This document provides calculations for sizing ventilation requirements for a generator room and transformer room. It calculates heat loads, required airflow, and intake/exhaust area sizes for different equipment configurations including generators running, generators off with radiator fan cooling, and generators off with no cooling. Intake and exhaust areas are based on specified air velocities and a louver free area of 50% is used. Total required intake/exhaust areas are presented for the number of active generators and transformers.
This document provides calculations for sizing ventilation requirements for a generator room and transformer room. It calculates heat loads, required airflow, and intake/exhaust area sizes for different equipment configurations including generators running, generators off with radiator fan cooling, and generators off with no cooling. Intake and exhaust areas are based on specified air velocities and a louver free area of 50% is used. Total required intake/exhaust areas are presented for the number of active generators and transformers.
This document provides calculations for sizing ventilation requirements for a generator room and transformer room. It calculates heat loads, required airflow, and intake/exhaust area sizes for different equipment configurations including generators running, generators off with radiator fan cooling, and generators off with no cooling. Intake and exhaust areas are based on specified air velocities and a louver free area of 50% is used. Total required intake/exhaust areas are presented for the number of active generators and transformers.
This document provides calculations for sizing ventilation requirements for a generator room and transformer room. It calculates heat loads, required airflow, and intake/exhaust area sizes for different equipment configurations including generators running, generators off with radiator fan cooling, and generators off with no cooling. Intake and exhaust areas are based on specified air velocities and a louver free area of 50% is used. Total required intake/exhaust areas are presented for the number of active generators and transformers.
Download as XLS, PDF, TXT or read online from Scribd
Download as xls, pdf, or txt
You are on page 1of 7
At a glance
Powered by AI
The documents contain calculations for sizing ventilation systems for generator rooms, transformer rooms and engine rooms. Factors like heat dissipation, allowable temperature rise and flow velocity are considered to determine airflow requirements. Intake and exhaust areas are then sized based on the airflow and velocity.
The ventilation requirements are calculated for generator rooms, transformer rooms and engine rooms housing electrical equipment like generators and transformers. The calculations provide the airflow needed to prevent the room temperature from rising above recommended limits.
The factors considered in calculating ventilation requirements include the heat dissipated by the equipment, the design/allowable room temperature and temperature rise, and the airflow equation relating airflow to temperature difference.
kw = kVA x cosΦ Number of Generators : 1 Active + 0 Stand by cosΦ = 0.8
Radiator Fan "ON" when Generator "OFF" for Cooling
Design Temperature Maximum Allowable Room Temp. Resulting Allowable ⌂T
40 ºC 50 ºC 10 ºC = 18 ºF
Heat Rejected to Ambient by 1 generator when running:
Engine Dissipation = 717188 Btu/hr Generator Dissipation = Btu/hr Total = 717188 Btu/hr per generator Ventilation Requirements to prevent temperature rise above recommended limit cfm = Q = 717188 = 36893 cfm 1.08 x ⌂T 1.08 x 18 17411 lps per generator Air Flow as per catalogue per generator: Radiator Cooling Air = m3/min Combustion air = m3/min 0 m3/min = 49160 cfm
Intake area, is based on 1000 fpm velocity
Q = A x V => A= Q = 49160 = 49 ft2 = 4.6 m2 V 1000 Using an Intake Louver Free Area of 50% Gross Net Intake Area per Generator: 9.1 m2 4.6 m2
Total Required Intake Area for Gross Net
1 Operating Generators 9.1 m2 4.6 m2
Exhaust area, based on 1000 fpm velocity
Q = A x V => A= Q = 49160 = 49 ft2 = 4.6 m2 V 1000 Using an Intake Louver Free Area of 50% Gross Net Exhaust Area per Generator 9.1 m2 4.6 m2 Total Required Intake Area for 1 Operating Generators 9.1 m2 4.6 m2 Design calculation sheet Project no: AN07066 Date: 18/02/200 Sheet no.: 1 of 1 Computed by: Chadi Sassine
1.08 x ⌂T 1.08 x 18 2486 lps per transformer Total Ventilation Requirements per 1 Transformers 1 x 5266 = 5266 cfm 2486 lps Total
Intake area, is based on 200 fpm velocity
Q = A x V => A= Q = 5266 = 26.4 ft2 = 2.5 m2 V 200 Using an Intake Louver Free Area of 50% Gross Net Intake Area per Transformer 5.0 m2 2.5 m2
Total Required Intake Area for Gross Net
1 Operating Transformer 5.0 m2 2.5 m2
Exhaust area, based on 200 fpm velocity
Q = A x V => A= Q = 5266 = 26 ft2 = 2.4 m2 V 200 Using an Intake Louver Free Area of 50% Gross Net Exhaust Area per Transformer 4.9 m2 2.4 m2 Total Required Intake Area for 1 Operating Transformer 4.9 m2 2.4 m2 Design calculation sheet Project no: Date: Sheet no.: of Computed by:
Subject: Checked by:
Approved by:
Generator : Cummins Model : KOHLER 600ROZD-4 675 kVA
kw = kVA x cosΦ Number of Generators : 1 Active + 0 Stand by cosΦ = 0.8
Radiator Fan & Generator "OFF" : No Cooling
Design Temperature Maximum Allowable Room Temp. Resulting Allowable ⌂T
40 ºC 50 ºC 10 ºC = 18 ºF
Heat Rejected to Ambient by 1 generator has shut down:
Total = 100,000 Btu/hr per generator
Ventilation Requirements to prevent temperature rise above recommended limit
cfm = Q = 100000 = 5145 cfm 1.08 x ⌂T 1.08 x 18 2429 lps per generator
Intake area, is based on 200 fpm velocity
Q = A x V => A= Q = 5145 = 26 ft2 = 2.4 m2
V 200 Using an Intake Louver Free Area of 50% Gross Net Intake Area per Generator: 4.8 m2 2.4 m2
Total Required Intake Area for Gross Net
1 Operating Generators 4.8 m2 2.4 m2
Exhaust area, based on 250 fpm velocity
Q = A x V => A= Q = 5145 = 21 ft2 = 1.9 m2
V 250 Using an Intake Louver Free Area of 50% Gross Net Exhaust Area per Generator 3.8 m2 1.9 m2 Total Required Intake Area for 1 Operating Generators 3.8 m2 1.9 m2 25% Radiator Fan "ON" when Generator "OFF" for Cooling 30% Radiator Fan & Generator "OFF" : No cooling 40% 50% 55% 60% 65% 70% 75%