Figure 1 - Clearance To Pipes: Subject: Clearance Requirements For Cable Trays

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Figure 1 – Clearance to Pipes

Figure 2 – Clearances to Wall Figure 3 – Clearance to Beams

SUBJECT: CLEARANCE REQUIREMENTS FOR CABLE TRAYS

DESIGN STANDARD
3D-15.02 0
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 1 OF 2 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE FEB. 09

PROJ. GENERIC
APPR. P.Healy APPR. DATE .
Symbol Clearance Clearance (Special) Clearance (Special)
(Typical)

a 200 [8]

b 300 [12] * To Valves and Items To Uninsulated

c 300 [12] 1000 [40] Requiring Regular 1200 [48] Steam Pipes

d 200 [8] Maintenance

e 150 [6] *

f 50 [2]

g 400 [16] +

h 600 [24] *

i 75 [3]

k 300 [12] *

REFERENCES

* Dimensions b, e, h and k are minimum dimensions as per Code.

+ Larger vertical spacing between cable trays may be requested by Insurance Company to
avoid fire retardant coating or sprinklers for cables.

Note: 1. Clearances listed are Mechanical Safety and Code Requirements. Electrical 3D-15.05
clearance requirements for signal and power cable, conduit and cable tray can be
found in referenced design standard, elsewhere in this document.