries on the work site. The
approach involves the fabrication of temporary towers to support the piece-by-piece
fabrication of the major components in their final place. The temporary shoring tower’s
location will determine the actual deflected shape of the structure resulting from the
dead load of the structural steel only.
The advantage of aerial assembly is that it avoids the necessity of having a large
capacity crane and fabrication errors may be discovered and corrected without
postponing a single milestone-lifting event. The disadvantage of the aerial assembly is
the loss of productivity and potential for accidents related to high work. This approach
also introduces the risk that unexpected loads may be introduced in the structural
framing system by poorly designed shoring towers or long term settlement of the
shoring towers. Additionally, the manner in which the temporary towers are removed
may also introduce unexpected, albeit temporary, loads in the main structure.
236
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-4.3.3 Cantilevered Aircraft Maintenance Bay Framing System
A cantilevered system supports all of the gravity loads from the rear wall of the aircraft
maintenance bay. Lateral loads are resisted by the structural framing around the
perimeter of the structure. The roof framing system should be designed with a means to
correct out of tolerance construction without resorting to field modifications of any
member. Cantilevered roof systems are generally statically determinate in all phases of
construction.
C-4.3.3.1 Advantages
The system is advantageous in that it provides a column-free building face towards the
aircraft flightline. This maximizes the usable flightline frontage while decreasing the
number of obstructions to aircraft movements and provides for the maximum flexibility to
service future aircraft which may enter the inventory long after the hangar was
designed. The system provides the maximum flexibility for structural expansion to either
side of the hangar. However, if future expansion is anticipated, other disciplines must
consider such expansion in their design development. Additionally, the highest point of
the structure is generally towards the rear wall of the hangar, which may be
advantageous when the hangar is located near a runway and must remain below a glide
or transition slope.
C-4.3.3.2 Disadvantages
C-4.3.3.3 Considerations
Design documents for a cantilever system need to carefully consider the effect of
erection sequencing, actual versus predicted dead load deflection and environmental
conditions during the fabrication and erection. Additionally, the possibility of load
reversal on the main supporting elements as a result of high uplift forces must be
considered.
A header truss system spans the entire flightline face of the building and either rests
upon columns or towers at each flightline corner of the building or is continuous to the
foundation. The remaining walls of the hangar are conventionally framed. Lateral
237
UFC 4-211-01
13 April 2017
Change 1, November 2017
support is provided through the framing in the perimeter walls. The truss is typically
supported against lateral loads through dedicated horizontal truss system. The truss
should be designed to maintain a slight upward camber after all dead loads have been
placed. The truss may be fabricated on shoring towers in the air or on the ground and
lifted as a single unit. The truss may be designed as statically determinate,
indeterminate or initially determinate but becoming indeterminate at some point during
the erection sequence. The design should consider the effect of erection methodology
and sequence, in conjunction with determinacy of the system. Additionally, thermal
effects on statically determinate header trusses are particularly significant and the
designer of record should carefully evaluate these effects.
C-4.3.4.1 Advantages
The header truss is an efficient system to span intermediate lengths and provides a
relatively simple erection system, provided that the issues of static indeterminacy are
dealt with.
C-4.3.4.2 Disadvantages
The structural efficiency and stiffness decrease exponentially as the span of the truss
increases. This may be offset by increasing the depth of the truss. However, the
practical limits of transporting the fabricated hardware, erecting the assembled truss
and lateral bracing of the system and its individual components limit the truss depth to
something on the order of 25 foot (7.5 m). A header truss virtually precludes the use of
expansion joints; therefore, the hangar door span may be limited by the thermal
response of non-structural components. However, a three-hinged arch system allows an
expansion joint along the centerline of the hangar bay and extends the practical thermal
expansion limit. The header truss system also requires that flightline frontage be
dedicated to structural supports. Finally, the potential expansion of the hangar is
constrained by the presence of towers and lateral load resisting systems.
C-4.3.4.3 Considerations
Construction documents for a header truss system must clearly indicate the camber
requirements as well as supply the necessary information for the fabricator and erector
to predict the truss’s response at various states of construction, handling and loading.
The header truss may be designed as fixed, pinned or partially restrained at its supports
in order to balance the strength and deflection characteristics of the header truss with
the complexity of detailing and erection. The designer of a statically indeterminate truss
must carefully consider the influence that temperature, erection sequence and erection
rigging will have on the difficulty of completing connections as well as final camber and
this complexity must be communicated on the design documents.
The necessity of a large open, column free space will result in the lateral load resisting
system being located along the perimeter of the building. Widely separated lateral load
resisting elements may lead to high thermal stresses being developed. The designer is
238
UFC 4-211-01
13 April 2017
Change 1, November 2017
cautioned to balance the needs of other disciplines as to the location of cross-bracing
and the desire to produce a more torsionally resistant design against the potential for
developing high thermal stresses.
Hangars are prone to large eccentricities between centers of wind pressure and centers
of rigidity (especially cantilevered hangars). Even unfactored loads resulting from this
eccentricity may be significant. The designer should consider this eccentricity while
laying out the lateral load resisting system to locate the center of rigidity as near to the
center of applied force as practical.
Seismic design criteria may impose significant constraints upon the structural frame, not
only in the loads applied but also in the fundamental choice of framing system. The
allowable seismic force resisting systems and their limitations are identified in ASCE 7-
10, Table 12.2.1. A combination of site condition, design approach and structural layout
will determine the AISC criteria. A poor selection of framing, arrangement of bracing or
large asymmetries may result in expensive connection fabrication and testing
requirements or outright prohibition of the fundamental design. The facility designer’s
should investigate the seismic issues early in the design phase and plan the building’s
geometry and structure accordingly.
Hangars are prone to large eccentricities between centers of mass and centers of
rigidity. This is especially true for hangars with cantilevered roof framing systems.
Regardless of the structural system, the unfactored loads from this eccentricity may be
significant. For general information about structural loads, refer to UFC 3-301-01. For
detailed information, refer to UFC 3-310-04 and ANSI/AISC 341.
There may be additional benefits derived from efficiency in steel use and minimization
of exposed steel surfaces. The bi-axial strength characteristics provide for enhanced
electability and greater resistance to progressive collapse resulting from localized
damage. However, HSS connections are more challenging to design and often more
difficult to fabricate. The engineer of record should consider and clearly represent in the
contract drawings the difficulty of the HSS connections. Additionally, a greater reliance
on shop connections is the norm in HSS practice. The designer is encouraged to
consider the complications of transporting large, built-up elements to the site. HSS
connections may involve the use of welds that are not pre-approved and/or more
extensive weld testing than normally found on hot rolled steel construction.
239
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-4.6 Secondary Structural Systems
Historically, it has been difficult to maintain the necessary level of quality control
required to weld decks at side laps and at supports. Mechanical fasteners are the
desired option. Additionally, there may be significant economy in erection by allowing
pneumatic and powder actuated fastening systems. Most pneumatic and powder
actuated systems are proprietary in nature and not covered by the Uniform Guide
Specifications UFGS 05 30 00.
Hangar door guide systems are normally sized to allow total roof truss live load
deflection not to exceed 200 mm (8 inches). The designer of record is responsible for
coordinating the total anticipated roof deflection with the door guide manufacturer to
ensure that the design stroke of the hangar door guides is not exceeded. For cantilever
roof systems, the hangar door guide system should have adjustment capability to allow
for final leveling after all loads are in place. The construction documents must indicate
the expected maximum deflection, both upward and downward, as well as the allowable
deflection of the hangar door guide system.
C-4.6.3 Diaphragms
Given the difficulty in providing lateral load resistance for the large open spans
associated with hangar bay structures, it often appears desirable to incorporate the roof
deck into the lateral load system as a flexible diaphragm. However, these same large
spans involved in hangar structures often require large deflections in the frame before
the deck produces the desired resisting forces. Designers are therefore prevented from
relying on a steel deck as a diaphragm in the hangar bay and required to provide a
dedicated secondary horizontal lateral load. The deck may, however, be assumed to
provide local support to elements, such as top chord/flange support to joists/beams.
Generally bearing or shear wall systems of masonry or concrete are much stiffer that
the steel frame used in the hangar bay. Designers are cautioned to carefully consider
the differential movement likely to occur between the maintenance bay and the
shops/admin space when designing the interface.
C-5 MECHANICAL
C-5.1 Plumbing
The domestic heating water system will need to be sized to deliver the required hot
waterflow and temperature to meet the tepid water requirements for the operation of
one shower or eyewash station for 15 minutes.
240
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-5.2 HVAC
Overhead high intensity heaters for hangar bays are not allowed in Air Force and Navy
hangar bays for two reasons: clearances to aircraft and bridge crane equipment are
greater, presence of fueled, armed aircraft (Air Force). Low-intensity, gas-fired tube type
radiant heaters are preferred for overhead heating systems in Air Force and Navy
hangar bays.
In-floor radiant heat systems must be carefully considered for heating in hangar bays in
northern climates. This system is appealing because it does an effective job of heating
the floor, but the installation costs and impact on the floor slab design are significant.
Consider the amount of maintenance activities performed from the floor. Coordinate
closely with the system supplier on the design of the hangar floor slab, location of
insulation, and location of radiant tubing within the slab.
There are RPA aircraft that have internal avionics systems that are sensitive to high
temperatures and will alarm when the inside temperature gets up to 100ºF to 120ºF.
These aircraft might also have fuel systems that need to be kept below a certain
temperature. A conditioned hangar bay might be required which is inconsistent with
typical hangar design. Depending on the climate, evaporative cooling might be
considered. Portable preconditioned air carts can be considered in lieu of conditioning
the hangar bay.
Localized exhaust is typically done using a wall-mounted fume extractor built specifically
for small or limited workspace environments where air purification is desired. Includes a
free-hanging, self-supportive flex arm that can be easily maneuvered by the operator to
the desired location. Several filter combinations can be used depending on the
application.
Overhead low or high intensity radiant heaters are often the most life-cycle cost
effective method of heating Army hangars and most other high bay facilities. Some
quality high intensity radiant heaters have radiant efficiencies as high as 81%,
meanwhile low intensity tube heaters typically range from 35% to 60%. It must be noted
that radiant efficiency is not the same as thermal efficiency. Where work or maintenance
activities may be limited at times to specific areas in a hangar bay (such as where
maintenance is being conducted on one helicopter while other spaces have no activity),
high intensity radiant heaters applied in a spot or area heating method may be the most
life-cycle cost effective method of providing thermal comfort. The spot or area heating
241
UFC 4-211-01
13 April 2017
Change 1, November 2017
method allows for maximum radiant asymmetry where the ambient temperature may be
kept low.
In floor type radiant heating systems are more efficient than warm air systems as well;
however, the in-floor systems have long response times which do not allow for effective
unoccupied period temperature setbacks. Warm air systems should only be considered
in mild climates where there is minimal need to heat, and where air delivery
temperatures may be kept within 20 degrees of ambient room temperature. Delivery
temperatures which are greater than 20 degrees above the ambient temperature can
lead to excessive stratification in high bay facilities such as hangars.
Avoid locating piping under paved operational surfaces (taxiways and aircraft parking).
If using welded joints and fittings, give consideration to the maintenance of the system
and the provision of flanged joints at certain locations to allow for maintenance.
The hangar bay doors are often open for extended periods of time. Therefore, exposing
the hangar bay to high humidity, below freezing, and high temperature conditions.
Because of this, the hangar bay is considered an outdoor environment. Most
addressable output modules (control modules) are not UL listed to operate in these
conditions, and installing these devices in the hangar bay would be against the listing.
242
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-6.5 AFFF Trench Drain Location
For Navy: When approved by the NAVFAC FPE, under certain circumstances the
dedicated nose-dock area may be excluded from the AFFF trench drain boundary.
For Navy: When approved by the NAVFAC FPE, a blue beacon notification system
may be provided to indicate an AFFF trench nozzle discharge where a fire alarm voice
evacuation system is not provided.
In most hangar bays, directional loudspeakers should be used. It has been found that
providing directional speakers and aiming the speakers in the same general direction
increases message clarity and improves CIS scores. An example of this type of
installation includes providing ceiling only mounted speakers directed towards the floor
or providing speakers mounted only on the back wall directed towards the hangar bay
door opening. When opposing speakers are provided, such as speakers mounted on
opposing walls, the sound from one speaker will reach the occupant before the sound
from the other speaker. This results in an echo effect, which reduces message clarity.
Hangar bays often seem quiet during commissioning. However, during normal operation
and with the ventilation systems operating, hangar bays can have an average ambient
sound level approaching 75-80 dBA. The speaker system should be designed to deliver
a minimum sound power of 90 dBA throughout the hangar bay to account for the variety
of operating procedures.
C-7 ELECTRICAL
In locations where snow and freezing temperatures occur and a rolling door is provided
for the hangar bay consider a heating system for the tracks. If a heating system is not
provided the tracks may accumulate ice and/or snow and then ceases to function
properly. A hot water heating system may be used in lieu of an electric door track
heating system.
Pedestal mounted connections are placed within the hangar space. The pedestals are
permanently mounted within the space and create a fixed obstruction. The pedestals
bring the services closer to the aircraft and reduce the cable lengths. The cables may
be reeled up at the pedestal location or stored separately. The pedestals create an
obstruction free zone between the pedestal and the wall. Pedestals require little
maintenance.
243
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-7.3 Aircraft Grounding Points
Different grounding points may be used for different types of aircraft based on the size
of the aircraft. Consider the use of caps on the grounding point in the hangar bay. The
caps on the grounding points are difficult to maintain.
C-8 COMMUNICATIONS
Communications may include many different types of systems including but not limited
to unclassified data, classified data, telephone, public address, radios, satellites, and
intercom system. Each system has a special set of requirements. Identify the types of
systems required in the building early in the project and provision for the systems
accordingly.
Overhead cranes are often located close to overhead radiant heat systems. Coordinate
the two systems to avoid heat damage to the crane equipment. Common approaches
include automatic switching which deactivates the heaters located near the crane or,
locating shields or deflectors to protect the vulnerable elements of the crane.
Coordinate with the user to provide type of hangar door and controls required for
maintenance operations.
Rolling steel doors require significant depth for multiple tracks. Door pockets are always
preferred since they allow all door panels to be moved completely out of the door
opening. A door pocket is required unless the hangar door is wide enough that it is
acceptable to stack the doors along the tracks. Tracks extending the full length of the
door provide more flexibility on where the doors can be stacked. Confirm if the climate
requires the tracks to be heated. Specify rolling steel doors to allow them to be moved
with an aircraft tug in case of power failure. Tracks usually will be drained. Sand can
build up in the track in arid climates, requiring personnel sweep the tracks on a regular
basis. Best practices suggest the project Planner consult the installation and users to
choose a type of hangar door, and the operation requirements of the door.
Horizontal rolling hangar doors typically support their own gravity load and only impart
lateral (wind, seismic) loads to the main structural system through a track system at the
door head. The door head track is generally the responsibility of the hangar door
manufacturer. The designer of the hangar generally provides the support for the door
head track. The designer is cautioned to carefully consider the following:
The door track foundation will be considered a building foundation since it supports
building components. The door track foundation will bear below the building frost line at
or near the depth of the Aircraft Maintenance Bay foundations. The designer is
reminded that the door track foundation will be subject to aircraft wheel loads which may
control the design of the foundation.
Vertical Lift Fabric Doors require less depth and do not require pockets to provide
access to the full width of the opening. Larger openings require multiple panels with
fold-up mullions. Personnel doors in the hangar door may require the bottom 7 ft. (2.1
m) of the door to be rigid, causing unique header truss design to allow the door to
extend up beside the truss. Currently, VLFD backup manual operation requires hand
cranking from an elevated walkway at the VLFD hoist motor location and is extremely
laborious, difficult and time consuming. For these reasons, the UFC requires backup
systems to power the door. In case of a major failure such as a motor failure, the door
may be practically unusable for an extended period of time.
Vertical lift fabric doors are lighter than rolling doors, but the entire weight is carried by
the superstructure. Additionally, beyond a practical limit of about 60 ft. (18.3 m) multiple
door leaves are required. A complicated swinging mullion with additional overhead
equipment is required for every vertical lift fabric door beyond the first. However, vertical
lifting fabric doors do not require door pockets to entirely clear the hangar opening nor
do they require extensive support at grade.
The main load collecting members for a vertical lift fabric door panel generally span
horizontally, from mullion to mullion. As such, the mullions serve as load collectors for a
very large tributary area which is then delivered to the main framing system as a
concentrated force. At a basic, conceptual level, the structural engineer is cautioned to
consider how these forces will be collected and distributed back to earth. To the
maximum extent practical, the principle framing of the hangar structure should align with
the mullion locations.
At present the fabric utilized on the VLFDs does not meet the minimum blast resistance
requirements of UFC 4-010-01. Therefore, to utilize a VLFD in the Aircraft Maintenance
Bay, the Aircraft Maintenance Bay needs to be classified as Low Occupancy as defined
by UFC 4-010-01. If the Aircraft Maintenance Bay meets this requirement, then it must
also be structurally isolated from any shops/office spaces that cannot be classified as
Low Occupancy. Otherwise, it must be verified through analysis that the adjacent
245
UFC 4-211-01
13 April 2017
Change 1, November 2017
inhabited office/shops spaces would not collapse if the Aircraft Maintenance Bay
collapses in accordance with UFC 4-010-01.
At present the fabric utilized on the VLFDs does not comply with impact-resistance
requirements on facilitates located in "Wind-Borne Debris Regions". The fabric does not
meet the testing criteria of ASTM E1996 Standard specification for Performance of
Exterior windows, Glazed curtain Walls, Doors, and Storm Shutters Impacted by Wind
Borne Debris in Hurricanes and ASTM E1886 Standard Test Method for Performance of
Exterior windows, curtain walls, doors and Storm Shutters Impacted by Missile(s) and
Exposed to Cyclic Pressure Differentials. The designer is cautioned when using VLFDs
in "Wind-Born Debris Regions".
Large maintenance hangars usually opt for either rolling steel doors or vertical lift fabric
doors. Vertical lift bi-fold/canopy doors are common on small hangars for private
aircraft, but are much less common in military hangars. They have many of the
advantages of VLFDs; no pocket required, very little depth. They are significantly limited
in size.
Vertical lift canopy doors are typically constructed of steel framing (hot rolled and/or cold
formed) and clad with metal panel siding. The entire weight of the door and associated
counterweights is carried by the superstructure. Generally, the door width is limited to
roughly 100 ft. (30.5 m) but longer spans have successfully been installed. Additionally,
the height of the door is limited to roughly 25 ft. (7.6 m) because of the large cantilever
that develops on the door jambs as the door opens. At a basic, conceptual level, the
structural engineer is cautioned to consider how the weight of the door and
counterweights and door opening forces and how they will be resisted by the
superstructure and distributed back to earth. There has not been success installing
these doors in a multiple leaf configuration with a swinging mullion similar to the Vertical
Lift Fabric door.
Aircraft Maintenance Hangars require a vertical lift fabric door system or horizontal
sliding doors for the purpose of closing the aircraft maintenance bay. Best practices
include the project Planner consulting the installation and users to choose a type of
hangar door, and the operation requirements of the door before issuing the 1391.
However, less common hangar door options are available in the market place. These
optional door types need project specific approval from the appropriate Service design
criteria manager or waiver authority for this UFC. The design team is cautioned to
consider all facets of these doors effects on the building design when considering these
doors. The design team also needs to consider the ease of use, long term maintenance
and emergency opening capabilities when considering hangar door types.
246
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-11 FALL PREVENTION AND PROTECTION SYSTEMS
Provide fall prevention and/or fall protection in accordance with UFC 3-110-03. Most
hangars do not have mechanical equipment on the Aircraft Maintenance Bay roofs but
there may be other equipment such as antenna platforms requiring interior access and
fall protection. Aircraft maintenance workers are often required to work on top of aircraft,
well above the floor surface. It is common practice and is a requirement in similar
circumstances, for workers to be protected against falls from aircraft surfaces through
the provision of a Personal Fall Arrest System (including flexible horizontal life line and
rigid horizontal rail systems). However, hangars with bridge cranes represent a special
challenge in that the cranes and personal fall protection system compete for access to
same work space, workers protected from falls by the use of a personal fall arrest
system are now at risk of having their self-retracting lanyards (SRL) struck by a moving
crane. It is important for the designers of aircraft hangars to understand the conflicts
between the two systems and the means by which they can coexist. Additionally,
personal fall protection system may experience the same coordination issues with
overhead radiant heat systems as do overhead cranes. The designer should consult the
discussion on cranes which appear later in this section.
The HLL system consists of a flexible, wire rope or synthetic cable (usually a stainless
steel cable) that is installed in a horizontal or nearly horizontal plane between two or
more anchorages and to which a self- retracting lanyard (SRL) is attached. The SRL
has an integral locking snap hook at the end that attaches to the dorsal D ring of the
person's full body harness. Both the crane and HLL are usually installed at higher
elevations. In order to perform work more efficiently on an aircraft, a network of HLL
systems is generally required. The HLLs should be laid out in a system which accounts
for the location of the aircraft and maximizes the freedom of movement of the users.
Additionally, mobile attachment devices (trans-fasteners) used to have an added
mobility to move between intermediate anchorages with 100% tie-off. The HLL may
include energy absorber and lifeline tensioner. The self-retracting lanyard attached to
the HLL is a deceleration device made of synthetic rope, webbing or wire rope that
automatically locks at the onset of a fall. It pays out and automatically retracts onto the
drum during normal movement.
RHR system is a pre-engineered anchorage subsystem that uses one or more trolleys
on a horizontal track (often and I-beam or slotted tube) designed for the attachment of
components of a personal fall protection system. Horizontal Track system is a form of
RHR system that typically encloses a trolley inside a formed channel or track. A self-
retracting lanyard (SRL) is also attached to the RHR system for tying off to the dorsal D
ring of the full body harness.
247
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-11.4 Quality Control
Flexible HLL systems and Rigid Horizontal Rail systems are typically proprietary in
nature. The manufacturer should provide calculation and drawings showing that the
system was tested and certified under the supervision of a qualified person and is
appropriate for the application. There two types of HLL and RHR systems. Type 1 are
designed, tested and certified by the manufacturer of the system and installed and used
by the purchaser (or purchaser's representatives) in accordance with the manufacturer's
requirements, Type 2 systems are designed, tested, certified and installed by the
manufacturer and used by the purchaser of the system (or their representatives) in
accordance with the manufacture's requirements.
The following are few of the conflicts that will occur between the HLL system(s) and the
crane(s):
During the movement and operation of the crane a conflict will exist when personnel are
tied to the HLL systems because the SRLs when extended will be in the path of the
crane. A Lockout/Tag out program should be in place which precludes the cranes and
PFAS from being used simultaneously in a given area. If the crane is activated,
personnel should detach themselves from the HLL systems and the lanyards of the
SRLs should be retracted inside the elevation of the crane.
There is some difficulty in developing a system which raises and lowers the snap hooks.
There are two methods to lower the snap hooks to personnel's level. The first one is
using a power tagline system, which is a motorized winch that raises and lowers the
lanyards to the users' level, activated by a control panel. The second method is using a
manual tagline system to lower the snap-hook manually by a person on the ground
level. In practice, the power tagline system is preferable in that it can be interlocked with
the crane controls; however, the automatic system involves greater cost and complexity.
The manual system is generally simpler but requires greater diligence in use. In any
case, a tagline system will be required to ensure that both systems can be safely
operated. When the lanyard of the self-retracting device is retracted out of the crane's
path, there should be a minimum clearance around the crane envelope of 3 inches
(75 mm) from the top and 2 inches (50 mm) on either side.
If the HLL is installed below the crane rail, there may be interference with the crane
operation unless a system to retract the HLL to the sidewalls is provided. Such systems
generally come in one of two forms: (1) The HLL is suspended from a bridge beam
which is lower than the bridge crane and supported from tracks located outboard of the
bridge crane tracks. (2) The HLL is suspended from beams cantilevered off of the side
walls, much like a jib crane, which can rotate flush to the side walls. The large open,
column-free areas of hangar bays generally make these systems impractical in hangar
248
UFC 4-211-01
13 April 2017
Change 1, November 2017
usage. If the HLL requirements can be narrowed to a smaller portion of the total hangar
floor area, these systems may become acceptable. The above conflicts with the crane
may also apply to the RHR systems.
There are other personal fall arrest systems that can be specified, but these are
typically portable systems which can be more appropriately classified as equipment
then building systems:
These are costly but safer than the use of PFAS. The work stands should be equipped
with guardrails on three sides and a swing gate at the stairs or ladder side. Often, work
stands must be customized to fit a small range of aircraft types. This then necessitates
providing new work stands should the aircraft being serviced in the hangar change.
These are typically a single drop eyelet for a D-ring, supported from a jib arm on a
portable derrick. The derricks are generally cumbersome, requiring additional
equipment to relocate them, and offer only a limited range of movement to the user.
These types of systems are generally not appropriate for a maintenance hangar unless
the aircraft are expected to be static for long periods of time.
C-12.1 General
The aviation industry is constantly developing new aircraft. Emerging aircraft and
variants of existing aircraft are entering the military arsenal more often than this UFC
can be updated. When designing a hangar for an emerging aircraft there are a number
of issues to confirm.
• Review the Facilities Requirements Document (FRD) for the aircraft for
any specific requirements that could affect the hangar design.
• Communicate with the users to find out what is different or unusual about
the new aircraft from a maintenance point of view that may require
unusual systems or spaces.
o For example, The F-16 engine is dropped out of the aircraft for
maintenance. However, the F-35 engine is pulled out of the aircraft,
requiring significantly more space aft of the aircraft than the
standard clearances in this UFC would provide.
• Emerging aircraft are more likely to have secret components that may
require special storage rooms or other security measures.
249
UFC 4-211-01
13 April 2017
Change 1, November 2017
C-12.2 Unmanned Aircraft Systems
C-12.2.1 General
Unmanned Aircraft Systems (UAS) are composed of the aircraft as well as personnel
and equipment to launch, control, recover and maintain the aircraft. The aircraft itself is
typically called an Unmanned Aerial Vehicle (UAV). The term Remotely Piloted Aircraft
(RPA) is preferred by the Air Force. UAS are currently one of the fastest group of
emerging aircraft with a number of different systems in use by each Service and new
variants being introduced at an increasing rate. Review the Service-specific chapters for
guidance on which UAS this UFC applies to.
UAV/RPAs vary in size, range, capabilities, and many other characteristics. Aircraft
Maintenance Hangars housing UAS have spaces similar to other military aircraft. The
aircraft maintenance bays, maintenance shops, administration and support spaces are
not appreciably different from those found in other hangars. As discussed in the C-12.1:
General it is important to find out what may be unusual about the design aircraft that
could affect the hangar.
C-12.2.3 Communications
Communication systems are more important to UAS than other aircraft and often
require line of sight from the aircraft to antennae used to control the aircraft. As a result,
the hangar may have an array of antennae on top of the building. Consider location as
well as safe access to these antennae for maintenance.
The Mission Control Systems (MCS) where the UAV/RPAs are controlled may be either
separate or may be attached to the maintenance hangar. MCS spaces may have
specific requirements such as higher security and back-up systems for power and
communication. The MCS control rooms and electronic rooms may need to be shielded
from electromagnetic interference. Designers need to seek requirements for associated
facilities elsewhere, as they are not included in this UFC.
250
UFC 4-211-01
13 April 2017
Change 1, November 2017
APPENDIX D: QUESTIONNAIRE
D-1.1 Civil
• Identify the type of aircraft and the aircraft mix that will populate the
hangar.
• Will aircraft be brought into the hangar with fuel in them? (Identifies the
type of fire suppression system you need.)
• Consider towing vehicles turning clearances, access and egress from
hangar bay when sizing hangar bays.
• Will spot repair of corrosion control, grinding, bird interaction repair,
sanding, or painting on the aircraft frame or any parts be required inside
the hangar? If so, provide Material Safety Data Sheets for all materials
solid or liquid being used on the aircraft frame or inside the hangar to
determine if engineering control is required to mitigate hazard. (This may
impact spaces by requiring larger exhaust systems, specialized filters and
other items when exposure to heavy metals is likely)
• Identify any area and/or need to weld, paint, grind, sand, or apply paint or
corrosion control materials on the aircraft frame or other aircraft parts. Has
a preliminary hazard list been completed and a risk assessment code
been determined for the facility which identifies if controls are required?
Based on the risk assessment code, is a preliminary hazard analysis
required? (Engineering controls may be required) Provide this document
to the designers for inclusion in the hangar design.
• Based on the operations and the exhaust from the building, will an air
permit be required or will it need to be added as an air emissions source
251
UFC 4-211-01
13 April 2017
Change 1, November 2017
to the permit for the installation? (Additional filtration may be required by
the state for the exhaust. This increases the size of the fans and pollution
control costs.)
• What is the total occupant load? How does administration occupancy
compare to Aircraft Repair occupancy? (This identifies the size and
number of changing rooms and lockers for each group) In addition, are
work clothes or disposable suits (i.e. Tyvek suits) provided for those
people working in the shops/ hangar bays who may be exposed to
hazardous materials and chemical? Identify where laundry facilities or
disposal facilities for Tyvek suits are located.
• Identify how the spread of hazardous materials, dust and/or chemicals are
controlled, contained, and disposed. Segregation of regulated areas and
methods of demarcation may be required (such as full height partitions
and ventilation systems). (Note: Areas of facilities utilizing these
hazardous materials and/or chemicals must be designated as regulated
areas whenever exposure can be expected to be in excess of the
permissible exposure limit(s), and must be demarcated from the
surrounding workspace in a manner that establishes and alerts building
occupants of those boundaries of the regulated area.) Identify containment
processes and methods to monitor effectiveness of housekeeping
procedures, decontamination procedures, and engineering controls
tailored to each facility 8. Is Chromium VI or other toxins being utilized in
the hangar bay or workshops? If so, then proper decontamination
procedures and separate showers must be in place to protect the
personnel and surrounding work areas.
• Will waste oil drains be required? If so, give locations in hangar for
receptacles funnels.
• Will there be a drum room? If so, how many drums should it hold? What
types of chemicals will be stored?
• Where are hazardous waste containers to be located?
• Will mission functions be incorporated into the hangar building?
• How many employees, both direct and indirect, are expected to occupy
the hangar per shift?
• Will tail docks, wing docks, fuselage docks or nose docks be required? If
so, what utilities will be hooked up to them?
• What type of power tooling will be mounted in hangar? Examples include
drill presses, grinders, shear, and brakes. In what location will this
machinery be mounted? What type of utilities will be required for
operation?
• Will there be rolling service doors? If so, give location and size. (Will any
locations require power for motor operators?)
• Verify shop requirements.
252
UFC 4-211-01
13 April 2017
Change 1, November 2017
o Type of shops?
o Square footage needed for each shop?
o The location in the building?
o Machinery location?
o Floor coatings required?
o Number and size of roll-up doors to outside of hangar.
o Will the shops require any other services such as shipping and
receiving docks? Waste disposal/recycling?
• Will there be an inspection area? If so, give square footage, location and
utilities required.
• Will a parts cleaning shop be required? If so, give square footage,
location, utilities required. Also, please note any special or heavy drain
items such as salt bath ovens or large ovens. Provide material safety data
sheets for all cleaning products including application rates, methods,
durations and frequencies.
• Will there be a lunch/break room? If so, please indicate square footage,
location of building, number of employees per shift, if vending machines
will be used, what type of floor, and if suspended acoustical ceilings will be
required.
• Will there be a secured area? Verify the requirements.
• What aircraft should the hangar be able to house/maintain?
• Will there be a wash bay in the hangar?
D-1.3 Structural
253
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Will overhead or in-ground mechanical utilities be required? If so, what
locations?
• Will breathing compressed air be required?
• What will be the heaviest cfm drawn from hoses? (Quantity of outlets?)
• Will door track heating be required?
• Will door track drainage be required?
• What type of utilities will be required around the inside perimeter of the
hangar? Utilities may include compressed air, water, pre-conditioned air.
Provide location and capacity required.
• If there is equipment mounted in the hangar bay what utilities will be
required for the equipment?
• Verify shop requirements.
o What mechanical utilities are required in each shop?
o Are floor drains needed?
o Overhead air reels?
o Machinery utility requirements?
• Any fluid discharges that may harm metal piping that would require an
acid waste system? (X-ray room)
• Will there be any operational requirements for emergency eye
wash/shower units? (Locations?)
• What locations are required for hose reels for water or air? (Overhead,
column mounted or shop areas?)
• What is the expected hangar bay maintenance occupancy?
• Does the maintenance schedule vary with seasons?
• How does the maintenance schedule vary dependent upon peacetime or
military conflict status?
• What maintenance activities will be performed, and for what percentage of
time?
D-1.5 Fire Protection
• What is the history of the site's domestic/fire water supply? Does the water
supply pressure fluctuate throughout the year?
• Is the fire water supply at the site known to have MIC or galvanic
corrosion?
• Will there be rack storage in the facility? If so, what is the product stored?
How high will it be stored, and how will it be stored? Will open rack
shelving be used? Will the product be stored on wood or plastic pallets?
254
UFC 4-211-01
13 April 2017
Change 1, November 2017
• Will the facility have shelved storage exceeding 8 ft. (2.4 m)? If so,
describe the shelving arrangement and products stored.
• Will there be flammable, combustible, or corrosive liquids in the building
which will not be located in a flammable storage cabinet? If so, what is the
liquid, how is it stored, and how much is stored?
• Will tires be stored in the building? If so, how will they be stored?
• What is the typical parking arrangement of the aircraft in the hangar bay,
and what fuels will be used by these aircraft?
• Will ejection seat maintenance be done in the building? What is the largest
quantity of ordinance accumulated in the seat maintenance room any one
time?
• Are flares stored in the building? If so, what is the quantity of flares stored,
how will they be stored, and where will they be stored?
• Is the site considered to have reliable power as defined by the
UFC 3-600-01?
• What system is used by the fire alarm receiving station?
• Are there site specific mass notification messages required?
• Will live voice messaging be required in the building from the receiving
station?
• Will the activation of pre-recorded mass notification messages by the
receiving station be required in the building?
• Will a supervised Knox box be required on the building? If so, how many?
D-1.6 Electrical
255
UFC 4-211-01
13 April 2017
Change 1, November 2017
• If there is equipment mounted in the hangar bay what power will be
required for the equipment?
• What loads should be served with emergency power?
• Will emergency power be provided via a permanent generator or a
portable generator?
• Will additional mission functions be incorporated into the hangar that
requires a generator connection?
• Verify shop requirements.
o What electrical utilities are required in each shop?
o Overhead electric reels?
o Machinery electrical utility requirements?
o Will grounding be required in any shops?
o Will static dissipative floors be required in any shops?
• Will the project site require a high level of corrosion protection? Is the site
on the coast where it is susceptible to salt water corrosion?
• Will there be pedestals in the hangar bay?
• Define the limits of the electrical hazardous (classified) locations including
the hangar bay, adjacent spaces and shops with hazardous locations.
D-1.7 Communications
256
UFC 4-211-01
13 April 2017
Change 1, November 2017
D-1.8 Security
257
UFC 4-211-01
13 April 2017
Change 1, November 2017
258
UFC 4-211-01
13 April 2017
Change 1, November 2017
APPENDIX E: PHOTOGRAPHS
E-1 PHOTOGRAPHS
Figure E-1: Maintenance Hangar Including Two Hangar Bays and Associated
Shops
259
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-3: Maintenance Hangar with Associated Shops and Office on Both
Sides of the Hangar
Figure E-4: Integrated UAS/RPA Hangar with Maintenance and Mission Spaces
260
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-5: Large Body Aircraft Hangar with Attached Shops and Office Space
and Sliding Doors
Figure E-6: Helicopter Hangar Bay with Sliding Doors, Sliding Door Tracks and
Overhead Cranes
261
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-7: Helicopter Hangar Bay with Converters, Pedestals and Safety Lane
262
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-9: Overhead Bridge Crane with Cabled Controls within Hangar Bay
Figure E-10: Hangar Bay with Bridge Cranes and Fall Arrest
263
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-11: Overhead Bridge Crane within a Shop
264
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-12: Sliding Hangar Door Tracks
265
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-13: Vertical Lift Fabric Door with Mullions and Multiple Sections and Fall
Arrest System
Figure E-14: Vertical Lift Fabric Door Mullion and Mullion Pit
266
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-15: Floor Mounted 400 Hz Converter with Permanently Attached Cables
Figure E-16: Permanent Pedestals with 400 Hz, 120V, Communications and
Compressed Air
267
UFC 4-211-01
13 April 2017
Change 1, November 2017
Figure E-17: Example of Fire Pan, for Acceptance Test of Optical
268