CDVR Caterpillar Settings PDF
CDVR Caterpillar Settings PDF
CDVR Caterpillar Settings PDF
PC Version 252-7515-03
--------------------------------------------
--------------------------------------------
--------------------------------------------
--------------------------------------------
--------------------------------------------
--------------------------------------------
Page 1
CDVR PC Software Settings
Generator Overvoltage: 1 (0=Disabled, 1=Enabled)
Generator Overvoltage Fault Type: 0 (0=Alarm, 1=Shutdown)
Generator Overvoltage Trip Value: 135 (%)
Generator Overvoltage Time Delay: 2,0 (Seconds)
Generator Undervoltage: 1 (0=Disabled, 1=Enabled)
Generator Undervoltage Fault Type: 0 (0=Alarm, 1=Shutdown)
Generator Undervoltage Trip Value: 60 (%)
Generator Undervoltage Time Delay: 30,0 (Seconds)
Loss of Sensing Time Delay: 2,0 (Seconds)
Exciter Diode Monitor Trip Value: 2,0 (Amps)
Fault Reset Too Long: 1 (0=Disabled, 1=Enabled)
Fault Reset Too Long Fault Type: 0 (0=Alarm, 1=Shutdown)
Shutdown Override Flag: 0 (0=Disabled, 1=Enabled)
--------------------------------------------
Page 2