QSK50 Series
1750-1825kVA
Technical Data
Generator set specification
Model C1750D5P (Rad)/ C1825D5P (HE)
Rating Prime
Power Rating kVA/Kwe 1750/ 1400 (Rad) 1800/ 1440 (HE)
Output Voltage and Frequency 415 Volts- 50 Hz
Power Factor 0.8 (lag)
No. of phases 3
Engine specifications
Make Cummins
Model QSK 50 G10
No. of cylinders 16 ‘Vee’
Aspiration Turbocharged-Aftercooled
Bore and Stroke 159 mm x 159 mm
Displacement 50 liters
Output 2000 BHP (1491KWm)
Fuel consumption @ 75% load 257 lph (HE)
Fuel consumption @ 100% load 341 lph (HE)
Total wet weight (DG Set- Open) Max 10709 kgs
Length x Width x Height (DG set- Open) 6115 mm X 2167 mm X 2483 mm
Compression Ratio 15:1
Piston Speed 7.95 m/s
Governor / Class Electronic/A1
Lubricating oil sytem capacity 235 liters
Coolant capacity (Engine only) 140.1 lits.
Combustion air intake @100 % load (+/- 5%) 4017 cfm / 114 m3/min
Fan air flow across radiator RTF
Exhaust Temperature 484.4 0C
Alternator specifications
Make Stamford-LT
Frame size / Model No. PI734E
Voltage Regulation + 0.5%
Insulation Class H
Standard Enclosure IP 23
Winding Pitch 2 / 3 Pitch
Stator Winding Double Layer lap, form wound
Rotor Dynamically balanced with grade 2.5
Wave form distortion No load 1.5% non-distorting,
balanced linear load <5%
Telephone interference Factor Better than 50
Total Harmonic Factor Better than 2%
Conformance standards
IS 4722, BS 5000, IS 1460, ISO 8528, ISO 13018, ISO 3046
Rating definitions
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten
percent overload capability is available in accordance with ISO 3046.
Standby power: Applicable for supplying power to varing electical load for duration of power interrupting of a reliable utility source.
Emergency Stanby Power (ESP) is in accordance with ISO 8528. Fuel stop power in accordance with ISO 3046, AS 2789, DIN 6271
and ISO 13018.
- Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460
- Fuel consumption tolerance is +5%
Diesel Generator Set QSK50 Series Specification Sheet
Genset Rating Length Width Height Wet Weight## Standard Fuel Tank
Model (kVA) (mm) (mm) (mm) (kg) Capacity - External
C1750D5P/C1825D5P* 1750/1825 6115 2167 2483 12543 990
##
Approximate Weight
Authorised Representative