Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PSBU-021-QSK50 - 1750 - 1825kVA-Rev-2 - 19 June 2018

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Diesel Generator Set

QSK50 Series
1750-1825kVA

Reliable and Durable Standard Scope


Cummins ‘QSK50 series’ diesel engine is a V 16
®
Engine: Cummins® ‘QSK50 series’ direct injection,
cylinder engine with a 50 litre displacement. Cummins water cooled engine, 16 cylinder, 4 stroke, rated at
heavy-duty engine, Robust Platform - Rugged 4-cycle, 1500 RPM, conforming to ISO 3046 / IS 13018 has the
industrial diesel delivers reliable power, low emissions following specifications:
and fast response to load changes. High pressure fuel ƒƒCummins Full Authority electronics
pump, Modular Common Rail fuel System (MCRS) and ƒƒCummins MCRS - Fuel System
state of the art integrated electronic control system ƒƒCummins turbocharger, pulse tuned exhaust manifold,
provide superior diagnostics. Enhanced reliability of the stainless steel exhaust flexible connections (2 Turbos)
engine through a more powerful filtration system. This ƒƒPlate type lube oil coolant inhibitor
Quantum series utilizes sophisticated electronics and ƒƒOutboard aftercoolers
premium engineering to provide outstanding performance ƒƒFull flow paper element filters - fuel, lube oil
levels, reliability and versatility. Each component has been ƒƒDry type replaceable paper element air cleaner with
specifically developed and rigorously tested for G-Drive restriction indicator
products, ensuring high performance, durability and ƒƒFlywheel housing & flywheel to suit single / double
reliability. (optional) bearing alternator
ƒƒStarting motor – Electric
Unmatched Warranty ƒƒBattery charging alternator
Cummins® ‘QSK50 series’ diesel engine generating sets ƒƒCummins PowerCommand® microprocessor based
are a truly cost effective solution to long term power need genset controller
backed by industry best, 2 years / 5000 hrs warranty for ƒƒFirst fill of lube oil and coolant
Prime Rated Gensets and 2 years / 1000 hrs (500 hrs/
year) for Standby Rated Gensets. Alternator: Stamford brushless alternator
ƒƒSeperately excited, self-regulated
ƒƒSalient pole revolving field
Cummins Advantage ƒƒSingle / double bearing
Special features of Cummins® ‘QSK50 series’ engines ƒ VPI epoxy impregnated insulation technology
like full authority electronic injection, low temperature ƒƒRe-greasable deep groove Single bearing
aftercooler, optimised turbocharging and precision ƒ Excitation - PMG based brushless
injection timing make these engines the ultimate in
exceptional fuel efficiency all across the operating range. Accessories:
ƒƒSilencer suitably optimized to reduce noise
Single Source Power Assurance ƒƒSturdy base rail
Design, manufacture and testing of engine, alternator ƒƒ990 ltrs. free standing fuel tank
and other accessories is done by Cummins Group of ƒƒBatteries with connecting leads and terminals
companies for optimum performance and is backed by
a countrywide product support network with a single
source responsibility for the entire package.
Diesel Generator Set QSK50 Series Specification Sheet

Optionals Alternator data


Engine: Lube oil / Coolant heater with thermostatic switch, ƒƒLine-to-neutral and line-to-line AC volts
Air Starter ƒƒ3-phase AC current
Alternator: Space heater, RTDs (Std. for HT), BTDs, Double ƒƒFrequency
Bearing ƒƒkW, kvar, power factor kVA (three phase and total)
Control Panel: AMF control panel, Battery charger, Remote/ Engine data
Auto start panel, Auto/Manual synchronizing panel, Audio/ ƒƒDC voltage
Visual annunciation for faults ƒƒEngine speed
ƒƒLube oil pressure
ƒƒCoolant temperature/ low level
Control panel: PowerCommand® PC 3.3 ƒƒComprehensive FAE data (where applicable)
The PowerCommand® control Other data
system is an integrated ƒƒGenset model data
microprocessor based ƒƒStart attempts, starts, running hours, kW hours
generator set control system ƒƒLoad profile (operating hours at % load in 5% increments)
providing voltage regulation, ƒƒFault history
engine protection, alternator ƒƒData logging and fault simulation (requires InPower)
protection, operator interface and
isochronous governing.
Standard control functions
Digital governing
AmpSentry – Includes integral AmpSentry protection, which
ƒƒIntegrated digital electronic isochronous governor
provides a full range of alternator protection function which are
ƒƒTemperature dynamic governing
matched to the alternator provided.
Digital voltage regulation
Power management –Control function provides battery
ƒƒIntegrated digital electronic voltage regulator
monitoring, testing and a smart starting control system.
ƒƒ3-phase, 4-wire line-to-line sensing
Advanced control methodology – Three phase sensing, ƒƒConfigurable torque matching
FET based full wave rectified voltage regulation and a PWM AmpSentry AC protection
output for stable operation with all load types.
ƒƒAmpSentry protective relay
Communications interface – Control comes standard ƒƒOver current and short circuit shutdown
with PCCNet and Modbus interface. ƒƒOver current warning
Regulation compliant – Prototype tested: UL, CSA and ƒƒSingle and three phase fault regulation
CE compliant. ƒƒOver and under voltage shutdown
ƒƒOver and under frequency shutdown
Service - InPower™ PC-based service tool available for
ƒƒOverload warning with alarm contact
detailed diagnostics, setup, data logging and fault simulation.
ƒƒReverse power and reverse var shutdown
Reliable design – For reliable operations in harsh ƒƒField overload
environment. Engine protection
Multi-language support ƒƒBattery voltage monitoring, protection and testing
Independent of PC/ laptop for setting up ƒƒOver speed shutdown
ƒƒLow oil pressure warning and shutdown
ƒƒHigh coolant temperature warning and shutdown
Operator panel features ƒƒLow coolant level warning or shutdown
ƒƒLow coolant temperature warning
Operator panel features – The operator panel, in addition
ƒƒFail to start (over crank) shutdown
to the alternator, displays the Utility/ AC Bus data.
ƒƒFail to crank shutdown
Operator/ display functions ƒƒCranking lockout
ƒƒ320 x 240 pixels graphic LED backlight LCD with bar graph ƒƒSensor failure indication
for displaying electrical parameters ƒƒLow fuel level warning or shutdown
ƒƒAuto, manual, start, stop, fault reset and lamp test/panel
lamp switches
ƒƒAlpha-numeric display with pushbuttons
ƒƒLED lamps indicating genset running, remote start, not in
auto, common shutdown, common warning, manual run
mode, auto mode and stop
Paralleling control functions
ƒƒDigital frequency synchronization and voltage matching
ƒƒIsochronous kW and kvar load sharing controls
ƒƒDroop kW and kvar control
ƒƒSync check
ƒƒExtended paralleling (Peak Shave/Base Load)
ƒƒDigital power transfer control (AMF) provides load transfer
operation in open or closed transition or soft (ramping)
transfer mode
Diesel Generator Set QSK50 Series Specification Sheet

Control functions Options


ƒƒTime delay start and cool down ƒƒAuxiliary output relays (2)
ƒƒReal time clock for fault and event time stamping
ƒƒExerciser clock and time of day start/stop
ƒƒData logging
ƒƒCycle cranking
ƒƒLoad shed/ dump as per configurable priority
ƒƒConfigurable inputs and outputs (4)
ƒƒRemote emergency stop

Technical Data
Generator set specification
Model C1750D5P (Rad)/ C1825D5P (HE)
Rating Prime
Power Rating kVA/Kwe 1750/ 1400 (Rad) 1800/ 1440 (HE)
Output Voltage and Frequency 415 Volts- 50 Hz
Power Factor 0.8 (lag)
No. of phases 3

Engine specifications
Make Cummins
Model QSK 50 G10
No. of cylinders 16 ‘Vee’
Aspiration Turbocharged-Aftercooled
Bore and Stroke 159 mm x 159 mm
Displacement 50 liters
Output 2000 BHP (1491KWm)
Fuel consumption @ 75% load 257 lph (HE)
Fuel consumption @ 100% load 341 lph (HE)
Total wet weight (DG Set- Open) Max 10709 kgs
Length x Width x Height (DG set- Open) 6115 mm X 2167 mm X 2483 mm
Compression Ratio 15:1
Piston Speed 7.95 m/s
Governor / Class Electronic/A1
Lubricating oil sytem capacity 235 liters
Coolant capacity (Engine only) 140.1 lits.
Combustion air intake @100 % load (+/- 5%) 4017 cfm / 114 m3/min
Fan air flow across radiator RTF
Exhaust Temperature 484.4 0C
Alternator specifications
Make Stamford-LT
Frame size / Model No. PI734E
Voltage Regulation + 0.5%
Insulation Class H
Standard Enclosure IP 23
Winding Pitch 2 / 3 Pitch
Stator Winding Double Layer lap, form wound
Rotor Dynamically balanced with grade 2.5
Wave form distortion No load 1.5% non-distorting,
balanced linear load <5%
Telephone interference Factor Better than 50
Total Harmonic Factor Better than 2%

*- With External Cooling system


RTF- Refer to Factory

Conformance standards
IS 4722, BS 5000, IS 1460, ISO 8528, ISO 13018, ISO 3046

Rating definitions
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten
percent overload capability is available in accordance with ISO 3046.
Standby power: Applicable for supplying power to varing electical load for duration of power interrupting of a reliable utility source.
Emergency Stanby Power (ESP) is in accordance with ISO 8528. Fuel stop power in accordance with ISO 3046, AS 2789, DIN 6271
and ISO 13018.
- Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460
- Fuel consumption tolerance is +5%
Diesel Generator Set QSK50 Series Specification Sheet

Typical Open Genset Dimensions

Genset Rating Length Width Height Wet Weight## Standard Fuel Tank
Model (kVA) (mm) (mm) (mm) (kg) Capacity - External
C1750D5P/C1825D5P* 1750/1825 6115 2167 2483 12543 990
##
Approximate Weight

Authorised Representative

Cummins Power Systems Offices


Bengaluru: Tel.: (080) 2325 9161 / 63, 2325 9165 / 67
Fax: (080) 2325 9164
Chandigarh: Tel.: (0172) 224 0371-73
Fax: (0172) 224 0372
Chennai: Tel.: (044) 2446 8110 / 2446 8113
Fax: (044) 2491 1120
Gurgaon: Tel.: (0124) 391 0900-01
Fax : (0124) 391 0916
Hyderabad: Tel.: (040) 2340 9970 / 2340 9980
Fax. (040) 2340 9990
Jaipur: Tel.: (0141) 236 4944
Fax: (0141) 403 8794
Kolkata: Tel.: (033) 2287 8065 / 2287 2481
Fax: (033) 2290 3839
Lucknow: Tel.: (0522) 230 5049 / 230 5059
Fax: (0522) 230 5035
Mohali: Tel.: (0172) 224 0371 / 72 / 73
Fax: (0172) 224 0371 / 72 / 73
Vadodara: Tel.: (0265) 233 0627 / 3053627
Fax: (0265) 234 0623

Visit our facebook page at :


Cummins Power Generation India
Cummins India Limited
“Our energy working for you.” Power Systems Business
Cummins India Office Campus
Tower-A, 8th Floor, S. No. 21,
Balewadi, Pune – 411 045 (India)
Cummins is registered trademarks of Cummins Inc. Specifi cations
are subject to change without notice. Email: cpgindia@cummins.com
PSBU/021/QSK50 1750-1825kVA/HD/MP/Revision-2 (14/03/2018) www.cumminsindia.com

You might also like