Professional Documents
Culture Documents
Buffer Module - QUINT-BUFFER/24DC/24DC/40 - 2320393: Product Description
Buffer Module - QUINT-BUFFER/24DC/24DC/40 - 2320393: Product Description
com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
QUINT buffer module with maintenance-free capacitor-based energy storage for DIN rail mounting, input: 24
V DC, output: 24 V DC/40 A, with integrated SFB (selective fuse breaking) technology, including mounted
universal DIN rail adapter UTA 107
Product Description
Short-term mains interruptions are bridged by QUINT BUFFER, a maintenance-free capacitor-based buffer module with SFB technology (selective
fuse breaking technology). Systems can therefore also run in unstable networks or, in the event of longer failures, are correctly shut down after
all relevant process data is saved. The buffer module also acts as a energy storage device for peak loads and for tripping fuses. For function
monitoring, an active switching output and a control lamp are used. With the integrated diode, loads can be divided into buffered and unbuffered
loads. The buffer time is thus extended and the buffered loads are protected against errors in the internal network.
GTIN
GTIN 4046356554114
Technical data
Dimensions
Width 64 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 67 mm
Ambient conditions
07/30/2018 Page 1 / 6
https://www.phoenixcontact.com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Technical data
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height 2000 m
Input data
Input voltage 24 V DC
Input voltage range 18 V DC ... 30 V DC
Current consumption (maximum) 45 A (Conduction current)
Current consumption (idle) 0.1 A (No-load)
Current consumption (charging process) 0.7 A (charging process)
Fixed connect threshold < 20 V DC (< 22 V; < 24 V; < 26 V)
Variable connect threshold (UIN - 1 V)/0.1 s
General
IQ technology no
Net weight 1.1 kg
Memory medium Electrolytic capacitor
Protection class III
MTBF (IEC 61709, SN 29500) > 902000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
07/30/2018 Page 2 / 6
https://www.phoenixcontact.com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Technical data
Connection data, input
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 8
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Signaling
Output name Power Good signal output active (high = buffer module charged)
Output description Power Good
Output voltage + 24 V
Continuous load current 20 mA
Status display LED "Power Good", green
Note on status display Buffer module is loaded: LED ON
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Screw thread M4
07/30/2018 Page 3 / 6
https://www.phoenixcontact.com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Technical data
Standards and Regulations
Test field strength 10 V/m
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-4-5
Signal 1 kV (Test Level 2 - asymmetrical)
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
EN 50178/VDE 0160 (PELV)
and their assembly into electrical power installations
Standard – Safety extra-low voltage EN 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0106-101
UL approvals UL/C-UL Recognized UL 60950-1
UL Listed UL 508
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Drawings
Block diagram
Input Output
Backup
Threshold
Power
Good
GND
07/30/2018 Page 4 / 6
https://www.phoenixcontact.com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Approvals
Approvals
Approvals
UL Recognized / UL Listed / cUL Recognized / cUL Listed / EAC / EAC / ABS / BV / DNV GL / LR / cULus Recognized / cULus Listed
Ex Approvals
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
EAC
EAC-Zulassung
RU C-
EAC
DE.A*30.B.01082
http://www.veristar.com/portal/veristarinfo/generalinfo/
BV 41516/A0 BV
approved/approvedProducts/equipmentAndMaterials
07/30/2018 Page 5 / 6
https://www.phoenixcontact.com/pi/products/2320393
Buffer module - QUINT-BUFFER/24DC/24DC/40 - 2320393
Approvals
LR
http://www.lr.org/en 17/20032
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
cULus Listed
07/30/2018 Page 6 / 6