ADR-833

ANALOG ADDRESSABLE
EXTINGUISHING CONTROL UNIT

Technical Manual

Manufacturer TELEFIRE Fire & Gas Detectors LTD


5 Halapid St.
P.O.B. 7036
Petach Tikva 49250
Israel

Tel: ++ 972 3 921 1955

Fax: ++ 972 3 921 1816

Email: marketing@telefire.co.il 31 October 2002


Web Site: www.telefire.co.il Rev.: 1.12
Telefire ADR-833
Rev 1.12 31 October 2002

General
The ADR-833 Automatic Extinguishing Control Unit is intended to supervise, control and
activate automatic extinguishing systems.
The ADR-833 is a multi-input/output control unit connected and supervised by the
analog addressable control panel ADR-3000.
The fire detectors belonging to the automatic extinguishing system are monitored from
the analog addressable control panel. The extinguishing control and command are
performed by the ADR-833, via the analog detection loop.
The ADR-833 contains 3 supervised outputs, 2 relays and 3 supervised inputs. The
outputs activate: (a) the automatic extinguishing cylinders, (b) the fire alarm horn and (c)
the evacuation announciators. The relays are: one for trouble and the other for alarm.
The inputs are: (a) manual extinguishing release – electrically, (b) extinguishing inhibit
and (c) extinguishing cylinder pressure switch (refer to figure 1).
The ADR-833 operates on 24Vdc supply fed directly from the control panel or from a
remote power supply such as Telefire's ADR-34A Analog Addressable Power Supply or
ADR-9090P Analog Addressable Power Supply.
The ADR-833 is an analog addressable device controlled by the analog addressable
control panel and occupies only one address, even with the several inputs and outputs.

Keypad and Display


The ADR-833 has an LCD display consisting of two rows of 20 characters each, in
addition to the LED Lamps that indicate alarm, trouble or normal operation statuses.
The keypad contains four buttons:
1. Extinguishing inhibit button – to abort the automatic extinguishing process during the
countdown.
2. Bell or buzzer silence – to silence alarm or trouble signals.
3. Reset button.
4. Menu button – reserved for future use.

Inputs and Outputs


In the ADR-833 all input and output lines are supervised and protected against short
circuit and disconnection. They are terminated with an End-Of-Line (E.O.L.) resistor of
5.1 K at the end of each line.
In case of trouble in one of the lines, the yellow Trouble LED will turn on and the trouble
description will be displayed on the LCD screen. For example, short on the
extinguisher’s pressure switch line will be displayed as –

TROUBLE

PRESSURE SW. SHORT


A message is sent to the analog addressable control panel and from the control panel to
the RM-4005 Remote Panels – if any are installed.

– Page 1 –
Telefire ADR-833
Rev 1.12 31 October 2002

In addition, the local trouble buzzer will sound. To silence the buzzer, use the silence
button. The trouble buzzer is silenced only on the ADR-833 unit. This does not affect
the trouble signaling, either on the main control panel, or on the remote panels.
After the silencing, the word SILENCED blinks on the LCD. Fixing the trouble will
automatically cancel the trouble display and restore the unit to normal operation.

Unit Operation

Programming and Installation


Prior to the ADR-833 installation and connection, you should program the address using
the PROG-4000 Analog Addressable Programming Unit.
Connect all the input and output devices while the ADR-833 is not energized from the
power source (refer to figure 2).
Before connecting the automatic extinguishing, perform a test by connecting a dummy
load to perform a simulation and system testing. It is recommended to leave the system
with the dummy load for up to one week, to ensure the system’s proper operation and
sensitivity adjustment.
After concluding the test period, remove the dummy load and connect the automatic
extinguishing cylinders.

Fuses
The ADR-833 Automatic Extinguishing Control Unit operates on 24Vdc and is protected
by a 1A fuse, located on the printed circuit board.
In case of a blown fuse, the ADR-833 continues to operate only in the supervision mode
powered from the detection line.
The trouble message is displayed on the LCD as follows –

TROUBLE

FUSE F1 BLOW OUT


The trouble LED does not light and a trouble message is sent to the main control unit.
Replace the blown fuse with a new one of the same specifications and value.

Extinguishing Inhibit
Extinguishing inhibit can be done in two cases:
1. In normal operation, before performing system maintenance.
2. When receiving a fire alarm and after deciding to abort the automatic extinguishing
process during the countdown.

– Page 2 –
Telefire ADR-833
Rev 1.12 31 October 2002

Pressing the extinguishing inhibit button, will stop the automatic extinguishing process
and will display the following message on the LCD screen –

TROUBLE

EXTINGUISHER INHIBIT
The yellow trouble LED will light and a trouble message will be sent to the main control
unit.
To silence the local buzzer use the silence button.
Press the reset button to cancel the extinguishing inhibit condition and restore the
system normal operation.

Fire Alarm
During a fire alarm, the fire red LED will light, the alarm message will be displayed on the
LCD screen, the unit’s buzzer will sound and the alarm horn will sound – if connected.
Silencing the alarm will affect the local alarm devices only, and will not affect the rest of
the alarm devices belonging to the main system.

Automatic Extinguishing
After receiving a fire alarm signal from the detectors belonging to the automatic
extinguishing system and performing the ADR-833 activation conditions as programmed
in the main control unit, the unit will start the automatic extinguishing process.
At the beginning, the evacuation output will be activated and after the pre-set time delay,
the automatic extinguisher will be activated.
The following message will be displayed on the LCD screen:

ALARM

EXTING. ACTIVATED
Even after pressing the reset button, the message will remain on the LCD screen and a
trouble message will be sent and displayed on the main control panel, to ensure
replacing the empty extinguishing cylinder.
Only after initiating the unit on the main control panel by an authorized person, the ADR-
833 will resume to normal operation.
The initiating process is done by entering the device program menu on the control panel,
entering the access code, selecting the ADR-833 address and pressing the Program
button.

– Page 3 –
Telefire ADR-833
Rev 1.12 31 October 2002

Analog Detection Line

24Vdc in

Alarm Horn

LCD Display

Evacuation Signal

Pressure Switch

Alarm Contact

Extinguisher Command
Trouble Contact

FIRE FIRE

Manual Release Switch Abort Switch


ADR-833-001 (10/02)

FIGURE -1: Extinguishing devices connected to the adr-833 control unit

– Page 4 –
Telefire ADR-833
Rev 1.12 31 October 2002

O.K

ALARM

TROUBLE
ADR-833 EXTINGUISHING CONTROL UNIT

MENU
INHIBIT SILENSE RESET
FUSE 1A

ANALOG 24VDC PUSH EXTING PRESS EXTING HORN EVAC ALARM TROUBLE
LINE IN BUTTON INHIBIT SWITCH OUT OUT OUT CONTACT CONTACT
PROG + - + - + - + - + - + - + - + - NC C NO NC C NO

For auxiliary command


Programming Main
connector fuse

24 Vdc supply from the control Evacuation output


panel or remote power
supply such as Telefire’s ADR-34A
or ADR-9090P Manual release Horn output
push button

Abort switch Extinguishing command output

Extinguisher pressure switch output

FIGURE -2: Extinguishing field connections

Certification
Telefire's ADR-833 Analog Addressable Extinguishing Control Unit has the following
approvals:
• SI 1220 Approved
• EN54 Approved

– Page 5 –