Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

2416 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 104

Installation and Operation Handbook Contents

MODEL 2416 PID CONTROLLER


INSTALLATION AND OPERATION HANDBOOK

Contents Page

Chapter 1 INSTALLATION .................................................................1-1


Chapter 2 OPERATION ......................................................................2-1
Chapter 3 ACCESS LEVELS..............................................................3-1

Chapter 4 TUNING..............................................................................4-1
Chapter 5 PROGRAMMER OPERATION ..........................................5-1

Chapter 6 CONFIGURATION .............................................................6-1


Chapter 7 USER CALIBRATION ........................................................7-1

Appendix A UNDERSTANDING THE ORDERING CODE ................... A-1

Appendix B SAFETY and EMC INFORMATION ................................. B-1


Appendix C TECHNICAL SPECIFICATION ......................................... C-1

Appendix D UK OFFICE ADDRESSES ................................................ D-1


Appendix E LOAD CURRENT MONITORING AND DIAGNOSTICS... E-1

“This product is covered by one or more of the following US Patents:

5,484,206; Additional patents pending.

PDSIO and INSTANT ACCURACY are trademarks of Eurotherm.”

Issue 8 Jul-99 Applies to 2416 controller software version 3.0 i


Installation and Operation Handbook Installation

Chapter 1 INSTALLATION
The 2416 controller is a versatile, high stability temperature or process controller, with self
and adaptive tuning, in 1/16 DIN size (48 x 48mm). It has a modular hardware construction,
which accepts up to three plug-in output modules and one communications module, to satisfy
a wide range of control requirements. All 2416 controllers have a basic 8-segment
programmer built-in as standard.

The 2416 is available as either a:


• standard controller: Model 2416/CC
• setpoint programming controller: Models 2416/CP and 2416/P4
• motorised valve controller: Model 2416/VC
• setpoint programming motorised valve controller: Models 2416/VP and 2416/V4

This chapter consists of two parts:


• MECHANICAL INSTALLATION
• ELECTRICAL INSTALLATION.

Before proceeding, please read the chapter called, Safety and EMC Information.

Terminal covers
Sleeve

Ratchets

Display screen

Label

Panel retaining clips


Latching ears Panel sealing gasket

Figure 1-1 2416 1/16 DIN controller

2416 Controller 1-1


Installation Installation and Operation Handbook

WARNING
You must ensure that the controller is correctly configured for your application.
Incorrect configuration could result in damage to the process being controlled, and/or
personal injury. It is your responsibility as the installer to ensure that the configuration
is correct. The controller may either have been configured when ordered, or may need
configuring now. See Chapter 6, Configuration.

MECHANICAL INSTALLATION

Controller labels
The labels on the sides of the controller identify the ordering code, the serial number, and the
wiring connections.

Appendix A, Understanding the Ordering Code explains the hardware and software
configuration of your particular controller.

Outline dimensions

48mm 150mm
1.89in 5.91in
2416
2416

OP1
OP1

OP2
48mm OP2

SP2
SP2
1.89in REM
REM

AUTO RUN
MAN HOLD

IP65, NEMA 4X sealing gasket

Figure 1-2 Outline dimensions

The electronic assembly of the controller plugs into a rigid plastic sleeve, which in turn fits
into the standard DIN size panel cut-out shown in Figure 1-3.

1-2 2416 Controller


Installation and Operation Handbook Installation

Panel cut-out and recommended minimum spacing of controllers

Panel cut-out
-0
45 x 45mm +0.6

-0
1.77 x 1.77in +0.02

38mm (1.5in)
10mm (0.4in)

Figure 1-3 Panel cut-outs and minimum spacing

To install the controller

1. Prepare the control panel cut-out to the size shown in Figure 1-3.

2. Insert the controller through the panel cut-out.

3. Spring the upper and lower panel retaining clips into place. Secure the controller in
position by holding it level and pushing both retaining clips forward.

4. Peel off the plastic film protecting the front of the indicator.

Note: If the panel retaining clips subsequently need removing, in order to extract the
controller from the control panel, they can be unhooked from the side with either your fingers
or a screwdriver.

Unplugging and plugging-in the controller

If required, the controller can be unplugged from its sleeve by easing the latching ears
outwards and pulling it forward out of the sleeve. When plugging the controller back into its
sleeve, ensure that the latching ears click into place in order to secure the IP65 sealing.

2416 Controller 1-3


Installation Installation and Operation Handbook

ELECTRICAL INSTALLATION
This section consists of five topics:
• Rear terminal layout
• Fixed connections
• Plug-in module connections
• Typical wiring diagram
• Motorised valve connections
All electrical connections are made to the screw terminals at the rear of the controller. These
2
screw terminals accept wire sizes from 0.5 to 2.5mm (14 to 22 awg) and should be tightened
to a torque of 0.4 Nm (3.5 lb in). If you wish to use crimp connectors, we recommend AMP
2
part number 16500. These accept wire sizes from 0.5 to 1.5 mm (16 to 22 AWG).

REAR TERMINAL LAYOUT


The terminals are arranged in three columns at the rear of the controller. Each column is
protected by a clear plastic hinged cover to prevent hands or metal making accidental contact
with live wires. Viewed from the rear and with the controller upright, the right-hand column
carries the connections for the power supply and sensor input. The other two columns carry
the connections to the plug-in modules. The connections depend upon the type of module
installed, if any. To discover which plug-in modules are installed in your controller, please
refer to the ordering code and wiring data on the labels on the sides of the controller.
The rear terminal layout is shown below.
Note: The plug-in sleeve supplied with high voltage controllers are keyed to prevent a low
voltage unit being inserted into them.

+ 20 − 29Vac/dc
M 24
O L Line
1A
D
HA
N
− Neutral
85 to 264Vac
U
L Low voltage supply
1B E HB N Neutral
1
M
2A O HC Ground*
D C
U O
L M
2B E M HD VI
2 S
M +
3A O HE V+
D +
U T/C PV
L RTD/
3B E HF V− Pt100 −
3 −

Figure 1-4 Rear terminal layout


*The ground connection is provided as a return for internal EMC filters. It is not required
for safety purposes, but must be connected in order to satisfy EMC requirements.

1-4 2416 Controller


Installation and Operation Handbook Installation

FIXED CONNECTIONS
The power supply and sensor inputs are always wired to the same fixed positions whatever
plug-in modules are installed.

Power supply connections


These are as shown in Figure 1-4.

Sensor input connections


The diagrams below show the connections for the various types of input.
The input will have been configured in accordance with the ordering code.

Thermocouple Resistance mA input Volts or mV inputs


thermometer

VI VI VI VI

2.49Ω +
V+ V+ V+ current V+
sense PV
V- V- V- resistor V- -

Fig 1-5 Sensor input connections

2416 Controller 1-5


Installation Installation and Operation Handbook

PLUG-IN MODULE CONNECTIONS


In Figure 1-4, Modules 1, 2 and 3, and Comms are plug-in modules.
Modules 1, 2 and 3
Module positions 1, 2 and 3 each have two terminals. They will accept four types of module:
Relay, Logic (non-isolated), Triac, and DC (non-isolated) output.

Collectively, these can be configured to operate in six different ways:


Heating control
Cooling control
Alarm output
Program event output
PDSIO mode 1*, which provides logic heating using a Eurotherm TE10S solid state relay
with feedback of a load failure alarm.
PDSIO mode 2*, which provides logic heating using a Eurotherm TE10S solid state
relay, with feedback of the load current reading and two alarms: solid state relay failure
and heater circuit failure.

* PDSIO stands for ‘Pulse Density Signalling Input/Output’. This is a proprietary technique
developed by Eurotherm for bi-directional transmission of analogue and digital data over a
simple 2-wire connection.

Snubbers
The relay and triac modules have an internal 15nF/100Ω ‘snubber’ connected across their
output, which is used to prolong contact life and to suppress interference when switching
inductive loads, such as mechanical contactors and solenoid valves.

WARNING
When the relay contact is open or the triac is off, the snubber circuit passes 0.6mA at
110Vac and 1.2mA at 240Vac. You must ensure that this current, passing through the
snubber, will not hold on low power electrical loads. It is your responsibility as the
installer to ensure that this does not happen. If the snubber circuit is not required, it
can be removed from the relay module (but not the triac) by breaking the PCB track
that runs crosswise adjacent to the edge connectors of the module. Insert the blade of a
screwdriver into one of the two slots that bound it, and twist.

The table below shows the module connections and which functions each module can
perform. The heating output is normally connected to module 1, the cooling output to
module 2 and the alarm output to module 3, although the actual function of each module will
depend upon how your controller has been configured.
Note: Module 1 is connected to terminals 1A and 1B
Module 2 is connected to terminals 2A and 2B
Module 3 is connected to terminals 3A and 3B.

1-6 2416 Controller


Installation and Operation Handbook Installation

Module type Terminal identity Possible functions

A B

Relay: 2-pin Heating, Cooling, or Alarm output


Program event output
(2A, 264 Vac max.) Valve raise or lower

Logic: non-isolated + − Heating, Cooling, or Alarm output


PDSIO mode 1,
(18Vdc at 20mA) PDSIO mode 2,
Program event

Triac Heating, Cooling,


Program event
(1A, 30 to 264Vac) Line Load Valve raise or lower
DC control: non-isolated Heating, Cooling.
+ − Retransmission of PV, setpoint or
(10Vdc, 20mA max.)
control output

Table 1-1 Module 1, 2 and 3 connections

To check which modules are installed in your particular controller, and which functions they
are configured to perform, refer to the ordering code and the wiring information on the
controller side labels.
Communications module
The Communications module position will accept any of the modules listed in Table 1-2
below.
The serial communications can be configured for either Modbus, or EI bisynch protocol.

Communications module Terminal identity (COMMS)

Module type HA HB HC HD HE HF

2-wire EIA-485 serial − − − Common A (+) B (−)


communications

EIA-232 serial − − − Common Rx Tx


communications

4-wire EIA-485 serial − A′ B′ Common


A B
communications (Rx+) (Rx−) (Tx+) (Tx−)

PDSIO Setpoint − − − − Signal Common


retransmission

PDSIO remote setpoint input -- -- -- --


Signal Common

Table 1-2 Communications connections

2416 Controller 1-7


Installation Installation and Operation Handbook

Wiring of 2-wire EIA-485 serial communications link


PC

2-wire EIA-485 is a connection which allows up to 32


Com TX RX controllers to be multi-dropped from a single communications
Local link over a distance of up to 1.2Km. To ensure reliable
Earth operation of the communications link, (without data
corruption due to noise or line reflections) the connections
232 between the controller should be made using a twisted pair of
wires inside a screened cable with the connections
Local terminated with resistors in the manner shown in this
Earth diagram. This diagram also shows the use of a Eurotherm
Com RX TX KD485 converter to connect the EIA-485 link into a standard
Eurotherm Universal EIA-232 computer port.
Communications Interface
KD485

Com B A

A
HE
B Series 2000
HF Controller
Com
HD
Local
Earth

Local Local Local


Ground
Ground Ground
Zone 1
Zone 1 Zone 2

Local
Earth A A A
Galvanic HE
B B B Series 2000
Local Isolation HF
Ground Com Controller
Com Barrier Com
Zone 1 HD

Local
Earth Local Earth

Local
Ground
Zone 1 For reasons of safety
Up to 32 S2000 controllers or
Interface Units may do not connect to
Local be included on the network local earth here.
Earth
A HE
E Series 2000
B
HF Controller
F
Area 1 Com HD
D

Note:
All resistors are 220 ohm 1/4W carbon composition.
Local grounds are at equipotential. Where equipotential is not available wire into
separate zones using a galvanic isolator.
Use a repeater (KD845) for more than 32 units.

Figure 1-6 EIA-485 wiring

1-8 2416 Controller


Installation and Operation Handbook Installation

TYPICAL WIRING DIAGRAM

Line Neutral

Cooling Power Controller


Fuse 1A(T) Fuse 2A(T)

1A HA L
Logic heating
output
1B HB N

2A HC
C
Triac cooling O
output M
2B HD VI
M
S

3A HE V+

3B HF V-

Heating power fuse


(load dependent)

- TE10 Solid
State Relay
+

Cooling Heater T/C


Solenoid Valve

Fig 1-7 Typical wiring diagram, Model 2416 Controller

2416 Controller 1-9


Installation Installation and Operation Handbook

MOTORISED VALVE CONNECTIONS


Motorised valves are wired to relay, or triac, outputs installed in module positions 1 and 2.
The convention is to configure Output 1 as the RAISE output and Output 2 as the LOWER
output. The controller does not require a position feedback potentiometer.

Motor supply

M
1A O HA L Line
D
U
L
RAISE 1B E HB N Neutral
1

Motorised M
O C HC Ground
valve 2A
D O
U
L M
2B E M HD VI
LOWER S
2
RTD/
Pt100
M
HE V+
+
3A O
D +
U T/C PV
L
3B E HF V-
− −
3

Fig 1-8 Motorised valve connections

1-10 2416 Controller


Installation and Operation Handbook Operation

Chapter 2 OPERATION

This chapter has nine topics:

• FRONT PANEL LAYOUT


• BASIC OPERATION
• OPERATING MODES
• AUTOMATIC MODE
• MANUAL MODE
• PARAMETERS AND HOW TO ACCESS THEM
• NAVIGATION DIAGRAM
• PARAMETER TABLES
• ALARM MESSAGES

2416 Controller 2-1


Operation Installation and Operation Handbook

FRONT PANEL LAYOUT

2416
2416

Output 1 on OP1
OP1
Upper readout
Output 2 on OP2
OP2

Setpoint 2 active SP2


SP2
Remote setpoint active Lower readout
(flashes for comms) REM
REM

Auto mode active AUTO RUN Program running


MAN HOLD Run/Hold button
Auto/Man button
(Press & hold to reset)
Manual mode active Program in Hold

Page Scroll Down Up


Button Button Button Button

Figure 2-1 Front panel layout

2-2 2416 Controller


Installation and Operation Handbook Operation

Button or Name Explanation


indicator

Output If a DC When lit, it indicates that the output installed in


OP1 1 output is module position 1 is on. This is normally the heating
installed output on a temperature controller.

Output OP1 & When lit, it indicates that the output installed in
OP2 2 OP2 will module position 2 is on. This is normally the cooling
not light output on a temperature controller.

When lit, this indicates that setpoint 2, (or a setpoint


SP2 Setpoint 2
3-16) has been selected.

When lit, this indicates that a remote setpoint input


REM Remote setpoint
has been selected.
‘REM’ will also flash when communications is active.

When pressed, this toggles between automatic and


manual mode:
• If the controller is in automatic mode the AUTO
AUTO Auto/Manual light will be lit.
MAN button • If the controller is in manual mode, the MAN light
will be lit.
The Auto/Manual button can be disabled in
configuration level.

• Press once to start a program (RUN light on.)


• Press again to hold a program (HOLD light on)
RUN Run/Hold button • Press again to cancel hold and continue running
HOLD (HOLD light off and RUN light ON)
• Press and hold in for two seconds to reset a
program (RUN and HOLD lights off)
The RUN light will flash at the end of a program.
The HOLD light will flash during holdback.

Page button Press to select a new list of parameters.

Scroll button Press to select a new parameter in a list.

Down button Press to decrease a value in the lower readout.

Up button Press to increase a value in lower readout.

Figure 2-2 Controller buttons and indicators

2416 Controller 2-3


Operation Installation and Operation Handbook

BASIC OPERATION
Switch on the power to the controller. It runs through a self-test sequence for about three
seconds and then shows the temperature, or process value, in the upper readout and the
setpoint in the lower readout. This is called the Home display. It is the one that you will use
most often.


D
Measured temperature,
or process value


D Setpoint

Figure 2-3 Home display


On this display you can adjust the setpoint by pressing the or buttons. Two
seconds after releasing either button, the display blinks to show that the controller has
accepted the new value.
Note: You can get back to the Home display at any time by pressing and together.
Alternatively you will always be returned to the Home display if no button is pressed for 45
seconds, or whenever the power is turned on. If, however, a flashing alarm message is present
the controller reverts to the Home display after 10 seconds.
Alarms
If the controller detects an alarm condition, it flashes an alarm message in the Home display.
For a list of all the alarm messages, their meaning and what to do about them, see Alarms at
the end of this chapter.

2-4 2416 Controller


Installation and Operation Handbook Operation

OPERATING MODES
The controller has two basic modes of operation:
• Automatic mode in which the output power is automatically adjusted to maintain the
temperature or process value at the setpoint.
• Manual mode in which you can adjust the output power independently of the setpoint.
You toggle between the modes by pressing the AUTO/MAN button. The displays which
appear in each of these modes are explained in this chapter.
Two other modes are also available:
• Remote Setpoint mode in which the setpoint is generated from an external source.
In this mode the REM light will be on.
• Programmer mode which is explained in Chapter 5, Programmer Operation.

2416 Controller 2-5


Operation Installation and Operation Handbook

AUTOMATIC MODE
You will normally work with the controller in automatic mode. If the MAN light is on, press
the AUTO/MAN button to select automatic mode. The AUTO light will come on.

Power on The Home display


Check that the AUTO light is on.
The upper readout shows the measured temperature, or
process value. The lower readout shows the setpoint.

D To adjust the setpoint up or down, press or .

D (Note: If Setpoint Rate Limit has been enabled, then the
lower readout will show the active setpoint. If or
is pressed, it will change to show and allow adjustment of,
the target setpoint.)

Press once
Display units
A single press of the button will flash the display

D units for 0.5 seconds, after which you will be returned to
/
 the Home display.
Flashing of the display units may have been disabled in
configuration, in which case a single press will take you
straight to the display shown below.

x2 Press twice
% Output power demand
The % output power demand is displayed in the lower
0 readout. This is a read-only value. You cannot adjust it.
D Press and together to return to the Home display.

If the controller is configured as Valve Position and


Manual is selected the Output Power is displayed as
;0. This is the inferred position of the valve
Press

Pressing from the Output Power display may access further parameters. These may be in
this scroll list if the ‘Promote’ feature has been used (see Chapter 3, Edit Level). When you
reach the end of this scroll list, pressing will return you to the Home display.

2-6 2416 Controller


Installation and Operation Handbook Operation

MANUAL MODE
If the AUTO light is on, press the AUTO/MAN button to select manual mode. The MAN
light will come on.

Power on
The Home display
Check that the MAN light is on.
The upper readout shows the measured temperature or
process value. The lower readout shows the % output.

D To adjust the output, press or .

D (Note: If Output Rate Limit has been enabled, then the
lower readout will show the working output. If or
is pressed, it will change to show and allow adjustment of,
the target output.)

Press once
Display units
A single press of will flash the display units for 0.5

D seconds, after which you will be returned to the Home
/
 display.
Flashing of the display units may have been disabled in
configuration in which case you a single press will take
you straight to the display shown below.

Press twice
x2
Setpoint
To adjust the setpoint value, press or .
0

D

Press

Pressing from the Output Power display may access further parameters. Other
parameters may be in this scroll list if the ‘Promote’ feature has been used (see Chapter 3,
Edit Level). When you reach the end of this scroll list, pressing will return you to the
Home display.

2416 Controller 2-7


Operation Installation and Operation Handbook

PARAMETERS AND HOW TO ACCESS THEM


Parameters are settings within the controller that determine how it will operate.
For example, alarm setpoints are parameters that set the points at which alarms will occur.
For ease of access, the parameters are arranged in lists as shown in the navigation diagram on
the following page. The names of these lists are called the list headers. The lists are:

Home list PID list Communications list


Run list Motor list Information list
Programmer list Setpoint list Access list.
Alarm list Input list
Autotune list Output list
Each list has a ‘List Header’ display.
List header displays

) List header

)O6 Always displays ‘)O6’

Figure 2-4 Typical list header display

A list header can be recognised by the fact that it always shows ‘)O6’ in the lower readout.
The upper readout is the name of the list. In the above example, ) indicates that it is the
Alarm list header. List header displays are read-only.

To step through the list headers press . Depending upon how your controller has been
configured, a single press may momentarily flash the display units. In this case, a double
press will be necessary to take you to the first list header. Continued pressing of will
step through the list headers eventually returning you to the Home display.

To step through the parameters within a particular list, press .


When you reach the end of the list, you will return to the list header.
From within a list you can return to the list header at any time can by pressing . To step
to the next list header, press once again.

2-8 2416 Controller


Installation and Operation Handbook Operation

Parameter names
In the navigation diagram, (Fig2-6) each box depicts the display for a selected parameter.
The upper readout shows the name of the parameter and the lower readout its value.
The Operator parameter tables later in this chapter list all the parameter names and their
meaning.

The navigation diagram shows all the parameters that can, potentially, be present in the
controller. In practice, only those associated with a particular configuration will appear.

The shaded boxes in the diagram indicate parameters that are hidden in normal operation.
To see all the available parameters, you must select Full access level. For more information
about this, see Chapter 3, Access Levels.
Parameter displays

)
Parameter name

D Parameter value

Figure 2-5 Typical parameter display

Parameter displays show the controller’s current settings. The layout of parameter displays
is always the same: the upper readout shows the parameter name and the lower readout its
value. Alterable parameters can be changed using or . In the above example, the
parameter mnemonic is ) (indicating Alarm 1, full scale low), and the parameter value
is D.
To change the value of a parameter
First, select the required parameter. The parameter name is shown in the upper readout and
the parameter value in the lower readout.
To change the parameter value, press either or . During adjustment, single presses
change the value by one digit.
Keeping the button pressed speeds up the rate of change.
Two seconds after releasing either button, the display blinks to show that the controller has
accepted the new value.

2416 Controller 2-9


Operation Installation and Operation Handbook

NAVIGATION DIAGRAM (PART A)


Home Run Programmer Alarm Autotune PID Motor
1 1
List List List List List List List
3


D 59. 05/! ) 69. 0O ,65

D )O6 )O6 )O6 )O6 )O6 )O6


D 05! 05!D. BBB2 69. !D0 6,
/     D
0 66 #
BBB2 5 6 N.D6
D 59.    0OD 
,B 00 # ; BBB2 5D6 0 D6
96/

  D  
,0 @ 5,0D8 BBB2  6O ,1D6
 #/95  ,.  96/
DO ! =)D8 #@ 6
#/95 D
6A0 @D. #@
5D
5
5,0D5 D D
!D6 !D. #@ #
#
D 96/ 96/
56
D 6!6 6@0 #@  )
)
05!D6
 5,0D5 96/ 96/
D 6!6 ) 6 5)D
5)D
6 95

  D D
./ D 56 O! D0 0

D ./ D 
/96D. !D.
 !D. D65 6OD

@. 6@0

 
./ . 6@0 D: 6D

!D 6@0
=* D D
@ =*
Figure 2-6a Navigation diagram (Part A)

2-10 2416 Controller


Installation and Operation Handbook Operation

NAVIGATION DIAGRAM (PART B)


Setpoint Input Output Comms Information Access
List List List List List List

0 O0 /0 , O./ 


)O6 )O6 )O6 )O6 )O6 )O6

) O)6 0D)/ 5 O 0 /


0  D 6 0
)B5 ) 0D#O )/!D) !/6/
)/ 6 D D 05
0 The parameters 055 )/!D#

D that follow
depend upon
 D
0
the controller
0 @D )/!D =D0
D configuration.
D D D D
5,D0
Refer to the
@D# $@D )/!D6
D
parameter table.
(over Page)
D D 
D0

5,6D6 $@D# /.6D )/!D:
D
They cover: user
calibration. D 96/ D
;

/.6D# #D
56
 96/ D 5D)
./
0 0

)/D6 .D0 ,6 N 0
 DD
 
0 )4 D0  0
D D
Notes:
0 #4 1. These lists are present only in controllers with the programming
D feature.
2. The last three characters depend upon the type of alarm
0
D)4 #D6A configured.
D )/ 3. This list is only present in motorised valve controllers.
4. Absolute setpoint limits are set in configuration, see Chapter 6.

0
D#4 # The shaded boxes are normally hidden in Operator level. To
D  see all the available parameters you must select Full level.
See Chapter 3, Access Levels.

055
 Figure 2-6b Navigation diagram (Part B)

2416 Controller 2-11


Operation Installation and Operation Handbook

PARAMETER TABLES
Name Description

Home list Extra parameters may be present if promote feature has been used.
Home Measured value and Setpoint
0 % Output level
0 Target setpoint (if in Manual mode )
,B Auto-man select
,0 Heater current (With PDSIO mode 2)
DO Customer defined identification number

59. Program run list − Present only in setpoint programming controllers


05! 
Active program number (Only on program versions)
66 Program status (  59. $/) # .
, , , , )
00 Programmer setpoint
@ Number of cycles remaining in the program
! Active segment number
6A0 Active segment type
!D6 Segment time remaining in the segment units
6!6 Target setpoint
56 Ramp rate (if a rate segment)
05!D6 Program time remaining in hours
6 Fast run through program ( ./ / @)
/96D. Event output states ( / /.) (not 8-segment programmer)
@. Not operational in 2416. Set to ./D
!D * Flash active segment type in the lower readout of the home display ( ./ / @)
05/! Program edit list − Present only in setpoint programming controllers
05!D. Select program number (Only on  program versions)
# Holdback type ( )/ #O .)
, , , or
# ; Holdback value (in display units)
5,0D8 Ramp units (, ,O., or #/95) [for both 5,0D5 and 5,0D6 type segments]
=)D8 Dwell units (, ,O., or #/95)
@D. Number of program cycles ( to , or ‘/.6’)
!D. Segment number
6@0 Segment type:(.) (5,0D5=ramp rate) (5,0D6=ramp time) (=*) (60) ()))

* This parameter can only be changed when the program is in reset

Continued on next page:

2-12 2416 Controller


Installation and Operation Handbook Operation

Continued from previous page:

The following parameters depend on the 6@0 selected, as shown below.


. 5,0D5 5,0D6 =* 60 ))
# ✓ ✓ ✓ ✓ Holdback type:  )/ #O/5 .
6!6 ✓ ✓ ✓ Target setpoint for a ‘5,0’ or ‘60’ segment
56 ✓ Ramp rate for a ‘5,0D5’ segment
95 ✓ ✓ ‘=*’ time / time to target for a ‘5,0D6’ segment
05!D. ✓ ))ed 05/!ram number
@D. ✓ No. of cycles of ))ed program
/96. ✓ ✓ ✓ ✓ ✓ Event output: //. (not 8-segment programmer)
@. ✓ ✓ ✓ ✓ Not operational in 2416. Set to ./D
.D6 ✓ End of prog − =*, 46,  0

Name Description Name Description

Alarm list B) PV Full scale low alarm


B B B Alarm 1 setpoint value B# PV Full scale high alarm

B B B Alarm 2 setpoint value B: PV Deviation band alarm


B B B Alarm 3 setpoint value B#O PV Deviation high alarm
 B B B Alarm 4 setpoint value B)/ PV Deviation low alarm
In place of dashes, the last three characters B)5 Load Current low alarm
indicate the alarm type as follows: B#5 Load Current high alarm
Note: It is possible to indicate only up to B)
Not available in 2416
four alarm conditions (known as soft B#
Not available in 2416
alarms). They can be “wired” to operate
relays within the limitations of the number of B)0 Working Output low alarm
output modules available. For more B#0 Working Output high alarm
information see Configuration - Chapter 6. B)0 Working Setpoint low alarm
B#0 Working Setpoint high alarm
56 Rate of change alarm (AL 4
only)
#@ Alarm 1 Hysteresis (display
units)
#@
Alarm 2 Hysteresis (display
units)
#@ Alarm 3 Hysteresis (display
units)
#@  Alarm 4 Hysteresis (display
units)
) 6 Loop Break Time in minutes
O! Enable Diagnostic alarms ‘ ./’ /
‘@’

2416 Controller 2-13


Operation Installation and Operation Handbook

Name Description Name Description

69. Autotune list ,65 Motor list - see Table 4-3


69. One-shot autotune enable
6, Valve travel time in seconds
5 Adaptive tune enable
N..6 Valve inertia time in secs
5D6 Adaptive tune trigger level in
D6 Valve backlash time in secs


display units. Range = 1 to 9999
,1D6 Minimum ON time of output pulse
Automatic Droop Compensation
(PD control only) 8D5 Not available in 2416

0O PID list 0 Setpoint list


!D0 If Gain Scheduling has been
enabled (see Chapter 4), this ) Select 0 0 , depending
to
parameter sets the PV below on configuration
which ‘0OD ’ is active and above )B5 Local ()/) or remote (5,6)
which ‘0OD
’ is active. setpoint select
6 ‘ 0OD 0OD

’ or ‘ ’ selected 0 Setpoint one value


0 Proportional Band 6
( ) 0
Setpoint two value

6O
(in display units)
6 5,D0 Remote setpoint value
5,6D6
Integral Time in secs ( )
6 Derivative Time in secs ( 6 ) Remote setpoint trim
5 Manual Reset (%) 6
( ) 56 Ratio setpoint
# Cutback High 6
( ) )/D6 Local setpoint trim
) Cutback Low 6
( ) 0 ) Setpoint 1 low limit
5)D Relative Cool Gain 6
( ) 0 # Setpoint 1 high limit
0
Proportional Band 6

( )
0
D)
6

Setpoint 2 low limit


6O

6

Integral Time in secs (


6

)
0
D# Setpoint 2 high limit
Derivative Time in secs (
5D
Manual Reset (%) 6

(
)
)
)/D) Local trim low Theses

#
Cutback High 6

( )
parameters only
appear if
)
Cutback Low 6

( ) PDSIO is fitted
5)D
Relative Cool Gain 6

( ) )/D# Local trim high and )/D6


The following three parameters are used for (remote setpoint
cascade control. If this facility is not being + local trim) in
used, then they can be ignored. SP Config list is
D0 SP, or PV, feedforward propband selected
D65 Feedforward trim % 055 Setpoint Rate Limit
D: PID feedforward limits ± % #D6A Holdback Type for setpoint rate
limit ( )/ #O .
, , , or )
# Holdback Value for setpoint rate
limit in display units. (#D6A ≠
 )

2-14 2416 Controller


Installation and Operation Handbook Operation

Name Description Name Description

O0 Input list /0 Output list


O)6 IP filter time constant (0.0 - 999.9 Does not appear if Motorised Valve control
configured.
seconds).
,O 0D)/ Low power limit (%)
0D#O
Emmisivity - when the input is
configured for a pyrometer High power limit (%)
The next 3 parameters appear only if User 055 Output Rate Limit (% per sec)
Calibration has been enabled. (Refer to 0 Forced output level (%)
Chapter 7.) By default they are hidden @D# Heat cycle time (0.2S to 999.9S)
when in Operator level. To prevent
$@D# Heat hysteresis (display units)
unauthorised adjustment, we recommend
that they are only made available in 9)) /.6D# Heat output min. on-time (secs)
Auto (0.05S), or 0.1 - 999.9S
access level.
) 6 @D Cool cycle time (0.2S to 999.9S)
‘ ’ - reinstates the factory $@D Cool hysteresis (display units)
calibration and disables User
calibration. Next 2 parameters /.6D Cool output min. on-time (secs)
Auto (0.05S), or 0.1 - 999.9S
will not appear.
‘85 ’ - reinstates any previously
#D Heat/cool deadband (display
units)
set User calibration. All
parameters below now appear.
.D0 Power level in programmer in end
segment. This is a single
)D Selected calibration point − parameter for all programs
‘./.’, ’O0 D)’, ‘O1 D#’ D0 Sensor Break Output Power (%)

% * User calibration adjust, if )D =


’O0 D)’, ‘O1 D#’
D IP calibration offset
,;D IP measured value (at terminals)
%D IP Cold Junction Compensation
)OD IP Linearised Value
0;D) PV Select. Not operational in
2416
* Do not make adjustments using the %
parameter unless you wish to change the
controller calibration.

2416 Controller 2-15


Operation Installation and Operation Handbook

Name Description

, Comms list


5 Communications Address

O./ Information list


O0 Configure lower readout of Home
./. 6 )95
display to: , , ,
0 66 05!D6
, ,
)/!D) PV minimum
)/!D# PV maximum
)/!D PV mean value
)/"D6 Time PV above Threshold level
)/"D: PV Threshold for Timer Log
5D) @ ./
Logging Reset - ‘ / ’
The following set of parameters is for
diagnostic purposes.
,6 Processor utilisation factor
=D0 Working output
D0 Feedforward component of output
; PID output to motorised valve
0 0 Proportional component of output
N 0 Integral component of output
 0 Derivative component of output

 Access List


/ Access password
!/6/ Goto level - 05, 9)), O6 or
/.
/. Configuration password

2-16 2416 Controller


Installation and Operation Handbook Operation

ALARMS
Alarm annunciation
Alarms are flashed as messages in the Home display. A new alarm is displayed as a double
flash followed by a pause, old (acknowledged) alarms as a single flash followed by a pause.
If there is more than one alarm condition, the display cycles through all the relevant alarm
messages. Table 2-1 and Table 2-2 list all of the possible alarm messages and their meanings.
Alarm acknowledgement and resetting
Pressing both and at the same time will acknowledge any new alarms and reset any
latched alarms.
Alarm modes
Alarms will have been set up to operate in one of several modes, either:
• Non-latching, which means that the alarm will reset automatically when the Process
Value is no longer in the alarm condition.
• Latching, which means that the alarm message will continue to flash even if the alarm
condition no longer exists and will only clear when reset.
• Blocking, which means that the alarm will only become active after it has first entered a
safe state on power-up.
Alarm types
There are two types of alarm: Process alarms and Diagnostic alarms.
Process alarms
These warn that there is a problem with the process which the controller is trying to control.

Alarm Alarm
Display What it means Display What it means

_)* PV Full Scale Low alarm _)


* Not available in 2416

_#* PV Full Scale High alarm _#


* Not available in 2416

_:* PV Deviation Band alarm _)0* Working Output Low alarm

_#O* PV Deviation High alarm _#0* Working Output High alarm

_)/* PV Deviation Low alarm _)0* Working Setpoint Low alarm

_)5* Load Current Low alarm _#0* Working Setpoint High alarm

_#5* Load Current High alarm 56 PV Rate of change alarm


Always assigned to Alarm 4

* In place of the dash, the first character will indicate the alarm number.
Table 2-1 Process alarms

2416 Controller 2-17


Operation Installation and Operation Handbook

Diagnostic alarms
These indicate that a fault exists in either the controller or the connected devices.

Display What it means What to do about it


shows

D5 Electrically Erasable This fault will automatically take you into
Memory Error: Configuration level. Check all of the
The value of an operator, configuration parameters before returning to
or configuration, parameter Operator level. Once in Operator level, check
has been corrupted. all of the operator parameters before resuming
normal operation. If the fault persists, or occurs
frequently, contact Eurotherm Controls.

D5 Sensor Break: Check that the sensor is correctly connected.


Input sensor is unreliable
or the input signal is out of
range.

)D5 Loop Break Check that the heating and cooling circuits are
The feedback loop is open working properly.
circuit.

)D Load failure This is an alarm generated by feedback from a


Indication that there is a Eurotherm TE10S solid state relay (SSR)
fault in the heating circuit operating in PDSIO mode 1 - see Chapter 1,
or the solid state relay. Electrical Installation. It indicates either an
open or short circuit SSR, blown fuse, missing
supply or open circuit heater.

5D Solid state relay failure This is an alarm generated by feedback from a
Indication that there is a Eurotherm TE10S solid state relay (SSR)
fault in the solid state operating in PDSIO mode 2 - see Chapter 1,
relay. Electrical Installation. It indicates either an
open or short circuit condition in the SSR.

#65D Heater failure This is an alarm generated by feedback from a


Indication that there is a Eurotherm TE10S solid state relay (SSR)
fault in heating circuit. operating in PDSIO mode 2 - see Chapter 1,
Electrical Installation. It indicates either a blown
fuse, missing supply, or open circuit heater.

#=D5 Hardware error Check that the correct modules are fitted.
Indication that a module is
of the wrong type, missing,
or faulty.

./DO/ No I/O This error message normally occurs when pre-


None of the expected I/O configuring a controller without installing any of
modules are fitted. the required I/O modules.

Table 2-2a Diagnostic alarms - continued on the next page

2-18 2416 Controller


Installation and Operation Handbook Operation

Diagnostic alarms (continued)


These indicate that a fault exists in either the controller, or the connected devices.

Display What it means What to do about it


shows

5,6D Remote input failure. Either Check for open, or short circuit wiring on the
the PDSIO input, or the PDSIO, or remote DC, input.
remote DC input, is open or
short circuit

)))) Out of range low reading Check the value of the input.

#### Out of range high reading Check the value of the input.

55 Error 1: ROM self-test fail Return the controller for repair.

55
Error 2: RAM self-test fail Return the controller for repair.

55 Error 3: Watchdog fail Return the controller for repair.

55 Error 4: Keyboard failure Switch the power off and then on, without
Stuck button, or a button touching any of the controller buttons.
was pressed during power
up.

55 Error 5: Faulty internal Check printed circuit board interconnections.


communications. If the fault cannot be cleared, return the
controller for repair.

55 Fault in ‘Digital Filter Chip’ Check connections to the cross board. This is
the PCB that the plug in modules are
connected to.

05 Pot break Check connections on VP feedback


potentiometer

./DO/ Missing input/output Check the correct modules are fitted


hardware

78D5 Tune Error If any one Check response time of process: check that
stage of the tuning process the sensor has not failed: check that the loop
exceeds 2 hours the tune is not broken. Acknowledge by pressing
error alarm appears ‘page’ key and ‘scroll’ key together

Table 2-2b Diagnostic alarms

2416 Controller 2-19


Installation and Operation Handbook Access Levels

Chapter 3 ACCESS LEVELS


This chapter describes the different levels of access to the operating parameters within the
controller.

There are three topics:


• THE DIFFERENT ACCESS LEVELS
• SELECTING AN ACCESS LEVEL
• EDIT LEVEL

THE DIFFERENT ACCESS LEVELS


There are four access levels:
• Operator level, which you will normally use to operate the controller.
• Full level, which is used to commission the controller and the process being controlled.
• Edit level, which is used to set up the parameters that you want an operator to be able to
see and adjust when in Operator level.
• Configuration level, which is used to set up the fundamental characteristics of the
controller.

Access Display What you can do Password


level shows Protection
Operator 05 In this level, operators can view and adjust the No
value of parameters defined in Edit level (see
below).

Full 9)) In this level, all the parameters relevant to a Yes


particular configuration are visible. All alterable
parameters may be adjusted.

Edit O6 In this level, you can determine which Yes


parameters an operator is able to view and
adjust in Operator level. You can hide, or
reveal, complete lists, individual parameters
within each list and you can make parameters
read-only or alterable. (See Edit level at the end
of this chapter).

Configuration /. This special level allows access to set up the Yes
fundamental characteristics of the controller.

Figure 3-1 Access levels

2416 Controller 3-1


Access Levels Installation and Operation Handbook

SELECTING AN ACCESS LEVEL


Access to Full, Edit or Configuration levels is protected by a password to prevent
unauthorised access.
If you need to change the password, see Chapter 6, Configuration.

Access list header


Press until you reach the access list header ‘’.

Press
Password entry
The password is entered from the ‘/’ display.
Enter the password using or . Once the correct password
has been entered, there is a two second delay after which the
lower readout will change to show ‘0’ indicating that access
is now unlocked.
The pass number is set to ‘ ’ when the controller is shipped from
the factory.

Note; A special case exists if the password has been set to ‘’. In
this case access will be permanently unlocked and the lower
readout will always show ‘0’.

Press to proceed to the ‘!/6/’ page.

(If an incorrect password has been entered and the controller is


still ‘locked’ then pressing returns you to the ‘’ list
header.)
Access to Read-only Configuration
From this display, pressing and together will take you
into Read-Only Configuration without entering a password. This
will allow you to view all of the configuration parameters, but not
adjust them. If no button is pressed for ten seconds, you will be
returned to the Home display. Alternatively, pressing and
together takes you immediately back to the Home display.

3-2 2416 Controller


Installation and Operation Handbook Access Levels

Level selection
The ‘!/6/’ display allows you to select the required
access level.
Use and to select from the following display
codes: 05: Operator level
9)): Full level
O6: Edit level
/.: Configuration level
Press

If you selected either ‘05’, ‘9))’ or ‘O6’ level


you will be returned to the ‘’ list header in the level
that you chose. If you selected ‘/.’, you will get a
display showing ‘/.’ in the upper readout (see below).

Alternative path if
Configuration password
‘/.’ selected
When the ‘/.’ display appears, you must enter the
Configuration password in order to gain access to this
level. Do this by repeating the password entry procedure
described in the previous section.
The configuration password is set to ‘
’ when the
controller is shipped from the factory. If you need to
change the configuration password, see Chapter 6,
Configuration.

Press
Configuration level
The first display of configuration is shown. See Chapter
6, Configuration, for details of the configuration
parameters.
For instructions on leaving configuration level, see
Chapter 6, Configuration.

Returning to Operator Level


To return to operator level from either ‘9))’ or ‘O6’ level, repeat entry of the password
and select ‘05’ on the ‘!/6/’ display.
In ‘O6’ level, the controller will automatically return to operator level if no button is
pressed for 45 seconds.

2416 Controller 3-3


Access Levels Installation and Operation Handbook

EDIT LEVEL
Edit level is used to set which parameters you can view and adjust in Operator level. It also
gives access to the ‘Promote’ feature, which allows you to select and add (‘Promote’) up to
twelve parameters into the Home display list, thereby giving simple access to commonly used
parameters.

Setting operator access to a parameter


First you must select O6 level, as shown on the previous page.
Once in O6 level, you select a list, or a parameter within a list, in the same way as you
would in Operator, or Full, level − that is to say, you move from list header to list header by
pressing , and from parameter to parameter within each list using .
However, in Edit level what is displayed is not the value of a selected parameter, but a code
representing that parameter’s availability in Operator level.
When you have selected the required parameter, use and buttons to set its availability
in Operator level.
There are four codes:
)65 Makes a parameter alterable in Operator level.
05 Promotes a parameter into the Home display list.
5 Makes a parameter, or list header, read-only (it can be viewed but not altered).
#N Hides a parameter, or list header.
For example:

The parameter selected is Alarm 2, Full Scale Low


It is alterable in Operator level

Hiding or revealing a complete list


To hide a complete list of parameters, all you have to do is hide the list header. If a list
header is selected, only two selections are available: 5 and #N.
(It is not possible to hide the ‘’ list, which always displays the code: ‘)O6’.)
Promoting a parameter
Scroll through the lists to the required parameter and choose the ‘05’ code. The parameter
is then automatically added (promoted) into the Home display list. (The parameter will also
be accessible, as normal, from the standard lists.) A maximum of twelve parameters can be
promoted. Promoted parameters are automatically ‘alterable’.
Please note, in the ‘05! )O6’, the parameters from segment number (!D.) onwards
cannot be promoted.

3-4 2416 Controller


Installation and Operation Handbook Tuning

Chapter 4 TUNING
Before tuning please read Chapter 2, Operation, to learn how to select and change a
parameter.

This chapter has five main topics:


• WHAT IS TUNING?
• AUTOMATIC TUNING
• MANUAL TUNING
• COMMISSIONING OF MOTORISED VALVE CONTROLLERS
• GAIN SCHEDULING

WHAT IS TUNING?
In tuning, you match the characteristics of the controller to that of the process being
controlled in order to obtain good control. Good control means:
• Stable ‘straight-line’ control of the temperature at setpoint without fluctuation
• No overshoot, or undershoot, of the temperature setpoint
• Quick response to deviations from the setpoint caused by external disturbances, thereby
restoring the temperature rapidly to the setpoint value.
Tuning involves calculating and setting the value of the parameters listed in Table 4-1. These
parameters appear in the ‘0O’ list.

Parameter Code Meaning or Function

Proportional 0 The bandwidth, in display units, over which the output power is
band proportioned between minimum and maximum.

Integral time 6O Determines the time taken by the controller to remove steady-
state error signals.

Derivative 6 Determines how strongly the controller will react to the rate-of-
time change of the measured value.

High Cutback # The number of display units, above setpoint, at which the
controller will increase the output power, in order to prevent
undershoot on cool down.

Low cutback ) The number of display units, below setpoint, at which the
controller will cutback the output power, in order to prevent
overshoot on heat up.

Relative cool 5) Only present if cooling has been configured and a module is
gain fitted. Sets the cooling proportional band, which equals the 0
value divided by the 5) value.

Table 4-1 Tuning parameters

2416 Controller 4-1


Tuning Installation and Operation Handbook

AUTOMATIC TUNING
Two automatic tuning procedures are provided in the 2416:
• A one-shot tuner which automatically sets up the initial values of the parameters listed in
Table 4-1 on the previous page.
• Adaptive tuning which continuously monitors the error from setpoint and modifies the
PID values if necessary.

The ‘one-shot’ tuner works by switching the output on and off to induce an oscillation in the
measured value. From the amplitude and period of the oscillation, it calculates the tuning
parameter values.
If the process cannot tolerate full heating or cooling being applied during tuning, then the
level of heating or cooling can be restricted by setting the heating and cooling power limits in
the ‘/0’ list. However, the measured value must oscillate to some degree for the tuner to be
able to calculate values.
A One-shot Tune can be performed at any time, but normally it is performed only once
during the initial commissioning of the process. However, if the process under control
subsequently becomes unstable (because its characteristics have changed), you can re-tune
again for the new conditions.
It is best to start tuning with the process at ambient temperature. This allows the tuner to
calculate more accurately the low cutback and high cutback values which restrict the amount
of overshoot, or undershoot.
How to tune
1. Set the setpoint to the value at which you will normally operate the process.

2. In the ‘69.’ list, select ‘69.’ and set it to ‘/.’.

3. Press the Page and Scroll buttons together to return to the Home display. The display
will flash ‘69.’ to indicate that tuning is in progress.

4. The controller induces an oscillation in the temperature by first turning the heating on,
and then off. The first cycle is not complete until the measured value has reached the
required setpoint.

5. After two cycles of oscillation the tuning is completed and the tuner switches itself off.

6. The controller then calculates the tuning parameters listed in Table 4-1 and resumes
normal control action.

If you want ‘Proportional only’, ‘PD’, or ‘PI’ control, you should set the ‘6O’ or ‘6’
parameters to  before commencing the tuning cycle. The tuner will leave them off and
will not calculate a value for them.

4-2 2416 Controller


Installation and Operation Handbook Tuning

Typical automatic tuning cycle

Temperature
Setpoint

Time

Calculation of the cutback values


Low cutback and High cutback are values that restrict the amount of overshoot or undershoot
that occurs during large step changes in temperature (for example, under start-up conditions).
If either low cutback, or high cutback, is set to ‘96/’ the values are fixed at three times the
proportional band, and are not changed during automatic tuning.

Adaptive tune
Adaptive tuning is a background algorithm, which continuously monitors the error from
setpoint and analyses the control response during process disturbances. If the algorithm
recognises an oscillatory, or under-damped, response it recalculates the 0, 6O and 6
values.

Adaptive tune is triggered whenever the error from setpoint exceeds a trigger level. This
trigger level is set in the parameter ‘5D6’, which is found in the Autotune list. The value is
in display units. It is automatically set by the controller, but can also be manually
re-adjusted.

Adaptive tune should be used with:


1. Processes whose characteristics change as a result of changes in the load, or setpoint.
2. Processes that cannot tolerate the oscillation induced by a One-shot tune.

Adaptive tune should not be used:


1. Where the process is subjected to regular external disturbances that could mislead the
adaptive tuner.
2. On highly interactive multiloop applications. However, moderately interactive loops,
such as multi-zone extruders, should not give a problem.

2416 Controller 4-3


Tuning Installation and Operation Handbook

MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results, you can tune the controller
manually. There are a number of standard methods for manual tuning. The one described
here is the Ziegler-Nichols method.

With the process at its normal running temperature:

1. Set the Integral Time ‘6O’ and the Derivative Time ‘6’ to .

2. Set High Cutback and Low Cutback, ‘#’ and ‘)’, to ‘96/’.

3. Ignore the fact that the temperature may not settle precisely at the setpoint.

4. If the temperature is stable, reduce the proportional band ‘0’ so that the temperature just
starts to oscillate. If the temperature is already oscillating, increase the proportional band
until it just stops oscillating. Allow enough time between each adjustment for the loop to
stabilise. Make a note of the proportional band value ‘B’ and the period of oscillation
‘T’.

5. Set the 0, 6Oand 6 parameter values according to the calculations given in Table 4-2.

Type of control Proportional Integral time ‘ti’ Derivative time


band ‘Pb’ ‘td’

Proportional only 2xB OFF OFF

P + I control 2.2xB 0.8xT OFF

P + I + D control 1.7xB 0.5xT 0.12xT

Table 4-2 Tuning values

4-4 2416 Controller


Installation and Operation Handbook Tuning

Setting the cutback values


The above procedure sets up the parameters for optimum steady state control. If
unacceptable levels of overshoot or undershoot occur during start-up, or for large step
changes in temperature, then manually set the cutback parameters ‘)’ and ‘#’.

Proceed as follows:

1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb
= Hcb = 3 x Pb).
2. Note the level of overshoot, or undershoot, that occurs for large temperature changes (see
the diagrams below).

In example (a) increase ‘)’ by the overshoot value. In example (b) reduce ‘)’ by the
undershoot value.

Example (a)

Temperature

Overshoot Setpoint

Example (b)
Temperature

Setpoint
Undershoot

Time

Where the temperature approaches setpoint from above, you can set ‘#’ in a similar
manner.

2416 Controller 4-5


Tuning Installation and Operation Handbook

Integral action and manual reset


In a full three-term controller (that is, a PID controller), the integral term ‘ 6O’ automatically
removes steady state errors from the setpoint. If the controller is set up to work in two-term
mode (that is, PD mode), the integral term will be set to ‘’. Under these conditions the
measured value may not settle precisely at setpoint. When the integral term is set to ‘’
the parameter manual reset (code ‘5’) appears in the ‘0O )O6’ in ‘9))’ level. This
parameter represents the value of the power output that will be delivered when the error is
zero. You must set this value manually in order to remove the steady state error.

Automatic droop compensation (Adc)


The steady state error from the setpoint, which occurs when the integral term is set to ‘ ’
is sometimes referred to as ‘droop’. ‘’ automatically calculates the manual reset value in
order to remove this droop. To use this facility, you must first allow the temperature to
stabilise. Then, in the autotune parameter list, you must set ‘’ to ). The controller
will then calculate a new value for manual reset, and switch ‘’ to ‘,.’.

‘’ can be repeated as often as you require, but between each adjustment you must allow
time for the temperature to stabilise.

Tune Error
If any one stage of the automatic tuning process is not completed within two hours a
diagnostic alarm will occur. The display shows 68D5 - Tune Error.
This alarm could occur if:
1. The process to be tuned has a very slow response time
2. The sensor has failed or is incorrectly aligned
3. The loop is broken or not responding correctly

4-6 2416 Controller


Installation and Operation Handbook Tuning

MOTORISED VALVE CONTROL


The 2416 can be configured for motorised valve control as an alternative to the standard PID
control algorithm. This algorithm is designed specifically for positioning motorised valves.
These are ordered, pre-configured, as Model numbers:
• 2416/VC motorised valve controllers
• 2416/VP motorised valve controllers with a single setpoint programmer
• 2416/V4 motorised valve controllers storing four setpoint programs.

Figure 1-8 in Chapter 1 shows how to connect a motorised valve controller. The control is
performed by delivering open, or close, pulses in response to the control demand signal.

The motorised valve algorithm operates in the so-called boundless mode, which does not
require a position feedback potentiometer for control purposes.
The desired control mode is selected in the ‘O.6’ list in configuration level.
The following parameter list will appear in the navigation diagram shown in Chapter 2, if
your controller is configured for motorised valve control.

Name Description Values

,65 Motor list Min Max Default


6, Valve travel time in seconds. D
D D
This is the time taken for the valve to travel from
its fully closed position to its fully open position.

N.D6 Valve inertia time in seconds. 


D 
This is the time taken for the valve to stop moving
after the output pulse is switched off.

D6 Valve backlash time in seconds. 


D 
This is the minimum on-time required to reverse
the direction of the valve. i.e. the time to
overcome the mechanical backlash.

,1D6 Output pulse minimum on-time, in seconds. 96/ D 96/


8D5 Valve sensor break strategy. 56, 90, =. 56
Table 4-3 Motorised valve parameter list

2416 Controller 4-7


Tuning Installation and Operation Handbook

COMMISSIONING THE MOTORISED VALVE CONTROLLER


The commissioning procedure for bounded control mode is as follows:
1. Measure the time taken for the valve to be raised from its fully closed to its fully open
position and enter this as the value in seconds into the ‘6,’ parameter.
2. Set all the other parameters to the default values shown in Table 4-3.
The controller can then be tuned using any of the automatic, or manual, tuning procedures
described earlier in this chapter. As before, the tuning process, either automatic or manual,
involves setting the values of the parameters in Table 4-1.
Adjusting the minimum on-time ‘,1D6’
The default value of 0.2 seconds is satisfactory for most processes. If, however, after tuning
the process, the valve activity is excessively high, with constant oscillation between raise and
lower pulses, the minimum on-time can be increased.
The minimum on-time determines how accurately the valve can be positioned and therefore
the control accuracy. The shorter the time, the more precise the control. However, if the
time is set too short, process noise will cause an excessively busy valve.
Inertia and backlash settings
The default values are satisfactory for most processes, i.e. ‘’.
Inertia is the time taken for the valve to stop after the output pulse is turned off. If this
causes a control problem, the inertia time needs to be determined and then entered into the
parameter, ‘N.D6’. The inertia time is subtracted from the raise and lower output pulse
times, so that the valve moves the correct distance for each pulse.
Backlash is the output pulse time required to reverse the direction of the valve, i.e. the time
taken to overcome the mechanical backlash of the linkages. If the backlash is sufficient to
cause a control problem, then the backlash time needs to be determined and then entered into
the parameter, ‘D6’.
The above two values are not part of the automatic tuning procedure and must be entered
manually.

4-8 2416 Controller


Installation and Operation Handbook Tuning

GAIN SCHEDULING
Gain scheduling is the automatic transfer of control between one set of PID values and
another. In the case of the 2416 controller, this is done at a presettable process value. It is
used for the more difficult to control processes which exhibit large changes in their response
time or sensitivity at, for example, high and low temperatures, or when heating or cooling.
The 2416 has two sets of PID values. You can select the active set from either a parameter in
the PID list, or you can transfer automatically in gain scheduling mode. The transfer is
bumpless and will not disturb the process being controlled.

To use gain scheduling, follow the steps below:


Step1: Enable in configuration level
Gain scheduling must first be enabled in Configuration level.
!$ Goto the N.6 /. list, select the parameter !$, and
set it to @.
@

Step 2: Set the transfer point


Once gain scheduling has been enabled, the parameter !D0
will appear at the top of the 0O list in 9)) access level.
!D1 This sets the value at which transfer occurs. PID1 will be
 active when the process value is below this setting and PID2
when the process value is above it. The best point of transfer
depends on the characteristics of the process. Set a value
between the control regions that exhibit the greatest change.

Step 3: Tuning

You must now set up the two sets of PID values. The values can be manually set, or
automatically tuned as described earlier in this chapter. When tuning automatically you must
tune twice, once above the switching point !D0 and again below the switching point. When
tuning, if the process value is below the transfer point !D0 the calculated values will
automatically be inserted into PID1 set and if the process value is below !D0, the calculated
values will automatically be inserted into PID2 set.

2416 Controller 4-9


Installation and Operation Handbook Programmer Operation

Chapter 5 PROGRAMMER OPERATION


This chapter deals with the setpoint programming option. All 2416 instruments have a basic
8-segment programmer built-in as standard. This facility must be enabled by the user, as
explained in the section, Configuring the Programmer.
Other programmer versions are listed below, and have 16-segments in each program.
Standard controller with:
a single program: Model 2416/CP.
four stored programs: Model 2416/P4.
Motorised valve controller with:
a single program: Model 2416/VP.
four stored programs: Model 2416/V4.
The 8-segment programmer differs from the other programmers in that it will not provide
event outputs. Otherwise they all operate in the same way.

There are seven topics:


• WHAT IS SETPOINT PROGRAMMING?
• PROGRAMMER STATES
• RUNNING A PROGRAM FROM THE RUN LIST
• RUNNING A PROGRAM USING THE RUN/HOLD BUTTON
• AUTOMATIC BEHAVIOUR
• CONFIGURING THE PROGRAMMER
• CREATING A NEW PROGRAM, OR MODIFYING AN EXISTING PROGRAM.

To understand how to select and change parameters in this chapter you will need to have read
Chapter 2, Operation and Chapter 3, Access Levels.

2416 Controller 5-1


Programmer Operation Installation and Operation Handbook

WHAT IS SETPOINT PROGRAMMING?


Many applications need to vary temperature, or process value, with time. Such applications
need a controller which varies a setpoint as a function of time. All 2416 programmer models
will do this.

The setpoint is varied by using a setpoint program. Within each 2416 controller there is a
software module, called the programmer, which stores one, or more, such programs and
drives the setpoint according to the selected program. The program is stored as a series of
‘ramp’ and ‘dwell’ segments, as shown below.

Setpoint

Time
Fig 5-1 Setpoint profile

(If the 8-segment programmer is being used, then the information in the next paragraph does not apply.)
In each segment you can define the state of up to two outputs, each of which can be used to
trigger external events. These are called event outputs and can drive either relay, logic, or
triac outputs, depending on the modules installed.

A program is executed either, once, repeated a set number of times, or repeated continuously.
If repeated a set number of times, then the number of cycles must be specified as part of the
program.

5-2 2416 Controller


Installation and Operation Handbook Programmer Operation

There are five different types of segment:

Ramp The setpoint ramps linearly, from its current value


to a new value, either at a set rate (called ramp-rate
programming), or in a set time (called time-to-target
programming). You must specify the ramp rate, or
the ramp time, and the target setpoint, when creating
or modifying a program.

Dwell The setpoint remains constant for a specified


period.

Step The setpoint steps instantaneously from its current


value to a new value.

Call The main program calls another program as a


subroutine. The called program then drives the
setpoint until it returns control to the main program.
This facility is only available on those controllers
capable of storing 4 programs.

End A program either ends in this segment, or


repeats. You specify which is the case when you
create, or modify, a program (see the final topic in
this chapter). When a program ends, the
programmer is put into either, a continuous Dwell
state with all outputs staying unchanged, or the Reset
state.

Table 5-1 Segment Types

2416 Controller 5-3


Programmer Operation Installation and Operation Handbook

PROGRAMMER STATES
Programs has five states:− Reset, Run, Hold, Holdback and End.

State Description Indication

Reset In Reset, the programmer is inactive and the Both the RUN and
controller behaves as a standard controller, with the HOLD lights will be
setpoint determined by the value set in the lower off
readout.

Run In Run, the programmer varies the setpoint RUN light on


according to the active program.

Hold In Hold, the program is frozen at its current point. In HOLD light on
this state you can make temporary changes to any
program parameter (for example, a target setpoint, a
dwell time, or the time remaining in the current
segment). Such changes only remain effective
until the program is reset and run again, when
they are overwritten by the stored program
values.

Note: When a program is running, you cannot alter


a ))ed program until it becomes active within
that program.

Holdback Holdback indicates that the measured value is HOLD light flashes
deviating from the setpoint by more than a pre-set
amount and that the program is in Hold, waiting for
the process to catch up. See Holdback in the
section on Automatic behaviour later this Chapter.

A master controller can re-transmit a setpoint value HOLD light flashes


to a number of slave units using PDSIO setpoint
retransmission. Any of the slave units can generate
a holdback signal which will also flash the HOLD
light. Holdback will also occur if the PDSIO output is
open circuit. This can be disabled in configuration
by selecting the 0 output as 0D.# - ‘setpoint
retransmission without holdback’

End The program is complete. RUN light flashes

Table 5-2 Program States

5-4 2416 Controller


Installation and Operation Handbook Programmer Operation

RUNNING A PROGRAM FROM THE RUN LIST

The Run List


From the Home display, press until you reach the ‘59.’ list
header.

Press

Program number
This display will only appear on controllers that can hold more
than one program (Models 2416/P4 & 2416/V4). Use or
to select the required program number, from 1 to 4.

Press

Status selection
Use or to select:
• 59. Run program.
• $/) Hold program.
•  Program reset.

After two seconds, the lower readout blinks and the chosen state is
now active.
To return to the Home display press and together.
Other parameters
To access the other parameters in the ‘59.’ list, continue to press
. These parameters are shown in the ‘Program run list’ in
Chapter 2, Parameter Tables. They show the current status of the
active program.

Temporary changes
Temporary changes can be made to the parameters in this ‘59.’ list, (for example a setpoint,
ramp rate, or an unelapsed time), by first placing the programmer into ‘$/)’. Such changes
will remain active only for the duration of the segment; the segment parameters will revert to
their original (stored) values whenever the segment is re-executed.

2416 Controller 5-5


Programmer Operation Installation and Operation Handbook

RUNNING A PROGRAM USING THE RUN/HOLD BUTTON


If you are using a four (4) program version of the controller, you must first select the number
of the program that you want to run. . Do this in the ‘59.’ list - see the previous topic,
Running a program from the Run list.
Then:

Press once to run a program (RUN light on)


RUN RUN / HOLD Press again to hold a program (HOLD light on)
HOLD button Press again to cancel hold and continue running
(HOLD light off, RUN light on)
Press and hold in for two seconds to reset a
program (RUN and HOLD lights off).

Note: The RUN/HOLD button can be disabled, either when ordering the controller, or
subsequently in configuration. This will force you to operate the program from the ‘59.’ list
all the time. The main advantage of this method is that it will reduce the chance of
accidentally changing the state of a program.

AUTOMATIC BEHAVIOUR
The preceding topics explain how to operate the programmer manually.
The following topics cover aspects of its automatic behaviour: Servo, Holdback and Power
Failure.
Servo
When a program is RUN, the setpoint can start either from the initial controller setpoint, or
from the process value. Whichever it is, the starting point is called the ‘servo’ point and you
set it up in configuration. When the program starts, the transition of the setpoint to its
starting point is called ‘servoing’.
The normal method is to servo to the process value, because this will produce a smooth and
bumpless start to the program. However, if you want to guarantee the time period of the first
segment, you should set the controller to servo to its setpoint.

Holdback
As the setpoint ramps up, or down (or dwells), the measured value may lag behind, or deviate
from, the setpoint by an undesirable amount. ‘Holdback’ is available to freeze the program
at its current state, should this occur. The action of Holdback is the same as a deviation
alarm. It can be enabled, or disabled. Holdback has two parameters - a value and a type.
If the error from the setpoint exceeds the set ‘holdback’ value, then the Holdback feature, if
enabled, will automatically freeze the program at its current point and flash the HOLD light.
When the error comes within the holdback value, the program will resume normal running.
There are four different Holdback types. The choice of type is made by setting a parameter
when creating a program, and may be one of the following:−
‘’ − Disables Holdback − therefore no action is taken.

5-6 2416 Controller


Installation and Operation Handbook Programmer Operation

‘)/’ − Deviation Low Holdback holds the program back when the process variable
deviates below the setpoint by more than the holdback value.
‘#O’ − Deviation High Holdback holds the program back when the process variable
deviates above the setpoint by more than the holdback value.
‘.’ − Deviation Band Holdback is a combination of the two. It holds the program back
when the process variable deviates either above, or below, the setpoint by more
than the holdback value.
There is a single Holdback Value which applies to the whole program. However, the
Holdback type and whether or not it is enabled, can be applied to the program as a whole, or
individually in each segment.
Power failure
If power is lost and then restored, while a program is running, the behaviour of the
programmer is determined by the setting of the parameter ‘0=5D’ Power fail strategy in
Programmer configuration. This can have one of three settings:− /.6 (Continue), 5,0D
(Ramp from PV), or 56 (Reset).
If ‘/.6’ is selected, then when power is restored the program continues from where it was
interrupted when power was lost. All parameters, such as the setpoint and time remaining in
the active segment, will be restored to their power-down values. For applications that need to
bring the measured process value to the setpoint as soon as possible, this is the best strategy.
If ‘5,0D’ is selected, then when power is restored the setpoint starts at (‘servos to’) the
current measured value, and then ramps to the target setpoint of the active segment at the last
ramp rate used by the program. This strategy provides a smoother recovery. The two
diagrams below illustrate the respective responses, Fig5-2 if power fails during a dwell
segment and Fig5-3 if it fails during a ramp segment.

Segment dwell
Setpoint Setpoint
time = t1 + t2
Target setpoint
t1 t2
Power off

Power on
Power off
Power on -
Servo to new PV level

Ramp Time Time


Segment Dwell Segment Ramp Segment

Figure 5-2 Continue after a power fail Figure 5-3 Ramp back after a power fail

If ‘56’ is selected, then when power is restored the program terminates.

2416 Controller 5-7


Programmer Operation Installation and Operation Handbook

CONFIGURING THE PROGRAMMER


Configuration defines:
• the number of stored programs (not 8-segment programmer)
• the holdback strategy
• the power fail strategy
• the servo type
• if event outputs are available. (not 8-segment programmer)
When first installing a programmer, you should check that the configuration conforms to
your requirement.
To check or change the configuration, select Configuration level. See Chapter 6.

Programmer list header


After selecting Configuration mode, press until the 04!
/. header is displayed.

Press
Number of programs
Use or to select:
• ./.: Disable built-in 8-segment programmer
• : Enable built-in 8-segment programmer
For 16-segment programmers:
• ./.: no programs
• : One stored program
• : Four stored programs
Press

Holdback Strategy
# Use or to select:
! • !: Holdback type to be set in each segment
• 05/!: Holdback type to be set for the whole program

Press Continued on the next page.

5-8 2416 Controller


Installation and Operation Handbook Programmer Operation

Power fail strategy


0=5D Use

or to select:
/.6: Continue from last setpoint
/.6 • 5,0D: Ramp from PV to setpoint at last ramp rate
• 56: Reset the program

Press

Servo type
5:/ Use or to select:
• 6/D0; Servo to PV
6/D1; • 6/D0 Servo to SP

Press

Event Outputs (not in 8-segment programmer)


Use or to select:
• ./: Event outputs disabled
• @: Event outputs enabled

Note: The term A. appears on 2416 but is not operational


@. and should be set to ./. It appears in order to maintain software
consistency with 2408 and 2404 controllers.

Press to return to the list header

2416 Controller 5-9


Programmer Operation Installation and Operation Handbook

CREATING A NEW PROGRAM OR MODIFYING AN EXISTING ONE


The only difference between creating a new program and modifying an existing one, is that a
new program starts with all its segments set to ‘.’ in the ‘6@0’ parameter. The
procedure for both consists of setting up the parameters in the ‘05/!’ list of the Operation
Navigation Diagram shown in Chapter 2. As explained earlier, under ‘Programmer States’,
temporary changes can be made to these parameters while in the HOLD state, but permanent
changes (to the stored values) can only be made when the programmer is in the Reset state.
So, before modifying a stored program first make sure that it is in Reset and then follow the
procedure below:

Program edit list


From the Home display press until you reach the ‘05/!
)O6’ header.

Press
Program number
This display only appears on the four-program controllers.
Use or to select the number of the program which you
wish to modify (from 1 to 4).

Press
Holdback type
[Only appears when Holdback has been selected for the whole
program.]
Use or to select:
•  Holdback disabled
• )/ Deviation Low Holdback
• #O Deviation High Holdback.
• . Deviation Band Holdback

Press
Holdback value
Use or to set a value.

Press (Continued on the next page.)

5-10 2416 Controller


Installation and Operation Handbook Programmer Operation

Ramp units
Use or to select:
• 
• ,O.
• #/95

Press
Dwell units
Use or to select:
• 
• ,O.
• #/95

Press

Number of program cycles


Use or to set the number of program cycles required from
to , or ‘/.6’ for continuous cycling.

Press

Segment number
Use or to select the number, [1 to 8 (8-seg programmer)], or
1 to 16.
The parameters that follow ‘!D.’ set up the characteristics of
the individually-selected segment number. By defining the
characteristics of each segment of the program, you define the
whole program.

Press

Continued on the next page.

2416 Controller 5-11


Programmer Operation Installation and Operation Handbook

Segment type
Select the segment type using or :
• 5,0D5 Ramp to a new setpoint at a set rate
• 5,0D6 Ramp to a new setpoint in a set time
• =* Dwell for a set time
• 60 Step to a new setpoint
• )) Call another program as a subroutine
(only available in 4-program controllers)
• . Make this segment end of program.

Press

The parameters that follow ‘6@0’ depend on the type of segment selected.
Parameter Segment type selected
5,0D5 5,0D6 =* 60 )) .
# 9 9 9 9
6!6 9 9 9
56 9
95 9 9
05!D. 9
/96. 9 9 9 9 9
@D. 9
=* 9
.D6 9
0=5 9
Table 5-3 Parameters that follow segment 6@0

Holdback type
# [Only appears when Holdback per segment has been selected.]
Use or to select:
. • : Holdback disabled
• )/: Deviation Low Holdback
• #O: Deviation High Holdback
• .: Deviation Band Holdback
Press
Target setpoint
6"6 Target setpoint for ‘5,0D5’, ‘5,0D6’ or ‘60’ segments.
 Set the target setpoint using or .

Press Continued on the next page.

5-12 2416 Controller


Installation and Operation Handbook Programmer Operation

Ramp rate
Ramp rate for ‘56’ segments.
Using or , set a value for the ramp rate, ranging from 0.00
to 999.9 (the units will be the ramp units (‘5,0D8’) set earlier in
this sequence).

Press

Duration time
Time for a ‘=*’ segment, or time to target for a ‘5,0D6’
segment.
Set the time using or . You have set the units earlier in
this sequence.

Press

Called program number


Only appears for ‘))’ segments. (4-program controllers only)
Set a called program number from 1 to 4, using or .

Press

Number of cycles of the called program


Only appears for ‘))’ segments. (4-program controllers only)
Set the number of cycles of the cALLed program from 1 to 999,
using or .

Press

Continued on the next page.

2416 Controller 5-13


Programmer Operation Installation and Operation Handbook

Event output 1 (not 8-segment programmer)


Appears in all segments, except ‘))’ segments.
Use or to set output 1:
•  Off in the current segment
• /. On the current segment.

Press

Further event outputs (not 8-segment programmer)


Up to eight (8) event outputs may appear in this list where ‘n’ =
event number .
Pressing will step through all the remaining event outputs. In
practice, the 2416 has a maximum of three physical outputs,
although more than one event can be combined onto a single
physical output. See Chapter 6, Configuration.
Use or to set:
•  Off in the current segment
• /. On the current segment.

Press

End segment type

.D6 Use or to select:

=* • =* An indefinite dwell


• 56 Reset
•  0 End Segment Output Power Level

Press

Power Value [End Segment]


1=5 Use or to set the power value in the range ±100.0%.
This power level is clipped by the parameters ‘0D#O’ and
D ‘0D)/’ before being applied to the process.

Note: In programmer/controller software versions 3.56


onwards, this parameter has been replaced by a parameter
.D0 which appears at the end of the output list, see
Chapter 2.

Press to return to the 05/!B)O6 header.

5-14 2416 Controller


Installation and Operation Handbook Configuration

Chapter 6 CONFIGURATION
This chapter consists of six topics:

• SELECTING CONFIGURATION LEVEL


• SELECTING A CONFIGURATION PARAMETER
• LEAVING CONFIGURATION LEVEL
• CHANGING THE PASSWORDS
• NAVIGATION DIAGRAM
• CONFIGURATION PARAMETER TABLES.

In configuration level you set up the fundamental characteristics of the controller.


These are:
• The type of control (e.g. reverse or direct acting)
• The Input type and range
• The Setpoint configuration
• The Alarms configuration
• The Programmer configuration
• The Communications configuration
• The Modules 1, 2 & 3 configuration
• Calibration
• The Passwords

WARNING
Configuration is protected by a password and should only be carried out by a qualified
person, authorised to do so. Incorrect configuration could result in damage to the
process being controlled and/or personal injury. It is the responsibility of the person
commissioning the process to ensure that the configuration is correct.

2416 Controller 6-1


Configuration Installation and Operation Handbook

SELECTING CONFIGURATION LEVEL


There are two alternative methods of selecting Configuration level:
• If you have already powered up, then follow the access instructions given in Chapter 3,
Access levels.
• Alternatively, press and together when powering up the controller. This will
take you directly to the ‘/.’ password display.

Password entry
When the ‘/.’ display appears, you must enter the
/. Configuration password (which is a number) in order to
/. gain access to Configuration level.
Enter the password using the or buttons.
The configuration password is set to ‘
’ when the
controller is shipped from the factory.

Once the correct password has been entered, there is a two


second delay, after which the lower readout will change to
/. ‘0’ indicating that access is now unlocked.
1 Note: A special case exists if the password has been set to
‘’. In this situation, access is permanently unlocked and
the lower readout will always show ‘0’.

Press to enter configuration.

(If an incorrect password has been entered and the


O.6 controller is still ‘locked’ then pressing at this point
will take you to the ‘?O6’ display with ‘./’ in the lower
/. readout. Simply press to return to the ‘/.’
display.)

You will obtain the first display of configuration.

6-2 2416 Controller


Installation and Operation Handbook Configuration

SELECTING A CONFIGURATION PARAMETER


The configuration parameters are arranged in lists as shown in the navigation diagram in
Figure 6.1.
To step through the list headers, press the Page button.
To step through the parameters within a particular list press the Scroll button.
When you reach the end of the list you will return to the list header.
You can return directly to the list header at any time by pressing the Page button.

Parameter names
Each box in the navigation diagram shows the display for a particular parameter. The upper
readout shows the name of the parameter and the lower readout its value. For a definition of
each parameter, see the Configuration Parameter Tables at the end of this chapter. To change
the value of a selected parameter, use the and buttons.

The navigation diagram shows all the lists headers and parameters that can, potentially, be
present in the controller. In practice, those actually present will vary according to the
particular configuration choices you make.

CHANGING THE PASSWORDS


There are TWO passwords. These are stored in the Password configuration list and can be
selected and changed in the same manner as any other configuration parameter.
The password names are:
‘D0’ which protects access to Full level and Edit level
‘.D0’ which protects access to Configuration level.

LEAVING CONFIGURATION LEVEL


To leave the Configuration level and return to Operator level Press until the ‘?O6’
display appears.
Alternatively, pressing and together will take you directly to the ‘?O6’ display.

?O6
./ Use or to select ‘@’. After a two-second
delay, the display will blank then revert to the Home
display in Operator level.

2416 Controller 6-3


Configuration Installation and Operation Handbook

NAVIGATION DIAGRAM (PART A)


Instrument Process Value Input Setpoint Alarms Programmer Comms
Config Config Config Config Config Config Config

O.6 0; O0 0 ) 04! #
/. /. /. /. /. /. /.

65) 9.O6 O.06 .0 ) 06A0 O


0O /  (D6
#
 ,
6 D0 % 5,D65 )6$ # 9.
5: .... 96/  ./ ! ,/
//) 5.!D) O,1 ,D65 )/ 0=5D 9
)O.  96/  ./ /.6 
6OD6 5.!D# O.1D) 05D65 )
5:/ 056A

 D  ) 6/D0; ./.
6@0 O.1D# 5,0D8 )6$ /96 5
0; D 0 ./ ./ 9))
,B ;)D) 5,6 )/ @. )@
O D ./. ./ ./ ./
5B$ ;)D# )
O D 
0=5 )6$
@ ./
=D6 )/
./. ./
0D65 )
./ 
5D6 )6$
D0 ./
0 )/
./ ./

./.
!$ Fig 6.1a Navigation Diagram (Part A)
./
6-4 2416 Controller
Installation and Operation Handbook Configuration

NAVIGATION DIAGRAM (PART B)


(1)
Module 1 Module 2 Module 3 Custom Calibration Password
Config Config Config Config Config Config


  86 ) 0 ?O6
/. /. /. /. /. /. ./

O O O O. 5) D0
5)A 5)A 5)A D ./.
9. 9. 9. 8)D 8) .D0
#6 ) N" D ./

;)D) ;)D) . O.


16 D)
  ./5 D 
;)D# ;)D# ) 8)D
16 D#
  ./
D 
96D) 96D) )
O.  D)
D D ./
DD D
96D# 96D# ) 8)D  D#

D
D ./ D D
See parameter tables

O. 
D
8)D
D
Note:
1. 8-point custom linearisation. Only appears when
‘ O0B/.’ has ‘ O.16 ,;D
’=‘ ’, or ‘,D ;D
’, or ‘ ’.
2. The navigation diagram shows typical parameters,
but is dependant upon the exact configuration of the
instrument. The following sheets show the full list of
parameters.

Fig 6.1b Navigation Diagram (Part B)

2416 Controller 6-5


Configuration Installation and Operation Handbook

CONFIGURATION PARAMETER TABLES


Name Description Values Meaning

O.6 Instrument configuration


65) Control type 0O PID control
.D On/off control
;0 Boundless motorised valve
control - no feedback required
;0  Bounded motorised valve
control - feedback required
6 Control action 5: Reverse acting
O5 Direct acting
//) Type of cooling )O. Linear
/O) Oil (50mS minimum on-time)
#
 Water (non-linear)
. Fan (0.5S minimum on-time)
/.D On/off cooling
6OD6 Integral & derivative  Seconds, OFF to 9999
time units ,O. Minutes, OFF to 999.9
6@0 Derivative type 0; Operates on rate of change of
55 PV
Operates on rate of change of
error
,B Front panel Auto/Man button . Enabled
O Disabled
5B$ Front panel Run/Hold button . Enabled
O Disabled
0=5 Power feedback /. On
 Off
=D6 Feed forward type ./. None
 Normal feed forward
0D Setpoint feed forward
0;D PV feed forward
0D65 Manual/Auto transfer when ./ Non-bumpless transfer
using PD control @ Bumpless transfer - (Pre-loads
Manual Reset value)
5D6 Sensor break output D0 Go to pre-set value
#/) Freeze output
0 Forced manual output ./ Bumpless Auto/Manual transfer
65 Returns to the Manual value
that was set when last in
Manual mode
61 Steps to forced output level.
0 /1B)O6
Value set in ‘ ’ of ‘ ’
in Operator Level
 BCD input function ./. Not used
05/! Only functional in Models 2408
& 2404. Set ‘’ to ‘./.
0 Select setpoint number
!$ Gain Schedule Enable ./ Disabled
@ Enabled

6-6 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning

1; Process value config


9.O6 Inststrument units  Celsius
 Fahrenheit
( Kelvin
./. Display units blanked
D1 Decimal places in the .... None
...D.
..D..
displayed value One
Two
5."D) Range low Low range limit. Also setpoint limit for
alarms and programmers
5."D$ Range high High range limit. Also setpoint limit for
alarms and programmers

Notes:

1. Pyrometer Emmisivity
Controllers which are specifically supplied for pyrometer inputs (not Exergen K80), have
the curve downloaded in the Custom Input. The parameter, ,O, Pyrometer
Emmisivity, appears in the Input List on page 2-15. This parameter is also now correctly
adjusted.

2. Range
If a decimal point was configured, negative display and setpoint ranges were limited to -
99.9 in previous software versions. The range has been increased to -199.9 by combining
the negative sign with the figure one. This allows Setpoints, Process Variables, Alarm
Setpoints and Programmers to be set to -199.9.

2416 Controller 6-7


Configuration Installation and Operation Handbook

Name Description Values Meaning

O0 Input configuration
O.06 Input type %D6 J thermocouple
(D6 K thermocouple
)D6 L thermocouple
5D6 R thermocouple (Pt/Pt13%Rh)
D6 B thermocouple (Pt30%Rh/Pt6%Rh)
.D6 N thermocouple
6D6 T thermocouple
D6 S thermocouple (Pt/Pt10%Rh)
0)
PL 2 thermocouple
D6 Custom downloaded t/c (default = type C)
56 100Ω platinum resistance thermometer
,; Linear millivolt
:/)6 Linear voltage
, Linear milliamps
5 ; Square root volts
5  Square root milliamps
* See ‘96’ List. ,;D 8-point millivolt custom linearisation*
;D 8-point Voltage custom linearisation*
,D 8-point milliamp custom linearisation*
% Cold Junction  No cold junction compensation
Compensation 96/ Automatic internal compensation
// o
0 C external reference
/ o
45 C external reference
  o
50 C external reference
O,1 Sensor Break Impedance  Disabled (applies to any input)
Caution:
If sensor break is disabled the
controller will not detect open circuit
faults
96/ Factory set
#O Impedance of input > 15KΩ
#OD#O Impedance of input > 30KΩ
Linear Input Scaling − The next four parameters only appear if a linear input is chosen.

O.0D) Displayed Value


Input value low

O.0D# ;)D#
Input value high

;)D) Display reading low


;)D)
;)D# O.0D) O.0D#
Electrical
Input Display reading high

6-8 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning

0 Setpoint configuration
.0 Number of setpoints
, ,  Select number of setpoints available
5,D65 Remote Tracking  Disable
65 Local setpoint tracks remote setpoint
,D65 Manual Track  Disable
65 Local setpoint tracks PV when in manual
05D65 Programmer Track  Disable
65 Local setpoint tracks programmer SP
5,0D8 Setpoint rate limit units 0 Per second
0,O. Per minute
0#5 Per hour
5,6 Remote setpoint configuration ./. Disable
0 Remote setpoint
)/D6 Remote setpoint + local trim
5,6D6 Remote trim + local setpoint

) Alarm configuration Values Table A - Alarm types


Value Alarm type
The controller contains four ‘soft’ alarms, (indication only)
 No alarm
)
which are configured in this list. Once configured, they
can be attached to a physical output in module positions PV Full scale low

 or . # PV Full scale high
) : PV Deviation band
#O
Alarm 1 Type see Table A
)6$ Latching .//@/:.6/,.* )/
PV Deviation high

)/ .//@
PV Deviation low
Blocking
)5 Load Current low
)
Alarm 2 Type see Table A #5 Load Current high
)6$ Latching .//@/:.6/,.* )
Not usable on 2416
)/ .//@ #
Not usable on 2416
)0
Blocking
) Alarm 3 Type see Table A
#0
Working Output low

)6$ Latching .//@/:.6/,.* )0


Working Output high
Working Setpoint low
)/ Blocking .//@ #0 Working Setpoint high
) Alarm 4 Type see Table A 56 PV Rate of change
)6$ Latching .//@/:.6/,.* AL4 only

)/ Blocking (not if ‘)’ = ‘56’) .//@


* Alarm Modes
‘./’ means that the alarm will be non-latching. :.6
‘ ’ means that the alarm is used to trip
‘@’ means that the alarm will be latched, with
an external event. If this option is selected
the front panel alarm message will not appear.
automatic resetting. Automatic resetting means that
if a reset is actioned before the alarm has cleared, ,.
‘ ’ means that the alarm will be latched,
then it will automatically reset when it clears. and can only be reset after it has first cleared
(called ‘manual reset mode’).

2416 Controller 6-9


Configuration Installation and Operation Handbook

The following parameters apply if the standard 8-segment programmer is to be configured.


04! Programmer configuration Values Meaning
06A0 Programmer type ./. Programmer disabled (factory setting)
8-segment programmer enabled
# Holdback ! Holdback is individually selectable in
each segment.
05/! Holdback is applied across the whole
Program.
0=5D Power fail recovery /.6 Continue from last setpoint (SP)
5,0D Ramp from PV to SP at last ramp rate
56 Reset the program
5:/ Starting setpoint of a 6/D0; From the Process Value (PV)
program (Servo point) 6/D0 From the setpoint

The following parameters apply if a 16-segment programmer is to be configured.


04! Programmer configuration Values Meaning
06A0 Programmer type ./. Programmer disabled
Single program
 Four programs
# Holdback ! Holdback is individually selectable in
each segment.
05/! Holdback is applied across the whole
Program.
0=5D Power fail recovery /.6 Continue from last setpoint (SP)
5,0D Ramp from PV to SP at last ramp rate
56 Reset the program
5:/ Starting setpoint of a 6/D0; From the Process Value (PV)
program (Servo point) 6/D0 From the setpoint
/96 Programmable event ./ Disabled
outputs @ Enabled
@- Synchronisation of programs ./ Disabled
of several programmers
Not usable in Model 2416
@ Enabled
./
Select ‘ ’

6-10 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning


# Comms 1 module config
O Identity of the module installed , EIA-232, or 2-wire EIA-485, or 4-wire
EIA-485 comms
0 PDSIO retransmission
0DO PDSIO input

For ‘O’ = ‘,’ use this parameter table:


9. Function ,/ Modbus protocol
NDO Eurotherm Bisynch protocol
9 Baud Rate
,
, , , D
(19,200)
)A Delay - quiet period, required by ./ No delay
some comms adaptors @ Delay active - 10mS
The following parameters only appear if the function chosen is Modbus protocol.
056A Comms Parity ./. No parity
:. Even parity
 Odd parity
5 Comms Resolution 9)) Full resolution
N.6 Integer resolution
)A Delay - quiet period, required by ./ No delay
some comms adaptors @ Delay active - 10mS
For ‘O’ = ‘1’ use this parameter table:
9. Function ./. No PDSIO function
0D/0 PDSIO setpoint retransmission
0;D/0 PDSIO PV retransmission
5D0 PDSIO error signal retransmission
0D/0 PDSIO output power retransmission
Displayed Value

;)D) VAL.H Retransmitted Value Low

;)D# VAL.L Retransmitted


Output
Retransmitted Value High
0% 100%

2416 Controller 6-11


Configuration Installation and Operation Handbook

Name Description Values Meaning

For ‘O’ = ‘0O’ use this parameter table:


9. Function 0DO0 PDSIO setpoint input
Displayed Value

;)D) VAL.H Setpoint Displayed Value - Low

;)D# VAL.L Electrical Input


Setpoint Displayed Value - High
0% 100%

6-12 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning

 Module 1 configuration
O Identity of module installed 5)A Relay output
D0 Non-isolated DC output
)/! Logic/PDSIO output
5 Triac output

For ‘O’ = ‘5)A’, ‘)/!’, or ‘5’ use this parameter table:


9. Function ./. Function disabled
N! Digital output function
#6 Heating output
) Cooling output
91 Open motorised valve
=. Close motorised valve
(Only if ‘O’ = ‘)/!’) 5D PDSIO mode 1 heating
(Only if ‘O’ = ‘)/!’) 5D
PDSIO mode 2 heating
;)D) % PID demand signal giving
96D)
PID Demand Signal

minimum output − ‘ ’
;)D# VAL.H
% PID demand signal giving
maximum output − ‘ 96D#’
96D) Minimum average power
96D#
VAL.L Electrical
Output
Out.L Out.H Maximum average power
. Sense of output ./5 Normal (output energises
(Only if ‘9.’ = ‘N!’) when TRUE, e.g program
events)
O.: Inverted (output de-energises
when TRUE, e.g. alarms)
When ‘ .’ appears, then further parameters are available. See the table on the next
page.

2416 Controller 6-13


Configuration Installation and Operation Handbook

Name Description Values Meaning

The following digital events appear after ‘ .


’. Any one, or more, of the events can be
@
combined on to the output (see Fig. 6-2) by selecting ‘ ’ in the lower readout.
B B B Alarm 1 active @ ./ B B B
/ ( )
) = alarm type (e.g. ).

BBB Alarm 2 active @ / ./ If an alarm has not been configured
BBB Alarm 3 active @ / ./ in ‘) /.’ list, then display will
BBB Alarm 4 active @ / ./ differ:- e.g. Alarm 1 = ‘) ’.
,. * Controller in manual mode @ / ./
5 * Sensor break @ / ./
0. * PV out of range @ / ./
)5 * Loop break @ / ./
)D * Load failure alarm @ / ./
69. * Tuning in progress @ / ./
D * Voltage output open circuit, or @ / ./
mA output open circuit
5,6D * PDSIO module connection open @ / ./
circuit
O0 D * Input 1 fail (not usable on 2416) @/./
.=D) * New Alarm has occurred @ / ./
. * End of setpoint rate limit, or end @ / ./
of program
@. * Program Synchronisation active @ / ./ (Not available in 2416 - set to ‘./’)
05!D. * Programmer event output @ / ./
active, where ‘n’ = event number
from 1 to 8. (Not available with
8-segment programmer.)

* These alarms are always non-latching. Process alarms 1, 2, 3 and 4 are


configurable as alarm latching or non-latching, see the ‘)’ List

./5
Digital
OR
N! SEnS
Events
O.: Output
Module
Figure 6-2 Combining several digital events on to one output

6-14 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning

For ‘O’ = ‘D0’, use this parameter table:


9. Function ./. Function disabled
#6 Heating output
) Cooling output
0; Retransmission of PV
=0 Retransmission of setpoint
55 Retransmission of error signal
0 Retransmission of OP power
;)D) %PID, or Retransmission Value % PID, or Retrans’n Value,
VAL.H giving minimum output
;)D# % PID, or Retrans’n Value,
giving maximum output
9.O6 :/)6 = Volts, , = milliamps
96D) VAL.L Minimum electrical output
96D# Out.L Out.H
Electrical
Output Maximum electrical output


 Module 2 configuration
As per module 1 configuration, but excluding the ‘ 5D ’, ‘5D
’ options on a logic output.
 Module 3 configuration
As per module 2 configuration.

96 8-point Custom Linearisation


(1)

O. Displayed Value Custom input 1

;)D ;)D
Linearisation Value representing O.

O.  ;)D
;)D Electrical
Custom input 8

;)D O. O. O. 
Input
Linearisation Value representing O. 

Note:
1. Custom Linearisation is only available when ‘O1B /. list has ‘O.16’
set to ‘,;D’, or ‘,D’, or ‘;D’
2. Custom curves must be continuously increasing or decreasing in value and
input

2416 Controller 6-15


Configuration Installation and Operation Handbook

Name Description Values Meaning

) Calibration

In this mode you can


1. Calibrate the instrument using a mV source - 5) or ref source
cal.
2. Offset the calibration to account for errors in actual sensor
measurement and a ref sensor - 8) or user calibration
3. Return to factory set calibration - 7 or factory set calibration.
5) Calibration
point
./. No calibration
Goto User
calibration table-
See also chapter 7

0; Calibrate main Process Value input. Go to input


0;D
Calibrate DC input, or PV 2.(not
2416)
Calibation table

D#O Calibrate DC output high - Module 1


D)/ Calibrate DC output low - Module 1

D#O
Go to
Calibrate DC output high - Module 2 DC Output

D)/ Calibrate DC output low - Module 2 Calibration
D#O Calibrate DC output high - Module 3 table
D)/ Calibrate DC output low - Module 3

INPUT CALIBRATION
For ‘)’ = ‘0;’, or ‘0;D
’, the following parameters apply.
0; PV Calibration Value N) Idle
,:D) Select 0mV as the calibration point
,:D# Select 50mV as the calibration point
; Select 0Volt as the calibration point
1. Select calibration value ;  Select 10V as the calibration point
2. Apply specified input % o
Select 0 C CJC calibration point
3. Press to step to ‘!’ 56 Select 400Ω as the calibration point
#N  High impedance: 0Volt cal’n point
#N D High impedance: 1.0 Volt cal’n point
See Note below. 6 Restore factory calibration
! Start calibration ./ Waiting to calibrate PV point
Select ‘@’ with or @ Start calibration
Wait for calibration to 9A Busy calibrating
complete. /. PV input calibration completed
N) Calibration failed

6-16 2416 Controller


Installation and Operation Handbook Configuration

Name Description Values Meaning

DC Output Calibration
The following parameters apply to DC output modules ie for 5) = D#O to D)/
)D# Output Calibration High  
= Factory set calibration.
Trim value until output = 9V, or
18mA
)D) Output Calibration Low  
= Factory set calibration.
Trim value until output = 1V, or
2mA

User calibration
8) User calibration enable Yes/no
16 D) Low calibration point for Input 1 The factory calibration point at which the low
point offset was performed.
16 D# High calibration point for Input 1 The factory calibration point at which the high
point offset was performed.
 D) Offset Low for Input 1 Calculated offset, in display units.
 D# Offset High for Input 1 Calculated offset, in display units.

Name Description Values Meaning

0 Password configuration


D0 FuLL or Edit level password
.D0 Configuration level
password

?O6 Exit configuration .//@

2416 Controller 6-17


Installation and Operation Handbook User Calibration

Chapter 7 USER CALIBRATION


This chapter has five topics:
• WHAT IS THE PURPOSE OF USER CALIBRATION?
• USER CALIBRATION ENABLE
• OFFSET CALIBRATION
• TWO POINT CALIBRATION
• CALIBRATION POINTS AND CALIBRATION OFFSETS

To understand how to select and change parameters in this chapter you will need to have read
Chapter 2 - Operation, Chapter 3- Access Levels and Chapter 6 - Configuration.

WHAT IS THE PURPOSE OF USER CALIBRATION?


The basic calibration of the controller is highly stable and set for life. User calibration
allows you to offset the ‘permanent’ factory calibration to either:

1. Calibrate the controller to your reference standards.


2. Match the calibration of the controller to that of a particular transducer or sensor input.
3. Calibrate the controller to suit the characteristics of a particular installation.
4. Remove long term drift in the factory set calibration.

User calibration works by introducing a single point, or two-point, offset onto the factory set
calibration.

2416 Controller 7-1


User Calibration Installation and Operation Handbook

USER CALIBRATION ENABLE


The User calibration facility must first be enabled in configuration level by setting the
parameter ‘8)' in the ) /. list to '@'. This will make the User calibration
parameters visible in Operator ‘9))’ level. This procedure is described in Chapter 6,
Configuration, but for convenience is summarised below: .

The Calibration Configuration List

) Press until you reach the ‘)B/. ’ list.

×2 Press until you reach ‘8)’.

User Calibration Enable

8) Use or to select:


• @: Calibration enable
@ • ./: Calibration disabled

+ Press and together to go to the ?O6 display.

Exit configuration
Use or to select ‘@’ to return to Operator level.

7-2 2416 Controller


Installation and Operation Handbook User Calibration

OFFSET CALIBRATION
Offset calibration is used to apply a single fixed offset over the full display range of the
controller.
Displayed Value

Factory Calibration

Fixed Offset
Input

To calibrate, proceed as follows:


1. Connect the input of the controller to the source device to which you wish to calibrate.
2. Set the source to the desired calibration value.
3. The controller will display the current measurement of the value.
4. If the displayed value is correct, then the controller is correctly calibrated and no further
action is necessary. If it is incorrect, then follow the steps shown below.
Select ‘9))’ access level, as described in Chapter 3.

Input list header


Press until you reach the input list header.

x2 Press until you reach the ‘)’ display.


Calibration type
• 6:
)
Factory Calibration
• 85: User Calibration
to select ‘6’.
6 Use or
Selecting ‘6’ reinstates the factory calibration and allows the
application of a single fixed offset.

Press

continued on the next page

2416 Controller 7-3


User Calibration Installation and Operation Handbook

Set Offset 1

D Use
(PV1).
or to set the offset value of Process Value 1

 The offset value is in display units.

Press

The table below shows the parameters which appear after


‘D ’. These are all read only values and are for information.
Press to step through them.

,;D IP1 measured value (at terminals)


See table on the %D IP1 Cold Junction Compensation
right for additional
parameters )OD IP1 Linearised Value
0;D) Not available in Model 2416

If you do not want to look at these parameters, then press


and this returns you to the ‘O0B)O6’ header.

To protect the calibration against unauthorised adjustment, return


to Operator level and make sure that the calibration parameters
are hidden. Parameters are hidden using the ‘Edit’ facility
described in Chapter 3, Access Levels.

7-4 2416 Controller


Installation and Operation Handbook User Calibration

TWO-POINT CALIBRATION
The previous section described how to apply an offset, or trim, calibration, which applies a
fixed offset over the full display range of the controller. A two-point calibration is used to
calibrate the controller at two points and applies a straight line between them. Any readings
above, or below, the two calibration points will be an extension of this straight line. For this
reason it is best to calibrate with the two points as far apart as possible.

Displayed Value Offset introduced


User Calibration

Calibration high-point value Factory Calibration

High-point calibration x

Low-point calibration x
Calibration low-point value

Input
Offset introduced

Proceed as follows:
1. Decide upon the low and high points at which you wish to calibrate.
2. Perform a two point calibration in the manner described below.

Input list header


Press until you reach the input list header, ‘O1 )O6’.

x2 Press until you reach the ‘)’ display.


Calibration type
• 6: Factory Calibration
) • 85: User Calibration
Use or to select ‘85’.
85 Selecting ‘85’ enables two-point calibration.
[If two-point calibration is unsatisfactory, select ‘6’ to
return to the factory set calibration.]
Press

2416 Controller 7-5


User Calibration Installation and Operation Handbook

Select Low-point Calibration


)D This is the Calibration Status display. This display shows that
no input is selected for calibration.
• ./.: No selection. If ./. selected go to page 7-4
./. • O1 D): Input 1 (PV1) calibration low-point selected
• O1 D#: Input 1 (PV1) calibration high-point selected
• O1
D): Not available in Model 2416
• O1
D#: Not available in Model 2416
Use / to select the parameter for the Low Calibration
point of Input 1, ‘O1 D)’ & follow route shown on this page.

Press

Adjust low-point calibration

&
This is the display for adjusting the Low Calibration point of
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.

 Make sure that the calibration source is connected to the
terminals of Input 1, switched on and feeding a signal to the
controller. It should be set to the desired low-point calibration
value. If the lower readout does not show this value, then use
/ to adjust the reading to the required value.

Press to return to the ‘O1B)O6’ header.

To perform the High-point Calibration, repeat the above


procedure, selecting ‘O1 D#’ in the ‘)D’ display for
adjustment.

x2 Press twice.

Calibration type

) ‘85’ was selected for the Low-point Calibration, and has
remained selected.

85

Press

7-6 2416 Controller


Installation and Operation Handbook User Calibration

Select High-point Calibration

) This is the Calibration Status display, again.

O1 D) Use / to select the parameter for the High-point


Calibration of Input 1, ‘O1 D#’.

Press

Adjust High-point Calibration


This is the display for adjusting the High Calibration point of

&
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.


 Feed the desired high-point calibration signal to the controller,
from the calibration source. If the lower readout does not
show this value, then use / to adjust the reading to the
required value.

Press to return to the ‘O1B)O6’ header.

To protect the calibration against unauthorised adjustment


return to Operator level and make sure that the calibration
parameters are hidden. Parameters are hidden using the
‘O6’ facility described in Chapter 3.

2416 Controller 7-7


User Calibration Installation and Operation Handbook

CALIBRATION POINTS AND CALIBRATION OFFSETS


If you wish to see the points at which the User calibration was performed and the value of the
offsets introduced, then these are shown in Configuration, in ‘)B/. ’.
The parameters are:
Name Parameter description Meaning
16 D) Low calibration point for Input 1 The factory calibration point at which the low
point offset was performed.
16 D# High calibration point for Input 1 The factory calibration point at which the high
point offset was performed.
 D) Offset Low for Input 1 Calculated offset, in display units.
 D# Offset High for Input 1 Calculated offset, in display units.

Note: The value of each of the parameters in the above table may also be altered by using
the / buttons.

7-8 2416 Controller


Installation and Operation Handbook Understanding The Ordering Code

Appendix A
UNDERSTANDING THE ORDERING CODE
The 2416 controller has a modular hardware construction, which accepts up to three plug-in
Input/Output modules and one communications module, to satisfy a wide range of control
requirements.

The ordering code is in two parts. The hardware coding and an optional configuration
coding. The hardware coding specifies the basic build of the controller and the plug-in
modules that are fitted.

Part 1: Part 2:
Hardware coding Configuration
Plug-in
Basic build I/O modules

2416

Model Module Display


number 1 units
Function Module
Supply 2 Sensor Options
voltage Module Range
3 min
Comms Range
Manual max

The controller may have been ordered with just the hardware build specified, or with
configuration included. This is indicated by the ordering code on the side of the controller.

2416 Controller A-1


Understanding the Ordering Code Installation and Operation Handbook

Part 1A: Hardware coding

Model Function Supply Module 1


number voltage
2416 CC VH LH
Continue next page

Function Module 1 Table A : Alarm relay


CC Controller/8-seg XX None functions
Programmer Relay: 2-pin FH High alarm
CP Single 16-segment R2 Fitted unconfigured FL Low alarm
Programmer RH PID heating DB Deviation band
P4 Four Program 16- RU Valve raise output DL Low dev. alarm
segment Or Alarm 1: select from table A DH High dev alarm
VC Valve positioner (VP) Logic non-isolated
/8 segment Prog. L2 Fitted unconfigured
VP VP/Single Prog. 16- LH PID heating
segment M1 PDSIO mode 1(1)
V4 VP/Four Program. M2 PDSIO mode 2(1)
16-segment Triac
T2 Fitted unconfigured
TH PID heating
TU Valve raise output
DC control non-isolated
D2 Unconfigured
Supply voltage H1 0-20mA heating
VH 85 to 264Vac H2 4-20mA heating
VL 20 to 29Vac/dc H3 0-5Vdc heating
H4 1-5Vdc heating
H5 0-10Vdc heating

A-2 2416 Controller


Installation and Operation Handbook Understanding The Ordering Code

Part 1B: Hardware coding

Plug-in modules
continued
Module 2 Module 3 Comms 1 Manual

RC RH MB ENG

Module 2 Module 3 Manual


XX None XX None XXX No manual
Relay: 2-pin Relay: 2-pin ENG English
R2 Fitted unconfigured R2 Fitted unconfigured FRA French
RC PID cooling PO Program event 2 GER German
RW Valve lower output LF PDSIO load failure ITA Italian
PO Program event output 1 HF PDSIO heater failure
Or Alarm 2: select from table A SF PDSIO SSR failure
Comms
Logic non- isolated Or Alarm 4 select from table A
XX None
L2 Fitted unconfigured Other modules
LC PID cooling EIA-485 ( 2 wire )
L2 Logic unconfigured
Y2 Fitted unconfigured
Triac non-isolated
YM Modbus protocol
T2 Fitted unconfigured T2 Triac unconfigured
YE EI Bisynch protocol
TC PID cooling D2 DC unconfigured
TW Valve lower output EIA-232
non- Isolated
A2 Fitted unconfigured
DC control non-isolated First character
AM Modbus protocol
D2 Unconfigured V− PV retransmission
AE EI Bisynch protocol
C1 0-20mA cooling S− Setpoint retransmission
C2 4-20mA cooling EIA-485 ( 4 wire )
O− Output retransmission
C3 0-5Vdc cooling F2 Fitted unconfigured
Z− Error retransmission
C4 1-5Vdc cooling FM Modbus protocol
Second character FE EI Bisynch protocol
C5 0-10Vdc cooling −1 0 to 20mA
PDSIO input
−2 4 to 20mA M6 Fitted unconfigured
−3 0 to 5V RS Setpoint input
−4 1 to 5V PDSIO output
−5 0 to 10V M7 Fitted unconfigured
PT PV retransmission
TS Setpoint retrans
OT Output retrans

2416 Controller A-3


Understanding the Ordering Code Installation and Operation Handbook

Hardware
coding Part 2: Configuration
Sensor Range Range Units Options
input min max
See note 2
K 0 1000 C CF

Sensor input Range min &max


Standard sensor inputs °C °F
J J thermocouple -210 to 1200 -340 to 2192
K K thermocouple -200 to 1372 -325 to 2500
T T thermocouple -200 to 400 -325 to 750
L L thermocouple -200 to 900 -325 to 650
N N thermocouple -250 to 1300 -418 to 2370
R Type R - Pt13%Ph/Pt -50 to 1768 -58 to 3200
S Type S - Pt10%Rh/Pt -50 to 1768 -58 to 3200
B Type B - 0 to 1820 32 to 3308
Pt30%Rh/Pt6%Rh
P Platinel II 0 to 1369 32 to 2496
C *Type C 0 to 2319 32 to 4200
W5%Re/W26%Re
(Hoskins)*
Z RTD/PT100 -200 to 850 -325 to 1562
Process inputs
F -9.99 to + 80mV 0 to 9999
Y 0-20 mA Linear 0 to 9999
A 4-20 mA Linear 0 to 9999
W 0-5V DC Linear 0 to 9999
G 1-5V DC Linear 0 to 9999
V 0-10V DC Linear 0 to 9999
Custom Sensor inputs (* replaces type C thermocouple)
D Type D - 0 to 2399 32 to 4350
W3%Re/W25%Re
E E thermocouple -270 to 1000 -450 to 1830 Options
1 Ni/Ni18%Mo 0 to 1399 32 to 2550 Add as many options as required
2 Pt20%Rh/Pt40%Rh 0 to 1870 32 to 3398 Control options
3 W/W26%Re 0 to 2000 32 to 3632 NF On/Off control
(Englehard) DP Direct acting PID
4 W/W26%Re 0 to 2010 32 to 3650 control
(Hoskins) PD Power feedback
5 W5%Re/W26%Re 10 to 2300 50 to 4172 disabled
(Englehard) Cooling options
6 W5%Re/W26%Re 0 to 2000 32 to 3632 CF Fan cooling
(Bucose) CW Water cooling
7 Pt10%Rh/Pt40%Rh 200 to 1800 392 to 3272 CL Oil cooling
Front panel buttons
MD Auto/man button
disabled
Units RD Run/hold button
C Centigrade disabled
F Fahrenheit Programmer options
K Kelvin HD Dwell time in hours
X Blank HR Ramp rate in units/hour
(minutes is standard)

A-4 2416 Controller


Installation and Operation Handbook Understanding The Ordering Code

Notes:
1. PDSIO is a proprietary technique developed by Eurotherm for bi-directional
transmission of analogue and digital data between instruments.
Mode 1: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
a general load fault alarm.
Mode 2: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
load current and two alarms: solid state relay failure and heater circuit failure.
2. Range min and Range max: Thermocouple and RTD sensor inputs will always display
over the full operating range shown in Sensor input table. For these inputs, the values
entered here are the low and high setpoint limits. For process inputs, the values are the
display scaling. corresponding to the minimum and maximum input values.

2416 Controller A-5


Installation and Operation Handbook Safety Information

SAFETY and EMC INFORMATION


Please read this section carefully before installing the controller

This controller is intended for industrial temperature and process control applications when it
will meet the requirements of the European Directives on Safety and EMC. Use in other
applications, or failure to observe the installation instructions of this handbook may impair
the safety or EMC protection provided by the controller. It is the responsibility of the
installer to ensure the safety and EMC of any particular installation.
Safety
This controller complies with the European Low Voltage Directive 73/23/EEC, amended by
93/68/EEC, by the application of the safety standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection requirements of the EMC Directive
89/336/EEC, amended by 93/68/EEC, by the application of a Technical Construction File.
This instrument satisfies the general requirements of an industrial environment as described
by EN 50081-2 and EN 50082-2. For more information on product compliance refer to the
Technical Construction File.

SERVICE AND REPAIR


This controller has no user serviceable parts. Contact your nearest Eurotherm Controls agent
for repair.
Caution: Charged capacitors
Before removing an instrument from its sleeve, disconnect the supply and wait at least two
minutes to allow capacitors to discharge. Failure to observe this precaution will expose
capacitors that may be charged with hazardous voltages. In any case, avoid touching the
exposed electronics of an instrument when withdrawing it from the sleeve.
Electrostatic discharge precautions
When the controller is removed from its sleeve, some of the exposed electronic components
are vulnerable to damage by electrostatic discharge from someone handling the controller.
To avoid this, before handling the unplugged controller discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels or they will become illegible.
Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean
other exterior surfaces of the product.

2416 Controller B-1


Safety Information Installation and Operation Handbook

INSTALLATION SAFETY REQUIREMENTS

Safety Symbols
Various symbols are used on the instrument, they have the following meaning:
Caution, (refer to the Functional earth
! accompanying documents) (ground) terminal

The functional earth connection is not required for safety purposes but to ground RFI filters.
Personnel
Installation must only be carried out by qualified personnel.
Enclosure of live parts
To prevent hands or metal tools touching parts that may be electrically live, the controller
must be installed in an enclosure.
Caution: Live sensors
All isolated inputs and outputs have reinforced insulation to provide protection against
electric shock. The non-isolated dc, logic and PDSIO outputs are all electrically connected to
the main process variable input, (thermocouple etc.). If the temperature sensor is connected
directly to an electrical heating element then these non-isolated inputs and outputs will also
be live. The controller is designed to operate under these conditions. However you must
ensure that this will not damage other equipment connected to these inputs and outputs and
that service personnel do not touch connections to these i/o while they are live. With a live
sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs
and outputs must be mains rated.
Wiring
It is important to connect the controller in accordance with the wiring data given in this
handbook. Take particular care not to connect AC supplies to the low voltage sensor input or
DC or logic inputs and output. Only use copper conductors for connections (except
thermocouple inputs) and ensurethat the wiring installations comply with all local wiring
regulations. For example in the UK use the latest version of the IEE wiring regulations,
(BS7671). In the USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should
be in close proximity to the controller, within easy reach of the operator and marked as the
disconnecting device for the instrument.
Earth leakage current
Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the
design of an installation of multiple controllers protected by Residual Current Device, (RCD)
or Ground Fault Detector, (GFD) type circuit breakers.

B-2 2416 Controller


Installation and Operation Handbook Safety Information

Overcurrent protection
To protect the internal PCB tracking within the controller against excess currents, the AC
power supply to the controller and power outputs must be wired through the fuse or circuit
breaker specified in the technical specification.
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not
exceed 264Vac:
• line or neutral to any other connection;
• relay output to logic or dc sensor connections;
• any connection to ground.
The controller should not be wired to a three phase supply with an unearthed star connection.
Under fault conditions such a supply could rise above 264Vac with respect to ground and the
product would not be safe.
Voltage transients across the power supply connections, and between the power supply and
ground, must not exceed 2.5kV. Where occasional voltage transients over 2.5kV are
expected or measured, the power installation to both the instrument supply and load circuits
should include a transient limiting device.
These units will typically include gas discharge tubes and metal oxide varistors that limit and
control voltage transients on the supply line due to lightning strikes or inductive load
switching. Devices are available in a range of energy ratings and should be selected to suit
conditions at the installation.
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the controller is
mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a
suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of
the cabinet. Where condensation is likely, for example at low temperatures, include a
thermostatically controlled heater in the cabinet.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part of
the system should fail. In temperature control applications the primary danger is that the
heating will remain constantly on. Apart from spoiling the product, this could damage any
process machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process;
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on;
• an external valve or contactor sticking in the heating condition;
• the controller setpoint set too high.

2416 Controller B-3


Safety Information Installation and Operation Handbook

Where damage or injury is possible, we recommend fitting a separate over-temperature


protection unit, with an independent temperature sensor, which will isolate the heating
circuit.
Please note that the alarm relays within the controller will not give protection under all failure
conditions.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the temperature sensor while the
controller is still powered up. Under these conditions, as additional protection against
electric shock, we recommend that the shield of the temperature sensor is grounded. Do not
rely on grounding through the framework of the machine.

INSTALLATION REQUIREMENTS FOR EMC


To ensure compliance with the European EMC directive certain installation precautions are
necessary as follows:
• For general guidance refer to Eurotherm Controls EMC Installation Guide, HA025464.
• When using relay or triac outputs it may be necessary to fit a filter suitable for
suppressing the emissions. The filter requirements will depend on the type of load. For
typical applications we recommend Schaffner FN321 or FN612.
• If the unit is used in table top equipment which is plugged into a standard power socket,
then it is likely that compliance to the commercial and light industrial emissions standard
is required. In this case to meet the conducted emissions requirement, a suitable mains
filter should be installed. We recommend Schaffner types FN321 and FN612.
Routing of wires
To minimise the pick-up of electrical noise, the wiring for low voltage dc and particularly the
sensor input should be routed away from high-current power cables. Where it is impractical
to do this, use shielded cables with the shield grounded at both ends.

B-4 2416 Controller


Installation and Operation Handbook Technical Specification

TECHNICAL SPECIFICATION
Input
Range +100mV and 0 to 10Vdc (auto ranging)
Sample Rate 9Hz (110mS)
Resolution <1µV for +100mV range, <0.2mV for 10Vdc range
o
Linearity Better than 0.2 C
o
Calibration accuracy The greater of 0.25% of reading or + 1 C or +1LSD
User calibration Low and high offsets can be applied
Input filter Off to 999.9 secs
Thermocouple types Refer to the ordering code sensor input table
Cold junction >30 to 1 rejection of ambient temperature changes in automatic
TM
compensation mode. Uses INSTANT ACCURACY cold junction sensing
technology to eliminate warm up drift and to respond quickly to
ambient temperature changes.
o
External references 0, 45, and 50 C
RTD/PT100 input 3-wire, Pt100 DIN43750. Bulb current 0.3mA. Up to 22Ω in each
lead without error

Digital Outputs
Relay rating Min: 12V, 100mAdc. Max:2A, 264Vac resistive
Application: heating, cooling, alarms or program event
Single logic output 18Vdc, 20mA. This output is not isolated from the main process
value input. Application: heating, cooling, alarms or program event
Digital o/p functions As per the ordering code
Triac rating 1A, 30 to 264Vac resistive (isolated)

Analogue outputs
Range Scaleable between 0-10Vdc
0-20mA (non-isolated)
Analogue output Refer to ordering code
functions

Control functions
Control modes PID or PI with overshoot inhibition, PD, PI, P, or On/Off, or
motorised valve control
Cooling algorithms Linear, water (non-linear), fan (min on time), oil
Tuning One shot (automatic tune of PID and overshoot inhibition
parameters) and continuous adaptive tuning. Automatic calculation
of of manual reset value when using PD control.
Auto/manual control Bumpless transfer or forced manual output
Setpoint rate limit 0.00 to 999.9 display units per second, minutes or hour

2416 Controller C-1


Technical Specification Installation and Operation Handbook

Alarms
Number of alarms Four
Alarm types Absolute high or low. Deviation band, deviation high, deviation
low. Rate of change
Alarm modes Latching or non-latching. Blocking. Energised or de-energised in
alarm

Setpoint programming
Number of programs One or four
Segments per 16
program
Event outputs Up to two

Communications (all modules are isolated)


Modbus Š RS232,2-wire,RS 485 and 4 wire RS485 modules
Baud rate 1200, 2400, 4800, 9600 and 19,200 baud

PDSIO
Slave input (isolated) Remote setpoint input with holdback to master
Master output Isolated from main PV. Retransmission of setpoint, process value
or output

General
Display Dual, 4 digit x 7 segment LED. Up to two decimal places
Supply 85 to 264Vac, 48 to 62 Hz, 10 W max OR
24Vdc or ac -15%, +20%. 10W max
o
Operating ambient 0 to 55 C and 5 to 90% RH non-condensing
o
Storage temperature -10 to +70 C
Panel sealing IP65
Dimensions 48mm wide x 48mm high x 150mm deep
Weight 250g
EMC standards EN50081-2 & EN 50082-2 generic standards for industrial
environments
Safety standards Meets EN61010, installation category II (voltage transients must not
exceed 2.5kV), pollution degree 2
Atmospheres Not suitable for use above 2000m or in explosive or corrosive
atmospheres. Electrically conductive pollution must be excluded
from the cabinet in which this controller is mounted

C-2 2416 Controller


Installation and Operation Handbook Addresses

EUROTHERM CONTROLS LIMITED

UK SALES OFFICE
Eurotherm Controls Limited
Faraday Close, Durrington
Worthing
West Sussex BN13 3PL
Telephone Sales: (01903) 695888
Technical: (01903) 695777
Service: (01903) 695444
Fax (01903) 695666

email http://www.eurotherm.co.uk

Sales and support in over 30 countries worldwide


For countries not listed overleaf enquiries/orders to:

Eurotherm Controls Limited


Export Dept.,
Faraday Close, Durrington, Worthing
West Sussex, BN13 3PL
Telephone (01903) 268500
Fax (01903) 265982
Telex 87114 EUROWG G

2416 Controller D-1


Installation and Operation Handbook Load Current Monitoring and Diagnostics

Appendix E LOAD CURRENT MONITORING AND


DIAGNOSTICS
Current flowing in a system of electrical heating elements (the ‘Load’) can be displayed on
the controller by using a Eurotherm TE10 SSR fitted with intelligent current transformer,
PDCTX, or an SSR or contactor with an external PDCTX.
Load current monitoring and diagnostics may be used with any time proportioned output,
fitted in module position 1A, and uses the logic output wires which drive the SSR to return
signals back to the controller These signals represent the RMS value of the load current
during the ON period, or load related alarm conditions. It is not designed for analogue
outputs i.e. phase angle control.
It is also designed for single phase operation only.
There are three modes of operation:-

1. Mode 1
Detects if there is a break in the heater circuit. This includes heater or SSR open circuit. A
single Load Failure alarm message is displayed on the lower readout of the controller.

2. Mode 2
Provides the following:-

Display of true RMS load current On the Displays the true RMS current in the ON
lower readout of the controller state to the load.
Low current alarm Analogous to Partial Provides advanced warning of failure of
Load Failure (PLF) supplied in some one or more heaters in parallel
Eurotherm SSRs
High current alarm Activated when the Typically used where element bunching
heater exceeds a set limit may occur
SSR short circuit This will apply full power to the heaters
which could result in an over temperature
condition. This alarm provides early
warning.
Heater failure Indicates open circuit load conditions

2416 Controller E-1


Load Current Monitoring and Diagnostics Installation and Operation Handbook

1.

EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)

Hardware Required

1. Eurotherm SSR type TE10/PDS2 OR


2. Eurotherm intelligent current transformer type PD/CTX + contactor or zero voltage
switching SSR
2416 controller configured for PDSIO mode 2 option using logic output. This module must
be fitted in module position 1. (order code M2).

L N
Controller
Fuse 2A(T)
Alternative current regulator
+ L arrangements:-
1A
- C N
1B
O The Eurotherm TE10/PDS2 contains
M integral power regulator and intelligent
M
S Heater PDCTX
1 + power fuse The PDCTX can be supplied separately for
V+
PV (load use with any SSR or logic thyristor unit as
V- shown in the diagram below.
- dependent)
The output drive capability of the PDCTX is
5V at 7mA maximum

To logic output
To L 1A & 1B
This
represents
a single
- +
turn PDCTX
L N through the Intelligent
TE10 CT Current
Solid Transformer
State
Relay Logic input
SSR
To
- + Heater
- +

T/C
Heater

Figure E.1 Connections for Mode 1 & 2

WARNING!
Take care that the controller is correctly wired for the mode of operation which is
configured. Failure to do so may be hazardous in some situations.

E-2 2416 Controller


Installation and Operation Handbook Load Current Monitoring and Diagnostics

OPERATION
To Read Load Current (mode 2 only)

Do This This Is The Display You Should See Additional Notes


Current will be displayed in It will revert to the
From the ‘N./’ list
,0 the lower readout. See
also ‘Display Modes’
HOME display after
45 seconds or 10
Press until
 below. seconds if an alarm
is present
,0 is shown in
the upper display
This display will be shown if:
,0 I. The controller is unable to resolve the reading
II. The controller is obtaining a reading
BBBB III. The measurement has timed out i.e. current has
not flowed for 15 seconds.

To Display Load Current Continuously in the Lower Readout (mode 2 only)


Do This This Is The Display You Should See Additional Notes
From the ‘HOME’ Current will be
display, Figure 1.4, displayed in the
O0 lower readout
continuously when
Press until ,0 the controller reverts
O0 is shown in to the HOME
the upper display
display, see also
‘Display Modes’
Press or below.
until ,0 is
displayed in the
lower display

Display Modes
SSR RMS On State Current
This is the default state when high or low current alarms are configured. The load current
displayed is the steady state true rms current measured during the ON period.
The minimum on times are:-
Mode 2 0.1second

2416 Controller E-3


Load Current Monitoring and Diagnostics Installation and Operation Handbook

How Heater Alarms Are Displayed

Do This This Is The Display You Should See Additional Notes


HOME Display

If an alarm is Actual OP1 OP2 If more than one


alarm is active, the

D
present it will flash a Temperature
four character (PV) display will alternate
mnemonic in the )5 between the alarm
messages and the
lower display
default parameter in
the lower display

The Alarm Messages are:-

Mnemonic Meaning Description


The following two messages are alarms which are produced as a result of failure within the
process. In place of dashes the alarm number will appear i.e ,
, , or 
B)5 Alarm number Used for partial load failure detection. To avoid nuisance
- Low Current tripping due to supply voltage variations set to a value at
least 15% below the minimum normal operating current
B#5 Alarm number Used for load overcurrent protection. To avoid nuisance
- High Current tripping due to supply voltage variations set to a value at
least 15% above the maximum normal operating current.
Note: This alarm is not intended to provide
instantaneous safety protection from short circuit fault
conditions
The following message is a diagnostic alarm which appears for mode 1 operation only.
) Load Fail This includes failure of the heater circuit or the SSR
The following two messages are diagnostic alarms produced as a result of failure within the
equipment or wiring connections. They appear for modes 2 and 5 operation only. They may
be enabled using the O! parameter in the ) )O6, see ‘SHORT CIRCUIT SSR
ALARM AND HEATER FAIL ALARM’
#65D Heater Fail No current is being drawn while the controller output
demand signal is on
5D SSR Fail The load is continuously on while the controller output
demand signal is off

E-4 2416 Controller


Installation and Operation Handbook Load Current Monitoring and Diagnostics

TO SET THE ALARM TRIP LEVELS


Do This This Is The Display You Should See Additional Notes
From the HOME To select the Alarm
display ) List header

press until the )O6


) )O6 is
displayed


or  To select the
Press button indicates the alarm diagnostic alarm
number; parameter found
until the desired BBB indicates the under the Alarm List
alarm number is alarm type:- header
displayed e.g. )5 or #5
BBB
Press or
The alarm trip level
is set to 123
to adjust the alarm
trip level

SHORT CIRCUIT SSR ALARM AND HEATER FAIL ALARM


These alarms exist as Diagnostic Alarms in the controller. To make the alarm active it is
only necessary to turn on the diagnostic alarm feature in the Alarm List in the Operator Level
Do This This Is The Display You Should See Reason
From the HOME
This opens the list
display press
button until the )
) which contains the
)O6 is displayed )O6 O! mnemonic

Press until This activates the


O! is displayed O! mnemonic to
O! allow Diagnostic

@ Alarms to be
displayed in the
Press or lower readout of the
to select @ HOME display

RELAY OUTPUTS
Any plug in module can be used for alarms provided they are not already being used for
another purpose , such as control. Any one or more alarms can be attached to an output,
which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operating
external beacons or audible devices.

2416 Controller E-5


Load Current Monitoring and Diagnostics Installation and Operation Handbook

TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS


Configuration of PDS load current diagnostics is in four parts:-

1. Configure the Logic Module for PDSIO Mode 1 or 2 operation.


2. Configure the Low and High Current trip alarms.
3. Attach the alarms to operate an output relay.
4. Set up the Scaling Factor.

First enter Configuration Level. See Chapter 5

TO CONFIGURE THE LOGIC MODULE FOR PDSIO MODES 1 OR 2

Do This This Is The Display You Should See Additional Notes


This opens the
Press
 /.
until the
 configuration list
displayed
is
/. associated with
module position 1A

Press to show This shows the


O O identity of the
)/" module
The module identity
is logic output

Press to show
9. This shows the
function of module
9.
Press or
to show 5 or
5 The module function
is set to PDSIO
5
as required. mode 1

This is the lower PID


;)D)
Press to show demand level
;)D)
D To set the minimum
PID signal to 0%
Press or
to show D

E-6 2416 Controller


Installation and Operation Handbook Load Current Monitoring and Diagnostics

Press to show This is the upper


;)D#) ;)D# PID demand level
D To set the maximum
PID signal to 100%
Press or
to show D

Warning! If 87D) is set to


any figure other than 0 the This is the minimum
Press to show minimum output power will be
87D)
output power
87D) limited to this level. You must
D ensure that this does not
present an unsafe condition for
the process To set the min
Press or
output power to 0
to show D

87D#
Press to show This is the maximum
87D# output power
D To set the max
output power to 100
Press or
to show D

Press to show . This sets the output


signal to normal for
. ./5 heating control

Press or
to show ./5

2416 Controller E-7


Load Current Monitoring and Diagnostics Installation and Operation Handbook

TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS


Alarm 1 will be configured as Load Current Low ()5)
Alarm 2 will be configured as Load Current High (#5)
Do This This Is The Display You Should See Additional Notes
Press button This opens the
configuration list
until the ) /. ) which contains the
is displayed /. Alarms

After 0.5 sec the To select alarm 1


Press to show
) (alarm 1) ) display will blink to
)5 show the alarm type
has been accepted To make alarm 1 =
Press or Low Current
to show )5

Press until After 0.5 sec the To select alarm 2.


)
(alarm 2) )
display will blink to
appears #5 show the alarm type
has been accepted To make alarm 2 =
High Current
Press or
to show #5

Note:- The above alarms are known as SOFT ALARMS because they are indication
only.

E-8 2416 Controller


Installation and Operation Handbook Load Current Monitoring and Diagnostics

TO ATTACH SOFT ALARMS TO A RELAY OUTPUT


Any one alarm indicated above may be attached to an output (normally a relay).
Alternatively any combination of alarms may be attached to operate a relay using the
procedure below:-

Do This This Is The Display You Should See Additional Notes


Press “PAGE” key Any output module
as many times can be configured
as necessary to 
for an alarm output
/.  provided it is not
/. used for any other
purpose, eg as a
control output.
In place of  you
should select the
module required, i.e.
 or


A means that the


Press until BBBB denotes alarm 1 selected output will
BBB is displayed BBB followed by three letters activate when an
alarm occurs in
A which denote the alarm
type e.g. )5
normal operation
./ means the
Press or output will not
to select @ or
activate

Repeat the above


step for every alarm
to be attached to the
output

Alarms Connected to a
./5 Relay Output
3A
Soft N!
Alarms OR .
O.: Output
Module 3B

2416 Controller E-9


Load Current Monitoring and Diagnostics Installation and Operation Handbook

THE SCALING FACTOR


The value of the current displayed on the controller is scaled using the scaling factor. This is
found in the O.6 /. list. It is set, by default, to 100 and assumes a single turn
through the current transformer. If two turns are made through the current transformer it will
be necessary to adjust the scaling factor to 50 to obtain the same reading.
Under normal conditions you should not need to change the scaling factor.
If, however, you wish to change the sensitivity of the current reading, for example, to read
very low currents you may need to change the number of turns through the PDCTX and/or
adjust the scaling factor to compensate. See also note 1 below.

TO ADJUST THE SCALING FACTOR


Do This This Is The Display You Should See Additional Notes
Press button
O.6
until O.6 /. is /.
displayed

Press until
)D#O is displayed )D#O

Press or
to change the
scaling factor

Note 1:-
Minimum Resolvable Current
TE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10.
PDCTX 4A RMS for a single turn through the PDCTX
Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase
the number of turns through the PDCTX and adjust the scaling factor to compensate.
For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to
25 as shown in the table below.
Scalar = 100/N Where N = Turns through PDCTX
N Scalar N Scalar
1 100 5 20
2 50 10 10
4 25

Maximum Resolvable Current


TE10 Determined by the maximum range of the SSR
PDCTX 100A (or 100 ampere turns)

Finally Exit configuration level. See Chapter 5.

E-10 2416 Controller

Informações sobre programação


www.soliton.com.br - e-mail: soliton@soliton.com.br

SOLITON CONTROLES INDUSTRIAIS LTDA


Rua Alfredo Pujol, 1010 - Santana - São Paulo - SP.
Tel:11 - 6950-1834 / Fax: 11 - 6979-8980 - e-mail: vendas@soliton.com.br

You might also like