2416 Manual
2416 Manual
2416 Manual
Contents Page
Chapter 4 TUNING..............................................................................4-1
Chapter 5 PROGRAMMER OPERATION ..........................................5-1
Chapter 1 INSTALLATION
The 2416 controller is a versatile, high stability temperature or process controller, with self
and adaptive tuning, in 1/16 DIN size (48 x 48mm). It has a modular hardware construction,
which accepts up to three plug-in output modules and one communications module, to satisfy
a wide range of control requirements. All 2416 controllers have a basic 8-segment
programmer built-in as standard.
Before proceeding, please read the chapter called, Safety and EMC Information.
Terminal covers
Sleeve
Ratchets
Display screen
Label
WARNING
You must ensure that the controller is correctly configured for your application.
Incorrect configuration could result in damage to the process being controlled, and/or
personal injury. It is your responsibility as the installer to ensure that the configuration
is correct. The controller may either have been configured when ordered, or may need
configuring now. See Chapter 6, Configuration.
MECHANICAL INSTALLATION
Controller labels
The labels on the sides of the controller identify the ordering code, the serial number, and the
wiring connections.
Appendix A, Understanding the Ordering Code explains the hardware and software
configuration of your particular controller.
Outline dimensions
48mm 150mm
1.89in 5.91in
2416
2416
OP1
OP1
OP2
48mm OP2
SP2
SP2
1.89in REM
REM
AUTO RUN
MAN HOLD
The electronic assembly of the controller plugs into a rigid plastic sleeve, which in turn fits
into the standard DIN size panel cut-out shown in Figure 1-3.
Panel cut-out
-0
45 x 45mm +0.6
-0
1.77 x 1.77in +0.02
38mm (1.5in)
10mm (0.4in)
1. Prepare the control panel cut-out to the size shown in Figure 1-3.
3. Spring the upper and lower panel retaining clips into place. Secure the controller in
position by holding it level and pushing both retaining clips forward.
4. Peel off the plastic film protecting the front of the indicator.
Note: If the panel retaining clips subsequently need removing, in order to extract the
controller from the control panel, they can be unhooked from the side with either your fingers
or a screwdriver.
If required, the controller can be unplugged from its sleeve by easing the latching ears
outwards and pulling it forward out of the sleeve. When plugging the controller back into its
sleeve, ensure that the latching ears click into place in order to secure the IP65 sealing.
ELECTRICAL INSTALLATION
This section consists of five topics:
• Rear terminal layout
• Fixed connections
• Plug-in module connections
• Typical wiring diagram
• Motorised valve connections
All electrical connections are made to the screw terminals at the rear of the controller. These
2
screw terminals accept wire sizes from 0.5 to 2.5mm (14 to 22 awg) and should be tightened
to a torque of 0.4 Nm (3.5 lb in). If you wish to use crimp connectors, we recommend AMP
2
part number 16500. These accept wire sizes from 0.5 to 1.5 mm (16 to 22 AWG).
+ 20 − 29Vac/dc
M 24
O L Line
1A
D
HA
N
− Neutral
85 to 264Vac
U
L Low voltage supply
1B E HB N Neutral
1
M
2A O HC Ground*
D C
U O
L M
2B E M HD VI
2 S
M +
3A O HE V+
D +
U T/C PV
L RTD/
3B E HF V− Pt100 −
3 −
FIXED CONNECTIONS
The power supply and sensor inputs are always wired to the same fixed positions whatever
plug-in modules are installed.
VI VI VI VI
2.49Ω +
V+ V+ V+ current V+
sense PV
V- V- V- resistor V- -
* PDSIO stands for ‘Pulse Density Signalling Input/Output’. This is a proprietary technique
developed by Eurotherm for bi-directional transmission of analogue and digital data over a
simple 2-wire connection.
Snubbers
The relay and triac modules have an internal 15nF/100Ω ‘snubber’ connected across their
output, which is used to prolong contact life and to suppress interference when switching
inductive loads, such as mechanical contactors and solenoid valves.
WARNING
When the relay contact is open or the triac is off, the snubber circuit passes 0.6mA at
110Vac and 1.2mA at 240Vac. You must ensure that this current, passing through the
snubber, will not hold on low power electrical loads. It is your responsibility as the
installer to ensure that this does not happen. If the snubber circuit is not required, it
can be removed from the relay module (but not the triac) by breaking the PCB track
that runs crosswise adjacent to the edge connectors of the module. Insert the blade of a
screwdriver into one of the two slots that bound it, and twist.
The table below shows the module connections and which functions each module can
perform. The heating output is normally connected to module 1, the cooling output to
module 2 and the alarm output to module 3, although the actual function of each module will
depend upon how your controller has been configured.
Note: Module 1 is connected to terminals 1A and 1B
Module 2 is connected to terminals 2A and 2B
Module 3 is connected to terminals 3A and 3B.
A B
To check which modules are installed in your particular controller, and which functions they
are configured to perform, refer to the ordering code and the wiring information on the
controller side labels.
Communications module
The Communications module position will accept any of the modules listed in Table 1-2
below.
The serial communications can be configured for either Modbus, or EI bisynch protocol.
Module type HA HB HC HD HE HF
Com B A
A
HE
B Series 2000
HF Controller
Com
HD
Local
Earth
Local
Earth A A A
Galvanic HE
B B B Series 2000
Local Isolation HF
Ground Com Controller
Com Barrier Com
Zone 1 HD
Local
Earth Local Earth
Local
Ground
Zone 1 For reasons of safety
Up to 32 S2000 controllers or
Interface Units may do not connect to
Local be included on the network local earth here.
Earth
A HE
E Series 2000
B
HF Controller
F
Area 1 Com HD
D
Note:
All resistors are 220 ohm 1/4W carbon composition.
Local grounds are at equipotential. Where equipotential is not available wire into
separate zones using a galvanic isolator.
Use a repeater (KD845) for more than 32 units.
Line Neutral
1A HA L
Logic heating
output
1B HB N
2A HC
C
Triac cooling O
output M
2B HD VI
M
S
3A HE V+
3B HF V-
- TE10 Solid
State Relay
+
Motor supply
M
1A O HA L Line
D
U
L
RAISE 1B E HB N Neutral
1
Motorised M
O C HC Ground
valve 2A
D O
U
L M
2B E M HD VI
LOWER S
2
RTD/
Pt100
M
HE V+
+
3A O
D +
U T/C PV
L
3B E HF V-
− −
3
Chapter 2 OPERATION
2416
2416
Output 1 on OP1
OP1
Upper readout
Output 2 on OP2
OP2
Output OP1 & When lit, it indicates that the output installed in
OP2 2 OP2 will module position 2 is on. This is normally the cooling
not light output on a temperature controller.
BASIC OPERATION
Switch on the power to the controller. It runs through a self-test sequence for about three
seconds and then shows the temperature, or process value, in the upper readout and the
setpoint in the lower readout. This is called the Home display. It is the one that you will use
most often.
D
Measured temperature,
or process value
D Setpoint
OPERATING MODES
The controller has two basic modes of operation:
• Automatic mode in which the output power is automatically adjusted to maintain the
temperature or process value at the setpoint.
• Manual mode in which you can adjust the output power independently of the setpoint.
You toggle between the modes by pressing the AUTO/MAN button. The displays which
appear in each of these modes are explained in this chapter.
Two other modes are also available:
• Remote Setpoint mode in which the setpoint is generated from an external source.
In this mode the REM light will be on.
• Programmer mode which is explained in Chapter 5, Programmer Operation.
AUTOMATIC MODE
You will normally work with the controller in automatic mode. If the MAN light is on, press
the AUTO/MAN button to select automatic mode. The AUTO light will come on.
Press once
Display units
A single press of the button will flash the display
D units for 0.5 seconds, after which you will be returned to
/
the Home display.
Flashing of the display units may have been disabled in
configuration, in which case a single press will take you
straight to the display shown below.
x2 Press twice
% Output power demand
The % output power demand is displayed in the lower
0 readout. This is a read-only value. You cannot adjust it.
D Press and together to return to the Home display.
Pressing from the Output Power display may access further parameters. These may be in
this scroll list if the ‘Promote’ feature has been used (see Chapter 3, Edit Level). When you
reach the end of this scroll list, pressing will return you to the Home display.
MANUAL MODE
If the AUTO light is on, press the AUTO/MAN button to select manual mode. The MAN
light will come on.
Power on
The Home display
Check that the MAN light is on.
The upper readout shows the measured temperature or
process value. The lower readout shows the % output.
D To adjust the output, press or .
D (Note: If Output Rate Limit has been enabled, then the
lower readout will show the working output. If or
is pressed, it will change to show and allow adjustment of,
the target output.)
Press once
Display units
A single press of will flash the display units for 0.5
D seconds, after which you will be returned to the Home
/
display.
Flashing of the display units may have been disabled in
configuration in which case you a single press will take
you straight to the display shown below.
Press twice
x2
Setpoint
To adjust the setpoint value, press or .
0
D
Press
Pressing from the Output Power display may access further parameters. Other
parameters may be in this scroll list if the ‘Promote’ feature has been used (see Chapter 3,
Edit Level). When you reach the end of this scroll list, pressing will return you to the
Home display.
) List header
A list header can be recognised by the fact that it always shows ‘)O6’ in the lower readout.
The upper readout is the name of the list. In the above example, ) indicates that it is the
Alarm list header. List header displays are read-only.
To step through the list headers press . Depending upon how your controller has been
configured, a single press may momentarily flash the display units. In this case, a double
press will be necessary to take you to the first list header. Continued pressing of will
step through the list headers eventually returning you to the Home display.
Parameter names
In the navigation diagram, (Fig2-6) each box depicts the display for a selected parameter.
The upper readout shows the name of the parameter and the lower readout its value.
The Operator parameter tables later in this chapter list all the parameter names and their
meaning.
The navigation diagram shows all the parameters that can, potentially, be present in the
controller. In practice, only those associated with a particular configuration will appear.
The shaded boxes in the diagram indicate parameters that are hidden in normal operation.
To see all the available parameters, you must select Full access level. For more information
about this, see Chapter 3, Access Levels.
Parameter displays
)
Parameter name
Parameter displays show the controller’s current settings. The layout of parameter displays
is always the same: the upper readout shows the parameter name and the lower readout its
value. Alterable parameters can be changed using or . In the above example, the
parameter mnemonic is ) (indicating Alarm 1, full scale low), and the parameter value
is D.
To change the value of a parameter
First, select the required parameter. The parameter name is shown in the upper readout and
the parameter value in the lower readout.
To change the parameter value, press either or . During adjustment, single presses
change the value by one digit.
Keeping the button pressed speeds up the rate of change.
Two seconds after releasing either button, the display blinks to show that the controller has
accepted the new value.
D 59. 05/! ) 69. 0O ,65
D )O6 )O6 )O6 )O6 )O6 )O6
D 05! 05!D. BBB2 69. !D0 6,
/
D
0 66 #
BBB2 5 6 N.D6
D 59. 0OD
,B 00 # ;
BBB2 5D6 0 D6
96/
D
,0 @ 5,0D8 BBB2 6O ,1D6
#/95 ,.
96/
DO ! =)D8 #@ 6
#/95 D
6A0 @D. #@
5D
5
5,0D5 D D
!D6 !D. #@
#
#
D 96/ 96/
56
D 6!6 6@0 #@ )
)
05!D6
5,0D5 96/ 96/
D 6!6 ) 6 5)D
5)D
6 95
D D
./ D 56 O! D0 0
D ./ D
/96D. !D.
!D. D65 6OD
@. 6@0
./ . 6@0 D: 6D
!D 6@0
=* D D
@ =*
Figure 2-6a Navigation diagram (Part A)
0
D#4 # The shaded boxes are normally hidden in Operator level. To
D see all the available parameters you must select Full level.
See Chapter 3, Access Levels.
055
Figure 2-6b Navigation diagram (Part B)
PARAMETER TABLES
Name Description
Home list Extra parameters may be present if promote feature has been used.
Home Measured value and Setpoint
0 % Output level
0 Target setpoint (if in Manual mode )
,B Auto-man select
,0 Heater current (With PDSIO mode 2)
DO Customer defined identification number
display units. Range = 1 to 9999
,1D6 Minimum ON time of output pulse
Automatic Droop Compensation
(PD control only) 8D5 Not available in 2416
6O
(in display units)
6 5,D0 Remote setpoint value
5,6D6
Integral Time in secs ( )
6 Derivative Time in secs ( 6 ) Remote setpoint trim
5 Manual Reset (%) 6
( ) 56 Ratio setpoint
# Cutback High 6
( ) )/D6 Local setpoint trim
) Cutback Low 6
( ) 0 ) Setpoint 1 low limit
5)D Relative Cool Gain 6
( ) 0 # Setpoint 1 high limit
0
Proportional Band 6
( )
0
D)
6
6
)
0
D# Setpoint 2 high limit
Derivative Time in secs (
5D
Manual Reset (%) 6
(
)
)
)/D) Local trim low Theses
#
Cutback High 6
( )
parameters only
appear if
)
Cutback Low 6
( ) PDSIO is fitted
5)D
Relative Cool Gain 6
Name Description
ALARMS
Alarm annunciation
Alarms are flashed as messages in the Home display. A new alarm is displayed as a double
flash followed by a pause, old (acknowledged) alarms as a single flash followed by a pause.
If there is more than one alarm condition, the display cycles through all the relevant alarm
messages. Table 2-1 and Table 2-2 list all of the possible alarm messages and their meanings.
Alarm acknowledgement and resetting
Pressing both and at the same time will acknowledge any new alarms and reset any
latched alarms.
Alarm modes
Alarms will have been set up to operate in one of several modes, either:
• Non-latching, which means that the alarm will reset automatically when the Process
Value is no longer in the alarm condition.
• Latching, which means that the alarm message will continue to flash even if the alarm
condition no longer exists and will only clear when reset.
• Blocking, which means that the alarm will only become active after it has first entered a
safe state on power-up.
Alarm types
There are two types of alarm: Process alarms and Diagnostic alarms.
Process alarms
These warn that there is a problem with the process which the controller is trying to control.
Alarm Alarm
Display What it means Display What it means
_)5* Load Current Low alarm _#0* Working Setpoint High alarm
* In place of the dash, the first character will indicate the alarm number.
Table 2-1 Process alarms
Diagnostic alarms
These indicate that a fault exists in either the controller or the connected devices.
D5 Electrically Erasable This fault will automatically take you into
Memory Error: Configuration level. Check all of the
The value of an operator, configuration parameters before returning to
or configuration, parameter Operator level. Once in Operator level, check
has been corrupted. all of the operator parameters before resuming
normal operation. If the fault persists, or occurs
frequently, contact Eurotherm Controls.
)D5 Loop Break Check that the heating and cooling circuits are
The feedback loop is open working properly.
circuit.
5D Solid state relay failure This is an alarm generated by feedback from a
Indication that there is a Eurotherm TE10S solid state relay (SSR)
fault in the solid state operating in PDSIO mode 2 - see Chapter 1,
relay. Electrical Installation. It indicates either an
open or short circuit condition in the SSR.
#=D5 Hardware error Check that the correct modules are fitted.
Indication that a module is
of the wrong type, missing,
or faulty.
5,6D Remote input failure. Either Check for open, or short circuit wiring on the
the PDSIO input, or the PDSIO, or remote DC, input.
remote DC input, is open or
short circuit
)))) Out of range low reading Check the value of the input.
#### Out of range high reading Check the value of the input.
55 Error 1: ROM self-test fail Return the controller for repair.
55
Error 2: RAM self-test fail Return the controller for repair.
55 Error 4: Keyboard failure Switch the power off and then on, without
Stuck button, or a button touching any of the controller buttons.
was pressed during power
up.
55 Fault in ‘Digital Filter Chip’ Check connections to the cross board. This is
the PCB that the plug in modules are
connected to.
78D5 Tune Error If any one Check response time of process: check that
stage of the tuning process the sensor has not failed: check that the loop
exceeds 2 hours the tune is not broken. Acknowledge by pressing
error alarm appears ‘page’ key and ‘scroll’ key together
Configuration /. This special level allows access to set up the Yes
fundamental characteristics of the controller.
Press
Password entry
The password is entered from the ‘/’ display.
Enter the password using or . Once the correct password
has been entered, there is a two second delay after which the
lower readout will change to show ‘0’ indicating that access
is now unlocked.
The pass number is set to ‘ ’ when the controller is shipped from
the factory.
Note; A special case exists if the password has been set to ‘’. In
this case access will be permanently unlocked and the lower
readout will always show ‘0’.
Level selection
The ‘!/6/’ display allows you to select the required
access level.
Use and to select from the following display
codes: 05: Operator level
9)): Full level
O6: Edit level
/.: Configuration level
Press
Alternative path if
Configuration password
‘/.’ selected
When the ‘/.’ display appears, you must enter the
Configuration password in order to gain access to this
level. Do this by repeating the password entry procedure
described in the previous section.
The configuration password is set to ‘
’ when the
controller is shipped from the factory. If you need to
change the configuration password, see Chapter 6,
Configuration.
Press
Configuration level
The first display of configuration is shown. See Chapter
6, Configuration, for details of the configuration
parameters.
For instructions on leaving configuration level, see
Chapter 6, Configuration.
EDIT LEVEL
Edit level is used to set which parameters you can view and adjust in Operator level. It also
gives access to the ‘Promote’ feature, which allows you to select and add (‘Promote’) up to
twelve parameters into the Home display list, thereby giving simple access to commonly used
parameters.
Chapter 4 TUNING
Before tuning please read Chapter 2, Operation, to learn how to select and change a
parameter.
WHAT IS TUNING?
In tuning, you match the characteristics of the controller to that of the process being
controlled in order to obtain good control. Good control means:
• Stable ‘straight-line’ control of the temperature at setpoint without fluctuation
• No overshoot, or undershoot, of the temperature setpoint
• Quick response to deviations from the setpoint caused by external disturbances, thereby
restoring the temperature rapidly to the setpoint value.
Tuning involves calculating and setting the value of the parameters listed in Table 4-1. These
parameters appear in the ‘0O’ list.
Proportional 0 The bandwidth, in display units, over which the output power is
band proportioned between minimum and maximum.
Integral time 6O Determines the time taken by the controller to remove steady-
state error signals.
Derivative 6 Determines how strongly the controller will react to the rate-of-
time change of the measured value.
High Cutback # The number of display units, above setpoint, at which the
controller will increase the output power, in order to prevent
undershoot on cool down.
Low cutback ) The number of display units, below setpoint, at which the
controller will cutback the output power, in order to prevent
overshoot on heat up.
Relative cool 5) Only present if cooling has been configured and a module is
gain fitted. Sets the cooling proportional band, which equals the 0
value divided by the 5) value.
AUTOMATIC TUNING
Two automatic tuning procedures are provided in the 2416:
• A one-shot tuner which automatically sets up the initial values of the parameters listed in
Table 4-1 on the previous page.
• Adaptive tuning which continuously monitors the error from setpoint and modifies the
PID values if necessary.
The ‘one-shot’ tuner works by switching the output on and off to induce an oscillation in the
measured value. From the amplitude and period of the oscillation, it calculates the tuning
parameter values.
If the process cannot tolerate full heating or cooling being applied during tuning, then the
level of heating or cooling can be restricted by setting the heating and cooling power limits in
the ‘/0’ list. However, the measured value must oscillate to some degree for the tuner to be
able to calculate values.
A One-shot Tune can be performed at any time, but normally it is performed only once
during the initial commissioning of the process. However, if the process under control
subsequently becomes unstable (because its characteristics have changed), you can re-tune
again for the new conditions.
It is best to start tuning with the process at ambient temperature. This allows the tuner to
calculate more accurately the low cutback and high cutback values which restrict the amount
of overshoot, or undershoot.
How to tune
1. Set the setpoint to the value at which you will normally operate the process.
3. Press the Page and Scroll buttons together to return to the Home display. The display
will flash ‘69.’ to indicate that tuning is in progress.
4. The controller induces an oscillation in the temperature by first turning the heating on,
and then off. The first cycle is not complete until the measured value has reached the
required setpoint.
5. After two cycles of oscillation the tuning is completed and the tuner switches itself off.
6. The controller then calculates the tuning parameters listed in Table 4-1 and resumes
normal control action.
If you want ‘Proportional only’, ‘PD’, or ‘PI’ control, you should set the ‘6O’ or ‘6’
parameters to before commencing the tuning cycle. The tuner will leave them off and
will not calculate a value for them.
Temperature
Setpoint
Time
Adaptive tune
Adaptive tuning is a background algorithm, which continuously monitors the error from
setpoint and analyses the control response during process disturbances. If the algorithm
recognises an oscillatory, or under-damped, response it recalculates the 0, 6O and 6
values.
Adaptive tune is triggered whenever the error from setpoint exceeds a trigger level. This
trigger level is set in the parameter ‘5D6’, which is found in the Autotune list. The value is
in display units. It is automatically set by the controller, but can also be manually
re-adjusted.
MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results, you can tune the controller
manually. There are a number of standard methods for manual tuning. The one described
here is the Ziegler-Nichols method.
1. Set the Integral Time ‘6O’ and the Derivative Time ‘6’ to .
2. Set High Cutback and Low Cutback, ‘#’ and ‘)’, to ‘96/’.
3. Ignore the fact that the temperature may not settle precisely at the setpoint.
4. If the temperature is stable, reduce the proportional band ‘0’ so that the temperature just
starts to oscillate. If the temperature is already oscillating, increase the proportional band
until it just stops oscillating. Allow enough time between each adjustment for the loop to
stabilise. Make a note of the proportional band value ‘B’ and the period of oscillation
‘T’.
5. Set the 0, 6Oand 6 parameter values according to the calculations given in Table 4-2.
Proceed as follows:
1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb
= Hcb = 3 x Pb).
2. Note the level of overshoot, or undershoot, that occurs for large temperature changes (see
the diagrams below).
In example (a) increase ‘)’ by the overshoot value. In example (b) reduce ‘)’ by the
undershoot value.
Example (a)
Temperature
Overshoot Setpoint
Example (b)
Temperature
Setpoint
Undershoot
Time
Where the temperature approaches setpoint from above, you can set ‘#’ in a similar
manner.
‘’ can be repeated as often as you require, but between each adjustment you must allow
time for the temperature to stabilise.
Tune Error
If any one stage of the automatic tuning process is not completed within two hours a
diagnostic alarm will occur. The display shows 68D5 - Tune Error.
This alarm could occur if:
1. The process to be tuned has a very slow response time
2. The sensor has failed or is incorrectly aligned
3. The loop is broken or not responding correctly
Figure 1-8 in Chapter 1 shows how to connect a motorised valve controller. The control is
performed by delivering open, or close, pulses in response to the control demand signal.
The motorised valve algorithm operates in the so-called boundless mode, which does not
require a position feedback potentiometer for control purposes.
The desired control mode is selected in the ‘O.6’ list in configuration level.
The following parameter list will appear in the navigation diagram shown in Chapter 2, if
your controller is configured for motorised valve control.
GAIN SCHEDULING
Gain scheduling is the automatic transfer of control between one set of PID values and
another. In the case of the 2416 controller, this is done at a presettable process value. It is
used for the more difficult to control processes which exhibit large changes in their response
time or sensitivity at, for example, high and low temperatures, or when heating or cooling.
The 2416 has two sets of PID values. You can select the active set from either a parameter in
the PID list, or you can transfer automatically in gain scheduling mode. The transfer is
bumpless and will not disturb the process being controlled.
Step 3: Tuning
You must now set up the two sets of PID values. The values can be manually set, or
automatically tuned as described earlier in this chapter. When tuning automatically you must
tune twice, once above the switching point !D0 and again below the switching point. When
tuning, if the process value is below the transfer point !D0 the calculated values will
automatically be inserted into PID1 set and if the process value is below !D0, the calculated
values will automatically be inserted into PID2 set.
To understand how to select and change parameters in this chapter you will need to have read
Chapter 2, Operation and Chapter 3, Access Levels.
The setpoint is varied by using a setpoint program. Within each 2416 controller there is a
software module, called the programmer, which stores one, or more, such programs and
drives the setpoint according to the selected program. The program is stored as a series of
‘ramp’ and ‘dwell’ segments, as shown below.
Setpoint
Time
Fig 5-1 Setpoint profile
(If the 8-segment programmer is being used, then the information in the next paragraph does not apply.)
In each segment you can define the state of up to two outputs, each of which can be used to
trigger external events. These are called event outputs and can drive either relay, logic, or
triac outputs, depending on the modules installed.
A program is executed either, once, repeated a set number of times, or repeated continuously.
If repeated a set number of times, then the number of cycles must be specified as part of the
program.
PROGRAMMER STATES
Programs has five states:− Reset, Run, Hold, Holdback and End.
Reset In Reset, the programmer is inactive and the Both the RUN and
controller behaves as a standard controller, with the HOLD lights will be
setpoint determined by the value set in the lower off
readout.
Hold In Hold, the program is frozen at its current point. In HOLD light on
this state you can make temporary changes to any
program parameter (for example, a target setpoint, a
dwell time, or the time remaining in the current
segment). Such changes only remain effective
until the program is reset and run again, when
they are overwritten by the stored program
values.
Holdback Holdback indicates that the measured value is HOLD light flashes
deviating from the setpoint by more than a pre-set
amount and that the program is in Hold, waiting for
the process to catch up. See Holdback in the
section on Automatic behaviour later this Chapter.
Press
Program number
This display will only appear on controllers that can hold more
than one program (Models 2416/P4 & 2416/V4). Use or
to select the required program number, from 1 to 4.
Press
Status selection
Use or to select:
• 59. Run program.
• $/) Hold program.
• Program reset.
After two seconds, the lower readout blinks and the chosen state is
now active.
To return to the Home display press and together.
Other parameters
To access the other parameters in the ‘59.’ list, continue to press
. These parameters are shown in the ‘Program run list’ in
Chapter 2, Parameter Tables. They show the current status of the
active program.
Temporary changes
Temporary changes can be made to the parameters in this ‘59.’ list, (for example a setpoint,
ramp rate, or an unelapsed time), by first placing the programmer into ‘$/)’. Such changes
will remain active only for the duration of the segment; the segment parameters will revert to
their original (stored) values whenever the segment is re-executed.
Note: The RUN/HOLD button can be disabled, either when ordering the controller, or
subsequently in configuration. This will force you to operate the program from the ‘59.’ list
all the time. The main advantage of this method is that it will reduce the chance of
accidentally changing the state of a program.
AUTOMATIC BEHAVIOUR
The preceding topics explain how to operate the programmer manually.
The following topics cover aspects of its automatic behaviour: Servo, Holdback and Power
Failure.
Servo
When a program is RUN, the setpoint can start either from the initial controller setpoint, or
from the process value. Whichever it is, the starting point is called the ‘servo’ point and you
set it up in configuration. When the program starts, the transition of the setpoint to its
starting point is called ‘servoing’.
The normal method is to servo to the process value, because this will produce a smooth and
bumpless start to the program. However, if you want to guarantee the time period of the first
segment, you should set the controller to servo to its setpoint.
Holdback
As the setpoint ramps up, or down (or dwells), the measured value may lag behind, or deviate
from, the setpoint by an undesirable amount. ‘Holdback’ is available to freeze the program
at its current state, should this occur. The action of Holdback is the same as a deviation
alarm. It can be enabled, or disabled. Holdback has two parameters - a value and a type.
If the error from the setpoint exceeds the set ‘holdback’ value, then the Holdback feature, if
enabled, will automatically freeze the program at its current point and flash the HOLD light.
When the error comes within the holdback value, the program will resume normal running.
There are four different Holdback types. The choice of type is made by setting a parameter
when creating a program, and may be one of the following:−
‘’ − Disables Holdback − therefore no action is taken.
‘)/’ − Deviation Low Holdback holds the program back when the process variable
deviates below the setpoint by more than the holdback value.
‘#O’ − Deviation High Holdback holds the program back when the process variable
deviates above the setpoint by more than the holdback value.
‘.’ − Deviation Band Holdback is a combination of the two. It holds the program back
when the process variable deviates either above, or below, the setpoint by more
than the holdback value.
There is a single Holdback Value which applies to the whole program. However, the
Holdback type and whether or not it is enabled, can be applied to the program as a whole, or
individually in each segment.
Power failure
If power is lost and then restored, while a program is running, the behaviour of the
programmer is determined by the setting of the parameter ‘0=5D’ Power fail strategy in
Programmer configuration. This can have one of three settings:− /.6 (Continue), 5,0D
(Ramp from PV), or 56 (Reset).
If ‘/.6’ is selected, then when power is restored the program continues from where it was
interrupted when power was lost. All parameters, such as the setpoint and time remaining in
the active segment, will be restored to their power-down values. For applications that need to
bring the measured process value to the setpoint as soon as possible, this is the best strategy.
If ‘5,0D’ is selected, then when power is restored the setpoint starts at (‘servos to’) the
current measured value, and then ramps to the target setpoint of the active segment at the last
ramp rate used by the program. This strategy provides a smoother recovery. The two
diagrams below illustrate the respective responses, Fig5-2 if power fails during a dwell
segment and Fig5-3 if it fails during a ramp segment.
Segment dwell
Setpoint Setpoint
time = t1 + t2
Target setpoint
t1 t2
Power off
Power on
Power off
Power on -
Servo to new PV level
Figure 5-2 Continue after a power fail Figure 5-3 Ramp back after a power fail
Press
Number of programs
Use or to select:
• ./.: Disable built-in 8-segment programmer
• : Enable built-in 8-segment programmer
For 16-segment programmers:
• ./.: no programs
• : One stored program
• : Four stored programs
Press
Holdback Strategy
# Use or to select:
! • !: Holdback type to be set in each segment
• 05/!: Holdback type to be set for the whole program
Press
Servo type
5:/ Use or to select:
• 6/D0; Servo to PV
6/D1; • 6/D0 Servo to SP
Press
Press
Program number
This display only appears on the four-program controllers.
Use or to select the number of the program which you
wish to modify (from 1 to 4).
Press
Holdback type
[Only appears when Holdback has been selected for the whole
program.]
Use or to select:
• Holdback disabled
• )/ Deviation Low Holdback
• #O Deviation High Holdback.
• . Deviation Band Holdback
Press
Holdback value
Use or to set a value.
Ramp units
Use or to select:
•
• ,O.
• #/95
Press
Dwell units
Use or to select:
•
• ,O.
• #/95
Press
Press
Segment number
Use or to select the number, [1 to 8 (8-seg programmer)], or
1 to 16.
The parameters that follow ‘!D.’ set up the characteristics of
the individually-selected segment number. By defining the
characteristics of each segment of the program, you define the
whole program.
Press
Segment type
Select the segment type using or :
• 5,0D5 Ramp to a new setpoint at a set rate
• 5,0D6 Ramp to a new setpoint in a set time
• =* Dwell for a set time
• 60 Step to a new setpoint
• )) Call another program as a subroutine
(only available in 4-program controllers)
• . Make this segment end of program.
Press
The parameters that follow ‘6@0’ depend on the type of segment selected.
Parameter Segment type selected
5,0D5 5,0D6 =* 60 )) .
# 9 9 9 9
6!6 9 9 9
56 9
95 9 9
05!D. 9
/96. 9 9 9 9 9
@D. 9
=* 9
.D6 9
0=5 9
Table 5-3 Parameters that follow segment 6@0
Holdback type
# [Only appears when Holdback per segment has been selected.]
Use or to select:
. • : Holdback disabled
• )/: Deviation Low Holdback
• #O: Deviation High Holdback
• .: Deviation Band Holdback
Press
Target setpoint
6"6 Target setpoint for ‘5,0D5’, ‘5,0D6’ or ‘60’ segments.
Set the target setpoint using or .
Ramp rate
Ramp rate for ‘56’ segments.
Using or , set a value for the ramp rate, ranging from 0.00
to 999.9 (the units will be the ramp units (‘5,0D8’) set earlier in
this sequence).
Press
Duration time
Time for a ‘=*’ segment, or time to target for a ‘5,0D6’
segment.
Set the time using or . You have set the units earlier in
this sequence.
Press
Press
Press
Press
Press
Press
Chapter 6 CONFIGURATION
This chapter consists of six topics:
WARNING
Configuration is protected by a password and should only be carried out by a qualified
person, authorised to do so. Incorrect configuration could result in damage to the
process being controlled and/or personal injury. It is the responsibility of the person
commissioning the process to ensure that the configuration is correct.
Password entry
When the ‘/.’ display appears, you must enter the
/. Configuration password (which is a number) in order to
/. gain access to Configuration level.
Enter the password using the or buttons.
The configuration password is set to ‘
’ when the
controller is shipped from the factory.
Parameter names
Each box in the navigation diagram shows the display for a particular parameter. The upper
readout shows the name of the parameter and the lower readout its value. For a definition of
each parameter, see the Configuration Parameter Tables at the end of this chapter. To change
the value of a selected parameter, use the and buttons.
The navigation diagram shows all the lists headers and parameters that can, potentially, be
present in the controller. In practice, those actually present will vary according to the
particular configuration choices you make.
?O6
./ Use or to select ‘@’. After a two-second
delay, the display will blank then revert to the Home
display in Operator level.
O.6 0; O0 0 ) 04! #
/. /. /. /. /. /. /.
86 ) 0 ?O6
/. /. /. /. /. /. ./
O O O O. 5) D0
5)A 5)A 5)A D ./.
9. 9. 9. 8)D 8) .D0
#6 ) N" D ./
O.
D
8)D
D
Note:
1. 8-point custom linearisation. Only appears when
‘ O0B/.’ has ‘ O.16 ,;D
’=‘ ’, or ‘,D ;D
’, or ‘ ’.
2. The navigation diagram shows typical parameters,
but is dependant upon the exact configuration of the
instrument. The following sheets show the full list of
parameters.
Notes:
1. Pyrometer Emmisivity
Controllers which are specifically supplied for pyrometer inputs (not Exergen K80), have
the curve downloaded in the Custom Input. The parameter, ,O, Pyrometer
Emmisivity, appears in the Input List on page 2-15. This parameter is also now correctly
adjusted.
2. Range
If a decimal point was configured, negative display and setpoint ranges were limited to -
99.9 in previous software versions. The range has been increased to -199.9 by combining
the negative sign with the figure one. This allows Setpoints, Process Variables, Alarm
Setpoints and Programmers to be set to -199.9.
O0 Input configuration
O.06 Input type %D6 J thermocouple
(D6 K thermocouple
)D6 L thermocouple
5D6 R thermocouple (Pt/Pt13%Rh)
D6 B thermocouple (Pt30%Rh/Pt6%Rh)
.D6 N thermocouple
6D6 T thermocouple
D6 S thermocouple (Pt/Pt10%Rh)
0)
PL 2 thermocouple
D6 Custom downloaded t/c (default = type C)
56 100Ω platinum resistance thermometer
,; Linear millivolt
:/)6 Linear voltage
, Linear milliamps
5 ; Square root volts
5 Square root milliamps
* See ‘96’ List. ,;D 8-point millivolt custom linearisation*
;D 8-point Voltage custom linearisation*
,D 8-point milliamp custom linearisation*
% Cold Junction No cold junction compensation
Compensation 96/ Automatic internal compensation
// o
0 C external reference
/ o
45 C external reference
o
50 C external reference
O,1 Sensor Break Impedance Disabled (applies to any input)
Caution:
If sensor break is disabled the
controller will not detect open circuit
faults
96/ Factory set
#O Impedance of input > 15KΩ
#OD#O Impedance of input > 30KΩ
Linear Input Scaling − The next four parameters only appear if a linear input is chosen.
O.0D# ;)D#
Input value high
0 Setpoint configuration
.0 Number of setpoints
, , Select number of setpoints available
5,D65 Remote Tracking Disable
65 Local setpoint tracks remote setpoint
,D65 Manual Track Disable
65 Local setpoint tracks PV when in manual
05D65 Programmer Track Disable
65 Local setpoint tracks programmer SP
5,0D8 Setpoint rate limit units 0 Per second
0,O. Per minute
0#5 Per hour
5,6 Remote setpoint configuration ./. Disable
0 Remote setpoint
)/D6 Remote setpoint + local trim
5,6D6 Remote trim + local setpoint
)/ .//@
PV Deviation low
Blocking
)5 Load Current low
)
Alarm 2 Type see Table A #5 Load Current high
)6$ Latching .//@/:.6/,.* )
Not usable on 2416
)/ .//@ #
Not usable on 2416
)0
Blocking
)
Alarm 3 Type see Table A
#0
Working Output low
Module 1 configuration
O Identity of module installed 5)A Relay output
D0 Non-isolated DC output
)/! Logic/PDSIO output
5 Triac output
minimum output − ‘ ’
;)D# VAL.H
% PID demand signal giving
maximum output − ‘ 96D#’
96D) Minimum average power
96D#
VAL.L Electrical
Output
Out.L Out.H Maximum average power
. Sense of output ./5 Normal (output energises
(Only if ‘9.’ = ‘N!’) when TRUE, e.g program
events)
O.: Inverted (output de-energises
when TRUE, e.g. alarms)
When ‘ .’ appears, then further parameters are available. See the table on the next
page.
./5
Digital
OR
N! SEnS
Events
O.: Output
Module
Figure 6-2 Combining several digital events on to one output
Module 2 configuration
As per module 1 configuration, but excluding the ‘ 5D ’, ‘5D
’ options on a logic output.
Module 3 configuration
As per module 2 configuration.
;)D ;)D
Linearisation Value representing O.
O. ;)D
;)D Electrical
Custom input 8
;)D O. O.
O.
Input
Linearisation Value representing O.
Note:
1. Custom Linearisation is only available when ‘O1B /. list has ‘O.16’
set to ‘,;D’, or ‘,D’, or ‘;D’
2. Custom curves must be continuously increasing or decreasing in value and
input
) Calibration
INPUT CALIBRATION
For ‘)’ = ‘0;’, or ‘0;D
’, the following parameters apply.
0; PV Calibration Value N) Idle
,:D) Select 0mV as the calibration point
,:D# Select 50mV as the calibration point
; Select 0Volt as the calibration point
1. Select calibration value ; Select 10V as the calibration point
2. Apply specified input % o
Select 0 C CJC calibration point
3. Press to step to ‘!’ 56 Select 400Ω as the calibration point
#N High impedance: 0Volt cal’n point
#N D High impedance: 1.0 Volt cal’n point
See Note below. 6 Restore factory calibration
! Start calibration ./ Waiting to calibrate PV point
Select ‘@’ with or @ Start calibration
Wait for calibration to 9A Busy calibrating
complete. /. PV input calibration completed
N) Calibration failed
DC Output Calibration
The following parameters apply to DC output modules ie for 5) = D#O to
D)/
)D# Output Calibration High
= Factory set calibration.
Trim value until output = 9V, or
18mA
)D) Output Calibration Low
= Factory set calibration.
Trim value until output = 1V, or
2mA
User calibration
8) User calibration enable Yes/no
16 D) Low calibration point for Input 1 The factory calibration point at which the low
point offset was performed.
16 D# High calibration point for Input 1 The factory calibration point at which the high
point offset was performed.
D) Offset Low for Input 1 Calculated offset, in display units.
D# Offset High for Input 1 Calculated offset, in display units.
To understand how to select and change parameters in this chapter you will need to have read
Chapter 2 - Operation, Chapter 3- Access Levels and Chapter 6 - Configuration.
User calibration works by introducing a single point, or two-point, offset onto the factory set
calibration.
Exit configuration
Use or to select ‘@’ to return to Operator level.
OFFSET CALIBRATION
Offset calibration is used to apply a single fixed offset over the full display range of the
controller.
Displayed Value
Factory Calibration
Fixed Offset
Input
Press
Set Offset 1
D Use
(PV1).
or to set the offset value of Process Value 1
Press
TWO-POINT CALIBRATION
The previous section described how to apply an offset, or trim, calibration, which applies a
fixed offset over the full display range of the controller. A two-point calibration is used to
calibrate the controller at two points and applies a straight line between them. Any readings
above, or below, the two calibration points will be an extension of this straight line. For this
reason it is best to calibrate with the two points as far apart as possible.
High-point calibration x
Low-point calibration x
Calibration low-point value
Input
Offset introduced
Proceed as follows:
1. Decide upon the low and high points at which you wish to calibrate.
2. Perform a two point calibration in the manner described below.
Press
&
This is the display for adjusting the Low Calibration point of
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.
Make sure that the calibration source is connected to the
terminals of Input 1, switched on and feeding a signal to the
controller. It should be set to the desired low-point calibration
value. If the lower readout does not show this value, then use
/ to adjust the reading to the required value.
x2 Press twice.
Calibration type
) ‘85’ was selected for the Low-point Calibration, and has
remained selected.
85
Press
Press
&
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.
Feed the desired high-point calibration signal to the controller,
from the calibration source. If the lower readout does not
show this value, then use / to adjust the reading to the
required value.
Note: The value of each of the parameters in the above table may also be altered by using
the / buttons.
Appendix A
UNDERSTANDING THE ORDERING CODE
The 2416 controller has a modular hardware construction, which accepts up to three plug-in
Input/Output modules and one communications module, to satisfy a wide range of control
requirements.
The ordering code is in two parts. The hardware coding and an optional configuration
coding. The hardware coding specifies the basic build of the controller and the plug-in
modules that are fitted.
Part 1: Part 2:
Hardware coding Configuration
Plug-in
Basic build I/O modules
2416
The controller may have been ordered with just the hardware build specified, or with
configuration included. This is indicated by the ordering code on the side of the controller.
Plug-in modules
continued
Module 2 Module 3 Comms 1 Manual
RC RH MB ENG
Hardware
coding Part 2: Configuration
Sensor Range Range Units Options
input min max
See note 2
K 0 1000 C CF
Notes:
1. PDSIO is a proprietary technique developed by Eurotherm for bi-directional
transmission of analogue and digital data between instruments.
Mode 1: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
a general load fault alarm.
Mode 2: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
load current and two alarms: solid state relay failure and heater circuit failure.
2. Range min and Range max: Thermocouple and RTD sensor inputs will always display
over the full operating range shown in Sensor input table. For these inputs, the values
entered here are the low and high setpoint limits. For process inputs, the values are the
display scaling. corresponding to the minimum and maximum input values.
This controller is intended for industrial temperature and process control applications when it
will meet the requirements of the European Directives on Safety and EMC. Use in other
applications, or failure to observe the installation instructions of this handbook may impair
the safety or EMC protection provided by the controller. It is the responsibility of the
installer to ensure the safety and EMC of any particular installation.
Safety
This controller complies with the European Low Voltage Directive 73/23/EEC, amended by
93/68/EEC, by the application of the safety standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection requirements of the EMC Directive
89/336/EEC, amended by 93/68/EEC, by the application of a Technical Construction File.
This instrument satisfies the general requirements of an industrial environment as described
by EN 50081-2 and EN 50082-2. For more information on product compliance refer to the
Technical Construction File.
Safety Symbols
Various symbols are used on the instrument, they have the following meaning:
Caution, (refer to the Functional earth
! accompanying documents) (ground) terminal
The functional earth connection is not required for safety purposes but to ground RFI filters.
Personnel
Installation must only be carried out by qualified personnel.
Enclosure of live parts
To prevent hands or metal tools touching parts that may be electrically live, the controller
must be installed in an enclosure.
Caution: Live sensors
All isolated inputs and outputs have reinforced insulation to provide protection against
electric shock. The non-isolated dc, logic and PDSIO outputs are all electrically connected to
the main process variable input, (thermocouple etc.). If the temperature sensor is connected
directly to an electrical heating element then these non-isolated inputs and outputs will also
be live. The controller is designed to operate under these conditions. However you must
ensure that this will not damage other equipment connected to these inputs and outputs and
that service personnel do not touch connections to these i/o while they are live. With a live
sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs
and outputs must be mains rated.
Wiring
It is important to connect the controller in accordance with the wiring data given in this
handbook. Take particular care not to connect AC supplies to the low voltage sensor input or
DC or logic inputs and output. Only use copper conductors for connections (except
thermocouple inputs) and ensurethat the wiring installations comply with all local wiring
regulations. For example in the UK use the latest version of the IEE wiring regulations,
(BS7671). In the USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should
be in close proximity to the controller, within easy reach of the operator and marked as the
disconnecting device for the instrument.
Earth leakage current
Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the
design of an installation of multiple controllers protected by Residual Current Device, (RCD)
or Ground Fault Detector, (GFD) type circuit breakers.
Overcurrent protection
To protect the internal PCB tracking within the controller against excess currents, the AC
power supply to the controller and power outputs must be wired through the fuse or circuit
breaker specified in the technical specification.
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not
exceed 264Vac:
• line or neutral to any other connection;
• relay output to logic or dc sensor connections;
• any connection to ground.
The controller should not be wired to a three phase supply with an unearthed star connection.
Under fault conditions such a supply could rise above 264Vac with respect to ground and the
product would not be safe.
Voltage transients across the power supply connections, and between the power supply and
ground, must not exceed 2.5kV. Where occasional voltage transients over 2.5kV are
expected or measured, the power installation to both the instrument supply and load circuits
should include a transient limiting device.
These units will typically include gas discharge tubes and metal oxide varistors that limit and
control voltage transients on the supply line due to lightning strikes or inductive load
switching. Devices are available in a range of energy ratings and should be selected to suit
conditions at the installation.
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the controller is
mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a
suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of
the cabinet. Where condensation is likely, for example at low temperatures, include a
thermostatically controlled heater in the cabinet.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part of
the system should fail. In temperature control applications the primary danger is that the
heating will remain constantly on. Apart from spoiling the product, this could damage any
process machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process;
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on;
• an external valve or contactor sticking in the heating condition;
• the controller setpoint set too high.
TECHNICAL SPECIFICATION
Input
Range +100mV and 0 to 10Vdc (auto ranging)
Sample Rate 9Hz (110mS)
Resolution <1µV for +100mV range, <0.2mV for 10Vdc range
o
Linearity Better than 0.2 C
o
Calibration accuracy The greater of 0.25% of reading or + 1 C or +1LSD
User calibration Low and high offsets can be applied
Input filter Off to 999.9 secs
Thermocouple types Refer to the ordering code sensor input table
Cold junction >30 to 1 rejection of ambient temperature changes in automatic
TM
compensation mode. Uses INSTANT ACCURACY cold junction sensing
technology to eliminate warm up drift and to respond quickly to
ambient temperature changes.
o
External references 0, 45, and 50 C
RTD/PT100 input 3-wire, Pt100 DIN43750. Bulb current 0.3mA. Up to 22Ω in each
lead without error
Digital Outputs
Relay rating Min: 12V, 100mAdc. Max:2A, 264Vac resistive
Application: heating, cooling, alarms or program event
Single logic output 18Vdc, 20mA. This output is not isolated from the main process
value input. Application: heating, cooling, alarms or program event
Digital o/p functions As per the ordering code
Triac rating 1A, 30 to 264Vac resistive (isolated)
Analogue outputs
Range Scaleable between 0-10Vdc
0-20mA (non-isolated)
Analogue output Refer to ordering code
functions
Control functions
Control modes PID or PI with overshoot inhibition, PD, PI, P, or On/Off, or
motorised valve control
Cooling algorithms Linear, water (non-linear), fan (min on time), oil
Tuning One shot (automatic tune of PID and overshoot inhibition
parameters) and continuous adaptive tuning. Automatic calculation
of of manual reset value when using PD control.
Auto/manual control Bumpless transfer or forced manual output
Setpoint rate limit 0.00 to 999.9 display units per second, minutes or hour
Alarms
Number of alarms Four
Alarm types Absolute high or low. Deviation band, deviation high, deviation
low. Rate of change
Alarm modes Latching or non-latching. Blocking. Energised or de-energised in
alarm
Setpoint programming
Number of programs One or four
Segments per 16
program
Event outputs Up to two
PDSIO
Slave input (isolated) Remote setpoint input with holdback to master
Master output Isolated from main PV. Retransmission of setpoint, process value
or output
General
Display Dual, 4 digit x 7 segment LED. Up to two decimal places
Supply 85 to 264Vac, 48 to 62 Hz, 10 W max OR
24Vdc or ac -15%, +20%. 10W max
o
Operating ambient 0 to 55 C and 5 to 90% RH non-condensing
o
Storage temperature -10 to +70 C
Panel sealing IP65
Dimensions 48mm wide x 48mm high x 150mm deep
Weight 250g
EMC standards EN50081-2 & EN 50082-2 generic standards for industrial
environments
Safety standards Meets EN61010, installation category II (voltage transients must not
exceed 2.5kV), pollution degree 2
Atmospheres Not suitable for use above 2000m or in explosive or corrosive
atmospheres. Electrically conductive pollution must be excluded
from the cabinet in which this controller is mounted
UK SALES OFFICE
Eurotherm Controls Limited
Faraday Close, Durrington
Worthing
West Sussex BN13 3PL
Telephone Sales: (01903) 695888
Technical: (01903) 695777
Service: (01903) 695444
Fax (01903) 695666
email http://www.eurotherm.co.uk
1. Mode 1
Detects if there is a break in the heater circuit. This includes heater or SSR open circuit. A
single Load Failure alarm message is displayed on the lower readout of the controller.
2. Mode 2
Provides the following:-
Display of true RMS load current On the Displays the true RMS current in the ON
lower readout of the controller state to the load.
Low current alarm Analogous to Partial Provides advanced warning of failure of
Load Failure (PLF) supplied in some one or more heaters in parallel
Eurotherm SSRs
High current alarm Activated when the Typically used where element bunching
heater exceeds a set limit may occur
SSR short circuit This will apply full power to the heaters
which could result in an over temperature
condition. This alarm provides early
warning.
Heater failure Indicates open circuit load conditions
1.
Hardware Required
L N
Controller
Fuse 2A(T)
Alternative current regulator
+ L arrangements:-
1A
- C N
1B
O The Eurotherm TE10/PDS2 contains
M integral power regulator and intelligent
M
S Heater PDCTX
1 + power fuse The PDCTX can be supplied separately for
V+
PV (load use with any SSR or logic thyristor unit as
V- shown in the diagram below.
- dependent)
The output drive capability of the PDCTX is
5V at 7mA maximum
To logic output
To L 1A & 1B
This
represents
a single
- +
turn PDCTX
L N through the Intelligent
TE10 CT Current
Solid Transformer
State
Relay Logic input
SSR
To
- + Heater
- +
T/C
Heater
WARNING!
Take care that the controller is correctly wired for the mode of operation which is
configured. Failure to do so may be hazardous in some situations.
OPERATION
To Read Load Current (mode 2 only)
Display Modes
SSR RMS On State Current
This is the default state when high or low current alarms are configured. The load current
displayed is the steady state true rms current measured during the ON period.
The minimum on times are:-
Mode 2 0.1second
or To select the
Press button indicates the alarm diagnostic alarm
number; parameter found
until the desired BBB indicates the under the Alarm List
alarm number is alarm type:- header
displayed e.g. )5 or #5
BBB
Press or
The alarm trip level
is set to 123
to adjust the alarm
trip level
@ Alarms to be
displayed in the
Press or lower readout of the
to select @ HOME display
RELAY OUTPUTS
Any plug in module can be used for alarms provided they are not already being used for
another purpose , such as control. Any one or more alarms can be attached to an output,
which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operating
external beacons or audible devices.
Press to show
9. This shows the
function of module
9.
Press or
to show 5 or
5 The module function
is set to PDSIO
5
as required. mode 1
87D#
Press to show This is the maximum
87D# output power
D To set the max
output power to 100
Press or
to show D
Press or
to show ./5
Note:- The above alarms are known as SOFT ALARMS because they are indication
only.
Alarms Connected to a
./5 Relay Output
3A
Soft N!
Alarms OR .
O.: Output
Module 3B
Press until
)D#O is displayed )D#O
Press or
to change the
scaling factor
Note 1:-
Minimum Resolvable Current
TE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10.
PDCTX 4A RMS for a single turn through the PDCTX
Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase
the number of turns through the PDCTX and adjust the scaling factor to compensate.
For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to
25 as shown in the table below.
Scalar = 100/N Where N = Turns through PDCTX
N Scalar N Scalar
1 100 5 20
2 50 10 10
4 25