Approximate Methods of Distribution System Analysis (2) : 3 Lecture's Outline
Approximate Methods of Distribution System Analysis (2) : 3 Lecture's Outline
Lecture 3rd
Approximate Methods of
Distribution System Analysis (2)
Course Teacher:
Dr. Muhammad Mohsin Aman
Course Code:
EE-524
Course Title:
Electrical Power Distribution System Engineering -1
Venue:
Department of Electrical Engineering , NED University Karachi.
1
Distribution of Loads
Distribution of Loads
Two load models can be assumed for voltage drop calculations:
• Uniformly Distributed Loads
• Lumped Load models
10
11
12
In Equation 3.17, Z represents the total impedance from the source to the end of the
line. The voltage drop is the total from the source to the end of the line.
13
14
Figures 3.7 and 3.8 give two different models that can be used to calculate the
total voltage drop from the source to the end of a line with uniformly distributed
loads.
15
When the model of Figure 3.8 is used to compute the total three-phase power loss, the
result is
It is obvious that the two models give different results for power loss. The question is,
which one is correct? The answer is neither one.
16
17
18
Where R = r ⋅ l, the total resistance per phase of the line segment, Equation 3.25 gives
the total three-phase power loss for a discrete number of nodes and line segments.
19
20
21
22
Distribution of Loads
In the previous lecture, we have seen two load models can be assumed for
voltage drop calculations:
• Uniformly Distributed Loads
• Lumped Load models
23
�1 �
Vdrop total � Re � � Z � I T �
�2 �
In Equation, Z represents the total impedance from the source to the end of the line.
The voltage drop is the total from the source to the end of the line.
24
25
• A circuit model for Equation 3.26 is given in Figure 3.9. From a comparison of
Figures 3.7 and 3.8, used for voltage drop calculations, to Figure 3.9, used for power
loss calculations, it is obvious that the same model cannot be used for both voltage
drop and power loss calculations.
26
27
�In Figure 3.10 the total voltage drop down the line is given by:
28
�where
• Z = total line impedance in ohms
• k = factor of the total line length where the first part of the load current is
modeled
• c = factor of the total current to place at the end of the line such that
IT = Ix +c⋅IT
29
�Equation 3.29 shows that the terms inside the brackets on both sides of the
equal sign need to be set equal, that is
30
�The same procedure can be followed for the power loss model. The total
three-phase power loss in Figure 3.10 is given by:
�The model for the power loss of Figure 3.9 gives the total three-phase
power loss as:
31
32
33
34
35
36
37
Rectangle
�A rectangular area of length l and width w is to be served by a primary
main feeder. The feeder area is assumed to have a constant load density with
three phase laterals uniformly tapped off of the primary main.
�Figure 3.12 is a model for the rectangular area.
38
Rectangle
�Figure 3.12 represents a rectangular area of constant load density being
served by a three-phase main running from node n to node m.
�It is desired to determine the total voltage drop and the total three-phase
power loss down the primary main from node n to node m.
39
Rectangle
�The total current entering the area is given by:
Rectangle
�The total voltage drop down the primary main feeder is
where Z = z ⋅ l
�Equation 3.43 gives the same result as that of Equation 3.17, which was
derived for loads uniformly distributed along a feeder.
�The only difference is the manner in which the total current (IT) is
determined.
41
Rectangle
�The bottom line is that the total load of a rectangular area can be modeled at
the centroid of the rectangle as shown in Figure 3.13.
�It must be understood that in Figure 3.13, with the load modeled at the
centroid, the voltage drop computed to the load point will represent the total
voltage drop from node n to node m.
42
Rectangle
�A similar derivation can be done in order to determine the total three phase
power loss down the feeder main. The power loss in the incremental length is
where R = r ⋅ l
43
Rectangle
�Equation 3.44 gives the same result as that of Equation 3.26. The only
difference, again, is the manner in which the total current IT is determined.
�The model for computing the total three-phase power loss of the primary
main feeder is shown in Figure 3.14. Once again, it must be understood that
the power loss computed using the model of Figure 3.14 represents the total
power loss from node n to node m.
44
Problem
Lumping Loads in Rectangle Configurations
45
Problem
�It is proposed to serve a rectangular area of length 10,000 ft. and width of
6000 ft. The load density of the area is 2500 kVA/mile2 with a power factor of
0.9 lagging.
�The primary main feeder uses 336,400 26/7 ACSR on a pole configured as
shown in Figure 3.3. The impedance of the line was computed to be
46
Problem
�The question at hand is what minimum standard nominal voltage level can
be used to serve this area without exceeding a voltage drop of 3% down the
primary main? The choices of nominal voltages are 4.16 kV and 12.47 kV.
Compute, also, the total three-phase power loss.
�The area to be served is shown in Figure 3.15.
47
Solution
�sa
48
Solution
�sa
49
Solution
�It is clear that the nominal voltage of 4.16 kV will not meet the criteria of a
voltage drop less than 3.0%. For a nominal voltage of 12.47 kV, the total area
current is
50
Solution
�The nominal voltage of 12.47 kV is more than adequate to serve this load. It
would be possible at this point to determine how much larger the area could be
and still satisfy the 3.0% voltage drop constraint.
51
Solution
�For the 12.47 kV selection, the total three-phase power loss down the
primary main is
52
53
Triangle
�Figure 3.16 represents a triangular area of constant load density being
served by a three-phase main running from node n to node m.
�It is desired to determine the total voltage drop and the total three-phase
power loss down the primary main from node n to node m.
54
Triangle
�The area of the triangle is
55
Triangle
�asasd
56
Triangle
�asasd
57
Triangle
�Equation 3.53 shows that the total voltage drop from the vertex to the base
of the triangular area can be computed by modeling the total triangle load two-
thirds of the distance between the vertex and the base of the triangle.
�The model for the voltage drop calculation is shown in Figure 3.17.
58
Triangle
�A similar derivation can be made for the power loss model. The power loss
in the incremental line segment is
59
Triangle
�The total three-phase power loss from node n to node m becomes:
�Equation 3.55 gives the total three-phase power loss down the primary main
from node n to node m.
60
Triangle
�The model for the power loss is given in Figure 3.18.
61
Problem
Lumping Loads in Triangle Configurations
62
Problem
�The triangular area shown in Figure 3.19 is to be served by a feeder of
nominal voltage 12.47 kV. The load density of the area is 3500
kVA/mile2 at a power factor of 0.9 lagging. The conductor on the
primary main is 336,400 26/7 ACSR, and the configuration of the pole is
that of Figure 3.3.
�The impedance of the line is
z=0.306+j0.6272 ohm/mile and the Kdrop
factor is 0.00035291% drop/kVA-mile
�Krise factor for the given conductor
is 0.00040331% rise/kvar-mile.
63
Problem
�Use the Kdrop factor from the line of Example 3.2 and determine the percent
voltage drop from node n to node m.
64
Solution
�sads
65
Solution
�sads
66
Solution
�Suppose now that a shunt capacitor bank is to be installed somewhere
along the primary main in order to limit the percent voltage drop to node
m to 3.0%. Two decisions must be made:
1. Three-phase rating of the capacitor bank
2. Location of the capacitor bank
�The total reactive power of the area was computed to be 2462.6 kvar.
That means that a capacitor bank rated up to 2462.6 can be used without
causing the feeder to go into a leading power factor condition. Since this
is assumed to be the peak load, a capacitor bank rated at 1800 kvar (three-
phase) will be used in order to prevent a leading power factor condition
for a smaller load. Depending upon the load curve during the day, this
bank may or may not have to be switched. 67
Solution
�dsad
68
Solution
�The total three-phase power loss down the primary main before the
shunt capacitor is added is computed by lumping the total triangular load
at:
69