P630 Demo
P630 Demo
P630 Demo
©2006 Page 1 of 71
Issue A.3
3 November 2006
PRACTICAL DEMONSTRATION:
Location: Q:\P630_Tutorial\P630_intro.doc
OBJECTIVES:
To gain familiarisation of the menu structure, the setting files and programmable scheme logic of
the MiCOM PX30 relays
To provide a step by step guide to configuring and testing the differential function for a small
transformer.
T&D
Automation & Information Systems - St Leonards Avenue – Stafford – ST17 4LX – England
Tel: +44 (0)1785 223251 – Fax: +44 (0)1785 212232
AREVA T&D UK LTD. Registered Office: St Leonards Avenue – Stafford – ST17 4LX
Registered in England: 4955841
P630 INTRODUCTION
Page 2 of 71
Issue A.
3 November 2006
Table of Contents
1. INTRODUCTION .............................................................................................................4
1.1. SCOPE ............................................................................................................................4
1.2. QUICK START: I NEED TO KNOW ................................................................................4
1.3. SECTION ABSTRACTS ..................................................................................................4
2. LOCAL CONTROL .........................................................................................................5
2.1. FRONT PANEL ...............................................................................................................5
2.1.1. LCD & Keypad.................................................................................................................5
2.1.2. LED Indications ...............................................................................................................5
2.2. MENU STRUCTURE & NAVIGATION ............................................................................6
2.2.1. Structure – Top Level ......................................................................................................8
2.2.2. Structure - Parameters ....................................................................................................8
2.2.3. Structure - Operation .....................................................................................................10
2.2.4. Structure - Events..........................................................................................................11
2.3. MODIFYING PARAMETERS ........................................................................................12
2.3.1. Selecting Parameters ....................................................................................................12
2.3.2. Changing Parameters – Edit Mode ...............................................................................13
2.3.3. Default Condition: The Cold Restart..............................................................................14
2.3.4. Clearing the ‘Alarm’ LED ...............................................................................................15
2.3.5. Clearing the ‘Trip’ LED ..................................................................................................15
2.3.6. The ‘Out of Service’ LED ...............................................................................................16
3. S&R-103 SETTING SOFTWARE..................................................................................17
3.1. COMMUNICATING WITH THE RELAY ........................................................................17
3.1.1. Connections ..................................................................................................................17
3.1.2. Launching the Software.................................................................................................17
3.1.3. Checking Communication Settings................................................................................17
3.2. IDENTIFICATION OF THE DEVICE .............................................................................18
3.3. SETTING FILE EXTRACTION ......................................................................................19
3.4. DATA MODEL EXTRACTION .......................................................................................20
3.5. MODULE IDENTIFICATION..........................................................................................21
3.6. MODIFYING PARAMETERS ........................................................................................22
3.6.1. Selecting Parameters ....................................................................................................22
3.6.2. Changing Parameters ...................................................................................................22
4. SETTING CONFIGURATION........................................................................................24
4.1. STARTING POINT ........................................................................................................24
4.2. ENABLING PROTECTION............................................................................................25
4.2.1. Select function from the available list of functions.........................................................25
4.2.2. Enable function from the selected functions..................................................................26
4.2.3. Enable master protection enable...................................................................................27
4.3. CONFIGURING OUTPUT RELAYS ..............................................................................28
4.3.1. Mapping protection outputs as inputs to trip commands ...............................................29
4.3.2. Mapping trip command outputs to output relays............................................................30
4.3.3. *** Test Point 1 *** .........................................................................................................31
4.3.4. Minimum duration, latching and resetting of trip commands .........................................31
4.3.5. *** Test Point 2 *** .........................................................................................................32
4.3.6. Mapping the WATCHDOG contact................................................................................32
4.4. CONFIGURING OPTO-INPUTS ...................................................................................34
4.4.1. Mapping opto inputs as inputs to blocking commands ..................................................35
4.4.2. Mapping blocking command outputs to function inputs.................................................36
P630 INTRODUCTION
Page 3 of 71
Issue A.
3 November 2006
1. INTRODUCTION
Protection devices in the MiCOM 30 Series are described in detail in the respective technical
manuals, as regards their technical merits, functional characteristics, and handling during
installation, connection, commissioning, and operation.
However, the technical manuals are very comprehensive due to the innumerable features of
MiCOM 30 Series devices. Unfamiliar users may have a hard time with learning how to operate a
device.
1.1. SCOPE
This document is intended to help those users get started. The intention is to accompany the user
through the initial stages of communication and setting support.
By learning those basic operating procedures, it is hoped that the user will be able to continue in
confidence, using the full technical manual for reference and this document for support.
2. LOCAL CONTROL
2.1. FRONT PANEL
The front plate of the relay is as shown in Figure 2-1.
MiCOM
TRIP H4 H5
ALARM H3 H6
OUT OF SERVICE H2 H7
HEALTHY H1 H8
EDIT H0 H9
C = CLEAR
C
G G H10
= READ G
H11
= ENTER H12
H13
G G
H14
G
H15
G H16
The description of all data points in this menu tree, is called the data model.
The values associated with each data point, is called the settings file.
To logically view a settings file you need the data model. Fortunately this can be extracted from
the relay directly, if it is not available in the setting software, see section 3.4.
The menu tree begins with the device type at the top and then branches out below into the three
main folders entitled, Parameters, Operation and Events, which form the first folder level. Below
this first folder level are two more folder levels, so that the entire folder structure consists of three
main branches and a maximum of three folder levels. After this the logical structure falls naturally
into the function groups, which forms the lowest logical organisation of data points.
This structure is shown in Figure 2-2.
P630 INTRODUCTION
Page 7 of 71
Issue A.
3 November 2006
►DeviceID
This branch contains all the information regarding the relay type and version , for example
software, language and hardware versions.
►Config.parameters
This branch contains two types of ‘settings’, contained within individual function groups.
i. Settings to enable configuration of relay I/O, comms and the fault recorder.
ii. A complete list of protection and control functions that contain a single configuration
status that can be enabled or disabled. This makes the corresponding settings for
that function visible in the ►Function parameters►General functions branch.
►Function parameters
The menu structure of this branch is shown in Figure 2-5.
1
X represents the subset number.
P630 INTRODUCTION
Page 10 of 71
Issue A.
3 November 2006
MiCOM Px3x
MiCOM Px3x
Parameters
Par/ Par/
Device ID Config.parameters
Par/Conf/
LOC
Par/Conf/LOC Par/Conf/LOC
Language (tongue) Decimal delimiter
English dot
Although it is possible to select any data point in the menu tree and read the associated value by
pressing the keys, it is not possible to switch directly to the ‘Edit’ mode. This safeguard prevents
unintended changes in the settings. To access edit mode the password has to be entered.
Changing a parameter (e.g. ‘MiCOM Px3x/Parameters/Config.paramters/LOC/Decimal delimiter’):
Note: Edit mode can be left without changing a parameter by pressing the CLEAR key instead of
the ENTER key.
Par/Conf/LOC
Decimal delimiter
Dot
Par/Conf/LOC
Decimal delimiter
Dot
********
Par/Conf/LOC
Decimal delimiter
Dot
Par/Conf/LOC
Decimal delimiter
Comma
Par/Func/Glob/MAIN
Protection enabled
No (=off)
Oper/CrtlTest/MAIN
Cold restart
don't execute
Oper/CrtlTest/MAIN
Cold restart
execute
Then press the ENTER key and the device will reboot:
********************
**** REBOOT *****
********************
********************
TEST
>>>>>>>>
After a cold restart any non default settings have been deleted and all records have been cleared.
All parameters are set to their default value.
P630 INTRODUCTION
Page 15 of 71
Issue A.
3 November 2006
Oper/Rec/MT_RC
Mon. signal record.
In order to switch off the ALARM LED, clear the monitoring signal memory.
(‘MiCOM Px3x/Operation/Control and Testing/MT_RC/Reset recording’):
Oper/CrtlTest/MT_RC
Reset recording
2
Oper/CrtlTest/MT_RC
Reset recording
2
execute
Press the ENTER key. The number of entries in the monitoring signal memory will be changed to
‘0’ and the ALARM LED will go ‘off’:
Oper/CrtlTest/MT_RC
Reset recording
0
Par/Func/Glob/MAIN
Protection enabled
Yes (=on)
Note: The ‘Out of Service’ LED, may occur for the following reasons there have to be corrected
before the LED can be extinguished.
Par/Func/Glob/OUTP
Outp.rel.block USER
No
Par/Func/Glob/MAIN
Protection enabled
Yes (=on)
Par/Func/Glob/MAIN
Trip cmd.block. USER
No
The ‘Out of Service’ LED may occur due to the self-monitoring function, which has detected an
internal fault of the device. In that case the ALARM LED is also energised. Readout the
corresponding entries in the monitoring signal memory, as described in section 2.3.4 and rectify
the situation.
P630 INTRODUCTION
Page 17 of 71
Issue A.
3 November 2006
3.1.1. Connections
Power the relay, ensuring that the appropriate auxiliary voltage has been selected. Plug in the
serial connection lead between the computer and the 9-pin port on the front of the relay. This is
shown in below in Figure 3-1.
Par/Conf/PC
Transm.enab.cycl.dat
Without
Once these settings have been confirmed press the Identify button and the S&R-103 will start
communicating with the relay. The S&R-103 will scan each baud rate looking for the relay.
If communication is successful, the following screen shown in Figure 3-4 will be displayed.
P630 INTRODUCTION
Page 19 of 71
Issue A.
3 November 2006
The dialog box will disappear and the setting window will show a red star next to the setting to
indicate that is has changed from the original setting file. This is shown in Figure 3-13.
4. SETTING CONFIGURATION
The configuration options of the PX30 range of relays is vast and extremely flexible. However this
adds to the complexity of the relay and reduces the simplicity of the user interface. It is therefore
highly recommended to attempt setting configuration and changes via the communication port
using the S&R-103 software.
In this section a single function will be enabled and configured to drive an output relay, with an opto
input configured as a block. These functions cover the primary operations that a user may wish to
accomplish.
The function that will be enabled is over current protection (IDMT1).
The function group should now be visible in the following two locations:
P630 INTRODUCTION
Page 26 of 71
Issue A.
3 November 2006
Locate Enable PS1, select Yes and send to the relay. This is where the individual setting group
protection settings can be configured. The function default is No in the remaining subsets 2-4.
Locate the setting Min. trip t. P. This is the minimum trip time; change the setting to zero for
instantaneous operation.
P630 INTRODUCTION
Page 27 of 71
Issue A.
3 November 2006
The protection function is now enabled; however the protection function outputs need to be
configured.
P630 INTRODUCTION
Page 28 of 71
Issue A.
3 November 2006
ii. Map a protection/control function output into a ‘Tripping’ command and then map
this to an output relay. This is normally perfectly adequate for most applications and
will be described within this section.
iii. Use the ‘LOGIC’ feature. This is more flexible for complex implementations; this
function will be described in section 5. LOGIC should not be used for mapping trip
outputs, see section 5 for further information.
P630 INTRODUCTION
Page 29 of 71
Issue A.
3 November 2006
Locate Fct. assignm. K901. The following relevant assignment options could be applied.
Choose MAIN Gen. trip command 1. Notice that it is possible to assign the protection output
directly.
To assign a minimum duration locate Min. dur. trip cmd. 1. Select 1s and send to relay.
P630 INTRODUCTION
Page 32 of 71
Issue A.
3 November 2006
The watchdog contact is conventionally a normally closed contact, which is energised closed by
the relay, hence if the relay powers off or there is an auxiliary supply problem then the contact will
naturally open communicating a problem. Therefore modify the corresponding relay contact
setting.
P630 INTRODUCTION
Page 33 of 71
Issue A.
3 November 2006
The relay can also monitor its output contacts to verify that operation has taken place, when the
relay logic commands an operation.
Locate MAIN Fct. assign. fault. Assign this contact to the trip relay output and any other relay
outputs as necessary. There are also settings for the current circuit supervision and failures of
complete hardware modules.
P630 INTRODUCTION
Page 34 of 71
Issue A.
3 November 2006
ii. Map an opto input through the ‘Blocking’ command. This is normally perfectly
adequate for most applications and will be described within this section.
iv. Use the ‘LOGIC’ feature. This is more flexible for complex implementations; this
function will be described in section 5.
P630 INTRODUCTION
Page 35 of 71
Issue A.
3 November 2006
This has mapped the opto input as an input into this blocking command. Any other opto inputs can
also be mapped to this command. Notice that it is possible to assign the opto input to
protection/control inputs directly, such as IDMT1 Block Iref, P> EXT, which can be used to block
the IDMT1 positive sequence over current protection.
Next we have to decide if this input is active ‘high’ or active ‘low’, these settings are in the same
location.
If other protection functions were enabled, then any number of protection block inputs could be
assigned to the blocking command.
The opto input is now configured to the protection block input through the blocking command 1.
MAIN Gen. trip command 1 Output of trip command 1 with the application of timing functions
if required see section 4.3.4.
MAIN Gen. trip signal 1 The output of trip command 1, which ignores any timing
functions applied to the trip command.
MAIN Gen. trip signal The logical ‘OR’ of all trip commands (1-4).
MAIN General started The logical ‘OR’ of all start outputs.
P630 INTRODUCTION
Page 38 of 71
Issue A.
3 November 2006
Select the LED Fct. Assignm. H*, (where * is 5-16) and select the input desired and send to relay.
H4 can be configured, but by default it is set to illuminate on a protection trip.
5. SCHEME LOGIC
The scheme logic is a powerful feature that enables users to link binary signals within a framework
of Boolean equations.
It is important to remember that although the scheme logic is flexible, it can slow down signals due
the additional computation required. This means that trip signals (if at all possible) should not be
assigned through LOGIC. Output relays should be driven by trip commands and the protection
trip signals should be gated with LOGIC output, within the trip commands.
Only a basic use of LOGIC is shown here, refer to the manual for further applications.
Locate the function group LOGIC, select the With option and send to the relay.
P630 INTRODUCTION
Page 40 of 71
Issue A.
3 November 2006
A Any number of input signals can be configured as inputs with the boolean functions ‘AND’,
‘OR’ and ‘NOT’.
B The logic outputs are available for use in the Trip or Blocking Command functions or any
other LOGIC functions and they can be mapped to relay outputs. The timing functions can
be used to affect the pick-up, drop-off or duration of the output signal LOGIC Output (t) in
comparison to the signal LOGIC Output.
C The outputs can also be assigned directly to any internal functions such as blocking or
control signal inputs.
The LOGIC input signal 1 is now mapped into the LOGIC function 1.
No locate Op. mode t output 1 and set it to Minimum time, which makes the LOGIC output
signals identical; this is required because within the trip commands, only the (t) signals are
available for mapping.
P630 INTRODUCTION
Page 42 of 71
Issue A.
3 November 2006
The LOGIC function 1 signal output is now mapped to the IDMT1 protection blocking signal.
When either the opto input or IDMT function operate then a trip output will occur.
P630 INTRODUCTION
Page 43 of 71
Issue A.
3 November 2006
6. FAULT RECORDER
The fault recorder can be used to record the analogue and digital channels, when a trigger signal is
received.
The fault recorder will now start recording when a trip signal is initiated.
P630 INTRODUCTION
Page 46 of 71
Issue A.
3 November 2006
Fault records can be accessed by pressing the read key at the relay default display.
P630 INTRODUCTION
Page 47 of 71
Issue A.
3 November 2006
Follow the instructions and save the file in comtrade format for viewing.
P630 INTRODUCTION
Page 48 of 71
Issue A.
3 November 2006
There are various ways of observing these measurements. Via the relay front panel at the location
given above, or by configuration of cyclic measurements using the S&R-103 software as described
in section 7.2.
The relay can also be configured to display default measurements on the display. Locate Fct.
Operation Panel and select the required measurements from the list.
P630 INTRODUCTION
Page 50 of 71
Issue A.
3 November 2006
These measurements will now scroll round at the default display, for the period indicated by the
setting Hold-time for Panels, after an initial duration of Autom. Return time, highlighted below.
If a current is applied to the relay, the measurement can now be seen on the front panel, however
if this current is a fault current, then the quantity displayed will read ‘Not measured’. This is
because a fault is in progress and to read these currents the fault panel requires configuration, see
section 7.3.
To activate the default display, without having to wait for the Autom. Return time to expire, press
the up arrow and the clear key simultaneously.
The measurements will scroll round the display in an identical way to the operation panel during
the overload.
P630 INTRODUCTION
Page 51 of 71
Issue A.
3 November 2006
The measurements will scroll round the display in an identical way to the operation panel.
See section 6 for details on configuring the fault recorder and clearing records.
P630 INTRODUCTION
Page 52 of 71
Issue A.
3 November 2006
An option box will appear; select configure and select the measurements from the list that are
required.
Select OK and then select Start and the measurements will appear.
P630 INTRODUCTION
Page 53 of 71
Issue A.
3 November 2006
The list can be saved to avoid reconfiguration each time the feature is utilised.
P630 INTRODUCTION
Page 54 of 71
Issue A.
3 November 2006
Then select the reference file with respect to one that is already open.
The number of deviations will then be displayed, if any. The file can then be opened and the
deviations read.
In this example it can be seen that the CT ratios are different between the two files.
P630 INTRODUCTION
Page 55 of 71
Issue A.
3 November 2006
Check that the language of the data model is set to Reference Language English
P630 INTRODUCTION
Page 56 of 71
Issue A.
3 November 2006
The settings file can then be configured. If however when the file is downloaded to the relay, a
message is displayed informing that the data model is incorrect, perform a relay identification as
detailed in section 3.2. This will result in the following information with the data model version
displayed.
The setting file is 605 but the relay is 603. Close the dialog box so that only the settings file is
open and select Tools and Convert Settings File from the menu
P630 INTRODUCTION
Page 57 of 71
Issue A.
3 November 2006
Select a name and location for the newly converted file. And then select the data model version
that the file is to be converted to, in this case P633 – 603 German.
A file compare is then performed automatically (see section 9.1) and the option to observe the
deviations is given. The new file can then be opened and downloaded successfully to the relay.
P630 INTRODUCTION
Page 58 of 71
Issue A.
3 November 2006
Parameter Setting
Frequency 50Hz
VT Primary Voltage 3.3kV
HV CT Primary Current 400A
HV Neutral CT Primary Current 400A
LV CT Primary Current 3000A
LV Neutral CT Primary Current 3000A
VT Secondary Voltage 110V
HV CT Secondary Current 1A
HV Neutral CT Secondary Current 1A
LV CT Secondary Current 1A
LV Neutral CT Secondary Current 1A
Transformer HV Voltage 3.3kV
Transformer LV Voltage 0.42kV
Transformer Rating 2MVA
Transformer Group Dny11
First stage current setting 0.1
Second stage current setting 11
Third stage current setting 11
Configure LED (of limited use in this example due to instantaneous protection function)
►Parameters►Config.parameters►LED►Fct. assignm. H16… Set to DIFF starting
10.1.7. Configure the Fault Recorder and the Operation & Fault Pages
Configure fault recorder by specifying a trigger
►Parameters►Function parameters►Global►FT_RC►Fct ssign. trigger… Set to MAIN Gen. trip signal
Assign the ‘read’ key as a shortcut to the fault record
►Parameters►Config.parameters►LOC►Assignment read key… Set to FT_RC Fault recording 1
Assign some useful parameters to the operation panel
►Parameters►Config.parameters►LOC►Fct. Operation Panel► Configure the following for example.
DIFF Diff. current 1
DIFF Restrain. Current 1
Current IA, a p.u.
Current IA, b p.u.
Assign some useful parameters to the operation panel
►Parameters►Config.parameters►LOC►Fct. Fault Panel► Configure the following for example.
FT_DA Diff. current 1
FT_DA Restrain. Current 1
FT_DA Fault curr. IP, a p.u.
FT_DA Fault curr. IP, b p.u.
P630 INTRODUCTION
Page 61 of 71
Issue A.
3 November 2006
S ref 2 MVA
I ref ,b = = = 2886.75
3 • Vnom ,b 3 • 0.4kV
The CT matching factors are therefore.
I nom ,a 400
Kam, a = = = 1.143
I ref ,a 349.9
I nom ,a 3000
Kam, b = = = 1.039
I ref ,a 2886.75
However these can be extracted from the relay. Select read at the following location.
►Parameters►Function parameters►General functions►DIFF
The relay will verify that these reference currents and matching factors are within sensible ranges.
If not then a warning will be displayed.
P630 INTRODUCTION
Page 62 of 71
Issue A.
3 November 2006
The values given above are also available using an Excel worksheet. A screen shot of the above
settings is shown below.
P630 INTRODUCTION
Page 63 of 71
Issue A.
3 November 2006
To check the differential settings by single end injection, the vector group matching factor together
with the set vector group ID, needs to be taken into account in addition to the amplitude-matching
factor and zero sequence filtering. The vector group matching factors are given in section 11.2.
I diff × I nom , x
I inj =
K am , x × K s , y , z
Z = Transformer end a, b, c or d.
I diff = operate setting
If the test has been performed correctly, the recorded results should closely match those shown in
the following graph. The plot clearly shows that the relay increases it setting, as the through fault
current increases, thus minimising the chances of mal-operation due to CT saturation.
P630 INTRODUCTION
Page 68 of 71
Issue A.
3 November 2006
Differential Characteristic
3.5
3
Differential Current (Amps)
2.5
1.5
0.5
Expected Characteristic
0
0 1 2 3 4 5 6 7 8
Bias Current (Amps)
It should be noted, that although the equations given in the table above, will enable testing to verify
the correct characteristic has been chosen, the accuracy is not exact.
The exact operating differential current can therefore accurately be calculated at follows.
⎛ ⎛ m1 ⎞ ⎞
Differential Current = Bias Current • m1 + ⎜⎜ Idiff ⎜1 − ⎟ ⎟⎟
⎝ ⎝ 2 ⎠⎠
If the bias/restrain current is above IR,m2 (4A in this example) then m1 should be substituted by
m2.
P630 INTRODUCTION
Page 69 of 71
Issue A.
3 November 2006
11. MISCELLANEOUS
11.1. ZERO SEQUENCE FILTERING
For earth fault transformer winding(s), zero sequence filtering is enabled by default and it is
essential to prevent tripping for external earth faults.
It is only in the case of isolated transformer windings were no filtering is required, this is because
for internal faults, no zero sequence current can flow in either side of the transformer, hence there
is no danger of mal-tripping. On the other hand, for external single phase faults, zero sequence
current when not filtered will be seen at one side, but this is the case when we do want the relay to
trip, as it is an external fault.
In case of resistive faults it is better to disable filtering, which will increase relay sensitivity by
adding Io back into the measurement quantity, which reduces the amount of phase current needed
for tripping.
P630 INTRODUCTION
Page 70 of 71
Issue A.
3 November 2006
Transformer end a b, c or d
DIFF: Diff. current 1 0.67 0.67 0.58 0.33 0.00 0.33 0.58 0.67 0.58 0.33 0.00 0.33 0.58
DIFF: Diff. current 2 0.33 0.33 0.00 0.33 0.58 0.67 0.58 0.33 0.00 0.33 0.58 0.67 0.58
DIFF: Diff. current 3 0.33 0.33 0.58 0.67 0.58 0.33 0.00 0.33 0.58 0.67 0.58 0.33 0.00
Factors for single end, two phase, phase opposed feed in phases B to C, zero sequence filtered.
Transformer end a b, c or d
DIFF: Diff. current 1 0.00 0.00 0.58 1.00 1.15 1.00 0.58 0.00 0.58 1.00 1.15 1.00 0.58
DIFF: Diff. current 2 1.00 1.00 1.15 1.00 0.58 0.00 0.58 1.00 1.15 1.00 0.58 0.00 0.58
DIFF: Diff. current 3 1.00 1.00 0.58 0.00 0.58 1.00 1.15 1.00 0.58 0.00 0.58 1.00 1.15
Factors for single end, one phase feed in phase A, NOT zero sequence filtered.
Transformer end a b, c or d
DIFF: Diff. current 1 1.00 1.00 0.00 0.00 1.00 0.00 0.00
DIFF: Diff. current 2 0.00 0.00 0.00 1.00 0.00 0.00 1.00
DIFF: Diff. current 3 0.00 0.00 1.00 0.00 0.00 1.00 0.00
Factors for single end, two phase, phase opposed feed in phases B-C, NOT zero sequence
filtered.
Transformer end a b, c or d
DIFF: Diff. current 1 0.00 0.00 1.00 1.00 0.00 1.00 1.00
DIFF: Diff. current 2 1.00 1.00 1.00 0.00 1.00 1.00 0.00
DIFF: Diff. current 3 1.00 1.00 0.00 1.00 1.00 0.00 1.00
P630 Introduction
Page 71 of 71
Issue A.
3 November 2006
VERSION CONTROL
Issue Author(s) Reason for change Date
A.1 A Hill Original 15-02-2005
A.2 C Smith Reformat and extension of material 03-05-2005
A.3 C Smith Corrected the watchdog settings 25-05-2005