Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Regulador CDVR

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76

RENR7941-01 May 2005

Specifications Systems Operation Testing and Adjusting


Caterpillar Digital Voltage Regulator (CDVR)

i01658146

Important Safety Information


Most accidents that involve product operation, maintenance and repair are caused by failure to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially hazardous situations before an accident occurs. A person must be alert to potential hazards. This person should also have the necessary training, skills and tools to perform these functions properly. Improper operation, lubrication, maintenance or repair of this product can be dangerous and could result in injury or death. Do not operate or perform any lubrication, maintenance or repair on this product, until you have read and understood the operation, lubrication, maintenance and repair information. Safety precautions and warnings are provided in this manual and on the product. If these hazard warnings are not heeded, bodily injury or death could occur to you or to other persons. The hazards are identified by the Safety Alert Symbol and followed by a Signal Word such as DANGER, WARNING or CAUTION. The Safety Alert WARNING label is shown below.

The meaning of this safety alert symbol is as follows: Attention! Become Alert! Your Safety is Involved. The message that appears under the warning explains the hazard and can be either written or pictorially presented. Operations that may cause product damage are identified by NOTICE labels on the product and in this publication. Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard. The warnings in this publication and on the product are, therefore, not all inclusive. If a tool, procedure, work method or operating technique that is not specifically recommended by Caterpillar is used, you must satisfy yourself that it is safe for you and for others. You should also ensure that the product will not be damaged or be made unsafe by the operation, lubrication, maintenance or repair procedures that you choose. The information, specifications, and illustrations in this publication are on the basis of information that was available at the time that the publication was written. The specifications, torques, pressures, measurements, adjustments, illustrations, and other items can change at any time. These changes can affect the service that is given to the product. Obtain the complete and most current information before you start any job. Caterpillar dealers have the most current information available.

When replacement parts are required for this product Caterpillar recommends using Caterpillar replacement parts or parts with equivalent specifications including, but not limited to, physical dimensions, type, strength and material. Failure to heed this warning can lead to premature failures, product damage, personal injury or death.

RENR7941-01

3 Table of Contents

Table of Contents
Specifications Section
Electrical ................................................................. 4 Dimensions ............................................................. 8

Systems Operation Section


General Information ................................................ 9 Startup Profile Function ......................................... 11 Loading and Stopping Profile ................................ 12 Voltage Regulation ................................................ 13 Line Loss Compensation ...................................... 13 Reactive Voltage Droop ........................................ 14 Cross Current Compensation ............................... 15 KVAR Regulation .................................................. 15 Power Factor Regulation ...................................... 16 Parameters ........................................................... 17 Remote Communication ....................................... 18

Testing and Adjusting Section


Testing and Adjusting General Information .............................................. 21 Service Tools ........................................................ 21 Startup Procedure ................................................. 22 Parameter Viewing and Configuration (Caterpillar PC Software) ............................................................. 24 Parameter Viewing and Configuration (Caterpillar Electronic Technician) ......................................... 50 Gain Setting - Adjust ............................................. 53 Troubleshooting .................................................... 54 No Voltage - Troubleshoot .................................... 55 Low Voltage - Troubleshoot .................................. 57 High Voltage - Troubleshoot ................................. 58 Unstable Voltage - Troubleshoot ........................... 59 Reverse VAR Condition - Troubleshoot ................ 59 Poor Voltage Regulation - Troubleshoot ............... 60 No Line Loss Compensation - Troubleshoot ......... 61 No Voltage Droop - Troubleshoot ......................... 61 Wiring Diagrams ................................................... 62

Index Section
Index ..................................................................... 76

4 Specifications Section

RENR7941-01

Specifications Section
i02194952

Electrical
SMCS Code: 4467
Table 1

Specifications Regulation Regulator temperature drift Configurable Volts/Hz characteristic Regulator response time Regulator sensing Regulator stability 0.25% from no load to full load. Less than 1% for any 40 C (72 F) change over the ambient operating temperature range. Two slope ranges adjustable from 1 to 10 V/Hz. See the Regulation Characteristic Illustration. Maximum of 10 milliseconds. True RMS 3-phase sensing is standard. Single phase sensing is available. Variable sense range: 90 to 600 volts. The regulator maintains stable output voltage within 0.25% for total harmonic distortion of the generator output voltage waveform up to 30%, and within 0.50% for total harmonic distortion of the generator output voltage waveform up to 40%. These values are based on a typical 6 SCR bridge. Less than 50. Complies with MIL STD 461C Part 9 and VDE 0875 level N. 10% of regulator sensing voltage. Adjustable from 0 to 10%. Diagnostics identify operation outside of programmed limits. Specific fault information is available even after the unit has been powered down. CANBUS only. For total harmonic distortion of the generator output voltage waveform up to 30%, the regulator maintains stable output voltage within 0.25%. For total harmonic distortion of the generator output voltage waveform up to 40%, the regulator maintains stable output voltage within 0.50%. These values are based on a typical 6 SCR bridge. Adjustable from 0 to 10%. Shuts off generator output when excitation current exceeds normal operating currents for 10 seconds or instantaneous shutoff if output current exceeds approximately 28 Amperes. 40 C (40 F) to +70 C (+ 158 F). 40 C (40 F) to +85 C (+ 185 F). 5 watts at idle, 55 watts at rated output. Withstands up to 20 gs in three mutually perpendicular planes . Withstands 4.5 gs at frequencies between 18 and 2000 Hz in three mutually perpendicular planes. 5% salt spray for 48 hours at 38 C (100.4 F) at 115% of the nominal operating voltage. 1.47 kg (3.24 lb.). Meets 89/336/EEC Electromagnetic Compatibility Directive. 24 6 volt DC power supply required (0.5 amp).
(continued)

Telephone influence factor (TIF) Fine voltage adjust range Regulator voltage gain (Line loss compensation) Fault detection and identification

Harmonic tolerance

Reactive droop adjustment Overexcitation protection

Ambient operating temperature Storage temperature range Power dissipation Shock Vibration Salt fog Weight Electromagnetic compatibility Power supply

RENR7941-01

5 Specifications Section

(Table 1, contd)

Specifications Conformity UL CSA CE UL Recognized per Standard 508, UL File No. E97035. Certified per Standard CAN/CSA-C22.2 No. 14-95, CSA Dile No. LR 23131. Conforms to the following standards: Radiated Emissions EN50081-2, Radiated Immunity (electric field) EN61000-4-3 (10 V/m), Radiated Immunity (conducted) EN61000-4-6 (10 VRMS), Conducted Emissions EN50081-2 (EN55011, Class A), ESD Immunity EN50082-2 (4 KV contact, 8 KV air), EFT Immunity EN50082-2 (2 KV coupling clamp), Magnetic Immunity EN50082-2 (30ARMS, 50 Hz), Safety EN61010-1.

Illustration 1 Regulation Characteristic

g01040043

6 Specifications Section

RENR7941-01

Table 2

Summary of Operating Parameters Parameter Voltage Regulation Rating Generator Type Specifications 120 to 15000 Volts PM SE AREP Voltage 80 to 264 Volts (3) 100 to 280 Volts (1) Output Rating Frequency 50 to 400 Hz Burden (Continuous) 1150 VA (63 VDC applications) or 1900 VA (125 VDC applications) Maximum Forcing (10 Seconds) Voltage 125 or 250 Volts Current 25 or 20 Amperes

Power Input

Maximum Continuous Voltage 63 or 125 Volts Current 12 or 10 Amperes Voltage 90 to 600 Volts

Sensing

Maximum VA Burden per 1 VA Maximum VA Burden 1 VA Maximum Resistance 39 Ohms

Reactive Droop

Maximum Current 5 Amperes

Exciter Field Resistance

Minimum Resistance 3 Ohms

RENR7941-01

7 Specifications Section

Illustration 2 Per-Unit Block Diagram For Rotating Rectifier Excitation System.

g01108552

Vs Sensing Voltage Vc Compensated Terminal Voltage Vref Reference Voltage Kg Programmed Gain Kp Proportional Gain Ki Integral Gain Kd Derivative Gain Td Derivative Time Vp Input From The Power Source For The Excitation System Vrlmt Forcing Limit Ta Alternator Time Limit Vr Regulated Voltage

Te Exciter Time Constant Ke Exciter Gain Efd Exciter Field

8 Specifications Section

RENR7941-01

i02195086

Dimensions
SMCS Code: 4467

Illustration 3 Dimensions of the Caterpillar Digital Voltage Regulator (A) 276.4 mm (10.88 inch) (B) 190.5 mm (7.50 inch) (C) 139.7 mm (5.50 inch) (D) 162.1 mm (6.38 inch) (E) 72.9 mm (2.87 inch) (F) 71.4 mm (2.81 inch) (G) 15.0 mm (0.59 inch) (H) 4.06 mm (0.16 inch)

g01040044

RENR7941-01

9 Systems Operation Section

Systems Operation Section


i02195084

General Information
SMCS Code: 4467

Illustration 4 (1) P6 Connector (2) LED Indicator (3) P12 Connector (4) P9 Connector (5) J4 Connector

g01118951

The Caterpillar Digital Voltage Regulator (CDVR) is a microprocessor based voltage regulator. The main purpose of a digital voltage regulator is to regulate the output voltage of a generator that is used with an engine generator set. Control power for the Digital Voltage Regulator is supplied from an external 24 DCV source. The power stage of the Digital Voltage Regulator can be supplied from a multi-pole, high frequency, permanent magnet generator (PMG), from the generator output (shunt excitation), or from auxiliary windings that are included on some generators. Connections to the Digital Voltage Regulator are made through three multi-pin, plug type connectors. The communication between the Digital Voltage Regulator and a service tool is accomplished using a CANBUS protocol. The Caterpillar Digital Voltage Regulator has three multiple-pin, plug-type connectors. These connectors are labeled P6, P9, and P12. See illustration 4.

Connector P6 is a six-pin header that mates with a six-pin connector. Connector P9 is a nine-pin header that mates with a nine-pin connector. Connector P12 is a twelve-pin header that mates with a twelve-pin connector. The regulator has a nine-pin D-sub connector that is labeled J4. This connector is used for interface with IBM-compatible personal computers. Note: The Caterpillar Digital Voltage Regulator should be hard-wired to earth ground with at least a 16 AWG copper wire that is attached to the ground terminal P6-6. Note: When the unit is configured in a system with other devices, a separate lead should be used to ground the bus from each device.

10 Systems Operation Section

RENR7941-01

Note: When the digital voltage regulator is installed remotely from the generator, special care should be given during installation to ensure proper engineering procedures are followed to prevent electromagnetic noise from reducing the performance of the regulator or other system components. Note: When mounting the regulator remotely, the sensing wires, PMG wires, and exciter field wires should each be routed in their own separate tray or conduit. The optional customer wiring should be separated from all other signals in a control wiring conduit. The voltage sensing wires should be twisted together. Exciter field wires should also be twisted together.

Connector P9

Connectors
Connector P6

Illustration 6 Pinout for the P9 Connector Table 4

g01013761

P9 Terminal Functions Terminal P9-1 P9-2 P9-3 P9-4 P9-5 P9-6 P9-7
Illustration 5 Pinout for the P6 Connector Table 3
g01013614

Function CANbus - High CANbus - Low CANbus - Drain (Shield) Contact Sense - Lower Contact Sense - Raise Contact Sense - Common Contact Sense - Excitation Disable Contact Sense - Fault Reset Contact Sense - Var/PF Enable

P9-8 P9-9

P6 Terminal Functions Terminal P6-1 P6-2 P6-3 P6-4 P6-5 P6-6 Power Input Power Input Power Input FF+ Chassis Ground Function

RENR7941-01

11 Systems Operation Section

Connector P12

Programmable stability settings Soft start control with an adjustable time setting
in AVR mode characteristic

Dual slope voltage versus frequency (V/Hz) Three-phase or single-phase voltage sensing Single-phase current sensing Field current and field voltage sensing Ten protection functions
i02195062

Startup Profile Function


SMCS Code: 4467
Illustration 7 Pinout for the P12 Connector Table 5
g01013628

The parameters that are related to the startup profile function are listed below.

Generator Rated Voltage


P12 Terminal Functions Function B-phase generator current sensing (CT1) B-phase generator current sensing (CT2) 10 DCV Input (B), Alarm Output Driver (24V, 100mA) Fault Shutdown Driver (24V, 100mA) 10 DCV Input (A), + 18 to 30 V Control Power Input (B-) 18 to 30 V Control Power Input (B+) Driver Supply (50) (24V, 100mA) Generator Voltage Sensing - C (T3), lead 20 for SR4 and SR4B generators)(1) Generator Voltage Sensing - B (T2), lead 24 for SR4 and SR4B generators)(1) Generator Voltage Sensing - A (T1), lead 22 for SR4 and SR4B generators)(1)

Terminal P12-1 P12-2 P12-3 P12-4 P12-5 P12-6 P12-7 P12-8 P12-9 P12-10 P12-11 P12-12
(1)

Knee Frequency Underfrequency Point


The digital voltage regulator will begin to build voltage following the Soft Start settings before the configurable underfrequency point has been reached. After the configurable underfrequency point has been reached, the digital voltage regulator will begin to build voltage following a volts per hertz profile. When the speed reaches the knee frequency point, the loading/stopping profile takes effect. The startup profile function will not be initiated again unless the frequency drops below the underfrequency point. The underfrequency point is defaulted to 25 Hz, with a range of 20 to 40 Hz. This is the same underfrequency setpoint used by the loading/stopping setpoint. The knee frequency point is the point at which the digital voltage regulator will regulate to the voltage specified by the generator output voltage parameter.

Refer to the generator set wiring diagrams.

The Caterpillar Digital Voltage Regulator has the following features:

Three control modes:


1. Automatic voltage regulation (AVR) 2. Power factor (PF) regulation 3. Reactive power (VAR) regulation

12 Systems Operation Section

RENR7941-01

i02195080

Loading and Stopping Profile


SMCS Code: 4467

Illustration 8

g01012488

The parameters that are related to the loading and stopping profile are listed below.

Generator Output Voltage Knee Frequency Decreasing V/Hz Slope 1 Decreasing V/Hz Slope 2 Minimum Voltage Underfrequency Point

Voltage regulators are generally of the volts per hertz type or the constant voltage type. The digital voltage regulator can perform as a constant voltage regulator or a volts per hertz type regulator depending on user configuration. Volts per hertz type regulators are commonly used with reciprocating internal combustion engine driven generator sets because they provide an automatic means for the engine to recover from a large block load. In the digital voltage regulator, the block load recovery performance is configurable so that it may be field optimized for each specific application. When the generator is running and if a large load is applied, the frequency and voltage will drop. The loading/stopping function minimizes the amount of time that it takes the engine and generator to recover and increases the ability to pick up large loads.

RENR7941-01

13 Systems Operation Section

As a large load is applied, the engine speed will begin to drop (frequency decreases). As the frequency decreases below the knee frequency, the voltage reference will decrease on a Volts/Hz slope according to the decreasing slope 1 value. If the frequency decrease continues beyond the knee frequency minus 5 Hz, then the voltage reference will decrease on a Volts/Hz slope according to the decreasing slope 2 value until the minimum voltage level is reached. The digital voltage regulator will try to regulate the generator output voltage at the minimum voltage, unless the underfrequency point is reached where the generator output voltage will decrease to a minimum value. As the engine recovers from the load increase, the voltage will increase in the reverse order as it decreased, unless the frequency dropped below the underfrequency point. If the frequency dropped below the underfrequency point, the startup profile will be used for the recovery. In some applications it is desirable to maintain a constant voltage at the possible sacrifice of a larger frequency dip during load transients. The digital voltage regulator can accommodate these applications if the knee frequency is configured for a lower value than normal. The actual value will depend on the specific application. When used in this application, the load transients must be kept small in order to allow the engine to recover without dropping below the knee frequency. When a large block load is switched on to the system, the engine speed temporarily decreases as the engine produces the additional power requirement by burning more fuel. If the regulator is set to act as a volts per hertz type, it will reduce the output voltage according to the slope of the V/Hz curve. The reduction in voltage reduces the power requirement of the load, thus allowing the engine to recover faster for a given block load. If the regulator is set to act as a constant voltage type, the regulator will not reduce the output voltage for a change in speed (addition of block load). Therefore, it will take the engine a longer time to regain speed and supply the total power requirement of the load. If the regulator is set to act as a constant voltage type, care must be taken to keep block load applications small enough so that the engine can recover in acceptable time.
i02195058

Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain
Once startup has been achieved and the generator output frequency is above the corner frequency, the regulator will normally act to keep the generator output voltage constant. As changes in generator loading cause the voltage to sag or rise, the regulator will automatically adjust generator excitation to maintain the output voltage. If loading causes the generator frequency to drop below the knee frequency, the loading and stopping profile as previously described will be followed. See System Operation, Loading And Stopping Profile. The CDVR can be connected to a Manual Voltage Control. For a wiring diagram of Manual Voltage Control see Testing and Adjusting, Wiring diagrams. A remote voltage adjust toggle switch may be used to fine tune the generator output voltage. When used, the active value of voltage reference may be adjusted 10%. Voltage may be changed in software (at the Settings or the Metering screen in the CDVR PC software, or under the Voltage Regulator Control Parameters screen in the Caterpillar Electronic Technician (ET)). Note: In order to change the new voltage setpoint, the EEPROM button must be pressed in the CDVR PC software, or the Enter key must be pressed in Cat ET after the new setpoint is entered.
i02195081

Line Loss Compensation


SMCS Code: 4467 In some installations where a single generator is used with long feeder lines to the load, it may be advantageous to provide line loss compensation. Line loss compensation is commonly referred to as IR compensation. In this mode, a CT must be provided in order to measure the generator current. The parameters that are related to line loss compensation are listed below.

Voltage Regulation
SMCS Code: 4467 The parameters that are related to voltage regulation are listed below.

Rated Generator Voltage Generator PT Primary Voltage Rating

14 Systems Operation Section

RENR7941-01

Rated Generator Voltage Generator PT Primary Voltage Rating Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain Generator CT Current Primary Rating Generator CT Current Secondary Rating Load Compensation Mode IR Compensation Rated Generator Current
Current flowing through a long conductor causes a voltage drop due to the resistance of the wire. Therefore, the voltage at the load end of the conductor will be lower than the voltage at the generator end due to the voltage drop along the conductor. This condition is commonly referred to as line losses. In order to improve the power quality, the digital voltage regulator can compensate for this phenomenon. As generator load increases, the regulator will cause the output voltage to rise slightly at the generator terminals in order to compensate for line losses. Voltage gain controls the amount of compensation. It should be adjusted to yield a constant voltage at the location of the load. Line loss compensation is mutually exclusive to reactive voltage droop. These two functions work opposite of one another and can not be used at the same time. If a CT is provided but line loss compensation is not desired, the setpoint percent must be set to zero.
i02195067

Rated Generator Voltage Generator PT Primary Voltage Rating Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain Generator CT Current Primary Rating Generator CT Current Secondary Rating Load Compensation Mode Droop Percentage Rated Generator Current
When generators operate in parallel, two primary objectives are for the generators to share both the real power requirements and the reactive power requirements of the system electrical load. The engine governors will control sharing of the real power requirements (kW) and the voltage regulator will control sharing of the reactive power requirements (KVAR) of the total system load. If the output voltage of one generator is slightly higher than the other generators, it will supply lagging reactive current to the other generators connected in the group. This current will circulate between generators, possibly causing ampere overloading. One method of minimizing this effect is to cause an individual generators output voltage to sag, or droop, in proportion to the lagging reactive current flow from it as measured with a current transformer (CT). For proper reactive load sharing, the regulator must know the rated generator output current, the CT current at rated generator current and the desired percentage of output voltage droop when the generator is at rated reactive output current.

Reactive Voltage Droop


SMCS Code: 4467 Parameters that are related to voltage regulation with reactive droop are listed below.

RENR7941-01

15 Systems Operation Section

As reactive lagging generator output current increases, the regulator will cause the output voltage to droop (lower the voltage) proportionally. If the measured reactive output current is leading, the output voltage will rise. In either case, this action will tend to reduce the reactive current for better KVAR sharing with other units. The droop percentage controls how much the generator output voltage will vary for a given amount of reactive current. It is important that the connected CT polarity is correct for the voltage to droop with lagging current flow. Reactive droop compensation is mutually exclusive to line droop compensation. These two functions work opposite of one another and can not be used at the same time.
i02194980

Cross current compensation is often used to minimize circulating current flow between the generators which are connected in parallel. The advantage of this operating mode is that all generators contribute in order to establish the same output voltage to the load. Cross current compensation is only used for paralleling multiple gensets. Cross current compensation is not used when paralleling with a utility. Operation is similar to the reactive voltage droop mode except that the secondary circuits of the current transformers of all generators are interconnected in a series string. Each generator is initially adjusted in order to provide the same output voltage. When all generators share the same current, in magnitude and phase (according to the CT ratio), there will be no significant current output on the secondary of any generator CT. If one of the generators carries more current or the current that the generator carries is lagging or leading relative to the others, a net difference current signal will be created in that CT. If that generator is supplying more reactive (lagging) current than other generators, the phase polarity and the magnitude of the signal returned to the digital voltage regulator will be such to cause a slight decrease in the generated voltage, reducing the amount of reactive current. Less reactive (or more leading) current will cause the generator voltage to rise. The net result is that the generated voltage and the output current of each generator is trimmed toward an operating point where all generators will share the same load current in proportion to the CT ratio, with the little or no circulating current between them. Droop percentage controls the amount of individual generator voltage droop (or rise) for a given amount of CT signal. However, because the CT secondary circuits are all interconnected, the CT signal seen by any individual regulator is not representative of the actual current flowing in that particular generator. Any display or calculations that might use that signal as if it were the actual generator current will provide erroneous results. Reactive voltage droop needs to be selected and an enable contact needs to be closed in order to enable cross current compensation. See Testing and Adjusting, Wiring Diagrams for a wiring diagram of the cross current compensation circuit.
i02195082

Cross Current Compensation


SMCS Code: 4467 Parameters related to voltage regulation with cross current compensation (CCC) are listed below.

Rated Generator Voltage Generator PT Primary Voltage Rating Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain Generator CT Current Primary Rating Generator CT Current Secondary Rating Load Compensation Mode Droop Percentage Rated Generator Current

KVAR Regulation
SMCS Code: 4467 Parameters that are related to KVAR regulation are listed below.

16 Systems Operation Section

RENR7941-01

Rated Generator Voltage Generator PT Primary Voltage Rating Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain Rated Generator Current Generator CT Current Primary Rating Generator CT Current Secondary Rating Operating Mode VAR Setpoint VAR Integral Gain VAR Loop Gain
When the generator is connected in parallel with an infinite bus (utility), the voltage of the generator is controlled by the infinite bus. The voltage of the generator will change as the infinite bus voltage changes. It is not possible to control the system voltage when the generator is connected to an infinite bus. In this instance, it is necessary for the digital voltage regulator to regulate the reactive power output which is supplied by the generator. There are two methods for regulating the reactive power output.

Voltage is regulated by the digital voltage regulator in the KVAR operating mode so that the generator produces a constant value of reactive power (KVARs) regardless of the real power output of the generator. In this case, the power factor (generator) will change when the real power output of the generator changes. A current transformer (CT) is necessary for this mode to work. KVAR mode must be selected in software (at the Metering screen in the CDVR PC software, or under the VAR/PF Mode Selection screen in the Caterpillar Electronic Technician (ET). The contact for the KVAR/PF enable must also be closed. Refer to the following contacts: P9-6 and P9-9. A remote KVAR/PF adjust toggle switch may be used in order to fine-tune the KVAR setpoint. Refer to the following contacts: P9-4, P9-5, and P9-6. This switch may be the same switch used for remote voltage adjustment. When the contact for KVAR/PF is closed, and the KVAR mode is selected, the switch will not affect voltage. Note: The KVAR/PF (Aux breaker) contact does not specify if the CDVR is in KVAR or PF mode specifically. KVAR mode must be selected in software (at the Metering screen in the CDVR PC software, or under the VAR/PF Mode Selection screen in Cat ET. In KVAR mode, the generator will supply a constant amount of reactive power to the system as set by the reference (KVAR) regardless of the real power output (kW) of the generator set. The generator will supply real power (kW) to the system. This is determined by the engine governor and/or the device that is used for sharing the load. Due to the amount of reactive power on the utility, current overloading of the system (due to large reactive current requirements) is possible. In the KVAR mode, the generator can supply a fixed amount of reactive power to the system. For stable operation of the generator in the KVAR regulating mode, the generator must be connected to a utility or a system that is much larger than the generator. When the breaker (tie) is closed to the utility, connect terminal P9-9 and terminal P9-6 in order to enable the KVAR mode. When the terminal P9-9 and terminal P9-6 are disconnected from each other, the regulator will be in a voltage control operating mode with the following or without the following: droop and line loss compensation.
i02195068

KVAR Regulation Power Factor (PF) Regulation


Note: KVAR stands for Kilo-Volt-Ampere-Reactive, which is the unit of measurement for reactive power.

Power Factor Regulation


SMCS Code: 4467 Parameters that are related to PF regulation are listed below.

RENR7941-01

17 Systems Operation Section

Rated Generator Voltage Generator PT Primary Voltage Rating Generator PT Secondary Voltage Rating Voltage Setpoint Generator Frequency Knee Frequency Integral Gain Derivative Gain Proportional Gain Loop Gain Rated Generator Current Generator CT Current Primary Rating Generator CT Current Secondary Rating Operating Mode PF Setpoint PF Integral Gain PF Loop Gain Reactive Droop
When the generator is connected in parallel with an infinite bus (utility), the voltage of the generator is controlled by the infinite bus. The voltage of the generator will change as the infinite bus voltage changes. It is not possible to control the system voltage when the generator is connected to an infinite bus. In this instance, it is necessary for the digital voltage regulator to regulate the reactive power output which is supplied by the generator. There are two methods for regulating the reactive power output.

For stable operation of the generator in the PF regulating mode, the generator must be connected to a utility or system that is much larger than the generator. When the tie breaker is closed to the utility, connect terminals P9-9 and P9-6 in order to enable the PF mode. When the terminals P9-9 and P9-6 are disconnected from each other, the regulator will be in a voltage control operating mode with or without droop or line loss compensation as previously described. PF mode must be selected in software and the KVAR/PF contact must be closed. Refer to the following contacts: P9-6 and P9-9. When the contact is not closed the regulator operates in AVR mode. A remote KVAR/PF adjust toggle switch may be used in order to fine-tune the PF setpoint. Refer to the following contacts: P9-4, P9-5, and P9-6. This switch may be the same switch used for remote voltage adjustment. Raising this setpoint will make the PF more lagging (positive PF). Lowering this set point will make the PF more leading (negative PF). When the contact for KVAR/PF is closed, and the PF mode is selected, the switch will not adjust the voltage setting Note: The KVAR/PF contact does not specify if the CDVR is in KVAR or PF mode specifically. PF mode must be selected in software Note: When operating in parallel operations, make sure that Droop mode is selected in the Settings screen in the PC software. A 0% droop may be selected.
i02195070

Parameters
SMCS Code: 4467

General Information
Parameters are pieces of information which are used within the memory of the digital voltage regulator. Each parameter has a specific range of values. Parameters tell the digital voltage regulator how to operate. Service personnel can configure certain parameters to the requirements of a specific site. Configuration changes the value of a particular parameter. There is an upper and lower limit for the value of each parameter. The limits can not be exceeded. In order to view or configure the values of the parameters see Testing And Adjusting, Parameter Viewing And Configuring Procedure.

KVAR Regulation Power Factor Regulation


Note: KVAR stands for kilo-Volt-Ampere-Reactive, which is the unit of measurement for reactive power. When the digital voltage regulator is in the power factor operating mode, it regulates so that the generator produces a constant power factor, regardless of the real power output of the generator. In this case, the reactive current will change when the real power output of the generator changes. A current transformer (CT) is necessary for this mode to work. PF operating mode must be selected.

18 Systems Operation Section

RENR7941-01

i02195066

Remote Communication
SMCS Code: 4467 The digital voltage regulator has the capability to communicate with a remote personal computer or programmable logic controller. The J4 connector of the digital voltage regulator provides an RS-232 port necessary for communication. The RS-232 port is a 9-pin communication media including a wire for Receive, a wire for Transmit, and a common Signal Ground. The common signal ground is NOT a bonding ground and should not be grounded to the case or frame. It is to be connected to the RS-232 device Signal Ground connection point. Cable length should be limited to 15 m (50 ft) maximum for the RS-232 signal wiring. Caterpillar 1U-9484 cable is recommended.

Illustration 9 Table 6

g01008946

Pin 1 2 3 4 5 6 7 8 9

Function Transmit Data Receive Data Signal Ground -

Name TXD RXD GND -

Direction N/A From Regulator To Regulator N/A N/A N/A N/A N/A N/A

RENR7941-01

19 Systems Operation Section

Illustration 10

g01136853

Note: Battery power (24 VDC) must be available at P12-8 (B+) and P12-7 (B-) in order for the remote communications port to operate. A windows program is available to communicate with the digital voltage regulator. The program is called Caterpillar PC Software (part number 252-5715). Caterpillar PC Software allows the user to perform the following operations.

Viewing and modifying the parameters in a


windowed PC environment regulator to a file

Sending the parameters to the digital voltage Saving the existing digital voltage regulator settings Viewing the metering and fault information
For information on changing and viewing the parameters of the voltage regulator, see Testing and Adjusting, Parameter Viewing and Configuring Procedure.

Illustration 11

g01016734

When RS-232 Port is selected, the Password dialog box appears and prompts you to enter a password. See illustration 11. Note: Each voltage regulator is delivered with cat as the password.

Establishing Communication
Communication between the voltage regulator and the PC software must be established before viewing the metering values, reading settings, or changing settings. PC software screen settings are updated only after communication is opened or the communication settings have been changed. Open the voltage regulator communication port by clicking Communications on the menu bar, hovering the mouse pointer over Open Comm Port and clicking RS-232 Port.

Illustration 12

g01016736

20 Systems Operation Section

RENR7941-01

After the correct password is entered, the Comm Port screen is displayed. See illustration 12. Select Comm 1, Comm 2, Comm 3, or Comm 4 as the active communication port on your PC and click the Initialize button. The PC software initializes communication by obtaining the configuration settings from the voltage regulator.

Illustration 13

g01016737

Note: The Caterpillar PC software may display the Please wait... dialog box that is shown in illustration 13 when initializing communication, obtaining configuration settings, or performing other tasks. It is important to wait until the box disappears before trying to execute communication commands. Issuing commands while the Please wait... dialog box is present may disrupt communication between the PC software and the voltage regulator.

Terminating Communication
Voltage regulator communication is terminated by clicking Communications on the menu bar and clicking Close Comm Port. The user will be prompted to save the settings to the EEPROM. This question is asked even if no changes were made to the voltage regulator settings. When the close command is executed (with a Yes or No to save settings to the EEPROM), communication with the voltage regulator is terminated. If the PC software is exited the (by clicking File on the Menu bar and then Exit) without first closing communication, the option will still be given to save the settings to the EEPROM.

RENR7941-01

21 Testing and Adjusting Section

Testing and Adjusting Section Testing and Adjusting


i02195085

i02195064

Service Tools
SMCS Code: 0785

General Information
SMCS Code: 4467

Illustration 15

g01021519

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death.
Illustration 14
g01021519

Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.

PREVENTATIVE MAINTENANCE
The only preventive maintenance that is required on the voltage regulator is to periodically check that the connections between the voltage regulator and the system are clean and tight. Voltage regulator units are manufactured using state-of-the-art, surface-mount technology. As such, Caterpillar recommends that no repair procedures be attempted by anyone other than Caterpillar dealer technicians.

Illustration 16 6V-7070 Caterpillar Digital Multimeter

g00241203

Caterpillar Digital Multimeters can be used to measure voltage, resistance or current up to 10 amperes. Rectifiers can also be checked by using the diode function. See Special Instruction, SEHS7734, Use Of The 6V-7070 And 6V-7800 Multimeter for the correct operation of the 6V-7070 Digital Multimeter.

22 Testing and Adjusting Section

RENR7941-01

1. Connect the digital voltage regulator. Refer to Testing and Adjusting, Wiring Diagrams for a proper illustration. Take care to follow notes and observe polarities. 2. Apply battery power only to the regulator. 3. Connect serial cable between CDVR and PC. Start CDVR PC Software and establish communication. For more details, refer to Establishing Communications located in the Remote Communication section. 4. Verify that all of the parameters are properly adjusted for the application. The following fields may need to be entered for first configuration. For more details, refer to Settings Definitions located in the Parameter Viewing and Configuration (Caterpillar PC Software) section. a. System Configuration

Illustration 17 8T-0900 AC/DC Clamp-On Ammeter

g00538441

The 8T-0900 Ammeter may be used to measure current up to 1200 amperes. When you are measuring line current on multiple lead units, measure the current in each conductor per phase and add the currents together. See Special Instruction, SEHS8420, Using the 8T900 AC/DC Clamp-On Ammeter 0651 for the correct operation of the 8T-0900 Ammeter.
i02195063

Rated Voltage (V) Rated Current (A) Frequency

Startup Procedure
SMCS Code: 4467

PT Primary (V) PT Secondary (V) - A PT is required if the


generator is rated at more than 600 VAC. If no PT is installed, set the PT Primary and PT Secondary to rated voltage.

CT Primary Power Input Frequency (Hz) - Refer to


Table 7.

Sensing Mode - Three Phase is the typical


Caterpillar setting.

Illustration 18

g01021519

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.

RENR7941-01

23 Testing and Adjusting Section

Table 7

Over Excitation - Configure as required by


50HZ 50HZ 200HZ 60HZ 60HZ 240HZ

Operating Frequency Self Excited Generators Permanent Magnet Generators Low and Medium Voltage 6 Pole Generators High Voltage 2600 Frame Generators High Voltage 2400 and 2800 Frame Generators

the application.

Exciter Diode Monitor - Configure as


required by the application. the application.

Loss of Sensing - Configure as required by


133HZ 200HZ 150HZ 160HZ 240HZ 180Hz

Over Excitation: Type - Threshold is the

b. Setting Adjustments

default setting. If Inverse Time is selected, the time setting must be changed to a suggested value of 2 (based on the time dial settings for the SR4B Generator curve). If this value is not changed, over excitation protection may not exist.

AVR Voltage (V) - Desired voltage for AVR


mode.

5. Press the EEPROM button to save the settings in the CDVR. 6. Start the engine. Make the final adjustments, as required. 7. Press the EEPROM button to save the settings in the CDVR. 8. Record all settings. For more details, refer to Settings File located in the Parameter Viewing and Configuration (Caterpillar PC Software) section. 9. Press Get From Unit to verify that the settings were saved. 10. Disable communications (if desired). For more details, refer to Terminating Communications located in the Remote Communication section.

VAR (percent of rated) - For VAR mode. Power Factor - Must select Droop under
Load Compensation Mode for PF control. for the regulator on startup.

Soft Start Bias (percent) - A starting value Soft Start Time (sec.) - For emergency

applications, this value may need to be set to 2 seconds, or less.

Knee Frequency (Hz) - Select a value that is 0.2 to 2 Hz below rated frequency. Slope 1 (V/Hz) - 2V/Hz suggested. Slope 2 (V/Hz) - Refer to Illustration 19.
c. Control Gain Settings

For applications that require special PID

settings, refer to the Gain Setting - Adjust section.

d. Protections Settings

"Shutdown Override" Button - Leave


disabled.

Generator Overvoltage - Configure as


required by the application. required by the application. application.

Generator Undervoltage - Configure as Reverse VAR - Configure as required by the Fault Reset Too Long - Configure as
required by the application.

24 Testing and Adjusting Section

RENR7941-01

Illustration 19

g01012488

i02204904

Parameter Viewing and Configuration (Caterpillar PC Software)


SMCS Code: 4467-NQ In order to view and configure the parameters of the digital voltage regulator, a PC with the Caterpillar PC software is required. Note: Before performing this procedure, study the list of parameters in order to determine the desired parameter and the corresponding range of values. The value of some parameters are only for viewing by the user and may not be configurable. Note: It will be convenient to have the entire list of parameters available while performing this procedure. See System Operation, Parameters. The Caterpillar PC Software provides the communication link between the voltage regulator and the user. All voltage regulator settings are entered and read through this software. Within this software, voltage regulator settings can be saved in a computer file and used later in order to configure other units with the same settings.

Caterpillar PC Software operates with an IBM compatible personnel computer using a Microsoft Windows 95 or later operating system. The minimum recommended operating requirements are listed below:

IBM compatible PC, 486DX2 or faster (100 MHz or


higher microprocessor is recommended)

CD-ROM drive One available serial port

Installing the Caterpillar PC Software


Caterpillar PC Software contains a setup utility that installs the program on the PC. An uninstall utility is loaded with the program that can be used to remove the application from the PC. Use the following procedure to install the PC software. 1. Insert the CD-ROM into the PCs CD-ROM drive 2. Click the Windows Start button and then select Run. In the Open: field, enter D:/Setup.exe, where D is the designator letter for your PC CD-ROM drive. Then click OK.

RENR7941-01

25 Testing and Adjusting Section

When Caterpillar PC Software is installed, a folder with the name Caterpillar is added to the Windows program menu. This folder is accessed by clicking the Start button and pointing to Programs.

Starting Caterpillar PC Software

Illustration 20

g01033156

The PC software is started by clicking the Windows Start button, pointing to Programs, the Caterpillar folder, and then clicking the voltage regulator icon. At startup, a dialog box with the program title and version number is displayed briefly. After this dialog box is displayed, the System Configuration screen is displayed. See Illustration 20.

Changing Settings
The settings are arranged into the following five groups:

System configuration Setting Adjustments Control Gain Settings Protections Settings Metering/Operation and Alarms

Establishing Communication
Communication between the voltage regulator and the PC must be established before any settings can be viewed or changed. For more information on establishing communications, see Systems Operation, Remote Communication.

26 Testing and Adjusting Section

RENR7941-01

Illustration 21 Systems Configuration screen (1) System Configuration button (2) Setting Adjustment button (3) Control Gain Button (4) Protection Setting button (5) Metering/Operation button (6) Get From Unit button (7) EEPROM button

g01033158

Each setting group has a corresponding button that can be selected to access that group of settings. See Illustration 21. The five setting groups can also be accessed by clicking Screens on the menu bar and then selecting the desired setting group from the list. Once a setting group is accessed, the individuals settings of the group can be viewed and changed. A setting is changed by clicking within the setting field and typing the setting. The minimum, maximum and increments (steps) for a setting are displayed on the status bar when the cursor is placed within that setting field. A changed setting is sent to the voltage regulator when the Enter key on the PC is pressed. A setting in a field with the pull-down menu is sent to the voltage regulator when the setting is selected from the pull-down menu.

Sending and Receiving Settings


When communication is enabled, voltage regulator settings can be sent or received through the PC software.

Sending Settings
Settings changes are sent to the voltage regulator by pressing the Enter key on the PC or by selecting a setting from a pull-down menu. This causes the selected setting displayed on the setting screen to become the voltage regulator setting.

Receiving Settings
Voltage regulator settings are retrieved by clicking the Get From Unit button (6). This causes the current settings of the voltage regulator to be displayed on the settings screen.

RENR7941-01

27 Testing and Adjusting Section

Saving Settings to the Memory of the Voltage Regulator


Settings are saved in nonvolatile memory (EEPROM). In the event of a power loss, these are the settings that will be active at start-up. If the settings are changed and sent to the voltage regulator, but the settings are not sent to the EEPROM, the changed settings will be lost if the operating power to the voltage regulator is lost. When exiting an application or closing communication, the software will prompt the user to save the settings to the EEPROM. This question is asked even if no changes were made to the settings. When communication is enabled, setting changes are saved to the EEPROM by clicking the EEPROM button (7). The opportunity to save the settings to the EEPROM is also given through a dialog box when the application is exited or communication is closed.

Setting Definitions
Each of the five setting groups have a corresponding screen in the PC software. The setting of each screen are categorized by one or more tabs. In the following paragraphs, setting are arranged and defined according to the organization of the PC application screens and tabs.

System Configuration
The System Configuration screen consists of one tab labeled Configuration. Click the Configure button (1) in order to access the System Configuration screen or click Screens on the menu bar and click System Configuration.

28 Testing and Adjusting Section

RENR7941-01

Configuration Tab

Illustration 22

g01033156

Rated Voltage (V) The rated AC generator voltage is entered in this field. Voltages within the range of 90 to 15000 ACV may be entered in 1 ACV increments. Rated Current (A) The maximum rated AC generator current is entered in this setting field. Currents up to 9999 Amperes may be entered in 1 Ampere increments. Rated kVAR This field is a read-only field that displays the rated, calculated reactive power, based on the values that are entered in the Rated Voltage and Rated current fields. Frequency This setting is used to select a nominal system operating frequency of 50 Hz or 60Hz. PT Primary (V) The primary AC voltage rating of the potential transformer (PT) is entered in this field. Voltages within the range of 90 and 15000 ACV may be entered in 1 ACV increments.

PT Secondary (V) The secondary AC voltage rating of the PT is entered in this field. Voltages within the range of 90 and 600 ACV may be entered in 1 ACV increments. Note: A PT is required if the generator is rated at more than 600 VAC. If no PT is installed, set the PT primary and PT secondary to rated voltage. CT Primary The AC current rating of the primary winding of the CT is entered in this field. Currents up to 9999 Amperes may be entered in 1 Ampere increments. CT Secondary This field is a read-only field that displays the rated value of the current that is present at the secondary winding of the CT. This regulator is designed for a 5 Ampere secondary winding only.

RENR7941-01

29 Testing and Adjusting Section

Power Input Frequency (Hz) The frequency value of the operating power applied to the voltage regulator is entered in this field. This would be the frequency of the permanent magnet generator or the frequency of the generator in the case of self-excited generator. Frequencies within the range of 50 to 400 Hz may be entered in 1 Hz increments. Refer to table 8 for the correct frequency values.
Table 8

Operating Frequency Self Excited Generators Permanent Magnet Generators Low and Medium Voltage 6 Pole Generators High Voltage 2600 Frame Generators High Voltage 2400 and 2800 Frame Generators

50HZ 50HZ 200HZ

60HZ 60HZ 240HZ

133HZ 200HZ 150HZ

160HZ 240HZ 180Hz

Sensing Mode This setting is used to configure the voltage regulator for the single-phase or three-phase voltage sensing. PC Software Part Number This is a read-only field that displays the version of the PC software part number. Embedded Software Part Number This is a read-only field that displays the version of the embedded software part number. Hardware Part Number This is a read-only field that displays the version of the Hardware part number. Serial Number This is a read-only field that displays the serial number of the voltage regulator connected to the PC. Communication between the voltage regulator and the PC must be enabled in order to read the firmware version.

Setting Adjustments
The Setting Adjustments screen consists of two tabs labeled Setpoint and Startup. Click the Settings button (2) in order to access the Setting Adjustments screen or click Screens on the menu bar and click Setting Adjustments.

30 Testing and Adjusting Section

RENR7941-01

Setpoint Tab

Illustration 23

g01009341

AVR Voltage (V) This setting field is used to enter the desired generator output terminal voltage. The range of voltages is dependent on the value in the Voltage Adjustment Band (percent of rated) field. Values may be entered in increments of 0.1 ACV. VAR (percent of rated) The VAR setpoint determines the level of generator VARs that are maintained by the voltage regulator when the digital voltage regulator is in the VAR mode. Percentage values within the range of -100 to 100 percent may be entered in increments of 0.1 percent. A setting in the overexcited direction will have a positive value and a setting in the underexcited direction will have a negative value.

Power Factor The Power Factor setpoint determines the level of generator power factor that is maintained by the voltage regulator when the voltage regulator is in the power factor mode. Settings within the range of 0.600 lagging to 0.600 leading may be entered in increments of 0.001. A setting in the lagging direction will have a positive value and a setting in the leading direction will have a negative value. Before setting a leading power factor, consult the reactive capability curve for the generator being used. Load Compensation Mode: Mode Three settings may be selected from the drop-down menu for this operating mode: Off, Droop, or Line Drop (Line Loss). Selecting Off disables all load compensation. Selecting Droop enables the reactive droop compensation feature of the voltage regulator. Selecting Line Drop enables the voltage regulator to compensate for a line drop by increasing the generator output voltage as the generator load increases.

RENR7941-01

31 Testing and Adjusting Section

When operating in parallel operations, make sure Droop mode is selected. Reactive Droop Compensation and Line Drop Compensation are briefly described below: Reactive Droop Compensation - The voltage regulator provides a Reactive Droop Compensation feature for three-phase generators in order to assist in the sharing of reactive load during parallel generator operation. The voltage regulator calculates the reactive portion of the generator load using the sensed generator output voltage and current quantities. The voltage regulator then modifies the voltage regulation setpoint accordingly.

Load Compensation Mode: Setpoint (percent) This setting field is enabled only when Droop or Line Drop is selected as the Load Compensation mode. A percentage of zero to 10.00 percent may be entered in increments of 0.01. Voltage Adjustment Band (percent of rated) This setting is entered as a percentage of the rated generator voltage and is used to limit the range of the AVR setpoint. A percentage value of zero to 15.00 percent may be entered in increments of 0.01. Note: Adjusting the voltage using the DC bias input or the Fine Adjustment buttons in the CDVR PC software will only change the voltage setpoint. It will not change the voltage adjustment band.

A unity power factor generator load results in

almost no change in generator output voltage. results in a reduction of generator output voltage. results in an increase of generator output voltage.

A lagging power factor generator load (inductive)

A leading power factor generator load (capacitive)


Droop is adjustable up to 10 percent with rated B-phase line currents (5 amperes applied through terminals P12-1 and P12-2) and 0.8 power factor. The droop is adjustable via the communication port(s). Reactive Droop Compensation is mutually exclusive to line drop compensation. These two functions work opposite of one another and, therefore, cannot be used at the same time. In addition, the Reactive Droop Compensation feature allows paralleling of three-phase generators when connected for Cross Current Compensation (CCC). This method of connection allows reactive load shared between generators with very little voltage droop. The droop level adjustment acts as the sensitivity adjustment when connected for CCC. Line Drop Compensation - The voltage regulator provides a Line Drop Compensation feature for three-phase generators in order to assist in compensating for voltage drops in the lines between the generator and the load. The voltage regulator calculates the magnitude of generator output current and modifies the voltage setpoint accordingly. An increase in generator output current results in an increase in generator output voltage. Line Drop Compensation is adjustable up to 10 percent with rated B-phase line current (5 amperes applied through terminals P12-1 and P12-2). The Line Drop Compensation is adjustable via the communication port(s). Line Drop Compensation is mutually exclusive to Droop. These two functions work opposite of one another and, therefore, cannot be used at the same time.

32 Testing and Adjusting Section

RENR7941-01

Startup Tab

Illustration 24

g01033638

RENR7941-01

33 Testing and Adjusting Section

Illustration 25

g01012488

Soft Start Bias (percent) The Soft Start Bias setting determines the generator voltage offset during startup. A percentage value of 0.00 to 90.00 may be entered in increments of 0.01 percent. This value is a percentage of generator rated voltage. This value may not be reached if the regulator reaches the minimum frequency setpoint first (as entered in the Under Frequency Mode). After the configurable underfrequency point has been reached, the digital voltage regulator will begin to build voltage following a volts-per-hertz profile. Refer to Illustration 25. Soft Start Time (sec.) The Soft Start Time establishes the length of time for the generator terminal voltage to increase to the prescribed level from the Soft Start Bias %. A value of 0.00 to 120.00 seconds may be entered in increments of 0.01 seconds. This time may be cut short if the regulator reaches the minimum frequency setpoint first (as entered in the Under Frequency Mode). After the configurable underfrequency point has been reached, the digital voltage regulator will begin to build voltage following a volts-per-hertz profile. Refer to Illustration 25.

Knee Frequency (Hz) The Knee Frequency setting defines the value of frequency that causes the voltage regulator to adjust the voltage setpoint so that the generator terminal voltage follows the selected volts per hertz slope. A value of 45.00 to 65.00 hertz may be entered in increments of 0.01 hertz. Knee Frequency should typically be set from 0.2 to 2 Hz less than the Genset operating frequency. The knee frequency should be adjusted closer to the nominal frequency in applications where the Genset engine and governor is slow in recovering frequency during a transient load event. Frequency Deviation from Corner Frequency (Hz) This field is a read-only field. The fixed value is subtracted from the Corner Frequency value in order to determine when the generator underfrequency operation changes from slope 1 to slope 2. Slope 1 (V/Hz) When the generator frequency is between the corner frequency and the corner frequency minus 5 hertz, the voltage setpoint is automatically adjusted so that the generator voltage follows volts per hertz slope 1. Slope 1 is adjusted by this setting field. A setting of zero to 10.00 may be entered in increments of 0.01.

34 Testing and Adjusting Section

RENR7941-01

Slope 2 (V/Hz) When the generator frequency is between the corner frequency minus 5 hertz and the Minimum Frequency setting, the voltage setpoint is automatically adjusted so that the generator voltage follows volts per hertz slope 2. Slope 2 is adjusted by this setting field. A setting of zero to 10.00 may be entered in increments of 0.01. Note: Volts per Hz slope value can be used to improve transient response time. Minimum Voltage (percent of rated) The Minimum Voltage setting defines the voltage level where the voltage regulator transitions from the underfrequency characteristic to a constant voltage characteristic. The Minimum Voltage setting is expressed as a percentage of nominal generator voltage. A value of 50.00 to 100.00 percent may be entered in increments of 0.01. Minimum Frequency (Hz) The Minimum Frequency setting defines the value of the generator frequency where the excitation is removed. A frequency value of 20.00 to 40.00 hertz may be entered in increments of 0.01 hertz.

Control Gain
The Control Gain screen consists of a single tab labeled Control Gain. Click the Gain button (3) in order to access the Control Gain screen or click Screens on the menu bar and click Control Gain.

RENR7941-01

35 Testing and Adjusting Section

Control Gain Tab

Illustration 26

g01009752

Proportional Gain Kp This setting selects the proportional constant stability parameter. The voltage regulator supplies a value that is equivalent to Kp multiplied by the error between the voltage setpoint and the actual generator output voltage. Kp values of 0 to 1,000 may be entered in increments of 0.01. If the transient response has too much overshoot, then Kp may be decreased. If the transient response is too slow, then Kp may be increased. Integral Gain Ki This setting selects the integral constant stability parameter. The voltage regulator supplies a value that is equivalent to Ki multiplied by the integral of the error between the voltage setpoint and the actual generator output voltage. Ki values of 0 to 1,000 may be entered in increments of 0.01.

Increasing the value of Ki decreases the time required to reach steady state. Derivative Gain Kd This setting selects the derivative constant stability parameter. The voltage regulator provides an output value that is equivalent to Kd multiplied by the derivative of the error between the voltage setpoint and the actual generator output voltage. Kd values of 0 to 1,000 may be entered in increments of 0.01. Increasing the value of Kd reduces transient response ringing. Noise Filter Time Constant Td This setting selects the noise filter time constant and is used in order to reduce high-frequency noise. Values of 0.00 to 1.00 may be entered in increments of 0.01.

36 Testing and Adjusting Section

RENR7941-01

Loop Gain Kg This setting adjusts the loop-gain level of the PID algorithm. Loop Gain values of 0 to 1,000 may be entered in increments of 0.01. Loop gain Kg is an overall gain multiplier affecting all gain parameters, and should be used as a first gain adjustment. Increasing Loop Gain may be used to increase transient response and reduce time to steady state. Decreasing loop gain will reduce overshoot but will lengthen time to steady state. VAR Integral Gain Ki This setting adjusts the integral gain and determines the characteristic of the voltage regulator dynamic response to a changed VAR setting. Ki values of 0 to 1,000 may be entered in increments of 0.01. VAR Loop Gain Kg This setting adjusts the loop-gain level of the PI algorithm for VAR control. Values of 0 to 1,000 may be entered in increments of 0.01. PF Integral Gain Ki This setting adjusts the integral gain and determines the characteristic of the voltage regulator dynamic response to a changed power factor setting. Values of 0 to 1,000 may be entered in increments of 0.01. PF Loop Gain Kg This setting adjusts the loop-gain level of the PI algorithm for power factor control. Values of 0 to 1,000 may be entered in increments of 0.01. PID Pre-Settings One of 20 preset stability ranges within the voltage regulator can be selected from this pull-down menu. Selection of one of the 20 preset stability ranges disables the Proportional Gain (Kp), Integral Gain (Ki), and Derivative Gain (Kd) settings of the Control Gain tab. Selecting (Custom PID Settings) from the PID Pre-Settings menu enables the Kp, Ki, and Kd settings. Caterpillar does not recommend using the current PID Pre-Settings in the list except the Custom PID Settings. The default settings from the Custom PID Settings will work well for most SR4 and SR4B generator applications. If an adjustment is to be made, the Loop Gain Kg should be used as a first adjustment approach. PID Button Press the PID button in order to open the PID Calculator screen. See illustration 27. The PID Calculator is used in order to calculate proportional gain (Kp), integral gain (Ki), and derivative gain (Kd) for a PID-type controller. The generator and the exciter time constant values are entered into the PID Calculator in order to calculate these values. AVR overall gain (Kg) and derivative filter time constant Td can be entered and saved in a file. Refer to the PID Calculator section for additional information.

RENR7941-01

37 Testing and Adjusting Section

PID Calculator

Illustration 27

g01009819

The PID parameters are calculated for the desired system response with a settling time of about one-third of the generator time constant and about 10 percent overshoot. Excitation Control Data Gen. Information Up to 20 characters of descriptive text for the generator can be entered in this field. When a PID record is created, this text identifies the record. Gen Time Constant [Tdo]-[Seconds] The open-circuit generator time constant (Tdo) can be selected from this pull-down menu. Time constant values of 1 to 15 seconds can be entered in 0.05 second increments. Note: Values for specific generators can be obtained from the Technical Marketing Information System.

Exciter Time Constant [Te]-[Seconds] The exciter time constant (Te) can be selected from this pull-down menu. The value displayed in this menu depend on the generator time constant (Tdo) that is selected. Available values range from one-fifth to one-half of Tdo in 0.01 second increments. The maximum possible exciter time constant is 3 seconds. Default Exciter Time Constant When this box is checked, manual selection of the exciter time constant is disabled and Te is set at one-sixth the value of the generator time constant (Tdo). This is not recommended for SR4 and SR4B generators. AVR Control Parameters Proportional Gain (Kp) This is a read-only value. The value is calculated from the values that are selected from the generator time constant (Tdo) and exciter time constant (Te) pull-down menus. Integral Gain (Ki) This is a read-only value. The value is calculated from the values that are selected from the generator time constant (Tdo) and exciter time constant (Te) pull-down menus.

38 Testing and Adjusting Section

RENR7941-01

Derivative Gain (Kd) This is a read-only value. The value is calculated from the values selected from the generator time constant (Tdo) and exciter time constant (Te) pull-down menus. Time Constant (Td) The time constant value entered in this field is used to reduce high-frequency noise. The Td value entered is recommended to be less than 0.2 (Kd, Kp). Td values from zero to 1.00 may be entered in 0.01 increments. Entering a value of zero disables the filtering. AVR Overall Gain (Kg) The AVR overall gain is entered in this field. A Kg value of zero to 1000.00 may be entered. Note: If the Update CDVR PC Software button is pressed, a default value of 1.00 is loaded into this field. Make sure to adjust this value as needed. PID Record List This area of the PID Calculator screen lists all of the saved PID records that are available. Remove Record Button Records in the PID Record List can be selected and deleted by clicking this button. Add Record Button A record containing the excitation control data and AVR control parameters can be added to the PID Record List by clicking this button. The Save button must be pressed in order to save the record in the list. Update CAT PC Software Button Transfers the AVR control parameters calculated in the PID calculator and recorded to the Control Gain Screen. Close Button Clicking this button closes the PID Calculator and returns to the Control Gain screen.

RENR7941-01

39 Testing and Adjusting Section

Table 9

Power Input to Voltage Regulator (PM / SE / AREP Systems)

Power Input to Exciter Nominal Requirements Full Forcing Requirements Full Forcing Voltage 65V Full Forcing Current 15A

SE/PM Input to Frequency Range Voltage Regulator Kato 2600 Frame Kato 2800 Frame 6100 6100 6100 1400 /4P 1400 /4P 1400 /4P 1600 /4P 1600 /4P 1600 /4P 1800 /4P 1800 /4P 1800 /4P SR4/ SR4B SR4/ SR4B 70 to 105V 120V 140V 140V 140V 180V

Number of Phases 3

Exciter Nominal Voltage Input 35V

Exciter Exciter Exciter Nominal Time Current Resistance Constant Input Te 10A 3.7 ohms 0.22 sec

PM

240 Hz

PM PM SE AREP PM SE AREP PM SE AREP PM SE AREP PM SE

90 Hz 120 Hz 60 Hz 50/180 Hz 200/240 Hz 50/60 Hz

1 3 1 2x1 3

50V 40V 40V 40V 45V 45V

5A 4A 4A 4A 4.5A 4.5A 4.5A 6A 6A 6A 4A 4A 4A 10A 10A

10 ohms 10 ohms 10 ohms 10 ohms 10 ohms 10 ohms 10 ohms 10 ohms 10 Ohms 10 ohms 21 ohms 21 ohms 21 ohms 3.7 ohms 3.7 ohms

0.18 sec 0.22 sec 0.22 sec 0.22 sec 0.056 sec 0.056 sec 0.056 sec 0.059 sec 0.059 sec 0.059 sec 0.22 sec 0.22 sec 0.22 sec 0.22 sec 0.22 sec

90V 60V 60V 60V 80V

10A 10A 10A 10A 10A

140V 180V

50/180 Hz 200/240 Hz 50/60 Hz

2x1 3

45V 60V 60V

80V 150V

10A 15A

240 V 180V 240V 240V 70 to 105V 240V

50/180 Hz 240 Hz 60 Hz 60 Hz 240 Hz 60 Hz

2x1 3 1 1 3 1

60V 84V 84V 84V 35V 35V

150V 190V 190V 190V 65V 65V

15A 8.5A 8.5A 8.5A 15A 15A

Protection Settings
The Protection Settings screen consists of a single tab labeled Protection. Click the Protection button to access the Protection Settings screen or click Screens on the menu bar and click Protection Settings.

40 Testing and Adjusting Section

RENR7941-01

Protection Tab

Illustration 28

g01009884

SHUTDOWN OVERRIDE Button This button is used to prevent excitation shutdown for any protected function. The button displays ENABLED when selected and the button displays DISABLED when the button is deselected. Enabling this button does not disable output drivers or CANBUS messages. The following protections do not rely on disabling excitation to cause a shutdown and, therefore, are not affected by the Shutdown Override button.

Generator Overvoltage: Enabled Selecting the Enabled checkbox enables generator overvoltage protection. Deselecting the Enabled check box disables generator overvoltage protection and the associated settings.

Generator Overvoltage Generator Undervoltage Loss of Excitation (Reverse Var) Fault Reset too long
Note: The position of this button cannot be saved into the EEPROM. The default value of Disabled is loaded when power is cycled on the CDVR.

RENR7941-01

41 Testing and Adjusting Section

Generator Overvoltage: Fault Type Two options can be selected from this pull-down menu, Alarm or Shutdown. When Alarm is selected and a generator overvoltage condition is detected, the Alarm output driver energizes, a J1939 alarm message is sent via the CAN communication port, and the Fault LED will be lit constantly. For units equipped with an RS-232 communication port, an Alarm fault will be annunciated via the PC software. When Shutdown is selected and a generator overvoltage condition is detected, the Fault Shutdown output driver energizes, a J1939 shutdown message is sent, and the Fault LED will flash. For units equipped with an RS-232 communication port, a Shutdown fault will be annunciated via the PC software. The voltage regulator does NOT disable excitation when a Generator Overvoltage fault is detected. Generator Overvoltage: Trip Value (percent) This setting determines the voltage threshold where an overvoltage trip will occur. Voltage values of 105 to 135 percent of the rated voltage may be entered in increments of 1 percent. Generator Overvoltage: Time Delay (Sec.) This setting assigns the length of time from when an overvoltage condition is detected until the voltage regulator issues an alarm or shuts down excitation. A time value of 2.0 to 30 seconds may be entered in 0.1 second increments. Reverse VAR: Enabled Selecting the Enabled checkbox enables reverse VAR protection. Deselecting the Enabled checkbox disables reverse VAR protection and the associated settings. Note: If Reverse VAR protection is enabled and the CT connections are reversed, a reverse VAR alarm or shutdown will occur. Reverse VAR: Fault Type Two options can be selected from this pull-down menu, Alarm or Shutdown. When Alarm is selected and loss of excitation is detected, the Alarm output driver energizes, a J1939 alarm message is sent via the CAN communication port, and the Fault LED is lit constantly. For units equipped with an RS-232 communication port, an Alarm fault will be annunciated via the PC software. When Shutdown is selected and loss of excitation is detected, the Fault Shutdown output driver energizes, a J1939 shutdown message is sent via the CAN communication port, and the Fault LED flashes. For units equipped with an RS-232 communication port, a Shutdown fault will be annunciated via the PC software. The voltage regulator does NOT disable excitation when a Loss of Excitation (Reverse Var) fault is detected.

Reverse VAR: Trip Value (percent) This setting determines the level of reverse VAR flow, expressed as a percentage of nominal, positive VAR flow, where a loss of excitation trip occurs. A value of 10 to 100 percent may be entered in increments of 1 percent. Reverse VAR: Time Delay (Secs) This setting assigns the length of time from when the reverse VAR trip value is exceeded until the voltage regulator issues an alarm or shuts down. A time value of 0.1 to 9.9 seconds may be entered in 0.1 second increments. Generator Undervoltage: Enabled Selecting the Enabled checkbox enables generator undervoltage protection. Deselecting the Enabled checkbox disables generator undervoltage protection and the associated settings. Generator Undervoltage: Fault Type Two options can be selected from this pull-down menu, Alarm or Shutdown. When Alarm is selected and generator undervoltage is detected, the Alarm output driver energizes, a J1939 alarm message is sent via the CAN communication port, and the Fault LED is on constantly. For units equipped with an RS-232 communication port, an Alarm fault will be annunciated via the PC software. When Shutdown is selected and generator undervoltage is detected, the Shutdown output driver energizes, a J1939 shutdown message is sent via the CAN communication port, and the Fault LED flashes. For units equipped with an RS-232 communication port, a Shutdown fault will be annunciated via the PC software. The voltage regulator does NOT disable excitation when a Generator Undervoltage fault is detected. Generator Undervoltage: Trip Value (percent) This setting determines the level of voltage, expressed as a percentage of nominal generator voltage, where a generator undervoltage trip occurs. A value of 60 to 95 percent may be entered in 1 percent increments. Generator Undervoltage: Time Delay (Secs) This setting assigns the length of time from when a generator undervoltage condition is detected until the voltage regulator issues an alarm or shuts down excitation. A time value of 10.0 to 120.0 seconds may be entered in 0.1 second increments. Over Excitation: Type Two options can be selected from this pull-down menu, Inv Time (for inverse curves) or Threshold (for a fixed time delay). The voltage regulator disables excitation when an overexcitation fault is detected unless a global Shutdown Override command is in effect.

42 Testing and Adjusting Section

RENR7941-01

Note: Selecting Inv Time requires changing the time setting to a suggested value of 2 (based on the time dial settings for the SR4B Generators curve). If this value is changed, over excitation protection may not exist. Over Excitation: Trip Value (Amps) This setting determines the level of field current that will cause an overexcitation trip. Values of 0 to 12.0 amperes may be entered in 0.1 ampere increments. When in Threshold mode, the suggested value for the SR4 and SR4B generators is 12 amperes. When in Inv Time mode, the value entered should be determined by the full load excitation level of the generator and application. This entered value becomes a per unit value. For example, if a value of 12 is entered and a time setting of 2 is chosen, then 2.0 on the Field Current axis of the Inverse Time curve corresponds to 24A. This will give the CDVR approximately 17 seconds before shutdown (provided the same level of current exists). If a trip value lower than the full load excitation level is entered, the CDVR will allow less time before shutdown for a given current level. Over Excitation: Time Setting This setting assigns the length of time from when an overexcitation condition is detected and when the voltage regulator issues an alarm or shuts down the excitation. A time value of 1.0 to 10.0 seconds may be entered in 0.1 second increments. The required value for the SR4 and SR4B generators is 10 seconds. If Inv Time is selected, this value becomes the time dial setting for the generator. See Illustration 29.

Illustration 29 Inverse Time Characteristic for Overexcitation limiter

g01119160

RENR7941-01

43 Testing and Adjusting Section

Exciter Diode Monitor (EDM): Trip Value (Amps) This setting determines the level of current that is indicative of a failed exciter diode. The RMS ripple current of the field is measured. If the current level exceeds the diode fault threshold setpoint for five seconds, a diode fault is detected. The voltage regulator disables excitation when a diode fault is detected unless a global Shutdown Override command is in effect. A value of 1.0 to 10.0 amperes may be entered in 0.1 ampere increments. If the regulator shuts down on instantaneous Field Overcurrent of 28A or more, the EDM alarm LED will not illuminate in the Metering screen. Loss of Sensing (LOS): Time Delay (Secs) The value of this setting determines the time delay between when a loss of sensing voltage is recognized and the voltage regulator responds by removing the field excitation. A time value of zero to 25.0 seconds may be entered in 0.1 second increments. The voltage regulator disables excitation when a Loss of Generator Sensing fault is detected unless a global Shutdown Override command is in effect. Fault Reset Too Long: Enabled Selecting the Enabled checkbox enables the voltage regulator to issue an alarm or a shut down fault if the fault reset input is closed longer than 10 seconds. Fault Reset Too Long: Fault Type Two options can be selected from this pull-down menu, Alarm or Shutdown. When Alarm is selected and the Fault Reset contact input remains closed for more than 10 seconds, the Alarm output driver energizes, a J1939 alarm message is sent via the CAN communication port, and the Fault LED lights constantly. For units equipped with an RS-232 communication port, an Alarm fault will be annunciated via the PC software. When Shutdown is selected and the Fault Reset contact input remains closed for more than 10 seconds, the Fault Shutdown output driver energizes, a J1939 alarm message is sent via the CAN communication port, and the Fault LED will flash. For units equipped with an RS-232 communication port, the voltage regulator will attempt to annunciate the Shutdown fault via the PC software. The voltage regulator does NOT disable excitation when a Fault Reset Closed Too Long condition is detected.

Metering, Operation, and Alarms


The Metering, Operation, and Alarms screen consists of a single tab labeled Metering. Click the Metering button to access the Metering, Operation, and Alarms screen or click Screens on the menu bar and click Metering/Operation.

44 Testing and Adjusting Section

RENR7941-01

Metering Tab

Illustration 30

g01010266

GEN VOLTAGE (V): Vab This field is a read-only field that displays the phase-to-phase voltage of phase A and phase B. GEN VOLTAGE (V): Vbc This field is a read-only field that displays the phase-to-phase voltage of phase B and phase C. GEN VOLTAGE (V): Vca This field is a read-only field that displays the phase-to-phase voltage of phase C and phase A. GEN VOLTAGE (V): Vavg This field is a read-only field that displays the average value of the three phase-to-phase voltages.

GEN CURRENT (A): Ib This field is a read-only field that displays the value of the current on the B-phase of the generator. GEN FREQ (Hz): Freq This field is a read-only field that displays the value of the frequency of the generator voltage. GEN POWER: kWatts This field is a read-only field that displays the value of real power that is being output from the generator. GEN POWER: kVA This field is a read-only field that displays the value of apparent power that is being output by the generator.

RENR7941-01

45 Testing and Adjusting Section

GEN POWER: kVAR This field is a read-only field that displays the value of reactive power that is being output by the generator. GEN POWER: PF This field is a read-only field that displays the value of the power factor that the generator is operating at. AUX DC INPUT (V): Vaux This field is a read-only field that displays the level of dc control voltage that is applied from a remote device to the voltage regulator terminals P12-3 (B) and P12-6 (A). Note: These terminals can be used as an alternate method of adjusting voltage in AVR mode or adjusting PF or VAR in PF or VAR mode, respectively (when used with an existing remote VAR/PF controller). This input acts as a DC bias. When the CDVR is in AVR mode, a 1 VDC change on the terminals corresponds to a 1 percent change in the voltage setpoint. A 1V DC change gives a 10 percent VAR change (in VAR mode) and a 0.04 PF change (in PF mode). If the DC voltage is removed from the 10 VDC Control input, the operating setpoint will return to the original value regardless of pressing the EEPROM button. Note: Adding a DC voltage when the operating setpoint is near the voltage adjust band limit may allow the regulator to operate outside of the voltage adjust band. EXCITER FIELD: Vfd (V) This field is a read-only field that displays the value of the exciter field voltage. EXCITER FIELD: Ifd (A) This field is a read-only field that displays the value of the exciter field current. OPERATING MODE One of three operating modes may be selected as active: AVR, VAR, or PF. When an operating mode is active, the corresponding indicator color changes from black to red for AVRmode. When an operating mode is active, the corresponding indicator color changes from black to green for the VAR mode and the PF mode. Note: When either KVAR or PF mode are selected, the appropriate button must be selected and the Auxiliary breaker contact that is connected to P9-6 (KVAR/PF enable contact) and P9-9 (contact sense common) must be closed. Note: Droop should be enabled whenever the CDVR is operated in PF or VAR Mode. The newest version of the CDVR PC firmware will not allow the operator to select PF or VAR Mode unless Droop is selected in the Settings menu first. The Droop setting can be set to 0 percent.

FINE ADJUSTMENT The Raise and Lower buttons control the fine adjustment of the operating setpoint. These buttons perform the same function as closing the appropriate set of contacts connected to the Contact Sense Raise input (terminal P9-5) and Contact Sense - Lower input (terminal P9-4) of the voltage regulator. Each click of the Raise button increases the voltage setpoint by 0.1 V, each click of the Lower button decreases the voltage setpoint by 0.1 V. Note: The PT ratio will affect this setting. Note: An alternate method of adjusting voltage is to adjust the DC voltage between terminals P12-3 and P12-6. SETPOINT: AVR (V) This setting field is used to enter the desired generator terminal voltage. The background color of this field is green when the voltage regulator is in AVR mode. Note: The PT ratio will affect this setting. SETPOINT: VAR (percent of nom.) This setting determines the level of generator VARs maintained by the voltage regulator when operating in VAR mode. The background color of this field is green when the voltage regulator is regulating the VAR setpoint. A percentage value of zero to 100.0 may be entered in 0.1 percent increments. SETPOINT: Power Factor This setting determines the level of power factor regulation maintained by the voltage regulator. The background color of this field is green when the voltage regulator is regulating the power factor setpoint. A power factor value of 0.600 to 0.600 may be entered in 0.001 increments. STATUS Four indicators indicate the operating status of the voltage regulator: Droop, Line Drop, Under Frequency, and Soft Start. The Droop indicator turns red when the Reactive Droop Compensation feature is selected. The Reactive Droop Compensation feature is used during parallel generator operation to assist in the sharing of reactive load. The Line Drop indicator turns red when the Line Drop Compensation feature is selected The Line Drop Compensation feature is used to compensate for voltage drops in the lines between the generator and the load. The Under Frequency indicator turns red when the generator frequency decreases below the Knee Frequency setting and excitation is terminated. The Soft Start indicator turns red when the Soft Start feature is active to control the time for generator voltage to ramp up during startup.

46 Testing and Adjusting Section

RENR7941-01

CONTACT INPUTS Five indicators provide the status of the voltage regulator switch inputs: Raise, Lower, VAR / PF, Excitation Disable, and Fault Reset. The Raise indicator turns red when contact closure at terminals P9-5 (Contact Sense - Raise) and P9-6 (Contact Sense - Common) is detected. The Lower indicator turns red when contact closure at terminals P9-4 (Contact Sense - Lower) and P9-6 (Contact Sense - Common) is detected. The Var/PF indicator turns red when contact closure at terminals P9-9 (Contact Sense - Var/PF Enable) and P9-6 (Contact Sense - Common) is detected. The Excitation Disable indicator turns red when contact closure at terminals P9-7 (Contact Sense Excitation Disable) and P9-6 (Contact Sense Common) is detected. The Fault Reset indicator turns red when contact closure at terminals P9-8 (Contact Sense - Fault Reset) and P9-6 (Contact Sense - Common) is detected. ALARMS Ten indicators annunciate alarm conditions. Alarm indicators include the following alarms: Internal Memory Failure, Internal Watchdog Failure, Exciter Diode Monitor, Excitation Loss, Generator Overvoltage, Generator Undervoltage, Overexcitation, Loss of Sensing, Field Overcurrent, and Fault Reset Too Long. When the voltage regulator detects an alarm condition, the appropriate indicator changes from black to red. ALARMS: Shutdown Override Status This indication provides the status (position) of the Shutdown Override Button. The button displays ENABLED when selected and DISABLED when deselected.

Settings Files
Caterpillar PC software enables you to print a list of voltage regulator settings, save voltage regulator settings in a file, and open a settings file in order to upload those settings to a voltage regulator. A settings file may also be opened and edited with any text editing software.

RENR7941-01

47 Testing and Adjusting Section

Printing the Settings Files

Illustration 31 Print Icon

g01040303

Illustration 32

g01016740

48 Testing and Adjusting Section

RENR7941-01

Illustration 33

g01016741

A printout of voltage regulator settings can be useful for record keeping or comparison purposes. The voltage regulator settings can be printed by clicking the print icon (1) or clicking File on the menu bar and then clicking Print. When the print command is given, a dialog box provides the opportunity to add a title and comments to the settings list. See illustration 32. Each entry is limited to a maximum of 54 characters. After this information is entered, click on OK. The Print Settings box will appear. See illustration 33. This dialog box is used in order to select the desired printer, change and verify the printer settings, and preview the printed settings list. Click on the Print button in order to print the settings list.

RENR7941-01

49 Testing and Adjusting Section

Saving the Settings Files

Illustration 34 Save Icon

g01040305

Saving the voltage regulator settings in a file for uploading to other voltage regulator units saves setup time when configuring multiple units with the same settings. A settings file can also be created in the PC software without being connected to a voltage regulator. The settings of the desired screens can be changed and these settings can then be saved to a file. Once a settings file is created, the file can be edited using any text editing software, and the file can then be saved for uploading. A settings file is created by clicking the save icon (1) or by clicking File on the menu bar and then clicking Save. When the command is given, a Save As dialog box is displayed where the settings are assigned a file name and then saved. All voltage regulator settings files are automatically given a .dv2 extension.

Uploading the Settings Files to the Voltage Regulator


A voltage regulator settings file downloaded from a voltage regulator or created within the PC software can be uploaded to multiple voltage regulator units. Only a voltage regulator settings file with a .dv2 extension can be uploaded to a voltage regulator unit. Before uploading a file, communication must be initiated with the voltage regulator that is to receive the settings. See Systems Operation, Remote Communication. The upload process is started by clicking the open icon or clicking File on the menu bar and then clicking Open. An Open dialog box is then displayed where the desired settings file is navigated to and selected. Clicking Open uploads the settings file. The default settings for the CDVR are stored in a file called Defaults.DV2 in the CDVR PC Software folder on the PC.

50 Testing and Adjusting Section

RENR7941-01

i02195051

Parameter Viewing and Configuration (Caterpillar Electronic Technician)


SMCS Code: 4467-NQ The following materials are needed to program the Voltage Regulator with Caterpillar Electronic Technician (ET):

3. Wait for the software to recognize the ECMs. See illustration 35.

CDVR Caterpillar ET Software 24 Volt DC Control Power to the voltage regulator IBM-compatible PC with serial port, 486DX2 or
faster (100 MHz or higher microprocessor is recommended)

Communication Adapter II
Follow the steps below in order to program the voltage regulator with Caterpillar ET: 1. Apply 24 Volt DC control power to the voltage regulator. 2. Connect the Communication Adapter II module between the computer and the primary CANBUS port and start the Cat ET Software. Select the appropriate communication port, if prompted.

Illustration 35 ECMs detected screen

g01112515

RENR7941-01

51 Testing and Adjusting Section

Illustration 36 Connect button

g01112560

4. If the software does not automatically connect, click on the CONNECT button at the top of the screen as shown in illustration 36.

Illustration 37 Configuration tool

g01113063

5. The Service menu contains a drop down menu containing the Configuration Tool button as shown in illustration 37. Click on the Configuration Tool button . Select the CDVR from the list by clicking on it once.

Illustration 38 Available ECMs

g01113076

52 Testing and Adjusting Section

RENR7941-01

6. Verify that the CDVR is listed in the left panel under AVAILABLE ECM(S)as shown in illustration 38.

Illustration 39 Configuration group

g01113082

7. Select the configuration group to be viewed by clicking on it in the left panel. See illustration 39. If necessary, expand the CDVR folder in the left panel by clicking the + symbol next to the CDVR label. The various parameters to be programmed or viewed in that particular configuration group become visible in the right panel.

Illustration 40 Parameter selection

g01113121

8. To program a parameter, double click that parameter in the right panel (or highlight the parameter by single clicking it, then pressing ENTER). See illustration 40.

RENR7941-01

53 Testing and Adjusting Section

Illustration 41 Change Parameter Value

g01113102

9. Type the new value (or select a new value from the drop down menu, if given) in the CHANGE PARAMETER VALUE window and click on OK. Click on YES to confirm. See illustration 41. 10. Repeat steps 7 through 9 for each parameter to be programmed.

Illustration 42 Disconnect button

g01113109

11. To disconnect communication, click the DISCONNECT button. See illustration 42.
i02290013

1. Starting with the factory defaults (Kp = 200, Ki = 600, Td = 0, and Kg = 50), adjust Kg to achieve the desired response. If that response is not achievable, proceed to Step 2. 2. Perform a step of reference test by recording the generator terminal voltage with a chart recorder or similar device. Limit the step sizes to 5% or less of terminal voltage (e.g. from 480V to 504V). a. If the response is too slow, increase Ki. b. If the response is oscillatory or has a large amount of overshoot, decrease Ki or Kd.

Gain Setting - Adjust


SMCS Code: 4467 The following steps should only to be used as a guide if the default settings in the CDVR do not give acceptable performance. Each generator has its own requirements that are application specific.

54 Testing and Adjusting Section

RENR7941-01

c. If the desired response is still not achievable, proceed to Step 3. 3. If Tdo and Te are known, use the PID calculator in order to obtain the starting PID values. If Tdo is known but Te is not known, use the PID calculator with the default exciter time constant (Te = Tdo/6). If the desired response is not obtainable with these PID values, proceed to Step 4. 4. Start with Kp = 10, Ki = 2, Kd = 2, Td = 0, and Kg = 30. If the voltage setpoint is not achieved, increase Kg until the machine terminal voltage is approximately equal to the set value. Reduce Ki to 0.01. The terminal voltage should decrease. Adjust Kg in order to obtain 90% of set terminal voltage (e.g. if the voltage setpoint is 480V, adjust Kg to achieve 432V). 5. With Kg set as determined in Step 4, set Kp = 40, Ki = 10, Kd = 10, and Td = 0. Perform a step of reference test, no more than 5% step (e.g. from 480V to 504V). Adjust Kp to achieve 80% of the final value. (403V in the example) in the desired time frame. The desired rise time should be based on how fast you want the combined generator and CDVR to respond. In most application, this will be in the range of 0.5 seconds to 1 second. Once Kp is adjusted, increase Ki in order to get the desired response. If overshoot/ringing occurs, reduce Ki and then increase Kp, Ki, and Kd (keeping the ratio constant). Note: Many people use a load application/rejection test to adjust the voltage regulator. If available, use an inductive load. A resistive load is not the best way to adjust the voltage regulators PID values. If the only load available is a resistive load, beware that the engine/speed governors response will significantly affect the voltage regulators performance.
i02195060

Alarm or Shutdown Faults


Faults that are discussed in this section will not cause excitation to be turned off unless some external means of removing excitation is wired into the Alarm or the Shutdown Fault output driver. Shutdown faults that always cause excitation to be turned off are discussed in Testing and Adjusting, No Voltage Troubleshoot. Open communication with the voltage regulator in order to determine which fault condition has occurred. If the Fault LED is lit constantly, this indicates that the Alarm output driver is active. If the Fault LED is flashing, this indicates that the Shutdown output driver is active. If an Excitation Loss (reverse VAR) fault has occurred, a reverse VAR condition has been detected in excess of the programmed threshold for longer than the programmed time delay. If an incorrect fault detection is suspected, verify that the programmed settings are compatible with the application. If settings are correct, it is possible to get an incorrect fault detection if the generator voltage and the generator current sensing inputs to the voltage regulator are not properly wired for ABC rotation. Verify correct wiring of the generator voltage and generator current sensing inputs to the voltage regulator. See Testing and Adjusting, Wiring Diagrams. If a Generator Overvoltage fault has occurred, a generator overvoltage condition has been detected at the generator voltage sensing input(s) of the voltage regulator in excess of the programmed threshold for longer than the programmed time delay. See Testing and Adjusting, High Voltage - Troubleshoot. If a Generator Undervoltage fault has occurred, a generator undervoltage condition has been detected at the generator voltage sensing input(s) of the voltage regulator in excess of the programmed threshold for longer than the programmed time delay. See Testing and Adjusting, Low Voltage Troubleshoot. If the Fault Reset contact input is closed for more than 10 seconds, a Fault Reset Too Long fault has occurred. Remove the short across the Fault Reset contact input. Resetting the voltage regulator may be achieved either by momentarily closing the Fault Reset contact input or by cycling 24 VDC control power.

Troubleshooting
SMCS Code: 4467 If the voltage regulator does not operate as expected, first check the programmable settings for the appropriate function. Use the following troubleshooting procedures when difficulties are encountered in the operation of the excitation system.

RENR7941-01

55 Testing and Adjusting Section

i02195074

No Voltage - Troubleshoot
SMCS Code: 4467-035

4. Check for correct input power to the voltage regulator. Refer to Specification, Electrical, for input power requirements. OK If voltage is present, go to step 5. NOT OK If PMG voltage is not present, refer to the generator manual for the repair procedures and check for an open circuit. STOP. 5. Verify that the residual voltage applied to the power input is at least 6 ACV. OK If the applied voltage is 6 ACV or greater, go to step 6. NOT OK If the applied voltage is less than 6 ACV, refer to the generator manual and flash the generator field. Install blocking diodes in series with the battery in order to prevent damage to the voltage regulator and/or the battery. STOP. 6. Verify that the fuse is not open. OK If no fuses are open, go to step 7. NOT OK Replace any fuses that are open. STOP. 7. Verify that the common alarm/Shutdown LED indicator on the voltage regulator is not flashing. OK If no protective fault has caused the excitation to be turned off, go to step 14. NOT OK If the LED indicator is flashing, open communications with the voltage regulator to determine if a protective shutdown fault has occurred that would cause excitation to be turned off. If protective shutdown fault has occurred that would cause excitation to be turned off, go to step 8. 8. If an Exciter Diode Monitor (EDM) fault has occurred, stop the machine, insure that the power input to the voltage regulator is removed, and unplug P6 on the voltage regulator. a. Refer to the generator manual for instructions on checking the rotating exciter diodes. Have the rotating exciter diode assembly checked for open or shorted diodes. If an open or shorted diode is present in the rotating exciter diode assembly, refer to the generator manual for instructions on how to replace the rotating rectifier assembly.

Illustration 43

g01021519

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that all of the wiring is properly connected. Refer to Testing and Adjusting, Wiring Diagrams. OK If the wiring connections are correct, go to step 2. NOT OK If the wiring is improperly connected or the wiring is loose, reconnect the wiring properly. STOP. 2. Verify that the generator is running at rated speed. OK If the generator is spinning at rated speed, go to step 3. NOT OK If the generator is not at rated speed, increase generator speed to the rated value. STOP. 3. The digital voltage regulator is PMG power or Shunt powered. PMG power Proceed to step 4. Shunt Powered Proceed to step 5.

56 Testing and Adjusting Section

RENR7941-01

b. After repairs are complete, reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. c. The generator may be restarted. If there is no problem with the rotating exciter diode assembly, the EDM trip value may be set too low. An EDM fault may occur with good rotating exciter diodes under varying loads if the trip level is set too low. Set the EDM trip level to a value greater than the RMS ripple current present in the exciter field under normal operating conditions in order to prevent a false trip. d. Reconnect P6. Reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. e. The generator may be restarted. If an Exciter Diode Monitor (EDM) fault has not occurred, go to step 9. 9. If an Over Excitation fault has occurred, stop the machine and have the generator and/or load conditions checked for a generator or load fault that could cause excessive exciter field current to flow. Also have the system checked for loose or open connections to the voltage regulator sensing inputs. Any faults must be repaired. a. After repairs are complete, reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. b. The generator may be restarted. If no generator or load fault has occurred and there are no loose or open connections to the sensing inputs of the voltage regulator, verify that the Over Excitation trip level and the delay settings are properly adjusted for the generator. c. Set the Over Excitation trip level slightly above the requirement of the application but not so high as to render the protection ineffective or damage the system. d. Reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. e. The generator may be restarted. If the Over Excitation fault still exists, the instantaneous trip value of 28 Amperes may have been reached by a faulty diode. The EDM virtual fault LED will not indicate in this case since there is a 5 second delay associated with the EDM fault protection. Go to Step 8. If an Over Excitation fault has not occurred, go to step 10.

Note: SR4 and SR4B generators may require up to 12 Amperes for full load excitation. A 10 second delay is needed in order to insure 300 percent short circuit current requirements. 10. If a Loss of Sensing fault has occurred, stop the machine and have the system checked for loose or open connections to the voltage sensing inputs of the voltage regulator. a. Have the generator and/or load conditions checked for a generator or load fault that could cause the sensed voltage to be low. b. If the generator is equipped with voltage transformers for stepping the generator voltage down to levels usable by the voltage regulator, verify that the transformers are functional and that any transformer fuses are not open. c. If transformer fuses are found to be open, replace the fuses. d. Any faults must be repaired. After repairs are complete, reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. e. The generator may be restarted. If a Loss of Sensing fault has not occurred, go to step 11. 11. If a Field Overcurrent fault has occurred, stop the machine and have the generator and/or load conditions checked for a generator or load fault that could cause excessive exciter field current to flow. Also have the system checked for loose or open connections to the voltage regulator sensing inputs. A Field Overcurrent fault is detected when output current from the voltage regulator exceeds approximately 28 A. OK If a Field Overcurrent fault has not occurred, go to step 12. NOT OK Any fault must be repaired. After repairs are complete, reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. The generator may be restarted. STOP. 12. If an Internal Memory Failure fault has occurred, try resetting the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 VDC control power. STOP. If an Internal Memory fault has not occurred, go to step 13.

RENR7941-01

57 Testing and Adjusting Section

NOT OK If after resetting the voltage regulator another Internal Memory Failure occurs, replace the voltage regulator. STOP. 13. If an Internal Watchdog Failure fault has occurred, reset the voltage regulator by momentarily closing the Fault Reset contact or by cycling 24 volt control power. OK If an Internal Watchdog Failure fault has not occurred, go to step 14. NOT OK If after resetting the voltage regulator another Internal Watchdog Failure fault occurs, replace the voltage regulator. STOP. 14. Replace the voltage regulator unit. If replacing the voltage regulator unit does not correct the problem, go to step 15. 15. There is a problem with the generator. Refer to the generator manual to troubleshoot the problem.
i02195079

1. Verify that the voltage adjustment is not set too low. OK If the voltage adjustment is correct, go to step 2. NOT OK If the voltage adjustment is too low, adjust the voltage to the correct setpoint. STOP. 2. Verify that the underfrequency setpoint (knee frequency) is not greater than the generator frequency. OK If the underfrequency setpoint is correct, go to step 3. NOT OK If the underfrequency setpoint is too high, adjust the setpoint below the rated generator frequency. STOP. 3. Verify that the generator is running at rated speed. OK If the generator is running at rated speed, go to step 5. NOT OK If the generator is not at rated speed, increase the generator speed to the rated level. STOP. 4. PMG power or Shunt powered regulator PMG power Proceed to step 5. Shunt powered Proceed to step 6. 5. Check for the correct input power to the voltage regulator. Refer to Specification, Electrical for input power requirements. OK If the voltage is at the required level, go to step 7.

Low Voltage - Troubleshoot


SMCS Code: 4467-035

Illustration 44

g01021519

NOT OK If the voltage regulator input voltage is low, refer to the generator manual for PMG repair. STOP.

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.

6. Verify that the potential transformer (if used) has the correct turns ratio and is supplying the correct voltage to the power input. OK If the turns ratio of the power potential transformer is correct, go to step 7. NOT OK If the turns ratio of the potential transformer is incorrect, is sized too small, or the transformer is not supplying the correct power, replace the potential transformer.

58 Testing and Adjusting Section

RENR7941-01

STOP. 7. Verify that the sensing potential transformer (if used) has the correct turns ratio and is operating correctly. OK If the sensing potential transformer is operating correctly, go to step 8. NOT OK If the turns ratio of the sensing potential transformer is incorrect, replace the sensing potential transformer. STOP. 8. Low generator output voltage may occur when operating in droop mode with an inductive load. If the low voltage condition is not caused by the droop function, go to step 9. 9. Replace the voltage regulator.
i02195083

OK If the voltage adjustment is correct, go to step 2. NOT OK If the voltage adjustment is too high, adjust the voltage to the correct setpoint. STOP. 2. Verify that the sensing potential transformer (if used) has the correct turns ratio. OK If the sensing potential transformer is correct, go to step 3. NOT OK If the turns ratio of the sensing potential transformer is incorrect, replace the sensing potential transformer with the correct one. STOP. 3. High generator output voltage may occur when operating in droop mode with a capacitive load. If the high voltage condition is not caused by the droop function, go to step 4. 4. High generator output voltage may occur when operating in line drop compensation mode with a large generator load. If the high voltage condition is not caused by the line drop compensation function, go to step 5. 5. Verify that the fuses for the sensing potential transformer (if used) are not open. OK If the fuses for the sensing potential transformer are correct, go to step 6. NOT OK If the fuses for the sensing potential transformer are open, replace the fuses. STOP.

High Voltage - Troubleshoot


SMCS Code: 4467-035

Illustration 45

g01021519

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that the voltage adjustment is not set too high.

6. Verify that the auxiliary input voltage going to the voltage regulator is present or abnormally high. Higher than normal voltage at this input will cause a higher than normal generator voltage. If voltage is present on the auxiliary input, remove the input by removing the wiring going to the voltage regulator. If the wire is removed and the generator voltage returns to the desired level, investigate where the voltage is coming from, possible a VAR/PF controller or another source of control. If the auxiliary input voltage is not present or abnormally high, go to step 7. 7. Replace the voltage regulator.

RENR7941-01

59 Testing and Adjusting Section

i02195059

Unstable Voltage Troubleshoot


SMCS Code: 4467-035

OK If the stability range setting is correct, go to step 4. NOT OK If the stability range setting is incorrect, reset the stability range. STOP. 4. Verify that the stability level is properly set. If the stability level is not properly set, reset the stability level.
i02290126

Reverse VAR Condition Troubleshoot


SMCS Code: 4467-035
g01021519

Illustration 46

Switchgear or the genset control panel will initiate Reverse Var Tripping. 1. Operate the generator in Stand-Alone mode.

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that the governor for the engine is operating properly. OK If the governor is operating properly, go to step 2. NOT OK If the governor is not operating properly, refer to the engine manual in order to troubleshoot the problem. STOP. 2. Verify that the sensing and input power leads are connected securely. OK If the sensing or input power lead connections are secure, go to step 3. NOT OK If the sensing or input power leads are not connected securely, tighten the connections. STOP. 3. Verify that the voltage regulator stability range is set to the proper range.

2. Start the CDVR PC software, establish communication, and go to the Metering screen. 3. Apply a small reactive load. 4. Check the kWatts and Kvar values in the Metering screen. 5. If both kWatts and Kvar are negative, the CT may be wired backwards. Check the wiring to the CT. Alternately, the A and C sensing leads may be reversed. Physically check the connections from the bus bars to the sensing inputs for correct ordering (12-10, 12-11, and 12-12 are C-B-A respectively). 6. If either kWatts or kVar is negative, and the other is positive, the A and B, or B and C sensing leads may be reversed. Physically check the connections from the bus bars to the sensing inputs for correct ordering (12-10, 12-11, and 12-12 are C-B-A respectively).

60 Testing and Adjusting Section

RENR7941-01

i02195069

Poor Voltage Regulation Troubleshoot


SMCS Code: 4467-035

OK If the PMG leads are not grounded, go to step 4. NOT OK If the PMG leads are grounded, isolate the PMG leads from ground. STOP. 4. Verify that the generator frequency is not dropping below the voltage regulator underfrequency setpoint when load is applied to the generator. OK If poor regulation is not related to voltage regulator underfrequency operation, go to step 5. NOT OK If the generator frequency is dropping below the underfrequency setpoint, reduce the setpoint if possible. Also check the engine and generator for proper sizing in relation to the applied load.

Illustration 47

g01021519

STOP. Note: Measure the PMG voltage from line to line.

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that the chassis of the voltage regulator is properly grounded. OK If the voltage regulator is properly grounded, go to step 2. NOT OK If the voltage regulator is not properly grounded, connect a dedicated ground wire to terminal P6-6 on the voltage regulator. STOP. 2. Check for grounded field leads. OK If the field leads are not grounded, go to step 3. NOT OK If the field leads are grounded, isolate the field leads from ground. STOP. 3. Check for grounded PMG leads.

5. Verify that regulation is not being affected by normal droop operation. If droop operation is not affecting regulation, go to step 6. 6. Verify that regulation is not being affected by normal line loss compensation. If line loss compensation is not affecting regulation, replace the voltage regulator. On new applications and when commissioning, check the PID value. If voltage fluctuates at steady-state N.L. or F.L., reduce Kg or if at 1.0 reduce Kp. Recalculate PID in calculator. Note: Self Excited (shunt powered) generators will have a greater input power voltage than PMG generators. This will require a lower gain settings (Kg first then Kp if necessary) on comparably sized machine. Adjust Kg values first, then Kp values to reach acceptable steady-state and transient responses.

RENR7941-01

61 Testing and Adjusting Section

i02195078

No Line Loss Compensation Troubleshoot


SMCS Code: 4467-035

5. Verify that the load that is being applied to the generator for droop testing is not a purely resistive load. If only a resistive load is being applied to the generator, apply an inductive load and retest. If the load being applied to the generator is inductive, go to step 6. 6. Verify that the current sensing transformer that is being used is compatible with the voltage regulator. For example, a current sensing transformer with a 1-ampere output rating would produce very little droop since the voltage regulator has a 5-ampere current transformer input. If the current transformer input is incorrect, replace the current sensing transformer for compatibility. If the current transformer input is correct, go to step 7. 7. If all of the previous steps fail to correct the malfunction, replace the voltage regulator.

Illustration 48

g01021519 i02195073

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that the voltage regulator is programmed for line loss compensation. If the voltage regulator is programmed for line loss compensation, go to step 2. 2. Verify that the voltage regulator line drop setting is not adjusted to 0%. If the line drop setting is adjusted to 0%, increase the setpoint above 0%. If the line drop setting is adjusted to above 0%, go to step 3. 3. Check for an open in the circuit connected to voltage regulator terminals P12-1 and P12-2 and CT2. If there is an open circuit, repair as necessary. If there is not an open circuit, go to step 4. 4. Verify that all connections are correct according to Testing and Adjusting, Wiring Diagrams. If connections are incorrect, correct the problem. If connections are correct, go to step 5.

No Voltage Droop Troubleshoot


SMCS Code: 4467-035

Illustration 49

g01021519

The Cat Digital Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death. Service by trained personnel only. The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed. 1. Verify that the voltage regulator is programmed for droop mode. If the voltage regulator is programmed for droop mode, go to step 2.

62 Testing and Adjusting Section

RENR7941-01

2. Verify that the voltage regulator droop setting is not adjusted to 0% droop. If the droop setting is adjusted to 0% droop, increase the setpoint above 0%. If the droop setting is adjusted to above 0%, go to step 3. 3. Check for an open in the circuit connected to voltage regulator terminals P12-1 and P12-2 and CT2. If there is an open circuit, repair as necessary. If there is not an open circuit, go to step 4. 4. Verify that all connections are correct according to Testing and Adjusting, Wiring Diagrams. If connections are incorrect, correct the problem. If connections are correct, go to step 5. 5. Verify that the load that is being applied to the generator for droop testing is not a purely resistive load. If only a resistive load is being applied to the generator, apply an inductive load and retest. If the load being applied to the generator is inductive, go to step 6. 6. Verify that the current sensing transformer that is being used is compatible with the voltage regulator. For example, a current sensing transformer with a 1-ampere output rating would produce very little droop since the voltage regulator has a 5-ampere current transformer input. If the current transformer input is incorrect, replace the current sensing transformer for compatibility. If the current transformer input is correct, go to step 7. 7. If all of the previous steps fail to correct the malfunction, replace the voltage regulator.
i02195054

Wiring Diagrams
SMCS Code: 4467; 7566

RENR7941-01

63 Testing and Adjusting Section

Illustration 50 Typical connections for PMG power input, ABC rotation, and three-phase voltage sensing Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01015474

(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. (H) Sensing potential transformer is required if line voltage exceeds 600 VAC. (I) When generator rotation is ACB, the connections for the CTB should be reversed.

64 Testing and Adjusting Section

RENR7941-01

Illustration 51 Typical connections for shunt power input, ABC rotation, and single-phase voltage sensing Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01015488

(G) Sensing potential transformer is required if line voltage exceeds 600 VAC. (H) When generator rotation is ACB, the connections for the CTB should be reversed.

RENR7941-01

65 Testing and Adjusting Section

Illustration 52 Typical connections for shunt power input, ABC rotation, and three-phase voltage sensing Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01015546

(G) Sensing potential transformer is required if line voltage exceeds 600 VAC. (H) When generator rotation is ACB, the connections for the CTB should be reversed.

66 Testing and Adjusting Section

RENR7941-01

Illustration 53 Typical connections for PMG power input, ABC rotation, and single-phase voltage sensing Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01015576

(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. (H) Sensing potential transformer is required if line voltage exceeds 600 VAC. (I) When generator rotation is ACB, the connections for the CTB should be reversed.

RENR7941-01

67 Testing and Adjusting Section

Illustration 54 Typical connections for PMG power input, ABC rotation, and single-phase voltage sensing Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01145364

(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. (H) Sensing potential transformer is required if line voltage exceeds 600 VAC. (I) When generator rotation is ACB, the connections for the CTB should be reversed.

68 Testing and Adjusting Section

RENR7941-01

Illustration 55 Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01112935

Typical connections for Auxiliary Winding Regulation Excitation Principle (AREP) power input, ABC rotation, and three phase voltage sensing (G) Sensing potential transformer is required if line voltage exceeds 600 VAC. (H) When generator rotation is ACB, the connections for the CTB should be reversed.

RENR7941-01

69 Testing and Adjusting Section

Illustration 56 Typical connections for PMG power input, ABC rotation, and single phase direct voltage sensing (generator less than 600 volts) Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01112701

(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. (H) Sensing potential transformer is required if line voltage exceeds 600 VAC. (I) When generator rotation is ACB, the connections for the CTB should be reversed.

70 Testing and Adjusting Section

RENR7941-01

Illustration 57 Typical connections for PMG power input and three phase direct voltage sensing (generator less than 600 volts) Notes: (A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open. (B) When excitation disable switch is open, excitation is enabled. (C) When fault reset switch is momentarily closed, any shutdown fault is reset. (D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint. (E) Alarm Driver and Shutdown Fault Driver are normally off. (F) The 10 VDC input provides adjustment of setpoints.

g01112717

(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. (H) Sensing potential transformer is required if line voltage exceeds 600 VAC. (I) When generator rotation is ACB, the connections for the CTB should be reversed.

RENR7941-01

71 Testing and Adjusting Section

Illustration 58 Typical connections for cross current compensation

g01112653

72 Testing and Adjusting Section

RENR7941-01

Illustration 59 Typical connections for cross current compensation (two CDVRs).

g01172352

RENR7941-01

73 Testing and Adjusting Section

Illustration 60 Typical connections for cross current compensation (one CDVR and one DVR).

g01172354

74 Testing and Adjusting Section

RENR7941-01

Illustration 61 Typical connections for cross current compensation (three CDVRs).

g01172355

RENR7941-01

75 Testing and Adjusting Section

Illustration 62 Typical connections for a manual voltage control

g01112822

Index
C Cross Current Compensation ................................ 15 D Dimensions.............................................................. 8 E Electrical .................................................................. 4 G Gain Setting - Adjust.............................................. 53 General Information........................................... 9, 21 Connectors......................................................... 10 PREVENTATIVE MAINTENANCE ..................... 21 H High Voltage - Troubleshoot .................................. 58 I Important Safety Information ................................... 2 K KVAR Regulation................................................... 15 L Line Loss Compensation ....................................... 13 Loading and Stopping Profile ................................ 12 Low Voltage - Troubleshoot................................... 57 N No Line Loss Compensation - Troubleshoot ......... 61 No Voltage - Troubleshoot..................................... 55 No Voltage Droop - Troubleshoot .......................... 61 P Parameter Viewing and Configuration (Caterpillar Electronic Technician).......................................... 50 Parameter Viewing and Configuration (Caterpillar PC Software) ............................................................. 24 Changing Settings.............................................. 25 Installing the Caterpillar PC Software ................ 24 Sending and Receiving Settings ........................ 26 Setting Definitions .............................................. 27 Settings Files ..................................................... 46 Starting Caterpillar PC Software ........................ 25 Parameters ............................................................ 17 General Information ........................................... 17 Poor Voltage Regulation - Troubleshoot................ 60 Power Factor Regulation ....................................... 16 R Reactive Voltage Droop......................................... Remote Communication ........................................ Establishing Communication.............................. Terminating Communication .............................. Reverse VAR Condition - Troubleshoot................. S Service Tools ......................................................... 21 Specifications Section ............................................. 4 Startup Procedure ................................................. 22 Startup Profile Function .......................................... 11 Systems Operation Section ..................................... 9 T Table of Contents..................................................... 3 Testing and Adjusting ............................................ 21 Testing and Adjusting Section ............................... 21 Troubleshooting..................................................... 54 Alarm or Shutdown Faults.................................. 54 U Unstable Voltage - Troubleshoot ........................... 59 V Voltage Regulation ................................................ 13 W Wiring Diagrams .................................................... 62 14 18 19 20 59

2005 Caterpillar All Rights Reserved

Printed in U.S.A.

You might also like