Main Control Board User Manual
Main Control Board User Manual
Main Control Board User Manual
USER MANUAL
V - 1.0
SKY 301 USER MANUAL
2
CONTENTS
3
SKY 301 SPECIFICATIONS
4
EXPLANATION OF TERMINALS
R, S, T _______________ System Main Phases
MP (N) ______________ Neutral
U, V, W ______________ Fast Motor Outputs
U1, V1, W1____________Slow Motor Outputs
10A__________________ Security Circuit Neutral
11A__________________ Security Circuit 140 Turning (Contactor Coil Voltage)
110__________________ Security Circuit Supply
120___________________Security Circuit Stop Turns
130___________________Security Circuit Door Turns
140___________________Security Circuit Lock Turns
1F____________________Phase (direct connected to the one of the system main phases)
1_____________________Car Socket Voltage (220V AC)
2_____________________Car Lamp (220V AC)
810 & 2001_____________Pump
840 & 2000_____________Brake
401 – 408______________ Car Call Button Inputs and Lamps (common 100)
142___________________ For Two Speed Systems – Level Stopper Magnet (common 100)
817___________________ Lower-Level Stopper Magnet (common 100)
818___________________ Top-Level Stopper Magnet (common 100)
803___________________ Min load Contact (common 100)
804___________________ Overload Contact (common 100)
805___________________ Full load Contact (common 100)
KK ___________________Contactor Feedback (common 100)
869___________________ Revision Switch Input (common 100)
500___________________ Revision Down Input (common 100)
501___________________ Revision Up Input (common 100)
M1___________________ Magnet Switch for Floor Selection (common 100)
K20__________________ Automatic Door Open Button (common 100)
DTS__________________ Automatic Door Close Button (common 100)
01____________________Overload Indicator (common 100)
02____________________Out of Service Indicator (common SCOM connector)
12____________________Busy Indicator (common SCOM connector)
031___________________Down Indicator (common SCOM connector)
032___________________Up Indicator (common SCOM connector)
a.b.c.d.e.f.g.2g_________ Digital Display Outputs 24V DC ( common100)
GP1__________________ Auxiliary Input (common100)
+24___________________Digital Common
100___________________ (+) 24V DC
1000__________________ (–) 24V DC
190___________________Simple Control Common
K3___________________ Automated Door Close Signal (common K15)
K5___________________ Automated Door Open Signal (common K15)
K15__________________ K3 - K5 Common Input
YED_________________ Auxiliary Relay Contact
YED_________________ Auxiliary Relay Contact
5
SKY 301 PARAMETER SETTINGS
1. Press the ‘enter’ button to enter the parameter settings menu,
2. Press ‘up’ or ‘down’ buttons in order to find the desired setting,
3. Press ‘enter’ button to change the value of the desired parameter, the chosen parameter is
going to be blink, set the parameter to desired value by using ‘up’ and ‘down’ buttons (if you
don’t want to store the value in memory press ‘escape’ button),
4. After setting the parameter value, press ‘enter’ button to memorize it, then it passes the next
parameter.
5. Press ‘escape’ button to exit from parameter settings menu.
6
AUXILIARY INPUT AND OUTPUT SETTINGS
There are;
o 1 auxiliary input
o 1 auxiliary output (relay), existing on the board for general purpose.
If there occurs a problem in one of the inputs on the card (T2, 142, 817, 818, M1, KG, 869, 500,
501, 803, 804, 805, K20, DTS) as a result of any reason such as short circuiting or wrong
wiring… change the parameter input with the auxiliary input (GP1) without moving the card out
of the panel. After this change the card will continue its normal operation.
o Put off the wire of the ‘142’ connector on the card and put the same wire on
‘GP1’ connector.
o Enter the parameter settings menu and come to the ‘aux. input sel’ parameter,
o Press ‘enter’ button, set the ‘aux. input’ value as ‘142’ by using the ‘up’ button.
Press ‘enter’ button to store last change in the memory. After this setting the
‘GP1’ input will operate as ‘142’ input.
o This process can be applied to the all inputs on the card
If there occurs a problem with one of the relays on the card (RU1, RU2, RH, RF, LIR, KLR,
AUTO, 031, 032, 01, 02, 12) this auxiliary input can be used instead of the broken relay.
o Change the wire of ‘P1’ connector with the one of the ‘YED’ connector, and the
wire of ‘P2’ connector to the other ‘YED’ connector,
o In the parameter settings mode, find the ‘aux. output sel.’ parameter and press
‘enter’ button,
o Choose ‘auxiliary output’ as ‘LIR’ by using ‘up’ button and memorize it by
pressing ‘enter’ button,
o This process can be applied to the all relay outputs on the card.
7
SKY 301 PARAMETER LIST
PARAMETER SETTING LIMITS FACTORY VALUE EXPLANATION
PANEL GET Be operated at inspection
INSPECTION mode on card
- simple collection
COLLECTION TYPE simple control
- mixed collection
-manual
DOOR TYPE -half automatic manual
-full automatic
-one speed
OPERATION TYPE -two speed Two speed
-speed control
-M1 counter
MAGNET STRING M1 counter
-encoder
8
PARAMETER SETTING LIMITS FACTORY VALUE EXAMPLE
Time to go to the park floor
PARK TIME 3 – 99 s 10 s after turn off the busy
indicator
After pump pull, lock will
LOCK TIME 5 – 15 s 8s wait up to the chosen value
9
CAUTIONS FOR PREMONTAGE
In order to be exact convenience of the lift system to the EN 81-1/2 standards as electrically, the
control card, control panel, security circuit and electrical connections must be convenient to
concerned standards. The producers whom willing to build panel with SKY 301 must have
enough level of information and experience about EN 81-1/2 standard and other standards,
regulations, and instructions. SKY ELEVATOR assumes no responsibility for panels not build
towards the given directions. SKY ELEVATOR guarantees that SKY 301 is convenience to the
EN 81-1/2 but inside and outside connections of the control panel and other electrical
connections are under responsibility of mounter.
There must be 10mm distance between the SKY 301 control card and the panel.
The SKY 301 control card must be fixed from 4 holes at the edges.
After the puncturing to place SKY 301 card and other components in the panel, the panel
must be cleaned very carefully from iron pieces and conductor wires otherwise these
pieces can be cause damage while transferring the panel from somewhere to another.
The contactors that are used for the AC motor lifts must be chosen according to the
EN60947 AC3 class and must be enduring for the motor power. The connection must be
done according to the directions shown in the SKY 301 schema.
The cooperative motor placed on the main contactors must be chosen according to the
EN60947 and must be controlled that contactors are active/inactive in the same time with
power contacts.
The bridge diode connections of the brake and pump must be done according to the
schema and must be used isolated lugs.
Panel manufacturer must control all the connections and do the required tests after
finishing the panel.
10
CAUTIONS FOR MONTAGE
The information given in this section must be taken as suggestion and SKY ELEVATOR
assumes no responsibility for any damage caused during the applications of the given
information.
The connections between the control panel and motor; car and lift shaft must be done
carefully according to the SKY 301 schema.
The 3-phase supply voltage must be connected to the R, S, T connectors on the panel
with suitable fuse (chose due to motor power) and network neutral must be connected to
the MP connector.
Grounding cables and neutral must be separately connected and the panel body must be
perfectly grounded.
All stopper linkages specified in EN 81-1/2 standards must be placed in lift and the
connections of these linkages must be done to the control panel according to the SKY
301 schema. All the used contactors must be convenient to the EN 60947 standards.
11
CAUTIONS FOR INSTALLATION OF CONTROL PANEL
Be sure that the connections between the control panel and lift system are done according
to the SKY 301 schema.
Control if there is any short circuit in the connections with a suitable measuring device.
Take the ‘motor protection circuit stopper’ to ‘ON’ position and turn on the panel electric.
Control that the led of ‘02’ on the board and ‘out of service’ lamp on the floor buttons are
light up.
Control that the voltage between the 100 – 1000 connectors is 20-26V DC.
Be sure that all security contacts are connected according to the schema and operates
correctly. Control the security inputs activity from 120, 130, 140 leds.
The revision switch on the control panel is in ON position so the car will operate only at
low speed. Control that the low speed coil is correctly coiled by routing the car with the
up and down buttons placed on the control panel. If the car goes to wrong direction
change place of any two ends (U2, V2, W2) of low speed coil on the control panel.
Measure the voltage between 2001 – 810 and 2000 – 840 connectors while car is in
motion. The value must be in 180 – 240V DC interval.
Place the car on one of the middle floors and take the ‘car top revisions switch’ to ‘OFF’
position. The ‘Out of Service’ indicators will turn off on the floor buttons
Be sure that the lift going the true direction by giving log (call)s if it operated wrong
change place of any two connections (U2, V2, W2).
12
CAUTION!
WHEN THE LFIT OPERATES NORMALLY, 817 AND 818 BISTABIL SWITCHES
MUST NOT BE SHORTED WITH THE ‘100’ CONNECTOR.
CAUTION!
THE SECURITY PARAMETERS (120 STOP - 130 DOOR – 140 LOCK) MUST NOT BE
SHORTENED.
CAUTION!
In case of a problem sent the card to the producer firm for control and fix.
13
RISK ANALIZE
The contactor connector (11A) on the SKY 301 card must be connected to the security
system turning.
Panel direction and motion connectors do not be closed by hand. In such case security
circuits can not block motion of the lift.
The 24V AC fuse on the card must not be shunted. If the fuse blows constantly look for a
short circuit at the shaft system and inside the panel.
Car lamp supply voltage (1F) must be connected to the one of the main phases before
thermic relay.
When motor calefacted, the motor thermistor ends must be connected to the ‘T2’
connector to avoid the car stay between the floors.
Door frames must be connected to the grounding bar. If grounding is not proper, security
circuits have a risk of shunted through door chassis.
After long time operations, dust, dirt, oil can be affect the performance of the security
system. Please do not ignore plug and lock functions in periodic controls.
Sky Elevator
ISTANBUL
Tel:+90 2124441988
www.sky-elevator.com
14
15