Generator Room Ventilation

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 7
At a glance
Powered by AI
The documents contain calculations for sizing ventilation systems for generator rooms, transformer rooms and engine rooms. Factors like heat dissipation, allowable temperature rise and flow velocity are considered to determine airflow requirements. Intake and exhaust areas are then sized based on the airflow and velocity.

The ventilation requirements are calculated for generator rooms, transformer rooms and engine rooms housing electrical equipment like generators and transformers. The calculations provide the airflow needed to prevent the room temperature from rising above recommended limits.

The factors considered in calculating ventilation requirements include the heat dissipated by the equipment, the design/allowable room temperature and temperature rise, and the airflow equation relating airflow to temperature difference.

Design calculation sheet

Project no: AN07066 Date: 18/02/08 Sheet no.: 1 of 1 Computed by:

Subject: Generator Room Checked by:

Louvers Sizing Approved by:

Generator : Cummins Model : Caterpillar 1000 kVA


kw = kVA x cosΦ
Number of Generators : 1 Active + 0 Stand by cosΦ = 0.8

Radiator Fan "ON" when Generator "OFF" for Cooling

Design Temperature Maximum Allowable Room Temp. Resulting Allowable ⌂T

40 ºC 50 ºC 10 ºC = 18 ºF

Heat Rejected to Ambient by 1 generator when running:


Engine Dissipation = 717188 Btu/hr
Generator Dissipation = Btu/hr Total =
717188 Btu/hr
per generator
Ventilation Requirements to prevent temperature rise above recommended limit
cfm = Q = 717188 = 36893 cfm
1.08 x ⌂T 1.08 x 18 17411 lps
per generator
Air Flow as per catalogue per generator:
Radiator Cooling Air = m3/min
Combustion air = m3/min
0 m3/min = 49160 cfm

Intake area, is based on 1000 fpm velocity


Q = A x V => A= Q = 49160 = 49 ft2 = 4.6 m2
V 1000
Using an Intake Louver Free Area of 50%
Gross Net
Intake Area per Generator: 9.1 m2 4.6 m2

Total Required Intake Area for Gross Net


1 Operating Generators 9.1 m2 4.6 m2

Exhaust area, based on 1000 fpm velocity


Q = A x V => A= Q = 49160 = 49 ft2 = 4.6 m2
V 1000
Using an Intake Louver Free Area of 50%
Gross Net
Exhaust Area per Generator 9.1 m2 4.6 m2
Total Required Intake Area for
1 Operating Generators 9.1 m2 4.6 m2
Design calculation sheet
Project no: AN07066 Date: 18/02/200 Sheet no.: 1 of 1 Computed by: Chadi Sassine

Subject: Transformer Room Ventilation Checked by: Jad Laham

Approved by: Jad Laham

Transformer : France Transfo Model : 1000 kVA


kw = kVA x cosΦ
Number of Transformer : 1 cosΦ = 0.8

Design Temperature Maximum Allowable Room Temp. Resulting Allowable ⌂T

30 ºC 40 ºC 10 ºC = 18 ºF

Heat Rejected to Ambient by 1 Transformer: 30 kW = 102360 Btu/hr


per Transformer

Total Heat Generation : 1 Transformers 30 kw = 102360 Btu/hr


Total
Ventilation Requirements per Transformer

cfm = Q = 102360 = 5266 cfm


1.08 x ⌂T 1.08 x 18 2486 lps
per transformer
Total Ventilation Requirements per 1 Transformers
1 x 5266 = 5266 cfm
2486 lps
Total

Intake area, is based on 200 fpm velocity


Q = A x V => A= Q = 5266 = 26.4 ft2 = 2.5 m2
V 200
Using an Intake Louver Free Area of 50%
Gross Net
Intake Area per Transformer 5.0 m2 2.5 m2

Total Required Intake Area for Gross Net


1 Operating Transformer 5.0 m2 2.5 m2

Exhaust area, based on 200 fpm velocity


Q = A x V => A= Q = 5266 = 26 ft2 = 2.4 m2
V 200
Using an Intake Louver Free Area of 50%
Gross Net
Exhaust Area per Transformer 4.9 m2 2.4 m2
Total Required Intake Area for
1 Operating Transformer 4.9 m2 2.4 m2
Design calculation sheet
Project no: Date: Sheet no.: of Computed by:

Subject: Checked by:

Approved by:

Generator : Cummins Model : KOHLER 600ROZD-4 675 kVA


kw = kVA x cosΦ
Number of Generators : 1 Active + 0 Stand by cosΦ = 0.8

Radiator Fan & Generator "OFF" : No Cooling

Design Temperature Maximum Allowable Room Temp. Resulting Allowable ⌂T

40 ºC 50 ºC 10 ºC = 18 ºF

Heat Rejected to Ambient by 1 generator has shut down:

Total = 100,000 Btu/hr per generator

Ventilation Requirements to prevent temperature rise above recommended limit


cfm = Q = 100000 = 5145 cfm
1.08 x ⌂T 1.08 x 18 2429 lps
per generator

Intake area, is based on 200 fpm velocity

Q = A x V => A= Q = 5145 = 26 ft2 = 2.4 m2


V 200
Using an Intake Louver Free Area of 50%
Gross Net
Intake Area per Generator: 4.8 m2 2.4 m2

Total Required Intake Area for Gross Net


1 Operating Generators 4.8 m2 2.4 m2

Exhaust area, based on 250 fpm velocity

Q = A x V => A= Q = 5145 = 21 ft2 = 1.9 m2


V 250
Using an Intake Louver Free Area of 50%
Gross Net
Exhaust Area per Generator 3.8 m2 1.9 m2
Total Required Intake Area for
1 Operating Generators 3.8 m2 1.9 m2
25% Radiator Fan "ON" when Generator "OFF" for Cooling
30% Radiator Fan & Generator "OFF" : No cooling
40%
50%
55%
60%
65%
70%
75%