North American Hazardous Location Approval FLEX I/O Spring-clamp Terminal Base Units
The following terminal bases are Hazardous Location approved: 1794-TBN, Cat. No. 1794-TB3S, -TB3SK, -TB32S, -TB3GS, -TB3GSK, -TB3TS, -TB3TSK
-TBNK, -TB2, -TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, 10
1 4
-TB3GSK, -TB3T, -TB3TK, -TB3TS, -TB3TSK, -TB32S, -TB32.
3
The following information applies when operating Informations sur l’utilisation de cet équipement en 11
this equipment in hazardous locations: environnements dangereux :
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent 5
use in Class I Division 2 Groups A, B, C, D, Hazardous qu’à une utilisation en environnements de Classe I Division 2 2
Locations and nonhazardous locations only. Each product is Groupes A, B, C, D dangereux et non dangereux. Chaque produit 6
supplied with markings on the rating nameplate indicating est livré avec des marquages sur sa plaque d’identification qui
the hazardous location temperature code. When combining indiquent le code de température pour les environnements 7
products within a system, the most adverse temperature dangereux. Lorsque plusieurs produits sont combinés dans un
code (lowest “T” number) may be used to help determine the système, le code de température le plus défavorable (code de 8
overall temperature code of the system. Combinations of température le plus faible) peut être utilisé pour déterminer le
equipment in your system are subject to investigation by the code de température global du système. Les combinaisons 9 12 13 12
local Authority Having Jurisdiction at the time of d’équipements dans le système sont sujettes à inspection par les
installation. autorités locales qualifiées au moment de l’installation.
EXPLOSION HAZARD RISQUE D’EXPLOSION
WARNING
• Do not disconnect equipment
AVERTISSEMENT
• Couper le courant ou s’assurer que
FLEX I/O Terminal Base Units
unless power has been removed l’environnement est classé non Cat. No. 1794-TBN, -TBNK
or the area is known to be dangereux avant de débrancher
nonhazardous. l'équipement. 10
• Do not disconnect connections to • Couper le courant ou s'assurer que 4
this equipment unless power has l’environnement est classé non 1
been removed or the area is dangereux avant de débrancher les 3
known to be nonhazardous. connecteurs. Fixer tous les
Secure any external connections connecteurs externes reliés à cet 11
that mate to this equipment by équipement à l'aide de vis, loquets 6
using screws, sliding latches, coulissants, connecteurs filetés ou
threaded connectors, or other autres moyens fournis avec ce 5
means provided with this product. produit.
• Substitution of components may • La substitution de composants peut 2
impair suitability for Class I, rendre cet équipement inadapté à 8
Division 2. une utilisation en environnement de
• If this product contains batteries, Classe I, Division 2.
they must only be changed in an • S’assurer que l’environnement est
area known to be nonhazardous. classé non dangereux avant de 15
changer les piles. 9
European Hazardous Location Approval FLEX I/O Fused Terminal Base Units
The following adapters are European Zone 2 approved: 1794-TBN, -TBNK, -TB2,
-TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, -TB3GSK, -TB3T, Cat. No. 1794-TBNF, -TBNFK
-TB3TK, -TB3TS, -TB3TSK. 10
4 14
1
3
European Zone 2 Certification (The following applies when the product bears the Ex
or EEx Marking) 11
5
This equipment is intended for use in potentially explosive atmospheres as defined by European
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 2
Requirements relating to the design and construction of Category 3 equipment intended for use
in potentially explosive atmospheres, given in Annex II to this Directive. 6
Compliance with the Essential Health and Safety Requirements has been assured by compliance 6
with EN 60079-15 and EN 60079-0. 14 15 9
WARNING Observe the following additional Zone 2 certification requirements. FLEX I/O Knifeswitch Terminal Base Unit
• This equipment is not resistant to sunlight or other sources of UV Cat.Cat.
NoNo.
1794-TBKD
1794-TBKD
radiation.
• This equipment must be installed in an enclosure providing at least IP54 10 4
protection when applied in Zone 2 environments. 1 3
• This equipment shall be used within its specified ratings defined by
Allen-Bradley. 16
• Provision shall be made to prevent the rated voltage from being 11
exceeded by transient disturbances of more than 40% when applied in 5
Zone 2 environments. 2
• Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided 6, 7
with this product. 6, 7
• Do not disconnect equipment unless power has been removed or the 9
area is known to be nonhazardous.
Description
1 Female flexbus connector
FLEX I/O Cage-clamp Terminal Base Units 2 Terminal base unit
Cat. No. 1794-TB2, -TB3, -TB3K, -TB32, -TB3G, -TB3GK, -TB3T, -TB3TK 3 Male flexbus connector
10
1 4 4 Keyswitch - set to the position required for the installed module
3 5 Mounting holes for panel mounting
11 6, 7, Input/output terminal strips for connecting inputs/output wiring, commons, power
1794-TB2 8 connections, customer power supplies, chassis grounds
5
2 9 Locking tab
6 10 Module locking latch
7 11 Cover plug for male flexbus connector
8 1794-TB3, -TB3K, -TB32, 12 Cold-junction compensation terminals (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK only)
9 -TB3G, -TB3GK, -TB3T, -TB3TK 13 Chassis ground terminations (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK, -TB3G, -TB3GS,
-TB3GSK only)
14 Fuses - eight 5x20 mm (1794-TBNF, -TBNFK only)
15 Terminal strip cover (1794-TBN, -TBNK -TBNF, -TBNFK only)
16 Knife switches (1794-TBKD only)
ATTENTION During mounting of all devices, be sure that all debris (such as metal chips or
wire strands) is kept from falling into the module. Debris that falls into the
module could cause damage upon application of power.
1. Remove the cover plug (if used) in the male connector of the unit to which
you are connecting this terminal base unit.
2. Check to make sure the 16 pins in the male connector on the adjacent Gently push the flexbus connector into the side of the side of the adapter to
device are straight and in line so that the mating female connector on this complete the backplane connection.
terminal base unit will mate correctly.
6. Refer to the installation instructions for specific wiring information for the
3. Make certain the female connector (B) is fully retracted.
module you are installing in this terminal base.
4. Position the terminal base unit on the 35 x 7.5 DIN rail (A) (A-B pt no.
7. Repeat the above steps to install the next terminal base.
199-DR1).
ATTENTION Do not force the terminal base into the adjacent base/adapter. Forcing the units
together can bend or break the hook and allow the units to separate and break ATTENTION When using FLEX I/O modules in a high-vibration installation, especially when
communication over the backplane. mounting the DIN rail vertically, use DIN-rail locks (A-B part number
1492-EA35) to prevent accidental separation of the terminal block units.
C A
Inputs/Outputs
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
B
NC
A Inputs/Outputs NC
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
C
Position the terminal base at a slight angle and hook it over the top of the DIN rail. NC +V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
B
-V Commons -V
Common Common
Make sure the hook (C) on the terminal base slides under the edge of the adapter and the 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
flexbus connector is fully retracted. Slide the terminal base over, tight against the adapter. C
Voltage Voltage
5. Rotate the terminal base onto the DIN rail with the top of the rail hooked In +V Terminals 35 to 50 not available on 1794-TB2 Out +V
under the lip on the rear of the terminal base. Use caution to make Voltage
sure that the female flexbus connector does not strike any of -V (Common) = Terminals B-16 and B-33 (1794-TB3 shown)
+V (Voltage In) = Terminals C-34 and C-51
the pins in the mating connector. For daisy-chaining: Supply in - C-34 (+) and B-16 (-)
Supply out - C-51 (+) and B-33 (-)
WiringWiring
Connections for the
Connections 1794-TB3G,
for the -TB3GK,
1794-TB3G, -TB3GS,
1794-TB3GK, -TB3GSK
1794-TB3GS
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
Inputs/Outputs
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
B
Chassis Inputs/Outputs Chassis
Ground Ground
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
C
+V COM NC Chassis Chassis NC +V COM
Ground Ground
24V dc Chassis Grounds for Shields 24V dc
Supply In Supply Out
I/O I/O
Press down on the terminal base to lock it on the DIN rail. If the terminal base does not lock
into place, use a screwdriver or similar device to open the locking tab, press down on the +24V dc = Terminals C-34, C-50 (1794-TB3G shown)
COM = C-35, C-51
base, and release the locking lever to lock the base in place. Chassis Ground = Terminals B-16, B-33, C-38, C-40 through 45, C-47
NC = No connection
For daisy-chaining: Supply in - C-34 (+), C-35 (-)
Supply out - C-50 (+), C-51 (-)
Wiring Connections for the 1794-TBN, 1794-TBNK, 1794-TBNF, 1794-TBNFK For Spring-clamp Terminal Base Units: 1794-TB3S, -TB3TS, -TB3GS, -TB32S,
Even Numbered I/O Terminals 0 to 14 -TB3SK, -TB3TSK, -TB3GSK
COM
″ Insert a 2.54…3.05 mm (0.10…0.12 in.) wide-bladed screwdriver into the slot and lift up.
COM
16 0 2 4 6 8 10 12 14 33
B
Insert wire, and remove screwdriver.For Cage-clamp Terminal Base Units: 1794-TB2,
-TB3, -TB3K, -TB3T,-TB3TK, -TB3G, -TB3GK, -TB32
34 1 3 5 7 9 11 13 15 51
C
+V +V ″ Tighten screws to 0.8 Nm (7 lb-in).
Odd Numbered I/O Terminals 1 to 15 For Knifeswitch Cage-clamp Terminal Base Unit: 1794-TBKD
+V = Terminals C-34, C-51 (1794-TBN shown) ″ Tighten screws to 0.53 Nm (6 lb-in).
COM (-V) = Terminals B-16, B-33 For NEMA Screw-clamp Terminal Base Units: 1794-TBN, -TBNK, -TBNF,
-TBNFK
Wiring Connections for the 1794-TB3T,
Wiring Connections for the- 1794-TB3T,
TB3TK, -TB3TS, -TB3TSK
-TB3TS ″ Tighten screws to 1.02 Nm (9 lb-in).
Inputs/Outputs
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Install or Change a Fuse in the 1794-TBNF or 1794-TBNFK Terminal Base
A
Channel Channel Channel Channel Channel Channel Channel Channel Unit
+ 0 -- + 1 -- + 2 -- + 3 -- + 4 -- + 5 -- + 6 -- + 7 --
This terminal base unit has fuse holders for 5x20 mm fuses on each of the eight
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
even-numbered I/O terminals (0 through 14 - row B). To install or change a fuse:
B
C C N0 C N1 C N2 C N3 C N4 C N5 C N6 C N7 C
1. Press the fuse holder down toward the terminal strip.
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
Press down to open.
C
+V Supply CJC Chassis Ground CJC +V Supply
In Out
+V) = 24V dc Supply In - Terminals C-34, C-35 (1794-TB3T shown)
-V = 24V dc Common Terminal B-16
+V = Supply Out - Terminals C-50, C-51
-V = Terminal B-33
C = -V dc common
16
CH0 RET CH1 RET CH2 RET CH3 RET CH4 RET CH5
17 18 19 20 21 22 23 24 25 26 27
RET CH6 RET CH7 RET
28 29 30 31 32 33
4. Rotate the fuse holder back to vertical until it snaps into the locked
B
position.
-V Inputs/Outputs -V
Common
The 1794-TBNF and 1794-TBNFK terminal base units are shipped with eight 5x20
Common
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 mm, 1.6 A, 250V AC slow-blow fuses, one for each even-numbered terminal (0
C through 14 on row B). These fuses are suitable for use with the 1794-OA8 AC
Voltage Voltage output module. Refer to the specific installation instructions for fusing
In +V Common Out +V
recommendations for your particular module.
+V (Voltage In) = Terminals C-34, C-51
-V (Common) = Terminals B-16, B-33, C-35 through C-50
For daisy-chaining: Supply in - C-34 (+), B-16 (-) Use the Knifeswitch Terminal Base
Supply out - C-51 (+), B-33 (-) The knifeswitch terminal base has 16 individual mechanical-knifeswitch circuit
breakers (two for each channel). Each switch opens or closes one side (input/output
and return) for a channel.
Typical Wiring Guidelines
1. Place a small-bladed screwdriver into the slot of the knifeswitch of the I/O
point circuit that you wish to break.
2. Rotate downward to open the circuit.
Wiring when total current draw through base is greater than 10 A.
Total current draw through any base must not be greater than 10 A.
This opens the path of an individual circuit.
3. To reestablish the circuit, rotate the knifeswitch back into the terminal base
unit until it snaps into place.
Thermocouple
or Analog Module Digital Module Digital Module Digital Module
24V dc
24V dc
24V dc
General
North American T4A (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK,
General temp code -TB3S,-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)
Terminal screw 0.56...0.79 Nm (5...7 lb-in) (1794-TB3TK, -TB3G, -TB3GK, -TB2, -TB32, -TB3, IEC temp code T4 (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S,
torque -TB3K, -TB3T) -TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK)
0.3...0.6 Nm (2.6...5.3 lb-in) (1794-TBKD)
1.4 Nm (12 lb-in) (1794-TBN, -TBNF, -TBNFK, -TBNK) T6 (1794-TB2)
Dimensions, 94 x 94 x 69 mm (HxWxD) (3.7 x 3.7 x 2.7 in.)
Supply voltage FLEXBUS: 5V DC, 640 mA approx. (with module installed in terminal base)
range (max) I/O Terminals: 2A max
V/COM Terminals: 125V DC/AC, 50/60Hz, 10A (1794-TB3SK, -TB3TK,-TB2, -TB3, (1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
-TB3K, -TB3S, -TB3TK, -TB3TS) Grounding Guidelines, publication 1770-4.1.
V/COM Terminals: 31.2V DC/AC, 50/60Hz, 10A (1794-TB3GSK, -TB3G, -TB3GS,
-TB3GK, -TB32, -TB32S
V/COM Terminals: 250V DC/AC, 50/60Hz, 10A (1794-TBN, -TBNF, -TBNFK, Environmental
-TBNK)
Attribute Value
1794-TBKD only
FLEXBUS: 5V DC, 640 mA Operating IEC 60068-2-1 (Test Ad, Operating Cold),
Terminal Block: 120V AC, 50/60Hz, 10A temperature IEC 60068-2-2 (Test Bd, Operating Dry Heat),
Disconnecting Switch: 3A, 20mΩ IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F) (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK,
ATTENTION -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3SK, -TB3TS, -TB3TSK,
A disconnecting switch does not shut off the current. Make or break a circuit TB32, -TB32S, -TBN, -TBNK)
only under no-load conditions.
0…55 °C (32…131 °F) (1794-TBKD)
Isolation voltage Capable of 250V (continuous) maximum, Basic Insulation Type, Field Wiring -20…55 °C (-4…131 °F) (1794-TBNF, -TBNFK, -TB2)
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TBN, -TBNF, Non-operating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
-TBNFK, -TBNK) temperature IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
Capable of 125V (continuous) maximum, Basic Insulation Type, Field Wiring IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Terminals to FLEXBUS, or the lesser of the installed module (1794-TB3SK, Shock):
-TB3TK, -TB3TK, -TB3TSK, -TB2, -TB3, -TB3K, -TB3S, -TB3TS) -40…85 °C (-40…185 °F)
Capable of 50V (continuous) maximum, Basic Insulation Type, Field Wiring -20…85 °C (-4…185 °F) (1794-TBKD)
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TB3G,
-TB3GS, -TB3GK, -TB3GSK, -TB32, -TB32S) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
2500V DC/sec, Field Wiring Terminals to FLEXBUS.
220V DC/sec, Field Wiring Terminals to Functional Ground. (1794-TBKD) Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Voltage rating See Working Voltage and Isolation Voltage Ratings for nominal values Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g (Except for 1794-TBKD)
Enclosure type None (open-style)
rating Non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
shock 50 g (Except for 1794-TBKD)
Ex (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, TB3TK,
-TB3SK, -TB3TSK, -TBN, -TBNK)
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
(1794-TB2)
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T6 X)
EN 60079-0; General Requirements (Zone 2)
TÜV (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK,
-TB3SK, -TB3TSK, -TBNF, -TBNFK)
TÜV Certified for Functional Safety:
Capable of SIL 2
(1) See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and
other certification details.
A 94
(3.7)
23
59 35 (0.9)
35 (2.3) (1.4)
(1.4)
Mounting Dimensions
21 (0.83)
mm 50 94
(2.0) (3.7)
(in.) 80
(3.2)
80
87 (3.2)
(3.4)
28
(1.2)
68 94 94
(2.7) (3.7) (3.7) B
Adapter (1794-ASB shown) Terminal Base (1794-TB3S shown) Terminal Base (1794-TB3 shown) C
87 x 68 x 69 94 x 94 x 69 94 x 94 x 69
(3.4 x 2.7 x 2.7) (3.7 x 3.7 x 2.7) (3.7 x 3.7 x 2.7)
Secure DIN rail approximately every 200 mm (7.87 in.).
Measure here for
Maintain at least 25.4 (1.0) air space around your FLEX I/O system installation. vertical mounting
position with
A = Mounting hole dimensions for optional mounting kit. adapter up.
B = DIN rail.
C = Operating temperature 25.4 (1.0) below each module when mounted in any position Measure here for horizontal position.
must not exceed 55 ˚C (131 ˚F).