Figure 1 - Clearance To Pipes: Subject: Clearance Requirements For Cable Trays
Figure 1 - Clearance To Pipes: Subject: Clearance Requirements For Cable Trays
Figure 1 - Clearance To Pipes: Subject: Clearance Requirements For Cable Trays
DESIGN STANDARD
3D-15.02 0
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 1 OF 2 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE FEB. 09
PROJ. GENERIC
APPR. P.Healy APPR. DATE .
Symbol Clearance Clearance (Special) Clearance (Special)
(Typical)
a 200 [8]
c 300 [12] 1000 [40] Requiring Regular 1200 [48] Steam Pipes
e 150 [6] *
f 50 [2]
g 400 [16] +
h 600 [24] *
i 75 [3]
k 300 [12] *
REFERENCES
+ Larger vertical spacing between cable trays may be requested by Insurance Company to
avoid fire retardant coating or sprinklers for cables.
Note: 1. Clearances listed are Mechanical Safety and Code Requirements. Electrical 3D-15.05
clearance requirements for signal and power cable, conduit and cable tray can be
found in referenced design standard, elsewhere in this document.
DESIGN STANDARD
3D-15.02 0
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 2 OF 2 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE FEB. 09
PROJ. GENERIC
APPR. P.Healy APPR. DATE .