CT PT Test Report
CT PT Test Report
CT PT Test Report
S.K.Mondal
Sr.Engr.
5% 20% 100% 120%
Ratio Error in % 0.00542 0.00487 0.00325 0.00248
20 VA & 0.8 Lagging Phase Error in min 3.55 3.26 2.62 2.32
Class of Accuracy 0.1 0.1 0.1 0.1
Ratio Error in % 0.0546 0.0485 0.0397 0.0310
5 VA & 0.8 Lagging Phase Error in min 2.89 2.45 2.12 1.85
Class of Accuracy 0.1 0.1 0.1 0.1
Sec. wdg. resistance at room temp. in Ω 0.20
Knee Point Voltage (Vk) in V 15.61
Exciting Current (Io) in mA 2.62
S.K.Mondal
Sr.Engr.
ROUTINE TEST REPORT OF 3.3KV RESIN CAST IN DOOR TYPE
CURRENT TRANSFORMER
S.K.Mondal
Sr.Engr.
Class of Accuracy 0.1 0.1 0.1 0.1
Ratio Error in % 0.0554 0.0501 0.0451 0.0324
5 VA & 0.8 Lagging Phase Error in min 2.25 2.12 2.01 1.79
Class of Accuracy 0.1 0.1 0.1 0.1
Sec. wdg. resistance at room temp. in Ω 0.20
Knee Point Voltage (Vk) in V 15.61
Exciting Current (Io) in mA 2.62
S.K.Mondal
Sr.Engr.
ROUTINE TEST REPORT OF 3.3KV RESIN CAST IN DOOR TYPE
CURRENT TRANSFORMER
S.K.Mondal
Sr.Engr.
Class of Accuracy 0.1 0.1 0.1 0.1
Ratio Error in % 0.0545 0.0485 0.0345 0.0213
5 VA & 0.8 Lagging Phase Error in min 3.78 3.12 2.36 1.85
Class of Accuracy 0.1 0.1 0.1 0.1
Sec. wdg. resistance at room temp. in Ω 0.20
Knee Point Voltage (Vk) in V 15.61
Exciting Current (Io) in mA 2.62
S.K.Mondal
Sr.Engr.