Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Spec 00492

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Technical Information: Arc Flash

Arc Flash Protection


Spec-00492
B
PH (763)
FX (763)
Arc 422-2211
Flash422-2600
Protection Technical
Arc Information
Flash

What is Arc Flash?


An arc flash explosion is a very dangerous and often costly electrical system malfunction that occurs as a short circuit between electrified
conductors. When the isolation between the conductors is breached or can’t contain the applied voltage, the air immediately surrounding
the short can ionize, creating an intense energy flash of 5,000 F or more.
Often, an arc flash event is triggered by operator movement or contact with the energized equipment. This is a particular threat when faults
occur within an enclosure. A phase-to-ground or phase-to-phase fault that results in an explosion can cause fatal injuries and severe burns
and produce considerable property damage.

Standards Organizations and Arc Flash


Protection
To protect operators, OSHA and NFPA 70E standards require a “flash
protection boundary.” OSHA has adopted the National Fire Protection
Association’s “70E Standards for Electric Safety in the Workplace” as
an acceptable means of compliance to meet this requirement.
The Occupational Safety and Health Administration (OSHA) maintains
that electrical work should only take place on de-energized
equipment. Access to potentially energized equipment capable of
generating an arc flash must be limited to qualified personnel with
extensive protective clothing and equipment, including fire-resistant
suits and hoods along with non-conductive wands.
The National Electric Code requires that electrical control panels
that might generate arc flash carry a permanent label applied by the
panel builder.
Incident Energy
Incident energy, defined by NFPA as “the amount of energy
impressed on a surface, a certain distance from a source, generated
during an electrical arc event,” is a key term in understanding arc-
flash hazards. Incident energy is a measure of the heat created by the
electrical arc and is expressed in calories per centimeter-squared.
The two most important numbers to remember are 1.2 and 40.
Incident energy levels greater than 1.2 calories per centimeter-
squared can produce second-degree burns. The NFPA 70E requires
that workers wear personal protective equipment (PPE) when
working with 50 volts or more. Arc flash levels above 40 calories
per centimeter-squared can be fatal, usually resulting in a massive
pressurized blast with sound pressure waves and projectiles. The PPE
is available for exposures up to 100 calories per centimeter-squared;
however, the force from the pressurized blast can be fatal regardless
of the PPE.
Refer to the NFPA website, , for complete information.

How Does NFPA 70E Relate to My Enclosure?


NFPA 70E requires protective equipment and clothing if an operator intends to open an electrical enclosure containing voltage greater than
50 VAC. NFPA 70E does not consider arc flash hazard to personnel once the enclosure is closed. Hoffman offers enclosures and accessories
that comply with the equipment requirements of NFPA 70.
Please note, there are no tests specified in the NFPA 70E standard that rate an enclosure’s resistance to arc flash energy. There is also nothing
that can be done to the enclosure, other than keeping it closed, that would be a suitable alternative to the requirement in the NFPA 70E that
states that personnel must wear protective clothing when opening an enclosure that may contain live power.

Subject to change without notice PH (763) 422-2211 • FX (763) 422-2600 • hoffmanonline.com © 2009 Hoffman Enclosures Inc. 1
Spec-00492 B
Technical Information: Arc Flash
Arc Flash Protection
Preventing Arc Flash Explosions
Protective Clothing
Anyone working on equipment that might generate an arc flash is
required to wear protective clothing, including fire-retardant suits,
gloves, face shield/goggles and other gear as stated in the Standards.
Equipment that Limits Exposure
Although no single piece of equipment can completely eliminate
arc flash hazards, making it convenient to perform most routine
maintenance tasks without directly accessing the equipment can
significantly reduce the risk.
Providing external plug-ins to equipment inside an enclosure is one
approach. Properly designed and insulated panels that are wired
to the appropriate equipment inside allows operators to change
settings and monitor performance without opening the enclosure.
INTERSAFE® Data Interface Ports by Hoffman are mounted on an
enclosure to allow access to the programming devices inside the
enclosure without opening the enclosure door.
Another approach to minimize exposure is to keep manuals and
various worksheets outside the enclosure, but still conveniently close
to the equipment. A data pocket that mounts on the outside of the
enclosure protects manuals and records when closed but is easily
accessed when necessary.
Finally, a power isolation enclosure, a smaller enclosure, interlocked
to the main enclosure can be installed to isolate, or sequester, the
fused disconnect switch or circuit breaker from the main control
panel.
With a traditional disconnect switch inside the main enclosure, live
power is still present on the line side of the disconnect switch. Since
live power is still being fed upstream to the disconnect switch on the
panel, the threat of an arc flash incident remains.
Warning Label An external disconnect enclosure attaches to the side of the main
The label is the first step. However, arc flash levels may change as control enclosure and houses only the disconnect switch or circuit
routine maintenance and repair are performed. breaker, physically removing it from the main enclosure. Power
The arc flash hazard level of any piece of equipment depends on passes from the disconnect enclosure to the main enclosure via a
the available fault current and the time it takes to trip the nearest terminal block mounted on the shared enclosure walls. When the
upstream overcurrent protection device. In most cases, a local utility disconnect switch is off, there is no power coming into the main
engineer can determine the fault current levels; however, these fault control enclosure. The live line side of the disconnect switch is
current values may be based on the impedance of the transformer isolated in the SEQUESTRTM Enclosure.
that serves the facility, and additional impedances upstream of the Besides housing the external disconnect, the Hoffman SEQUESTR
transformer can lower the number. If these additional impedances External Disconnect Enclosure System interlocks the doors of the
are not included in the calculations, then the incident energy levels main control cabinet when the disconnect switch is powered on.
may be underestimated. This allows users to comply with the disconnect door interlocking
Short circuit current levels in electric utility systems are continuously requirements of UL 508A, NFPA79, IEC 60204 and HS 1738, the most
changing as both electricians and maintenance workers replace common electrical standards for industrial machinery.
overcurrent devices, fuses and panel boards or upgrades are made to Because the disconnect switch or circuit breaker is now isolated, the
the system. Any of these changes can have an effect on the arc flash SEQUESTR Enclosure enables technicians to work inside the main
energy level, but may not be noted on the warning label. enclosure without the need for PPE (after verifying that power is off
to the load side of the switch).

2 Subject to change without notice PH (763) 422-2211 • FX (763) 422-2600 • hoffmanonline.com © 2009 Hoffman Enclosures Inc.
Spec-00492 B

You might also like