Manual Book Inverter A-800
Manual Book Inverter A-800
Manual Book Inverter A-800
INVERTER
FR-A800
FR-A800
INSTRUCTION MANUAL (DETAILED)
High functionality and high performance
FR-A820-00046(0.4K) to 04750(90K)(-GF)
FR-A840-00023(0.4K) to 06830(280K)(-GF)
FR-A842-07700(315K) to 12120(500K)(-GF)
FR-A846-00023(0.4K) to 03610(132K)
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
FR-A800
FR-A800
MODEL
Model
INSTRUCTION
Instruction MANUAL
Manual (Detailed)
MODEL
Model code 1A2-P52
XXX-XXX
CODE
Chapter 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CONTENTS
1.3 Operation steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 Removal and reinstallation of the operation panel or the front covers. . . . . . . . . . . . . . . . . . . 33
2.7.1 PU connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
2.7.2 USB connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
2.7.3 RS-485 terminal block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
1
2.9 Parameter settings for a motor with encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
2.11 Wiring for use of the CC-Link IE Field Network (FR-A800-GF) . . . . . . . . . . . . . . . . . . . . . . . 107
3.5 Countermeasures against deterioration of the 400 V class motor insulation . . . . . . . . . . . . . 128
2
4.2.3 Displaying the set frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
4.5.1 Setting the frequency on the operation panel (example: operating at 30 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
4.5.2 Perform PU operation using the setting dial like a potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
CONTENTS
4.5.3 Setting the frequency with switches (multi-speed setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
4.5.4 Setting the frequency using an analog signal (voltage input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
4.5.5 Setting the frequency using an analog signal (current input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
4.7.1 Giving a start command by using external signals for JOG operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
4.7.2 Giving a start command from the operation panel for JOG operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
229
5.3.1 Setting procedure of Real sensorless vector control (speed control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
5.3.2 Setting procedure of Vector control (speed control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
5.3.3 Setting procedure of PM sensorless vector control (speed control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
5.3.4 Setting the torque limit level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
5.3.5 Performing high-accuracy, fast-response control (gain adjustment for Real sensorless vector control, Vector control, and PM
sensorless vector control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
5.3.6 Troubleshooting in the speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
5.3.7 Speed feed forward control, model adaptive speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
5.3.8 Torque bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
5.3.9 Avoiding motor overrunning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
5.3.10 Notch filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
5.4 Torque control under Real sensorless vector control and Vector control . . . . . . . . . . . . . . . 263
3
5.4.3 Setting procedure for Vector control (torque control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
5.4.4 Torque command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
5.4.5 Speed limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
5.4.6 Torque control gain adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
5.4.7 Troubleshooting in torque control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
5.4.8 Torque control by variable-current limiter control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
5.5 Position control under vector control and PM sensorless vector control . . . . . . . . . . . . . . . . 284
5.6 Adjustment during Real sensorless vector control, Vector control, PM sensorless vector control
316
4
5.9.4 Reverse rotation prevention selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
5.9.5 Frequency setting via pulse train input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
5.9.6 JOG operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
5.9.7 Operation by multi-speed setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
CONTENTS
5.10.7 I/O phase loss protection selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
5.10.8 Retry function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
5.10.9 Limiting the output frequency (maximum/minimum frequency). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
5.10.10 Avoiding machine resonance points (frequency jump) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
5.10.11 Stall prevention operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
5.10.12 Load characteristics fault detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
5.10.13 Motor overspeeding detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
5.11.1 Speed indication and its setting change to rotations per minute. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
5.11.2 Monitor item selection on operation panel or via communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
5.11.3 Monitor display selection for terminals FM/CA and AM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
5.11.4 Adjustment of terminal FM/CA and terminal AM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
5.11.5 Energy saving monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
5.11.6 Output terminal function selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
5.11.7 Output frequency detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
5.11.8 Output current detection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
5.11.9 Output torque detection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
5.11.10 Remote output function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
5.11.11 Analog remote output function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467
5.11.12 Fault code output selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469
5.11.13 Pulse train output to announce cumulative output energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470
5.11.14 Detection of control circuit temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
5.11.15 Encoder pulse dividing output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
5
5.14.7 Traverse function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552
5.14.8 Anti-sway control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554
5.14.9 Orientation control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555
5.14.10 PID control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571
5.14.11 Changing the display increment of numerical values used in PID control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 585
5.14.12 PID Pre-charge function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
5.14.13 Dancer control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 591
5.14.14 Automatic restart after instantaneous power failure/flying start with an induction motor . . . . . . . . . . . . . . . . . . . . . . . . . 598
5.14.15 Automatic restart after instantaneous power failure/flying start with an IPM motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605
5.14.16 Offline auto tuning for a frequency search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607
5.14.17 Power failure time deceleration-to-stop function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 611
5.14.18 PLC function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 615
5.14.19 Trace function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 617
5.20 Checking parameters changed from their initial values (initial value change list) . . . . . . . . . 716
6
5.21.7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 735
CONTENTS
6.4 List of fault displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 742
7
8.1 Inverter rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 790
8.2.1 Vector control dedicated motor SF-V5RU (1500 r/min series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 794
8.2.2 Vector control dedicated motor SF-THY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 797
8.2.3 IPM motor MM-CF (2000 r/min series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 798
9.1 For customers replacing the conventional model with this inverter . . . . . . . . . . . . . . . . . . . . 820
9.2 Specification comparison between PM sensorless vector control and induction motor control . .
823
9.3 Parameters (functions) and instruction codes under different control methods . . . . . . . . . . . 824
8
Safety instructions
Thank you for choosing Mitsubishi Electric inverter.
This Instruction Manual (Detailed) provides detailed instructions for advanced settings of the FR-A800 series inverters.
Incorrect handling might cause an unexpected fault. Before using this product, read the Instruction Manual (Startup, Detailed)
carefully to ensure proper use of this product.
Do not attempt to install, operate, maintain or inspect this product until you have read the Instruction Manuals and appended
documents carefully. Do not use this product until you have a full knowledge of this product mechanism, safety information and
instructions.
Installation, operation, maintenance and inspection must be performed by qualified personnel. Here, qualified personnel means
a person who meets all the following conditions:
• A person who possesses a certification in regard with electric appliance handling, or person took a proper engineering
training. Such training may be available at your local Mitsubishi Electric office. Contact your local sales office for schedules
and locations.
• A person who can access operating manuals for the protective devices (for example, light curtain) connected to the safety
control system, or a person who has read these manuals thoroughly and familiarized himself/herself with the protective
devices.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury,
CAUTION or may cause only material damage.
Note that even the level may lead to a serious consequence depending on conditions. Be sure to follow the
instructions of both levels as they are critical to personnel safety.
9
Electric shock prevention
WARNING
Do not remove the front cover or the wiring cover while the inverter power is ON, and do not run the inverter with the
front cover or the wiring cover removed as the exposed high voltage terminals or the charging part of the circuitry can
be touched. Otherwise you may get an electric shock.
Even if power is OFF, do not remove the front cover except for wiring or periodic inspection as the inside of the inverter
is charged. Otherwise you may get an electric shock.
Before wiring or inspection, check that the LED display of the operation panel is OFF. Any person who is involved in
wiring or inspection shall wait for 10 minutes or longer after the power supply has been cut off, and check that there are
no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF,
and it is dangerous.
The inverter must be earthed (grounded). Earthing (grounding) must conform to the requirements of national and local
safety regulations and electrical code (NEC section 250, IEC 61140 class 1 and other applicable standards). A neutral-
point earthed (grounded) power supply must be used for 400 V class inverter to be compliant with EN standard.
Any person who is involved in wiring or inspection of this product shall be fully competent to do the work.
The product body must be installed before wiring. Otherwise you may get an electric shock or be injured.
Setting dial and key operations must be performed with dry hands to prevent an electric shock. Otherwise you may get
an electric shock.
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric
shock.
Do not change the cooling fan while power is ON as it is dangerous.
Do not touch the printed circuit board or handle the cables with wet hands. Otherwise you may get an electric shock.
Never touch the motor terminals, etc. right after powering OFF as the DC voltage is applied to the motor for 1 second at
powering OFF if the main circuit capacitor capacity is measured. Otherwise you may get an electric shock.
Before wiring or inspection for a PM motor, confirm that the PM motor is stopped as a PM motor is a synchronous motor
with high-performance magnets embedded inside and high-voltage is generated at the motor terminals while the motor
is running even after the inverter power is turned OFF. In an application, such as fan and blower, that the motor may be
driven by the load, connect a low-voltage manual contactor at the inverter's output side and keep it open during wiring
and inspection of the inverter. Otherwise you may get an electric shock.
Fire prevention
CAUTION
The inverter must be installed on a nonflammable wall without any through holes so that nobody touches the heatsink,
etc. on the rear side of the inverter. Installing it on or near flammable material may cause a fire.
If the inverter has become faulty, the inverter power must be switched OFF. A continuous flow of large current may cause
a fire.
When using a brake resistor, a sequence that will turn OFF power when a fault signal is output must be configured.
Otherwise the brake resistor may excessively overheat due to damage of the brake transistor and such, causing a fire.
Do not connect a resistor directly to the DC terminals P/+ and N/-. Doing so could cause a fire.
Be sure to perform daily and periodic inspections as specified in the Instruction Manual. If this product is used without
any inspection, a burst, breakage, or a fire may occur.
10
Injury prevention
CAUTION
The voltage applied to each terminal must be as specified in the Instruction Manual. Otherwise burst, damage, etc. may
occur.
The cables must be connected to the correct terminals. Otherwise burst, damage, etc. may occur.
The polarity (+ and -) must be correct. Otherwise burst, damage, etc. may occur.
While power is ON or for some time after power-OFF, do not touch the inverter as it will be extremely hot. Touching these
devices may cause a burn.
Additional instructions
The following instructions must be also followed. If the product is handled incorrectly, it may cause unexpected fault, an injury,
or an electric shock.
11
CAUTION
Transportation and installing
Any person who is opening a package using a sharp object, such as a knife or cutter, must wear gloves to prevent injuries
caused by the edge of the sharp object.
The product must be transported in correct method that corresponds to the weight. Failure to do so may lead to injuries.
Do not stand or place any heavy object on the product.
Do not stack the boxes containing products higher than the number recommended.
When carrying the product, do not hold it by the front cover. Doing so may cause a fall or failure of the product.
During installation, caution must be taken not to drop the inverter as doing so may cause injuries.
The product must be installed on the surface that withstands the weight of the product.
Do not install the product on a hot surface.
The installing orientation of the inverter must be correct.
The inverter must be installed on a strong surface securely with screws so that it does not drop.
Do not install or operate the inverter if it is damaged or has parts missing.
Foreign conductive objects must be prevented from entering the inverter. That includes screws and metal fragments or
other flammable substance such as oil.
As the inverter is a precision instrument, do not drop or subject it to impact.
The surrounding air temperature must be between -10 and +50°C*1 (non-freezing) for the inverter at HD (heavy duty),
ND (normal duty) (initial setting), or LD (light duty) rating, and between -10 and +40°C*2 (non-freezing) for the inverter at
SLD (super light duty) rating. Otherwise the inverter may be damaged.
The ambient humidity must be 95% RH or less (non-condensing) for the inverter. Otherwise the inverter may be
damaged. (Refer to page 37 for details.)
The temporary storage temperature (applicable to a short limited time such as a transportation time) must be between -
20 and +65°C. Otherwise the inverter may be damaged.
The inverter must be used indoors (without corrosive gas, flammable gas, oil mist, dust and dirt). Otherwise the inverter
may be damaged.
The inverter must be used at an altitude of 2500 m or less, with 5.9 m/s2 or less vibration*3 at 10 to 55 Hz (directions of
X, Y, Z axes). Otherwise the inverter may be damaged. (Refer to page 37 for details.)
If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.), included in fumigants to sterilize or disinfect wooden
packages, infiltrate into the product, the product may be damaged. Prevent residual fumigant components from being
infiltrated into the product when packaging, or use an alternative sterilization or disinfection method (heat disinfection,
etc.). Note that sterilization of disinfection of wooden package should be performed before packing the product.
Wiring
Do not install a power factor correction capacitor, surge absorber, or radio noise filter on the inverter's output side. These
devices on the inverter output side may be overheated or burn out.
The output of the inverter (output terminals U, V, W) must be correctly connected to a motor. Otherwise the motor rotates
inversely.
Even after the inverter power is turned OFF, a PM motor is running for a while and the inverter's output terminals U, V,
and W wired to the PM motor hold high voltages all that while. To wire other terminals after the terminals U, V, and W
were wired, be sure that the PM motor is stopped. Otherwise you may get an electric shock.
Never connect a PM motor to the commercial power supply. Applying the commercial power to the input terminals (U,
V, W) on a PM motor will burn the PM motor. The PM motor must be applied a power from the inverter with the output
terminals (U, V, W).
Test operation
Before starting the test operation, confirm or adjust the parameter settings. A failure to do so may cause some machines
to make unexpected motions.
*1 0 to +50°C for the FR-A800-GF.
*2 0 to +40°C for the FR-A800-GF.
*3 2.9 m/s2 or less for the FR-A840-04320(160K) or higher.
12
WARNING
Usage
Any person must stay away from the inverter after using the retry function as the inverter will restart suddenly after
inverter output shutoff.
It may happen depending on the inverter's function settings that the inverter does not stop its output even when the
STOP/RESET key on the operation panel is pressed. To prepare for it, provide a separate circuit and switch (to turn the
inverter power OFF, or apply a mechanical brake, etc.) for an emergency stop.
Be sure to turn OFF the start (STF/STR) signal before clearing the fault as the inverter will restart the motor suddenly
after a fault clear.
Do not use a PM motor for an application that the motor may be driven by the load and run at a speed higher than the
maximum motor speed.
Use only a three-phase induction motor or PM motor as a load on this inverter. Connection of any other electrical
equipment to the inverter output may damage the equipment.
Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control)
may rotate a motor at a low speed even though a start command (STF or STR) is not given. The inverter at a start
command ON may also rotate the motor at a low speed even though a speed limit value is set to zero Therefore, confirm
that the motor running does not cause any safety problem before performing pre-excitation.
Do not modify the product.
Do not remove any part which is not instructed to be removed in the Instruction Manuals. Doing so may lead to a failure
or damage of the product.
13
CAUTION
Usage
The electronic thermal O/L relay function may not be enough for protection of a motor from overheating. It is
recommended to install an external thermal relay or a PTC thermistor for overheat protection.
Do not use a magnetic contactor on the inverter input side for frequent starting/stopping of the inverter. Otherwise the
life of the inverter decreases.
Use a noise filter or other means to minimize the electromagnetic interference with other electronic equipment used
nearby the inverter.
Appropriate measures must be taken to suppress harmonics. Otherwise harmonics in power systems generated from
the inverter may heat/damage a power factor correction capacitor or a generator.
For a 400 V class motor driven by the inverter, use an insulation-enhanced motor, or take measures to suppress surge
voltage. Otherwise surge voltage attributable to the line constants may occur at the motor terminals, deteriorating the
insulation of the motor.
As all parameters return to their initial values after the Parameter clear or All parameter clear is performed, the needed
parameters for the inverter operation must be set again before the operation is started.
The inverter can be easily set for high-speed operation. Therefore, consider all things related to the operation such as
the performance of a motor and equipment in a system before the setting change.
The stop state of the inverter by the inverter's brake function (DC injection brake function) cannot be held. Install a device
to apply brakes to a motor or equipment in a system for safety.
Before running an inverter which have been stored and not been operated for a long period, perform an inspection and
a test operation.
To avoid damage to the product due to static electricity, static electricity in your body must be discharged before you
touch the product.
Only one PM motor can be connected to one inverter.
A PM motor must be used under PM sensorless vector control. Do not use a synchronous motor, induction motor, or
synchronous induction motor.
Do not connect a PM motor to the inverter at a setting for the induction motor control (initial setting). Do not connect an
induction motor to the inverter at a setting for PM sensorless vector control. Doing so will cause a failure.
As a process of starting a PM motor, turn ON the inverter power first, and then close the contactor on the output side of
the inverter.
Emergency stop
A safety backup such as an emergency brake must be provided for devices or equipment in a system to prevent
hazardous conditions in case of the inverter failure.
If a breaker on the inverter input side is tripped, the wiring must be checked for a fault (such as short circuit), and internal
parts of the inverter for a damage, etc. Identify and remove the cause of the trip before resetting the tripped breaker (or
before applying the power to the inverter again).
When any protective function is activated, take an appropriate corrective action before resetting the inverter to resume
the operation.
Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test on the control circuit of the inverter. Doing so will cause a failure.
Disposal
The product must be treated as industrial waste.
General instruction
For clarity purpose, illustrations in this Instruction Manual may be drawn with covers or safety guards removed. Ensure
all covers and safety guards are properly installed prior to starting operation. For details on the PM motor, refer to the
Instruction Manual of the PM motor.
14
CHAPTER 1
CHAPTER 1 INTRODUCTION
4
10
15
1 INTRODUCTION
The contents described in this chapter must be read before using this product.
Always read the instructions before use.
For the separated converter type, refer to the "INTRODUCTION" in the FR-A802 (Separated Converter Type) Instruction
Manual (Hardware).
For the IP55 compatible model, refer to the "INTRODUCTION" in the FR-A806 (IP55/UL Type 12 specification) Instruction
Manual (Hardware).
Abbreviations
Item Description
DU Operation panel (FR-DU08)
Operation panel Operation panel (FR-DU08) and LCD operation panel (FR-LU08)
Parameter unit Parameter unit (FR-PU07)
PU Operation panel and parameter unit
Inverter Mitsubishi Electric inverter FR-A800 series
FR-A800-GF FR-A800 series inverter with built-in CC-Link IE Field Network communication function
Vector control compatible option FR-A8AP/FR-A8AL/FR-A8APR/FR-A8APS (plug-in option), FR-A8TP (control terminal option)
Pr. Parameter number (Number assigned to function)
PU operation Operation using the PU (operation panel/parameter unit)
External operation Operation using the control circuit signals
Combined operation Combined operation using the PU (operation panel/parameter unit) and External operation
Mitsubishi Electric standard SF-JR
motor
Mitsubishi Electric constant- SF-HRCA
torque motor
Vector control dedicated motor SF-V5RU
Mitsubishi Electric IPM motor MM-CF
Trademarks
• Microsoft and Visual C++ are registered trademarks of Microsoft Corporation in the United States and other countries.
• Ethernet is a registered trademark of Fuji Xerox Corporation in Japan.
• MODBUS is a registered trademark of SCHNEIDER ELECTRIC USA, INC.
• Other company and product names herein are the trademarks and registered trademarks of their respective owners.
16 1. INTRODUCTION
1.1 Product checking and accessories 1
Unpack the product and check the rating plate and the capacity plate of the inverter to ensure that the model agrees with the
order and the product is intact. 2
Inverter model
3
Symbol Voltage class Symbol Structure, functionality Symbol Description Symbol Type∗1
2 200 V class 0 Standard model 00023 to 12120 Inverter SLD rated current (A) 1 FM
4 400 V class 2 Separated converter type 0.4K to 500K Inverter ND rated capacity (kW) 2 CA 4
6 IP55 compatible model
5
F R - A 8 2 0 - 00046 - 1 -
6
Circuit board Plated
Symbol Symbol Function
coating∗2 conductor
None Without Without None Standard type
60 With Without With built-in CC-link IE
7
GF
06∗3 With With Field Network function
8
Rating plate
Inverter model 02'(/)5$ 9
Input rating ,1387;;;;;
Output rating 287387;;;;;
SERIAL 6(5,$/;;;;;;;;;
10
Country of origin 0$'(,1;;;;;
*1 Specification differs by the type. Major differences are shown in the following table.
Initial setting
Type Monitor output Built-in EMC Rated Pr.19 Base frequency
Control logic
filter frequency voltage
FM Terminal FM (pulse train output)
9999 (same as the power
(terminal FM Terminal AM (analog voltage OFF Sink logic 60 Hz
supply voltage)
equipped model) output (0 to ±10 VDC))
Terminal CA (analog current
CA
output (0 to 20 mADC)) 8888 (95% of the power
(terminal CA ON Source logic 50 Hz
Terminal AM (analog voltage supply voltage)
equipped model)
output (0 to ±10 VDC))
*2 Conforming to IEC60721-3-3 3C2/3S2
*3 Applicable for the FR-A820-00340(5.5K) or higher, and the FR-A840-00170(5.5K) or higher.
NOTE
• In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current.
(Example) FR-A820-00046(0.4K)
1. INTRODUCTION
1.1 Product checking and accessories
17
Accessory
• Fan cover fixing screws
These screws are necessary for compliance with the EU Directives. (Refer to the Instruction Manual (Startup).)
Capacity Screw size (mm) Quantity
FR-A820-00105(1.5K) to FR-A820-00250(3.7K)
M3×35 1
FR-A840-00083(2.2K), FR-A840-00126(3.7K)
FR-A820-00340(5.5K), FR-A820-00490(7.5K)
M3×35 2
FR-A840-00170(5.5K), FR-A840-00250(7.5K)
FR-A820-00630(11K) to FR-A820-01250(22K)
M4×40 2
FR-A840-00310(11K) to FR-A840-00620(22K)
18 1. INTRODUCTION
1.1 Product checking and accessories
1.2 Component names 1
Component names are as follows.
2
(a)
(b)
(t)
(c) 3
(d) (u)
(e)
(h)
(o)
(f) 4
(g)
(p)
5
(s)
(i)
6
(q)
(j)
7
(k)
(r)
8
(m)
(l)
9
(n)
10
1. INTRODUCTION
1.2 Component names
19
Refer to
Symbol Name Description
page
Connects the operation panel or the parameter unit. This connector also
(a) PU connector 83
enables the RS-485 communication.
(b) USB A connector Connects a USB memory device. 84
Connects a personal computer and enables communication with FR
(c) USB mini B connector 84
Configurator2.
(d) RS-485 terminals Enables RS-485, MODBUS RTU communication. 85
Terminating resistor selection switch Select whether or not to use the terminating resistor for RS-485
(e) 85
(SW1) communication.
(f) Plug-in option connector 1 Connects a plug-in option or a communication option. (For the FR-A800-GF, Instruction
(g) Plug-in option connector 2 a CC-Link IE Field Network communication circuit board is installed to the Manual of
(h) Plug-in option connector 3 connector 1. Refer to page 107.) the option
(i) Voltage/current input switches (SW2) Selects between voltage and current for the input via terminals 2 and 4. 473
(j) Control circuit terminal block Connects cables for the control circuit. 68
(k) EMC filter ON/OFF connector Turns ON/OFF the EMC filter. 118
(l) Main circuit terminal block Connects cables for the main circuit. 54
(m) Charge lamp Stays ON while the power is supplied to the main circuit. 55
This cover is removable without unplugging cables. (FR-A820-01250(22K) or
(n) Wiring cover 57
lower, FR-A840-00620(22K) or lower)
(o) Alarm lamp Turns ON when the protective function of the inverter is activated. 55
(p) Power lamp Stays ON while the power is supplied to the control circuit (R1/L11, S1/L21). 55
Remove this cover for the installation of the product, installation of a plug-in
(communication) option, RS-485 terminal wiring, switching of the voltage/
(q) Front cover (upper side) 33
current input switches, etc. (The FR-A800-GF had a front cover with an LED
display cover.)
(r) Front cover (lower side) Remove this cover for wiring. 33
(s) Operation panel (FR-DU08) Operates and monitors the inverter. 136
Cools the inverter. (FR-A820-00105(1.5K) or higher, FR-A840-00083(2.2K) or
(t) Cooling fan 780
higher)
Switches (SW3 and SW4) for
(u) Do not change the initial setting (OFF
OFF
). —
manufacturer setting ON
20 1. INTRODUCTION
1.2 Component names
1.3 Operation steps 1
Installation/mounting
Inverter
output 3
frequency Wiring of the power
supply and motor
(b)
(Hz) Time
Start command ON (S)
Control mode selection (c) 4
How
How
o Start command via the PU connector
to
to give
e aa start
5
give start and RS-485 terminal of the inverter
command?
command?
m and plug-in option (Communication)
(d)
How
How w to
to How
How w to
to 7
give
give aa frequency
frequency
re give
give aa frequency
frequency
re
command?
command?
m command?
command?
m
8
Perform frequency Perform frequency
Change frequency
Set from the setting by a voltage setting by a current
with ON/OFF switches
PU (operation panel/ output device output device
9
connected to terminals
parameter unit). (Connection across (Connection across
(multi-speed setting)
terminals 2 and 5) terminals 4 and 5)
(PU) (External) (External) (External)
(e) (f) (g) (h)
10
Change of frequency Perform frequency Perform frequency
Set from the setting by a voltage setting by a current
with ON/OFF switches
PU (operation panel/ output device output device
connected to terminals
parameter unit). (Connection across (Connection across
(multi-speed setting)
terminals 2 and 5) terminals 4 and 5)
(PU) (External) (External) (External)
1. INTRODUCTION
1.3 Operation steps
21
Symbol Overview Refer to page
(a) Install the inverter. 37
(b) Perform wiring for the power supply and the motor. 55
Select the control method (V/F control, Advanced magnetic flux vector control, Vector control, or PM sensorless
(c) 215
vector control).
(d) Give the start command via communication. 625
(e) Give both the start and frequency commands from the PU. (PU operation mode) 147
Give the start command from the PU and the frequency command via terminals RH, RM, and RL. (External/PU
(f) 149
combined operation mode 2)
Give the start command from the PU and the frequency command by voltage input via terminal 2. (External/PU
(g) 150
combined operation mode 2)
Give the start command from the PU and the frequency command by current input via terminal 4. (External/PU
(h) 151
combined operation mode 2)
Give the start command via terminal STF or STR and the frequency command from the PU. (External/PU
(i) 153
combined operation mode 1)
Give the start command via terminal STF or STR and the frequency command via terminals RH, RM, and RL.
(j) 154
(External operation mode)
Give the start command via terminal STF or STR and the frequency command by voltage input via terminal 2.
(k) 155
(External operation mode)
Give the start command via terminal STF or STR and the frequency command by current input via terminal 4.
(l) 157
(External operation mode)
22 1. INTRODUCTION
1.3 Operation steps
1.4 About the related manuals 1
The manuals related to FR-A800 are as follows.
Manual name Manual number
2
FR-A800 Instruction Manual (Startup) IB-0600493
FR-A800-GF Instruction Manual (Startup) IB-0600600
FR-A802 (Separated Converter Type) Instruction Manual (Hardware) IB-0600533 3
FR-A802-GF (Separated Converter Type) Instruction Manual (Hardware) IB-0600601
FR-CC2 (Converter unit) Instruction Manual IB-0600542
FR-A806 (IP55/UL Type 12 specification) Instruction Manual (Hardware) IB-0600531ENG
FR Configurator 2 Instruction Manual IB-0600516ENG 4
FR-A800/F800 PLC Function Programming Manual IB-0600492ENG
FR-A800/F800 Safety Stop Function Instruction Manual BCN-A23228-001
5
10
1. INTRODUCTION
1.4 About the related manuals
23
MEMO
24 1. INTRODUCTION
1.4 About the related manuals
CHAPTER 2
CHAPTER 2 INSTALLATION AND WIRING
4
10
25
2 INSTALLATION AND WIRING
This chapter explains the installation and the wiring of this product.
Always read the instructions before use.
For the separated converter type, refer to the "INSTALLATION AND WIRING" in the FR-A802 (Separated Converter Type)
Instruction Manual (Hardware).
For the IP55 compatible model, refer to the "INSTALLATION AND WIRING" in the FR-A806 (IP55/UL Type 12 specification)
Instruction Manual (Hardware).
USB host
(A connector)
3
Communication
status indicator USB
(LED)(USB host)
(c) Molded case circuit breaker
(MCCB) or earth leakage current
USB device
4
breaker (ELB), fuse
(Mini B connector)
Personal computer
5
(FR Configurator 2)
6
(d) Magnetic contactor (MC)
(e) AC reactor
(FR-HAL)
(f) DC reactor
(FR-HEL)
(n) High-duty brake resistor (FR-ABR) 7
P/+(P3)
PR
IM connection PM connection
8
U VW U VW
R/L1 S/L2 T/L3
P/+ P1 P/+ N/-
(q) Contactor
10
Example) No-fuse
switch
(DSN type)
(h) High power factor (i) Power regeneration (l) Resistor unit
converter common converter (FR-BR, MT-BR5) Earth (Ground)
(FR-HC2) (FR-CV)
(j) Power regeneration
converter (MT-RC) : Install these options as required.
5
2.1.2 Peripheral devices
Check the model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. 6
Refer to the following table to prepare appropriate peripheral devices.
10
NOTE
• Select an MCCB according to the power supply capacity.
• Install one MCCB per inverter. For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the
Instruction Manual (Startup) or Instruction Manual (Hardware), and select an appropriate fuse or molded case circuit breaker
(MCCB).
MCCB INV M
MCCB INV M
2
Magnetic contactor at the inverter's input line
• This is a matrix showing the model name of the Mitsubishi magnetic contactor to be installed at the inverter's input line
according to the selected inverter and rating. 3
Without AC/DC power factor improving reactor With AC/DC power factor improving reactor
Voltage Inverter model
SLD LD ND HD SLD LD ND HD
FR-A820-00046(0.4K) S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 4
FR-A820-00077(0.75K) S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10
FR-A820-00105(1.5K) S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10
FR-A820-00167(2.2K)
FR-A820-00250(3.7K)
S-T21
S-T25
S-T21
S-T25
S-T10
S-T21
S-T10
S-T10
S-T10
S-T21
S-T10
S-T21
S-T10
S-T10
S-T10
S-T10
5
FR-A820-00340(5.5K) S-T35 S-T35 S-T35 S-T21 S-T35 S-T25 S-T21 S-T10
FR-A820-00490(7.5K) S-T50 S-T35 S-T35 S-T35 S-T35 S-T35 S-T35 S-T21
FR-A820-00630(11K) S-T65 S-T50 S-T35 S-T35 S-T50 S-T50 S-T35 S-T35 6
200 V
FR-A820-00770(15K) S-T65 S-T65 S-T50 S-T35 S-T50 S-T50 S-T50 S-T35
class
FR-A820-00930(18.5K) S-T100 S-T100 S-T65 S-T50 S-T65 S-T65 S-T50 S-T50
FR-A820-01250(22K)
FR-A820-01540(30K)
S-N150
S-N150
S-T100
S-N150
S-T100
S-T100
S-T65
S-T100
S-T100
S-N150
S-T100
S-N125
S-T65
S-T100
S-T50
S-T65
7
FR-A820-01870(37K) S-N180 S-N180 S-N150 S-T100 S-N150 S-N150 S-N125 S-T100
FR-A820-02330(45K) S-N220 S-N220 S-N180 S-N150 S-N180 S-N180 S-N150 S-N125
FR-A820-03160(55K) — — S-N220 S-N180 S-N300 S-N300 S-N180 S-N150 8
FR-A820-03800(75K) — — — — S-N400 S-N300 S-N300 S-N180
FR-A820-04750(90K) — — — — S-N600 S-N400 S-N300 S-N300
FR-A840-00023(0.4K)
FR-A840-00038(0.75K)
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
9
FR-A840-00052(1.5K) S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10
FR-A840-00083(2.2K) S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10 S-T10
FR-A840-00126(3.7K) S-T21 S-T21 S-T10 S-T10 S-T12 S-T12 S-T10 S-T10 10
FR-A840-00170(5.5K) S-T21 S-T21 S-T21 S-T10 S-T21 S-T21 S-T12 S-T10
FR-A840-00250(7.5K) S-T21 S-T21 S-T21 S-T21 S-T21 S-T21 S-T21 S-T12
FR-A840-00310(11K) S-T35 S-T35 S-T21 S-T21 S-T21 S-T21 S-T21 S-T21
FR-A840-00380(15K) S-T35 S-T35 S-T35 S-T21 S-T35 S-T35 S-T21 S-T21
FR-A840-00470(18.5K) S-T35 S-T35 S-T35 S-T35 S-T35 S-T35 S-T35 S-T21
FR-A840-00620(22K) S-T50 S-T50 S-T35 S-T35 S-T50 S-T50 S-T35 S-T35
400 V FR-A840-00770(30K) S-T65 S-T65 S-T50 S-T35 S-T50 S-T50 S-T50 S-T35
class FR-A840-00930(37K) S-T100 S-T100 S-T65 S-T50 S-T65 S-T65 S-T50 S-T50
FR-A840-01160(45K) S-N150 S-T100 S-T100 S-T65 S-T100 S-T100 S-T65 S-T50
FR-A840-01800(55K) — — S-T100 S-T100 S-N150 S-T100 S-T100 S-T65
FR-A840-02160(75K) — — — — S-N180 S-N150 S-T100 S-T100
FR-A840-02600(90K) — — — — S-N220 S-N180 S-N150 S-T100
FR-A840-03250(110K) — — — — S-N300 S-N220 S-N180 S-N150
FR-A840-03610(132K) — — — — S-N300 S-N300 S-N220 S-N180
FR-A840-04320(160K) — — — — S-N400 S-N300 S-N300 S-N220
FR-A840-04810(185K) — — — — S-N600 S-N400 S-N300 S-N300
FR-A840-05470(220K) — — — — S-N600 S-N600 S-N400 S-N300
FR-A840-06100(250K) — — — — S-N600 S-N600 S-N600 S-N400
FR-A840-06830(280K) — — — — S-N800 S-N600 S-N600 S-N600
To reinstall the operation panel, align its connector on the back with the PU connector of the inverter, and insert the operation 9
panel. After confirming that the operation panel is fit securely, tighten the screws. (Tightening torque: 0.40 to 0.45 N·m)
Loosen
(a) Loosen the screws on the front cover (lower side). (These screws cannot be removed.)
(b) While holding the areas around the installation hooks on the sides of the front cover (lower side), pull out the front cover
(lower side) using its upper side as a support.
(c) With the front cover (lower side) removed, wiring of the main circuit terminals and control circuit terminals can be
performed.
Loosen
(a) With the front cover (lower side) removed, loosen the mounting screws on the front cover (upper side). (These screws
cannot be removed.)
(FR-A820-00340(5.5K) to FR-A820-01540(30K) and FR-A840-00170(5.5K) to FR-A840-00770(30K) have two mounting
screws.)
(b) While holding the areas around the installation hooks on the sides of the front cover (upper side), pull out the cover using
its upper side as a support.
(c) With the front cover (upper side) removed, wiring of the RS-485 terminals and installation of the plug-in option can be
performed.
Fasten
Fasten
(a) Insert the upper hooks of the front cover (upper side) into the sockets of the inverter.
Securely install the front cover (upper side) to the inverter by fixing the hooks on the sides of the cover into place.
(b) Tighten the mounting screw(s) at the lower part of the front cover (upper side). (FR-A820-00340(5.5K) to FR-A820-
01540(30K) and FR-A840-00170(5.5K) to FR-A840-00770(30K) have two mounting screws.)
(c) Install the front cover (lower side) by inserting the upper hook into the socket of the front cover (upper side).
(d) Tighten the mounting screws at the lower part of the front cover (lower side).
8
(a) When the mounting screws are removed, the front cover (lower side) can be removed.
(b) With the front cover (lower side) removed, wiring of the main circuit terminals can be performed.
9
Removal of the front cover (upper side) (FR-A820-01870(37K) or higher,
FR-A840-00930(37K) or higher)
10
(a) (b) (c)
Loosen
(a) With the front cover (lower side) removed, loosen the mounting screws on the front cover (upper side). (These screws
cannot be removed.)
(b) While holding the areas around the installation hooks on the sides of the front cover (upper side), pull out the cover using
its upper side as a support.
(c) With the front cover (upper side) removed, wiring of the RS-485 terminals and installation of the plug-in option can be
performed.
Fasten Fasten
(a) Insert the upper hooks of the front cover (upper side) into the sockets of the inverter.
Securely install the front cover (upper side) to the inverter by fixing the hooks on the sides of the cover into place.
(b) Tighten the mounting screw(s) at the lower part of the front cover (upper side).
(c) Fasten the front cover (lower side) with the mounting screws.
NOTE
• Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.
Temperature
The permissible surrounding air temperature of the inverter is between -10°C and +50°C (-10°C and +40°C at the SLD rating).
(The permissible surrounding air temperature of the FR-A800-GF is between 0 and +50°C (0 and +40°C for the SLD rating).)
Always operate the inverter within this temperature range. Operation outside this range will considerably shorten the service
lives of the semiconductors, parts, capacitors and others. Take the following measures to keep the surrounding air temperature
of the inverter within the specified range.
Humidity
Operate the inverter within the ambient air humidity of usually 45 to 90% (up to 95% with circuit board coating). Too high
humidity will pose problems of reduced insulation and metal corrosion. On the other hand, too low humidity may cause a spatial
electrical breakdown. The humidity conditions for the insulation distance defined in JEM 1103 standard "Insulation Distance
from Control Equipment" is 45 to 85%.
Countermeasure
• Place the inverter in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 41.)
• Purge air.
Pump clean air from outside to make the in-enclosure air pressure higher than the outside air pressure.
High altitude
Use the inverter at an altitude of within 1000 m. For use at an altitude above 1000 m (up to 2500 m), consider a 3% reduction
in the rated current per 500 m increase in altitude.
If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate dielectric
strength.
10
NOTE
• The amount of heat generated shown assumes that the output current is inverter rated current, power supply voltage is 440 V
(400 V class), and carrier frequency is 2 kHz.
400 V class
FR-A840-00770(30K)
FR-A840-00930(37K)
655
780
575
720
480
590
385
485
275
330
250
300
210
250
175
215
10
FR-A840-01160(45K) 970 880 740 610 370 340 280 250
FR-A840-01800(55K) 1400 1140 890 730 600 500 400 330
FR-A840-02160(75K) 1780 1470 1250 925 740 630 540 425
FR-A840-02600(90K) 2235 1820 1540 1230 915 755 660 540
FR-A840-03250(110K) 2540 1960 1590 1260 1060 840 710 590
FR-A840-03610(132K) 2830 2500 1950 1570 1220 1100 850 680
FR-A840-04320(160K) 3250 2660 2410 1850 1400 1140 1040 800
FR-A840-04810(185K) 3700 3250 2690 2380 1600 1400 1160 1020
FR-A840-05470(220K) 4090 3570 3180 2590 1760 1530 1370 1110
FR-A840-06100(250K) 4650 4090 3570 3150 2000 1760 1530 1350
FR-A840-06830(280K) 5280 4620 4130 3530 2270 1980 1770 1520
NOTE
• The amount of heat generated shown assumes that the output current is inverter rated current, power supply voltage is 440 V
(400 V class), and carrier frequency is 2 kHz.
Natural
Being a totally enclosed type, this system is the most
Natural ventilation (totally appropriate for hostile environment having dust, dirt, oil
enclosed type) mist, etc. The enclosure size increases depending on
INV the inverter capacity.
Heat
pipe
Heat pipe This is a totally enclosed for enclosure downsizing.
INV
10 cm
or more
20 cm
or more 2
5 cm
5 cm 5 cm 10 cm 10 cm or more
or more*1,*2 or more*1,*2 or more or more *1,*3
Inverter
Vertical 3
Allow clearance.
10 cm
or more
20 cm
or more 4
*1 For the FR-A820-00250(3.7K) or lower and FR-A840-00126(3.7K) or lower, allow 1 cm or more clearance.
*2 When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of 40°C or less (30°C or
*3
less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.
For replacing the cooling fan of the FR-A840-04320(160K) or higher, 30 cm of space is necessary in front of the inverter. Refer to page 780 for
5
fan replacement.
Inverter Inverter
Enclosure Enclosure
(a) Horizontal arrangement (b) Vertical arrangement
Arrangement of multiple inverters
Inverter Inverter
484 662
300 300
15
200 200
13
954
984
954
Hole
985
Hole
(Unit:mm) (Unit:mm)
18
15
Shift 2
Upper
installation
frame
3
5
Lower
installation
Shift frame 6
Installation of the inverter on the enclosure
Push the inverter heat sink part outside the enclosure, and fix the inverter to the panel with upper and lower installation frames.
Enclosure
7
Inside the
enclosure Exhausted air
Cooling Dimension of
wind the outside of
185 mm the enclosure
NOTE
• As the heat sink part protruded through the panel includes a cooling fan, this type of installation is not suitable for the
environment of water drops, oil, mist, dust, etc.
• Be careful not to drop screws, dust etc. into the inverter and cooling fan section.
Type FM
FR-A820-00770(15K) to 01250(22K),
FR-A840-00470(18.5K) to 01800(55K)
DC reactor Brake resistor∗8
(FR-HEL)∗1
DC reactor Brake resistor Brake unit
(FR-HEL)∗1 (FR-ABR)∗7∗8 (Option)
Sink logic Brake unit R
R (Option) Jumper
Main circuit terminal Earth
(Ground) ∗9
Control circuit terminal Jumper Jumper
Earth P1 P/+ P3 PR N/-
(Ground)
Inrush
P1 P/+ PX PR N/- current
limit circuit
MCCB MC R
R/L1 Inrush current U
Three-phase V Motor
S/L2 limit circuit M
AC power W
T/L3
supply ON EMC filter Earth (Ground)
Jumper R1/L11 ON/OFF
∗2 S1/L21 OFF connector
Earth
(Ground)
Main circuit
Control input signals Control circuit Relay output∗10
(No voltage input allowed)∗3
STF C1
Forward rotation start
STR B1
Reverse rotation start Relay output 1
A1 (Fault output)
STP(STOP)
Start self-holding selection
RH C2
High speed
RM B2
Multi-speed Middle speed Relay output 2
selection A2
RL
Low speed
JOG ∗4 RUN Open collector output∗11
Jog operation Running
RT SU
Second function selection Up to frequency
MRS IPF
Output stop Instantaneous
RES OL power failure
Reset Overload
Terminal 4 input selection AU FU
Frequency detection
SOURCE
10
Earth
(Ground)
Main circuit
Control input signals Control circuit Relay output∗10
(No voltage input allowed)∗3
STF C1
Forward rotation start
STR B1
Reverse rotation start Relay output 1
A1 (Fault output)
STP(STOP)
Start self-holding selection
RH C2
High speed
RM B2
Multi-speed Middle speed Relay output 2
selection A2
RL
Low speed
JOG ∗4 RUN Open collector output∗11
Jog operation Running
RT SU
Second function selection Up to frequency
MRS IPF
Output stop Instantaneous
RES OL power failure
Reset Overload
Terminal 4 input selection AU FU
Frequency detection
SOURCE
NOTE 5
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the
cables of the main circuit for input and output separated.
• After wiring, wire offcuts must not be left in the inverter. 6
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switches correctly. Incorrect setting may cause a fault, failure or malfunction.
7
10
Earth
(Ground)
Main circuit
Control input signals Control circuit Relay output∗10
(No voltage input allowed)∗3 C1
STF
Forward rotation start
B1 Relay output 1
STR
Reverse rotation start (Fault output)
A1
STP(STOP)
Start self-holding selection
C2
RH
High speed
B2
RM Relay output 2
Multi-speed Middle speed A2
selection
RL
Low speed
JOG ∗4 RUN Open collector output∗11
Jog operation Running
RT SU
Second function selection Up to frequency
IPF
MRS Instantaneous
Output stop
OL power failure
RES Overload
Reset
FU
Terminal 4 input selection AU Frequency detection
SOURCE
*1 For the FR-A820-03800(75K) or higher, the FR-A840-02160(75K) or higher, or whenever a 75 kW or higher motor is used, always connect a DC
reactor (FR-HEL), which is available as an option. (To select a DC reactor, refer to page 790, and select one according to the applicable motor
capacity.)
When a DC reactor is connected to the FR-A820-03160(55K) or lower or the FR-A840-01800(55K) or lower, if a jumper is installed across
terminals P1 and P/+, remove the jumper before installing the DC reactor.
10
Earth
(Ground)
Main circuit
Control input signals Control circuit Relay output∗10
(No voltage input allowed)∗3 C1
STF
Forward rotation start
B1 Relay output 1
STR
Reverse rotation start (Fault output)
A1
STP(STOP)
Start self-holding selection
C2
RH
High speed B2
RM Relay output 2
Multi-speed Middle speed A2
selection
RL
Low speed
JOG ∗4 RUN Open collector output∗11
Jog operation Running
RT SU
Second function selection Up to frequency
IPF
MRS Instantaneous
Output stop
OL power failure
RES Overload
Reset
FU
Terminal 4 input selection AU Frequency detection
SOURCE
NOTE 5
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the
cables of the main circuit for input and output separated.
• After wiring, wire offcuts must not be left in the inverter. 6
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switches correctly. Incorrect setting may cause a fault, failure or malfunction.
7
10
NOTE
• When connecting an optional brake resistor (FR-ABR) or a brake unit (FR-BU2, FR-BU, BU), remove the jumpers across
terminals PR and PX. For the details, refer to page 96.
4
M
Power supply Motor Charge lamp M Charge lamp
Power supply Motor
7
R/L1 S/L2 T/L3 PX Charge lamp
M 8
Charge lamp Power supply Motor
M
Power supply Motor
FR-A820-00770(15K) to FR-A820-01250(22K)
FR-A840-00470(18.5K), FR-A840-00620(22K)
FR-A820-01540(30K)*1,
FR-A840-00770(30K)
9
R1/L11 S1/L21 Charge lamp
Charge lamp
Jumper
10
R1/L11 S1/L21
Jumper
Jumper
P3 PR P/+
Jumper
M
Power supply Motor
Power supply
M Motor
Jumper
Jumper
Jumper
M
Power supply Motor Jumper M
Power supply Motor
FR-A820-03800(75K), FR-A820-04750(90K) FR-A840-00930(37K) to FR-A840-01800(55K)
FR-A840-03250(110K) to FR-A840-04810(185K)
R1/L11 S1/L21
Charge lamp R1/L11 S1/L21
Charge lamp
Jumper
Jumper Jumper
M
Power supply DC reactor Motor
(option)
*1 Terminals P3 and PR of the FR-A820-01540(30K) are not provided with a screw. Do not connect anything to these.
6
Handling of the wiring cover
(FR-A820-00630(11K) to 01250(22K), FR-A840-00310(11K) to 00620(22K))
For the hook of the wiring cover, cut off the necessary parts using a pair of needle-nose pliers etc. 7
NOTE
• Cut off the same number of lugs as wires. If parts where no wire is put through have been cut off (10 mm or more), protective 8
structure (IEC60529) becomes an open type (IP00).
10
*2
temperature of 90°C or higher. It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
For all the 200 V class capacities and FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
10
temperature of 75°C (THHW cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (THHN cable).
It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction Manual (Startup) or Instruction Manual
(Hardware).)
*3 For the FR-A820-00770(15K) or lower and the FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 70°C (PVC cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A820-00930(18.5K) or higher and the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum
permissible temperature of 90°C (XLPE cable). It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
*4 The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1, and a screw for earthing
(grounding).
The screw size for terminals PR and PX on FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in parentheses.
The screw size for earthing (grounding) terminal on FR-A820-00930(18.5K) or higher and FR-A840-04320(160K) or higher is indicated in
parentheses.
The screw size for terminal P/+ for option connection on the FR-A840-03250(110K) and FR-A840-03610(132K) is indicated in parentheses.
*2
temperature of 90°C or higher. It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
For all the 200 V class capacities and FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
10
temperature of 75°C (THHW cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (THHN cable).
It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction Manual (Startup) or Instruction Manual
(Hardware).)
*3 For the FR-A820-00770(15K) or lower and the FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 70°C (PVC cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A820-00930(18.5K) or higher and the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum
permissible temperature of 90°C (XLPE cable). It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
*4 The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1, and a screw for earthing
(grounding).
The screw size for terminals PR and PX on FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in parentheses.
The screw size for earthing (grounding) terminal on FR-A820-00930(18.5K) or higher and FR-A840-04320(160K) or higher is indicated in
parentheses.
The screw size for terminal P/+ for option connection on the FR-A840-03250(110K) and FR-A840-03610(132K) is indicated in parentheses.
*2
temperature of 90°C or higher. It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
For all the 200 V class capacities and FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
10
temperature of 75°C (THHW cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (THHN cable).
It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction Manual (Startup) or Instruction Manual
(Hardware).)
*3 For the FR-A820-00770(15K) or lower and the FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 70°C (PVC cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A820-00930(18.5K) or higher and the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum
permissible temperature of 90°C (XLPE cable). It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
*4 The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1, and a screw for earthing
(grounding).
The screw size for terminals PR and PX on FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in parentheses.
The screw size for earthing (grounding) terminal on FR-A820-00930(18.5K) or higher and FR-A840-04320(160K) or higher is indicated in
parentheses.
The screw size for terminal P/+ for option connection on the FR-A840-03250(110K) and FR-A840-03610(132K) is indicated in parentheses.
NOTE
• Tighten the terminal screw to the specified torque.
A screw that has been tightened too loosely can cause a short circuit or malfunction.
A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
300 m
When driving a 400 V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor
terminals, deteriorating the insulation of the motor. In this case, take one of the following measure.
• Use a "400 V class inverter-driven insulation-enhanced motor" and set Pr.72 PWM frequency selection according to the
wiring length.
Wiring length 50 m or Wiring length longer
Wiring length 50 to 100 m
shorter than 100 m
15 (14.5 kHz) or lower 9 (9 kHz) or lower 4 (4 kHz) or lower
• For the FR-A840-01800(55K) or lower, connect a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) at the output
side of the inverter. For the FR-A840-02160(75K) or higher, connect a sine wave filter (MT-BSL/BSC) at the output side of
the inverter.
With PM motor
Use the wiring length of 100 m or shorter when connecting a PM motor.
Use one PM motor for one inverter. Multiple PM motors cannot be connected to an inverter.
When the wiring length exceeds 50 m for a 400 V class motor driven by an inverter under PM sensorless vector control, set "9"
(6 kHz) or less in Pr.72 PWM frequency selection.
NOTE
• Especially for long-distance wiring, the inverter may be affected by a charging current caused by stray capacitances of the
wiring, leading to an activation of the overcurrent protection, malfunction of the fast-response current limit operation, or even
to an inverter failure. It may also cause a malfunction or fault of the equipment connected ON the inverter output side. If the
fast-response current limit function malfunctions, disable this function. (Refer to Pr.156 Stall prevention operation selection
on page 409.)
• A surge voltage suppression filter (FR-ASF-H/FR-BMF-H) can be used under V/F control and Advanced magnetic flux vector
control.
A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under different control methods.
• For the details of Pr.72 PWM frequency selection, refer to page 339.
• Refer to page 128 to drive a 400 V class motor by an inverter.
• The carrier frequency is limited during PM sensorless vector control. (Refer to page 339.)
(I) Independent earthing (grounding): Best (II) Common earthing (grounding): Good (III) Common earthing (grounding) cable: Not allowed
NOTE
• To be compliant with the EU Directive (Low Voltage Directive), refer to the Instruction Manual (Startup).
2 4
6
V / 0 to 10 V). Use Pr.858 to switch terminal functions.
Input resistance:
Input 0 to ±5 VDC or 0 to ±10 VDC to add this signal to the
10 ± 1 kΩ,
1
Frequency setting
auxiliary
frequency setting signal input via terminal 2 or 4. Use Pr.73
to switch between input 0 to ±5 VDC and 0 to ±10 VDC
permissible maximum 473 7
voltage:
(initial setting). Use Pr.868 to switch terminal functions.
±20 VDC
Common terminal for the frequency setting signal (via
5
Frequency setting
common
terminal 2, 1, or 4) and for the analog output terminals AM — 473 8
and CA. Do not earth (ground).
Applicable PTC
thermistor specification,
Thermistor
*1 The terminal function can be selected by Pr.178 to Pr.196 (Input terminal function selection). (Refer to page 496.)
*2 Set Pr.73, Pr.267, and the voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage with each of the voltage/current input switch ON (current input is selected) or a current with each of the switch OFF (voltage
input is selected) could cause component damage of the inverter or analog circuits of output devices. (For the details, refer to page 473.)
*3 Sink logic is initially set for the FM-type inverter.
*4 Source logic is initially set for the CA-type inverter.
— compatible)
Mini B connector (receptacle).
By connecting an inverter to the personal Transmission speed: 12 6
USB B connector computer through USB, FR Configurator2 can Mbps 84
be used for setting the inverter, monitoring, and
testing the operation.
7
CC-Link IE Field Network (FR-A800-GF)
Refer
Type
Terminal
name
Terminal function description to 8
page
PORT 1
CC-Link IE
PORT 2
Communication can be made via the CC-Link IE Field Network. 107
9
Safety stop signal
10
Terminal Refer to
Terminal name Terminal function description Rated specification
symbol page
Use terminals S1 and S2 to receive the safety stop signal input
Safety stop input from the safety relay module. Terminals S1 and S2 can be used
S1 at a time (dual channel).
(channel 1)
The Inverter judges the condition of the internal safety circuit from
Input resistance: 4.7 kΩ,
the status (shorted/opened) between terminals S1 and SIC, or
input current: 4 to 6
between S2 and SIC. When the status is opened, the inverter
mADC (with 24 VDC
output is shut off.
Safety stop input input)
S2 In the initial status, terminal S1 and S2 are shorted with terminal
(channel 2) PC by shorting wires. Terminal SIC is shorted with terminal SD.
Remove the shorting wires and connect the safety relay module
when using the safety stop function.
Safety stop input
SIC Common terminal for terminals S1 and S2. —
terminal common 80
The data of the inverter output status is output to the safety relay
module. Permissible load:
The output is in HIGH state during occurrence of the internal 24 VDC
Safety monitor
safety circuit fault. The output is in LOW state otherwise. (27 VDC at maximum),
output
So (SO) (The open collector transistor is ON (conductive) in LOW state. 0.1 A
(open collector
The transistor is OFF (not conductive) in HIGH state.) (The voltage drop is 3.4
output)
Refer to the Safety Stop Function Instruction Manual if the output V at maximum while the
becomes in HIGH state even though both terminals S1 and S2 signal is ON.)
are open. (Contact your sales representative for this manual.)
Safety monitor
SOC output Common terminal for terminal So (SO). —
terminal common
Jumper connector
SOURCE
SINK
NOTE
• Make sure that the jumper connector is installed correctly.
• Never change the control logic while power is ON.
• To change the control logic for the FR-A800-GF, remove the control circuit terminal block and change the jumper connector
position. (Refer to page 783 for details on how to remove the terminal block.) After changing the jumper connector position,
reinstall the control circuit terminal block securely in place.
Current Sink
STF Current
connector
R STF
R Source
connector
STR
R STR
R
SD
SE - + TB17 SE + - TB18
24 VDC 24 VDC
24 VDC
voltage PC voltage
Fuse TB17
circuit
TB18
circuit
TB18 SD
6
24 VDC SD
10
Wiring method
Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the sheath
of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1. Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Cable sheath stripping length
10 mm
*1 A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*2 Applicable for terminals A1, B1, C1, A2, B2, C2.
• NICHIFU Co., Ltd.
Cable gauge Blade terminal Insulation cap product Crimping tool product
(mm2) product number number number
0.3 to 0.75 BT 0.75-11 VC 0.75 NH 69
3. Insert the wires into a socket. When using a single wire or stranded wires without a blade
terminal, push the open/close button all the way down with a
flathead screwdriver, and insert the wire.
Open/close button
Flathead screwdriver
NOTE
• When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires.
• Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage
or injury.
Flathead screwdriver
2
4
NOTE
• Pulling out the wire forcefully without pushing the open/close button all the way down may damage the terminal block.
• Use a small flathead screwdriver (tip thickness: 0.4 mm / tip width: 2.5 mm).
If a flathead screwdriver with a narrow tip is used, terminal block may be damaged.
5
Commercially available products (as of February 2016)
+24 V Inverter
PC
+24 V
STF, etc
External signal input using transistor External signal input using transistor
(sink logic) (source logic)
• To suppress EMI, use shielded or twisted cables for the control circuit terminals and run them away from the main and
power circuits (including the 200 V relay sequence circuit). For the cables connected to the control circuit terminals,
connect their shields to the common terminal of the connected control circuit terminal. When connecting an external power
supply to terminal PC, however, connect the shield of the power supply cable to the negative side of the external power
supply. Do not directly earth (ground) the shield to the enclosure, etc.
• Always apply a voltage to the fault output terminals (A1, B1, C1, A2, B2, and C2) via a relay coil, lamp, etc.
• For the FR-A820-03160(55K) or higher and FR-A840-02160(75K) or higher, separate the wiring of the control circuit away
from the wiring of the main circuit.
Make cuts in rubber bush of the inverter side and lead the wires through.
<Wiring example>
Rubber bush
(viewed from inside)
R/L1
S/L2
5
(a) T/L3
(b)
6
R1/L11
(d)
S1/L21
7
Main circuit terminal block
(c) 10
R1/L11
(a) S1/L21
(b)
R/L1
(d)
MC
FR-A820-00770(15K)
to 01250(22K)
FR-A840-00470(18.5K), FR-A820-01540(30K) FR-A820-01870(37K) or higher
00620(22K) FR-A840-00770(30K) FR-A840-00930(37K) or higher
Power supply
terminal block for
the control circuit
NOTE
• When using separate power supplies, always remove the jumpers across terminals R/L1 and R1/L11 and across S/L2 and S1/
L21. The inverter may be damaged if the jumpers are not removed.
• When the control circuit power is supplied from other than the input line of the MC, the voltage of the separate power supply
must be the same as that of the main control circuit .
• The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter
capacity.
Power supply
Inverter
capacity
FR-A820-00630(11K) or lower
60 VA
FR-A840-00380(15K) or lower
FR-A820-00770(15K) or higher
80 VA
FR-A840-00470(18.5K) or higher
• If the main circuit power is switched OFF (for 0.1 seconds or more) then ON again, the inverter is reset and a fault output will
not be held.
NOTE
• When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter operation is disabled. 7
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is
performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using
Pr.30. (Refer to page 689.))
8
Confirming the 24 V external power supply input
• During the 24 V external power supply operation, "EV" blinks on the operation panel. The alarm lamp also blinks. Thus, 9
the 24 V external power supply operation can be confirmed even when the operation panel is removed.
Blinking
Blinking 10
POWER ALARM
• During the 24 V external power supply operation, the 24 V external power supply operation (EV) signal is output. To use
the EV signal, set "68 (positive logic) or 168 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign function to an output terminal.
NOTE
• Use terminal So (SO) to output a fault and to prevent restarting of the inverter. The signal output from terminal So (SO) cannot
be used to input a safety stop signal to other devices.
2
Inverter R/L1 S/L2 T/L3
3
So (SO)
Logic
SOC
4
IGBTs
+24V
PC Fuse Gate Gate
5
CPU ASIC Driver Driver
RESET
24 VDC
S2 G G
S1
6
Emergency
stop button SIC
SD
Safety relay module /
Safety programmable controller
7
U V W
8
Safety stop function operation
Input
Internal
safety
Input terminal*1*2
Output
terminal
Output
signal*8*9*10 Inverter operating status
Operation panel indication 9
power
circuit status S1 S2 So (SO) SAFE E.SAF*6 SA*7
OFF — — — OFF OFF Output shutoff (Safe state) Not displayed Not displayed
Normal ON ON ON*3 OFF Operation enabled Not displayed Not displayed 10
Normal ON OFF *4 *4 Output shutoff (Safe state) Displayed Displayed
OFF OFF
Normal OFF ON OFF*4 OFF*4 Output shutoff (Safe state) Displayed Displayed
Normal OFF OFF *3 *3 Output shutoff (Safe state) Not displayed Displayed
ON ON
ON
Not
Fault ON ON OFF OFF Output shutoff (Safe state) Displayed
displayed*5
Fault ON OFF OFF OFF Output shutoff (Safe state) Displayed Displayed
Fault OFF ON OFF OFF Output shutoff (Safe state) Displayed Displayed
Fault OFF OFF OFF OFF Output shutoff (Safe state) Displayed Displayed
*1 The terminal ON state shows that the terminal is conducted (the line is closed), and the OFF state shows that the terminal is not conducted (the
line is open).
*2 When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter. (In the initial status,
terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)
*3 If any of the protective functions shown in the following table is activated, terminal So (SO) and the SAFE signal turn OFF.
Fault type Operation panel indication Fault type Operation panel indication
Option fault E.OPT Speed deviation excess detection E.OSD
Communication option fault E.OP1 to E.OP3 Signal loss detection E.ECT
Parameter storage device fault E.PE Excessive position fault E.OD
Retry count excess E.RET Brake sequence fault E.MB1 to E.MB7
Parameter storage device fault E.PE2 E.CPU
CPU fault
Operation panel power supply E.5 to E.7
short circuit/RS-485 terminals E.CTE
Encoder phase fault E.EP
power supply short circuit
24 VDC power fault E.P24 Magnetic pole position unknown E.MP
Safety circuit fault E.SAF
Internal circuit fault E.13
Overspeed occurrence E.OS
*10 The use of SAFE signal has not been certified for compliance with safety standards.
For more details, refer to the Safety Stop Function Instruction Manual.
Find a PDF file of the manual in the CD-ROM enclosed with the product.
2.7.1 PU connector 2
Mounting the operation panel or the parameter unit on the enclosure
surface 3
• Having an operation panel or a parameter unit on the enclosure surface is convenient. With a connection cable, the
operation panel or the parameter unit can be mounted to the enclosure surface and connected to the inverter.
Use the option FR-CB2[ ], or connectors and cables available on the market. 4
(To mount the operation panel, the optional connector (FR-ADP) is required.)
Securely insert one end of the connection cable until the stoppers are fixed.
5
Parameter unit connection cable
(FR-CB2[ ]) (option)
8
STF FWD PU
NOTE
• Refer to the following table when fabricating the cable on the user side. Keep the total cable length within 20 m.
• Commercially available products (as of February 2015)
Communication operation
• Using the PU connector as a computer network port enables communication operation from a personal computer, etc.
When the PU connector is connected with a personal, FA or other computer by a communication cable, a user program
can run to monitor the inverter or read and write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation).
For the details, refer to page 625.
USB host
(A connector) USB memory device
Communication status
Place a flathead screwdriver,
indicator (LED)
etc. in a slot and push up the
cover to open. USB device
(Mini B connector)
• When the inverter recognizes the USB memory device without any problem, " " is briefly displayed on the
operation panel.
• When the USB memory device is removed, " " is briefly displayed on the operation panel.
• The operating status of the USB host can be checked on the LED display of the inverter.
LED display status Operating status
OFF No USB connection.
ON The communication is established between the inverter and the USB device.
Fast blinking The USB memory device is being accessed. (Do not remove the USB memory device.)
Slow blinking Error in the USB connection.
• When a device such as a USB charger is connected to the USB connector and an excessive current (500 mA or higher)
flows, USB host error " " (UF warning) is displayed on the operation panel.
• When the UF warning appears, the USB error can be canceled by removing the USB device and setting Pr.1049 = "1".
(The UF warning can also be canceled by resetting the inverter power or resetting with the RES signal.)
NOTE
• For the details of FR Configurator2, refer to the Instruction Manual of FR Configurator2.
5
(f) 1
2
O
N
SW2
PB1
PZ1
PA1
PIN
PG
PG
PIN and PO
(c) SW3
are not used.
O
N
(e)
1
2
3
4
SW1
PB2
PZ2
PA2
PO
SD
SD
(a) (a)
(b) (a)
NOTE
• When the encoder's output voltage differs from its input power supply voltage, the signal loss detection (E.ECT) may occur.
• Incorrect wiring or faulty setting to the encoder will cause a fault such as an overcurrent (E.OC[ ]) and an inverter overload
(E.THT). Correctly perform the encoder wiring and setting.
1 O
driver (initial status)
2
2 N
SW2
SW3
O
N
1
2
3
4
Complementary
SW1
4
• Use the terminating resistor selection switches (SW1) to select ON/OFF of the internal terminating resistor.
Set the switches ON (initial status) when an encoder output type is differential line driver, and set OFF when
complementary.
5
ON: With internal terminating resistor (initial status)
OFF: Without internal terminating resistor
Internal terminating
resistor-ON
6
(initial status)
1 O
7
2 N
SW2
SW3
O
N
1
2
3
4
SW1
Internal terminating
8
resistor-OFF
9
NOTE
• Set all switches to the same setting (ON/OFF).
• Set the switches OFF when sharing an encoder with another unit (NC (computerized numerical controller), etc.) having a
terminating resistor under the differential line driver setting. 10
NOTE
• The SW2 switches are for manufacturer setting. Do not change the setting.
• When the power supply of the inverter is turned OFF, also turn off the power supply of the encoder. Otherwise, the plug-in
option may be damaged.
Encoder cable
SF-JR/HR/JRCA/HRCA with encoder
FR-A800
F-DPEVSB 12P 0.2 mm2 D/MS3057-12A
(FR-A8AP) PLG
Approx. 140 mm
11 mm
M A B
N C
PG H L
SD K T P D
K E
S R
J F
H G
D/MS3106B20-29S
(As viewed from wiring side)
2 mm2
SF-V5RU, SF-THY
FR-A800
(FR-A8AP) PLG
PA1 A
PA2 B
PB1 C
F-DPEVSB 12P 0.2 mm2 D/MS3057-12A PB2 D
PZ1 F
Approx. 140 mm PZ2 G Positioning keyway
11 mm
Earth cable
M A B
PG S N C
L
60 mm SD R T P D
L D/MS3106B20-29S K E
S R
A P clip for earthing (grounding) a shielded cable is provided. J
H G F
D/MS3106B20-29S
(As viewed from wiring side)
2 mm2
3
5 mm
NOTE
• Information on blade terminals
4
Commercially available products (as of January 2017)
Phoenix Contact Co., Ltd.
M2
0.3
0.5
AI 0,34-6TQ
AI 0,5-6WH
A 0,34-7
A 0,5-6
CRIMPFOX 6 6
NICHIFU Co., Ltd.
Terminal screw Cable gauge Blade terminal Insulation cap Crimping tool 7
size (mm2) product number product number product number
M2 0.3 to 0.75 BT 0.75-7 VC 0.75 NH 69
• When using a blade terminal (without insulation sleeve), take caution that the twisted wires do not come out. 8
9
• Connection terminal compatibility table
Motor SF-V5RU, SF-THY SF-JR/HR/JRCA/HRCA (with encoder)
Encoder cable FR-V7CBL FR-JCBL 10
PA1 PA PA
PA2 Do not connect anything to this. PAR
PB1 PB PB
PB2 Do not connect anything to this. PBR
FR-A8AP terminal
PZ1 PZ PZ
PZ2 Do not connect anything to this. PZR
PG PG 5E
SD SD AG2
PA2 B
PB2 N
10 Differential PLG PB1 C
Frequency command 3 PZ1 B PB2 D
Frequency setting 2 PLG
2 PZ2 P *2 Differential PZ1 F
potentiometer
Complementary PZ2 G *2
1/2 W 1 kΩ 1 5 PG H
Complementary PG S
Terminating SD K Terminating SD R
resistor ON resistor
Torque limit PG PG
(+) 1 ON
command (-) *3 SD *3
SD 12 VDC power
(±10 V) (-) 5 VDC power supply *4 *6 (+) (-) supply *5
*6
(+)
OFF OFF
*5
*4
• Torque control
Vector control dedicated motor (SF-V5RU,
Standard motor with encoder (SF-JR), 5 V differential line driver
SF-THY), 12 V complementary
PB2 N PA2 B
10 Differential PLG PB1 C
Speed limit command 3 PZ1 B PB2 D
Frequency setting 2
2 PZ2 P *2 F
PLG
potentiometer Differential PZ1
1/2 W 1 kΩ 1 Complementary PZ2 G *2
5 PG H
Complementary PG S
Terminating SD K SD
Terminating R
Torque command (+) 1 resistor ON resistor
PG ON PG
(±10 V) (-) *3 SD *3
SD 12 VDC power
(+) (-) 5 VDC power supply *4 *6 (+) (-) supply *5
OFF *6 OFF
*5
*4
PG S
SD R
2 mm2
Encoder cable
Shield
P-clip
• When one encoder is shared between the FR-A8AP and CNC (computerized numerical controller), its output signal should
be connected as follows. In this case, the wiring length between the FR-A8AP and CNC should be as short as possible,
within 5 m.
Inverter
Encoder
(FR-A8AP)
CNC
Maximum 5 m
(two parallel cables)
NOTE
• For the details of the optional encoder dedicated cable (FR-JCBL/FR-V7CBL), refer to page 88.
• The FR-V7CBL is provided with a P-clip for earthing (grounding) shielded cables.
• The following table shows parameters to be set according to the Vector control compatible option to be used.
8
FR-A8AP/FR-A8AL
Item FR-A8APR parameter FR-A8APS parameter FR-A8TP parameter
parameter
Encoder/Resolver rotation
direction
Pr.359 Pr.852
9
— (obtained via
Number of detector pulses Pr.369 — (fixed pulses of 1024) communication from the Pr.851
encoder)
10
SF-V5RU
(1500 r/min series) 0*3 30 Motor capacity 4 1 (initial value) 2048
Vector control SF-V5RU
dedicated (other than the 1500 0*3 1 (13)*1 Motor capacity 4 1 (initial value) 2048
motor r/min series)
SF-THY 0*3 30 (33)*1 Motor capacity 4 1 (initial value) 2048
Other
Rated motor Number of
manufacturer's —
current 0 (3)*1 Motor capacity
motor poles
*2 *2
standard motor
Other
manufacturer's Rated motor Number of
constant-torque
—
current 1 (13)*1 Motor capacity
motor poles
*2 *2
motor
PM motor Refer to the Instruction Manual of the FR-A8APR.
*1 Offline auto tuning is required. (Refer to page 509.)
*2 Set this parameter according to the motor.
*3 Use the thermal protector input provided with the motor.
• When using the inverter with the SF-V5RU (1500 r/min series), refer to the following table to set Pr.83 Rated motor
voltage and Pr.84 Rated motor frequency.
SF-V5RU SF-V5RU
Motor Motor
200 V 400 V 200 V 400 V
capacity capacity
Pr.83 (V) Pr.84 (Hz) Pr.83 (V) Pr.84 (Hz) Pr.83 (V) Pr.84 (Hz) Pr.83 (V) Pr.84 (Hz)
1.5 kW 188 52 345 52 18.5 kW 171 51 346 51
2.2 kW 188 52 360 52 22 kW 160 51 336 51
3.7 kW 190 52 363 52 30 kW 178 51 328 51
5.5 kW 165 51 322 51 37 kW 166 51 332 51
7.5 kW 164 51 331 51 45 kW 171 51 342 51
11 kW 171 51 320 51
55 kW 159 51 317 51
15 kW 164 51 330 51
• When using the inverter with the SF-V5RU1, SF-V5RU3, or SF-V5RU4, refer to the following table to set Pr.83 Rated
motor voltage and Pr.84 Rated motor frequency.
Pr.83 setting
Motor model Pr.84 setting
200 V class 400 V class
SF-V5RU1-30kW or lower 160 V 320 V
SF-V5RU1-37kW 170 V 340 V
33.33 Hz
SF-V5RU3-22kW or lower 160 V 320 V
SF-V5RU3-30kW 170 V 340 V
SF-V5RU4-3.7kW and 7.5kW 150 V 300 V
SF-V5RU4 and motors other 16.67 Hz
160 V 320 V
than described above
Terminal PR
Terminal PX
2) Connect the brake resistor
across terminals P/+ and PR. Terminal P/+ Terminal PX
(The jumper should remain
Terminal PR 2) Connect the brake resistor
disconnected.)
across terminals P/+ and Terminal P/+
PR. (The jumper should Terminal PR
remain disconnected.)
Brake resistor
Brake resistor
1
1) Remove the screws in terminals PR 2) Connect the brake resistor across
and PX and remove the jumper. terminals P/+ and PR. (The jumper
should remain disconnected.)
Jumper
2
Terminal P/+
Terminal PR Terminal PR
3
Terminal PX
Brake resistor 4
Brake resistor
Brake resistor
9
FR-A840-00770(30K) FR-A840-00930(37K) to FR-A840-01800(55K)
10
Connect the brake resistor Connect the brake resistor
across terminals P3 and PR. across terminals P3 and PR.
Terminal P3
Terminal P3 Terminal PR
Terminal PR
Brake resistor
Brake resistor
*1 Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
NOTE
• For the FR-A820-00490(7.5K) or lower and the FR-A840-00250(7.5K) or lower, the jumper across terminals PR and PX must
be disconnected before connecting the dedicated brake resistor. Doing so may damage the inverter.
• A brake resistor cannot be used with options such as brake units, high power factor converters, and power regeneration
converters.
• When the regenerative brake transistor is damaged, the following sequence is recommended to prevent overheat and
burnout of the brake resistor.
Thermal Thermal
relay <Example 2> relay
<Example 1>
MC Inverter (OCR)(∗2) FR-ABR MC Inverter (OCR)(∗2) FR-ABR
R/L1 P/+ R R/L1 P/+ R
Power (P3) Power (P3)
S/L2 S/L2
Supply Supply
T/L3
PX T/L3 PX
T T
F PR PR
F
Disconnect jumper. (∗1) B Disconnect jumper. (∗1)
MC OFF ON MC
OFF ON
C
OCR OCR
MC Contact MC Contact
*1 Since the FR-A820-00630(11K) or higher and FR-A840-00310(11K) or higher are not provided with terminal PX, a jumper need not to be
removed.
*2 Refer to the following table for the thermal relay models for each capacity. Refer to the following diagram for the connection. (Always install a
thermal relay when using a brake resistor whose capacity is 11K or higher.)
FR-ABR-3.7K TH-N20CXHZ-3.6A
200 V FR-ABR-5.5K TH-N20CXHZ-5A
FR-ABR-7.5K TH-N20CXHZ-6.6A 2/T1 6/T3
FR-ABR-H2.2K TH-N20CXHZ-1.3A
FR-ABR-H3.7K TH-N20CXHZ-2.1A
400 V
FR-ABR-H5.5K TH-N20CXHZ-2.5A
FR-ABR-H7.5K TH-N20CXHZ-3.6A
FR-ABR-H11K TH-N20CXHZ-6.6A
FR-ABR-H15K TH-N20CXHZ-6.6A
FR-ABR-H22K TH-N20-9A
9
Set parameters as follows:
• Pr.30 Regenerative function selection = "1"
• Set Pr.70 Special regenerative brake duty according to the amount and frequency of the regenerative driving, and make 10
sure that the resistor can consume the regenerative power properly. (Refer to page 689.)
• When the regenerative brake transistor is damaged, install a thermal relay as shown in the following sequence to prevent
overheat and burnout of the brake resistor. Properly select a thermal relay according to the regenerative driving frequency
or the rated power or resistance of the brake resistor.
*1 Since the FR-A820-00630(11K) or higher and FR-A840-00310(11K) or higher are not provided with terminal PX, a jumper need not to be
removed.
CAUTION
• If the resistor selection is incorrect, overcurrent may damage the inverter built-in brake transistor. Besides, the resistor
may be burned due to overheat.
• If the selection of the thermal relay is incorrect, the resistor may be burned due to overheat.
T ∗2
MC MC
GRZG type ∗6
discharging
OCR resistor
MCCB MC R R
R/L1 U Motor External thermal
Three-phase AC
power supply
S/L2 V M relay ∗5
T/L3 W
Inverter FR-BU2
∗4 PR A
PR
∗3 P/+ P/+ B
PX ∗1 ∗1
N/- N/- C
BUE
∗4
SD
10 m or less
*1 When wiring, make sure to match the terminal symbols (P/+, N/-) on the inverter and on the brake unit (FR-BU2). (Incorrect connection will
damage the inverter and brake unit.)
*2 When the power supply is 400 V class, install a stepdown transformer.
*3 Be sure to remove the jumper across terminals PR and PX when using the FR-BU2 with the inverter of FR-A820-00490(7.5K) or lower, or FR-
A840-00250(7.5K) or lower.
*4 The wiring distance between the inverter, brake unit (FR-BU2) and discharging resistor must be within 5 m. Even when the cable is twisted, the
wiring length must be within 10 m.
*5 It is recommended to install an external thermal relay to prevent overheat of the discharging resistor.
*6 For the connection method of the discharging resistor, refer to the Instruction Manual of the FR-BU2.
• Recommended external thermal relay
Recommended external
Brake unit Discharging resistor
thermal relay
FR-BU2-1.5K GZG 300W-50Ω (one) TH-N20CXHZ 1.3A
FR-BU2-3.7K GRZG 200-10Ω (three in series) TH-N20CXHZ 3.6A 1/L1 5/L3
TH-N20
NOTE
• Set "1" in Pr.0 Brake mode selection in the FR-BU2 to use a GRZG type discharging resistor.
• Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
Inverter FR-BU2
∗3
PR
P/+
PR A 4
P/+ B
PX ∗1
N/- N/- C
BUE
∗4
10 m or less
SD 5
*1 When wiring, make sure to match the terminal symbols (P/+, N/-) on the inverter and on the brake unit (FR-BU2). (Incorrect connection will
damage the inverter and brake unit.)
*2
*3
When the power supply is 400 V class, install a stepdown transformer.
Be sure to remove the jumper across terminals PR and PX when using the FR-BU2 with the inverter of FR-A820-00490(7.5K) or lower, or FR-
6
A840-00250(7.5K) or lower.
*4 The wiring distance between the inverter, brake unit (FR-BU2) and resistor unit (FR-BR) must be within 5 m. Even when the cable is twisted, the
*5
wiring length must be within 10 m.
The contact between TH1 and TH2 is closed in the normal status and is open at a fault. 7
NOTE
• Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
8
Connection example with the MT-BR5 type resistor unit
After making sure that the wiring is correct and secure, set Pr.30 Regenerative function selection = "1" and Pr.70 Special 9
regenerative brake duty = "0 (initial value)". Set Pr.0 Brake mode selection = "2" in the brake unit FR-BU2.
T ∗2
10
MCCB MC ON OFF CR1
Three phase Motor
R/L1 U
AC power S/L2 V M MC
supply T/L3 W MC
10 m ∗4
∗1 or less CR1
P/+ P ∗3 P TH1
N/- ∗3 N P
PR
BUE PR
SD A TH2
B
C
Inverter Brake unit Resistor unit
∗5
FR-BU2 MT-BR5
*1 When wiring, make sure to match the terminal symbols (P/+, N/-) on the inverter and on the brake unit (FR-BU2). (Incorrect connection will
damage the inverter and brake unit.)
*2 When the power supply is 400 V class, install a stepdown transformer.
*3 The wiring distance between the inverter, brake unit (FR-BU2) and resistor unit (FR-BR) must be within 5 m. Even when the cable is twisted, the
wiring length must be within 10 m.
*4 The contact between TH1 and TH2 is open in the normal status and is closed at a fault.
*5 The CN8 connector used with the MT-BU5 type brake unit is not used.
NOTE
• The warning "oL" of the stall prevention (overvoltage) does not occur while Pr.30 Regenerative function selection = "1" and
Pr.70 Special regenerative brake duty = 0% (initial value). (Refer to page 689.)
T ∗2
MC MC
FR-BR
MCCB MC
R/L1 U Motor
P TH1
Three-phase AC
S/L2 V M
power supply PR
T/L3 W TH2
Inverter FR-BU
PR
HA
PR
∗3 P/+ P/+ HB
PX ∗1
N/- N/- HC
∗4
10 m or less
*1 When wiring, make sure to match the terminal symbols (P/+, N/-) on the inverter and on the brake unit (FR-BU(H)). (Incorrect connection will
damage the inverter.)
*2 When the power supply is 400 V class, install a stepdown transformer.
*3 For the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower, be sure to remove the jumper across terminals PR and PX.
*4 The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) must be within 5 m. Even when the cable is twisted, the
wiring length must be within 10 m.
NOTE
• If the transistors in the brake unit should become faulty, the resistor will overheat. Install a magnetic contactor on the inverter's
input side and configure a circuit that shut off the current in case of a fault.
• Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
Inverter MC
MCCB MC Motor
U
R/L1 V M
Three-phase Brake unit
AC power S/L2 W (BU type) Remove the
supply T/L3 jumper
TB
N/-
N OCR HC
P/+
PR HB
∗2
PX HA
Discharging
resistor OCR
PC
PR Fit a jumper
P
*1 When the power supply is 400 V class, install a stepdown transformer.
*2 For the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower, be sure to remove the jumper across terminals PR and PX.
NOTE
• The wiring distance between the inverter, brake unit, and discharging resistor must be within 2 m. Even when the cable is
twisted, the wiring length must be within 5 m.
• If the transistors in the brake unit should become faulty, the resistor will overheat and result in a fire. Install a magnetic
contactor on the inverter's input side and configure a circuit that shut off the current in case of a fault.
• Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
NOTE
• The voltage phases of terminals R/L1, S/L2, and T/L3 and the voltage phases of terminals R4/L14, S4/L24, and T4/L34 must
be matched.
• The control logic (sink logic/source logic) of the high power factor converter and the inverter must be matched. (Refer to page
72.)
• Do not connect a DC reactor (FR-HEL) to the inverter when the FR-HC2 is connected.
R1/L11 W
S1/L21
Dedicated stand-alone FR-CV type
reactor (FR-CVL) Power regeneration Inverter
common converter
MCCB MC1
R/L11 R2/L12
Three-phase R2/L1
AC power S/L21 S2/L22
S2/L2 P/L+ P/+
supply T/L31 T2/L32 ∗2
T2/L3 N/L- N/-
P24 PC
R/L11
SD SD
S/L21 ∗4
RDYA
T/MC1 ∗5
RDYB X10 ∗3
RSO RES
SE
*1 Remove jumpers across terminals R/L1 and R1/L11 as well as across terminals S/L2 and S1/L21, and connect the power supply for the control
circuit to terminals R1/L11 and S1/L21. Do not connect anything to power input terminals (R/L1, S/L2, and T/L3). Incorrect connection will damage
the inverter. (The E.OPT fault (option fault) occurs. (Refer to page 757.))
*2 Do not install an MCCB across terminals P/+ and N/- (between terminals P/L+ and P/+ or between N/L- and N/-). Connecting the opposite polarity
of terminals N/- and P/+ will damage the inverter.
*3 Use Pr.178 to Pr.189 (Input terminal function selection) to assign the terminals used for the X10 signal. (Refer to page 496.)
*4 Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter without connecting them will damage the
power regeneration common converter.
*5 Always connect terminal RDY on the FR-HC2 to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect
terminal SE on the FR-HC2 to terminal SD on the inverter. Not connecting these terminals may damage the FR-CV.
NOTE
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must
be matched.
• Use the sink logic (factory setting) when the FR-CV is connected. It cannot be connected when the source logic is selected.
• Do not connect a DC reactor (FR-HEL) to the inverter when the FR-CV is connected.
R
MT-RCL
R2 P N RES
Reset signal 6
R2
S S2 STF
S2 SD
7
T T2
T2
C
B
R Alarm signal
A
S
T
RDY
8
R1 Ready signal
S1 SE
9
MT-RC
NOTE
• When using the inverter with the MT-RC, install a magnetic contactor (MC) at the input side of the inverter so that power is 10
supplied to the inverter after one second or more has elapsed after powering ON the MT-RC. When power is supplied to the
inverter prior to the MT-RC, the inverter and the MT-RC may be damaged or the MCCB may be shut off or damaged.
Inverter input power supply (MC2) ON
• When connecting the power coordination reactor and others, refer to Instruction Manual of the MT-RC for precautions.
10 cm or more
5 cm or 5 cm or 5 cm or 5 cm or
more more more more
P1 P/+
FR-HEL
Remove
the jumper
• Select a DC reactor according to the applied motor capacity. (Refer to page 790.) For the FR-A820-03800(75K) or higher,
the FR-A840-02160(75K) or higher, and when a 75 kW or higher motor is used, always connect a DC reactor.
• Since the DC reactor (FR-HEL) is electrically connected to the enclosure through mounting screws, the DC reactor is
earthed (grounded) by being securely mounted to the enclosure. However, if the DC reactor is not earthed (grounded)
securely enough, an earthing (grounding) cable may be used.
When using an earthing (grounding) cable for the FR-HEL-(H)55K or lower, wire the cable to the installation hole where
varnish is removed. (Refer to the Instruction Manual of the FR-HEL.)
For the FR-HEL-(H)75K or higher, use an earth (ground) terminal to perform earthing (grounding). (Refer to the Instruction
Manual of the FR-HEL.)
NOTE
• The wiring distance must be within 5 m.
• As a reference, the cable gauge for the connection must be equal to or larger than that of the power supply cables (R/L1, S/
L2, T/L3) and the earthing (grounding) cable. (Refer to page 57.)
6
QJ71GF11-T2 type
MELSEC-Q CC-Link IE Field Network
Master/Local Module User's Manual
...............SH-080917ENG Power Motor Power Motor
LJ71GF11-T2 type Ethernet cable supply supply
MELSEC-L CC-Link IE Field Network
Master/Local Module User's Manual
...............SH-080972ENG 7
Cascade connection
• Up to 20-layer connection is available for the cascade connection.
NOTE
• Refer to the MELSEC iQ-R, MELSEC-Q, or MELSEC-L CC-Link IE Field Network Master/Local Module User's Manual for the
detailed network configurations.
*1 SC-E5EW cable is for in-enclosure and indoor uses. SC-E5EW-L cable is for outdoor use.
NOTE
• For CC-Link IE Field Network wiring, use the recommended wiring components by CC-Link Partner Association.
• Cables for CC-Link IE Controller Network cannot be used for CC-Link IE Field Network.
• Depending on the cable connector shape, the cable may not be connected to the communication connector.
Hubs
• Use hubs that meet the following conditions. Operation is not guaranteed if the hubs do not meet these conditions.
- Compliance with the IEEE802.3 (1000BASE-T)
- Support of the auto MDI/MDI-X function
- Support of the auto-negotiation function
- Switching hub (layer 2 switch)*1
*1 A repeater hub is not available.
RUN D.LINK
SD ERR Operation status indication LED
RD L.ERR
Earth plate
NOTE
• Do not remove the CC-Link IE Field Network communication circuit board or the earth plate.
NOTE 9
• PORT 1 and PORT 2 do not need to be distinguished.
- When only one connector is used in star topology, either PORT 1 or PORT 2 is applicable.
- When using two connectors for line topology and ring topology, an Ethernet cable can be connected to the connectors in any
combination For example, the cable can be connected across two of PORT 1 or across PORT 1 and PORT 2. 10
Connection between Connection between
PORT1 and PORT1, PORT2 and PORT2 PORT1 and PORT2
Precautions
• Do not touch the core of the cable-side or module-side connector, and protect it from dirt or dust. If oil from your hand, dirt
or dust is attached to the core, it can increase transmission loss, arising a problem in data link.
• Do not use Ethernet cables with broken latches. Doing so may cause the cable to unplug or malfunction.
• Hold the connector part when connecting and disconnecting the Ethernet cable. Pulling a cable connected to the module
may damage the module or cable, or result in malfunction due to poor contact.
• The maximum station-to-station distance is 100 m. However, the distance may be shorter depending on the operating
environment of the cable. For details, contact your cable manufacturer.
• Check the instructions on page 107 before wiring, and perform correct wiring.
• When the operations listed below are performed, all stations on the network may be reconnected. At that time, a data link
error may momentarily occur in all the stations, and the communication error E.OP1 may occur in the connected inverters.
Network configuration Operation
Star topology • Powering ON/OFF a slave station or the switching hub
• Connecting/disconnecting an Ethernet cable connected to the switching hub
• Disconnecting an Ethernet cable from a slave station and connecting it to another slave station or to
the switching hub
• Disconnecting ten stations or more, or disconnecting half the number of slave stations in the system or
more
• Changing the network topology when adding a slave station
Line topology / ring topology • Simultaneously powering ON/OFF multiple stations
• Simultaneously connecting/disconnecting Ethernet cables to/from multiple stations (When a data link
faulty station returns, a data link error will occur in all the stations.)
• Disconnecting ten stations or more, or disconnecting half the number of slave stations in the system or
more
• Changing the network topology when adding a slave station
A momentary error
in all stations
• To keep outputting a data link error (inverter communication error), set Pr.500 Communication error execution waiting
time or Pr.502 Stop mode selection at communication error.
NOTE
• When wiring cables to the inverter's RS-485 terminals, take caution not to let the cables touch the CC-Link IE Field Network
communication circuit board or of the inverter's circuit board. Otherwise, electromagnetic noises may cause malfunctions.
• After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction.
RUN D.LINK
SD ERR
RD L.ERR
10
10
113
3 PRECAUTIONS FOR USE OF THE INVERTER
This chapter explains the precautions for use of this product.
Always read the instructions before use.
For the separated converter type, refer to the "PRECAUTIONS FOR USE OF THE INVERTER" in the FR-A802 (Separated
Converter Type) Instruction Manual (Hardware).
For the IP55 compatible model, refer to the "PRECAUTIONS FOR USE OF THE INVERTER" in the FR-A806 (IP55/UL Type
12 specification) Instruction Manual (Hardware).
Countermeasures
• If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.
• By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
NOTE
• Long wiring will increase the leakage current.
• High motor capacity will increase the leakage current. The leakage current of the 400 V class is larger than that of the 200 V
class.
*1 The leakage currents of the 400 V class are about twice as large.
2.0 100
Leakage currents (mA)
Leakage currents (mA)
120 1. 0
80 0. 7
100
1.0 0. 5
60
80 0.7
0. 3
0.5 40
60 0. 2
0.3 20
40
0.2 0 0. 1
20 2 3.5 8 142238 80150 1. 5 3. 7 7. 5 15223755
5.5 30 60 100 2. 2 5.5 1118. 53045
0 0.1
2 3.5 8 14 2238 80150 1.5 3.7 7.5 15223755 Cable size (mm2) Motor capacity (kW)
5.5 30 60 100 2.2 5.5 11 18.5 3045
2
Cable size(mm ) Motor capacity (kW) For " " connection, the amount of leakage current is appox.1/3 of the above value.
NOTE
• Install the earth leakage circuit breaker (ELB) on the input side of the inverter.
• In the connection earthed-neutral system, the sensitivity current is blunt against a ground fault in the inverter output side.
Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (NEC
section 250, IEC 61140 class 1 and other applicable standards)
• When the breaker is installed on the output side of the inverter, it may be unnecessarily operated by harmonics even if the
effective value is within the rating.
In this case, do not install the breaker since the eddy current and hysteresis loss will increase, leading to temperature rise.
• The following models are standard breakers: BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA, NV-2F, earth leakage relay
(except NV-ZHA), and NV with AA neutral wire open-phase protection.
The other models are designed for harmonic and surge suppression: NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-C2,
earth leakage alarm breaker (NF-Z), NV-ZHA, and NV-H.
Basic techniques
• Do not run the power cables (I/O cables) and signal cables of the inverter in parallel with each other and do not bundle
them.
• Use shielded twisted pair cables for the detector connecting and control signal cables and connect the sheathes of the
shielded cables to terminal SD.
• Ground (Earth) the inverter, motor, etc. at one point.
Inverter generated
electromagnetic
Air propagated
noise
Noise directly
radiated from inverter
Path (a) 6
noise
Noise radiated from
power supply cable
Path (b)
(e) Telephone
Noise radiated from
motor connection cable
Path (c) 7
Electromagnetic
(g) (g)
Path (d), (e) (b)
induction noise
Electrostatic
Path (f)
(a) Sensor
power supply
8
induction noise
Instrument Receiver (c) Inverter
Electrical path Noise propagated through (f) (a) (f)
Path (g)
propagated noise power supply cable (d)
Noise from earthing
(c) Sensor
9
(grounding) cable due to Path (h) Motor M
leakage current
10
Noise propagation
Countermeasure
path
When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g.
instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal
cables are run near the inverter, the devices may malfunction due to by air-propagated electromagnetic noises. The
following countermeasures must be taken:
• Install easily affected devices as far away as possible from the inverter.
• Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
(a), (b), (c)
• Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle
them.
• Set the EMC filter ON/OFF connector of the inverter to the ON position. (Refer to page 118.)
• Inserting a line noise filter into the output suppresses the radiated noise from the cables.
• Use shielded cables as signal cables and power cables and run them in individual metal conduits to produce further
effects.
When the signal cables are run in parallel with or bundled with the power cables, magnetic and static induction noises
may be propagated to the signal cables to cause malfunction of the devices and the following countermeasures must
be taken:
• Install easily affected devices as far away as possible from the inverter.
(d), (e), (f) • Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
• Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle
them.
• Use shielded cables as signal cables and power cables and run them in individual metal conduits to produce further
effects.
When the power supplies of the peripheral devices are connected to the power supply of the inverter in the same line,
inverter-generated noises may flow back through the power supply cables to cause malfunction of the devices and
(g) the following countermeasures must be taken:
• Set the EMC filter ON/OFF connector of the inverter to the ON position. (Refer to page 118.)
• Install the line noise filter (FR-BLF, FR-BSF01) to the power cables (output cables) of the inverter.
13 1
mount
34 1
30 1
(mm)
TDK
The impedance values above are reference values, and not guaranteed values.
NOTE
• For compliance with the EU EMC Directive, refer to the Instruction Manual (Startup).
OFF ON
OFF ON
OFF ON
OFF ON
FILTER FILTER
OFF
OFF
ON
ON
3
EMC filter OFF EMC filter ON EMC filter OFF EMC filter ON EMC filter OFF EMC filter ON EMC filter OFF EMC filter ON
FR-A820-00046(0.4K), FR-A820-00046(0.4K)
00077(0.75K) to 00250(3.7K)
FR-A820-00340(5.5K)
to 00630(11K)
FR-A820-00770(15K)
to 01250(22K)
FR-A820-01540(30K) or higher
FR-A840-00770(30K) or higher 4
FR-A840-00023(0.4K) FR-A840-00170(5.5K) FR-A840-00470(18.5K),
to 00126(3.7K) to 00380(15K) 00620(22K)
EMC filter
ON/OFF
connector
5
NOTE
• Fit the connector or shorting wire to either ON or OFF position.
• Enabling (turning ON) the EMC filter increases leakage current. (Refer to page 115.)
• Countermeasures
The harmonic current generated from the inverter to the input side differs according to various conditions such as the wiring
7
impedance, whether a reactor is used or not, and output frequency and output current on the load side.
For the output frequency and output current, we understand that this should be calculated in the conditions under the rated
load at the maximum operating frequency.
8
DC reactor 9
(FR-HEL)
MCCB MC P/+ P1 10
Power supply
R X
R/L1 U
S Y
S/L2 V M
T Z
T/L3 W
AC reactor Inverter Do not install power
(FR-HAL)
factor improving capacitor.
NOTE
• The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged by the
harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate overcurrent
protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is driven by the inverter.
For power factor improvement, install a reactor on the inverter input side or in the DC circuit.
Calculation of equivalent
capacity total
Equal to or less
than reference
capacity Equivalent
capacity total
Above reference
capacity
Calculation of outgoing
harmonic current
Conversion factor
Classification Circuit type Conversion factor Ki
Without reactor K31 = 3.4
Three-phase bridge (capacitor With reactor (AC side) K32 = 1.8
3
smoothing) With reactor (DC side) K33 = 1.8
With reactors (AC, DC sides) K34 = 1.4
When a high power factor converter
5 Self-excitation three-phase bridge K5 = 0
is used
Applicable
Fundamental
wave current (A)
Fundamental
wave current
Rated
Outgoing harmonic current converted from 6.6 kV (mA) (No reactor, 100%
operation ratio)
10
capacity
motor (kW) converted from
200 V 400 V (kVA) 5th 7th 11th 13th 17th 19th 23rd 25th
6.6 kV (mA)
0.4 1.61 0.81 49 0.57 31.85 20.09 4.165 3.773 2.107 1.519 1.274 0.882
0.75 2.74 1.37 83 0.97 53.95 34.03 7.055 6.391 3.569 2.573 2.158 1.494
1.5 5.50 2.75 167 1.95 108.6 68.47 14.20 12.86 7.181 5.177 4.342 3.006
2.2 7.93 3.96 240 2.81 156.0 98.40 20.40 18.48 10.32 7.440 6.240 4.320
3.7 13.0 6.50 394 4.61 257.1 161.5 33.49 30.34 16.94 12.21 10.24 7.092
5.5 19.1 9.55 579 6.77 376.1 237.4 49.22 44.58 24.90 17.95 15.05 10.42
7.5 25.6 12.8 776 9.07 504.4 318.2 65.96 59.75 33.37 24.06 20.18 13.97
11 36.9 18.5 1121 13.1 728.7 459.6 95.29 86.32 48.20 34.75 29.15 20.18
15 49.8 24.9 1509 17.6 980.9 618.7 128.3 116.2 64.89 46.78 39.24 27.16
18.5 61.4 30.7 1860 21.8 1209 762.6 158.1 143.2 79.98 57.66 48.36 33.48
22 73.1 36.6 2220 25.9 1443 910.2 188.7 170.9 95.46 68.82 57.72 39.96
30 98.0 49.0 2970 34.7 1931 1218 252.5 228.7 127.7 92.07 77.22 53.46
37 121 60.4 3660 42.8 2379 1501 311.1 281.8 157.4 113.5 95.16 65.88
45 147 73.5 4450 52.1 2893 1825 378.3 342.7 191.4 138.0 115.7 80.10
55 180 89.9 5450 63.7 3543 2235 463.3 419.7 234.4 169.0 141.7 98.10
capacity
R/L1 U AC reactor
Power 3000
S Y
supply
S/L2 V M 2000 4
T Z 1000
T/L3 W
110165 247 330 420 550 kVA
Inverter capacity
5
10
NOTE
• Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000 times),
frequent starts and stops of the magnetic contactor must be avoided. Turn ON or OFF the start (STF/STR) signal for the
inverter start control to run or stop the inverter.
MCCB MC
R/L1 U To the
Power motor
S/L2 V
supply
T/L3 W
R1/L11
∗2
S1/L21
T ∗1
Inverter
Operation preparation
C1
OFF ON
MC B1
A1
MC
RA
STF/STR
Start/Stop SD
MC Start
RA
Stop RA
10
Rectifying the motor insulation and limiting the PWM carrier frequency according to the wiring
length
For the 400 V class motor, use an insulation-enhanced motor.
Specifically,
• Order a "400 V class inverter-driven insulation-enhanced motor".
• For the dedicated motor such as the constant-torque motor and low-vibration motor, use an "inverter-driven dedicated
motor".
• Set Pr.72 PWM frequency selection as indicated below according to the wiring length.
Wiring length
Shorter than 50 m 50 to 100 m Longer than 100 m
Pr.72 PWM frequency selection 15 (14.5 kHz) or lower 9 (9 kHz) or lower 4 (4 kHz) or lower
NOTE
• For the details of Pr.72 PWM frequency selection, refer to page 339. (When using an optional sine wave filter (MT-BSL/BSC),
set "25" (2.5 kHz) in Pr.72.)
• For the details of the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) and the sine wave filter (MT-BSL/BSC), refer to
the Instruction Manual of each option.
• A surge voltage suppression filter (FR-ASF-H/FR-BMF-H) can be used under V/F control and Advanced magnetic flux vector
control. A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under different control methods.
• The carrier frequency is limited during PM sensorless vector control. (Refer to page 339.)
10
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Time
ALM ON OFF
(when output
at NC contact)
ON OFF
RES
Reset processing
(about 1 s)
Reset ON
Checking the inverter operating status by the Inverter operation ready signal output from the
inverter ... (b)
The Inverter operation ready (RY) signal is output when the inverter power is ON and the inverter becomes operative. Check
if the RY signal is output after powering ON the inverter.
3
supply
ON OFF
STF
ON
RH
4
Output frequency
DC injection brake
operation point
DC injection
Pr. 13 Starting
brake operation
5
frequency
Reset
Time
processing
RY
ON OFF 6
RUN ON OFF
Checking the motor operating status by the start signal input to the inverter and by the Output
current detection signal output from the inverter ... (d)
7
The Output current detection (Y12) signal is output when the inverter operates and currents flows into the motor.
Check if the Y12 signal is output while a start signal (the STF/STR signal for forward/reverse rotation command) is input to the
inverter. The Y12 signal is initially set to be output at 150% inverter rated current. Adjust the level to around 20% using no load
8
current of the motor as reference with Pr.150 Output current detection level.
Like the Inverter running (RUN) signal, even after the start signal is turned OFF, the Y12 signal is kept output until the inverter
stops the output to a decelerating motor. For the logic check, configure a sequence considering the inverter's deceleration time.
9
Backup method which does not use the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of 10
the inverter itself. For example, if an inverter CPU fails in a system interlocked with the inverter's Fault, start, and RUN signals,
no Fault signals will be output and the RUN signal will be kept ON because the inverter CPU is down.
Provide a speed detector to detect the motor speed and current detector to detect the motor current, and consider the backup
system such as performing a check as follows according to the level of importance of the system.
Controller
System failure
Inverter Sensor
(speed, temperature,
air volume, etc.)
10
135
4 BASIC OPERATION
This chapter explains the basic operation of this product.
Always read the instructions before use.
(d)
(e)
(f)
(j) (g)
(k)
(l)
(m)
(h)
(i)
(d)
Frequency unit LED ON when the actual frequency is monitored. (Blinks when the set frequency is 4
indicator monitored.)
Shows a numeric value (readout) of a monitor item such as the frequency or a
(e) Monitor (5-digit LED) parameter number.
(The monitor item can be changed according to the settings of Pr.52, Pr.774 to Pr.776.) 5
PLC function LED
(f) ON when the PLC function of the inverter is valid.
indicator
FWD key: Starts forward rotation operation. Its LED is ON during forward rotation
operation. 6
REV key: Starts reverse rotation operation. Its LED is ON during reverse rotation
operation.
(g) FWD key, REV key Either LED blinks under the following conditions.
• When the frequency command is not given even if the forward/reverse command is 7
given.
• When the frequency command is equal to the starting frequency or lower.
• When the MRS signal is being input.
4. BASIC OPERATION
4.1 Operation panel (FR-DU08)
137
4.1.2 Basic operation of the operation panel
Basic operation
Operation mode switchover/Frequency setting
∗5
Parameter clear All parameter clear Faults history clear Parameter copy
Group parameter setting Automatic parameter setting IPM initialization Initial value change list
Function
Trace function∗3
Past eight faults can be displayed. (The latest fault is ended by ".".)
When no fault history exists, is displayed.
Hold down
*1 For the details of operation modes, refer to page 370.
*2 The monitor item can be changed. (Refer to page 424.)
*3 For the details of the trace function, refer to page 616.
*4 For the details of faults history, refer to page 745.
*5 The USB memory mode indication appears while a USB memory device is connected. (Refer to page 84.)
Parameter clear
Clears and resets parameter settings to the initial values. Calibration
parameters and offline auto tuning parameters are not cleared. For the 707
3
details of the uncleared parameters, refer to page 824.
Clears and resets parameter settings to the initial values. Calibration
All parameter clear parameters and the offline auto tuning parameters are also cleared. For
the details of the uncleared parameters, refer to page 824.
707 4
Fault history clear Deletes the faults history. 740
Parameter copy
Copies the parameter settings saved in the inverter to the operation
panel. The parameters copied to the operation panel can be also copied 708
5
to other inverters.
Identifies the parameters that have been changed from their initial
Initial value change list 715
settings.
Changes the parameters to the settings required to drive an IPM motor
6
IPM initialization (MM-CF) as a batch. Also changes the parameters back to the settings 224
required to drive an induction motor.
Automatic parameter
Changes parameter settings as a batch. The target parameters include
communication parameters for the Mitsubishi Electric human machine
7
333
setting interface (GOT) connection and the parameters for the rated frequency
settings of 50 Hz/60 Hz.
Group parameter setting Displays parameter numbers by function groups. 195 8
4.1.3 Correspondences between digital and actual
9
characters
There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on
the operation panel: 10
0 1 2 3 4 5 6 7 8 9 A B(b) C c D(d)
E(e) F(f) G(g) H(h) I(i) J(j) K(k) L(l) M(m) N n O o P(p) Q(q)
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
4. BASIC OPERATION
4.1 Operation panel (FR-DU08)
139
4. Selecting the parameter
Turn until " " (Pr.1) appears. Press to read the present set value.
" " (initial value) appears.
Turn to change the set value to " ". Press to confirm the selection. " " and " "
are displayed alternately.
• Press three times to return the monitor display to the indication of the frequency.
NOTE
• If a parameter write condition is not satisfied, a parameter write error appears on the LCD display. (Refer to page 745.)
Calibration error
• When Pr.77 Parameter write selection = "0 (initial setting)," the parameter setting change is only available while the inverter
is stopped and under the PU operation mode. To enable the parameter setting change while the inverter is running or under
the operation mode other than PU operation mode, change the Pr.77 setting. (Refer to page 328.)
• Press on the operation panel in the monitor mode to switch the monitor item between output frequency, output current,
3
and output voltage.
4
Operating procedure
1. Press during inverter operation to monitor the output frequency. [Hz] indicator turns ON.
5
2. Press to monitor the output current. This operation is valid under any operation mode of the inverter and
whether the inverter is running or at a stop. The unit of current "A" appears. 6
3. Press to monitor the output voltage. The unit of voltage "V" appears.
NOTE
• Other monitor item, such as output power or set frequency, is also available. Use Pr.52 Operation panel main monitor
7
selection or Pr.774 Operation panel monitor selection 1 to Pr.776 Operation panel monitor selection 3 to change the
setting. (Refer to page 424.)
8
4.2.2 First priority monitor screen
The first priority monitor screen, which is displayed first when the operation panel becomes in the monitor mode, is selectable. 9
To set it, press for a while when the desired monitor item is displayed on a monitor screen.
The following show the procedure to set the monitor screen displaying the output current as the first priority monitor screen.
10
Operating procedure
1. Change the mode of the operation panel to the monitor mode, and switch the monitor screen to the one on which
the output current can be monitored.
2. Press for a while (1 second). The output current monitor screen is set as the first priority monitor screen.
3. When the operation panel is in the monitor mode next time, the output current monitored value is displayed first.
NOTE
• Use Pr. 52 Operation panel main monitor selection or Pr.774 Operation panel monitor selection 1 to Pr.776 Operation
panel monitor selection 3 to change the monitor item. (Refer to page 424.)
( ) while the inverter runs in the PU operation mode or in the External/PU combined operation mode 1 (Pr.79 Operation
NOTE
• Use Pr.992 Operation panel setting dial push monitor selection to change the item to be displayed. (Refer to page 424.)
4. BASIC OPERATION
4.2 Monitoring the inverter
141
4.3 Easy setting of the inverter operation mode
The operation mode suitable for start and speed command combinations can be set easily using Pr.79 Operation mode
selection.
The following shows the procedure to operate with the external start command (STF/STR) and the frequency command by
using .
Operating procedure
1. Press and for 0.5 seconds.
Blinking
2. Turn until " " (External/PU combined operation mode 1) appears. (For other settings, refer to the
following table.)
Blinking
3. Press to confirm the selection. External/PU combined operation mode 1 (Pr.79 = "3") is set.
Operation method
Operation panel indication Frequency Operation mode
Start command
command
, *1 PU operation mode
Blinking
External Analog
External operation mode
(STF, STR) voltage input
Blinking
External
*1 External/PU combined operation mode 1
(STF, STR)
Blinking
Analog
, External/PU combined operation mode 2
voltage input
Blinking
• " " appears if a setting change is attempted during inverter operation. Turn OFF the start command ( /
2
, or STF/STR signal).
• If is pressed before pressing , the easy setting is terminated and the operation panel returns to the monitor
mode. If the easy setting is terminated while Pr.79 = "0 (initial value)", check the inverter operation mode because the inverter
3
may switch its operation mode between the PU operation mode and the External operation mode.
10
4. BASIC OPERATION
4.3 Easy setting of the inverter operation mode
143
4.4 Frequently-used parameters (simple mode
parameters)
Parameters that are frequently used for the FR-A800 series are grouped as simple mode parameters.
When Pr.160 User group read selection = "9999", only the simple mode parameters are displayed on the operation panel.
This section explains the simple mode parameters.
• Pr.160 User group read selection can narrow down the displayed parameters to only the simple mode parameters. (In the
initial setting, all parameters are displayed.) Set Pr.160 User group read selection as required. (To change the parameter
setting, refer to page 139.)
6 D303
Multi-speed
setting (low speed)
0.01 Hz 10 Hz 0 to 590 Hz 7
5 s*9
7 F010 Acceleration time 0.1 s 0 to 3600 s Sets the acceleration time.
15 s*10
5 s*9
349
8
8 F011 Deceleration time 0.1 s 0 to 3600 s Sets the deceleration time.
15 s*10
*6
H000 Electronic thermal 0.01 A Inverter rated 0 to 500 A*6 Protects the motor from heat. Set the rated
9
C103 O/L relay 0.1 A*7 current *8
0 to 3600 A*7 motor current.
394
9
Operation mode Select the start and frequency command
79 D000 1 0 0 to 4, 6, 7 370
selection sources.
125 T022
Terminal 2
frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
Allows the frequency at the maximum
potentiometer setting (5 V in the initial setting)
156, 10
482
gain frequency to be changed.
Terminal 4 Allows the frequency at the maximum current
158,
126 T042 frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz input (20 mA in the initial setting) to be
482
gain frequency changed.
This function restricts the parameters that are
User group read
160 E440 1 0 0, 1, 9999 read by the operation panel and parameter 337
selection
unit.
0, 3003,
Selects the PM sensorless vector control and
PM parameter 3103, 8009,
998 E430 1 0 set the parameters that are required to drive a 224
initialization 8109, 9009,
PM motor.
9109
Changes parameter settings as a batch. The
target parameters include communication
1, 2, 10, 11,
Automatic parameters for the Mitsubishi Electric human
999 E431 1 9999 12, 13, 20, 333
parameter setting machine interface (GOT) connection and the
21, 9999
parameters for the rated frequency settings of
50/60 Hz.
*1 Initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower.
*2 Initial values for the FR-A820-00105(1.5K) to FR-A820-00250(3.7K), FR-A840-00052(1.5K) to FR-A840-00126(3.7K).
*3 Initial values for the FR-A820-00340(5.5K), FR-A820-00490(7.5K), FR-A840-00170(5.5K), FR-A840-00250(7.5K).
*4 Initial values for the FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-01800(55K).
*5 Initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) and higher.
*6 For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*7 For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
*8 The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the inverter rated current.
*9 The initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
*10 Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) and higher.
*11 The initial value in "FM" column is for the FM-type inverter that has terminal FM, and that in "CA" column is for the CA-type inverter that has
terminal CA.
4. BASIC OPERATION
4.4 Frequently-used parameters (simple mode parameters)
145
Parameters for the CC-Link IE Field Network communication (FR-A800-
GF)
Refer
Pr. Initial
Pr. Name Unit Range Application to
group value
page
0 to 8, 10 to 20, 22,
DO0 output 25 to 28, 30 to 36,
313 M410 1 9999
selection 38 to 57, 60, 61,
63, 64, 68, 70, 79,
80, 84 to 99, 100 to
108, 110 to 116,
DO1 output 120, 122, 125 to Assign signals to the remote registers RX10 450,
314 M411 1 9999
selection 128, 130 to 136, to RX12. 722
138, to 157, 160,
161, 163, 164,
168, 170, 179,
DO2 output 180, 184 to 199,
315 M412 1 9999 200 to 208, 300 to
selection
308, 9999
NOTE
• When Pr.160 in the FR-A800-GF is set to "9999", the parameters for the CC-Link IE Field Network communication, as well as
the simple mode parameters, are displayed.
• Use the operation panel (FR-DU08) to give a start command and a frequency command. (PU operation)
6
Operation panel (FR-DU08)
7
Turn until the target frequency " " (30.00 Hz) appears. The indication blinks for about five seconds.
While the indication is flashing, press to confirm the selection for the frequency. " " and " "are
displayed alternately. After about three seconds of alternate display, the monitor display goes back to " " (the
indication of a monitored value).
(If is not pressed during the flashing for about five seconds, the monitor display goes back to " " (0.00
Press or to start running. The frequency value on the monitor increases according to the setting of
Pr.7 Acceleration time, and " " (30.00 Hz) appears on the monitor.
(To change the set frequency, return to step 3. The previously set frequency appears.)
4. BASIC OPERATION
4.5 Basic operation procedure (PU operation)
147
5. Deceleration → stop
Press to stop. The frequency value on the monitor decreases according to the setting of Pr.8 Deceleration
time, the monitor displays " " (0.00 Hz), and the motor stops rotating.
NOTE
• To display the set frequency under PU operation mode or External/PU combined operation mode 1 (Pr.79 = "3"), press .
• can also be used like a potentiometer to perform inverter operation. (Refer to page 148.)
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.79 Operation mode selectionpage 370
• Set Pr.161 Frequency setting/key lock operation selection = "1" (setting dial potentiometer).
The following shows the procedure to change the frequency from 0 Hz to 60 Hz during operation.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
4. Start
Turn until " " appears. The value in the flashing indication is set as the value of a set frequency (The
NOTE
• If the indication changes from the blink of "60.00" to the display of "0.00", Pr.161 Frequency setting/key lock operation
selection may be set to a value other than "1".
• Simply turning enables frequency setting whether the inverter is running or at a stop.
• The newly-set frequency is saved as the set frequency in EEPROM after 10 seconds.
• With the setting dial, the frequency can go up to the setting value of Pr.1 Maximum frequency. Check the Pr.1 Maximum
frequency setting, and adjust the setting according to the application.
Parameters referred to
Pr.1 Maximum frequencypage 407
Pr.161 Frequency setting/key lock operation selectionpage 324
Inverter Speed 1
4
6
RH
ON
RM
ON
RL
The following shows the procedure to operate at a low speed (10 Hz).
7
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode. 8
2. Changing the operation mode
Set "4" in Pr.79. [PU] and [EXT] indicators are ON. (To change the setting, refer to page 142.)
9
3. Setting the frequency
Turn ON the low-speed switch (RL signal).
Acceleration time, and " " (10.00 Hz) appears on the monitor.
5. Deceleration → stop
Press to stop. The frequency value on the monitor decreases according to the setting of Pr.8 Deceleration
time, the monitor displays " " (0.00 Hz), and the motor stops rotating. Turn OFF the low-speed switch (RL
signal).
NOTE
• Initially, the high-speed switch (RH signal) is set to 60 Hz for the FM type inverter or 50 Hz for the CA type inverter. The middle-
speed switch (RM signal) is set to 30 Hz, and the low-speed switch (RL signal) is set to 10 Hz. (To change the settings, use
Pr.4, Pr.5, and Pr.6, respectively.)
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• Up to 15-speed switching operation can be performed.
Parameters referred to
Pr.4 to Pr.6 Multi-speed settingpage 391
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.79 Operation mode selectionpage 370
4. BASIC OPERATION
4.5 Basic operation procedure (PU operation)
149
4.5.4 Setting the frequency using an analog signal
(voltage input)
[Connection diagram] (The inverter supplies 5 V power to the frequency setting potentiometer via terminal 10.)
Inverter
Operation panel
(FR-DU08)
10
Frequency setting
2
potentiometer
5
Potentiometer
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
3. Start
5. Deceleration
Turn the frequency setting potentiometer counterclockwise slowly to full. The frequency value on the monitor
decreases according to the setting of Pr.8 Deceleration time, the monitor displays " " (0.00 Hz), and the
motor stops rotating. [FWD] or [REV] indicator blinks.
6. Stop
NOTE
• To change the frequency (60 Hz) at the maximum voltage input (initial value: 5 V), adjust Pr.125 Terminal 2 frequency setting
gain frequency.
• To change the frequency (0 Hz) at the minimum voltage input (initial value: 0 V), adjust the calibration parameter C2
Terminal 2 frequency setting bias frequency.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.79 Operation mode selectionpage 370
Pr.125 Terminal 2 frequency setting gain frequencypage 482
C2 (Pr.902) Terminal 2 frequency setting bias frequencypage 482
[Connection diagram] 4
Inverter
Operation panel
AU signal AU (FR-DU08) 5
SD
Current signal 4(+)
source
(4 to 20mADC) 5(-) 6
The following shows the procedure to operate at 60 Hz.
Operating procedure 7
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
8
2. Changing the operation mode
Set "4" in Pr.79. [PU] and [EXT] indicators are ON. (To change the setting, refer to page 139.)
4. Start
10
Press or . [FWD] or [REV] indicator blinks as no frequency command is given.
6. Deceleration
Input a current of 4 mA or less. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, the monitor displays " " (0.00 Hz), and the motor stops rotating. [FWD] or [REV] indicator
blinks.
7. Stop
NOTE
• Pr.184 AU terminal function selection must be set to "4 (initial value)" (AU signal).
• To change the frequency (60 Hz) at the maximum current input (initial value: 20 mA), adjust Pr.126 Terminal 4 frequency
setting gain frequency.
• To change the frequency (0 Hz) at the minimum current input (initial value: 4 mA), adjust the calibration parameter C5
Terminal 4 frequency setting bias frequency.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.79 Operation mode selectionpage 370
Pr.126 Terminal 4 frequency setting gain frequencypage 482
4. BASIC OPERATION
4.5 Basic operation procedure (PU operation)
151
Pr.184 AU terminal function selectionpage 496
C5 (Pr.904) Terminal 4 frequency setting bias frequencypage 482
Inverter
Operation panel
7
Forward rotation STF (FR-DU08)
start
Reverse rotation STR
Switch
start
SD 8
Turn until the target frequency " " (30.00 Hz) appears. The indication blinks for about five seconds.
While the indication is flashing, press to confirm the selection for the frequency. " " and " "are
displayed alternately. After about three seconds of alternate display, the monitor display goes back to " " (the
indication of a monitored value). (If is not pressed during the flashing for about five seconds, the monitor
display goes back to " " (0.00 Hz). In that case, turn again and set the frequency.)
4. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of Pr.8 Deceleration time, the monitor displays " " (0.00 Hz), and the motor stops rotating.
4. BASIC OPERATION
4.6 Basic operation procedure (External operation)
153
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF terminal function selection must be set to "60" (or Pr.179 STR terminal function selection must be set to "61")
(initial value).
• Setting Pr.79 Operation mode selection = "3" enables multi-speed operation.
• If on the operation panel is pressed during the External operation, the inverter stops and the PU stop warning is
activated (" " appears on the LCD display of the operation panel). To reset the PU stop warning, turn OFF the start switch
Parameters referred to
Pr.4 to Pr.6 Multi-speed settingpage 391, Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.178 STF terminal function selection, Pr.179 STR terminal function selectionpage 496
Pr.79 Operation mode selectionpage 370
[Connection diagram]
Speed 1
Output frequency (Hz)
The following shows the procedure to operate at a high speed (60 Hz).
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
4. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of Pr.8 Deceleration time, the monitor displays " " (0.00 Hz), and the motor stops rotating. [FWD] or [REV]
indicator turns OFF. Turn OFF the high-speed switch (RH signal).
10
Frequency setting
potentiometer
2
5
10
Potentiometer
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
2. Start
Turn ON the start switch (STF/STR signal). [FWD] or [REV] indicator blinks as no frequency command is given.
4. Deceleration
Turn the frequency setting potentiometer counterclockwise slowly to full. The frequency value on the monitor
decreases according to the setting of Pr.8 Deceleration time, the monitor displays " " (0.00 Hz), and the motor
stops rotating. [FWD] or [REV] indicator blinks.
5. Stop
Turn OFF the start switch (STF/STR signal). [FWD] or [REV] indicator turns OFF.
4. BASIC OPERATION
4.6 Basic operation procedure (External operation)
155
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF terminal function selection must be set to "60" (or Pr.179 STR terminal function selection must be set to "61")
(initial value).
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.178 STF terminal function selection, Pr.179 STR terminal function selectionpage 496
The following shows the procedure to change the frequency at 5 V from 60 Hz (initial value) to 50 Hz using a frequency setting
potentiometer for 0 to 5 VDC input. Set 50 Hz in Pr.125 so that the inverter outputs 50 Hz at 5 V input.
Operating procedure
1. Selecting the parameter
Press to confirm the selection. " " and " "are displayed alternately.
Press three times to select the monitor mode, and change the monitor item to the frequency.
4. Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in 4.6.3.)
The motor is operated at 50 Hz.
NOTE
• To change the frequency at the input of 0 V (minimum voltage), use the calibration parameter C2.
Initial value
60Hz
(50Hz)
Output frequency
(Hz)
Gain Pr.125
Bias
C2
(Pr.902)
0 100%
0 Frequency setting signal 5V
0 10V
C3(Pr.902) C4(Pr.903)
Parameters referred to
Pr.125 Terminal 2 frequency setting gain frequencypage 482 2
C2 (Pr.902) Terminal 2 frequency setting bias frequencypage 482
C4 (Pr.903) Terminal 2 frequency setting gainpage 482
Operating procedure
9
1. Turning ON the power of the inverter
The operation panel is in the monitor mode. 10
2. Selecting the input via terminal 4
Turn ON the Terminal 4 input selection (AU) signal. Input via terminal 4 to the inverter is enabled.
3. Start
Turn ON the start switch (STF/STR signal). [FWD] or [REV] indicator blinks as no frequency command is given.
5. Deceleration
Input a current of 4 mA or less. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, the monitor displays " " (0.00 Hz), and the motor stops rotating. [FWD] or [REV] indicator
blinks.
6. Stop
Turn OFF the start switch (STF/STR signal). [FWD] or [REV] indicator turns OFF.
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.184 AU terminal function selection must be set to "4 (initial value)" (AU signal).
4. BASIC OPERATION
4.6 Basic operation procedure (External operation)
157
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.184 AU terminal function selectionpage 496
The following shows the procedure to change the frequency at 20 mA from 60 Hz (initial value) to 50 Hz using a frequency
setting potentiometer for 4 to 20 mA input. Set 50 Hz in Pr.126 so that the inverter outputs 50 Hz at 20 mA input.
Operating procedure
1. Selecting the parameter
Press to confirm the selection. " " and " "are displayed alternately.
Press three times to select the monitor mode and to monitor a frequency.
4. Start
Turn ON the start switch (STF or STR) to apply a 20 mA current (refer to steps 3 and 4 in 4.6.5).
Operate at 50 Hz.
NOTE
• To change the frequency at the input of 4 mA (minimum current), use the calibration parameter C5.
Initial value
60Hz
(50Hz)
Output frequency
(Hz)
Gain Pr.126
Bias
C5
(Pr.904)
0 20 100%
0 4 20mA
0 1 Frequency setting signal 5V
0 2 10V
C6(Pr.904) C7(Pr.905)
• Other adjustment methods for the frequency setting current gain are the following: adjustment by applying a current through
terminals 4 and 5, and adjustment using a specified point without applying a current through terminals 4 and 5. (Refer to page
482.)
Parameters referred to
Pr.126 Terminal 4 frequency setting gain frequencypage 482
C5 (Pr.904) Terminal 4 frequency setting bias frequencypage 482
C7 (Pr.905) Terminal 4 frequency setting gainpage 482
[Connection diagram] 5
Inverter
Switch
SD 7
The following shows the procedure to operate at 5 Hz.
Operating procedure
8
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
9
2. Turning ON the JOG signal
Turn ON the JOG switch (JOG signal). The inverter is set ready for the JOG operation.
4. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency decreases according to the setting of Pr.16 Jog
acceleration/deceleration time. " " (0.00 Hz) appears on the LCD display, and the motor stops rotating.
[FWD] or [REV] indicator turns OFF. Turn OFF the JOG switch (JOG signal).
NOTE
• To change the running frequency, change the setting of Pr.15 Jog frequency (initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of Pr.16 Jog acceleration/deceleration time (initial value:
0.5 seconds).
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration timepage 390
Pr.79 Operation mode selectionpage 370
4. BASIC OPERATION
4.7 Basic operation procedure (JOG operation)
159
4.7.2 Giving a start command from the operation panel
for JOG operation
Operation panel
(FR-DU08)
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Press twice to choose the PUJOG operation mode. The display shows " ", and [PU] indicator is ON.
Hold or down to keep the JOG operation. The frequency increases according to the setting of Pr.16
Jog acceleration/deceleration time, and " " (5.00 Hz) appears on the LCD display.
4. Deceleration → stop
Release or . The frequency decreases according to the setting of Pr.16 Jog acceleration/
deceleration time. " " (0.00 Hz) appears on the LCD display, and the motor stops rotating.
NOTE
• To change the running frequency, change the setting of Pr.15 Jog frequency (initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of Pr.16 Jog acceleration/deceleration time (initial value:
0.5 seconds).
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration timepage 390
161
5 PARAMETERS
This chapter explains the function setting for use of this product.
Always read the instructions before use.
The following marks are used to indicate the controls. (Parameters without any mark are valid for all the controls.)
Mark Control method Applied motor
V/F V/F control
Magnetic flux Advanced magnetic flux vector control Three-phase induction motor
Sensorless Real sensorless vector control
Vector Vector control Three-phase induction motor, PM motor
PM PM sensorless vector control PM motor
The setting range and the initial value of parameters differ depending on the structure or functions of the inverter. The following
common designations are used for each type of the inverter models.
Inverter model Common designation
FR-A8[]0 Standard model
FR-A8[]2 Separated converter type
FR-A8[]6 IP55 compatible model
NOTE
• Simple indicates simple mode parameters. Use Pr.160 User group read selection to indicate the simple mode parameters
only (initial setting is to indicate the extended mode parameters).
• The changing of the parameter settings may be restricted in some operating statuses. Use Pr.77 Parameter write selection
to change the setting of the restriction.
• Refer to page 824 for instruction codes for communication and availability of Parameter clear, all clear, and Parameter copy.
162 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr.
group
Name Setting range setting
increments FM CA page setting 1
6% *1
4% *1
0 G000 Torque boost Simple 0 to 30% 0.1% 3%*1 672
2
2%*1
1%*1
Maximum 120 Hz*2
3
1 H400 0 to 120 Hz 0.01 Hz 407
frequency Simple 60 Hz*3
Minimum
2 H401
frequency Simple
0 to 120 Hz 0.01 Hz 0 Hz 407 4
3 G001 Base frequency Simple 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 673
Basic function
6 D303
Multi-speed setting (low
0 to 590 Hz 0.01 Hz 10 Hz 391 6
speed) Simple
5 s*4
7 F010 Acceleration time Simple 0 to 3600 s 0.1 s 349
15 s*5
7
5 s*4
8 F011 Deceleration time Simple 0 to 3600 s 0.1 s 349
15 s*5
H000
Electronic thermal O/L
relay Simple
0 to 500 A*2 0.01 A*2
Inverter 394, 509,
8
9
C103 Rated motor 0 to 3600 A*3 0.1 A*3 rated current 519
current Simple
10 G100
DC injection brake
0 to 120 Hz, 9999 0.01 Hz 3 Hz 681 9
DC injection brake
operation frequency
DC injection brake
11 G101 0 to 10 s, 8888 0.1 s 0.5 s 681
operation time
4%*6 10
DC injection brake
12 G110
operation voltage
0 to 30% 0.1% 2%*6 681
*6
1%
— 13 F102 Starting frequency 0 to 60 Hz 0.01 Hz 0.5 Hz 363, 364
— 14 G003 Load pattern selection 0 to 5, 12 to 15 1 0 674
15 D200 Jog frequency 0 to 590 Hz 0.01 Hz 5 Hz 390
JOG operation
Jog acceleration/
16 F002 0 to 3600 s 0.1 s 0.5 s 390
deceleration time
Acceleration/deceleration
21 F001 0, 1 1 0 349
time increments
5. PARAMETERS
5.1 Parameter list
163
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Stall prevention operation
Stall prevention
24 D304
setting
Multi-speed setting (4
to to 0 to 590 Hz, 9999 0.01 Hz 9999 391
speed to 7 speed)
27 D307
Multi-speed input
— 28 D300 0, 1 1 0 391
compensation selection
Acceleration/deceleration
— 29 F100 0 to 6 1 0 354
pattern selection
0 to 2, 10, 11, 20,
21, 100 to 102, 110, 1 0
111, 120, 121*11
Regenerative function 2, 10, 11, 102,
— 30 E300 689
selection 1 10
110, 111*12
0, 2, 10, 20, 100, 102,
1 0
110, 120*13
31 H420 Frequency jump 1A 0 to 590 Hz, 9999 0.01 Hz 9999 408
Frequency jump
Output frequency
42 M442 0 to 590 Hz 0.01 Hz 6 Hz 461
detection
Output frequency
43 M443 detection for reverse 0 to 590 Hz, 9999 0.01 Hz 9999 461
rotation
Second acceleration/
44 F020 0 to 3600 s 0.1 s 5s 349, 590
deceleration time
45 F021 Second deceleration time 0 to 3600 s, 9999 0.1 s 9999 349, 590
46 G010 Second torque boost 0 to 30%, 9999 0.1% 9999 672
Second V/F (base
47 G011 0 to 590 Hz, 9999 0.01 Hz 9999 673
Second function
frequency)
Second stall prevention
48 H600 0 to 400% 0.1% 150% 409
operation level
Second stall prevention
49 H601 0 to 590 Hz, 9999 0.01 Hz 0 Hz 409
operation frequency
Second output frequency
50 M444 0 to 590 Hz 0.01 Hz 30 Hz 461
detection
Second electronic thermal 0 to 500 A, 9999 *2 0.01 A*2
H010 O/L relay 394, 509,
51 9999
C203 Rated second motor 0 to 3600 A, 9999 *3 0.1 A*3 519
current
164 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
0, 5 to 14, 17 to 20, 22
Operation panel main to 36, 38 to 46, 50 to 57,
52 M100 1 0 424
monitor selection 61, 62, 64, 67, 71 to 75,
87 to 98, 100 2
Monitoring function
5
58 A703 Restart cushion time 0 to 60 s 0.1 s 1s 597
6
— 59 F101 Remote function selection 0 to 3, 11 to 13 1 0 359
Energy saving control
— 60 G030 0, 4, 9 1 0 678
selection 7
0 to 500 A, 9999 *2 0.01 A*2
acceleration/deceleration
64 F520
Starting frequency for
0 to 10 Hz, 9999 0.01 Hz 9999 368
9
elevator mode
— 65 H300 Retry selection 0 to 5 1 0 405
— 66 H611
Stall prevention operation
reduction starting 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 409
10
frequency
Number of retries at fault
67 H301 0 to 10, 101 to 110 1 0 405
occurrence
Retry
0 to 6, 13 to 16, 20,
23, 24, 30, 33, 34, 40,
43, 44, 50, 53, 54, 70, 505, 509,
— 71 C100 Applied motor 1 0
73, 74, 330, 333, 334, 519
8090, 8093, 8094,
9090, 9093, 9094
0 to 15*2
— 72 E600 PWM frequency selection 1 2 339
0 to 6, 25*3
— 73 T000 Analog input selection 0 to 7, 10 to 17 1 1 473, 478
— 74 T002 Input filter time constant 0 to 8 1 1 480
Reset selection/ 0 to 3, 14 to 17*2
disconnected PU
— 0 to 3, 14 to 17, 100 to 14
detection/PU stop
selection 103, 114 to 117*3
E100 Reset selection 1
— 75 Disconnected PU 0 320
E101 0, 1
detection
E102 PUStop selection 1
*2
0
E107 Reset limit 1 0
0, 1*3
5. PARAMETERS
5.1 Parameter list
165
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Fault code output
— 76 M510 0 to 2 1 0 469
selection
— 77 E400 Parameter write selection 0 to 2 1 0 328
Reverse rotation
— 78 D020 0 to 2 1 0 386
prevention selection
Operation mode
— 79 D000 0 to 4, 6, 7 1 0 370, 378
selection Simple
0.4 to 55 kW, 9999*2 0.01 kW*2 215, 509,
80 C101 Motor capacity 9999
0 to 3600 kW, 9999 *3
0.1 kW *3 519
215, 509,
81 C102 Number of motor poles 2, 4, 6, 8, 10, 12, 9999 1 9999
519
0 to 500 A, 9999*2 0.01 A*2
82 C125 Motor excitation current 9999 509
*3
0 to 3600 A, 9999 0.1 A*3
200 V*7 215, 509,
83 C104 Rated motor voltage 0 to 1000 V 0.1 V
400 V*8 519
215, 509,
84 C105 Rated motor frequency 10 to 400 Hz, 9999 0.01 Hz 9999
519
Excitation current break
85 G201 0 to 400 Hz, 9999 0.01 Hz 9999 677
point
Excitation current low
86 G202 0 to 300%, 9999 0.1% 9999 677
speed scaling factor
Motor constant
166 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Third acceleration/
110 F030 0 to 3600 s, 9999 0.1 s 9999 349
deceleration time
111 F031 Third deceleration time 0 to 3600 s, 9999 0.1 s 9999 349
2
Third function
112 G020 Third torque boost 0 to 30%, 9999 0.1% 9999 672
113 G021 Third V/F (base frequency) 0 to 590 Hz, 9999 0.01 Hz 9999 673
Third stall prevention
114 H602 0 to 400% 0.1% 150% 409
operation level
Third stall prevention
3
115 H603 0 to 590 Hz 0.01 Hz 0 Hz 409
operation frequency
Third output frequency
116 M445 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 461
detection 4
PU communication station
117 N020 0 to 31 1 0 636
number
48, 96, 192, 384, 576,
118 N021 PU communication speed 1 192 636
768, 1152 5
PU communication stop bit
— 0, 1, 10, 11 1
PU—connector communication
124 N028
PU communication CR/LF
selection
0 to 2 1 1 636 9
Terminal 2 frequency
— 125 T022 setting gain 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 482
frequency Simple
10
Terminal 4 frequency
— 126 T042 setting gain 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 482
frequency Simple
PID control automatic
127 A612 0 to 590 Hz, 9999 0.01 Hz 9999 570
switchover frequency
0, 10, 11, 20, 21, 40 to
43, 50, 51, 60, 61, 70,
71, 80, 81, 90, 91, 100,
128 A610 PID action selection 1 0 570, 590
PID operation
5. PARAMETERS
5.1 Parameter list
167
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Backlash acceleration
140 F200 0 to 590 Hz 0.01 Hz 1 Hz 354
Backlash measure
stopping frequency
Backlash acceleration
141 F201 0 to 360 s 0.1 s 0.5 s 354
stopping time
Backlash deceleration
142 F202 0 to 590 Hz 0.01 Hz 1 Hz 354
stopping frequency
Backlash deceleration
143 F203 0 to 360 s 0.1 s 0.5 s 354
stopping time
0, 2, 4, 6, 8, 10, 12, 102,
— 144 M002 Speed setting switchover 1 4 422
104, 106, 108, 110, 112
PU display language
PU
606
failure selection
First cushion time for
163 A704 0 to 20 s 0.1 s 0s 597
restart
First cushion voltage for
164 A705 0 to 100% 0.1% 0% 597
restart
Stall prevention operation
165 A710 0 to 400% 0.1% 150% 597
level for restart
Output current detection
Current detection
168 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
E000
— 168
E080
Parameter for manufacturer setting. Do not set.
— 169
E001
E081
2
170 M020 Watt-hour meter clear 0, 10, 9999 1 9999 424
Cumulative
monitor
RL terminal function
180 T702 1 0 496
selection
RM terminal function
181 T703 1 1 496
selection 8
RH terminal function
182 T704 1 2 496
selection
RT terminal function
183 T705 1 3 496
selection 9
AU terminal function 0 to 20, 22 to 28, 37, 42
184 T706 1 4 496
selection to 48, 50 to 53, 57 to 59,
JOG terminal function 62, 64 to 74, 76 to 80,
185 T707
selection 85, 87 to 89, 92 to 96, 1
9999
5 496
10
CS terminal function
186 T708 1 6 496
selection
MRS terminal function 24*11*13
187 T709 1 496
selection 10*12
STOP terminal function
188 T710 1 25 496
selection
RES terminal function
189 T711 1 62 496
selection
5. PARAMETERS
5.1 Parameter list
169
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
0 to 8, 10 to 20, 22,
25 to 28, 30 to 20, 36,
ABC1 terminal function 38 to 57, 60, 61, 63, 64, 1
195 M405 99 450
selection 67, 68, 70, 79, 80, 84,
85, 90, 91, 94 to 99,
100 to 108, 110 to 116,
120, 122, 125 to 128,
130 to 136, 138 to 157,
160, 161, 163, 164,
167, 168, 170, 179,
ABC2 terminal function 180, 184, 185, 190,
196 M406 191, 194 to 199, 200 to 1 9999 450
selection
208, 211 to 213, 300 to
308, 311 to 313, 9999
Multi-speed
setting
Soft-PWM operation
— 240 E601 0, 1 1 1 339
selection
Analog input display unit
— 241 M043 0, 1 1 0 482
switchover
Terminal 1 added
— 242 T021 compensation amount 0 to 100% 0.1% 100% 478
(terminal 2)
Terminal 1 added
— 243 T041 compensation amount 0 to 100% 0.1% 75% 478
(terminal 4)
Cooling fan operation
— 244 H100 0, 1, 101 to 105 1 1 402
selection
245 G203 Rated slip 0 to 50%, 9999 0.01% 9999 700
compensation
170 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
252 T050 Override bias 0 to 200% 0.1% 50% 478
compensation
Frequency
deceleration start
Subtraction starting
7
263 A732 0 to 590 Hz, 9999 0.01 Hz 60 Hz 50 Hz 610
frequency
Power-failure deceleration
264 A733 0 to 3600 s 0.1 s 5s 610
time 1
Power-failure deceleration
8
265 A734 0 to 3600 s, 9999 0.1 s 9999 610
time 2
Power failure deceleration
266 A735 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 610
time switchover frequency 9
— 267 T001 Terminal 4 input selection 0 to 2 1 0 473
Monitor decimal digits
— 268 M022 0, 1, 9999 1 9999 424
selection
— 269 E023 Parameter for manufacturer setting. Do not set. 10
Stop-on contact/load
torque high- speed
— 270 A200 0 to 3, 11, 13 1 0 546, 549
frequency control
selection
High-speed setting
Stop-on-contact Load torque high speed
Middle-speed setting
272 A202 0 to 400% 0.1% 100% 549
minimum current
273 A203 Current averaging range 0 to 590 Hz, 9999 0.01 Hz 9999 549
factor
0 to 9, 9999*2
PWM carrier frequency at
276 A206 1 9999 546
stop-on contact 0 to 4, 9999*3
5. PARAMETERS
5.1 Parameter list
171
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
278 A100 Brake opening frequency 0 to 30 Hz 0.01 Hz 3 Hz 541
279 A101 Brake opening current 0 to 400% 0.1% 130% 541
Brake opening current
280 A102 0 to 2 s 0.1 s 0.3 s 541
detection time
Brake operation time at
281 A103 0 to 5 s 0.1 s 0.3 s 541
Brake sequence
start
282 A104 Brake operation frequency 0 to 30 Hz 0.01 Hz 6 Hz 541
Brake operation time at
283 A105 0 to 5 s 0.1 s 0.3 s 541
stop
Deceleration detection
284 A106 0, 1 1 0 541
function selection
Overspeed detection
A107
frequency 259, 541,
285 0 to 30 Hz, 9999 0.01 Hz 9999
Speed deviation excess 700
H416
detection frequency
286 G400 Droop gain 0 to 100% 0.1% 0% 702
Droop control
172 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
313*17 M410 DO0 output selection
0 to 8, 10 to 20, 22, 25
1 9999 450
to 28, 30 to 36, 38 to 57,
314*17 M411 DO1 output selection
60, 61, 63, 64, 68, 70,
1 9999 450
2
*17 79, 80, 84 to 99, 100 to
315 M412 DO2 output selection 1 9999 450
108, 110 to 116, 120,
122, 125 to 128, 130 to
316*16 M413 DO3 output selection 1 9999 450
136, 138 to 157, 160,
161, 163, 164, 168,
3
317*16 M414 DO4 output selection 1 9999 450
CC-Link IE
333 N032
RS-485 communication
0, 1 1 0 636
8
data length
RS-485 communication
N033 0, 1 1 1
stop bit length
RS-485 communication 9
RS-485 communication
5. PARAMETERS
5.1 Parameter list
173
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Stop position command
350*9 A510
selection
0, 1, 9999 1 9999 554
command
Orientation in-position
357*9 A532
zone
0 to 255 1 5 554
174 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
*9 A525 Orientation selection 0 to 2, 10 to 12 1 0 554
393
Number of machine side
394*9 A540 0 to 32767 1 1 554
gear teeth
2
Orientation control
mode setting
Pre-scale function
416 A802 0 to 5 1 0 614
selection
417 A803 Pre-scale setting value 0 to 32767 1 1 614
Position command source 0 to 2, 10, 100, 110, 7
419 B000 1 0 288, 304
selection 1110
Command pulse scaling
factor numerator
420 B001
(electronic gear
1 to 32767 1 1 309 8
numerator)
Command pulse
multiplication denominator
421 B002
(electronic gear
1 to 32767 1 1 309 9
denominator)
422 B003 Position control gain 0 to 150 s-1 1 s-1 25 s-1 312
Position control
434*17 N110
IE)
0 to 255 1 0 665
5. PARAMETERS
5.1 Parameter list
175
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
0, 1, 3 to 6, 13 to 16, 20,
23, 24, 30, 33, 34, 40,
43, 44, 50, 53, 54, 70,
450 C200 Second applied motor 73, 74, 330, 333, 334, 1 9999 505
8090, 8093, 8094,
9090, 9093, 9094,
9999
0 to 6, 10 to 14, 20,
Second motor control
451 G300 100 to 106, 110 to 114, 1 9999 215
method selection
9999
0.4 to 55 kW, 9999*2 0.01 kW*2
453 C201 Second motor capacity 9999 509, 519
0 to 3600 kW, 9999*3 0.1 kW*3
Number of second motor
454 C202 2, 4, 6, 8, 10, 12, 9999 1 9999 509, 519
poles
0 to 500 A, 9999*2 0.01 A*2
Second motor constant
0.1%*2
462 C224 Second motor constant (X) 0 to 100%, 9999 9999 509
0.01%*3
Second motor auto tuning 509, 519,
463 C210 0, 1, 11, 101 1 0
setting/status 606
176 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Digital position control
464 B020 sudden stop deceleration 0 to 360 s 0.1 s 0s 288
time
465 B021
First target position lower
0 to 9999 1 0 288
2
4 digits
First target position upper
466 B022 0 to 9999 1 0 288
4 digits
467 B023
Second target position
0 to 9999 1 0 288
3
lower 4 digits
Second target position
468 B024 0 to 9999 1 0 288
upper 4 digits
Third target position lower
4
469 B025 0 to 9999 1 0 288
4 digits
Third target position upper
470 B026 0 to 9999 1 0 288
4 digits
Fourth target position
5
471 B027 0 to 9999 1 0 288
lower 4 digits
Fourth target position
472 B028 0 to 9999 1 0 288
upper 4 digits
Fifth target position lower
6
473 B029 0 to 9999 1 0 288
4 digits
Fifth target position upper
474 B030 0 to 9999 1 0 288
4 digits 7
Sixth target position lower
475 B031 0 to 9999 1 0 288
4 digits
Sixth target position upper
476 B032
4 digits
0 to 9999 1 0 288
8
Seventh target position
Simple position control
5. PARAMETERS
5.1 Parameter list
177
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
495 M500 Remote output selection 0, 1, 10, 11 1 0 466
Remote
output
Communication error
— 501*17 N012
occurrence count display
0 1 0 630
Maintenance timer 1
504 E711 0, 9998, 9999 1 9999 345
warning output set time
S-pattern time at a
519 F403 0.1 to 2.5 s 0.1 s 0.1 s 354
completion of deceleration
— 522 G105 Output stop frequency 0 to 590 Hz, 9999 0.01 Hz 9999 686
MODBUS RTU
— 539 N002 communication check time 0 to 999.8 s, 9999 0.1 s 9999 652
interval
Frequency command sign
— 541*17 N100
selection
0, 1 1 0 665
USB communication
547 N040 0 to 31 1 0 666
station number
USB
PU mode operation
551 D013 1 to 3, 9999 1 9999 380
command source selection
— 552 H429 Frequency jump range 0 to 30 Hz, 9999 0.01 Hz 9999 408
553 A603 PID deviation limit 0 to 100%, 9999 0.1% 9999 570
PID control
*2 A*2
0 to 500 A 0.01
Current average value
Inverter rated
557 E722 monitor signal output 346
0 to 3600 A*3 0.1 A*3 current
reference current
178 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Operating time carrying-
— 564 M031 (0 to 65535) 1 0 424
over times
Second motor excitation
— 565 G301
current break point
0 to 400 Hz, 9999 0.01 Hz 9999 677 2
Second motor excitation
— 566 G302 current low-speed scaling 0 to 300%, 9999 0.1% 9999 677
factor
3
Second monitor
constant
0 to 3*11*12
Multiple rating
5
570 E301 Multiple rating setting 1 2 326
1, 2*13
— 574 C211
Second motor online auto
0 to 2 1 0 527
7
tuning
Output interruption
575 A621 0 to 3600 s, 9999 0.1 s 1s 570
detection time
PID control
576 A622
Output interruption
0 to 590 Hz 0.01 Hz 0 Hz 570
8
detection level
Output interruption cancel
577 A623 900 to 1100% 0.1% 1000% 570
level
592 A300
Traverse function
0 to 2 1 0 551
9
selection
Maximum amplitude
593 A301 0 to 25% 0.1% 10% 551
amount
Amplitude compensation
10
594 A302 amount during 0 to 50% 0.1% 10% 551
Traverse
deceleration
Amplitude compensation
595 A303 amount during 0 to 50% 0.1% 10% 551
acceleration
Amplitude acceleration
596 A304 0.1 to 3600 s 0.1 s 5s 551
time
Amplitude deceleration
597 A305 0.1 to 3600 s 0.1 s 5s 551
time
175 to 215 VDC*7/350
— 598 H102 Undervoltage level 0.1 V 9999 403
to 430 VDC*8, 9999
X10 terminal input 0*11*13
— 599 T721 0, 1 1 689
selection 1*12
First free thermal
600 H001 0 to 590 Hz, 9999 0.01 Hz 9999 394
reduction frequency 1
Electronic thermal
5. PARAMETERS
5.1 Parameter list
179
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Second motor permissible
— 608 H016 110 to 250%, 9999 1% 9999 394
load level
PID set point/deviation
PID control
635*9 M610
signal selection
0 to 3 1 0 306
selection
output
656 M531 Analog remote output 1 800 to 1200% 0.1% 1000% 467
657 M532 Analog remote output 2 800 to 1200% 0.1% 1000% 467
658 M533 Analog remote output 3 800 to 1200% 0.1% 1000% 467
659 M534 Analog remote output 4 800 to 1200% 0.1% 1000% 467
180 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Increased magnetic
excitation deceleration
Increased magnetic
661 G131
Magnetic excitation
0 to 40%, 9999 0.1% 9999 699
2
increase rate
Increased magnetic
662 G132
excitation current level
0 to 300% 0.1% 100% 699
3
Control circuit temperature
— 663 M060 0 to 100°C 1°C 0°C 471
signal output level
— 665 G125
Regeneration avoidance
0 to 200% 0.1% 100% 696
4
frequency gain
Power failure stop
— 668 A786 0 to 200% 0.1% 100% 610
frequency gain
SF-PR slip amount 5
— 673 G060 adjustment operation 2 to 4, 6, 9999 1 9999 680
selection
SF-PR slip amount
— 674 G061
adjustment gain
0 to 500% 0.1% 100% 680
6
679 G420 Second droop gain 0 to 100%, 9999 0.1% 9999 702
Second droop filter time
680 G421 0 to 1 s, 9999 0.01 s 9999 702
constant
Second droop
686 E712
switchover
Maintenance timer 2 0 (1 to 9998) 1 0 345
9
Maintenance
Maintenance timer 2
687 E713 0 to 9998, 9999 1 9999 345
warning output set time
688 E714 Maintenance timer 3 0 (1 to 9998) 1 0 345 10
Maintenance timer 3
689 E715 0 to 9998, 9999 1 9999 345
warning output set time
— 690 H881 Deceleration check time 0 to 3600 s, 9999 0.1 s 1s 259
Second free thermal
692 H011 0 to 590 Hz, 9999 0.01 Hz 9999 394
reduction frequency 1
Electronic thermal
5. PARAMETERS
5.1 Parameter list
181
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
702 C106 Maximum motor frequency 0 to 400 Hz, 9999 0.01 Hz 9999 519
Induced voltage constant 0 to 5000 mV (rad/s), 0.1 mV
706 C130 9999 519
(phi f) 9999 (rad/s)
707 C107 Motor inertia (integer) 10 to 999, 9999 1 9999 519
711 C131 Motor Ld decay ratio 0 to 100%, 9999 0.1% 9999 519
712 C132 Motor Lq decay ratio 0 to 100%, 9999 0.1% 9999 519
Starting resistance tuning
717 C182 0 to 200%, 9999 0.1% 9999 519
compensation
Starting magnetic pole 0 to 6000 μs,
721 C185 position detection pulse 10000 to 16000 μs, 1μs 9999 519
width 9999
724 C108 Motor inertia (exponent) 0 to 7, 9999 1 9999 519
Motor protection current
725 C133 100 to 500%, 9999 0.1% 9999 519
level
Motor constant
754 A652 automatic switchover 0 to 590 Hz, 9999 0.01 Hz 9999 570
frequency
Second PID action set
755 A651 0 to 100%, 9999 0.01% 9999 570
point
Second PID proportional
756 A653 0.1 to 1000%, 9999 0.1% 100% 570
band
757 A654 Second PID integral time 0.1 to 3600 s, 9999 0.1 s 1s 570
Second PID differential
758 A655 0.01 to 10 s, 9999 0.01 s 9999 570
time
759 A600 PID unit selection 0 to 43, 9999 1 9999 584
182 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
760 A616 Pre-charge fault selection 0, 1 1 0 587
761 A617 Pre-charge ending level 0 to 100%, 9999 0.1% 9999 587
762 A618 Pre-charge ending time
Pre-charge upper
0 to 3600 s, 9999 0.1 s 9999 587
2
763 A619 0 to 100%, 9999 0.1% 9999 587
detection level
764 A620 Pre-charge time limit 0 to 3600 s, 9999 0.1 s 9999 587
PID Pre-charge
765 A656
Second pre-charge fault
selection
0, 1 1 0 587 3
Second pre-charge ending
766 A657 0 to 100%, 9999 0.1% 9999 587
level
767 A658
Second pre-charge ending
0 to 3600 s, 9999 0.1 s 9999 587 4
time
Second pre-charge upper
768 A659 0 to 100%, 9999 0.1% 9999 587
detection level
769 A660
Second pre-charge time
0 to 3600 s, 9999 0.1 s 9999 587
5
limit
Operation panel monitor
774 M101 1 9999 424
selection 1
Monitoring
1 to 3, 5 to 14, 17 to 20,
775 M102
Operation panel monitor 22 to 36, 38 to 46, 50 to
1 9999 424
6
selection 2 57, 61, 62, 64, 67, 71 to
Operation panel monitor 75, 87 to 98, 100, 9999
776 M103 1 9999 424
selection 3
A681 4 mA input fault operation 7
— 777 0 to 590 Hz, 9999 0.01 Hz 9999 492
T053 frequency
A682
— 778 4 mA input check filter 0 to 10 s 0.01 s 0s 492
T054 8
Operation frequency
— 779 N014 during communication 0 to 590 Hz, 9999 0.01 Hz 9999 630
error
— 788 G250
Low speed range torque
characteristic selection
0, 9999 1 9999 227 9
Acceleration time in low-
— 791 F070 0 to 3600 s, 9999 0.1 s 9999 349
speed range
— 792 F071
Deceleration time in low-
0 to 3600 s, 9999 0.1 s 9999 349
10
speed range
Pulse increment setting for 0.1, 1, 10, 100, 1000
— 799 M520 0.1 kWh 1 kWh 470
output power kWh
0 to 6, 9 to 14, 20,
— 800 G200 Control method selection 1 20 215
100 to 106, 109 to 114
— 801 H704 Output limit level 0 to 400%, 9999 0.1% 9999 235, 270
— 802 G102 Pre-excitation selection 0, 1 1 0 681
Constant output range
803 G210 torque characteristic 0 to 2, 10, 11 1 0 235, 270
Torque command
selection
Torque command source
804 D400 0 to 6 1 0 270
selection
Torque command value
805 D401 600 to 1400% 1% 1000% 270
(RAM)
Torque command value
806 D402 600 to 1400% 1% 1000% 270
(RAM, EEPROM)
807 H410 Speed limit selection 0 to 2 1 0 274
Speed limit
5. PARAMETERS
5.1 Parameter list
183
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Torque limit input method
810 H700 0 to 2 1 0 235
selection
811 D030 Set resolution switchover 0, 1, 10, 11 1 0 235, 422
Torque limit level
812 H701 0 to 400%, 9999 0.1% 9999 235
(regeneration)
Torque limit
level setting
184 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Analog input offset
849 T007 0 to 200% 0.1% 100% 480
adjustment
850 G103 Brake operation selection 0 to 2 1 0 681
Control terminal option- 2
851*9 C240
Number of encoder pulses
0 to 4096 1 2048 93
Torque monitoring
866 M042 0 to 400% 0.1% 150% 435
reference
protection selection
function
5. PARAMETERS
5.1 Parameter list
185
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Regeneration avoidance
882 G120 0 to 2 1 0 696
operation selection
Regeneration avoidance
186 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
C0
M310 FM/CA terminal calibration — — — 440
(900)*10
C1
(901)*10
M320 AM terminal calibration — — — 440 2
C2 Terminal 2 frequency
T200 0 to 590 Hz 0.01 Hz 0 Hz 482
(902)*10 setting bias frequency
C3
T201
Terminal 2 frequency
0 to 300% 0.1% 0% 482
3
(902)*10 setting bias
125 Terminal 2 frequency
T202 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 482
(903)*10 setting gain frequency
C4 Terminal 2 frequency
4
T203 0 to 300% 0.1% 100% 482
(903)*10 setting gain
C5 Terminal 4 frequency
T400 0 to 590 Hz 0.01 Hz 0 Hz 482
(904)*10 setting bias frequency 5
C6 Terminal 4 frequency
T401 0 to 300% 0.1% 20% 482
(904)*10 setting bias
126
(905)*10
T402
Terminal 4 frequency
setting gain frequency
0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 482 6
C7 Terminal 4 frequency
T403 0 to 300% 0.1% 100% 482
(905)*10 setting gain
C12
T100
Terminal 1 bias frequency
0 to 590 Hz 0.01 Hz 0 Hz 482
7
(917)*10 (speed)
C13
Calibration parameter
5. PARAMETERS
5.1 Parameter list
187
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
C42
A630 PID display bias coefficient 0 to 500, 9999 0.01 9999 584
(934)*10
C43 PID display bias analog
PID display
0 to 3, 5 to 14, 17 to 20,
Operation panel setting
22 to 36, 38 to 46, 50 to
992 M104 dial push monitor 1 0 424
57, 61, 62, 64, 67, 71 to
selection
75, 87 to 98, 100
994 G403 Droop break point gain 0.1 to 100%, 9999 0.1% 9999 702
995 G404 Droop break point torque 0.1 to 100% 0.1% 100% 702
188 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
1020 A900 Trace operation selection 0 to 4 1 0 616
1021 A901 Trace mode selection 0 to 2 1 0 616
1022 A902 Sampling cycle
Number of analog
0 to 9 1 2 616
2
1023 A903 1 to 8 1 4 616
channels
1024 A904 Sampling auto start 0, 1 1 0 616
1025 A905 Trigger mode selection 0 to 4 1 0 616 3
Number of sampling
1026 A906 0 to 100% 1% 90% 616
before trigger
Analog source selection
1027 A910
(1ch)
201 616
4
Analog source selection
1028 A911 202 616
(2ch)
Analog source selection
1029 A912
(3ch) 1 to 3, 5 to 14, 17 to 20,
22 to 24, 32 to 36, 39 to
203 616
5
Analog source selection
1030 A913 42, 46, 52 to 54, 61, 62, 204 616
(4ch)
64, 67, 71 to 75, 87 to 1
Analog source selection
1031 A914
(5ch)
98, 201 to 213, 222 to
227, 230 to 232, 235 to
205 616 6
Analog source selection 238
1032 A915 206 616
(6ch)
Analog source selection
1033 A916
(7ch)
207 616 7
Trace
1038 A930
Digital source selection
(1ch)
1 616 9
Digital source selection
1039 A931 2 616
(2ch)
1040 A932
Digital source selection
3 616
10
(3ch)
Digital source selection
1041 A933 4 616
(4ch)
1 to 255 1
Digital source selection
1042 A934 5 616
(5ch)
Digital source selection
1043 A935 6 616
(6ch)
Digital source selection
1044 A936 7 616
(7ch)
Digital source selection
1045 A937 8 616
(8ch)
1046 A938 Digital trigger channel 1 to 8 1 1 616
Digital trigger operation
1047 A939 0, 1 1 0 616
selection
— 1048 E106 Display-off waiting time 0 to 60 min 1 min 0 323
— 1049 E110 USB host reset 0, 1 1 0 324
DC brake judgment time
1072 A310 for anti-sway control 0 to 10 s 0.1 s 3s 553
operation
Anti-sway control
Anti-sway control
5. PARAMETERS
5.1 Parameter list
189
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Deceleration time at
— 1103 F040 0 to 3600 s 0.1 s 5s 349
emergency stop
1106 M050 Torque monitor filter 0 to 5 s, 9999 0.01 s 9999 424
Monitoring
0 to 65535 1 0 614
1199 A859 parameters 1 to 50
Target position/speed
— 1220 B100 0 to 2 1 0 853
selection
190 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Start command edge
1221 B101 0, 1 1 0 288
detection selection
First positioning
1222 B120
acceleration time
0.01 to 360 s 0.01 s 5s 288 2
First positioning
1223 B121 0.01 to 360 s 0.01 s 5s 288
deceleration time
1224 B122 First positioning dwell time 0 to 20000 ms 1 ms 0 ms 288
First positioning sub- 0 to 2, 10 to 12, 100 to
3
1225 B123 1 10 288
function 102, 110 to 112
Second positioning
1226 B124 0.01 to 360 s 0.01 s 5s 288
acceleration time
Second positioning
4
1227 B125 0.01 to 360 s 0.01 s 5s 288
deceleration time
Second positioning dwell
1228 B126 0 to 20000 ms 1 ms 0 ms 288
time
Second positioning sub- 0 to 2, 10 to 12, 100 to
5
1229 B127 1 10 288
function 102, 110 to 112
Third positioning
1230 B128 0.01 to 360 s 0.01 s 5s 288
acceleration time 6
Third positioning
1231 B129 0.01 to 360 s 0.01 s 5s 288
deceleration time
Third positioning dwell
1232 B130
time
0 to 20000 ms 1 ms 0 ms 288
7
Third positioning sub- 0 to 2, 10 to 12, 100 to
1233 B131 1 10 288
function 102, 110 to 112
Fourth positioning
1234 B132
acceleration time
0.01 to 360 s 0.01 s 5s 288
8
Simple position control
Fourth positioning
1235 B133 0.01 to 360 s 0.01 s 5s 288
deceleration time
Fourth positioning dwell
1236 B134
time
0 to 20000 ms 1 ms 0 ms 288 9
Fourth positioning sub- 0 to 2, 10 to 12, 100 to
1237 B135 1 10 288
function 102, 110 to 112
1238 B136
Fifth positioning
acceleration time
0.01 to 360 s 0.01 s 5s 288 10
Fifth positioning
1239 B137 0.01 to 360 s 0.01 s 5s 288
deceleration time
1240 B138 Fifth positioning dwell time 0 to 20000 ms 1 ms 0 ms 288
Fifth positioning sub- 0 to 2, 10 to 12, 100 to
1241 B139 1 10 288
function 102, 110 to 112
Sixth positioning
1242 B140 0.01 to 360 s 0.01 s 5s 288
acceleration time
Sixth positioning
1243 B141 0.01 to 360 s 0.01 s 5s 288
deceleration time
Sixth positioning dwell
1244 B142 0 to 20000 ms 1 ms 0 ms 288
time
Sixth positioning sub- 0 to 2, 10 to 12, 100 to
1245 B143 1 10 288
function 102, 110 to 112
Seventh positioning
1246 B144 0.01 to 360 s 0.01 s 5s 288
acceleration time
Seventh positioning
1247 B145 0.01 to 360 s 0.01 s 5s 288
deceleration time
Seventh positioning dwell
1248 B146 0 to 20000 ms 1 ms 0 ms 288
time
Seventh positioning sub- 0 to 2, 10 to 12, 100 to
1249 B147 1 10 288
function 102, 110 to 112
Eighth positioning
1250 B148 0.01 to 360 s 0.01 s 5s 288
acceleration time
Eighth positioning
1251 B149 0.01 to 360 s 0.01 s 5s 288
deceleration time
Eighth positioning dwell
1252 B150 0 to 20000 ms 1 ms 0 ms 288
time
5. PARAMETERS
5.1 Parameter list
191
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Eighth positioning sub- 0 to 2, 10 to 12, 100 to
1253 B151 1 10 288
function 102, 110 to 112
Ninth positioning
1254 B152 0.01 to 360 s 0.01 s 5s 288
acceleration time
Ninth positioning
1255 B153 0.01 to 360 s 0.01 s 5s 288
deceleration time
Ninth positioning dwell
1256 B154 0 to 20000 ms 1 ms 0 ms 288
time
Ninth positioning sub- 0 to 2, 10 to 12, 100 to
1257 B155 1 10 288
function 102, 110 to 112
Tenth positioning
1258 B156 0.01 to 360 s 0.01 s 5s 288
acceleration time
Tenth positioning
1259 B157 0.01 to 360 s 0.01 s 5s 288
deceleration time
Tenth positioning dwell
1260 B158 0 to 20000 ms 1 ms 0 ms 288
time
Tenth positioning sub- 0 to 2, 10 to 12, 100 to
1261 B159 1 10 288
function 102, 110 to 112
Eleventh positioning
1262 B160 0.01 to 360 s 0.01 s 5s 288
acceleration time
Eleventh positioning
1263 B161 0.01 to 360 s 0.01 s 5s 288
deceleration time
Eleventh positioning dwell
1264 B162 0 to 20000 ms 1 ms 0 ms 288
time
Eleventh positioning sub- 0 to 2, 10 to 12, 100 to
1265 B163 1 10 288
function 102, 110 to 112
Twelfth positioning
1266 B164 0.01 to 360 s 0.01 s 5s 288
Simple position control
acceleration time
Twelfth positioning
1267 B165 0.01 to 360 s 0.01 s 5s 288
deceleration time
Twelfth positioning dwell
1268 B166 0 to 20000 ms 1 ms 0 ms 288
time
Twelfth positioning sub- 0 to 2, 10 to 12, 100 to
1269 B167 1 10 288
function 102, 110 to 112
Thirteenth positioning
1270 B168 0.01 to 360 s 0.01 s 5s 288
acceleration time
Thirteenth positioning
1271 B169 0.01 to 360 s 0.01 s 5s 288
deceleration time
Thirteenth positioning
1272 B170 0 to 20000 ms 1 ms 0 ms 288
dwell time
Thirteenth positioning 0 to 2, 10 to 12, 100 to
1273 B171 1 10 288
sub-function 102, 110 to 112
Fourteenth positioning
1274 B172 0.01 to 360 s 0.01 s 5s 288
acceleration time
Fourteenth positioning
1275 B173 0.01 to 360 s 0.01 s 5s 288
deceleration time
Fourteenth positioning
1276 B174 0 to 20000 ms 1 ms 0 ms 288
dwell time
Fourteenth positioning 0 to 2, 10 to 12, 100 to
1277 B175 1 10 288
sub- function 102, 110 to 112
Fifteenth positioning
1278 B176 0.01 to 360 s 0.01 s 5s 288
acceleration time
Fifteenth positioning
1279 B177 0.01 to 360 s 0.01 s 5s 288
deceleration time
Fifteenth positioning dwell
1280 B178 0 to 20000 ms 1 ms 0 ms 288
time
Fifteenth positioning sub- 0, 2, 10, 12, 100, 102,
1281 B179 1 10 288
function 110, 112
Home position return
1282 B180 0 to 6 1 4 288
method selection
Home position return
1283 B181 0 to 30 Hz 0.01 Hz 2 Hz 288
speed
192 5. PARAMETERS
5.1 Parameter list
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group
increments
FM CA page setting
1
Home position return
1284 B182 0 to 10 Hz 0.01 Hz 0.5 Hz 288
creep speed
Home position shift
1285 B183
amount lower 4 digits
0 to 9999 1 0 288 2
Home position shift
1286 B184 0 to 9999 1 0 288
amount upper 4 digits
Travel distance after
1287 B185 proximity dog ON lower 4 0 to 9999 1 2048 288 3
digits
Travel distance after
Simple position control
1290 B188
Home position return
stopper waiting time
0 to 10 s 0.1 s 0.5 s 288 5
Position control terminal
1292 B190 0, 1 1 0 288
input selection
1293 B191
Roll feeding mode
selection
0, 1 1 0 288 6
Position detection lower 4
1294 B192 0 to 9999 1 0 311
digits
1295 B193
Position detection upper 4
digits
0 to 9999 1 0 311 7
Position detection
1296 B194 0 to 2 1 0 311
selection
1297 B195
Position detection
0 to 32767 1 0 311 8
hysteresis width
Second position control
— 1298 B013
gain 0 to 150 s-1 1 s-1 25 s-1 312
— 1299 G108
Second pre-excitation
0, 1 1 0 681
9
selection
1300 to N500 to Communication option parameters.
—
1343 N543 For details, refer to the Instruction Manual of the option.
—
1348 G263 P/PI control switchover 0 Hz 0.01 Hz 0 to 400 Hz 244 10
frequency
1349 G264 Emergency stop operation 0 1 0, 1, 10, 11 349
—
selection
1350 to N550 to Communication option parameters.
—
1359 N559 For details, refer to the Instruction Manual of the option.
1410 A170 Starting times lower 4 0 to 9999 1 0 545
—
digits
1411 A171 Starting times upper 4 0 to 9999 1 0 545
—
digits
Motor induced voltage
— 1412 C135 0 to 2, 9999 1 9999 519
constant (phi f) exponent
Second motor induced
— 1413 C235 voltage constant (phi f) 0 to 2, 9999 1 9999 519
exponent
5. PARAMETERS
5.1 Parameter list
193
Minimum Initial value
Pr. Refer to Customer
Pr. Name Setting range setting
group FM CA page setting
increments
Load characteristics
1480 H520 0, 1 (2 to 5, 81 to 85) 1 0 417
measurement mode
Load characteristics load
1481 H521 0 to 400%, 8888, 9999 0.1% 9999 417
reference 1
Load characteristics load
1482 H522 0 to 400%, 8888, 9999 0.1% 9999 417
reference 2
Load characteristics load
1483 H523 0 to 400%, 8888, 9999 0.1% 9999 417
reference 3
Load characteristics fault detection
194 5. PARAMETERS
5.1 Parameter list
5.1.2 Use of a function group number for the 1
identification of parameters
A parameter identification number shown on the PU can be switched from a parameter number to a function group number.
2
As parameters are grouped by function and displayed by the group, the related parameters can be set continually at a time.
1
The parameter number is used for the identification of parameters, 4
and displayed in numerical order.
The function group number is used for the identification of
2
parameters, and displayed in alphanumeric order.
5
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode. 6
2. Selecting the parameter setting mode
Press to choose the parameter setting mode. (The parameter number read previously appears on the 12- 7
segment LCD display.)
3. Selecting a parameter
8
Turn until " " (Group parameter setting) appears.
Press to confirm the selection. The setting “ “(initial value) will appear.
9
4. Selecting the use of the function group number
Turn to change the set value to " " (function group number). Press to confirm the Group parameter 10
setting. " " and " " are displayed alternately after the setting is completed.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Press to choose the parameter setting mode. (The parameter number read previously appears on the 12-
segment LCD display.)
Press several times until " " appears. Parameter groups can now be selected.
5. PARAMETERS
5.1 Parameter list
195
5. Enabling the function group selection
Turn until " " (Protective function parameter 4) appears. Press to confirm the selection.
" " will appear, which shows that the operation panel is ready for selection of a number in the group
of Protective function parameter 4.
6. Selecting a parameter
Turn until " " (P.H400 Maximum frequency) appears. Press to display the present set
Turn to change the set value to " ". Press to confirm the selection. " " and
196 5. PARAMETERS
5.1 Parameter list
5.1.3 Parameter list (by function group number)
E: Environment setting Refer
1
Pr.
Pr. Name to
parameters group
page
Parameters for the inverter operating environment. E700 255 Life alarm status display
Inrush current limit circuit life
341
2
Refer E701 256*4 display
341
Pr.
Pr. Name to
group Control circuit capacitor life
page E702 257 341
Parameter for manufacturer setting. Do not
display 3
E000 168 Main circuit capacitor life
set. E703 258*4 display
341
Parameter for manufacturer setting. Do not
E001 169 Main circuit capacitor life
259*4
E020 1006
set.
Clock (year) 318
E704
measuring
341
4
E710 503 Maintenance timer 1 345
E021 1007 Clock (month, day) 318
Maintenance timer 1 warning
E022 1008 Clock (hour, minute) 318 E711 504 345
output set time
E023 269
Parameter for manufacturer setting. Do not E712 686 Maintenance timer 2 345 5
set.
Maintenance timer 2 warning
Parameter for manufacturer setting. Do not E713 687 345
E080 168 output set time
set.
E081 169
Parameter for manufacturer setting. Do not
E714 688 Maintenance timer 3
Maintenance timer 3 warning
345
6
set. E715 689 345
output set time
E100 75 Reset selection 320
E720 555 Current average time 346
E101 75 Disconnected PU detection 320
E102 75 PUStop selection 320
E721 556 Data output mask time 346 7
Current average value monitor
E103 145 PU display language selection 322 E722 557 346
signal output reference current
E104 990 PU buzzer control 322
E105 991 PU contrast adjustment 322
F: Parameters for the settings of 8
E106 1048 Display-off waiting time 323
E107 75 Reset limit 320 the acceleration/deceleration time
E108 1000 Direct setting selection 323 and the acceleration/deceleration 9
E110 1049 USB host reset 324
Frequency setting/key lock
pattern
E200 161 324
operation selection Parameters for the motor acceleration/deceleration
E201 295
Frequency change increment
amount setting
325 characteristics. 10
Regenerative function Refer
E300 30 689 Pr.
selection Pr. Name to
group
E301 570 Multiple rating setting 326 page
E302 977 Input voltage mode selection 327 Acceleration/deceleration
F000 20 349
reference frequency
E400 77 Parameter write selection 328
Acceleration/deceleration time
E410 296 Password lock level 331 F001 21 349
increments
E411 297 Password lock/unlock 331
Jog acceleration/deceleration
Parameter for manufacturer setting. Do not F002 16 390
E415 1499 time
set.
597,
E420 888 Free parameter 1 333 F003 611 Acceleration time at a restart
604
E421 889 Free parameter 2 333
F010 7 Acceleration time Simple 349
PM parameter
E430 998 224 F011 8 Deceleration time Simple 349
initialization Simple
Automatic parameter Second acceleration/ 349,
F020 44
E431 999 333 deceleration time 590
setting Simple
349,
User group read selection F021 45 Second deceleration time
E440 160 337 590
Simple Acceleration/deceleration time
F022 147 349
User group registered display/ switching frequency
E441 172 337
batch clear Third acceleration/
F030 110 349
E442 173 User group registration 337 deceleration time
E443 174 User group clear 337 F031 111 Third deceleration time 349
E490 989 Parameter copy alarm release 708 Deceleration time at
F040 1103 349
E600 72 PWM frequency selection 339 emergency stop
E601 240 Soft-PWM operation selection 339 Acceleration time in low-speed
F070 791 349
range
PWM frequency automatic
E602 260 339
switchover
5. PARAMETERS
5.1 Parameter list
197
Refer Pr. Refer
Pr. Pr. Name
Pr. Name to group to page
group
page PU mode operation command
D013 551 380
Deceleration time in low-speed source selection
F071 792 349
range Reverse rotation prevention
D020 78 386
Acceleration/deceleration selection
F100 29 354
pattern selection 235,
D030 811 Set resolution switchover
F101 59 Remote function selection 359 422
363, 386,
F102 13 Starting frequency D100 291 Pulse train I/O selection
364 435
F103 571 Holding time at a start 363 Input pulse division scaling
D101 384 386
Backlash acceleration factor
F200 140 354
stopping frequency D110 385 Frequency for zero input pulse 386
Backlash acceleration Frequency for maximum input
F201 141 354 D111 386 386
stopping time pulse
Backlash deceleration Pulse train torque command
F202 142
stopping frequency
354 D120 432*1 bias
270
198 5. PARAMETERS
5.1 Parameter list
Pr. Refer Pr. Refer
Pr. Name Pr. Name
group to page group to page
H012 693
Second free thermal reduction
394 H522 1482
Load characteristics load
417
1
ratio 1 reference 2
Second free thermal reduction Load characteristics load
H013 694 394 H523 1483 417
frequency 2 reference 3
Second free thermal reduction Load characteristics load 2
H014 695 394 H524 1484 417
ratio 2 reference 4
Second free thermal reduction Load characteristics load
H015 696 394 H525 1485 417
frequency 3 reference 5
Second motor permissible Load characteristics maximum
3
H016 608 394 H526 1486 417
load level frequency
PTC thermistor protection Load characteristics minimum
H020 561 394 H527 1487 417
level
PTC thermistor protection
frequency
Upper limit warning detection
4
H021 1016 394 H531 1488 417
detection time width
H022 876*1 Thermal protector input 394 Lower limit warning detection
H532 1489 417
H030 875 Fault definition 401
width
Upper limit fault detection
5
Cooling fan operation H533 1490 417
H100 244 402 width
selection
Lower limit fault detection
Earth (ground) fault detection H534 1491 417
H101 249
at start
403 width 6
Load status detection signal
H102 598 Undervoltage level 403
H535 1492 delay time / load reference 417
H103 997 Fault initiation 404 measurement waiting time
H200 251
Output phase loss protection
selection
404 H600 48
Second stall prevention
409 7
operation level
Input phase loss protection Second stall prevention
H201 872*4 selection
404 H601 49 409
operation frequency
H300 65 Retry selection 405
H602 114
Third stall prevention
409
8
Number of retries at fault operation level
H301 67 405
occurrence Third stall prevention
H302 68 Retry waiting time 405 H603 115 409
operation frequency
H303 69 Retry count display erase 405 Stall prevention operation 9
H400 1 Maximum frequency Simple 407 H610 23 level compensation factor at 409
double speed
H401 2 Minimum frequency Simple 407
Stall prevention operation
H402 18
High speed maximum
407
H611 66
reduction starting frequency
409 10
frequency Stall prevention level at 0 V
H410 807 Speed limit selection 274 H620 148 409
input
Forward rotation speed limit/ Stall prevention level at 10 V
H411 808 274 H621 149 409
speed limit input
Reverse rotation speed limit/ Voltage reduction selection
H412 809 274
reverse-side speed limit H631 154 during stall prevention 409
H414 1113 Speed limit method selection 274 operation
H415 873*1 Speed limit 259 Torque limit input method
H700 810 235
selection
Speed deviation excess 259,
H416 285 Torque limit level
detection frequency 700 H701 812 235
(regeneration)
H417 853*1 Speed deviation time 259
Torque limit level (3rd
H420 31 Frequency jump 1A 408 H702 813 235
quadrant)
H421 32 Frequency jump 1B 408 Torque limit level (4th
H422 33 Frequency jump 2A 408 H703 814 235
quadrant)
H423 34 Frequency jump 2B 408 235,
H704 801 Output limit level
H424 35 Frequency jump 3A 408 270
H425 36 Frequency jump 3B 408 H710 815 Torque limit level 2 235
H429 552 Frequency jump range 408 Torque limit level during
H720 816 235
Stall prevention operation 235, acceleration
H500 22
level (Torque limit level) 409 Torque limit level during
H721 817 235
Stall prevention operation deceleration
H501 156 409
selection H730 874 OLT level setting 235
Load characteristics H800 374 Overspeed detection level 421
H520 1480 417
measurement mode H881 690 Deceleration check time 260
Load characteristics load
H521 1481 417
reference 1
5. PARAMETERS
5.1 Parameter list
199
M: Monitoring and its output Pr.
Refer
Pr. Name to
signal group
page
Parameters for the settings regarding the monitoring to check M301 158 AM terminal function selection 435
the inverter's operating status and the output signals for the C0
M310 FM/CA terminal calibration 440
(900)*2
monitoring.
C1
M320 AM terminal calibration 440
Pr.
Refer (901)*2
Pr. Name to M321 867 AM output filter 440
group
page
C8
M000 37 Speed display 422 M330 Current output bias signal 440
(930)*2
M001 505 Speed setting reference 422
C9
M002 144 Speed setting switchover 422 M331 Current output bias current 440
(930)*2
M020 170 Watt-hour meter clear 424
C10
Energization time carrying- M332 Current output gain signal 440
M021 563 424 (931)*2
over times
C11
Monitor decimal digits M333 Current output gain current 440
M022 268 424 (931)*2
selection
Cumulative power monitor 424, M334 869 Current output filter 440
M023 891
digit shifted times 444 RUN terminal function
M400 190 450
M030 171 Operation hour meter clear 424 selection
Operating time carrying-over M401 191 SU terminal function selection 450
M031 564 424
times M402 192 IPF terminal function selection 450
Frequency monitoring M403 193 OL terminal function selection 450
M040 55 435
reference M404 194 FU terminal function selection 450
M041 56 Current monitoring reference 435 ABC1 terminal function
M405 195 450
M042 866 Torque monitoring reference 435 selection
Analog input display unit ABC2 terminal function
M043 241 482 M406 196 450
switchover selection
Monitor negative output 424, M410 313*5*6 DO0 output selection 450
M044 290
selection 435 *5*6
M411 314 DO1 output selection 450
M045 1018 Monitor with sign selection 424
M050 1106 Torque monitor filter 424
M412 315*5*6 DO2 output selection 450
M051 1107 Running speed monitor filter 424 M413 316*5 DO3 output selection 450
Excitation current monitor M414 317*5 DO4 output selection 450
M052 1108 424
filter M415 318*5 DO5 output selection 450
Control circuit temperature *5
M060 663 471 M416 319 DO6 output selection 450
signal output level
Operation panel main monitor M420 320*5 RA1 output selection 450
M100 52 424
selection M421 321 *5 RA2 output selection 450
Operation panel monitor
M101 774 424 M422 322*5 RA3 output selection 450
selection 1
235,
Operation panel monitor M430 157 OL signal output timer
M102 775 424 409
selection 2
M431 289 Inverter output terminal filter 450
Operation panel monitor
M103 776 424 Output current detection
selection 3 M433 166 464
signal retention time
Operation panel setting dial 435,
M104 992 M440 870 Speed detection hysteresis 461
push monitor selection 424
M200 892 Load factor 444 M441 41 Up-to-frequency sensitivity 461
Energy saving monitor M442 42 Output frequency detection 461
M201 893 444
reference (motor capacity) Output frequency detection for
M443 43 461
Control selection during reverse rotation
M202 894 commercial power-supply 444 Second output frequency
M444 50 461
operation detection
Power saving rate reference Third output frequency 465,
M203 895 444 M445 116
value detection 461
M204 896 Power unit cost 444 M446 865 Low speed detection 461
Power saving monitor average M460 150 Output current detection level 464
M205 897 444
time Output current detection
M461 151 464
Power saving cumulative signal delay time
M206 898 444
monitor clear M462 152 Zero current detection level 464
Operation time rate (estimated M463 153 Zero current detection time 464
M207 899 444
value) Output current detection
FM/CA terminal function M464 167 464
M300 54 435 operation selection
selection
200 5. PARAMETERS
5.1 Parameter list
Refer Pr. Refer
Pr. Pr. Name
Pr. Name to group to page
group
page T052 573 4 mA input check selection 492 1
M470 864 Torque detection 465 4 mA input fault operation
T053 777 492
M500 495 Remote output selection 466 frequency
M501
M502
496
497
Remote output data 1
Remote output data 2
466
466
T054 778
C12
4 mA input check filter
Terminal 1 bias frequency
492
2
T100 482
M510 76 Fault code output selection 469 (917)*2 (speed)
Pulse increment setting for C13
M520 799 470
output power T101
(917)*2
Terminal 1 bias (speed) 482
3
Analog remote output C14 Terminal 1 gain frequency
M530 655 467 T102 482
selection
(918)*2 (speed)
M531 656 Analog remote output 1 467
C15
M532 657 Analog remote output 2 467 T103
(918)*2
Terminal 1 gain (speed) 482 4
M533 658 Analog remote output 3 467
C16 Terminal 1 bias command
M534 659 Analog remote output 4 467 T110 487
(919)*2 (torque)
M600 863*1
Control terminal option-
Encoder pulse division ratio
472
T111
C17
Terminal 1 bias (torque) 487
5
(919)*2
M601 413*1 Encoder pulse division ratio 472
C18 Terminal 1 gain command
Cumulative pulse clear signal T112 487
M610 635*1 306 (920)*2 (torque)
selection
C19
6
Cumulative pulse division T113 Terminal 1 gain (torque) 487
M611 636*1 scaling factor
306 (920)*2
Control terminal option- C2 Terminal 2 frequency setting
T200 482
M612 637*1 Cumulative pulse division 306 (902)*2 bias frequency 7
scaling factor C3 Terminal 2 frequency setting
T201 482
M613 638*1 Cumulative pulse storage 306 (902)*2 bias
125 Terminal 2 frequency setting
T: Multi-function input terminal
T202
(903)*2 gain frequency
482 8
C4 Terminal 2 frequency setting
parameters T203
(903)*2 gain
482
5. PARAMETERS
5.1 Parameter list
201
Pr. Refer Refer
Pr. Name Pr.
group to page Pr. Name to
group
STOP terminal function page
T710 188 496
selection C131 711 Motor Ld decay ratio 519
RES terminal function C132 712 Motor Lq decay ratio 519
T711 189 496
selection C133 725 Motor protection current level 519
T720 17 MRS input selection 499 Motor induced voltage
C135 1412 519
T721 599 X10 terminal input selection 689 constant (phi f) exponent
Power failure stop external 93, 554,
T722 606
signal input selection
610 C140 369*1 Number of encoder pulses
700
RT signal function validity 93, 554,
T730 155
condition selection
500 C141 359*1 Encoder rotation direction
700
T740 699 Input terminal filter 496 Encoder signal loss detection
C148 376*1 enable/disable selection
530
202 5. PARAMETERS
5.1 Parameter list
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group
page
group
page 1
Control terminal option- Second deceleration detection
C241 852*1 Encoder rotation direction
93 A126 648
function selection
541
C242 862*1 Encoder option selection 220 Second brake opening current
Control terminal option-Signal
A128 650
selection
541 2
C248 855*1 loss detection enable/disable 530 Second brake operation
A129 651 541
selection frequency selection
Second brake sequence
C282 741
Second starting resistance
tuning compensation
519 A130 641
operation selection
541 3
Second motor magnetic pole A170 1410 Starting times lower 4 digits 545
C285 742 519
detection pulse width A171 1411 Starting times upper 4 digits 545
Stop-on contact/load torque
546, 4
A: Application parameters A200 270 high- speed frequency control
selection
549
Parameters for the setting of a specific application. High-speed setting maximum
A201 271 549
Pr.
Refer
current
Middle-speed setting minimum
5
Pr. Name to A202 272 549
group current
page
Electronic bypass sequence A203 273 Current averaging range 549
A000 135
selection
532
A204 274
Current averaging filter time
549
6
A001 136 MC switchover interlock time 532 constant
A002 137 Start waiting time 532 Stop-on contact excitation
A205 275 current low-speed scaling 546
A003 138 Bypass selection at a fault
Automatic switchover
532
factor 7
PWM carrier frequency at stop-
A004 139 frequency from inverter to 532 A206 276 546
on contact
bypass operation
A300 592 Traverse function selection 551
A005 159
Automatic switchover
frequency range from bypass 532 A301 593 Maximum amplitude amount 551 8
to inverter operation Amplitude compensation
A302 594 551
Self power management amount during deceleration
A006 248 538
selection
Main circuit power OFF waiting
A303 595
Amplitude compensation
amount during acceleration
551 9
A007 254 538 A304 596 Amplitude acceleration time 551
time
A100 278 Brake opening frequency 541 A305 597 Amplitude deceleration time 551
A101 279 Brake opening current 541 A310 1072
DC brake judgment time for
anti-sway control operation
553 10
Brake opening current
A102 280 541 Anti-sway control operation
detection time A311 1073 553
A103 281 Brake operation time at start 541 selection
A104 282 Brake operation frequency 541 A312 1074 Anti-sway control frequency 553
A105 283 Brake operation time at stop 541 A313 1075 Anti-sway control depth 553
Deceleration detection A314 1076 Anti-sway control width 553
A106 284 541 A315 1077 Rope length 553
function selection
Overspeed detection A316 1078 Trolley weight 553
A107 285 541
frequency A317 1079 Load weight 553
Brake opening current Stop position command
A108 639 541 A510 350*1 554
selection selection
Brake operation frequency A511 360*1 16-bit data selection 554
A109 640 541
selection
A512 361*1 Position shift 554
365,
Automatic acceleration/
A110 292 368, A520 362*1 Orientation position loop gain 554
deceleration
541 Completion signal output
A521 363*1 delay time
554
Second brake opening
A120 642 541
frequency A522 364*1 Encoder stop check time 554
A121 643 Second brake opening current 541
A523 365*1 Orientation limit 554
Second brake opening current
A122 644 541 A524 366*1 Recheck time 554
detection time
Second brake operation time A525 393*1 Orientation selection 554
A123 645 541
at start A526 351*1 Orientation speed 554
Second brake operation *1
A124 646 541 A527 352 Creep speed 554
frequency
Second brake operation time A528 353*1 Creep switchover position 554
A125 647 541
at stop Position loop switchover
A529 354*1 position
554
5. PARAMETERS
5.1 Parameter list
203
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group group
page page
DC injection brake start C43
A530 355*1 position
554 A631 PID display bias analog value 584
(934)*2
Internal stop position C44
A531 356*1 command
554 A632 PID display gain coefficient 584
(935)*2
A532 357*1 Orientation in-position zone 554 C45
A633 PID display gain analog value 584
A533 358*1 Servo torque selection 554 (935)*2
Number of machine side gear A640 1142 Second PID unit selection 570
A540 394*1 teeth
554
A641 1143 Second PID upper limit 570
Number of motor side gear A642 1144 Second PID lower limit 570
A541 395*1 teeth
554
A643 1145 Second PID deviation limit 570
Orientation speed gain (P
A542 396*1 554 Second PID signal operation
term) A644 1146 570
selection
A543 397*1 Orientation speed integral time 554 A650 753 Second PID action selection 570
Orientation speed gain (D A651 755 Second PID action set point 570
A544 398*1 term)
554
Second PID control automatic
A652 754 570
A545 399*1 Orientation deceleration ratio 554 switchover frequency
Number of machine end A653 756 Second PID proportional band 570
A546 829*1 encoder pulses
554
A654 757 Second PID integral time 570
A600 759 PID unit selection 584 A655 758 Second PID differential time 570
570, Second pre-charge fault
A601 131 PID upper limit A656 765 587
590 selection
570, Second pre-charge ending
A602 132 PID lower limit A657 766 587
590 level
A603 553 PID deviation limit 570 Second pre-charge ending
A658 767 587
A604 554 PID signal operation selection 570 time
PID upper limit manipulated Second pre-charge upper
A605 1134 590 A659 768 587
value detection level
PID lower limit manipulated A660 769 Second pre-charge time limit 587
A606 1135 590
value Second output interruption
A661 1147 570
Integral stop selection at detection time
A607 1015 570
limited frequency Second output interruption
A662 1148 570
570, detection level
A610 128 PID action selection
590 Second output interruption
A663 1149 570
570, cancel level
A611 133 PID action set point
590 Second PID set point/deviation
A664 1140 570
PID control automatic input selection
A612 127 570
switchover frequency Second PID measured value
A665 1141 570
570, input selection
A613 129 PID proportional band
590 Second PID display bias
A670 1136 584
570, coefficient
A614 130 PID integral time
590 Second PID display bias
A671 1137 584
570, analog value
A615 134 PID differential time
590 Second PID display gain
A672 1138 584
A616 760 Pre-charge fault selection 587 coefficient
A617 761 Pre-charge ending level 587 Second PID display gain
A673 1139 584
A618 762 Pre-charge ending time 587 analog value
Pre-charge upper detection A680 573 4 mA input check selection 492
A619 763 587
level 4 mA input fault operation
A681 777 492
A620 764 Pre-charge time limit 587 frequency
Output interruption detection A682 778 4 mA input check filter 492
A621 575 570
time Automatic restart after 597,
Output interruption detection A700 162 instantaneous power failure 604,
A622 576 570 selection 606
level
Output interruption cancel Rotation direction detection
A623 577 570 A701 299 597
level selection at restarting
PID set point/deviation input 570, 597,
A624 609 A702 57 Restart coasting time
selection 590 604
PID measured value input 570, A703 58 Restart cushion time 597
A625 610
selection 590 A704 163 First cushion time for restart 597
C42 First cushion voltage for
A630 PID display bias coefficient 584 A705 164 597
(934)*2 restart
204 5. PARAMETERS
5.1 Parameter list
Pr.
Refer B: Position control parameters
Pr. Name to
group
page Parameters for the position control setting. 1
Stall prevention operation Refer
A710 165 597 Pr.
level for restart Pr. Name to
group
A711 298 Frequency search gain 606 page
A712 560 Second frequency search gain 606 Position command source 288, 2
B000 419
A730 261 Power failure stop selection 610 selection 304
Subtracted frequency at Command pulse scaling factor
A731 262 610 B001 420 numerator (electronic gear 309
A732 263
deceleration start
Subtraction starting frequency 610
numerator) 3
Command pulse multiplication
Power-failure deceleration
A733 264 610 B002 421 denominator (electronic gear 309
time 1
denominator)
A734 265
Power-failure deceleration
610 B003 422 Position control gain 312
4
time 2
B004 423 Position feed forward gain 312
Power failure deceleration time
A735 266 610 Position command
switchover frequency
A785 294 UV avoidance voltage gain 610
B005 424 acceleration/deceleration time
constant
309
5
Power failure stop frequency
A786 668 610 Position feed forward
gain B006 425 312
command filter
PLC function operation
A800 414
selection
614 B007 426 In-position width 311 6
B008 427 Excessive level error 311
Inverter operation lock mode
A801 415 614 B009 428 Command pulse selection 304
setting
A802 416 Pre-scale function selection 614 B010 429 Clear signal selection 304
A803 417 Pre-scale setting value 614 B011 430 Pulse monitor selection 304 7
PLC function flash memory B012 446 Model position control gain 312
A804 498 614
clear B013 1298 Second position control gain 312
A810 to
A859
1150 to
1199
PLC function user parameters
1 to 50
614 B020 464
Digital position control sudden
stop deceleration time
288 8
A900 1020 Trace operation selection 616 First target position lower 4
B021 465 288
A901 1021 Trace mode selection 616 digits
A902 1022 Sampling cycle 616 B022 466
First target position upper 4
digits
288 9
A903 1023 Number of analog channels 616
Second target position lower 4
A904 1024 Sampling auto start 616 B023 467 288
digits
A905 1025 Trigger mode selection
Number of sampling before
616
B024 468
Second target position upper 4
288
10
A906 1026 616 digits
trigger
Third target position lower 4
A910 1027 Analog source selection (1ch) 616 B025 469 288
digits
A911 1028 Analog source selection (2ch) 616 Third target position upper 4
A912 1029 Analog source selection (3ch) 616 B026 470 288
digits
A913 1030 Analog source selection (4ch) 616 Fourth target position lower 4
B027 471 288
A914 1031 Analog source selection (5ch) 616 digits
A915 1032 Analog source selection (6ch) 616 Fourth target position upper 4
B028 472 288
A916 1033 Analog source selection (7ch) 616 digits
A917 1034 Analog source selection (8ch) 616 Fifth target position lower 4
B029 473 288
digits
A918 1035 Analog trigger channel 616
Fifth target position upper 4
Analog trigger operation B030 474 288
A919 1036 616 digits
selection
A920 1037 Analog trigger level 616 Sixth target position lower 4
B031 475 288
digits
A930 1038 Digital source selection (1ch) 616
Sixth target position upper 4
A931 1039 Digital source selection (2ch) 616 B032 476 288
digits
A932 1040 Digital source selection (3ch) 616
Seventh target position lower 4
A933 1041 Digital source selection (4ch) 616 B033 477 288
digits
A934 1042 Digital source selection (5ch) 616 Seventh target position upper
B034 478 288
A935 1043 Digital source selection (6ch) 616 4 digits
A936 1044 Digital source selection (7ch) 616 Eighth target position lower 4
B035 479 288
A937 1045 Digital source selection (8ch) 616 digits
A938 1046 Digital trigger channel 616 Eighth target position upper 4
B036 480 288
digits
Digital trigger operation
A939 1047 616 Ninth target position lower 4
selection B037 481 288
digits
5. PARAMETERS
5.1 Parameter list
205
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group group
page page
Ninth target position upper 4 Sixth positioning acceleration
B038 482 288 B140 1242 288
digits time
Tenth target position lower 4 Sixth positioning deceleration
B039 483 288 B141 1243 288
digits time
Tenth target position upper 4 B142 1244 Sixth positioning dwell time 288
B040 484 288
digits B143 1245 Sixth positioning sub-function 288
Eleventh target position lower Seventh positioning
B041 485 288 B144 1246 288
4 digits acceleration time
Eleventh target position upper Seventh positioning
B042 486 288 B145 1247 288
4 digits deceleration time
Twelfth target position lower 4 B146 1248 Seventh positioning dwell time 288
B043 487 288
digits
Seventh positioning sub-
Twelfth target position upper 4 B147 1249 288
B044 488 288 function
digits
Eighth positioning
Thirteenth target position B148 1250 288
B045 489 288 acceleration time
lower 4 digits Eighth positioning
Thirteenth target position B149 1251 288
B046 490 288 deceleration time
upper 4 digits
B150 1252 Eighth positioning dwell time 288
Fourteenth target position
B047 491 288 Eighth positioning sub-
lower 4 digits B151 1253 288
function
Fourteenth target position
B048 492 288 Ninth positioning acceleration
upper 4 digits B152 1254 288
time
Fifteenth target position lower Ninth positioning deceleration
B049 493 288
4 digits B153 1255 288
time
Fifteenth target position upper
B050 494 288 B154 1256 Ninth positioning dwell time 288
4 digits
B155 1257 Ninth positioning sub-function 288
Target position/speed
B100 1220 853 Tenth positioning acceleration
selection B156 1258 288
time
Start command edge detection
B101 1221 288 Tenth positioning deceleration
selection B157 1259 288
time
First positioning acceleration
B120 1222 288 B158 1260 Tenth positioning dwell time 288
time
B159 1261 Tenth positioning sub-function 288
First positioning deceleration
B121 1223 288 Eleventh positioning
time B160 1262 288
acceleration time
B122 1224 First positioning dwell time 288
Eleventh positioning
B123 1225 First positioning sub-function 288 B161 1263 288
deceleration time
Second positioning
B124 1226 288 Eleventh positioning dwell
acceleration time B162 1264 288
time
Second positioning
B125 1227 288 Eleventh positioning sub-
deceleration time B163 1265 288
function
B126 1228 Second positioning dwell time 288
Twelfth positioning
Second positioning sub- B164 1266 288
B127 1229 288 acceleration time
function
Twelfth positioning
Third positioning acceleration B165 1267 288
B128 1230 288 deceleration time
time
B166 1268 Twelfth positioning dwell time 288
Third positioning deceleration
B129 1231 288 Twelfth positioning sub-
time B167 1269 288
function
B130 1232 Third positioning dwell time 288
Thirteenth positioning
B131 1233 Third positioning sub-function 288 B168 1270 288
acceleration time
Fourth positioning
B132 1234 288 Thirteenth positioning
acceleration time B169 1271 288
deceleration time
Fourth positioning
B133 1235 288 Thirteenth positioning dwell
deceleration time B170 1272 288
time
B134 1236 Fourth positioning dwell time 288 Thirteenth positioning sub-
Fourth positioning sub- B171 1273 288
B135 1237 288 function
function
Fourteenth positioning
Fifth positioning acceleration B172 1274 288
B136 1238 288 acceleration time
time
Fourteenth positioning
Fifth positioning deceleration B173 1275 288
B137 1239 288 deceleration time
time Fourteenth positioning dwell
B138 1240 Fifth positioning dwell time 288 B174 1276 288
time
B139 1241 Fifth positioning sub-function 288
206 5. PARAMETERS
5.1 Parameter list
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group
page
group
page 1
Fourteenth positioning sub- Operation frequency during
B175 1277 288 N014 779 630
function communication error
Fifteenth positioning PU communication station
B176 1278
acceleration time
288 N020 117
number
636 2
Fifteenth positioning N021 118 PU communication speed 636
B177 1279 288
deceleration time N022 119 PU communication data length 636
Fifteenth positioning dwell
B178 1280
time
288 N023 119
PU communication stop bit
length
636 3
Fifteenth positioning sub- PU communication parity
B179 1281 288 N024 120 636
function check
B180 1282
Home position return method
selection
288 N025 121 PU communication retry count 636 4
PU communication check time
B181 1283 Home position return speed 288 N026 122 636
interval
Home position return creep PU communication waiting
B182 1284 288 N027 123 636
speed
Home position shift amount
time setting 5
B183 1285 288 PU communication CR/LF
lower 4 digits N028 124 636
selection
Home position shift amount RS-485 communication station
B184 1286 288
upper 4 digits N030 331
number
636
6
Travel distance after proximity N031 332 RS-485 communication speed 636
B185 1287 288
dog ON lower 4 digits
RS-485 communication data
Travel distance after proximity N032 333 636
length
B186 1288
dog ON upper 4 digits
288
N033 333
RS-485 communication stop
636
7
Home position return stopper bit length
B187 1289 288
torque
RS-485 communication parity
Home position return stopper N034 334 636
check selection
B188 1290
waiting time
288
RS-485 communication retry
8
Position control terminal input N035 335 636
B190 1292 288 count
selection RS-485 communication check
B191 1293 Roll feeding mode selection 288 N036 336 636
Position detection lower 4
time interval
RS-485 communication
9
B192 1294 311 N037 337 636
digits waiting time setting
Position detection upper 4 RS-485 communication CR/LF
B193 1295 311 N038 341 636
B194 1296
digits
Position detection selection 311
selection
USB communication station
10
N040 547 666
Position detection hysteresis number
B195 1297 311
width USB communication check
N041 548 666
time interval
N: Communication operation N080 343 Communication error count 652
Frequency command sign
parameters N100 541*6 selection
665
Parameters for the setting of communication operation such N110 434*6 Network number (CC-Link IE) 665
as the communication specifications or operating N111 435*6 Station number (CC-Link IE) 665
characteristics. N500 to 1300 to
Communication option parameters.
N543, 1343,
Refer For details, refer to the Instruction Manual
Pr. N550 to 1350 to
Pr. Name to of the option.
group N559 1359
page
N000 549 Protocol selection 630
Communication EEPROM
G: Control parameters
N001 342 630
write selection Parameters for motor control.
MODBUS RTU communication
N002 539 652 Refer
check time interval Pr.
Pr. Name to
Communication reset group
N010 349*6 630 page
selection
G000 0 Torque boost Simple 672
Communication error
N011 500*6 execution waiting time
630
G001 3 Base frequency Simple 673
Communication error G002 19 Base frequency voltage 673
N012 501*6 occurrence count display
630
G003 14 Load pattern selection 674
Stop mode selection at G010 46 Second torque boost 672
N013 502 630
communication error
G011 47 Second V/F (base frequency) 673
G020 112 Third torque boost 672
5. PARAMETERS
5.1 Parameter list
207
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group group
page page
G021 113 Third V/F (base frequency) 673 Slip compensation time
G204 246 700
Energy saving control constant
G030 60 678
selection Constant output range slip
G205 247 700
G040 100 V/F1 (first frequency) 679 compensation selection
G041 101 V/F1 (first frequency voltage) 679 Constant output range speed
G206 1116 244
control P gain compensation
G042 102 V/F2 (second frequency) 679
Constant output range torque 235,
V/F2 (second frequency G210 803
G043 103 679 characteristic selection 270
voltage)
G211 820 Speed control P gain 1 244
G044 104 V/F3 (third frequency) 679
G212 821 Speed control integral time 1 244
G045 105 V/F3 (third frequency voltage) 679
Torque control P gain 1
G046 106 V/F4 (fourth frequency) 679 280,
G213 824 (current loop proportional
G047 107 V/F4 (fourth frequency voltage) 679 317
gain)
G048 108 V/F5 (fifth frequency) 679 Torque control integral time 1 280,
G049 109 V/F5 (fifth frequency voltage) 679 G214 825
(current loop integral time) 317
SF-PR slip amount adjustment
G060 673 680 G215 823*1 Speed detection filter 1 316
operation selection
G216 827 Torque detection filter 1 316
SF-PR slip amount adjustment
G061 674 680 G217 854 Excitation ratio 316
gain
Reverse rotation excitation Speed control integral term
G218 1115 244
G080 617 current low-speed scaling 677 clear time
factor Speed feed forward control/
DC injection brake operation G220 877 model adaptive speed control 253
G100 10 681 selection
frequency
DC injection brake operation G221 878 Speed feed forward filter 253
G101 11 681 Speed feed forward torque
time G222 879 253
G102 802 Pre-excitation selection 681 limit
G103 850 Brake operation selection 681 G223 881 Speed feed forward gain 253
G105 522 Output stop frequency 686 G224 828 Model speed control gain 253
G106 250 Stop selection 688 G230 840 Torque bias selection 255
Special regenerative brake G231 841 Torque bias 1 255
G107 70*3 duty
689 G232 842 Torque bias 2 255
Second pre-excitation G233 843 Torque bias 3 255
G108 1299 681
selection G234 844 Torque bias filter 255
DC injection brake operation G235 845 Torque bias operation time 255
G110 12 681
voltage Torque bias balance
G236 846 255
Regeneration avoidance compensation
G120 882 696
operation selection Fall-time torque bias terminal 1
G237 847 255
Regeneration avoidance bias
G121 883 696
operation level Fall-time torque bias terminal 1
G238 848 255
Regeneration avoidance at gain
G122 884 deceleration detection 696 G240 367*1 Speed feedback range 700
sensitivity
Regeneration avoidance
G241 368*1 Feedback gain 700
G123 885 compensation frequency limit 696 Low speed range torque
G250 788 227
value characteristic selection
Regeneration avoidance Per-unit speed control
G124 886 696 G260 1121 244
voltage gain reference frequency
Regeneration avoidance Speed control P gain 1 (per-
G125 665 696 G261 1117 244
frequency gain unit system)
Increased magnetic excitation Model speed control gain (per-
G262 1119 253
G130 660 deceleration operation 699 unit system)
selection G263 1348 P/PI control switchover
244
Magnetic excitation increase frequency
G131 661 699
rate G264 1349 Emergency stop operation
349
Increased magnetic excitation selection
G132 662 699
current level Second motor control method
G300 451 215
G200 800 Control method selection 215 selection
G201 85 Excitation current break point 677 Second motor excitation
G301 565 677
Excitation current low speed current break point
G202 86 677 Second motor excitation
scaling factor
G203 245 Rated slip 700 G302 566 current low-speed scaling 677
factor
208 5. PARAMETERS
5.1 Parameter list
Refer Refer
Pr. Pr.
Pr. Name to Pr. Name to
group
page
group
page 1
G311 830 Speed control P gain 2 244 Second droop function
G422 681 702
G312 831 Speed control integral time 2 244 activation selection
G423 682 Second droop break point gain 702
G313
G314
834
835
Torque control P gain 2
Torque control integral time 2
280
280 Second droop break point 2
G424 683 702
torque
G315 833*1 Speed detection filter 2 316
G601 1003 Notch filter frequency 261
G316 837 Torque detection filter 2 316
Second motor low-speed
G602
G603
1004
1005
Notch filter depth
Notch filter width
261
261
3
G350 747 range torque characteristic 227
selection Speed control gain (Advanced
G932 89 222
magnetic flux vector)
Speed control P gain 2 (per-
G361 1118
unit system)
244
G942 569
Second motor speed control
222 4
gain
G400 286 Droop gain 702
G401 287 Droop filter time constant 702 *1 The setting is available when a plug-in option for Vector
control is installed.
G402 288
Droop function activation
selection
702 *2 On the LCD operation panel or the parameter unit used as the 5
command source, the parameter number in parentheses
G403 994 Droop break point gain 702
appears instead of that starting with the letter C.
G404 995 Droop break point torque 702 *3 The setting is available for the standard model.
G410 653 Speed smoothing control 705 *4 The setting is available for the standard model and the IP55
compatible model.
6
Speed smoothing cutoff
G411 654 705 *5 The setting is available when the PLC function is enabled.
frequency
*6 The setting is available for the FR-A800-GF or when a
G420 679 Second droop gain 702
G421 680
Second droop filter time
702
compatible plug-in option is installed.
7
constant
10
5. PARAMETERS
5.1 Parameter list
209
5.2 Control method
V/F control (initial setting), Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and PM
sensorless vector control are available with this inverter.
V/F control
The inverter controls the output frequency (F) and the output voltage (V) so that the ratio of frequency to voltage (V/F) is kept
constant when the frequency is changed.
NOTE
• Advanced magnetic flux vector control requires the following conditions.
If these conditions are not satisfied, select V/F control. Otherwise, malfunctions such as insufficient torque, uneven rotation
may occur.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (It must be 0.4 kW
or higher.)
If a motor with substantially low rated current compared with the inverter rated current, however, is used, speed and torque
accuracies may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated
current.
• The motor described in the following table is used.
Motor Condition
Mitsubishi Electric standard motor (SF-JR)
Mitsubishi Electric high-efficiency motor (SF-
HR)
Mitsubishi Electric constant-torque motor (SF- The offline auto tuning is not required.
JRCA 4P, SF-HRCA)
Mitsubishi Electric high-performance energy-
saving motor (SF-PR)
Other motor (Mitsubishi motor SF-TH, etc. or
The offline auto tuning is required.
other manufacturer's motor)
NOTE
• Real sensorless vector control requires the following conditions.
If these conditions are not satisfied, select V/F control. Otherwise, malfunctions such as insufficient torque, uneven rotation
may occur.
210 5. PARAMETERS
5.2 Control method
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (It must be 0.4 kW
or higher.)
If a motor with substantially low rated current compared with the inverter rated current, however, is used, speed and torque 1
accuracies may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated
current.
• Offline auto tuning is performed.
Offline auto tuning is necessary under Real sensorless vector control even when the Mitsubishi Electric motor is used.
2
• Single-motor operation (one motor to one inverter) is performed.
• A surge voltage suppression filter (FR-ASF/FR-BMF) or sine wave filter (MT-BSL/BSC) is not used.
3
Vector control
• With a Vector control compatible option installed, full-scale Vector control operation of a motor with encoder can be
4
performed. Speed control (zero speed control, servo lock), torque control, and position control can be performed with fast
response and high accuracy. With the FR-A8APR installed, Vector control operation of a motor with resolver can be
performed.
5
• Vector control has excellent control characteristic compared to other control methods such as V/F control. Its control
characteristic is equal to those of DC machines.
• This control method is useful for the following purposes:
- To minimize the speed fluctuation even at a severe load fluctuation
6
- To generate a low speed torque
- To prevent machine from damage due to a too large torque (To set the torque limit)
- To control the torque or position 7
- To control a torque generated in a motor in a servo-lock state (the motor with its shaft stopped)
NOTE 8
• Vector control requires the following conditions.
When the conditions are not satisfied, malfunctions such as insufficient torque, uneven rotation may occur.
• The rated motor current should be equal to or less than the inverter rated current. (It must be 0.4 kW or higher.)
If a motor with substantially low rated current compared with the inverter rated current, however, is used, speed and torque
9
accuracies may deteriorate due to torque ripples, etc. As a reference, select the motor with the rated motor current that is 40%
or higher of the inverter rated current.
• The Vector control of PM motors can be performed when a PM motor with resolver is used together with the FR-A8APR. 10
(Torque control is not available for a PM motor.)
• The motor described in the following table is used.
Motor Condition
Vector control dedicated motor SF-V5RU (1500 r/min series)
Mitsubishi Electric standard motor with encoder (SF-JR)
Mitsubishi Electric high-efficiency motor with encoder (SF-HR) The offline auto tuning is not required.
Mitsubishi Electric constant-torque motor with encoder (SF-
JRCA 4P, SF-HRCA)
Other motors (motors other than SF-V5RU 1500 r/min series,
The offline auto tuning is required.
other manufactures' motors, etc.)
5. PARAMETERS
5.2 Control method
211
• Performing the IPM parameter initialization makes the IPM motor MM-CF ready for the PM sensorless vector control.
PM sensorless vector control image
Inverter Ooutput
Speed voltage
command Inverter
Controller
circuit
NOTE
• The PM sensorless vector control requires the following conditions.
• The motor described in the following table is used.
Motor Condition
Mitsubishi Electric IPM motor (MM-CF) The offline auto tuning is not required.
IPM motor (other than MM-CF), SPM motor The offline auto tuning is required.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (It must be 0.4 kW
or higher.)
If a motor with substantially low rated current compared with the inverter rated current, however, is used, speed and torque
accuracies may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated
current.
• Single-motor operation (one motor to one inverter) is performed.
• The wiring length from the inverter to the motor is 100 m or less. (Refer to page 66.) (When the wiring length from the inverter
to the IPM motor MM-CF exceeds 30 m, perform offline auto tuning.)
• A surge voltage suppression filter (FR-ASF/FR-BMF) or sine wave filter (MT-BSL/BSC) is not used.
M: Mutual inductance
S: Slip
r2
id M iq
S id: Excitation current
iq: Torque current
im: Motor current
In the above diagram, currents flowing in the induction motor can be classified into a current id (excitation current) for making
a magnetic flux in the motor and a current iq (torque current) for causing the motor to develop torque.
212 5. PARAMETERS
5.2 Control method
In Vector control, the voltage and output frequency are calculated to control the motor so that the excitation current and torque
current flow to the optimum as described below:
1
iq motor current im
torque current
excitation current
id 4
• The excitation current is controlled to place the internal magnetic flux of the motor in the optimum status.
• The torque command value is derived so that the difference between the motor speed command and the actual speed 5
(speed estimated value for Real sensorless vector control) obtained from the encoder connected to the motor shaft is zero.
Torque current is controlled so that torque as set in the torque command is developed.
6
Motor-generated torque (TM), slip angular velocity (ωs) and the motor's secondary magnetic flux (Φ2) can be found by the
following calculation:
TM Φ2 · iq 7
Φ2 = M · id
iq
ωs = r2
L2 id 8
where, L2: secondary inductance
L2 = 2 + M
9
Vector control provides the following advantages:
• Vector control has excellent control characteristic compared to V/F control and other controls. The control characteristic of
the Vector control is equal to those of DC machines. 10
• It is applicable to fast response applications with which induction motors were previously regarded as difficult to use.
Applications requiring a wide variable-speed range from extremely low speed to high speed, frequent acceleration/
deceleration operations, continuous four-quadrant operations, etc.
• Torque control is enabled (when an induction motor is used).
• It allows servo-lock torque control which generates a torque in the motor shaft while stopped. (Not available under Real
sensorless vector control.)
5. PARAMETERS
5.2 Control method
213
Block diagram of Real sensorless vector control
IM
PWM
modulation
Magnetic Pre-excitation
φ2 id * + Vd
flux current Output
control - control voltage
id
conversion
Torque
ω* + Speed iq * + Vq
ω0
current
- control control
-
ω FB iq
+ ω0
ω FB +
id
ωs Current
iq iq
conversion
Slip
calculation iq
φ2 Magnetic
id
flux Vd
calculation Vq
Speed estimation
IM
Encoder
PWM
modulation
φ2 Magnetic id * + Pre-excitation
Vd
flux current Output
control - control voltage
id
conversion
iq* Torque
ω* + Speed + Vq
ω0
current
- control control
-
ω FB iq
+ ω0
ω FB +
id
ωs Current
iq iq
conversion
Slip
calculation
φ2 Magnetic id
flux
calculation
214 5. PARAMETERS
5.2 Control method
Speed control operation is performed to zero the difference between the speed command (ω*) and actual rotation value
Speed control detected by encoder (ωFB). At this time, the motor load is found and its result is transferred to the torque current
controller as a torque current command (iq*).
1
Torque current A voltage (Vq) is calculated to flow a current (iq) which is identical to the torque current command (iq*) found by the
control speed controller.
Magnetic flux The magnetic flux (Φ2) of the motor is derived from the excitation current (id). The excitation current command (id*) is 2
control calculated to use that motor magnetic flux (Ф2) as a predetermined magnetic flux.
Excitation current
A voltage (Vd) is calculated to flow a current (id) which is identical to the excitation current command (id*).
control
Output frequency Motor slip (ωs) is calculated on the basis of the torque current value (iq) and magnetic flux (Φ2). The output frequency 3
calculation (ω0) is found by adding that slip (ωs) to the feedback (ωFB) found by a feedback from the encoder.
The above results are used to make PWM modulation and run the motor.
4
5.2.2 Changing the control method and mode
Set the control method and the control mode.
V/F control, Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and PM sensorless vector
5
control are the control methods available for selection.
The available control modes are speed control, torque control, and position control modes.
Select a control mode under Real sensorless vector control, Vector control, and PM sensorless vector control. Under Real 6
sensorless vector control, select a control mode from the speed control, torque control, and position control modes. Under
Vector control, select a control mode from the speed control, torque control, and position control modes. The control method
is initially set to V/F control. 7
When using an IPM motor MM-CF, simply performing the IPM parameter initialization enables the PM sensorless vector control
and selects the speed control and position control.
• Select a control method and a control mode by setting Pr.800(Pr.451) Control method selection. 8
• The control mode can be switched using a mode switching signal (MC).
10
5. PARAMETERS
5.2 Control method
215
Pr. Name Initial value Setting range Description
0 to 6, 13 to 16, 20,
23, 24, 30, 33, 34, 40,
By selecting a standard motor or constant-torque motor,
71 43, 44, 50, 53, 54, 70,
Applied motor 0 the thermal characteristic and motor constant of each
C100 73, 74, 330, 333, 334,
motor are set.
8090, 8093, 8094,
9090, 9093, 9094
0.4 to 55 kW*1
80 Set the applied motor capacity.
Motor capacity 9999 0 to 3600 kW*2
C101
9999 V/F control
81 2, 4, 6, 8, 10, 12 Set the number of motor poles.
Number of motor poles 9999
C102 9999 V/F control
83
C104
Rated motor voltage 200/400 V*3 0 to 1000 V Set the rated motor voltage (V).
Setting the motor capacity and the number of motor poles (Pr.80, Pr.81)
• Motor specifications (the motor capacity and the number of motor poles) must be set to select Advanced magnetic flux
vector control, Real sensorless vector control, Vector control, or PM sensorless vector control.
• Set the motor capacity (kW) in Pr.80 Motor capacity and set the number of motor poles in Pr.81 Number of motor poles.
NOTE
• Setting the number of motor poles in Pr.81 changes the Pr.144 Speed setting switchover setting automatically. (Refer to
page 422.)
216 5. PARAMETERS
5.2 Control method
Selection of the control method and the control mode
• Select a control method (and a control mode) from V/F control (speed control), Advanced magnetic flux vector control 1
(speed control), Real sensorless vector control (speed control or torque control), Vector control (speed control, torque
control, or position control), or PM sensorless vector control (speed control or position control).
Settings 2
of Pr.80
Pr.71 Pr.800 Pr.451
(Pr.453) Control method Control mode Remarks
(Pr.450) setting*1 setting*1
and Pr.81
(Pr.454) 3
0, 100 Speed control —
1, 101 Torque control —
MC signal ON: torque
2, 102
Speed control /
torque control
control 4
MC signal OFF: speed
switchover
control
3, 103 Position control —
Speed control /
MC signal ON: position 5
control
4, 104 Vector control*2 position control
MC signal OFF: speed
switchover
control
Position control /
MC signal ON: torque 6
control
5, 105 torque control
MC signal ON: position
Induction switchover
control
motor*3 Torque control 7
6, 106 (variable-current —
limiter control)
9, 109 — Vector control test operation
10, 110 Speed control — 8
11, 111 Torque control —
Other than Real sensorless vector MC signal ON: torque
9999 control Speed control /
12, 112 torque control
control
MC signal OFF: speed 9
switchover
control
20 (initial Advanced magnetic flux
20 Speed control —
value)
9999 (initial
vector control
10
— Advanced magnetic flux vector control for the second motor
value)
9, 109 — PM sensorless vector control test operation
13, 113 Position control*7 —
*1 The setting values of 100 and above are used when the fast-response operation is selected.
*2 Advanced magnetic flux vector control is applied if a Vector control compatible option is not installed.
*3 For an induction motor, the setting "13, 14, 113, or 114" in Pr.800 (Pr.451) has the same meaning as the setting "10 or 110" in Pr.800 (Pr.451)
(speed control under Real sensorless vector control).
*4 For the IPM motor MM-CF, the setting other than "9, 13, 14, 109, 113, 114, or 9999" in Pr.800 (Pr.451) has the same meaning as the setting "20
or 110" in Pr.800 (Pr.451) (speed control under PM sensorless vector control).
*5 For an IPM motor other than the MM-CF or a SPM motor, the setting other than "9, 109, or 9999" in Pr.800 (Pr.451) has the same meaning as
the setting "20 or 110" in Pr.800 (Pr.451) (speed control under PM sensorless vector control).
*6 V/F control is applied when Pr.80 or Pr.81 is "9999", regardless of the Pr.800 setting. When Pr.71 is set to the IPM motor MM-CF, PM sensorless
vector control is enabled even if Pr.80 ≠ "9999" or Pr.81 = "9999".
*7 Setting Pr.788 (Pr.747) = "0" (low-speed range torque characteristic disabled) selects speed control.
5. PARAMETERS
5.2 Control method
217
Selecting the fast-response operation (Pr.800 (Pr.451) = “100 to 106, or
109 to 114")
• Setting Pr.800 (Pr.451) = "any of 100 to 106 or 109 to 114" selects the fast-response operation. The fast-response
operation is available during Vector control, Real sensorless vector control, and PM sensorless vector control.
Speed response
Fast-response operation
Control method Normal-response operation
Pr.800 (Pr.451) = “100 to 106, or 109 to
Pr.800 (Pr.451) = “0 to 6, or 9 to 14”
114”
Vector control 130 Hz at maximum 50 Hz at maximum
20 Hz at maximum*2
Real sensorless vector control 50 Hz at maximum*1
10 Hz at maximum*3
PM sensorless vector control 50 Hz at maximum 30 Hz at maximum
*1 When driving a 3.7 kW no-load motor.
*2 For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*3 For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
NOTE
• During fast-response operation, the carrier frequency is always 4 kHz. (Refer to page 339.)
• The inverter overload trip (E.THT) is more likely to occur when fast-response operation is set at the SLD or LD rating.
NOTE
• Since current is not detected and voltage is not output, monitors related to current and voltage such as output current and
output voltage, etc. and output signals do not function.
• For speed calculation, speed is calculated in consideration of Pr.880 Load inertia ratio.
• Since current synchronization operation occurs during the test operation for PM sensorless vector control, the output
frequency becomes the same value as the command frequency.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
218 5. PARAMETERS
5.2 Control method
—: Not available
Monitor item
Monitoring on
DU/PU
Output via FM/
CA/AM
Monitor item
Monitoring on
DU/PU
Output via FM/
CA/AM
1
Output frequency ○ ○ PID deviation ○ ○*3
Fault indication ○ — Input terminal status ○ —
Frequency setting value ○ ○ Output terminal status ○ — 2
Option input terminal
Motor speed ○ ○ ○ —
status
Option output terminal
Converter output voltage ○ ○
status
○ — 3
Electronic thermal O/L relay
load factor ×*2 ×*2 Motor thermal load factor ○*4 ○*4
Parameters referred to
Pr.52 Operation panel main monitor selectionpage 424
Pr.158 AM terminal function selectionpage 435
Changing the control method with external terminals (RT signal, X18
signal)
• Control method (V/F control, Advanced magnetic flux vector control, Real sensorless vector control, Vector control) can
be switched using external terminals.
The control method can be switched using either the Second function selection (RT) signal or the V/F switchover (X18)
signal.
• When using the RT signal, set the second motor in Pr.450 Second applied motor and set the second motor's control
method in Pr.451 Second motor control method selection. Turning ON the RT signal enables the second function,
enabling the switchover of the control method.
5. PARAMETERS
5.2 Control method
219
• When using the X18 signal, turning ON the X18 signal switches the presently-selected control method (Advanced magnetic
flux vector control, Real sensorless vector control, Vector control) to the V/F control. Use this method to switch the control
method for one motor. At this time, the second functions including the electronic thermal O/L relay characteristic are not
changed. (To switch the second functions, use the RT signal.)
To input the X18 signal, set "18" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
Second motor control method Pr.453, Pr.454
First motor control method Pr.450 setting Pr.451 setting
(RT signal-ON) settings
9999 — —
V/F control — — 9999
— 9999*2 —
Advanced magnetic flux vector
20
control Induction motor
V/F control Real sensorless vector control 10 to 14
0 to 6, 100 to
Induction motor Other than 9999
Vector control 106
IPM/SPM motor 0, 3, 4, 6
Other than
PM sensorless vector control IPM/SPM motor
9999
Same control as the first motor*1 9999 — —
V/F control — *2 —
9999
Advanced magnetic flux vector
Advanced magnetic flux vector control*1 control 20, 9999
Induction motor
Real sensorless vector control*1 Real sensorless vector control 10 to 14
Vector control*1 0 to 6, 100 to
Induction motor Other than 9999
PM sensorless vector control Vector control 106
IPM/SPM motor 0, 3, 4, 6
Other than
PM sensorless vector control IPM/SPM motor
9999
*1 V/F control is set by turning ON the X18 signal. If the X18 signal is unassigned, RT signal performs the same function; Turning ON the RT signal
selects V/F control.
*2 V/F control when Pr.453 or Pr.454 is set to "9999" regardless of the Pr.451 setting. When Pr.450 is set to the IPM motor MM-CF, PM sensorless
vector control is enabled even if Pr.453 ≠ "9999" or Pr.454 = "9999".
NOTE
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• The RT signal is a second function selection signal. The RT signal also enables other second functions. (Refer to page 500.)
• The control method could be changed by external terminals (RT signal, X18 signal) while the inverter is stopped. If a signal is
switched during the operation, the control method changes after the inverter stops.
*1 When Pr.450 Second applied motor ="9999", the first motor is selected even if the RT signal turns ON.
NOTE
• Pr.862 setting is valid even when either the plug-in option or control terminal option is installed. For using the control terminal
option alone, the motor does not run when Pr.862 is the initial value as it is. (When the RT signal is OFF)
220 5. PARAMETERS
5.2 Control method
Changing the control mode with external terminals (MC signal)
• To use ON/OFF of the MC signal to switch the control mode, set Pr.800 or Pr.451. Refer to page 217and set Pr.800 or 1
Pr.451.
To input the MC signal, set "26" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
• When using an analog input terminal (terminal 1, 4) for torque limit and torque command, switching of the control mode 2
changes the terminal function as follows:
• Functions of the terminal 1 under different control modes
Speed control/torque control Speed control/position control Position control/torque control 3
Pr.868 switchover*1 switchover*2 switchover*3
setting Speed control Torque control Speed control Position control Position control Torque control
(MC signal-OFF) (MC signal-ON) (MC signal-OFF) (MC signal-ON) (MC signal-OFF) (MC signal-ON)
0
Auxiliary speed Speed limit Auxiliary speed Speed limit
4
(initial — —
setting assistance setting assistance
value)
Magnetic flux Magnetic flux Magnetic flux Magnetic flux Magnetic flux Magnetic flux
1
command*4 command*4 command*4 command*4 command command 5
Regenerative Regenerative Regenerative Regenerative
2 driving torque limit — driving torque limit driving torque limit driving torque limit —
(Pr.810 = 1) (Pr.810 = 1) (Pr.810 = 1) (Pr.810 = 1)
Torque command Torque command 6
3 — — — —
(Pr.804 = 0) (Pr.804 = 0)
Torque limit Torque command Torque limit Torque limit Torque limit Torque command
4
(Pr.810 = 1) (Pr.804 = 0) (Pr.810 = 1) (Pr.810 = 1) (Pr.810 = 1) (Pr.804 = 0)
Forward/reverse Forward/reverse
7
5 — rotation speed limit — — — rotation speed limit
(Pr.807 = 2) (Pr.807 = 2)
6
9999
—
—
—
—
Torque bias
—
—
—
—
—
—
—
8
• Terminal 4 functions by control
Speed control/torque control
switchover*1
Speed control/position control
switchover*2
Position control/torque control
switchover*3
9
Pr.858
setting Speed control Torque control Speed control Position control Position control Torque control
(MC signal-OFF) (MC signal-ON) (MC signal-OFF) (MC signal-ON) (MC signal-OFF) (MC signal-ON)
0
Speed command Speed limit Speed command Speed limit 10
(initial — —
value)
(AU signal-ON) (AU signal-ON) (AU signal-ON) (AU signal-ON)*4
Magnetic flux Magnetic flux Magnetic flux Magnetic flux Magnetic flux Magnetic flux
1
command*4*5 command*4*5 command*4*5 command*4*5 command*5 command*5
Torque limit Torque limit Torque limit Torque limit
4 — —
(Pr.810 = 1)*6 (Pr.810 = 1)*6 (Pr.810 = 1)*6 (Pr.810 = 1)*6
9999 — — — — — —
— : No function
*1 Real sensorless vector control (Pr.800 = "12"), vector control (Pr.800 = "2")
*2 Vector control (Pr.800 = "4"), PM sensorless vector control (Pr.800="14")
*3 Vector control (Pr.800 = "5")
*4 This function is valid under vector control.
*5 Invalid when Pr.868 = "1”.
*6 Invalid when Pr.868 = "4”.
NOTE
• Switching between the speed control and the torque control is always enabled regardless of the motor status: in a stop, in
running, or in DC injection brake (during pre-excitation).
• During operation, switching between speed control and position control or between torque control and position control occurs
when the output frequency reaches Pr.865 Low speed detection or lower with no position command given.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.450 Second applied motorpage 505
Pr.804 Torque command source selectionpage 270
Pr.807 Speed limit selectionpage 274
5. PARAMETERS
5.2 Control method
221
Pr.810 Torque limit input method selectionpage 235
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignmentpage 477
• To use the Advanced magnetic flux vector control, set the motor capacity, the number of motor poles, and the motor type using
Pr.80 and Pr.81.
Other manufacturer’s
constant-torque motor
— 1 (13) Offline auto tuning is required.*2
4. Set the motor capacity and number of motor poles (Pr.80, Pr.81). (Refer to page 215.)
V/F control is performed when the setting is "9999" (initial value).
5. Set the rated motor voltage and frequency (Pr.83, Pr.84). (Refer to page 509.)
As required
• Perform the offline auto tuning (Pr.96). (Refer to page 509.)
• Select the online auto tuning (Pr.95). (Refer to page 527.)
222 5. PARAMETERS
5.2 Control method
NOTE
• To perform driving in a better accuracy, perform offline auto tuning, then set the online auto tuning, and select Real sensorless 1
vector control.
• Under this control, rotations are more likely to be uneven than under V/F control. (This control method is not suitable for
grinder, wrapping machine, etc., which require even rotation at a low speed.)
• For the FR-A820-03160(55K) or lower and the FR-A840-01800(55K) or lower, the operation with a surge voltage suppression 2
filter (FR-ASF-H/FR-BMF-H) installed between the inverter and the motor may reduce the output torque.
• The optional sine wave filter (MT-BSL/BSC) cannot be used between the inverter and the motor.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
3
Keeping the motor speed constant when the load fluctuates (speed 4
control gain)
Initial Setting
Pr. Name
value range
Description 5
Makes adjustments to keep the motor speed constant during variable load
Speed control gain
89 0 to 200% operation under Advanced magnetic flux vector control. The reference
(Advanced magnetic flux 9999
G932 value is 100%.
vector)
9999 The gain set by Pr.71. (The gain set in accordance with the motor.) 6
Makes adjustments to keep the second motor speed constant during
569 Second motor speed 0 to 200% variable load operation under Advanced magnetic flux vector control. The
9999
G942 control gain
9999
reference value is 100%.
The gain set by Pr.450. (The gain set in accordance with the motor.)
7
• Use Pr.89 to keep the motor speed constant during variable load operation.
(This parameter is useful to make adjustments on the motor speed after replacing a conventional model with an FR-A800
series model.)
8
9
Load torque
10
Speed
NOTE
• The RT signal is a Second function selection signal. The RT signal also enables other second functions. (Refer to page 500.)
The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.71, Pr.450 Applied motorpage 505
Pr.800, Pr.451 Control method selectionpage 215
5. PARAMETERS
5.2 Control method
223
5.2.4 Selecting the PM sensorless vector control
PM
• The parameters required to drive an MM-CF IPM motor are automatically changed as a batch. (Refer to page 225.)
• [PM] indicator on the operation panel (FR-DU08) is turned ON when the PM sensorless vector control is set.
The following shows the procedure to initialize the parameter settings for an MM-CF IPM motor by selecting IPM parameter
initialization on the operation panel.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Turn to change the value to " ", and press to confirm it.
" " and " " are displayed alternately. The setting is completed.
Setting Description
0 Parameter settings for an induction motor
3003 Parameter settings for MM-CF IPM motor (rotations per minute)
NOTE
• If parameters are initialized for a PM motor in the IPM initialization mode, the Pr.998 PM parameter initialization setting is
automatically changed.
• In the initial parameter setting, the capacity same as the inverter capacity is set in Pr.80 Motor capacity. To use a motor
capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity by selecting the mode on the operation
panel.
• To set a speed by adjusting frequencies or to monitor it, use Pr.998. (Refer to page 225.)
224 5. PARAMETERS
5.2 Control method
Initializing the parameters required for the PM sensorless vector control
(Pr.998) 1
• PM parameter initialization sets parameters required for driving an IPM motor MM-CF.
• The offline auto tuning enables the operation with an IPM motor other than MM-CF and with SPM motors.
• Two MM-CF PM parameter initialization methods are available; setting Pr.998 PM parameter initialization, and selecting 2
IPM initialization (" ") on the operation panel.
Pr. Name
Initial
value
Setting
range
Description 3
Parameter settings for an induction motor The parameter settings required to drive
0
(frequency) an induction motor are set.
3003
parameter settings for MM-CF IPM motor
(rotations per minute) The parameters settings required to drive
4
parameter settings for MM-CF IPM motor an IPM motor are set.
3103
(frequencies)
8009
The parameter settings required to drive an
IPM motor other than MM-CF are set.
5
The parameters settings required to drive
(rotations per minute) (after tuning) an IPM motor are set. (Set Pr.71 Applied
998 PM parameter
0 The parameter settings required to drive an motor and perform offline auto tuning in
E430 initialization
8109 IPM motor other than MM-CF are set.
(frequency) (after tuning)
advance. (Refer to page 519.)) 6
The parameters settings required to drive
an SPM motor are set. (rotations per
9009 The parameters settings required to drive
minute)
(after tuning)
an SPM motor are set. (Set Pr.71 Applied 7
motor and perform offline auto tuning in
The parameters settings required to drive advance. (Refer to page 519.))
9109 an SPM motor are set. (frequency)
(after tuning) 8
• To use a motor capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity before performing PM
parameter initialization.
• When Pr.998 = "3003, 8009, or 9009", the monitor is displayed and the frequency is set using the motor rotations per 9
minute. To use frequency to display or set, set Pr.998 = "3103, 8109, or 9109".
• Set Pr.998 = "0" to change the PM sensorless vector control parameter settings to the parameter settings required to drive
an induction motor. 10
• When using an IPM motor or SPM motor other than MM-CF, set Pr.998 = "8009, 8109, 9009, or 9109".
NOTE
• Make sure to set Pr.998 before setting other parameters. If the Pr.998 setting is changed after setting other parameters, some
of those parameters are initialized too. (Refer to "PM parameter initialization list" for the parameters that are initialized.)
• To change back to the parameter settings required to drive an induction motor, perform Parameter clear or All parameter clear.
• If the setting of Pr.998 PM parameter initialization is changed between "3003, 8009, 9009 (rotations per minute)" ↔ "3103,
8109, 9109 (frequency)", the target parameters are respectively set to their initial values.
The purpose of Pr.998 is not to change the display units. Use Pr.144 Speed setting switchover to change the display units
between rotations per minute and frequency. The parameter enables switching of display units between rotations per minute
and frequency without initializing the parameter settings.
Example) Changing the Pr.144 setting between "6" and "106" switches the display units between frequency and rotations per
minute.
• For an inverter out of the capacity range of the IPM motor MM-CF, "3003 or 3103" cannot be set. (Refer to page 798 for the
capacities of MM-CF motors.)
• The PM parameter initialization (Pr.998) changes parameter settings for the first motor. When a PM motor is used as the
second motor, parameters for the second motor must be set individually.
5. PARAMETERS
5.2 Control method
225
• Performing the Parameter clear or the All parameter clear resets these parameter settings to the settings required to drive
an induction motor.
Setting
Induction PM motor (rotations Setting increments
PM motor (frequency)
motor per minute)
Pr. Name 0 (initial value) 8009, 8109,
9009 9109 3003, 0, 3103,
3003 3103
(other (other 8009, 8109,
FM CA (MM-CF) (MM-CF)
than MM- than MM- 9009 9109
CF) CF)
120 Hz*1 Maximum Maximum
motor motor
1 Maximum frequency 3000 r/min rotations 200 Hz 1 r/min 0.01 Hz
60 Hz*2 per frequency*
8
minute*8
Multi-speed setting (high
4 60 Hz 50 Hz 2000 r/min Pr.84 133.33 Hz Pr.84 1 r/min 0.01 Hz
speed)
Rated Rated 0.01 A*1
Inverter motor motor
9 Electronic thermal O/L relay — —
rated current 0.1 A*2
current*10 current*10
Pr.84 × Pr.84 ×
13 Starting frequency 0.5 Hz 8 r/min*5 10% 0.5 Hz*6 10%
1 r/min 0.01 Hz
Pr.84 × Pr.84 ×
15 Jog frequency 5 Hz 200 r/min 13.33 Hz 1 r/min 0.01 Hz
10% 10%
High speed maximum 120 Hz*1
18 3000 r/min — 200 Hz — 1 r/min 0.01 Hz
frequency 60 Hz*2
Acceleration/deceleration
20 60 Hz 50 Hz 2000 r/min Pr.84 133.33 Hz Pr.84 1 r/min 0.01 Hz
reference frequency
Stall prevention operation
22
level 150%*7 150%*7 0.1%
37 Speed display 0 0 1
Frequency monitoring
55 60 Hz 50 Hz 2000 r/min Pr.84 133.33 Hz Pr.84 1 r/min 0.01 Hz
reference
Rated Rated 0.01 A*1
Current monitoring Inverter motor motor
56 Pr.859 Pr.859
reference rated current 0.1 A*2
current*10 current*10
71 Applied motor 0 330*3 — 330*3 — 1
Motor Motor 0.01 kW*1
80 Motor capacity 9999 capacity — capacity —
(MM-CF)*4 (MM-CF)*4 0.1 kW*2
226 5. PARAMETERS
5.2 Control method
Setting
Induction PM motor (rotations Setting increments
motor per minute)
PM motor (frequency) 1
Pr. Name 0 (initial value) 8009, 8109,
9009 9109 3003, 0, 3103,
3003 3103
(other (other 8009, 8109,
FM CA (MM-CF)
than MM-
(MM-CF)
than MM- 9009 9109 2
CF) CF)
Current average value Rated Rated 0.01 A*1
Inverter motor motor
557 monitor signal output Pr.859 Pr.859
reference current
rated current
current*10 current*10 0.1 A*2 3
820 Speed control P gain 1 60% 30% 1%
821 Speed control integral time 1 0.333 s 0.333 s 0.001 s
824
Torque control P gain 1
(current loop proportional 100% 100% 1%
4
gain)
Torque control integral time
825 5 ms 20 ms 0.1 ms
1 (current loop integral time) 5
870 Speed detection hysteresis 0 Hz 8 r/min 0.5 Hz*9 0.5 Hz 1 r/min 0.01 Hz
Regeneration avoidance
Pr.84 × Pr.84 ×
885 compensation frequency 6 Hz 200 r/min 13.33 Hz 1 r/min 0.01 Hz
limit value
10% 10%
6
*1
Energy saving monitor Inverter rated 0.01 kW
893 Motor capacity (Pr.80)
reference (motor capacity) current 0.1 kW*2
C14
(918)
Terminal 1 gain frequency
(speed)
60 Hz 50 Hz 2000 r/min Pr.84 133.33 Hz Pr.84 1 r/min 0.01 Hz 7
120 Hz*1 Maximum Maximum
motor motor
Per-unit speed control
1121
reference frequency 60 Hz*2
3000 r/min rotations
per
200 Hz
frequency*
1 r/min 0.01 Hz 8
8
minute*8
— : Not changed
*1 Initial value for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
9
*2 Initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) and higher.
*3 When Pr.71 Applied motor = "333, 334, 8093, 8094, 9093, or 9094", the Pr.71 setting are not changed.
*4
*5
When a value other than "9999" is set, the set value is not changed.
200 r/min when Pr.788 Low speed range torque characteristic selection = "0". 10
*6 13.33 Hz when Pr.788 Low speed range torque characteristic selection = "0".
*7 110% for SLD, 120% for LD, 150% for ND, and 200% for HD (Refer to Pr.570 Multiple rating setting on page 326.)
*8 The Pr.702 Maximum motor frequency is used as the maximum motor frequency (rotations per minute). When Pr.702 ="9999 (initial value)",
the Pr.84 Rated motor frequency is used as the maximum motor frequency (rotations per minute).
*9 The setting value is converted from frequency to rotations per minute. (It differs according to the number of motor poles.)
*10 Refer to page 798 for the rated motor current of MM-CF.
NOTE
• If IPM parameter initialization is performed in rotations per minute (Pr.998 = "3003, 8009, or 9009"), the parameters not listed
in the table and the monitor items are also set and displayed in rotations per minute.
The torque characteristics in a low-speed range under PM sensorless vector control can be changed.
Initial Setting
Pr. Name Operation status
value range
Disables the low-speed range torque characteristic (current
0
788 Low speed range torque synchronization operation).
9999
G250 characteristic selection Enables the low-speed range torque characteristic (high frequency
9999*1 superposition control)
Disables the low-speed range torque characteristic (current
Second motor low-speed 0
747 synchronization operation) while the RT signal is ON.
range torque characteristic 9999
G350 Enables the low-speed range torque characteristic (high frequency
selection 9999*1 superposition control) while the RT signal is ON.
5. PARAMETERS
5.2 Control method
227
*1 The low-speed range high-torque characteristic (current synchronization operation) is disabled for PM motors other than MM-CF, even if "9999"
is set.
NOTE
• Position control under PM sensorless vector control is not available when the current synchronization operation is selected.
Zero speed and servo lock are also disabled during current synchronization operation.
• For torque characteristics, refer to page 798.
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
228 5. PARAMETERS
5.2 Control method
5.3 Speed control under Real sensorless vector 1
control, vector control, PM sensorless vector
control 2
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
229
Control block diagram
Analog input offset
Terminal 2 bias [C2, C3 (Pr. 902)] adjustment [Pr. 849] Operation Mode
AU Terminal 2 gain [Pr. 125, C4 (Pr. 903)] [Pr. 79]
Terminal 2
Terminal 4 bias [C5, C6 (Pr. 904)] Analog
AU Terminal 4 gain [Pr. 126, C7 (Pr. 905)] input
Terminal 4 selection
[Pr. 858 = 0] [Pr. 73]
Terminal 1
[Pr. 868 = 0]
RT [Pr.822=9999]
[Pr. 822]
Speed setting [Pr. 74]
filter [Pr. 822 = 9999]
RT [Pr. 832 = 9999] [Pr. 832]
[Pr. 74]
[Pr. 832 = 9999]
RL Multi-speed
RM selection
[Pr. 4 to 6,
RH 24 to 27,
REX 232 to 239]
Option
Operation panel
Acceleration/deceleration processing
Maximum/minimum setting
[Pr. 1] Running
[Pr. 13] [Pr. 10]
[Pr. 2] A
[Pr. 7] [Pr. 8] During stop
Vector control
[Pr. 800 = 0]
PM sensorless vector control
[Pr. 802 = 1] LX [Pr. 800 = 9, 13, 14]
Servo lock
zero speed control
[Pr. 802 = 0]
Real sensorless
Decelerates to stop
Vector control
[Pr. 11] LX
Zero speed control [Pr. 800 = 10]
Decelerates to stop
[Pr. 850 = 1] [Pr. 11] LX
Zero speed control
DC injection brake operation
[Pr. 850 = 0]
230 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Speed feed forward control
Speed feed forward Speed feed
torque limit
[Pr. 879]
forward
filter [Pr. 878]
1
Load inertia ratio Speed feed forward
J.s gain
[Pr. 880] [Pr. 881]
2
Model adaptive speed control
J [Pr. 880]
Torque
coefficient
Model speed
3
calculation
[Pr. 877 = 1]
Speed Notch +
RT + Model speed 1 RT +
+ control filter + B
A control gain
4
[Pr. 877 = 2] - P gain 1 [Pr. 1003]
[Pr. 828] J .s - +
[Pr. 877 = 0] [Pr. 820] Speed control [Pr. 1004]
X44
integral [Pr. 1005]
time 1
[Pr. 821]
Integration
X44 cleared to 0
0
When torque bias is selected Torque bias
operation
5
RT Speed time [Pr. 845]
RT control +
P gain 2
[Pr. 830] +
6
Speed control
X44 integral
time 2
[Pr. 831]
Integration
X44 cleared to 0
0
When torque bias is selected Torque bias operation time [Pr. 845]
Vector control
Speed detection filter
7
[Pr. 800 = 0]
Communication option
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
231
5.3.1 Setting procedure of Real sensorless vector
control (speed control)
Sensorless
Operating procedure
1. Perform secure wiring. (Refer to page 46.)
3. Set the overheat protection of the motor (Pr.9). (Refer to page 394.)
4. Set the motor capacity and number of motor poles (Pr.80 and Pr.81). (Refer to page 215.)
V/F control is performed when the setting is "9999" (initial value).
5. Set the rated motor voltage and the rated motor frequency (Pr.83 and Pr.84). (Refer to page 509.)
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The speed command setting range under Real sensorless vector control is 0 to 400 Hz.
• The carrier frequency is limited during Real sensorless vector control. (Refer to page 339.)
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower). Vector control must be selected.
• Performing pre-excitation (LX signal and X13 signal) under torque control may start the motor running at a low speed even
when the start signal (STF or STR) is not input. The inverter at a start command ON may also rotate the motor at a low speed
even though a speed limit value is set to zero Therefore, confirm that the motor running will not cause any safety problem
before performing pre-excitation.
• Switching between the Forward rotation command (STF) and Reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• When performing continuous operations under Real sensorless vector control in FR-A820-00250(3.7K) or lower or FR-A840-
00126(3.7K) or lower, the speed fluctuation increases when the value is 20 Hz or less, and in the low-speed range of less than
1 Hz, there may be torque shortage. In such case, stop the inverter and restart it to improve the situation.
• In case of starting the motor while the motor is coasting under Real sensorless vector control, the frequency search must be
set for the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10"). (Refer to page 597.)
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 or 10 poles) (available
at 60 Hz or higher when the rating is 60 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
232 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
5.3.2 Setting procedure of Vector control (speed control)
Vector 1
Operating procedure
1. Perform secure wiring. (Refer to page 90.) 2
Install a Vector control compatible option.
4. Set the overheat protection of the motor (Pr.9). (Refer to page 394.) 4
When using the SF-V5RU or a motor equipped with a thermal sensor, set Pr.9 = 0 A.
5. Set the motor capacity and number of motor poles (Pr.80 and Pr.81). (Refer to page 215.)
5
V/F control is performed when the setting is "9999" (initial value).
6. Set the rated motor voltage and the rated motor frequency (Pr.83 and Pr.84). (Refer to page 509.)
NOTE
• The speed command setting range under Vector control is 0 to 400 Hz.
• The carrier frequency is limited during Vector control. (Refer to page 339.)
• For Vector control for a motor with a resolver, refer to the Instruction Manual of the FR-A8APR.
This inverter is set for a general-purpose motor in the initial setting. Follow the following procedure to change the setting for the
PM sensorless vector control.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
233
Driving an MM-CF IPM motor
Operating procedure
1. Perform IPM parameter initialization. (Refer to page 224.)
Set "3003 or 3103" in Pr.998 PM parameter initialization, or select "3003" in “ " (IPM initialization).
Setting Description
Parameter settings for MM-CF IPM motor (rotations
3003
per minute)
Parameter settings for MM-CF IPM motor
3103
(frequencies)
As required
• Perform offline auto tuning for a PM motor. (Refer to page 519.)
NOTE
• To change to the PM sensorless vector control, perform PM parameter initialization at first. If parameter initialization is
performed after setting other parameters, some of those parameters are initialized too. (Refer to page 225 for the parameters
that are initialized.)
• To use a motor capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity before performing PM
parameter initialization.
• The speed setting range for an MM-CF IPM motor is between 0 and 200 Hz.
• The carrier frequency is limited during PM sensorless vector control. (Refer to page 339.)
• Constant-speed operation cannot be performed in the low-speed range of 200r/min or less under current synchronization
operation. (Refer to page 227.)
• During PM sensorless vector control, the RUN signal is output about 100 ms after turning ON the start command (STF, STR).
The delay is due to the magnetic pole detection.
• During PM sensorless vector control, the automatic restart after instantaneous power failure function operates only when an
MM-CF IPM motor is connected
When a built-in brake or a regeneration unit is used, the frequency search may not be available at 2200 r/min or higher.
The restart operation cannot be performed until the motor speed drops to a frequency where the frequency search is available.
2. Perform the offline auto tuning for a PM motor (Pr.96). (Refer to page 519.)
Set "1" (offline auto tuning without rotating motor (for other than MM-CF)) in Pr.96, and perform tuning.
234 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
3. Configure the initial setting for the PM sensorless vector control using Pr.998. (Refer to page 225.)
When the setting for the PM motor is selected in Pr.998 PM parameter initialization, the PM sensorless vector
control is selected. [PM] on the operation panel (FR-DU08) is lit when the PM sensorless vector control is set.
1
Setting Description
Parameter settings for an IPM motor other than MM-CF
8009
(rotations per minute) 2
Parameter settings for an IPM motor other than MM-CF
8109
(frequency)
9009
Parameter settings for an SPM motor (rotations per
minute)
3
9109 Parameter settings for an SPM motor (frequency)
6
NOTE
• To change to the PM sensorless vector control, perform PM parameter initialization at first. If parameter initialization is
performed after setting other parameters, some of those parameters are initialized too. (Refer to page 225 for the parameters
that are initialized.)
7
• To use a motor capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity before performing PM
parameter initialization.
• The carrier frequency is limited during PM sensorless vector control. (Refer to page 339.) 8
• Constant-speed operation cannot be performed in the low-speed range of 200r/min or less under current synchronization
operation. (Refer to page 227.)
• During PM sensorless vector control, the RUN signal is output about 100 ms after turning ON the start command (STF, STR).
The delay is due to the magnetic pole detection.
9
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
235
Setting
Pr. Name Initial value Description
range
0 to 400% Set the torque current limit level.
801
Output limit level 9999 The torque limit setting value is used for limiting the torque current
H704 9999
level.
The motor power output is
The torque rises in the low-
0 limited to be constant in the
speed range.
constant power range.
The torque is limited to be
The torque is kept constant in
1 constant in the constant power
the low-speed range.
range.
The torque is limited to be
Constant output range The torque is kept constant in constant in the constant power
803
torque characteristic 0 2 the low-speed range. (The range unless the output limit of
G210
selection torque current is limited.) the torque current is reached.
(The torque current is limited.)
The motor power output is
The torque is kept constant in
10 limited to be constant in the
the low-speed range.
constant power range.
The torque is limited to be
The torque rises in the low-
11 constant in the constant power
speed range.
range.
0 The internal torque limit 2 cannot be used.
Torque limit by the parameter setting (Pr.805 or Pr.806)
1
(-400 to 400%)
2 The internal torque limit 2 cannot be used.
804 Torque command source
0 Torque limit through the CC-Link/CC-Link IE Field Network
D400 selection 3
communication (FR-A8NC, FR-A8NCE, FR-A800-GF)
4 The internal torque limit 2 cannot be used
5 Torque limit through the CC-Link/CC-Link IE Field Network
6 communication (FR-A8NC, FR-A8NCE, FR-A800-GF)
805 Torque command value 600 to Writes the torque limit value in RAM. Regards 1000% as 0%, and
1000%
D401 (RAM) 1400% set torque command by an offset of 1000%.
Writes the torque limit value in RAM and EEPROM.
806 Torque command value 600 to
1000% Regards 1000% as 0%, and set torque command by an offset of
D402 (RAM, EEPROM) 1400%
1000%.
0 Internal torque limit 1 (torque limited by parameter settings)
810 Torque limit input method
0 1 External torque limit (torque limited by terminals 1 and 4)
H700 selection
2 Internal torque limit 2 (torque limited by communication options)
Speed setting, running speed
0
monitor increments 1 r/min Torque limit setting increments
Speed setting, running speed 0.1%
1
811 monitor increments 0.1 r/min
Set resolution switchover 0
D030 Speed setting, running speed
10
monitor increments 1 r/min Torque limit setting increments
Speed setting, running speed 0.01%
11
monitor increments 0.1 r/min
812 Torque limit level 0 to 400% Set the torque limit level for forward rotation regenerative driving.
9999
H701 (regeneration) 9999 Limit using Pr.22 or the analog terminal values.
813 Torque limit level (3rd 0 to 400% Set the torque limit level for reverse rotation power driving.
9999
H702 quadrant) 9999 Limit using Pr.22 or the analog terminal values.
814 Torque limit level (4th 0 to 400% Set the torque limit level for reverse rotation regenerative driving.
9999
H703 quadrant) 9999 Limit using Pr.22 or the analog terminal values.
When the torque limit selection (TL) signal is ON, Pr.815 is the
815 0 to 400%
Torque limit level 2 9999 torque limit value regardless of Pr.810.
H710
9999 The torque limit set to Pr.810 is valid.
816 Torque limit level during 0 to 400% Set the torque limit value during acceleration.
9999
H720 acceleration 9999 The same torque limit as constant speed.
817 Torque limit level during 0 to 400% Set the torque limit value during deceleration.
9999
H721 deceleration 9999 The same torque limit as constant speed.
858 Terminal 4 function The torque limit level can be changed with setting value "4" and the
0 0, 1, 4, 9999
T040 assignment signal to terminal 4.
868 Terminal 1 function The torque limit level can be changed with setting value "4" and the
0 0 to 6, 9999
T010 assignment signal to terminal 1.
236 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Setting
Pr. Name Initial value Description
range
874
OLT level setting 150% 0 to 400%
The inverter can be set to be shut off at activation of torque limit 1
H730 and stalling of the motor. Set the output to be shut off.
*1 When changing from V/F control or Advanced magnetic flux vector control to Real sensorless vector control or Vector control in FR-A820-
00250(3.7K) or lower or FR-A840-00126(3.7K) or lower, 150% changes to 200%.
2
NOTE
• The lower limit for the torque limit level under Real sensorless vector control is set to 30% even if a value lower than 30% is set.
• When the low-speed range high-torque characteristic is disabled under PM sensorless vector control (Pr.788 = "0"), the torque
limit is not activated in a low-speed range with a rated frequency of less than 10%.
3
• Under PM sensorless vector control, the torque limit level is reduced inversely proportional to the output frequency in the
constant output range of the rated motor frequency or higher.
4
Block diagram of torque limit
<Vector control>
Speed control
Torque limit
Iq current control
5
Speed command +
IM
-
6
Encoder
Reverse Forward
regeneration driving
Reverse quad4 quad1 Forward
rotation (Pr.814) (Pr.22) rotation
Speed
quad3 quad2
(Pr.813) (Pr.812)
Reverse Forward
driving regeneration
-
Rated speed
Torque limit level using analog input (terminals 1, 4) (Pr.810 = "1", Pr.858,
Pr.868)
• The torque is limited with the analog input of terminal 1 or terminal 4. (External torque limit)
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
237
• Torque limit using analog input is valid with a limit value lower than the internal torque limit (Pr.22, Pr.812 to Pr.814). (If
the torque limit using analog input exceeds the internal torque limit, the internal torque limit is valid.)
• When inputting the torque limit value from terminal 1, set Pr.868 Terminal 1 function assignment = "4". When inputting
from terminal 4, set Pr.858 Terminal 4 function assignment = "4".
• When Pr.858 = "4" and Pr.868 = "2", the torque for regenerative driving is limited with the terminal 1 analog input, and the
torque for power driving is limited with the terminal 4 analog input.
Torque limit
+ Torque limit
+
Reverse Forward
Reverse regeneration driving
Forward
regeneration driving Terminal 4 input or Terminal 4 input or
internal torque limit internal torque limit
Reverse quad4 quad1 Forward whichever is smaller whichever is smaller
∗ (Pr. 814) (Pr. 22) ∗ quad4
rotation rotation Reverse rotation quad1 Forward rotation
Speed Speed
∗ quad3 quad2 ∗
(Pr. 813) (Pr. 812) Terminal 4 input or quad3 quad2 Terminal 4 input or
internal torque limit internal torque limit
Reverse Forward whichever is smaller whichever is smaller
driving regeneration Reverse Forward
driving regeneration
- -
Rated speed Rated speed
∗ Analog input (terminal 1, 4) or internal torque control (Pr. 22 etc.) whichever is smaller
When Pr. 858=4, Pr. 868=2
• The torque limit using analog input can be corrected with the calibration parameters C16 (Pr.919) to C19 (Pr.920), and
C38 (Pr.932) to C41 (Pr.933). (Refer to page 487.)
Torque(%)
400 400
Torque(%)
150 150
Gain Gain
C18(Pr.920) C40(Pr.933)
Bias Initial Bias
Initial
C16(Pr.919) value C38(Pr.932)
value
0 100% 0 20 100%
0 Torque setting signal 5V 0 4 20mA
0 10V Torque setting signal
C17(Pr.919) C19(Pr.920) C39(Pr.932) C41(Pr.933)
NOTE
• When inputting an analog signal to the terminal 1, give a positive voltage (0 to +10 V (+5 V)).
When a negative voltage (0 to -10 V (-5 V)) is input, the torque limit value set by the analog signal becomes "0".
238 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
• Functions of terminals 1 and 4 by control (— : no function)
Pr.858 setting*1 Terminal 4 function Pr.868 setting*2
0 (initial value)
Terminal 1 function
Speed setting assistance
1
1*4 Magnetic flux command*4
2 —
0
Speed command (AU signal-ON)
3 — 2
(initial value) 4 Torque limit (Pr.810 = 1)
5 —
6 Torque bias (Pr.840 = 1 to 3) 3
9999 —
Magnetic flux command*4 0 (initial value) Speed setting assistance
*3 *4
Magnetic flux command*4
— 1
2 —
4
3 —
1*4
4 Torque limit (Pr.810 = 1)
Magnetic flux command*4
5 — 5
6 Torque bias (Pr.840 = 1 to 3)
9999 —
0 (initial value) Speed setting assistance
Torque limit (Pr.810 = 1)
1*4 Magnetic flux command*4
6
Power driving torque limit (Pr.810 =1) 2 Regenerative torque limit (Pr.810=1)
Torque limit (Pr.810 = 1) 3 —
4*2
— *3 4 Torque limit (Pr.810 = 1) 7
5 —
Torque limit (Pr.810 = 1) 6 Torque bias (Pr.840=1 to 3)
9999 — 8
9999 — — —
*1 When Pr.868 ≠ "0", the other functions of terminal 1 (auxiliary input, override function, PID control) do not operate.
*2 When Pr.858 ≠ "0", PID control and speed commands using terminal 4 do not operate even when the AU signal is ON.
*3 When both Pr.858 and Pr.868 are "1" (magnetic flux command) or "4" (torque limit), the function of terminal 1 has higher priority, and terminal 4 9
does not function.
*4 Valid when Vector control compatible options are installed and the Vector control is selected.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
239
Torque limit
+
Reverse regeneration Forward driving
Pr.805(Pr.806) Pr.805(Pr.806)
RWwC, RWw2 quad4 quad1 RWwC, RWw2
Speed
Pr.805(Pr.806) quad3 quad2 Pr.805(Pr.806)
RWwC, RWw2 RWwC, RWw2
Reverse driving Forward regeneration
Torque limit
+
Reverse regeneration Forward driving
RWwF
quad4 RWwC
quad1
Speed
RWwE quad3 quad2 RWwD
NOTE
• When "2" is set in Pr.810 while the communication option is not connected, a protective function (E.OPT) is activated. (PLC
function disabled)
• For the details of the FR-A8NC and the FR-A8NCE, refer to the Instruction Manual of each option. For the details of the CC-
Link IE Field Network, refer to page 716.
Reverse Forward
regeneration driving
Pr.815 Pr.815
- quad4 quad1 +
Speed
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
240 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Setting the torque limit values during acceleration/deceleration
individually (Pr.816, Pr.817) 1
• The torque limit during acceleration and deceleration can be set individually. Torque limit using the setting values of Pr.816
Torque limit level during acceleration and Pr.817 Torque limit level during deceleration is as follows.
• If 1 s elapses while the difference between the set speed and rotation speed is within ±2 Hz, the torque limit level during 2
acceleration/deceleration (Pr.816 or Pr.817) changes to the torque control level during constant speed (Pr.22).
• When the difference between the set speed and rotation speed is -2 Hz or less, the torque limit level during deceleration
Torque limit level during deceleration (Pr.817) activates. 3
Output
frequency
(Hz) -2 Hz < set speed - rotation speed < 2 Hz
Set
frequency
4
-2 Hz set speed - rotation speed
5
Torque limit Time
level Acceleration Constant speed Deceleration
Pr.816
6
Pr.817
1s
NOTE
• The Pr.816 and Pr.817 settings are invalid under position control.
8
*1 For the details of the increments of speed setting and running speed monitoring, refer to page 422.
NOTE
• The internal resolution of the torque limit is 0.024% (100/212), and fractions below this resolution are rounded off.
• When Real sensorless vector control is selected, fractions below a resolution equivalent to 0.1% are rounded off even if Pr.811
= "10 or 11" is set.
• For details on changing the speed setting increments, refer to page 422.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
241
• Use Pr.85 Excitation current break point to change the low-speed range, and use Pr.86 Excitation current low speed
scaling factor to change the torque in the low-speed range. When Pr.85 = "9999 (initial value)", a predetermined
frequency is used. When Pr.86 = "9999 (initial value)", a predetermined scaling factor is used (refer to page 677).
*1 This is applicable only under Real sensorless vector control. The upper limit of the torque at 0 Hz is determined by multiplying the torque limit in
the constant-torque range by the scaling factor set in Pr.86.
• To avoid overload or overcurrent of the inverter or motor, use Pr.801 Output limit level to limit the torque current.
Pr.801 setting Description
0 to 400% Set the torque current limit level.
9999 The torque limit setting value (Pr.22, Pr.812 to Pr.817, etc.) is used for limiting the torque current.
Pr.803=0 Pr.803=1
Torque Torque
Low-speed Constant torque Low-speed Constant torque
range range Constant power range range range Constant power range
Pr.803=2
Torque
Low-speed Constant torque
range range Constant power range
Pr.803=10 Pr.803=11
Torque Torque
Low-speed Constant torque Low-speed Constant torque
range range Constant power range range range Constant power range
NOTE
• When the torque limit setting value (Pr.22, Pr.812 to Pr.817, etc.) is less than the value set in Pr.801, the Pr.801 setting is
used for limiting the torque current.
242 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
• When a high load is applied and the torque limit is activated under speed control or position control, the motor stalls. At
this time, if a state where the rotation speed is lower than the value set in Pr.865 Low speed detection and the output
torque exceeds the level set in Pr.874 OLT level setting continues for 3 seconds, Stall prevention stop (E.OLT) is
1
activated and the inverter output is shut off.
Torque
2
Pr.874 Torque limit
Output torque
Time 3
Output
frequency
Pr.865
4
Time
Start signal
5
(STF)
3s
Fault signal
(ALM) E.OLT occurrence
NOTE 6
• Under V/F control or Advanced magnetic flux vector control, if the output frequency drops to 0.5 Hz due to the stall prevention
operation and this state continues for 3 seconds, a fault indication (E.OLT) appears, and the inverter output is shut off. This
operation is activated regardless of the Pr.874 setting.
• This fault does not occur under torque control. 7
Adjusting the signal output under torque limit operation and output 8
timing (OL signal, Pr.157)
• If the output torque exceeds the torque limit level and the torque limit is activated, the overload warning (OL signal) is turned
ON for 100 ms or longer. When the output torque drops to the torque limit level or lower, the output signal also turns OFF. 9
• Pr.157 OL signal output timercan be used to set whether to output the OL signal immediately, or whether to output it after
a certain time period has elapsed.
Pr.157 setting Description 10
0 (initial value) Output immediately.
0.1 to 25 Output after the set time (s).
9999 Not output.
• The OL signal is also output during the regeneration avoidance operation (" " display (overvoltage stall)).
Overload state
(OL operation)
OL output signal
NOTE
• OL signal is assigned to the terminal OL in the initial status. The OL signal can also be assigned to other terminals by setting
"3 (positive logic) or 103 (negative logic)" in any of Pr.190 to Pr.196 (output terminal function selection).
• Changing the terminal assignment using Pr.190 to Pr.196 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.22 Stall prevention operation levelpage 409
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.840 Torque bias selectionpage 255
Pr.865 Low speed detectionpage 461
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
243
5.3.5 Performing high-accuracy, fast-response control
(gain adjustment for Real sensorless vector
control, Vector control, and PM sensorless vector
control)
Sensorless Vector PM
The load inertia ratio (load moment of inertia) for the motor is calculated in real time from the torque command and rotation
speed during motor driving by the Vector control. Because the optimum gain for speed control and position control is set
automatically from the Load inertia ratio and the response level, the work required for gain adjustment is reduced. (Easy gain
tuning)
If the load inertia ratio cannot be calculated due to load fluctuations, or under Real sensorless vector control or PM sensorless
vector control, the control gain can be set automatically by entering the load inertia ratio manually.
Manual gain adjustment is useful for achieving optimum machine performance or improving unfavorable conditions, such as
vibration and acoustic noise during operation with high load inertia or gear backlash.
Initial Setting
Pr. Name Description
value range
818 Easy gain tuning response level Set the response level.
2 1 to 15
C112 setting 1 (Slowest) to 15 (Fastest)
0 No easy gain tuning
819 Gain is calculated with load calculation
Easy gain tuning selection 0 1
C113 (This function is valid under Vector control.)
2 Gain is calculated with load (Pr.880) manual input
The proportional gain during speed control is set. (Setting this
820 parameter higher improves the trackability for speed command
Speed control P gain 1 60% 0 to 1000%
G211 changes. It also reduces the speed fluctuation caused by external
disturbance.)
The integral time during speed control is set. (Setting this
821
Speed control integral time 1 0.333 s 0 to 20 s parameter lower shortens the return time to the original speed
G212
when the speed fluctuates due to external disturbance.)
830 0 to 1000% Second function of Pr.820 (valid when RT signal is ON)
Speed control P gain 2 9999
G311 9999 The Pr.820 setting is applied to the operation.
831 0 to 20 s Second function of Pr.821 (enabled when the RT signal is ON)
Speed control integral time 2 9999
G312 9999 The Pr.821 setting is applied to the operation.
880
Load inertia ratio 7-fold 0 to 200-fold Set the load inertia ratio for the motor.
C114
1115 Speed control integral term Set time until the integral term is reduced and cleared after P
0 ms 0 to 9998 ms
G218 clear time control switching.
1116 Constant output range speed Set a compensation amount of the speed control P gain in the
0% 0 to 100%
G206 control P gain compensation constant output range (rated speed or higher).
1117 Speed control P gain 1 (per-unit 0 to 300 Set a proportional gain under speed control in the per-unit system.
9999
G261 system) 9999 The Pr.820 setting is applied to the operation.
1118 Speed control P gain 2 (per-unit 0 to 300 Second function of Pr.1117 (valid when RT signal ON)
9999
G361 system) 9999 The Pr.1117 setting is applied to the operation.
1121 Per-unit speed control 120 Hz*1 Set the speed at 100% when setting speed control P gain or
0 to 400 Hz
G260 reference frequency 60 Hz*2 model speed control gain in the per-unit system.
1348 P/PI control switchover
0 Hz 0 to 400 Hz Set the motor speed for the P/PI control switchover.
G263 frequency
*1 For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*2 For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
244 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Block diagram of easy gain tuning function
<Vector control> Automatic setting Load
inertia
1
moment
Detector
Command
+
-
Speed control/position loop gain
Model speed control gain
+
-
Current
control
Motor Encoder 2
[Pr.820, Pr.821, Pr.828, Pr.422]
5
Response level
setting [Pr.818]
Speed/position feedback 6
NOTE
• Easy gain tuning is valid for the first motor. When applying the second motor (RT signal is ON), tuning is not performed. 7
Execution procedure for easy gain tuning (Pr.819 = "1" Load inertia ratio
automatic calculation) 8
Easy gain tuning (load inertia ratio automatic calculation) is only valid in the speed control and position control modes of Vector
control. It is invalid under torque control, V/F control, Advanced magnetic flux vector control, Real sensorless vector control,
and PM sensorless vector control.
9
1. Set the response level in Pr.818 Easy gain tuning response level setting.
Setting this parameter higher improves the trackability for commands, but setting it too high causes vibration. The 10
following figure shows the relationship between the setting and the response level.
Pr. 818 setting 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Slowest Middle Fastest
Response level response response response
Guideline of
mechanical resonance 8 10 12 15 18 22 28 34 42 52 64 79 98 122 150
frequency (Hz)
2. The load inertia ratio is calculated during acceleration/deceleration, and from this value and the value of Pr.818 Easy
gain tuning response level setting, the gain for each control is set automatically.
Pr.880 Load inertia ratio is used as the initial value of the load inertia ratio when performing tuning. During tuning,
the estimated value is set in Pr.880.
The calculation of the load inertia ratio may take excessive time or otherwise not be performed properly if the
following conditions are not satisfied.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
245
• The time in acceleration/deceleration driving until 1500 r/min is reached in 5 s or less.
• The rotation speed in driving is 150 r/min or higher.
• The acceleration/deceleration torque is 10% or higher.
• No sudden external disturbances during acceleration/deceleration.
• The load inertia ratio is about 30-fold or lower.
• No gear backlash or belt sagging.
3. Press or to calculate the continuous load inertia ratio, or calculate the gain.
(The operation command during External operation is the STF or STR signal.)
Execution procedure for easy gain tuning (Pr.819 = "2" Load inertia ratio
manual input)
Easy gain tuning (Load inertia ratio manual input) is valid in the speed control mode under Real sensorless vector control, the
speed control and position control modes under Vector control, and the speed control mode under PM sensorless vector
control.
1. Set the load inertia ratio for the motor in Pr.880 Load inertia ratio.
2. Set "2" (easy gain tuning enabled) in Pr.819 Easy gain tuning selection. After setting, Pr.820 Speed control P
gain 1 and Pr.821 Speed control integral time 1 are set automatically.
Operation is performed with the adjusted gain from the next operation.
3. Perform the test operation, and set the response level in Pr.818 Easy gain tuning response level setting. Setting
this parameter higher improves the trackability for commands, but setting it too high causes vibration. (The response
level can be adjusted during operation when Pr.77 Parameter write selection ="2" (parameters can be written
during operation).)
NOTE
• When Pr.819 = "1 or 2" is set, even if the Pr.819 setting value is returned to "0" after tuning is performed, the data that was
set in each parameter is retained in the tuning results.
• If good precision cannot be obtained even after executing easy gain tuning, because of external disturbances or other reasons,
perform fine adjustment manually. At this time, set the setting value of Pr.819 to "0" (no easy gain tuning).
NOTE
• If easy gain tuning is executed at an inertia equal to or higher than the specified value under Vector control, a fault such as
hunting may occur. Also, if the motor shaft is fixed by the servo lock or position control, the bearing may be damaged. In this
case, do not perform easy gain tuning. Adjust the gain manually.
• The load inertia ratio is only calculated under Vector control.
246 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Adjusting the speed control gain manually (Pr.819 = "0" No easy gain
tuning) 1
• The speed control gain can be adjusted for the conditions such as abnormal machine vibration, acoustic noise, slow
response, and overshoot.
• Setting 60% (initial value) in Pr.820 Speed control P gain 1 is equivalent to 120 rad/s (speed response of a single motor). 2
(Equivalent to the half the rad/s value during Real sensorless vector control or with the FR-A820-03800(75K) or higher and
the FR-A840-02160(75K) or higher during Vector control.) Setting this parameter higher speeds up the response, but
setting this too high causes vibration and acoustic noise. 3
• Setting Pr.821 Speed control integral time 1 lower shortens the return time to the original speed during speed fluctuation,
but setting it too low causes overshoot.
Proportional gain 4
∗1
200 (100)rad/s
120 (60)rad/s ∗1 5
Pr.820
60% 100% Setting
(initial value ∗2) 6
*1 The value in parentheses is applicable during Real sensorless vector control or with the FR-A820-03800(75K) or higher and FR-A840-02160(75K)
or higher during Vector control.
*2 Performing PM parameter initialization changes the settings. (Refer to page 225.)
7
• Actual speed gain is calculated as follows when load inertia is applied.
Load
fluctuation
8
Speed
Since increasing the proportional gain enhances the 9
response level and decreases the speed fluctuation.
10
JM JM: Motor inertia
Actual speed gain = Speed gain of a single motor
JM+JL JL: Load inertia converted as the motor axis inertia
• Adjustment procedure
2. If it cannot be adjusted well, change Pr.821 setting, and perform step 1 again.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
247
No. Movement / condition Adjustment method
Set Pr.820 and Pr.821 higher.
If acceleration is slow, raise the setting by 10% and then set the value to 80 to 90% of the
Pr.820
1 Load inertia is too high. setting immediately before vibration/noise starts occurring.
If overshoots occur, set about 80 to 90% of the maximum value without overshooting while
Pr.821
increasing the setting value by twice.
Set Pr.820 lower and Pr.821 higher.
Vibration or acoustic Set about 80 to 90% of the maximum value without any vibration/noise while decreasing the
Pr.820
2 noise are generated from setting value by 10%.
machines. If overshoots occur, set about 80 to 90% of the maximum value without overshooting while
Pr.821
increasing the setting value by twice.
Set Pr.820 higher.
3 Response is slow. If acceleration is slow, set about 80 to 90% of the maximum value without any vibration/
Pr.820
acoustic noise while increasing the setting value by 5%.
Set Pr.821 lower.
Return time (response
4 Set about 80 to 90% of the maximum value without overshooting or unstable movements while
time) is long.
decreasing the setting value of Pr.821 by half.
Overshoots or unstable Set Pr.821 higher.
movements occur.
5 Set about 80 to 90% of the maximum value without overshooting or unstable movements while increasing
or unstable movements
occur. the setting value of Pr.821 by double.
NOTE
• When adjusting the gain manually, set Pr.819 Easy gain tuning selection to "0" (no easy gain tuning) (initial value).
• Pr.830 Speed control P gain 2 and Pr.831 Speed control integral time 2 are valid when terminal RT is ON. In this case,
replace them for Pr.820 and Pr.821 in the description above.
248 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Compensating the speed control P gain in the constant output range
(Pr.1116) 1
• In the constant output range (rated speed or higher), the response of speed control is reduced due to weak field. Thus, the
speed control P gain is needed to be compensated using Pr.1116 Constant output range speed control P gain
compensation. 2
• In Pr.1116, set a compensation amount for the doubled rated speed regarding the speed control P gain at the rated speed
or lower as 100%.
(Speed control P gain at rated speed or higher) = (Speed control P gain at rated speed or lower) × (100% + compensation 3
amount)
Compensation amount = Pr.1116/Rated speed × (Speed - Rated speed)
Ratio multiplied to 4
speed control P gain
Pr.1116=100%
200%
Pr.1116=50%
5
150%
7
0% Speed
Rated speed Rated speed×2
Setting the speed control P gain in the per-unit system (Pr.1117, Pr.1118,
Pr.1121) 8
• The speed control P gain can be set in the per-unit (pu) system.
• In the per-unit system:
When "1" is set, the torque (Iq) command is 100% (rated Iq) when the speed deviation is 100%. 9
When "10" is set, the torque (Iq) command is 10% (rated Iq) when the speed deviation is 100%.
Set the 100% speed in Pr.1121 Per-unit speed control reference frequency.
• The speed control P gain becomes as follows according to Pr.1117 Speed control P gain 1 (per-unit system), Pr.1118 10
Speed control P gain 2 (per-unit system), and the RT signal.
Pr.1117 Pr.1118 Pr.830 RT signal Speed control P gain
— OFF Pr.820
9999 ON Pr.820
9999 9999
Other than
ON Pr.830
9999
Other than
9999 — — Pr.1117
9999
Other than OFF Pr.820
9999 —
9999 ON Pr.1118
Other than Other than OFF Pr.1117
—
9999 9999 ON Pr.1118
NOTE
• The per-unit system setting is available only under Real sensorless vector control or Vector control.
• When the speed control P gain or model speed control gain is set in the per-unit system, the easy gain tuning selection
(Pr.819="1 or 2") becomes invalid.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
249
• To input the X44 signal, set "44" in any of Pr.178 to Pr.189 (input terminal function selection) to assign the function to
a terminal.
• The shock of P/PI control switchover is absorbed by setting Pr.1115 Speed control integral term clear time. When the
X44 signal is turned ON, integration is stopped and the accumulated integral term is reduced and cleared according to the
setting of Pr.1115 Speed control integral term clear time (initial value is 0 ms).
In Pr.1115, set time when the integral term is reduced from 100% to 0% regarding the rated torque current (Iq) as 100%.
Turning OFF the X44 signal resumes the integral operation.
X44-OFF Speed
integral
operation
Integral term
reduction
0
X44-ON
Speed estimator
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• The speed loop integration can be disabled at the emergency stop using Pr.1349 Emergency stop operation selection.
(Refer to page 349.)
NOTE
• The speed loop integration can be disabled at the emergency stop using Pr.1349 Emergency stop operation selection.
(Refer to page 349.)
250 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
5.3.6 Troubleshooting in the speed control
Sensorless Vector PM 1
No. Condition Possible cause Countermeasure
• Check the wiring.
Set V/F control (set Pr.80 Motor capacity or Pr.81 Number of motor poles to
2
"9999") and check the motor rotation direction. For SF-V5RU (1500 r/min series),
set Pr.19 Base frequency voltage to 170 V (340 V) when the value is 3.7 kW or
lower, and set it to 160 V (320 V) when the value is higher, and set Pr.3 Base
frequency to 50 Hz.
3
Motor wiring is incorrect.
• When a forward signal is input, rotation in the counterclockwise direction as
viewed from the motor shaft direction is correct. (Clockwise rotation means that
the phase sequence of the inverter secondary side wiring is different.)
4
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
251
No. Condition Possible cause Countermeasure
• Check that the speed command sent from the controller is correct. (Take EMC
measures.)
Speed command varies.
• Set Pr.72 lower.
• Set Pr.822 Speed setting filter 1 higher. (Refer to page 480.)
Motor speed • Raise the torque limit.
4 Torque shortage.
fluctuates. (Refer to the torque limit for speed control on page 235.)
• Perform easy gain tuning.
Speed control gain is not
• Adjust Pr.820 Speed control P gain 1 and Pr.821 Speed control integral time
suitable for the machine.
1.
(Resonance occurs.)
• Perform speed feed forward control or model adaptive speed control.
• Perform easy gain tuning.
Speed control gain is too
Hunting (vibration or • Set Pr.820 lower and Pr.821 higher.
high.
acoustic noise) • Perform speed feed forward control or model adaptive speed control.
5
occurs in the motor Torque control gain is
• Set Pr.824 Torque control P gain 1 (current loop proportional gain) lower.
or the machine. too high.
Motor wiring is incorrect. • Check the wiring.
Acceleration/ • Raise the torque limit.
deceleration time is Torque shortage. (Refer to the torque limit for speed control on page 235.)
6
different from the • Perform speed feed forward control.
setting. Load inertia is too high. • Set acceleration/deceleration time suitable for the load.
• Perform easy gain tuning.
Speed control gain is not
• Adjust Pr.820 and Pr.821.
suitable for the machine.
• Perform speed feed forward control or model adaptive speed control.
Machine movement Response is slow
7
is unstable. because of the inverter's
acceleration/ • Set the optimum acceleration/deceleration time.
deceleration time
setting.
High carrier frequency is
Rotation ripple affecting the motor • Set Pr.72 lower.
8 occurs during the rotation.
low-speed operation. Speed control gain is too
• Set Pr.820 higher.
low.
Parameters referred to
Pr.3 Base frequency, Pr.19 Base frequency voltagepage 673
Pr.72 PWM frequency selectionpage 339
Pr.80 Motor capacity, Pr.81 Number of motor polespage 215
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequencypage 482
Pr.359 Encoder rotation direction, Pr.369 Number of encoder pulses, Pr.851 Control terminal option-Number of encoder pulses, Pr.852 Control terminal
option-Encoder rotation directionpage 86
Pr.822 Speed setting filter 1page 480
Pr.824 Torque control P gain 1 (current loop proportional gain)page 280
252 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
5.3.7 Speed feed forward control, model adaptive speed
control 1
Sensorless Vector PM
• Speed feed forward control or model adaptive speed control can be selected using parameter settings. 2
Under speed feed forward control, the motor trackability for speed command changes can be improved.
Under model adaptive speed control, the speed trackability and the response level to motor external disturbance torque
can be adjusted individually. 3
Initial Setting
Pr. Name Description
value range
828
G224
Model speed control gain 60% 0 to 1000% Set the gain for the model speed controller. 4
Speed feed forward 0 Perform normal speed control.
877
control/model adaptive 0 1 Perform speed feed forward control.
G220
speed control selection 2 Model adaptive speed control becomes valid. 5
878 Set the primary delay filter for the result of the speed feed forward
Speed feed forward filter 0s 0 to 1 s
G221 calculated from the speed command and load inertia ratio.
879 Speed feed forward torque
150% 0 to 400% Set a maximum limit for the speed feed forward torque.
G222 limit 6
880
Load inertia ratio 7-fold 0 to 200-fold Set the load inertia ratio for the motor.
C114
881
G223
Speed feed forward gain 0% 0 to 1000% Set the calculation result for speed feed forward as the gain.
7
0 to 300 Set the gain for the model speed controller in the per-unit system.
1119 Model speed control
9999
G262 gain(per-unit system) 9999
The Pr.828 setting is applied to the operation.
1121 Per-unit speed control 120 Hz*1 Set the speed at 100% when setting speed control P gain or model
8
0 to 400 Hz
G260 reference frequency 60 Hz*2 speed control gain in the per-unit system.
Speed +
+ control +
Speed command Torque control M
P gain 1
- [Pr. 820] +
Speed control
Actual speed controller
integral time 1
[Pr. 821]
Speed estimator
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
253
NOTE
• The speed feed forward control is enabled for the first motor.
• Even if the driven motor is switched to the second motor while Pr.877 = "1", the second motor is operated as Pr.877 = "0".
• Under PM sensorless vector control, the notch filter is available when low-speed range high-torque characteristic is enabled
by Pr.788 Low speed range torque characteristic selection ="9999 (initial value)". (Refer to page 227.)
J
Torque coefficient
(J: [Pr. 880])
Speed
estimator
NOTE
• The model adaptive speed control is enabled for the first motor.
• Even if the driven motor is switched to the second motor while Pr.877 ="2", the second motor is operated as Pr.877 = "0".
• Under PM sensorless vector control, the notch filter is available when low-speed range high-torque characteristic is enabled
by Pr.788 Low speed range torque characteristic selection ="9999 (initial value)". (Refer to page 227.)
• Under model adaptive speed control, because the appropriate gain values for the model and actual loop sections are based
on the response that was set for easy gain tuning, when raising the response level, Pr.818 Easy gain tuning response level
setting must be re-evaluated (raised).
• The per-unit system setting(Pr.1119) is available only under Real sensorless vector control or Vector control.
• When the speed control P gain or model speed control gain is set in the per-unit system, the easy gain tuning selection
(Pr.819 = "1 or 2") becomes invalid.
254 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Combining with easy gain tuning
• The following table shows the relationship between speed feed forward and model adaptive speed control, and the easy 1
gain tuning function.
Easy gain tuning selection (Pr.819) setting
0 1 2 2
The inertia ratio value
calculated by easy gain
Pr.880 Load inertia ratio . Manual input tuning is displayed. Manual Manual input
input is available only during
a stop.
3
The tuning result is The tuning result is
Pr.820 Speed control P gain 1 Manual input displayed. Write is not displayed.
available. Write is not available. 4
The tuning result is The tuning result is
Pr.821 Speed control integral time
Manual input displayed. Write is not displayed.
1
available. Write is not available.
1
Set the torque bias amount using terminal 1 in any of C16 to C19. (When 10
the squirrel cage rises during forward motor rotation.)
Set the torque bias amount using terminal 1 in any of C16 to C19. (When
2
the squirrel cage rises during reverse motor rotation.)
840
Torque bias selection 9999 The torque bias amount using terminal 1 can be set automatically in C16
G230 3
to C19 and Pr.846 according to the load.
Torque bias command via PROFIBUS-DP communication (FR-A8NP) (-
24
400% to 400%)
Torque bias command via PROFIBUS-DP communication (FR-A8NP) (-
25
327.68% to 327.67%)
9999 No torque bias, rated torque 100%
841 600 to
Torque bias 1 Negative torque bias amount (-400% to -1%)
G231 999%
842 1000 to
Torque bias 2 9999 Positive torque bias amount (0 to 400%)
G232 1400%
843
Torque bias 3 9999 No torque bias setting
G233
844 0 to 5 s The time until the torque starts up.
Torque bias filter 9999
G234 9999 The same operation as 0 s.
845 Torque bias operation 0 to 5 s The time for retaining the torque of the torque bias amount.
9999
G235 time 9999 The same operation as 0 s.
846 Torque bias balance 0 to 10 V Set the voltage for the balanced load.
9999
G236 compensation 9999 The same operation as 0 V. (Fixed to 0 V/0%.
847 Fall-time torque bias 0 to 400% The bias value setting in the torque command.
9999
G237 terminal 1 bias 9999 The same as (C16, C17(Pr.919)) when ascending
848 Fall-time torque bias 0 to 400% The gain value setting in the torque command.
9999
G238 terminal 1 gain 9999 The same as (C18, C19(Pr.920)) when ascending
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
255
Block diagram
Speed command Speed command + Speed + + Torque
control IM
P gain + + control
-
Speed
control PLG
integral time CW
0 Cage
Integration cleared to 0
[Pr. 845]
Internal parameters
[Pr. 840 = 0] [Pr. 840 = 1, 2, 3]
X42 [Pr. 841]
Torque bias selection 1
X43 [Pr. 842]
Torque bias selection 2 [Pr. 843]
C16, C17 CW Cage
SD +
[Pr. 919] [Pr. 826]
-
C18, C19 Torque setting filter 1
[Pr. 846] [Pr. 920] CW > Cage Terminal 1 Load
detector
Setting the torque bias amount using contact input (Pr.840 = "0", Pr.841
to Pr.843)
• Select the torque bias amount shown in the following table using the corresponding contact signal combination.
• To input the X42 signal, set "42" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function to
a terminal, and to input the X43 signal, set "43".
Torque bias selection1 Torque bias selection2
Torque bias amount
(X42) (X43)
OFF OFF 0%
Pr.841 -400% to +400% (Setting value: 600 to
ON OFF
1400%)
Pr.842 -400% to +400% (Setting value: 600 to
OFF ON
1400%)
Pr.843 -400% to +400% (Setting value: 600 to
ON ON
1400%)
When Pr.841 = 1025, the torque bias is 25%. When Pr.842 = 975, the torque bias is -25%. When Pr.843 = 925, the torque bias
is -75%.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Setting the torque bias amount using terminal 1 (Pr.840 ="1, 2", Pr.847,
Pr.848)
• Calculate the torque bias from the load input to terminal 1 as shown in the following diagram, and then apply the torque
bias.
• To set the torque bias amount with a voltage input to terminal 1, set Pr.868 Terminal 1 function assignment ="6".
256 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
• The torque bias amount (Pr.847) and gain amount (Pr.848) when descending (reverse motor rotation when the Pr.840
setting is "1", forward motor rotation when the setting is "2") can be set in a range of 0 to 400%. When Pr.847 or
Pr.848 ="9999", the setting is the same for both descending and ascending (C16 to C19).
1
Pr.840
When ascending When descending
setting
(Forward motor rotation) (Reverse motor rotation) 2
Bias amount Bias amount
Torque command
3
terminal 1 gain Fall-time
C18(Pr. 920) torque bias
terminal 1
C17(Pr. 919) bias C17(Pr. 919)
1 Terminal 1 Terminal 1
Pr. 848 input
input
NOTE
• Input 0 to 10 V (torque command) to the terminal 1 that is used for the torque bias function. Any negative input voltage is 9
regarded as 0 V.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
257
• Set the terminal 1 to accept inputs of load detection voltage, set "3" in Pr.840 Torque bias selection, and adjust the
parameter settings according to the following procedures.
Setting Pr.846
NOTE
• To perform a torque bias operation after the automatic setting is completed, set Pr.840 to "1" or "2".
NOTE
• For the details of the FR-A8NP setting, refer to the Instruction Manual of the FR-A8NP.
258 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
• Set the time for continuing the output torque simply by using the command value for the torque bias in Pr.845 Torque bias
operation time.
1
Speed
2
Torque bias
Output torque 4
Time when torque is Pr. 845
generated by
torque bias setting
Pre-excitation LX ∗1
5
Start signal
*1 When pre-excitation is not performed, the torque bias functions at the same time as the start signal.
6
NOTE
• When torque bias is enabled and Pr.868 = "6", terminal 1 operates as a torque command instead of a frequency setting
auxiliary. When override compensation is selected using Pr.73 Analog input selection and terminal 1 is the main speed, no
7
main speed (main speed = 0 Hz) is set.
• The torque bias is valid for the first motor. When applying the second motor (RT signal is ON), the torque bias function is not
performed. 8
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
9
Parameters referred to
Pr.73 Analog input selectionpage 473
Pr.178 to Pr.189 (Input terminal function selection)page 496
C16 to C19 (Pr.919, Pr.920) (torque setting voltage (current) bias/gain)page 487
10
5.3.9 Avoiding motor overrunning
Vector
Motor overrunning due to excessive load torque or an error in the setting of the number of encoder pulses can be avoided.
Setting
Pr. Name Initial value Description
range
Set the speed deviation excess detection frequency
(difference between the actual rotation speed and speed
285 Speed deviation excess detection 0 to 30 Hz
9999 command value) at which the protective function (E.OSD)
H416 frequency*1 activates.
9999 No speed deviation excess
Set the time from when the speed deviation excess state
853*2 Speed deviation time 1.0 s 0 to 100 s is entered to when the protective function (E.OSD)
H417 activates.
873*2 Speed limit 20 Hz 0 to 400 Hz
Set the frequency limit with the set frequency + Pr.873
H415 value.
Set the time required to shut off output due to
690 0 to 3600 s
Deceleration check time 1.0 s deceleration check after the start signal is OFF.
H881
9999 No deceleration check
*1 This is the overspeed detection frequency under encoder feedback control. (Refer to page 700.)
*2 The setting is available when a Vector control compatible option is installed.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
259
• When the difference (absolute value) between the speed command value and actual rotation speed in speed control under
Vector control is equal to higher than the setting value in Pr.285 Speed deviation excess detection frequency for a
continuous time equal to or longer than the setting value in Pr.853 Speed deviation time, the speed deviation excess
detection (E.OSD) activates to shut off the inverter output.
Set frequency
Frequency
Pr.285
(Hz)
Actual speed
Time
Pr.853
Fault output OFF ON
(ALM)
Speed deviation
excessive fault activated
(E. OSD)
Speed limit(Pr.873)
• This function prevents overrunning even when the setting value for and the value of the actual number of pulses are
different. When the setting value for the number of encoder pulses is lower than the actual number of pulses, because the
motor may increase speed, the output frequency is limited with the frequency of (set frequency + Pr.873).
Set speed + Pr. 873 value
Actual speed
Set speed
at error occurrence
Speed during
normal operation
NOTE
• When the automatic restart after instantaneous power failure function is selected (Pr.57 Restart coasting time ≠ "9999") and
the setting value for the number of encoder pulses is lower than the actual number of pulses, the output speed is limited with
the synchronous speed of the value of Pr.1 Maximum frequency + Pr.873.
• When a regenerative driving torque limit is applied and the speed limit function activates, the output torque may drop suddenly.
Also, when the speed limit function activates during pre-excitation operation, output phase loss (E.LF) may occur.
If the setting for the number of encoder pulses is confirmed as correct, it is recommended that Pr.873 be set to the maximum
value (400 Hz).
• Even if the set frequency is lowered after inverter operation, the speed limit value is not lowered. During deceleration, the
speed is limited at frequency command value + Pr.873.
Pr.690
Time
Start signal
(STF, STR) ON
Fault output
(ALM) ON
E.OSD
260 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
NOTE
• The deceleration check is enabled in the speed control of the Vector control. 1
• If the protective function (E.OSD) operates due to deceleration check, check whether the Pr.369 Number of encoder pulses
setting is correct.
2
Parameters referred to
Pr.285 Overspeed detection frequencypage 700
Pr.369 Number of encoder pulses, Pr.851 Control terminal option-Number of encoder pulsespage 93
3
5.3.10 Notch filter
Sensorless Vector PM
The response level of speed control in the resonance frequency band of mechanical systems can be lowered to avoid 4
mechanical resonance.
Pr. Name
Initial
value
Setting
range
Description 5
0 No notch filter
1003
Notch filter frequency 0 8 to 1250
G601 Set the frequency for the center of gain attenuation.
1004
Hz
6
Notch filter depth 0 0 to 3 0 (Deep) → 3 (Shallow)
G602
1005
Notch filter width 0 0 to 3 0 (Narrow) → 3 (Wide)
G603 7
Pr.1003
Gain
8
Notch filter frequency
0dB Frequency
Pr.1005 9
Notch filter width
Pr.1004 10
Notch filter depth
NOTE
• If a value higher than 500 Hz is set in Pr.1003 while the response speed is normal (Pr.800 = any of "0 to 5 and 9 to 14"), the
inverter operates at 500 Hz.
5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
261
Parameters referred to
Pr.800 Control method selectionpage 215
262 5. PARAMETERS
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
5.4 Torque control under Real sensorless vector 1
control and Vector control
2
Refer
Purpose Parameter to set
to page
Torque command source selection or
Torque command
P.D400 to P.D403, P.G210, Pr.801, Pr.803 to Pr.806,
270
3
torque command value setting P.H704 Pr.1114
To prevent the motor from
Speed limit P.H410 to P.H412, P.H414 Pr.807 to Pr.809, Pr.1113 274
overspeeding
10
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
263
Block diagram
Constant power range
Torque command
torque characteristic selection
Terminal 1 bias [C16,C17 (Pr. 919)] source selection
[Pr. 803]
Terminal 1 gain [C18,C19 (Pr. 920)] [Pr. 804]
Terminal 1
[Pr. 868 = 3, 4]
RT [Pr. 826 = 9999]
Torque
setting
[Pr. 826]
filter [Pr. 74]
[Pr. 826 = 9999]
RT [Pr. 836 = 9999]
[Pr. 836]
[Pr. 74]
[Pr. 836 = 9999]
Parameter
[Pr. 805, Pr. 806] Pulse train torque command bias [Pr.432]
Pulse train torque command gain [Pr.433]
Pulse train input
(FR-A8AL)
CC-Link/CC-Link IE Field/PROFIBUS-DP
(FR-A8NC/FR-A8NCE/FR-A8NP)
RT Torque control
+
P gain 2
[Pr. 834] +
Torque control
integral time 2
[Pr. 835]
Real sensorless RT
vector control Speed
[Pr. 823]
[Pr. 800 = 11] estimation
RT
[Pr. 833]
264 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
1
Analog input offset
Speed limit
adjustment
Terminal 2 bias [C2, C3 (Pr. 902)] [Pr. 849]
AU
Terminal 2 gain [Pr. 125, C4 (Pr. 903)]
Terminal 2 Analog
Terminal 4 bias [C5, C6 (Pr. 904)] input
2
AU Terminal 4 gain [Pr. 126, C7(Pr. 905)] selection
Terminal 4 [Pr. 73]
[Pr. 858 = 0]
Terminal 1
[Pr. 868 = 0]
RT [Pr. 822 = 9999]
Speed
setting
[Pr. 822]
[Pr. 74]
3
filter [Pr. 822 = 9999]
7
[Pr. 1] Forward
Terminal 1 input -10 to 0V rotation
Terminal 1 bias [C12,C13(Pr. 917)]
Forward
Terminal 1 Terminal 1 gain [C14,C15(Pr. 918)] Terminal 1 input 0 to 10V rotation
[Pr. 868 = 5]
Reverse
Terminal 1 input -10 to 0V rotation
RT [Pr. 822 = 9999]
Speed
setting
[Pr. 822]
[Pr. 74]
8
filter [Pr. 822 = 9999]
RT [Pr. 832 = 9999]
[Pr. 832]
[Pr. 832 = 9999]
[Pr. 74]
9
Maximum/minimum
Acceleration/deceleration processing
setting ∗
[Pr.1]
[Pr.2]
A 10
[Pr.7] [Pr.8]
∗ When [Pr. 807 =2] and [Pr. 1 Maximum
frequency] is the speed limit,
acceleration/deceleration processing is not
performed.
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
265
Operation transition
Speed limit value is
increased up to preset value
according to the Pr.7
Acceleration time setting. Speed limit value Speed limit value is decreased
down to zero according to the Pr.8
Deceleration time setting.
Start signal
Output torque is provided
according to the terminal 1
Speed control is peformed during speed setting.
Output torque
limit. (Thus, torque according to the
commanded is not developed.)
• If the setting value of Pr.7 and Pr.8 is "0", turning OFF the start signal enables speed control, and the output torque is
controlled by the torque limit value.
Speed limit value
Item Description
External
STF, STR signal
operation
Start signal
PU operation or of operation panel/ parameter unit
Torque Select the method to give the torque command, and give the torque
command command.
Select the method to give the speed limit command, and input the speed
Speed limit
limit value.
266 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
The following diagram indicates operation relative to commands given by analog input via terminal 1.
Speed
Pr.7
Speed limit value
∗ Pr.8
1
∗ ∗
Speed
2
STF
(Forward
Time
3
rotation
command) Speed limit Speed limit Torque Speed limit
Torque control operation
operation
(Speed control)
operation control operation
(Speed control) operation (Speed control) 4
OL ON ON ON
∗When the speed limit activates, torque according to the commanded is not developed.
• At the STF signal ON, the speed limit value is raised in accordance with the setting of Pr.7. 5
• Speed control is performed when the actual speed exceeds the speed limit value.
• At the STF signal OFF, the speed limit value is lowered in accordance with the setting of Pr.8.
• Under torque control, the actual operation speed is a constant speed when the torque command and load torque are 6
balanced.
• The direction of motor torque generation is determined by a combination of the input torque command polarity and the start
signal, as given in the following table. 7
Polarity of torque Torque generation direction
command STF signal ON STR signal ON
+ torque command
Forward direction (forward
power driving / reverse
Reverse direction (forward
regenerative driving / reverse
8
regenerative driving) power driving)
Reverse direction (forward Forward direction (forward
- torque command regenerative driving / reverse
power driving)
power driving / reverse
regenerative driving)
9
NOTE
• Once the speed limit is activated, speed control is performed and internal torque limit (Pr.22 Torque limit level) is enabled. 10
(Initial value) In this case, it may not be possible to return to torque control.
Torque limit should be external torque limit (terminals 1 and 4). (Refer to page 235.)
• Under torque control, the undervoltage avoidance function (Pr.261 = "11" or "12"), which is one of the power failure time
deceleration-to-stop function, is invalid.
When Pr.261 = "11 (12)", the operation is performed in the same manner as if Pr.261 = "1 (2)".
• Under torque control, perform linear acceleration/deceleration (Pr.29 = "0 (initial value)"). When acceleration/deceleration
patterns other than the linear acceleration/deceleration are selected, the protective function of the inverter may be activated.
(Refer to page 354.)
• Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control) may
rotate a motor at a low speed even though a start command (STF or STR) is not given. The inverter at a start command ON
may also rotate the motor at a low speed even though a speed limit value is set to 0. It must be confirmed that the motor running
does not cause any safety problem before performing pre-excitation.
Operating procedure
1. Perform secure wiring. (Refer to page 46.)
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
267
3. Set the motor overheat protection (Pr.9). (Refer to page 394.)
4. Set the motor capacity and the number of motor poles (Pr.80 and Pr.81). (Refer to page 215.)
V/F control is performed when the setting is "9999" (initial value).
5. Set the rated motor voltage and frequency (Pr.83 and Pr.84). (Refer to page 509.)
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The carrier frequency is limited during Real sensorless vector control. (Refer to page 339.)
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower).
• Performing pre-excitation (LX signal and X13 signal) under torque control may start the motor running at a low speed even
when the start signal (STF or STR) is not input. The inverter at a start command ON may also rotate the motor at a low speed
even though a speed limit value is set to 0. Confirm that the motor running does not cause any safety problem before
performing pre-excitation.
• Switching between the forward rotation command (STF) and reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• When performing continuous operations under Real sensorless vector control in FR-A820-00250(3.7K) or lower or FR-A840-
00126(3.7K) or lower, the speed fluctuation increases when the value is 20 Hz or less, and in the low-speed range of less than
1 Hz, there may be torque shortage. In such case, stop the inverter and restart it to improve the situation.
• If starting may occur while the motor is coasting under Real sensorless vector control, the frequency search must be set for
the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10").
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 or 10 poles) (available
at 60 Hz or higher when the rating is 2 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
Operating procedure
1. Perform secure wiring. (Refer to page 90.)
Install a Vector control compatible option.
3. Set the motor and the encoder (Pr.71, Pr.359 (Pr.852), and Pr.369 (Pr.851)). (Refer to page 93.)
268 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
4. Set the overheat protection of the motor (Pr.9). (Refer to page 394.)
When using the SF-V5RU or a motor equipped with a thermal sensor, set Pr.9 = 0 A.
1
5. Set the motor capacity and the number of motor poles (Pr.80 and Pr.81). (Refer to page 215.)
V/F control is performed when the setting is "9999" (initial value).
6. Set the rated motor voltage and frequency (Pr.83 and Pr.84). (Refer to page 93.) 2
7. Select the control method (Pr.800). (Refer to page 215.)
Select Pr.800 Control method selection = "1" (torque control), "2" (speed/torque switchover), or "5" (position/
3
torque switchover) to enable torque control.
NOTE
• The carrier frequency is limited during Vector control. (Refer to page 339.) 7
• Torque control is not available under the Vector control with PM motors with a resolver.
10
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
269
5.4.4 Torque command
Sensorless Vector
For torque control selection, the torque command source can be selected.
Initial
Pr. Name Setting range Description
value
432 Pulse train torque For 0 pulses/s, set the torque to be used during stall prevention
0% 0 to 400%
D120*1 command bias operation.
433 Pulse train torque For 400k pulses/s, set the torque command to be used during stall
150% 0 to 400%
D121*1 command gain prevention operation.
801 0 to 400% Set the torque current limit level.
Output limit level 9999
H704 9999 The torque limit setting value is used for limiting the torque current level.
0, 10 Constant motor output command
1, 11 Constant torque command
Constant output range In the torque command setting,
803 The torque is constant unless the
torque characteristic 0 select torque command for the
G210 output limit of the torque current is
selection 2 constant output area .
reached. (The torque current is
limited.)
0 Torque command given by analog input via terminal 1
Torque command (-400% to 400%) given by the parameter setting
1
(Pr.805 or Pr.806)
2 Torque command given by the pulse train input (FR-A8AL)
Torque limit through the CC-Link/CC-Link IE Field Network
communication (FR-A8NC, FR-A8NCE, FR-A800-GF)
804 Torque command 3
0 Torque command given through PROFIBUS-DP communication (FR-
D400 source selection
A8NP)
4 12/16-bit digital input (FR-A8AX)
5 Torque limit through the CC-Link/CC-Link IE Field Network
communication (FR-A8NC, FR-A8NCE, FR-A800-GF)
6 Torque command given through PROFIBUS-DP communication (FR-
A8NP)
805 Torque command value Writes the torque command value in RAM. Regards 1000% as 0%, and
1000% 600 to 1400%
D401 (RAM) set torque command by an offset of 1000%.
806 Torque command value Writes the torque command value in RAM and EEPROM Regards
1000% 600 to 1400%
D402 (RAM, EEPROM) 1000% as 0%, and set torque command by an offset of 1000%.
0 Not reversed Select whether to reverse the
1114 Torque command torque command polarity or not
1
D403 reverse selection 1 Reversed when the reverse rotation
command (STR) is turned ON.
*1 The setting is available when the FR-A8AL is installed.
Vector control
NOTE
• When the torque command exceeding the torque limit value (Pr.22, Pr.810, Pr.812 to Pr.817) is given, the output torque is
within the torque limit value. (Refer to page 263.)
270 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
Torque command given by analog input (terminal 1) (Pr.804 = "0 (initial
value)") 1
• Torque commands are given by voltage (current) input via terminal 1.
• Set Pr.868 Terminal 1 function assignment = "3 or 4" to give the torque command via terminal 1.
• Torque commands given by analog inputs can be calibrated by the calibration parameters C16 (Pr.919) to C19 (Pr.920) 2
(Refer to page 487.)
Torque command
150%
3
-150%
5
Torque command given by parameter (Pr.804 = "1")
• Set Pr.805 Torque command value (RAM) or Pr.806 Torque command value (RAM, EEPROM)to set the torque
command value.
6
For Pr.805 or Pr.806, regard 1000% as 0%, and set torque command by offset from 1000%.
The following diagram shows relation between the Pr.805 or Pr.806 setting and the actual torque command value.
• To change the torque command value frequently, write it in Pr.805. To change torque command value frequently, write in
7
Pr.805.
• When the CC-Link IE Field Network communication (FR-A8NCE/FR-A800-GF) is used, the torque command given from
the remote register (RWw2) is valid.
8
Torque command value
400%
9
Pr.805, Pr.806
600% settings
1000% 1400% 10
Torque command value
-400% =Pr.805(or Pr.806)-1000%
NOTE
• When the torque command is set by Pr.805 (RAM), powering OFF the inverter erases the changed parameter value.
Therefore, the parameter set value is the one saved by Pr.806 (EEPROM) when the power is turned back on.
• If giving torque command by parameter setting, set the speed limit value properly to prevent overspeeding. (Refer to page
274.)
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
271
• Use Pr.428 Command pulse selection to select a type of pulse train input to the FR-A8AL.
Pr.428 setting Command pulse train type During forward rotation During reverse rotation
Negative PP
1 Pulse train + sign
logic NP L H
Positive PP
4 Pulse train + sign
logic NP H L
• Use Pr.432 Pulse train torque command bias and Pr.433 Pulse train torque command gain to set the bias and gain
values for the torque command respectively.
Torque command value
Pr.433 setting
Pr.432 setting
Pulse train input frequency
0 400kpps
NOTE
• For the details of the FR-A8AL, refer to the Instruction Manual of the FR-A8AL.
272 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
*2 The torque command can also be given by setting a value in Pr.805 or Pr.806.
*3 Setting range if set by operation panel or parameter unit is "673 to 1327 (-327% to 327%)"; setting increment is 1%.
NOTE 1
• For the details of the FR-A8NC, FR-A8NCE, and FR-A8NP setting, refer to the Instruction Manual for the respective
communication options.
For the details of the CC-Link IE Field Network, refer to page 716. 2
• For the details of the setting using the PLC function, refer to the PLC Function Programming Manual.
NOTE
• For the details of FR-A8AX setting, refer to the Instruction Manual of FR-A8AX
4
• To avoid overload or overcurrent of the inverter or motor, use Pr.801 Output limit level to limit the torque current in the
constant power range. 9
Pr.801 setting Description
0 to 400% Set the torque current limit level.
9999 The torque limit setting value (Pr.22, Pr.812 to Pr.817, etc.) is used for limiting the torque current. 10
Pr.803 = 0, 1, 10, 11
Torque
Constant power range
Constant torque range Pr. 803 = 1, 11:
constant torque command
Pr. 803 = 0, 10:
constant power command
(torque reduction)
Speed
Rated speed
Pr.803 = 2
Torque
Constant torque range Constant power range
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
273
Reverse selection of the torque command (Pr.1114)
• The Pr.1114 Torque command reverse selection setting determines whether or not the torque command polarity is
reversed when the reverse rotation command (STR) is turned ON.
Torque command polarity at STR signal ON
Pr.1114 setting
(sign)
0 Not reversed
1 (Initial value) Reversed
Parameters referred to
Pr.868 Terminal 1 function assignmentpage 477
Calibration parameter C16 (Pr.919) to C19 (Pr.920) (terminal 1 bias, gain torque)page 487
When operating under torque control, motor overspeeding may occur if the load torque drops to a value less than the torque
command value, etc. Set the speed limit value to prevent overspeeding.
If the actual speed reaches or exceeds the speed limit value, the control method switches from torque control to speed control,
preventing overspeeding.
Initial value Setting
Pr. Name Description
FM CA range
0 Uses the speed command during speed control as the speed limit.
Sets speed limits for forward and reverse directions individually by
1
807 using Pr.808 and Pr.809.
Speed limit selection 0
H410 Forward/reverse rotation speed limit
2 Applies speed limit by analog voltage input to the terminal 1. Speed
limit for forward/reverse side is switched by its polarity.
808 Forward rotation speed
60 Hz 50 Hz 0 to 400 Hz Sets the forward side speed limit.
H411 limit/speed limit
Reverse rotation speed 0 to 400 Hz Sets the reverse side speed limit.
809
limit/reverse-side speed 9999
H412 9999 Pr.808 setting value is effective.
limit
9999 Speed limit mode 1
0 Speed limit mode 2
1113 Speed limit method 1 Speed limit mode 3
0
H414 selection 2 Speed limit mode 4
X93 signal OFF: Speed limit mode 3
10
X93 signal ON: Speed limit mode 4
274 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
Control block diagram (speed limit mode 1)
Torque command
Speed estimated value < speed limit value
+
Torque control Motor
1
Pr. 807 Speed limit selection
Same method 0 -
as speed command input
Parameter(Pr. 808, Pr. 809)
1 + Speed control
(proportional control)
Encoder 2
Forward/reverse rotation 2
speed limit - Speed estimated value speed limit value
Speed estimator
Real sensorless vector control
3
Vector control
Using the speed command during speed control (Pr.1113 = "9999", Pr.807
= "0"). 4
• Speed limit is set by the same method as speed setting during speed control. (Speed setting by PU (operation panel/
parameter unit), multi-speed setting, plug-in option, etc.)
• When the start signal turns ON, the limit level increases from 0 Hz to the set speed by taking the time set in Pr.7
5
Acceleration time. When the start signal turns OFF, the limit level at the time decreases to the operation start level of
Pr.10 DC injection brake operation frequency, by taking the time set in Pr.8 Deceleration time.
Speed
The speed setting 6
value is the speed
Forward rotation limit value.
Pr.7 Pr.8
Speed setting
value during
7
speed control
Time
Torque controllable 8
range
Reverse rotation
STF(STR) ON OFF
9
NOTE
• The second and third acceleration/deceleration time can be set.
• When speed limit command exceeds Pr.1 Maximum frequency setting, the speed limit value becomes Pr.1 setting. When
speed limit command falls below Pr.2 Minimum frequency setting, the speed limit value becomes Pr.2 setting. Also, the
10
speed limit command is smaller than Pr.13 Starting frequency, the speed limit value becomes 0 Hz.
• To perform speed limit by analog input, calibrate analog input terminals 1, 2 and 4. (Refer to page 482.)
• To use analog inputs to perform speed limit, turn the external signals (RH, RM, RL) OFF. If any of the external signals (RH,
RM, RL) is ON, speed limit by multi-speed are enabled.
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
275
• When Pr.809 = "9999" (initial value), speed limit is determined by the setting value of Pr.808 for both forward and reverse
rotations.
Speed
Torque controllable range
Forward rotation
Forward rotation
Speed limit Pr.808 Pr.7 Pr.8
Speed limit Pr.808
150 150
Time
Output torque 0
(%) Speed limit Pr.809
Speed limit Pr.809 Torque controllable range
Reverse rotation
Reverse rotation
STF(STR) ON OFF
When terminal 1 input is "-10 to 0 V" When terminal 1 input is "0 to 10 V"
Speed
Torque controllable range Speed
Forward rotation
Pr.1 Forward rotation
Terminal 1
input
150 0 150 150 0 150
Output torque (%) Output
torque (%)
Terminal 1 input
Speed
Torque controllable range
Speed
Torque controllable range
Pr.1
Pr.7 Pr.8
The forward rotation
Terminal 1 input (0 to 10 V)
speed limit
The forward rotation speed
limit
Time Time
Terminal 1 input
(-10 to 0 V)
Pr.7 Pr.8
The reverse Pr.1
rotation speed The reverse rotation
limit speed limit
276 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
NOTE
• To perform speed limit by using terminal 1, calibrate terminal 1. (Refer to page 482.) 1
Speed limit mode 2 (Pr.1113 = "0" initial value)
• Following the polarity change in the torque command, the polarity of the speed limit value changes. This prevents the 2
speed from increasing in the torque polarity direction. (When the torque command value is 0, the polarity of the speed limit
value is positive.)
• When Pr.807 Speed limit selection = "0, 2", the setting during speed control is applied for the speed limit. When Pr.807 3
Speed limit selection = "1", Pr.808 Forward rotation speed limit/speed limit is applied for the speed limit.
• When the load has reversed the rotation opposite to the torque polarity, the setting of Pr.809 Reverse rotation speed
limit/reverse-side speed limit is applied for the speed limit. (The speed limit value and reverse-side speed limit value are 4
limited at Pr.1 Maximum frequency (maximum 400 Hz under Vector control).)
Reverse-side Torque
speed limit value command
-Pr.809 value Speed limit value
5
7
-Speed limit value Reverse-side
speed limit value
Pr.809
8
Range where torque
Rotation speed control is available
9
Rotation speed Range where torque
control is available
Pr.809
Pr.7 Pr.8 Reverse-side
Speed limit value speed limit value
10
Time Time
Speed limit value
Pr.7 Pr.8
-Pr.809
Reverse-side
speed limit value
When the torque command value is positive When the torque command value is negative
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
277
• When the torque command becomes negative, the setting of Pr.809 Reverse rotation speed limit/reverse-side speed
limit is applied to prevent the speed from increasing in the reverse rotation direction. (The speed limit value and reverse-
side speed limit value are limited at Pr.1 Maximum frequency (maximum 400 Hz under Vector control).)
Unwinding Winding
(regenerative driving) (power driving)
Forward Forward
rotation rotation
Winding Unwinding
(power driving) (regenerative driving)
Reverse
Reverse rotation
rotation
Time
-Pr.809
Reverse-side
Pr.7 Pr.8
-Pr.809 speed limit value
Reverse-side
speed limit value
278 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
• When the torque command becomes negative, the setting of Pr.809 Reverse rotation speed limit/reverse-side speed
limit is applied to prevent the speed from increasing in the reverse rotation direction. (The speed limit value and reverse-
side speed limit value are limited at Pr.1 Maximum frequency (maximum 400 Hz under Vector control).)
1
Unwinding Winding
(regenerative driving) (power driving)
Forward
2
Forward
rotation rotation
3
Winding Unwinding
(power driving) (regenerative driving)
Reverse
4
Reverse rotation
rotation
5
Torque Reverse-side Torque Reverse-side
command speed limit value command speed limit value
Speed limit value value Pr.809 value Speed limit value Pr.809
8
Range where torque
control is available
Time
Pr.7 Pr.8 Time
Speed limit value
Pr.7 Pr.8
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
279
NOTE
• During the speed limit operation, " " (SL) is displayed on the operation panel and the OL signal is output.
• OL signal is assigned to terminal OL in the initial status. Set "3" in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign the RT signal to another terminal. Changing the terminal assignment using Pr.190 to Pr.196 may affect
the other functions. Set parameters after confirming the function of each terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.1 Maximum frequency, Pr.2 Minimum frequencypage 407
Pr.4 to Pr.6, Pr.24 to 27, Pr.232 to Pr.239 (multi-speed operation)page 391
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.13 Starting frequencypage 363
Pr.190 to Pr.196 (output terminal function selection)page 450
Pr.868 Terminal 1 function assignmentpage 477
Pr.125, Pr.126, C2 to C7, C12 to C15 (Frequency setting voltage (current) bias/gain)page 482
Operation is normally stable enough in the initial setting, but some adjustments can be made if abnormal vibration, noise or
overcurrent occur for the motor or machinery.
Setting
Pr. Name Initial value Description
range
Torque control P
824
gain 1 (current loop 100% 0 to 500% Set the current loop proportional gain.
G213
proportional gain)
Torque control
825 integral time 1
5 ms 0 to 500 ms Set current loop integral compensation time.
G214 (current loop integral
time)
Sets the current loop proportional gain when RT signal
0 to 500%
834 Torque control P is ON.
9999
G313 gain 2
9999
The Pr.824 setting is applied to the operation.
Sets the current loop integral compensation time when
0 to 500 ms
835 Torque control RT signal is ON.
9999
G314 integral time 2
9999
The Pr.825 setting is applied to the operation.
280 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
NOTE
• The RT signal is a second function selection signal which also enables other second functions. (Refer to page 500.) 1
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
2
Adjustment procedure
Adjust if any of phenomena such as unusual vibration, noise, current or overcurrent is produced by the motor or machinery.
Parameters referred to
Pr.72 PWM frequency selectionpage 339
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.800 Control method selectionpage 215
Pr.807 Speed limit selectionpage 274
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
281
C16 to C19 (torque setting voltage (current) bias/gain)page 487
By changing the torque limit value for speed control, torque control can be performed.
Initial
Pr. Name Setting range Description
value
6 Vector control
Variable-current limiter
Torque control under Vector control torque control)
106
(fast-response operation)
0 to 5, 100 to 105 Vector control
800 Control method
20 9, 109 Vector control test operation
G200 selection
10 to 12, 110 to 112 Real sensorless vector control
13 to 14, 113, 114 (PM sensorless vector control)
V/F control (Advanced magnetic flux vector control, PM sensorless
20
vector control)
Select the control method for the second motor.
0 to 6, 10 to 14, 20,
451 Second motor control The second motor is enabled when the RT signal is ON.
9999 100 to 106, 110 to 114
G300 method selection The setting range is the same as that of Pr.800.
9999 The setting value of Pr.800 is used.
• By adding the bias amount to the line speed (master speed) as the speed command value to saturate the speed controller
and changing the torque limit value, torque control can be performed.
• For a positive bias amount (the speed command value faster than the line speed), power driving is applied, and for a
negative bias amount (the speed command value slower than the line speed), regenerative driving is applied.
• Speed control is the basic control. For how to set the speed command and torque limit value, refer to the description of
speed control (page 229).
Line speed
Generated torque
Power driving
0
Regenerative driving
• Under speed control with Pr.800 = "0 or100", when the speed command value is changed by an external force, the torque
limit is invalid during a change in the speed command value to adjust the internal speed command value to the actual
speed.
Under variable speed limiter control with Pr.800 = "6 or 106", the process to adjust the speed command value to the actual
speed is not performed, and thus the torque limit remains valid. This prevents torque from suddenly changing at a speed
change.
0 0
Torque limit value Torque limit value
(absolute value) (absolute value)
0 0
Generated torque
0 0
Pr.800=0, 100 Pr.800=6, 106
282 5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
NOTE
• When Pr.800 = "6 or 106" (torque control by a variable-current limiter), Pr.690 Deceleration check time and Pr.873 Speed 1
limit are ignored.
Parameters referred to 2
Pr.690 Deceleration check timepage 259
Pr.873 Speed limitpage 259
Pr.800 Control method selection, Pr.451 Second motor control method selectionpage 215
10
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
283
5.5 Position control under vector control and PM
sensorless vector control
Refer to
Purpose Parameter to set
page
Pr.419, Pr.464 to
P.B000, P.B020 to P.B050,
To perform Simple position control Parameter position Pr.494, Pr.1221 to
P.B101, P.B120 to P.B188, 288
by setting parameters command Pr.1290, Pr.1292,
P.B190 to P.B195
Pr.1293
To perform position control by pulse Simple pulse train position
P.B000, P.B009, P.B010 Pr.419, Pr.428, Pr.429 304
input to the inverter command
To adjust the gear ratio of the motor
Electronic gear settings P.B001, P.B002, P.B005 Pr.420, Pr.421, Pr.424 309
and machine
Position adjustment P.B007 to P.B008, P.B192 Pr.426 to Pr.427,
311
parameter settings to P.B195 Pr.1294 to Pr.1297
To improve the precision of the
P.B003, P.B004, P.B006, Pr.422, Pr.423, Pr.425,
position control Position control gain
P.B012, P.B013, P.G220, Pr.446, Pr.828, Pr.877, 312
adjustment
P.G224, P.C114 Pr.880, Pr.1298
Pulse monitor selection P.B011 Pr.430 306
To monitor pulses
Cumulative pulse monitoring P.M610 to P.M613 Pr.635 to Pr.638 306
• In position control, speed commands, which are calculated to eliminate the difference between the command pulse
(parameter setting) and the feedback pulse number, are output to rotate the motor.
• This inverter can perform simple positioning by contact input or position control by simple pulse input to the inverter.
Point table
Position Speed Acceleration/deceleration time Dwell time Auxiliary function
STR
Model position Model speed
Electronic Pr.424 control gain control gain
Command pulse Command pulse selection gear Pr.446 Pr.828
(FR-A8AL) 1 + +
Pr.420 J
Pr.428 Torque coefficient
PGP, PP Pr.421 - -
Command pulse
(FR-A8AL) Position command
integral integral
acceleration/deceleration 0
PGN, NP
time constant Speed feed
forward gain
Command pulse Command pulse selection 2 Pr.877
0,1 2 0,1 2 1 2 0
Pr.428 Position
JOG
loop gain
Pulse train sign Pr.422 +
+ +
Deviation +
NP M
- counter - +
Speed control Toruque
control
Pr.429 Differentiation
Clear signal Encoder
selection
Position feedback
284 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Operation example
• Calculate the speed command so that the difference between the number of pulses of the internal pulse train (if Pr.419 = 1
"0", command pulses are used in the inverter from the number of pulses defined by parameters (Pr.465 to Pr.494)) and
the number of pulses in the feedback from the motor terminal encoder (estimated value when PM sensorless vector control
is used) is 0, and then rotate the motor based on the calculation. 2
1) Once a pulse train is input, pulses are accumulated in the deviation counter, and the droop pulses in this counter
become position control pulses and speed command.
2) When the motor starts to rotate in response to the speed command from the inverter, feedback pulses are also
3
generated by the encoder at the same time. Subtract the encoder feedback pulses or feedback estimate value from the
droop pulses in the deviation counter. The deviation counter keeps rotating the motor while keeping a certain droop
amount.
3) If the command pulse input stops, the amount of droop pulses in the deviation counter decreases and thus the speed
4
slows down. When there is no droop pulse, the motor stops.
4) If the number of droop pulses becomes smaller than the value set in Pr.426 In-position width, the system determines
that positioning is complete and the In-position (Y36) signal is turned ON.
5
9
Pulse train Rough Fine Rough
LX signal 10
Servo on
STF (STR)
Forward (reverse)
Y36 signal
In-position signal
• The pulses are slow during motor acceleration and fast at full speed. The pulses become slower during deceleration, and
eventually reach 0 and the motor stops a little after the command pulse.
This time difference is necessary to ensure stop accuracy and is called stop setting time.
NOTE
• To assign the Pre-excitation/servo ON (LX) signal, set "23" in any of Pr.178 to Pr.189 (Input terminal function selection).
• To assign the In-position (Y36) signal, set "36" in any of Pr.190 to Pr.196 (Output terminal function selection).
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (input terminal function selection)page 496
Pr.190 to Pr.196 (output terminal function selection)page 450
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
285
5.5.2 Setting procedure of Vector control (position
control)
Vector
Operating procedure
1. Perform secure wiring. (Refer to page 86.)
Install a Vector control compatible option.
3. Set the motor and the encoder (Pr.71, Pr.359 (Pr.852), Pr.369 (Pr.851)). (Refer to page 93.)
4. Set the overheat protection of the motor (Pr.9). (Refer to page 394.)
When using the SF-V5RU or a motor equipped with a thermal sensor, set Pr.9 = 0 A.
5. Set the motor capacity and number of motor poles (Pr.80, Pr.81). (Refer to page 215.)
V/F control is performed when the setting is "9999" (initial value).
6. Set the rated motor voltage and frequency (Pr.83, Pr.84). (Refer to page 94.)
As required
• Set the electronic gear. (Refer to page 309.)
• Set the position adjustment parameters. (Refer to page 311.)
• Adjust the position control gain. (Refer to page 312.)
• Set the torque limit. (Refer to page 235.)
NOTE
• The carrier frequency is limited during Vector control. (Refer to page 339.)
• For Vector control for a motor with a resolver, refer to the Instruction Manual of the FR-A8APR.
286 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
5.5.3 Setting procedure of PM sensorless vector control
(position control) 1
PM
Operating procedure 2
1. Perform IPM parameter initialization. (Refer to page 224.)
Set "3003 or 3103" in Pr.998 PM parameter initialization or select "3003" in “ " (IPM parameter initial 3
settings).
Setting Description
3003 Parameter settings for MM-CF IPM motor (rotations per minute) 4
3103 Parameter settings for MM-CF IPM motor (frequencies)
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
287
5.5.4 Simple positioning function by parameters
Vector PM
Set positioning parameters such as the number of pulses (position) and acceleration/deceleration time in advance to create a
point table (point table method). Positioning operation is performed by selecting the point table.
Pr. Name Initial value Setting range Description
Simple position control by point table (position command
0
given by setting parameters)
Position command given by the pulse train input to the FR-
1
A8AL*1
Simple pulse train position command given by the pulse
2
train input to the inverter
Simple position control by point table (position command
10 given by setting parameters)
The home position data is retained at servo-OFF.
419 Position command Simple position control by point table (position command
0 given by setting parameters)
B000 source selection 100
The monitor value of the current position 2 is cleared when
the home position return is completed.
Simple position control by point table (position command
given by setting parameters)
110 The home position data is retained at servo-OFF.
The monitor value of the current position 2 is cleared when
the home position return is completed.
Simple position control by point table (position command
1110 given by setting parameters)
The absolute position control with the FR-A8APS is valid.*2
Digital position control Set the time period until the inverter stops when the forward
464
sudden stop 0s 0 to 360 s rotation (reverse rotation) command is turned OFF with the
B020
deceleration time position feed forward function.
465 First target position
0 0 to 9999
B021 lower 4 digits
Set the target position of the point table 1.
466 First target position
0 0 to 9999
B022 upper 4 digits
467 Second target position
0 0 to 9999
B023 lower 4 digits
Set the target position of the point table 2.
468 Second target position
0 0 to 9999
B024 upper 4 digits
469 Third target position
0 0 to 9999
B025 lower 4 digits
Set the target position of the point table 3.
470 Third target position
0 0 to 9999
B026 upper 4 digits
471 Fourth target position
0 0 to 9999
B027 lower 4 digits
Set the target position of the point table 4.
472 Fourth target position
0 0 to 9999
B028 upper 4 digits
473 Fifth target position
0 0 to 9999
B029 lower 4 digits
Set the target position of the point table 5.
474 Fifth target position
0 0 to 9999
B030 upper 4 digits
475 Sixth target position
0 0 to 9999
B031 lower 4 digits
Set the target position of the point table 6.
476 Sixth target position
0 0 to 9999
B032 upper 4 digits
477 Seventh target position
0 0 to 9999
B033 lower 4 digits
Set the target position of the point table 7.
478 Seventh target position
0 0 to 9999
B034 upper 4 digits
479 Eighth target position
0 0 to 9999
B035 lower 4 digits
Set the target position of the point table 8.
480 Eighth target position
0 0 to 9999
B036 upper 4 digits
288 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Pr. Name Initial value Setting range Description
481 Ninth target position
B037 lower 4 digits
0 0 to 9999
Set the target position of the point table 9.
1
482 Ninth target position
0 0 to 9999
B038 upper 4 digits
483
B039
Tenth target position
lower 4 digits
0 0 to 9999 2
Set the target position of the point table 10.
484 Tenth target position
0 0 to 9999
B040 upper 4 digits
485
B041
Eleventh target position
lower 4 digits
0 0 to 9999 3
Set the target position of the point table 11.
486 Eleventh target position
0 0 to 9999
B042 upper 4 digits
487
B043
Twelfth target position
lower 4 digits
0 0 to 9999 4
Set the target position of the point table 12.
488 Twelfth target position
0 0 to 9999
B044 upper 4 digits
489
B045
Thirteenth target
position lower 4 digits
0 0 to 9999 5
Set the target position of the point table 13.
490 Thirteenth target
0 0 to 9999
B046 position upper 4 digits
491 Fourteenth target
0 0 to 9999
6
B047 position lower 4 digits
Set the target position of the point table 14.
492 Fourteenth target
0 0 to 9999
B048 position upper 4 digits
493 Fifteenth target position
0 0 to 9999
7
B049 lower 4 digits
Set the target position of the point table 15.
494 Fifteenth target position
0 0 to 9999
B050 upper 4 digits
0
Turning OFF the forward (reverse) rotation command stops 8
1221 Start command edge the motor in the setting time of Pr.464.
0
B101 detection selection Position forward is continued even if the forward (reverse)
1
rotation command is turned OFF.
1222 First positioning 9
5s 0.01 to 360 s
B120 acceleration time
1223 First positioning
5s 0.01 to 360 s
B121
1224
deceleration time
First positioning dwell
Set the characteristics of the point table 1. 10
0 ms 0 to 20000 ms
B122 time
1225 First positioning sub- 0 to 2, 10 to 12, 100 to
10
B123 function 102, 110 to 112
1226 Second positioning
5s 0.01 to 360 s
B124 acceleration time
1227 Second positioning
5s 0.01 to 360 s
B125 deceleration time
Set the characteristics of the point table 2.
1228 Second positioning
0 ms 0 to 20000 ms
B126 dwell time
1229 Second positioning sub- 0 to 2, 10 to 12, 100 to
10
B127 function 102, 110 to 112
1230 Third positioning
5s 0.01 to 360 s
B128 acceleration time
1231 Third positioning
5s 0.01 to 360 s
B129 deceleration time
Set the characteristics of the point table 3.
1232 Third positioning dwell
0 ms 0 to 20000 ms
B130 time
1233 Third positioning sub- 0 to 2, 10 to 12, 100 to
10
B131 function 102, 110 to 112
1234 Fourth positioning
5s 0.01 to 360 s
B132 acceleration time
1235 Fourth positioning
5s 0.01 to 360 s
B133 deceleration time
Set the characteristics of the point table 4.
1236 Fourth positioning dwell
0 ms 0 to 20000 ms
B134 time
1237 Fourth positioning sub- 0 to 2, 10 to 12, 100 to
10
B135 function 102, 110 to 112
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
289
Pr. Name Initial value Setting range Description
1238 Fifth positioning
5s 0.01 to 360 s
B136 acceleration time
1239 Fifth positioning
5s 0.01 to 360 s
B137 deceleration time
Set the characteristics of the point table 5.
1240 Fifth positioning dwell
0 ms 0 to 20000 ms
B138 time
1241 Fifth positioning sub- 0 to 2, 10 to 12, 100 to
10
B139 function 102, 110 to 112
1242 Sixth positioning
5s 0.01 to 360 s
B140 acceleration time
1243 Sixth positioning
5s 0.01 to 360 s
B141 deceleration time
Set the characteristics of the point table 6.
1244 Sixth positioning dwell
0 ms 0 to 20000 ms
B142 time
1245 Sixth positioning sub- 0 to 2, 10 to 12, 100 to
10
B143 function 102, 110 to 112
1246 Seventh positioning
5s 0.01 to 360 s
B144 acceleration time
1247 Seventh positioning
5s 0.01 to 360 s
B145 deceleration time
Set the characteristics of the point table 7.
1248 Seventh positioning
0 ms 0 to 20000 ms
B146 dwell time
1249 Seventh positioning 0 to 2, 10 to 12, 100 to
10
B147 sub-function 102, 110 to 112
1250 Eighth positioning
5s 0.01 to 360 s
B148 acceleration time
1251 Eighth positioning
5s 0.01 to 360 s
B149 deceleration time
Set the characteristics of the point table 8.
1252 Eighth positioning dwell
0 ms 0 to 20000 ms
B150 time
1253 Eighth positioning sub- 0 to 2, 10 to 12, 100 to
10
B151 function 102, 110 to 112
1254 Ninth positioning
5s 0.01 to 360 s
B152 acceleration time
1255 Ninth positioning
5s 0.01 to 360 s
B153 deceleration time
Set the characteristics of the point table 9.
1256 Ninth positioning dwell
0 ms 0 to 20000 ms
B154 time
1257 Ninth positioning sub- 0 to 2, 10 to 12, 100 to
10
B155 function 102, 110 to 112
1258 Tenth positioning
5s 0.01 to 360 s
B156 acceleration time
1259 Tenth positioning
5s 0.01 to 360 s
B157 deceleration time
Set the characteristics of the point table 10.
1260 Tenth positioning dwell
0 ms 0 to 20000 ms
B158 time
1261 Tenth positioning sub- 0 to 2, 10 to 12, 100 to
10
B159 function 102, 110 to 112
1262 Eleventh positioning
5s 0.01 to 360 s
B160 acceleration time
1263 Eleventh positioning
5s 0.01 to 360 s
B161 deceleration time
Set the characteristics of the point table 11.
1264 Eleventh positioning
0 ms 0 to 20000 ms
B162 dwell time
1265 Eleventh positioning 0 to 2, 10 to 12, 100 to
10
B163 sub-function 102, 110 to 112
1266 Twelfth positioning
5s 0.01 to 360 s
B164 acceleration time
1267 Twelfth positioning
5s 0.01 to 360 s
B165 deceleration time
Set the characteristics of the point table 12.
1268 Twelfth positioning
0 ms 0 to 20000 ms
B166 dwell time
1269 Twelfth positioning sub- 0 to 2, 10 to 12, 100 to
10
B167 function 102, 110 to 112
290 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Pr. Name Initial value Setting range Description
1270 Thirteenth positioning
B168 acceleration time
5s 0.01 to 360 s 1
1271 Thirteenth positioning
5s 0.01 to 360 s
B169 deceleration time
Set the characteristics of the point table 13.
1272
B170
Thirteenth positioning
dwell time
0 ms 0 to 20000 ms 2
1273 Thirteenth positioning 0 to 2, 10 to 12, 100 to
10
B171 sub-function 102, 110 to 112
1274
B172
Fourteenth positioning
acceleration time
5s 0.01 to 360 s 3
1275 Fourteenth positioning
5s 0.01 to 360 s
B173 deceleration time
Set the characteristics of the point table 14.
1276
B174
Fourteenth positioning
dwell time
0 ms 0 to 20000 ms 4
1277 Fourteenth positioning 0 to 2, 10 to 12, 100 to
10
B175 sub- function 102, 110 to 112
1278
B176
Fifteenth positioning
acceleration time
5s 0.01 to 360 s 5
1279 Fifteenth positioning
5s 0.01 to 360 s
B177 deceleration time
1280 Fifteenth positioning
0 ms 0 to 20000 ms
Set the characteristics of the point table 15.
6
B178 dwell time
1281 Fifteenth positioning 0, 2, 10, 12, 100, 102,
10
B179 sub-function 110, 112
0 Dog type 7
1 Count type
2 Data set type
1282
B180
Home position return
method selection
4
3 Stopper type
Ignoring the home position (servo-ON position as the home
8
4
position)
5 Dog type back end reference
6 Count type with front end reference 9
1283 Home position return
2 Hz 0 to 30 Hz Set the speed for the home position return operation.
B181 speed
1284 Home position return
B182 creep speed
0.5 Hz 0 to 10 Hz Set the speed immediately before the home position return.
10
1285 Home position shift
0 0 to 9999 Set the home position shift distance.
B183 amount lower 4 digits
Home position shift amount lower = Pr.1286 × 10000 digits
1286 Home position shift + Pr.1285
0 0 to 9999
B184 amount upper 4 digits
Travel distance after
1287
proximity dog ON lower 2048 0 to 9999
B185 Set the travel distance after detecting the proximity dog.
4 digits
Travel distance after proximity dog = Pr.1288 × 10000 +
Travel distance after Pr.1287
1288
proximity dog ON upper 0 0 to 9999
B186
4 digits
1289 Home position return Set the activation level of torque limit operation for the
40% 0 to 200%
B187 stopper torque stopper-type home position return.
1290 Home position return Set the waiting time until home position return is started
0.5 s 0 to 10 s
B188 stopper waiting time after the inverter detects the pressing status.
Sudden stop signal (X87) normally open input (NO contact
0
1292 Position control terminal input)
0
B190 input selection Sudden stop signal (X87) normally closed input (NC
1
contact input)
1293 Roll feeding mode 0 Roll feed disabled
0
B191 selection 1 Roll feed enabled
*1 During position control under Vector control, if "1" is set in Pr.419 while the FR-A8AL is not installed (or is disabled), a protective function (E.OPT)
is activated.
*2 During position control under Vector control, if "1110" is set in Pr.419 while the FR-A8APS is not installed (or is disabled), a protective function
(E.OPT) is activated.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
291
Positioning by a point table (Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to Pr.239,
Pr.465 to Pr.494, and Pr.1222 to Pr.1281)
• Create a the point table by setting the following parameters.
Position data
[command Maximum Acceleration Deceleration Auxiliary Point table selection signal
Point table Dwell time
side] speed time time function
Upper Lower REX RH RM RL
1 Pr.466 Pr.465 Pr.4 Pr.1222 Pr.1223 Pr.1224 Pr.1225 OFF ON OFF OFF
2 Pr.468 Pr.467 Pr.5 Pr.1226 Pr.1227 Pr.1228 Pr.1229 OFF OFF ON OFF
3 Pr.470 Pr.469 Pr.6 Pr.1230 Pr.1231 Pr.1232 Pr.1233 OFF OFF OFF ON
4 Pr.472 Pr.471 Pr.24 Pr.1234 Pr.1235 Pr.1236 Pr.1237 OFF OFF ON ON
5 Pr.474 Pr.473 Pr.25 Pr.1238 Pr.1239 Pr.1240 Pr.1241 OFF ON OFF ON
6 Pr.476 Pr.475 Pr.26 Pr.1242 Pr.1243 Pr.1244 Pr.1245 OFF ON ON OFF
7 Pr.478 Pr.477 Pr.27 Pr.1246 Pr.1247 Pr.1248 Pr.1249 OFF ON ON ON
8 Pr.480 Pr.479 Pr.232 Pr.1250 Pr.1251 Pr.1252 Pr.1253 ON OFF OFF OFF
9 Pr.482 Pr.481 Pr.233 Pr.1254 Pr.1255 Pr.1256 Pr.1257 ON OFF OFF ON
10 Pr.484 Pr.483 Pr.234 Pr.1258 Pr.1259 Pr.1260 Pr.1261 ON OFF ON OFF
11 Pr.486 Pr.485 Pr.235 Pr.1262 Pr.1263 Pr.1264 Pr.1265 ON OFF ON ON
12 Pr.488 Pr.487 Pr.236 Pr.1266 Pr.1267 Pr.1268 Pr.1269 ON ON OFF OFF
13 Pr.490 Pr.489 Pr.237 Pr.1270 Pr.1271 Pr.1272 Pr.1273 ON ON OFF ON
14 Pr.492 Pr.491 Pr.238 Pr.1274 Pr.1275 Pr.1276 Pr.1277 ON ON ON OFF
15 Pr.494 Pr.493 Pr.239 Pr.1278 Pr.1279 Pr.1280 Pr.1281 ON ON ON ON
The value is calculated with 2048 (pulse/r) ×100 (rotations per minute) × 4 (multiplier) = 819200 (feed length)
To set 819200 as the first feed length, separate the number into the upper and lower 4 digits as follows:
292 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• Set the auxiliary function for parameters corresponding to each point table.
Auxiliary function
parameter setting
Sign (100 s digit)
Command method
(10 s digit)
Operation method
(1 s digit)
1
0 Individual (0)
1 Absolute position Continuous (1)
2 command (0) Loop operation using the point table selected at the 2
start of the operation (2)
Plus (0)
10 Individual (0)
11 Incremental position Continuous (1)
12 command (1) Loop operation using the point table selected at the 3
start of the operation (2)
100 Individual (0)
101
102
Absolute position
command (0)
Continuous (1)
Loop operation using the point table selected at the
4
start of the operation (2)
Minus (1)
110 Individual (0)
111 Incremental position
command (1)
Continuous (1) 5
112 Loop operation using the point table selected at the
start of the operation (2)
30Hz(Pr.5)
5s 5s
(Pr.1222) (Pr.1223) 6s 6s
0 (Pr.1226) (Pr.1227) Time
Servo ON
(LX) ON
STF ON
RH ON
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
293
NOTE
• During continuous operation, the position command speed drops to 0 in each point table operation before starting the next
point table operation.
• During continuous operation, no point table selection signal is received. Select the position feed length using point table before
turning ON the start command. Only the maximum frequency can be changed during operation.
*1 The positioning operation is the loop. To stop the operation, turn OFF the STF (STR) signal, or turn ON the X87 (sudden stop) input signal.
Operation
3. The operation is switched to the one using the point table 4 (end point).
4. According to the setting in the auxiliary function for the point table 4 (Pr.1237 = "12"), the operation is switched to
the one using the point table 2 selected at the start (loops back to the start point from the end point).
294 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• The following figure shows an operation example using the following point table.
Point table
Target position
Upper Lower
Maximum
speed (Hz)
Acceleration Deceleration
time (s) time (s)
Dwell time
(ms)
Auxiliary function 1
1 (absolute position,
1 5 0 30 1 1 0
continuous)
2 3 0 20 Invalid Invalid 0
11 (incremental 2
position, individual)
1 (absolute position,
3 10 0 10 Invalid Invalid 0
continuous)
4 6 0 5 Invalid Invalid 0
10 (incremental 3
position, individual)
Position command
4
Acceleration time (1 s)
speed of point table 1 Deceleration time (1 s)
30 Hz of point table 1
(Pr.4) 20 Hz
(Pr.5)
10 Hz
(Pr.6) 5 Hz
(Pr.24)
5
0
50000 30000 20000 60000 Time
RM
RL 8
• Set "0" as the dwell time to perform variable speed operation.
NOTE
• The setting values of the point table 1 are used as acceleration/deceleration time.
• After turning ON the start signal, only the setting values of Pr.1283 Home position return speed, Pr.1284 Home position
return creep speed can be changed.
• Perform home position return at the motor switchover.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
295
Selecting the home position return method (Pr.1282 to Pr.1288)
Pr.1282 Home position return
Description
setting method
Deceleration starts when the Proximity dog signal is turned ON. For the home position after turn OFF
of the Proximity dog signal, the position specified by the first Z-phase signal or the position of the first
Z-phase signal shifted by the home position shift amount (Pr.1285, Pr.1286) is used.
Home position
Position command Point table 1
return speed
speed deceleration time
Home position
Creep speed shift amount
0 Dog type*1
Point table 1 Home
Vector
acceleration time position
0
Z-phase Time
LX
STF
Deceleration starts when the proximity dog signal is turned ON. After the proximity dog, the motor
travels the specified travel distance (Pr.1287, Pr.1288). Then, it uses the position specified by the first
Z-phase signal or position of the Z-phase signal shifted by the home position shift amount (Pr.1285,
Pr.1286).
Home position
Position command Point table 1
return speed
speed deceleration time
Home position
Creep speed
1 Count type*1 shift amount
Point table 1 Travel distance
Vector Home
after proximity
acceleration time dog position
0
Time
Z-phase
X76 Proximity dog
296 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Pr.1282 Home position return
Description
setting method
A workpiece is pressed to a mechanical stopper, and the position where it is stopped is set as the 1
home position.
Pressing is confirmed when the estimated speed value has fallen blow Pr.865 Low speed detection
for 0.5 s during activation of the torque limit operation. (While the stopper-type home position is
performed, Pr.1289 Home position return stopper torque is applied.) After Pr.1290 Home position 2
return stopper waiting time has passed after pressing is confirmed, the home position is shifted by
the home position shift distance (Pr.1285 and Pr.1286). After a position command is created and the
absolute value of the droop pulse (after electronic gear) falls below the in-position width, the home
position return is completed. 3
Normal Normal
Torque limit level (Pr.22)
Pressing confirmation level (Pr.1289)
(Pr.22)
0
Home position
Time
5
Point table 1 acceleration time
Creep speed
0.5s Pr.1290
Point table 1
Torque limit deceleration time 6
Point table selection Pressing confirmed
signal
Servo-ON (LX) 7
Start signal
The servo ON position is used as the home position.
RDY
Deceleration starts at the front end of the proximity dog. After the back end is passed, the position is
10
shifted by the post-dog travel distance and home position shift amount. The position after the shifts is
set as the home position.
Set pulses required for deceleration from the creep speed or more as the total of the post-dog travel
distance and home position shift amount.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
297
Pr.1282 Home position return
Description
setting method
Deceleration starts at the front end of the proximity dog, and the position is shifted by the post-dog
travel distance and home position shift distance. The position after the shifts is set as the home
position.
Set pulses required for changing the speed from the home position speed to the creep speed or more
as the total of the post-dog travel distance and home position shift amount.
*1 If it is set under PM sensorless vector control, Home position return parameter setting error (HP3) occurs.
NOTE
• Home position return automatic back-off function
In a system that uses home position return with proximity dog, if the home position return is commanded while the motor is in
a position within the proximity dog, the motor moves out of the proximity dog once, then starts deceleration to stop when it
comes to the proximity dog again. The home position return is performed automatically after that.
Creep speed
Home position
Home position
Home position return start position
return speed
X76 Proximity dog
• The home position return failure (ZA) signal is output while the home position return warning is occurring. To use the ZA
signal, set "56 (positive logic) or 156 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function selection) to
assign the function.
298 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• If STF(STR) is turned OFF during positioning or home position returning when Pr.1221 = "0 (initial value)" is set, it stops
in the time set as Pr.464 Digital position control sudden stop deceleration time.
1
When Pr.1221="0 (initial value)" is set When Pr.1221="1" is set
2
Position command Position command
speed speed
0
Time
0
Time
3
Pr.464
Servo ON Servo ON
(LX) ON (LX) ON
STF ON STF ON 4
• Turning ON the Sudden stop signal (X87) during positioning operation or home position return operation, the motor stops
in the setting time of Pr.464. To assign the X87 signal, set "87" in any of Pr.178 to Pr.189(Input terminal function 5
selection).
6
Position command
speed
0
Time
7
Pr.464
Servo ON
(LX) ON
STF ON 8
X87 ON
• The input logic of the X87 signal Pr.1292 Position control terminal input selection can be set using.
Pr.1292 setting Input logic (X87) 9
Normally open input (NO contact
0 (initial value)
input specification)
1
Normally closed input (NC contact
input specification)
10
NOTE
• When deceleration time longer than the normal deceleration time (including Pr.1223) is set in Pr.464, the normal deceleration
time is applied.
• The X87 signal is effective during position control JOG operation.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
299
• Basic operation example
Position command
speed
Indication of position
command or
0 1000 0 1000 current position
Point table selection
signal
Servo-ON (LX)
Start signal (STF)
Position command
Speed
Motor speed
Dwell time
Point table 1
Point table 2
0
Time
Point table selection signal
(RH)
LX
STF
Y36
MEND
PBSY
300 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• Output signal operation during positioning with home position return
1
Home position
Speed return speed
Home position
Creep speed shift amount
Home
position 2
0
Z-phase Time
3
X76 Proximity dog
LX
STF
ZP 4
Y36
PBSY
MEND 5
NOTE
• When the LX signal is turned OFF, the home position return completed (ZP) signal is turned OFF. When the LX signal is turned
ON again while Pr.419 = "10", the ZP signal is also turned ON. 6
Parameters referred to
Pr.20 Acceleration/deceleration reference frequencypage 349 7
Pr.29 Acceleration/deceleration pattern selectionpage 354
Position control by the command from the positioning module of the programmable controller is available using the FR-A8AL.
Pr. Name Initial value Setting range Description 9
Simple position control by point table (position command given
0
by setting parameters)
1 Position command given by the FR-A8AL pulse train input*1 10
Simple pulse train position command given by the pulse train
2
input to the inverter
Simple position control by point table (position command given
10 by setting parameters)
The home position data is retained at servo-OFF.
Simple position control by point table (position command given
419 Position command source by setting parameters)
0 100
B000 selection The monitor value of the current position 2 is cleared when the
home position return is completed.
Simple position control by point table (position command given
by setting parameters)
110 The home position data is retained at servo-OFF.
The monitor value of the current position 2 is cleared when the
home position return is completed.
Simple position control by point table (position command given
1110 by setting parameters)
The absolute position control with the FR-A8APS is valid.*2
0 Forward/Reverse pulse train
Pulse train + rotation direction
1 Negative logic
sign
428 2 A/B phase pulse train
Command pulse selection 0
B009 3 Forward/Reverse pulse train
Pulse train + rotation direction
4 Positive logic
sign
5 A/B phase pulse train
*1 During position control under Vector control, if "1" is set in Pr.419 while the FR-A8AL is not installed (or is disabled), a protective function (E.OPT)
is activated.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
301
*2 During position control under Vector control, if "1110" is set in Pr.419 while the FR-A8APS is not installed (or is disabled), a protective function
(E.OPT) is activated.
Connection diagram
• Connection with the positioning module of RD75P type MELSEC iQ-R series is also available.
Vector-control-dedicated motors
MCCB Inverter
R/L1 U U
Three-phase
AC power S/L2 V V
IM
supply T/L3 W W
E
Forward stroke end
Earth
STF
(Ground)
Reverse stroke end STR
Pre-excitation (servo on) LX *6
Torque limit SD
Positioning module
MELSEQ iQ-R RD75P command (+) 1
(±10V) (-) 5
FLS
RLS
FR-A8AL
DOG
PA A *1
STOP SD Complementary
PAR B
CLEAR CR
PB C
PP Differential
PULSE F PBR D
*7 PGP Terminating Encoder
NP resistor PZ F
PULSE R ON
PGN PZR G *2
CLRCOM SD PG S
OFF
PG024 VDD SD R
*4
PG0COM FPZ2 PG24
RDYCOM VDD *5 *3
COM OPC
READY RDY
*1 The pin number differs according to the encoder used. Speed control, torque control, and position control by pulse train input are available with
or without the Z-phase being connected.
*2 Connect the encoder so that there is no looseness between the motor and motor shaft. Speed ratio must be 1:1.
*3 Earth (ground) the shield of the encoder cable to the enclosure using a tool such as a P-clip. (Refer to page 86.)
*4 For the complementary, set the terminating resistor selection switch to the OFF position (initial status). (Refer to page 86.)
*5 A separate external power supply of 15 V is necessary according to the encoder power specification. When the encoder output is the differential
line driver type, only 5 V can be input. When the 24 V power supply of the FR-A8AL is used, the power is supplied to the encoder through terminal
PG24. When the 5 V/12 V power supply of the FR-A8AL is used, the power is supplied to the encoder through terminal PGV. Do not use the
external power supply simultaneously with the 5 V/12 V power supply or the 24 V power supply. Make the voltage of the external power supply
the same as the encoder output voltage, and connect the external power supply between terminals PG and SD.
*6 Assign the function using Pr.178 to Pr.184, Pr.187 to Pr.189 (input terminal function selection).
*7 The pulse signal from the position module is available for both open collector and differential line driver. However, the connections are different.
(The following figure shows an example for differential line driver.) For the connection method, refer to the Instruction Manual of the FR-A8AL.
302 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Operation outline
• If the pre-excitation/servo ON (LX) signal is turned ON, output shutoff is canceled and the position control preparation 1
ready (RDY) signal is turned ON after 0.1 seconds. When the STF signal (forward stroke end) or the STR signal (reverse
stroke end) is turned ON, the motor rotates according to the command pulse. When the forward (reverse) stroke end signal
is turned OFF, the motor does not rotate in the corresponding direction. 2
Forward rotation
Actual rotation
Reverse rotation
3
Base signal
Servo on (LX)
Forward stroke end (STF)
4
Reverse stroke end (STR)
Position control preparation ready (RDY)
6
Interface between the position module and the inverter.
• To operate an inverter using a positioning module, the interfaces for the position command pulse train must agree with
each other. 7
Output form Hardware Input pulse frequency
OPC
Open collector Max 200k pulses/s
9
PP(NP)
SD
OPC
Differential line driver PP(NP) Max 500k pulses/s
PGP(PGN)
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
303
• The command pulse is switchable according to the position module as shown in the following table.
During forward During reverse Setting of
Command pulse train type Remarks
rotation rotation Pr.428
RD75 (CW/CWW mode)
Forward pulse train PP (Note)When (CW/CWW mode) and (PULSE/
0 (initial value)
Reverse pulse train NP SIGN mode) are connected incorrectly, the
motor moves only one direction.
PP
Pulse train + sign 1 RD75 (PULSE/SIGN mode)
Negative NP L H
logic The number of pulses are multiplied by 4 to
count. When differential line driver is used,
PP the number of pulses after the number
A phase pulse train
2 encoder pulses is quadruplicated should be
B phase pulse train NP 500k pulses/s or lower. When open collector
is used, the number should be 200k pulses/s
or lower.
PP
Pulse train + sign 4
NP H L
Positive
logic The number of pulses are multiplied by 4 to
count. When differential line driver is used,
PP the number of pulses after the number
A phase pulse train
5 encoder pulses is quadruplicated should be
B phase pulse train NP 500k pulses/s or lower. When open collector
is used, the number should be 200k pulses/s
or lower.
The simple position pulse train command can be input by pulse train input and simple position pulse train signal (NP) to the
JOG terminal.
Pr. Name Initial value Setting range Description
Simple position control by point table (position command given
0
419 Position command source by setting parameters)
0
B000 selection Simple pulse train position command given by the pulse train
2
input to the inverter
428 0 to 2 Pulse train + rotation direction Negative logic
Command pulse selection 0
B009 3 to 5 sign Positive logic
304 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Operation outline
• If the Pre-excitation/servo ON (LX) signal is turned ON, output shutoff is canceled and the Position control preparation 1
ready (RDY) signal is turned ON after 0.1 s. When STF (forward stroke end signal) or STR (reverse stroke end signal) is
turned ON, the motor rotates according to the command pulse. When the forward (reverse) stroke end signal is turned
OFF, the motor does not rotate in the corresponding direction. 2
Forward rotation
Actual rotation
Reverse rotation 3
Base signal
Servo on (LX)
Forward stroke end (STF) 4
Reverse stroke end (STR)
Operation ready completion (RDY)
0.1s
Inverter pulse train command 5
Sign signal (NP)
In-position (Y36)
3 to 5
Positive Pulse train + rotation JOG 9
logic direction sign NP H L
• Select Vector control or PM sensorless vector control to select the position control method.
10
NOTE
• If Pr.419 = "2" (simple pulse train position command) is set, terminal JOG is used for the simple position pulse train input
regardless of the Pr.291 Pulse train I/O selection pulse train input/output selection setting.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
305
• For a terminal used for the CLR signal, set "59" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign
the function.
When Pr. 429 = "0" When Pr. 429 = "1 (initial value)"
NOTE
• The accumulated number of pulses is cleared at base shutoff or when the CLR/CLRN signal is turned ON.
• Refer to page 306 for the condition to clear the values of the position pulse.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
306 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• Also, setting "26 to 31" in Pr.52, Pr.774 to Pr.776, Pr.992 (multifunction monitor) changes the electronic gear operation
setting in the case of monitoring pulses. (Refer to page 424.)
1
Pr.430 setting Description
[][][]0 Displays the lower of the position command (accumulated value of command pulses).
[][][]1 Displays the upper of the position command (accumulated value of command pulses).
[][][]2 Displays the lower of the current position (accumulated value of feedback pulses*1).
2
[][][]3 Pulse monitor Displays the upper of the current position (accumulated value of feedback pulses*1).
[][][]4 selection Displays the lower of the accumulated value of droop pulses.
[][][]5 Displays the upper of the accumulated value of droop pulses. 3
[][]12 Displays the lower of the current position 2 (accumulated value of feedback pulses*1).
[][]13 Displays the upper of the current position 2 (accumulated value of feedback pulses*1).
[]0[][]
For pulse monitor
Displays the monitor item selected in the pulse monitor selection after the electronic gear operation. 4
Displays the monitor item selected in the pulse monitor selection before the electronic gear
[]1[][] selection
operation.
Displays the monitor item selected in the multifunction monitor (position command, current position,
0[][][]
and droop pulse) before the electronic gear operation. 5
For the multifunction Displays the item in the PLC function special register (position command, current position, droop
monitor/ pulse, and current position 2) before the electronic gear operation.
PLC function special Displays the monitor item selected in the multifunction monitor (position command, current position,
1[][][]
register and droop pulse) after the electronic gear operation. 6
Displays the item in the PLC function special register (position command, current position, droop
pulse, and current position 2) after the electronic gear operation.
Displays the monitor item selected in the multifunction monitor (position command, current position,
and droop pulse) after the electronic gear operation. 7
8888
Displays the item in the PLC function special register (position command, current position, droop
Output frequency pulse, and current position 2) after the electronic gear operation.
display Displays the monitor item selected in the multifunction monitor (position command, current position,
and droop pulse) before the electronic gear operation. 8
9999
Displays the item in the PLC function special register (position command, current position, droop
pulse, and current position 2) before the electronic gear operation.
*1 Accumulated value of estimated feedback pulses when PM sensorless vector control is used 9
• Position pulses are cleared according to the following conditions.
Position command / current position /
Current position 2
Clearing condition
droop pulse 10
Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 = Pr.419 =
0, 100 10, 110 1, 2 1110 0 10 100 110 1, 2 1110
Servo-OFF (LX-OFF)
○ × ○ × × × × × × ×
(output shutoff)
Clear signal input*2 ○ ○*3 ○ ×*5 ○ ○*3 ○ ○*3 ○ ×*5
Home position return
completed ○*1 ○*1*4 —*6 ○*1*4 × × ○*1 ○*1 —*6 ○*1
NOTE
• The monitor value of the current position 2 is not cleared when switching between the first and second motors.
• For the details of the special register for the PLC function, refer to the PLC Function Programming Manual.
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
307
• If -99999999 or 99999999 is exceeded on the pulse monitor, the monitor value is reset to 0.
Display data Monitor display without signs Monitor display with signs
Lower monitor
-10000
Upper monitor
Lower monitor
-100
Upper monitor
NOTE
• The pulse count starts at servo on.
308 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Cumulative pulse Cumulative pulse
Cumulative pulse
overflow times
Cumulative pulse
overflow times
1
Clear signal Clear signal
(X52, X53) ON (X52, X53) ON
2
Cleared at the ON edge Cleared while the signal is ON
NOTE
6
• When the power is turned OFF during the reset process, the cumulative pulse monitor value and the cumulative pulse overflow
times are not stored in the EEPROM.
• For storing the cumulative pulse monitor value and the cumulative pulse overflow times, in the EEPROM at power OFF, 7
connect R1/L11 with P/+, and S1/L21 with N/- so that the control power is retained. When connecting the FR-HC2 high power
factor converter or the converter unit (FR-CC2), assign the FR-HC2/FR-CC2 instantaneous power failure detection (X11)
signal to an input terminal to input the IPF signal from the FR-HC2/FR-CC2 to the terminal for X11 signal.
8
Parameters referred to
Pr.52 Operation panel main monitor selectionpage 424
9
5.5.9 Electronic gear settings
Vector PM 10
Set the gear ratio between the machine gear and motor gear.
Setting
Pr. Name Initial value Description
range
Command pulse scaling factor
420
numerator (electronic gear 1 1 to 32767
B001
numerator) Set the electronic gear.
Command pulse multiplication Pr.420 is the numerator and Pr.421 is the denominator.
421
denominator (electronic gear 1 1 to 32767
B002
denominator)
Use it when the rotation is not smooth because the
424 Position command acceleration/
0s 0 to 50 s electronic gear ratio is large (10 times or larger) and the
B005 deceleration time constant
rotation speed is slow.
The travel distance in 1 command pulse can be separately specified with a parameter and so an integer can be set as the travel
distance in 1 command pulse.
Δs Pr.420
Δ = ×
Pf Pr.421
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
309
The following formula shows the relationship between the motor speed and internal command pulse frequency.
Pr.420 No fo: internal command pulse frequency [pps]
fo × = Pf ×
Pr.421 60 No: motor rotation speed [r/min]
NOTE
• Set the electronic gear ratio in the range of 1/50 to 20. Note that, if the setting value is too small, the speed command will also
be too small; while if it is too large, the speed ripple will be too large.
The number of droop pulses (ε) is 8192 with the initial value Kp = 25 s-1.
Since the inverter has droop pulses during operation, a stop settling time (ts), which is the time between the zero command
output and the motor stop, is required. Set the operation pattern taking into the account the stop setting time.
1
ts = 3 × [s]
Kp
The stop settling time (ts) is 0.12 s for the initial value Kp = 25 s-1.
The accuracy of positioning ∆ε is (5 to 10) × ∆ = ∆ε [mm]
310 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• If the command pulse frequency varies rapidly when no acceleration time can be assigned to the command pulse,
overshoot or excessive error alarms may occur. Set this option in such a case to set the acceleration/deceleration time.
Normally it is set to 0.
1
Parameters referred to
Pr.422 Position control gainpage 312
2
5.5.10 Position adjustment parameter settings
Vector PM
3
Pr. Name Initial value Setting range Description
426 Set the number of droop pulses that triggers the In-position
In-position width 100 pulses 0 to 32767 pulses
B007 (Y36) signal. 4
Set the number droop pulses that activates Excessive
427 0 to 400K
Excessive level error 40K position fault (E.OD).
B008
9999 Function disabled
1294 Position detection lower
0 0 to 9999 Set the lower four digits of the position detection value.
5
B192 4 digits
1295 Position detection upper
0 0 to 9999 Set the upper four digits of the position detection value.
B193 4 digits
0 The position is detected on both the plus and minus sides. 6
1296 Position detection
0 1 The position is detected on the plus side only.
B194 selection
2 The position is detected on the minus side only.
1297
B195
Position detection
hysteresis width
0 0 to 32767
Set the hysteresis width for the detected position where the
Position detection level (FP) signal turns ON.
7
ON ON
FP (For Pr.1296 = 0)
ON
FP (For Pr.1296 = 1)
ON
FP (For Pr.1296 = 2)
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
311
• When a current position varies, the Position detection level (FP) signal may repeat ON/OFF (chatter). Setting hysteresis
to the detected position prevents chattering of the signal. Use Pr.1297 Position detection hysteresis width to set a
hysteresis width.
Current position
Position
[before electronic gear]
Pr.1297
Position detection level
Pr.1295 10000 + Pr.1294 Pr.1297
Time
ON ON ON
FP
Easy gain tuning is provided as an easy tuning method. For details about easy gain tuning, refer to page 244.
If easy gain tuning does not produce any effect, make fine adjustments by using the following parameters.
Set "0" to Pr.819 Easy gain tuning selection before setting the following parameters.
Pr. Name Initial value Setting range Description
422
B003
Position control gain 25 s-1 0 to 150 s-1 Set the gain for the position loop.
1298
Second position control gain 25 s-1 0 to 150 s-1 Set the position loop gain for the second motor.
B013
423 Function to cancel a delay caused by the droop pulses in the
Position feed forward gain 0% 0 to 100%
B004 deviation counter.
425 Position feed forward
0s 0 to 5 s Input the first delay filter for the feed forward command.
B006 command filter
446
B012
Model position control gain 25 s-1 0 to 150 s-1 Set the gain for the model position controller.
828
Model speed control gain 60% 0 to 1000% Set the gain for the model speed controller.
G224
Speed feed forward control/ 0, 1 Perform position feed forward control.
877
model adaptive speed 0
G220 2 Model adaptive position control becomes valid.
control selection
880
Load inertia ratio 7-fold 0 to 200-fold Set the load inertia ratio for the motor.
C114
Response is slow. Increase the setting value by 3 s-1 until immediately before an overshoot,
stop-time vibration or other instable phenomenon does not occur, and set
about 80 to 90% of that value.
Lower the setting value.
Overshoot, stop-time
vibration or other instable Lower the setting value by 3 s-1 until immediately before an overshoot, stop-
phenomenon occurs. time vibration or other instable phenomenon does not occur, and set about
80 to 90% of that value.
312 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
• This function has no effects on servo rigidity at a stop.
• Normally set this parameter to 0.
• When setting Pr.423, set Pr.877 = "0 or 1" to enable position feed forward control.
1
Model adaptive position control (Pr.446)
• Set each response for position commands and for load and external disturbances individually. 2
• Set this parameter when a sufficient position response cannot be obtained after setting Pr.422.
• When setting Pr.446, set Pr.877 = "2" to enable the model adaptive position control, Pr.828 Model speed control gain ≠
"0", and a load inertia ratio in Pr.880 Load inertia ratio. 3
• Set a small value in Pr.446 first, and then increase the setting gradually and use this parameter within the range where an
overshoot or vibration will not occur.
4
5.5.12 Troubleshooting in position control
5
Vector PM
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
313
Flowchart
Position control is not
exercised normally
Motor or machine is Y
hunting.
N
The position loop gain N
(Pr. 422) is high.
Y
Perform easy gain tuning.
The speed control gain is high.
Decrease Decrease the speed control
the position loop gain proportional gain (Pr. 820).
(Pr. 422). Increase the speed control
integral time (Pr. 821).
Machine operation is Y
unstable.
Insufficient torque.
N Increase the excitation
ratio (Pr. 854).
NOTE
• The speed command of position control is related to speed control. (Refer to page 229.)
314 5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
Parameters referred to
Pr.7 Acceleration timepage 349
Pr.8 Deceleration timepage 349 1
Pr.72 PWM frequency selectionpage 339
Pr.800 Control method selectionpage 215
Pr.802 Pre-excitation selectionpage 681
Pr.819 Easy gain tuning selectionpage 244
Pr.820 Speed control P gain 1page 244
Pr.821 Speed control integral time 1page 244
2
10
5. PARAMETERS
5.5 Position control under vector control and PM sensorless vector control
315
5.6 Adjustment during Real sensorless vector control,
Vector control, PM sensorless vector control
Refer to
Purpose Parameter to set
page
To stabilize speed and torque feedback Speed detection filter P.G215, P.G216, Pr.823, Pr.827,
316
signal Torque detection filter P.G315, P.G316 Pr.833, Pr.837
To change excitation ratio Excitation ratio P.G217 Pr.854 316
Set time constant of primary delay filter for speed feedback signal and torque feedback signal.
Speed loop response is reduced. Under ordinary circumstances, therefore, use the initial value as it is.
Pr. Name Initial value Setting range Description
0 Without filter
823
Speed detection filter 1 0.001 s Set the time constant of primary delay filter for speed
G215*1 0.001 to 0.1 s
feedback signal.
0 Without filter
827
Torque detection filter 1 0s Set the time constant of primary delay filter torque
G216 0.001 to 0.1 s
feedback signal.
Second function of Pr.823 (enabled when the RT
833 0 to 0.1 s
*1 Speed detection filter 2 9999 signal is ON)
G315
9999 Same as Pr.823 setting
Second function of Pr.827 (enabled when the RT
837 0 to 0.1 s
Torque detection filter 2 9999 signal is ON)
G316
9999 Same as Pr.827 setting
NOTE
• The RT signal is a second function selection signal which also enables other second functions. (Refer to page 500.)
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
The excitation ratio can be lowered to enhance efficiency for light loads. (Motor magnetic noise can be reduced.)
316 5. PARAMETERS
5.6 Adjustment during Real sensorless vector control, Vector control, PM sensorless vector control
Pr. Name Initial value
Setting
range
Description 1
854
Excitation ratio 100% 0 to 100% Set an excitation ratio when there is no load.
G217
2
Excitation ratio
[%]
100 3
(Initial value)
Pr.854
setting
4
0 100 Load[%]
5
NOTE
• When excitation ratio is reduced, output torque startup is less responsive.
• The setting of Pr.854 is invalid if Pr.858 Terminal 4 function assignment or Pr.868 Terminal 1 function assignment is set 6
to "1" (flux command according to terminal).
NOTE
• Pr.834 Speed control P gain 2 and Pr.831 Speed control integral time 2 are valid when terminal RT is ON.
In this case, replace them for Pr.824 and Pr.825 in the description above.
5. PARAMETERS
5.6 Adjustment during Real sensorless vector control, Vector control, PM sensorless vector control
317
5.7 (E) Environment setting parameters
Refer to
Purpose Parameter to set
page
To set the time Real time clock function P.E020 to P.E022 Pr.1006 to Pr.1008 318
To set a limit for the reset function.
Reset selection/
To shut off output if the operation panel
Disconnected PU P.E100 to
disconnects. Pr.75 320
detection/PUStop P.E102, P.E107
To force deceleration to a stop on the
selection/Reset limit
operation panel.
To select the display language of the PU display language
P.E103 Pr.145 322
parameter unit selection
To control the buzzer of the parameter unit and
PU buzzer control P.E104 Pr.990 322
operation panel
To adjust the LCD contrast of the parameter
PU contrast adjustment P.E105 Pr.991 322
unit
To turn OFF the operation panel when not
Display-off mode P.E106 Pr.1048 323
using it for a certain period of time
To switch the monitor display of the operation
panel to the PID set point setting screen by Direct setting P.E108 Pr.1000 323
simply turning the setting dial
To use the USB memory USB host reset P.E110 Pr.1049 324
To use the setting dial of the operation panel
Operation panel operation
like a potentiometer to set the frequency. P.E200 Pr.161 324
selection
To disable the operation panel.
To change the frequency change increments
Frequency change
which changes when using the setting dial of P.E201 Pr.295 325
increment amount setting
the operation panel.
To use the regeneration unit to increase the Regenerative brake
P.E300, P.G107 Pr.30, Pr.70 689
motor braking torque selection
To change the overload current rating
Multiple rating setting P.E301 Pr.570 326
specification
Input voltage mode
To input a voltage between 480 V and 500 V P.E302 Pr.977 327
selection
Parameter write disable
To prevent parameter rewriting P.E400 Pr.77 328
selection
To restrict parameters with a password Password P.E410, P.E411 Pr.296, Pr.297 331
To use parameters freely Free parameter P.E420, P.E421 Pr.888, Pr.889 333
To change parameter settings for an IPM motor
IPM parameter initialization P.E430 Pr.998 225
as a batch
Automatic parameter
To set multiple parameters as a batch P.E431 Pr.999 333
setting
Applicable parameter
Pr.160, Pr.172 to
To display the required parameters display and user group P.E440 to P.E443 337
Pr.174
function
Parameter copy alarm
To release the Parameter copy warning (CP) P.E490 Pr.989 708
release
PWM carrier frequency Pr.72, Pr.240,
To reduce the motor noise and EMI P.E600 to P.E602 339
changing Pr.260
Inverter parts life display P.E700 to P.E704 Pr.255 to Pr.259 341
Maintenance output Pr.503 to Pr.504,
To understand the maintenance time of P.E710 to P.E715 345
function Pr.686 to Pr.689
inverter parts and peripheral devices
Current average monitor
P.E720 to P.E722 Pr.555 to Pr.557 346
signal
318 5. PARAMETERS
5.7 (E) Environment setting parameters
The real time clock function is enabled using an optional LCD operation panel (FR-LU08).
Pr.
1006
Name Initial value Setting range Description
1
Clock (year) 2000 years 2000 to 2099 Set the year.
E020
101 to 131, 201 to 228, (229), Set the month and day.
1007 Clock (month, 101
301 to 331, 401 to 430, 501 to 531,
601 to 630, 701 to 731, 801 to 831,
1000's and 100's digits: January to December,
10's and 1's digits: 1 to end of month (28, 29, 30 or
2
E021 day) (January 1)
901 to 930, 1001 to 1031, 31).
1101 to 1130, 1201 to 1231 For December 31, set "1231".
0 to 59, 100 to 159, 200 to 259,
300 to 359, 400 to 459, 500 to 559,
3
600 to 659, 700 to 759, 800 to 859, 900 to
959, 1000 to 1059,
Set the hour and minute using the 24-hour clock.
1008 Clock (hour, 0
1100 to 1159, 1200 to 1259,
1300 to 1359, 1400 to 1459,
1000's and 100's digits: 0 to 23 hours, 4
E022 minute) (00:00) 10's and 1's digits: 0 to 59 minutes.
1500 to 1559, 1600 to 1659,
For 23:59, set "2359".
1700 to 1759, 1800 to 1859,
1900 to 1959, 2000 to 2059,
2100 to 2159, 2200 to 2259, 5
2300 to 2359
NOTE 7
• The clock's count-up data is saved in the inverter's EEPROM every 10 minutes.
• The clock does not count up while the control circuit power supply is OFF. The clock function must be reset after turning ON
the power supply. Use a separate power supply, such as an external 24 V power supply, for the control circuit of the simple
clock function, and supply power continuously to this control circuit. 8
• In the initial setting, inverter reset is performed if supplying power to the main circuit is started when power is supplied only to
the control circuit. Then, the clock information stored in EEPROM is restored. Reset at the start of supplying power to the main
circuit can be disabled by setting Pr.30 Regenerative function selection. (Refer to page 689.)
• The set clock is also used for functions such as faults history.
9
0. 00 Hz 0. 00 Hz 0. 00 Hz
−−− STOP PU −−− STOP PU −−− STOP PU
1:00
PREV SET NEXT
2:00
PREV SET NEXT
3:00
PREV SET NEXT
Synchronization Synchronization
• When the FR-LU08 is connected to the inverter, the internal clock of the inverter can be synchronized with the clock of FR-
LU08. (Real time clock function) With a battery (CR1216), the FR-LU08 time count continues even if the main power of the
inverter is turned OFF. (The time count of the inverter internal clock does not continue when the inverter power is turned
OFF.)
• To adjust the clock of FR-LU08, use the FR-LU08 and set Pr.1006 to Pr.1008.
NOTE
• Time adjustment between the inverter internal clock and the FR-LU08 is performed every one minute.
• When the FR-LU08 clock is initialized after the battery is exhausted for example, the inverter internal clock is valid.
5. PARAMETERS
5.7 (E) Environment setting parameters
319
5.7.2 Reset selection/disconnected PU detection/PU
stop selection
The reset input acceptance, disconnected PU (operation panel/parameter unit) connector detection function and PU stop
function (PU stop) can be selected.
Initial
Pr. Name Setting range Description
value
Reset selection/ 0 to 3, 14 to 17*1
Disconnected PU For the initial setting, reset is always enabled, without
75 14 0 to 3, 14 to 17, 100 to
detection/PU stop disconnected PU detection, and with the PU stop function.
selection 103, 114 to 117*2
0 Reset input is always enabled.
E100 Reset selection 0 Reset input is enabled only when the protective function is
1
activated.
Disconnected PU 0 Operation continues even when the PU is disconnected.
E101 0
detection 1 The inverter output is shut off when the PU is disconnected.
Decelerates to a stop when the STOP key is pressed in PU
0
operation mode only.
E102 PU stop selection 1 Decelerates to a stop when the STOP key for PU is pressed
1 in any of the PU, external and communication operation
modes.
0 Reset limit is disabled.
E107 Reset limit 0
1*2 Reset limit is enabled.
The parameters above do not return to their initial values even if parameter (all) clear is executed.
*1 The setting range of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower
*2 The setting range of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher
Pr.75
Reset selection Disconnected PU detection PU stop selection
setting*3
0, 100 Reset input always enabled
Operation continues even when
Reset input enabled only when the
1, 101 PU is disconnected.
protective function activated. Decelerates to a stop when is input in the PU
2, 102 Reset input always enabled
Inverter output shut off when PU operation mode only.
Reset input enabled only when the
3, 103 is disconnected.
protective function activated.
14 (initial
Reset input always enabled
value), 114 Operation continues even when
Reset input enabled only when the PU is disconnected.
15, 115 Decelerates to a stop when is input in any of
protective function activated.
16, 116 Reset input always enabled the PU, External and Network operation modes.
Inverter output shut off when PU
Reset input enabled only when the
17, 117 is disconnected.
protective function activated.
*3 Setting Pr.75 = any of "100 to 103 and 114 to 117" enables the Reset limit. (The setting is available for the FR-A820-03800(75K) or higher and
FR-A840-02160(75K) or higher.)
NOTE
• When the RES signal is input during operation, the motor coasts since the inverter being reset shuts off the output. Also, the
cumulative values of electronic thermal O/L relay and regenerative brake duty are cleared.
• The input of the PU reset key is only enabled when the protective function is activated, regardless of the P.E100 and Pr.75
settings.
320 5. PARAMETERS
5.7 (E) Environment setting parameters
NOTE
• When the PU has been disconnected since before power-ON, the output is not shut off. 1
• To restart, confirm that the PU is connected and then reset.
• When P.E101 = "0" or Pr.75 = "0, 1, 14, 15, 100, 101, 114, or 115" (operation continues even when PU disconnected),
decelerates to a stop when PU is disconnected during PU JOG operation.
• When RS-485 communication operation is performed through the PU connector, the reset selection/PU stop selection function 2
is valid but the disconnected PU detection function is invalid. (The communication is checked according to Pr.122 PU
communication check time interval.)
3
PU stop selection (P.E102)
• The inverter operation can be stopped by pressing on the PU in any of the operation modes of PU operation, 4
External operation, and Network operation.
• When the operation is stopped by stop command from the PU, " " (PU stop) is displayed on the PU. A fault output
5
is not provided.
• When P.E102 = "0" or Pr.75 = "0 to 3, 100 to 103" is set, deceleration stop using is valid only in the PU operation
mode.
6
NOTE
• When Pr.551 PU mode operation command source selection = "1" (PU mode RS-485 terminal), deceleration stop (PU
7
stop) is performed even when is input during operation in PU mode via RS-485 communication.
8
How to restart after stopping with input from the PU during External
operation (PU stop (PS) release method)
• PU stop release method for operation panel (FR-DU08)
9
1. After completion of deceleration to a stop, switch OFF the STF and STR signal.
1. After completion of deceleration to a stop, switch OFF the STF or STR signal.
Speed
Time
Key
Operation
panel
Key
STF ON
(STR) OFF
• The motor can be restarted by resetting the power supply or resetting with the RES signal.
NOTE
• Even when Pr.250 Stop selection ≠ "9999" is set and coasting stop is selected, deceleration stop and not coasting stop is
performed in the PU stop function during External operation.
5. PARAMETERS
5.7 (E) Environment setting parameters
321
Reset limit function (P.E107)
• When P.E107 = "1" or Pr.75 = any of "100 to 103 and 114 to 117", if an electronic thermal O/L relay or an overcurrent
protective function (E.THM, E.THT, E.OC[]) is activated while one of them has been already activated within 3 minutes,
the inverter does not accept any reset command (RES signal, etc.) for about 3 minutes from the second activation.
• The reset limit function is available with the FR-A820-03800(75K) or higher and the FR-A840-02160(75K) or higher.
NOTE
• Resetting the inverter power (turning OFF the control power) clears the accumulated thermal value.
• When the retry function is set enabled (Pr.67 Number of retries at fault occurrence ≠ "0"), the reset limit function is disabled.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which
is dangerous.
Parameters referred to
Pr.67 Number of retries at fault occurrencepage 405
Pr.79 Operation mode selectionpage 370
Pr.250 Stop selectionpage 688
Pr.551 PU mode operation command source selectionpage 380
NOTE
• When with buzzer is set, the buzzer sounds if an inverter fault occurs.
322 5. PARAMETERS
5.7 (E) Environment setting parameters
5.7.6 Display-off mode
The LED of the operation panel (FR-DU08) can be turned OFF when it has not been operated for a certain period of time. 1
Pr. Name Initial value Setting range Description
0 Display-off mode is disabled.
1048
E106
Display-off waiting time 0
1 to 60 min
Set time until the LED of the operation panel is turned 2
OFF.
• If the operation panel has not been operated for the time set in Pr.1048, the display-off mode is enabled and its LED is
turned OFF. 3
• In the display-off mode, the "MON" LED blinks slowly.
• The count to display off is reset at installation/removal of the operation panel, power-ON/OFF of the inverter, or inverter
reset. 4
• Display-off mode end condition
Operation of the operation panel
Occurrence of a warning, alarm, or fault 5
Installation/removal of the operation panel, power-ON/OFF of the inverter, or inverter reset
Connection/disconnection of the USB A connector
NOTE 6
• The "P.RUN" LED is ON in the display-off mode (when the PLC function is operating). (During PLC function operation)
7
5.7.7 Direct setting
The PID set point setting screen (direct setting screen) can be displayed first on the LCD operation panel (FR-LU08) according
to the parameter setting. 8
Pr. Name Initial value Setting range Description
0 Displays the Frequency setting screen.
1000
Direct setting selection 0
1 Displays the direct setting screen (for set point setting). 9
E108 Displays the direct setting screen (for set point setting)
2
and the frequency setting screen.
• This function is useful for setting the PID set point by operation panel.
• The monitor display can be switched from the main monitor screen to the set point setting screen for the PID action simply
10
by operation, according to the setting of Pr.1000 Direct setting selection. On each setting screen, turn to input
Example of screen switching and shifting when the PID control is enabled (Pr.128 ≠ "0")
∗2,∗3 ∗2,∗3 ∗3
Output frequency 12: 34 PID act set pnt 2ndPID set point Frequency Setting
Pres value 10.0PSI Pres value 10.0PSI Pres value 0.00Hz
Set value 10.0PSI (NEXT) Set value 10.0PSI (NEXT) Set value 100.00Hz
0.00 Hz
STOP PU STOP PU STOP PU STOP PU
PREV SET NEXT BACK SET NNEXT
EXT BACK SET NNEXT
EXT BACK SET NNEXT
EXT
One of the Main monitor screen Direct #1 screen ∗4 Direct #2 screen ∗4 Frequency setting screen ∗5
∗1 ∗2
∗3
(NEXT)
(NEXT)
Parameters referred to
Pr.128 PID action selection page 570
5. PARAMETERS
5.7 (E) Environment setting parameters
323
5.7.8 Resetting USB host errors
When a USB device is connected to the USB connector (connector A), the USB host error can be canceled without performing
an inverter reset.
Pr. Name Initial value Setting range Description
1049 0 Read only
USB host reset 0
E110 1 Resets the USB host.
• Parameter copy (refer to page 708) and the trace function (refer to page 616) can be used when a USB device (such as a
USB memory) is connected to the USB connector (connector A).
• When a device such as a USB charger is connected to the USB connector and an excessive current (500 mA or higher)
flows, USB host error " " (UF warning) is displayed on the operation panel.
• When the UF warning appears, the USB error can be canceled by removing the USB device and setting Pr.1049 = "1".
(The UF warning can also be canceled by resetting the inverter power or resetting with the RES signal.)
needs not to be pressed. (For the details of the operation method, refer to page 148.)
NOTE
• If the display changes from blinking "60.00" to "0.00", the setting value of Pr.161 may not be "1".
• The newly-set frequency is be saved as the set frequency in EEPROM after 10 s.
• When setting the frequency by turning the setting dial, the frequency goes up to the set value of Pr.1 Maximum frequency.
Be aware of what frequency Pr.1 is set to, and adjust the setting of Pr.1 according to the application.
Disabling the setting dial and key operation of the operation panel (by
holding down the MODE key for 2 seconds)
• Operation using the setting dial and keys of the operation panel (FR-DU08) can be disabled to prevent parameter changes,
unexpected starts or frequency changes.
• Set Pr.161 to "10 or 11" and then press for 2 seconds to disable setting dial or key operations.
• When setting dial and key operations are disabled, " " appears on the operation panel. If setting dial or key
operation is attempted while dial and key operations are disabled, " " appears. (When a setting dial or key
operation is not performed for 2 seconds, the monitor display appears.)
• To enable the setting dial and key operation again, press for 2 seconds.
324 5. PARAMETERS
5.7 (E) Environment setting parameters
NOTE
• Even if setting dial and key operations are disabled, the monitor indicator and are enabled. 1
• The PU stop cannot be released with key operations unless the operation lock is released first.
2
Parameters referred to
Pr.1 Maximum frequencypage 407
10
1 click 1 click
NOTE
• When machine speed display is selected in Pr.37 Speed display, the minimum increments of change are determined by
Pr.295 as well. Note that the setting value may differ as speed setting changes the set machine speed and converts it to the
speed display again.
• For Pr.295, the increments are not displayed.
• The Pr.295 setting is enabled only for the changes to the set frequency. It does not apply to the settings of other parameters
related to frequency.
• When 10 is set, the frequency setting changes in 10 Hz increments. Be cautious of excessive speed (in potentiometer mode).
Parameters referred to
Pr.37 Speed displaypage 422
5. PARAMETERS
5.7 (E) Environment setting parameters
325
5.7.11 Multiple rating setting
Four rating types of different rated current and permissible load can be selected. The optimal inverter rating can be chosen in
accordance with the application, enabling equipment size to be reduced.
Setting Description (overload current rating,
Pr. Name Initial value
range surrounding air temperature)
SLD rating,
0*1 110% 60 s, 120% 3 s (inverse-time characteristics)
at surrounding air temperature of 40°C
LD rating,
1 120% 60 s, 150% 3 s (inverse-time characteristics)
570 at surrounding air temperature of 50°C
Multiple rating setting 2
E301 ND rating,
2 150% 60 s, 200% 3 s (inverse-time characteristics)
at surrounding air temperature of 50°C
HD rating,
3*1 200% 60 s, 250% 3 s (inverse-time characteristics)
at surrounding air temperature of 50°C
326 5. PARAMETERS
5.7 (E) Environment setting parameters
200 V class FR-A820-[]
00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330 03160 03800 04750
Pr.570
(0.4K) (0.75K) (1.5K) (2.2K) (3.7K) (5.5K) (7.5K) (11K) (15K) (18.5K) (22K) (30K) (37K) (45K) (55K) (75K) (90K) 1
Pr. 400 V class: FR-A840-[]
setting 02600
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800 02160 (90K)
(0.4K) (0.75K) (1.5K) (2.2K) (3.7K) (5.5K) (7.5K) (11K) (15K) (18.5K) (22K) (30K) (37K) (45K) (55K) (75K) or
higher 2
0, 1 5 5 5 5 5 5 15 15 15 15 15 15 15 15 15 15 15
7
2 5 5 5 5 5 5 5 15 15 15 15 15 15 15 15 15 15
(s)
3 5 5 5 5 5 5 5 5 15 15 15 15 15 15 15 15 15
8
0, 1 10 10 10 10 10 10 30 30 30 30 30 30 30 30 30 30 30 3
2 5 5 5 5 5 5 5 15 15 15 15 15 15 15 15 15 15
(s)
3 5 5 5 5 5 5 5 5 15 15 15 15 15 15 15 15 15
0, 1 4 4 4 4 4 4 2 2 2 2 2 2 2 2 1 1 1
12
(%)
2 4 4 4 4 4 4 4 2 2 2 2 2 2 2 2 1 1 4
3 4 4 4 4 4 4 4 4 2 2 2 2 2 2 2 2 1
*2 The rated current and motor capacity differ depending on the inverter capacity. Refer to the inverter rated specifications (page 790).
*3 The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the inverter rated current.
• Setting Pr.292 Automatic acceleration/deceleration = "5 or 6 (lift mode)" changes the stall prevention operation level as
5
shown below.
Pr. Setting
0 1
Pr.570 setting
2 (initial value) 3
Refer to
page
6
5 110% 120% 150% 200%
292 365
6 115% 140% 180% 230%
7
NOTE
• When Pr.570 = "0" (SLD rating), carrier frequency automatic reduction is enabled regardless of the setting in Pr.260.
• To use the FR-A820-03160(55K) and the FR-A840-01800(55K) in the LD and SLD ratings, a DC reactor, which is available 8
as an option, corresponding to the applied motor is required.
• Setting the LD or SLD rating to the FR-A820-03160(55K) and the FR-A840-01800(55K) changes their parameter setting
increments and setting ranges in the same way as for the FR-A820-03800(75K) and the FR-A840-02160(75K) or higher. In an
example of Pr.9, the setting increment changes from "0.01 A" to "0.1 A" and the setting range changes from "0 to 500 A" to "0 9
to 3600 A". For the setting of each parameter, refer to the parameter list (on page 162).
Parameters referred to
10
Pr.260 PWM frequency automatic switchoverpage 339
NOTE
• Stand-alone options (except line noise filter) cannot be used when inputting a voltage between 480 and 500 V.
• The voltage protection level of the 200 V class inverters is not affected by the Pr.977 setting.
Parameters referred to
Pr.660 Increased magnetic excitation deceleration operation selectionpage 699
5. PARAMETERS
5.7 (E) Environment setting parameters
327
5.7.13 Parameter write selection
Whether to enable the writing to various parameters or not can be selected. Use this function to prevent parameter values from
being rewritten by misoperation.
Pr. Name Initial value Setting range Description
0 Writing is enabled only during stop.
77 1 Parameter writing is disabled.
Parameter write selection 0
E400 Parameter writing is enabled in any operation mode
2
regardless of the operation status.
• Pr.77 can be set at any time regardless of the operation mode or operation status. (Setting through communication is
unavailable.)
328 5. PARAMETERS
5.7 (E) Environment setting parameters
Writing parameters only during Pr. Name
434, 435 (CC-Link communication)
stop (Pr.77 = "0" initial value) 496, 497 (Remote output)
1
• Parameters can be written only during a stop in the PU 498 PLC function flash memory clear
operation mode. NET mode operation command source
550*2
• The following parameters can always be written selection
PU mode operation command source
2
regardless of the operation mode or operation status. 551*2 selection
555 to 557 (Current average value monitoring)
Pr. Name
(Multi-speed setting high-speed, middle-
656 to 659 (Analog remote output) 3
4 to 6 663 Control circuit temperature signal output level
speed, low-speed)
750, 751 Motor thermistor interface
22 Stall prevention operation level
755 to 758 (Second PID control)
24 to 27 (Multi-speed setting speed 4 to speed 7)
759 PID unit selection
4
52 Operation panel main monitor selection
774 to 776 (PU/DU monitor selection)
54 FM/CA terminal function selection
805 Torque command value (RAM)
55 Frequency monitoring reference
56 Current monitoring reference
806 Torque command value (RAM, EEPROM) 5
838 DA1 terminal function selection
72*1 PWM frequency selection
866 Torque monitoring reference
Reset selection/Disconnected PU detection/ 888, 889 (Free parameter)
75
PU stop selection
891 to 899 (Energy saving monitoring) 6
77 Parameter write selection
C0 (900) FM/CA terminal calibration
79*2 Operation mode selection
C1(901) AM terminal calibration
129 PID proportional band
130 PID integral time
C8 (930) Current output bias signal 7
C9 (930) Current output bias current
133 PID action set point C10 (931) Current output gain signal
134 PID differential time C11 (931) Current output gain current
158 AM terminal function selection 990 PU buzzer control 8
160 User group read selection 991 PU contrast adjustment
232 to 239 (Multi-speed setting speed 8 to speed 15) Operation panel setting dial push monitor
*1 992
240
241
Soft-PWM operation selection
Analog input display unit switchover 997
selection
Fault initiation
9
268 Monitor decimal digits selection 998*2 PM parameter initialization
271 High-speed setting maximum current 999 *2 Automatic parameter setting
272 Middle-speed setting minimum current 1000 Direct setting selection 10
273 Current averaging range 1006 Clock (year)
274 Current averaging filter time constant 1007 Clock (month, day)
Stop-on contact excitation current low-speed 1008 Clock (hour, minute)
275*1 scaling factor
1018 Monitor with sign selection
290 Monitor negative output selection
Analog meter voltage negative output
295 Frequency change increment amount setting 1019
selection
296, 297 (Password setting) 1048 Display-off waiting time
306 Analog output signal selection 1142 Second PID unit selection
310 Analog meter voltage output selection 1150 to 1199 (PLC function user parameters)
*2 Communication startup mode selection
340 1283 Home position return speed
345, 346 (DeviceNet communication) 1284 Home position return creep speed
416, 417 (PLC)
*1 Writing during operation is enabled in PU operation mode, but disabled in External operation mode.
*2 Writing during operation is disabled. To change the parameter setting value, stop the operation.
5. PARAMETERS
5.7 (E) Environment setting parameters
329
Pr. Name
656 to 659 (Analog remote output)
805 Torque command value (RAM)
806 Torque command value (RAM, EEPROM)
997 Fault initiation
*1 Writing during operation is disabled. To change the parameter setting value, stop the operation.
330 5. PARAMETERS
5.7 (E) Environment setting parameters
5.7.14 Password
Registering a 4-digit password can restrict parameter reading/writing. 1
Pr. Name Initial value Setting range Description
0 to 6, 99, 100 Select restriction level of parameter reading/writing
296
E410
Password lock level 9999 to 106, 199 when a password is registered. 2
9999 No password lock
1000 to 9998 Register a 4-digit password
297 Displays password unlock error count. (Reading only)
E411
Password lock/unlock 9999 (0 to 5) *1
(Valid when Pr.296 = "100 to 106, or 199") 3
*1 No password lock
9999
The above parameters can be set when Pr.160 User group read selection = "0". However, when Pr.296 ≠ 9999
(password lock is set), Pr.297 can always be set, regardless of the setting in Pr.160. 4
*1 When Pr.297 = "0 or 9999", writing is always enabled, but setting is invalid. (The display cannot be changed.)
*1 During Pr.296 = any of "100 to 106, and 199", if password unlock error has occurred 5 times, correct password does not unlock the restriction.
All parameter clear can unlock the restriction. (In this case, the parameters are returned to their initial values.)
2. Write a four-digit number (1000 to 9998) to Pr.297 as a password. (Writing is disabled when Pr.296 = "9999".) When
a password is registered, parameter reading/writing is restricted with the restriction level set in Pr.296 until
unlocking.
5. PARAMETERS
5.7 (E) Environment setting parameters
331
NOTE
• After registering a password, the read value of Pr.297 is always one of "0 to 5".
NOTE
• If the password is forgotten, it can be unlocked with all parameter clear, but doing so also clears the other parameters.
• All parameter clear cannot be performed during the operation.
• During the conditions where parameter reading is disabled (Pr.296 = any of "0, 4, 5, 99, 100, 104, 105, or 199"), do not use
FR Configurator2. It may not operate correctly.
• The password unlocking method differs between the operation panel, parameter unit, RS-485 communication, and
communication option.
332 5. PARAMETERS
5.7 (E) Environment setting parameters
NOTE
• When Pr.296 = "4, 5, 104, or 105" (password lock), the setting screen for PU JOG frequency is not displayed in the parameter 1
unit (FR-PU07).
• When the password is being locked, parameter copy using the operation panel, parameter unit, and USB memory is not
enabled.
2
Parameters referred to
Pr.77 Parameter write selectionpage 328
Pr.160 User group read selectionpage 337
Pr.550 NET mode operation command source selectionpage 380
3
Pr.551 PU mode operation command source selectionpage 380
NOTE
• Pr.888 and Pr.889 do not influence the operation of the inverter. 8
5. PARAMETERS
5.7 (E) Environment setting parameters
333
Automatic parameter setting (Pr.999)
• Select which parameters to automatically set from the following table, and set them in Pr.999. Multiple parameter settings
are changed automatically. Refer to page 335 for the list of parameters that are changed automatically.
Pr.999
Description Operation in the automatic parameter setting mode
setting
NOTE
• If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the parameters will not cause any problem.
334 5. PARAMETERS
5.7 (E) Environment setting parameters
3-line monitor setting
On the operation panel or parameter unit, the 3-line monitor is used as the first monitor.
1
Direct setting
Pressing the [FUNC] key on the FR-PU07-01 displays the direct setting screen. The PID action set point can be directly set
regardless of the operation mode or Pr.77 Parameter write selection setting. 2
Pressing the [FUNC] key on the direct setting screen displays the function menu.
Direct setting Parameter to be set
Direct setting 1 Pr.133 PID action set point 3
Direct setting 2 Pr.755 Second PID action set point
NOTE
• Always perform an inverter reset after the initial setting.
• For the details of connection with GOT, refer to the Instruction Manual of GOT.
5. PARAMETERS
5.7 (E) Environment setting parameters
335
GOT initial setting (RS-485 terminals) (Pr.999 = "11, 13")
Refer to
Pr. Name Initial value Pr.999 = "11" Pr.999 = "13"
page
79 Operation mode selection 0 0 0 370
332 RS-485 communication speed 96 192 1152
RS-485 communication stop bit length / data
333 1 10 0
length
334 RS-485 communication parity check selection 2 1 1 636
335 RS-485 communication retry count 1 9999 9999
336 RS-485 communication check time interval 0s 9999 9999
337 RS-485 communication waiting time setting 9999 0 ms 0 ms
340 Communication startup mode selection 0 1 1 378
341 RS-485 communication CR/LF selection 1 1 1 636
414 PLC function operation selection 0 — *1 614
2
549 Protocol selection 0 0 0 652
NOTE
• Always perform an inverter reset after the initial setting.
• For the details of connection with GOT, refer to the Instruction Manual of GOT.
336 5. PARAMETERS
5.7 (E) Environment setting parameters
Rated frequency (Pr.999 = "20" (50 Hz) or "21" (60 Hz))
Pr. Name
Initial value
Pr.999 = "21" Pr.999 = "20"
Refer to 1
FM type CA type page
3 Base frequency 60 Hz 50 Hz 60 Hz 50 Hz 673
4 Multi-speed setting (high speed)
Acceleration/deceleration reference
60 Hz 50 Hz 60 Hz 50 Hz 391
2
20 60 Hz 50 Hz 60 Hz 50 Hz 349
frequency
37 Speed display 0 0 422
55 Frequency monitoring reference 60 Hz 50 Hz 60 Hz 50 Hz 435 3
Stall prevention operation reduction
66 60 Hz 50 Hz 60 Hz 50 Hz 409
starting frequency
116 Third output frequency detection 60 Hz 50 Hz 60 Hz 50 Hz 409
125 (903)
Terminal 2 frequency setting gain
60 Hz 50 Hz 60 Hz 50 Hz
4
frequency
482
Terminal 4 frequency setting gain
126 (905) 60 Hz 50 Hz 60 Hz 50 Hz
frequency
263 Subtraction starting frequency 60 Hz 50 Hz 60 Hz 50 Hz 5
Power failure deceleration time 610
266 60 Hz 50 Hz 60 Hz 50 Hz
switchover frequency
386
505
Frequency for maximum input pulse
Speed setting reference
60 Hz
60 Hz
50 Hz
50 Hz
60 Hz
60 Hz
50 Hz
50 Hz
386
422
6
Forward rotation speed limit/speed
808 60 Hz 50 Hz 60 Hz 50 Hz 274
limit
C14 (918) Terminal 1 gain frequency (speed) 60 Hz 50 Hz 60 Hz 50 Hz 482 7
5.7.17 Extended parameter display and user group
function 8
This function restricts the parameters that are read by the operation panel and parameter unit.
Pr. Name Initial value Setting range Description 9
9999 Only simple mode parameters are displayed.
160 User group read
0 0 Displays simple mode and extended parameters.
E440 selection
1 Only parameters registered in user groups are displayed.
Displays the number of parameters that are registered in the
10
172 User group registered (0 to 16)
0 user groups. (Read-only)
E441 display/batch clear
9999 Batch clear of user group registrations
173
E442
User group registration 9999*1 0 to 1999, 9999 Sets the parameter number to register for the user group.
174
E443
User group clear 9999*1 0 to 1999, 9999 Sets the parameter number to clear from the user group.
5. PARAMETERS
5.7 (E) Environment setting parameters
337
NOTE
• When a plug-in option in installed on the inverter, the option parameters can also be read.
• Every parameter can be read regardless of the Pr.160 setting when reading parameters via a communication option.
• When reading the parameters using the RS-485 terminals, all parameters can be read regardless of the Pr.160 setting by
setting Pr.550 NET mode operation command source selection and Pr.551 PU mode operation command source
selection.
• When the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07) is installed, Pr.15 Jog frequency, Pr.16 Jog
acceleration/deceleration time, C42(Pr.934) PID display bias coefficient, C43(Pr.934) PID display bias analog value,
C44(Pr.935) PID display gain coefficient, C45(Pr.935) PID display gain analog value and Pr.991 PU contrast adjustment
are displayed as simple mode parameters.
Operating procedure
1. Power ON
Make sure the motor is stopped.
Press to choose the parameter setting mode. (The parameter number read previously appears)
4. Selecting a parameter
5. Parameter read
6. Parameter registration
Turn until " " (Pr.3) appears. Press to register the parameter.
338 5. PARAMETERS
5.7 (E) Environment setting parameters
Operating procedure
1. Power ON 1
Make sure the motor is stopped.
4. Selecting a parameter 4
Turn until " " (Pr.174) appears.
5. Parameter read 5
Press ." " appears.
NOTE
• Pr.77 Parameter write selection, Pr.160, Pr.296 Password lock level, Pr.297 Password lock/unlock and Pr.991 PU 8
contrast adjustment can always be read regardless of the user group setting. (For Pr.991, only when the FR-LU08 or the
FR-PU07 is connected.)
• Pr.77, Pr.160, Pr.172 to Pr.174, Pr.296, and Pr.297 cannot be registered in a user group.
• When Pr.174 is read, "9999" is always displayed. "9999" can be written, but it does not function.
9
• Pr.172 is disabled if set to a value other than "9999".
10
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration timepage 390
Pr.77 Parameter write selectionpage 328
Pr.296 Password lock level, Pr.297 Password lock/unlockpage 331
Pr.550 NET mode operation command source selectionpage 380
Pr.551 PU mode operation command source selectionpage 380
Pr.991 PU contrast adjustmentpage 322
5. PARAMETERS
5.7 (E) Environment setting parameters
339
• Changing the PWM carrier frequency can be effective for avoiding the resonance frequency of the mechanical system or
motor, as a countermeasure against EMI generated from the inverter, or for reducing leakage current caused by PWM
switching.
• Under Real sensorless vector control, vector control, and PM sensorless vector control, the following carrier frequencies
are used.
(For the control method and fast-response mode selection, refer to Pr.800 Control method selection on page 215.)
Carrier frequency (kHz)
Pr.72 setting Real sensorless vector control,
PM sensorless vector control Fast-response mode
Vector control
0 to 5 2 6*1
6 to 9 6*2 6
4
10 to 13 10*2 10
14, 15 14*2 14
*1 When low-speed range high-torque characteristic is disabled (Pr.788 = "0"), 2 kHz is used.
*2 In the low-speed range (3 Hz or lower) under Real sensorless vector control, the carrier frequency is automatically changed to 2 kHz.
(For FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower)
• When using an optional sine wave filter (MT-BSL/BSC), set "25" (2.5 kHz) in Pr.72. (FR-A820-03800(75K) or higher, FR-
A840-02160(75K) or higher.)
NOTE
• In the low-speed range (about 10 Hz or lower), the carrier frequency may be automatically lowered.
Motor noise increases, but not to the point of failure.
• When Pr.72 = "25", the following limitations apply.
- V/F control is forcibly set.
- Soft-PWM control is disabled.
- The maximum output frequency is 60 Hz.
NOTE
• While a sine wave filter (Pr.72 = "25") is being used, the Soft-PWM control is disabled.
340 5. PARAMETERS
5.7 (E) Environment setting parameters
• When the carrier frequency automatic reduction function is used, operation with the carrier frequency set to 3 kHz or higher
(Pr.72 ≥ 3) automatically reduces the carrier frequency for heavy-load operation as shown below.
1
Carrier frequency automatic reduction operation
Pr.260
Pr.570 setting FR-A820-04750(90K) or lower,
setting FR-A840-03250(110K) or higher
FR-A840-02600(90K) or lower
0 (SLD), 1 (LD)
The carrier frequency will reduce automatically with continuous operation of 85% of the inverter rated 2
current or higher.
1 The carrier frequency will reduce automatically with Continuous operation with the 85% or higher
2 (ND), 3 (HD) operation of 150% of the inverter ND rated current inverter rated current for the ND rating reduces the
or higher. carrier frequency automatically. 3
The carrier frequency will reduce automatically with continuous operation of 85% of the inverter rated
0 (SLD)
current or higher.
Without carrier frequency automatic reduction (Perform continuous operation with the carrier frequency
0
1 (LD)
set to 2 kHz or lower or with less than 85% of the inverter rated current for the ND rating.) 4
Without carrier frequency automatic reduction
(Perform continuous operation with the carrier
2 (ND), 3 (HD) Without carrier frequency automatic reduction
frequency set to 2 kHz or lower or with less than
85% of the inverter rated current for the ND rating.) 5
NOTE
• Reducing the PWM carrier frequency is effective as a countermeasure against EMI from the inverter or for reducing leakage 6
current, but doing so increases the motor noise.
• When the PWM carrier frequency is set to 1 kHz or lower (Pr.72 ≤ 1), the increase in the harmonic current causes the fast-
response current limit to activate before the stall prevention operation, which may result in torque shortage. In this case,
disable the fast-response current limit in Pr.156 Stall prevention operation selection. 7
• The lower limit of carrier frequency after the reduction under PM sensorless vector control (low-speed range high-torque
characteristic enabled) is 6 kHz.
• During fast-response operation, the carrier frequency automatic reduction function is disabled. 8
Parameters referred to
Pr.156 Stall prevention operation selectionpage 409
Pr.570 Multiple rating settingpage 326
9
Pr.788 Low speed range torque characteristic selectionpage 227
Pr.800 Control method selectionpage 215
5. PARAMETERS
5.7 (E) Environment setting parameters
341
*2 The setting is available only for standard models and IP55 compatible models.
• In the life diagnosis of the main circuit capacitor, the alarm signal (Y90) is not output unless measurement by turning OFF the
power supply is performed.
• Whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit or
internal air circulation fans have reached the life alarm output level can be checked with Pr.255 Life alarm status display
and the Life alarm (Y90) signal. (Internal air circulation fans are equipped with IP55 compatible models.)
Pr.255 Pr.255
bit4 bit3 bit2 bit1 bit0 bit4 bit3 bit2 bit1 bit0
Decimal Binary Decimal Binary
15 1111 × ○ ○ ○ ○ 31 11111 ○ ○ ○ ○ ○
14 1110 × ○ ○ ○ × 30 11110 ○ ○ ○ ○ ×
13 1101 × ○ ○ × ○ 29 11101 ○ ○ ○ × ○
12 1100 × ○ ○ × × 28 11100 ○ ○ ○ × ×
11 1011 × ○ × ○ ○ 27 11011 ○ ○ × ○ ○
10 1010 × ○ × ○ × 26 11010 ○ ○ × ○ ×
9 1001 × ○ × × ○ 25 11001 ○ ○ × × ○
8 1000 × ○ × × × 24 11000 ○ ○ × × ×
7 0111 × × ○ ○ ○ 23 10111 ○ × ○ ○ ○
6 0110 × × ○ ○ × 22 10110 ○ × ○ ○ ×
5 0101 × × ○ × ○ 21 10101 ○ × ○ × ○
4 0100 × × ○ × × 20 10100 ○ × ○ × ×
3 0011 × × × ○ ○ 19 10011 ○ × × ○ ○
2 0010 × × × ○ × 18 10010 ○ × × ○ ×
1 0001 × × × × ○ 17 10001 ○ × × × ○
0 0000 × × × × × 16 10000 ○ × × × ×
○: With warnings, ×: Without warnings
• The Life alarm (Y90) signal turns ON when any of the control circuit capacitor, main circuit capacitor, cooling fan, inrush
current limit circuit or internal air circulation fans reaches the life alarm output level.
• For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.190 to Pr.196 (output
terminal function selection).
NOTE
• When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life can be output separately to the Control circuit
capacitor life (Y86) signal, Main circuit capacitor life (Y87) signal, Cooling fan life (Y88) signal, and Inrush current limit circuit
life (Y89) signal.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Life display of the inrush current limit circuit (Pr.256) (Standard models
and IP55 compatible models)
• The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr.256.
342 5. PARAMETERS
5.7 (E) Environment setting parameters
• The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down from 100% (0 time) every
1%/10,000 times. As soon as 10% (900,000 times) is reached, Pr.255 bit 3 is turned ON and also a warning is output to
the Y90 signal.
1
Life display of the control circuit capacitor (Pr.257)
• The deterioration degree of the control circuit capacitor is displayed in Pr.257. 2
• In the operating status, the control circuit capacitor life is calculated from the energization time and temperature, and is
counted down from 100%. As soon as the control circuit capacitor life falls below 10%, Pr.255 bit 0 is turned ON and also
a warning is output to the Y90 signal. 3
Life display of the main circuit capacitor (Pr.258, Pr.259) (Standard
models and IP55 compatible models) 4
• For accurate life measurement of the main circuit capacitor, wait three hours or longer after turning OFF. The temperature left
in the main circuit capacitor affects measurement. 5
• The deterioration degree of the main circuit capacitor is displayed in Pr.258.
• With the main circuit capacitor capacity at factory shipment as 100%, the capacitor life is displayed in Pr.258 every time 6
measurement is made. When the measured value falls to 85% or lower, Pr.255 bit 1 is turned ON and also a warning is
output to the Y90 signal.
• Measure the capacitor capacity according to the following procedure and check the deterioration degree of the capacitor 7
capacity.
3. Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor capacity while the
inverter is OFF. 9
4. After confirming that the power lamp is OFF, turn ON the power again.
5. Check that "3" (measurement complete) is set in Pr.259, read Pr.258, and check the deterioration degree of the 10
main circuit capacitor.
Pr.259 Description Remarks
0 No measurement Initial value
Measurement starts when the power supply
1 Start measurement
is switched OFF.
2 During measurement
3 Measurement complete
Only displayed and cannot be set.
8 Forced end
9 Measurement error
5. PARAMETERS
5.7 (E) Environment setting parameters
343
NOTE
• When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr.259 = "8"), or "measurement
error" (Pr.259 = "9") may occur, or the status may remain in "measurement start" (Pr.259 = "1"). To perform measurement,
first eliminate the following conditions. Under the following conditions, even if "measurement complete" (Pr.259 = "3") is
reached, measurement cannot be performed correctly.
- FR-HC2, FR-CV, MT-RC, or a sine wave filter is connected.
- Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.
- The power supply is switched ON during measurement.
- The motor is not connected to the inverter.
- The motor is running (coasting).
- The motor capacity is smaller than the inverter capacity by two ranks or more.
- The inverter output is shut off or a fault occurred while the power was OFF.
- The inverter output is shut off with the MRS signal.
- The start command is given while measuring.
- The applied motor setting is incorrect.
• Operation environment: Surrounding air temperature (annual average of 40°C (free from corrosive gas, flammable gas, oil
mist, dust and dirt)).
Output current: 80% of the inverter rating
• Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of the
magnetic contactor must be avoided.
WARNING
• When measuring the main circuit capacitor capacity (Pr.259 = "1"), the DC voltage is applied to the motor for about 1
second at power OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.
NOTE
• When the inverter is mounted with two or more cooling fans, "FN" is displayed even only one of the fans is detected.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• For replacement of each part, contact the nearest Mitsubishi FA center.
internal fan fault " " (FN2) appears on the operation panel (FR-DU08) when the rotations per minute is less than
70% of the rated value for the internal air circulation fan. (FN is displayed on the parameter unit (FR-PU07).) As an alarm
display, Pr.255 bit 4 is turned ON and also a warning is output to the Y90 signal and Alarm (LF) signal.
344 5. PARAMETERS
5.7 (E) Environment setting parameters
• For the terminal used for the LF signal, set "98 (positive logic) or 198" (negative logic) in any of Pr.190 to Pr.196 (Output
terminal function selection).
1
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• For replacement of each part, contact the nearest Mitsubishi FA center.
2
Time
• The cumulative energization time of the inverter is stored in the EEPROM every hour and displayed in Pr.503 (Pr.686,
Pr.688) in 100 h increments. Pr.503 (Pr.686, Pr.688) is clamped at 9998 (999800 h).
• When the value in Pr.503 (Pr.686, Pr.688) reaches the time (100 h increments) set in Pr.504 (Pr.687, Pr.689), the
Maintenance timer (Y95) signal is output, and also " " (MT1), " " (MT2), or " " (MT3) is
displayed on the operation panel.
• For the terminal used for the Y95 signal output, assign the function by setting "95 (positive logic)" or "195 (negative logic)"
in any of Pr.190 to Pr.196 (Output terminal function selection).
5. PARAMETERS
5.7 (E) Environment setting parameters
345
NOTE
• The Y95 signal turns ON when any of MT1, MT2 or MT3 is activated. It does not turn OFF unless all of MT1, MT2 and MT3
are cleared.
• If all of MT1, MT2 and MT3 are activated, they are displayed in the priority of "MT1 > MT2 > MT3".
• The cumulative energization time is counted every hour. Energization time of less than 1 h is not counted.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
Programmable controller
Output Input
unit unit
Inverter
maintenance
time
parts have
reached their life
Operation example
• The pulse output of the Current average value monitor (Y93) signal is indicated below.
346 5. PARAMETERS
5.7 (E) Environment setting parameters
• For the terminal used for the Y93 signal output, assign the function by setting "93 (positive logic)" or "193 (negative logic)"
in any of Pr.190 to Pr.194 (Output terminal function selection). (This cannot be assigned by setting in Pr.195 ABC1
terminal function selection or Pr.196 ABC2 terminal function selection.)
1
From acceleration to constant speed operation
Output
frequency 2
Time
1 cycle (20 s) Next cycle
3
Y93 signal
Data output mask time End pulse
When the speed has changed to constant output as low pulse
from acceleration/deceleration, Y93 signal is
not output for Pr. 556 time.
Maintenance timer pulse
shape for 1 to 16.5 s
4
Start pulse The maintenance timer value (Pr. 503) is output
Output as Hi pulse shape for 1 s (fixed) as Hi output pulse shape for 2 to 9 s (16000h to
The output currents are averaged during the time 72000h).
Pr. 503 100h
5
period set in Pr.555. 5s
Signal output time=
40000h
Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9 s (10 to 180%) during start pulse output.
output current average value (A)
Signal output time= 5s
6
Pr. 557 (A)
The output time range is 0.5 to 9 seconds. When the output current average value is less than 10% of the setting value in
Pr.557, the output time is 0.5 seconds, and when it is more than 180%, the output time is 9 seconds.
For example, when Pr.557 = 10 A and the output current average value is 15 A:
15 A/10 A × 5 s = 7.5 s, thus the current average value monitor signal is Low output in 7.5 s intervals.
Signal output time
(s)
9
0.5
10 180 (%)
Output current average value
Pr.530 × 100
×5s (Maintenance timer value 100%/5 s)
40000h
5. PARAMETERS
5.7 (E) Environment setting parameters
347
The output time range is 2 to 9 s. When Pr.503 is less than 16,000 h, the output time is 2 seconds, and when it is more than
72,000 h, the output time is 9 seconds.
Signal output time
(s)
9
2
16000 72000 (h)
Maintenance timer value
NOTE
• Masking of the data output and sampling of the output current are not performed during acceleration/deceleration.
• If constant speed changes to acceleration or deceleration during start pulse output, it is judged as invalid data, and HIGH
output in 3.5 seconds intervals is performed for the start pulse and LOW output in 16.5 seconds intervals is performed for the
end signal. After the start pulse output is completed, minimum 1-cycle signal output is performed even if acceleration/
deceleration is performed.
Time
Previous cycle Invalid cycle (20 s) Next cycle
Y93
signal
Start pulse End signal
Output as high pulse shape for 3.5 s Output as low pulse shape for 16.5 s
• If the output current value (inverter output current monitor) is 0 A at the completion of the 1-cycle signal output, no signal is
output until the next constant-speed state.
• Under the following conditions, the Y93 signal is output with LOW output in 20 seconds intervals (no data output).
- When acceleration or deceleration is operating at the completion of the 1-cycle signal output
- When automatic restart after instantaneous power failure (Pr.57 Restart coasting time ≠ "9999") is set, and the 1-
cycle signal output is completed during the restart operation.
- When automatic restart after instantaneous power failure (Pr.57 ≠ "9999") is set, and the restart operation was being
performed at the completion of data output masking.
Parameters referred to
Pr.57 Restart coasting timepage 597, page 604
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.503 Maintenance timer 1, Pr.686 Maintenance timer 2, Pr.688 Maintenance timer 3page 345
348 5. PARAMETERS
5.7 (E) Environment setting parameters
5.8 (F) Setting of acceleration/deceleration time and 1
acceleration/deceleration pattern
2
Purpose Parameter to set Refer to page
Pr.7, Pr.8, Pr.16,
P.F000 to P.F003,
P.F010, P.F011,
Pr.20, Pr.21, Pr.44, 3
Pr.45, Pr.110,
To set the motor acceleration/ Acceleration/deceleration P.F020 to P.F022,
Pr.111, Pr.147, 349
deceleration time time P.F030, P.F031,
Pr.611, Pr.791,
P.F040, P.F070,
P.F071, P.G264
Pr.792, Pr.1103,
Pr.1349
4
P.F100, P.F200 to Pr.29, Pr.140 to
Acceleration/deceleration
To set the acceleration/deceleration P.F203, P.F300 to Pr.143, Pr.380 to
pattern and backlash 354
pattern suitable for an application
measures
P.F303, P.F400 to
P.F403
Pr.383, Pr.516 to
Pr.519
5
To command smooth speed transition
Remote setting function P.F101 Pr.59 359
with terminals
10
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
349
For the acceleration time at automatic restart after instantaneous power failure, refer to Pr.611 Acceleration time at a restart
(page 597, page 604).
Initial value
Pr. Name Setting range Description
FM CA
Acceleration/
Set the frequency that is the basis of acceleration/deceleration time.
20 deceleration
60 Hz 50 Hz 1 to 590 Hz As acceleration/deceleration time, set the frequency change time
F000 reference
from a stop status to Pr.20.
frequency
Acceleration/ 0 Increment: 0.1 s Select the increment for
21
deceleration time 0 the acceleration/
F001 1 Increment: 0.01 s
increments deceleration time setting.
16 Jog acceleration/ Set the acceleration/deceleration time for JOG operation (from stop
0.5s 0 to 3600 s
F002 deceleration time status to Pr.20). Refer to page 390.
0 to 3600 s Set the acceleration time for restart (from stop status to Pr.20).
611 Acceleration time
9999 Standard acceleration time (for example, Pr.7) is applied as the
F003 at a restart 9999
acceleration time at restart. Refer to page 597, page 604.
7 5 s*1
Acceleration time 0 to 3600 s Set the motor acceleration time (from stop status to Pr.20).
F010 15 s*2
8 5 s*1
Deceleration time 0 to 3600 s Set the motor deceleration time (from Pr.20 to stop status).
F011 15 s*2
Second
44
acceleration/ 5s 0 to 3600 s Set the acceleration/deceleration time when the RT signal is ON.
F020
deceleration time
45 Second 0 to 3600 s Set the deceleration time when the RT signal is ON.
9999
F021 deceleration time 9999 Acceleration time = deceleration time
Acceleration/ Set the frequency where the acceleration/deceleration time
0 to 590 Hz
147 deceleration time switches to the time set in Pr.44 and Pr.45.
9999
F022 switching
9999 Without the function
frequency
Third 0 to 3600 s Set the acceleration/deceleration time when the X9 signal is ON.
110
acceleration/ 9999
F030 9999 Third acceleration/deceleration is disabled.
deceleration time
111 Third deceleration 0 to 3600 s Set the deceleration time when the X9 signal is ON.
9999
F031 time 9999 Acceleration time = deceleration time
Set the acceleration time in a low-speed range (less than 1/10 of the
Acceleration time 0 to 3600 s
791 rated motor frequency).
in low-speed 9999
F070 The acceleration time set in Pr.7 is applied. (While the RT signal or
range 9999
the X9 signal is ON, the second or third function is enabled.)
Set the deceleration time in a low-speed range (less than 1/10 of the
Deceleration time 0 to 3600 s
792 rated motor frequency).
in low-speed 9999
F071 The deceleration time set in Pr.8 is applied. (While the RT signal or
range 9999
the X9 signal is ON, the second or third function is enabled.)
1103 Deceleration time Set the motor deceleration time at a deceleration by turning ON the
5s 0 to 3600 s
F040 at emergency stop X92 signal.
Speed loop integration
0 Droop control enabled.
enabled.
Speed loop integration
Emergency stop 1 Droop control enabled.
1349 disabled.
operation 0
G264 Speed loop integration
selection 10 Droop control disabled.
enabled.
Speed loop integration
11 Droop control disabled.
disabled.
*1 The initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
*2 Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) and higher.
350 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Control block diagram
JOG-ON
Output frequency 10% of the rated motor frequency 1
JOG
Acceleration time
(Pr.16)
Output frequency Pr.147 or
2
(or Pr.147= “9999” ) RT-OFF X9-OFF deceleration time
Acceleration and
deceleration time
(Pr.7, Pr.8) JOG-OFF
5
Acceleration time setting (Pr.7, Pr.20)
• Use Pr.7 Acceleration time to set the acceleration time required to reach Pr.20 Acceleration/deceleration reference
frequency from stop status. 6
• Set the acceleration time according to the following formula.
Acceleration time setting = Pr.20 × Acceleration time from stop status to maximum frequency / (maximum frequency - Pr.13)
• For example, the following calculation is performed to find the setting value for Pr.7 when increasing the output frequency 7
to the maximum frequency of 50 Hz in 10 s with Pr.20 = "60 Hz (initial value)" and Pr.13 = "0.5 Hz".
Time
10
Acceleration Pr.7 Deceleration Pr.8
time Pr.44 time Pr.45
Pr.110 Pr.111
Deceleration time setting = Pr.20 × deceleration time from maximum frequency to stop / (maximum frequency - Pr.10)
• For example, the following calculation is used to find the setting value for Pr.8 when increasing the output frequency to the
maximum frequency of 50 Hz in 10 s with Pr.20 = 120 Hz and Pr.10 = 3 Hz.
NOTE
• If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time cannot be made shorter than the
shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor torque.
• If the Pr.20 setting is changed, the Pr.125 and Pr.126 (frequency setting signal gain frequency) settings do not change.
Set Pr.125 and Pr.126 to adjust the gains.
• Under PM sensorless vector control, if the protective function (E.OLT) is activated due to insufficient torque in the low-speed
range, set longer acceleration/deceleration times only in the low-speed range in Pr.791 Acceleration time in low-speed range
and Pr.792 Deceleration time in low-speed range.
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
351
Changing the minimum increment of the acceleration/deceleration time
(Pr.21)
• Use Pr.21 to set the minimum increment of the acceleration/deceleration time.
Setting value "0" (initial value): minimum increment 0.1 s
Setting value "1": minimum increment 0.01 s
• Pr.21 setting allows the minimum increment of the following parameters to be changed.
Pr.7, Pr.8, Pr.16, Pr.44, Pr.45, Pr.110, Pr.111, Pr.264, Pr.265, Pr.791, Pr.792
NOTE
• Pr.21 setting does not affect the minimum increment setting of Pr.611 Acceleration time at a restart.
• The parameter can be set in five digits including the numbers below decimal point for the FR-DU08 and the FR-PU07. A "1000"
or more value is set in increments of 0.1 s even if Pr.21 = "1".
Output frequency
(Hz)
Set
frequency
Pr. 147
setting
Time
Pr.7 Pr.44 Pr.110 Pr.111 Pr.44 Pr.8 Pr.7 Pr.44 Pr.44 Pr.8
(Pr.45) (Pr.45)
RT signal ON
X9 signal ON
352 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern 1
selection setting. (Refer to page 354.)
• The RT and X9 signals can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• The RT (X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid. 2
(Refer to page 500.)
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
3
Setting the acceleration/deceleration time in the low-speed range (Pr.791,
Pr.792) 4
• If torque is required in the low-speed range (less than 10% of the rated motor frequency) under PM sensorless vector
control, set the Pr.791 Acceleration time in the low-speed range and Pr.792 Deceleration time in low-speed range
settings higher than the Pr.7 Acceleration time and Pr.8 Deceleration time settings so that the mild acceleration/
5
deceleration is performed in the low-speed range. Such a setting is especially effective when the low-speed range high-
torque characteristic is disabled (Pr.788 = "0"). (When RT signal or X9 signal is turned ON, the second or third acceleration/
deceleration time setting is prioritized.)
6
frequency (Hz)
7
Output
Low-speed range
(rated motor frequency/10)
Time 8
Acceleration time Deceleration time
in low-speed range in low-speed range
Slope set by Pr. 791 Slope set by Pr.792
Acceleration time
Slope set by Pr.7
Deceleration time
Slope set by Pr.8
9
NOTE
• Set Pr.791 higher than Pr.7, and Pr.792 higher than Pr.8. If set as Pr.791 < Pr.7, the operation is performed as Pr.791 =Pr.7. 10
If set as Pr.792 < Pr.8, the operation is performed as Pr.792 = Pr.8.
• Refer to page 798 for the rated motor frequency of MM-CF.
Time
Start signal ON OFF ON
X92 OFF ON OFF
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
353
• The droop control and the speed loop integration at the emergency stop by the Emergency stop (X92) signal can be
enabled/disabled using Pr.1349 Emergency stop operation selection.
Pr.1349 Description
setting Droop control Speed loop integration
0 Enabled Enabled
1 Enabled Disabled
10 Disabled Enabled
11 Disabled Disabled
NOTE
• The X92 signals can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• Refer to page 702 for details of the droop control.
• Refer to page 244 for details of the speed loop integration.
Parameters referred to
Pr.3 Base frequencypage 673
Pr.10 DC injection brake operation frequencypage 681
Pr.29 Acceleration/deceleration pattern selectionpage 354
Pr.125, Pr.126 (frequency setting gain frequency)page 482
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.264 Power-failure deceleration time 1, Pr.265 Power-failure deceleration time 2page 482
354 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Linear acceleration/deceleration (Pr.29 = "0" initial value)
• When the frequency is changed for acceleration, deceleration, etc. during inverter operation, the output frequency is 1
changed linearly (linear acceleration/deceleration) to reach the set frequency without straining the motor and inverter.
Linear acceleration/deceleration has a uniform frequency/time slope.
Setting value "0" 2
Output frequency
[Linear acceleration
/ deceleration]
3
(Hz)
Time
[S-pattern acceleration
/deceleration A]
fb 7
(Hz)
Time
• Acceleration/deceleration time calculation method when the set frequency is equal to or higher than the base frequency 8
Acceleration time t = (4/9) × (T/fb2) × f2 + (5/9) × T
Where T is the acceleration/deceleration time (s), f is the set frequency (Hz), and fb is the base frequency (rated motor
frequency) 9
• Reference (0 Hz to set frequency) of acceleration/deceleration time when Pr.3 = "60 Hz"
NOTE
• For the acceleration/deceleration time setting of the S-pattern acceleration/deceleration A, set the time to Pr.3 (Pr.84 under
PM sensorless vector control) instead of Pr.20 Acceleration/deceleration reference frequency.
f1
Output frequency
f2
(Hz)
Time
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
355
NOTE
• When the RT or X9 signal turns ON during acceleration or deceleration with the S-pattern acceleration/deceleration B enabled,
a pattern of acceleration or deceleration changes to linear at the moment.
[Anti-backlash measure
function]
Pr. 142
Pr. 140
Pr. 13
Time
Pr. 141 Pr. 143
NOTE
• Setting the backlash measures increases the acceleration/deceleration time by the stopping time.
Frequency
Pr.381
Pr.382
Pr.380
S-pattern Time
acceleration/
OFF ON OFF
deceleration
C switchover
(X20)
• Set the ratio (%) of time for drawing an S-shape in Pr.380 to Pr.383 with the acceleration time as 100%.
S-pattern
acceleration
Linear
acceleration
Ts Ts
T
356 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
NOTE
• At a start, the motor starts at Pr.13 Starting frequency when the start signal turns ON. 1
• If there is a difference between the speed command and speed at a start of deceleration due to torque limit operation etc., the
speed command is matched with the speed to make deceleration.
• Change the X20 signal after the speed becomes constant. S pattern operation before switching continues even if the X20
signal is changed during acceleration or deceleration. 2
• The X20 signal can be assigned to an input terminal by setting any of Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• When the RT or X9 signal turns ON during acceleration or deceleration with the S-pattern acceleration/deceleration C enabled,
a pattern of acceleration or deceleration changes to linear at the moment.
3
Time 9
Start signal ON
NOTE
• Even if the start signal is turned OFF during acceleration, the inverter does not decelerate immediately to avoid sudden 10
frequency change. (Likewise, the inverter does not immediately accelerate when deceleration is changed to re-acceleration
by turning the start signal ON during deceleration, etc.)
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
357
• For example, the following table shows the actual acceleration time when starting the inverter by selecting S-pattern
acceleration/deceleration D from a stop to 60 Hz, as shown below, with the initial parameter settings.
Pr. 517
Acceleration/deceleration
reference frequency (Pr. 20)
Pr. 517/2
Pr. 516
Starting frequency
T1 (Pr. 13)
T2
Pr.519
Pr.519/2
DC injection
brake operation
T1 frequency
(Pr. 10)
T2
Set deceleration time T1 = (set frequency - Pr.10 DC injection brake operation frequency) × Pr.8 / Pr.20
= (60 Hz - 3 Hz) × 5 s / 60 Hz
4.75 s (actual deceleration time at linear deceleration)
Actual deceleration time T2 = set deceleration time T1 + (Pr.518 + Pr.519) / 2
= 4.75 s + (0.1 s + 0.1 s) / 2
= 4.85 s (deceleration time at S-pattern deceleration)
NOTE
• When acceleration/deceleration time (such as Pr.7 and Pr.8) is set to "0 s" under Real sensorless vector control, Vector
control, and PM sensorless vector control (with MM-CF and Pr.788 Low speed range torque characteristic selection
="9999 (initial value)"), linear acceleration and deceleration are performed for the S-pattern acceleration/deceleration A to D
and backlash measures (Pr.29 ="1 to 5").
• Set linear acceleration/deceleration (Pr.29 ="0 (initial setting)") when torque control is performed under Real sensorless vector
control or Vector control. When acceleration/deceleration patterns other than the linear acceleration/deceleration are selected,
the protective function of the inverter may be activated.
358 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Variable-torque acceleration/deceleration (Pr.29 = "6")
• This function is useful for variable-torque load such as a fan and blower to accelerate/decelerate in short time. 1
Linear acceleration/deceleration is performed in the area where the output frequency > base frequency.
[Variable-torque acceleration/deceleration]
2
Output frequency
Set frequency
3
Pr.7 Pr.8 Time
Acceleration time Deceleration time
4
NOTE
• When the base frequency is out of the range 45 to 65 Hz, the linear acceleration/deceleration is performed even if Pr.29 = "6".
• Even if Pr.14 Load pattern selection = "1 (variable torque load)", variable torque acceleration/deceleration setting is 5
prioritized and the inverter operates as Pr.14 = "0 (constant torque load)".
• For the variable torque acceleration/deceleration time setting, set the time period to reach Pr.3 Base frequency. (Not the time
period to reach Pr.20 Acceleration/deceleration reference frequency.)
• The variable torque acceleration/deceleration is disabled during PM sensorless vector control. (Linear acceleration/ 6
deceleration is performed.)
Parameters referred to
7
Pr.3 Base frequencypage 673
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.20 Acceleration/deceleration reference frequencypage 349
Pr.10 DC injection brake operation frequencypage 681
Pr.14 Load pattern selectionpage 674
Pr.178 to Pr.189 (Input terminal function selection)page 496
8
5.8.3 Remote setting function
Even if the operation panel is located away from the enclosure, contact signals can be used to perform continuous variable-
9
speed operation, without using analog signals.
By simply setting this parameter, the acceleration, deceleration and setting clear functions of the remote speed setter (FR-FK)
become available.
10
Description
Initial Setting
Pr. Name RH, RM, RL signal Frequency setting Deceleration to the frequency
value range
function storage lower than the set frequency
0 Multi-speed setting —
1 Remote setting Displayed
2 Remote setting Not used
Not used Not available
(Turning STF/STR
3 Remote setting
OFF clears remotely-
59 Remote function
0 set frequency.)
F101 selection
11 Remote setting Displayed
12 Remote setting Not used
Not used Available
(Turning STF/STR
13 Remote setting
OFF clears remotely-
set frequency.)
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
359
• When Pr.59 ≠ "0" (remote setting function valid), the functions of the RH, RM and RL signals are changed to acceleration
(RH), deceleration (RM) and clear (RL).
Output frequency
Forward Inverter
rotation
STF When Pr.59 = "1, 2, 11, 12" When Pr.59 = "1, 11"
(Hz)
Acceleration
RH When Pr.59 = "3, 13"
Deceleration When Pr.59 = "2, 3, 12, 13"
RM 10
Clear
RL 2 Set frequency
∗1
SD 5
0 0Hz Time
Connection ON ON ON
diagram for remote setting Acceleration (RH)
Deceleration (RM) ON
Clear (RL) ON
Forward rotation (STF) ON ON ON ON
Power supply ON ON
∗1 External operation frequency (other than multi-speed) or PU running frequency
Acceleration/deceleration operation
• When the acceleration signal (RH) is turned ON, the set frequency increases. The increased speed at this time is
determined by the setting of Pr.44 Second acceleration/deceleration time. Turning OFF the RH signal stops increasing
the set frequency and run the motor at the frequency at that time.
• When the deceleration signal (RM) is turned ON, the set frequency decreases. The decreased speed at this time is
determined by the setting of Pr.45 Second deceleration time. When Pr.45 = "9999", the deceleration speed is the same
as Pr.44 setting. Turning OFF the RM signal stops decreasing the set frequency and runs the motor at the frequency at
that time.
• By setting Pr.59 = "11 to 13", the speed can be decelerated to the frequency lower than the main speed (set by the External
operation frequency (except multi-speed setting) or PU operation frequency).
Pr.59 = “ 1, 2, 3”
Output frequency
Forward rotation(STF) ON
ON
Acceleration(RH)
ON
Deceleration(RM)
NOTE
• While the RT signal is OFF, Pr.44 Second acceleration/deceleration time and Pr.45 Second deceleration time are used
as the set frequency accelerating/decelerating time at turn ON of the acceleration/deceleration signal. If the Pr.7 and Pr.8
settings are longer, the acceleration/deceleration time set by Pr.7 and Pr.8 are applied.
While the RT signal is ON, Pr.44 and Pr.45 settings are used as the acceleration/deceleration time regardless of the Pr.7 and
Pr.8 settings.
Output frequency
• During External operation, the remotely-set frequency set with RH and RM signals is added to the terminal 4 input and
External operation mode frequency (PU operation mode frequency when Pr.79 = "3" (External and PU combined
operation)) except multi-speed setting. (When compensating analog input, set Pr.28 Multi-speed input compensation
selection = "1". If the RH and RM signals are used for acceleration/deceleration while the frequency is set by analog
voltage input (terminal 2 or 4, selected by Pr.28 = "0"), the auxiliary input via terminal 1 is disabled.)
• During PU operation, the remotely-set frequency set with RH and RM signal operation is added to the PU running
frequency.
360 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Frequency setting storage
• When Pr.59 = "1, 11", the remotely-set frequency (frequency set by RH/RM operation) is stored to the memory (EEPROM). 1
When power is switched OFF once, then ON, operation is resumed with the stored set frequency.
• When Pr.59= "2, 3, 12, 13", the set frequency is not stored, so when switching the power ON again after being switched
OFF, the remotely-set frequency becomes 0 Hz. 2
• The remotely-set frequency is stored at the point when the start signal (STF or STR) turns OFF. Remotely-set frequency
is stored every minute after turning OFF (ON) the RH and RM signals together. Every minute, the frequency is overwritten
in the EEPROM if the latest frequency is different from the previous one when comparing the two. This cannot be written 3
with RL signals.
NOTE
• When switching the start signal from ON to OFF, or changing frequency by the RH or RM signal frequently, set the frequency 4
setting value storage function (write to EEPROM) invalid (Pr.59 = "2, 3, 12, 13"). If the frequency setting value storage function
is valid (Pr.59 = "1, 11"), the frequency is written to EEPROM frequently, and this will shorten the life of the EEPROM.
5
Clearing the settings
• When Pr.59 = "1, 2, 11, 12" and the clear signal (RL) is turned ON, the remotely-set frequency is cleared. When Pr.59 =
"3, 13" and the STF (STR) signal is turned OFF, the remotely-set frequency is cleared. 6
10
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
361
NOTE
• The range of frequency changeable by acceleration signal (RH) and deceleration signal (RM) is 0 to maximum frequency (Pr.1
or Pr.18 setting). Note that the maximum value of set frequency is (main speed + maximum frequency).
(Hz) The set frequency is clamped at (main speed + Pr.1)
• Even if the start signal (STF or STR) is OFF, turning ON the RH or RM signal varies the preset frequency.
• The RH, RM, or RL signal can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function
selection). Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each
terminal.
• The inverter can be used in the Network operation mode.
• The remote setting function is invalid during JOG operation and PID control operation.
• The multi-speed operation function is invalid when remote setting function is selected.
• Even when the remotely-set frequency is cleared by turning ON the RL (clear) signal after turning OFF (ON) both the RH and
RM signals, the inverter operates at the remotely-set frequency stored in the last operation if power is reapplied before one
minute has elapsed since turning OFF (ON) both the RH and RM signals.
Remotely-set frequency stored last time
Output frequency
(Hz)
Within 1 minute
Time
Acceleration (RH) ON
Deceleration (RM) OFF
ON
Clear (RL)
Forward rotation ON ON
(STF)
Power supply ON ON
• When the remotely-set frequency is cleared by turning ON the RL (clear) signal after turning OFF (ON) both the RH and RM
signals, the inverter operates at the frequency in the remotely-set frequency cleared state if power is reapplied before one
minute has elapsed since turning OFF (ON) both the RH and RM signals.
one minute
Operation is performed at the set
frequency 0Hz.
Time
Acceleration (RH) ON
Deceleration (RM) OFF
ON
Clear (RL)
CAUTION
• When using the remote setting function, set the maximum frequency again according to the machine.
Parameters referred to
Pr.1 Maximum frequency, Pr.18 High speed maximum frequencypage 407
362 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.44 Second acceleration/deceleration time, Pr.45 Second deceleration timepage 349
Pr.28 Multi-speed input compensation selectionpage 391
Pr.178 to Pr.189 (Input terminal function selection)page 496
1
5.8.4 Starting frequency and start-time hold function
V/F Magnetic flux Sensorless Vector 2
It is possible to set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when a starting torque is needed or the motor drive at start needs smoothing.
Pr. Name Initial value Setting range Description 3
13 Set the starting frequency at which the start signal is turned
Starting frequency 0.5 Hz 0 to 60 Hz
F102 ON.
571 0 to 10 s Set the holding time of Pr.13.
F103
Holding time at a start 9999
9999 The holding function at start is disabled. 4
Starting frequency setting (Pr.13)
• The frequency at start can be set in the range of 0 to 60 Hz. 5
• Set the starting frequency at which the start signal is turned ON.
Output
frequency
(Hz) 6
60
Setting range
Pr.13
7
0
Time
STF ON 8
NOTE
• The inverter does not start if the frequency setting signal has a value lower than that of Pr.13.
For example, while Pr.13 = 5 Hz, the inverter output starts when the frequency setting signal reaches 5 Hz. 9
Pr.13
0
Time
Pr. 571 setting time
STF ON
NOTE
• When Pr.13 ="0 Hz", the starting frequency is held at 0.01 Hz.
• When the start signal was turned OFF during start-time hold, deceleration is started at that point.
• At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold function is
invalid.
CAUTION
• Note that when Pr.13 is set to any value equal to or lower than Pr.2 Minimum frequency, simply turning ON the start
signal runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.2 Minimum frequencypage 407
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
363
5.8.5 Minimum motor speed frequency and hold
function at the motor start up
PM
Set frequency
Output
frequency
Pr.13
0
Time
Output from 0.01Hz
STF ON
NOTE
• Under induction motor control (under V/F control, Advanced magnetic flux vector control, Real sensorless vector control, and
Vector control), the output starts at the frequency set in Pr.13. Under PM sensorless vector control, the output always starts
at 0.01 Hz.
• The inverter does not start if the frequency setting signal has a value lower than that of Pr.13. For example, while Pr.13 = "20
Hz", the inverter output starts when the frequency setting signal reaches 20 Hz.
0
Time
Holds 0.01 Hz
Pr.571 setting time
STF ON
CAUTION
• Note that when Pr.13 is set to any value equal to or lower than Pr.2 Minimum frequency, simply turning ON the start
signal runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.2 Minimum frequencypage 407
Pr.7 Acceleration timepage 349
364 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
5.8.6 Shortest acceleration/deceleration and optimum
acceleration/deceleration (automatic acceleration/ 1
deceleration)
V/F Magnetic flux Sensorless Vector
2
The inverter can be operated with the same conditions as when the appropriate value is set to each parameter even when
acceleration/deceleration time and V/F pattern are not set. This function is useful for operating the inverter without setting
detailed parameters.
3
Initial
Pr. Name Setting range Description
value
0 Normal operation 4
1 Shortest acceleration/deceleration (without brakes)
11 Shortest acceleration/deceleration (with brakes)
292 Automatic acceleration/
F500 deceleration
0 3
5, 6
Optimum acceleration/deceleration
Lift operation 1, 2 (Refer to page 368.)
5
Brake sequence mode 1, 2
7, 8
(Refer to page 541.)
0 to 500 A*1 Set the reference current during shortest (optimum) 6
61
Reference current 9999 0 to 3600 A*2 acceleration/deceleration.
F510
9999 Rated output current value reference of the inverter
0 to 400%
Set the speed limit value (optimum value) during shortest
(optimum) acceleration.
7
62 Reference value at
9999 Shortest acceleration/deceleration: 150% as the limit value
F511 acceleration
9999 Optimum acceleration/deceleration: 100% as the optimum
value 8
Set the speed limit value (optimum value) during shortest
0 to 400%
(optimum) deceleration.
63 Reference value at
9999 Shortest acceleration/deceleration: 150% as the limit value
F512 deceleration
9999 Optimum acceleration/deceleration: 100% as the optimum
value
9
Shortest (optimum) acceleration/deceleration for both
0
acceleration and deceleration
293 Acceleration/deceleration
0 1
Shortest (optimum) acceleration/deceleration for 10
F513 separate selection acceleration only
Shortest (optimum) acceleration/deceleration for
2
deceleration only
*1 The setting range of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower
*2 The setting range of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
365
• When the shortest acceleration/deceleration is selected under V/F control and Advanced magnetic flux vector control, the
stall prevention operation level during acceleration/deceleration becomes 150% (adjustable using Pr.61 to Pr.63). The
setting of Pr.22 Stall prevention operation level and stall level by analog input are used only during a constant speed
operation.
Under Real sensorless vector control and Vector control, the torque limit level (Pr.22, etc.) is applied during acceleration/
deceleration. The adjustments by Pr.61 to Pr.63 are disabled.
• It is inappropriate to use for the following applications.
- Machines with large inertia (10 times or more), such as a fan. Since stall prevention operation is activated for a long
time, this type of machine may be shut off due to motor overloading, etc.
- When the inverter is always operated at a specified acceleration/deceleration time.
NOTE
• Even if automatic acceleration/deceleration has been selected, inputting the JOG signal (JOG operation), RT signal (Second
function selection) or X9 signal (Third function selection) during an inverter stop switches to the normal operation and give
priority to JOG operation, second function selection or third function selection. Note that during operation, an input of JOG and
RT signal does not have any influence even when the automatic acceleration/deceleration is enabled.
• Since acceleration/deceleration is made with the stall prevention operation being activated, the acceleration/deceleration
speed always varies according to the load conditions.
• By setting Pr.7 and Pr.8 appropriately, it is possible to accelerate/decelerate with a shorter time than when selecting the
shortest acceleration/deceleration.
366 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
NOTE
• Even if automatic acceleration/deceleration has been selected, inputting the JOG signal (JOG operation), RT signal (Second 1
function selection) or X9 signal (Third function selection) during an inverter stop will switch to the normal operation and give
priority to JOG operation, second function selection or third function selection. Note that JOG and RT signal input is invalid
even if JOG signal and RT signal are input during operation in the optimum acceleration/deceleration mode.
• Because of the learning method, the impact of the optimum acceleration/deceleration is not apparent in the first operation after 2
setting to the optimum acceleration/deceleration mode.
• The optimum value are calculated for only acceleration from 0 to 30 Hz or higher or deceleration from 30 Hz or higher to 0 Hz.
• The optimum acceleration/deceleration will not operate if the motor was not connected or the output current is less than 5%
of the rated current of the inverter.
3
• A Regenerative overvoltage trip during deceleration or stop (E.OV3) may occur during deceleration even if the optimum
acceleration/deceleration is selected with Pr.293 ="1 (optimum acceleration/deceleration during acceleration only)" setting. In
such case, set Pr.8 setting longer. 4
NOTE
• When Real sensorless vector control or Vector control is selected with the shortest acceleration/deceleration, Pr.61 to Pr.63
are invalid.
• Even if Pr.61 to Pr.63 are set once, changing the setting to other than the shortest acceleration/deceleration (Pr.292 ≠ "1 or
11") automatically resets to the initial setting (9999). Set Pr.61 to Pr.63 after setting Pr.292.
Parameters referred to
Pr.0 Torque boostpage 672
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
Pr.22 Stall prevention operation levelpage 409
Pr.22 Torque limit levelpage 235
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
367
5.8.7 Lift operation (automatic acceleration/
deceleration)
V/F
The inverter can be operated according to the load pattern of the lift with counterweight.
Initial
Pr. Name Setting range Description
value
0 Normal operation
Shortest acceleration/deceleration
1
(without brakes)
(Refer to page
Shortest acceleration/deceleration
292 Automatic acceleration/ 11 365.)
0 (with brakes)
F500 deceleration
3 Optimum acceleration/deceleration
5 Lift operation 1 (stall prevention operation level 150%)
6 Lift operation 2 (stall prevention operation level 180%)
7, 8 Brake sequence 1, 2 (Refer to page 541.)
0 to 500 A*1 Set the reference current during shortest (optimum)
61
Reference current 9999 0 to 3600 A*2 acceleration/deceleration.
F510
9999 Rated output current value reference of the inverter
64 Starting frequency for 0 to 10 Hz Set the starting frequency for the lift operation.
9999
F520 elevator mode 9999 Starting frequency is 2 Hz.
3%
Torque boost 0%
Regenerative Driving
0 100 120 140
current 115 current
(%)
• If the lift has a load in which the rated current of the inverter is exceeded, the maximum torque may be insufficient.
For a lift without counterweight, setting Pr.14 Load pattern selection to "2 or 3" (for lift load) and setting Pr.19 Base
frequency voltage appropriately give the maximum torque a greater advantage than when selecting the lift operation.
368 5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
NOTE
• The stall prevention operation level is automatically lowered according to the cumulative value of the electronic thermal O/L 1
relay so as to prevent an inverter overload trip (E.THT, E.THM) from occurring.
Parameters referred to
Pr.0 Torque boostpage 672
8
Pr.13 Starting frequencypage 363
Pr.14 Load pattern selectionpage 674
Pr.19 Base frequency voltagepage 673
Pr.22 Stall prevention operation levelpage 409
Pr.570 Multiple rating settingpage 326 9
10
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
369
5.9 (D) Operation command and frequency command
Refer to
Purpose Parameter to set
page
To select the operation mode Operation mode selection P.D000 Pr.79 370
To start up in Network operation mode at Communication startup
P.D000, P.D001 Pr.79, Pr.340 378
power-ON mode selection
Operation and speed
command sources during
To select the command source during Pr.338, Pr.339, Pr.550,
communication operation, P.D010 to P.D013 380
communication operation Pr.551
command source
selection
To prevent the motor from rotating Reverse rotation
P.D020 Pr.78 386
reversely prevention selection
To change the setting resolution of speed Set resolution switchover P.D030 Pr.811 422
To change the setting resolution of the
Set resolution switchover P.D030 Pr.811 422
torque limit
P.D100, P.D101, Pr.291, Pr.384 to
To set the frequency by pulse train input Pulse train input 386
P.D110, P.D111 Pr.386
To perform JOG operation JOG operation P.D200, P.F002 Pr.15, Pr.16 390
Pr.28, Pr.4 to Pr.6,
To control the frequency with combinations
Multi-speed operation P.D300 to P.D315 Pr.24 to Pr.27, Pr.232 391
of terminals
to Pr.239
To select the torque command method Torque command source P.D120 to P.D121, Pr.432 to Pr.433,
270
during torque control selection P.D400 to P.D402 Pr.804 to Pr.806
The following table lists valid and invalid commands in each operation mode.
370 5. PARAMETERS
5.9 (D) Operation command and frequency command
LED display
Pr.79
setting
Description : OFF
Refer to
page
1
: ON
PU operation
mode
2
External operation
0 Use the External/PU switchover mode ( ) to switch between the PU and External mode
373 3
(initial value) operation mode.
At power ON, the inverter is in the External operation mode.
NET operation
mode 4
8
Operation panel/parameter
External/PU combined unit or external signal input External signal input External/PU
3 (multi-speed setting, terminal combined 374
operation mode 1 (terminal STF, STR)
4)*1 operation mode 9
External signal input (terminal
External/PU combined or on operation
4 2 and 4, JOG, multi-speed 374
operation mode 2
selection, etc.) panel or parameter unit
PU operation 10
mode
Switchover mode
6 375
Switching of PU, External, and NET operation modes can be performed during operation.
External operation
mode
*1 The priorities of the frequency commands while Pr.79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
5. PARAMETERS
5.9 (D) Operation command and frequency command
371
• The operation mode can be selected from the operation panel or with the communication instruction code.
Programmable controller
Personal computer
Network operation PU operation mode
mode
Inverter
Operation panel
Personal computer
PU connector
External terminal 1
2
3 7
8
9
10
Potentiometer Switch
NOTE
• There are two settings, "3" and "4", with PU/External combined operation. The startup method differs according to the setting
value.
• In the initial setting, the stop function (PU Stop selection) by the operation panel or the parameter unit is effective in
modes other than the PU operation mode. (Refer to Pr.75 on page 320.)
NOTE
• For details on switching by external terminals, refer to the following pages.
PU operation external interlock (X12 signal)page 375
PU/External operation switchover (X16 signal)page 376
PU/NET operation switchover (X65 signal), External/NET operation switchover (X66 signal)page 377
Pr.340 Communication startup mode selectionpage 378
372 5. PARAMETERS
5.9 (D) Operation command and frequency command
Operation mode selection flow
Referring to the following table, select the basic parameter settings or terminal wiring related to the operation mode. 1
Method to give Frequency setting
Terminal wiring Parameter setting Operation method
start command method
STF (forward rotation)/STR
(reverse rotation) (Refer to Pr.79 = "2"
• Frequency setting 2
External (terminal 2 and 4, Frequency setting terminal ON
page 502.) (External operation
JOG, multi-speed, etc.) • Start command
Terminal 2 and 4 (analog) RL, mode fixed)
STF(STR)-ON
RM, RH, JOG, etc.
5. PARAMETERS
5.9 (D) Operation command and frequency command
373
• When Pr.79 = "0 or 2", the inverter starts up in the External operation mode at power-ON. (When using the Network
operation mode, refer to page 378.)
• When parameter changing is seldom necessary, setting "2" fixes the operation mode to the External operation mode.
When frequent parameter changing is necessary, setting "0" (initial value) allows the operation mode to be changed easily
to the PU operation mode by pressing of the operation panel. After switching to the PU operation mode, always
return to the External operation mode.
• The STF and STR signal are used as a start command, and the voltage to terminal 2 and 4, current signal, multi-speed
signal, and JOG signal are used as a frequency command.
Inverter
10
Frequency setting
2
potentiometer
5
Potentiometer
Inverter
Operation panel
Forward rotation STF (FR-DU08)
start
Reverse rotation STR
start
Switch SD
374 5. PARAMETERS
5.9 (D) Operation command and frequency command
• Set "4" in Pr.79. The mode cannot be changed to other operation modes.
Inverter
Operation panel 1
(FR-DU08)
10
Frequency setting
2
potentiometer
Potentiometer
5 2
NET operation→External
The switchover command to the External operation mode is transmitted via communication. 8
• The direction of operation is determined by the External operation input signal.
operation
• The setting frequency is determined by the external frequency command signal.
NET operation→PU Switch to the PU operation mode on the operation panel and parameter unit.
operation • For the direction of operation and frequency, the status during Network operation is continued. 9
PU operation interlock (Pr.79 = "7")
• The operation mode can be forcibly switched to the External operation mode by input of the PU operation external interlock
(X12) signal. This function prevents the operation mode from being accidentally unswitched from the PU operation mode.
10
If the operation mode left unswitched from the PU operation mode, the inverter does not reply to the commands sent
through external commands.
• To input the X12 signal, set "12" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
(For details on Pr.178 to Pr.189, refer to page 496.)
• Set Pr.79 = "7" (PU operation interlock).
• If the X12 signal is not assigned, the function of the MRS signal is switched to the PU operation interlock signal from MRS
(output stop).
Function/Operation
X12 (MRS) signal
Operation mode Parameter writing*1
Switching of the operation mode (External, PU, and NET) is
ON enabled Parameter writing is enabled
Output is stopped during External operation.
Operation mode is forcefully changed to the External operation
mode.
OFF External operation is enabled. Writing of parameters other than Pr.79 is disabled.
Switching to the PU or NET operation mode from the External
operation mode is disabled.
*1 Depends on the Pr.77 Parameter write selection setting and other parameter write conditions. (Refer to page 328.)
5. PARAMETERS
5.9 (D) Operation command and frequency command
375
• Functions/operations by X12 (MRS) signal ON/OFF
Operating status
Operation Switching to PU or
Operation X12 (MRS) signal Operating status
Status mode NET operation mode
mode
During stop ON→OFF*1 If frequency and start commands are given Not available
PU/NET During External*2 from external source, the inverter runs by
running ON→OFF*1 those commands. Not available
OFF→ON Available
During stop During stop
ON→OFF Not available
External External*2
During OFF→ON Running→Output stop Not available
running ON→OFF Output stop→Running Not available
*1 The mode is switched to the External operation mode regardless of the ON/OFF state of the start signals (STF, STR). Thus, the motor runs under
the External operation mode when the X12 (MRS) signal turns OFF with either of STF or STR in an ON state.
*2 When a fault occurs, the inverter can be reset by pressing on the operation panel.
NOTE
• The operation mode cannot be switched to the PU operation mode with the start signal (STF, STR) in an ON state even if the
X12 (MRS) signal is ON.
• If the MRS signal is ON and Pr.79 is written to a value other than "7" when the MRS signal is used as the PU interlock signal,
the MRS signal will act as a regular MRS function (output stop). Also, when Pr.79 = "7", the MRS signal becomes the PU
interlock signal.
• The logic of the signal follows the setting of Pr.17 MRS input selection also when the MRS signal is used as the PU operation
interlock signal. When Pr.17 = "2", ON and OFF in the above explanation are reversed.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
NOTE
• The status of the operation mode follows the Pr.340 Communication startup mode selection setting and the ON/OFF state
of the X65 and X66 signals. (For the details, refer to page 377.)
• The priority of Pr.79 and Pr.340 and signals is Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
376 5. PARAMETERS
5.9 (D) Operation command and frequency command
Switching the operation mode by external signals (X65, X66 signals)
• When Pr.79 = "0, 2 or 6", the PU operation mode and External operation modes can be changed to the Network operation 1
mode during a stop (during motor stop, start command OFF) by the PU/NET operation switchover (X65) signal, or the
External/NET operation switchover (X66) signal. (When Pr.79 = "6", switchover is enabled during operation.)
• To switch between the Network operation mode and the PU operation mode 2
1. Set Pr.79 = "0 (initial value) or 6".
4. When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the NET operation
mode is selected.
4
Pr.340 Pr.79 X65 signal state
Remarks
setting setting ON (PU) OFF (NET)
0 (initial value) PU operation mode*1 NET operation mode*2 —
5
1 PU operation mode PU operation mode fixed
2 NET operation mode NET operation mode fixed
3, 4 External/PU combined operation mode External/PU combined operation mode fixed 6
10, 12 Switching between operation modes is enabled
6 PU operation mode*1 NET operation mode*2 while running.
X12 (MRS) Switching between the External operation mode
ON and PU operation mode is enabled.*2
Output is shutoff in the External operation mode. 7
7
X12 (MRS) The operation mode is forcibly switched to the
External operation mode
OFF External operation mode.
*1
*2
When the X66 signal is ON, the NET operation mode is selected.
When the X16 signal is OFF, the PU operation mode is selected. Also, when "0" is set for Pr.550 NET mode operation command source
8
selection and the communication option is not connected (communication option is the command source), the PU operation mode is selected.
When the X16 signal is ON, the External operation mode is selected.
9
• To switch between the Network operation mode and the External operation mode
1. Set Pr.79 = "0 (initial value), 2, 6, 7". (When Pr.79 = "7" and the X12 (MRS) signal is ON, the operation mode can
be switched.) 10
2. Set Pr.340 Communication startup mode selection = "0" (initial value), "1" or "2".
3. Set "66" in one of Pr.178 to Pr.189 to assign the NET-External operation switching signal (X66) to a terminal.
4. When the X66 signal is ON, the NET operation mode is selected. When the X66 signal is OFF, the External
operation mode is selected.
0 (initial 3, 4 External/PU combined operation mode External/PU combined operation mode fixed
value), 1, 2 External operation Switching between operation modes is enabled
6 NET operation mode*1
mode*2 while running.
X12 (MRS) External operation
NET operation mode*1 Output is shutoff in the External operation mode.
ON mode*2
7
X12 (MRS) The operation mode is forcibly switched to the
External operation mode
OFF External operation mode.
*1 When Pr.550 NET mode operation command source selection = "0" (communication option control source) and no communication option is
connected, the External operation mode is selected.
*2 When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is assigned, the operation mode follows the ON/OFF
state of the X65 signal.
5. PARAMETERS
5.9 (D) Operation command and frequency command
377
NOTE
• The priority of Pr.79 and Pr.340 and signals is Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog frequencypage 390
Pr.4 to Pr.6, Pr.24 to 27, Pr.232 to Pr.239 multi-speed operationpage 391
Pr.75 Reset selection/disconnected PU detection/PU stop selectionpage 320
Pr.161 Frequency setting/key lock operation selectionpage 324
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.340 Communication startup mode selectionpage 378
Pr.550 NET mode operation command source selectionpage 380
378 5. PARAMETERS
5.9 (D) Operation command and frequency command
Selecting the operation mode for power-ON (Pr.340)
• Depending on the Pr.79 and Pr.340 settings, the operation mode at power-ON (reset) changes as described below. 1
Pr.340 Pr.79 Operation mode at power-ON, at
Operation mode switching
setting setting power restoration, or after a reset
0
(initial External operation mode
Switching among the External, PU, and NET operation modes is 2
value) enabled*2
7
mode 7
X12 (MRS) signal OFF External
operation mode
0 NET operation mode Switching between the PU and NET operation mode is enabled.*3
1 PU operation mode Same as Pr.340="0" setting 8
2 NET operation mode NET operation mode fixed
10, 12*1 3, 4 External/PU combined operation mode Same as Pr.340 = "0" setting
*3 Switching between the PU and NET operation modes is available with the key on the operation panel and the X65 signal.
Parameters referred to
Pr.57 Restart coasting timepage 597, page 604
Pr.79 Operation mode selectionpage 370
5. PARAMETERS
5.9 (D) Operation command and frequency command
379
5.9.3 Start command source and frequency command
source during communication operation
The start and frequency commands given from an external device can be made valid when using the RS-485 terminals or the
communication option. The command source in the PU operation mode can also be selected.
Initial Setting
Pr. Name Description
value range
Communication 0 Start command source is communication.
338
operation command 0
D010 1 Start command source is external.
source
0 Frequency command source is communication.
1 Frequency command source is external.
339 Communication speed
0 Frequency command source is external. (When there is no external
D011 command source
2 input, the frequency command given via communication is valid, and
the frequency command given via terminal 2 is invalid.)
The communication option is the command source when in the NET
0
operation mode.
The RS-485 terminals are the command source when in the NET
NET mode operation 1
550 operation mode.
command source 9999
D012 Communication option is recognized automatically.
selection
Normally, the RS-485 terminals are the command source. When the
9999
communication option is mounted, the communication option is the
command source.
The RS-485 terminals are the command source when in the PU
1
operation mode.
The PU connector is the command source when in the PU operation
2
PU mode operation mode.
551
command source 9999 The USB connector is the command source when in the PU operation
D013 3
selection mode.
USB automatic recognition.
9999 Normally, the PU connector is the command source. When the USB is
connected, the USB connector is the command source.
NOTE
• In the initial setting, "9999" (communication option automatic recognition) is set for Pr.550. Thus, if the communication option
is mounted, parameters cannot be written or the start and frequency commands cannot be sent by communications that use
the RS-485 terminals. (Monitoring or parameter reading can be performed.)
380 5. PARAMETERS
5.9 (D) Operation command and frequency command
NOTE
• When Pr.550 = "1" (NET mode RS-485 terminals) and Pr.551 ="1" (PU mode RS-485 terminals), the PU operation mode has 1
a precedence. For this reason, if the communication option is not mounted, switching to the Network operation mode is no
longer possible.
• Changed setting values are enabled at power-ON or inverter reset.
2
Command source
Pr.550 Pr.551
Communication Remarks
setting setting PU connector USB connector RS-485 terminals
option 3
PU operation NET operation
1 × ×
mode*1 mode*2
2 PU operation mode × ×
NET operation 4
mode*2
0 NET operation
3 × PU operation mode ×
mode*2
9999 PU operation PU operation NET operation
5
(initial ×
value) mode*3 mode*3 mode*2
PU operation Switching to NET operation mode
1 × ×
mode*1
×
disabled 6
NET operation
2 PU operation mode × ×
mode
1
3 × PU operation mode
NET operation
mode
× 7
9999 PU operation PU operation NET operation
(initial ×
mode*3 mode*3 mode
value)
PU operation NET operation
8
1 × ×
mode*1 mode*2
NET operation
2 PU operation mode ×
×
mode*2
With communication option
9
NET operation
× Without communication option
mode
9999
NET operation
(initial
value)
×
mode*2
With communication option 10
3 × PU operation mode
NET operation
× Without communication option
mode
NET operation
9999 × With communication option
PU operation PU operation mode*2
(initial *3 *3
value) mode mode NET operation
× Without communication option
mode
*1 The MODBUS RTU protocol cannot be used in the PU operation mode. To use the MODBUS RTU protocol, set Pr.551 = "2".
*2 If the communication option is not mounted, switching to the NET operation mode is not possible.
*3 When Pr.551= "9999", the priority of the PU command source is USB connector > PU connector.
5. PARAMETERS
5.9 (D) Operation command and frequency command
381
Controllability through communication
Controllability in each operation mode
Condition Combined Combined
Command NET operation
(Pr.551 Item PU External operation operation NET operation
interface (via RS-485
setting) operation operation mode 1 mode 2 *7 (via option)*8
terminals)
(Pr.79 = "3") (Pr.79 = "4")
Operation (start)
○ × × ○ ×
2 command
(PU Operation (stop)
command
○ ∆*4 ∆*4 ○ ∆*4
connector),
9999 Running frequency ○ × ○ × ×
(automatic Monitor ○ ○ ○ ○ ○
recognition,
without USB Parameter writing ○*5 ×*6 ○*5 ○*5 ×*6
connection) Parameter read ○ ○ ○ ○ ○
PU Inverter reset ○ ○ ○ ○ ○
connector*1 Operation (start)
× × × × ×
command
Operation (stop)
command ∆*4 ∆*4 ∆*4 ∆*4 ∆*4
Terminals
other than Running frequency × × × × ×
the above Monitor ○ ○ ○ ○ ○
*6 *6 *6 *6
Parameter writing × × × × ×*6
Parameter read ○ ○ ○ ○ ○
Inverter reset ○ ○ ○ ○ ○
Operation command
○ × × ○ ×
(start, stop)
Running frequency ○ × ○ × ×
1
(RS-485 Monitor ○ ○ ○ ○ ○
terminals) Parameter writing ○*5 ×*6 ○*5 ○*5 ×*6
Parameter read ○ ○ ○ ○ ○
RS-485 Inverter reset ○ ○ ○ ○ ○
terminals Operation command
(start, stop)
× × × × ○*2 ×
382 5. PARAMETERS
5.9 (D) Operation command and frequency command
Controllability in each operation mode
Condition Combined Combined
Command
interface
(Pr.551 Item PU External operation operation
NET operation
(via RS-485
NET operation 1
setting) operation operation mode 1 mode 2 *7 (via option)*8
terminals)
(Pr.79 = "3") (Pr.79 = "4")
Inverter reset ○ ○ ○ ○ ○
External
control Operation command 2
— (start, stop)
× ○ ○ × ×*2
circuit
terminal Frequency setting × ○ × ○ ×*2
○: Valid, ×: Invalid, ∆: Partially valid 3
*1
*2
RS-485 communication via PU connector
Follows the Pr.338 Communication operation command source and Pr.339 Communication speed command source settings. (Refer to
4
page 380.)
*3 At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.
*4 Only PU stop is enabled. "PS" is displayed on the operation panel during PU stop. Follows the Pr.75 Reset selection/Disconnected PU
detection/PUStop selection setting. (Refer to page 320.) 5
*5 Writing of some parameters may be disabled by the Pr.77 Parameter write selection setting and the operating condition. (Refer to page 328.)
*6 Some parameters are write-enabled independently of the operation mode and command source presence/absence. Writing is also enabled when
Pr.77 = "2".
(Refer to page 328.) Parameter clear is disabled. 6
*7 When Pr.550 NET mode operation command source selection = "1" (RS-485 terminals enabled), or Pr.550 NET mode operation command
source selection = "9999" with no communication option connected.
*8 When Pr.550 NET mode operation command source selection = "0" (communication option enabled), or Pr.550 NET mode operation
command source selection = "9999" with communication option connected. 7
Operation when a communication error occurs
Operation in each operation mode at error occurrences
Combined Combined
8
Condition NET operation NET
Fault type External operation operation
(Pr.551 setting) PU operation (via RS-485 operation
operation mode 1 mode 2
terminals)*5 (via option)*6
(Pr.79 = 3) (Pr.79 = "4")
Inverter fault — Stop
9
2 (PU connector)
PU connector 9999 (automatic Stop/continued*1*4
disconnection recognition)
Other than 2 Stop/continued*1
10
Stop/ Stop/
Communication error 2 (PU connector) Continued Continued
continued*2 continued*2
at PU connector
Other than 2 Continued
Stop/ Stop/
1 (RS-485 terminals) Continued Continued
Communication error continued*2 continued*2
at RS-485 terminals Stop/
Other than 1 Continued Continued
continued*2
3 (USB connector) Stop/
Communication error 9999 (automatic Continued
recognition) continued*2
at USB connector
Other than 3 Continued
Communication error Stop/
at communication — Continued
option continued*3
5. PARAMETERS
5.9 (D) Operation command and frequency command
383
Selection of control source in Network operation mode (Pr.338, Pr.339)
• There are two control sources: the start command source, which controls the signals related to the inverter stand command
and function selection, and the speed command source, which controls signals related to frequency setting.
• The following table shows the commands given via the external terminals or given through communication (via the RS-485
terminals or the communication option) in the Network operation mode.
384 5. PARAMETERS
5.9 (D) Operation command and frequency command
Pr.338 Communication operation command
Operation 0: NET 1: EXT
source
location
selection
Pr.339 Communication speed command 0: 1: 2: 0: 1: 2:
Remarks
1
source NET EXT EXT NET EXT EXT
44 X44 P/PI control switchover NET External
45 BRI2
Second brake sequence open
completion
NET External 2
46 TRG Trace trigger input Combined External
47 TRC Trace sampling start/end Combined External
48 X48 Power failure stop external External 3
Pr.414 = "1": Valid
when there is
external or network
50 SQ Sequence start External, NET External
input
Pr.414 = "2":
4
External
51 X51 Fault clear Combined External
52 X52 Cumulative pulse monitor clear NET External 5
Cumulative pulse monitor clear (control
53 X53 NET External
terminal option)
57 JOGF JOG forward rotation command — External
58 JOGR JOG reverse rotation command — External 6
59 CLRN NET position pulse clear NET
60 STF Forward rotation command NET External
61
62
STR
RES
Reverse rotation command
Inverter reset
NET
External
External
7
Pr.178 to Pr.189 settings
5. PARAMETERS
5.9 (D) Operation command and frequency command
385
NOTE
• The command source of communication follows the Pr.550 and Pr.551 settings.
• The Pr.338 and Pr.339 settings can be changed while the inverter is running when Pr.77 = "2". Note that the setting change
is applied after the inverter has stopped. Until the inverter has stopped, communication operation command source and
communication speed command source before the setting change are valid.
NOTE
• The ON/OFF state of the X67 signal is applied only during a stop. When the terminals are switched during operation, the ON/
OFF state is reflected after a stop.
• When the X67 is OFF, a reset via communication is disabled.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.28 Multi-speed input compensation selectionpage 391
Pr.59 Remote function selectionpage 349
Pr.79 Operation mode selectionpage 370
386 5. PARAMETERS
5.9 (D) Operation command and frequency command
Moreover, speed synchronized operation of an inverter can be performed by using the pulse train output together with the
terminal JOG.
1
Initial value Description
Pr. Name Setting range Pulse train input Pulse train output
FM CA
(terminal JOG) (terminal FM)
0 JOG signal*1 FM output*2 2
1 Pulse train input FM output*2
High-speed pulse train output
10*2 JOG signal*1 (50% duty) 3
High-speed pulse train output (50%
11*2 Pulse train input
duty)
291
Pulse train I/O selection 0 High-speed pulse train output
20*2 JOG signal*1
D100
(ON width fixed) 4
High-speed pulse train output (ON
21*2 Pulse train input
width fixed)
High-speed pulse train output (ON
Pull up resistor ∗1
JOG JOG 2 kΩ
2 kΩ
Pull down resistor ∗1
SD
SD
*1 When the wiring length is long with open collector outputs, the influence of stray capacitance causes the pulse to flatten out and prevents the
input pulse from being recognized.
When the wiring length is long (10 m or longer of shielded twisted pair cable with a recommended cable gauge of 0.75 mm2), connect the open
collector output signal to the power supply by an external pull-up resistor. The following table shows the reference resistance values for wiring
length. The stray capacitance of the wiring changes considerably according to how the cable is laid, thus the above wiring lengths are not
guaranteed values. When using a pull-up/down resistor, check the permissible load of the resistor and the permissible load current of the output
transistor, and use within the permissible range.
5. PARAMETERS
5.9 (D) Operation command and frequency command
387
• Connection with a complementary output system pulse generator
JOG JOG 2 kΩ
24 V power 24 V power
2 kΩ
SD
SD
NOTE
• When pulse train input is selected, the function assigned to terminal JOG by Pr.185 JOG terminal function selection is
invalid.
• When "2" (simple position pulse train command given by pulse train input) is set to Pr.419 Position command source
selection, the JOG terminal becomes the simple position pulse train terminal regarding of the Pr.291 setting.
• Pr.291 is the selection parameter for pulse train output/FM output. Thus, before changing the setting, check the specifications
of the device connected to the terminal FM. (For the pulse train output, refer to page 438.)
*1 The wiring length of complementary output is dependent on the output wiring specification of the complementary output unit. The stray
capacitance of the wiring changes considerably according to how the cable is laid, so the maximum wiring length is not a guaranteed value.
Limit value
60Hz(50Hz)
Pr. 386
frequency
Output
(Hz)
Input pulse
0Hz (pulse/s)
0 Maximum input pulse
Pr. 385
388 5. PARAMETERS
5.9 (D) Operation command and frequency command
NOTE
• The priority of the frequency command given by the external signals is "JOG operation > multi-speed operation > terminal 4 1
analog input". When pulse train input is enabled (Pr.291 = "1, 11, 21, 100" and Pr.384 ≠ "0"), terminal 2 analog input becomes
invalid.
2
Speed synchronized operation by pulse input/output
Inverter (master) Pull up
resistor*1
To next inverter (slave) 3
PC
Speed Speed
Pulse train
4
command command
JOG input FM
FM JOG
Pulse train
To next inverter (slave)
Pulse train
output output SD
SD SD 5
*1 When the wiring length between FM and JOG is long, the influence of stray capacitance causes the pulse to flatten out and prevents the input
pulse from being recognized. When the wiring length is long (10 m or longer of shielded twisted pair cable with a recommended cable size of 0.75
mm2), connect between terminal JOG and terminal PC with an external pull-up resistor. The following table shows the reference resistance values
for wiring length.
6
Wiring length Less than 10 m 10 to 50 m 50 to 100 m
Pull-up resistor Not required 1 kΩ 470 Ω
Load current (reference) 10 mA 35 mA 65 mA 7
The stray capacitance of the wiring changes considerably according to how the cable is laid, thus the above wiring lengths are not guaranteed
values.
When using a pull-up/down resistor, check the permissible load of the resistor and the permissible load current (terminal PC: 100 mA, high-speed 8
pulse train output: 85 mA), and use within the permissible range.
• Setting "100" in Pr.291 enables out of the pulse train input as it is to the pulse train output (terminal FM).
Connecting in a daisy chain enables speed synchronized operation of multiple inverters.
• Set Pr.384 to "125" for inverters that receive pulse train since the maximum pulse train output is 50k pulses/s.
9
• The maximum number of input pulses should be 50k pulses/s.
• When performing synchronized operation, wire according to the following procedure. (This is to prevent contact input of 24
V being applied to terminal FM.) 10
1. Set pulse train output (setting other than "0 or 1") to Pr.291 on the master side inverter.
3. Wire the slave side terminal JOG-SD to the master side terminal FM-SD.
NOTE
• After changing the Pr.291 setting, connect the JOG terminal to the terminal FM-SD. When FM output (voltage output) is taken
as the pulse train, take caution to prevent voltage from being applied to the terminal FM.
• Use sink logic (factory setting) for the slave side inverter. The inverter does not operate properly with source logic.
*1 A pulse propagation delay of about 1 to 2 μs in the slave occurs and further increases when the wiring length is long.
Parameters referred to
Pr.291 (Pulse train output)page 435
Pr.419 Position command source selectionpage 304
5. PARAMETERS
5.9 (D) Operation command and frequency command
389
5.9.6 JOG operation
The frequency and acceleration/deceleration time for JOG operation can be set. JOG operation is possible in both External
operation and PU.
JOG operation can be used for conveyor positioning, test operation, etc.
Initial
Pr. Name Setting range Description
value
15
Jog frequency 5 Hz 0 to 590 Hz Set the frequency during JOG operation.
D200
Set the motor acceleration/deceleration time during JOG operation.
For the acceleration/deceleration time, set the time until the
16 Jog acceleration/
F002 deceleration time
0.5 s 0 to 3600 s frequency*1 set in Pr.20 Acceleration/deceleration reference
frequency is reached.
The acceleration/deceleration times cannot be set separately.
The above parameter is displayed as a simple mode parameter when the LCD operation panel (FR-LU08) or the parameter
unit (FR-PU07) is mounted. Setting of this parameter is enabled when the operation panel (FR-DU08) is connected and "0" is
set to Pr.160 User group read selection. (Refer to page 337.)
*1 The Pr.20 initial value is set to 60 Hz for the FM type and to 50 Hz for the CA type.
Output frequency(Hz)
Output frequency(Hz) Pr.20
Pr.20 Pr.15 Forward
setting range rotation
Pr.15 Forward Reverse
Time
setting range rotation rotation
Reverse Time
rotation Pr.16
Pr.16
JOG signal ON
JOG operation in PU
• When the operation panel or parameter unit is in the JOG operation mode, the motor jogs only while the start button is
pressed. (For the operation method, refer to page 160.)
390 5. PARAMETERS
5.9 (D) Operation command and frequency command
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern 1
selection setting. (Refer to page 354.)
• The Pr.15 setting should be equal to or higher than the Pr.13 Starting frequency setting.
• The JOG signal can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal. 2
• During JOG operation, the second acceleration/deceleration cannot be selected via the RT signal. (Other second functions
are enabled (refer to page 500).)
• When the JOGR or STR signal is input while the JOGF signal is input, the motor is decelerated to stop.
• When the JOGF or STF signal is input while the JOGR signal is input, the motor is decelerated to stop.
3
• The three-wire type connection is not available for the JOGF and JOGR signals.
• When Pr.79 Operation mode selection = "4", JOG operation is started by one push of / on the operation panel 4
and stopped by .
• This function is invalid when Pr.79 = "3".
• Under the position control, when the position command speed creation is completed and the droop pulse is within in-position
5
width, the external JOG operation can be operated. (The JOG operation cannot be performed from PU.)
• For the external JOG operation, set Pr.291 Pulse train I/O selectionto a value which enables the JOG signal input. (Refer to
page 386.) 6
Parameters referred to
Pr.13 Starting frequencypage 363
Pr.20 Acceleration/deceleration reference frequency, Pr.21 Acceleration/deceleration time incrementspage 349
7
Pr.29 Acceleration/deceleration pattern selectionpage 354
Pr.79 Operation mode selectionpage 370
Pr.178 to Pr.189 (Input terminal function selection)page 496
8
5.9.7 Operation by multi-speed setting
Use these parameters to change among pre-set operation speeds with the terminals. The speeds are pre-set with parameters.
9
10
5. PARAMETERS
5.9 (D) Operation command and frequency command
391
Any speed can be selected by simply turning ON/OFF the contact signals (RH, RM, RL, and REX signals).
Initial value
Pr. Name Setting range Description
FM CA
28 Multi-speed input compensation 0 Without compensation
0
D300 selection 1 With compensation
4
Multi-speed setting (high speed) 60 Hz 50 Hz 0 to 590 Hz Sets the frequency when RH is ON.
D301
5 Multi-speed setting (middle
30 Hz 0 to 590 Hz Sets the frequency when RM is ON.
D302 speed)
6
Multi-speed setting (low speed) 10 Hz 0 to 590 Hz Sets the frequency when RL is ON.
D303
24
Multi-speed setting (speed 4)
D304
25
Multi-speed setting (speed 5)
D305
26
Multi-speed setting (speed 6)
D306
27
Multi-speed setting (speed 7)
D307
232
Multi-speed setting (speed 8)
D308
233 Frequency from 4th speed to 15th speed can
Multi-speed setting (speed 9)
D309 be set according to the combination of the RH,
9999 0 to 590 Hz, 9999
234 RM, RL and REX signals.
Multi-speed setting (speed 10)
D310 9999: Not selected
235
Multi-speed setting (speed 11)
D311
236
Multi-speed setting (speed 12)
D312
237
Multi-speed setting (speed 13)
D313
238
Multi-speed setting (speed 14)
D314
239
Multi-speed setting (speed 15)
D315
Inverter Speed 1
Output frequency (Hz)
(High speed)
NOTE
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• The RH, RM and RL signals are assigned to the terminals RH, RM and RL in the initial status. Set "0 (RL)", "1 (RM)", and "2
(RH)" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the signals to other terminals.
Multi-speed setting for 4th speed or more (Pr.24 to Pr.27, Pr.232 to Pr.239)
• The frequency from 4th speed to 15th speed can be set according to the combination of the RH, RM, RL, and REX signals.
Set the running frequencies in Pr.24 to Pr.27, Pr.232 to Pr.239. (In the initial status, 4th to 15th speeds are invalid.)
392 5. PARAMETERS
5.9 (D) Operation command and frequency command
• For the terminal used for REX signal input, set "8" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign
the function.
1
Output frequency
Speed 10
Speed 5 Speed 11
Speed 6 Speed 12
Forward Speed 9
rotation Inverter Speed 4 Speed 8
Speed 13
Speed 14
2
STF
(Hz)
Multi-speed selection
Speed 7 Speed 15
REX 10
Time
RH 2
Frequency setting
potentiometer
RH ON ON ON ON ON ON ON 3
RM
5 ON ON ON ON ON ON ON
RL RM
ON ON ON ON ON ON
4
SD RL
ON ON ON ON ON ON ON ON
REX
∗1
*1 When RH, RM and RL is set to OFF and REX is set to ON when "9999" is set to Pr.232 Multi-speed setting (speed 8), the inverter runs by the
frequency set to Pr.6. 5
Input compensation of multi-speed setting (Pr.28)
• Speed (frequency) can be compensated for the multi-speed setting and the remote setting by inputting the frequency
setting compensation signal (terminals 1, 2).
6
NOTE
• The priority of the frequency commands given by the external signals are "JOG operation > multi-speed operation > terminal 7
4 analog input > pulse train input > terminal 2 analog input". (For details on frequency commands given by analog input, refer
to page 482.)
• Valid in the External operation mode or PU/External combined operation mode (Pr.79 = "3 or 4").
• Multi-speed parameters can also be set during PU operation or External operation. 8
• The Pr.24 to Pr.27 and Pr.232 to Pr.239 settings have no priority among them.
• When Pr.59 Remote function selection ≠ "0", the multi-speed setting is invalid since the RH, RM, and RL signals are for
remote setting. 9
• When performing analog input compensation, set Pr.28 Multi-speed input compensation selection to "1".
• Select the terminals (terminals 1, 2) to use for compensation input voltage (0 to ± 5 V, 0 to ± 10 V) at Pr.73 Analog input
selection.
• When using terminal 1 for compensation input, set Pr.868 Terminal 1 function assignment = "0 (initial value)". 10
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog frequencypage 390
Pr.59 Remote function selectionpage 359
Pr.73 Analog input selectionpage 473
Pr.79 Operation mode selectionpage 370
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.868 Terminal 1 function assignmentpage 477
5. PARAMETERS
5.9 (D) Operation command and frequency command
393
5.10 (H) Protective function parameter
394 5. PARAMETERS
5.10 (H) Protective function parameter
Pr. Name Initial value Setting range Description
9 Inverter 0 to 500 A *2 1
Electronic thermal O/L relay *1 Set the rated motor current.
H000 rated current 0 to 3600 A*3
600 First free thermal reduction 0 to 590 Hz
9999
H001 frequency 1 9999 2
601 First free thermal reduction 1 to 100%
100% The electronic thermal O/L relay operation level can
H002 ratio 1 9999 be changed to match the motor temperature
602 First free thermal reduction 0 to 590 Hz characteristics with the combination of these three
H003 frequency 2
9999
9999 points (Pr.600, Pr.601), (Pr.602, Pr.603), (Pr.604, 3
1 to 100% Pr.9).
603 First free thermal reduction
100% 9999: Free thermal O/L relay invalid
H004 ratio 2 9999
604
H005
First free thermal reduction
frequency 3
9999
0 to 590 Hz 4
9999
607 Set the permissible load according to the motor
Motor permissible load level 150% 110 to 250%
H006 characteristics.
0 to 500 A*2 Enabled when the RT signal is ON. 5
51 Second electronic thermal O/L
9999 0 to 3600 A*3 Set the rated motor current.
H010 relay
9999 Second electronic thermal O/L relay invalid
692 Second free thermal reduction
9999
0 to 590 Hz 6
H011 frequency 1 9999
693 Second free thermal reduction 1 to 100%
100% The electronic thermal O/L relay operation level can
H012 ratio 1 9999
694 Second free thermal reduction 0 to 590 Hz
be changed to match the second motor temperature
characteristics with the combination of these three
7
9999
H013 frequency 2 9999 points (Pr.692, Pr.693), (Pr.694, Pr.695), (Pr.696,
1 to 100% Pr.51) when the RT signal is ON.
695 Second free thermal reduction
100% 9999: Second free thermal O/L relay invalid
H014 ratio 2 9999 8
696 Second free thermal reduction 0 to 590 Hz
9999
H015 frequency 3 9999
Set the permissible frequency when the RT signal is
608 Second motor permissible load
9999
110 to 250%
ON. 9
H016 level The Pr.607 setting is applied even when the RT signal
9999
is ON.
561 0.5 to 30 kΩ Set the PTC thermistor protection level (resistance).
H020
PTC thermistor protection level 9999
9999 PTC thermistor protection disabled 10
Set the time from when the resistance of the PTC
1016 PTC thermistor protection
0s 0 to 60 s thermistor reaches the protection level until the
H021 detection time
protective function is activated.
0 Terminal OH of the control terminal option (FR-A8TP)
876 is invalid.
Thermal protector input 1
H022*4 1 Terminal OH of the control terminal option (FR-A8TP)
is valid.
*1 The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the inverter rated current.
*2 The setting range of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower The minimum setting increment is 0.01 A.
*3 The setting range of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher The minimum setting increment is 0.1 A.
*4 The setting is available when the FR-A8TP is installed.
5. PARAMETERS
5.10 (H) Protective function parameter
395
• When using the Mitsubishi Electric constant-torque motor, set Pr.71 Applied motor = "1, 13 to 16, 50, 53, 54". (This setting
enables the 100% constant-torque characteristic in the low-speed range.)
Pr. 9 = 50% setting Pr. 9 = 100% setting
of inverter rating*1.2 of inverter rating*1.2
Operation time (min)
Minute display in
70 30Hz or more*3
30Hz
this region
52.5% 105%
50 100 150 230
Inverter output power (%)
(% to the inverter rated current)
*1 When setting Pr.9 to a value (current value) of 50% of the inverter rated current
*2 The % value denotes the percentage to the rated inverter current. It is not the percentage to the rated motor current.
*3 When you set the electronic thermal relay function dedicated to the Mitsubishi Electric constant-torque motor, this characteristic curve applies to
operation at 6 Hz or higher. (For selection of the operation characteristic , refer to page 505.)
*4 Transistor protection is activated depending on the temperature of the heatsink. The protection may be activated even with less than 150%
depending on the operating conditions.
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset to the initial value by the inverter's power
reset and reset signal input. Avoid unnecessary reset and power-OFF.
• Install an external thermal relay (OCR) between the inverter and motors to operate several motors, a multi-pole motor or a
dedicated motor with one inverter. When setting an external thermal relay, note that the current indicated on the motor rating
plate is affected by the line-to-line leakage current. (Refer to page 114.) The cooling effect of the motor drops during low-speed
operation. Use a thermal protector or a motor with built-in thermistor.
• The protective characteristic of the electronic thermal O/L relay is degraded when there is a large difference in capacity
between the inverter and motor, and when the set value is small. In such case, use an external thermal relay.
• A dedicated motor cannot be protected by an electronic thermal O/L relay. Use an external thermal relay.
• Set Pr.9 = "0" for Vector-control-dedicated motors (SF-V5RU) because they are equipped with thermal protectors.
• The transistor protection thermal O/L relay is activated early when the Pr.72 PWM frequency selection setting is increased.
396 5. PARAMETERS
5.10 (H) Protective function parameter
70
1
operation time [min]
Minute display in
2000r/min
Thermal relay (133.33Hz) or lower
this region
60
3000r/min
50 (200Hz)
2
240
2000r/min 3
Thermal relay operation time [s]
Second display in this region
(133.33Hz) or lower
180
3000r/min
120
(200Hz)
4
Range for the
transistor
protection
60 5
0
80 100 120 140 160 200 220 240 260 280 300
Current [%] 6
Protective function activated area: the area right of the characteristic curve
Normal operation area: the area left of the characteristic curve
*1 The % value denotes the percentage to the rated motor current. 7
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset to the initial value by the inverter's power
reset and reset signal input. Avoid unnecessary reset and power-OFF. 8
• When using a PM motor other than MM-CF, set the free thermal parameters (Pr.600 to Pr.604) in accordance with the motor
characteristic.
• The transistor protection thermal O/L relay is activated early when the Pr.72 PWM frequency selection setting is increased.
9
Set two types of electronic thermal O/L relays (Pr.51)
MC 10
IM
MC
U
V IM
W
RT
SD
• These settings are used when rotating two motors with different rated current separately by a single inverter. (When
rotating two motors together, use an external thermal relay.)
• Set the rated motor current for the second motor in Pr.51 Second electronic thermal O/L relay.
5. PARAMETERS
5.10 (H) Protective function parameter
397
• While the RT signal is ON, the setting values of Pr.51 is referred to provide thermal protection.
NOTE
• The RT signal is a second function selection signal which also enables other second functions. (Refer to page 500.)
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
240
Range for
180
the transistor
protection
120
60
0
80 100 120 140 160 180 200
Inverter output power (%)
(% to the inverter rated current)
Example of motor permissible load setting
(when Pr.9="100% of the inverter rating")
Electronic thermal O/L relay pre-alarm (TH) and warning signal (THP
signal)
• If the accumulated electronic thermal value reaches 85% of the Pr.9 or Pr.51 setting, electronic thermal O/L relay function
pre-alarm (TH) is displayed and the electronic thermal O/L relay pre-alarm (THP) signal is output. If the value reaches
100% of the Pr.9 setting, the motor thermal protection (E.THM/E.THT) is activated to shut off the inverter output. The
inverter output is not shut off with the TH display.
398 5. PARAMETERS
5.10 (H) Protective function parameter
• For the terminal used for the THP signal output, assign the function by setting "8 (positive logic) or 108 (negative logic)" in
any of Pr.190 to Pr.196 (Output terminal function selection).
Electronic thermal 100%
1
relay function 85%
operation level
NOTE 3
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
4
External thermal relay input (OH signal, E.OHT)
Thermal relay protector
Inverter
U
Motor 5
V M
W
OH
SD 6
External thermal relay input connection diagram
• The external thermal relay input (OH) signal is used when using the external thermal relay or the thermal protector built
into the motor to protect the motor from overheating.
7
• When the thermal relay is activated, the inverter output is shut off by the external thermal relay (E.OHT).
• For the terminal used for the OH signal input, set "7" in any of Pr.178 to Pr.189 (Input terminal function selection) to
assign the function.
8
• Vector-control-dedicated motors (SF-V5RU) are equipped with thermal protectors.
Inverter
∗1
SF-V5RU
9
PC
2W1kΩ G1
OH
G2
SD
10
Connecting the SF-V5RU thermal protector
*1 Connect the recommended 2 W 1 kΩ resistor between terminals PC and OH. (Refer to page 90.)
• When the control terminal option (FR-A8TP) is used, valid/invalid setting of the terminal OH can be changed using Pr.876
thermal protector input.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
5. PARAMETERS
5.10 (H) Protective function parameter
399
PTC thermistor input (Pr.561, Pr.1016, E.PTC)
Thermistor resistance
Thermistor curve
Inverter R2
Motor
U
V Pr.561
W
R1
10
2 Thermistor temperature
Temperature - resistance
existing range TN-DT TN
TN+DT
• Output from the PTC thermistor, which is built into the motor, can be input to the terminals 2 and 10. If the input from the
PTC thermistor reaches the resistor value set in Pr.561 PTC thermistor protection level, the PTC thermistor operation
(E.PTC) shuts off the inverter output.
• Confirm the characteristic of the PTC thermistor to be used, and set the resistance for Pr.561 around the center of the R1
and R2 values shown on the figure above so that it does not deviate from the protective function activating temperature
TN. If the Pr.561 setting becomes too close to R1 or R2, the protective function activating temperature may be too hot
(protection is delayed), or too cold (too much protection).
• When the PTC thermistor protection is enabled (Pr.561 ≠ "9999"), the resistance value for the PTC thermistor can be
displayed on the operation panel or via RS-485 communication. (Refer to page 424.)
• When the PTC thermistor protection level setting is used, use Pr.1016 PTC thermistor protection detection time to set
the time from when the resistance of the PTC thermistor reaches the protection level until the protective function (E.PTC)
is activated.
• If the resistance of the PTC thermistor falls below the protection level within the protection detection time, the elapsed time
count is cleared.
Pr.561
setting
Time
Pr.1016
ALM
E.PTC
NOTE
• When using terminal 2 for PTC thermistor input (Pr.561 ≠ "9999"), the terminal 2 does not operate as an analog frequency
command terminal. The PID and dancer control functions assigned to the terminal 2 is also disabled. Use Pr.133 PID action
set point to set the set point for the PID function.
• To input power to the PTC thermistor power supply, always use the terminal 10 and do not use any other terminals or an
external power supply. Otherwise, the PTC thermistor protection (E.PTC) does not operate properly.
• When E.PTC is activated, the alarm display, "External protection (AU terminal)", may appear on the parameter unit (FRPU07),
but it is not a fault.
400 5. PARAMETERS
5.10 (H) Protective function parameter
Overheat protection to match the characteristic of the motor (Pr.600 to
Pr.604, Pr.692 to Pr.696) 1
• The activation level of the electronic thermal O/L relay can be varied to match the motor temperature characteristic.
• The electronic thermal O/L relay operation level can be set with the combination of three points (Pr.600, Pr.601), (Pr.602,
Pr.603), (Pr.604, Pr.9). Two or more points are required for setting. 2
• The electronic thermal O/L relay operation level can be set with the combination of three points (Pr.692, Pr.693), (Pr.694,
Pr.695), (Pr.696, Pr.51) when the RT signal is ON.
Continuous operation characteristic 3
Load ratio (ratio to Pr.9 (Pr.51)) [%]
100%
Pr.603
(Pr.695)
4
Pr.601
(Pr.693)
5
Pr.600 Pr.602 Pr.604 Output frequency
(Pr.692) (Pr.694) (Pr.696)
Setting
6
Load ratio Setting Load ratio
example 1 example 2
100% 100%
Pr.9=100% of the rated Pr.600=120Hz
motor current 70% Pr.601=60%
Pr.600=6Hz Pr.602=3Hz 60%
Pr.601=50% 50% Pr.603=50% 50% 7
Pr.602=30Hz Pr.604=60Hz
Pr.603=70%
Pr.604=60Hz
6Hz 30Hz 60Hz Frequency
3Hz 60Hz 120Hz Frequency 8
• When setting Pr.600, Pr.602, Pr.604 (Pr.692, Pr.694, Pr.696) to the same frequency, the following graph's upper level is
applied.
Load ratio [%] 9
100
Pr.600 = 10Hz
80 Pr.601 = 80%
50
Pr.602 = 10Hz 10
Pr.603 = 50%
Pr.604 = 10Hz
10 Outout frequency[Hz]
NOTE
• Make sure to set the parameters according to the temperature characteristic of the motor used.
Parameters referred to
Pr.71 Applied motorpage 505
Pr.72 PWM frequency selectionpage 339
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
5. PARAMETERS
5.10 (H) Protective function parameter
401
Deceleration stop at motor thermal protection activation (Pr.875= "1")
• At activation of the external thermal relay (E.OHT), motor load (electronic thermal O/L relay) (E.THM) and PTC thermistor
(E.PTC) protective functions, the alarm output 2 (ER) signal is displayed, and the motor decelerates to stop. After it stops,
a fault signal (ALM) is output.
• When the ER signal comes ON, reduce the load or take other measures to allow the inverter to decelerate.
• During fault occurrence aside from the E.OHT, THM and E.PTC, the output is immediately shut off, and the fault is signal
(ALM) is output.
• To use the ER signal, set "97 (positive logic)" or "197 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal
function selection) to assign the function to the output terminal.
When Pr.875 = "1"
Output
frequency
Time
Fault output ON
(ALM, ALM2)
ON
Alarm output 2
(ER)
E.OHT E.OHT
occurrence display
NOTE
• Regardless of the Pr.875 setting, when the protective function is operating during position control, output is immediately shut
off. (No deceleration stop)
• For systems with a large load-side torque that prevents deceleration, setting value "0" is recommended.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
operation is faulty and " " (FN), the indication of the Fan alarm, is displayed on the operation panel. The Fan fault
output (FAN) signal and the Alarm (LF) signal are output.
• For the terminal used for the FAN signal output, set "25 (positive logic)" or "125 (negative logic)" in any of Pr.190 to Pr.196
(Output terminal function selection) and for LF signal, set "98 (positive logic)" or "198 (negative logic)".
Cooling fan operation control (Pr.244 = "1" (initial value), "101 to 105")
• The cooling fan operation is controlled when Pr.244 = "1". When the inverter is running, the cooling fan operates constantly.
When the inverter is stopped, the cooling fan operates depending on the temperature of the inverter heatsink. If the fan
stops although it meets the conditions for running, fan operation is regarded as faulty, [FN] is displayed on the operation
panel, and the fan signal and LF signals are output.
402 5. PARAMETERS
5.10 (H) Protective function parameter
• To prevent the cooling fan from turning ON and OFF repeatedly during frequent starts/stops (inching), the cooling fan stop
waiting time can be set. The waiting time when Pr.244 = "101 to 105" is Pr.244 - 100 (or 1 s, if the Pr.244 = "101").
1
Cooling fan operation command (Y206) signal
• The Cooling fan operation command (Y206) signal can be output when the inverter cooling fan meets the conditions for
running. The function can be used when the fan installed on the enclosure is synchronized with the inverter cooling fan. 2
• The Y206 signal indicates the operating command condition of the inverter cooling fan depending on the power supply ON/
OFF or the Pr.244 settings. The signal does not indicate the actual operation of the cooling fan. (The signal is output even
if the cooling fan is stopped due to a fault.) 3
• To use the Y206 signal, set "206 (positive logic) or 306 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal
function selection) to assign function to an output terminal.
NOTE
4
• The cooling fan is installed on the FR-A820-00105(1.5K) or higher and the FR-A840-00083(2.2K) or higher.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal. 5
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450 6
5.10.4 Earth (ground) fault detection at start
V/F Magnetic flux 7
Select whether to make earth (ground) fault detection at start. When enabled, earth (ground) fault detection is performed
immediately after a start signal input to the inverter.
Pr. Name Initial value Setting range Description
8
Without the earth (ground) fault detection at
249 Earth (ground) fault detection at 0
0 start
H101 start
1 With the earth (ground) fault detection at start 9
• If a ground fault is detected at start while Pr.249 = "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off. (Refer to page 756.)
• Pr.249 setting is enabled during V/F control and Advanced magnetic flux vector control. 10
• When the Pr.72 PWM frequency selection setting is high, enable the ground fault detection at start.
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use Pr.249 to enable/disable ground fault detection at operation start. Ground faults are detected always during operation
regardless of the Pr.249 setting.
5. PARAMETERS
5.10 (H) Protective function parameter
403
NOTE
• Do not use this function when switching to an external battery, since the inrush current when power is restored increases, as
the undervoltage level is decreased.
• For the 200 V class inverters, the setting is available for the FR-A820-02330(45K) or lower.
• The Pr.598 setting is valid for induction motors. When either of the first or second motor is a PM motor, the Pr.598 setting is
invalid.
NOTE
• If a protective function is already operating, no fault can be activated by Pr.997.
• The retry function is disabled when a protective function has been initiated by the fault initiation function.
• If a fault occurs after a protective function has been activated, the protective function indication does not change. The fault is
not saved in the faults history either.
Input phase loss protection selection (Pr.872) (Standard models and IP55
compatible models)
• When Pr.872 is set to "1", Input phase loss (E.ILF) protection is activated if one of three phases is detected to be lost for
1 s continuously.
404 5. PARAMETERS
5.10 (H) Protective function parameter
NOTE
• When several motors are connected, output phase loss cannot be detected even if the wiring to one motor loses phase. 1
• If an input phase is lost while Pr.872 = "1" (with input phase loss protection), Pr.261 Power failure stop selection ≠ "0" (power
failure stop function enabled), the motor decelerates to stop without outputting E.ILF.
• In the case of R/L1, S/L2 phase loss, the input phase loss protection does not operate, and the inverter output is shut off.
• If an input phase loss continues for a long time, the lives of converter section and capacitor of the inverter become shorter. 2
Parameters referred to
Pr.261 Power failure stop selectionpage 610 3
5.10.8 Retry function
This function allows the inverter to reset itself and restart at activation of the protective function (fault indication). The retry
4
generating protective functions can also be selected.
When the automatic restart after instantaneous power failure function is selected (Pr.57 Restart coasting time ≠ 9999), the
restart operation is also performed after a retry operation as well as after an instantaneous power failure. (For restart operation, 5
refer to page 597 and page 604 for selection.)
Pr. Name
Initial
Setting range Description
6
value
65
Retry selection 0 0 to 5 A fault for retry can be selected.
H300
0 No retry operation 7
Set the number of retries at a fault occurrence.
1 to 10
67 Number of retries at fault A fault output is not provided during the retry operation.
0
H301 occurrence Set the number of retries at a fault occurrence. (The setting value minus
101 to 110 100 is the number of retries.) 8
A fault output is provided during the retry operation.
68
Retry waiting time 1s 0.1 to 600 s Set the waiting time from a fault occurrence to a retry.
H302
69 Retry count display
9
0 0 Clear the number of restarts succeeded by retries.
H303 erase
• When retries fail consecutively more than the number of times set in Pr.67, a retry count excess (E.RET) occurs, resulting
in an inverter retries. (Refer to the Retry failure example.)
• Use Pr.68 to set the waiting time from a protective function activation to a retry in the range of 0.1 to 600 s.
• During retry operation, the During retry (Y64) signal is ON. For the Y64 signal, set "64 (positive logic)" or "164 (negative
logic)" in any of Pr.190 to Pr.196 (Output terminal function selection) to assign the function.
5. PARAMETERS
5.10 (H) Protective function parameter
405
• Writing "0" in Pr.69 clears the cumulative count.
Retry success
Pr. 68 × 4
Pr.68 (If it is below 3.1s, 3.1s is set.) Pr.68 Pr.68 Pr.68
Inverter Inverter
output output
frequency frequency
0 0 Time
Time
Retry start Success count + 1 First Second Third
Fault occurrence retry retry retry Retry failure
Fault Fault Fault (E.RET)
Retry success count occurrence occurrence occurrence
Fault signal ON
(ALM)
Y64 ON Y64 ON ON ON
NOTE
• Use the retry function only when the operation can be resumed after resetting a protective function activation. Making a retry
against the protective function, which is activated by an unknown condition, will lead the inverter and motor to be faulty. Identify
and remove the cause of the protective function activation before restarting the operation.
• If the retry function operates during PU operations, the operating conditions (forward/reverse rotation) are stored; and
operations resume after retry reset.
• Only the fault details for the first fault that occurred during retry are stored in the faults history.
• The reset by the retry function does not clear the accumulated data of the electronic thermal O/L relay, regenerative brake
duty, etc. (This is different from power supply reset or reset by RES signal.)
• When the parameter storage device fault (E.PE) is occurring and reading of the retry-function-related parameters is not
possible, retry cannot operated.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
406 5. PARAMETERS
5.10 (H) Protective function parameter
CAUTION 1
• When the retry function is set enabled, stay away from the motor and machine in the case of an output shutoff. The motor
and machine will start suddenly (after the reset time has elapsed) after the shutoff. When the retry function is selected,
apply the supplied CAUTION stickers to easily visible places.
2
Parameters referred to
Pr.57 Restart coasting timepage 597, page 604
2
Minimum frequency 0 Hz 0 to 120 Hz Set the lower limit of the output frequency.
H401
6
18 High speed maximum 120 Hz*1
0 to 590 Hz Set when operating at 120 Hz or higher.
H402 frequency 60 Hz*2
*1
*2
For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
7
Setting the maximum frequency (Pr.1, Pr.18)
• Set Pr.1 Maximum frequency to the upper limit of the output frequency. If the value of the frequency command given is 8
higher than the setting, the output frequency is clamped at the maximum frequency.
• To operate at a frequency higher than the 120 Hz, adjust the upper output frequency limit with Pr.18 High speed
maximum frequency. (When setting a frequency in Pr.18, the Pr.1 setting automatically changes to the frequency set in
9
Pr.18. Also, when setting a frequency in Pr.1, the Pr.18 setting automatically changes to the frequency set in Pr.1.)
Clamped at the
Output frequency maximum frequency
(Hz) 10
Pr.1
Pr.18
0 5, 10V
Clamped at the (4mA) (20mA)
minimum frequency
NOTE
• To operate with a frequency higher than 60 Hz using frequency-setting analog signals, change the Pr.125 (Pr.126) (frequency
setting gain) setting. Simply changing the Pr.1 and Pr.18 settings does not enable the operation at a frequency higher than
60 Hz.
• During Real sensorless vector control, Vector control, and PM sensorless vector control, the upper and lower limits are for the
commanded frequency. The final output frequency that is decided by each control may exceed the lower or upper limits.
• When Pr.15 Jog frequency is equal to or less than Pr.2, the Pr.15 setting takes precedence.
• If a jump frequency that exceeds Pr.1 (Pr.18) is set for the 3-point frequency jump, the maximum frequency setting is the set
frequency. If the jump frequency is less than the setting of Pr.2, the jump frequency is the set frequency. (The set frequency
can be equal to or lower than the frequency lower limit.) When stall prevention is activated to decrease the output frequency,
the output frequency may drop to Pr.2 or below.
5. PARAMETERS
5.10 (H) Protective function parameter
407
CAUTION
• Note that when Pr.2 is set to any value equal to or higher than Pr.13 Starting frequency, simply turning ON the start
signal runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.13 Starting frequencypage 363, page 364
Pr.15 Jog frequencypage 390
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequencypage 482
Frequency jump
Pr.36
frequency jump (Hz)
Set frequency after
Pr.35
Pr.33
Pr.34
Pr.32
Pr.31
Example 2) To jump the frequency to 35 Hz in the range of 30 Hz to 35 Hz, set 35 Hz in Pr.33 and 30 Hz in Pr.34.
Pr.33: 35 Hz
Pr.34: 30 Hz
408 5. PARAMETERS
5.10 (H) Protective function parameter
• When frequency jump ranges overlap, the lower limit of the lower jump range and the upper limit of the upper jump range
are used.
• When the set frequency decreases and falls within the jump range, the upper limit of the jump range is the set frequency.
1
When the set frequency increases and falls within the jump range, the lower limit of the jump range is the set frequency.
2
Set frequency after frequency jump
Pr.36
Pr.35
Pr.32 Pr.32 4
Pr.552 Jump range
Pr.31 Pr.552 Pr.31
Jump range Pr.552
Pr.552
This function monitors the output current and automatically changes the output frequency to prevent the inverter from shutting
off due to overcurrent, overvoltage, etc. It can also limit the stall prevention and fast-response current limit operation during
acceleration/deceleration and power/regenerative driving.
This function is disabled during Real sensorless vector control, Vector control and PM sensorless vector control.
• Stall prevention:
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is automatically
changed to reduce the output current. Also, the second stall prevention function can limit the output frequency range in
which the stall prevention function is enabled.
• Fast-response current limit:
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent.
5. PARAMETERS
5.10 (H) Protective function parameter
409
Initial value
Pr. Name Setting range Description
FM CA
0 Stall prevention operation disabled.
22 Stall prevention
150% Set the current limit at which the stall prevention operation
H500 operation level 0.1 to 400%*1 starts.
156 Stall prevention Enable/disable the stall prevention operation and the fast-
0 0 to 31, 100, 101
H501 operation selection response current limit operation.
Second stall 0 Second stall prevention operation disabled.
48
prevention operation 150% The stall prevention operation level can be changed using the
H600 0.1 to 400%*1
level RT signal.
0 Second stall prevention operation disabled.
Second stall
49 Set the frequency at which the Pr.48 stall prevention
prevention operation 0 Hz 0.01 to 590 Hz
H601 operation starts.
frequency
9999 Pr.48 is enabled when the RT signal is ON.
0 Third stall prevention operation disabled.
114 Third stall prevention
150% The stall prevention operation level can be changed using the
H602 operation level 0.1 to 400%*1 X9 signal.
0 Third stall prevention operation disabled.
115 Third stall prevention
0 Hz Set the frequency at which the stall prevention operation
H603 operation frequency 0.01 to 590 Hz
starts when the X9 signal turns ON.
Stall prevention The stall operation level when running at high speeds above
0 to 200%
23 operation level the rated frequency can be reduced.
9999
H610 compensation factor at
double speed 9999 Stall prevention operation disabled at double speed.
Stall prevention
66 Set the frequency at which the stall operation level reduction
operation reduction 60 Hz 50 Hz 0 to 590 Hz
H611 starts.
starting frequency
148 Stall prevention level at
H620 0 V input
150% 0 to 400%*1
The stall prevention operation level can be changed by the
149 Stall prevention level at analog signal input to the terminal 1 (terminal 4).
H621 10 V input
200% 0 to 400%*1
Output voltage reduction
0 Enable/disable the output
enabled
voltage reduction during stall
Output voltage reduction prevention operation.
1
disabled.
Voltage reduction
154 Output voltage reduction Use this setting when the
selection during stall 1 10
H631 enabled overvoltage protective function
prevention operation
(E.OV[]) is activated during stall
Output voltage reduction prevention operation in an
11
disabled. application with large load
inertia.
Set the OL signal output start time when stall prevention is
157 0 to 25 s
OL signal output timer 0s activated.
M430
9999 No OL signal output.
858 Terminal 4 function When set "4", the stall prevention level can be changed with
0 0, 1, 4, 9999
T040 assignment the signal to the terminal 4.
868 Terminal 1 function When set "4", the stall prevention level can be changed with
0 0 to 6, 9999
T010 assignment the signal to the terminal 1.
*1 The upper limit of stall prevention operation is limited internally to the following.
120% (SLD rating), 150% (LD rating), 220% (ND rating), or 280% (HD rating)
410 5. PARAMETERS
5.10 (H) Protective function parameter
Setting of stall prevention operation level (Pr.22)
• For Pr.22 Stall prevention operation level, set the ratio 1
Output current of the output current to the inverter's rated current at which
Pr.22
the stall prevention operation is activated. Normally, this
Output frequency
should be set at 150% (initial value). 2
• Stall prevention operation stops acceleration (makes
n De
tio ce deceleration) during acceleration, makes deceleration
e ra le
el
Ac
c Constant
speed
ra
tio
n
during constant speed, and stops deceleration during 3
deceleration.
Time
OL • When the stall prevention operation is performed, the
Stall prevention operation example Overload warning (OL) signal is output.
4
NOTE
• A continuous overloaded condition may activate a protective function such as motor overload trip (electronic thermal O/L relay
function) (E.THM).
5
• When Pr.156 has been set to activate the fast response current limit (initial value), the Pr.22 setting should not be higher than
170%. Such setting prevents torque generation.
• When Real sensorless vector control or Vector control is selected using Pr.800 Control method selection, Pr.22 serves as 6
the torque limit level.
For the FR-A820-00250(3.7K) or lower and the FR-A840-00126(3.7K) or lower, the initial value of Pr.22 is 200% instead of
150%.
7
10
5. PARAMETERS
5.10 (H) Protective function parameter
411
Disabling the stall prevention operation and fast-response current limit
according to operating conditions (Pr.156)
• Referring to the following table, enable/disable the stall prevention operation and the fast-response current limit operation,
and also set the operation at OL signal output.
*1 When "operation stop at OL signal output" is selected, the fault output " " (stop due to stall prevention) is displayed, and
operation stops.
*2 The OL signal and E.OLT are not outputted because fast-response current limit and stall prevention are not operating.
*3 Setting values "100, 101" can be individually set for power driving and regenerative driving. The setting value "101" disables the fast-response
current limit during power driving.
NOTE
• When the load is heavy or the acceleration/deceleration time is short, stall prevention operates and acceleration/deceleration
may not be performed according to the time set. Set the Pr.156 and stall prevention operation level to the optimum values.
• For lift applications, make settings to disable the fast-response current limit. Otherwise, the torque may be insufficient, causing
the load to drop.
412 5. PARAMETERS
5.10 (H) Protective function parameter
Adjusting the stall prevention operation signal and output timing (OL
signal, Pr.157) 1
• If the output current exceeds the stall prevention operation level and stall prevention is activated, Overload warning (OL)
signal turns ON for 100 ms or more. The output signal turns OFF when the output current falls to the stall prevention
operation level or less. 2
• Pr.157 OL signal output timer can be used to set whether to output the OL signal immediately, or whether to output it
after a certain time period has elapsed.
• This function also operates during regeneration avoidance operation (overvoltage stall). 3
Pr.157 setting Description
0 (initial value) Output immediately.
0.1 to 25 Output after the set time (s).
4
9999 Not output.
Overload state 5
(OL operation)
OL output signal
120
Stall prevention operation
72
level (%)
36
level (%)
• When operating at the rated motor frequency or higher, acceleration may not be made because the motor current does
not increase. Also, when operating in the high-frequency range, the current flowing to the locked motor becomes less than
the rated output current of the inverter; and even if the motor is stopped, the protective function does not operate (OL). In
a case like this, the stall prevention level can be reduced in the high-frequency range to improve the motor's operating
characteristics. This is useful when operating up to the high speed range, such as when using a centrifuge. Normally, set
Pr.66 Stall prevention operation reduction starting frequency to 60 Hz, and Pr.23 Stall prevention operation level
compensation factor at double speed to 100%.
• Calculation formula for stall prevention operation level
Stall prevention operation level (%) Pr.22 - A Pr.23 - 100
in the high-frequency range = A + B × [ Pr.22 - B ] × [ 100
]
• When Pr.23 = "9999" (initial value),the stall prevention operation level is constant at the Pr.22 level up to 590 Hz.
5. PARAMETERS
5.10 (H) Protective function parameter
413
Setting multiple stall prevention operation levels (Pr.48, Pr.49, Pr.114,
Pr.115)
• Setting Pr.49 Second stall prevention operation frequency = "9999" and turning ON the RT signal enables Pr.48
Second stall prevention operation level.
• For Pr.48 (Pr.114), set the stall prevention operation level that is effective in the output frequency range between 0 Hz and
Pr.49 (Pr.115). However, the operation level is Pr.22 during acceleration.
• Stop-on-contact operation can be used by decreasing the Pr.48 (Pr.114) setting and loosening the reduction torque.
• Pr.114 and Pr.115 are enabled when the X9 signal is ON. To input the X9 signal, set "9" in any of Pr.178 to Pr.189 input
terminal function selection to assign the function to the terminal.
Pr.49 setting Pr.115 setting Operation status
0 (initial value) The second (third) stall prevention function disabled.
0.01 Hz to 590 Hz The second (third) stall prevention function operates according to the frequency.*1
The second stall prevention function operates according to the RT signal.
Setting not
9999*2 available
RT signal ON: stall level set in Pr.48
RT signal OFF: stall level set in Pr.22
*1 For the stall prevention operation level, the smaller of Pr.22 and Pr.48 (Pr.115)has precedence.
*2 When Pr.858 = "4 (analog input to terminal 4 for stall prevention operation level)" or Pr.868 = "4 (analog input to terminal 1 for stall prevention
operation level)", turning ON the RT (X9) signal does not enable the second (third) stall prevention function. (Input to the terminal 4 or terminal 1
is valid.)
operation current
Stall prevention
Output
Output frequency (Hz) Output
During acceleration frequency (Hz)
Output frequency
frequency Set frequency
Pr.49(Pr.115) Pr.49(Pr.115)
Set frequency
NOTE
• When Pr.49 ≠ "9999" (level change according to frequency) and Pr.48 = "0%", the stall prevention function is disabled at or
lower than the frequency set in Pr.49.
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection)may affect the other functions.
Set parameters after confirming the function of each terminal.
• The RT (X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid.
(Refer to page 500.)
414 5. PARAMETERS
5.10 (H) Protective function parameter
• Set Pr.149 Stall prevention level at 0 V input to the current limit level when input voltage is 10 V/5 V (20 mA).
Current limit level (%) Set the current limit level at 10V/5V input
power (input current 20mA) using Pr.149. 1
200%
150%
100% 2
50%
NOTE
• The fast-response current limit cannot be set.
5. PARAMETERS
5.10 (H) Protective function parameter
415
• Set Pr.154 = "10 or 11" when the overvoltage protective function (E.OV[]) is activated during stall prevention operation in
an application with large load inertia. Note that turning OFF the start signal (STF/STR) or varying the frequency command
during stall prevention operation may delay the acceleration/deceleration start.
Pr.154 E.OC[] countermeasure E.OV[] countermeasure
0 Enabled —
1 (initial value) — —
10 Enabled Enabled
11 — Enabled
CAUTION
• Do not set the stall prevention operation current too low.
Doing so will reduce the generated torque.
• Be sure to perform the test operation.
Stall prevention operation during acceleration may extend the acceleration time.
Stall prevention operation during constant-speed operation may cause sudden speed changes.
Stall prevention operation during deceleration may extend the deceleration time.
Parameters referred to
Pr.22 Torque limit levelpage 235
Pr.73 Analog input selectionpage 473
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignmentpage 477
416 5. PARAMETERS
5.10 (H) Protective function parameter
5.10.12 Load characteristics fault detection
This function is used to monitor whether the load is operating in normal condition by storing the speed/torque relationship in 1
the inverter to detect mechanical faults or for maintenance. When the load operating condition deviates from the normal range,
the protective function is activated or the warning is output to protect the inverter or the motor.
Initial value Setting
2
Pr. Name Description
FM CA range
0 Load characteristics measurement is normally completed.
5. PARAMETERS
5.10 (H) Protective function parameter
417
• Use Pr.1486 Load characteristics maximum frequency and Pr.1487 Load characteristics minimum frequency to set
the output frequency range for load fault detection.
f1 f2 f3 f4 f5 Output frequency
(Pr.1487) (Pr.1486)
• Setting Pr.1480 Load characteristics measurement mode = "1" enables automatic measurement of the load
characteristics reference. (Load characteristics measurement mode)
• Use Pr.1486 and Pr.1487 to set the frequency band for the measurement, and set Pr.1480 = "1". After setting, when the
inverter is started, the measurement starts.
• The automatically measured load characteristics reference is written in Pr.1481 to Pr.1485.
• After the measurement is started, read Pr.1480 to display the status of the measurement. If "8" appears in the tens place,
the measurement has not properly completed.
Read value of Pr.1480
Status
Tens place Ones place
— 1 During measurement from the starting point to Point 1
— 2 During measurement from Point 1 to Point 2
— 3 During measurement from Point 2 to Point 3
— 4 During measurement from Point 3 to Point 4
— 5 During measurement from Point 4 to Point 5
— 0 Normal completion
Termination of measurement by an activation of a protective function, Inverter reset, turning ON of MRS
8 1 to 5 signal, turning OFF of the start command, or timeout. (The value in the ones place represents the above-
mentioned measurement point.)
• While measuring automatically, the During load characteristics measurement (Y213) signal is output. For the Y213 signal,
assign the function by setting "213 (positive logic)" or "313 (negative logic)" in any of in any of Pr.190 to Pr.196 (Output
terminal function selection).
418 5. PARAMETERS
5.10 (H) Protective function parameter
• Setting "8888" in Pr.1481 to Pr.1485 enables fine adjustment of load characteristics. When setting Pr.1481 to Pr.1485 =
"8888" during operation, the load status at that point is set in the parameter. (Only when the set frequency is within ±2 Hz
of the frequency of the measurement point, and SU signal is in the ON state.)
1
Example of starting measurement from the stop state
Frequency(Hz)
Load reference 5 recorded 2
f5(Pr.1486) Pr.41
Load reference 4 recorded
f4
Load reference 3 recorded
Pr.41
3
f3 Pr.41
Load reference 2 recorded
4
f2 Pr.41 Operation at the
Load reference set frequency
1 recorded
f1(Pr.1487) Pr.41
STF=ON
Pr.1480=1 Time
5
Measurement start
Pr.1492 Pr.1492 Pr.1492 Pr.1492 Pr.1492
10
Load fault detection setting (Pr.1488 to Pr.1491)
• When the load is deviated from the detection width set in Pr.1488 Upper limit warning detection width, the Upper limit
warning detection (LUP) signal is output. When the load is deviated from the detection width set in Pr.1489 Lower limit
warning detection width, the Lower limit warning detection (LDN) signal is output. At the same time, the Load fault
warning (LDF) appears on the operation panel.
• For the LUP signal, assign the function by setting "211 (positive logic)" or "311 (negative logic)" in any of Pr.190 to Pr.196
(Output terminal function selection). For the LDN signal, assign the function by setting "212 (positive logic)" or "312
(negative logic)" in any of Pr.190 to Pr.196 (Output terminal function selection).
• When the load is deviated from the detection width set in Pr.1490 Upper limit fault detection width, the protective
function (E.LUP) is activated and the inverter output is shut off. When the load is deviated from the detection width set in
Pr.1491 Lower limit fault detection width, the protective function (E.LDN) is activated and the inverter output is shut off.
5. PARAMETERS
5.10 (H) Protective function parameter
419
• To prevent the repetitive on/off operation of the signal due to load fluctuation near the detection range, Pr.1492 Load
status detection signal delay time / load reference measurement waiting time can be used to set the delay time. Even
when a fault is detected out of the detection range once, the warning is not output if the characteristics value returns to the
normal range from a fault state within the output delay time.
Pr.1492
LUP ON
LDN ON ON
E.LDN Output shutoff
LDF warning indication ON ON ON
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Setting example
• The load characteristics are calculated from the parameter setting and the output frequency.
• A setting example is as follows. The reference value is linearly interpolated from the parameter settings. For example, the
reference when the output frequency is 30 Hz is 26%, which is linearly interpolated from values of the reference 2 and the
reference 3.
Reference Frequency Load reference
Load characteristics reference 1 f1: Load characteristics minimum frequency (Pr.1487) = 10 Hz Pr.1481 = 15%
Load characteristics reference 2 f2 = (f5 - f1)/4 + f1 = 22.5 Hz Pr.1482 = 20%
Load characteristics reference 3 f3 = (f5 - f1)/2 + f1 = 35 Hz Pr.1483 = 30%
Load characteristics reference 4 f4 = (f5 - f1) × 3/4 + f1 = 47.5 Hz Pr.1484 = 60%
Load characteristics reference 5 f5: Load characteristics maximum frequency (Pr.1486) = 60 Hz Pr.1485 = 100%
Load(%)
120
100
80
60
40
26
20
0
0 10 20 30 40 50 60 70 Frequency(Hz)
NOTE
• When the load reference is not set for five points, the load characteristics value is determined by linear interpolation of the set
load reference values only. If there is only one load reference setting, the set load reference is used as the load reference all
through the range.
Parameters referred to
Pr.41 Up-to-frequency sensitivitypage 461
Pr.190 to Pr.196 (Output terminal function selection)page 450
420 5. PARAMETERS
5.10 (H) Protective function parameter
5.10.13 Motor overspeeding detection
The Overspeed occurrence (E.OS) is activated when the motor speed exceeds the overspeed detection level. This function 1
prevents the motor from accidentally speeding over the specified value, due to an error in parameter setting, etc.
Motor speed
5
Pr.374
Coast to stop
6
Time 7
ON
ALM
E.OS 8
NOTE
• During the encoder feedback control operation or under Vector control, the motor speed is compared against Pr.374. Under
Real sensorless vector control or PM sensorless vector control, the output frequency is compared against Pr.374. 9
10
5. PARAMETERS
5.10 (H) Protective function parameter
421
5.11 (M) Item and output signal for monitoring
422 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Initial value
Pr. Name
FM CA
Setting range Description
1
0 Monitoring and setting of frequency
37
Speed display 0 Set a number for the speed of machine operated at the
M000 1 to 9998*1 speed (frequency) set in Pr.505.
505 Speed setting 2
60 Hz 50 Hz 1 to 590 Hz Set the reference speed (frequency) for Pr.37.
M001 reference
144 Speed setting 0, 2, 4, 6, 8, 10, 12, 102, Set the number of motor poles for the indication of the
4
M002 switchover 104, 106, 108, 110, 112 motor speed.
Speed setting, running speed
3
0
monitor increments 1 r/min Torque limit setting
Speed setting, running speed increments 0.1%
1
811
D030
Set resolution
switchover
0
monitor increments 0.1 r/min
Speed setting, running speed
4
10
monitor increments 1 r/min Torque limit setting
Speed setting, running speed increments 0.01%
11
monitor increments 0.1 r/min
5
*1 The maximum value of the setting range differs according to the Pr.1 Maximum frequency, Pr.505 Speed setting reference, and it can be
calculated from the following formula.
The maximum value of Pr.37 < 65535 × Pr.505 / Pr.1 setting value (Hz).
The maximum setting value of Pr.37 is 9998 if the result of the above formula exceeds 9998. 6
Indication of motor speed (Pr.37, Pr.144)
• To change the indication to the motor speed, set the number of motor poles (2, 4, 6, 8, 10, or 12) or the number of motor
poles with the addition of 100 (102, 104, 106, 108, 110, or 112) in Pr.144. 7
• Whenever the number of motor poles set in Pr.81 Number of motor poles is changed, the Pr.144 setting changes
automatically in conjunction with Pr.81. However, the Pr.81 setting does not automatically change when the Pr.144 setting
is changed. 8
Example 1) Changing the initial value of Pr.81 to "2" will change the Pr.144 setting from "4" to "2".
Example 2) Changing the Pr.81 setting to "2" while Pr.144 = "104" will change the Pr.144 setting from "104" to "102".
9
Indication of machine speed (Pr.37, Pr.505)
• To change the indication to the machine speed, set a number in Pr.37 which corresponds to the speed of machine
operated at the frequency set in Pr.505. 10
• For example, when Pr.505 is set to 60 Hz and Pr.37 is set to "1000", the operation panel indicates "1000" as the monitor
value of machine speed while the machine is operated at the frequency of 60 Hz. "500" is displayed while the running
frequency is 30 Hz.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
423
Output frequency Set frequency Running speed Frequency setting
Pr.37 setting Pr.144 setting
indication indication indication Parameter setting
0 0.01 Hz 0.01 Hz 1 r/min*1*2 0.01Hz
0 *1*2
2 to 12 0.01 Hz (initial setting) 0.01 Hz (initial setting) 1 r/min (initial 0.01 Hz (initial setting)
(initial value) setting)
102 to 112 1 r/min*1*2 1 r/min*1*2 1 r/min*1*2 1 r/min*1
0 0.01 Hz 0.01 Hz 1 (machine speed*1) 0.01 Hz
1 to 9998 2 to 12 1 (machine speed*1 ) 1 (machine speed ) *1
1 (machine speed ) *1
1 (machine speed*1)
102 to 112 0.01 Hz 0.01 Hz 1 r/min*1*2 0.01 Hz
*1 Motor speed r/min conversion formula: frequency × 120 / number of motor poles (Pr.144)
Machine speed conversion formula: Pr.37 × frequency / Pr.505
The Pr.144 value in the above formula is “Pr.144 - 100" when any of "102 to 112" is set in Pr.144. The value is "4" when Pr.37 = 0 and Pr.144 = 0.
The item set in Pr.505 is consistently a frequency (Hz).
*2 The increment can be changed in Pr.811 from 1 r/min to 0.1 r/min.
NOTE
• The inverter's output frequency is displayed as synchronous speed under V/F control. The displayed value is "actual motor
speed" + "motor slip". When Advanced magnetic flux vector control, Real sensorless vector control or PM sensorless vector
control is selected, the actual motor speed (estimated value by motor slip calculation) is used. When the encoder feedback
control or vector control is selected, the actual motor speed from the encoder is used.
• When Pr.37 = "0" and Pr.144 = "0", the running speed monitor is displayed with the number of motor poles 4. (Displays 1800
r/min at 60 Hz)
• To change the PU main monitor (PU main display), refer to Pr.52.
• If the setting increment is changed to 1 r/min (Pr.811 = "0 or 10") after setting the running speed in 0.1 r/min (Pr.811 = "1 or
11"), the 0.1 r/min increment may be dropped, in order for the rotations per minute resolution to change from 0.1 r/min to 0.3
r/min (when using four poles).
• When using the machine speed display for the parameter unit (FR-PU07), do not change the speed with the up/down key if a
set speed above 65535 is displayed. The set speed may become an undetermined value.
• When the FR-A8ND is connected, the frequency display (setting) is used regardless of the Pr.37, Pr.144 settings.
• When Pr.811 = "1 or 11" with the 0.1 r/min increment, the upper limit is as follows.
Speed command setting range: 6000 r/min for 2 to 10 motor poles, 5900 r/min for 12 motor poles
Running speed monitor such as the operation panel: 6553.5 r/min
Full scale of the running speed motor for analog output (terminals FM, CA and AM): 6000 r/min
CAUTION
• Make sure to set the running speed and the number of motor poles.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Parameters referred to
Pr.1 Maximum frequencypage 407
Pr.22 Torque limit levelpage 235
Pr.52 Operation panel main monitor selectionpage 424
Pr.81 Number of motor polespage 215
Pr.800 Control method selectionpage 215
Pr.811 Set resolution switchoverpage 235
424 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Pr. Name Initial value Setting range Description
774 Operation panel monitor 1 to 3, 5 to 14,
M101 selection 1 17 to 20, 22 to Each of the initial items monitored on the operation panel or 1
775 Operation panel monitor 36, 38 to 46, 50 parameter unit in the monitor mode (output frequency,
M102 selection 2 9999 to 57, 61, 62, output current, and output voltage) can be switched to an
64, 67, 71 to 75, user-designated item.
776
M103
Operation panel monitor
selection 3
87 to 98, 100, 9999: Follows the Pr.52 setting. 2
9999
0 to 3, 5 to 14,
17 to 20, 22 to
992 Operation panel setting dial 0 36, 38 to 46, 50 Select the monitor item displayed on the operation panel at 3
M104 push monitor selection (set frequency) to 57, 61, 62, the time when the setting dial is pressed.
64, 67, 71 to 75,
87 to 98, 100
0 Set "0" to clear the watt-hour meter. 4
Set "10" to monitor the cumulative power in the range of 0 to
170 10
Watt-hour meter clear 9999 9999 kWh via communication.
M020
Set "9999" to monitor the cumulative power in the range of
9999
0 to 65535 kWh via communication. 5
563 Energization time carrying- (0 to 65535) The number of times that the cumulative energization time
0
M021 over times (Read-only) exceeded 65535 hours is displayed (read-only).
0 Value is displayed in 1 increments (an integer).
268 Monitor decimal digits
9999 1 Value is displayed in 0.1 increments. 6
M022 selection
9999 No function
Set the number of digits to move the decimal point of the
171
Operation hour meter clear 9999
0 Set "0" to clear the operation hour meter. 8
The readout is always 9999. Nothing changes when "9999"
M030 9999
is set.
564 Operating time carrying- (0 to 65535) The number of times that the operating time reaches 65535
0
M031 over times (Read-only) hours is displayed. Read-only. 9
Set the availability of negative signals output via terminal
290 Monitor negative output
0 0 to 7 AM, to the operation panel, and through communication.
M044 selection
(Refer to page 433.)
1018
Monitor with sign selection 9999
0 Select the item group to enable the indication of negative 10
M045 9999 signed numbers.
The filter time constant is selectable for monitoring of the
1106 0 to 5 s
Torque monitor filter 9999 torque. A larger setting results in slower response.
M050
9999 0.3 s filter
The filter time constant is selectable for monitoring of the
1107 Running speed monitor 0 to 5 s
9999 running speed. A larger setting results in slower response.
M051 filter
9999 0.08 s filter
The filter time constant is selectable for monitoring of the
1108 Excitation current monitor 0 to 5 s motor excitation current. A larger setting results in slower
9999
M052 filter response.
9999 0.3 s filter
RS-485
Pr.52, MODBUS
communication
Increment Pr.774 to RTU real
Monitor item dedicated -*1 Description
and unit Pr.776, time
monitor
Pr.992 monitor
(hexadecimal)
Output frequency
0.01 Hz*17 1/0/100 H01 40201 ○*21 The inverter output frequency is displayed.
(speed)*18
The inverter output current effective value is
Output current*7*9*18 0.01/0.1 A*6 2/0/100 H02 40202
displayed.
Output voltage*7*18 0.1 V 3/0/100 H03 40203 The inverter output voltage is displayed.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
425
RS-485
Pr.52, MODBUS
communication
Increment Pr.774 to RTU real
Monitor item dedicated -*1 Description
and unit Pr.776, time
monitor
Pr.992 monitor
(hexadecimal)
Fault indication — 0/100 — — Each of the last 8 faults is displayed individually.
Set frequency /
motor speed setting 0.01 Hz*17 5*2 H05 40205 The set frequency is displayed.
426 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
RS-485
Pr.52, MODBUS
communication
Monitor item
Increment
and unit
Pr.774 to
Pr.776,
dedicated
RTU real
time
-*1 Description 1
monitor
Pr.992 monitor
(hexadecimal)
Position command
(lower digits)
1 26 H1A 40226 ○
The position command (decimal) before the 2
Position command electronic gear is set is displayed.*10
1 27 H1B 40227 ○
(upper digits)
Current position
(lower digits)
1 28 H1C 40228 ○ The converted number of the position feedback
pulse into the number of pulses before the
3
Current position
1 29 H1D 40229 ○ electronic gear is set is displayed.*10
(upper digits)
Droop pulse (lower
digits)
1 30 H1E 40230 ○
The droop pulse before the electronic gear is set 4
Droop pulse (upper is displayed.*10
1 31 H1F 40231 ○
digits)
0.01/0.1
The output of a machine connected to the motor
shaft is displayed. It is determined by multiplying
6
Motor output 34 H22 40234
kW*6 the present output torque with the present motor
speed.
The number of pulses fed back from the encoder
in one cycle of the sampling is displayed (kept
7
displayed during a stop). (The output voltage is
displayed when a Vector control option is not
installed.)
Feedback pulse*11 — 35 H23 40235
The sampling time period varies depending on the 8
Pr.369 Number of encoder pulses setting.
1050 or less: 1 second
1051 to 2100: 0.5 seconds
2101 to 4096: 0.25 seconds 9
Torque (positive
polarity for driving
The value equal to the motor torque is displayed.
torque/negative
polarity for
0.1% 36 H24 40236 ○ A positive value for driving torque or a negative
value for regenerative braking torque is displayed.
10
regenerative braking
torque)
Trace status 1 38 H26 40238 The trace status is displayed. (Refer to page 616.)
SSCNET III The SSCNET III communication status between
communication the inverter and the controller is displayed.
1 39 H27 40239
status*11 The output voltage is displayed when the FR-
A8NS is not installed.
PLC function user The user-designated monitor item is displayed
40 H28 40240
monitor 1 using the PLC function.
PLC function user Each value of the following special registers is
Increment 41 H29 40241
monitor 2 displayed.
set in the
SD1216: displayed with the setting value "40"
register
SD1217: displayed with the setting value "41"
PLC function user SD1215
42 H2A 40242 SD1218: displayed with the setting value "42"
monitor 3 (Refer to the PLC Function Programming
Manual.)
The station number of the inverter enabling
Station number (RS-
1 43 H2B 40243 communication via the RS-485 terminals is
485 terminals)
displayed.
The station number of the inverter enabling
Station number (PU) 1 44 H2C 40244
communication via the PU connector is displayed.
The station number of the inverter enabling CC-
Station number (CC-
1 45 H2D 40245 Link communication is displayed. ("0" is displayed
Link)
when the FR-A8NS is not installed.)
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
427
RS-485
Pr.52, MODBUS
communication
Increment Pr.774 to RTU real
Monitor item dedicated -*1 Description
and unit Pr.776, time
monitor
Pr.992 monitor
(hexadecimal)
Power saving effect Increment 50 H32 40250
The energy saving effect monitoring is enabled.
and unit
The item to monitor is selectable from among the
vary
saved power, the average energy saving, and the
Cumulative energy depending
51 H33 40251 energy cost savings. Some of them can be
saving on the
displayed as a percentage according to the
parameter
parameter settings. (Refer to page 444.)
settings.
PID set point 0.1% 52 H34 40252 The set point, measured value, and deviation
PID measured value 0.1% 53 H35 40253 during PID control operation is displayed. (Refer
PID deviation 0.1% 54 H36 40254 ○ to page 579.)
The ON/OFF state of the input terminals on the
Input terminal status — H0F*12 40215*12 inverter is displayed. (Refer to page 431 for
details of indication on the DU.)
55*19
The ON/OFF state of the output terminals on the
Output terminal
status
— H10*13 40216*13 inverter is displayed. (Refer to page 431 for
details of indication on the DU.)
Option input terminal The ON/OFF state of the input terminals on the
— 56 — — digital input option (FR-A8AX) is displayed on the
status*11 DU. (Refer to page 431 for details.)
The ON/OFF state of the output terminals on the
Option output digital output option (FR-A8AY) or the relay output
— 57 — —
terminal status*11 option (FR-A8AR) is displayed on the DU. (Refer
to page 431 for details.)
The ON/OFF state of the input terminals X0 to X15
Option input terminal on the digital input option (FR-A8AX) is monitored
status 1 (for — — H3A*14 40258*14 via RS-485 communication or other
communication)*11 communication when the communication option is
installed.
Option input terminal The ON/OFF state of the input terminal DY on the
status 2 (for digital input option (FR-A8AX) is monitored via
— — H3B*15 40259*15 RS-485 communication or other communication
communication)*11 when the communication option is installed.
The ON/OFF state of the output terminals on the
Option output digital output option (FR-A8AY) or the relay output
terminal status (for — — H3C*16 40260*16 option (FR-A8AR) is monitored via RS-485
communication)*11 communication or other communication when the
communication option is installed.
The accumulated heat value of the motor thermal
Motor thermal load O/L relay is displayed.
0.1% 61 H3D 40261
factor The Motor overload trip (electronic thermal relay
function) (E.THM) occurs at 100%.
The accumulated heat value of the inverter
Inverter thermal load thermal O/L relay is displayed.
0.1% 62 H3E 40262
factor The Inverter overload trip (electronic thermal relay
function) (E.THT) occurs at 100%.
428 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
RS-485
Pr.52, MODBUS
communication
Monitor item
Increment
and unit
Pr.774 to
Pr.776,
dedicated
RTU real
time
-*1 Description 1
monitor
Pr.992 monitor
(hexadecimal)
Cumulative pulse
overflow times
— 74 H4A 40274
The number of the cumulative pulse overflow
○*20 times is displayed (for the FR-A8TP).
2
(control terminal
option)*11
The multi-revolution encoder counter is monitored
Multi-revolution
1 75 H4B 40275
when the FR-A8APS is installed. (The output 3
counter*11 voltage is monitored when the FR-A8APS is not
installed.)
32-bit cumulative
energy (lower 16 1 kWh — H4D 40277 4
bits)
32-bit cumulative The upper or lower 16 bits of the 32-bit cumulative
energy is displayed on each indication.
energy (upper 16 1 kWh — H4E 40278
bits)
It is monitored via RS-485 communication or other
communication with a communication option
5
32-bit cumulative 0.01 kWh/ installed. (To find the monitor codes for each
energy (lower 16 — H4F 40279
0.1 kWh*6 communication option, refer to the Instruction
bits)
32-bit cumulative 0.01 kWh/
Manual of each communication option.)
6
energy (upper 16 — H50 40280
bits) 0.1 kWh*6
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
429
*12 The details of bits for the input terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15 b0
STP
- - - - CS RES MRS JOG RH RM RL RT AU STR STF
(STOP)
*13 The details of bits for the output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15 b0
- - - - - - - - So (SO) ABC2 ABC1 FU OL IPF SU RUN
*14 The details of bits for the option input terminal status 1 are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AX.) Every bit is 0
(OFF) when the option is not installed.
b15 b0
X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X0
*15 The details of bits for the option input terminal status 2 are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AX. "—" denotes an
indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15 b0
- - - - - - - - - - - - - - - DY
*16 The details of bits for the option output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AY/A8AR. "—" denotes
an indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15 b0
- - - - - - RA3 RA2 RA1 Y6 Y5 Y4 Y3 Y2 Y1 Y0
*17 The increment is 1 when Pr.37 = "1 to 9998" or when Pr.144 = "2 to 12" or "102 to 112". (Refer to page 422.)
*18 The monitored values are retained even if an inverter fault occurs. Resetting clears the retained values.
*19 Parameter setting is not available for setting the item as the main monitor item on the LCD operation panel (FR-LU08) or the parameter unit (FR-
PU07). Use the monitor function of the FR-LU08 or the FR-PU07 for setting.
*20 Negative values are not displayed on the operation panel. The values "-1 to -32767" are displayed as "65535 to 32769" on the operation panel.
*21 Setting of Pr.1018 Monitor with sign selection is required. Also, it will be displayed without a minus sign on the operation panel. Confirm the
rotation direction with the [FWD] or [REV] indicator.
the monitor you want to display on the first monitor and hold down for 1 second. To return to the input current
monitor, display the input current monitor and hold down for 1 second.
• Power-on monitor (first monitor) • Second monitor • Third monitor • Fault monitor
With fault
For example, when Pr.52 = "20" (cumulative energization time), the monitor is displayed on the operation panel as shown
below.
• Power-on monitor (first monitor) • Second monitor • Third monitor • Fault monitor
With fault
Output frequency monitor Output current monitor Cumulative energization time monitor
• Pr.774 sets the output frequency monitor, Pr.775 sets the output current monitor, and Pr.776 sets the monitor description
to be displayed at the output voltage monitor position. When Pr.774 to Pr.776 = "9999" (initial value), the Pr.52 setting
value is used.
430 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
NOTE
• On the operation panel (FR-DU08), the "Hz" unit indicator is lit while displaying the output frequency, the "Hz" blinks when 1
displaying the set frequency.
*1 Displays the frequency that is output when the start command is ON. The value considers the maximum/minimum frequency and frequency
jumps. It is different from the frequency setting displayed when Pr.52 = "5". 5
NOTE
• During an error, the output frequency at error occurrence appears.
• During output shutoff by the MRS signal, the values displayed are the same as during a stop. 6
• During offline auto tuning, the tuning state monitor takes priority.
*1 Displays the frequency that is output when the start command is ON. The value considers the maximum/minimum frequency and frequency
10
jumps. It is different from the frequency setting displayed when Pr.992 = "5".
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
431
• On the I/O terminal monitor, the upper LEDs indicate the input terminal status, and the lower LEDs indicate the output
terminal status.
STP (STOP) Input terminal
AU RES STF JOG
RM RH CS
RT MRS STR - Display example -
RL
When signals STF,
RH and RUN are on
Center line is always ON
A
ABC1 RUN OL
SU FU
ABC2 IPF So (SO)
Output terminal
• The decimal point of the first digit on the LED is lit for the input option terminal monitor.
X1 X2 X4 X5 X7 X8
X0 X3 X6 X9
• The decimal point of the second digit on the LED is lit for the output option terminal monitor.
FR-A8AY
Y1 Y2 Y4 Y5
Y0 Y3 Y6
RA1 RA2RA3
FR-A8AR
Decimal point LED of second digit LED is always ON
*1 Energy is measured in the range of 0 to 99999.99 kWh, and displayed in five digits. The cumulative energy up to 999.99 kWh is displayed in 0.01
increments such as "999.99", and that of 1000 kWh or more is displayed in 0.1 increments such as "1000.0".
• The digit of monitored value can be moved to the right by the number of Pr.891 Cumulative power monitor digit shifted
times. For example, when the cumulative energy is 1278.56 kWh and Pr.891 is set to "2", "12.78" is displayed (in 100's of
units) on the operation panel and the communication data is converted into "12".
• When Pr.891 = "0 to 4" and the cumulative energy reaches more than the upper limit of readout, the readout peaks out at
the upper limit, which indicates that moving digit is necessary. When Pr.891 = "9999" and the cumulative energy reaches
more than the upper limit of readout, cumulative value is reset to 0 and the metering restarts.
• Setting "0" in Pr.170 clears the cumulative energy value.
NOTE
• Once "0" is set in Pr.170, the setting of Pr.170 is turned to "9999" or "10" afterwards.
432 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Cumulative energization time / actual operation time monitoring (Pr.171,
Pr.563, Pr.564) 1
• Cumulative energization time monitoring (Pr.52 = "20") accumulates energization time from shipment of the inverter every
hour.
• On the actual operation time monitoring (Pr.52 = "23"), the inverter running time is added up every hour. (Time is not added 2
up during a stop.)
• When the cumulative value exceeds 65535, the meter is reset to 0 and restarts adding up. To check how many times the
cumulative energization time meter has exceeded 65535 h, use Pr.563. To check how many times the actual operation 3
time meter has exceeded 65535 hours, use Pr.564.
• Setting "0" in Pr.171 clears the actual operation time meter. (The cumulative energization time meter cannot be cleared.)
NOTE
4
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
• The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
• Once "0" is set in Pr.171, the setting of Pr.171 is always turned to "9999" afterwards. Setting "9999" does not clear the actual 5
operation time meter.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
433
• Select the item group to enable the indication of negative signed numbers by setting Pr.1018 Monitor with sign selection.
Pr.1018 setting
Monitor item
9999 0
Output frequency — ○ *1
○: Negative numbers displayed with minus sign, —: Negative numbers not displayed (positive only)
*1 Negative numbers are not displayed on the operation panel. Confirm the rotation direction with the [FWD] or [REV] indicator.
NOTE
• When the output via terminal AM (analog voltage output) is set to "Negative numbers indication enabled", the output is within
the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• Parameter unit (FR-PU07) displays only positive values.
Parameters referred to
Pr.30 Regenerative function selection, Pr.70 Special regenerative brake dutypage 689
Pr.37 Speed display, Pr.144 Speed setting switchoverpage 422
Pr.55 Frequency monitoring reference, Pr.56 Current monitoring reference, Pr.866 Torque monitoring referencepage 435
434 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
5.11.3 Monitor display selection for terminals FM/CA and
AM 1
The monitored statuses can be output as the following items: analog voltage (terminal AM), pulse train (terminal FM) for the
FM type inverter, analog current (terminal CA) for the CA type inverter.
2
The signal (monitor item) to be output to terminal FM/CA and terminal AM can be selected.
Initial value
Pr. Name
FM CA
Setting range Description 3
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 36,
54 FM/CA terminal function
46, 50, 52 to 53, 61, Select the item monitored via terminal FM or CA.
M300 selection
1 62, 67, 70, 87 to 90, 4
(output 92, 93, 95, 97, 98
frequency) 1 to 3, 5 to 14, 17, 18,
158 21, 24, 32 to 34, 36,
M301
AM terminal function selection
46, 50, 52 to 54, 61,
Select the item monitored via terminal AM. 5
62, 67, 70, 87 to 98
Set the full-scale value when outputting the
55 Frequency monitoring
60 Hz 50 Hz 0 to 590 Hz frequency monitor value to terminals FM, CA and
M040 reference
AM. 6
0 to 500 A*1 Enter the full-scale value of a meter which
56 Inverter
Current monitoring reference corresponds to the output via terminal FM/CA or
M041 rated current 0 to 3600 A*2 terminal AM to monitor the output current.
866
Enter the full-scale value of a meter which 7
Torque monitoring reference 150% 0 to 400% corresponds to the output via terminal FM/CA or
M042
terminal AM to monitor the motor torque.
Set the availability of negative signals output via
290
M044
Monitor negative output
selection
0 0 to 7 terminal AM, to the operation panel, and through 8
communication. (Refer to page 433.)
Pulse train input Pulse train output
(terminal JOG) (terminal FM)
0 JOG signal*3 FM output*4
9
1 Pulse train input FM output*4
High-speed pulse train
10*4 JOG signal*3 output 10
(50% duty)
High-speed pulse train
11*4 Pulse train input output
291 (50% duty)
Pulse train I/O selection 0
D100 High-speed pulse train
20*4 JOG signal*3 output
(ON width fixed)
High-speed pulse train
21*4 Pulse train input output
(ON width fixed)
High-speed pulse train
output
100*4 Pulse train input (ON width fixed)
Output the pulse train
input without changes.
*1 For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*2 For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
*3 Function assigned to Pr.185 JOG terminal function selection.
*4 Valid only for the FM type inverters.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
435
• Refer to the following table and select the item to be monitored. (Refer to page 425 for the list of monitor items.)
Negative
Increment Pr.54 (FM/CA) Terminal FM, CA, AM
Monitor item (-) Remarks
and unit Pr.158 (AM) setting full-scale value
output
Output frequency 0.01 Hz 1 Pr.55 ○*3
*2 *1 2 Pr.56
Output current 0.01 A/0.1 A
200 V class: 400 V
Output voltage 0.1 V 3
400 V class: 800 V
Frequency setting value 0.01 Hz 5 Pr.55
The value converted
Refer to page 422 for the monitoring of
Motor speed 1 (r/min) 6 with the Pr. 37, Pr.144 ○*3
the operation speed.
value from Pr. 55.
Motor torque 0.1% 7 Pr.866 ○
Converter output 200 V class: 400 V
0.1 V 8
voltage*2 400 V class: 800 V
Regenerative brake Brake duty decided by
0.1% 9
duty*4 Pr.30, Pr.70.
Electronic thermal O/L Electronic thermal O/L
0.1% 10
relay load factor relay (100%)
Output current peak
value 0.01 A/0.1 A*1 11 Pr.56
436 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Negative
Increment Pr.54 (FM/CA) Terminal FM, CA, AM
Monitor item (-) Remarks
and unit Pr.158 (AM) setting full-scale value
output 1
Remote output value 1 0.1% 87 1000%
Remote output value 2 0.1% 88 1000% Refer to page 467 for the analog
remote output.
Remote output value 3
Remote output value 4
0.1%
0.1%
89
90
1000%
1000%
2
PID manipulated amount 0.1% 91*5 100% ○
Second PID set point 0.1% 92 100%
Second PID measured
0.1% 93 100%
3
value
Second PID deviation 0.1% 94*5 100% ○ Refer to page 579 for the PID control.
Second PID measured
value 2
0.1% 95 100% 4
Second PID manipulated
amount
0.1% 96*5 100% ○
*3
inverter or in other instances that cause the output current to fall below the specified value.
Setting of Pr.1018 Monitor with sign selection is required.
7
*4 The setting is available for the standard model.
*5 The setting is available only in Pr.158 (terminal AM).
2400
(55k)
1440
(50k)
Output Current
20 mADC
50Hz 590Hz
(initial value)
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
437
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the current value
(for example, 60 Hz or 120 Hz) at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal
5. Output voltage is proportional to the frequency. (The maximum output voltage is 10 VDC.)
Output voltage
10VDC
60Hz
60Hz *1 590Hz
(initial value)
*2
Setting range of Pr.55
-10VDC
438 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
FM output circuit
Inverter
1
24V
2.2K
2
3.3K FM
20K SD
3
Indicator
1mA full-scale
analog meter
(Digital indicator) 4
1mA 1440 pulses/s(+) (-)
FM FM
(+) (-) T1
Calibration
resistor *1 8VDC
5
SD SD
T2
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr.55 (frequency monitor)
6
Set with Pr.56 (current monitor)
*1 Not needed when the operation panel or the parameter unit is used for calibration.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
7
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, calibrate additionally with
the operation panel or parameter unit.
*2 In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
8
• When Pr.291 Pulse train I/O selection = "10, 11, 20, 21, or 100", this is high-speed pulse train output for open collector
output. A maximum pulse train of 55k pulses/s is outputted.
There are two types of pulse width: "50% duty" and "fixed ON width"; this cannot be adjusted with the calibration parameter 9
C0 (Pr.900) FM/CA terminal calibration.
10
High-speed pulse train output circuit
(example of connection to pulse counter)
Pulse counter
Pull up resistance *3
Inverter
FM
SD
*1 The pulses may weaken due to stray capacitance in the wiring if the wiring is long, and the pulse counter will be unable to recognize the pulses.
Connect the open collector output to the power source with a pull-up resistor if the wiring is too long.
Check the pulse counter specs for the pull-up resistance.
The resistance should be at 80 mA of the load current or less.
• When Pr.291 = "10, or 11", the pulse cycle is 50% duty (ON width and OFF width are the same).
• When Pr.291 = "20, 21, or 100", the pulse ON width is output at a fixed width (approx. 10 μs).
• At the "100" setting, the same pulse train from the pulse train input (terminal JOG) will be outputted. This is used when
running at a synchronized speed with more than one inverter. (Refer to page 386.)
Hi *4 Low
Hi *4 Low
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
439
*1 "HIGH" indicates when the open collector output transistor is OFF.
NOTE
• Terminal JOG input specifications (pulse train input or contact input) can be selected with Pr.291. When changing the setting
value, be careful not to change the terminal JOG input specifications. (Refer to page 386 for pulse train input.)
• Install a meter between terminals FM and SD after changing the Pr.291 setting value. During output the pulse train via terminal
FM (voltage output), be careful that voltage is not added to terminal FM.
• The meter cannot be used for the pulse input in a source logic type.
• If the All parameter clear is performed when the high-speed pulse train output is selected (Pr.291 = "10, 11, 20, 21, or 100"),
the output via terminal FM is changed from high-speed pulse train output to the voltage output because the Pr.291 setting
resets to the initial value "0". To perform the All parameter clear, remove the device connected to terminal FM first.
FM output circuit
3.3kΩ Pr.291
0, 1 Terminal FM
8.2V
10, 11,
20, 21, 100
440 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Terminal FM calibration (C0 (Pr.900))
• The output via terminal FM is set to the pulse output. By setting C0 (Pr.900), the meter connected to the inverter can be 1
calibrated by parameter setting without use of a calibration resistor.
• The pulse train output via terminal FM can be used for digital display on a digital counter. The output is 1440 pulses/s at
full scale. (Refer to page 435 for the full-scale value of each monitor item.) 2
Indicator
1mA full-scale (Digital indicator)
3
analog meter
1mA 1440 pulses/s(+) (-)
FM FM
(+) (-) T1
Calibration
SD
resistor *1 8VDC
SD 4
T2
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr.55 (frequency monitor)
Set with Pr.56 (current monitor) 5
*1 Not needed when the operation panel or the parameter unit is used for calibration.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, perform calibration using
6
the operation panel or parameter unit.
*2 In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
7
• Calibrate the output via terminal FM in the following procedure.
1. Connect an indicator (frequency meter) across terminals FM and SD on the inverter. (Note the polarity. Terminal FM
is positive.) 8
2. When a calibration resistor has already been connected, adjust the resistance to "0" or remove the resistor.
3. Set a monitor item in Pr.54 AM terminal function selection. (Refer to page 435.) 9
When the running frequency or inverter output current is selected on the monitor, set the running frequency or
current value at which the output signal will be 1440 pulses/s, using Pr.55 Frequency monitoring reference or
Pr.56 Current monitoring reference beforehand. Normally, at 1440 pulses/s the meter deflects to full-scale. 10
4. If the meter needle does not point to maximum even at maximum output, calibrate it with C0 (Pr.900).
NOTE
• When outputting an item such as the output current, which cannot reach a 100% value easily by operation, set Pr.54 to "21"
(reference voltage output) and calibrate. A pulse train of 1440 pulses/s are output via terminal FM.
• When Pr.310 Analog meter voltage output selection = "21", the output via terminal AM cannot be calibrated. For the details
of Pr.310, refer to the Instruction Manual of the FR-A8AY.
• The wiring length to terminal FM should be 200 m at maximum.
• The initial value of the calibration parameter C0 (Pr.900) is set to 1 mA full-scale and 1440 pulses/s terminal FM pulse train
output at 60 Hz. The maximum pulse train output of terminal FM is 2400 pulses/s.
• When connecting a frequency meter between terminals FM-SD and monitoring the running frequency, it is necessary to
change Pr.55 to the maximum frequency, since the FM terminal output will be saturated at the initial value when the maximum
frequency reaches 100 Hz or greater.
• Calibration with the calibration parameter C0 (Pr.900) cannot be done when Pr.291 Pulse train I/O selection = "10, 11, 20,
21, or 100" (high-speed pulse train output).
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
441
2. Changing the operation mode
Press to choose the parameter setting mode. (The parameter number read previously appears.)
5. Selecting a parameter
Turn until " " (C0(Pr.900) FM/CA terminal calibration) appears. Press to enable the
parameter setting.
The monitored value of the item (initially the output frequency) selected by Pr.54 FM/CA terminal function
selection will appear.
If stopped, press or to start the inverter operation. (To monitor the output frequency, motor connection
is not required.)
When a monitor that does not require inverter operation is set in Pr.54, calibration is also possible during a stop
status.
7. Scale adjustment
8. Setting completed
Press to confirm the selection. The monitored value and " " blink alternately.
NOTE
• Calibration can also be made for External operation. Set the frequency in the External operation mode, and make calibration
in the above procedure.
• Calibration can be performed during operation.
• For the operation from the parameter unit, refer to the Instruction Manual of the parameter unit.
442 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• Set the output current values (output monitor set with Pr.54) at zero and at the maximum current output via terminal CA
(using the calibration parameters C9 (Pr.930) and C11 (Pr.931). The output current calibrated by the calibration parameter
C0 (Pr.900) is 100% at this time.
1
Output signal value
(ammeter) for minimum analog output
CA
0 to 20mADC
Analog output current
(CA) (C10 (Pr.931))
Analog current
2
(+) (-) CO (Pr.900) 20mA output value for
100% maximum
output signal
5 (C11 (Pr.931)) 3
0
Output signal value 4
Output signal value
for zero analog current output
(C8 (Pr.930))
Analog current output value for zero output signal
(C9 (Pr.930))
5
• Calibrate the output via terminal CA in the following procedure.
1. Connect a 0-20 mADC indicator (frequency meter) across terminals CA and 5 on the inverter. (Note the polarity.
6
Terminal CA is positive.)
2. Set the initial value of the calibration parameter C8 (Pr.930) to C11 (Pr.931). If the meter needle does not indicate 7
zero when the current input is at zero, calibrate the meter using C8 (Pr.930) and C9 (Pr.930).
3. Set a monitor item in Pr.54 FM/CA terminal function selection. (Refer to page 435.)
When the running frequency or inverter output current is selected on the monitor, set the running frequency or 8
current value at which the output signal will be 20 mA, using Pr.55 or Pr.56 beforehand.
4. If the meter needle does not point to maximum even at maximum output, calibrate it with C0 (Pr.900).
9
NOTE
• When outputting an item such as output current, which cannot reach a 100% value easily by operation, set Pr.54 to "21"
(reference voltage output) and calibrate. A current of 20 mADC is output via terminal CA. 10
• When Pr.310 Analog meter voltage output selection = "21", the output via terminal CA cannot be calibrated. For the details
of Pr.310, refer to the Instruction Manual of the FR-A8AY.
• The output via terminal CA is enabled even if C8 (Pr.930) ≥ C10 (Pr.931), C9 (Pr.930) ≥ C11 (Pr.931).
Inverter
AM
10VDC
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
443
1. Connect a 0-10 VDC indicator (frequency meter) across terminal AM and terminal 5 on the inverter. (Note the
polarity. Terminal AM is positive.)
2. Set a monitor item in Pr.158 AM terminal function selection. (Refer to page 435.)
When the running frequency or inverter output current is selected on the monitor, set the running frequency or
current value at which the output signal is 10 V, using Pr.55 or Pr.56 beforehand.
3. If the meter needle does not point to maximum even at maximum output., calibrate it with C1 (Pr.901).
NOTE
• When outputting an item such as the output current, which cannot reach a 100% value easily by operation, set Pr.158 to "21"
(reference voltage output) and calibrate. A voltage of 10 VDC is output via terminal AM.
• When Pr.306 Analog output signal selection = "21", the output via terminal AM cannot be calibrated. For the details of
Pr.306, refer to the Instruction Manual of the FR-A8AY.
• Use Pr.290 Monitor negative output selection to enable negative signals output via terminal AM. The output voltage range
is -10 to +10 VDC. Calibrate the maximum positive value output via terminal AM.
Parameters referred to
Pr.54 FM/CA terminal function selectionpage 435
Pr.55 Frequency monitoring referencepage 435
Pr.56 Current monitoring referencepage 435
Pr.158 AM terminal function selectionpage 435
Pr.290 Monitor negative output selectionpage 435
Pr.291 Pulse train I/O selectionpage 386
444 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Pr. Name Initial value Setting range Description
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
445
Energy saving monitoring list
• The items in the energy saving effect monitoring (items which can be monitored when "50" is set in Pr.52, Pr.54, Pr.158,
Pr.774 to Pr.776, and Pr.992) are listed below.
(The items which can be monitored via terminal FM or CA (Pr.54 setting) and via terminal AM (Pr.158 setting) are limited
to [1 Power saving] and [3 Average power saving].)
446 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• The items in the cumulative energy saving monitoring (items which can be monitored when "51" is set in Pr.52, Pr.774 to
Pr.776, and Pr.992) are listed below.
(The digit of the cumulative energy saving monitored value can be moved to the right according to the setting of Pr.891
1
Cumulative power monitor digit shifted times.)
Energy saving
monitor item
Description and formula
Unit and
increment Pr.895
Parameter setting
Pr.896 Pr.897 Pr.899
2
It is defined as a cumulative energy saving during 0.01 kWh/
Power saving monitoring, determined by multiplying the saved 0.1 kWh
6 — 9999
amount power by the number of inverter operating hours.
Σ ([1 Power saving] × ∆t)
*1*2*3
9999
3
It is defined as a monetary value of the cumulative 0.01/
7 Power cost savings energy saving. — 0 to 500
0.1*1*3
[6 Power saving amount] × Pr.896 setting
It is defined as an estimated annual energy saving.
— 4
0.01 kWh/
Annual power saving [6 Power saving amount] Pr.899
0.1
8 × 24 × 365 × — 9999
amount Operation time during power 100 kWh*1*2*3 0 to
saving accumulation
100% 5
It is defined as a monetary value of annual energy 0.01/
Annual power cost
9 saving. — 0 to 500
savings
[8 Annual power saving amount] × Pr.896 setting 0.1*1*3
*1 For monitoring via communication (RS-485 communication, or other communication using a communication option), the increments are 1 in no 6
units. For example, a value "10.00 kWh" is converted into "10" for communication data.
*2 On the LCD operation panel or the parameter unit, a readout is displayed in units of kilowatt-hours (kW).
*3 The increment differs according to the inverter capacity. (Increment left of a slash for FR-A820-03160(55K) or lower, FR-A840-01800(55K) or
lower. Increment right of a slash for FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher.) 7
NOTE
• The operation panel and the parameter unit have a 5-digit display. This means, for example, that a monitored value up to
999.99 is displayed in 0.01 increments and a monitor value of 1000 or more is displayed in 0.1 increments as "1000.0". The 8
maximum monitored value displayed is "99999".
• The maximum monitored value via communication (RS-485 communication or other communication with communication
option installed) is 65535 when Pr.898 Power saving cumulative monitor clear = "9999". The maximum monitored value on
monitoring in 0.01 increments is "655.35", and that on monitoring in 0.1 increments is "6553.5". 9
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
447
• When the setting of Pr.897 is changed, when the inverter is powered ON, or when the inverter is reset, the averaging is
restarted. The Energy saving average value updated timing (Y92) signal is inverted every time the averaging is restarted.
When Pr.897=4 [Hr] Power
is off
Pr.897
Power saving During stop
instantaneous
value [kW]
Time
0 4 8 12 16 20
Operation start Average Average Last value
Average
Average power 0 in the first Average
saving [kW] measurement Time
Stores Hi/Low when the
power is off and starts.
Y92
0 4 8 12 16 0 4
• On [4 Average power saving rate] monitoring, the average hourly monitored value of [2 Power saving rate]) is displayed
when Pr.895 Power saving rate reference value is set to "0 or 1".
• On [5 Average power cost savings] monitoring, a monetary value of the average hourly energy saving ([3 Average
power saving] × Pr.896 setting) is displayed when the unit price, power cost per per kilowatt (hour), is set in Pr.896 Power
unit cost.
2. Change the setting of Pr.898 to "0" when you want to start measuring the energy saving. The cumulative value is
cleared and the cumulative energy saving meter restarts.
3. Change the setting of Pr.898 to "1" when you want to stop measuring the energy saving. The meter stops and the
cumulative value is fixed.
NOTE
• The cumulative value of energy saving is refreshed every hour. This means that the last cumulative value is displayed at a
restart of the inverter and the cumulative meter restarts if the time elapsed between turning OFF and re-turning ON of the
inverter is shorter than an hour. (In some cases, the cumulative energy value may decrease.)
448 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Estimated input power for the commercial power supply operation
(Pr.892, Pr.893, Pr.894) 1
• Select the pattern of the commercial power supply operation from among four patterns (discharge damper control (fan),
suction damper control (fan), valve control (pump) and commercial power drive), and set it in Pr.894.
• Set the motor capacity (pump capacity) in Pr.893 Energy saving monitor reference (motor capacity). 2
• Refer to the following graph to find the rate of power consumption (%) during commercial power supply operation based
on the selected pattern and the rate of motor rotations per minute with respect to the rated speed (the result of dividing the
present output frequency by Pr.3 Base frequency setting). 3
Commercial power-supply drive
110
100
Discharge side
90 damper control 4
(fan)
Power consumption [%] 80
Valve control
70 (pump)
60 5
50
40 Inlet damper control
(fan)
30 6
20
10
0
0 10 20 30 40 50 60 70 80 90100110 7
Ratio of speed to rating [%]
• The estimated input power (kW) for the commercial power supply operation is calculated from the motor capacity set in
Pr.893, the setting of Pr.892 Load factor, and the rate of power consumption using the following formula. 8
Estimated consumed power during Consumed power (%) Pr.892 (%)
commercial power supply operation (kW) = Pr.893 (kW) × 100
×
100
9
NOTE
• If the output frequency rises to the setting of Pr.3 Base frequency or higher, it stays at a constant value because the rotations
per minute cannot rise higher than the power supply frequency during commercial power supply operation. 10
2. Calculate the operation days per year (days/year) using the following formula: Average operation days per month ×
12 (months).
3. Calculate the annual operation time (h/year) from values determined in Step 1 and Step 2, using the following
formula.
Annual operation time (h/year) = average time (h/day) × number of operation days (days/year)
4. Calculate the operation time rate using the following formula, and set it in Pr.899.
Annual operation time (h/year)
Operation time rate (%) = × 100(%)
24 (h/day) × 365 (days/year)
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
449
NOTE
• Setting example for operation time rate: In the case where the average operation time per day is about 21 hours and the
average operation days per month is 16 days.
Annual operation time = 21 (h/day) × 16 (days/month) × 12 (months) = 4032 (h/year)
4032 (h/year)
Operation time rate (%) = × 100(%) = 46.03%
24 (h/day) × 365 (days/year)
• Calculate the annual energy saving from the value of [3 Average power saving] cumulated according to the setting of
Pr.899 Operation time rate (estimated value).
• When the power cost per hour is set in Pr.896 Power unit cost, the annual energy cost savings can be monitored.
The annual energy cost savings is determined by calculation using the following formula.
Annual power cost saving = annual power saving amount (kWh/year) × Pr.896
NOTE
• During regenerative driving, substitute the output power during the commercial power supply operation for the saved power
(therefore, input power = 0).
Parameters referred to
Pr.3 Base frequencypage 673
Pr.52 Operation panel main monitor selectionpage 424
Pr.54 FM/CA terminal function selectionpage 435
Pr.158 AM terminal function selectionpage 435
450 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Initial
Pr. Name Signal name Setting range
value 1
190 RUN terminal
0 RUN (Inverter running)
M400 function selection
191 SU terminal function
M401 selection
1 SU (Up to frequency) 0 to 8, 10 to 20, 22, 25 to 28, 30 to 36, 38 to 57,
60, 61, 63, 64, 67, 68, 70, 79, 80, 84, 85, 90 to 2
For open IPF (Instantaneous power
2*1 99, 100 to 108, 110 to 116, 120, 122, 125 to
192 IPF terminal function collector failure/undervoltage) 128, 130 to 136, 138 to 157, 160, 161, 163,
M402 selection output
9999*2 No function 164, 167, 168, 170, 179, 180, 184, 185, 190 to
193 OL terminal function
terminal
199, 200 to 208, 211 to 213, 300 to 308, 311 to 3
3 OL (Overload warning) 313, 9999
M403 selection
194 FU terminal function FU (Output frequency
4
M404
195
selection
ABC1 terminal
detection)
0 to 8, 10 to 20, 22, 25 to 28, 30 to 36, 38 to 57,
4
99 ALM (Fault)
M405 function selection 60, 61, 63, 64, 67, 68, 70, 79, 80, 84, 85, 90, 91,
For relay 94 to 99, 100 to 108, 110 to 116, 120, 122, 125
Initial
Pr. Name Setting range Description
value
289 Inverter output terminal 5 to 50 ms Set the time delay for the output terminal response.
9999
M431 filter 9999 No filtering of the output terminal.
*1 The initial value is for standard models and IP55 compatible models.
*2 The initial value is for separated converter types.
*3 The setting is available when the PLC function is enabled or when a compatible plug-in option is installed.
*4 The setting is available for the FR-A800-GF.
Setting Refer
Signal Related
Positive Negative Function Operation to
name parameter
logic logic page
Outputted during operation when the
0 100 RUN Inverter running inverter output frequency reaches Pr.13 — 456
Starting frequency or higher.
Outputted when the output frequency
1 101 SU Up to frequency *1 reaches the set frequency.
Pr.41 461
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
451
Setting Refer
Signal Related
Positive Negative Function Operation to
name parameter
logic logic page
452 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Setting Refer
Signal Related
Positive Negative Function Operation to
logic logic
name parameter
page 1
Forward rotation output
(output for a Vector control Outputted while a motor rotates in forward
30 130 Y30 459
direction.
compatible option)*4
Reverse rotation output
2
(output for a Vector control Outputted while a motor rotates in reverse
31 131 Y31 — 459
direction.
compatible option)*4
Regenerative status output
(output for a Vector control
Outputted while the motor is in a 3
32 132 Y32 regenerative braking state under Vector 459
compatible option)*4 control.
Outputted while pre-excitation is enabled or
33 133 RY2 Operation ready 2
during normal operation under Real
— 456 4
sensorless vector control, Vector control, or
PM sensorless vector control.
Outputted when the output frequency drops
34 134 LS Low speed detection
to the Pr.865 setting or lower.
Pr.865 461
5
Outputted when the motor torque is higher
35 135 TU Torque detection Pr.864 465
than the Pr.864 setting.
Outputted when the number of droop pulses
36 136 Y36 In-position
drops below the setting.
Pr.426 311
6
Outputted when the droop pulse is within the
in-position width and the position command
38 138 MEND Travel completed Pr.426 311
operation is completed or not performing
home position return. 7
Outputted when tuning at start-up is
39 139 Y39 Start time tuning completion Pr.95, Pr.574 527
completed.
Pr.1020 to
40 140 Y40 Trace status Outputted during trace operation.
Pr.1047
616
8
41 141 FB Speed detection Outputted when the actual motor rotations
Pr.42 to Pr.50,
42 142 FB2 Second speed detection per minute (estimate) reaches the setting of 461
Pr.116
Pr.42, Pr.50, or Pr.116.
43 143 FB3 Third speed detection
Outputted while the Forward rotation
9
command signal or Reverse rotation
command signal is ON. Outputted during
deceleration even while the Forward rotation
command signal or Reverse rotation 10
command signal is OFF
(except while pre-excitation is enabled (the
44 144 RUN2 Inverter running 2 LX signal is ON)). — 456
Also outputted while the Orientation
command (X22) signal is ON. Outputted
while the servo-lock function is working (the
LX signal is ON) in the position control
mode. (The signal output stops when the
servo-lock function stops (the LX signal is
OFF).)
Inverter running and start Outputted while the inverter is running or
45 145 RUN3 — 456
command is ON while the start command signal is ON.
Outputted when the power-failure
During deceleration at deceleration function is activated.
46 146 Y46 Pr.261 to Pr.266 610
occurrence of power failure (The signal output is retained until the
function stops.)
Pr.127 to Pr.134,
47 147 PID During PID control activated Outputted during the PID control operation. 570
Pr.575 to Pr.577
Outputted when the absolute deviation value Pr.127 to Pr.134,
48 148 Y48 PID deviation limit 570
exceeds the limit value. Pr.553, Pr.554
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
453
Setting Refer
Signal Related
Positive Negative Function Operation to
name parameter
logic logic page
49 149 Y49 During pre-charge operation
Outputted while the pre-charge function is
During second pre-charge
50 150 Y50 working.
operation
Pr.127 to Pr.134,
51 151 Y51 Pre-charge time over Outputted when the time period while the
Pr.241, Pr.553,
pre-charge function is working reaches the
52 152 Y52 Second pre-charge time over Pr.554, Pr.575 to 587
time limit set in Pr.764 or Pr.769. Pr.577, Pr.753 to
53 153 Y53 Pre-charge level over Outputted when the value higher than the Pr.769, C42, C45
detection level set in Pr.763 or Pr.768 is
54 154 Y54 Second pre-charge level over measured until the pre-charge function
stops during pre-charge operation.
Motor temperature detection Outputted when the temperature of the
55 155 Y55 thermistor-equipped vector control motor Pr.750 —
(for FR-A8AZ)*4 (SF-V5RU[]T/A) exceeds the detection level.
Outputted while the Home position return
56 156 ZA Home position return failure — 288
uncompleted warning is output.
During PM sensorless vector Outputted while the operation is performed Pr.71 to Pr.80,
57 157 IPM 224
control under PM sensorless vector control. Pr.998
Outputted when the current position
Pr.1294 to
60 160 FP Position detection level exceeds the position detection judgment 311
Pr.1297
value (set in Pr.1294 and Pr.1295).
During position command Outputted during the position command
61 161 PBSY
operation operation.
— 288
Home position return Outputted when the home position return
63 163 ZP
completed operation is completed.
64 164 Y64 During retry Outputted during retry operation. Pr.65 to Pr.69 405
Outputted when the inverter power output is
shut off due to power failure or undervoltage
67 167 Y67 Power failed*3 or when the power failure time deceleration-
Pr.261 to Pr.266 610
to-stop function is activated.
Outputted while the inverter operated with a
24 V external power supply
68 168 EV 24 V power supplied from an external — 78
operation
source.
Outputted while PID output suspension Pr.127 to Pr.134,
70 170 SLEEP PID output interruption 570
function is activated. Pr.575 to Pr.577
Outputted in pulses every time the
Pulse train output of output
79 179 Y79 cumulative value of energy outputted from Pr.799 470
power
the inverter reaches the Pr.799setting.
Outputted while the safety stop function is
80 180 SAFE Safety monitor output — 80
activated.
Outputted when the servo-lock function is
Position control preparation Pr.419, Pr.428 to
84 184 RDY working (the LX signal turns ON) and the 304
ready Pr.430
inverter is ready to operate.
Outputted during power failure or
85 185 Y85 DC current feeding*5 undervoltage of the AC power supply.
Pr.30 689
Control circuit capacitor life Outputted when the control circuit capacitor
86 186 Y86
(for Pr.313 to Pr.322)*6 approaches the end of its life.
Main circuit capacitor life Outputted when the main circuit capacitor
87 187 Y87
(for Pr.313 to Pr.322)*5*6 approaches the end of its life.
Cooling fan life Outputted when the cooling fan approaches
88 188 Y88
(for Pr.313 to Pr.322)*6 the end of its life. Pr.255 to Pr.259 341
Inrush current limit circuit life Outputted when the inrush current limit
89 189 Y89
(for Pr.313 to Pr.322)*5*6 circuit approaches the end of its life.
Outputted when any of the control circuit
capacitor, main circuit capacitor, inrush
90 190 Y90 Life alarm
current limit circuit, or the cooling fan
approaches the end of its life.
Fault output 3 (Power-OFF Outputted when the Fault occurs due to an
91 191 Y91 — 460
signal) inverter circuit fault or connection fault.
Switches between ON and OFF every time
the average energy saving is updated during Pr.52, Pr.54,
Energy saving average value
92 192 Y92 the energy saving monitoring. This signal Pr.158, Pr.891 to 444
updated timing
cannot be assigned to any of the relay output Pr.899
terminal (Pr.195, Pr.196, Pr.320 to Pr.322).
454 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Setting Refer
Signal Related
Positive Negative Function Operation to
logic logic
name parameter
page 1
Outputted in pulses for transmission of the
average current value and the maintenance
93 193 Y93 Current average monitor timer value. This signal cannot be assigned Pr.555 to Pr.557 346
to any of the relay output terminal (Pr.195, 2
Pr.196, Pr.320 to Pr.322).
Outputted when the inverter's protective
function is activated to stop the power output
94 194 ALM2 Fault output 2 (when the Fault occurs). The signal output — 460 3
continues during the inverter reset and stops
after the inverter reset finishes. *7
Outputted when the value of Pr.503 reaches
95 195 Y95 Maintenance timer signal
the Pr.504 setting or higher.
Pr.503, Pr.504 345 4
Outputted via a terminal by setting a proper
96 196 REM Remote output Pr.495 to Pr.497 466
number in a relative parameter.
The ER signal output follows the ALM signal
output when Pr.875 = "0 (initial value)".
5
When Pr.875 = "1" and when any of E.OHT,
E.THM, or E.PTC occurs, the inverter
97 197 ER Alarm output 2 Pr.875 401
decelerates the motor to a stop at a time of
the ER signal ON. When any of other faults 6
occurs, the ER signal outputs when the
inverter output stops.
Outputted when an Alarm (Fan alarm) or a 402,
98 198 LF Alarm
communication error occurs.
Pr.121, Pr.244
630 7
Outputted when the inverter's protective
function is activated to stop the power output
99 199 ALM Fault — 460
(when the Fault occurs). The signal output
stops when the inverter reset starts. 8
Outputted when the input value is lower than
200 300 FDN2 Second PID lower limit the lower limit set for the second PID control
operation.
Outputted when the input value is higher 9
201 301 FUP2 Second PID upper limit than the upper limit set for the second PID
Pr.753 to Pr.758
control operation.
Second PID forward/reverse Outputted during forward rotation operation
202 302 RL2
rotation output in the second PID control operation.
570
10
Second During PID control Outputted during the second PID control
203 303 PID2
activated operation.
Pr.753 to Pr.758,
SLEEP During second PID output Outputted while the second PID output
204 304 Pr.1147 to
2 shutoff suspension function is activated.
Pr.1149
Outputted when the absolute deviation value
Pr.753 to Pr.758,
205 305 Y205 Second PID deviation limit exceeds the limit value during the second
Pr.1145, Pr.1146
PID control operation.
Cooling fan operation Output when the cooling fan operation is
206 306 Y206 Pr.244 402
command commanded.
Outputted when the temperature of the
207 307 Y207 Control circuit temperature control circuit board reaches the detection Pr.663 471
level or higher.
208 308 PS PU stopped Output while the PU is stopped. Pr.75 320
Output when the load fault upper limit
211 311 LUP Upper limit warning detection
warning is detected.
Output when the load fault lower limit Pr.1480 to
212 312 LDN Lower limit warning detection 417
warning is detected. Pr.1492
During load characteristics Output during measurement of the load
213 313 Y213
measurement characteristics.
9999 — (No function) — — —
*1 Note that changing the frequency setting with an analog signal or the setting dial on the operation panel (FR-DU08) may cause the turning ON
and OFF of Up to frequency (SU) signal depending on its changing speed and the timing of the speed change determined by the acceleration/
deceleration time setting. (The signal state changing does not occur when the acceleration/deceleration time is set to 0 seconds.)
*2 This signal is available only for the standard model.
*3 This signal cannot be assigned to any of the output terminals for plug-in options (FR-A8AY and FR-A8AR).
*4 This signal is available when the compatible plug-in option or control terminal option is installed.
*5 This signal is available for the standard model or the IP55 compatible model.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
455
*6 This signal is available for the FR-A800-GF, when the PLC function is enabled, or when an option (FR-A8AY, FR-A8AR, FR-A8NC, or FR-A8NCE)
is installed. Use Pr.313 to Pr.322 to assign the function to the terminal. For the information of the availability of these parameters for each option,
refer to the Instruction Manual of the option.
*7 On restarting the inverter, the Fault output 2 (ALM2) signal turns OFF at the time the inverter power turns OFF.
NOTE
• One function can be assigned to more than one terminal.
• The function works during the terminal conducts when the parameter setting is any of "0 to 99, 200 to 299", and the function
works during the terminal does not conduct when the setting is "100 to 199, 300 to 399".
• When Pr.76 Fault code output selection = "1", the outputs of terminals SU, IPF, OL, and FU are used only for outputting the
fault code according to the Pr.76 setting. (When the inverter's protective function is activated, the signal for the fault code is
output.)
• The output of terminal RUN and the outputs of the relay output terminals are not affected by the Pr.76 setting.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• Do not assign the signal to terminals A1, B1, and C1 or terminals A2, B2, and C2 which frequently changes its state between
ON and OFF. Otherwise, the life of the relay contact may be shortened.
Time
RUN ON OFF
Pr.289 = 9999
ON OFF
RUN
Pr.289 ≠ 9999
Pr.289 Pr.289
NOTE
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output when the set
time of (Pr.157 + Pr.289) elapses.
• The signal output for the PLC function (see page 614) and for the fault code output (see page 467) are not affected by the
Pr.289 setting (not filtered for responsivity).
Inverter operation ready signals (RY, RY2 signals) and inverter running
signals (RUN, RUN2, RUN3 signals)
Operation under V/F control and Advanced magnetic flux vector control
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the inverter running signals
(RUN, RUN2 signals) turn ON. The signals are OFF while the inverter is stopped or during the DC injection brake operation.
456 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running or while the start command
signal is ON (When the start command signal is ON, the RUN3 signal is ON even while the inverter's protective function
is activated or while the MRS signal is ON.) The RUN3 signal is ON even during the DC injection brake operation, and the
1
signal is OFF when the inverter stops.
Power
supply
ON OFF 2
ON OFF
STF
ON
RH
3
Output frequency
DC injection brake
operation point
DC injection
brake
4
Pr. 13 operation
Reset Time
processing
5
ON OFF
RY
RUN ON OFF
(RUN2)
ON OFF
6
RUN3
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
Inverter output
Automatic restart after
instantaneous power failure
7
Start signal Start signal Start signal During DC
shutoff*2
Output OFF ON ON injection During coasting Inverter
signal (inverter (inverter (inverter brake running
Start Start Start Start
stopped) stopped) running) operation
signal ON signal OFF signal ON signal OFF
after
restart
8
RY*3 ON ON ON ON OFF ON*1 ON
RY2 OFF OFF OFF OFF OFF OFF OFF
RUN OFF OFF ON OFF OFF OFF ON 9
RUN2 OFF OFF ON OFF OFF OFF ON
RUN3 OFF ON ON ON ON OFF ON OFF ON
Operation under Real sensorless vector control, Vector control, and PM sensorless vector
control
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the Inverter running (RUN)
turns ON. The signal is OFF during an inverter stop, during the DC injection brake operation, during tuning at start-up, or
during pre-excitation.
• The Inverter running 2 (RUN2) signal is ON while the inverter is running or while the start command signal is ON. (When
the inverter's protective function is activated or the MRS signal is ON, the RUN2 signal turns OFF.)
• The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running or while the start command
signal is ON.
• The RUN2 and RUN3 signals are also ON when the start command signal is ON or during pre-excitation with the speed
command value 0. (However, the RUN2 signal is OFF during pre-excitation with the LX signal ON.)
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
457
• The Operation ready 2 (RY2) signal turns ON when the pre-excitation starts. The signal is ON during pre-excitation even
while the inverter stops its output. The signal is OFF during the inverter output shutoff.
Power
supply ON OFF
STF ON OFF
RH ON
MRS ON
Output frequency
Pre-excitation
(zero speed control)
Pr. 13
Reset
Time
processing
ON OFF
RY
ON OFF
RY2
ON OFF
RUN
ON OFF
RUN2
ON OFF
RUN3
NOTE
• When pre-excitation works with thePre-excitation/servo ON (LX) signal ON, the RY2 signal turns ON after 100 ms (500 ms for
FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher) from the time the LX signal turns ON. (When online auto
tuning at start-up is selected (Pr.95 = "1"), the time the signal turns ON is delayed by the tuning time.)
LX ON
100(500)ms
RY2 ON
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
During DC Automatic restart after
Inverter output
Start LX signal injection instantaneous power failure
signal
Start signal Start
ON brake shutoff*5
Output ON*1(during signal ON During coasting Inverter
OFF (during operation
signal pre- (inverter Start Start Start running
(inverter pre- (during Start
excitation) running) signal signal signal after
stopped) excitation) pre- signal ON
OFF ON OFF restart
excitation)
RY*6 ON ON ON ON ON OFF ON*2 ON
RY2 OFF ON ON ON*3 ON OFF OFF OFF
RUN OFF OFF ON *4 OFF OFF OFF ON
OFF
RUN2 OFF ON ON OFF*4 OFF OFF OFF ON
RUN3 OFF ON ON ON ON ON OFF ON OFF ON
*1 When the start signal is ON and the frequency command is 0 Hz, such state is designated as "during pre-excitation".
*2 The signal is OFF during power failure or undervoltage.
*3 The RY2 signal turns ON after 100 ms (500 ms for FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher) from the time the LX signal
turns ON.
*4 The signal is ON while the servo-lock function is ON (the LX signal is ON) in the position control mode.
*5 This means the state during a fault occurrence or while the MRS signal is ON, etc.
*6 The signal is OFF while power is not supplied to the main circuit.
458 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• To use the RY, RY2, RUN, RUN2, of RUN3 signal, set the corresponding number selected from the following table in any
of Pr.190 to Pr.196 (Output terminal function selection) to assign the function to an output terminal.
1
Pr.190 to Pr.196 settings
Output signal
Positive logic Negative logic
RY 11 111
RY2 33 133 2
RUN 0 100
RUN2 44 144
RUN3 45 145
3
NOTE
• The RUN signal (positive logic) is initially assigned to the terminal RUN.
4
Forward rotation output (Y30) signal and Reverse rotation output (Y31)
signal 5
• Under Vector control, the Forward rotation output (Y30) signal or the Reverse rotation output (Y31) signal is output
according to the actual rotation direction of the motor.
• During pre-excitation (zero-speed or servo-lock function ON) in the speed or torque control mode, the Y30 signal and the 6
Y31 signal are OFF. During the servo-lock function ON in the position control mode, however, the Y30 signal or the Y31
signal is ON according to the actual rotation direction of the motor, as well as during normal operation.
• To use the Y30 signal, set "30 (positive logic) or 130 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function 7
selection) to assign the function to the output terminal.
• To use the Y31 signal, set "31 (positive logic) or 131 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal. 8
Pre-excitation
9
Actual Forward
motor rotation
Time
speed Reverse
rotation
ON
10
Y30
Y31 ON
NOTE
• The Y32 signal is always OFF under V/F control, Advanced magnetic flux vector control, Real sensorless vector control, and
PM sensorless vector control.
• If the motor is rotated by an external force while the inverter is stopped, the Y30 signal and the Y31 signal keep OFF state.
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
459
• To use the Y32 signal, set "32 (positive logic) or 132 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
Driving
+
Time
Y32 ON OFF ON
NOTE
• The Y32 signal is always OFF under V/F control, Advanced magnetic flux vector control, Real sensorless vector control, and
PM sensorless vector control.
(trip)
Time
ALM ON OFF
ALM2 ON OFF
RES ON OFF
Reset processing
(about 1s)
Reset ON
NOTE
• For the details of the inverter faults, refer to page 745.
460 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• The following is the list of faults that output the Y91 signal. (For the details of faults, refer to page 745.)
7
5.11.7 Output frequency detection
If the inverter output frequency which reaches a specific value is detected, the relative signal is output.
8
Initial value Setting
Pr. Name Description
FM CA range
41 Up-to-frequency
M441 sensitivity
10% 0 to 100% Set the level where the SU signal turns ON.
9
42 Output frequency
6 Hz 0 to 590 Hz Set the frequency at which the FU (or FB) signal turns ON.
M442 detection
Output frequency Set the frequency at which the FU (or FB) signal turns ON only
43
M443
detection for reverse 9999
0 to 590 Hz
while the motor rotates in reverse direction. 10
rotation 9999 The frequency same as the Pr.42 setting is set.
50 Second output
30 Hz 0 to 590 Hz Set the frequency at which the FU2 (or FB2) signal turns ON.
M444 frequency detection
116 Third output frequency
60 Hz 50 Hz 0 to 590 Hz Set the frequency at which the FU3 (or FB3) signal turns ON.
M445 detection
865
Low speed detection 1.5 Hz 0 to 590 Hz Set the frequency at which the LS signal turns ON.
M446
870 Speed detection
0 Hz 0 to 5 Hz Set the hysteresis width for the detected frequency.
M400 hysteresis
Setting the notification zone of the output frequency reaching the set
point (SU signal, Pr.41)
• The Up to frequency (SU) signal is output when the output frequency reaches the set frequency.
• Set the value in the range of 1 to 100% in Pr.41 to determine tolerance for the set frequency (considered as 100% point).
• It may be useful to use this signal to start operating related equipment after checking that the set frequency has been
reached.
Set frequency Adjustment
Output frequency
range Pr.41
(Hz)
Time
OFF ON OFF
SU
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
461
Output frequency detection (FU, FU2, FU3 signals, FB, FB2, FB3 signals,
Pr.42, Pr.43, Pr.50, Pr.116)
• The Output frequency detection (FU) signal and the Speed detection (FB) signal are output when the output frequency
reaches or exceeds the Pr.42 setting.
• The FU, FU2, and FU3 signals are useful for applying or releasing electromagnetic brake, etc.
• The FU, FU2, and FU3 signal is output when the output frequency (frequency command) reaches the set frequency. On
the other hand, the FB, FB2, and FB3 signal is output when the detected actual speed (estimated speed under Real
sensorless vector control, or feedback value under Vector control) of the motor reaches the set frequency. The FU signal
and the FB signal are output at the same manner under V/F control or Advanced magnetic flux vector control or during the
encoder feedback control operation.
• The frequency detection dedicated to motor rotation in reverse direction is enabled by setting the frequency in Pr.43. This
setting is useful when the timing of the electromagnetic braking during forward rotation operation (for example, during lifting
up in the lifts operation) is different from that during reverse rotation operation (lifting down).
• When Pr.43 ≠ "9999", the Pr.42 setting is for the forward rotation operation and the Pr.43 setting is for the reverse rotation
operation.
• When a different detection point of the frequency is required, Pr.50 and Pr.116 are available. The FU2 (or FB2) signal can
be set to be output when the output frequency reaches the Pr.50 setting or higher, and the FU3 (or FB3) signal can be set
to be output when the output frequency reaches the Pr.116 setting or higher.
Forward
rotation
Output frequency
Pr.116
Pr.50
Pr.42
Pr.43 Time
Pr.50
(Hz)
Pr.116
Output Reverse
signal rotation
FU/FB OFF ON OFF ON OFF
• To use each signal, set the corresponding number selected from the following table in any of Pr.190 to Pr.196 (Output
terminal function selection) to assign the function to an output terminal.
Pr.190 to Pr.196 settings Related
Output signal
Positive logic Negative logic Parameter
FU 4 104
42, 43
FB 41 141
FU2 5 105
50
FB2 42 142
FU3 6 106
116
FB3 43 143
462 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• To use the LS signal, set "34 (positive logic) or 134 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
1
Output frequency
Pr.865
2
(Hz)
Time
LS ON OFF ON
3
Speed detection hysteresis (Pr.870)
Setting the hysteresis width for the detected frequency prevents chattering of the Speed detection (FB) signal. When an output
frequency fluctuates, the following signals may chatter (turns ON and OFF repeatedly). 4
• Up to frequency (SU) signal
• Speed detection (FB, FB2, FB3) signals
• Low speed detection (LS) signal 5
Setting hysteresis to the detected frequency prevents chattering of these signals.
Output frequency
(Hz)
6
Pr.870
SU output level
Pr.870
Output
frequency
(Hz) Set frequency
Pr.41
7
Pr.42 Pr.870
Pr.870 SU output level
Pr.870
8
Time
ON SU signal ON ON
FB
ON ON ON 9
Example of the speed detection (FB) signal Example of the up to frequency (SU) signal
NOTE
• In the initial setting, the FU signal is assigned to terminal FU, and the SU signal is assigned to terminal SU. 10
• All signals shown in the following table are OFF during the DC injection brake operation, during the pre-excitation (zero speed
control or servo lock) operation, and during tuning at start-up.
• The reference frequency in comparison with the set frequency differs depending on the control method.
Reference frequency
Control method or function
FU, FU2, FU3 FB, FB2, FB3, SU, LS
V/F control Output frequency Output frequency
Advanced magnetic flux vector Output frequency before the slip Output frequency before the slip
control compensation compensation
Estimated frequency (actual motor
Real sensorless vector control Frequency command value
speed)
Frequency converted from actual Frequency converted from actual motor
Encoder feedback control
motor speed speed
Frequency converted from actual motor
Vector control Frequency command value
speed
Estimated frequency (actual motor
PM sensorless vector control Frequency command value
speed)
• Setting a higher value in Pr.870 causes a lower responsivity of the signals for frequency detection (SU, FB, FB2, FB3, and LS
signals).
• The logic (ON/OFF switching) of the LS signal is the reverse of that of the FB signal.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.874 OLT level settingpage 235
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
463
5.11.8 Output current detection function
If the inverter output current which reaches a specific value is detected, the relative signal is output via an output terminal.
Initial
Pr. Name Setting range Description
value
150 Output current detection Set the level to detect the output current. Consider the value of
150% 0 to 400%
M460 level the rated inverter current as 100%.
Set the timing to detect the output current. Enter the delay time
151 Output current detection between the time when the output current reaches the set
0s 0 to 10 s
M461 signal delay time current or higher and the time when the Output current
detection (Y12) signal is output.
152 Set the level to detect the zero current. Consider the value of
Zero current detection level 5% 0 to 400%
M462 the inverter rated current as 100%.
Set the time from the time when the output current drops to the
153
Zero current detection time 0.5 s 0 to 10 s Pr.152 setting or lower to the time when the Zero current
M463
detection (Y13) signal is output.
0 to 10 s Set the retention time period during which the Y12 signal is ON.
166 Output current detection
0.1 s The Y12 signal is retained ON. The signal turns OFF at the next
M433 signal retention time 9999
start-up of the inverter.
167 Output current detection Select the inverter operation at the time when the Y12 signal
0 0, 1, 10, 11
M464 operation selection and the Y13 signal turn ON.
Pr.150
Output current
Pr.151
Time
Pr.166
Output current
detection signal OFF ON OFF
(Y12)
464 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• If the inverter output current drops to zero, slippage due to gravity may occur, especially in a lift application, because the
motor torque is not generated. To prevent this, the Y13 signal can be output from the inverter to apply the mechanical brake
at zero current output.
1
• To use the Y13 signal, set "13 (positive logic) or 113 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
• Use Pr.167 to select the inverter operation at the time when Y13 signal turns ON, whether the inverter output stops or the
2
inverter operation continues.
Pr.167 = "0"
3
Output
current
Pr.152
Pr.152
0[A]
0.1s ∗ Time 4
OFF ON
Start signal
OFF OFF
5
Zero current ON ON
detection time
(Y13) Pr.153 Pr.153
Detection time Detection time
6
signal is turned OFF after 0.1 s.
NOTE
• This function is enabled during online or offline auto tuning.
• The response time of the Y12 and Y13 signals is approximately 0.1 seconds. However, the response time varies according to 7
the load condition.
• When Pr.152 = "0", the zero current detection function is disabled.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal. 8
CAUTION 9
• The setting of the zero current detection level should not be too low, and the setting of the zero current detection time
should not be too long. Doing so may cause the signal for the zero current detection not to be outputted when the output
current is very low and the motor torque is not generated.
10
• A safety backup such as an emergency brake must be provided to prevent machines or equipment in hazardous
conditions even if the Zero current detection is used.
Parameters referred to
Online auto tuningpage 527
Offline auto tuningpage 509, page 519
Pr.190 to Pr.196 (Output terminal function selection)page 450
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
465
• To use the TU signal, set "35 (positive logic) or 135 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
Time
TU ON OFF
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
Setting
Pr. Name Initial value Description
range
Remote output data is cleared
0 when the inverter power is turned
OFF. Remote output data is cleared
Remote output data is retained during an inverter reset.
1 even after the inverter power is
495 turned OFF.
Remote output selection 0
M500 Remote output data is cleared
10 when the inverter power is turned
OFF. Remote output data is retained
Remote output data is retained during an inverter reset.
11 even after the inverter power is
turned OFF.
496 Set a decimal number to enter a binary number in every bit
Remote output data 1 0 0 to 4095
M501 corresponding to each of the output terminals on the inverter.
Set a decimal number to enter a binary number in every bit
497
Remote output data 2 0 0 to 4095 corresponding to each of the output terminals on the option FR-
M502
A8AY or FR-A8AR.
ABC1
RUN
IPF
SU
FU
OL
∗1
∗1
∗1
∗1
∗1
466 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Pr.497
b11 b0
1
RA3 ∗3
RA2 ∗3
RA1 ∗3
Y6 ∗2
Y5 ∗2
Y4 ∗2
Y3 ∗2
Y2 ∗2
Y1 ∗2
Y0 ∗2
∗1
∗1
*1
*2
Any value
Y0 to Y6 are available when the output-extending option (FR-A8AY) is installed.
2
*3 RA1 to RA3 are available when the relay output option (FR-A8AR) is installed.
Reset ON Reset ON
9
REM ON OFF REM ON
∗
∗ When Pr.495 = "1", the signal condition saved in EEPROM
(condition of the last power OFF) is applied. 10
NOTE
• The output terminal to which the REM signal is not assigned by using Pr.190 to Pr.196 does not turn ON or OFF when "1 or
0" is set in bit corresponding to each of the terminals by using Pr.496 and Pr.497. (ON/OFF command affects only the terminal
to which the REM signal is assigned.)
• When Pr.495 = "1 or 11" (remote output data retained at power OFF), take measures to keep the control circuit power ON,
such as connecting terminal R1/L11 with terminal P/+ and connecting terminal S1/L21 with terminal N/- . If the control power
is not retained, the output signal after the inverter power turns ON is not guaranteed to work. When the high power factor
converter (FR-HC2) or the converter unit (FR-CC2) is connected to the inverter, assign the FR-HC2/FR-CC2 connection,
instantaneous power failure detection (X11) signal to an input terminal and input the IPF signal from the FR-HC2/FR-CC2 to
the inverter via the terminal to which the X11 signal is assigned.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
467
Initial Setting
Pr. Name Description
value range
Remote output data is cleared when the
0
inverter power is turned OFF. Remote output data is cleared
Remote output data is retained even after during an inverter reset.
1
655 Analog remote output the inverter power is turned OFF.
0
M530 selection Remote output data is cleared when the
10 Remote output data is
inverter power is turned OFF.
retained during an inverter
Remote output data is retained even after
11 reset.
the inverter power is turned OFF.
Value output via the terminal for which "87"
656 800 to
Analog remote output 1 1000% is set in the terminal function selection
M531 1200%
parameter (Pr.54 or Pr.158)
Value output via the terminal for which "88"
657 800 to Set the analog value outputted
Analog remote output 2 1000% is set in the terminal function selection
M532 1200% via terminal FM or CA, via
parameter (Pr.54 or Pr.158)
terminal AM, and via the
Value output via the terminal for which "89"
658 800 to analog output terminal on the
Analog remote output 3 1000% is set in the terminal function selection
M533 1200% option FR-A8AY.
parameter (Pr.54 or Pr.158)
Value output via the terminal for which "90"
659 800 to
Analog remote output 4 1000% is set in the terminal function selection
M534 1200%
parameter (Pr.54 or Pr.158)
55K
1440 50K
0 0
800 1000 1100 1200 800 1000 1100 1200
Analog remote output value [%] Analog remote output value [%]
Terminal FM (FM output) Terminal FM (High-speed pulse train output)
• When Pr.54 FM/CA terminal function selection = "87, 88, 89, or 90" (remote output), the type CA inverter can output
any analog current via terminal CA.
• Terminal CA output [mA] = 20 [mA] × (Analog remote output value - 1000)/100
Where the output range is 0 to 20 mA.
Output current [mA]
20
0
800 1000 1100 1200
Analog remote output value [%]
Terminal CA
468 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• When Pr.158 AM terminal function selection = "87, 88, 89, or 90", an analog voltage can be output via terminal AM.
• Terminal AM output [V] = 10 [V] × (Analog remote output value - 1000)/100
The output range is -10 to +10 V regardless of the Pr.290 Monitor negative output selection setting.
1
Output voltage [V]
10
2
800 900 0 3
1000 1100 1200
Analog remote output value [%]
4
-10
Terminal AM
9
Analog Analog
output output
Analog output Analog Analog
clear output
saved
output
held
10
Signal condition during a reset
Pr.655 = 0, 1 Pr.655 = 10, 11
Reset ON Reset ON
Analog Analog
output output
∗
∗ When Pr.655 = "1", the signal condition saved in EEPROM
(condition of the last power OFF) is applied.
NOTE
• When Pr.655 = "1 or 11" (remote output data retained at power OFF), take measures to keep the control circuit power ON,
such as connecting terminal R1/L11 with terminal P/+ and connecting terminal S1/L21 with terminal N/- (while power is
supplied via input terminals R/L1, S/L2 and T/L3). If the control power is not retained, the output signal after the inverter power
turns ON is not guaranteed to work. When connecting the high power factor converter FR-HC2, assign the instantaneous
power failure detection (X11) signal to an input terminal to input the IPF signal from the FR-HC2 to the terminal for X11 signal.
Parameters referred to
Pr.54 FM/CA terminal function selectionpage 435
Pr.158 AM terminal function selectionpage 435
Pr.290 Monitor negative output selectionpage 435
Pr.291 Pulse train I/O selectionpage 435
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
469
Pr. Name Initial value Setting range Description
0 Without fault code output
76
Fault code output selection 0 1 With fault code output
M510
2 Fault code is output only when a fault occurs
• Fault codes can be output to the output terminals by setting Pr.76 Fault code output selection = "1 or 2".
• When the setting is "2", a fault code is only output when a fault occurs. In normal operation the terminal outputs the signal
assigned in Pr.191 to Pr.194 (output terminal function selection).
• The fault codes that can be output are shown in the following table. (0: Output transistor OFF, 1: Output transistor ON)
Operation panel Output terminal operation
indication Fault code
SU IPF OL FU
(FR-DU08)
Normal*1 0 0 0 0 0
E.OC1 0 0 0 1 1
E.OC2 0 0 1 0 2
E.OC3 0 0 1 1 3
E.OV1 to E.OV3 0 1 0 0 4
E.THM 0 1 0 1 5
E.THT 0 1 1 0 6
E.IPF 0 1 1 1 7
E.UVT 1 0 0 0 8
E.FIN 1 0 0 1 9
E.BE 1 0 1 0 A
E. GF 1 0 1 1 B
E.OHT 1 1 0 0 C
E.OLT 1 1 0 1 D
E.OPT
1 1 1 0 E
E.OP1 to E.OP3
Terminals other than the
1 1 1 1 F
above
*1 When Pr.76 = "2", the terminal outputs the signal assigned by Pr.191 to Pr.194.
NOTE
• If an error occurs while Pr.76 ≠ "0", the output terminals SU, IPF, OL, and FU output the signals in the table above regardless
of the settings in Pr.191 to Pr.194 (Output terminal function selection). Take caution when controlling the inverter with the
output signals set by Pr.191 to Pr.194.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
470 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
• The inverter does not stop cumulating (can continue to cumulate) the output energy even if the retry function or the
automatic restart after instantaneous power failure function works because the cause of the function activation is a mini
power failure which is too short to cause an inverter reset.
1
• If a power failure occurs, the cumulative value is reset to 0 kWh and restart cumulating.
• To use the Y79 signal, set "79 (positive logic) or 179 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
2
Output power
20kWh
3
10kWh
Pulse output of 4
output power OFF Time
(Y79)
ON for 0.15s
When Pr.799 = 10 5
NOTE
• Because the accumulated data in the inverter is cleared when control power is lost by power failure or at an inverter reset, the
value on the monitor cannot be used to charge electricity bill. 6
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal. (Refer to page 450.)
• Do not assign the signal to terminal ABC1 or terminal ABC2 whose pulse outputs are frequently turned ON/OFF. Otherwise,
the life of the relay contact may be shortened.
7
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 450
8
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the Pr.663 setting.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.54 FM/CA terminal function selectionpage 435
Pr.158 AM terminal function selectionpage 435
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
471
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.290 Monitor negative output selectionpage 435
2 divisions
Division ratio A-phases (500 pulses)
1/2 B-phases
NOTE
• Control of motor rotation (forward or reverse) by phase difference between A phase and B phase is as follows.
When A phase is 90° advanced as compared to B phase: Forward rotation
When A phase is 90° behind as compared to B phase: Reverse rotation
472 5. PARAMETERS
5.11 (M) Item and output signal for monitoring
5.12 (T) Multi-function input terminal parameters 1
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
473
Analog input specification selection
• For terminals 2 and 4 used for analog input, the voltage input (0 to 5 V, 0 to 10 V) and current input (0 to 20 mA) are
selectable. To change the input specification, change the setting of Pr.73 (Pr.267) and the voltage/current input selection
switch (switch 1 or switch 2).
Voltage/current
input switch
Switch 2
Switch 1
2 4
Input
Switch state Input specification Rated specification
terminal
ON Current input For voltage input, the input resistance is 10±1 kΩ and the
Switch 1 Terminal 2
OFF Voltage input (initial status) maximum permissible voltage is 20 VDC.
ON Current input (initial status) For current input, the input resistance is 245±5 Ω and the
Switch 2 Terminal 4 maximum permissible current is 30 mA.
OFF Voltage input
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Set Pr.73 (Pr.267) and the voltage/current input selection switch according to the analog signal input. The incorrect
settings shown in the following table cause a failure. The inverter does not operate properly with other incorrect settings.
Setting causing a failure
Operation
Switch setting Terminal input
Causes an analog signal output circuit failure in an external device (due to increased loads on the
ON (Current input) Voltage input
signal output circuit of the external device).
Causes an input circuit failure in the inverter (due to an increased output power in the analog signal
OFF (Voltage input) Current input
output circuit of an external device).
NOTE
• Check the number of the voltage/current input selection switch before setting, because it is different from the switch number
indicated on the FR-A700 series inverter.
474 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Set Pr.73 and the voltage/current input selection switch according to the following table.
Pr.73 setting
Terminal 2
Switch 1
Terminal 1
Compensation input
terminal compensation Reversible polarity
1
input input
method
0 0 to 10 V*1 OFF 0 to ±10 V
1 (initial value) 0 to 5 V*1 OFF 0 to ±10 V Terminal 1 addition 2
2 0 to 10 V *1 OFF 0 to ±5 V compensation
12 0 to 10 V*1 OFF 0 to ±5 V 5
13 0 to 5 V*1 OFF 0 to ±5 V
Applied
14 0 to 10 V OFF 0 to ±10 V*1
Terminal 2 override
15 0 to 5 V OFF 0 to ±5 V*1 6
16 *1 ON 0 to ±10 V
0 to 20 mA Terminal 1 addition
17 0 to 20 mA*1 ON 0 to ±5 V compensation
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
475
• The power supply 5 V (10 V) can be input by either using the internal power supply or preparing an external power supply.
The internal power supply is 5 VDC output between terminals 10 and 5, and 10 VDC output between terminals 10E and 5.
Inverter internal power source
Terminal Frequency setting resolution Pr.73 (terminal 2 input voltage)
voltage
10 5 VDC 0.030/60 Hz 0 to 5 VDC input
10E 10 VDC 0.015/60 Hz 0 to 10 VDC input
• To supply the 10 VDC input to terminal 2, set "0, 2, 4, 10, 12, or 14" in Pr.73. (The initial value is 0 to 5 V.)
• Set "1 (0 to 5 VDC)" or "2 (0 to 10 VDC)" in Pr.267 and turn OFF the voltage/current input selection switch to input voltage
through terminal 4. Turning ON the AU signal activates the terminal 4 input.
NOTE
• The wiring length of terminal 10, 2, and 5 should be 30 m at maximum.
Inverter
Forward STF
rotation AU Voltage/current
input switch
SD
4 to 20mADC
Frequency Current
input
4
setting equipment 5 2 4
• Set "6, 7, 16, or 17" in Pr.73 and turn ON the voltage/current input selection switch to input current through terminal 2. In
this case, the AU signal does not need to be turned ON.
Inverter
Forward STF
Voltage/current
rotation SD input switch
4 to 20mADC
Frequency Current
input
2
setting equipment 5 2 4
476 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
• Set a positive or negative input (0 to ±5 V or 0 to ±10 V) to terminal 1 to allow the operation of forward/reverse rotation
according to the polarity of the input value.
1
Reverse Set frequency Forward
(Hz)
rotation rotation
60
Reversible
2
Not reversible +5
(+10)
-5 0 Terminal 1 input (V) 3
(-10)
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
477
• Functions of terminal 4 under different controls
V/F control Real sensorless vector control, Vector control, PM sensorless vector control
Pr.858
Advanced magnetic flux vector
setting Speed control Torque control Position control
control
0
Frequency command Speed command (AU signal-
(initial Speed limit (AU signal-ON) —
(AU signal-ON) ON)
value)
1 — Magnetic flux command *1*2 Magnetic flux command *1*2 Magnetic flux command *1*2
Stall prevention operation level
4
input Torque limit (Pr.810 = 1)*3 — Torque limit (Pr.810 = 1)*3
9999 — — — —
—: No function
*1 This function is valid under Vector control.
*2 Invalid when Pr.868 = "1”.
*3 Invalid when Pr.868 = "4".
NOTE
• When Pr.868 = "1" (magnetic flux command) or "4" (stall prevention / torque limit), the terminal 4 function is enabled regardless
of the ON/OFF state of the AU signal.
Parameters referred to
Advanced magnetic flux vector controlpage 222
Real sensorless vector controlpage 215
Pr.804 Torque command source selectionpage 270
Pr.807 Speed limit selectionpage 274
Pr.810 Torque limit input method selectionpage 235
Pr.840 Torque bias selectionpage 255
Forward Inverter
rotation
STF
SD
10
2
5
Auxiliary input 1
0 to 10V( 5V)
• A compensation signal can be added to the main speed setting for such as synchronous or continuous speed control
operation.
478 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
• Set "0 to 3, 6, 7, 10 to 13, 16, or 17" in Pr.73 to add the voltage determined by the terminal 1 input when the main speed
setting is input through terminal 2.
• When a negative voltage obtained from the addition, it is regarded as 0 and the operation is stopped when Pr.73 = "0 to
1
3, 6, or 7", and the operation is reversed (polarity reversible operation) after the STF signal is turned ON when Pr.73 = "10
to 13, 16, or 17".
• The terminal 1 compensation input can be added to the multi-speed setting or terminal 4 (initial value: 4 to 20 mA).
2
• The degree of addition to terminal 2 is adjustable with Pr.242 and the degree of addition to terminal 4 is adjustable with
Pr.243.
Pr.242
3
Analog command value with use of terminal 2 = terminal 2 input + terminal 1 input ×
100(%)
Analog command value with use of terminal 4= terminal 4 input + terminal 1 input ×
Pr.243 4
100(%)
Output frequency Output frequency
When voltage across
terminals 2 and 5 is 2.5 V
When voltage across
terminals 2 and 5 is 2.5 V 5
(5 V) (5 V)
When voltage
When voltage
across terminals
across terminals 6
2 and 5 is 0 V
2 and 5 is 0 V
-5 V -2.5 V
(-10 V) (-5 V)
0 +2.5 V +5 V Terminal 1
(+5 V) (+10 V)
-5 V -2.5 V
(-10 V) (-5 V)
0 +2.5 V +5 V Terminal 1
(+5 V) (+10 V)
7
Forward rotation Reverse rotation Forward rotation
STF Signal STF Signal
ON
8
ON
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
479
• How to calculate the set frequency when the override function is used:
Compensation (%)
Set frequency (Hz) = Main speed setting frequency (Hz) ×
100(%)
NOTE
• To use terminal 4, the AU signal needs to be turned ON.
• To make compensation input for multi-speed operation or remote setting, set Pr.28 Multi-speed input compensation
selection = "1" (with compensation) (initial value "0").
• After changing the Pr.73 setting, check the setting of the voltage/current input selection switch. Incorrect setting may cause a
fault, failure, or malfunction. (Refer to page 473 for the setting.)
Parameters referred to
Pr.28 Multi-speed input compensation selectionpage 391
Pr.73 Analog input selectionpage 473
480 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Block diagram
Pr.822 = 9999
Pr.74 1
Speed command
RT-OFF
Pr.822
Terminal 1 (2, 4) input 2
RT-ON Pr.822 9999
Pr.74
Pr.826 = 9999
Speed command 3
Pr.826
Pr.826 9999 4
Pr.832 = 9999
Pr.832
5
Pr.832 9999
6
Pr.836 = 9999
Pr.836
Pr.836 9999
7
Analog input time constant (Pr.74)
• Use this parameter to eliminate noise on the frequency setting circuit. 8
• Increase the filter time constant if the operation is unstable due to noise or other factors.
If the setting is too large, response becomes slow. (The time constant can be between 0 and 8, which are about 5 ms to 1
s.) 9
Analog speed command input time constant (Pr.822, Pr.832)
• Use Pr.822 Speed setting filter 1 to set the primary delay filter time constant to the external speed command (analog
input command). Increase the setting of the time constant to allow delays in follow-up of the speed command or when the
10
analog input voltage is unstable.
• Use Pr.832 Speed setting filter 2 to change the time constant to use one inverter to switch operation between two or more
motors.
• Pr.832 Speed setting filter 2 is enabled when the RT signal is ON.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
481
*1 It depends on the Pr.73 setting.
Frequency
command Slope determined
according to Pr.125
and C2 to C4
Slope does not
change.
NOTE
• The analog input filter is invalid (no filter) during PID control operation.
Parameters referred to
Pr.73 Analog input selectionpage 473
Pr.125, C2 to C4 (bias and gain of the terminal 2 frequency setting)page 482
*1 The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
482 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Relationship between the analog input terminal function and the
calibration parameter 1
• Calibration parameter according to the terminal 1 function
2
Regenerative driving torque 5
limit
3 Torque command C16 (Pr.919) Terminal 1 bias command C18 (Pr.920) Terminal 1 gain command
(torque) (torque)
Stall prevention operation
4 level*1/
C17 (Pr.919) Terminal 1 bias (torque) C19 (Pr.920) Terminal 1 gain (torque)
6
torque limit / torque command
C12 (Pr.917) Terminal 1 bias frequency C14 (Pr.918) Terminal 1 gain frequency
Forward/reverse rotation speed
5 (speed) (speed)
limit
C13 (Pr.917) Terminal 1 bias (speed) C15 (Pr.918) Terminal 1 gain (speed) 7
C16 (Pr.919) Terminal 1 bias command C18 (Pr.920) Terminal 1 gain command
6 Torque bias input (torque) (torque)
C17 (Pr.919) Terminal 1 bias (torque) C19 (Pr.920) Terminal 1 gain (torque)
9999 No function — — 8
• Calibration parameter according to the terminal 4 function
Pr.858
setting
Terminal function
Bias setting
Calibration parameter
Gain setting
9
C5 (Pr.904) Terminal 4 frequency setting Pr.126 Terminal 4 frequency setting gain
0
bias frequency frequency
(initial Frequency command
value)
C6 (Pr.904) Terminal 4 frequency setting
bias
C7 (Pr.905) Terminal 4 frequency setting
gain
10
C38 (Pr.932) Terminal 4 bias command C40 (Pr.933) Terminal 4 gain command
1 Magnetic flux command (torque) (torque)
C39 (Pr.932) Terminal 4 bias (torque) C41 (Pr.933) Terminal 4 gain (torque)
Stall prevention operation level C38 (Pr.932) Terminal 4 bias command C40 (Pr.933) Terminal 4 gain command
4 *1 (torque) (torque)
/
torque limit C39 (Pr.932) Terminal 4 bias (torque) C41 (Pr.933) Terminal 4 gain (torque)
9999 No function — —
*1 Use Pr.148 Stall prevention level at 0 V input or Pr.149 Stall prevention level at 10 V input to adjust bias or gain for setting the stall prevention
operation level.
To change the frequency for the maximum analog input (Pr.125, Pr.126)
• Use Pr.125 (Pr.126) to change the frequency setting (gain) for the maximum analog input voltage (current).
(C2 (Pr.902) to C7 (Pr.905) settings do not need to be changed.)
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
483
• Use Pr.126 to set the output frequency to the 20 mA input of the frequency command current (4 to 20 mA).
60Hz 60Hz
(50Hz) (50Hz)
(Hz)
Output frequency
(Hz)
Gain
Pr.125 Gain Pr.126
Bias C14(Pr.918) Bias
C2 C5
C12(Pr.917) (Pr.904)
0 100% 0 20 100%
0 5V 0 4 20mA
Frequency setting signal
0 10V 0 1 Frequency setting signal 5V
0 20mA 0 2 10V
C3(Pr.902) C4(Pr.903) C6(Pr.904) C7(Pr.905)
C13(Pr.917) C15(Pr.918)
• There are three methods to adjust the bias/gain frequency setting voltage (current).
Adjustment by applying voltage (current) between terminals 2 and 5 (4 and 5) to set the voltage (current) at the bias/gain
torque. page 484
Adjustment by selecting the voltage (current) at the bias/gain torque without applying voltage (current) between terminals
2 and 5 (4 and 5). page 485
Adjustment by changing the frequency without adjusting the voltage (current). page 486
NOTE
• When the slope of the frequency is changed after calibration of terminal 2, the slope of the frequency is also changed for
terminal 1.
• When voltage is applied to terminal 1 while calibration of terminal 2 or terminal 4 is in progress, the terminal 1 input value is
added to the terminal 2 (4) input value.
• Always calibrate the input after changing the voltage/current input signal with Pr.73 (Pr.267) and the voltage/current input
selection switch.
NOTE
• When voltage is applied to terminal 1 while the terminal 1 input specification (0 to ±5 V, 0 to ±10 V) does not agree with the
main speed (terminal 2 or terminal 4 input) specification (0 to 5 V, 0 to 10 V, 0 to 20 mA), the analog input is not correctly
displayed. (For example, when 0 V is applied to terminal 2 and 10 V is applied to terminal 1 in the initial status, the value is
indicated as 5 V (100%).)
Set "0 (initial value)" in Pr.241 to use the % display.
484 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
2. Changing the operation mode
Press to choose the parameter setting mode. (The parameter number read previously appears.) 2
4. Calibration parameter selection
Turn until " " (C4 (Pr.903) Terminal 2 frequency setting gain) appears for terminal 2, or
4
" " (C7 (Pr.905) Terminal 4 frequency setting gain) for terminal 4.
Press to confirm the selection. The analog voltage (current) % and " " (" ") are displayed 8
alternately.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Turn until " " (C4 (Pr.903) Terminal 2 frequency setting gain) appears for terminal 2, or
" " (C7 (Pr.905) Terminal 4 frequency setting gain) for terminal 4.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
485
6. Analog voltage (current) display
Press to display the analog voltage (current) value (%) currently applied to terminal 2 (4).
When is turned, the gain voltage (current) value (%) currently set to the parameter appears.
Turn until the desired gain voltage (current) value (%) appears.
8. Setting completed
Press to confirm the selection. The analog voltage (current) % and " " (" ") are displayed
alternately.
NOTE
• Press after step 6 to check the present bias/gain frequency setting. The setting cannot be checked after step 7.
Adjustment by changing the frequency without adjusting the voltage (current) (Example of
changing the gain frequency from 60 Hz to 50 Hz)
Operating procedure
1. Selecting the parameter
Turn until " " (Pr.125) appears for terminal 2, or " " (Pr.126) for terminal 4.
Press to confirm the selection. " " and " " (" ") are displayed alternately.
Press three times to select the monitor mode, and change the monitor item to the frequency.
4. Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in page 155.)
The motor is operated at 50 Hz.
NOTE
• If the frequency meter (display meter) connected between terminal FM and SD (CA and 5) does not indicate exactly 60 Hz,
set the calibration parameter C0 FM/CA terminal calibration. (Refer to page 440.)
• If the voltage (current) values at the gain and bias frequencies are too close to each other, an error " " may be
indicated.
• Changing C4 (Pr.903) or C7 (Pr.905) (gain adjustment) will not change Pr.20.
Input to terminal 1 (frequency setting auxiliary input) is added to the frequency setting signal.
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• To set the value to 120 Hz or higher, the Pr.18 High speed maximum frequency needs to be 120 Hz or higher. (Refer to
page 407.)
• Use the calibration parameter C2 (Pr.902) or C5 (Pr.904) to set the bias frequency. (Refer to page 483.)
486 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
CAUTION 1
• Be cautious when setting any value other than "0" as the bias frequency at 0 V (0 mA). Even if a speed command is not
given, simply turning ON the start signal will start the motor at the preset frequency.
Parameters referred to 2
Pr.1 Maximum frequency, Pr.18 High speed maximum frequencypage 407
Pr.20 Acceleration/deceleration reference frequencypage 349
Pr.73 Analog input selection, Pr.267 Terminal 4 input selectionpage 473
Pr.79 Operation mode selectionpage 370
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignmentpage 477 3
5.12.6 Torque (magnetic flux) setting voltage (current)
bias and gain 4
Sensorless Vector PM
The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to 5 VDC, 0 to 10 VDC, or 5
4 to 20 mA).
Use Pr.73 Analog input selection or Pr.267 Terminal 4 input selection to switch among input 0 to 5 VDC, 0 to 10 V, and 4
to 20 mA. (Refer to page 473.)
6
Initial
Pr. Name Setting range Description
value
C16 (919) Set the bias torque (magnetic flux) for the terminal 1
T110*1
Terminal 1 bias command (torque) 0% 0 to 400%
input. 7
C17 (919) Set the converted % of the bias voltage for the terminal
Terminal 1 bias (torque) 0% 0 to 300%
T111*1 1 input.
C18 (920)
Terminal 1 gain command (torque) 150% 0 to 400%
Set the gain (maximum) torque (magnetic flux) for the 8
T112*1 terminal 1 input.
C19 (920) Set the converted % of the gain voltage for the terminal
Terminal 1 gain (torque) 100% 0 to 300%
T113*1 1 input.
C38 (932) Set the bias torque (magnetic flux) for the terminal 4
9
*1 Terminal 4 bias command (torque) 0% 0 to 400%
T410 input.
C39 (932) Set the converted % of the bias current (voltage) for the
Terminal 4 bias (torque) 20% 0 to 300%
T411*1 terminal 4 input. 10
C40 (933) Set the gain (maximum) torque (magnetic flux) for the
Terminal 4 gain command (torque) 150% 0 to 400%
T412*1 terminal 4 input.
C41 (933) Set the converted % of the gain current (voltage) for the
Terminal 4 gain (torque) 100% 0 to 300%
T413*1 terminal 4 input.
241 Analog input display unit 0 % display Select the unit for analog input
0
M043 switchover 1 V/mA display display.
*1 The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
487
Relationship between the analog input terminal function and the
calibration parameter
• Calibration parameter according to the terminal 1 function
*1 Use Pr.148 Stall prevention level at 0 V input and Pr.149 Stall prevention level at 10 V input to adjust bias and gain for setting the stall
prevention operation level.
• Calibration parameter according to the terminal 4 function
*2 Use Pr.148 Stall prevention level at 0 V input and Pr.149 Stall prevention level at 10 V input to adjust bias and gain for setting the stall
prevention operation level.
To change the torque for the maximum analog input (C18 (Pr.920), C40
(Pr.933))
• Use C18 (Pr.920) or C40 (Pr.933) to change the torque setting (gain) for the maximum analog input voltage (current).
488 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
• Set the bias torque of the terminal 4 input using C38 (Pr.932). (The initial value is the torque for 4 mA.)
• Use C40 (Pr.933) to set the torque to the 20 mA input of the torque command current (4 to 20 mA).
1
400
Torque(%)
400
Torque(%)
150
2
Gain
(-5V) C18(Pr.920) 150 Gain
(-10V) Bias Initial value C40
C16(Pr.919) (Pr.933)
-100%
0 100% Bias Initial value
3
0 Torque setting signal 5V
0 10V C38
C17(Pr.919) C19(Pr.920) (Pr.932)
0 20 100%
∗1 -150
0 4
Torque setting signal
20mA 4
Calibration example of terminal 1 C39(Pr.932) C41(Pr.933)
*1 A negative voltage (0 to -10 V (-5 V)) is valid as a torque command. However, when a negative voltage is input as a torque limit value, the torque 5
limit is regarded as "0".
• There are three methods to adjust the bias/gain torque setting voltage (current).
Adjustment by applying voltage (current) between terminals 1 and 5 (4 and 5) to set the voltage (current) at the bias/gain 6
torque. page 489
Adjustment by selecting the voltage (current) at the bias/gain torque without applying voltage (current) between terminals
1 and 5 (4 and 5). page 490 7
Adjustment by changing the torque without adjusting the voltage (current). page 491
NOTE
• Always calibrate the input after changing the voltage/current input signal with Pr.73 (Pr.267) and the voltage/current input 8
selection switch.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
489
4. Calibration parameter selection
Turn until " " (C19 (Pr.920) Terminal 1 gain (torque)) appears for terminal 1, or " " (C41
(Pr.933) Terminal 4 gain (torque)) for terminal 4.
Press to display the analog voltage (current) % currently applied to the terminal 1 (4).
8. Setting completed
Press to confirm the selection. The analog voltage (current) % and " " (" ") are displayed
alternately.
Adjustment by selecting the voltage (current) at the bias/gain torque without applying voltage
(current) between terminals 1 and 5 (4 and 5)
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Turn until " " (C19 (Pr.920) Terminal 1 gain (torque)) appears for terminal 1, or " " (C41
(Pr.933) Terminal 4 gain (torque)) for terminal 4.
Press to display the analog voltage (current) % currently applied to the terminal 1 (4).
When is turned, the gain voltage (current) value (%) currently set to the parameter appears.
Turn until the desired gain voltage (current) value (%) appears.
490 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
8. Setting completed
Press to confirm the selection. The analog voltage (current) % and " " (" ") are displayed 1
alternately.
• Press after step 6 to check the present bias/gain torque setting. The setting cannot be checked after step 7.
4
Adjustment by changing the torque without adjusting the voltage (current) (Example of
changing the gain torque from 150% to 130%) 5
Operating procedure
1. Selecting the parameter
6
Turn until " " (Pr.920) appears for terminal 1, or " " (Pr.933) for terminal 4.
4. Start
Turn ON the start switch (STF or STR) to apply a voltage across terminals 1 and 5 (4 and 5),
10
Operation is performed with 130% torque.
NOTE
• If the voltage (current) values at the gain and bias torques are too close to each other, an error (" ") may be
indicated.
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• Use the calibration parameter C16 (Pr.919) or C38 (Pr.932) to set the bias torque. (Refer to page 488.)
CAUTION
• Be cautious when setting any value other than "0" as the bias torque at 0 V (0 mA). Even if a torque command is not
given, simply turning ON the start signal will supply torque to the motor.
Parameters referred to
Pr.20 Acceleration/deceleration reference frequencypage 349
Pr.73 Analog input selection, Pr.267 Terminal 4 input selectionpage 473
Pr.79 Operation mode selectionpage 370
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignmentpage 477
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
491
5.12.7 Checking of current input on analog input terminal
When current is input to the analog input terminal 2 or terminal 4, the input current can be checked and the operation when the
input falls below the specified level (the analog current input is lost) can be selected. The operation can be continued even
when the analog current input is lost.
Initial Setting
Pr. Name Description
value range
Operation continues with output frequency before the current
1
input loss.
4 mA input fault (E.LCI) is activated when the current input loss
2
is detected.
573
4 mA input check selection 9999 The inverter output decelerates the motor to a stop when the
T052
3 current input loss is detected. After the motor is stopped, 4 mA
input fault (E.LCI) is activated.
4 Operation continues at the frequency set in Pr.777.
9999 No current input check
Set the frequency for operation when the current input is lost.
777 4 mA input fault operation 0 to 590 Hz
9999 (Valid when Pr.573 = "4")
T053 frequency
9999 No current input check when Pr.573 = "4"
778
4 mA input check filter 0s 0 to 10 s Set the current input loss detection time.
T054
∗1
2mA 4mA 20mA
Analog input
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Continuing operation when the analog current input is lost (Pr.573 = "1,
4", Pr.777)
• When Pr.573 = "1", operation continues at the output frequency before the current input loss.
• When Pr.573 = "4" and Pr.777 ≠ "9999", operation continues at the frequency set in Pr.777.
• When the start command is turned OFF during current input loss, the inverter output decelerates the motor to a stop
immediately, and the operation is not restarted even if a start command is input again.
• When the current input is restored, the LF signal is turned OFF, and operation is performed according to the current input.
492 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
• The following is the operation example during External operation.
1
Pr.573=1 : Operation continued with the frequency before being lost
Pr.573=4 : Operation continued with Pr.777 setting
Output frequency
2
Analog input Return
Input current
20mA decrease
3
4mA 3mA
2mA
Time
STF
LF signal 4
• The following is the operation example during PID control (reverse action) operation.
Pr.573=1 : Operation continued with the frequency before being lost
Pr.573=4 : Operation continued with Pr.777 setting
5
Output frequency
Input current
6
20mA
Set point (fixed) decrease
Return
Measured value
4mA 2mA 3mA 7
Time
STF
LF signal 8
PID signal On during input decrease
NOTE
• When the setting is changed to the continuous operation (Pr.573 = "1 or 4") after the input current loss, the frequency before
9
loss is regarded as 0 Hz.
E.LCI occurs
Output frequency
Input current
20mA decrease
Set point (fixed)
Return
Measured value
4mA 2mA 3mA
Time
STF
LF signal
PID signal
ALM signal
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
493
• When the analog current input is restored during the deceleration, the motor is accelerated again and operates according
to the current input.
• The following is the operation example during PID control (reverse action) operation.
Input current
20mA decrease
Set point (fixed)
Return
Measured value
4mA 2mA 3mA
Time
STF
LF signal
PID signal
ALM signal
• The following is the operation example when the analog input current is restored during deceleration under PID control
(reverse action).
Input current
20mA
Set point (fixed) decrease
Return
Measured value
4mA 2mA 3mA
Time
STF
LF signal
OFF during
deceleration
PID signal
494 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Functions related to current input check
Function Operation
Refer to 1
page
When the operation continues, the minimum frequency setting is valid even during current
Minimum frequency 407
input loss.
The multi-speed setting signal is prioritized even during current input loss (the motor operates 2
according to the multi-speed setting even during continuous operation at the predetermined
frequency or during deceleration to a stop).
Multi-speed operation 391
When the multi-speed setting signal is turned OFF while the input current is lost during the
multi-speed operation, the motor is decelerated to a stop even if the parameter is set to 3
continue operation when the current input is lost.
JOG operation is prioritized even during current input loss (the motor operation switches to
JOB operation even during continuous operation at the predetermined frequency or during
JOG operation
deceleration to a stop).
390 4
When the JOG signal is turned OFF while the input current is lost during the JOG operation,
the motor is decelerated to a stop even if the parameter is set to continue operation when the
current input is lost.
MRS signal
The MRS signal is enabled even during current input loss (output is shut off by turning ON the
MRS signal even during continuous operation at the predetermined frequency or during 499
5
deceleration to a stop).
When the operation using the remote setting function is changed to the continuous operation
Remote setting after the current input is lost, acceleration, deceleration, and clear operations by the remote 359
setting are disabled. The operations are enabled after restoration of current input.
6
When the protective function is activated during continuous operation after the current input
Retry function is lost and the retry function is used successfully, operation continues without clearing the 405
frequency setting. 7
When the operation using compensation by addition or override compensation is changed to
Compensation by addition,
the continuous operation after the current input is lost, compensation by addition or override 478
override compensation
compensation is disabled. The operations are enabled after restoration of current input.
The current before the filter time is applied is used for input loss detection. 8
Input filter time constant The current after the filter time is applied is used for continuous operation at the output 492
frequency before the input loss.
PID calculation is stopped during current input loss. However, PID control is not disabled (the
operation does not return to normal).
During the pre-charge, end determination or fault determination by the pre-charge function is
9
PID control not performed when the current input is lost. 570
The sleep function is prioritized even during current input loss. When the clearing condition of
the sleep function is met during current input loss, continuous operation at the predetermined
frequency is restored.
10
The power failure stop function is prioritized even if current input loss is detected during power
failure.
After the power failure stop and re-acceleration, operation continues at the output frequency
Power failure stop 610
before the input loss.
When the protective function E.LCI is selected when the current input is lost, E.LCI is
activated after the power failure stop.
Traverse operation is performed based on the frequency even during continuous operation
Traverse function 551
during current input loss.
Parameters referred to
Pr.73 Analog input selection, Pr.267 Terminal 4 input selectionpage 473
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
495
5.12.8 Input terminal function selection
Use the following parameters to select or change the input terminal functions.
Initial
Pr. Name Initial signal Setting range
value
0 to 20, 22 to 28, 37, 42 to 48, 50 to 53, 57 to 60,
178 STF terminal
60 STF (Forward rotation command) 62, 64 to 74, 76, 77 to 80, 85, 87 to 89, 92 to 96,
T700 function selection
9999
0 to 20, 22 to 28, 37, 42 to 48, 50 to 53, 57 to 59,
179 STR terminal
61 STR (Reverse rotation command) 61, 62, 64 to 74, 76, 77 to 80, 85, 87 to 89, 92 to
T701 function selection
96, 9999
180 RL terminal function
0 RL (Low-speed operation command)
T702 selection
181 RM terminal function
1 RM (Middle-speed operation command)
T703 selection
182 RH terminal function
2 RH (High-speed operation command)
T704 selection
183 RT terminal function
3 RT (Second function selection)
T705 selection
184 AU terminal function
4 AU (Terminal 4 input selection)
T706 selection 0 to 20, 22 to 28, 37, 42 to 48, 50 to 53, 57 to 59,
185 JOG terminal 62, 64 to 74, 76, 77 to 80, 85, 87 to 89, 92 to 96,
5 JOG (Jog operation selection) 9999
T707 function selection
186 CS terminal function CS (Selection of automatic restart after
6
T708 selection instantaneous power failure / flying start)
187 MRS terminal 24*1 MRS (Output stop)
T709 function selection 10 *2 X10 (Inverter run enable)
188 STOP terminal
25 STP (STOP) (Start self-holding selection)
T710 function selection
189 RES terminal
62 RES (Inverter reset)
T711 function selection
Initial
Pr. Name Setting range Description
value
699 5 to 50 ms Set the time delay for the input terminal response.
Input terminal filter 9999
T740 9999 No filter for the input terminal
*1 The initial value is for standard models and IP55 compatible models.
*2 The initial value is for separated converter types.
496 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Signal Refer to
Setting Function Related parameter
name page
Selection of automatic restart after instantaneous power failure / Pr.57, Pr.58, Pr.162 to
597, 604
1
flying start Pr.165, Pr.299, Pr.611
6 CS
Pr.57, Pr.58, Pr.135 to
Electronic bypass function 532
Pr.139, Pr.159
7 OH External thermal relay input*3 Pr.9 394
2
15-speed selection (Combination with multi-speeds of RL, RM, and Pr.4 to Pr.6, Pr.24 to Pr.27,
8 REX 391
RH) Pr.232 to Pr.239
9 X9 Third function selection Pr.110 to Pr.116 500 3
10 X10 Inverter run enable (FR-HC2/FR-CV/FR-CC2 connection) Pr.30, Pr.70, Pr.599 689
FR-HC2/FR-CC2 connection, instantaneous power failure
11 X11 Pr.30, Pr.70 689
detection
12 X12 PU operation external interlock Pr.79 370 4
13 X13 External DC injection brake operation start Pr.10 to Pr.12 681
Pr.127 to Pr.134, Pr.575 to
14 X14 PID control valid 570
Pr.577
15 BRI Brake opening completion Pr.278 to Pr.285 541
5
16 X16 PU/External operation switchover (External operation with X16-ON) Pr.79, Pr.340 370
Load pattern selection forward/reverse rotation boost (For
17 X17 Pr.14 674
18 X18
constant-torque with X17-ON)
V/F switchover (V/F control with X18-ON) Pr.80, Pr.81, Pr.800 215
6
19 X19 Load torque high-speed frequency Pr.270 to Pr.274 549
20 X20 S-pattern acceleration/deceleration C switchover Pr.380 to Pr.383 354
22 X22 Orientation command (for Vector control compatible options) *4*6 Pr.350 to Pr.369 554 7
23 LX Pre-excitation/servo ON *5 Pr.850 681
Output stop Pr.17 499
24 MRS
Electronic bypass function
Pr.57, Pr.58, Pr.135 to
532 8
Pr.139, Pr.159
STP
25 Start self-holding selection Pr.250 502
(STOP)
26 MC Control mode switchover Pr.800 215 9
27 TL Torque limit selection Pr.815 235
28 X28 Start-time tuning start external input Pr.95 527
37
42
X37
X42
Traverse function selection
Torque bias selection 1
Pr.592 to Pr.597
Pr.840 to Pr.845
551
255
10
43 X43 Torque bias selection 2 Pr.840 to Pr.845 255
Pr.820, Pr.821, Pr.830,
44 X44 P/PI control switchover (P control with X44-ON) 244
Pr.831
45 BRI2 Second brake sequence open completion Pr.641 to Pr.648 541
46 TRG Trace trigger input Pr.1020 to Pr.1047 616
47 TRC Trace sampling start/end Pr.1020 to Pr.1047 616
Pr.261 to Pr.266, Pr.294,
48 X48 Power failure stop external 610
Pr.668
50 SQ Sequence start Pr.414 614
51 X51 Fault clear Pr.414 614
52 X52 Cumulative pulse monitor clear (for Vector control compatible plug-
in options)
Pr.635 306
53 X53 Cumulative pulse monitor clear (control terminal option) (for FR-
A8TP)
57 JOGF JOG forward rotation command Pr.15, Pr.16 390
58 JOGR JOG reverse rotation command Pr.15, Pr.16 390
Pr.291, Pr.419 to Pr.430,
59 CLRN NET position pulse clear 305
Pr.464
Forward rotation command (assignable to the STF terminal
60 STF Pr.250 502
(Pr.178) only)
Reverse rotation command (assignable to the STR terminal
61 STR Pr.250 502
(Pr.179) only)
62 RES Inverter reset Pr.75 320
64 X64 PID forward/reverse action switchover Pr.127 to Pr.134 570
65 X65 PU/NET operation switchover (PU operation with X65-ON) Pr.79, Pr.340 370
66 X66 External/NET operation switchover (NET operation with X66-ON) Pr.79, Pr.340 370
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
497
Signal Refer to
Setting Function Related parameter
name page
Command source switchover (command by Pr.338 or Pr.339
67 X67 Pr.338, Pr.339 380
enabled with X67-ON)
Pr.291, Pr.419 to Pr.430,
68 NP Simple position pulse train sign 305
Pr.464
Pr.291, Pr.419 to Pr.430,
69 CLR Simple position droop pulse clear 305
Pr.464
70 X70 DC feeding operation permission*7 Pr.30 689
71 X71 DC feeding cancel *7 Pr.30 689
Pr.127 to Pr.134, Pr.575 to
72 X72 PID P control switchover 570
Pr.577
Pr.127 to Pr.134, Pr.575 to
73 X73 Second PID P control switchover 570
Pr.577
74 X74 Magnetic flux decay output shutoff Pr.850 683
76 X76 Proximity dog Pr.1282 to Pr.1288 288
77 X77 Pre-charge end command Pr.760 to Pr.764 587
78 X78 Second pre-charge end command Pr.765 to Pr.769 587
79 X79 Second PID forward/reverse action switchover Pr.753 to Pr.758 570
80 X80 Second PID control valid Pr.753 to Pr.758 570
85 X85 SSCNET III communication disabled (for FR-A8NS) *6 Pr.499 —
87 X87 Sudden stop Pr.464 to Pr.494 288
88 LSP Upper stroke limit (for FR-A8NS)*6 — —
89 LSN Lower stroke limit (for FR-A8NS)*6 — —
92 X92 Emergency stop Pr.1103 349
93 X93 Torque control selection Pr.1113 274
94 X94 Control signal input for main circuit power supply MC Pr.30, Pr.137, Pr.248, Pr.254 538
95 X95 Converter unit fault input Pr.57, Pr.58, Pr.135 to
532
96 X96 Converter unit fault (E.OHT, E.CPU) input Pr.139, Pr.159
9999 — No function — —
*1 When Pr.59 Remote function selection ≠ "0", functions of the RL, RM, and RH signals are changed as shown in the table.
*2 When Pr.270 Stop-on contact/load torque high- speed frequency control selection = "1, 3, 11, or 13", functions of the RL and RT signals
are changed as shown in the table.
*3 The OH signal is activated when the relay contact is open.
*4 When a stop position command is input from outside for orientation control, the FR-A8AX (16-bit digital input option) is required.
*5 Servo ON is enabled in the position control mode.
*6 Available when the plug-in option is connected. For details, refer to the Instruction Manual of each option.
*7 The setting is available only for standard models and IP55 compatible models.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• The priorities of the speed commands are defined as follows: JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the Inverter run enable (X10) signal is not assigned, or when the PU operation external interlock (X12) signal is not
assigned while Pr.79 Operation mode selection = "7", the MRS signal performs the same function.
• The same terminals are used to assign the multi-speed (7-speed) setting and the remote setting. The multi-speed setting and
the remote setting cannot be assigned separately.
• When the Load pattern selection forward/reverse rotation boost (X17) signal is not assigned, the RT signal performs the same
function.
• When Pr.419 = "2" (simple pulse train position command), the terminal JOG is used for the simple position pulse train input
regardless of the setting in Pr.291 Pulse train I/O selection.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
498 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Adjusting the response of input terminals (Pr.699)
• Response of the input terminals can be delayed in a range between 5 to 50 ms. (The following is the operation example 1
of the STF signal.)
Output frequency
ON OFF
Time 3
STF
Pr.699 9999
Pr.699 Pr.699 4
NOTE
• The Pr.699 setting is invalid (no filter) for the following signals.
— Input signals which are already in the ON state when the power is turned ON 5
— Input signals used for the PLC function
— Inverter run enable (X10) signal, Simple position pulse train sign (NP) signal, Simple position droop pulse clear (CLR) signal
6
5.12.9 Inverter output shutoff
The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be selected. 7
Initial
Pr. Name Setting range Description
value
0 Normally open input
2 Normally closed input (NC contact input specification)
8
17
MRS input selection 0 External terminal: Normally closed input (NC contact input
T720
4 specification)
Communication: Normally open input
9
Output shutoff signal (MRS signal)
MRS MRS
SD (PC) SD (PC)
Time
MRS signal ON
STF (STR)
signal ON
• When the Output stop (MRS) signal is turned ON while operating the inverter, the inverter output is instantaneously shut
off.
• The response time of the MRS signal is within 2 ms.
• The MRS signal is used in the following cases.
Application Description
To stop the motor using a mechanical brake (e.g.
The inverter output is shut off when the mechanical brake operates.
electromagnetic brake)
To provide interlock to disable the motor operation by the With the MRS signal ON, the motor cannot be driven by the inverter even if
inverter the start signal is input to the inverter.
When the start signal is turned OFF, the inverter decelerates the motor to
To coast the motor to a stop a stop in the preset deceleration time, but when the MRS signal is turned
ON, the motor coasts to a stop.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
499
MRS signal logic inversion (Pr.17 = "2")
• When "2" is set in Pr.17, the input specification of the MRS signal is changed to normally closed (NC contact). The inverter
will shut off the output when the MRS signal is turned ON (when the contact is opened).
NOTE
• The MRS signal is assigned to terminal MRS in the initial status. By setting "24" in any of Pr.178 to Pr.189 (Input terminal
function selection), the MRS signal can be assigned to the other terminal.
• When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
• The MRS signal is valid regardless of whether it is input through the external terminal or via network, but when the MRS signal
is used as the Inverter run enable (X10) signal, input the signal through the external terminal.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
500 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
• The following are the examples of the applications of the second (third) functions.
Switching between regular use and emergency use
Switching between heavy load and light load
1
Changing the acceleration/deceleration time
Switching characteristics of main motor and sub motor
Connection diagram example for the second functionExample of the second acceleration/deceleration time
2
Setting value "0" (initial value)
Inverter
Output frequency
Start STF/STR
Second function selection RT
High speed RH
Acceleration
time is applied 4
Middle speed Time
RM
SD RT
RH 5
RM
• Turning ON the RT signal enables the second function, and turning ON the X9 signal enables the third function. The
following table shows the functions which can be changed to the second or third function.
6
First function Second function Third function
Function Refer to page
Parameter number Parameter number Parameter number
Torque boost Pr.0 Pr.46 Pr.112 672
7
Base frequency Pr.3 Pr.47 Pr.113 673
Acceleration time Pr.7 Pr.44 Pr.110 349
Deceleration time Pr.8 Pr.44, Pr.45 Pr.110, Pr.111 349 8
Electronic thermal O/L relay Pr.9 Pr.51 *2
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
501
*2 When the RT signal is OFF, the first function is valid. When it is ON, the second function is valid.
NOTE
• The RT signal is assigned to terminal RT in the initial status. By setting "3" in any of Pr.178 to Pr.189 (Input terminal function
selection), the RT signal can be assigned to the other terminal.
• When both the RT and X9 signals are ON, the X9 signal (third function) is valid.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 496
Forward
rotation start STF Start signal STF
Reverse Forward
rotation rotation
rotation rotation
Output frequency
Output frequency
Time Time
ON ON
STF STF
ON ON
STR STR
2-wire type connection example (Pr.250 = "9999") 2-wire type connection example (Pr.250 = "8888")
502 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
NOTE
• By setting Pr.250= "0 to 100, 1000 to 1100", the motor will coast to a stop when the start command is turned OFF. (Refer to 1
page 688.)
• The STF and STR signals are assigned to the STF and STR terminals in the initial status. The STF signal can be assigned to
terminal STF only using Pr.178 STF terminal function selection, and the STR signal can be assigned to terminal STR only
using Pr.179 STR terminal function selection. 2
9
Reverse Forward
rotation rotation
rotation rotation
Output frequency
Output frequency
Time Time
10
ON ON ON
STF STF
ON
STR STR ON
NOTE
• The STP (STOP) signal is assigned to terminal STP (STOP) in the initial status. Set "25" in any of Pr.178 to Pr.189 to assign
the STP (STOP) signal to another terminal.
• When the JOG operation is enabled by turning ON the JOG signal, the STOP signal will be disabled.
• Even when the output is stopped by turning ON the MRS signal, the self-holding function is not canceled.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
503
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)page 391
Pr.178 to Pr.189 (Input terminal function selection)page 496
504 5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
5.13 (C) Motor constant parameters 1
5. PARAMETERS
5.13 (C) Motor constant parameters
505
Setting the applied motor
• Refer to the following list and set the parameters according to the applied motor.
Electronic thermal O/L relay
Motor constant value range when performing function
Pr.71 Pr.450 Motor
offline auto tuning (increment) Constant-
Standard PM
torque
0
Standard motor (such as SF-JR) ○
(Pr.71 initial value)
Constant-torque motor (SF-
JRCA, etc.) Pr.82 (Pr.455) and Pr.859 (Pr.860)
1 ○
SF-V5RU (other than the 1500 r/ • 0 to 500 A, 9999 (0.01 A)*2
min series) • 0 to 3600 A, 9999 (0.1 A)*3
Standard motor (such as SF-JR) Pr.90 (Pr.458), Pr.91 (Pr.459)
2 — Adjustable 5 points V/F (refer to • 0 to 50 Ω, 9999 (0.001 Ω)*2 ○
page 679) *3
• 0 to 400 mΩ, 9999 (0.01 mΩ)
Mitsubishi Electric standard motor Pr.92 (Pr.460), Pr.93 (Pr.461) (Induction motor)
20 ○
(SF-JR 4P 1.5kW or lower)
• 0 to 6000 mH, 9999 (0.1 mH)*2
Vector control dedicated motor
• 0 to 400 mH, 9999 (0.1 mH)*3
30 SF-V5RU (1500 r/min series) ○
Pr.92 (Pr.460), Pr.93 (Pr.461) (PM motor)
SF-THY
• 0 to 500 mH, 9999 (0.01 mH)*2
Mitsubishi Electric high-efficiency
40 • 0 to 50 mH, 9999 (0.001 mH)*3 ○
motor SF-HR
Pr.94 (Pr.462)
Mitsubishi Electric constant-
50 • 0 to 100%, 9999 (0.1%)*2 ○
torque motor SF-HRCA
*3
Mitsubishi Electric high- • 0 to 100%, 9999 (0.01%)
70 performance energy-saving motor Pr.706 (Pr.738) ○
SF-PR • 0 to 5000 mV (rad/s), 9999
(0.1 mV (rad/s))
330*1 IPM motor MM-CF ○
8090 IPM motor (other than MM-CF) ○
9090 SPM motor ○
3 (4)*4 Standard motor (such as SF-JR) ○
Constant-torque motor (SF-
JRCA, etc.)
13 (14)*4 SF-V5RU (other than the 1500 r/
○
min series)
Mitsubishi Electric standard motor
23 (24)*4 (SF-JR 4P 1.5kW or lower)
○
506 5. PARAMETERS
5.13 (C) Motor constant parameters
Electronic thermal O/L relay
Motor constant value range when performing function
Pr.71 Pr.450 Motor
offline auto tuning (increment)
Standard
Constant-
PM
1
torque
5. PARAMETERS
5.13 (C) Motor constant parameters
507
Function RT signal ON (second motor) RT signal OFF (first motor)
Electronic thermal O/L relay Pr.51 Pr.9
Applied motor Pr.450 Pr.71
Control method selection Pr.451 Pr.800
Motor capacity Pr.453 Pr.80
Number of motor poles Pr.454 Pr.81
Motor excitation current Pr.455 Pr.82
Rated motor voltage Pr.456 Pr.83
Rated motor frequency Pr.457 Pr.84
Motor constant (R1) Pr.458 Pr.90
Motor constant (R2) Pr.459 Pr.91
Motor constant (L1)/d-axis inductance (Ld) Pr.460 Pr.92
Motor constant (L2)/q-axis inductance (Lq) Pr.461 Pr.93
Motor constant (X) Pr.462 Pr.94
Auto tuning setting/status Pr.463 Pr.96
Frequency search gain Pr.560 Pr.298
Online auto tuning selection Pr.574 Pr.95
Induced voltage constant (phi f) Pr.738 Pr.706
Motor Ld decay ratio Pr.739 Pr.711
Motor Lq decay ratio Pr.740 Pr.712
Starting resistance tuning compensation Pr.741 Pr.717
Starting magnetic pole position detection pulse
Pr.742 Pr.721
width
Maximum motor frequency Pr.743 Pr.702
Motor inertia (integer) Pr.744 Pr.707
Motor inertia (exponent) Pr.745 Pr.724
Motor protection current level Pr.746 Pr.725
Torque current/Rated PM motor current Pr.860 Pr.859
NOTE
• The RT signal is the Second function selection signal. The RT signal also enables other second functions. (Refer to page 500.)
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
NOTE
• When selecting the automatic change of torque boost for the SF-PR motor, set Pr.14 Load pattern selection = "0 (initial
value)".
• When the Pr.0 setting is changed from its initial value, the automatic change is not performed.
508 5. PARAMETERS
5.13 (C) Motor constant parameters
Pr.12 value (%) after automatic
Inverter Pr.0 value (%) after automatic change
change 1
Constant-
Standard
torque SF-PR*3 Constant-
Motor*1 Standard
FR-A820-[] FR-A840-[] motor *2 torque SF-PR *3
Motor*1
SLD/ ND/ SLD/ ND/ Pr.81 ≠
Pr.81 = 2 Pr.81 = 4 Pr.81 = 6
motor*2 2
LD HD LD HD 2, 4, 6
00046 (0.4K) 00023 (0.4K) 6 6 4 4 4 4 4 4 4
00077 (0.75K) 00038 (0.75K) 6 6 4 7.4 6 6.4 4 4 4
00105 (1.5K) 00052 (1.5K) 4 4 3 5.8 5 3.7 4 4 2.5 3
00167 (2.2K) 00083 (2.2K) 4 4 2.5 6 4.5 3.3 4 4 2.5
00250 (3.7K) 00126 (3.7K) 4 4 2.5 6.4 4.5 4.2 4 4 2.5
00340 (5.5K) 00170 (5.5K) 3 2 2 4.5 3.7 3.3 4 2 2 4
00490 (7.5K) 00250 (7.5K) 3 2 2 4.4 4.5 3.8 4 2 2
00630 (11K) 00310 (11K) 2 2 1.5 3.5 3.3 3.5 2 2 1.5
00770 (15K) 00380 (15K) 2 2 1.5 4.5 3 3.5 2 2 1.5
00930 (18.5K) 00470 (18.5K) 2 2 1.5 4 3.2 3 2 2 1.5 5
01250 (22K) 00620 (22K) 2 2 1.5 2.5 3.4 3 2 2 1
01540 (30K) 00770 (30K) 2 2 1 3 2 2.5 2 2 1
01870 (37K)
02330 (45K)
00930 (37K)
01160 (45K)
2
1.5 2
2
1.5 2
1
1
2
2
2.5
2
2.6
2.4
2
2
2
2
1
1
6
03160 (55K) 01800 (55K) 1.5 2 1.5 2 0.7 2 2 0.7 2 2 1
03800(75K) 02160(75K)
or higher or higher
1 1 1 1 1 1 1 1 1
7
*1 Pr.71 = "0, 2 to 6, 20, 23, 24, 40, 43, or 44" (standard motor)
*2 Pr.71 = "1, 13 to 16, 50, 53, or 54" (constant-torque motor)
*3 Pr.71 = "70, 73, or 74" (SF-PR)
8
NOTE
• When the Pr.0 and Pr.12 settings are changed from their initial values, the automatic change is not performed.
• When the SF-PR motor is selected (Pr.71 = "70, 73, or 74"), the output current may become large due to a small load by setting
Pr.81 Number of motor poles according to the number of the SF-PR motor poles. 9
• When the SF-PR motor is used, the output current tends to increase compared with the case where the SF-JR or SF-HR motor
is used. Depending on the load conditions, the output current may increase even though the torque boost value has been
automatically changed. When the protective function such as the electronic thermal O/L relay (E.THT, E.THM) or stall 10
prevention (OL, E.OLT) is activated, adjust the Pr.0 Torque boost according to the load.
CAUTION
• Make sure to set this parameter correctly according to the motor used. Incorrect setting may cause the motor and the
inverter to overheat and burn.
Parameters referred to
Pr.0 Torque boostpage 672
Pr.12 DC injection brake operation voltagepage 681
Pr.14 Load pattern selectionpage 674
Pr.96 Auto tuning setting/statuspage 509
Pr.100 to Pr.109 (Adjustable 5 points V/F)page 679
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.684 Tuning data unit switchoverpage 509
Pr.800 Control method selectionpage 215
5. PARAMETERS
5.13 (C) Motor constant parameters
509
For the offline auto tuning for a PM motor, refer to page 519.
Initial
Pr. Name Setting range Description
value
684 Tuning data unit 0 Internal data converted value
0
C000 switchover 1 The value is indicated in A, Ω, mH, or %.
0 to 6, 13 to 16, 20, 23, 24,
30, 33, 34, 40, 43, 44, 50,
71 By selecting a motor, the thermal characteristic and motor
Applied motor 0 53, 54, 70, 73, 74, 330, 333,
C100 constant of each motor are set.
334, 8090, 8093, 8094,
9090, 9093, 9094
0.4 to 55 kW*2
80 Set the applied motor capacity.
Motor capacity 9999 0 to 3600 kW*3
C101
9999 V/F control
81 Number of motor 2, 4, 6, 8, 10, 12 Set the number of motor poles.
9999
C102 poles 9999 V/F control
Inverter 0 to 500 A*2
9 Electronic rated Set the rated motor current.
C103 thermal O/L relay 0 to 3600 A*3
current*1
83 Rated motor 200/
0 to 1000 V Set the rated motor voltage (V).
C104 voltage 400 V*4
84 Rated motor 10 to 400 Hz Set the rated motor frequency (Hz).
9999
C105 frequency 9999 The setting value of Pr.3 Base frequency is used.
707 Motor inertia Set the motor inertia.
9999 10 to 999, 9999
C107 (integer) 9999: The constant value of Mitsubishi Electric motor (SF-PR,
724 Motor inertia SF-JR, SF-HR, SF-JRCA, SF-HRCA, SF-V5RU (1500 r/min
9999 0 to 7, 9999 series) and so on) is used.
C108 (exponent)
0 No offline auto tuning
1 Offline auto tuning is performed without rotating the motor.
96 Auto tuning
0 Offline auto tuning is performed without rotating the motor (V/F
C110 setting/status 11
control, IPM motor MM-CF). (Refer to page 606.)
101 Offline auto tuning is performed while rotating the motor.
90 Motor constant 0 to 50 Ω, 9999*5
9999
C120 (R1) 0 to 400 mΩ, 9999*3*5
91 Motor constant 0 to 50 Ω, 9999*2*5
9999
C121 (R2) 0 to 400 mΩ, 9999*3*5
Motor constant 0 to 6000 mH, 9999*2*5
92
(L1)/d-axis 9999
C122 0 to 400 mH, 9999*3*5 Tuning data (The value measured by offline auto tuning is
inductance (Ld)
Motor constant automatically set.)
93 0 to 6000 mH, 9999*2*5
(L2)/q-axis 9999 9999: The constant value of Mitsubishi Electric motor (SF-PR,
C123 0 to 400 mH, 9999*3*5 SF-JR, SF-HR, SF-JRCA, SF-HRCA, SF-V5RU (1500 r/min
inductance (Lq)
series) and so on) is used.
94 Motor constant
C124 (X)
9999 0 to 100%, 9999*5
510 5. PARAMETERS
5.13 (C) Motor constant parameters
Initial
Pr. Name Setting range Description
value
454
Number of 2, 4, 6, 8, 10, 12 Set the number of poles of the second motor. 1
second motor 9999
C202 9999 V/F control
poles
0 to 500 A*2
51 Second electronic
9999 0 to 3600 A*3
This function is enabled when the RT signal is ON.
Set the rated motor current.
2
C203 thermal O/L relay
9999 Second electronic thermal O/L relay disabled.
456 Rated second 200/
C204 motor voltage 400 V*4
0 to 1000 V Set the rated voltage (V) of the second motor.
3
457 Rated second 10 to 400 Hz Set the rated frequency (Hz) of the second motor.
9999
C205 motor frequency 9999 The Pr.84 Rated motor frequency setting is used.
744
C207
Second motor
inertia (integer)
9999 10 to 999, 9999 Set the motor inertia of the second motor. 4
9999: The constant value of Mitsubishi Electric motor (SF-PR,
745 Second motor
9999 0 to 7, 9999 SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
C208 inertia (exponent)
0 No auto tuning for the second motor. 5
Offline auto tuning is performed without rotating the second
1
Second motor motor.
463
auto tuning 0 Offline auto tuning is performed without rotating the motor (V/F
C210 11
setting/status control, IPM motor MM-CF). (Refer to page 606.) 6
Offline auto tuning is performed while rotating the second
101
motor.
458 Second motor 0 to 50 Ω, 9999*2*5
C220 constant (R1)
9999
0 to 400 mΩ, 9999*3*5
7
459 Second motor 0 to 50 Ω, 9999*2*5
9999
C221 constant (R2) 0 to 400 mΩ, 9999*3*5
Second motor 0 to 6000 mH, 9999*2*5
8
460 constant (L1) / d-
9999
C222 axis inductance 0 to 400 mH, 9999*3*5
(Ld)
Second motor 0 to 6000 mH, 9999*2*5
Tuning data of the second motor
(The value measured by offline auto tuning is automatically
9
461 constant (L2) / q- set.)
9999
C223 axis inductance 0 to 400 mH, 9999*3*5 9999: The constant value of Mitsubishi Electric motor (SF-PR,
(Lq) SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
462 Second motor 10
C224 constant (X)
9999 0 to 100%, 9999*5
5. PARAMETERS
5.13 (C) Motor constant parameters
511
• The function is enabled under Advanced magnetic flux vector control, Real sensorless vector control, and Vector control.
• By using the offline auto tuning function, the optimum operation characteristics are obtained for a motor other than Mitsubishi
Electric standard motors (SF-JR 0.4 kW or higher), high-efficiency motors (SF-HR 0.4 kW or higher), Mitsubishi Electric
constant-torque motors (SF-JRCA 4P, SF-HRCA 0.4 kW to 55 kW), Mitsubishi Electric high-performance energy-serving
motor (SF-PR), or Vector control dedicated motors (SF-V5RU (1500 r/min series)), such as an induction motor of other
manufacturers, SF-JRC, or SF-TH, or with a long wiring length (30 m or longer).
• Tuning is enabled even when a load is connected to the motor.
• During offline auto tuning, the motor rotation can be locked (Pr.96 = "1") or unlocked (Pr.96 = "101"). The tuning is more
accurate when the motor can rotate (unlocked).
• Reading/writing of the motor constants tuned by offline auto tuning are enabled. The offline auto tuning data (motor constants)
can be copied to another inverter using the operation panel.
• The offline auto tuning status can be monitored on the operation panel or the parameter unit.
512 5. PARAMETERS
5.13 (C) Motor constant parameters
Setting
• To perform tuning, set the following parameters about the motor. 1
First Second
motor motor Name Initial value Description
Pr. Pr.
80 453 Motor capacity 9999 (V/F control) Set the motor capacity (kW). 2
81 454 Number of motor poles 9999 (V/F control) Set the number of motor poles (2 to 12).
Control method Set this parameter under Vector control or Real sensorless vector
800 451 20
selection
Electronic thermal O/L
control.
3
9 51 Inverter rated current Set the rated motor current (A).
relay
83 456 Rated motor voltage 200 V / 400 V*1 Set the rated motor voltage (V) printed on the motor's rating plate.*2
84 457
Rated motor
9999 Set the rated motor frequency (Hz).*2When the setting is "9999", the 4
frequency Pr.3 Base frequency setting is used.
Set this parameter according to the motor.*3 Three types of motor
71 450 Applied motor 0 (standard motor) constant setting ranges, units and tuning data can be stored according
to settings.
5
Set "1" or "101".
1: Tuning is performed without rotating the motor. (Excitation noise
Auto tuning setting/
96 463
status
0 occurs at this point.)
101: Tuning is performed while rotating the motor. The motor can rotate 6
up to the speed near the rated motor frequency.
*1 The initial value differs according to the voltage class (200 V / 400 V).
*2
*3
For the settings for the SF-V5RU, refer to page 93.
Set Pr.71 Applied motor according to the motor to be used and the motor constant setting range. According to the Pr.71 setting, the range of
7
the motor constant parameter setting values and units can be changed. (For other setting values of Pr.71, refer to page 505.)
Pr.71 setting
Motor constant
Motor constant
8
Motor parameter Motor constant parameter
parameter
mH, %, and A unit Ω, mΩ, and A unit setting
internal data setting
setting
Mitsubishi Electric SF-JR, SF-TH 0 (initial value) 3 (4) — 9
standard motor SF-JR 4P 1.5 kW or lower 20 23 (24) —
Mitsubishi Electric SF-HR 40 43 (44) —
high-efficiency motor Others
SF-JRCA 4P, SF-TH (constant-
0 (initial value) 3 (4) —
10
1 13 (14) —
Mitsubishi Electric torque)
constant-torque motor SF-HRCA 50 53 (54) —
Others (SF-JRC, etc.) 1 13 (14) —
Mitsubishi Electric
high-performance SF-PR 70 73 (74) —
energy-saving motor
SF-V5RU (1500 r/min series)
30 33 (34) —
Vector control SF-THY
dedicated motor SF-V5RU (other than the 1500 r/min
1 13 (14) —
series)
Other manufacturer's 5 (Wye connection motor)
— 0 (initial value) 3 (4)
standard motor 6 (delta connection motor)
Other manufacturer's 15 (Wye connection motor)
— 1 13 (14)
constant-torque motor 16 (delta connection motor)
NOTE
• When the SF-V5RU (other than the 1500 r/min series) is used, be sure to perform auto tuning after setting "1, 13, or 14" in
Pr.71 and setting Pr.83 and Pr.84.
• When Pr.11 DC injection brake operation time = "0" or Pr.12 DC injection brake operation voltage = "0", offline auto
tuning is performed at the initial setting of Pr.11 or Pr.12.
• When position control is selected (Pr.800 = "3 or 5" (when the MC signal is OFF)), offline auto tuning is not performed.
• If "wye connection" or "delta connection" is incorrectly selected in Pr.71, Advanced magnetic flux vector control, Real
sensorless vector control, and Vector control are not performed properly.
5. PARAMETERS
5.13 (C) Motor constant parameters
513
• For tuning accuracy improvement, set the following parameters when the motor constants are known in advance.
Mitsubishi Electric motor
First motor Second
Name (SF-JR, SF-HR, SF-JRCA, Other motors
Pr. motor Pr.
SF-HRCA, SF-V5RU)
707 744 Motor inertia (integer) Motor inertia*4Jm = Pr.707 × 10^(-
9999 (initial value)
724 745 Motor inertia (exponent) Pr.724) (kg·m2)
*4 The setting is valid only when a value other than "9999" is set in both Pr.707 (Pr.744) and Pr.724 (Pr.745).
Performing tuning
• Before performing tuning, check the monitor display of the operation panel or parameter unit if the inverter is in the state ready
for tuning. The motor starts by turning ON the start command while tuning is unavailable
NOTE
• Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of the MRS signal.
• To force tuning to end, use the MRS or RES signal or press on the operation panel.
(Turning OFF the start signal (STF signal or STR signal) also ends tuning.)
• During offline auto tuning, only the following I/O signals are valid (initial value).
Input terminals <valid signals>: STP (STOP), OH, MRS, RT, RES, STF, STR, S1, and S2
Output terminals: RUN, OL, IPF, FM/CA, AM, A1B1C1, and So (SO)
• When the rotation speed and the output frequency are selected for terminals FM/CA and AM, the progress status of offline
auto tuning is output in 15 steps from FM/CA and AM.
• Do not perform ON/OFF switching of the Second function selection (RT) signal during offline auto tuning. Auto tuning will not
be performed properly.
• Setting offline auto tuning (Pr.96 Auto tuning setting/status = "1 or 101") will make pre-excitation invalid.
• When the offline auto tuning with motor rotation is selected (Pr.96 Auto tuning setting/status = "101"), take caution and
ensure safety against the rotation of the motor.
• Since the Inverter running (RUN) signal turns ON when tuning is started, pay close attention especially when a sequence which
releases a mechanical brake by the RUN signal has been designed.
• When executing offline auto tuning, input the operation command after switching ON the main circuit power (R/L1, S/L2, T/L3)
of the inverter.
• While Pr.79 Operation mode selection = "7", turn ON the PU operation external interlock (X12) signal for tuning in the PU
operation mode.
1 101
--- STOP PU --- STOP PU
PREV NEXT PREV NEXT
514 5. PARAMETERS
5.13 (C) Motor constant parameters
• Note: Offline auto tuning time (with the initial setting)
Offline auto tuning setting
No motor rotation (Pr.96 = "1")
Time
About 25 to 120 s (The time depends on the inverter capacity and motor type.)
1
About 40 s
With motor rotation (Pr.96 = "101") (The following offline auto tuning time is set according to the acceleration/deceleration time setting.
Offline auto tuning time = acceleration time + deceleration time + about 30 s) 2
• When offline auto tuning ends, press on the operation panel during PU operation. For External operation, turn OFF
the start signal (STF signal or STR signal).
This operation resets the offline auto tuning, and the PU's monitor display returns to the normal indication.
3
(Without this operation, next operation cannot be started.)
NOTE 4
• The motor constants measured once during offline auto tuning are stored as parameters and their data are held until offline
auto tuning is performed again. However, the tuning data is cleared when performing All parameter clear.
• Changing Pr.71 (Pr.450) after tuning completion will change the motor constant. For example, if "3" is set in Pr.71 after tuning
is performed with Pr.71 = "0", the tuning data becomes invalid. To use the tuned data, set "0" again in Pr.71.
5
• If offline auto tuning has ended in error (see the following table), motor constants are not set. Perform an inverter reset and
6
perform tuning again.
Calculation error.
Check the Pr.84 Rated motor frequency setting.
Check the settings of Pr.83 and Pr.84.
9
93
The motor is not connected. Check the motor wiring and make the setting again.
Rotation tuning frequency setting error
Check the Pr.1 Maximum frequency and Pr.31 to
94 (The frequency command for the tuning was given to exceed the
maximum frequency setting, or to be in the frequency jump range.)
Pr.36 Frequency jump settings. 10
• When tuning is ended forcibly by pressing or turning OFF the start signal (STF or STR) during tuning, offline auto
tuning does not end properly. (The motor constants have not been set.)
Perform an inverter reset and perform tuning again.
• When the rated power supply of the motor is 200/220 V (400/440 V) 60 Hz, set the rated motor current multiplied by 1.1 in
Pr.9 Electronic thermal O/L relay after tuning is complete.
• For a motor with a PTC thermistor, thermal protector, or other thermal detector, set "0" (motor overheat protection by
inverter invalid) in Pr.9 to protect the motor from overheating.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter starts
normal operation. Therefore, when the STF (STR) signal is ON, the motor starts forward (reverse) rotation.
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
CAUTION
• Note that the motor may start running suddenly.
• For performing offline auto tuning with motor rotation in vertical lift applications, etc., caution is required to avoid falling
due to insufficient torque.
5. PARAMETERS
5.13 (C) Motor constant parameters
515
Changing the motor constants
• The motor constants can be set directly when the motor constants are known in advance, or by using the data measured
during offline auto tuning.
• According to the Pr.71 (Pr.450) setting, the range of the motor constant parameter setting values and units can be
changed. The changed settings are stored in the EEPROM as the motor constant parameters.
Changing the motor constants (when setting the Pr.92 and Pr.93 motor
constants in units of mH)
• Set Pr.71 as follows.
Motor Pr.71 setting
SF-JR 0 (initial value)
Mitsubishi Electric standard motor
SF-JR 4P 1.5 kW or lower 20
Mitsubishi Electric high-efficiency motor
SF-HR 40
SF-JRCA 4P 1
Mitsubishi Electric constant-torque motor
SF-HRCA 50
Mitsubishi Electric high-performance
SF-PR 70
energy-saving motor
SF-V5RU (1500 r/min series) 30
Vector control dedicated motor
SF-V5RU (other than the 1500 r/min series) 1
• Use the following formula to find the Pr.94 setting value and set a desired value as the motor constant parameter.
M2
The setting value of Pr.94 =(1 - )×100(%)
L1×L2
R1 I1 I2
R1: Primary resistance
R2: Secondary resistance
I1: Primary leakage inductance
I2: Secondary leakage inductance
V M R2/S M: Excitation inductance
S: Slip
516 5. PARAMETERS
5.13 (C) Motor constant parameters
NOTE
• If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi Electric motors (SF-PR, SF-JR, SF-HR, SF- 1
JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
• Set desired values as the motor constant parameters. The display units of the read motor constants can be changed with 8
Pr.684 Tuning data unit switchover. Setting Pr.684 = "1" disables parameter setting changes.
Pr.684 = 0 (initial value) Pr.684 = 1
First motor
Pr.
Second
motor Pr.
Name
Setting range
Setting
Range indication
Unit
Initial
value
9
increments indication
Motor excitation 0 to 500 A, 9999*1 0.01 A*1
82 455
current 0 to 3600 A, 9999 *2 0.1 A*2 10
0 to 50 Ω, 9999*1 0.001 Ω*1
90 458 Motor constant (R1)
0 to 400 mΩ, 9999*2 0.01 mΩ*2
0 to 50 Ω, 9999*1 0.001 Ω*1
91 459 Motor constant (R2)
*2
0 to 400 mΩ, 9999 0.01 mΩ*2
Motor constant (L1)/ 0 to 6000 mH, 9999*1 0.1 mH*1
92 460 d-axis inductance 0 to ***, 9999 1
(Ld) 0 to 400 mH, 9999*2 0.01 mH*2
9999
Motor constant (L2)/ 0 to 6000 mH, 9999*1 0.1 mH*1
93 461 q-axis inductance
(Lq) 0 to 400 mH, 9999*2 0.01 mH*2
0.1%*1
94 462 Motor constant (X) 0 to 100%, 9999
0.01%*2
Torque current/ 0 to 500 A, 9999*1 0.01 A*1
859 860 Rated PM motor
current 0 to 3600 A, 9999*2 0.1 A*2
Frequency search
298 560 0 to 32767, 9999 1 0 to 32767, 9999 1
gain
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: To slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
5. PARAMETERS
5.13 (C) Motor constant parameters
517
• If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi Electric motors (SF-PR, SF-JR, SF-HR, SF-
JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
Changing the motor constants (when setting the Pr.92 and Pr.93 motor
constants in units of Ω)
• Set Pr.71 as follows.
Pr.71 setting
Applied motor
Wye connection motor Delta connection motor
Standard motor 5 6
Constant-torque motor 15 16
NOTE
• If "wye connection" or "delta connection" is incorrectly selected in Pr.71, Advanced magnetic flux vector control, Real
sensorless vector control, and Vector control are not performed properly.
• If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi Electric motors (SF-PR, SF-JR, SF-HR, SF-
JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
518 5. PARAMETERS
5.13 (C) Motor constant parameters
• Turning ON the RT signal enables the parameter settings for the second motor as follows.
Function
RT signal-ON
(second motor)
RT signal-OFF
(first motor)
1
Motor capacity Pr.453 Pr.80
Number of motor poles Pr.454 Pr.81
Motor excitation current Pr.455 Pr.82 2
Rated motor voltage Pr.456 Pr.83
Rated motor frequency Pr.457 Pr.84
Motor constant (R1) Pr.458 Pr.90
Motor constant (R2) Pr.459 Pr.91
3
Motor constant (L1)/d-axis inductance
Pr.460 Pr.92
(Ld)
Motor constant (L2)/q-axis inductance
(Lq)
Pr.461 Pr.93 4
Motor constant (X) Pr.462 Pr.94
Auto tuning setting/status Pr.463 Pr.96
Frequency search gain Pr.560 Pr.298 5
NOTE
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal. 6
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
7
Parameters referred to
Pr.1 Maximum frequencypage 407
Pr.9 Electronic thermal O/L relaypage 394
Pr.31 to Pr.36 Frequency jumppage 408 8
Pr.71 Applied motorpage 505
Pr.156 Stall prevention operation selectionpage 409
Pr.178 to Pr.189 (input terminal function selection)page 496
Pr.190 to Pr.196 (output terminal function selection)page 450
Pr.800 Control method selectionpage 215 9
5.13.3 Offline auto tuning for a PM motor (motor constant
tuning) 10
PM
Initial
Pr. Name Setting range Description
value
684 Tuning data unit 0 Internal data converted value
0
C000 switchover 1 The value is indicated in A, Ω, mH, or mV.
0 to 6, 13 to 16, 20, 23, 24,
30, 33, 34, 40, 43, 44, 50,
71 By selecting a motor, the thermal characteristic and motor
Applied motor 0 53, 54, 70, 73, 74, 330,
C100 constant of each motor are set.
333, 334, 8090, 8093,
8094, 9090, 9093, 9094
0.4 to 55 kW*2
80 Set the applied motor capacity.
Motor capacity 9999 0 to 3600 kW*3
C101
9999 V/F control
81 2, 4, 6, 8, 10, 12 Set the number of motor poles.
Number of motor poles 9999
C102 9999 V/F control
5. PARAMETERS
5.13 (C) Motor constant parameters
519
Initial
Pr. Name Setting range Description
value
Inverter 0 to 500 A*2
9 Electronic thermal O/L rated Set the rated motor current.
C103 relay 0 to 3600 A*3
current*1
83 200/
Rated motor voltage 0 to 1000 V Set the rated motor voltage (V).
C104 400 V*4
10 to 400 Hz Set the rated motor frequency (Hz).
520 5. PARAMETERS
5.13 (C) Motor constant parameters
Initial
Pr. Name Setting range Description
value
0.4 to 55 kW*2
1
453 Set the capacity of the second motor.
Second motor capacity 9999 0 to 3600 kW*3
C201
9999 V/F control
454 Number of second
9999
2, 4, 6, 8, 10, 12 Set the number of poles of the second motor. 2
C202 motor poles 9999 V/F control
0 to 500 A*2
51 Second electronic Set the rated current of the second motor.
C203 thermal O/L relay
9999 0 to 3600 A*3 3
9999 The second electronic thermal O/L relay is disabled.
456 Rated second motor 200 V/ 400
0 to 1000 V Set the rated voltage (V) of the second motor.
C204 voltage V*4
10 to 400 Hz Set the rated frequency (Hz) of the second motor. 4
The MM-CF constant is used when the IPM motor MM-CF is
457 Rated second motor
9999 selected for the second motor, and the inverter internal data is
C205 frequency 9999
used when a PM motor other than MM-CF is selected. Use the
correct setting according to the motor specification. 5
0 to 400 Hz Set the permissible speed (frequency) of the second motor.
The maximum frequency of an MM-CF motor when MM-CF is
743 Second motor
9999
C206 maximum frequency 9999
selected.
The Pr.457 setting is used when a motor other than MM-CF is
6
selected.
744 Second motor inertia
9999 10 to 999, 9999
C207
745
(integer)
Second motor inertia
Set the motor inertia of the second motor.
9999: The MM-CF inertia is used for the IPM motor MM-CF.
7
9999 0 to 7, 9999
C208 (exponent)
0, 101 No auto tuning for the second motor.
5. PARAMETERS
5.13 (C) Motor constant parameters
521
*3 For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
*4 The initial value differs according to the voltage class (200 V / 400 V).
*5 The setting range and unit change according to the Pr.71 (Pr.450) setting.
Setting
• To perform tuning, set the following parameters about the motor.
First motor Second Driving a PM motor Setting for
Name
Pr. motor Pr. other than MM-CF MM-CF
80 453 Motor capacity Motor capacity (kW)
81 454 Number of motor poles Number of motor poles (2 to 12) Set by the IPM parameter initialization.
9 51 Electronic thermal O/L relay Rated motor current (A) (Refer to page 225.)
84 457 Rated motor frequency Rated motor frequency (Hz)
Rated motor voltage (V)
83 456 Rated motor voltage Rated motor voltage (V)
written on the rating plate
8090, 8093 (IPM motor)
71 450 Applied motor 330, 333*1
9090, 9093 (SPM motor)*1
96 463 Auto tuning setting/status 1 11
*1 Set Pr.71 Applied motor according to the motor to be used. According to the Pr.71 setting, the range of the motor constant parameter setting
values and units can be changed. (For other setting values of Pr.71, refer to page 505.)
Pr.71 setting
Motor Motor constant parameter Motor constant parameter
Ω, mH, and A unit setting internal data setting
MM-CF 330 333 (334)
IPM motor
Other than MM-CF 8090 8093 (8094)
SPM motor 9090 9093 (9094)
NOTE
• Under PM sensorless vector control, tuning cannot be performed even when Pr.96 = "101". When the MM-CF is set to the
applied motor, tuning cannot be performed even when Pr.96 = "1 or 101".
522 5. PARAMETERS
5.13 (C) Motor constant parameters
• For tuning accuracy improvement, set the following parameters when the motor constants are known in advance.
First motor
Second
monitor Name
Setting for a PM motor Setting for 1
Pr. other than MM-CF MM-CF
Pr.
702 743 Maximum motor frequency Maximum motor frequency (Hz) 9999 (initial value)
707 744 Motor inertia (integer) Motor inertia *1
9999 (initial value) 2
724 745 Motor inertia (exponent) Jm = Pr.707 × 10^(-Pr.724) (kg·m2)
725 746 Motor protection current level Maximum current level of the motor (%) 9999 (initial value)
*1 The setting is valid only when a value other than "9999" is set in both Pr.707 (Pr.744) and Pr.724 (Pr.745).
3
Performing tuning
• Before performing tuning, check the monitor display of the operation panel or parameter unit if the inverter is in the state ready
4
for tuning. The motor starts by turning ON the start command while tuning is unavailable
5
• In the PU operation mode, press / on the operation panel.
For External operation, turn ON the start command (STF signal or STR signal). Tuning starts. 6
NOTE
• Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of the MRS signal.
7
• To force tuning to end, use the MRS or RES signal or press on the operation panel. (Turning OFF the start signal (STF
Pr.96 (Pr.463) 1 11 1 11
setting Operation panel (FR-DU08) display Parameter unit (FR-LU08) display
5. PARAMETERS
5.13 (C) Motor constant parameters
523
• When offline auto tuning ends, press on the operation panel during PU operation. For External operation, turn OFF
the start signal (STF signal or STR signal). This operation resets the offline auto tuning, and the PU's monitor display
returns to the normal indication. (Without this operation, next operation cannot be started.)
NOTE
• The motor constants measured once during offline auto tuning are stored as parameters and their data are held until offline
auto tuning is performed again. However, the tuning data is cleared when performing All parameter clear.
• Changing Pr.71 after tuning completion will change the motor constant. For example, if the Pr.71 setting is changed to "8093"
after tuned with Pr.71 = "8090", the tuning data become invalid. To use the tuned data, set "8090" again in Pr.71.
• If offline auto tuning has ended in error (see the following table), motor constants are not set.
Perform an inverter reset and perform tuning again.
Error display Error cause Countermeasures
8 Forced end Set Pr.96 (Pr.463)="1 or 11" and try again.
9 Inverter protective function operation Make the setting again.
Check for the power supply voltage fluctuation.
92 The converter output voltage fell to 75% of the rated voltage.
Check the Pr.84Rated motor frequency setting.
Calculation error
93 Check the motor wiring and make the setting again.
The motor is not connected.
Rotation tuning frequency setting error
(The frequency command for the tuning was given to exceed Check the Pr.1 Maximum frequency and Pr.31 to Pr.36
94
the maximum frequency setting, or to be in the frequency Frequency jump settings.
jump range.)
• When tuning is ended forcibly by pressing or turning OFF the start signal (STF or STR) during tuning, offline auto
tuning does not end properly. (The motor constants have not been set.)
Perform an inverter reset and perform tuning again.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter starts normal operation. Therefore, when the STF (STR) signal is ON, the motor starts
forward (reverse) rotation.
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed even when a protective function that performs a retry is activated.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
CAUTION
• Note that the motor may start running suddenly.
524 5. PARAMETERS
5.13 (C) Motor constant parameters
Parameters updated by tuning results after tuning
First motor Second
Name
Other than MM-CF V/F control, MM-CF
Description
1
Pr. motor Pr. Pr.96 (Pr.463) = 1 Pr.96 (Pr.463) = 11
90 458 Motor constant (R1) ○ ○ Resistance per phase
Motor constant (L1)/d-axis
92 460
inductance (Ld)
○ — d-axis inductance 2
Motor constant (L2)/q-axis
93 461 ○ — q-axis inductance
inductance (Lq)
711 739 Motor Ld decay ratio ○ — d-axis inductance decay ratio
712 740 Motor Lq decay ratio ○ — q-axis inductance decay ratio
3
Starting resistance tuning
717 741 ○ ○
compensation
When the setting value is
10000 or more: With polarity
4
Starting magnetic pole position
721 742 ○ — inversion for compensation,
detection pulse width
voltage pulse (Pr. setting
Torque current/Rated PM
minus 10000) μs
5
859 860 ○ —
motor current
96 463 Auto tuning setting/status ○ ○
5. PARAMETERS
5.13 (C) Motor constant parameters
525
NOTE
• If "9999" is set, tuning data will be invalid. The MM-CF constant is used for the IPM motor MM-CF, and the inverter internal
constant is used for a PM motor other than MM-CF.
• To change a motor induced voltage constant of PM motors, the setting in Pr.706 Induced voltage constant (phi f) or Pr.738
Second motor induced voltage constant (phi f) must be changed. If the constant after the change exceeds the setting range
of Pr.706 or Pr.738 (0 to 5000 mV (rad/s)), set Pr.1412 Motor induced voltage constant (phi f) exponent or Pr.1413
Second motor induced voltage constant (phi f) exponent. Set a value in the exponent n in the formula, Pr.706 (Pr.738) ×
10n [mV (rad/s)], to set the induced voltage constant (phi f).
• When Pr.71 (Pr.450) = "8093, 8094, 9093, or 9094", or Pr.1412 (Pr.1413) = "9999", the motor induced voltage constant is as
set in Pr.706 (Pr.738). (No exponent setting)
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: to slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
• If "9999" is set, tuning data will be invalid. The MM-CF constant is used for the IPM motor MM-CF, and the inverter internal
constant is used for a PM motor other than MM-CF.
• To change a motor induced voltage constant of PM motors, the setting in Pr.706 Induced voltage constant (phi f) or Pr.738
Second motor induced voltage constant (phi f) must be changed. If the constant after the change exceeds the setting range
of Pr.706 or Pr.738 (0 to 5000 mV (rad/s)), set Pr.1412 Motor induced voltage constant (phi f) exponent or Pr.1413 Second
motor induced voltage constant (phi f) exponent. Set a value in the exponent n in the formula, Pr.706 (Pr.738) × 10n [mV
(rad/s)], to set the induced voltage constant (phi f).
• When Pr.71 (Pr.450) = "8093, 8094, 9093, or 9094", or Pr.1412 (Pr.1413) = "9999", the motor induced voltage constant is as
set in Pr.706 (Pr.738). (No exponent setting)
526 5. PARAMETERS
5.13 (C) Motor constant parameters
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 394
Pr.71 Applied motorpage 505
Pr.178 to Pr.189 (Input terminal function selection)page 496
1
Pr.800 Control method selectionpage 215
If online auto tuning is selected under Advanced magnetic flux vector control, Real sensorless vector control, or Vector control,
favorable torque accuracy is retained by adjusting temperature even when the resistance value varies due to increase in the 3
motor temperature.
Pr. Name Initial value Setting range Description
0 No online auto tuning
4
95
Online auto tuning selection 0 1 Online auto tuning is performed at startup.
C111
2 Magnetic flux observer (continuous tuning)
574
Second motor online auto tuning 0 0 to 2
Select online auto tuning for the second motor. 5
C211 (The settings are the same as those in Pr.95.)
2. Check that Pr.96 Auto tuning setting/status = "3 or 103" (offline auto tuning completion). 9
3. Set Pr.95 Online auto tuning selection = "1" (online auto tuning at start).
Online auto tuning is enabled at the next start.
10
4. Check that the following parameters are set before starting operation.
Pr. Description
9 Rated motor current or electronic thermal O/L relay
71 Applied motor
80 Motor capacity (with the rated motor current equal to or less than the inverter rated current)*1
81 Number of motor poles
*1 If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
5. PARAMETERS
5.13 (C) Motor constant parameters
527
NOTE
• When performing the online auto tuning at start for a lift, consider using a brake sequence function for the brake opening timing
at a start, or tuning using the external terminal. The tuning takes about 500 ms at the most after starting. However, during this
time, it is possible that not enough torque is provided and caution is required to prevent the object from dropping. Use of the
Start-time tuning start external input (X28) signal is recommended to perform tuning. (Refer to page 528.)
• Perform online auto tuning at startup when the motor is stopped.
• The online auto tuning is disabled when the MRS signal is being input, the setting speed is Pr.13 Starting frequency or lower
(V/F control, Advanced magnetic flux vector control), an inverter fault is occurring, or the inverter's startup condition is not
satisfied.
• Online auto tuning does not operate during deceleration and restart from DC injection brake operation.
• It is disabled during JOG operation.
• If automatic restart after instantaneous power failure is selected, automatic restart is prioritized. (Online auto tuning at startup
is not performed during frequency search.)
If automatic restart after instantaneous power failure is used together, perform online auto tuning while stopping operation with
the X28 signal. (Refer to page 528.)
• Zero current detection and output current detection are enabled during online auto tuning.
• The RUN signal is not output during online auto tuning. The RUN signal is turned ON at operation startup.
• If the time between the inverter stop and restart is within 4 seconds, tuning is performed at startup but its result will not be
applied.
Time
X28signal ON
Start signal
528 5. PARAMETERS
5.13 (C) Motor constant parameters
While the motor is stopped While the X28 signal is OFF
1
Tuning is performed at start when X28 signal is OFF
ON ON ON ON ON (even when Y39 is ON).
X28 Signal OFF X28 Signal OFF
Y39 signal
OFF Y39 signal OFF
3
Y39 signal is OFF when the motor is stopped Tuning is not
and X28 is turned OFF. However if the performed if the
secondary magnetic flux exists after motor stop, Y39 signal is ON. OFF
the signal remains ON. Start signal
Start signal OFF
4
Output frequency
0Hz
Time
While the X28 signal is ON Switching motor 5
ON Second motor
X28 Signal OFF Motor First motor First motor
switching
6
Tuning is not performed at start since X28 signal
and Y39 signal is ON. RT signal ON
Tune
Tuning status OFF
Completed X28 signal
at starting
Tune
ON
Completed
Y39 signal OFF Tuning status
at starting Y39 turns OFF when the
driven motor is switched
7
ON ON
to the second motor
OFF
OFF Y39 signal
Start signal Y39 turns ON due
Secondary magnetic to the residual second
Start OFF
ON flux exists a few seconds magnetic flux at the
first motor.
8
signal
Output
frequency 0Hz Output
Time frequency
0Hz
Time
9
NOTE
• Even if the start signal is turned ON during zero speed control or servo lock, tuning is performed at startup. 10
• The Y39 signal remains ON after the motor is stopped as long as the second flux remains.
• The X28 signal is disabled while the Y39 signal is ON.
• The STF and STR signals are enabled after completing tuning at start.
• The Inverter running (RUN) signal is not turned ON during online auto tuning. The RUN signal is turned ON after starting up.
• This function is disabled under V/F control or PM sensorless vector control.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) or Pr.190 to Pr.196 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
NOTE
• Offline auto tuning is not necessary when magnetic flux observer is selected for SF-V5RU, SF-JR (with encoder), SF-HR (with
encoder), SF-JRCA (with encoder) or SF-HRCA (with encoder). (However, when the wiring length is long (30 m or longer as
a reference), perform offline auto tuning so that the resistance arises in the long wiring can be reflected to the operation.)
5. PARAMETERS
5.13 (C) Motor constant parameters
529
• Perform tuning using Pr.574 Second motor online auto tuning.
• Pr.574 is enabled when the Second function selection (RT) signal is turned ON.
Pr. Description
450 Applied motor
453 Motor capacity (with the rated motor current equal to or less than the inverter rated current)*1
454 Number of motor poles
*1 If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
NOTE
• The RT signal is the Second function selection signal. The RT signal also enables other second functions. (Refer to page 496.)
The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 394
Pr.71 Applied motorpage 505
Pr.80 Motor capacitypage 215, page 509, page 519
Pr.81 Number of motor polespage 215, page 509, page 519
Pr.96 Auto tuning setting/statuspage 509, page 519
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.800 Control method selectionpage 215
Signal loss detection (E.ECT) is turned ON to shut off the inverter output when the encoder signal is lost during encoder
feedback control or orientation control operation or under Vector control.
Pr. Name Initial value Setting range Description
376 855 Encoder signal loss 0 Signal loss detection disabled
detection enable/ 0
C148*1 C248*2 disable selection
1 Signal loss detection enabled
*1 The setting is available when a Vector control compatible plug-in option is installed.
*2 These parameters are available when the control terminal option (FR-A8TP) is installed.
530 5. PARAMETERS
5.13 (C) Motor constant parameters
5.14 (A) Application parameters 1
P.A600 to P.A607,
Pr.127 to Pr.134, Pr.553, 9
Pr.554, Pr.575 to Pr.577,
P.A610 to P.A615,
Pr.609, Pr.610, Pr.753 to
P.A621 to P.A625,
PID control Pr.758, Pr.1015, Pr.1134, 570
P.A640 to P.A644,
P.A650 to P.A655,
Pr.1135, Pr.1140,
Pr.1141, Pr.1143 to
10
To perform process control, such as for P.A661 to P.A665
the pump flow volume and air volume Pr.1149
P.A616 to P.A620,
PID Pre-charge Pr.760 to Pr.769 587
P.A656 to P.A660
C42 to C45 (Pr.934,
P.A630 to P.A633,
PID display adjustment Pr.935), Pr.1136 to 584
P.A670 to P.A673
Pr.1139
P.A601, P.A602,
P.A605, P.A606,
Pr.44, Pr.45, Pr.128 to
To control the dance roll for winding/ P.A610, P.A611,
Dancer control Pr.134, Pr.609, Pr.610, 590
unwinding P.A613 to P.A615,
Pr.1134, Pr.1135
P.A624, P.A625,
P.F020, P.F021
To continue operating at analog current
4 mA input check P.A680 to P.A682 Pr.573, Pr.777, Pr.778 492
input loss
Automatic restart after
instantaneous power failure P.A700 to P.A705, Pr.57, Pr.58, Pr.162 to
597
/ flying start function for P.A710 to P.F003 Pr.165, Pr.299, Pr.611
induction motors
Frequency search accuracy P.A700, P.A711,
To restart without stopping the motor at Pr.96, Pr.162, Pr.298,
improvement (V/F control, P.A712, P.C110, 606
instantaneous power failure Pr.463, Pr.560
offline auto tuning) P.C210
Automatic restart after
instantaneous power failure P.A700, P.A702,
Pr.57, Pr.162, Pr.611 604
/ flying start function for P.F003, P.F004
IPM motors
Power failure time
To decelerate the motor to a stop at P.A730 to P.A735,
deceleration-to-stop Pr.261 to Pr.266, Pr.294 610
instantaneous power failure P.A785
function
5. PARAMETERS
5.14 (A) Application parameters
531
Refer to
Purpose Parameter to set
page
P.A800 to P.A804, Pr.414 to Pr.417, Pr.498,
To operate with sequence program PLC 614
P.A811 to P.A860 Pr.1150 to Pr.1199
P.A900 to P.A906,
To store the inverter running status to a
Trace P.A910 to P.A920, Pr.1020 to Pr.1047 616
USB memory device
P.A930 to P.A939
Initial
Pr. Name Setting range Description
value
0 Coasting time differs according to the inverter capacity.*1
57 Set the waiting time for the inverter to perform a restart after restoring
Restart coasting time 9999 0.1 to 30 s
A702 power due to an instantaneous power failure.
9999 No restart
58
Restart cushion time 1s 0 to 60 s Set the voltage cushion time for restart.
A703
135 Electronic bypass 0 Without electronic bypass sequence
0
A000 sequence selection 1 With electronic bypass sequence
136 MC switchover
1s 0 to 100 s Set the operation interlock time for MC2 and MC3.
A001 interlock time
137 Set a time period that is a little longer than the time period from the ON
Start waiting time 0.5 s 0 to 100 s
A002 signal input to the actual pick-up operation of MC3 (0.3 to 0.5 s).
0 Inverter output stop (motor coasting) at inverter failure
138 Bypass selection at a Automatic switchover to commercial power supply operation at inverter
0
A003 fault 1 failure. (Switchover is not possible when an external thermal relay
(E.OHT) or CPU fault (E.CPU) is occurring.)
Set the frequency where the inverter operation is switched to commercial
power supply operation.
Automatic switchover
139 0 to 60 Hz The inverter operation is performed from a start to Pr.139 setting, then it
frequency from inverter 9999
A004 switches automatically to the commercial power supply operation when
to bypass operation the output frequency is equal to or above Pr.139.
9999 Without automatic switchover
Set the frequency where the commercial power supply operation, which
has been switched from the inverter operation with Pr.139, switches back
to inverter operation.
When the frequency command becomes less than (Pr.139 - Pr.159), the
0 to 10 Hz
motor switches automatically to inverter operation and operates at the
Automatic switchover
frequency of the frequency command. Turning OFF a inverter start
159 frequency range from command (STF/STR) also switches the operation to the inverter
9999
A005 bypass to inverter
operation.
operation
To switch the commercial power supply operation, which has been
switched from the inverter operation with Pr.139, to the inverter operation
9999 again, the inverter start command (STF/STR) is turned OFF. The
operation switches to the inverter operation, and the motor decelerates to
a stop.
*1 The coasting time when Pr.57 = "0" is as shown below. (When Pr.162 Automatic restart after instantaneous power failure selection is set to
the initial value.)
FR-A820-00105(1.5K) or lower and FR-A840-00052(1.5K) or lower: 0.5 s
FR-A820-00167(2.2K) to FR-A820-00490(7.5K) and FR-A840-00083(2.2K) to FR-A840-00250(7.5K): 1 s
FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-01800(55K): 3.0 s
FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher: 5.0 s
532 5. PARAMETERS
5.14 (A) Application parameters
• When switching between inverter operation and commercial power supply operation, commercial power supply may be
accidentally applied to the output side of the inverter. To avoid such situation, provide an interlock where the magnetic
contactor at the commercial power supply side turns ON at turn OFF of the magnetic contactor at the inverter output side.
1
The inverter's electronic bypass sequence that outputs timing signals for the magnetic contactors can act as a complicated
interlock between the commercial power supply operation and the inverter operation.
2
NOTE
• The commercial power supply operation is not available with Mitsubishi Electric Vector control dedicated motors (SF-V5RU).
3
Connection diagram
• A typical connection diagram of the electronic bypass sequence is shown below.
4
MC2
MCCB MC1
External
thermal relay
5
MC3
R/L1 U
S/L2 V IM
T/L3 W
R1/L11 6
S1/L21
Inverter start MC1
(forward rotation) ∗1
STF MC1
Inverter/bypass
operation interlock
CS
MRS
MC3 MC2
7
∗1
∗3 MC2 ∗2
External thermal OH 24VDC
Reset RES MC3
MC2
SD
10
MC3
∗1
8
Frequency
setting signal 2 SE
5
MC2
10
External
Converter unit Inverter thermal relay
MCCB MC1
P/+ MC3
R/L1 P/+ U
S/L2 N/- N/- V IM
T/L3 Inverter start W
(forward rotation) STF
R1/L11 Inverter/bypass CS
S1/L21 operation interlock MRS ∗3 MC1
SE SD ∗1
MC1
RDA X10
∗4 ALM MC2
External X95 ∗3 ∗1 MC3
OH MC2 ∗2
thermal ∗4 Y214 X96 ∗3 24VDC
Reset RES
SD RSO RES MC3
∗1 MC2
Frequency 10
2 MC3
setting signal
5
SE
R1/L11
S1/L21
5. PARAMETERS
5.14 (A) Application parameters
533
NOTE
• Use the Electronic bypass function in External operation mode. In addition, the wiring terminals R1/L11 and S1/L21 must be
connected to a separate power source that does not go through MC1. Be sure to connect using a separate power supply.
• Be sure to provide a mechanical interlock for MC2 and MC3.
Notation MC operation
○ ON
× OFF
During inverter operation: MC2-OFF, MC3-ON
—
During commercial power supply operation: MC2-ON, MC3-OFF
Invariance The operation status before changing the signal state to ON or OFF is held.
534 5. PARAMETERS
5.14 (A) Application parameters
• The output signals are as shown below.
Signal
Applied terminal
(Pr.190 to Pr.196 setting)
Description 1
Operation output signal of the magnetic contactor MC1 on
MC1 17
the inverter's input side.
MC2 18
Operation output signal of the magnetic contactor MC2
for the commercial power supply operation.
2
Operation output signal of the magnetic contactor MC3 on
MC3 19
the inverter's output side.
Power supply
ON
OFF
4
Operation interlock ON ON : Operation enabled
(MRS) OFF OFF: Operation disabled
5
Inverter run command ON ON : Forward rotation
(STF) OFF OFF: Stop
Inverter/commercial ON ON : Inverter operation
power supply (CS) OFF OFF: Commercial power supply operation
MC for commercial ON
power supply operation OFF
Indicates the delay time until
the MC turns on (off).
7
(MC2)
Pr.136 MC switchover interlock time
Pr.137 MC3 start (waiting time)
Pr.137 Pr.58
Pr.57 Reset time
Each timer
Pr.57 Pr.136 Pr.136 Pr.57
Pr.58 Switchover cushion time 8
9
Operating status
(motor speed)
INV Coasting Bypass Coasting INV Stop
10
operation operation operation
• Example of operation sequence with automatic bypass sequence (Pr.139 ≠ "9999", Pr.159 = "9999")
ON
STF
OFF
Output frequency Pr.139
Frequency command
Time
Actual motor speed
Time
INV ON
operation MC3
OFF
Commercial ON
power supply MC2 OFF
operation
C A A B C D
A : Pr.136 MC switchover interlock time B : Pr.137 Start waiting time
C : Pr.57 Restart coasting time D : Pr.58 Restart cushion time
5. PARAMETERS
5.14 (A) Application parameters
535
• Example of operation sequence with automatic bypass sequence (Pr.139 ≠ "9999", Pr.159 ≠ "9999")
ON
STF
OFF
Output frequency Pr.139
Pr.159
Frequency command
Time
Actual motor speed
Time
INV ON
operation MC3 OFF
Commercial ON
power supply MC2
operation OFF
C A A B C D A A B C D
A : Pr.136 MC switchover interlock time B : Pr.137 Start waiting time
C : Pr.57 Restart coasting time D : Pr.58 Restart cushion time
Operating procedure
• Operation flowchart
• Pr.135 = "1" (open collector output terminal of inverter)
Power supply ON • Pr.136 = 2.0 s
• Pr.137 = 1.0 s (Set the time until MC3 is actually turned ON and the inverter and motor
are electrically connected. If the time is short, the restart may not function properly.)
Setting the parameters
• Pr.57 = 0.5 s
• Pr.58 = 0.5 s (Always set this to switchover from the commercial power supply operation
Start inverter operation
to the inverter operation.)
Constant-speed commercial
power supply operation
Deceleration (stop)
inverter operation
536 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• Connect the control power (R1/L11, S1/L21) in front of the input-side MC1. If the control power is connected behind the input- 1
side MC1, the electronic bypass sequence function will not operate.
• The electronic bypass sequence function is only enabled when Pr.135 = "1" and in the External operation mode or combined
operation mode (PU speed command and External operation command with Pr.79 = "3"). MC1 and MC3 turn ON when Pr.135
= "1" and in an operation mode other than mentioned above. 2
• MC3 turns ON when the MRS and CS signals are ON and the STF (STR) signal is OFF. If the motor was coasted to a stop
from commercial power supply operation at the previous stop, the motor starts running only after waiting the time set in Pr.137.
• Inverter operation is only available when the MRS, STF (STR), and CS signals are ON. In all other cases (when the MRS signal
is ON), commercial power supply operation is available.
3
• When the CS signal is OFF, the motor switches to the commercial power supply operation. However, when the STF (STR)
signal is OFF, the motor decelerates to a stop during inverter operation.
• From the point where MC2 and MC3 are both turned OFF, there is a waiting time set with Pr.136, till MC2 or MC3 is turned ON. 4
• Even when the electronic bypass sequence is enabled (Pr.135 = "1"), the Pr.136 and Pr.137 settings are ignored in PU
operation mode.
In addition, the input terminals (STF, CS, MRS, OH) return to perform their normal functions.
• When the electronic bypass sequence function (Pr.135 = "1") and PU operation interlock function (Pr.79 = "7") are used at the
5
same time, the MRS signal is shared with the PU operation external interlock if the X12 signal is not assigned. (The inverter
operation is available when the MRS and CS signals are ON.)
• Set the acceleration time to the level that does not activate the stall prevention operation. 6
• If switching to the commercial power supply operation while a failure such as an output short circuit has occurred between the
magnetic contactor MC3 and the motor, the damage may further spread. If a failure has occurred between the MC3 and the
motor, a protection circuit such as using the OH signal input must be provided.
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196may affect other functions. Set parameters after
7
confirming the function of each terminal.
• Switching with the electronic bypass sequence is not available during retry. Switching occurs after the retry. When the
electronic bypass is valid at a fault (Pr.138 = "1"), switching occurs also during retry. 8
• When the electronic bypass sequence function and the retry function of the converter unit are used at the same time for the
separated converter type, set 101 or more in the number of retries at fault occurrence (Pr.67) on the converter unit side. When
a value less than 100 is set, ALM signal does not turn ON until the retry count is exceeded. In this case, the electronic bypass
at a fault is not performed until the retry count is exceeded.
9
• To use X95 and X96 signals for the separated converter type, use a converter unit manufactured in August 2014 or later.
5. PARAMETERS
5.14 (A) Application parameters
537
*3 * MC operation is as shown below.
Notation MC operation
○ ON
× OFF
During inverter operation: MC2-OFF, MC3-ON
—
During commercial power supply operation: MC2-ON, MC3-OFF
Parameters referred to
Pr.11 DC injection brake operation timepage 681
Pr.57 Restart coasting timepage 597, page 604
Pr.58 Restart cushion timepage 597
Pr.79 Operation mode selectionpage 370
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
By turning ON the magnetic contactor (MC) on the input side before the motor is started and turning OFF the MC after the motor
is stopped, power is not supplied to the main circuit, reducing the standby power.
Initial Setting
Pr. Name Description
value range
0 Self power management function disabled
Self power management function enabled (main circuit OFF at protective
248 Self power management 1
0 function activation)
A006 selection
Self power management function enabled (main circuit OFF at protective
2
function activation due to a circuit failure)
137 Set a time period that is a little longer than the time period from the ON
Start waiting time 0.5 s 0 to 100 s
A002 signal input to the actual pick-up operation of MC1 (0.3 to 0.5 s).
Set the waiting time until the main circuit power supply is turned OFF
1 to 3600 s
254 Main circuit power OFF after the motor is stopped.
600 s
A007 waiting time The main circuit power supply is turned OFF only when the protective
9999
function selected by Pr.248 is activated.
Power supply to the inverter: AC (terminals R, S, and T)
When power is supplied only to the control circuit, and then switched to
100, 101
be supplied to both the control and main circuits, inverter reset is not
performed.
30 Regenerative function
0 0 to 2, 10,
E300 selection
11, 20, 21,
102, 110, For other settings, refer to page 689.
111, 120,
121
Connection diagram
• Terminal R1, S1 inputs
538 5. PARAMETERS
5.14 (A) Application parameters
• 24 V external power supply input
24VDC
+24
24VDC
+24 +24
24VDC 3
SD 24VDC 24VDC
SE SD SD SE
DC brake 10
Time
Pr.11 Pr.254 Pr.137
STF ON OFF ON
MC1 ON OFF ON
R1S1 input/
Power supply mode RST input RST input
external 24 V input
5. PARAMETERS
5.14 (A) Application parameters
539
• When the protective function of the inverter is activated, the MC1 signal is immediately turned OFF according to the Pr.248
setting. (The MC1 signal is turned OFF before the time set in Pr.254 has passed.)
When Pr.248 ="1", the MC1 signal is turned OFF when the protective function is activated due to any cause.
When Pr.248 ="2", the MC1 signal is turned OFF only when the protective function is activated due to an error resulted
from a failure in the inverter circuit or a wiring error (refer to the following table). (For the fault details, refer to page 745.)
Fault type
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
24 VDC power fault (E.P24)
Operation panel power supply short circuit/RS-485 terminals power supply short circuit
(E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault (E.13/E.PBT)
• To enable the self power management function for the separated converter type, enable the self power management
function also on the converter unit side. To activate the self power management function when a converter unit fault occurs,
connect the terminal to which Y17 signal of the converter unit is assigned and the terminal to which X94 signal of the
inverter is assigned.
Y17 output signal MC1 output signal MC1 output signal actual
Main circuit power supply
(converter unit) (inverter) operation
OFF OFF OFF Stop
OFF ON OFF Stop
ON OFF OFF Stop
ON ON ON Supplied
• To use the X94 signal, set "94" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function to
an input terminal.
540 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• When the start signal is turned OFF before the time set in Pr.137 has passed after the start signal is turned ON, the inverter 1
does not start and the MC1 signal is turned OFF after the time set in Pr.254 has passed. If the start signal is turned ON again
before the time set in Pr.254 has passed, the inverter immediately starts outputting.
Output frequency
(Hz)
Output frequency
(Hz)
2
Time Time
STF ON OFF STF ON OFF ON
3
MC1 ON OFF MC1 ON
Pr.137
Pr.254
Pr.137
Pr.254
4
• At inverter reset, the status of the MC1 signal is held and operation of the magnetic contactor is not performed.
• When the inverter stops the output due to, for example, the Output stop (MRS) signal, the MC1 signal is turned OFF after the
time set in Pr.254 has passed. 5
• During the stop, turning ON the External DC injection brake operation start signal (X13) and Pre-excitation/servo ON signal
(LX) turns ON the MC1 signal.
• To avoid inverter reset when supplying power to the main circuit is started when power is supplied only to the control circuit,
set 100 or more in Pr.30. (For the separated converter type, setting Pr.30 of the converter unit is also required.)
6
• When supplying power to the main circuit is started when power is supplied only to the control circuit, there is a slight waiting
time before starting.
• Repeated operation of the magnetic contactor due to frequent start and stop or activation of the protective function may shorten 7
the inverter life.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
• To use X94 signal for the separated converter type, use a converter unit manufactured in August 2014 or later.
8
Parameters referred to
Pr.11 DC injection brake operation timepage 681
9
Pr.30 Regenerative function selectionpage 689
Pr.190 to Pr.196 (Output terminal function selection)page 450
Initial Setting
Pr. Name Description
value range
278 Set the rated slip frequency of the motor + approx. 1.0 Hz. This can be
Brake opening frequency 3 Hz 0 to 30 Hz
A100 set only when Pr.278 ≤ Pr.282.
Set between 50 and 90% because load slippage is more likely to occur
279 when a start setting is too low.
Brake opening current 130% 0 to 400%
A101 The inverter rated current is regarded as 100%, or the rated motor
torque is regarded as 100%. (According to Pr.639 setting)
280 Brake opening current
0.3 s 0 to 2 s Generally set between 0.1 and 0.3 s.
A102 detection time
Set the mechanical delay time until braking eases. When Pr.292 = "8",
281
Brake operation time at start 0.3 s 0 to 5 s set the mechanical delay time until braking eases + approx. 0.1 to 0.2
A103
s.
Turn OFF the Brake opening request (BOF) signal and set the
282 frequency for operating the electromagnetic brake. Generally, set the
Brake operation frequency 6 Hz 0 to 30 Hz
A104 setting value of Pr.278 + 3 to 4 Hz. This can be set only when Pr.282
≥ Pr.278.
283 When Pr.292 = "7", set the mechanical delay time until the brake
Brake operation time at stop 0.3 s 0 to 5 s
A105 closes + 0.1 s. When Pr.292 = "8", set the mechanical delay time until
the brake closes + approx. 0.2 to 0.3 s.
5. PARAMETERS
5.14 (A) Application parameters
541
Initial Setting
Pr. Name Description
value range
0 The deceleration detection function disabled.
284 Deceleration detection
0 The protective function activates when the deceleration speed of the
A106 function selection 1
deceleration operation is not normal.
The Brake sequence fault (E.MB1) is activated when the difference
285 Overspeed detection 0 to 30 Hz between the detection frequency and output frequency is equal to or
9999
A107 frequency*1 greater than the setting value under encoder feedback control.
9999 Overspeed detection disabled.
0 Normal operation
Operation with the shortest acceleration/deceleration time.(Refer to
1, 11
page 365.)
292 Automatic acceleration/ Operation with the optimum acceleration/deceleration time.(Refer to
0 3
F500 deceleration page 365.)
5, 6 Lift operation 1, 2. (Refer to page 368.)
7 Brake sequence mode 1
8 Brake sequence mode 2
639 Brake opening current 0 Brake opening by output current
0
A108 selection 1 Brake opening by motor torque
0 Brake closing operation by frequency command
640 Brake operation frequency
0 Brake closing operation by the actual motor rotation speed (estimated
A109 selection 1
value)
0 Normal operation when the RT signal is ON
641 Second brake sequence 7 Second brake sequence 1 when the RT signal is ON
0
A130 operation selection 8 Second brake sequence 2 when the RT signal is ON
9999 First brake sequence is valid when the RT signal is ON
642 Second brake opening
3 Hz 0 to 30 Hz Refer to Pr.278.
A120 frequency
643
Second brake opening current 130% 0 to 400% Refer to Pr.279.
A121
644 Second brake opening current
0.3 s 0 to 2 s Refer to Pr.280.
A122 detection time
645 Second brake operation time
0.3 s 0 to 5 s Refer to Pr.281.
A123 at start
Set the second brake sequence function.
646 Second brake operation
6 Hz 0 to 30 Hz Refer to Pr.282. The second brake sequence function is
A124 frequency
enabled when the RT signal is ON.
647 Second brake operation time
0.3 s 0 to 5 s Refer to Pr.283.
A125 at stop
648 Second deceleration speed
0 0, 1 Refer to Pr.284.
A126 detection selection
650 Second brake opening current
0 0, 1 Refer to Pr.639.
A128 selection
651 Second brake operation
0 0, 1 Refer to Pr.640.
A129 frequency selection
*1 The speed deviation excess detection frequency is used when Vector control compatible option is mounted during Vector control. (Refer to page
259 for details.)
Connection diagram
MC
Sink logic
Mechanical
Pr.184 = 15 brake
Pr.190 = 20
MCCB
R/L1 U
Power
S/L2 V Motor
supply
T/L3 W
Start signal STF 24VDC
Multi-speed signal RH ∗2
∗3 MC
RUN(BOF) Brake opening request
Brake opening completion signal AU(BRI) ∗1 signal (BOF)
(BRI)
SD SE
542 5. PARAMETERS
5.14 (A) Application parameters
*3 Be careful of the permissible current of the built-in transistors on the inverter. (24 VDC 0.1 A)
NOTE 1
• The automatic restart after instantaneous power failure function and orientation function do not operate when brake sequence
is selected.
• To use this function, set the acceleration/deceleration time to 1 s or higher.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196 (Output 2
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
5. PARAMETERS
5.14 (A) Application parameters
543
• When the inverter decelerates to the frequency set to Pr.282 Brake operation frequency during deceleration, the inverter
turns OFF the brake opening request signal (BOF) and decelerates further to the frequency set in Pr.278. After
electromagnetic brake operation completes and the inverter recognizes the turn OFF of the BRI signal, the inverter holds
the frequency set in Pr.278 for the time set in Pr.283 Brake operation time at stop. And after the time set in Pr.283
passes, the inverter decelerates again. The inverter outputs is shut off when the frequency reaches Pr.13 Starting
frequency setting or 0.5 Hz, whichever is lower.
Output frequency(Hz)
Target frequency
Pr.13 setting
Pr.280 or 0.5Hz,
Pr.282 Pr.281 whichever is lower
Pr.278
Pr.13
Time
ON Pr.283
STF
Output current or motor torque Pr.279
(select by Pr.639)
Brake opening request ON
(BOF signal)
Brake opening completion ON
(BRI signal)
Electromagnetic brake Closed Opened Closed
operation
Target frequency
Pr.280 Pr.13 setting
Pr.282 or 0.5Hz,
Pr.281
Pr.278 whichever is lower
Pr.13
Time
ON Pr.283
STF
Output current or motor torque
(select by Pr.639) Pr.279
Brake opening request ON
(BOF signal)
Electromagnetic brake Closed Opened Closed
operation
NOTE
• Even if the brake sequence operation has been selected, inputting the JOG signal (JOG operation) changes the operation
method to normal operation and give a priority to the JOG operation. Note that the JOG signal input by the brake sequence
function is invalid during operation.
544 5. PARAMETERS
5.14 (A) Application parameters
• Select the operation of the Second brake sequence function with Pr.641 Second brake sequence operation selection.
0 (initial value)
Pr.641 setting Brake sequence function when the RT signal is ON
Normal operation (The first and second brake sequence functions invalid)
1
7 Second brake sequence mode 1
8 Second brake sequence mode 2
9999 First brake sequence mode is valid 2
• Set "45" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the Second brake sequence open
completion signal (BRI2) to the input terminal.
• To use the Second brake opening request signal (BOF2), set "22 (positive logic)" or "122 (negative logic)" in any of Pr.190
3
to Pr.196 (Output terminal function selection) to assign the function to the output terminal.
• The method of setting the second brake sequence parameters is the same as that for the corresponding first brake
sequence function parameters.
4
• Switchover of the brake sequence function by RT signal is valid when the inverter is stopped.
Protective function 5
• If one of the following faults occur while the brake sequence function is enabled, the inverter enters an fault status, shuts
off output, and turns OFF the brake opening request signal (BOF).
Fault 6
Description
indication
When (detection frequency) - (output frequency) ≥ Pr.285 during encoder feedback control.
E.MB1
When Pr.285 (Overspeed detection function) = 9999, overspeed is not detected.
When deceleration is not normal during deceleration operation from the set frequency to the frequency set in Pr.282. (when
7
E.MB2
Pr.284 = 1) (except stall prevention operation)
E.MB3 When the BOF signal turned ON while the motor is at a stop. (load slippage prevention function)
E.MB4
When more than 2 s have elapsed after the start command (forward or reverse rotation) is input, but the BOF signal does
not turn ON.
8
E.MB5 When more than 2 s have elapsed after the BOF signal turned ON, but the BRI signal does not turn ON.
E.MB6 When the inverter had turned ON the brake opening request signal (BOF), but the BRI signal turned OFF.
E.MB7 When more than 2 s have elapsed after the BOF signal turned OFF at a stop, but the BRI signal does not turn OFF. 9
NOTE
• During PM sensorless vector control, the brake sequence function is available with the IPM motor MM-CF only.
• During deceleration, inverter output is shut OFF when the frequency reaches Pr.13Starting frequency or 0.5 Hz, whichever
10
is lower. For Pr.278 Brake opening frequency, set a frequency equal to or higher than the Pr.13 setting or 0.5 Hz.
• Pr.285 Overspeed detection frequency is valid under encoder feedback control (used with the FR-A8AP (option)) even if a
value other than "7 or 8" is set in Pr.292 Automatic acceleration/deceleration.
• Setting Pr.278 too high activates the stall prevention and may cause E.MB4.
• E.MB4 occurs when the acceleration time from Pr.13 to Pr.278 + Pr.280 reaches or exceeds 2 s.
Output frequency (Hz)
Less than 2s
Output
frequency
Pr.278 (Hz)
Pr.13
Pr.280
Time
ON
Brake opening request
(BOF signal)
Parameters referred to
Pr.3 Base frequencypage 673
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
5. PARAMETERS
5.14 (A) Application parameters
545
Confirming the starting times can be used to determine the timing of the maintenance, or can be used as a reference for system
inspection or parts replacement.
Pr. Name Initial value Setting range Description
1410 Starting times lower 4 Displays the lower four digits of the number of the inverter starting
0 0 to 9999
A170 digits times.
1411 Starting times upper 4 Displays the upper four digits of the number of the inverter starting
0 0 to 9999
A171 digits times.
• Every start signal input (the RUN signal ON) while the inverter output is stopped is counted as the inverter starting time.
(Starting during pre-excitation is also counted.)
STF ON ON ON ON ON
LX ON
RUN ON ON ON ON
Output
frequency
Time
4
3
2
Start count 1
indication
• The lower four digits of the number of starting times is displayed in Pr.1410 Starting times lower 4 digits, and the upper
four digits of the number of starting times is displayed in Pr.1411 Starting times upper 4 digits.
• The maximum count is "99999999". When "99999999" is exceeded on the monitor, the monitor value is reset to 0.
Display data Monitor display
Pr.1410 (Lower digits monitor)
10000
Pr.1411 (Upper digits monitor)
NOTE
• Any value can be set in Pr.1410 or Pr.1411. Set "0" to clear the number on the monitor.
• Starting during offline auto tuning is not counted.
• Under position control, the count increases when the LX signal turns ON.
• The counting is enabled even if the RUN signal is not assigned to an output terminal.
• (For RUN signal, refer to page 450.)
• Starting during the test operation (Pr.800 = "9") is not counted.
To ensure accurate positioning at the upper limit, etc. of a lift, stop-on-contact control causes the mechanical brake to close
while the motor creates a holding torque to keep the load in contact with a mechanical stopper, etc.
This function suppresses vibration that is likely to occur when the load is stopped upon contact in lift applications, thereby
ensuring reliable and highly accurate positioning stop.
<Without stop-on-contact control> <With stop-on-contact control>
Lift Lift
546 5. PARAMETERS
5.14 (A) Application parameters
Setting
Pr. Name Initial value Description
range 1
6 Multi-speed setting (low
10 Hz 0 to 590 Hz Set the output frequency for stop-on-contact control.
D303 speed)
22 Stall prevention operation
H500 level
150% 0 to 400%
Set the stall prevention operation level for stop-on-contact control. 2
48 Second stall prevention
150% 0 to 400%
H600 operation level The smaller value set in either Pr.22 or Pr.48 has priority.
0 Normal
1 Stop-on-contact control 3
2 Load torque high-speed frequency control (Refer to page 549.)
Stop-on contact/load torque Stop-on contact + load torque high speed frequency control (Refer
270 3
A200
high- speed frequency control 0
selection 11
to page 549)
Stop-on-contact control
4
Stop-on contact + load torque high E.OLT is invalid under stop-
13 speed frequency control on-contact control
(Refer to page 549.)
Set the force (holding torque) for stop-on-contact control.
5
Stop-on contact excitation 0 to 300%
275
current low-speed scaling 9999 Normally, set the scaling factor between 130 to 180%.
A205
factor 9999 Not compensated.
0 to 9*1 Set a PWM carrier frequency for stop-on-contact control. 6
For Real sensorless vector control, the carrier frequency is always 2
276 PWM carrier frequency at 0 to 4*2 kHz when the setting value is 0 to 5 and always 6 kHz when the
9999
A206 stop-on contact setting value is 6 to 9. (Valid at the output frequency of 3 Hz or less.)
9999 7
As set in Pr.72 PWM frequency selection.
*1 The setting range of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower
*2 The setting range of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher
8
Connection and operation example
Stop-on contact 9
Output frequency
10
Mechanical Pr.5
brake
Pr.6
MCCB 0 Time
R/L1 U
Power (a) (b) (c)
S/L2 V Motor
supply RH ON
T/L3 W
RM OFF ON
Forward rotation command STF
High-speed operation command RH∗ RL OFF ON
Middle-speed operation command RM∗ ∗
RT OFF ON
Stop-on contact selection 0 RL∗
Stop-on contact selection 1 RT∗ ∗ Goes into stop-on-contact control mode when
SD both RL and RT switch on.
RL and RT may be switched on in any order
with any time difference
∗ The input terminal used differs according to the Pr.180 to Pr.189 settings. (a): Acceleration time(Pr.7)
(b): Deceleration time(Pr.8)
(c): Second deceleration time(Pr.44/Pr.45)
5. PARAMETERS
5.14 (A) Application parameters
547
• Setting Pr.270 = "11 or 13" disables stall prevention stop (E.OLT) during stop-on-contact control (with both RL and RT
signals ON).
NOTE
• By increasing the Pr.275 setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OCT) may occur
or the machine may oscillate in stop-on-contact status.
• The stop-on-contact function is different from the servo-lock function, and if used to stop or hold a load for an extended period,
this function can cause the motor to overheat. After a stop, immediately switch to a mechanical brake to hold the load.
• Under the following operating conditions, the stop-on-contact function is invalid:
PU operation (Pr.79), JOG operation (JOG signal), PU + External operation (Pr.79), PID control function operation (Pr.128),
Remote setting function operation (Pr.59), Automatic acceleration/deceleration operation (Pr.292), Start time tuning,
Orientation control function operation
• When performing stop-on-contact control during encoder feedback control, encoder feedback control is invalid due to a
transition to the stop-on-contact control mode.
*1 When RL and RT are ON, Pr.49 Second stall prevention operation frequency is invalid.
*1 By 0 to 5 V (0 to 10 V), 4 to 20 mA input
548 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions. 1
Set parameters after confirming the function of each terminal.
Parameters referred to 2
Pr.4 to Pr.6, Pr.24 to Pr.27 (multi-speed setting)page 391
Pr.15 Jog frequencypage 390
Pr.22 Stall prevention operation level, Pr.48 Second stall prevention operation level levelpage 409
Pr.22 Torque limit levelpage 235
Pr.59 Remote function selectionpage 359
Pr.72 PWM frequency selectionpage 339
3
Pr.79 Operation mode selectionpage 370
Pr.95 Online auto tuning selectionpage 527
Pr.128 PID action selectionpage 570
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.270 Stop-on contact/load torque high- speed frequency control selectionpage 549
4
Pr.292 Automatic acceleration/decelerationpage 365, page 368
8
frequency control> frequency control>
Light
Faster
9
Whether there is a load or The lift with a light load or without
not, the lift is moved a load is moved faster than the lift
vertically at the same speed. with a load.
(The output frequency is increased
only during power driving.)
10
Initial value
Pr. Name Setting range Description
FM CA
4 Multi-speed setting
60 Hz 50 Hz 0 to 590 Hz Set the higher-speed frequency.
D301 (high speed)
5 Multi-speed setting
30 Hz 0 to 590 Hz Set the lower-speed frequency.
D302 (middle speed)
0 Normal
1 Stop-on-contact control (Refer to page 546.)
2 Load torque high-speed frequency control
Stop-on contact + load Stop-on contact (refer to page 546) + load torque high speed
270 3
torque high speed 0 frequency control
A200
frequency control 11 Stop-on-contact control
Stop-on contact + load torque high E.OLT is invalid under
13 speed frequency control stop on-contact control.
(Refer to page 546.)
271 High-speed setting
50% 0 to 400%
A201 maximum current Set the upper and lower limits of the current at high and middle
272 Middle-speed setting speeds.
100% 0 to 400%
A202 minimum current
Set the average current during acceleration from (Pr.273 × 1/2) Hz
0 to 590 Hz
273 Current averaging to (Pr.273) Hz.
9999
A203 range Set the average current during acceleration from (Pr.5 × 1/2) Hz to
9999
(Pr.5) Hz.
Set the time constant of the primary delay filter relative to the output
274 Current averaging filter current.
16 1 to 4000
A204 time constant (The time constant [ms] is 0.5 × Pr.274, and the initial value is 8 ms.)
A larger setting results in a stable operation with poorer response.
5. PARAMETERS
5.14 (A) Application parameters
549
Connection diagram
MC
Sink logic
Mechanical
Pr.186 = 19 brake
MCCB
R/L1 U
Power supply S/L2 V Motor
T/L3 W
Start signal STF
*1 The applied terminals differ by the settings of Pr.180 to Pr.189 (Input terminal function selection)
Pr.5
1
Pr.5
2
A B Time
Current averaging range Current averaging range
Less than Pr.272 setting rated current
Pr.271 setting rated current or more
STF
ON OFF ON OFF ON OFF
(STR)
X19 ON ON ON OFF
550 5. PARAMETERS
5.14 (A) Application parameters
• When the average current is larger than "inverter rated current × Pr.271 setting (%)" and smaller than "inverter rated
current × Pr.272 setting (%)", linear compensation is performed as shown below.
1
Frequency
Pr.4 2
(60Hz/50Hz)
Pr.5
(30Hz)
3
Pr.271 Pr.272 Average current
(50%) (100%)
9
Parameters referred to
Pr.4 to Pr.6, Pr.24 to Pr.27 (multi-speed setting)page 391
Pr.57 Restart coasting timepage 597, page 604
Pr.59 Remote function selectionpage 359
Pr.79 Operation mode selectionpage 370
10
Pr.128 PID action selectionpage 570
Pr.178 to Pr.189 (Input terminal function selection)page 496
5. PARAMETERS
5.14 (A) Application parameters
551
• Assigning the Traverse function selection (X37) signal to the input terminal enables the traverse function only when the
X37 signal is ON. (When the X37 signal is not assigned, the traverse function is always available.) To input the X37 signal,
set "37" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a terminal.
Output frequency(Hz) Traverse operation
f0: set frequency
f2 f1: amplitude amount from the set frequency
f1 Pr.7 (f0 × Pr.593/100)
f2: compensation amount at transition from
f0
acceleration to deceleration
f1 (f1 × Pr.594/100)
f3 f3: compensation amount at transition from
Pr.8
deceleration to acceleration
(f1 × Pr.595/100)
Pr.7 t2 t1 t1: time from acceleration during traverse
(Pr.597) (Pr.596) operation (Time from (f0 − f1) to (f0 + f1))
Time(s) (Pr.596)
STF(STR) t2: time from deceleration during traverse
ON
signal operation (Time from (f0 + f1) to (f0 − f1))
X37 signal ON (Pr.597)
• The motor accelerates to the set frequency f0 according to the normal Pr.7 Acceleration time at turn ON of the start
command (STF or STR).
• When the output frequency reaches f0 and the X37 signal turns ON, the inverter begins traverse operation and accelerates
to f0 + f1. The acceleration time at this time is according to the Pr.596 setting. (If the X37 signal turns ON before the output
frequency reaches f0, traverse operation begins after the output frequency reaches f0.)
• After the inverter accelerates to f0 + f1, this is compensated with f2 (f1 × Pr.594), and the inverter decelerates to f0 - f1.
The deceleration time at this time is according to the Pr.597 setting.
• After the inverter decelerates to f0 - f1, this is compensated with f3 (f1 × Pr.595), and the inverter accelerates again to f0
+ f1.
• When the X37 signal turns OFF during traverse operation, the inverter accelerates/decelerates to f0 according to the
normal acceleration/deceleration time (Pr.7, Pr.8). If the start command (STF or STR) is turned OFF during traverse
operation, the inverter decelerates to a stop according to the normal deceleration time (Pr.8).
NOTE
• If the set frequency (f0) and traverse operation parameters (Pr.598 to Pr.597) are changed during traverse operation, this is
applied in operations after the output frequency reaches f0 before the change was made.
• If the output frequency exceeds Pr.1 Maximum frequency or Pr.2 Minimum frequency during traverse operation, the output
frequency is clamped at the maximum/minimum frequency when the set pattern exceeds the maximum/minimum frequency.
• When the traverse function and S-pattern acceleration/deceleration (Pr.29 ≠ "0") are selected, S-pattern acceleration/
deceleration operation occurs only in the range operated at the normal acceleration/deceleration time (Pr.7, Pr.8).
Acceleration/deceleration during traverse operation is performed linearly.
• If stall prevention activates during traverse operation, traverse operation stops and normal operation begins. When stall
prevention operation is completed, the inverter accelerates/decelerates to f0 at the normal acceleration/deceleration time
(Pr.7, Pr.8). After the output frequency reaches f0, the traverse operation begins again.
• If the value of the amplitude inversion compensation amount (Pr.594, Pr.595) is too large, an overvoltage trip or stall
prevention occurs, and pattern operation cannot be performed as set.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base frequencypage 673
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
552 5. PARAMETERS
5.14 (A) Application parameters
5.14.8 Anti-sway control
When an object is moved by a gantry crane, swinging is suppressed on the crane's traveling axis. 1
Initial Setting
Pr. Name Description
value range
1072
DC brake judgment time Set the time from when the output frequency becomes the Pr.10 DC injection 2
for anti-sway control 3s 0 to 10 s brake operation frequency or less to when the DC injection brake (zero speed
A310
operation control or the servo lock) operation starts.
1073 Anti-sway control 0 Anti-sway control disabled
A311 operation selection
0
1 Anti-sway control enabled 3
0.05 to 3 Hz Set a swinging frequency of the object.
1074 Anti-sway control
1 Hz Anti-sway control is performed using a swinging frequency estimated by the
A312 frequency 9999
inverter according to the settings of Pr.1077 to Pr.1079.
1075 4
Anti-sway control depth 0 0 to 3 0 (Deep) → 3 (Shallow)
A313
1076
Anti-sway control width 0 0 to 3 0 (Narrow) → 3 (Wide)
A314
1077
5
Rope length 1m 0.1 to 50 m Set the rope length of the crane.
A315
1078 1 to
Trolley weight 1 kg Set the weight of the trolley.
A316
1079
50000 kg
1 to
6
Load weight 1 kg Set the weight of the object.
A317 50000 kg
Time
RL ON
RM ON
STF ON
NOTE
• Under torque control or position control, the anti-sway control is disabled.
• During operation of the power failure time deceleration-to-stop function, or when the automatic restart after instantaneous
power failure is enabled (Pr.57 ≠ "9999"), the anti-sway control is disabled.
5. PARAMETERS
5.14 (A) Application parameters
553
• If the Pr.1076 setting is too large (the width is too wide), the response level of speed control drops, and the system may
become unstable.
• After setting Pr.1074 = "9999", set the crane rope length in the Pr.1077 Rope length, the trolley weight in the Pr.1078
Trolley weight, and the weight of an object in the Pr.1079 Load weight. Then, anti-sway control is performed using a
swinging frequency estimated by the inverter.
Actual rotation
Pr.10 DC injection brake
operation frequency
Time
NOTE
• During anti-sway control operation, even if the motor rotation is restricted to one direction in the Pr.78 Reverse rotation
prevention selection, the motor may rotate in a direction opposite to the setting.
• A protective function (E.OSD) may be activated during vibration control. When using anti-sway control, set Pr.690
Deceleration check time = "9999 (initial value)" to disable the deceleration check function.
• When anti-sway control is enabled, regeneration avoidance, shortest acceleration/deceleration, and the traverse function are
disabled.
• Do not set anti-sway control and droop control together.
Parameters referred to
Pr.10 DC injection brake operation frequencypage 681
Pr.78 Reverse rotation prevention selectionpage 386
Pr.286 Droop gainpage 702
Pr.292 Automatic acceleration/decelerationpage 365
Pr.592 Traverse function selectionpage 551
Pr.690 Deceleration check timepage 259
Pr.875 Fault definitionpage 401
Pr.882 Regeneration avoidance operation selectionpage 696
The inverter can adjust the stop position (Orientation control) using a position detector (encoder) attached to a place such as
the main shaft of the machine.
A Vector control compatible option is required.
Because Pr.350 Stop position command selection is initially set to "9999", the orientation control function is invalid.
Initial Setting
Pr. Name Description
value range
0 Internal stop position command (Pr.356)
350 Stop position
9999 1 External stop position command (FR-A8AX 16-bit data)
A510*1 command selection
9999 Orientation control invalid
351
Orientation speed 2 Hz 0 to 30 Hz Turning ON the X22 signal decelerates the motor speed to the set value.
A526*1
352
Creep speed 0.5 Hz 0 to 10 Hz After the speed reaches the orientation speed, the speed decreases to the
A527*1
creep speed set in Pr.352 as soon as the current position pulse reaches the
353 Creep switchover
511 0 to 16383 creep switchover position set in Pr.353.
A528*1 position
554 5. PARAMETERS
5.14 (A) Application parameters
Initial Setting
Pr. Name Description
value range
354 Position loop As soon as the current position pulses reach the set position loop 1
*1 96 0 to 8191
A529 switchover position switchover position, control is changed to the position loop.
355 After the motor moves into the position loop, the motor stops by the DC
DC injection brake
A530*1 start position
5 0 to 255 injection brake when the current position pulses reach the specified start
position of the DC injection brake. 2
356 Internal stop position When "0" is set in Pr.350, the internal position command is activated and
0 0 to 16383
A531*1 command the setting value of Pr.356 becomes the stop position.
357 Orientation in-
5 0 to 255 Set the in-position width at a stop of the orientation. 3
A532*1 position zone
358 Servo torque
1 0 to 13 Operation at orientation completion can be selected.
A533*1 selection
Set when using a motor (encoder) for 4
which forward rotation is clockwise Set for the operation at 120 Hz or
0
less.
(CW) viewed from the shaft
100
CW
Set for the operation at a frequency 5
higher than 120 Hz.
359 852
Encoder rotation
C141* C241* 1 Set when using a motor for which
direction Set for the operation at 120 Hz or
2 3 1 forward rotation (encoder) is
counterclockwise (CCW) viewed
less. 6
from the shaft
Set for the operation at a frequency
7
101 CCW
higher than 120 Hz.
5. PARAMETERS
5.14 (A) Application parameters
555
Initial Setting
Pr. Name Description
value range
Orientation is executed from the
0
current rotation direction.
Orientation is executed from the
1 Motor end orientation
forward rotation direction.
Orientation is executed from the
2
393 reverse rotation direction.
Orientation selection 0
A525*1 Orientation is executed from the
10
current rotation direction.
Orientation is executed from the
11
forward rotation direction. Machine end orientation*6
556 5. PARAMETERS
5.14 (A) Application parameters
Motor end orientation connection example
Three-phase
MCCB MC
R/L1
Inverter
U
SF-JR motor with encoder
U
For complementary type (SF-V5RU)
∗1
MCCB MC OCR SF-V5RU
1
A
S/L2 V V Three-phase
AC power IM AC power
B
FAN
supply T/L3 W W supply C
E
Forward rotation start STF
Earth (Ground)
Inverter U
V
U
V
IM
2
FR-A8AP W W
Reverse rotation start STR PA1 C ∗2 E
Orientation command X22 ∗3 PA2 R External Earth (Ground)
Contact input common SD
ORA ∗4
PB1 A
thermal relay
PC
input ∗11 CS(OH)
2W1kΩ
G1
Thermal
relay
protector
3
PB2 N
ORM SD G2
∗4 Encoder
PZ1 B FR-A8AP PA1 A ∗2
SE
SD
Differential PZ2 P ∗5 PA2 B
4
PB1 C
PG H
PB2 D
X15 Complementary
SD K Encoder
Differential PZ1 F
X14
X1
Terminating
resistor ON
PG
SD ∗6 Complementary
PZ2
PG
G
S
∗5
5
X0 ∗7 ∗8 (+) (-) 5VDC power SD R
Terminating
DY supply ∗9 resistor ON PG
OFF ∗6
6
SD
∗8 (+) (-) 12VDCpower
FR-A8AX ∗7 supply ∗9
OFF
∗10
*1 Single-phase power supply (200 V/50 Hz, 200 to 230 V/60 Hz) is used for the fan for a 7.5 kW or lower dedicated motor.
*2 The pin number differs according to the encoder used.
*3 Use Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a terminal. (Refer to page 496.) 7
*4 Use Pr.190 to Pr.196 (Output terminal function selection) to assign the function to a terminal. (Refer to page 450.)
*5 Connect the encoder so that there is no looseness between the motor and motor shaft. Speed ratio must be 1:1.
*6 Connect the shield of the encoder cable to the enclosure using a tool such as a P-clip. (Refer to page 92.)
*7 For the differential line driver, set the terminating resistor selection switch to the ON position (initial status) to use. (Refer to page 87.) 8
Note that the terminating resistor switch should be set to the OFF position when sharing the same encoder with another unit (NC, etc.) or when
the terminating resistor is connected to another unit. For the complementary, set the switch to the OFF position.
*8 For terminal compatibility of the FR-JCBL, the FR-V5CBL, and the FR-A8AP, refer to page 87.
*9 A separate power supply of 5 V/12 V/15 V/24 V is necessary according to the encoder power specification. Make the voltage of the external power
supply same as the encoder output voltage, and connect the external power supply between PG and SD. When performing encoder feedback
9
control and Vector control together, an encoder and power supply can be shared.
*10 When a stop position command is input from outside, a plug-in option FR-A8AX is required. Refer to page 558 for the external stop position
command.
*11 Connect the recommended 2W1kΩ resistor between terminals PC and OH. (Recommended product: MOS2C102J 2W1kΩ by KOA Corporation)
10
Insert the input line and the resistor to a 2-wire blade terminal, and connect the blade terminal to terminal OH. (For the recommended 2-wire blade
terminals, refer to page 73.)
Insulate the lead wire of the resistor, for example by applying a contraction tube, and shape the wires so that the resistor and its lead wire do not
touch other cables. Caulk the lead wire securely together with the thermal protector input line using a 2-wire blade terminal. (Do not subject the
lead wire's bottom area to an excessive pressure.)
To use a terminal as terminal OH, assign the External thermal relay input (OH) signal to an input terminal. (Set "7" in any of Pr.178 to Pr.189.)
When OH signal is assigned to terminal RH (Pr.182 = “7”)
PC RH (OH)
Setting
• When the Orientation command (X22) signal is turned ON during operation after the parameters are set, the motor is
decelerated to the orientation switchover speed. Then, the inverter calculates the orientation stop distance, further
decelerates the motor and the motor enters the orientation state (servo lock). The Orientation complete (ORA) signal is
output when the motor is within the orientation complete width.
5. PARAMETERS
5.14 (A) Application parameters
557
Setting I/O signals
Signal Signal name Description
Orientation Turn ON the X22 signal to start the orientation operation.
X22
command For the X22 signal input, set "22" in any of Pr.178 to Pr.189 to assign the function.
The output is in LOW state when the orientation stop can be made within the orientation complete width while
Orientation
ORA the start signal and X22 signal are input (ON).
complete
For the ORA signal output, set "27 (positive logic)" or "127 (negative logic)" in Pr.190 to Pr.196.
The output is in LOW state when the orientation stop cannot be made within the orientation complete width
ORM Orientation fault while the start signal and X22 signal are input (ON).
For the ORM signal output, set "28 (positive logic)" or "128 (negative logic)" in Pr.190 to Pr.196.
270 90 90 270
(3072) (1024) (1024) (3072)
• When the external stop position command (Pr.350 = "1") is selected while the FR-A8AX option is mounted, 16-bit data
(binary input) is used to give the stop position.
• The value set in Pr.360 16-bit data selection should be the divided value minus 1.
Pr.360 setting Description
0 External position command is invalid (speed command or torque command via the FR-A8AX)
Position command direct input
The 16-bit digital signal via the FR-A8AX is the direct stop position command.
<Example>
1
When the Pr.369 Number of encoder pulses setting is "1024", the stop position command "0 to 4095" can be input using
the FR-A8AX, and the digital signal of "2048 (H800)" is input to stop the motor at a 180° position. A command greater than
4096 is considered as 4095.
Set the stop position command by dividing up to 128 stop positions.
If the external stop command input is greater than the setting, the stop positions are the same as those in the maximum
2 to 127 external stop command value.
<Example>
When the number of stop positions is 90 (divided at intervals of 4°), 90 - 1 = 89. Hence, set "89".
[Example 1] When Pr.369 = "1024" [Example 2] With 8 stop positions [Example 3] With 120 stop positions
Pr.360 = "1" Pr.360 = "7" Pr.360 = "119"
Origin (0) (7 or more) Origin(0) (1) Origin (0)
CW 315 45 CW CW
90 90 270 At intervals 90
270 (6)270 of 3
(1024(H400)) (2) (90) (30)
(3072(HC00))
(5)225 135
180 180 (3) 180
(2048(H800)) (4) (60)
558 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• Values in parentheses indicate binary data input from the terminals. Even if the position pulse monitor (Pr.52 Operation panel 1
main monitor selection = "19") is selected, the data monitored is not the number of stop positions. It is the number of pulses
from 0 to 65535.
• FR-A8AX parameters (Pr.300 to Pr.305) are invalid. (Valid when Pr.360 = "0")
• Terminal DY (data read timing input signal) becomes invalid during Vector control. (The position data is downloaded at the 2
start of orientation.)
• Internal stop position command is given when no option is mounted or Pr.360 = "0" even if "1" (external stop position
command) is set in Pr.350.
3
• Relationship between stop position command and 16-bit data
Pr.350
Pr.360
Operation status 4
Stop position 16-bit data
16-bit data selection Stop position command Speed command
command selection (FR-A8AX)
0: speed command Internal (Pr.356) Speed command 16-bit data
0: internal 1, 2 to 127: position External command
5
Internal (Pr.356) Invalid
command (or PU)
0: speed command Internal (Pr.356) Speed command 16-bit data
10
Monitor display change
Monitor Remarks
When "19" is set in Pr.52 Operation panel main monitor selection, the position pulse
Position pulse monitor monitor is displayed instead of the output voltage monitor of the PU.
(Displayed only when the Vector control compatible option is mounted.)
When "22" is set in Pr.52, the orientation status is displayed instead of the output voltage
monitor of the PU. (Displayed only when the Vector control compatible option is mounted.)
0: Other than orientation operation or orientation speed is not reached
1: Orientation speed is reached
2: Creep speed is reached
Orientation status*1 3: Position loop is reached
4: Orientation complete
5: Orientation fault (pulse stop)
6: Orientation fault (orientation limit)
7: Orientation fault (recheck)
8: Continuous multi-point orientation
5. PARAMETERS
5.14 (A) Application parameters
559
• If the position detection value from the encoder enters ±∆θ during orientation stop, the Orientation complete (ORA) signal
is output.
Set point
360
Pr.357
Pr.369
4 times
Number of encoder pulses
2. After the speed reaches the orientation speed, the speed further decreases to the Pr.352 Creep speed as soon as
the current position pulse reaches the Pr.353 Creep switchover position.
(Pr.352 is initially set to 0.5 Hz, Pr.353 is initially set to "511".)
3. Moreover, as soon as the current position pulse reaches the Pr.354 Position loop switchover position, control is
changed to the position loop. (Pr.354 is initially set to "96".)
4. After the motor moves into the position loop, the motor decelerates and stops by the DC injection brake as soon as
the current position pulse reaches the Pr.355 DC injection brake start position. (Pr.355 is initially set to "5".)
5. When the motor stops in Pr.357 Orientation in-position zone, the orientation complete (ORA) signal is output after
Pr.363 Completion signal output delay time. If the motor does not stop within the in-position width because of
external force, etc., the ORA signal turns OFF after the time set in Pr.363. (Pr.357 is initially set to "5", Pr.363 is
initially set to 0.5 s.)
6. If the orientation is not completed continuously in Pr.365 Orientation limit after passing the creep switchover
position, the orientation fault signal (ORM) is output.
7. After the orientation starts, if the motor is stopped by external force, etc. before reaching the in-position width and
the ORA signal is not output, the ORM signal is output after the Pr.364 Encoder stop check time. If the motor is
moved out of the in-position width by external force, etc. after the ORA signal has been output once, the ORA signal
turns OFF after the set time in Pr.363. If the orientation is not completed within the time set in Pr.364, the ORM
signal is output.
8. If the ORA and ORM signals have been output once, but the start signal (STF or STR) is turned OFF while the X22
signal is ON, the ORA or ORM signal is output again after Pr.366 Recheck time.
9. The ORA and ORM signals cannot be output while the X22 signal is OFF.
560 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• When the orientation command turns OFF while the start signal is ON, the speed accelerates to the command speed. 1
Orientation Position loop
speed Home position
Orientation stop position command
DC injection brake 2
Creep switchover position Position loop switchover position
Creep
speed
• If hunting of the motor shaft occurs during orientation stop, set a larger value in Pr.354 or a smaller value in Pr.352 to prevent it.
Orientation speed (set with Pr.351)
3
Main spindle speed (encoder) Creep speed (set with Pr.352)
1)
Pr.351 2) 3) 4)
Pr.352
0 Time 4
Start signal (STF, STR) ON OFF
Orientation command (X22) OFF OFF
ON
Creep switchover position
(set with Pr.353)
5
DC injection Position loop switchover
Current position signal brake start
position (set with Pr.354)
(set with Pr.355) Stop position command
Origin signal 6
DC injection brake OFF ON OFF
Pr.352
Time
Start signal (STF, STR) OFF ON OFF
5. PARAMETERS
5.14 (A) Application parameters
561
Continuous multi-point orientation (V/F control, Advanced magnetic flux
vector control)
• Orientation during orientation operation or start signal is ON
Start signal ON
Orientation command ON
ON ON
DY
50ms or more is necessary
Position signal
Position command latch Position command latch
• The position data is read at the rising edge of DY. (For the details, refer to the Instruction Manual of FR-A8AX).
• When the position signal is within the creep switchover position, the speed starts up to the creep speed not to the
orientation speed.
• When the position signal is outside the creep switchover position, the speed starts up to the orientation speed.
• The DC injection brake operates if the position signal is within the DC injection brake start position.
• 16-bit data with the FR-A8AX is valid only when the DY signal is ON.
NOTE
• Couple the encoder with the motor shaft or with the shaft that stops the main shaft at the specified position. Couple it with the
speed ratio of 1:1 and without any mechanical looseness.
• The DC injection brake operates at orientation stop. Release the DC injection brake as soon as possible (within several
seconds), as continuous operation of the DC injection brake will cause the motor to overheat, leading to burnout.
• Because the servo lock function is not available after orientation stop, provide a holding mechanism, such as a mechanical
brake or knock pin, when secure holding of the main shaft is required.
• To ensure correct positioning, the encoder must be set in the proper rotation direction, and the A and B phases must be
connected correctly.
• If the pulse signal from the encoder stops due to encoder signal loss, etc. during orientation, the Orientation fault (ORM) signal
may be output.
• When performing orientation control, enable the DC injection brake (refer to page 681). When the DC injection brake is
disabled, orientation operation cannot be completed.
• When orientation control is performed, the DC injection brake operates regardless of the External DC injection brake operation
start (X13) signal even when Pr.11 DC injection brake operation time = "8888" (DC injection brake external selection).
• To terminate orientation, the start signal (STF or STR) must be first switched OFF, and then the Orientation command (X22)
signal must be switched OFF.As soon as this X22 signal is switched OFF, orientation control ends. (Depending on the (Pr.358
Servo torque selection setting, the orientation status continues if the X22 signal remains ON even if the DC injection brake
is released by turning OFF the start signal. Because of this, the orientation status on the monitor does not show "0".
• When the retry function of Pr.358 Servo torque selection is selected, the retry operation is performed three times including
the first orientation.
• When performing orientation control, properly set Pr.350 Stop position command selection and Pr.360 16-bit data
selection (external position command selection). If the values set are incorrect, proper orientation control will not be
performed.
• When orientation control is performed, PID control is disabled.
562 5. PARAMETERS
5.14 (A) Application parameters
Servo torque selection (Pr.358) (V/F control, Advanced magnetic flux
vector control) 1
Operation for each Pr.358 setting
Function and description Remarks
0 1 2 3 4 5 6 7 8 9 10 11 12 13
a.Servo torque function until
○: With servo torque function 2
output of the Orientation × ○ ○ ○ ○ × ○ × ○ × ○ × × ○
×: Without servo torque function
complete (ORA) signal
○: With retry function
b. Retry function × × × × × × × ○ × × × ○ × ×
×: Without retry function 3
c. Output frequency
○: With frequency compensation
compensation when the motor × × ○ ○ × ○ ○ × × × × × ○ ○
×: Without frequency compensation
stops outside the in-position zone
d. DC injection brake and servo 4
torque when the motor exits the
○: DC injection brake enabled
in-position zone after output of ○ × × × × ○ ○ ○ ○ ○ ○ ○ ○ ○
×: Servo torque enabled
the Orientation complete (ORA)
signal 5
○: When the start signal (STF, STR) or
e. Turning OFF the orientation
orientation command is turned OFF
complete signal (ORA) when the ○ ○ ○ × × ○ ○ ○ ○ × × × × ×
×: When the orientation command is
orientation operation is ended.
turned OFF 6
○: Turns OFF the complete signal
when the motor exits the in-position
f. Complete signal when the
zone
motor exits the in-position zone
after output of the Orientation
○ ○ ○ ○ ○ × × × × × × × × × ×: Complete signal remains ON even if
the motor exits the in-position zone
7
complete (ORA) signal
(the Orientation fault (ORM) signal is
not output)
10
5. PARAMETERS
5.14 (A) Application parameters
563
NOTE
• When the orientation command turns OFF while the start signal is ON, the motor accelerates to the command speed.
• When the motor shaft stops outside of the set setting range of the stop position, the motor shaft is returned to the stop position
by the servo torque function (if enough torque is generated).
Position loop gain (Pr.362) (V/F control, Advanced magnetic flux vector
control)
• When the servo torque function is selected using Pr.358 Servo torque selection, the output frequency for generating
servo torque gradually increases to the Pr.352 Creep speed according to the slope set in Pr.362 Orientation position
loop gain.
• Although the operation becomes faster when the value is increased, hunting may occur in the machine.
564 5. PARAMETERS
5.14 (A) Application parameters
Description of orientation operation (Vector control)
• Setting the rotation direction (Pr.393 Orientation selection) 1
Rotation
Pr.393 setting Remarks
direction
0 (initial value) Pre-orientation Orientation is executed from the current rotation direction.
Orientation is executed from the forward rotation direction.
2
Forward rotation
1 (If the motor is running in reverse, orientation is executed from the forward
orientation
rotation direction after deceleration.) Motor end orientation
2
Reverse rotation
Orientation is executed from the forward rotation direction.
(If the motor is running forward, orientation is executed from the reverse
3
orientation
rotation direction after deceleration.)
10 Pre-orientation Orientation is executed from the current rotation direction.
11 Forward rotation
orientation
Orientation is executed from the forward rotation direction. (If the motor is
running in reverse, orientation is executed from the forward rotation
4
direction after deceleration.) Machine end orientation
12 Reverse rotation Orientation is executed from the forward rotation direction. (If the motor is
orientation running forward, orientation is executed from the reverse rotation direction
after deceleration.)
5
Orientation from the current rotation direction (Pr.393 = "0 (initial value)")
(Vector control) 6
• When the Orientation command (X22) signal is input, the motor speed decelerates from the running speed to Pr.351
Orientation speed. At the same time, the orientation stop position command is read in. (The stop position command is
determined by the setting of Pr.350 Stop position command selection, Pr.360 16-bit data selection)
7
Speed
(forward
Speed
(reverse
[t] 8
rotation) rotation)
[t]
X22
ORA
OFF ON
OFF ON
X22
ORA
OFF ON
OFF ON
9
• When the orientation switchover speed is reached, the encoder Z phase pulse is confirmed, and the control changes from
speed control to position control (Pr.362 Orientation position loop gain). 10
• The distance to the orientation stop position is calculated at switching of the control, and the motor decelerates to a stop
with a set deceleration pattern (Pr.399 Orientation deceleration ratio) and enters the orientation (servo lock) state.
• Once in the Pr.357 Orientation in-position zone, the Orientation complete (ORA) signal is output.
• The home position can be moved using Pr.361 Position shift.
CAUTION
• If the X22 is turned OFF while the start signal is input, the motor accelerates toward the speed of the current speed
command. Therefore, to stop, turn the Forward rotation (Reverse rotation) signal OFF.
5. PARAMETERS
5.14 (A) Application parameters
565
• If the motor is running in reverse, it decelerates, change to the forward rotation direction, and then orientation stop is
executed.
Speed
Speed [t]
(forward
rotation) (reverse
[t]
rotation)
X22
ORA X22
ORA
Orientation from the reverse rotation direction (Pr.393 = "2, 12") (Vector
control)
• If the motor is running in the forward rotation direction, it executes an orientation stop with the same method as "orientation
from the current rotation direction".
• If the motor is running in forward, it decelerates, change to the reverse rotation direction, and then orientation stop is
executed.
X22
X22
ORA ORA
NOTE
• Couple the encoder with the motor shaft that stops the shaft at the specified position. Couple it with the speed ratio of 1:1 and
without any mechanical looseness.
• To ensure correct positioning, the encoder must be set in the proper rotation direction, and the A and B phases must be
connected correctly.
• If the pulse signal from the encoder stops due to encoder signal loss, etc. during orientation, orientation may not be completed.
• To terminate orientation, the start (STF or STR) signal must be first switched OFF, and then the Orientation (X22) signal must
be switched OFF. As soon as this X22 signal is switched OFF, orientation control ends.
• When performing orientation control, properly set Pr.350 Stop position command selection and Pr.360 16-bit data
selection.
If the values set are incorrect, proper orientation control will not be performed.
• When orientation control is performed, PID control is disabled.
• If Signal loss detection (E.ECT) is displayed when the X22 signal is ON, causing the inverter to trip, check for a break in the
cable of the Z phase of the encoder.
1. Increase the Pr.362 Orientation position loop gain value to the extent that rocking*2 does not occur during
orientation stop.
566 5. PARAMETERS
5.14 (A) Application parameters
3. Pr.398 Orientation speed gain (D term) is the lag/advance compensation gain.
The limit cycle*3 can be prevented by increasing the value, and operation can be stopped stably. However, the torque
1
decreases in relation to the position deviation, and the motor stops with deviation.
*1 Servo rigidity: The response when a position control loop is configured.
When the servo rigidity is raised, the holding force increases and operation becomes stabilized, but vibration occurs more easily.
When the servo rigidity is lowered, the holding force decreases, and the settling time increases. 2
*2 Rocking: Movement in which return occurs when the stopping position is exceeded.
*3 Limit cycle: This is a phenomenon that generates ± continuous vibration centering on the target position.
NOTE
• Orientation stop operation fails, causing an excessive position error. or if the motor performs forward/reverse reciprocation 9
operation , review the settings of Pr.393 Orientation selection (on page 556) and Pr.359 Encoder rotation direction (on
page 555).
10
Pr.351 Orientation speed (initial value: 2 Hz) (Vector control)
• Set the speed when switching between the speed control mode and the position control mode is performed under
orientation operation.
Decreasing the set speed enables stable orientation stop. Note that the orientation time increases.
[Hz]
Frequency
NOTE
• When "19" is set in Pr.52 Operation panel main monitor selection, the position pulse monitor is displayed instead of the
output voltage monitor on the PU.
5. PARAMETERS
5.14 (A) Application parameters
567
Machine end orientation connection diagram (Vector control)
• To perform machine end orientation control, the following settings are required.
- Install a plug-in option (FR-A8AP/FR-A8AL or FR-A8APR) and a control terminal option (FR-A8TP) to the inverter, a motor end
encoder to the control terminal option, and a machine end encoder to the plug-in option.
- Set "1" in Pr.862 Encoder option selection.
- Set Pr.393 Orientation selection = "10 to 12". (Refer to page 565.)
- Set the gear ratio by setting Pr.394 Number of machine side gear teeth and Pr.395 Number of motor side gear teeth. (Refer to
page 568.)
MCCB MC Inverter SF-JR motor with encoder For 24 V complementary type (SF-V5RU)
R/L1 U U MCCB MC OCR SF-V5RU
Three-phase ∗1
S/L2 V V
AC power IM Three-phase
FAN
supply T/L3 W W AC power
supply
E
Earth Inverter U U
V V
FR-A8TP (Ground) W
IM
W
Forward rotation start STF PA3 C ∗2 E
R Earth
Reverse rotation start STR PAR3 (Ground)
FR-A8TP PC Thermal
Orientation command X22∗3 A relay
PB3 External OH
G1 protector
Contact input common thermal relay
SD PBR3 N input ∗11 SD G2
ORA∗4 Encoder
Differential
PZ3 B PA3 A ∗2
ORM
∗4 P PAR3 B
PZR3 ∗5
PB3 C
SE Complementary PG H Differential PBR3 D
SD SD K PZ3 F
Encoder
Terminating
resistor ON
Complementary PZR3 G ∗5
PG
Terminating PG S
∗7 SD ∗6 resistor ON
SD R
∗8 (+) (-) 5 VDC power ∗7 PG24
OFF
supply ∗9 OFF ∗8 ∗6
∗9
FR-A8AX FR-A8AP FR-A8AP
PA1 A ∗2
X15 ∗10 PA1 A ∗2 Machine end Machine end
X14 PA2 A encoder encoder
PB1 B
Differential (differential Differential
X1 PB1 B line driver) Encoder
PZ1 Z
X0 PB2 B Complementary
∗5
Complementary
DY Encoder
PZ1 Z Terminating PG +
resistor ON
Terminating SD -
PZ2 Z ∗5 ∗7 PG
resistor ON
OFF SD ∗6
PG +
∗7 (-) Power supply ∗9
(+)
SD - ∗8
OFF
PG
SD ∗6
(+) (-) Power supply ∗9
*1 Single-phase power supply (200 V/50 Hz, 200 to 230 V/60 Hz) is used for the fan for a 7.5 kW or lower dedicated motor.
*2 The pin number differs according to the encoder used.
*3 Use Pr.178 to Pr.182, Pr.185, or Pr.1899 (input terminal function selection) to assign the function to a terminal. (Refer to page 496.)
*4 Use Pr.190 to Pr.192, or Pr.195 (output terminal function selection) to assign the function to a terminal. (Refer to page 450.)
*5 Connect the encoder so that there is no looseness between the motor and motor shaft. Speed ratio must be 1:1.
*6 Earth (ground) the shield of the encoder cable to the enclosure using a tool such as a P-clip. (Refer to page 87.)
*7 For the differential line driver, set the terminating resistor selection switch to the ON position. (Refer to page 92.)
Note that the terminating resistor switch should be set to the OFF position (initial status) when sharing the same encoder with another unit (NC,
etc.) having a terminating resistor under the differential line driver setting.
For the complementary, set the switch to the OFF position.
*8 For terminal compatibility between the FR-A8TP and the FR-JCBL/FR-V7CBL, refer to the Instruction Manual of the FR-A8TP.
*9 A separate power supply of 5 V/12 V/15 V is necessary according to the encoder power specification. When the encoder output is the differential
line driver type, only 5 V can be input. Make the voltage of the external power supply same as the encoder output voltage, and connect the external
power supply between PG and SD. If using the 24V power supply of the FR-A8TP, 24V power can be supplied from terminal PG24.
When performing encoder feedback control and Vector control together, an encoder and power supply can be shared.
*10 When a stop position command is input from outside, a plug-in option FR-A8AX is required. Refer to page 558 for the external stop position
command.
*11 To enable terminal OH, set Pr.876 Thermal protector input = "1 (initial value)". (Refer to page 399.)
568 5. PARAMETERS
5.14 (A) Application parameters
• Set the encoder orientation gear ratio in Pr.394 Number of machine side gear teeth, Pr.395 Number of motor side gear
teeth An accurate gear ratio (or pulley ratio) from the motor shaft to the spindle is necessary.
1
Set the correct numbers of gear teeth in Pr.394 and Pr.395.
Pr.394 = A × C × E
Pr.395 = B × D × F 2
Exercise care so that the A × C × E and B × D × F settings do not exceed 32767. If either or both of them exceed that value, make
approximations.
Spindle A 3
B
C
(A to F indicate the
D E
4
numbers of gear teeth.) F Motor
NOTE
• Pulley ratio: Ratio of vector-driven motor side pulley diameter to spindle side pulley diameter 5
A B A
B
6
Spindle side Motor side
NOTE
• For other settings, refer to descriptions of motor end orientation control in this manual.
5. PARAMETERS
5.14 (A) Application parameters
569
5.14.10 PID control
Process control such as flow rate, air volume or pressure are possible on the inverter.
A feedback system can be configured and PID control can be performed using the terminal 2 input signal or parameter setting
value as the set point and the terminal 4 input signal as the feedback value.
570 5. PARAMETERS
5.14 (A) Application parameters
Pr. Name Initial value Setting range Description
1 Input of measured value from terminal 1
2 Input of measured value from terminal 2
1
610 PID measured value 3 Input of measured value from terminal 4
3
A625 input selection Input of set point, deviation value via CC-Link/CC-Link IE Field
4
5
Network communication
Input measured value by PLC function
2
Integral stopped at the limit, manipulation range of ±100%, integral
0
cleared during output interruption
1
Integral continued at the limit, manipulation range of ±100%, 3
integral cleared during output interruption
Integral stopped at the limit, manipulation range of 0 to 100%,
2
1015 Integral stop selection at integral cleared during output interruption
A607 limited frequency
0
10
Integral stopped at the limit, manipulation range of ±100%, integral 4
stopped during output interruption
Integral continued at the limit, manipulation range of ±100%,
11
integral stopped during output interruption
12
Integral stopped at the limit, manipulation range of 0 to 100%, 5
integral stopped during output interruption
0, 10, 11, 20, 21,
50, 51, 60, 61, 70,
753 Second PID action
71, 80, 81, 90, 91, 6
0 100, 101, 1000, Refer to Pr.128.
A650 selection
1001, 1010,
1011, 2000,
2001, 2010, 2011 7
Second PID control
754
automatic switchover 9999 0 to 590 Hz, 9999 Refer to Pr.127.
A652
frequency
755 Second PID action set
9999 0 to 100%, 9999 Refer to Pr.133.
8
A651 point
756 Second PID proportional 0.1 to 1000%,
100 Refer to Pr.129.
A653 band 9999
757
Second PID integral time 1 s
0.1 to 3600 s,
Refer to Pr.130.
9
A654 9999
758 Second PID differential
9999 0.01 to 10 s, 9999 Refer to Pr.134.
A655 time
1140 Second PID set point/ Set the second PID control.
10
2 1 to 5 Refer to Pr.609.
A664 deviation input selection For how to enable the second PID
1141 Second PID measured control, refer to page 582.
3 1 to 5 Refer to Pr.610.
A665 value input selection
1143
Second PID upper limit 9999 0 to 100%, 9999 Refer to Pr.131.
A641
1144
Second PID lower limit 9999 0 to 100%, 9999 Refer to Pr.132.
A642
Refer to Pr.553.
1145 Second PID deviation
9999 0 to 100%, 9999 (The Y205 signal is
A643 limit
output.)
1146 Second PID signal
0 0 to 3, 10 to 13 Refer to Pr.554.
A644 operation selection
Second output
1147
interruption detection 1s 0 to 3600 s, 9999 Refer to Pr.575.
A661
time
Second output
1148
interruption detection 0 Hz 0 to 590 Hz Refer to Pr.576.
A662
level
1149 Second output
1000% 900 to 1100% Refer to Pr.577.
A663 interruption cancel level
5. PARAMETERS
5.14 (A) Application parameters
571
Basic configuration of PID control
Pr.128 ="10, 11" (deviation value signal input)
Inverter circuit
Measured value
P action
Time
I action
Time
PI action
Time
PD action
PD action is a combination of proportional action (P) and differential action (D), and applies a manipulated amount according
to the speed of the deviation to improve excessive characteristics.
[Example of action when the measured value changes proportionately]
Set point
Deviation
Measured value
P action
Time
D action
Time
PD
action
Time
572 5. PARAMETERS
5.14 (A) Application parameters
PID action
PID action is a combination of PI and PD action, which enables control that incorporates the respective strengths of these
actions.
1
Set point
Measured value
Deviation
2
P action
Time
I action
3
Time
D action
Time
4
PID action
Time
5
(Note) PID action is the result of all P, I and D actions being added together.
Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output frequency) is increased, and
6
when the deviation is a minus value, the manipulated amount is decreased.
Deviation Set point
[Heating] 7
+ X>0
Set Cold Increase
point X<0 Hot Decrease
- Measured value 8
Feedback signal
(measured value)
Forward action 9
When deviation X = (set point - measured value) is a minus value, the manipulated amount (output frequency) is increased,
and when the deviation is a plus value, the manipulated amount is decreased.
[Cooling]
Measured value 10
+ X>0 Set point
Set Too cold Decrease
point - X<0 Hot Increase
Feedback signal
(measured value) Deviation
5. PARAMETERS
5.14 (A) Application parameters
573
Connection diagram
• Sink logic Inverter
MCCB Motor Pump
• Pr.128 = 20 R/L1 U
Power supply
• Pr.183 = 14 S/L2 V M P
T/L3 W
• Pr.191 = 47
• Pr.192 = 16 Forward
rotation STF
• Pr.193 = 14 Reverse STR
• Pr.194 = 15 rotation
RT(X14)∗3 2-wire type 3-wire
PID control
selection SD ∗2(PID)SU During PID action Detector type
∗2(FUP)FU Upper limit
Setting 10 ∗2(FDN)OL Lower limit
- + + - +
Potentiometer 2 ∗2(RL)IPF
Forward rotation
output
(Set point setting) Reverse rotation
5
output
1 (OUT) (24V)
4 ∗4 SE Output signal common (COM)
0 24V
Power
supply ∗1
AC1φ
200/220V 50/60Hz
*1 Prepare a power supply matched to the power supply specifications of the detector.
*2 The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3 The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection)
*4 The AU signal need not be input.
Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
574 5. PARAMETERS
5.14 (A) Application parameters
• Switch the power voltage/current specifications of terminals 2 and 4 by Pr.73 Analog input selection or Pr.267 Terminal
4 input selection to match the specification of the input device. After changing the Pr.73 or Pr.267 settings, check the
voltage/current input selection switch. Incorrect setting may cause a fault, failure, or malfunction. (Refer to page 473 for
1
the setting.)
Pr.128
setting
Pr.609
Pr.610
PID action Set point input Measured value input Deviation input 2
0 PID invalid — — —
10 Reverse action
— — Terminal 1
11 Invalid Forward action 3
20 Reverse action *1
Terminal 2 or Pr.133 Terminal 4 —
21 Forward action
40 to 43 Enabled Dancer control For details on dancer control, refer to page 590.
50 Reverse action CC-Link/CC-Link IE 4
— — Field Network
51 Forward action
communication*2
60 Reverse action
CC-Link/CC-Link IE Field
CC-Link/CC-Link IE
Field Network —
5
61 Forward action Network communication*2
communication*2
70 Reverse action PLC function
71 Forward action
— — (with frequency 6
applied)*3
Invalid
80 Reverse action PLC function
PLC function
(with frequency —
81 Forward action (with frequency applied)*3
applied)*3 7
90 Reverse action PLC function
— — (without frequency
91 Forward action
applied)*3
100 Reverse action PLC function PLC function
8
(without frequency (without frequency —
101 Forward action
applied)*3 applied)*3
1000
1001
Reverse action
Forward action
According to Pr.609*1 According to Pr.610 — 9
1010 Reverse action
— — According to Pr.609
1011 Forward action
2000
Reverse action (without 10
Enabled frequency reflected)
According to Pr.609*1 According to Pr.610 —
Forward action (without
2001
frequency reflected)
Reverse action (without
2010
frequency reflected)
— — According to Pr.609
Forward action (without
2011
frequency reflected)
*1 When Pr.133 ≠ "9999", the Pr.133 setting is valid.
*2 For the details of CC-Link/CC-Link IE field communication, refer to the Instruction Manual of the option FR-A8NC, FR-A8NCE.
*3 For the details of the PLC function, refer to the FR-A800 PLC Function Programming Manual.
• The set point/deviation input method can also be flexibly selected by Pr.609 PID set point/deviation input selection and
the measured value input method can be selected by Pr.610 PID measured value input selection. Selection by Pr.609
and Pr.610 is valid when Pr.128 = "1000 to 2011".
Pr.609 to Pr.610 settings Input method
1 Terminal 1*4
2 Terminal 2*4
3 Terminal 4*4
4 CC-Link/CC-Link IE Field Network communication
5 PLC function
*4 When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%)
5. PARAMETERS
5.14 (A) Application parameters
575
NOTE
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
Input/output signals
• Assigning the PID control valid signal (X14) to the input terminal by Pr.178 to Pr.189 (Input terminal function selection)
enables PID control to be performed only when the X14 signal is turned ON. When the X14 signal is OFF, regular inverter
running is performed without PID action . (When the X14 signal is not assigned, PID control is enabled only by setting
Pr.128 ≠ "0".)
• Input signal
Pr.178 to
Signal Function Pr.189 Description
setting
X14 PID control valid 14 When this signal is assigned to the input terminal, PID control is enabled when this
X80 Second PID control valid 80 signal is ON.
PID forward/reverse
X64 64
action switchover
PID control is switched between forward and reverse action without changing
Second PID forward/ parameters by turning ON this signal.
X79 reverse action 79
switchover
X72 PID P control switchover 72
Second PID P control Integral and differential values can be reset by turning ON this signal.
X73 73
switchover
576 5. PARAMETERS
5.14 (A) Application parameters
• Output signal
Pr.190 to
Pr.196
1
Signal Function setting Description
Positive Negative
SLEEP2
During second PID
204 304
interruption detection time) ≠ "9999". This signal turns ON when the PID 6
output shutoff output suspension function is activated.
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
7
confirming the function of each terminal.
Output frequency 10
Without PID
control PID control
Pr.127
Time
STF
PID
5. PARAMETERS
5.14 (A) Application parameters
577
• The stop action when the inverter output is shut off by the SLEEP function can be selected.
Inverter operation
Pr.554 setting
At FUP signal, FDN signal output*1 At Y48 signal output*1 At SLEEP operation start
0 (initial value) Signal output only
Signal output only
1 Signal output + output shutoff (E.PID)
Coasts to stop
2 Signal output only
Signal output + output shutoff (E.PID)
3 Signal output + output shutoff (E.PID)
10 Signal output only
Signal output only
11 Signal output + output shutoff (E.PID)
Deceleration stop
12 Signal output only
Signal output + output shutoff (E.PID)
13 Signal output + output shutoff (E.PID)
*1 When each of Pr.131, Pr.132 and Pr.553settings corresponding to each of the FUP, FDN and Y48 signals is "9999" (no function), signal output
and protective function are not available.
Output frequency
Pr.576
RUN OFF
PID
SLEEP ON
578 5. PARAMETERS
5.14 (A) Application parameters
When Pr.554="10 to 13", reverse operation (Pr.128="10") 1
Deviation
3
Output frequency
Deceleration stop ∗1
Pr.576 4
Less than Pr.575
Pr.575 or more SLEEP period
Time
OFF
5
RUN
PID
SLEEP ON
6
*1 When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration, Pr.576 Output interruption detection level is invalid.
NOTE
• While the integral stop is selected, the integral stop is enabled when any of the following conditions is met.
5. PARAMETERS
5.14 (A) Application parameters
579
• Set the following values to Pr.52 Operation panel main monitor selection, Pr.774 to Pr.776 (Operation panel monitor
selection), Pr.992 Operation panel setting dial push monitor selection, Pr.54 FM/CA terminal function selection
and Pr.158 AM terminal function selection for each monitor.
Monitor range
Parameter Monitor Minimum
Terminal FM/ Terminal Operation Remarks
Setting description increment
CA AM panel
52 PID set point
Second PID set
0.1% 0 to 100%*1
92 point/deviation
input selection "0" is displayed at all times when PID control
PID measured is based in deviation input.
53
value
0.1% 0 to 100%*1
Second PID
93
measured value
PID measured Displays PID measured value even if the PID
67
value 2 control operating conditions are not satisfied
0.1% 0 to 100%*1 while the PID control is enabled.
Second PID
95 "0" is displayed at all times when PID control
measured value 2
is based in deviation input.
54 PID deviation 900% to
1100% Using Pr.290 Monitor negative output
Setting not -100% to
Second PID 0.1% or selection, negative values can be output to
94 available 100%*1*2 -100% to
deviation the terminal AM and displayed with a minus
100%*1 sign on the operation panel (FR-DU08).
PID manipulated 900% to When signed indication is invalid, the
91 indicated values are from "900%" to "1100%"
amount 1100%
Setting not -100% to on the operation panel. (0% is offset and
Second PID 0.1% or
available 100%*2 -100% to displayed as "1000%".)
96 manipulated
amount 100%
*1 When C42(Pr.934) and C44(Pr.935) are set, the minimum increment changes from unit % to no unit, and the monitor range can be changed.
(Refer to page 584.)
*2 When the minus value display is set disabled using Pr.290, the terminal AM output becomes "0".
Adjustment procedure
1. Enable PID control
When Pr.128 ≠ "0", PID control is enabled.
Set the set point, measured value and deviation input methods at Pr.128, Pr.609 and Pr.610.
3. Terminal setting
Set the I/O terminals for PID control. (Pr.178 to Pr.189 (Input terminal function selection), Pr.190 to Pr.196
(Output terminal function selection))
5. Operation
580 5. PARAMETERS
5.14 (A) Application parameters
Calibration example
(Adjust room temperature to 25°C by PID control using a detector that outputs 4 mA at 0°C and 20 mA at 50°C.) 1
Start
4
Make calibration. Make the following calibration∗1 when the target setting input (0 to 5 V)
and detector output (4 to 20mA) must be calibrated.
5
Setting of set point • To set the set point to 50% using voltage input
The terminal 2 specification is 0 V for 0%, and 5 V for 100%. Thus, to set to 50%, input 2.5 V to the terminal 2.
Input a voltage across terminals 2-5
• To set the set point to 50% using parameters
according to the set value %.
Set Pr.133 = "50". (If C42(Pr.934) and C44(Pr.935) ≠ "9999", set "25 (no % conversion)" directly in Pr.133.)
Operation When performing operation, first set the proportional band (Pr. 129) to a slightly larger value, the integral time 6
(Pr. 130) to a slightly longer time, and the differential time (Pr. 134) to "9999" (no function), and while looking
Set the proportional band (Pr. 129) at the system operation, decrease the proportional band (Pr. 129) and increase the integral time (Pr. 130).
to a slightly larger value, the integral
time (Pr. 130) to a slightly longer For slow response system where a deadband exists, differential control (Pr. 134) should be turned ON and
7
time, and the differential time (Pr. increased slowly.
134) to "9999" (no function), and turn
ON the start signal.
Parameter adjustment
To stabilize the measured value, change
Parameter optimization
While the measured value is stable
9
the proportional band (Pr. 129) to a larger throughout the operation status, the
value, the integral time (Pr. 130) to a proportional band (Pr. 129) may be
slightly longer time, and the differential decreased, the integral time (Pr. 130)
10
time (Pr. 134) to a slightly shorter time. decreased, and the differential time (Pr. 134)
may be increased.
Adjustment end
1. 1. Apply the input (for example, 0 V) of set point setting 0% across terminals 2 and 5.
2. Using C2 (Pr.902), enter the frequency (for example, 0 Hz) to be output by the inverter when the deviation is 0%.
4. Apply the input (for example, 5 V) of set point setting 100% across terminals 2 and 5.
5. Using Pr.125, enter the frequency (for example, 60 Hz) to be output by the inverter when the deviation is 100%.
5. PARAMETERS
5.14 (A) Application parameters
581
NOTE
• When the set point is set at Pr.133, the setting frequency of C2 (Pr.902) is equivalent to 0% and the setting frequency of Pr.125
(Pr.903) is equivalent to 100%.
1. Apply the input (for example, 4 mA) of measured value 0% across terminals 4 and 5.
3. Apply the input (for example, 20 mA) of measured value 100% across terminals 4 and 5.
NOTE
• Set the frequencies set at C5 (Pr.904) and Pr.126 to each of the same values set at C2 (Pr.902) and Pr.125.
• The display unit for analog input can be changed from "%" to "V" or "mA". (Refer to page 484.)
• The following figure shows the results of having performed the calibration above.
0 0 0
0 5 (V) 0 4 20 (mA) 0 100 Deviation (%)
*1 While Pr.155 = "0", the second function is enabled immediately after RT signal turns ON. While Pr.155 = "10", the second function is enabled
only during constant speed operation when RT signal turns ON. (For the details, refer to page 500.)
*2 When dancer control is selected, the setting is not applied to the frequency.
582 5. PARAMETERS
5.14 (A) Application parameters
• The second PID function parameters and signals function in the same way as the following parameters and signals of the
first PID function. Refer to the first PID function when setting the second PID functions.
1
First PID function parameters Second PID function parameters
Classification
Pr. Name Pr. Name
PID control automatic switchover Second PID control automatic
127
frequency
754
switchover frequency 2
128 PID action selection 753 Second PID action selection
129 PID proportional band 756 Second PID proportional band
130
131
PID integral time
PID upper limit
757
1143
Second PID integral time
Second PID upper limit
3
132 PID lower limit 1144 Second PID lower limit
133 PID action set point 755 Second PID action set point
134 PID differential time 758 Second PID differential time 4
Parameter 553 PID deviation limit 1145 Second PID deviation limit
554 PID signal operation selection 1146 Second PID signal operation selection
Output interruption detection Second output interruption detection
575
time
1147
time 5
Output interruption detection Second output interruption detection
576 1148
level level
577 Output interruption cancel level
PID set point/deviation input
1149 Second output interruption cancel level
Second PID set point/deviation input
6
609 1140
selection selection
PID measured value input Second PID measured value input
610 1141
selection selection
7
First PID function parameters Second PID function parameters
Classification
Signal Name Signal Name
X14 PID control valid
PID forward/reverse action
X80 Second PID control valid
Second PID forward/reverse action
8
Input signal X64 X79
switchover switchover
X72 PID P control switchover X73 Second PID P control switchover
FUP PID upper limit FUP2 Second PID upper limit 9
FDN PID lower limit FDN2 Second PID lower limit
PID forward/reverse rotation Second PID forward/reverse rotation
RL RL2
Output signal output output
PID During PID control activated PID2 Second During PID control activated 10
SLEEP PID output interruption SLEEP2 During second PID output shutoff
Y48 PID deviation limit Y205 Second PID deviation limit
NOTE
• Even if the X14 signal is ON, PID control is stopped and multi-speed or JOG operation is performed when the multi-speed
operation (RH, RM, RL, or REX) signal or JOG signal (JOG operation) is input.
• PID control is invalid under the following settings.
Pr.79 Operation mode selection = "6" (Switchover mode)
• Note that input to the terminal 1 is added to the terminals 2 and 4 inputs. For example when Pr.128 = "20 or 21", the terminal
1 input is considered as a set point and added to the set point of the terminal 2.
• To use terminal 4 and 1 inputs in PID control, set "0" (initial value) to Pr.858 Terminal 4 function assignment and Pr.868
Terminal 1 function assignment. When a value other than "0", PID control is invalid.
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196may affect other functions. Set parameters after
confirming the function of each terminal.
• When PID control is selected, the minimum frequency becomes the frequency of Pr.902 and the maximum frequency becomes
the frequency of Pr.903.
(The Pr.1 Maximum frequency and Pr.2 Minimum frequency settings also are valid.)
5. PARAMETERS
5.14 (A) Application parameters
583
• During PID operation, the remote operation function is invalid.
• When control is switched to PID control during normal operation, the frequency during that operation is not carried over, and
the value resulting from PID calculation referenced to 0 Hz becomes the command frequency.
Frequency
command
Frequency command
during normal operation
PID action ON
Normal operation PID operation Normal operation
Parameters referred to
Pr.59 Remote function selectionpage 359
Pr.73 Analog input selectionpage 473
Pr.79 Operation mode selectionpage 370
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.290 Monitor negative output selectionpage 435
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gainpage 482
Setting
Pr. Name Initial value Description
range
Change the unit of the PID control-related values that is
759 0 to 43 displayed on the LCD operation panel (FR-LU08) or the
PID unit selection 0 parameter unit (FR-PU07).
A600
9999 Without display unit switching
Set the coefficient of the bias side (minimum) of measured value
C42(934) 0 to 500
PID display bias coefficient 9999 input.
A630*1
9999 Displayed in %.
C43(934) Set the converted % of the bias side (minimum) current/voltage
PID display bias analog value 20% 0 to 300%
A631*1 of measured value input.
Set the coefficient of the gain side (maximum) of measured value
C44(935) 0 to 500
PID display gain coefficient 9999 input.
A632*1
9999 Displayed in %.
C45(935) Set the converted % of the gain side (maximum) current/voltage
PID display gain analog value 100% 0 to 300%
A633*1 of measured value input.
1136 Second PID display bias 0 to 500
9999 Refer to C42(934).
A670 coefficient 9999
1137 Second PID display bias
20% 0 to 300% Refer to C43(934).
A671 analog value
1138 Second PID display gain 0 to 500
9999 Refer to C44(935). Second PID control
A672 coefficient 9999
1139 Second PID display gain
100% 0 to 300% Refer to C45(935).
A673 analog value
1142 0 to 43,
Second PID unit selection 9999 Refer to Pr.759.
A640 9999
*1 The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
Calibration of PID display bias and gain (C42 (Pr.934) to C45 (Pr.935))
• When both C42 (Pr.934) and C44 (Pr.935) ≠ "9999", the bias and gain values for the set point, measured value and
deviation in PID control can be calibrated.
584 5. PARAMETERS
5.14 (A) Application parameters
• "Bias"/"gain" function can adjust the relation between PID displayed coefficient and measured value input signal that is
externally input. Examples of these measured value input signals are 0 to 5 VDC, 0 to 10 VDC, or 4 to 2 mADC. (The
terminals used for measured value input can be selected at Pr.128, Pr.609, Pr.610.)
1
• Set the value that is displayed when the PID measured value (control amount) is 0% to C42 (Pr.934) and the value that is
displayed when the PID measured value (control amount) is 100% to C44 (Pr.935).
• When both of C42 (Pr.934) and C44 (Pr.935) ≠"9999" and Pr.133 is set as the set point, the setting of C42 (Pr.934) is
2
treated as 0%, and C44 (Pr.935) as 100%.
Initial value
100 3
Coefficient
4
Gain
Bias C44 (Pr.935)
C42 (Pr.934)
0 20 100%
5
0 4 20mA
Frequency setting signal
0 1 5V
6
0 2 10V
C43 (Pr.934) C45 (Pr.935)
• Take caution when the following condition is satisfied because the inverter recognizes the deviation value as a negative 10
(positive) value even though a positive (negative) deviation is given: Pr.934 (PID bias coefficient) > Pr.935 (PID gain
coefficient).
To perform a reverse action, set Pr.128 PID action selection to forward action. Alternatively, to perform a forward action,
set Pr.128 to reverse action. In this case, the PID output shutoff release level is (1000 - Pr.577).
Pr.934 < Pr.935 (normal setting) Pr.934 ≥ Pr.935
Reverse action Reverse action setting to Pr.128 Reverse action Forward action setting to Pr.128
Forward action Forward action setting to Pr.128 Forward action Reverse action setting to Pr.128
PID output shutoff release level Pr.577 - 1000 PID output shutoff release level 1000 - Pr.577
(Example) Set the following: Pr.934 = "500" or 20% (4 mA is applied), Pr.935 = "100" or 100% (20 mA is applied).
When the set point = 400 and the measured value = 360, the deviation is +40 (>0), but the inverter recognizes the deviation
as -10% (<0). Because of this, operation amount does not increase in the reverse operation setting.
The operation amount increases when the forward operation is set.
To perform PID output shutoff release at deviation of +40 or higher, set Pr.577 = "960".
5. PARAMETERS
5.14 (A) Application parameters
585
500
100
0
20% 100%
∗ ( ) indicates the deviation value (0%) (25%) (35%) (100%)
which the inverter can recognize
Deviation -10%
• The display of the following parameters is changed according to the C42 (Pr.934), C44 (Pr.935), Pr.1136, and Pr1138
settings.
Pr. Name Pr. Name
131 PID upper limit 1143 Second PID upper limit
132 PID lower limit 1144 Second PID lower limit
133 PID action set point 755 Second PID action set point
553 PID deviation limit 1145 Second PID deviation limit
577 Output interruption cancel level 1149 Second output interruption cancel level
761 Pre-charge ending level 766 Second pre-charge ending level
763 Pre-charge upper detection level 768 Second pre-charge upper detection level
Changing the PID display coefficient of the LCD operation panel (FR-
LU08) or the parameter unit (FR-PU07) (Pr.759)
• Use Pr.759 PID unit selection to change the unit of the displayed value on the FR-LU08 or the FR-PU07. For the
coefficient set in C42 (Pr.934) to C44 (Pr.935), the units can be changed as follows.
Unit Unit
Pr.759 setting Unit name Pr.759 setting Unit name
indication indication
9999 % % 21 CMS Cubic Meter per Second
0 — (No indication) 22 ftM Feet per Minute
1 K Kelvin 23 ftS Feet per Second
2 C Degree Celsius 24 m/M Meter per Minute
3 F Degree Fahrenheit 25 m/S Meter per Second
4 PSI Pound-force per Square Inch 26 lbH Pound per Hour
5 MPa Mega Pascal 27 lbM Pound per Minute
6 kPa Kilo Pascal 28 lbS Pound per Second
7 Pa Pascal 29 iWC Inch Water Column
8 bar Bar 30 iWG Inch Water Gauge
9 mbr Millibar 31 fWG Feet of Water Gauge
10 GPH Gallon per Hour 32 mWG Meter of Water Gauge
11 GPM Gallon per Minute 33 iHg Inches of Mercury
12 GPS Gallon per Second 34 mHg Millimeters of Mercury
13 L/H Liter per Hour 35 kgH Kilogram per Hour
14 L/M Liter per Minute 36 kgM Kilogram per Minute
15 L/S Liter per Second 37 kgS Kilogram per Second
16 CFH Cubic Feet per Hour 38 ppm Pulse per Minute
17 CFM Cubic Feet per Minute 39 pps Pulse per Second
18 CFS Cubic Feet per Second 40 kW Kilowatt
19 CMH Cubic Meter per Hour 41 hp Horse Power
42 Hz Hertz
20 CMM Cubic Meter per Minute
43 rpm Revolution per Minute
586 5. PARAMETERS
5.14 (A) Application parameters
5.14.12 PID Pre-charge function
This function drives the motor at a certain speed before starting PID control. This function is useful for a pump with a long hose, 1
since PID control would start before the pump is filled with water, and proper control would not be performed without this
function,
2
Initial Setting
Pr. Name Description
value range
Fault indication with output shutoff immediately after pre-charge fault
760
A616
Pre-charge fault selection 0
0
occurs. 3
1 Fault indication with deceleration stop after pre-charge fault occurs.
761 0 to 100% Set the measured amount to end the pre-charge operation.
Pre-charge ending level 9999
A617
762
9999
0 to 3600 s
Without pre-charge ending level
Set the time to end the pre-charge operation.
4
Pre-charge ending time 9999
A618 9999 Without pre-charge ending time
Set the upper limit for the pre-charged amount. A pre-charge fault
763 Pre-charge upper detection
9999
0 to 100% occurs when the measured value exceeds the setting during pre-
charging.
5
A619 level
9999 Without Pre-charge upper detection level
Set the time limit for the pre-charged amount. A pre-charge fault occurs
764
A620
Pre-charge time limit 9999
0 to 3600 s
when the pre-charge time exceeds the setting. 6
9999 Without Pre-charge time limit
765 Second pre-charge fault
0 0, 1 Refer to Pr.760.
A656 selection
766 Second pre-charge ending
9999
0 to 100%,
Refer to Pr.761.
7
A657 level 9999
Set the second pre-charge function.
767 Second pre-charge ending 0 to 3600 s,
9999 Refer to Pr.762. The second pre-charge function is
A658 time 9999
768 Second pre-charge upper 0 to 100%,
valid when the RT signal is ON. 8
9999 Refer to Pr.763.
A659 detection level 9999
769 0 to 3600 s,
Second pre-charge time limit 9999 Refer to Pr.764.
A660 9999
9
Operation selection for the pre-charge function
• To enable the pre-charge function when PID control is enabled, set the pre-charge end conditions at Pr.761 Pre-charge
ending level and at Pr.762 Pre-charge ending time, or set "77" to Pr.178 to Pr.189 (Input terminal function selection). 10
When operation is started, the inverter runs at the frequency set to Pr.127 PID control automatic switchover frequency
to enter the pre-charge state.
• Pre-charge ends and PID control starts after a pre-charge ending condition is satisfied.
• The pre-charge function is also activated at a start after release of a PID output suspension (SLEEP) state or MRS (output
shutoff). The PID output suspension (SLEEP) function is not activated until the started pre-charge operation ends.
• During pre-charge operation, the During pre-charge operation (Y49) signal is output. For the terminal used for Y49 signal
output, set "49 (positive logic)" or "149 (negative logic)" in any of Pr.190 to Pr.196 (output terminal function selection)
to assign the function.
• The pre-charge function valid/invalid settings and pre-charge ending conditions are as follows:
Pre-charge ending condition setting Pre-charge
Pr.127 setting Valid pre-charge ending condition*1
Pr.761 setting Pr.762 setting X77 signal function
9999 — — —
Disabled —
Not assigned
9999
Assigned — — X77
9999
Not assigned — Time —
Other than 9999
Other than Assigned — Time X77
9999 Not assigned Enabled Result — —
9999
Assigned Result — X77
Other than 9999
Not assigned Result Time —
Other than 9999
Assigned Result Time X77
*1 When two or more ends conditions are satisfied, the pre-charge operation ends by the first-satisfied condition.
5. PARAMETERS
5.14 (A) Application parameters
587
NOTE
• During the pre-charge operation, it is regarded as integrated value = estimated value. The motor speed may drop shortly from
the automatic switchover frequency depending on the parameter settings.
• Parameter changes and switchover to the second PID control are applied immediately. If PID control has not started when the
settings were changed, PID control starts with changed settings. (If PID control has already started, these settings do not
apply. If the changed settings already satisfies a condition to start PID control, the PID control starts as soon as these are
changed.)
• The pre-charge also ends when PID control is set to invalid, the start command has been turned OFF, and output has been
shut off.
Time
PID control
Output frequency[Hz]
Pr.127
0Hz Time
STF
Y49
• When the elapsed time reaches the pre-charge ending time (Pr.762 Pre-charge ending time ≠ "9999")
The pre-charge operation ends when the pre-charge time reaches the Pr.762 setting or higher, then the PID control is
performed.
Output frequency[Hz]
Pr.127
Ending time
Pr.762 PID control
0Hz Time
STF
Y49
Output frequency[Hz]
Pr.127
PID control
Time
0Hz
STF
10ms or more
X77
Y49
588 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• When the PID output suspension (SLEEP) function is in use, and the X77 signal is set to valid after this function is released, 1
set the X77 signal to OFF after checking that the during the During pre-charge operation (Y49) signal is OFF.
• When the PID output suspension (SLEEP) function is in use, and PID control is to be performed immediately after this function
is released, leave the X77 signal ON until PID control ends.
• When the pre-charge operation is valid, the pre-charge operation is performed at the output shutoff cancellation (MRS signal, 2
etc.). (The pre-charge operation is also performed in the case of instantaneous power failure when the automatic restart after
instantaneous power failure is valid.)
• When the control method is changed to PID control from a control with higher priority in frequency command (multi-speed
setting, JOG operation, etc.), the motor is accelerated/decelerated until its speed reaches the automatic switchover frequency
3
(Pr.127), and the pre-charge is performed.
4
Operation setting at pre-charge fault
• The protective function can be activated when limit values are exceeded if the time limit is set at Pr.764 Pre-charge time
limit and the measured value limit level is set at Pr.763 Pre-charge upper detection level. 5
• Whether to shut off output immediately after the protective function is activated or after a deceleration stop can be selected
by Pr.760. (Pre-charge protective function is effective regardless of the setting of pre-charge ending conditions.)
• When the time limit is exceeded, the Pre-charge time over (Y51) signal is output. When the measured value limit level is 6
exceeded, the Pre-charge level over (Y53) signal is output. For the Y51 signal, set "51 (positive logic)" or "151 (negative
logic)" to Pr.190 to Pr.196 (Output terminal function selection), and for the Y53 signal, set "53 (positive logic)" or "153
(negative logic)" in Pr.190 to Pr.196 (Output terminal function selection) to assign the functions to terminals. 7
NOTE
• For Pr.764 Pre-charge time limit, set a value greater than Pr.762 Pre-charge ending time.
• For Pr.763 Pre-charge upper detection level, set a value greater than Pr.761 Pre-charge ending level. 8
• Example of protective function by time limit (Pr.760 = "0")
Measured value[PSI]
9
Ending level
Pr.761
10
Time
Output frequency[Hz]
Pr.127 When Pr.760 = "0",
output is immediately shut off.
Pr.764
0Hz Time
STF
Y49
Y51
ALM
E.PCH
5. PARAMETERS
5.14 (A) Application parameters
589
• Example of protective function measured value limit (Pr.760 = "1")
Measured value[PSI]
Pr.763
Time
Output frequency[Hz]
Pr.127
When Pr.760 = "1",
output is shut off after the motor decelerates to a stop.
0Hz
Time
STF
Y49
Y53
ALM
E.PCH
NOTE
• The second PID pre-charge function is valid also when the first pre-charge function is set to invalid and the second pre-charge
function is set.
• When "10" (second function enabled only during constant-speed operation) is set to Pr.155, the second PID function is not
selected even if the RT signal turns ON.
590 5. PARAMETERS
5.14 (A) Application parameters
Pr. Name Initial value Setting range Description
Set the deceleration time during dancer control.
0 to 3600 s
In dancer control, this parameter becomes the deceleration time of the 1
45 Second deceleration
9999 main speed.
F021 time
This setting does not operate as the second deceleration time.
9999 Pr.44 is the deceleration time.
0 No PID action 2
40 PID reverse action Additive method: Fixed
128 41 PID forward action Additive method: Fixed
PID action selection 0 For dancer control
A610 42 PID reverse action Additive method: Ratio 3
43 PID forward action Additive method: Ratio
Others Refer to page 570.
If a narrow proportional band is set (small parameter setting value), the
manipulated amount changes considerably by slight changes in the 4
measured value.
129 0.1 to 1000%
PID proportional band 100% As a result, response improves as the proportional band becomes
A613
narrower, though stability worsens as shown by the occurrence of hunting.
Gain Kp=1/proportional band 5
9999 No proportional control
With deviation step input, this is the time (Ti) used for obtaining the same
manipulated amount as proportional band (P) by only integral (I) action.
130
A614
PID integral time 1s
0.1 to 3600 s
Arrival to the set point becomes quicker the shorter an integral time is set, 6
though hunting is more likely to occur.
9999 No integral control
Set the upper limit.
131 0 to 100%
The FUP signal is output when the feedback value exceeds this setting. 7
PID upper limit 9999 The maximum input (20 mA/5 V/10 V) of the measured value (terminal 4)
A601 is equivalent to 100%.
9999 No function
Set the lower limit. 8
The FDN signal is output when the measured value (terminal 4) falls below
132 0 to 100% the setting range.
PID lower limit 9999 The maximum input (20 mA/5 V/10 V) of the measured value is equivalent
A602
to 100%. 9
9999 No function
133 0 to 100% Set the set point during PID control.
PID action set point 9999
A611 9999 Input of set point by terminal selected by Pr.609
With deviation ramp input, this is the time (Td) used for obtaining the
10
manipulated amount only by proportional action (P).
134 0.01 to 10 s
PID differential time 9999 Response to changes in deviation increase greatly as the differential time
A615
increases.
9999 No differential control
1 Input of set point from terminal 1
2 Input of set point from terminal 2
609 PID set point/deviation 3 Input set point from terminal 4
2
A624 input selection Input of set point, deviation value via CC-Link/CC-Link IE Field Network
4
communication
5 Input of set point by PLC function
1 Input of measured value from terminal 1
2 Input of measured value from terminal 2
610 PID measured value 3 Input of measured value from terminal 4
3
A625 input selection Input of set point, deviation value via CC-Link/CC-Link IE Field Network
4
communication
5 Input measured value by PLC function
1134 PID upper limit
100% 0 to 100% Set the upper limit of PID action.
A605 manipulated value
1135 PID lower limit
100% 0 to 100% Set the lower limit of PID action.
A606 manipulated value
5. PARAMETERS
5.14 (A) Application parameters
591
Block diagram of dancer control
Acceleration/deceleration
of main speed
Ratio
PID deviation
Acceleration/
Limit deceleration
Pr.128 = 42, 43 +
PID control X14 +
Dancer roll +
setting point 1
Kp(1+ +Td S)
- Ti S Pr.128 = 40, 41
Pr.133
Convert to 0 to 100%
Potentiometer
Terminal 4
*1 The main speed can be selected in all operation modes, External (analog voltage input, multi-speed), PU (digital frequency setting) and
Communication (RS-485).
Output frequency
Main speed
Time
STF ON
NOTE
• Normally, set Pr.7 Acceleration time and Pr.8 Deceleration time to 0 s. When the Pr.7 and Pr.8 settings are large, dancer
control response becomes slow during acceleration/deceleration.
• The Pr.127 PID control automatic switchover frequency setting is enabled. The larger setting value between Pr.7 and
Pr.44 is used as the acceleration time during normal operation. For the deceleration time, the larger setting value between
Pr.8 and Pr.45 is used. (For the details of Pr.127, refer to page 570.)
• If an automatic restart after instantaneous power failure is activated during dancer control, E.OC[] or E.OV[] is likely to occur.
In such case, disable the automatic restart after instantaneous power failure function (Pr.57 = "9999").
592 5. PARAMETERS
5.14 (A) Application parameters
Connection diagram
• Sink logic
MCCB
Inverter 1
• Pr.128 = 41 Motor
R/L1 U
• Pr.182 = 14 Power supply S/L2 V IM
T/L3 W
• Pr.193 = 14 2
• Pr.194 = 15
Forward rotation STF
• Pr.133 = Set point
Reverse rotation STR
10
∗2 (FDN)OL Lower limit 4
Main speed command
2
setting potentiometer ∗1
5 SE Output signal common
Feedback value of
dancer roll position 4 ∗4
5
*1 The main speed command differs according to each operation mode (External, PU, communication).
*2
*3
The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection).
6
*4 The AU signal need not be input.
• To enable dancer control, set "40 to 43" in Pr.128 PID action selection. 10
• Dancer control is enabled only when the PID control valid (X14) signal turns ON when "14" is set in one of Pr.178 to Pr.182
(Input terminal function selection) and X14 signal is assigned. When the X14 signal is not assigned, dancer control is
enabled only by the Pr.128 setting.
• Input the main speed command (External, PU, Communication). Dancer control is also supported by the main speed
command in all operation modes.
• Input the set point between the terminals 2 and 5 (the setting can be selected using Pr.133 or Pr.609) and input the
measured value signal (dancer roll position detection signal) between the inverter terminals 4 and 5 (the setting can be
selected using Pr.610).
• The action of Pr.129 PID proportional band, Pr.130 PID integral time, Pr.131 PID upper limit, Pr.132 PID lower limit
and Pr.134 PID differential time is the same as PID control action. In the relationship between the control amount (%)
and frequency in PID control, 0% and 100% are equivalent to the frequencies set to Pr.902 and Pr.903, respectively.
NOTE
• When Pr.128 is set to "0" or the X14 signal is OFF, regular inverter running not dancer control is performed.
• Dancer control is enabled by turning ON/OFF the bits of terminals assigned the X14 signal by RS-485 communication or over
the network.
• When dancer control is selected, set the PID output suspension function (Pr.575 Output interruption detection time =
"9999")
• When Pr.561 PTC thermistor protection level ≠ "9999", terminal 2 cannot be used for the main speed command. Terminal
2 becomes the PTC thermistor input terminal.
5. PARAMETERS
5.14 (A) Application parameters
593
Selection of set point/measured value input method (Pr.609, Pr.610)
• Select the set point input method by Pr.609 PID set point/deviation input selection and the measured value input
method by Pr.610 PID measured value input selection. Switch the power voltage/current specifications of terminals 2
and 4 by Pr.73 Analog input selection or Pr.267 Terminal 4 input selection to match the specification of the input
device.
• When Pr.133 PID action set point ≠ "9999", Pr.133 is the set point. When the set point is set at Pr.133, the setting
frequency of Pr.902 is equivalent to 0% and the setting frequency of Pr.903 is equivalent to 100%.
Pr.609, Pr.610 settings Input method
1 *1
Terminal 1
2 Terminal 2*1
3 Terminal 4*1
4 CC-Link/CC-Link IE Field Network communication
5 PLC function
*1 When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%)
NOTE
• After changing the Pr.73 or Pr.267 settings, check the voltage/current input selection switch. Incorrect setting may cause a
fault, failure or malfunction. (Refer to page 473 for the setting.)
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
• The following shows the relationship between the input values of the analog input terminals, and the set point and
measured value.
*2 Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to page 473.)
594 5. PARAMETERS
5.14 (A) Application parameters
Selection of additive method for PID calculation result
• When ratio is selected as the additive method (Pr.128 = "42, 43"), PID calculation result × (ratio of main speed) is added 1
to the main speed. The ratio is determined by the Pr.125 Terminal 2 frequency setting gain frequency and C2 (Pr.902)
Terminal 2 frequency setting bias frequency settings. In the initial status, 0 to 60 Hz is set for 0 to 100%. Thus, 60 Hz
main speed is regarded as 100%, and the 30 Hz main speed is regarded as 50%. 2
Output frequency Initial value
60Hz
Gain
Pr.125 4
Bias
C2(Pr.902)
0
Frequency setting signal
100%
5
NOTE
• Even if C4 (Pr.903) is set to other than 100%, the frequency setting signal is treated at 100%.
• Even if C3 (Pr.902) is set to other than 0%, the frequency setting signal is treated as 0%. 6
• If C2(Pr.902) is set to other than 0 Hz, the frequency setting signal is 0% at the C2 (Pr.902) frequency setting or below.
Setting the upper and lower limits of the PID manipulated amount 7
(Pr.1134, Pr.1135)
• Set the upper and lower limits of the PID manipulated amount. 8
• The upper limit of the manipulated amount is the frequency obtained by adding the value resulting from frequency
conversion of Pr.1134 to the main speed.
The lower limit of the manipulated amount is the frequency obtained by subtracting the value resulting from frequency 9
conversion of Pr.1135 from the main speed.
Time
Input/output signals
• The following signals can be used by assigning functions to Pr.178 to Pr.189 (Input terminal function selection) and
Pr.190 to Pr.196 (Output terminal function selection).
• Input signal
Pr.178 to
Signal Function Pr.189 Description
setting
When this signal is assigned to the input terminal, PID control is enabled when this signal is
X14 PID control valid 14
ON.
PID forward/
PID control is switched between forward and reverse action without changing parameters by
X64 reverse action 64
turning ON this signal.
switchover
PID P control
X72 72 Integral and differential values can be reset by turning ON this signal.
switchover
5. PARAMETERS
5.14 (A) Application parameters
595
• Output signal
Pr.190 to Pr.196
setting
Signal Function Description
Positive Negative
logic logic
Output when the measured value signal exceeds Pr.131 PID upper limit
FUP PID upper limit 15 115
(Pr.1143 Second PID upper limit).
Output when the measured value signal falls below Pr.132 PID lower limit
FDN Lower limit output 14 114
(Pr.1144 Second PID lower limit).
"Hi" is output when the output display of the parameter unit is forward rotation
PID forward/reverse
RL 16 116 (FWD) and "Low" is output when the display is reverse rotation (REV) and stop
rotation output
(STOP).
During PID control
PID 47 147 Turns ON during PID control.
activated
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
NOTE
• Refer to page 579 for details on other PID control monitors.
596 5. PARAMETERS
5.14 (A) Application parameters
Adjustment procedure for dancer roll position detection signal
• When the input of terminal 4 is voltage input, 0 V and 5 V (10 V) are the lower limit position and upper limit position, 1
respectively (initial value). When it is current input, 4 mA and 20 mA are the lower limit position and upper limit position,
respectively (initial value). When the potentiometer has an output of 0 to 7 V, C7 (Pr.905) must be calibrated at 7 V.
2
20mA 5V(10V) Upper limit
position
3
4mA 0V 4
0% 100% Lower limit Potentiometer, etc.
Feedback value position
2. Input 0 V across terminals 4 and 5, and calibrate C6 (Pr.904). (The % display that is indicated at analog calibration
6
is not related to the % of the feedback value.)
3. Input 7 V across terminals 4 and 5, and calibrate C7 (Pr.905). (The % display that is indicated at analog calibration
is not related to the % of the feedback value.) 7
4. Set Pr.133 to "50%".
NOTE 8
• After changing the Pr.267 setting, check the voltage/current selection switch. Incorrect setting may cause a fault, failure or
malfunction. (Refer to page 473 for the setting.)
• If the Multi-speed operation (RH, RM, RL, or REX) signal, or JOG signal is input during regular PID control, PID control is
interrupted. However, at dancer control, these signals are treated as main speed commands, so PID control is continued. 9
• During dancer control, Pr.44 and Pr.45 (Second acceleration/deceleration time) is the parameter for setting the acceleration/
deceleration time for the main speed command. This function does not work as a second function.
• When the switchover mode is set by setting "6" to Pr.79, dancer control (PID control) is invalid. 10
• The acceleration/deceleration action of the main speed command is the same as that when the frequency is increased or
decrease by analog input. The SU signal sometimes stays ON even if operation is turned ON/OFF by the start signal. The set
frequency monitor is the value "main speed command + PID control" which is constantly changing.
• With the main speed setting frequency setting, acceleration/deceleration is performed for the acceleration/deceleration time
set in Pr.44 and Pr.45, and with the output frequency setting, acceleration/deceleration is performed for the acceleration/
deceleration time set in Pr.7 and Pr.8. For this reason, with the output frequency, when the time set in Pr.7 and Pr.8 is longer
than the time set in Pr.44 and Pr.45, acceleration/deceleration is performed for the acceleration/deceleration time set in Pr.7
and Pr.8.
• The limit of the integral term is the smaller of 100% and the value after conversion of the straight line after interpolation of Pr.1
Maximum frequency by Pr.902 and Pr.903 to the PID manipulated amount.
However, note that the lower limit frequency limits the output frequency, but does not restrict the action of the integral item.
Parameters referred to
Pr.57 Restart coasting timepage 597
Pr.59 Remote function selectionpage 359
Pr.73 Analog input selectionpage 473
Pr.79 Operation mode selectionpage 370
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.561 PTC thermistor protection levelpage 394
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gainpage 482
5. PARAMETERS
5.14 (A) Application parameters
597
• When switching from commercial power supply operation over to inverter running
• When an instantaneous power failure occurs during inverter running
• When the motor is coasting at start
Initial Setting
Pr. Name Description
value range
0 Frequency search only performed at the first start
Reduced voltage start only at the first start
1
(no frequency search)
Automatic restart after 2 Encoder detection frequency search
162
instantaneous power 0 3 Frequency search only performed at the first start (reduced impact restart)
A700
failure selection 10 Frequency search at every start
11 Reduced voltage start at every start (no frequency search)
12 Encoder detection frequency search at every start
13 Frequency search at every start (reduced impact restart)
0 Without rotation direction detection
1 With rotation direction detection
Rotation direction
299 When Pr.78 Reverse rotation prevention selection = "0", with rotation
detection selection at 0
A701 direction detection
restarting 9999
When Pr.78 Reverse rotation prevention selection= "1 or 2", without
rotation direction detection
0 Coasting time differs according to the inverter capacity.*1
57 Set the waiting time for the inverter to perform a restart after restoring power
Restart coasting time 9999 0.1 to 30 s
A702 due to an instantaneous power failure.
9999 No restart
58
Restart cushion time 1s 0 to 60 s Set the voltage cushion time for restart.
A703
163 First cushion time for
0s 0 to 20 s Set the voltage cushion time for restart.
A704 restart
Consider this matched to the size of the load amount (moment of inertia/
164 First cushion voltage for
0% 0 to 100% torque).
A705 restart
165 Stall prevention operation Set the stall prevention level at restart operation on the assumption that the
150% 0 to 400%
A710 level for restart inverter rated current is 100%.
Set the acceleration time to reach Pr.20 Acceleration/deceleration
0 to 3600 s
611 Acceleration time at a reference frequency at restart.
9999
F003 restart Standard acceleration time (for example, Pr.7) is applied as the acceleration
9999
time at restart.
*1 The coasting time when Pr.57 = "0" is as shown below. (When Pr.162 and Pr.570 are set to the initial value.)
FR-A820-00105(1.5K) or lower and FR-A840-00052(1.5K) or lower: 0.5 s
FR-A820-00167(2.2K) to FR-A820-00490(7.5K) and FR-A840-00083(2.2K) to FR-A840-00250(7.5K): 1 s
FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-01800(55K): 3.0 s
FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher: 5.0 s
• To operate the inverter with the automatic restart after instantaneous power failure function enabled, check the following
points.
• Set Pr.57 Restart coasting time = "0".
• When the Selection of automatic restart after instantaneous power failure / flying start (CS) signal is assigned to the input
terminal, restart operation is enabled at turn-ON of the CS signal.
IPF OFF ON
• The inverter output is shut off at the activation of the Instantaneous power failure (E.IPF) or Undervoltage (E.UVT). (Refer
to page 754 for E.IPF or E.UVT.)
• When E.IPF or E.UVT is activated, the Instantaneous power failure/undervoltage (IPF) signal is output.
598 5. PARAMETERS
5.14 (A) Application parameters
• The IPF signal is assigned to terminal IPF in the initial status. By setting "2 (positive logic) or 102 (negative logic)" in any
of Pr.190 to Pr.196 (Output terminal function selection), the IPF signal can be assigned to another terminal.
• When the automatic restart after instantaneous power failure function is selected, motor driving is resumed at the power
1
restoration after an instantaneous power failure or undervoltage. (E.IPF and E.UVT are not activated.)
MCCB MC1
R/L1 U
MC3 3
S/L2 V M
T/L3 W
R1/L11
S1/L21
STF
CS MC
4
SD switchover
sequence
CS
For use for only automatic
restart after instantaneous
RDA
IPF
X10
X11
5
SD
power failure or flying start, CS
turn ON the CS signal in
SE SD
advance.
Only with restart after instantaneous power failure Separated converter type 6
• Restart is enabled at turn-ON of the Selection of automatic restart after instantaneous power failure / flying start (CS)
signal.
• The inverter operation is disabled at turn-OFF of the CS signal while Pr.57 Restart coasting time ≠ "9999" (with restart). 7
• Separated converter types detect the instantaneous power failure on the converter unit side. Perform wiring so that the IPF
signal transmitted from the converter unit is input to the terminal to which the X11 signal is assigned.
On the converter unit side, enable the restart operation. (For setting the converter unit, refer to the Instruction Manual of 8
the converter unit.)
• For the terminal used for the X10 or X11 signal, set "10" (X10) or "11" (X11) in Pr.178 to Pr.189 and assign the function.
(For separated converter types, the X10 signal is assigned to the terminal MRS in the initial setting.) 9
• For the X10 signal of separated converter types, NC contact input specification is selected in the initial setting. Set Pr.599
= "0" to change the input specification to NO contact.
NOTE
10
• The CS signal is assigned to terminal CS in the initial setting. By setting "6" to any of Pr.178 to Pr.189 (Input terminal function
selection), the CS signal can be assigned to other terminals. Changing the terminal assignment may affect other functions.
Set parameters after confirming the function of each terminal.
• If the CS signal is not assigned to any input terminal, solely setting Pr.57 enables the restart operation at all times.
5. PARAMETERS
5.14 (A) Application parameters
599
Setting for the automatic restart after instantaneous power failure
operation (Pr.162)
• The Pr.162 settings and the instantaneous power failure automatic restart operation under each operation mode are as
shown below.
V/F control,
Pr.162 Restart Real sensorless PM sensorless
Advanced magnetic flux vector control Vector control
setting operation vector control vector control
Without encoder With encoder
0 (initial value) At first start Frequency search Frequency search
1 At first start Reduced voltage start Reduced voltage start
Encoder detection
2 At first start Frequency search
frequency search
Frequency search Frequency search
3 At first start (reduced impact (reduced impact Frequency Frequency search
Encoder
restart) restart) search for PM motor
detection
10 At every start Frequency search Frequency search (reduced impact (Refer to page
frequency search
11 At every start Reduced voltage start Reduced voltage start restart) 604.)
Encoder detection
12 At every start Frequency search
frequency search
Frequency search Frequency search
13 At every start (reduced impact (reduced impact
restart) restart)
Restart operation with frequency search (Pr.162 ="0, 3, 10, or 13", Pr.299)
• When Pr.162 = "0 (initial value), 3, 10, or 13", the motor speed is detected at a power restoration so that the motor can re-
start smoothly.
• The encoder also detects the rotation direction so that the inverter can re-start smoothly even during the reverse rotation.
• Whether or not to detect the rotation direction can be selected by Pr.299 Rotation direction detection selection at
restarting. If the motor capacity is different from the inverter capacity, set Pr.299 = "0" (no rotation direction detection).
• When the rotation direction is detected, the following operation is performed according to Pr.78 Reverse rotation
prevention selection setting.
Pr.78 setting
Pr.299 setting
0 1 2
9999 ○ × ×
0 (initial value) × × ×
1 ○ ○ ○
○: With rotation direction detection ×: Without rotation direction detection
• By setting "3 or 13" in Pr.162, the restart can be made smoother with even less impact than when "0 or 10" is set in Pr.162.
When the inverter is restarted with "3, 13" set in Pr.162, offline auto tuning is required. (For details on offline auto tuning
of Advanced magnetic flux vector control and Real sensorless vector control, refer to page 509, and for details on offline
auto tuning of V/F control, refer to page 606.)
V/F control, Advanced magnetic flux vector control Real sensorless vector control
Instantaneous (power failure) time Instantaneous (power failure) time
Power supply
Power supply
(R/L1, S/L2,
(R/L1, S/L2,
T/L3)
T/L3)
Motor speed N Motor speed N
(r/min)
(r/min)
Inverter output * Inverter output
frequency f(Hz) frequency f(Hz)
output voltage *
Inverter output
voltage E(V) E(V)
Speed
Restart cushion Coasting + detection Acceleration time
Speed time (Pr.57) time
Coasting time (Pr.58 setting) at a restart
+ detection (Pr.611 setting)
time (Pr.57) time
* The output shut off timing differs
* The output shut off timing differs Acceleration time according to the load condition.
according to the load condition. at a restart
(Pr.611 setting)
600 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• The rotation speed detection time (frequency search) changes according to the rotation speed of the motor. (maximum 1 s) 1
• When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent protective function (E.OC[]) is
sometimes activated and prevents the inverter from restarting.
• If two or more motors are connected to one inverter, this function operates abnormally. (The inverter does not restart
successfully.) 2
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• If reverse operation is detected when "1" (reverse rotation disabled) is set to Pr.78, operation decelerates by reverse rotation
and then changes to forward rotation when the start command is forward rotation. The inverter does not restart when the start
3
command is reverse rotation.
• When "3 or 13" is set to Pr.162, limit the wiring length to within 100 m.
4
Restart operation without frequency search (Pr.162 = "1 or 11")
• When Pr.162 = "1 or 11", reduced voltage start is used for the restart operation. In this method, the voltage is raised 5
gradually while keeping the output frequency level at the level before an instantaneous power failure, regardless of the
motor's coasting speed.
V/F control, Advanced magnetic flux vector control 6
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3) 7
Motor speed N
(r/min)
Inverter output *
frequency f(Hz) 8
Inverter output
voltage E(V)
Coasting time
9
Pr.57 setting Restart cushion time
(Pr.58 setting)
* The output shut off timing differs according to the load condition.
10
NOTE
• This restart method uses the output frequency that was active before the instantaneous power failure stored in memory. If the
instantaneous power failure time is 0.2 s or more, the output frequency can no longer be stored and held in memory, so the
restart is performed from Pr.13 Starting frequency (initial value: 0.5 Hz).
• During Real sensorless vector control, Pr.162 is set to "3 or 13" (reduced impact restart).
5. PARAMETERS
5.14 (A) Application parameters
601
• By encoder detection frequency search, the Pr.299 Rotation direction detection selection at restarting setting are
invalid.
Instantaneous (power failure) time
Power supply
(R/L1, S/L2, T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz) ∗
Output voltage E(V)
NOTE
• When "2 or 12" are set to Pr.162 when encoder feedback control is invalid, the automatic restart is with a frequency search
(Pr.162 = "0 or 10").
• In Vector control, encoder detection frequency search is used regardless of the Pr.162 setting. The Pr.58 and Pr.299 settings
are invalid at this time.
• For the encoder feedback control, refer to page 700.
NOTE
• When output is shut off using safety stop function (terminals S1 and S2), the inverter restarts in the same way as when output
is shut off by MRS (X10) signal.
602 5. PARAMETERS
5.14 (A) Application parameters
• Inverter operation is sometimes hindered by the size of the moment of inertia (J) of the load or running frequency. Adjust
this coasting time within the range 0.1 s to 30 s to match the load specification.
• Set the waiting time when the sine wave filter is used (Pr.72 PWM frequency selection = "25") to 3 seconds or more.
1
Restart cushion time (Pr.58)
• The cushion time is the time takes to raise the voltage to the level required for the specified speed after the motor speed 2
detection (output frequency before the instantaneous power failure when Pr.162= "1 or 11").
• Normally, the motor runs at the initial value as it is. However, adjust to suit the moment of inertia (J) of the load or the size
of the torque. 3
NOTE
• Pr.58 is invalid under Real sensorless vector control or Vector control.
4
Adjustment of restart operation (Pr.163 to Pr.165, Pr.611)
• The voltage cushion time at a restart can be adjusted by Pr.163 and Pr.164 as shown in the figure on the left. 5
Voltage
100%
6
Pr.164
7
CAUTION
• Provide a mechanical interlock for MC1 and MC2. The inverter will be damaged if power supply is input to the
inverter output section.
• When the automatic restart after instantaneous power failure function is selected, the motor suddenly starts
(after reset time passes) when an instantaneous power failure occurs. Stay away from the motor and machinery.
Apply the supplied CAUTION stickers to easily visible places when automatic restart after instantaneous power
failure has been selected.
Parameters referred to
Pr.7 Acceleration time, Pr.21 Acceleration/deceleration time incrementspage 349
Pr.13 Starting frequencypage 363, page 364
Pr.65, Pr.67 to Pr.69 Retry functionpage 405
Pr.78 Reverse rotation prevention selectionpage 386
Pr.178 to Pr.189 (Input terminal function selection)page 496
5. PARAMETERS
5.14 (A) Application parameters
603
5.14.15 Automatic restart after instantaneous power
failure/flying start with an IPM motor
PM
When using the IPM motor MM-CF, the inverter operation can be restarted without stopping the motor operation.
When the automatic restart after instantaneous power failure function is selected, the motor driving is resumed in the following
situations:
• When power comes back ON during inverter driving after an instantaneous power failure
• When the motor is coasting at start
IPF OFF ON
• The inverter output is shut off at the activation of the Instantaneous power failure (E.IPF) or Undervoltage (E.UVT). (Refer
to page 745 for E.IPF or E.UVT.)
• When E.IPF or E.UVT is activated, the Instantaneous power failure/undervoltage (IPF) signal is output.
• The IPF signal is assigned to terminal IPF in the initial status. By setting "2 (positive logic) or 102 (negative logic)" in any
of Pr.190 to Pr.196 (Output terminal function selection), the IPF signal can be assigned to another terminal.
• When the automatic restart after instantaneous power failure function is selected, motor driving is resumed at the power
restoration after an instantaneous power failure or undervoltage. (E.IPF and E.UVT are not activated.)
NOTE
• The CS signal is assigned to terminal CS in the initial setting. By setting "6" to any of Pr.178 to Pr.189 (Input terminal function
selection), the CS signal can be assigned to other terminals. Changing the terminal assignment may affect other functions.
Set parameters after confirming the function of each terminal.
• If the CS signal is not assigned to any input terminal, solely setting Pr.57 enables the restart operation at all times.
• If the restart operation is selected, instantaneous power failure (E.IPF) is disabled while the fault output signal is output at an
instantaneous power failure.
• The SU and FU signals are not output during the restart. These signals are output after the restart cushion time passes.
• Restart operation is also performed after the inverter reset is released or after the retry by the retry function occurs.
• The automatic restart after instantaneous power failure function is invalid when the load torque high-speed frequency control
(Pr.270 = "2, 3, 13") is set.
604 5. PARAMETERS
5.14 (A) Application parameters
Selection of restart operation (Pr.162)
• At a power restoration, the encoder detects the motor speed by a frequency search so that the inverter can re-start 1
smoothly.
• The encoder also detects the rotation direction so that the inverter can re-start smoothly even during the reverse rotation.
• When "10 to 13)" is set in Pr.162, a restart operation is performed at each start and automatic restart after instantaneous 2
power failure. When "0 to 3" is set in Pr.162, a restart operation is performed at the first start after a power-ON, and from
the second power-ON onwards, a start from the starting frequency is performed.
Instantaneous (power failure) time 3
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
4
Inverter output *
frequency f (Hz)
Inverter output
voltage E (V)
5
Speed
Coasting + detection
time (Pr.57) time
Acceleration time
at a restart
6
* The output shut off timing differs (Pr.611 setting)
according to the load condition
NOTE 7
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• Restart operation with reduced voltage is not available for PM sensorless vector control. 8
Restart coasting time (Pr.57)
• Coasting time is the time from the motor speed detection to the restart operation start. 9
• To enable restart operation, set "0" (no coasting time) in Pr.57 Restart coasting time. Generally, this setting does not
interfere with inverter operation.
• Inverter operation is sometimes hindered by the size of the moment of inertia (J) of the load or running frequency. Adjust 10
this coasting time within the range 0.1 s to 30 s to match the load specification.
NOTE
• Changing the Pr.21 Acceleration/deceleration time increments setting does not affect the Pr.611 setting increment.
• An IPM motor is a motor with interior permanent magnets. Regression voltage is generated when the motor coasts at an
instantaneous power failure or at a flying start. The inverter's DC bus voltage rises if the motor coasts fast or makes a flying
start in this condition.
When using the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999"), it is recommended to also use
the regenerative avoidance function (Pr.882 Regeneration avoidance operation selection = "1") to make startups stable. If
the overvoltage protective function (E.OV[]) still occurs with the regeneration avoidance function, also use the retry function
(Pr.67).
• During PM sensorless vector control, the automatic restart after instantaneous power failure function operates only when an
IPM MM-CF motor is connected.
When a built-in brake or a regeneration unit is used, the frequency search may not be available at 2200 r/min or higher. The
restart operation cannot be performed until the motor speed drops to a frequency where the frequency search is available.
5. PARAMETERS
5.14 (A) Application parameters
605
CAUTION
• An IPM motor is a motor with interior permanent magnets. High voltage is generated at motor terminals while the motor
is running.
Do not touch motor terminals and other parts until the motor stops to prevent an electric shock.
• When the automatic restart after instantaneous power failure function is selected, the motor suddenly starts (after reset
time passes) when an instantaneous power failure occurs.
Stay away from the motor and machinery.
Apply the supplied CAUTION stickers to easily visible places when automatic restart after instantaneous power failure
has been selected.
Parameters referred to
Pr.13 Starting frequencypage 363, page 364
Pr.65, Pr.67 to Pr.69 Retry functionpage 405
Pr.78 Reverse rotation prevention selectionpage 386
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.882 Regeneration avoidance operation selectionpage 696
Under V/F control or when driving the IPM motor MM-CF, the accuracy of the "frequency search", which is used to detect the
motor speed for the automatic restart after instantaneous power failure and flying start, can be improved.
Initial
Pr. Name Setting range Description
value
0 Frequency search only performed at the first start
1 Reduced voltage start only at the first start (no frequency search)
2 Encoder detection frequency search
Automatic restart after Frequency search only performed at the first start (reduced impact
162 3
instantaneous power 0 restart)
A700
failure selection 10 Frequency search at every start
11 Reduced voltage start at every start (no frequency search)
12 Encoder detection frequency search at every start
13 Frequency search at every start (reduced impact restart)
The offline auto tuning automatically sets the gain required for the
0 to 32767
298 frequency search.
Frequency search gain 9999
A711 The constant value of Mitsubishi Electric motor (SF-PR, SF-JR, SF-
9999
HR, SF-JRCA, SF-HRCA, or MM-CF) is used.
The offline auto tuning automatically sets the gain required for the
0 to 32767
560 Second frequency frequency search of the second motor.
9999
A712 search gain The constant value of Mitsubishi Electric motor (SF-PR, SF-JR, SF-
9999
HR, SF-JRCA, SF-HRCA, or MM-CF) is used for the second motor.
0 No offline auto tuning
Offline auto tuning is performed under Advanced magnetic flux vector
96 Auto tuning setting/ 1, 101 control, Real sensorless vector control, or Vector control. (Refer to
0
C110 status page 509.)
Offline auto tuning is performed without rotating the motor (for IPM
11
motor MM-CF).
0 to 50 Ω, 9999*1 Tuning data
90 (The value measured by offline auto tuning is automatically set.)
Motor constant (R1) 9999
C120 0 to 400 mΩ, 9999*2 9999: The constant value of Mitsubishi Electric motor (SF-PR, SF-JR,
SF-HR, SF-JRCA, SF-HRCA and so on) is used.
0 No auto tuning for the second motor.
Offline auto tuning is performed for the second motor. (Refer to page
1, 101
463 Second motor auto 509.)
0
C210 tuning setting/status Offline auto tuning is performed without rotating the second motor
11 (under V/F control or PM sensorless vector control (IPM motor MM-
CF)).
458 Second motor 0 to 50 Ω, 9999*1 Tuning data of the second motor
9999
C220 constant (R1) 0 to 400 mΩ, 9999*2 (The settings are the same as those in Pr.90.)
606 5. PARAMETERS
5.14 (A) Application parameters
Offline auto tuning for a frequency search (reduced impact restart)
• When the frequency search (reduced impact restart) is selected by setting Pr.162 Automatic restart after instantaneous 1
power failure selection = "3 or 13", perform offline auto tuning.
2. Set the rated motor current (initial value is inverted rated current) in Pr.9 Electronic thermal O/L relay. (Refer to
8
page 394.)
Performing tuning
• Before performing tuning, check the monitor display of the operation panel or parameter unit if the inverter is in the state ready
for tuning. The motor starts by turning ON the start command while tuning is unavailable
5. PARAMETERS
5.14 (A) Application parameters
607
NOTE
• It takes about 10 s for tuning to complete. (The time depends on the inverter capacity and motor type.)
• Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of the MRS signal.
• To force tuning to end, use the MRS or RES signal or on the operation panel.
(Turning OFF the start signal (STF signal or STR signal) also ends tuning.)
• During offline auto tuning, only the following I/O signals are valid (initial value).
Input terminals <valid signals>: STP (STOP), OH, MRS, RT, RES, STF, STR, S1, and S2
Output terminals: RUN, OL, IPF, FM/CA, AM, A1B1C1, and So (SO)
• When the rotation speed and the output frequency are selected for terminals FM/CA and AM, the progress status of offline
auto tuning is output in 15 steps from FM/CA and AM.
• Do not perform ON/OFF switching of the Second function selection (RT) signal during offline auto tuning. Auto tuning will not
be performed properly.
• Since the RUN signal turns ON when tuning is started, pay close attention especially when a sequence which releases a
mechanical brake by the RUN signal has been designed.
• When executing offline auto tuning, input the operation command after switching ON the main circuit power (R/L1, S/L2, T/L3)
of the inverter.
• While Pr.79 Operation mode selection = "7", turn the PU operation external interlock (X12) signal ON to tune in the PU
operation mode.
AutoTune 12:34
TUNE
Setting 11
--- STOP PU
PREV NEXT
AutoTune 12:34
TUNE
Tuning in progress 12
STF FWD PU
PREV NEXT
AutoTune 12:34
TUNE
• When offline auto tuning ends, press on the operation panel during PU operation. For External operation, turn OFF
the start signal (STF signal or STR signal). This operation resets the offline auto tuning, and the PU's monitor display
returns to the normal indication. (Without this operation, next operation cannot be started.)
• At tuning completion, the tuning results are set in the following parameters:
Parameter Name
90 Motor constant (R1)
298 Frequency search gain
96 Auto tuning setting/status
NOTE
• The motor constants measured once during offline auto tuning are stored as parameters and their data are held until offline
auto tuning is performed again. However, the tuning data is cleared when performing All parameter clear.
• If offline auto tuning has ended in error, motor constants are not set.
608 5. PARAMETERS
5.14 (A) Application parameters
Perform an inverter reset and perform tuning again.
8
Error display
Forced end
Error cause Countermeasures
Set "11" in Pr.96 and retry.
1
9 Inverter protective function operation Make the setting again.
Set the acceleration/deceleration time longer.
91
The current limit (stall prevention) function is
activated.
Set Pr.156 Voltage reduction selection during stall prevention 2
operation = "10, 1".
The converter output voltage fell to 75% of the rated
92 Check for the power supply voltage fluctuation.
voltage.
93
Calculation error
Check the motor wiring and make the setting again.
3
The motor is not connected.
Rotation tuning frequency setting error
(The frequency command for the tuning was given Check the Pr.1 Maximum frequency and Pr.31 to Pr.36
94
to exceed the maximum frequency setting, or to be Frequency jump settings. 4
in the frequency jump range.)
• When tuning is ended forcibly by pressing or turning OFF the start signal (STF or STR) during tuning, offline auto
tuning does not end properly. (The motor constants have not been set.)
5
Perform an inverter reset and restart tuning.
• If the rated power supply of the motor is 200/220 V (400/440 V) 60 Hz, set the rated motor current multiplied by 1.1 in
Pr.9Electronic thermal O/L relay after tuning is complete.
6
• For a motor with a PTC thermistor, thermal protector or other thermal detection, set "0" (motor overheat protection by
inverter invalid) in Pr.9 to protect the motor from overheating.
7
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter starts
normal operation. Therefore, when the STF (STR) signal is ON, the motor starts forward (reverse) rotation.
8
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
9
Tuning the second motor (Pr.463)
• When one inverter switches the operation between two different motors, set the second motor in Pr.450 Second applied 10
motor, set Pr.463 Second motor auto tuning setting/status = "11", and perform tuning of the second motor.
• Turning ON the RT signal enables the parameter settings for the second motor as shown below.
RT signal-ON RT signal-OFF
Function
(second monitor) (first motor)
Motor constant (R1) Pr.458 Pr.90
Frequency search gain Pr.560 Pr.298
Auto tuning setting/status Pr.463 Pr.96
NOTE
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
CAUTION
• Note that the motor may start running suddenly.
• For the offline auto tuning in vertical lift applications, etc., caution is required to avoid falling due to insufficient torque.
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 394
Pr.65, Pr.67 to Pr.69 Retry functionpage 405
Pr.71 Applied motor, Pr.450 Second applied motorpage 505
Pr.79 Operation mode selectionpage 370
Pr.156 Stall prevention operation selectionpage 409
Pr.178 to Pr.189 (Input terminal function selection)page 496
5. PARAMETERS
5.14 (A) Application parameters
609
5.14.17 Power failure time deceleration-to-stop function
At instantaneous power failure or undervoltage, the motor can be decelerated to a stop or to the set frequency for the re-
acceleration.
• For the standard model, remove the jumpers between terminals R/L1 and R1/L11 and terminals S/L2 and S1/L21, and
connect terminals R1/L11 and P/+ and terminals S1/L21 and N/-.
• If an undervoltage, power failure or input phase loss occurs when Pr.261 Power failure stop selection ≠ "0", the motor
decelerates to a stop.
610 5. PARAMETERS
5.14 (A) Application parameters
• The power failure time deceleration stop function operates as follows at an input phase loss.
Pr.261
0
Pr.872 Operation when an input phase loss occurs
Operation continues
1
0
1 Input phase loss (E.ILT)
0 Operation continues
1, 2
1 Deceleration stop 2
21, 22 — Deceleration stop
• For the separated converter type, remove the jumpers between terminals R/L1 and R1/L11 and terminals S/L2 and S1/
L21 of the converter unit, and connect terminals R1/L11 and P/+ and terminals S1/L21 and N/-. Do not remove the jumpers
3
of terminal R1/L11 and terminal S1/L21 of the inverter. (In the initial status of the separated converter type, terminals P/+
and R1/L11 and terminals N/- and S1/L21 are connected.)
• For the separated converter type, connect the terminal to which PWF signal of the converter unit is assigned and the 4
terminal to which X48 signal of the inverter is assigned. Also, set Pr.261of the converter unit in accordance with the inverter
setting. (Refer to the Instruction Manual of the converter unit.)
5
Outline of operation of deceleration stop at a power failure
• If an undervoltage or power failure occurs, the output frequency is turned OFF only for the frequency set to Pr.262
Subtracted frequency at deceleration start. 6
• The motor decelerates for the time set to Pr.264 Power-failure deceleration time 1. (The deceleration time setting is the
time it takes for the motor to stop from Pr.20 Acceleration/deceleration reference frequency.)
• Change the deceleration time (slope) to stop using Pr.265 Power-failure deceleration time 2 when the frequency is too 7
low to obtain the regenerative energy or in other instances.
Power supply
Output
Pr.264
Power-failure
8
Subtracted
frequency frequency at deceleration time 1
Power-failure deceleration start Pr.265
deceleration Pr.262
9
Power-failure
time switchover deceleration
frequency time 2
Pr.266 Time
5. PARAMETERS
5.14 (A) Application parameters
611
Power failure stop function (Pr.261 = "1, 11, or 21")
• Even if power is restored during deceleration triggered by a power failure, deceleration stop is continued after which the
inverter stays stopped. To restart operation, turn the start signal OFF then ON again.
Pr.261 = "1"
Power
supply
During deceleration at
Output frequency
Time
STF
Y46
NOTE
• If the automatic restart after instantaneous power failure is selected (Pr.57 Restart coasting time ≠ "9999") while the power
failure time deceleration stop function is set enabled (Pr.261 = "1, 11, or 21"), the power failure time deceleration stop function
is disabled.
• When the power failure time deceleration stop function is enabled (Pr.261 = "1, 11 or 21"), the inverter does not start even if
the power is turned ON or inverter reset is performed with the start signal (STF/STR) ON. Turn OFF the start signal once and
then ON again to make a start.
Power supply ON
Not started as inverter Output
is stopped due to power frequency
failure
Time
STF OFF ON
Y46 ON
612 5. PARAMETERS
5.14 (A) Application parameters
NOTE
• The undervoltage avoidance function is invalid under torque control by Real sensorless vector control. When Pr.261="11 (12)", 1
the operation is performed in the same manner as Pr.261="1 (2)".
Power
Pr.261 = 21
5
supply
During deceleration at
occurrence of power failure
Output
frequency
Deceleration time : Automatic adjustment
Time
7
STF
5. PARAMETERS
5.14 (A) Application parameters
613
NOTE
• When "2" is set to Pr.30 Regenerative function selection (when the FR-HC2 or FR-CV is used), the deceleration stop
function is invalid at a power failure.
• If the "output frequency - Pr.262" at undervoltage or at power failure is a negative value, it is regarded as 0 Hz. (DC injection
brake operation is performed without deceleration.)
• The power failure time deceleration stop function is disabled during a stop or when the breaker is tripped.
• The Y46 signal turns ON if an undervoltage occurs even if a deceleration at a power failure has not occurred. For this reason,
the Y46 signal is sometimes output instantaneously when the power supply is turned OFF, but this is not a fault.
• When the power failure time deceleration stop function is selected, undervoltage protection (E.UVT), instantaneous power
failure protection (E.IPF) and input phase loss protection (E.ILF) are invalid.
• When the load is high during PM sensorless vector control, an undervoltage sometimes causes the inverter to coast to a stop.
• To use the power failure time deceleration-to-stop function for the separated converter type, use a converter unit manufactured
in August 2014 or later.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
CAUTION
• Even if the power failure time deceleration stop function is set, some loads might cause the inverter to trip and the motor
to coast.
The motor coasts if sufficient regenerative power is not obtained from the motor.
Parameters referred to
Pr.12 DC injection brake operation voltagepage 681
Pr.20 Acceleration/deceleration reference frequency, Pr.21 Acceleration/deceleration time incrementspage 349
Pr.30 Regenerative function selectionpage 689
Pr.57 Restart coasting timepage 597, page 604
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.872 Input phase loss protection selectionpage 404
614 5. PARAMETERS
5.14 (A) Application parameters
Initial Setting
Pr. Name Description
value range 1
0 PLC function disabled
The SQ signal is enabled by input from a
414 PLC function operation 1 command source (external input terminal/
A800 selection
0
PLC function enabled communication). 2
The SQ signal is enabled by input from an
2
external input terminal.
The inverter start command is enabled regardless of the operating status of
415 Inverter operation lock
0
0
the sequence program. 3
A801 mode setting The inverter start command is enabled only while the sequence program is
1
running.
Unit scale factor
0: No function When the pulse train is input from terminal 4
1: ×1 JOG, the number of sampling pulses can be
416 Pre-scale function
0 0 to 5 2: ×0.1 converted.
A802 selection
3: ×0.01 The result of conversion is stored to SD1236.
4: ×0.001 Number of sampled pulses = Input pulse value 5
5: ×0.0001 per count cycle × Pre-scale setting value
417 (Pr.417) × Unit scale factor (Pr.416)
Pre-scale setting value 1 0 to 32767 Pre-scale setting value
A803
0: Clears the flash memory fault display (no operation after 6
writing while the flash memory is in normal operation).
9696: Clears the flash memory (no operation after writing Write
while the flash memory is at a fault).
498 PLC function flash 0, 9696 Other than 0 and 9696: Outside the setting range 7
0
A804 memory clear (0 to 9999) 0: Normal display
1: The flash memory is not cleared because the PLC
function is enabled.
9696: During flash memory clearing operation or flash
Read
8
memory fault
Desired values can be set.
1150 to
1199 User parameters 1 to
0 0 to 65535
Because devices D206 to D255 used by the PLC function can be mutually
accessed, the values set to Pr.1150 to Pr.1199 can be used by the
9
A810 to User parameters 50
sequence program. The result of performing calculation by a sequence
A859
program can also be monitored by Pr.1150 to Pr.1199.
NOTE
• For the details of the PLC function, refer to the PLC Function Programming Manual and the Instruction Manual of FR
Configurator2.
5. PARAMETERS
5.14 (A) Application parameters
615
Monitor mode Parameter setting mode Function mode Faults history mode
• The following data can be copied by copying the project data via USB memory device.
Copy from inverter to USB Copy from USB memory
Extension File type
memory device device to inverter
.QPA Parameter file Supported Supported
.QPG Program file Supported Supported
.C32 Function block source information Supported Supported
.QCD Global text comment information Supported Supported
.DAT Project management information Supported Not available
.TXT Copy information Supported Not available
NOTE
• If the project data of the PLC function is locked with a password using FR Configurator 2, copying to the USB memory device
and verification are disabled. Also if set to write-disabled, writing to the inverter is disabled. (For the details of the PLC function,
refer to the PLC Function Programming Manual and the Instruction Manual of FR Configurator2.)
Parameters referred to
Pr.338 Communication operation command sourcepage 380
616 5. PARAMETERS
5.14 (A) Application parameters
Setting
Pr. Name Initial value Description
range 1
0 Without trace operation
1 Sampling start
1020
Trace operation selection 0 2 Forced trigger
A900
3 Sampling stop 2
4 Transfer of data to USB memory device
0 Memory mode
1021
A901
Trace mode selection 0 1 Memory mode (automatic transfer) 3
2 Recorder mode
Set the sampling cycle.
0: 0.125 ms, 1: 0.252 ms, 2: 1 ms, 3: 2 ms,
1022
A902
Sampling cycle 2 0 to 9 4: 5 ms, 5: 10 ms, 6: 50 ms, 7: 100 ms, 8: 500 ms, 9: 1 s 4
(For the setting values "0" and "1", the cycle varies according to the
control mode.)
1023 Number of analog
4 1 to 8 Select the number of analog channels for sampling.
A903 channels 5
0 Manual sampling start
1024
Sampling auto start 0 Sampling starts automatically when the power supply is turned ON
A904 1
or at a reset
0 Fault trigger 6
1 Analog trigger
1025
Trigger mode selection 0 2 Digital trigger
A905
3
4
Analog or digital trigger (OR logic)
Both analog and digital triggers (AND logic)
7
1026 Number of sampling Set the percentage of the pre-trigger sampling time with respect to
90% 0 to 100%
A906 before trigger the overall sampling time.
1027 Analog source selection
201 8
A910 (1ch)
1028 Analog source selection
202 1 to 3, 5 to
A911 (2ch)
14, 17 to 20,
1029 Analog source selection
203 22 to 24, 32 9
A912 (3ch) to 36, 39 to
1030 Analog source selection 42, 46, 52 to
204
A913 (4ch) 54, 61, 62,
1031 Analog source selection
205
64, 67, 71 to
Select the analog data (monitor item) for sampling on each channel.
10
A914 (5ch) 75, 87 to 98,
1032 Analog source selection 201 to 213,
206 222 to 227,
A915 (6ch)
230 to 232,
1033 Analog source selection
207 235 to 238
A916 (7ch)
1034 Analog source selection
208
A917 (8ch)
1035
Analog trigger channel 1 1 to 8 Select the analog channel to be the trigger.
A918
Sampling starts when the value of the analog monitor exceeds the
0
1036 Analog trigger operation value set at the trigger level (Pr.1037)
0
A919 selection Sampling starts when the value of the analog monitor falls below the
1
value set at the trigger level (Pr.1037)
Set the level at which the analog trigger turns ON.
1037
Analog trigger level 1000 600 to 1400 The trigger level is the value obtained by subtracting 1000 from the
A920
set value.
5. PARAMETERS
5.14 (A) Application parameters
617
Setting
Pr. Name Initial value Description
range
1038 Digital source selection
1
A930 (1ch)
1039 Digital source selection
2
A931 (2ch)
1040 Digital source selection
3
A932 (3ch)
1041 Digital source selection
4
A933 (4ch)
1 to 255 Select the digital data (I/O signal) for sampling on each channel.
1042 Digital source selection
5
A934 (5ch)
1043 Digital source selection
6
A935 (6ch)
1044 Digital source selection
7
A936 (7ch)
1045 Digital source selection
8
A937 (8ch)
1046
Digital trigger channel 1 1 to 8 Select the digital channel to be the trigger.
A938
1047 Digital trigger operation 0 Trace starts when the signal turns ON
0
A939 selection 1 Trace starts when the signal turns OFF
Operation outline
• This function samples the status (analog monitor and digital monitor) of the inverter, traces the sampling data when a
trigger (trace start condition) is generated, and saves the resulting trace data.
• When the trace function is set enabled, samplings are collected and the inverter goes into the pre-trigger status.
• In the pre-trigger status, samples are collected, and the trigger standby status is entered when sufficient samples for the
number of pre-trigger samples have been collected.
• When the trigger is generated in the trigger standby status, the trace is started and the trace data is saved.
Sampling data
0% 90%
Sampling data
0% 90% 100%
Sampling data
0% 90% 100%
618 5. PARAMETERS
5.14 (A) Application parameters
• There are two trace data save methods, memory mode and recorder mode.
Pr.1021
setting
Mode Description 1
0 Memory mode In this mode, trace data is saved sequentially to internal RAM on the inverter.
If automatic transfer is set, the trace data in internal RAM is transferred to USB memory device
1
Memory mode
when the trigger is being generated.
Data can be transferred to USB memory device as long as data is held in internal RAM.
2
(automatic transfer) Trace data in internal RAM is cleared when the power supply is turned OFF or when the inverter
is reset.
2 Recorder mode
In this mode, trace data is saved directly to USB memory device.
Sampling data is fixed at 8 analog channels and 8 digital channels.
3
The sampling cycle in this mode is longer than in the memory mode. (1 ms or longer)
NOTE
• When the trace function is used in the recorder mode, use USB memory device having at least 1 GB of free space.
4
• Data transferred to USB is saved in the "TRC" folder under the "FR_INV" folder.
• Up to 99 sets of trace data can be saved in the USB memory device. When data transfer to USB memory reaches 99 sets of
trace data, data is successively overwritten starting with the older data. 5
• By using FR Configurator2, the trace data of the internal RAM can be directly transmitted to the personal computer via the
USB cable. For details, refer to the Instruction Manual of FR Configurator2.
6
Setting of sampling cycle (interval) and number of sampling channels
(Pr.1022, Pr.1023)
• Set the sampling cycle (interval).
7
The shortest cycle in the recorder mode is 1 ms. When the recorder mode is set, sampling is performed at a sampling cycle
of 1 ms even if "0 or 1" is set to Pr.1022 Sampling cycle.
• When the memory mode is set, the number of analog channels to sample can be set in the Pr.1023 Number of analog
8
channels. Start setting from the smaller channel number. Up to 8 channels can be set. The sampling time becomes shorter
the more channels are set.
The number of digital channels is always 8 when the recorder mode is used or when digital channels are used. 9
• The sampling time differs according to the sampling cycle and the number of sampling channels.
Memory mode sampling time (per channel)
Number of Channels
Minimum (Pr.1022 = "0") Maximum (Pr.1022 = "9")
10
1 213 ms 1704 s
2 160 ms 1280 s
3 128 ms 1024 s
4 106.5 ms 852 s
5 91 ms 728 s
6 80 ms 640 s
7 71 ms 568 s
8 64 ms 512 s
5. PARAMETERS
5.14 (A) Application parameters
619
Analog source (monitor item) Setting
Monitor item*1
Minus (-) Trigger level
value display*2 criterion*3
selection Cumulative pulse overflow *4
72 ○
• Select the analog sources (monitor items) to be set to times
Pr.1027 to Pr.1034 from the following table. Cumulative pulse (control *4
73 ○
terminal option)
Setting Minus (-) Trigger level Cumulative pulse overflow
Monitor item*1 74 ○ *4
value display*2 criterion*3 times (control terminal option)
1 Output frequency/speed *4 75 Multi-revolution counter 65535
*4 87 Remote output value 1 ○ *4
2 Output current
*4 88 Remote output value 2 ○ *4
3 Output voltage
Frequency setting value/motor 89 Remote output value 3 ○ *4
5 *4
speed setting *4
90 Remote output value 4 ○
6 Running speed *4
91 PID manipulated amount ○ *4
7 Motor torque *4
Second PID set point/deviation *4
*4 92
8 Converter output voltage input selection
93 Second PID measured value *4
9*5 Regenerative brake duty *4
620 5. PARAMETERS
5.14 (A) Application parameters
*5 Monitoring is available only for standard models.
*6 Rated motor frequency × 120 / number of motor poles
*7 Inverter output voltage is displayed when the FR-A8NS is not installed.
1
10
5. PARAMETERS
5.14 (A) Application parameters
621
Digital source (monitor item) selection
• Select the digital sources (input/output signals) to be set to Pr.1038 to Pr.1045 from the following table. When a value
other than the below, "0" (OFF) is applied for indication.
Setting Setting
Signal name Remarks Signal name Remarks
value value
0 — 101 RUN
1 STF 102 SU
2 STR 103 IPF
For the details of the signals, refer to
3 AU 104 OL
page 450.
4 RT 105 FU
5 RL 106 ABC1
For the details of the signals, refer to
6 RM 107 ABC2
page 496.
7 RH 121 DO0
8 JOG 122 DO1
9 MRS 123 DO2 For the details of the signals, refer to
10 STP (STOP) 124 DO3 the Instruction Manual of the FR-
11 RES 125 DO4 A8AY (option).
12 CS 126 DO5
21 X0 127 DO6
22 X1 128 RA1 For the details of the signals, refer to
23 X2 129 RA2 the Instruction Manual of the FR-
24 X3 130 RA3 A8AR (option).
25 X4
26 X5
27 X6
28 X7 For the details of the signals, refer to
29 X8 the Instruction Manual of the FR-
30 X9 A8AX (option).
31 X10
32 X11
33 X12
34 X13
35 X14
36 X15
37 DY
*1 In Pr.1037, set the number obtained by adding 1,000 to the trigger level.
622 5. PARAMETERS
5.14 (A) Application parameters
• Set the trigger generation conditions for the digital monitor.
Pr.1047
setting
Trigger generation conditions 1
0 Trace starts when the digital data targeted for the trigger turns ON
1 Trace starts when the digital data targeted for the trigger turns OFF
1 Sampling start
7
2 Forced trigger (sampling stop)
3 Sampling stop
4 Data transmission
8
• Trace operation can also be set in the trace mode on the operation panel.
10
Parameter setting mode Sampling start Data transmission
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
5. PARAMETERS
5.14 (A) Application parameters
623
Monitoring the trace status
• The trace status can be monitored on the operation panel by setting "38" in Pr.52 Operation panel main monitor
selection, Pr.774 to Pr.776 (Operation panel monitor selection), or Pr.992 Operation panel setting dial push
monitor selection.
The content depends on the digits on the operation panel.
Trace status
Monitor value
Fourth digit Third digit Second digit First digit
0 or no display*1 No trace data in internal RAM USB memory not accessed Trigger not detected Trace stopped
USB memory being
1 Trace data in internal RAM Trigger detected Trace operation
accessed
2 — USB memory transfer error — —
3 — USB buffer overrun — —
*1 The value(s) "0" to the left of the leftmost non-zero value is(are) not shown in the monitor display. For example, if no trace data is in internal RAM,
the USB memory is not accessed, no trigger is detected, and the trace operation is performed, "1" appears. (not "0001")
• When copying the traced data to a USB memory device, the operating status of the USB host can be checked with the
inverter LED.
Refer to page page 84 for an outline of the USB communication function.
LED display status Operating status
OFF No USB connection.
ON The communication is established between the inverter and the USB device.
Traced data is being transmitted. (In the memory mode, transmission command is being issued. In the recorder mode,
Blinking rapidly
sampling is being performed.)
Blinking slowly Error in the USB connection.
• During trace operation, the Trace status (Y40) signal can be output.
To use the Y40 signal, set "40 (positive logic) or 140 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign function to an output terminal.
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.52 Operation panel main monitor selectionpage 424
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
624 5. PARAMETERS
5.14 (A) Application parameters
5.15 (N) Communication operation parameters 1
8 to 1
5. PARAMETERS
5.15 (N) Communication operation parameters
625
NOTE
• Pins No. 2 and 8 provide power to the operation panel or parameter unit. Do not use these pins for RS-485 communication.
• Do not connect the PU connector to the computer's LAN board, FAX modem socket, or telephone modular connector. The
product could be damaged due to differences in electrical specifications.
Inverter
Computer Side Terminals Cable connection and signal direction
PU connector
Signal name Description
Communication cable
RDA Receive data SDA
RDB Receive data SDB
SDA Send data RDA
SDB Send data RDB
RSA Request to send
RSB Request to send
∗1
CSA Clear to send
CSB Clear to send
0.2 mm2 or more
SG Signal ground SG
FG Frame ground
*1 Make connection in accordance with the Instruction Manual of the computer to be used with. Fully check the terminal numbers of the computer
since they vary with the model.
NOTE
• When performing RS-485 communication with multiple inverters, use the RS-485 terminals. (Refer to page 628.)
• Computer-inverter connection cable
Refer to the following for the connection cable (RS-232C to RS-485 converter) between the computer with an RS-232C
interface and an inverter. Commercially available products (as of February 2015)
Model Manufacturer
Interface embedded cable
DAFXIH-CAB (D-SUB25P for personal computer)
DAFXIH-CABV (D-SUB9P for personal computer)
+ Diatrend Corp.
Connector conversion cable DINV-485CAB (for inverter)*2
Interface embedded cable dedicated for inverter
DINV-CABV*2
*2 The conversion cable cannot connect multiple inverters. (The computer and inverter are connected in a 1:1 pair.) This product is an RS-
232C to RS-485 conversion cable that has a built-in converter. No additional cable or connector is required. For the product details, contact
the manufacturer.
626 5. PARAMETERS
5.15 (N) Communication operation parameters
• Refer to the following table when fabricating the cable on the user side.
Commercially available products (as of February 2015)
5
P5S SG SDA1 SDB1 RDA1 RDB1
(VCC) (GND) (TXD1+) (TXD1-) (RXD1+) (RXD1-)
OPEN
6
VCC GND + TXD - + RXD -
7
VCC GND + TXD - + RXD -
100Ω
P5S SG SDA2 SDB2 RDA2 RDB2
8
(VCC) (GND) (TXD2+) (TXD2-) (RXD2+) (RXD2-)
9
Name Description
RDA1 (RXD1+) Inverter receive+
RDB1 (RXD1-)
RDA2 (RXD2+)
Inverter receive-
Inverter receive + (for branch)
10
RDB2 (RXD2-) Inverter receive - (for branch)
SDA1 (TXD1+) Inverter send+
SDB1 (TXD1-) Inverter send-
SDA2 (TXD2+) Inverter send + (for branch)
SDB2 (TXD2-) Inverter send - (for branch)
P5S (VCC) 5 V (permissible load current 100 mA)
SG (GND) Earthing (grounding) (connected to terminal SD)
5. PARAMETERS
5.15 (N) Communication operation parameters
627
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• When the FR-A820-01250(22K) or lower, or the FR-A840-00620(22K) or lower is used with a plug-in option, lead the wires
through the hole on the side face of the front cover for wiring of the RS-485 terminals.
• When the FR-A820-01540(30K) of higher, or the FR-A840-00770(30K) or higher is used with a plug-in option, lead the wires
on the left side of the plug-in option for wiring of the RS-485 terminals.
Computer Computer
Inverter Inverter
RS-485 RS-485
RS-485 terminals Maximum terminals
interface/ ∗ RS-232C 15 m ∗
terminals cable
Converter
628 5. PARAMETERS
5.15 (N) Communication operation parameters
RS-485 terminal wiring method
• Wiring between a computer and an inverter for RS-485 communications 1
Computer
RDA
RDB 2
SDA
SDB
RSA
∗2
3
+
+
-
-
RSB
∗1
CSA
SDB1
SDA1
RDB1
RDA1
CSB
SG SG
4
FG
+
+
+
+
+
+
-
-
-
-
-
-
-
RSB
∗1
CSA
SDB1
SDA1
SDB2
SDA2
RDB1
RDA1
RDB2
RDA2
SDB1
SDA1
SDB2
SDA2
RDB1
RDA1
RDB2
RDA2
SDB1
SDA1
RDB1
RDA1
CSB 8
SG SG SG SG SG SG
FG Station 0 Station 1 Station n
*1 Make connection in accordance with the Instruction Manual of the computer to be used with. 9
Fully check the terminal numbers of the computer since they vary with the model.
*2 On the inverter most remotely connected with the computer, set the terminating resistor switch in the ON (100 Ω) position.
NOTE 10
• For branching, connect the wires as shown below.
To computer ground
To computer receive
Computer Inverter
TXD+
Transmission TXD-
enable RXD+
Reception RXD-
Pass a wire
enable SG SG
5. PARAMETERS
5.15 (N) Communication operation parameters
629
NOTE
• A program should be created so that transmission is disabled (receiving state) when the computer is not sending and reception
is disabled (sending state) during sending to prevent the computer from receiving its own data.
Setting
Pr. Name Initial value Description
range
549 0 Mitsubishi inverter protocol (computer link)
Protocol selection 0
N000 1 MODBUS RTU protocol
Communication Parameter values written by communication are written to the EEPROM and
342 0
EEPROM write 0 RAM.
N001
selection 1 Parameter values written by communication are written to the RAM.
349 0 Enables the error reset function in any operation mode.
* Communication reset
N010 0
1
selection 1 Enables the error reset function only in the Network operation mode.
500 Set the time from when the communication line error occurs until the inverter
Communication error
N011* 0 0 to 999.8 s starts the operation for the communication error (when a communication
execution waiting time
1 option is used).
501 Communication error
Displays the communication error occurrence count (when a communication
N012* occurrence count 0 0
option is used).
1 display
502 Stop mode selection at 0 to 4, 11,
0 Select the operation at a communication error occurrence.
N013 communication error 12
Operation frequency 0 to 590 Hz Set the frequency for the operation when a communication error occurs.
779
during communication 9999
N014 9999 Operation continues at the same frequency before the communication error.
error
*1 The setting is available only when a communication option is installed.
*2 If in communication by the communication option, "E.OP1" is displayed.
NOTE
• Turning OFF the inverter's power supply clears the modified parameter settings when Pr.342 = "1 (write only to RAM)".
Therefore, the parameter values at next power-ON are the values last stored in EEPROM.
• The parameter setting written in RAM cannot be checked on the operation panel. (The values displayed on the operation panel
are the ones stored in EEPROM.)
630 5. PARAMETERS
5.15 (N) Communication operation parameters
Operation selection at a communication error (Pr.502, Pr.779)
• For communication using RS-485 terminals or a communication option, operation at a communication error can be 1
selected. The operation is active under the Network operation mode.
• Select the stop operation at the retry count excess (Pr.335, enabled only when the Mitsubishi inverter protocol is selected)
or at a signal loss detection (Pr.336, Pr.539). 2
At fault occurrence At fault removal
Pr.502
Fault type Fault (ALM) Fault (ALM)
setting Operation Indication
signal
Operation Indication
signal 3
0
Output stop
(initial Output shutoff E. SER*1 ON
value) status E. SER*1 ON
• The motor is decelerated to a stop according to the setting of Pr.111 Third deceleration time when an error occurs while
9
Pr.502 = "11 or 12".
0
Pr.502 setting
Output shutoff
Operation to a stop at a communication error occurrence
10
1 to 4 Deceleration stop according to the selected deceleration time (selectable using the RT or X9 signal)
11, 12 Deceleration stop according to the setting of Pr.111
• When a communication error is detected while communication with the RS-485 terminals is performed, the Alarm (LF)
signal is output to an output terminal of the inverter. To use the LF signal, set "98 (positive logic) or 198 (negative logic)"
in any of Pr.190 to Pr.196 (Output terminal function selection) to assign the function to the output terminal. (To output
the LF signal even if communication through RS-485 terminals is not performed for the time set in Pr.336 or longer, or
during communication using a communication option, set "3 or 4" in Pr.502.)
5. PARAMETERS
5.15 (N) Communication operation parameters
631
• The following charts show operations when a communication line error occurs.
Output frequency
to stop
Time Time
Fault display Display Fault display Display
(E.SER/E.OP1) (E.SER/E.OP1)
Fault output OFF ON Fault output OFF ON
(ALM) (ALM)
Alarm output OFF ON OFF Alarm output OFF ON OFF
(LF) (LF)
to stop
Output frequency
Pr.779 ≠“9999”
(Runs at the frequency setting of Pr.779)
Time Time
Fault display Display Fault display Not displayed
(E.SER/E.OP1)
Fault output OFF Fault output OFF
(ALM) (ALM)
Alarm output OFF ON OFF Alarm output OFF ON OFF
(LF) (LF)
Pr.502 = "4"
Fault recognition Fault removal
Pr.779
Pr.779 ≠“9999”
(Runs at the frequency setting of Pr.779)
Time
Warning display Display
(CF)
Fault output OFF
(ALM)
Alarm output OFF ON OFF
(LF)
632 5. PARAMETERS
5.15 (N) Communication operation parameters
• The following charts show operations when a communication option fault occurs.
Motor coasting 2
Output frequency
Output frequency
Decelerates to stop
3
Time Fault display Time
Fault display
(E.1) Display (E.1) Display 4
Fault output Fault output
(ALM) OFF ON (ALM) OFF ON
Alarm output Alarm output
(LF) OFF (LF) OFF
5
Pr.502 = "4" Fault occurrence Fault removal
7
Pr.779
Pr.779 ≠“9999”
(Runs at the frequency setting of Pr.779)
Warning display
Time 8
(CF) Display
Fault output
(ALM)
Alarm output
OFF
9
(LF) OFF ON
10
5. PARAMETERS
5.15 (N) Communication operation parameters
633
NOTE
• When a communication option is used, the protective function [E.OP1 (fault data: HA1)] is activated at error occurrences on
the communication line. The protective function [E.1 (fault data: HF1)] is activated at error occurrences in the communication
circuit inside the option.
• Fault output indicates the Fault (ALM) signal and an alarm bit output.
• When the fault output is set enabled, fault records are stored in the faults history. (A fault record is written to the faults history
at a fault output.)
• When the fault output is not enabled, fault record is overwritten to the faults history temporarily but not stored.
• After the fault is removed, the fault indication goes back to normal indication on the monitor, and the faults history goes back
to the previous status.
• When Pr.502 ≠ "0", the normal deceleration time setting (settings like Pr.8, Pr.44, and Pr.45) is applied as the deceleration
time. Normal acceleration time setting (settings like Pr.7 and Pr.44) is applied as the acceleration time for restart.
• When Pr.502 = "2, 3, or 4", the inverter operates with the start command and the speed command, which were used before
the fault.
• If a communication line error occurs, then the error is removed during deceleration while Pr.502 = "2", the motor re-accelerates
from that point. (When a communication option is used, acceleration does not restart at a communication option error.)
• The Pr.502 and Pr.779 settings are valid when communication is performed via the RS-485 terminals or a communication
option.
• These parameters are valid under the Network operation mode. When performing communication through RS-485 terminals,
set Pr.551 PU mode operation command source selection ≠ "1".
• Pr.502 is valid for the device that has the command source under the Network operation mode. If a communication option is
installed while Pr.550 = "9999 (initial setting)", a communication error in RS-485 terminals occurs and Pr.502 becomes invalid.
• If the communication error setting is disabled with Pr.335 = "9999" or Pr.539 = "9999" while Pr.502 = "3 or 4", the inverter does
not operate with the frequency set in Pr.779 when a communication error occurs.
• If a communication error occurs while continuous operation at Pr.779 is selected with Pr.502 = "3 or 4", the inverter operates
at the frequency set in Pr.779 even though the speed command source is at the external terminals.
Example) If a communication error occurs while Pr.339 = "2" and the RL signal is input through an external terminal, the
operation is continued at the frequency set in Pr.779.
• During position control, an error occurs even if "2" is set in Pr.502.
CAUTION
• When Pr.502 = "3" and a communication line error occurs, or Pr.502 = "4" and a communication line error or a
communication option fault occurs, the operation continues. When setting "3 or 4" in Pr.502, provide a safety stop
countermeasure other than via communication. For example, input a signal through an external terminal (RES, MRS, or
X92) or press the PU stop on the operation panel.
Waiting time setting from the communication line error occurrence to the
communication error activation (Pr.500)
• When a communication option is used, use Pr.500 Communication error execution waiting time to set the time from
when the communication line error occurs until the inverter starts the operation for the communication error.
• When a communication line error occurs and lasts longer than the time set in Pr.500, it is recognized as a communication
error. If the communication returns to normal within the time, it is not recognized as a communication error, and the
operation continues.
634 5. PARAMETERS
5.15 (N) Communication operation parameters
• Operation from the error occurrence until the Pr.500 setting time elapses
Fault type
Pr.502
setting
Operation Indication Fault output 1
0
1
Operation
Communication line 2
continues.*1
Normal*1 Not provided.*1 2
3
4
0, 3 Output shutoff "E. 1" Output
Output to decelerate
3
Communication option 1, 2 "E. 1" after stop Output after stop
and stop the motor
4 Operation continues. "CF" warning Not output
*1 When the communication returns to normal within the time period set in Pr.500, the protective function (E.OP1) is not activated. 4
Displaying and clearing the communication error count (Pr.501)
• When a communication option is used, the cumulative count of communication error occurrences can be displayed. Write
5
"0" to clear this cumulative count.
• When a communication line error occurs, the setting of Pr.501 Communication error occurrence count display
increases by one.
6
• The cumulative count of communication error occurrences is counted from 0 to 65535. When the count exceeds 65535,
the displayed value is cleared and the counting starts over from 0 again.
NOTE 8
• Communication error count is temporarily stored in the RAM memory. The error count is stored in EEPROM only once per
hour. If power reset or inverter reset is performed, Pr.501 setting will be the one that is last stored to EEPROM depending on
the reset timing.
9
Error reset operation selection at inverter fault (Pr.349)
• An error reset command from a communication option can be invalidated in the External operation mode or the PU 10
operation mode.
Pr.349 setting Description
0 (initial value) Error reset is enabled independently of operation mode.
1 Error reset is enabled in the Network operation mode.
NOTE
• The changed value in Pr.340 is applied after the next power-ON or inverter reset.
• The Pr.340 setting can be changed on the operation panel in any operation mode.
• When setting a value other than "0" in Pr.340, make sure that the communication settings of the inverter are correct.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.111 Third deceleration timepage 349
5. PARAMETERS
5.15 (N) Communication operation parameters
635
Pr.79 Operation mode selectionpage 370
Pr.340 Communication startup mode selectionpage 378
Pr.335 RS-485 communication retry countpage 636
Pr.336 RS-485 communication check time intervalpage 636
Pr.539 MODBUS RTU communication check time intervalpage 652
Pr.550 NET mode operation command source selectionpage 380
Pr.551 PU mode operation command source selectionpage 380
636 5. PARAMETERS
5.15 (N) Communication operation parameters
Parameters related to RS-485 terminal communication
Pr. Name
Initial Setting
Description
1
value range
0 to 31
331 RS-485 communication (0 to Enter the station number of the inverter.
0
N030 station number
247)*1*2
(Same specifications as Pr.117)
2
3, 6, 12, 24,
332 RS-485 communication 48, 96, 192, Select the communication speed.
96
N031 speed 384, 576, (Same specifications as Pr.118)
768, 1152 3
RS-485 communication
N032
data length
0 0, 1 Select the data length. (Same specifications as P.E022)*3
RS-485 communication
N033
stop bit length
1 0, 1 Select the stop bit length. (Same specifications as P.E023)*4 4
RS-485 communication Select the stop bit length and data bit length. (Same specifications as
333 stop bit length / data 1 0, 1, 10, 11
length Pr.119)*3*4
334 RS-485 communication Select the parity check specifications.
5
2 0, 1, 2
N034 parity check selection (Same specifications as Pr.120)
335 RS-485 communication 0 to 10, Set the permissible number of retries for unsuccessful data reception.
1
N035*5 retry count 9999 (Same specifications as Pr.121)
RS-485 communication is available, but the inverter trips in the NET
6
0
operation mode.
336 RS-485 communication
0s 0.1 to 999.8 Set the interval of the communication check (Signal loss detection) time.
N036*5 check time interval
s (Same specifications as Pr.122) 7
9999 No communication check (Signal loss detection)
337 RS-485 communication 0 to 150 ms, Set the waiting time between data transmission to the inverter and the
9999
N037*5 waiting time setting 9999 response. (Same specifications as Pr.123)
341 RS-485 communication Select the presence/absence of CR/LF. 8
1 0, 1, 2
N038*5 CR/LF selection (Same specifications as Pr.124)
*1 When "1" (MODBUS RTU protocol) is set in Pr.549, the setting range within parentheses is applied.
*2
*3
When a value outside the setting range is set, the inverter operates at the initial value.
In the MODBUS RTU protocol, the data length is fixed at 8 bits.
9
*4 In the MODBUS RTU protocol, Pr.334 setting is applied as the stop bit length. (Refer to page 652.)
*5 In the MODBUS RTU protocol, this is invalid.
NOTE 10
• The monitor items and parameter settings can be read during communication with the Pr.336 RS-485 communication check
time interval = "0 (initial value)" setting, but such operation will become faulty once the operation mode is changed to the NET
operation mode. When the NET operation mode is selected as the start-up operation mode, communication is performed once,
then a Communication fault (inverter) (E.SER) occurs. To perform operation or parameter writing via communication, set
"9999" or a large setting value in Pr.336. (The setting value is determined by the computer program.) (Refer to page 643.)
• Always reset the inverter after making the initial settings of the parameters. After changing the communication-related
parameters, communication cannot be made until the inverter is reset.
5. PARAMETERS
5.15 (N) Communication operation parameters
637
Communication specifications
• The communication specifications are given below.
Related
Item Description
parameter
Communication protocol Mitsubishi inverter protocol (computer link communication) Pr.551
Conforming standard EIA-485 (RS-485) —
Pr.117
Number of connectable units 1: N (maximum 32 units), the setting range of station number is 0 to 31.
Pr.331
PU connector Selected among 4800/9600/19200/38400/57600/76800/115200 bps. Pr.118
Communication
Selected among 300/600/1200/2400/4800/9600/19200/38400/57600/76800/
speed RS-485 terminals Pr.332
115200 bps.
Control procedure Asynchronous method —
Communication method Half-duplex system —
Pr.119
Character system ASCII (7 bits or 8 bits can be selected.)
Pr.333
Start bit 1 bit —
Pr.119
Stop bit length 1 bit or 2 bits can be selected.
Communication Pr.333
specifications Pr.120
Parity check Check (at even or odd numbers) or no check can be selected.
Pr.334
Error check Sum code check —
Pr.124
Terminator CR/LF (whether or not to use it can be selected)
Pr.341
Pr.123
Waiting time setting Availability of the setting is selectable.
Pr.337
Communication procedure
• Data communication between the computer and inverter is made in the following procedure.
(a) Request data is sent from the computer to the inverter. (The inverter will not send data unless requested.)
(b) Communication waiting time
(c) The inverter sends reply data to the computer in response to the computer request.
(d) Inverter data processing time
(e) An answer from the computer in response to reply data (c) of the inverter is transmitted. (Even if (e) is not sent, subsequent
communication is made properly.)
638 5. PARAMETERS
5.15 (N) Communication operation parameters
• Communication operation presence/absence and data format types are as follows.
Symbol Operation
Operation
command
Operation
frequency
Multi
command
Parameter
write
Inverter
reset
Monitor
Parameter
read
1
Communication request is sent to the
a inverter in accordance with the user A, A1 A A2 A A B B
b
program in the computer.
Inverter data processing time With With With With Without With With
2
No error*1 E, E1,
(Request C C C1*3 C C*2 E2, E3
E
Reply data from the
c inverter (Data (a) is
accepted) 3
checked for an error.) With error
(Request D D D D D*2 D D
rejected)
d Computer processing delay time 10 ms or more 4
*1
No error Without Without
(No inverter Without Without Without Without Without (C)
Reply from computer in (C) (C)
processing)
e
response to reply data c
(Data c is checked for With error 5
error.) (Inverter
Without Without F Without Without F F
outputs c
again.)
*1 In the communication request data from the computer to the inverter, 10 ms or more is also required after "no data error (ACK)". (Refer to page
6
642.)
*2 Reply from the inverter to the inverter reset request can be selected. (Refer to page 646.)
*3 At mode error, and data range error, C1 data contains an error code. (Refer to page 651.) Except for those errors, the error is returned with data
format D. 7
• Data writing format
a. Communication request data from the computer to the inverter
Number of characters
8
Format
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Inverter
ENQ Instruction Sum
A *1
station
code
*3 Data
check
*4
9
number*2
Inverter
ENQ Instruction Sum
A1 *1
station *3 Data *4
number*2
code check
10
Inverter Send Receive
ENQ Instruction Sum
A2 *1
station *3 data data Data 1 Data 2 *4
code check
number*2 type type
c. Reply data from the inverter to the computer (No data error detected)
Number of characters
Format
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Inverter
ACK
C *1
station *4
number *2
c. Reply data from the inverter to the computer (Data error detected)
Number of characters
Format
1 2 3 4 5
*1 *2 Error *4
D NAK Inverter station number code
5. PARAMETERS
5.15 (N) Communication operation parameters
639
a. Communication request data from the computer to the inverter
Number of characters
Format
1 2 3 4 5 6 7 8 9
Inverter station
B ENQ*1 Instruction code *3 Sum check *4
number *2
c. Reply data from the inverter to the computer (No data error detected)
Number of characters
Format
1 2 3 4 5 6 7 8 9 10 11 12 13
Inverter station
E STX*1 Read data ETX *1 Sum check *4
number *2
Inverter station
E1 STX *1 Read data ETX*1 Sum check *4
number *2
Inverter station
E2 STX *1 Read data ETX*1 Sum check *4
number *2
Number of characters
Format
1 2 3 4 to 23 24 25 26 27
Inverter station
E3 STX*1 Read data (Inverter model information) ETX*1 Sum check *4
number*2
c. Reply data from the inverter to the computer (Data error detected)
Number of characters
Format
1 2 3 4 5
Inverter station Error
D NAK *1 *4
number *2 code
e. Transmission data from the computer to the inverter when reading data
Number of characters
Format
1 2 3 4
C Inverter station
(No data error ACK*1 *4
detected) number *2
F Inverter station
(Data error NAK *1 *4
detected) number *2
Data definitions
• Control code
Signal name ASCII code Description
STX H02 Start Of Text (Start of data)
ETX H03 End Of Text (End of data)
ENQ H05 Enquiry (Communication request)
ACK H06 Acknowledge (No data error detected)
LF H0A Line Feed
CR H0D Carriage Return
NAK H15 Negative Acknowledge (Data error detected)
640 5. PARAMETERS
5.15 (N) Communication operation parameters
• Data
Indicates the data such as frequency and parameters transferred to and from the inverter. The definitions and ranges of
set data are determined in accordance with the instruction codes. (Refer to page 646.)
1
• Waiting time
Specify the waiting time between the receipt of data at the inverter from the computer and the transmission of reply data.
2
Set the waiting time in accordance with the response time of the computer in the range of 0 to 150 ms in 10 ms increments.
(For example; 1 = 10 ms, 2 = 20 ms)
When Pr.123 or Pr.337 (waiting time setting) ≠ "9999", create a communication request data without waiting time in the 3
data format. (The number of characters decreases by 1.)
Inverter
Computer
5
*1 When Pr.123 = "9999", the waiting time is the data setting value × 10 ms. When Pr.123 ≠ "9999", the waiting time is the value set in Pr.123.
*2 The time is about 10 to 30 ms. It varies depending on the instruction code.
NOTE 6
• The data check time varies depending on the instruction code. (Refer to page 642.)
Instruction
check
ENQ Station code Data
9
time
10
H30+H31+H45+H31+H31+H30+H37+H41+H44
= H1F4
Sum
* When the Pr.123 or Pr.337 (Waiting time setting) "9999", create the communication request
data without "waiting time" in the data format. (The number of characters decreases by 1.)
(Example 2) Sum
Data read
STX Station checkETX
Inverter Computer number code
0 1 1 7 7 0 3 0 Binary code
ASCII Code H02 H30 H31 H31 H37 H37 H30 H03 H33 H30
H30+H31+H31+H37+H37+H30
= H130
Sum
• Error code
If any error is found in the data received by the inverter, its error definition is sent back to the computer together with the
5. PARAMETERS
5.15 (N) Communication operation parameters
641
NAK code.
Error code Error item Error description Inverter operation
The number of errors consecutively detected in
H0 Computer NAK error communication request data from the computer is greater
than the permissible number of retries.
H1 Parity error The parity check result does not match the specified parity.
The inverter output is shut off
The sum check code in the computer does not match that of
H2 Sum check error (E.PUE/E.SER) if error occurs
the data received by the inverter.
continuously more than the
The data received by the inverter has a grammatical mistake.
permissible number of retries.
H3 Protocol error Or, data receive is not completed within the predetermined The LF signal is output.
time. CR or LF is not as set in the parameter.
H4 Framing error The stop bit length differs from the initial setting.
New data has been sent by the computer before the inverter
H5 Overrun error
completes receiving the preceding data.
H6 — — —
The inverter does not accept the
The character received is invalid (other than 0 to 9, A to F,
H7 Character error received data. However, the
control code).
inverter output is not shut off.
H8 — — —
H9 — — —
Parameter write was attempted in other than the computer
HA Mode error link operation mode, when operation command source is not
selected or during Inverter operation. The inverter does not accept the
received data. However, the
HB Instruction code error The specified instruction code does not exist.
inverter output is not shut off.
Invalid data has been specified for parameter writing, running
HC Data range error
frequency setting, etc.
HD — — —
HE — — —
HF Normal (no error) — —
Response time
Data sending time (refer to the following formula)
Inverter data processing time Waiting time Data check time
Computer (setting 10 ms) (depends on the
instruction code*3)
Inverter
Time
Inverter 10 ms or more necessary
Computer Data sending time (refer to the following formula)
642 5. PARAMETERS
5.15 (N) Communication operation parameters
Retry count setting (Pr.121, Pr.335)
• Set the permissible number of retries at data receive error occurrence. (Refer to page 641 for data receive error for retry.) 1
• When the data receive errors occur consecutively and the number of retries exceeds the permissible number setting, a
communication fault (PU connector communication: E.PUE, RS-485 terminal communication: E.SER) occurs and the
inverter output is shut off. 2
• When a data transmission error occurs while "9999" is set, the inverter does not trip but outputs the Alarm (LF) signal. To
use the LF signal, set "98 (positive logic) or 198 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to an output terminal. 3
Example: PU connector communication, Pr. 121 = "1" (initial value)
Fault (E.PUE)
4
ENQ
ENQ
Computer Inverter Illegal Illegal
ACK
NAK
NAK
Inverter Computer
6
Example: PU connector communication, Pr. 121 = "9999"
ENQ
ENQ
ENQ
Illegal Illegal Normal
Computer Inverter
7
ACK
NAK
NAK
ACK
Inverter Computer
ALM OFF
NOTE
9
• For the RS-485 terminal communication, the operation at a communication error occurrence depends on the Pr.502 Stop
mode selection at communication error setting. (Refer to page 630.)
10
Signal loss detection (Pr.122, Pr.336 RS-485 communication check time
interval)
• If a signal loss (communication stop) is detected between the inverter and computer as a result of a signal loss detection,
a communication error (PU connector communication: E.PUE, RS-485 terminal communication: E.SER) occurs and the
inverter output is shut off.
• The LF signal is not output when a signal loss is detected. However, when a signal loss is detected via communication
through the RS-485 terminals while Pr.502 = "3 or 4", the LF signal is output.
• When the setting is "9999", communication check (signal loss detection) is not made.
• When the setting is "0", communication through the PU connector is not possible. The monitor items and parameter
settings can be read during communication via RS-485 terminals, but a communication error (E.SER) occurs instantly
when the operation mode is switched to the Network operation.
• A signal loss detection is made when the setting is any of "0.1 s to 999.8 s". To make a signal loss detection, it is necessary
to send data (for details on control codes, refer to page 640) from the computer within the communication check time
interval. (The inverter makes a communication check (clearing of communication check counter) regardless of the station
number setting of the data sent from the master).
5. PARAMETERS
5.15 (N) Communication operation parameters
643
• Communication check is started at the first communication in the operation mode having the operation source (PU
operation mode for PU connector communication in the initial setting or Network operation mode for RS-485 terminal
communication).
ENQ
Computer Inverter
Inverter Computer
Fault (E.PUE)
Check start
Pr.122
Communication
check counter
Time
ALM OFF ON
Programming instructions
• When data from the computer has any error, the inverter does not accept that data. Hence, in the user program, always
insert a retry program for data error.
• All data communication, for example, run command or monitoring, are started when the computer gives a communication
request. The inverter does not return any data without the computer's request. Hence, design the program so that the
computer gives a data read request for monitoring, etc. as required.
• Program example: To switch to the Network operation mode
644 5. PARAMETERS
5.15 (N) Communication operation parameters
Microsoft® Visual C++® (Ver.6.0) programming example
#include <stdio.h>
#include <windows.h>
1
void main(void){
HANDLE hCom; // Communication handle
DCB
COMMTIMEOUTS
hDcb;
hTim;
// Structure for setting communication settings
// Structure for setting timeouts
2
char szTx[0x10]; // Send buffer
char szRx[0x10]; // Receive buffer
char
int
szCommand[0x10];// Command
nTx,nRx; // For storing buffer size
3
int nSum; // For calculating sum code
BOOL bRet;
int nRet;
int i;
4
// **** Open COM1 port ****
hCom = CreateFile("COM1", (GENERIC_READ | GENERIC_WRITE), 0, NULL, OPEN_EXISTING, FILE_ATTRIBUTE_NORMAL, NULL);
if(hCom != NULL) {
// **** Set COM1 port communication ****
GetCommState(hCom,&hDcb); // Get current communication information
5
h D c b . D C B l en g th = size o f( DC B ) ; // Structure size setting
hDcb.BaudRate = 19200; // Communication speed = 19200 bps
hDcb.ByteSize = 8; // Data length = 8 bits
hDcb.Parity = 2;
hDcb.StopBits = 2;
// Parity check at even numbers
// Stop bit = 2 bits 6
bRet = SetCommState(hCom,&hDcb); // Setting of changed communication information
if(bRet == TRUE) {
// **** Set COM1 port timeout ****
GetCommTimeouts(hCom,&hTim);
hTim.WriteTotalTimeoutConstant = 1000;
// Get current timeout values
// Write timeout 1 second 7
hTim.ReadTotalTimeoutConstant = 1000; // Read timeout 1 second
hTim.ReadTotalTimeoutConstantSetCommTimeouts(hCom,&hTim);// Setting of changed timeout values
// **** Setting of command for switching the station number 1 inverter to the Network operation mode ****
sprintf(szCommand,"01FB10000");
nTx = strlen(szCommand);
// Send data (NET operation write)
// Send data size 8
// **** Generate sum code ****
nSum = 0; // Initialize sum data
for(i = 0;i < nTx;i++) {
nSum += szCommand[i];
nSum &= (0xff);
// Calculate sum code
// Mask data 9
}
nRet = WriteFile(hCom,szTx,nTx,&nTx,NULL);
// **** Send ****
if(nRet != 0) {
nRet = ReadFile(hCom,szRx,sizeof(szRx),&nRx,NULL);
// **** Receive ****
if(nRet != 0) {
// **** Display receive data ****
for(i = 0;i < nRx;i++) {
printf("%02X ",(BYTE)szRx[i]);// Output received data to console
// Display ASCII code in Hexadecimal' In case of 0', "30" is displayed.
}
printf("\n\r");
}
}
}
CloseHandle(hCom); // Close communication port
}
}
5. PARAMETERS
5.15 (N) Communication operation parameters
645
General flowchart
Port open
Communication setting
CAUTION
• Always set the communication check time interval before starting operation to prevent hazardous conditions.
• Data communication is not started automatically but is made only once when the computer provides a communication
request. If communication is disabled during operation due to signal cable breakage etc., the inverter cannot be stopped.
When the communication check time interval has elapsed, the inverter output will be shut off (E.PUE, E.SER).
Turn the RES signal of the inverter ON or shut off the power supply to coast the motor to a stop.
• If communication is broken due to signal cable breakage, computer fault etc., the inverter does not detect such a fault.
This should be fully noted.
646 5. PARAMETERS
5.15 (N) Communication operation parameters
Number of
Read/ Instruction
Item Data description data digits
write code
(format)*1 1
Output H0000 to HFFFF: Output frequency in 0.01 Hz increments
frequency / Read H6F (The display can be changed to the rotations per minute using Pr.37, Pr.144, 4 digits (B.E/D)
speed and Pr.811. (Refer to page page 424.))
H0000 to HFFFF: Output current (hexadecimal) 2
Increment 0.01 A (FR-A820-03160(55K) or lower, FR-A840-01800(55K) or
Output current Read H70 lower) 4 digits (B.E/D)
Increment 0.1 A (FR-A820-03800(75K) or higher, FR-A840-02160(75K) or
higher) 3
Output voltage Read H71 H0000 to HFFFF: Output voltage (hexadecimal) in 0.1 V increments 4 digits (B.E/D)
Special monitor Read H72 H0000 to HFFFF: Monitor data selected in the instruction code HF3 4 digits (B.E/D)
2 digits (B.E1/
Special monitor
Read H73
D) 4
Monitor selection data (Refer to page 424 for details on selection No.)
selection No. 2 digits (A1, C/
Write HF3
D)
H0000 to HFFFF: Two latest fault records
5
b15 b8 b7 b0
Monitor
5. PARAMETERS
5.15 (N) Communication operation parameters
647
Number of
Read/ Instruction
Item Data description data digits
write code
(format)*1
All parameters return to initial values.
Whether to clear communication parameters or not can be selected
according to the data.
• Parameter clear
H9696: Parameters including communication parameters are cleared.
H5A5A: Parameters other than communication parameters are cleared.*2
• All parameter clear
H9966: Parameters including communication parameters are cleared.
Parameter clear
Write HFC H55AA: Parameters other than communication parameters are cleared.*2 4 digits (A,C/D)
All parameter clear
For the details of whether or not to clear parameters, refer to page 824.
When a clear is performed with H9696 or H9966, communication related
parameter settings also return to the initial values. When resuming the
operation, set the parameters again.
Performing a clear will clear the instruction code HEC, HF3, and HFF
settings.
Only H9966 and H55AA (All parameter clear) are valid when a password is
registered (refer to page 331).
Read H00 to H63 Refer to the instruction code (page 824) and write and/or read parameter 4 digits (B.E/D)
Parameter values as required. When setting Pr.100 and later, the link parameter
Write H80 to HE3 extended setting must be set. 4 digits (A,C/D)
2 digits (B.E1/
Read H7F
Link parameter Parameter settings are switched according to the H00 to H0D settings. D)
extended setting For details of the settings, refer to the instruction code (page 824). 2 digits (A1, C/
Write HFF
D)
Second parameter When setting the calibration parameters*3 2 digits (B.E1/
Read H6C
changing (instruction *4 D)
H00: Frequency
code H01: Parameter-set analog value 2 digits (A1, C/
HFF = 1, 9) Write HEC
H02: Analog value input from terminal D)
Read/ Available for writing 2 commands, and monitoring 2 items for reading data. 10 digits (A2,
Multi command HF0
write (Refer to page 651 for details.) C1/D)
The inverter model can be read in ASCII code.
Model information monitor
"H20" (blank code) is set for blank area. 20 digits (B, E3/
Inverter model Read H7C
Example) FR-A840-1 (FM type): D)
H46,H52,H2D,H41,H38,H34,H30,H2D,H31,H20,H20...H20
The inverter ND rated capacity can be read in ASCII code.
Data is read in increments of 0.1 kW, and rounds down to 0.01 kW
6 digits (B, E2/
Capacity Read H7D increments.
D)
"H20" (blank code) is set for blank area.
Example) 0.75K: " 7" (H20, H20, H20, H20, H20, H37)
*1 Refer to page 638 for data formats (A, A1, A2, B, C, C1, D, E, E1, E2, E3, F).
*2 Turning OFF the power supply while clearing parameters with H5A5A or H55AA returns the communication parameter settings to the initial
settings.
*3 Refer to the following calibration parameter list for details on the calibration parameters.
*4 The gain frequency can be also written using Pr.125 (instruction code: H99) or Pr.126 (instruction code: H9A).
NOTE
• Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
• For the instruction codes HFF, HEC, and HF3, their values once written are held, but cleared to zero when an inverter reset
or all clear is performed.
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
Example) When reading the C3 (Pr.902) and C6 (Pr.904) settings from the inverter of station No. 0.
Computer send data Inverter send data Description
a ENQ 00 FF 0 01 7D ACK 00 "H01" is set in the extended link parameter.
b ENQ 00 EC 0 01 79 ACK 00 "H01" is set in the second parameter changing.
c ENQ 00 5E 0 0A STX 00 0000 ETX 20 C3 (Pr.902) is read. 0% is read.
d ENQ 00 60 0 F6 STX 00 0000 ETX 20 C6 (Pr.904) is read. 0% is read.
To read/write C3 (Pr.902) or C6 (Pr.904) after inverter reset or parameter clear, execute from (a) again.
648 5. PARAMETERS
5.15 (N) Communication operation parameters
List of calibration parameters
Pr. Name
Instruction code 1
Read Write Extended
C2 (902) Terminal 2 frequency setting bias frequency 5E DE 1
C3 (902)
125 (903)
Terminal 2 frequency setting bias
Terminal 2 frequency setting gain frequency
5E
5F
DE
DF
1
1
2
C4 (903) Terminal 2 frequency setting gain 5F DF 1
C5 (904) Terminal 4 frequency setting bias frequency 60 E0 1
C6 (904) Terminal 4 frequency setting bias 60 E0 1 3
126 (905) Terminal 4 frequency setting gain frequency 61 E1 1
C7 (905) Terminal 4 frequency setting gain 61 E1 1
C12 (917) Terminal 1 bias frequency (speed) 11 91 9
C13(917) Terminal 1 bias (speed) 11 91 9
4
C14 (918) Terminal 1 gain frequency (speed) 12 92 9
C15 (918) Terminal 1 gain (speed) 12 92 9
C16 (919) Terminal 1 bias command (torque) 13 93 9 5
C17 (919) Terminal 1 bias (torque) 13 93 9
C18 (920) Terminal 1 gain command (torque) 14 94 9
C19 (920) Terminal 1 gain (torque) 14 94 9
C8 (930) Current output bias signal 1E 9E 9 6
C9 (930) Current output bias current 1E 9E 9
C10 (931) Current output gain signal 1F 9F 9
C11 (931) Current output gain current 1F 9F 9 7
C38 (932) Terminal 4 bias command (torque) 20 A0 9
C39 (932) Terminal 4 bias (torque) 20 A0 9
C40 (933) Terminal 4 gain command (torque) 21 A1 9
C41 (933) Terminal 4 gain (torque) 21 A1 9 8
C42 (934) PID display bias coefficient 22 A2 9
C43 (934) PID display bias analog value 22 A2 9
C44 (935)
C45 (935)
PID display gain coefficient
PID display gain analog value
23
23
A3
A3
9
9
9
10
5. PARAMETERS
5.15 (N) Communication operation parameters
649
Operation command
Instruction
Item Bit length Description*1*4 Example
code
b0: AU (Terminal 4 input selection)
b1: Forward rotation command
b2: Reverse rotation command [Example 1] H02 Forward rotation
b3: RL (Low-speed operation b7 b0
command)
Operation b4: RM (Middle-speed operation
0 0 0 0 0 0 1 0
HFA 8 bits
command command)
[Example 2] H00 Stop
b5: RH (High-speed operation
command) b7 b0
b6: RT (Second function selection) 0 0 0 0 0 0 0 0
b7: MRS (Output stop)*2
b0: AU (Terminal 4 input selection)
b1: Forward rotation command
b2: Reverse rotation command
b3: RL (Low-speed operation
command)
b4: RM (Middle-speed operation
command)
b5: RH (High-speed operation [Example 1] H0002 Forward rotation
command) b15 b0
b6: RT (Second function selection)
Operation 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0
command HF9 16 bits b7: MRS (Output stop)*2
(extended) b8: JOG (Jog operation selection)*3 [Example 2] H0804 Low-speed reverse operation
b9: CS (Selection of automatic (When Pr. 189 RES terminal function selection is set to "0")
restart after instantaneous power b15 b0
failure / flying start)*3 0 0 0 0 1 0 0 0 0 0 0 0 0 1 0 0
b10: STP (STOP) (Start self-holding
selection)*3
b11: RES (Selection of automatic
restart after instantaneous power
failure / flying start)*3
b12 to b15: –
*1 The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.180 to Pr.189 (Input terminal
function selection) (page 496).
*2 The Inverter run enable signal is in the initial status for the separated converter type.
*3 JOG operation/automatic restart after instantaneous power failure/start self-holding selection/reset cannot be controlled over a network, so in the
initial status bit 8 to bit 11 are invalid. To use bit 8 to bit 11, change the signal by Pr.185, Pr.186, Pr.188, or Pr.189 (Input terminal function
selection) (page 496) (A reset can be executed by the instruction code HFD.)
*4 During RS-485 communication through the PU connector, only the Forward rotation command and Reverse rotation command signals can be
used.
650 5. PARAMETERS
5.15 (N) Communication operation parameters
Inverter status monitor
Item
Instruction Bit
Description*1 Example
1
code length
b0: RUN (Inverter running)
b1: Forward rotation output
2
[Example 1] H02 During forward
b2: Reverse rotation output b7 rotation
b0
Inverter b3: SU (Up to frequency) 0 0 0 0 0 0 1 0
status H7A 8 bits b4: OL (Overload warning)
monitor b5: IPF (Instantaneous power failure/ [Example 2] H80 Stop at fault
undervoltage)*2 b7
occurrence
b0 3
b6: FU (Output frequency detection) 1 0 0 0 0 0 0 0
b7: ABC1 (Fault)
b0: RUN (Inverter running)
b1: Forward rotation output 4
b2: Reverse rotation output
b3: SU (Up to frequency) [Example 1] H0002 During forward rotation
b4: OL (Overload warning)
Inverter b15 b0
status
H79 16 bits
b5: IPF (Instantaneous power failure/
*2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 5
monitor undervoltage)
(extended) b6: FU (Output frequency detection) [Example 2] H8080 Stop at fault occurrence
b7: ABC1 (Fault) b15 b0
b8: ABC2 (–)
b9: Safety monitor output
1 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 6
b10 to b14: –
b15: Fault occurrence
*1 The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.190 to Pr.196 (Output terminal
function selection).
7
*2 No function is assigned in the initial status for the separated converter type.
5. PARAMETERS
5.15 (N) Communication operation parameters
651
5.15.6 MODBUS RTU communication specification
Operation by MODBUS RTU communication or parameter setting is possible by using the MODBUS RTU communication
protocol through the RS-485 terminals of the inverter.
Initial Setting
Pr. Name Description
value range
0 Broadcast communication
331 RS-485 communication Specify the inverter station number.
0
N030 station number 1 to 247 Enter the inverter station numbers when two or more inverters are
connected to one personal computer.
3, 6, 12, 24,
Select the communication speed.
332 RS-485 communication 48, 96, 192,
96 The setting value × 100 equals the communication speed.
N031 speed 384, 576,
For example, enter 96 to set the communication speed of 9600 bps.
768, 1152
0 Stop bit length 1 bit
RS-485 communication stop
N033 1 Valid when Pr.N034 (Pr.334) =
bit length 1 Stop bit length 2 bits "0"
0 Stop bit length 1 bit
RS-485 communication stop 1 Stop bit length 2 bits
333 1
bit length / data length 10 Stop bit length 1 bit Valid when Pr.334 = "0"
11 Stop bit length 2 bits
Without parity check
0
Stop bit length 1 bit / 2 bits (depends on the setting of Pr.333)
334 RS-485 communication parity With parity check at odd numbers
2 1
N034 check selection Stop bit length 1 bit
With parity check at even numbers
2
Stop bit length 1 bit
343 Displays the communication error count during MODBUS RTU
Communication error count 0 —
N080 communication. Read-only.
MODBUS RTU communication is available, but the inverter output is
0
MODBUS RTU shut off in the NET operation mode.
539
communication check time 9999 Set the interval of the communication check (signal loss detection)
N002 0.1 to 999.8 s
interval time (same specifications as Pr.122).
9999 No communication check (signal loss detection)
549 0 Mitsubishi inverter protocol (computer link)
Protocol selection 0
N000 1 MODBUS RTU protocol
NOTE
• To use the MODBUS RTU protocol, set "1" in Pr.549 Protocol selection.
• If MODBUS RTU communication is performed from the master to the address 0 (station number 0), the data is broadcasted,
and the inverter does not send any reply to the master. To obtain replies from the inverter, set Pr.331 RS-485 communication
station number ≠ "0 (initial value)".
• Some functions are disabled in broadcast communication. (Refer to page 655.)
• If a communication option is installed with Pr.550 NET mode operation command source selection = "9999 (initial value)",
commands (operation commands) transmitted via RS-485 terminals become invalid. (Refer to page 380.)
652 5. PARAMETERS
5.15 (N) Communication operation parameters
Communication specifications
• The communication specifications are given below. 1
Related
Item Description
parameter
Communication protocol
Conforming standard
MODBUS RTU protocol
EIA-485 (RS-485)
Pr.549
—
2
Number of connectable units 1: N (maximum 32 units), setting is 0 to 247 stations Pr.331
Selected among 300/600/1200/2400/4800/9600/19200/38400/57600/76800/
Communication speed Pr.332
115200 bps 3
Control procedure Asynchronous method —
Communication method Half-duplex system —
Character
system
Binary (fixed at 8 bits) —
4
Start bit 1 bit —
Stop bit length Select from the following three types:
Communication
No parity check, stop bit length 1 bit / 2 bits (depends on the setting of Pr.333) Pr.333
specifications
Parity check Odd parity check , stop bit length 1 bit Pr.334 5
Even parity check, stop bit length 1 bit
Error check CRC code check —
Message format
Inverter response time
Query communication (Refer to the following table for the
data check time)
Query Message
Programmable controller
(Master)
Inverter (slave) Response Message
Data absence time
(3.5 bytes or more)
Broadcast communication
Query Message
Programmable controller
(Master)
Inverter (slave) No Response
5. PARAMETERS
5.15 (N) Communication operation parameters
653
• Query
A message is sent to the slave (the inverter) having the address specified by the master.
• Normal response
After the query from the master is received, the slave executes the request function, and returns the corresponding normal
response to the master.
• Error Response
When an invalid function code, address or data is received by the slave, the error response is returned to the master.
This response is appended with an error code that indicates the reason why the request from the master could not be
executed.
This response cannot be returned for errors, detected by the hardware, frame error and CRC check error.
• Broadcast
The master can broadcast messages to all slaves by specifying address 0. All slaves that receive a message from the
master execute the requested function. With this type of communication, slaves do not return a response to the master.
NOTE
• During broadcast communication, functions are executed regarded of the set inverter station number (Pr.331).
Eight-Bit Eight-Bit
Data Bytes Data Bytes
Message frames comprise the four message fields shown in the figures above.
A slave recognizes message data as one message when a 3.5 character long no-data time (T1: start/end) is added before
and after the data.
• Details of protocol
The following table explains the four message fields.
Start Address Function Data CRC check End
Start ADDRESS FUNCTION DATA CRC CHECK End
L H
T1 8 bits 8 bits n × 8 bits T1
8 bits 8 bits
654 5. PARAMETERS
5.15 (N) Communication operation parameters
Message field Description
"0 to 247" can be set in the single-byte (8-bit) length field. Set "0" when sending broadcast messages
Address field
(instructions to all addresses), and "1 to 247" to send messages to individual slaves. 1
The response from the slave also contains the address set by the master. The value set in Pr.331 RS-485
communication station number is the slave address.
"1 to 255" can be set as the function code in the single-byte (8-bit) length filed. The master sets the function to
be sent to the slave as the request, and the slave performs the requested operation. Refer to the function code 2
Function list for details of the supported function codes. An error response is generated when a function code other than
field those in the function code list is set.
The normal response from the slave contains the function code set by the master. The error response contains
H80 and the function code. 3
The format changes according the function code. (Refer to page 655.) The data, for example, includes the byte
Data field
count, number of bytes, and accessing content of holding registers.
Errors in the received message frame are detected. Errors are detected in the CRC check, and the 2 bytes length
data is appended to the message. When the CRC is appended to the message, the lower bytes of the CRC are 4
CRC check appended first, followed by the upper bytes.
field The CRC value is calculated by the sender that appends the CRC to the message. The receiver recalculates
the CRC while the message is being received, and compares the calculation result against the actual value that
was received in the error check field. If the two values do not match, the result is treated as an error. 5
Function code list
Read/ Broadcast
Message
format 6
Function name Code Outline
write communication reference
page
The data of the holding registers is read.
The various data of the inverter can be read from MODBUS 7
registers.
System environmental variable (Refer to page 660.)
Read holding register Read H03 Not available page 655
Real time monitor (Refer to page 425.)
Faults history (Refer to page 663.) 8
Model information monitor (Refer to page 663.)
Inverter parameters (Refer to page 661.)
Data is written to a holding register.
Data can be written to MODBUS registers to output instructions 9
Preset single register Write H06 to the inverter or set parameters. Available page 656
System environmental variable (Refer to page 660.)
Inverter parameters (Refer to page 661.)
Functions are diagnosed. (Communication check only) 10
A communication check can be made since the query message
Diagnostics Read H08 is sent and the query message is returned as it is as the return Not available page 657
message (subfunction code H00 function).
Subfunction code H00 (Return query data)
Data is written to multiple consecutive holding registers.
Data can be written to consecutive multiple MODBUS registers to
Preset multiple
Write H10 output instructions to the inverter or set parameters. Available page 657
registers
System environmental variable (Refer to page 660.)
Inverter parameters (Refer to page 661.)
The number of registers that were successfully accessed by the
previous communication is read.
Queries by function codes H03 and H10 are supported.
Read holding register
Read H46 The number and start address of holding registers successfully Not available page 658
access log
accessed by the previous communication are returned.
"0" is returned for both the number and start address for queries
other than function code H03 and H10.
5. PARAMETERS
5.15 (N) Communication operation parameters
655
• Query message setting
Message Description
Set the address to send messages to. Broadcast communication is not possible. (Invalid when "0"
a Slave address
is set.)
b Function Set H03.
Set the holding register address from which to start reading the data.
Starting address = start register address (decimal) - 40001
c Starting address
For example, when starting register address 0001 is set, the data of holding register address 40002
is read.
d No. of points Set the number of holding registers for reading data. Data can be read from up to 125 registers.
Example) Read the register values of 41004 (Pr.4) to 41006 (Pr.6) from slave address 17 (H11).
Query message
Slave address Function Starting address No. of points CRC check
H11 H03 H03 HEB H00 H03 H77 H2B
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
Normal response (Response message)
Slave address Function Byte count Data CRC check
H11 H03 H06 H17 H70 H0B HB8 H03 HE8 H2C HE6
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
Read value
Register 41004 (Pr.4): H1770 (60.00 Hz)
Register 41005 (Pr.5): H0BB8 (30.00 Hz)
Register 41006 (Pr.6): H03E8 (10.00 Hz)
656 5. PARAMETERS
5.15 (N) Communication operation parameters
Example) Write 60 Hz (H1770) to 40014 (running frequency RAM) of slave address 5 (H05).
Query message
1
Slave address Function Register address Preset data CRC check
H05 H06 H00 H0D H17 H70 H17 H99
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
Normal response (Response message)
2
The same data as those in the query message
NOTE 3
• With broadcast communication, no response is generated even if a query is executed, so when the next query is made, it must
be made after waiting for the inverter data processing time after the previous query is executed.
4
Diagnostics (diagnosis of functions) (H08 or 08)
• A communication check can be made since the query message is sent and the query message is returned as it is as the
return message (subfunction code H00 function). Subfunction code H00 (Return query data) 5
• Query message
a. Slave address b. Function c. Subfunction d. Data CRC check
(8 bits)
H08 H00 H00 H L L H 6
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
• Normal response (Response message)
a. Slave address b. Function c. Subfunction d. Data CRC check 7
H08 H00 H00 H L L H
(8 bits)
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
• Query message setting 8
Message Description
Set the address to send messages to. Broadcast communication is not possible. (Invalid when "0" is
a Slave address
b Function
set.)
Set H08.
9
c Subfunction Set H0000.
d Data Any 2-byte long data can be set. The setting range is H0000 to HFFFF.
NOTE
• With broadcast communication, no response is generated even if a query is executed, so when the next query is made, it must
be made after waiting for the inverter data processing time after the previous query is executed.
5. PARAMETERS
5.15 (N) Communication operation parameters
657
• Query message setting
Message Description
a Slave address Set the address to send messages to. Setting "0" enables broadcast communication.
b Function Set H10.
Set the holding register address from which to start writing the data.
Starting address = start register address (decimal) - 40001
c Starting address
For example, when starting register address 0001 is set, the data of holding register address 40002
is read.
d No. of registers Set the number of holding registers for writing data. Data can be written to up to 125 registers.
e Byte count The setting range is H02 to HFA (2 to 250). Set twice the value specified by d.
Set the amount of data specified by d. Write data is output Hi bytes first followed by Lo bytes, and
f Data is arranged as follows: data of start address, data of start address+1, data of start address+2, and
so forth.
• Content of normal response
The contents in the normal response (a to d, including the CRC check) are the same as those in the query messages.
Example) Write 0.5 s (H05) to 41007 (Pr.7) and 1 s (H0A) to 41008 (Pr.8) of slave address 25
(H19).
Query message
Slave
Function Starting address No. of registers Byte count Data CRC check
address
H19 H10 H03 HEE H00 H02 H04 H00 H05 H00 H0A H86 H3D
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
658 5. PARAMETERS
5.15 (N) Communication operation parameters
Example) Read the successful register start address and number of successful accesses from
slave address 25 (H19).
Query message
1
Slave address Function CRC check
H19 H46 H8B HD2
(8 bits) (8 bits) (8 bits) (8 bits) 2
Normal response (Response message)
Slave address Function Starting address No. of points CRC check 3
H19 H10 H03 HEE H00 H02 H22 H61
(8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits) (8 bits)
The number of holding registers that were successfully accessed was returned as two with the start address 41007 (Pr.7). 4
Error response
• An error response is returned if the query message received from the master contains an illegal function, address or data.
No response is returned for parity, CRC, overrun, framing, and busy errors.
5
NOTE
• No response is also returned in the case of broadcast communication. 6
• Error response (Response message)
a. Slave address b. Function c. Exception code CRC check 7
H80 + Function L H
(8 bits) (8 bits)
(8 bits) (8 bits) (8 bits)
Message Description 8
a Slave address Set the address received from the master.
b Function The function code requested by the master and H80 is set.
c Exception code The codes in the following table are set.
9
• Error code list
Code Error item Error description
01
ILLEGAL FUNCTION
The query message from the master has a function code that cannot be handled by the slave.
10
ILLEGAL FUNCTION
ILLEGAL DATA ADDRESS The query message from the master has a register address that cannot be handled by the slave.
02
ILLEGAL DATA ADDRESS*1 (No parameter, parameter cannot be read, parameter cannot be written)
ILLEGAL DATA VALUE The query message from the master has data that cannot be handled by the slave.
03
ILLEGAL DATA VALUE (Out of parameter write range, a mode is specified, or other error)
In other words, when function code H03 or H10 is used and multiple holding registers are accessed, an error response is not returned even if a
nonexistent holding register or holding register that cannot be read or written from/to is accessed.
NOTE
• An error response is returned if none of the accessed holding registers exist. When an accessed holding register does not
exist, the read value is 0 and the written data is invalid.
5. PARAMETERS
5.15 (N) Communication operation parameters
659
Error check items
Error item Error description Inverter operation
The data received by the inverter is different from the
Parity error
specified parity (Pr.334 setting).
The data received by the inverter is different from the stop
Framing error
bit length (Pr.334) setting.
When this error occurs, Pr.334 is
The next data has been sent by the master before the
Overrun error incremented by one.
inverter completes receiving the preceding data.
When this error occurs, the LF signal is
The data length of the message frame is checked, and an output.
Message frame error error is generated if the received data length is less than
4 bytes.
An error is generated if the data in the message frame
CRC check error
does not match the calculation result.
NOTE
• The LF signal can be assigned to an output terminal by setting Pr.190 to Pr.196 (Output terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
MODBUS register
• The following shows the MODBUS registers for system environment variables (read/write), real time monitor items (read),
parameters (read/write), faults history data (read/write), and model information monitor items (read).
• System environment variables
Register Definition Read/write Remarks
40002 Inverter reset Write Any value
40003 Parameter clear Write Set H965A.
40004 All parameter clear Write Set H99AA.
40006 *1 Write Set H5A96.
Parameter clear
40007 *1 Write Set HAA99.
All parameter clear
40009 Inverter status / control input command*2 Read/write Refer to the following.
40010 *3 Read/write Refer to the following.
Operation mode / inverter setting
40014 Running frequency (RAM value) Read/write The display can be changed to the rotations
per minute using Pr.37, Pr.144 and Pr.811.
40015 Running frequency (EEPROM value) Write
(Refer to page 424.)
*1 Settings in the communication parameters are not cleared.
*2 The data is written as a control input command for writing.
The data is read as the inverter status for reading.
*3 The data is written as an operation mode setting for writing.
The data is read as the operation mode status for reading.
660 5. PARAMETERS
5.15 (N) Communication operation parameters
• Inverter status / control input command
Bit
Control input command
Definition
Inverter status
1
0 Stop command RUN (Inverter running)*6
1 Forward rotation command Forward running
2 Reverse rotation command Reverse running 2
3 *4 *6
RH (High-speed operation command) SU (Up to frequency)
*4
4 RM (Middle-speed operation command) OL (Overload warning)*6
*4 The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.180 to Pr.189 (Input terminal
7
function selection) (page 496).
The signals assigned to the input terminals may be valid or invalid in the NET operation mode. (Refer to page 384.)
*5
*6
The Inverter run enable signal is in the initial status for the separated converter type.
The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.190 to Pr.196 (Output terminal
8
function selection) (page 450).
*7 No function is assigned in the initial status for the separated converter type.
• Operation mode / inverter setting
9
Mode Read value Write value
EXT H0000 H0010*8
PU H0001 H0011*8 10
EXT
H0002 —
JOG
PU
H0003 —
JOG
NET H0004 H0014
PU + EXT H0005 —
*8 Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to page 378.
Restrictions in each operation mode conform with the computer link specification.
• Real time monitor
Refer to page 424 for the register numbers and monitor items of the real time monitor.
• Parameters
Pr. Register Name Read/write Remarks
For details on parameter names,
41000 to
0 to 999 refer to the parameter list (page Read/write The parameter number + +41000 is the register number.
41999
162).
Terminal 2 frequency setting bias
C2 (902) 41902 Read/write
(frequency)
Terminal 2 frequency setting bias
42092 Read/write Analog value (%) set to C3 (902)
(analog value)
C3 (902)
Terminal 2 frequency setting bias Analog value (%) of the voltage (current) applied to
43902 Read
(terminal analog value) terminal 2
Terminal 2 frequency setting gain
125 (903) 41903 Read/write
(frequency)
5. PARAMETERS
5.15 (N) Communication operation parameters
661
Pr. Register Name Read/write Remarks
Terminal 2 frequency setting gain
42093 Read/write Analog value (%) set in C4 (903)
(analog value)
C4 (903)
Terminal 2 frequency setting gain Analog value (%) of the voltage (current) applied to
43903 Read
(terminal analog value) terminal 2
Terminal 4 frequency setting bias
C5 (904) 41904 Read/write
(frequency)
Terminal 4 frequency setting bias
42094 Read/write Analog value (%) set in C6 (904)
(analog value)
C6 (904)
Terminal 4 frequency setting bias Analog value (%) of the current (voltage) applied to
43904 Read
(terminal analog value) terminal 4
Terminal 4 frequency setting gain
126 (905) 41905 Read/write
(frequency)
Terminal 4 frequency setting gain
42095 Read/write Analog value (%) set in C7 (905)
(analog value)
C7 (905)
Terminal 4 frequency setting gain Analog value (%) of the current (voltage) applied to
43905 Read
(terminal analog value) terminal 4
Terminal 1 bias frequency
C12 (917) 41917 Read/write
(speed)
42107 Terminal 1 bias (speed) Read/write Analog value (%) set in C13 (917)
C13 (917) Terminal 1 bias (speed)
43917 Read Analog value (%) of voltage applied to terminal 1
(terminal analog value)
Terminal 1 gain frequency
C14 (918) 41918 Read/write
(speed)
42108 Terminal 1 gain (speed) Read/write Analog value (%) set in C15 (918)
C15 (918) Terminal 1 gain (speed)
43918 Read Analog value (%) of voltage applied to terminal 1
(terminal analog value)
Terminal 1 bias command
C16 (919) 41919 Read/write
(torque)
42109 Terminal 1 bias (torque) Read/write Analog value (%) set in C17 (919)
C17 (919) Terminal 1 bias (torque)
43919 Read Analog value (%) of voltage applied to terminal 1
(terminal analog value)
Terminal 1 gain command
C18 (920) 41920 Read/write
(torque)
42110 Terminal 1 gain (torque) Read/write Analog value (%) set in C19 (920)
C19 (920) Terminal 1 gain (torque)
43920 Read Analog value (%) of voltage applied to terminal 1
(terminal analog value)
Motor temperature detection
42115 Read/write
calibration (analog input)
C29 (925) Motor temperature detection
Analog value (%) between terminals TH1 and TH2 of the
43925 calibration (analog input) Read
FR-A8AZ
(terminal analog value)
Terminal 6 bias frequency
C30 (926) 41926 Read/write
(speed)
42116 Terminal 6 bias (speed) Read/write Analog value (%) set in C31 (926)
C31 (926) Terminal 6 bias (speed) Analog value (%) of the voltage applied to terminal 6 of the
43926 Read
(terminal analog value) FR-A8AZ
Terminal 6 gain frequency
C32 (927) 41927 Read/write
(speed)
42117 Terminal 6 gain (speed) Read/write Analog value (%) set in C33 (927)
C33 (927) Terminal 6 gain (speed) Analog value (%) of the voltage applied to terminal 6 of the
43927 Read
(terminal analog value) FR-A8AZ
Terminal 6 bias command
C34 (928) 41928 Read/write
(torque)
42118 Terminal 6 bias (torque) Read/write Analog value (%) set in C35 (928)
C35 (928) Terminal 6 bias (torque) Analog value (%) of the voltage applied to terminal 6 of the
43928 Read
(terminal analog value) FR-A8AZ
Terminal 6 gain command
C36 (929) 41929 Read/write
(torque)
42119 Terminal 6 gain (torque) Read/write Analog value (%) set in C37 (929)
C37 (929) Terminal 6 gain (torque) Analog value (%) of the voltage applied to terminal 6 of the
43929 Read
(terminal analog value) FR-A8AZ
C8 (930) 41930 Current output bias signal Read/write
C9 (930) 42120 Current output bias current Read/write Analog value (%) set in C9 (930)
C10 (931) 41931 Current output gain signal Read/write
662 5. PARAMETERS
5.15 (N) Communication operation parameters
Pr. Register Name Read/write Remarks
C11 (931) 42121 Current output gain current Read/write Analog value (%) set in C11 (931)
Terminal 4 bias command
1
C38 (932) 41932 Read/write
(torque)
42122 Terminal 4 bias (torque) Read/write Analog value (%) set in C39 (932)
C39 (932)
43932
Terminal 4 bias (torque)
(terminal analog value)
Read
Analog value (%) of the current (voltage) applied to
terminal 4
2
Terminal 4 gain command
C40 (933) 41933 Read/write
(torque)
C41 (933)
42123 Terminal 4 gain (torque) Read/write Analog value (%) set in C41 (933) 3
Terminal 4 gain (torque) Analog value (%) of the current (voltage) applied to
43933 Read
(terminal analog value) terminal 4
C42 (934) 41934 PID display bias coefficient Read/write
42124 PID display bias analog value Read/write Analog value (%) set in C43 (934) 4
C43 (934) PID display bias analog value Analog value (%) of the current (voltage) applied to
43934 Read
(terminal analog value) terminal 4
C44 (935) 41935 PID display gain coefficient Read/write
42125 PID display gain analog value Read/write Analog value (%) set in C45 (935) 5
C45 (935) PID display gain analog value Analog value (%) of the current (voltage) applied to
43935 Read
(terminal analog value) terminal 4
1000 to 45000 to
For details on parameter names,
refer to the parameter list (page Read/write The parameter number + 44000 is the register number.
6
1999 45359
162).
• Faults history
Register Definition Read/write Remarks
7
40501 Faults history1 Read/write
40502 Faults history2 Read
Being 2 bytes in length, the data is stored as H00○○.
40503 Faults history3 Read Refer to the lowest 1 byte for the error code. (For 8
40504 Faults history4 Read details on error codes, refer to page 742.)
40505 Faults history5 Read The faults history is batch-cleared by writing to register
40506 Faults history6 Read 40501.
40507 Faults history7 Read
Set any value as data. 9
40508 Faults history8 Read
• Model information monitor
Register Definition Read/write Remarks
10
44001 Model (1st and 2nd characters) Read
44002 Model (3rd and 4th characters) Read
44003 Model (5th and 6th characters) Read
44004 Model (7th and 8th characters) Read The inverter model can be read in ASCII code.
44005 Model (9th and 10th characters) Read "H20" (blank code) is set for blank area.
Example) FR-A840-1 (FM type):
44006 Model (11th and 12th characters) Read
H46, H52, H2D, H41, H38, H34, H30, H2D, H31,
44007 Model (13th and 14th characters) Read H20......H20
44008 Model (15th and 16th characters) Read
44009 Model (17th and 18th characters) Read
44010 Model (19th and 20th characters) Read
44011 Capacity (1st and 2nd characters) Read The capacity in the inverter model can be read in ASCII
44012 Capacity (3rd and 4th characters) Read code.
Data is read in increments of 0.1 kW, and rounds down to
0.01 kW increments.
44013 Capacity (5th and 6th characters) Read "H20" (blank code) is set for blank area.
Example) 0.75K: " 7" (H20, H20, H20, H20, H20, H37)
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
5. PARAMETERS
5.15 (N) Communication operation parameters
663
NOTE
• The communication error count is temporarily stored in the RAM memory. The value is not stored in EEPROM, and so is
cleared to 0 when power is reset and the inverter is reset.
Master Alarm data Alarm data Normal data Alarm data Normal data
Slave Reply data Reply data
Not increased
Communication
error count 0 1 2
(Pr. 343)
NOTE
• The LF signal can be assigned to an output terminal by setting Pr.190 to Pr.196. Changing the terminal assignment may affect
other functions. Set parameters after confirming the function of each terminal.
664 5. PARAMETERS
5.15 (N) Communication operation parameters
• The communication check time by query communication includes a no-data time (3.5 bytes).
This no-data time differs according to the communication speed, so take this no-data time into consideration when setting
the communication check time.
1
Example: RS-485 terminal communication, Pr. 539 = "0.1 to 999.8 s"
Query communication 2
Operation mode External NET
PLC (master)
Query Message1
Data absence time
Query Message2
3
Inverter (slave) (3.5 bytes or more)
Inverter (slave)
PLC (master) Fault 4
Response Message1 Response Message2 (E.SER)
Pr.539
Communication
check counter
5
Check start Time
ALM OFF ON
6
Broadcast communication
Operation mode External NET
7
Query Message1 Query Message2
PLC (master)
Inverter (slave)
Inverter (slave)
8
PLC (master) Data absence time Fault
(3.5 bytes or more) (E.SER)
Pr.539 9
Communication
check counter
Check start Time
ALM OFF ON 10
NOTE
• For the RS-485 terminal communication, the operation at a communication error occurrence depends on the Pr.502 Stop
mode selection at communication error setting. (Refer to page 630.)
Initial
Pr. Name Setting range Description
value
434 Network number (CC-
0 0 to 255 Enter the network number of the inverter.
N110 Link IE)
435 Station number (CC-Link
0 0 to 255 Enter the station number of the inverter.
N111 IE)
541 Frequency command 0 Signed frequency command value
0
N100 sign selection 1 Unsigned frequency command value
5. PARAMETERS
5.15 (N) Communication operation parameters
665
Network number and station number setting (Pr.434, Pr.435)
• Enter the inverter network number in Pr.434 Network number (CC-Link IE).
• The setting range of Pr.434 is "0 to 255", but its active range is "1 to 239". The values out of the active range are invalid
because such values cannot be transmitted to the master station.
• Use Pr.435 Station number (CC-Link IE) to enter the station number of the inverter.
• The setting range of Pr.435 is "0 to 255", but its active range is "1 to 120". The values out of the active range are invalid
because such values cannot be transmitted to the master station.
NOTE
• Use different station numbers for different devices. (If different devices have the same station number, the communication
cannot be performed properly. If an error occurs due to a duplicated number, re-assign the station numbers, then reset the
master station and the inverter power.)
• Station numbers do not have to be consecutive numbers.
• The Pr.434 and Pr.435 settings are applied after an inverter reset or next power-ON.
NOTE
• When Pr.541 = "1" (with sign)
- When EEPROM write is specified by turning ON of RY22, write mode error (error code H01) will occur.
- When both RY21 and RY22 are turned ON, RY21 has precedence.
- When power is turned ON (inverter reset), the initial setting status of the sign bit is "positive" and the set frequency is 0 Hz.
(The motor does not operate at the frequency set before turning OFF the power (inverter reset).)
- When set frequency is written with the instruction code of HED or HEE, the sign of the frequency command is not changed.
Parameters referred to
Pr.37 Speed display, Pr.144 Speed setting switchover, Pr.811 Set resolution switchoverpage 422
666 5. PARAMETERS
5.15 (N) Communication operation parameters
Initial
Pr. Name Setting range Description
value 1
547*1 USB communication
0 0 to 31 Specify the inverter station number.
N040 station number
USB communication is possible, however the inverter output is shut
0
off (E.USB) when the mode changes to the PU operation mode. 2
548*1 USB communication
9999
Set the communication check time interval.
N041 check time interval 0.1 to 999.8 s If a no-communication state persists for longer than the permissible
time, the inverter output is shut off (E.USB).
9999 No communication check 3
*1 The changed value is applied after the next power-ON or inverter reset.
• At the initial setting (Pr.551 PU mode operation command source selection = "9999"), communication with FR
10
Configurator2 can be made in the PU operation mode simply by connecting a USB cable. To fix the command source to
the USB connector in the PU operation mode, set "3" in Pr.551.
• Parameter setting and monitoring can be performed by using FR Configurator2. For details, refer to the Instruction Manual
of FR Configurator2.
Parameters referred to
Pr.551 PU mode operation command source selectionpage 380
5. PARAMETERS
5.15 (N) Communication operation parameters
667
Automatic connection system configuration
Four-wire multidrop
GOT2000
Terminating resistor
NOTE
• If the automatic recognition cannot be performed, initial setting in Pr.999 is required.
• For connection to a device other than the GOT2000 series, initial setting in Pr.999 is required.
• For details, refer to the GOT2000 Series Connection Manual (Mitsubishi Product).
Parameters referred to
Pr.999 Automatic parameter settingpage 333
5.15.10 Backup/restore
The GOT can be used for backing up inverter parameters and the data used in the PLC function of inverter.
The backup data stored in the GOT can be used to restore the data in the inverter.
Initial
Pr. Name Setting range Description
value
434 Network number (CC-Link
0 0 to 255 Enter the network number of the inverter.
N110*1 IE)
435
Station number (CC-Link IE) 0 0 to 255 Enter the station number of the inverter.
N111*1
*1 The setting is available in the inverter on which the FR-A8NCE is installed or when the FR-A800-GF inverter is used.
668 5. PARAMETERS
5.15 (N) Communication operation parameters
Ethernet CC-Link IE Field Network
1
Backup
2
Restore
MELSEC iQ-R
GOT2000 3
NOTE
• The backup/restore function is enabled only when the inverter is connected to a master station programmable controller. 6
• For the details of the connected devices, refer to the GOT2000 Series User's Manual (Monitor).
Backup/restore operation 10
• The GOT backs up all applicable data in all the inverters that can be identified with the network numbers and station
numbers in the controller list file.
• The GOT restores all relevant data of the inverters selected based on the network numbers and station numbers using the
backup data.
• The backup/restore cannot be performed in the following cases.
Operation Inverter status
Backup During an inverter reset
A password is registered or password protection is enabled (Pr.297 ≠ "9999").
During parameter copy using an operation panel or USB memory device (during writing to the inverter)
During restore
While password protection is enabled for files used in the PLC function (read protection)
While PLC function project data is written to, read from, or verified against a USB memory device
Restore During an inverter reset
During running
During auto tuning
A password is registered or password protection is enabled (Pr.297 ≠ "9999").
While parameter write is disabled (Pr.77 = "1")
During parameter copy using an operation panel or USB memory device (during writing to / reading from /
verification against the inverter)
During backup operation
During the RUN status of the PLC function
While password protection is enabled for files used in the PLC function (write protection)
While PLC function project data is written to, read from, or verified against a USB memory device
• On the operation panel, "RD" is displayed during backup, and "WR" is displayed during restore.
5. PARAMETERS
5.15 (N) Communication operation parameters
669
NOTE
• To enable the restore operation, Pr.434 Network number (CC-Link IE) and Pr.435 Station number (CC-Link IE) must be
set.
• Backup is performed for parameters for which parameter copy can be performed.
• For the details of backup/restore function, refer to the GOT2000 Series User's Manual (Monitor).
670 5. PARAMETERS
5.15 (N) Communication operation parameters
5.16 (G) Control parameters 1
5. PARAMETERS
5.16 (G) Control parameters
671
5.16.1 Manual torque boost
V/F
Voltage drop in the low-frequency range can be compensated, improving reduction of the motor torque in the low-speed range.
• Motor torque in the low-frequency range can be adjusted according to the load, increasing the motor torque at the start up.
• By using the RT signal or X9 signal, it is possible to switch between 3 types of torque boost.
100%
Output
voltage
Pr.0 Setting
Pr.46
Pr.112 range
0 Output Base
frequency frequency
(Hz)
NOTE
• The RT (X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid.
(Refer to page 500.)
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Set a larger value when the distance between the inverter and the motor is long or when there is not enough motor torque in
the low-speed range. It may cause overcurrent trip when it is set too large.
• Setting for Pr.0, Pr.46, and Pr.112 becomes enabled only when the V/F control is selected.
• When the initial value is set in Pr.0, the Pr.0 setting is automatically changed by changing the Pr.71 Applied motor or Pr.81
Number of motor poles setting. (Refer to page 505.)
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
672 5. PARAMETERS
5.16 (G) Control parameters
Parameters referred to
Pr.3 Base frequency, Pr.19 Base frequency voltagepage 673
Pr.71 Applied motorpage 505
Pr.178 to Pr.189 (Input terminal function selection)page 496
1
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
Initial value
3
Pr. Name Setting range Description
FM CA
3 Set the frequency at the rated motor torque. (50/60
Base frequency 60 Hz 50 Hz 0 to 590 Hz
G001 Hz) 4
0 to 1000 V Set the base voltage.
19
Base frequency voltage 9999 8888 8888 95% of the power supply voltage
G002
9999 Same as the power supply voltage
47 Second V/F (base 0 to 590 Hz Sets the base frequency when the RL signal is ON. 5
9999
G011 frequency) 9999 Second V/F disabled
113 Third V/F (base 0 to 590 Hz Set the base frequency when the X9 signal is ON.
9999
G021 frequency) 9999 Third V/F disabled 6
Starting frequency setting (Pr.3)
• When operating a standard motor, generally set the rated frequency of the motor in Pr.3 Base frequency. When the motor
operation require switching to the commercial power supply, set the power supply frequency in Pr.3. 7
• When the frequency described on the motor rating plate is "50 Hz" only, make sure to set to 50 Hz. When it is set to 60 Hz,
the voltage will drop too much, causing insufficient torque. As a result, the inverter output may be shut off due to overload.
A caution is required especially in case of Pr.14 Load pattern selection = "1" (variable torque load). 8
• When using the Mitsubishi Electric constant torque motor, set Pr.3 to 60 Hz.
9
Output voltage (V)
Pr.19
Output frequency 10
(Hz)
Pr.3
Pr.47
Pr.113
NOTE
• The RT (X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid.
(Refer to page 500.)
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
5. PARAMETERS
5.16 (G) Control parameters
673
• Pr.19 can be used in following cases.
(a) When regenerative driving (continuous regeneration, etc.) is performed frequently
Output voltage will get higher than the specification during the regenerative driving, which may cause overcurrent trip
(E.OC[]) by the increase in motor current.
(b) When the fluctuation of power supply voltage is high
When the power supply voltage exceeds the rated voltage of the motor, fluctuation of rotation speed or overheating
of motor may occur due to excessive torque or increase in motor current.
• When operating a Vector control dedicated motor (SF-V5RU, SF-V5RU1, SF-V5RU3, SF-V5RU4, SF-VR) with V/F control,
perform following settings.
NOTE
• When the operation becomes not possible due to failure in encoder, etc., under Vector control, set Pr.80 Motor capacity or
Pr.81 Number of motor poles = "9999" to perform V/F control.
• When the Advanced magnetic flux vector control, Real sensorless vector control, Vector control, or PM sensorless vector
control is selected, Pr.3, Pr.47, Pr.113, and Pr.19 will become disabled, and Pr.83 and Pr.84 will become enabled.
However, S-pattern curve with Pr.29 Acceleration/deceleration pattern selection = "1" (S-pattern acceleration/deceleration
A) will make Pr.3 or Pr.47 and Pr.113 enabled. (S-pattern curve under PM sensorless vector control is the rated frequency of
the motor.)
• When Pr.71 Applied motor = "2" (adjustable 5 points V/F), setting for Pr.47 and Pr.113 will become disabled. Also, Pr.19
cannot be set to "8888" or "9999".
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.14 Load pattern selectionpage 674
Pr.29 Acceleration/deceleration pattern selectionpage 354
Pr.71 Applied motorpage 505
Pr.83 Rated motor voltage, Pr.84 Rated motor frequencypage 509
Pr.178 to Pr.189 (Input terminal function selection)page 496
Optimal output characteristics (V/F characteristics) for application or load characteristics can be selected.
674 5. PARAMETERS
5.16 (G) Control parameters
Setting
Pr. Name Initial value Description
range 1
0 For constant-torque load
1 For variable-torque load
For constant-torque lift
2
(boost at reverse rotation: 0%) 2
For constant-torque lift
14 3
Load pattern selection 0 (boost at forward rotation: 0%)
G003
RT signal ON…for constant-torque load
4
RT signal OFF...for constant-torque lift, boost at reverse rotation 0% 3
RT signal ON…for constant-torque load
5
RT signal OFF...for constant-torque lift, boost at forward rotation 0%
12 to 15 Excitation current low-speed scaling factor (Refer to page 677.)
4
Application for constant-torque load (Pr.14 =“0”, initial value)
• The output voltage will change linearly against the output frequency at the base frequency or lower.
• Set this parameter when driving a load that has constant load torque even when the rotation speed is changed, such as 5
conveyor, dolly, or roll drive.
6
Pr.14 = 0
100%
Output voltage
Select for constant-torque load (setting value "0") even for fan and pump in following cases.
• When accelerating a blower with large moment of inertia (J) in a short period of time.
9
• When it is a constant-torque load such as rotary pump or gear pump.
• When the load torque increases in low speed such as screw pump.
10
Application for variable-torque load (Pr.14 =“1”)
• The output voltage will change in square curve against the output frequency at the base frequency or lower. (1.75th-power
curve for the FR-A820-01870(37K) or higher, and the FR-A840-00930(37K) or higher)
• Set this parameter when driving a load with load torque change proportionally against the square of the rotation speed,
such as a fan or pump.
Pr.14 = 1
100%
Output voltage
5. PARAMETERS
5.16 (G) Control parameters
675
• Set "3" for an elevated load that is in the driving mode during reverse rotation and in the regenerative load mode during
forward rotation according to the load weight, e.g. counterweight system.
Pr.14 = 2 Pr.14 = 3
For vertical lift loads For vertical lift loads
At forward rotation boost...Pr.0 setting At forward rotation boost...0%
At reverse rotation boost...0% At reverse rotation boost...Pr.0 setting
100% 100%
Forward Reverse
voltage
voltage
Output
Output
rotation rotation
Reverse Forward
Pr.0 rotation Pr.0 rotation
Base frequency Base frequency
Output frequency (Hz) Output frequency (Hz)
NOTE
• When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in Pr.19 Base frequency
voltage to prevent trip due to current at regeneration.
NOTE
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to 189 may affect other functions. Set parameters after confirming the function
of each terminal.
• Pr.14 will become enabled under V/F control.
• Other second functions will become enabled when the RT signal is ON.
Parameters referred to
Pr.0 Torque boostpage 672
Pr.3 Base frequencypage 673
Pr.178 to Pr.189 (Input terminal function selection)page 496
676 5. PARAMETERS
5.16 (G) Control parameters
5.16.4 Excitation current low-speed scaling factor
Magnetic flux Sensorless 1
Under Advanced magnetic flux vector control or Real sensorless vector control, the excitation current scaling factor in the low-
speed range can be adjusted.
2
Pr. Name Initial value Setting range Description
Excitation current low-speed scaling factor: Pr.86
0 to 5
Refer to page 674 for details of the operation under V/F control.
12*1
Forward rotation excitation current low-speed scaling factor: Pr.86 3
Reverse rotation excitation current low-speed scaling factor: Pr.617
Forward rotation excitation current low-speed scaling factor: Pr.617
14 13*1 Reverse rotation excitation current low-speed scaling factor: Pr.86
G003
Load pattern selection 0
Forward rotation excitation current low-speed scaling factor: Pr.86 4
14*1 Reverse rotation excitation current low-speed scaling factor: Pr.617
(X17-OFF), Pr.86 (X17 signal-ON)
Forward rotation excitation current low-speed scaling factor: Pr.617
15*1 (X17-OFF), Pr.86 (X17 signal-ON) 5
Reverse rotation excitation current low-speed scaling factor: Pr.86
0 to 400 Hz Set the frequency at which increased excitation is started.
85 Excitation current break SF-PR/SF-HR/SF-HRCA motor: The predetermined frequency is
G201 point
9999
9999 applied. 6
Motor other than the above: 10 Hz is applied.
0 to 300% Set an excitation current scaling factor at 0 Hz.
86 Excitation current low
G202 speed scaling factor
9999
9999
SF-PR/SF-HR/SF-HRCA motor: The predetermined scaling factor
is applied. 7
Motor other than the above: 130% is applied.
Set an excitation current scaling factor when different excitation
0 to 300%
617
Reverse rotation excitation
current low-speed scaling 9999
current scaling factors are used for forward and reverse rotation.
SF-PR/SF-HR/SF-HRCA motor: The predetermined scaling factor
8
G080
factor 9999 is applied.
Motor other than the above: 130% is applied.
• Under Advanced magnetic flux vector control or Real sensorless vector control, excitation current in the low-speed range
can be increased to improve torque. When Pr.14 = "12 to 15", the excitation current scaling factor can be switched for the
forward/reverse rotation.
• Increased excitation is applied when the output frequency is equal to or lower than the setting in Pr.85 Excitation current
break point. The excitation current scaling factor at 0 Hz is set in Pr.86 Excitation current low speed scaling factor.
Use Pr.565 Second motor excitation current break point and Pr.566 Second motor excitation current low-speed
scaling factor for the setting for using the second motor (RT signal-ON).
Excitation current scaling factor
Pr.86
(Pr.566)
100%
0
Pr.85 Output frequency
(Pr.565)
• When Pr.14 = "14 or 15" and the X17 signal is turned ON, the excitation current scaling factor is switched from the value
set in Pr.617 to the value set in Pr.86.
5. PARAMETERS
5.16 (G) Control parameters
677
• An excitation current low-speed scaling factor set in the parameter shown in the table is used according to the Pr.14 setting
and other conditions.
During forward rotation During reverse rotation
Pr.14 setting X17 signal
RT signal OFF RT signal ON RT signal OFF RT signal ON
0 to 5 — Pr.86 Pr.566 Pr.86 Pr.566
12 — Pr.86 Pr.566 Pr.617 Pr.617
13 — Pr.617 Pr.617 Pr.86 Pr.566
OFF Pr.86 Pr.566 Pr.617 Pr.617
14
ON Pr.86 Pr.566 Pr.86 Pr.566
OFF Pr.617 Pr.617 Pr.86 Pr.566
15
ON Pr.86 Pr.566 Pr.86 Pr.566
• When the SF-PR/SF-HR/SF-HRCA motor is used (Pr.71 = "40, 43, 44, 50, 53, 54, 70, 73, or 74") and "9999" is set in Pr.85/
Pr.86, the predetermined setting in the following table is applied.
The inverter will automatically perform energy saving operation without setting detailed parameters.
This control method is suitable for applications such as fans and pumps.
678 5. PARAMETERS
5.16 (G) Control parameters
NOTE
• In the energy saving operation mode, an energy saving effect is not expected for applications with high load torque or with the 1
equipment with frequent acceleration and deceleration.
• In the Optimum excitation control mode, an energy saving effect is not expected when the motor capacity is extremely small
compared with the inverter capacity or when multiple motors are connected to a single inverter.
• When the energy saving operation mode or Optimum excitation control mode is selected, the deceleration time may become 2
longer than the setting value. Also, it may cause overvoltage more often compared to constant-torque load characteristics, so
set the deceleration time longer.
• When the motor becomes unstable during the acceleration, set the acceleration time longer.
• Output current may increase slightly with the energy saving operation mode or the Optimum excitation control mode since the
3
output voltage is controlled.
4
5.16.6 Adjustable 5 points V/F
V/F
By setting a desired V/F characteristic from the start up to the base frequency or base voltage with the V/F control (frequency
5
voltage/frequency), a dedicated V/F pattern can be generated.
The optimal V/F pattern matching the torque characteristics of the facility can be set.
6
Pr. Name Initial value Setting range Description
Standard motor (such as SF-JR)
71 2
C100
Applied motor 0
Others
Adjustable 5 points V/F
Refer to page 505.
7
100
V/F1 (first frequency) 9999 0 to 590 Hz, 9999
G040
101 V/F1 (first frequency
0V 0 to 1000 V 8
G041 voltage)
102 V/F2 (second
9999 0 to 590 Hz, 9999
G042 frequency)
103 V/F2 (second frequency
0V 0 to 1000 V
9
G043 voltage)
104
V/F3 (third frequency) 9999 0 to 590 Hz, 9999
G044 Set each point of the V/F pattern (frequency, voltage).
105 V/F3 (third frequency
0V 0 to 1000 V
9999: Do not set V/F. 10
G045 voltage)
106
V/F4 (fourth frequency) 9999 0 to 590 Hz, 9999
G046
107 V/F4 (fourth frequency
0V 0 to 1000 V
G047 voltage)
108
V/F5 (fifth frequency) 9999 0 to 590 Hz, 9999
G048
109 V/F5 (fifth frequency
0V 0 to 1000 V
G049 voltage)
• By setting the V/F1 (first frequency voltage/first frequency) to V/F5 parameters in advance, a desired V/F characteristic
can be obtained.
• For an example, with the equipment with large static friction factor and small dynamic friction factor, large torque is required
only at the start up, so a V/F pattern that will raise the voltage only at the low-speed range is set.
• Setting procedure
5. PARAMETERS
5.16 (G) Control parameters
679
3. Set frequency and voltage to be set in Pr.100 to Pr.109.
Voltage
Base
frequency
voltage
Pr.19 V/F5
V/F4
Torque V/F3
boost V/F1
Pr.0 V/F2 Frequency
0 Base
V/F Characteristic frequency
Pr.3
CAUTION
• Make sure to set the parameters correctly according to the motor used. Incorrect setting may cause the motor to overheat
and burn.
NOTE
• The adjustable 5 points V/F is enabled under V/F control.
• When Pr.19 Base frequency voltage = "8888 or 9999", setting of Pr.71 = "2" is not available. To set "2" in Pr.71, set the rated
motor voltage in Pr.19.
• A write disable error " " is generated when the same frequency value is used for multiple points.
• Set frequency or voltage for each point in Pr.100 to Pr.109 within the range of Pr.3 Base frequency or Pr.19 Base frequency
voltage.
• When Pr.71 = "2", Pr.47 Second V/F (base frequency) and Pr.113 Third V/F (base frequency) are not available.
• When Pr.71 = "2", the inverter calculates the characteristic of the electronic thermal relay for a standard motor.
• By simultaneously using Pr.60 Energy saving control selection and the adjustable 5 points V/F, further energy saving effect
is expected.
• The Pr.0 Torque boost and Pr.12 DC injection brake operation voltage settings are automatically changed according to
the Pr.71 setting. (Refer to page 508.)
Parameters referred to
Pr.0 Torque boostpage 672
Pr.3 Base frequency, Pr.19 Base frequency voltagepage 673
Pr.12 DC injection brake operation voltagepage 681
Pr.47 Second V/F (base frequency), Pr.113 Third V/F (base frequency)page 679
Pr.60 Energy saving control selectionpage 678
Pr.71 Applied motor, Pr.450 Second applied motorpage 505
• As compared to our conventional SF-JR motor, the slip amount is small for the high-performance energy-saving SF-PR
motor. When replacing the SF-JR to the SF-PR, the slip amount is reduced and the rotations per minute increases.
Therefore, when the SF-PR is used with the same frequency setting as that of the SF-JR, power consumption may
increase as compared to the SF-JR.
• By setting the slip amount adjustment mode, the frequency command can be adjusted to keep the rotations per minute of
the SF-PR equivalent to those of the SF-JR for power consumption reduction.
680 5. PARAMETERS
5.16 (G) Control parameters
• Use Pr.674 SF-PR slip amount adjustment gain to fine-tune the rotations per minute. To reduce the rotations per minute
(to increase the compensation frequency), set a larger value in Pr.674. To increase the rotations per minute (to reduce the
compensation frequency), set a smaller value in Pr.674. (Lower rotations per minute reduce the power consumption, and
1
higher rotations per minute increase the power consumption.)
NOTE 2
• The slip amount adjustment is not available in the following conditions.
During acceleration/deceleration, during DC injection brake operation, during PID control, during orientation control, during
encoder feedback control, during stall prevention operation, during regeneration avoidance operation, during traverse
operation, and while the slip compensation is valid (Pr.245). 3
• The slip amount adjustment is not available when the applicable motor capacity of the inverter is not compatible with the SF-
PR. (For the details of applicable motor capacity, refer to page 790.)
4
5.16.8 DC injection brake, zero speed control, and servo
lock 5
• Adjust the braking torque and timing to stop the motor using the DC injection brake.
Zero speed control is also available under Real sensorless vector control, and zero speed control and servo lock are
selectable under Vector control or PM sensorless vector control.
6
When the DC injection brake operation is used, DC voltage is applied to the motor to prevent rotation of the motor shaft,
and when the zero speed control is used, Vector control is performed to keep 0 r/min. Either way, when a motor shaft is
rotated by external force, it does not go back to the original position.
7
When the servo lock control is used, the position of the motor shaft is held. When a motor shaft is rotated by external force,
it goes back to the original position.
• Select the magnetic flux decay output shutoff function to decay the magnetic flux before shutting off the output at a stop.
8
Pr. Name Initial value Setting range Description
5. PARAMETERS
5.16 (G) Control parameters
681
• The DC injection brake operation frequency depends on the stopping method.
Stopping method Parameter setting DC injection brake operation frequency
0.5 Hz or higher in Pr.10 Pr.10 setting
Press the STOP key on the operation panel. Lower than 0.5 Hz in Pr.10, and 0.5 Hz or
0.5 Hz
Turn OFF the STF/STR signal. higher in Pr.13
Lower than 0.5 Hz in both Pr.10 and Pr.13 Pr.10 or Pr.13 setting, whichever larger
Set frequency to 0 Hz — Pr.13 setting or 0.5 Hz, whichever smaller
• The DC injection brake operation frequency will be fixed to 0 Hz under PM sensorless vector control (low-speed range
high-torque mode disabled).
(Hz)
Output
frequency
Pr. 10 Operation
frequency
Time
DC injection Pr.12
brake Operation
voltage voltage
Time
NOTE
• When executing pre-excitation (zero speed control) under Real sensorless vector control, set Pr.10 DC injection brake
operation frequency to 0.5 Hz or lower since it may cause motor vibration, etc., at the time of deceleration stop.
• The initial value of Pr.10 will automatically switch to 0.5 Hz under Vector control.
(Hz)
Time
Pr.12
DC injection
brake voltage Time
STF ON
NOTE
• Under Real sensorless vector control, when the X13 signal turns ON while Pr.11 = "8888", the zero speed control is activated
regardless of the Pr.850 Brake operation selection setting.
• Under Vector control or PM sensorless vector control, zero speed control or servo lock will operate depending of the setting
of Pr.802.
• The X13 signal is disabled during PM sensorless vector control.
682 5. PARAMETERS
5.16 (G) Control parameters
Setting of operation voltage (torque) (Pr.12)
• Set the percentage against the power supply voltage in Pr.12 DC injection brake operation voltage. (The setting is not 1
used for zero speed control or servo lock.)
• The DC injection brake operation is not available when the setting of Pr.12 is 0%. (The motor will coast to stop.)
NOTE 2
• When the setting of Pr.12 is the initial value, the setting corresponding to the motor is set according to the Pr.71 Applied motor
setting. (Refer to page 508.) However, when an energy saving motor (SF-HR or SF-HRCA) is used, change the Pr.12 setting
as shown below. 3
Pr.12
Inverter
setting
FR-A820-00250(3.7K) or lower
FR-A840-00126(3.7K) or lower
4% 4
FR-A820-00340(5.5K), FR-A820-00490(7.5K)
3%
FR-A840-00170(5.5K), FR-A840-00250(7.5K)
FR-A820-00630(11K) to FR-A820-01250(22K), FR-A820-01870(37K) or higher
FR-A840-00310(11K) to FR-A840-00620(22K), FR-A840-00930(37K) or higher
2% 5
FR-A820-01540(30K)
1.5%
FR-A840-00770(30K)
• Even if the setting value of Pr.12 is made larger, braking torque will be limited so the output current will be within the rated 6
current of the inverter.
Magnetic flux decay output shutoff and the Magnetic flux decay output
shutoff signal (X74 signal, Pr.850 = "2")
• Frequent starts/stops (inching) under Real sensorless vector control may cause an inverter failure or create a difference
in operation with the motor. The reason is that some magnetic flux is left in the motor at shutoff of the inverter output. If this
is the case, set Pr.850 = "2" (magnetic flux decay output shutoff) or turn ON the Magnetic flux decay output shutoff (X74)
signal to decay the magnetic flux at a stop, and then shut off the output.
• While Pr.850 = "2", deceleration starts at turning OFF of the start command, and the magnetic flux decay output shutoff is
activated when the estimated speed becomes lower than Pr.10 DC injection brake operation frequency.
• While the brake sequence function is active, the magnetic flux decay output shutoff is activated when the running frequency
drops to 0.5 Hz or Pr.13 Starting frequency, whichever is smaller.
5. PARAMETERS
5.16 (G) Control parameters
683
• Inverter output voltage shutoff timing when Pr.850 = "2"
• Tuning ON the Magnetic flux decay output shutoff (X74) signal starts the magnetic flux decay output shutoff regardless of
the Pr.850 setting. For the X74 signal, set "74" in any of Pr.178 to 189 (Input terminal function selection) to assign the
function.
• Inverter output shutoff timing with X74 signal
RUN ON RUN ON
684 5. PARAMETERS
5.16 (G) Control parameters
NOTE
• When operating under controls other than Real sensorless vector control, the inverter will immediately shutoff the output when 1
the X74 signal is turned ON.
• Even under Real sensorless vector control, the inverter will immediately shutoff the output when the X74 signal is turned ON
during the automatic restart after instantaneous power failure and online auto tuning during the start up.
• If another output-shutoff trigger (inverter fault, turn-ON of the MRS signal, etc.) occurs during the magnetic flux decay 2
operation, the magnetic flux decay operation is terminated, and the output is shut off immediately.
• Unlike the MRS signal, voltage is output during the magnetic flux decay output shutoff operation, so take caution on electric
shocks.
• When the release timing of the mechanical brake is too fast, the motor shaft may be rotated by dropping or external force.
3
When the release timing is too late, the overcurrent prevention operation, stall prevention operation, or electronic thermal O/
L relay function may be activated. Perform release of the mechanical brake matching the equipment using the Output
frequency detection (FU) signal or Output current detection (Y12) signal. 4
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
5
Braking operation selection under Vector control or PM sensorless
vector control (Pr.802, Pr.1299)
• UsePr.802 Pre-excitation selection to select the braking operation when the pre-excitation is performed from either zero
6
speed control or servo lock.
• Turning ON the RT signal enables the second pre-excitation selection (when Pr.450 ≠ "9999").
7
Pr.802
Pre-
(Pr.1299) Description
excitation
setting
Even under a load, the inverter does not rotate the motor and holds 0 r/min. However, it will not return to 8
0 Zero speed its original position when the shaft moves due to external force.
(initial value) control This setting is invalid during position control. The inverter operates according to this setting only during
speed control.
Even under a load, the inverter holds the position of the motor shaft. When the shaft moves due to external 9
force, it will return to its original position after the external force is removed.
1 Servo lock
To perform the position control, this loop gain can be adjusted using Pr.422 Position control gain
(Pr.1298 Second position control gain).
• The relation between the DC injection brake operation and pre-excitation operation is as follows.
10
Control Pr.802 X13-ON
Control method Pr.850 Deceleration stop LX-ON
mode (Pr.1299) (Pr.11 = "8888")
V/F control — — — DC injection brake — DC injection brake
Advanced magnetic flux vector
— — — DC injection brake — DC injection brake
control
— 0 DC injection brake
Zero speed Zero speed
— 1 Zero speed
Speed
Magnetic flux decay
— 2 Zero speed Zero speed
output shutoff
Real sensorless vector control
— 0 DC injection brake
Zero speed Zero speed
— 1 Zero speed
Torque
Magnetic flux decay
— 2 Zero speed Zero speed
output shutoff
0 — Zero speed Zero speed Zero speed
Speed
1 — Servo lock Servo lock Servo lock
Vector control
Torque — — Zero speed Zero speed Zero speed
Position — — — Servo lock —
PM sensorless vector control,
low-speed range high-torque Speed — — DC injection brake — —
mode disabled
PM sensorless vector control, 0 Zero speed Zero speed
Speed — —
low-speed range high-torque 1 Servo lock Servo lock
mode enabled Position — — — Servo lock —
5. PARAMETERS
5.16 (G) Control parameters
685
Pre-excitation signal (LX signal)
• When the Pre-excitation/servo ON (LX) signal is turned ON while the motor stops under Real sensorless vector control,
Vector control, or PM sensorless vector control, pre-excitation (zero speed control / servo lock) starts.
• To input the LX signal, set "23" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
When Pr. 850 = 1
Output frequency
Pr. 10
Operation
frequency
(Hz) Time
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control) may
rotate a motor at a low speed even though a start command (STF or STR) is not input. The inverter at a start command ON
may also rotate the motor at a low speed even though a speed limit value is set to zero It must be confirmed that the motor
running will not cause any safety problem before performing pre-excitation.
• Note that during the pre-excitation operation, a voltage is applied to the motor even with the FWD/REV indicator OFF on the
operation panel.
• When offline auto tuning (Pr.96 Auto tuning setting/status = "1, 11, or 101") is performed during pre-excitation operation,
pre-excitation is disabled.
CAUTION
• During the orientation operation, do not set "0 or 8888" in Pr.11 and do not set "0" in Pr.12. The motor may not stop
properly.
• Install a mechanical brake to make an emergency stop or to stay stopped for a long time.
Wait until the machine stops completely, and fix the motor with a mechanical brake, then turn the LX signal (pre-
excitation) OFF.
Parameters referred to
Pr.13 Starting frequencypage 363, page 364
Pr.71 Applied motorpage 505
Pr.80 Motor capacitypage 509
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.422 Position control gain, Pr.1298 Second position control gainpage 312
Setting
Pr. Name Initial value Description
range
522 0 to 590 Hz Set the frequency to start coasting to a stop (output shutoff).
Output stop frequency 9999
G105 9999 No function
• When both of the frequency setting signal and output frequency fall to the frequency set in Pr.522 or lower, the inverter
stops the output and the motor coasts to a stop.
• The motor re-starts when the frequency setting signal exceeds Pr.522 + 2 Hz and is accelerated at the Pr.13 Starting
frequency (0.01 Hz under PM sensorless vector control).
686 5. PARAMETERS
5.16 (G) Control parameters
Example of when target frequency>Pr.522+2Hz, and start signal is ON/OFF
Output frequency
1
Target frequency
(fixed)
Pr.522+2Hz
2
Pr.522
Pr.13
Time
3
Inverter output shutoff
STF
RUN
4
Example of: target frequency = analog input command, start signal always ON
Analog input command 5
Pr.522+2Hz
Pr.522
6
Time
Output frequency
2 3 3
7
Pr.522+2Hz
Pr.522
1 1
8
Pr.13
NOTE
• When the output stop function is enabled (Pr.522 ≠ "9999"), the DC injunction brake (zero speed control / servo lock) operation
is disabled and the motor coasts to stop when the output frequency drops to the Pr.522 setting or lower.
• The motor starts acceleration again atPr.13 Starting frequency (0.01 Hz under PM sensorless vector control) when the
command value exceeds Pr.522 + 2 Hz again if the start signal remains ON while the motor is coasting after the frequency
drops to the Pr.522 setting or lower. Re-acceleration during coasting may cause an output shutoff of the inverter depending
on the parameter setting. (Activation of the restart function is recommended especially for a PM motor.)
• The output stop frequency function is disabled during PID control, JOG operation, power failure stop, traverse function
operation, offline auto tuning, orientation control, position control, torque control, or stop-on contact control.
• The output stop function does not operate during reverse rotation deceleration. However, when the frequency setting signal
and output frequency fall to Pr.522 or lower, the inverter output is shut off.
• During the output stop due to the output stop function (when forward/reverse command is given, but frequency command is
not given), the FWD/REV LED indicator on the operation panel blinks fast. (When the frequency command is not given even
if the forward/reverse command is given.)
CAUTION
• A PM motor is a motor with interior permanent magnets. High voltage is generated at motor terminals while the motor is
running.
Do not touch motor terminals and other parts until the motor stops to prevent an electric shock.
5. PARAMETERS
5.16 (G) Control parameters
687
Parameters referred to
Pr.10 DC injection brake operation frequency, Pr.11 DC injection brake operation time, Pr.12 DC injection brake operation voltagepage 681
Pr.13 Starting frequencypage 363, page 364
Description
Pr. Name Initial value Setting range
Start signal (STF/STR)*1 Stop operation
The motor coasts to a stop after a
STF signal: Forward rotation start
0 to 100 s lapse of the setting time when the
STR signal: Reverse rotation start
start signal is turned OFF.
The motor coasts to a stop after a
STF signal: Start signal
lapse of the (Pr.250 - 1000)
1000 to 1100 s STR signal: Forward/reverse rotation
250 Stop seconds when the start signal is
9999 signal
G106 selection turned OFF.
STF signal: Forward rotation start
9999
STR signal: Reverse rotation start
The motor is decelerated to a stop
STF signal: Start signal
when the start signal is turned OFF.
8888 STR signal: Forward/reverse rotation
signal
*1 For the start signal selection, refer to page 502.
Deceleration starts
Output frequency
DC brake
Time
Start
ON OFF
signal
RUN
signal ON OFF
Time
688 5. PARAMETERS
5.16 (G) Control parameters
NOTE
• The stop selection setting is disabled when following functions are operating. 1
Position control (Pr.419 = "0")
Power failure stop function (Pr.261)
PU stop (Pr.75)
Deceleration stop due to fault definition (Pr.875) 2
Deceleration stop due to communication error (Pr.502)
Offline auto tuning (with motor rotation)
• When Pr.250 ≠ "9999 or 8888", acceleration/deceleration is performed in accordance to the frequency command until the 3
output is shut off by turning OFF the start signal.
• When the restart signal is turned ON during the motor coasting, the operation is resumed from Pr.13 Starting frequency.
• Even with the setting of coasting to a stop, when the LX signal is turned ON, the motor does not coast but zero speed control
or servo lock is applied.
4
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 349
5
Pr.13 Starting frequencypage 363, page 364
Pr.75 Reset selection/disconnected PU detection/PU stop selectionpage 320
Pr.261 Power failure stop selectionpage 610
Pr.419 Position command source selectionpage 284
Pr.502 Stop mode selection at communication errorpage 630
6
Pr.875 Fault definitionpage 401
Initial
Pr. Name Setting range Description
value
0 to 2, 10, 11,
20, 21, 100 to
102, 110, 111,
120, 121*1
30 Regenerative function 0*1*3, 2, 10, 11, 102, Set the applied regeneration unit, the terminal used for power supply, and
E300 selection 10*2 whether to reset the inverter when the power is supplied to the main circuit.
110, 111*2
0, 2, 10, 20,
100, 102, 110,
120*3
70 Special regenerative
0% 0 to 100% Set the %ED of the built-in brake transistor operation.
G107*4 brake duty
599 X10 terminal input 0*1*3, 0 Normally open input
T721 selection 1*2 1 Normally closed input (NC contact input specification)
*1 The initial value or setting range for the standard model.
*2 The initial value or setting range for the separated converter type.
*3 The initial value or setting range for the IP55 compatible model.
*4 The setting is available for the standard model.
5. PARAMETERS
5.16 (G) Control parameters
689
Details of the setting value
• FR-A820-03160(55K) or lower, FR-A840-01800(55K) or lower
Power supply
Pr.30 Pr.70
Regeneration unit terminals of Remarks
setting*4 setting
inverter
0 (initial The regenerative brake duty will be as follows.
R, S, T
Built-in brake*3, value), 100 • FR-A820-00046(0.4K) to 00250(3.7K): 3%
brake unit P, N 10, 110 • FR-A820-00340(5.5K), 00490(7.5K): 2%
—
(FR-BU2 (GZG/GRZG/ • FR-A840-00023(0.4K) to 00250(7.5K): 2%
FR-BR), FR-BU, BU) R, S, T/P, N 20, 120 • Other than above: 0% (without the built-in brake
resistor)
R, S, T 1, 101
High-duty brake resistor 10%*1 The FR-ABR can be used with FR-A820-01250(22K) or
P, N 11, 111
(FR-ABR) 6%*2 lower and the FR-A840-00620(22K) or lower.
R, S, T/P, N 21, 121
High power factor converter
(FR-HC2), 0%
P, N 2, 102 —
Power regeneration common (initial value)
converter (FR-CV)
• FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher
Power supply terminals of
Regeneration unit Pr.30 setting*4 Pr.70 setting
inverter
R, S, T 0 (initial value), 100
Without regenerative function P, N 10, 110 —
R, S, T/P, N 20, 120
R, S, T 1, 101
Brake unit
P, N 11, 111 0% (initial value)
(FR-BU2 (MT-BR5))
R, S, T/P, N 21, 121
Power regeneration converter (MT-RC) R, S, T 1, 101 0% (initial value)
High power factor converter (FR-HC2) P, N 2, 102 —
• FR-A842-07700(315K) or higher
Regeneration unit Pr.30 setting*4
Without regenerative function (FR-CC2) 10 (initial value), 110
Brake unit
11, 111
(FR-CC2+FR-BU2 (MT-BR5))
High power factor converter (FR-HC2) 2, 102
NOTE
• For the use of a brake resistor other than the FR-ABR, contact your sales representative.
When using the built-in brake resistor or brake unit (FR-BU2, BU, FR-BU)
(FR-A820-03160(55K) or lower, FR-A840-01800(55K) or lower)
• When using the built-in brake, using the FR-BU2 in combination with the GZG/GRZG/FR-BR, or using the BU or FR-BU,
set Pr.30 = "0 (initial value), 10, 20, 100, 110, or 120". The Pr.70 setting is invalid. At this time, the regenerative brake duty
is as follows.
Inverter Regenerative brake duty
FR-A820-00250(3.7K) or lower 3%
FR-A820-00340(5.5K), FR-A820-00490(7.5K) 2%
FR-A840-00250(7.5K) or lower 2%
Other than the above 0% (without the built-in brake resistor)
NOTE
• The built-in brake resistor is equipped for the FR-A820-00490(7.5K) or lower, and the FR-A840-00250(7.5K) or lower.
690 5. PARAMETERS
5.16 (G) Control parameters
When using the high-duty brake resistor (FR-ABR) (FR-A820-01250(22K)
or lower, FR-A840-00620(22K) or lower) 1
• Set "1, 11, or 21" in Pr.30.
• Set Pr.70 as follows.
Inverter Pr.70 setting 2
FR-A820-00490(7.5K) or lower, FR-A840-00250(7.5K) or lower 10%
FR-A820-00630(11K) or higher, FR-A840-00310(11K) or higher 6%
3
When using the brake unit (FR-BU2) (FR-A820-03800(75K) or higher, FR-
A840-02160(75K) or higher)
• To use the FR-BU2 in combination with the MT-BR5, set as follows. 4
• Set "1, 11, or 21" in Pr.30.
• Set Pr.70 = 0% (initial value).
• Set the brake unit FR-BU2, Pr.0 Brake mode selection = "2". 5
NOTE
• The stall prevention (overvoltage), oL, does not occur while Pr.30 = "1, 11, or 21".
6
When using the power regeneration converter (MT-RC)
• Set "1 or 101" in Pr.30. 7
• Set Pr.70 = 0% (initial value).
(b) FR-HC2/FR-CC2 connection, instantaneous power failure detection (X11) signal: FR-HC2 connection, FR-CC2
connection
The X11 signal is used to store the command when the inverter is set to store the command before an instantaneous
power failure during the RS-485 communication.
Input the FR-HC2/FR-CC2 connection, instantaneous power failure detection signal.
• For the terminal used for the X10 or X11 signal, set "10" (X10) or "11" (X11) in any of Pr.178 to Pr.189 and assign the
function. (For the separated converter type, the X10 signal is assigned to terminal MRS in the initial setting.)
NOTE
• For details of the high-duty brake resistor (FR-ABR), brake unit, high power factor converter (FR-HC2), or power regeneration
common converter (FR-CV) connections, refer to page 96 to page 103. Also, for details of each option, refer to the Instruction
Manual of each option.
• Setting Pr.30 = "2" will reset the inverter, and "Err" is displayed on the operation panel during the reset.
Logic reversing of the Inverter run enable signal (X10 signal, Pr.599)
• Use Pr.599 X10 terminal input selection to select the X10 signal input specification between normally open (NO contact)
and normally closed (NC contact). With the normally closed (NC contact) input specification, the inverter output is shut off
by turning OFF (opening) the X10 signal.
5. PARAMETERS
5.16 (G) Control parameters
691
• Changing the inverter logic (NO/NC contact) with the Pr.599 setting is required according to the logic of the Inverter run
enable signal sent from the option unit.
• The response time of the X10 signal is within 2 ms.
Time
• Relationship between Pr.599 and the Inverter run enable signal of each option unit
Corresponding signals of the option unit Operation according to the X10
Pr.599 setting
FR-HC2 FR-CV FR-CC2 signal status
0 RDY (negative
X10-ON: Inverter output shutoff
(initial value of standard models and logic) RDYB RDB
(NO contact)
IP55 compatible models) (initial setting)
1
X10-OFF: Inverter output shutoff
(initial value of separated converter RDY (positive logic) RDYA RDA
(NC contact)
types)
NOTE
• If the X10 signal is unassigned while Pr.30 = "2" (FR-HC2/FR-CV connection) or "10 or 11" (DC feeding mode 1), the MRS
signal can be used as the X10 signal. At this time, logic setting for the signal will follow Pr.17 MRS input selection.
• The MRS signal is valid from either of communication or external, but when the MRS signal is to be used as the Inverter run
enable (X10) signal, it must be input from external.
• When the FR-HC or MT-HC is connected, set Pr.599 = "0 (initial value)".
• When the terminal assignment is changed with Pr.178 to Pr.189 (Input terminal function selection), wiring may be mistaken
due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming the function
of each terminal.
Regenerative brake duty warning output and the warning signal (RBP
signal) (standard models)
• When the regenerative brake duty reaches 85% of the Pr.70 setting, "RB" is indicated on the operation panel and the
Regenerative brake prealarm signal (RBP) signal is output. When it reaches 100% of the Pr.70 setting, it will become
regenerative overvoltage (E.OV[]).
• The inverter output is not shut off with the warning signal.
• For the terminal to be used for the RBP signal output, set "7 (positive logic) or 107 (negative logic)" to one of Pr.190 to
Pr.196 (Output terminal function selection), and assign the function.
Regenerative Time
brake pre-alarm OFF ON ON
(RBP)
NOTE
• When Pr.30 = "0 (initial value), 10, or 20" for the FR-A820-00630(11K) or higher and the FR-A840-00310(11K) or higher, "RB"
is not indicated.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
692 5. PARAMETERS
5.16 (G) Control parameters
Selection between resetting or not resetting during power supply to main
circuit (Pr.30 = "100, 101, 102, 110, 111, 120, or 121") 1
• Inverter reset is not performed if Pr.30 = "100" or more, and supplying power to the main circuit (input through terminals
R/L1, S/L2, and T/L3) is started when power is supplied only to the control circuit (input through terminals R1/L11 and S1/
L12, or 24 V external power supply input). 2
• When a communication option, etc. is used, communication interruption due to the inverter reset can be avoided.
NOTE
• When supplying power to the main circuit is started while the protective function of the inverter is activated, inverter reset is 3
performed even when "not resetting after power-ON" is selected.
R/L1
S/L2
Inrush
current
limit circuit
U
V
7
IM
T/L3 W
R1/L11
DC power MC S1/L21 Earth 8
(+) P/+ (Ground)
N/-
(-)
3
10 10
Frequency command 2
2
Frequency setting
potentiometer 1 5
1/2 W 1 kΩ
CAUTION
• Do not connect a separated converter type inverter to a DC power supply. Doing so may damage the inverter.
5. PARAMETERS
5.16 (G) Control parameters
693
Signal name Name Description Parameter setting
To operate with DC feeding, turn ON the X70 signal.
When the inverter output is shutoff due to power failure, it will be
possible to start up 200 ms after turning ON the X70 signal. (Automatic
DC feeding operation Set "70" in any of Pr.178 to
X70 restart after instantaneous power failure can start after the time set in
permission Pr.189.
Pr.57 has elapsed.)
When the X70 signal is turned OFF while operating the inverter, output
shutoff (Pr.261 = "0") or deceleration stop (Pr.261 ≠ "0") will occur.
Input
Turn ON when stopping the DC feeding.
When the X71 signal is turned ON during the operation of the inverter
and X70 signal is ON, output shutoff (Pr.261 = "0") or deceleration
Set "71" in any of Pr.178 to
X71 DC feeding cancel stop (Pr.261 ≠ "0") will occur, and Y85 signal will turn OFF after
Pr.189.
stopping.
After turning ON the X71 signal, operation is not possible even if the
X70 signal is turned ON.
This signal will turn ON during power failure or undervoltage of the AC
power supply. It will turn OFF when the X71 signal turns ON or power
restoration.
Set "85 (positive logic) or
The Y85 signal will not turn OFF even with the power restoration while
Output Y85 DC current feeding 185 (negative logic)" in any
the inverter is running, but turns OFF after stopping the inverter.
of Pr.190 to Pr.196.
When the Y85 signal is turned ON due to undervoltage, the Y85 signal
will not turn OFF even when the undervoltage is resolved.
The ON/OFF status is maintained when the inverter is reset.
• Following is the connection diagram of switching to DC power supply using the power failure detection of the inverter.
Inverter
MCCB MC Inrush
R/L1 current U
Three-phase AC S/L2 limit circuit V
power supply IM
T/L3 W
R1/L11
DC power MC1 S1/L21 Earth
P/+ (Ground)
(+)
N/-
(-)
*1 Assign the function using Pr.178 to Pr.182 (Input terminal function selection).
*2 Assign the function using Pr.190 to Pr.196 (Output terminal function selection).
694 5. PARAMETERS
5.16 (G) Control parameters
• Operation example at the time of power failure occurrence 1
AC power supply DC power supply
Control power
supply
ON
1
AC power supply
Y85(MC) ON
X70 ON 2
X71 ON
ON ON
3
STF(STR)
Motor
Output coasting
frequency
(Hz) 4
Time
Approx.
200ms 5
Back up operation
• Operation example at the time of power failure occurrence 2 (when the AC power supply is restored) 6
Control power supply AC DC AC
ON Power restoration
7
AC power supply
Turns off after stop
Y85(MC) ON while running
X70 ON
X71 OFF 8
STF(STR) ON ON
Motor
9
Output coasting
frequency
(Hz)
10
Time
Approx.200ms
Back up operation
• Operation example at the time of power failure occurrence 3 (when continuing the operation)
Control power AC DC AC
supply
ON Power restoration
AC power supply
X70 ON
X71 OFF
STF(STR) ON
Output
frequency
(Hz)
Time
Back up operation
5. PARAMETERS
5.16 (G) Control parameters
695
Power supply specification for DC feeding (standard models and IP55
compatible models)
Rated input DC voltage 283 to 339 VDC
200 V class
Permissible fluctuation 240 to 373 VDC
Rated input DC voltage 537 to 679 VDC
400 V class
Permissible fluctuation 457 to 740 VDC
NOTE
• The voltage between terminals P and N briefly increases to 415 V (830 V) or higher during the regenerative driving, so take
caution on the selection of the DC power supply.
• When an AC power supply is connected to terminals R/L1, S/L2, and T/L3 during DC feeding with Pr.30 = "2, 10, or 11" (DC
feeding), an option fault (E.OPT) will occur.
• When the inverter is operated by the DC power supply by setting Pr.30 = "2, 10, 11, 20, or 21" (DC deeding), Undervoltage
(E.UVT) and Instantaneous power failure (E.IPF) are not performed.
• When the DC power is switched ON, an inrush current higher than that for the AC power flows in the inverter. Minimize the
number of power-ON events.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) or Pr.190 to Pr.196 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
WARNING
• The value set in Pr.70 must not exceed the setting of the brake resistor used.
It may cause overheating.
Parameters referred to
Pr.17 MRS input selectionpage 499
Pr.57 Restart coasting timepage 597, page 604
Pr.178 to Pr.189 (Input terminal function selection)page 496
Pr.190 to Pr.196 (Output terminal function selection)page 450
Pr.261 Power failure stop selectionpage 610
696 5. PARAMETERS
5.16 (G) Control parameters
Setting
Pr. Name Initial value Description
range 1
0 The regeneration avoidance function is disabled.
Regeneration
882 1 The regeneration avoidance function is always enabled.
avoidance operation 0
G120 The regeneration avoidance function is enabled only during
selection 2
constant-speed operation. 2
200 V Set the bus voltage level to operate the regeneration avoidance
380 VDC
class operation. When the bus voltage level is set low, it will be harder
Regeneration to generate overvoltage error, but actual deceleration time will
883
G121
avoidance operation
400 V
300 to 1200
V be longer. 3
level 760 VDC Set the setting value higher than the (power supply voltage ×
class
√2 ) value.
Regeneration 0
The regeneration avoidance is disabled due to bus voltage
change rate.
4
884 avoidance at
0 Set the sensitivity to detect the bus voltage change rate.
G122 deceleration detection
sensitivity 1 to 5 Setting value 1 (detection sensitivity: low) to 5 (detection
sensitivity: high) 5
Regeneration Set the limit value for frequency to rise when the regeneration
0 to 590 Hz
885 avoidance avoidance function is activated.
6 Hz
G123 compensation
9999 The frequency limit is disabled.
frequency limit value 6
886 Regeneration Adjust the response during the regeneration avoidance
100% 0 to 200%
G124 avoidance voltage gain operation. Increasing the setting improves the response to
Regeneration change in the bus voltage. However, the output frequency may
665
G125
avoidance frequency
gain
100% 0 to 200% become unstable. If setting a smaller value in Pr.886 does not
suppress the vibration, set a smaller value in Pr.665.
7
Regeneration avoidance operation (Pr.882, Pr.883)
• When the regenerative voltage increases, the DC bus voltage will rise, which may cause an overvoltage fault (E.OV[]). The 8
regenerative status can be avoided by detecting this rise of bus voltage, and raising the frequency when the bus voltage
level exceeds Pr.883 Regeneration avoidance operation level.
• The regeneration avoidance operation can be selected to operate constantly or operate only during constant speed. 9
• The regeneration avoidance function is enabled by setting "1 or 2" in Pr.882 Regeneration avoidance operation
selection.
10
Regeneration avoidance operation Regeneration avoidance operation Regeneration avoidance operation
example for acceleration example for constant speed example for deceleration
Bus voltage
Bus voltage
Pr. 883
(VDC)
Pr. 883
Bus voltage
(VDC)
Pr. 883
(VDC)
Time
frequency(Hz)
Time Time
frequency(Hz)
frequency(Hz)
Output
Output
Output
During regeneration
avoidance function operation During regeneration
During regeneration Time
Time avoidance function operation Time
avoidance function operation
NOTE
• The slope of frequency rising or lowering by the regeneration avoidance operation will change depending on the regenerative
status.
• The DC bus voltage of the inverter will be approximately √2 times of the normal input voltage.
The bus voltage is about 311 VDC (622 VDC) when the input voltage is 220 VAC (440 VAC). However, it may vary depending
on the input power supply waveform.
• Make sure that the setting value of Pr.883 will not get under DC bus voltage level. The frequency will rise with operation of the
regeneration avoidance function even during operation other than the regenerative operation.
• The stall prevention (overvoltage) (oL) will only operate during deceleration, stopping the lowering of output frequency, but on
the other hand, the regeneration avoidance function will constantly operate (Pr.882 = "1") or operate only at constant speed
(Pr.882 = "2"), and raise the frequency depending on the amount of regeneration.
• When the motor becomes unstable due to operation of the stall prevention (overcurrent) (OL) during the regeneration
avoidance operation, increase the deceleration time or lower the setting of Pr.883.
• During position control, the regeneration avoidance function is not activated.
5. PARAMETERS
5.16 (G) Control parameters
697
Detecting the regenerative status faster during deceleration (Pr.884)
• Since a rapid change in bus voltage cannot be handled by bus voltage level detection during the regeneration avoidance
operation, deceleration is stopped by detecting the change in bus voltage and if it is equal to or lower than Pr.883
Regeneration avoidance operation level. Set the detectable bus voltage change rate as the detection sensitivity in
Pr.884 Regeneration avoidance at deceleration detection sensitivity. A larger set value increases the detection
sensitivity.
NOTE
• When the setting value is too small (detection sensitivity is not good), detection will not be possible, and regeneration
avoidance will operate even with the bus voltage change caused by a change in the input power.
Limit level
frequency(Hz)
Pr.885
Pr.885/2
Time
NOTE
• During the regeneration avoidance operation, the stall prevention (overvoltage) "oL" is displayed and the Overload warning
(OL) signal is output. Set the operation pattern at an OL signal output using Pr.156 Stall prevention operation selection.
Use Pr.157 OL signal output timer to set the OL signal output timing.
• The stall prevention is enabled even during regeneration avoidance operation.
• The regeneration avoidance function cannot decrease the actual deceleration time for the motor to stop. Since the actual
deceleration time is determined by the regenerative power consumption performance, consider using a regeneration unit (FR-
BU2, BU, FR-BU, FR-CV, FR-HC2) or brake resistor (FR-ABR, etc.) to decrease the deceleration time.
• When using a regeneration unit (FR-BU2, BU, FR-BU, FR-CV, FR-HC2) or brake resistor (FR-ABR, etc.) to consume the
regenerative power, set Pr.882 = "0 (initial value)" (the regeneration avoidance function is disabled). When consuming the
regenerative power at the time of deceleration with the regeneration unit, etc., set Pr.882 = "2" (enables regeneration
avoidance function only at the constant speed).
• When using the regeneration avoidance function under Vector control, noise may be generated from the motor during
deceleration. In such case, adjust the gain by performing easy gain tuning, etc. (Refer to page 244.)
698 5. PARAMETERS
5.16 (G) Control parameters
Parameters referred to
Pr.1 Maximum frequencypage 407
Pr.8 Deceleration timepage 349
Pr.22 Stall prevention operation levelpage 409
1
Setting
4
Pr. Name Initial value Description
range
Increased magnetic 0 Without the increased magnetic excitation deceleration function
660
G130
excitation deceleration
operation selection
0
1 With the increased magnetic excitation deceleration function 5
0 to 40% Set the increase of excitation.
The magnetic excitation increase rate is 10% under V/F control
661 Magnetic excitation
G131 increase rate
9999
9999
and Advanced magnetic flux vector control. 6
The magnetic excitation increase rate is 0% under
Real sensorless vector control and Vector control.
The increased magnetic excitation rate is automatically lowered
662
G132
Increased magnetic
excitation current level
100% 0 to 300% when the output current exceeds the setting value during increased 7
magnetic excitation deceleration.
• When the stall prevention (overvoltage) occurs during the increased magnetic excitation deceleration operation, increase
the deceleration time or raise the setting value of Pr.661. When the stall prevention (overcurrent) occurs, increase the
deceleration time or lower the setting value of Pr.661.
• Increased magnetic excitation deceleration is enabled under V/F control, Advanced magnetic flux vector control, Real
sensorless vector control (speed control), and Vector control (speed control).
NOTE
• Increased magnetic excitation deceleration will be disabled in the following conditions:
During PM sensorless vector control, power failure stop, orientation control, operation with the FR-HC2/FR-CV, energy saving
operation, Optimum excitation control, and stop-on-contact control.
5. PARAMETERS
5.16 (G) Control parameters
699
• When the inverter protective function (E.OC[], E.THT) is activated due to increased magnetic excitation deceleration,
adjust the level set in Pr.662.
• The overcurrent preventive function is disabled when Pr.662 = "0".
NOTE
• When the level set in Pr.662 is more than the one set in Pr.22 Stall prevention operation level, the overcurrent preventive
function is activated at the level set in Pr.22. (The level set in Pr.662 is applied when Pr.22 = "0".)
Parameters referred to
Pr.22 Stall prevention operation levelpage 409
Pr.30 Regenerative function selectionpage 689
Pr.60 Energy saving control selectionpage 678
Pr.162 Automatic restart after instantaneous power failure selectionpage 597, page 604
Pr.270 Stop-on contact/load torque high- speed frequency control selectionpage 546
Pr.261 Power failure stop selectionpage 610
Pr.350 Stop position command selectionpage 554
Under V/F control, the slip of the motor is estimated from the inverter output current to maintain the rotation of the motor
constant.
Setting
Pr. Name Initial value Description
range
245 0.01 to 50% Set the rated motor slip.
Rated slip 9999
G203 0, 9999 No slip compensation
Set the response time of the slip compensation. Reducing the
246 Slip compensation time
0.5 s 0.01 to 10 s value improves the response, but the regenerative overvoltage
G204 constant
(E.OV[]) error is more likely to occur with a larger load inertia.
No slip compensation in the constant power range (frequency
247 Constant output range slip 0
9999 range higher than the frequency set in Pr.3).
G205 compensation selection
9999 Slip compensation is performed in the constant power range.
• Calculate the rated motor slip and set the value in Pr.245 to enable slip compensation.
Slip compensation is not performed when Pr.245 = "0 or 9999".
Synchronized speed at the time of base frequency - rated rotation speed
Rated slip = × 100 [%]
Synchronized speed at the time of base frequency
NOTE
• When the slip compensation is performed, the output frequency may become larger than the set frequency. Set Pr.1 Maximum
frequency higher than the set frequency.
• Slip compensation will be disabled in the following conditions:
Stall prevention (oL, OL) operation, regeneration avoidance operation, auto tuning, encoder feedback control operation
Parameters referred to
Pr.1 Maximum frequencypage 407
Pr.3 Base frequencypage 673
This controls the inverter output frequency so that the motor speed is constant to the load variation by detecting the motor
speed with the speed detector (encoder) to feed back to the inverter.
A Vector control compatible option is required.
700 5. PARAMETERS
5.16 (G) Control parameters
Initial
Pr. Name Setting range Description
value 1
0, 2, 4, 6, 8, 10, 12,
144 Set the number of motor poles for the encoder
Speed setting switchover 4 102, 104, 106, 108,
M002 feedback control under V/F control.
110, 112
When the difference between the detected frequency 2
and the output frequency exceeds the set value during
285 Overspeed detection 0 to 30 Hz
9999 encoder feedback control, an inverter fault (E.MB1) is
H416 frequency*1 generated.
9999 Overspeed detection is disabled. 3
Set when using a motor for Set for the operation
0
which forward rotation at 120 Hz or less.
(encoder) is clockwise (CW)
viewed from the shaft
Set for the operation
4
100 CW at a frequency
higher than 120 Hz.
359*2*3
C141
852*4
C241
Encoder rotation direction 1
Set when using a motor for Set for the operation
5
1
which forward rotation at 120 Hz or less.
(encoder) is counterclockwise
(CCW) viewed from the shaft
Set for the operation 6
101 at a frequency
CCW
higher than 120 Hz.
NOTE
• Operating the inverter with Pr.144 = "0, 10, 12, 110, or 112" causes E.1 to E.3.
• When "102, 104, 106, or 108" is set in Pr.144, the value obtained by subtracting 100 from the set value will be set as the
number of poles.
• The Pr.144 setting changes automatically when setting the motor poles in Pr.81, but even if Pr.144 is changed, Pr.81 will not
automatically change.
• Control with correct speed is not possible if the number of poles for the applied motor is incorrect. Check first before operation.
• Encoder feedback control is not possible when the rotation direction setting of the encoder is incorrect. (Operation of the
inverter is possible.)
Check the indicator on the parameter unit to confirm the direction.
5. PARAMETERS
5.16 (G) Control parameters
701
Selection of encoder feedback control (Pr.367)
• When a value other than "9999" is set in Pr.367 Speed feedback range, encoder feedback control is enabled. Set a target
value (frequency at which stable speed operation is performed) and specify the range around the value. Normally, use the
frequency converted from the slip amount (r/min) at the rated motor speed (rated load). If the setting is too large, response
becomes slow.
Speed feedback range Driven load Regenerative load
Set value
(Set command)
NOTE
• Couple the encoder on the same axis as the motor axis without any mechanical clatter, with speed ratio of 1:1.
• Encoder feedback control is not performed during the acceleration and deceleration to prevent unstable operation such as
hunting.
• Encoder feedback control is performed after the output frequency has reached [set frequency] ± [speed feedback range] once.
• When following status occurs during encoder feedback control operation, the inverter output is not shut off, the output
frequency becomes the value obtained by [set frequency] ± [speed feedback range], and tracking of the motor speed is not
performed.
When the pulse signal from the encoder is lost due to a break, etc.
When correct pulse signal cannot be detected due to induction noise, etc.
When the motor is forcefully accelerated (regenerative rotation) or decelerated (motor lock) due to large external force
• Use the Inverter running (RUN) signal when releasing the brake from the motor with a brake. (The brake may not be released
when the Output frequency detection (FU) signal is used.)
• Do not turn OFF the external power supply for the encoder during encoder feedback control. Normal encoder feedback control
will not be possible.
Parameters referred to
Pr.81 Number of motor polespage 215, page 509
702 5. PARAMETERS
5.16 (G) Control parameters
This is effective in balancing the load when multiple inverters are connected.
0
No droop control during
acceleration/deceleration
3
(with 0 limit)
Continuous droop control
The Pr.84 setting is the droop
1 during operation
(with 0 limit)
compensation reference. 4
Continuous droop control
2 during operation
(without 0 limit)
No droop control during
5
10 acceleration/deceleration
288 Droop function activation (with 0 limit) The motor speed is the droop
0
G402 selection
11
Continuous droop control
during operation
compensation reference.
6
(with 0 limit)
No droop control during
20 acceleration/deceleration
(with 0 limit)
7
Constant droop control during The Pr.1121 setting is the
21 operation droop compensation
(with 0 limit)
Constant droop control during
reference.
8
22 operation
(without 0 limit)
994
Droop break point gain 9999
0.1 to 100%
Set the droop amount to be changed as % value of the rated
motor frequency.
9
G403
9999 No function
995
Droop break point torque 100% 0.1 to 100% Set the torque to change the droop amount.
G404 10
0 to 100% Refer to Pr.286.
679
Second droop gain 9999 The first droop control setting
G420 9999
is applied.
0 to 1 s Refer to Pr.287.
680 Second droop filter time
9999 The first droop control setting
G421 constant 9999
is applied.
0 to 2, 10, 11, Set the second droop control.
Refer to Pr.288.
681 Second droop function 20 to 22 The second droop control is
9999
G422 activation selection The first droop control setting enabled when the RT signal is
9999
is applied. ON.
0.1 to 100% Refer to Pr.994.
682 Second droop break point
9999 The first droop control setting
G423 gain 9999
is applied.
0.1 to 100% Refer to Pr.995.
683 Second droop break point
9999 The first droop control setting
G424 torque 9999
is applied.
Droop control
• Droop control is enabled under Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and
PM sensorless vector control.
• In the droop control, the speed command changes depending on the amount of the current for torque.
Set the droop amount at the rated torque in Droop gain as % value of the rated motor frequency (or motor speed when
Pr.288 = "10 or 11").
• The upper limit of the droop compensation frequency is 400 Hz or Pr.1 Maximum frequency, whichever smaller.
5. PARAMETERS
5.16 (G) Control parameters
703
• During PM sensorless vector control, the upper limit of the droop compensation frequency is 400 Hz, the frequency set in
Pr.1, or the maximum motor frequency, whichever the smallest.
Frequency
Droop compensation
Droop compensation frequency
reference Droop
gain
Torque
-100% 0 100%
When the output frequency is equal to or lower than the rated frequency set in Pr.84: K=1
Rated frequency (Pr.84)
When the output frequency is higher than the rated frequency set in Pr.84: K =
Output frequency
NOTE
• Set the droop gain equivalent to the rated slip of the motor.
Synchronized speed at the time of base frequency - rated rotation speed
Rated slip = × 100[%]
Synchronized speed at the time of base frequency
• The speed loop integration can be disabled at the emergency stop using Pr.1349 Emergency stop operation selection.
(Refer to page 349.)
*1 Under Advanced magnetic flux vector control, the operation is the same as the one when the setting is "0".
704 5. PARAMETERS
5.16 (G) Control parameters
Setting the break point for droop control (Pr.994, Pr.995)
• Set Pr.994 and Pr.995 to have a break point on a droop compensation frequency line. Setting a break point allows the 1
inverter to raise the droop compensation frequency for light-load (no load) operation without raising it for heavy-load
operation.
Increased amount of the
droop compensation Frequency 2
frequency
Droop break point gain
Droop compensation (Pr.994)
reference Droop gain 3
Droop compensation (Pr.286)
frequency
Droop break point torque
(Pr.995)
4
Torque
-100% 0 100%
NOTE 5
• The droop break point function is disabled when any of the following conditions is met. (Linear compensation by Pr.286 is
performed.)
Pr.995 = 100% (initial value)
Pr.286 < Pr.994 6
Pr.994 ≤ Pr.995 × Pr.286 / 100%
The output current (torque) of the inverter sometimes becomes unstable due to vibration caused by mechanical resonance.
Such vibration can be suppressed by reducing fluctuation of the output current (torque) by changing the output frequency.
Setting
Pr. Name Initial value Description
range
653 Speed smoothing Check the effect by increasing and decreasing the value at around
0% 0 to 200%
G410 control 100%.
654 Speed smoothing
20 Hz 0 to 120 Hz Set the minimum frequency for the torque variation cycle.
G411 cutoff frequency
5. PARAMETERS
5.16 (G) Control parameters
705
Control block diagram
Acceleration/deceleration
processing
+ Output frequency
Speed Frequency output
V/F control
command Voltage output
-
Speed smoothing control
Cutoff frequency
Pr.654
Proportional gain
Current for torque
Pr.653
Setting method
• When vibration caused by mechanical resonance occurs, set 100% in Pr.653 Speed smoothing control, perform
operation at the frequency with the largest vibration, and check if the vibration is suppressed after few seconds.
• If the setting is not effective, gradually increase the value set in Pr.653 and repeat the operation to check the effect to
determine the most effective value (Pr.653).
• If the vibration increases by increasing the value in Pr.653, decrease the value in Pr.653 from 100% to check the effect.
• When the vibrational frequency at which mechanical resonance occurs (during fluctuation of torque, speed, or converter
output voltage) is measured using an instrument such as a tester, set 1/2 to 1 times of the vibrational frequency in Pr.654
Speed smoothing cutoff frequency. (Setting the resonance frequency range mitigates vibration more effectively.)
Cutoff frequency
Current for
torque
Torque fluctuation
detection range
NOTE
• Depending on the equipment, the vibration may not be suppressed sufficiently or the setting is not effective.
706 5. PARAMETERS
5.16 (G) Control parameters
5.17 Parameter clear / All parameter clear 1
• Set "1" to Pr.CLR Parameter clear or ALL.CL All parameter clear to initialize all parameters. (Parameters cannot be cleared
2
when Pr.77 Parameter write selection = "1".)
• Pr.CL does not clear calibration parameters or the terminal function selection parameters.
• Refer to the parameter list on page 824 for parameters cleared with this operation. 3
Operating procedure 4
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
Turn to change the set value to " ". Press to set. " " and " " 9
(" ") are displayed alternately after parameters are cleared.
Description
Setting
Pr.CL Parameter clear ALLC All parameter clear
0 Initial display (Parameters are not cleared.)
The settings of all the parameters, including calibration
The settings of parameters except for calibration parameters
1 parameters and terminal function selection parameters, are
and terminal function selection parameters are initialized.
initialized.
NOTE
• " " and " " are displayed alternately when the operation mode is other than the PU operation mode.
1) Press .
turns ON, and " " appears on the monitor. (When Pr.79 ="0" (initial value))
• Stop the inverter first. Writing error occurs if parameter clear is attempted while the inverter is running.
• To clear parameters, the inverter must be in the PU operation mode even if "2" is set to Pr.77.
• For availability of the Parameter clear or All parameter clear operation for each parameter, refer to the parameter list on page
824.
5. PARAMETERS
5.17 Parameter clear / All parameter clear
707
5.18 Copying and verifying parameters on the operation
panel
NOTE
• When the copy destination is other than the FR-A800 series or when parameter copy is attempted after the parameter copy
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Turn to change the set value to " ". Press to start reading of the inverter parameter settings by
the operation panel. (It takes about 30 seconds to read all the settings. During reading, " " blinks.)
5. End reading
" " and " " are displayed alternately after settings are read.
NOTE
• " " appears when a parameter read error occurred. Perform the operation from step 3 again.
708 5. PARAMETERS
5.18 Copying and verifying parameters on the operation panel
Copying parameter settings read to the operation panel to the inverter
Operating procedure 1
1. Connect the operation panel to the destination inverter.
6. Ending copying
" " and " " are displayed alternately after copying ends.
8
7. When parameters are written to the destination inverter, reset the inverter before operation by, for example, turning
the power supply OFF. 9
NOTE
• " " appears when a parameter write error occurred. Perform the operation from step 3. again.
10
• " " and " " are displayed alternately when parameter copy is performed between the FR-A820-03160(55K)
or lower or FR-A840-01800(55K) or lower inverters and the FR-A820-03800(75K) or higher or FR-A840-02160(75K) or higher
inverters. When CP and 0.00 are displayed alternately, set Pr.989 Parameter copy alarm release as shown below (initial
value).
Operating procedure
1. Copy the parameter settings of the verification source inverter to the operation panel according to the procedure on
page 708.
5. PARAMETERS
5.18 Copying and verifying parameters on the operation panel
709
4. Selecting the parameter setting mode
Press to choose the parameter setting mode. (The parameter number read previously appears.)
6. Parameter verification
Turn to change to setting value " " (Parameter copy verification mode).
Press . Verification of the parameter settings copied to the operation panel and the parameter settings of the
verification destination inverter is started. (It takes about 60 seconds to verify all the settings. During verification,
● If there are different parameters, the different parameter number and " " are displayed alternately.
7. " " and " " are displayed alternately after verification ends.
NOTE
• When " " blinks, the set frequency may be incorrect. To continue verification, press .
710 5. PARAMETERS
5.18 Copying and verifying parameters on the operation panel
5.19 Copying and verifying parameters using a USB 1
memory
2
• Inverter parameter settings can be copied to a USB memory device.
• Parameter setting data copied to a USB memory device can be copied to other inverters or verified to see if they differ from
the parameter settings of other inverters. 3
• Parameter settings can also be imported to a personal computer and edited in FR Configurator2.
5
Monitor mode Parameter setting mode Function mode Faults history mode
6
USB memory mode
5. PARAMETERS
5.19 Copying and verifying parameters using a USB memory
711
NOTE
• When parameter settings are copied to the USB memory without specifying a parameter setting file number in the USB
memory, numbers are automatically assigned.
• Up to 99 files can be saved in the USB memory. When the USB memory already has 99 files, attempting copying of another
file to the USB memory causes the file quantity error (rE7).
• Refer to the Instruction Manual of FR Confirurator2 for the details on importing files to FR Configurator2.
• While password protection is enabled, parameter copy and parameter verification cannot be performed. (Refer to page 331.)
Press three times to display " " (file selection screen) and press . (To overwrite files on
the USB memory, display the file selection screen, turn to select the file number, and press .)
Turn to change to " ". Press to copy the parameter settings at the copy source to the USB
memory. (It takes about 15 seconds to copy all the settings. During copying, " " blinks.)
" " and the file number are displayed alternately after copying ends.
Procedure for copying parameters from the USB memory to the inverter
Operating procedure
1. Insert the USB memory device into the destination inverter.
Turn to select the file number to copy to the inverter, and press .
Press to write the parameters copied to the USB memory to the destination inverter. (It takes about 15
seconds to copy all the settings. During copying, " " blinks.)
" " and the file number are displayed alternately after copying ends.
● Perform this step while the inverter is stopped.
7. When parameters are written to the destination inverter, reset the inverter before operation by, for example, turning
the power supply OFF.
712 5. PARAMETERS
5.19 Copying and verifying parameters using a USB memory
NOTE
• " " or " " appears when a USB memory device error occurred. Check the connection of the USB memory
1
device and try the operation again.
• " " and " " are displayed alternately when parameter copy is performed between the FR-A820-03160(55K)
or lower or FR-A840-01800(55K) or lower inverters and the FR-A820-03800(75K) or higher or FR-A840-02160(75K) or higher
2
inverters. When CP and 0.00 are displayed alternately, set Pr.989 Parameter copy alarm release as shown below (initial
value).
• After setting Pr.989, perform setting of Pr.9, Pr.30, Pr.51, Pr.56, Pr.57, Pr.61, Pr.70, Pr.72, Pr.80, Pr.82, Pr.90 to Pr.94,
4
Pr.453, Pr.455, Pr.458 to Pr.462, Pr.557, Pr.859, Pr.860, and Pr.893 again.
• When the destination inverter is other than the FR-A800 series or when Parameter copy is attempted after the parameter copy
7. Parameter verification
Turn to display the setting " " (Parameter copy verification mode), and press .
Press to start verification of the parameter settings copied to the USB memory and the parameter settings of
the verification destination inverter. (It takes about 15 seconds to verify all the settings. During verification,
● If there are different parameters, the different parameter number and " " are displayed alternately.
5. PARAMETERS
5.19 Copying and verifying parameters using a USB memory
713
8. The verified file number and " " are displayed alternately after verification ends.
NOTE
• When " " blinks, the set frequency may be incorrect. To continue verification, press .
714 5. PARAMETERS
5.19 Copying and verifying parameters using a USB memory
5.20 Checking parameters changed from their initial 1
values (initial value change list)
2
Parameters changed from their initial values can be displayed.
Operating procedure
1. Turning ON the power of the inverter
3
The operation panel is in the monitor mode.
3. Selecting a parameter 5
Turn to " " (Initial value change list), and press .
Turn . The parameter numbers that have been changed from their initial value appear in order.
7
● If is pressed with parameters that have been changed, the parameter settings can be changed as they are.
(Parameter numbers are no longer displayed in the list when they are returned to their initial values.)
8
Other changed parameters appear by turning .
5. PARAMETERS
5.20 Checking parameters changed from their initial values (initial value change list)
715
5.21 CC-Link IE Field Network (FR-A800-GF)
Data flow and link device assignment (master and slave stations (except
for local stations))
One-to-one communication is possible between the master and slave stations.
The status information of the link devices (RY and RWw) of the master station is output to the external device of the slave
station, and the input status information from the external device of the slave station is stored in the link devices (RX and RWr)
of the master station.
No.2
Link
scan
Device (4)
RY, RWw RY, RWw
Station (4)
(2) Station No.1
No.1 (3) RY, RWw
Sequence
scan Station
Link refresh (3) Station No.2
D
EN
No.2
716 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
NOTE
• Refer to the MELSEC iQ-R, MELSEC-Q, or MELSEC-L CC-Link IE Field Network Master/Local Module User's Manual for the 1
detailed assignment methods for the link devices and link refresh.
RYn5
Jog operation command (terminal Jog
720 RXn5
Instantaneous power failure (terminal IPF
722
6
function)*1 function)*3
Second function selection (terminal RT Frequency detection (terminal FU
RYn6 720 RXn6 722
function)*1 function)*3
Current input selection (terminal AU
7
RYn7 *1 720 RXn7 Error (terminal ABC1 function)*3 722
function)
Selection of automatic restart after
RYn8 instantaneous power failure (terminal CS
*1
720 RXn8 — (terminal ABC2 function)*3 722 8
function)
RYn9 Output stop (terminal MRS function)*1 720
Start self-holding selection (terminal STOP
RYnA
function)*1
720
RXn9 to 9
Reserved —
RXnF
RYnB Reset (terminal RES function)*1 720
RYnC to
RYnF 10
Reserved — RX(n+1)0 Pr.313 assignment function (DO0)*4 722
RY(n+1)0 to
RY(n+1)2
RX(n+1)1 Pr.314 assignment function (DO1)*4 722
RX(n+1)2 Pr.315 assignment function (DO2)*4 722
RY(n+1)3 to RX(n+1)3 to
Reserved — Reserved —
RY(n+1)F RX(n+1)F
RY(n+2)0 Monitor command 720 RX(n+2)0 Monitoring 722
RY(n+2)1 Frequency setting command (RAM) 720 RX(n+2)1 Frequency setting completion (RAM) 722
Frequency setting command (RAM, Frequency setting completion (RAM,
RY(n+2)2 720 RX(n+2)2 722
EEPROM) EEPROM)
Torque command / torque limit setting
RY(n+2)3 Torque command / torque limit (RAM) 721 RX(n+2)3 722
completion (RAM)
Torque command / torque limit (RAM, Torque command / torque limit setting
RY(n+2)4 721 RX(n+2)4 722
EEPROM) completion (RAM, EEPROM)
RY(n+2)5 Instruction code execution request 721 RX(n+2)5 Instruction code execution completed 722
RY(n+2)6 to RX(n+2)6 to
Reserved — Reserved —
RY(n+3)9 RX(n+3)9
RY(n+3)A Error reset request flag 721 RX(n+3)A Error status flag 722
RX(n+3)B Remote station ready 722
RY(n+3)B to
Reserved — RX(n+3)C to
RY(n+3)F Reserved —
RX(n+3)F
*1 These signals are set in the initial setting. Using Pr.180 to Pr.189, input signals assigned to the device numbers can be changed. (Refer to page
496.)
*2 The signals are fixed. They cannot be changed using parameters.
*3 These signals are set in the initial setting. Using Pr.190 to Pr.196, output signals assigned to the device numbers can be changed. (Refer to page
450.)
*4 Output signal can be assigned using Pr.313 to Pr.315. (Refer to page 450.)
*5 "n" indicates a value determined by the station number setting.
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
717
Remote register (128 words (fixed))
Description Refer Description Refer
Address*3 Address*3
Upper 8 bits Lower 8 bits to page Upper 8 bits Lower 8 bits to page
RWwn Set frequency (0.01 Hz increments) 723 RWrn Reply code 724
RWwn+1 Reserved — RWrn+1 Reserved —
RWwn+2 Torque command / torque limit 723 RWrn+2 Reply code 724
RWwn+3 Reserved — RWrn+3 Reserved
RWwn+4 *1 723 RWrn+4 Reply code 724
PID set point (0.01% increments)
RWwn+5 PID measured value (0.01% increments)*1 723 RWrn+5 Reply code 724
RWwn+6 PID deviation (0.01% increments)*1 723 RWrn+6 Reply code 724
RWwn+7 to RWrn+7 to
Reserved — Reserved —
RWwn+F RWrn+F
Link parameter
RWwn+10
extended setting Instruction code*2 723 RWrn+10 Reply code 724
718 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Description Refer Description Refer
Address*3 Address*3
Upper 8 bits Lower 8 bits to page Upper 8 bits Lower 8 bits to page
RWrn+3A Electric thermal relay function load factor 724
1
RWrn+3B Output current peak value 724
RWrn+3C Converter output voltage peak value 724
RWrn+3D Input power 724 2
RWrn+3E Output power 724
RWrn+3F Input terminal status 724
RWrn+40 Output terminal status 724
RWrn+41 Load meter 724 3
RWrn+42 Motor excitation current 724
RWrn+43 Position pulse 724
RWrn+44 Cumulative energization time 724 4
RWrn+45 Reserved —
RWrn+46 Orientation status 724
RWrn+47 Actual operation time 724
RWrn+48 Motor load factor 724 5
RWrn+49 Cumulative power 724
RWrn+4A Position command (lower) 724
RWrn+4B
RWrn+4C
Position command (upper)
Current position (lower)
724
724
6
RWrn+4D Current position (upper) 724
RWrn+4E Droop pulse (lower) 724
RWrn+4F Droop pulse (upper) 724 7
RWrn+50 Torque command 724
RWrn+51 Torque current command 724
RWrn+52
RWrn+53
Motor output
Feedback pulse monitor
724
724
8
RWrn+54 Torque monitor 724
RWwn+3A
RWrn+55 Reserved —
to Reserved —
RWwn+73 RWrn+56 Trace status 724 9
RWrn+57 Reserved —
RWrn+58 PLC function user monitor 1 724
RWrn+59
RWrn+5A
PLC function user monitor 2
PLC function user monitor 3
724
724
10
RWrn+5B Station number (RS-485 terminals) 724
RWrn+5C Station number (PU) 724
RWrn+5D Station number (CC-Link) 724
RWrn+5E Motor temperature 724
RWrn+5F to
Reserved —
RWrn+61
RWrn+62 Power saving effect 724
RWrn+63 Cumulative energy saving 724
RWrn+64 PID set point 724
RWrn+65 PID measured value 724
RWrn+66 PID deviation 724
RWrn+67 to
Reserved —
RWrn+69
RWrn+6A Option input terminal status 1 724
RWrn+6B Option input terminal status 2 724
RWrn+6C Option output terminal status 724
RWrn+6D Motor thermal load factor 724
RWrn+6E Inverter thermal load factor 724
RWrn+6F Reserved —
RWrn+70 PTC thermistor value 724
RWrn+71
Reserved —
RWrn+72
RWrn+73 PID measured value 2 724
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
719
Description Refer Description Refer
Address*3 Address*3
Upper 8 bits Lower 8 bits to page Upper 8 bits Lower 8 bits to page
RWrn+74 to
Reserved —
RWrn+76
RWrn+77 Cumulative pulse 724
RWwn+74 RWrn+78 Cumulative pulse overflow times 724
to Reserved — RWrn+79 Cumulative pulse (control terminal option) 724
RWwn+7F Cumulative pulse overflow times (control
RWrn+7A 724
terminal option)
RWrn+7B to
Reserved —
RWrn+7F
*1 When Pr.128 = "50, 51, 60, or 61", the register is valid.
*2 Instructions will be processed in the order they are received. Thus, the read value of an instruction may differ at different timings if other writing
requests are being made.
*3 "n" indicates a value determined by the station number setting.
720 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Device No. Signal Description
When "1" is set in the torque command / torque limit (RY23), the set torque
command / torque limit (RWw2) is written to RAM of the inverter. 1
After the writing completes, "1" is set in the torque command / torque limit setting
RY23 Torque command / torque limit (RAM) completion (RX23).
The following value is written to RAM.
• During torque control*1: Torque command value 2
• During speed control / position control: Torque limit value
When "1" is set in the torque command / torque limit (RY24), the set torque
command / torque limit (RWw2) is written to RAM and EEPROM of the inverter.
After the writing completes, "1" is set in the torque command / torque limit setting 3
completion (RX24).
Torque command / torque limit (RAM, The following value is written to RAM and EEPROM.
RY24
EEPROM)
• During torque control*1: Torque command value
• During speed control / position control: Torque limit value
4
To change the torque command or the torque limit consecutively, be sure to write
data to the inverter RAM.
When "1" is set in the instruction code execution request (RY25), processes
corresponding to the instruction codes set to RWw10, 12, 14, 16, 18 and 1A are
5
RY25 Instruction code execution request executed. "1" is set in the instruction code execution request (RX25) after
completion of instruction codes. When an instruction code execution error occurs,
a value other than "0" is set in the reply code (RWr10, 12, 14, 16, 18, and 1A).
When "1" is set in the error reset request flag (RY3A) at an inverter fault, the
6
RY3A Error reset request flag inverter is reset, then "0" is set in the error status flag (RX3A). Refer to page
635 for operation conditions of inverter reset.
*1 Torque control cannot be performed with a PM motor. 7
10
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
721
Input signals (from the inverter to the master module)
Input signals to the master module are as follows. (Output signals from the inverter)
Device No. Signal Description
0: Other than forward running (during stop or reverse rotation)
RX0 Forward running
1: Forward running
0: Other than reverse running (during stop or forward rotation)
RX1 Reverse running
1: Reverse running
RX2 Running (terminal RUN function)
RX3 Up to frequency (terminal SU function)
RX4 Overload alarm (terminal OL function)
• Functions assigned to terminals RUN, SU, OL, IPF, FU, ABC1 and ABC2 are
Instantaneous power failure (terminal
RX5 activated.
IPF function)
• These signals are set in the initial setting. Using Pr.190 to Pr.196, output
Frequency detection (terminal FU signals assigned to the device numbers can be changed.
RX6
function)
RX7 Error (terminal ABC1 function)
RX8 — (terminal ABC2 function)
RX10 — (DO0 function) • Functions assigned to Pr.313 to Pr.315 are activated.
RX11 — (DO1 function) • No signal is assigned in the initial setting. Use Pr.313 to Pr.315 to assign
RX12 — (DO2 function) signals.
After "1" is set in the monitor command (RY20), and the monitored value is set in
RX20 Monitoring the remote register RWr26 to RWr2F, "1" is set in this signal. When "0" is set in
the monitor command (RY20), "0" is set in this signal.
After "1" is set in the frequency setting command (RY21) and the set frequency is
RX21 Frequency setting completion (RAM) written to the inverter RAM, "1" is set in this signal. When "0" is set in the
frequency setting command (RY21), "0" is set in this signal.
After "1" is set in the frequency setting command (RY22) and the set frequency is
Frequency setting completion (RAM,
RX22 written to the inverter RAM and EEPROM, "1" is set in this signal. When "0" is set
EEPROM)
in the frequency setting command (RY22), "0" is set in this signal.
After "1" is set in the torque command / torque limit (RY23) and the torque
Torque command / torque limit setting command / torque limit value is written to the inverter RAM, "1" is set in this signal.
RX23
completion (RAM) When "0" is set in the torque command / torque limit (RY23), "0" is set in this
signal.
After "1" is set in the torque command / torque limit (RY24) and the torque
Torque command / torque limit setting command / torque limit value is written to the inverter RAM and EEPROM, "1" is
RX24
completion (RAM, EEPROM) set in this signal. When "0" is set in the torque command / torque limit (RY24), "0"
is set in this signal.
After "1" is set in the instruction code execution request (RY25) and the
processes corresponding to the instruction codes (RWw10, 12, 14, 16, 18 and
RX25 Instruction code execution completed
1A) are executed, "1" is set in this signal. When "0" is set in the instruction code
execution request (RY25), "0" is set in this signal.
When an inverter error occurs (protective function is activated), "1" is set in this
RX3A Error status flag
signal.
When the inverter goes into the ready status upon completion of initial setting
after power-on or hardware reset, "1" is set in this signal.
When an inverter error occurs (protective function is activated), "0" is set in this
RX3B Remote station ready
signal.
The signal is used as an interlock during the write to/read from the master
module.
722 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Remote register (from the master module to the inverter)
Device No. Signal Description 1
• Specify the set frequency or rotations per minute (machine speed). At this time, whether
to write to RAM or EEPROM is decided with the RY21 and RY22 settings. After setting
the set frequency in this register, set "1" in RY21 or RY22 to write the frequency. After
RWw0 Set frequency*1*2 writing of frequency is completed, "1" is set in RX21 or RX22 in response to the input 2
command.
• The setting range is 0 to 590.00 Hz (0.01 Hz increments). Write "59000" when setting
590.00 Hz.
Torque command value Specify the torque command value / torque limit value. Set Pr.804 Torque command 3
source selection = "1, 3, 5, or 6" to activate this signal under Real sensorless vector
control, Vector control, and PM sensorless vector control. The value is written to the
RWw2*5 inverter either by RY23 or RY24. Pr.805 Torque command value (RAM) and Pr.806
Torque limit value
Torque command value (RAM, EEPROM) are updated as well. The setting range and
the setting increment depend on the Pr.804 setting. (Refer to page 726.)
4
Set the PID action set point.
RWw4 PID set point*3 Setting range: 0 to 100.00% • Input a value 100 times greater than the value to be
RWw5 PID measured value*3
Set the PID measured value.
Setting range: 0 to 100.00%
set. For example, enter "10000" when setting
100.00%.
5
Set the PID deviation. • Refer to page 570 for details of PID control.
RWw6 PID deviation*3 Setting range: -100.00 to 100.00%
RWw10,
Set an instruction code (refer to page 724) for an operation such as operation mode 6
switching, parameter read/write, error reference, and error clear in the lower eight bits. The
RWw12,
instructions are executed in the following order by setting "1" in RY25 after completing the
RWw14, Link parameter extended
register setting: RWw10, 12, 14, 16, 18, then 1A. After completing the execution up to
RWw16, setting / instruction code
RWw18,
RWw1A, "1" is set in RX25. Set HFFFF to disable an instruction by RWw10 to 1A.
Set the link parameter extended setting in the upper 8 bits.
7
RWw1A
Example) When reading Pr.160, instruction code is H0200.
RWw11, Set the data specified by the instruction code of RWw10, 12, 14, 16, 18 and 1A (when
RWw13,
RWw15,
required).
RWw10 and 11, 12 and 13, 14 and 15, 16 and 17, 18 and 19, and 1A and 1B correspond
8
Write data
RWw17, each other. Set "1" in RY25 after setting the instruction codes (RWw10, 12, 14, 16, 18 and
RWw19, 1A) and the corresponding register.
RWw1B Set "0" when the write data is not required.
Set the individual fault number of the faults history that you want to read. Up to the 8th
9
previous fault can be read.
RWw21 Faults history No.*4 Last two digits: H00 (most recent fault) to H07 (8th most recent fault)
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
723
Remote register (from the inverter to the master module)
Device No. Signal Description
When "1" is set in RY21 or RY22, the following reply codes are set for the frequency setting
command. The setting value "0" is set normally, and a value other than "0" is set at an error.
RWr0 Reply code H0000: Normal
H0001: Write mode fault
H0003: Setting range fault
When "1" is set in RY23 or RY24, the following reply codes are set for the torque command /
torque limit. The setting value "0" is set normally, and a value other than "0" is set at an error.
RWr2 Reply code
H0000: Normal
H0003: Setting range fault
When the PID command (RWw4 to RWw6) is set, the following reply code is set for the PID
RWr4, RWr5, command. The setting value "0" is set normally, and a value other than "0" is set at an error.
Reply code
RWr6 H0000: Normal
H0003: Setting range fault
When "1" is set in RY25, the following reply codes corresponding to the instruction code RWw10,
RWr10,
12, 14, 16, 18, and 1A are set. The setting value "0" is set normally, and a value other than "0" is
RWr12,
set at an error.
RWr14,
Reply code H0000: Normal
RWr16,
H0001: Write mode fault
RWr18,
H0002: Parameter selection fault
RWr1A
H0003: Setting range fault
RWr11,
RWr13,
RWr15,
Read data In a normal reply, a replay code for the instruction code is set.
RWr17,
RWr19,
RWr1B
The setting value "0" is set during normal inverter operation, and the data code of the
RWr20 Error status corresponding error is set at an error. (For the data codes or details of fault records, refer to page
742.)
The data code of faults history No. specified by RWw21 is stored in the lower 8 bits.
RWr21 Fault record (fault data)
Lower 8 bits of RWw21 will be reverted back to the upper 8 bits.
Fault record (output
RWr22 The output frequency of the faults history No. specified in RWw21 is stored.
frequency)
Fault record (output
RWr23 The output current of the faults history No. specified in RWw21 is always stored.
current)
Fault record (output
RWr24 The output voltage of the faults history No. specified in RWw21 is always stored.
voltage)
Fault record
RWr25 The energization time of the faults history No. specified in RWw21 is always stored.
(energization time)
RWr26 First monitor value
RWr27 Second monitor value
RWr28 Third monitor value
RWr29 Fourth monitor value
When "1" is set in RY20, the monitor value specified to the corresponding monitor code (RWw26
RWr2A Fifth monitor value
to RWw2F) is stored.
RWr2B Sixth monitor value
The output frequency, output current, and output voltage monitors are held at an inverter failure.
RWr2C Seventh monitor value
RWr2D Eighth monitor value
RWr2E Ninth monitor value
RWr2F Tenth monitor value
RWr30 to Fixed monitored data are saved regardless of the RY20 setting.
Monitor value
RWr7F The output frequency, output current, and output voltage monitors are held at an inverter failure.
Instruction code
Set instruction codes using the remote register (RWw). (Refer to page 723.)
724 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
The definition read by the instruction code is stored in the remote register (RWr). (Refer to page 724.)
Item
Read/
write
Instruction
code
Data description 1
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
Read H7B
Operation mode
H0002: PU operation mode, External/PU combined operation 1 and 2, PUJOG
operation
2
H0000: Network operation mode
Write HFB H0001: External operation mode
H0002: PU operation mode (Pr.79 = "6", Pr.340 = "10, 12")
H0000 to HFFFF: Output frequency in 0.01Hz increments (The display can be
3
Output frequency*1*2 Read H6F changed to the rotations per minute using Pr.37, Pr.144 and Pr.811. (Refer to page
422.))
Monitor Fault record Read H74 to H77 Fault record display example (instruction code H74)
With the read data H30A0
9
(Last fault : THT)
(Present fault : OPT)
b15 b8 b7 b0
0 0 1 1 0 0 0 0 1 0 1 0 0 0 0 0
10
Last fault Present fault
(H30) (HA0)
(Refer to page 742 for details on fault record read data.)
Set frequency (RAM) H6D Read the set frequency/speed from the RAM or EEPROM.
H0000 to HFFFF: Set frequency in 0.01 Hz increments
Read
Set frequency (EEPROM) H6E (The display can be changed to the rotations per minute using Pr.37, Pr.144, and
Pr.811. (Refer to page 422.))
Set frequency (RAM)*4 Write HED Write the set frequency/speed into the RAM or EEPROM.
H0000 to HE678 (0 to 590.00 Hz): frequency in 0.01 Hz increments
(The display can be changed to the rotations per minute using Pr.37, Pr.144, and
Set frequency (RAM and
Write HEE Pr.811. (Refer to page 422.))
EEPROM)*4 • To change the set frequency consecutively, write data to the inverter RAM.
(Instruction code: HED)
• Refer to the instruction code (page 824) and write and/or read parameter values as
Read H00 to H63 required.
• Write to Pr.77 and Pr.79 is disabled.
Parameter • When setting Pr.100 and later, set the link parameter extended setting.
• Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
Write H80 to HE3 • When changing the parameter values frequently, set "1" in Pr.342 to write them to
the RAM. (Refer to page 630.)
Batch clearing of fault records Write HF4 H9696: Batch clearing of fault records
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
725
Read/ Instruction
Item Data description
write code
All parameters return to initial values.
Whether to clear communication parameters or not can be selected according to the
data.
• Parameter clear
H9696: Communication parameters are cleared.
H5A5A*5: Communication parameters are not cleared.
Parameter clear • All parameter clear
Write HFC
All parameter clear H9966: Communication parameters are cleared.
H55AA*5: Communication parameters are not cleared.
For the details of whether or not to clear parameters, refer to page 824.
When clear is performed with H9696 or H9966, communication related parameter
settings also return to the initial values. When resuming the operation, set the
parameters again. Performing a clear will clear the instruction code HEC, HF3, and
HFF settings.
Inverter reset Write HFD H9696: Resets the inverter.
Read or write of bias and gain parameters (instruction codes H5E to H61 and HDE
Read H6C to HE1 with the link parameter extended setting = "1", H11 to H23 and H91 to HA3
*6
with the link parameter extended setting = "9").
Second parameter changing
H00: Frequency*7
Write HEC H01: Parameter-set analog value
H02: Analog value input from terminal
*1 When "100" is set in Pr.52 Operation panel main monitor selection, set frequency is monitored during a stop and output frequency is monitored
during running.
*2 When position control is selected, the number of pulses is monitored when Pr.430 ≠ "9999".
*3 Write data is in hexadecimal, and only two digits are valid. (The upper two digits are ignored.)
*4 Setting from the remote register (RWw0) is also available.
*5 Turning OFF the power supply while clearing parameters with H5A5A or H55AA returns the communication parameter settings to the initial
settings.
*6 Reading or writing is available when the link parameter extended setting = "1 or 9".
*7 The gain frequency can be also written using Pr.125 (instruction code: H99) or Pr.126 (instruction code: H9A).
NOTE
• When a 32-bit parameter setting or monitored value is read and the read value exceeds HFFFF, the reply data will be HFFFF.
• Relationship between the Pr.804 setting, the setting range, and the actual torque command / torque limit (when setting is
made from CC-Link IE Field Network communication)
Pr.804 setting Setting range Actual torque command Actual torque limit
1, 3 600 to 1400 (1% increments)*1 -400 to 400% 0 to 400%
-32768 to 32767 (two's
5, 6 -327.68 to 327.67% 0 to 327.67%
complement)*1
726 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
• Torque command / torque limit setting method
Setting method Setting procedure
1. Set the torque command / torque limit value in RWw2.
1
Writing in RWw2
2. Set "1" in RY23 (or RY24).
1. Set link parameter extended setting = H08 for RWw10 (12, 14, 16, 18, 1A).
Writing in Pr.805 or Pr.806
2. Set H85 or H86 as the instruction code.
3. Set the torque command / torque limit value in RWw11 (13, 15, 17, 19, 1B).
2
4. Set "1" in RY25.
PLC
Power Master station Input unit Output unit
8
CPU
supply QJ71GF11-T2 QX40 QY40P
Q02UCPU
Q61P-A1 (X/Y00 to 1F) (X20 to X2F) (Y30 to Y3F)
X20 Y30 9
Station 1 Station 2
Inverter Inverter 10
Pr.434 = 1 Pr.434 = 1
Pr.435 = 1 Pr.435 = 2
• In the programming example, network parameters of the master station are set as below. (Network parameters (module 1))
Item Setting condition
Network type CC-Link IE Field (master station)
Start I/O 0000
Network No. 1
Total number of (slave) stations 2
Mode Online (standard mode)
Network configuration Refer to the following.
Refresh parameter Refer to the following.
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
727
• Refresh parameters (assignment method: start/end)
Link side Master side
Device name Start End Device name Start End
SB 0000 01FF SB 0000 01FF
SW 0000 01FF SW 0000 01FF
RX 0000 007F X 1000 107F
RY 0000 007F Y 1000 107F
RWr 0000 00FF W 000000 0000FF
RWw 0000 00FF W 000100 0001FF
• Remote I/O (RX and RY) transmitted between the programmable controller CPU and intelligent device stations
RY3F to RY00
RY3F to RY00
• Remote registers (RWw and RWr) transmitted between the programmable controller CPU and the intelligent device
stations
W17E RWw7E
W17F RWw7F
W180 RWr0
W181 RWr1
W1FE RWr7E
W1FF RWr7F
728 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Programming example for reading the inverter status
The following program turns ON the signal Y00 of the output unit when the station 1 inverter starts running. 1
SB49 SW0B0.0
0 M0 Check the data link status of the station 1
3
M0 X1002
Y30 Turn ON the signal Y00 of the output unit
2
Inverter running (RX02)
6 END
3
X101F X1000
Remote input
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
One
RX3F to RX00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
station
[Inverter status]
4
b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
*1 These signals are assigned in the initial status. Use Pr.190 to Pr.196 and Pr.313 to Pr.315 (Output terminal function
8
selection) to change the output signals.
SB49 SW0B0.0
0 M0 Check the data link status of the station 1.
M0 X20
3 PLS M300
M300
7 SET M301
M301 X1025
9 MOV H0FB W110
Write the operation mode write code (HFB)
to RWw10 and the set data (H0000) to RWw11.
MOV H0 W111
SET M302
M302 X1025 Read the reply code (RWr10) to D2 when the instruction
18 MOV W10 D2 code execution completion (RX25) turns ON.
24 END
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
729
Programming example for setting the operation commands
The following program gives a forward rotation command and middle-speed operation command to the station 1 inverter.
SB49 SW0B0.0
0 M0 Check the data link status of the station 1.
M0 X20
3 Y1000 Forward rotation command (RY00)
7 END
Y100F Y1000
b15 b7 b0
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 RY3F to RY00 One station
[Run command] 1: ON
Middle speed Forward rotation 0: OFF
Run command
b0 : Forward rotation command b6 : Second function selection (RT)∗1
b1 : Reverse rotation command b7 : Terminal 4 input selection (AU)∗1
b2 : High-speed operation command (RH)∗1 b8 : Selection of automatic restart after instantaneous power failure (CS)∗1
b3 : Middle-speed operation command (RM)∗1 b9 : Output stop (MRS)∗1
b4 : Low-speed operation command (RL)∗1 b10 : Start self-holding selection (STOP)∗1
b5 : Jog operation selection (JOG)∗1 b11 : Inverter reset (RES)∗1
*1 These signals are assigned in the initial status. Use Pr.180 to Pr.189 (Input terminal function selection) to change
the input signals. Some signals are not controllable by a command from the programmable controller depending on the
setting.
The following program reads the output frequency of the station 1 inverter to output to D1.
Output frequency read code: H0001 (hexadecimal)
For the monitor codes, refer to page 424.
Example) The output frequency of 60 Hz is indicated as "H1770 (6000)".
SB49 SW0B0.0
0 M0 Check the data link status of the station 1.
M0 X20
3 Set the monitor code (H01) of output frequency
MOV H1 W126
in RWw26.
11 END
730 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to page 724 for the reply code (RWr10).)
0
SB49 SW0B0.0
M0 Check the data link status of the station 1.
1
M0 X20
3 PLS M300
M300
7
M301 X1025
SET M301 2
9 MOV H7 W110 Write the Pr. 7 read code (H07) to RWw10.
RST M301
3
SET M302
M302 X1025
16 MOV W11 D1 Read the acceleration time (RWr11) and the reply code
(RWr10) to output to D1 and D2 when the instruction code 4
MOV W10 D2 execution completion (RX25) turns ON.
RST Y1025 Turn OFF the instruction code execution request (RY25).
RST M302 5
24 END
6
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to page 824 for the settings.
7
Programming example for the parameter writing
The following program changes the setting value in Pr.7 Acceleration time of the station 1 inverter to 3.0 s. 8
• Acceleration time writing instruction code: H87 (hexadecimal)
• Acceleration time setting data: K30 (decimal)
For the details of instruction codes of each parameter, refer to the list of parameters (function codes) and instruction codes 9
under different control modes (on page 824).
The reply code (RWr10) to the instruction code execution is set in D2. (Refer to page 724 for the reply code (RWr10).)
SB49 SW0B0.0
10
0 M0 Check the data link status of the station 1.
M0 X20
3 PLS M300
M300
7 SET M301
M301 X1025
9 MOV H87 W110
Write the Pr. 7 write code (H87) to RWw10 and
the acceleration time setting data (K30) to RWw11.
MOV K30 W111
RST M301
SET M302
M302 X1025 Read the reply code (RWr10) to output to D2 when the
18 MOV W10 D2 instruction code execution completion (RX25) turns ON.
RST Y1025 Turn OFF the instruction code execution request (RY25).
RST M302
24 END
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to page 824 for the settings.
• For other functions, refer to the instruction codes (refer to page 724).
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
731
• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to page 724 for the reply code (RWr0).)
SB49 SW0B0.0
0 M0 Check the data link status of the station 1.
M0 X20
3 PLS M300
M300
7 SET M301
M301 X1021
9 MOV K5000 W100 Write the set frequency to RWw0.
SET M302
M302 X1021 Read the reply code (RWr0) to output to D2 when the
16 MOV W0 D2 frequency setting completion (RX21) turns ON.
22 END
NOTE
• To change the running frequency continuously from a programmable controller, check that the frequency setting complete (for
example, X1021) turns ON, and the reply code from the intelligent register is H0000. Then change the setting data (for
example, W100) continuously.
• To write the running frequency to the EEPROM, change the following points in the program shown above.
- Frequency setting command (from Y1021 to Y1022)
- Frequency setting completion (from X1021 to X1022)
<Timing chart for writing to the RAM> <Timing chart for writing to the EEPROM>
Y1021 Y1022
(∗2)
W100 W100
(∗1)
Inverter Inverter
running running
frequency frequency Apply to the inverter when the command Y1022 turns ON.
*1 To the EEPROM, a writing is performed only once after the command Y1022 turns ON.
*2 If the set data is changed at the command Y1022 ON, the change is not applied to the inverter.
732 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
The reply code (RWr10) to the instruction code execution is set in D2. (Refer to page 724 for the reply code (RWr10).)
SB49 SW0B0.0 1
0 M0 Check the data link status of the station 1.
M0 X20
3 PLS M300
7
M300
SET M301
2
M301 X1025
9 MOV H74 W110 Write the faults history No.1 and No.2 read
code (H74) to RWw10.
SET Y1025 Turn ON the instruction code execution request 3
(RY25).
RST M301
M302 X1025
SET M302
4
16 MOV W11 D1 Read the fault record (RWr11) and the reply code
(RWr10) to output to D1 and D2 when the instruction
MOV W10 D2 code execution completion (RX25) turns ON.
5
RST Y1025 Turn OFF the instruction code execution request
(RY25).
RST M302
24 END
6
0
SB49 SW0B0.0
M0 Check the data link status of the station 1.
8
M0 X103A X20
3 Y103A Turn ON the error reset request flag (RY3A).
Turn OFF the error reset request flag (RY3A)
Error status flag
7 END
when the error status flag (RX3A) is OFF.
9
NOTE 10
• The inverter reset with the flag RY3A shown above is enabled at an inverter fault only.
• When Pr.349 Communication reset selection = "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RY25) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection or change the operation mode to the
Network operation mode. (For the program example, refer to page 729.)
5.21.6 Instructions
Programming instructions
• Since the buffer memory data of the master station is kept transferred (refreshed) to/from the inverters, the TO instruction
need not be executed every scan in response to data write or read requests. (The execution of the TO instruction every
scan does not pose any problem.)
• If the FROM/TO instruction is executed frequently, data may not be written reliably. When transferring data between the
inverter and sequence program via the buffer memory, perform the handshake to confirm that data has been written
without error.
TO instruction TO instruction
Correct Incorrect
Write completion Write completion
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
733
Operating and handling instructions
• The commands only from the programmable controller can be accepted during CC-Link IE Field Network communication.
The run command from external and parameter unit is ignored.
• If multiple inverters have the same station number, the communication cannot be performed properly.
• The inverter protective function (E.OP1) is activated if data communication stops for more than the time set in Pr.500
Communication error execution waiting time due to a programmable controller fault, an open Ethernet cable etc. during
CC-Link IE Field Network operation.
• If the programmable controller (master station) is reset during CC-Link IE Field Network operation or if the programmable
controller is powered off, data communication stops and the inverter protective function (E.OP1) is activated. To reset the
programmable controller (master station), switch the operation mode to the External operation once, then reset the
programmable controller.
• When Pr.340 = "0 (initial value)", any inverter whose main power is restored is reset to return to the External operation
mode. To resume the Network operation, therefore, set the operation mode to the Network operation using the sequence
program. Set a value other than "0" in Pr.340 to start in the Network operation mode after inverter reset.
5.21.7 Troubleshooting
Description Point to be checked
Check for looseness of the connector between the CC-Link IE Field Network communication circuit
board and the inverter's control circuit board. Check that the Ethernet cable is installed correctly. (Check
for contact fault, break in the cable, etc.)
Check that Pr.434 Network number (CC-Link IE) and Pr.435 Station number (CC-Link IE) are
Operation mode does not switch to correctly set. (Check that their settings match with the program, that the network number is set within
the Network operation mode. the range, that no overlapping stations exist, and that the station number is set within the range.)
Check that the inverter is in the External operation mode.
Check that the operation mode switching program is running.
Check that the operation mode switching program has been written correctly.
Check that the inverter starting program is running.
Inverter does not start in the
Check that the inverter starting program has been written correctly.
Network operation mode.
Check that Pr.338 Communication operation command source is not set to External.
734 5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
CHAPTER 6
CHAPTER 6 PROTECTIVE FUNCTIONS
4
10
737
6 PROTECTIVE FUNCTIONS
This chapter explains the "PROTECTIVE FUNCTIONS" that operate in this product.
Always read the instructions before use.
NOTE
• The past eight faults can be displayed on the operation panel. (Faults history) (For the operation, refer to page 740.)
• On the operation panel, press to reset the inverter. (This may only be performed when a fault occurs. (Refer to page
3
751 of the Instruction Manual for faults.))
5
• Switch the power OFF once, then switch it ON again.
ON
6
OFF
• Turn ON the Reset (RES) signal for 0.1 s or more. (If the RES signal is kept ON, "Err" appears (blinks) to indicate that the 7
inverter is in a reset status.)
Inverter
8
RES
SD
9
NOTE
• OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an inverter fault with the start 10
signal ON restarts the motor suddenly.
6. PROTECTIVE FUNCTIONS
6.2 Reset method for the protective functions
739
6.3 Check and clear of the faults history
The operation panel stores the fault indications which appear when a protective function is activated to display the fault record
for the past eight faults. (Faults history)
Blinking Blinking
Faults history 1
Blinking Blinking
Press the
setting dial.
Latest fault
Press the
setting dial.
Month Year
*1 When an overcurrent trip occurs by an instantaneous overcurrent, the monitored current value saved in the faults history may be lower than the
actual current that has flowed.
*2 The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
2
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode. 3
2. Selecting the parameter setting mode
Press to choose the parameter setting mode. (The parameter number read previously appears.) 4
3. Selecting the parameter number
Turn until " " (Fault history clear) appears. Press to read the present set value. " " (initial 5
value) appears.
" " and " " are displayed alternately after parameters are cleared. 7
• Turn to read another parameter.
10
6. PROTECTIVE FUNCTIONS
6.3 Check and clear of the faults history
741
6.4 List of fault displays
If the displayed message does not correspond to any of the Operation panel Refer
Name
following or if you have any other problem, contact your sales indication to page
representative. Home position return uncompleted 750
• A message regarding operational fault and setting fault Continuous operation during 750
communication fault
by the operation panel and the parameter unit is
Load fault warning 750
displayed. The inverter output is not shut off.
Operation panel
Name
Refer Alarm
indication to page
• The inverter output is not shut off. An Alarm (LF) signal
Operation panel lock 745
can also be output with a parameter setting.
Password locked 745
Operation panel Refer
Name
to indication to page
745, Fan alarm 750
Parameter write error
746
Internal fan alarm 751
to
Fault
746, • When a protective function is activated, the inverter
Copy operation fault
747 output is shut off and a Fault (ALM) signal is output.
to
• The data code is used for checking the fault detail via
communication or with Pr.997 Fault initiation.
Error 747
Data code 16 to 199
6. PROTECTIVE FUNCTIONS
6.4 List of fault displays
743
Refer
Operation panel
Name to
indication
page
Operation panel
indication
LOCD 5
Name Password locked
Description Password function is active. Display and setting of parameters are restricted.
Check point -------------- 6
Enter the password in Pr.297 Password lock/unlock to unlock the password function before operating. (Refer to
Corrective action
page 331.)
Operation panel
7
Er1
indication
Name Write disable error
•
•
Parameter setting was attempted while Pr.77 Parameter write selection is set to disable parameter write.
Overlapping range has been set for the frequency jump.
8
Description • Overlapping range has been set for the adjustable 5 points V/F.
• The PU and inverter cannot make normal communication.
•
•
IPM parameter initialization was attempted while Pr.72 PWM frequency selection = "25".
Check the Pr.77 setting. (Refer to page 328.)
9
• Check the settings of Pr.31 to Pr.36 (frequency jump). (Refer to page 408.)
Check point • Check the settings of Pr.100 to Pr.109 (adjustable 5 points V/F). (Refer to page 679.)
•
•
Check the connection of PU and the inverter.
Check the Pr.72 setting. A sine wave filter cannot be used under PM sensorless vector control.
10
Operation panel
Er2
indication
Name Write error during operation
Description Parameter write was attempted while Pr.77 Parameter write selection = "0".
Check point • Check that the inverter is stopped.
• After stopping the operation, make parameter setting.
Corrective action
• When setting Pr.77 = "2", parameter write is enabled during operation. (Refer to page 328.)
Operation panel
Er3
indication
Name Calibration error
Description Analog input bias and gain calibration values have been set too close.
Check point Check the settings of the calibration parameters C3, C4, C6, and C7 (calibration functions). (Refer to page 482.)
Operation panel
Er4
indication
Name Mode designation error
• Parameter setting was attempted in the External or NET operation mode while Pr.77 Parameter write selection
Description = "1".
• Parameter write was attempted when the command source is not at the operation panel (FR-DU08).
• Check that the operation mode is the PU operation mode.
Check point
• Check that the Pr.551 PU mode operation command source selection setting is correct.
• After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to page 370.)
Corrective action • When Pr.77 = "2", parameter write is enabled regardless of the operation mode. (Refer to page 328.)
• Set Pr.551 = "2". (Refer to page 380.)
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
745
Operation panel
Er8
indication
Name USB memory device operation error
• An operation command was given during the USB memory device operation.
Description • A copy operation (writing) was performed while the PLC function was in the RUN state.
• A copy operation was attempted for a password locked project.
• Check if the USB memory device is operating.
Check point • Check if the PLC function is in the RUN state.
• Check if the project data is locked with a password.
• Perform the operation after the USB memory device operation is completed.
• Stop the PLC function. (Refer to page 614 and the PLC function programming manual.)
Corrective action
• Unlock the password of the project data using FR Configurator2. (Refer to the Instruction Manuals of FR
Configurator2 and GX Works2.)
Operation panel
rE1
indication
Name Parameter read error
• A failure has occurred at the operation panel side EEPROM while reading the copied parameters.
Description • A failure has occurred in the USB memory device while copying the parameters or reading the PLC function
project data.
Check point • --------------
• Perform parameter copy again. (Refer to page 708 and page 711.)
• Perform PLC function project data copy again. (Refer to page 614.)
Corrective action
• The USB memory device may be faulty. Replace the USB memory device.
• The operation panel (FR-DU08) may be faulty. Contact your sales representative.
Operation panel
rE2
indication
Name Parameter write error
• Parameter copy from the operation panel to the inverter was attempted during operation.
• A failure has occurred at the operation panel side EEPROM while writing the copied parameters.
Description
• A failure has occurred in the USB memory device while writing the copied parameters or PLC function project
data.
Check point • Check that the inverter is stopped.
• After stopping the operation, perform parameter copy again. (Refer to page 708.)
• The operation panel (FR-DU08) may be faulty. Contact your sales representative.
Corrective action
• Perform parameter copy or PLC project data copy again. (Refer to page 614 and page 711.)
• The USB memory device may be faulty. Replace the USB memory device.
Operation panel
rE3
indication
Name Parameter verification error
• The data in the inverter are different from the data in the operation panel.
• A failure has occurred at the operation panel side EEPROM during parameter verification.
Description • A failure has occurred in the USB memory device during parameter verification.
• The data in the inverter are different from the data in the USB memory device or the personal computer (FR
Configurator2).
Check point • Check the parameter setting of the source inverter against the setting of the destination inverter.
Operation panel
4
rE6
indication
Name File error
Description
• The parameter copy file in the USB memory device cannot be recognized.
• An error has occurred in the file system during transfer of the PLC function data or writing to RAM.
5
Check point • --------------
• Perform parameter copy again. (Refer to page 711.)
Corrective action
• Copy the PLC function project data again. (Refer to page 614.) 6
Operation panel
rE7
indication
Name File quantity error 7
• A parameter copy was attempted to the USB memory device in which the copy files from 001 to 099 had already
Description
been saved.
Check point
Corrective action
• Check if the number of copy files in the USB memory device has reached 99.
• Delete the copy file in the USB memory device and perform parameter copy again. (Refer to page 711.)
8
Operation panel
indication
rE8
9
Name No PLC function project file
Description The specified PLC function project file does not exist in the USB memory device.
Check point
• Check that the file exists in the USB memory device.
• Check that the folder name and the file name in the USB memory device is correct. 10
Corrective action The data in the USB memory device may be damaged.
Operation panel
Err.
indication
• The RES signal is turned ON.
• The operation panel and inverter cannot make normal communication (contact faults of the connector).
Description • This error may occur when the voltage at the input side of the inverter drops.
• When using a separate power source for the control circuit power (R1/L11, S1/L21) from the main circuit power
(R/L1, S/L2, T/L3), this error may appear at turning ON of the main circuit. It is not a fault.
• Turn OFF the RES signal.
Corrective action • Check the connection between the operation panel and the inverter.
• Check the voltage on the input side of the inverter.
Warning
Output is not shut off when a protective function is activated.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
747
Operation panel
OL FR-LU08 indication OL
indication
Name Stall prevention (overcurrent)
• When the output current of the inverter increases, the stall prevention (overcurrent) function is activated.
• The following section explains about the stall prevention (overcurrent) function.
When the output current (output torque under Real sensorless vector control or Vector
control) of the inverter exceeds the stall prevention level (Pr.22 Stall prevention
operation level, etc.), this function stops the increase in frequency until the overload
During acceleration
current decreases to prevent the inverter from resulting in overcurrent trip. When the
overload current is reduced below stall prevention operation level, this function increases
the frequency again.
When the output current (output torque under Real sensorless vector control or Vector
Description control) of the inverter exceeds the stall prevention level (Pr.22 Stall prevention
During constant- operation level, etc.), this function reduces frequency until the overload current
speed operation decreases to prevent the inverter from resulting in overcurrent trip. When the overload
current is reduced below stall prevention operation level, this function increases the
frequency up to the set value.
When the output current (output torque under Real sensorless vector control or Vector
control) of the inverter exceeds the stall prevention level (Pr.22 Stall prevention
operation level, etc.), this function stops the decrease in frequency until the overload
During deceleration
current decreases to prevent the inverter from resulting in overcurrent trip. When the
overload current is reduced below stall prevention operation level, this function decreases
the frequency again.
• Check that the Pr.0 Torque boost setting is not too large.
• The Pr.7 Acceleration time and Pr.8 Deceleration time settings may be too short.
• Check that the load is not too heavy.
Check point
• Check for any failures in peripheral devices.
• Check that the Pr.13 Starting frequency is not too large.
• Check that Pr.22 Stall prevention operation level is appropriate.
• Gradually increase or decrease the Pr.0 setting by 1% at a time and check the motor status. (Refer to page
672.)
• Set a larger value in Pr.7 and Pr.8. (Refer to page 349.)
• Reduce the load.
• Try Advanced magnetic flux vector control, Real sensorless vector control, or Vector control.
Corrective action
• Change the Pr.14 Load pattern selection setting.
• The stall prevention operation current can be set in Pr.22 Stall prevention operation level. (Initial value is
150%.) The acceleration/deceleration time may change. Increase the stall prevention operation level with Pr.22
Stall prevention operation level, or disable stall prevention with Pr.156 Stall prevention operation
selection. (Use Pr.156 to set either operation continued or not at OL operation.)
Operation panel
oL FR-LU08 indication oL
indication
Name Stall prevention (overvoltage)
• When the output voltage of the inverter increases, the stall prevention (overvoltage) function is activated.
• The regeneration avoidance function is activated due to excessive regenerative power of the motor. (Refer to
page 696.)
Description • The following section explains the stall prevention (overvoltage) function.
If the regenerative power of the motor becomes excessive to exceed the regenerative
During deceleration power consumption capability, this function stops decreasing the frequency to prevent
overvoltage trip. As soon as the regenerative power has reduced, deceleration resumes.
• Check for sudden speed reduction.
Check point
• Check if the regeneration avoidance function (Pr.882 to Pr.886) is being used. (Refer to page 696.)
Corrective action The deceleration time may change. Increase the deceleration time using Pr.8 Deceleration time.
Operation panel
RB FR-LU08 indication RB
indication
Name Regenerative brake pre-alarm (Standard models only)
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr.70 Special regenerative brake duty
Description
value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV[ ]) occurs.
• Check if the brake resistor duty is not too high.
Check point
• Check that the Pr.30 Regenerative function selection and Pr.70 settings are correct.
• Set the deceleration time longer.
Corrective action
• Check the Pr.30 and Pr.70 settings. (Refer to page 689.)
Corrective action
• Decrease the torque command value. 9
• Increase the speed limit level.
Operation panel
indication
CP FR-LU08 indication CP 10
Name Parameter copy
Appears when parameter copy is performed between the FR-A820-03160(55K) or lower / FR-A840-01800(55K)
Description
or lower inverters and the FR-A820-03800(75K) or higher / FR-A840-02160(75K) or higher inverters.
Resetting of Pr.9, Pr.30, Pr.51, Pr.56, Pr.57, Pr.61, Pr.70, Pr.72, Pr.80, Pr.82, Pr.90 to Pr.94, Pr.453, Pr.455,
Check point
Pr.458 to Pr.462, Pr.557, Pr.859, Pr.860 to Pr.462, Pr.557, Pr.859, Pr.860 and Pr.893 is necessary.
Corrective action Set the initial value in Pr.989 Parameter copy alarm release.
Operation panel
SA FR-LU08 indication —
indication
Name Safety stop
Description Appears when safety stop function is activated (during output shutoff). (Refer to page 80.)
• Check if an emergency stop device is activated.
Check point • Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not using the safety
stop function.
• An emergency stop device is active when using the safety stop function. Identify the cause of emergency stop,
ensure the safety and restart the system.
• When not using the safety stop function, short across terminals S1 and PC and across S2 and PC with shorting
Corrective action wire for the inverter to run.
• If " " is indicated when wires across S1 and SIC and across S2 and SIC are both conducted while using
the safety stop function (drive enabled), internal failure might be the cause. Check the wiring of terminals S1,
S2, and SIC and contact your sales representative if the wiring has no fault.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
749
to
Operation panel
MT1 to MT3 FR-LU08 indication MT1 to MT3
indication
Operation panel
UF FR-LU08 indication UF
indication
Name USB host error
Description Appears when an excessive current flows into the USB A connector.
Check point Check if a USB device other than a USB memory device is connected to the USB A connector.
• If a device other than a USB memory device is connected to the USB A connector, remove the device.
Corrective action
• Setting Pr.1049 USB host reset = "1" or inverter reset clears the UF indication.
to
Operation panel
HP1 to HP3 FR-LU08 indication HP1 to HP3
indication
Operation panel
CF FR-LU08 indication CF
indication
Name Continuous operation during communication fault
Appears when the operation continues while an error is occurring in the communication line or communication
Description
option (when Pr.502 = "4").
• Check for a break in the communication cable.
Check point
• Check for communication option faults.
• Check the connection of communication cable.
Corrective action
• Replace the communication option.
Operation panel
LDF FR-LU08 indication LDF
indication
Name Load fault warning
Appears when the load is deviated from the detection width set in Pr.1488 Upper limit warning detection width
Description
or Pr.1489 Lower limit warning detection width.
• Check if too much load is applied to the equipment, or if the load is too light.
Check point
• Check that the load characteristics settings are correct.
• Inspect the equipment.
Corrective action
• Set the load characteristics (Pr.1481 to Pr.1487) correctly.
Alarm
Output is not shut off when a protective function is activated. An Alarm signal can also be output with a parameter setting.
(Set "98" in Pr.190 to Pr.196 (Output terminal function selection). Refer to page 450.)
Operation panel
FN FR-LU08 indication FN
indication
Name Fan alarm
For the inverter that contains a cooling fan, FN appears on the operation panel when the cooling fan stops due
Description
to a fault, low rotation speed, or different operation from the setting of Pr.244 Cooling fan operation selection.
Check point Check the cooling fan for a failure.
Corrective action The fan may be faulty. Contact your sales representative.
•
during torque control under Real sensorless vector control.
Check that the inverter capacity matches with the motor capacity. (PM sensorless vector control)
8
• Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
• Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)
• If "E.OC1" always appears at start, disconnect the motor once and restart the inverter. If "E.OC1" still appears,
contact your sales representative.
9
• Check the wiring to make sure that output short circuit does not occur.
• Set 50 Hz in Pr.3 Base frequency. (Refer to page 673.)
• Lower the stall prevention operation level. Activate the fast-response current limit operation. (Refer to page
409.) 10
• Set the base voltage (rated voltage of the motor, etc.) in Pr.19 Base frequency voltage. (Refer to page 673.)
Corrective action
• Check RS-485 terminal connection (under Vector control).
• Check the wiring and specifications of the encoder and the motor. Perform the setting according to the
specifications of the encoder and the motor (under vector control). (Refer to page 86.)
• Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward)
during torque control under Real sensorless vector control.
• Choose inverter and motor capacities that match. (PM sensorless vector control)
• Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power
failure/flying start function. (Refer to page 604.) (PM sensorless vector control)
*1 Differs according to ratings. The rating can be changed using Pr.570 Multiple rating setting. (Refer to page 326.)
148% for SLD rating,170% for LD rating, 235% for ND rating (initial setting), and 280% for HD rating
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
751
Operation panel Overcurrent trip during constant
E.OC2 FR-LU08 indication
indication speed
Name Overcurrent trip during constant speed
Description When the inverter output current reaches or exceeds approximately 235%*2 of the rated current during constant-
speed operation, the protection circuit is activated and the inverter output is shut off.
• Check for sudden load change.
• Check for a short-circuit in the output circuit.
• Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is
disabled.
Check point • Check that the power supply for RS-485 terminal is not shorted (under Vector control).
• Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to forward)
during torque control under Real sensorless vector control.
• Check that the inverter capacity matches with the motor capacity. (PM sensorless vector control)
• Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
• Keep the load stable.
• Check the wiring to make sure that output short circuit does not occur.
• Lower the stall prevention operation level. Activate the fast-response current limit operation. (Refer to page
409.)
• Check RS-485 terminal connection (under Vector control).
Corrective action
• Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward)
during torque control under Real sensorless vector control.
• Choose inverter and motor capacities that match. (PM sensorless vector control)
• Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power
failure/flying start function. (Refer to page 604.) (PM sensorless vector control)
*2 Differs according to ratings. The rating can be changed using Pr.570 Multiple rating setting. (Refer to page 326.)
148% for SLD rating,170% for LD rating, 235% for ND rating (initial setting), and 280% for HD rating
Operation panel
E.OC3 FR-LU08 indication OC During Dec
indication
Name Overcurrent trip during deceleration or stop
When the inverter output current reaches or exceeds approximately 235%*3 of the rated current during
Description deceleration (other than acceleration or constant speed), the protection circuit is activated and the inverter output
is shut off.
• Check for sudden speed reduction.
• Check for a short-circuit in the output circuit.
• Check for too fast operation of the motor's mechanical brake.
• Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is
disabled.
Check point
• Check that the power supply for RS-485 terminal is not shorted (under Vector control).
• Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to forward)
during torque control under Real sensorless vector control.
• Check that the inverter capacity matches with the motor capacity. (PM sensorless vector control)
• Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
• Set the deceleration time longer.
• Check the wiring to make sure that output short circuit does not occur.
• Check the mechanical brake operation.
• Lower the stall prevention operation level. Activate the fast-response current limit operation. (Refer to page
409.)
Corrective action • Check RS-485 terminal connection (under Vector control).
• Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward)
during torque control under Real sensorless vector control.
• Choose inverter and motor capacities that match. (PM sensorless vector control)
• Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power
failure/flying start function. (Refer to page 604.) (PM sensorless vector control)
*3 Differs according to ratings. The rating can be changed using Pr.570 Multiple rating setting. (Refer to page 326.)
148% for SLD rating,170% for LD rating, 235% for ND rating (initial setting), and 280% for HD rating
Operation panel
9
E.OV3 FR-LU08 indication OV During Acc
indication
Name Regenerative overvoltage trip during deceleration or stop
Description
If regenerative power causes the inverter's internal main circuit DC voltage to reach or exceed the specified
value, the protection circuit is activated to stop the inverter output. The circuit may also be activated by a surge
10
voltage produced in the power supply system.
• Check for sudden speed reduction.
Check point
• Check if the stall prevention operation is frequently activated in an application with a large load inertia.
• Set the deceleration time longer. (Set the deceleration time which matches the moment of inertia of the load.)
• Make the brake cycle longer.
Corrective action • Use the regeneration avoidance function (Pr.882 to Pr.886). (Refer to page 696.)
• Use the brake unit or power regeneration common converter (FR-CV) as required.
• Set Pr.154 Voltage reduction selection during stall prevention operation = "10 or 11". (Refer to page 409.)
Operation panel
E.THT FR-LU08 indication Inv. Overload
indication
Name Inverter overload trip (Electronic thermal O/L relay)*4
If the temperature of the output transistor elements exceeds the protection level with a rated output current or
Description
higher flowing without the overcurrent trip (E.OC[]), the inverter output is stopped. (Overload capacity 150% 60 s)
• Check that acceleration/deceleration time is not too short.
• Check that torque boost setting is not too large (small).
• Check that load pattern selection setting is appropriate for the load pattern of the using machine.
Check point
• Check the motor for the use under overload.
• Check that the encoder wiring and the specifications (encoder power supply, resolution, differential/
complementary) are correct. Check also that the motor wiring (U, V, W) is correct (under Vector control).
• Set the acceleration/deceleration time longer.
• Adjust the torque boost setting.
• Set the load pattern selection setting according to the load pattern of the using machine.
Corrective action
• Reduce the load.
• Check the wiring and specifications of the encoder and the motor. Perform the setting according to the
specifications of the encoder and the motor (under vector control). (Refer to page 86.)
*4 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal O/L relay function.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
753
Operation panel
E.THM FR-LU08 indication Motor Ovrload
indication
Name Inverter overload trip (Electronic thermal O/L relay)*5
The electronic thermal O/L relay function in the inverter detects motor overheat, which is caused by overload or
reduced cooling capability during low-speed operation. When the cumulative heat value reaches 85% of the Pr.9
Electronic thermal O/L relay setting, pre-alarm (TH) is output. When the accumulated value reaches the
Description
specified value, the protection circuit is activated to stop the inverter output. When the inverter is used to drive a
dedicated motor, such as a multiple-pole motor, or several motors, the motor cannot be protected by the
electronic thermal O/L relay. Install an external thermal relay on the inverter output side.
• Check the motor for the use under overload.
Check point • Check that the setting of Pr.71 Applied motor for motor selection is correct. (Refer to page 505.)
• Check that the stall prevention operation setting is correct.
• Reduce the load.
Corrective action • For a constant-torque motor, set the constant-torque motor in Pr.71.
• Set the stall prevention operation level accordingly. (Refer to page 409.)
*5 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal O/L relay function.
Operation panel
E.FIN FR-LU08 indication H/Sink O/Temp
indication
Name Heatsink overheat
When the heatsink overheats, the temperature sensor is activated, and the inverter output is stopped.
The FIN signal can be output when the temperature becomes approximately 85% of the heatsink overheat
Description protection operation temperature.
For the terminal used for the FIN signal output, assign the function by setting "26 (positive logic) or 126 (negative
logic)" from Pr.190 to Pr.196 (output terminal function selection). (Refer to page 450.)
• Check for too high surrounding air temperature.
Check point • Check for heatsink clogging.
• Check that the cooling fan is not stopped. (Check that FN is not displayed on the operation panel.)
• Set the surrounding air temperature to within the specifications.
Corrective action • Clean the heatsink.
• Replace the cooling fan.
Operation panel
E.IPF FR-LU08 indication Instantaneous power failure
indication
Name Instantaneous power failure (Standard models and IP55 compatible models only)
If a power failure occurs (or when power input to the inverter is shut off) for longer than 15 ms*6, the
instantaneous power failure protective function is activated to shut off the inverter output in order to prevent the
control circuit from malfunctioning. If a power failure persists for 100 ms or longer, the fault warning output is not
provided, and the inverter restarts if the start signal is ON upon power restoration. (The inverter continues
Description operating if an instantaneous power failure is within 15 ms*6.) In some operating status (load magnitude,
acceleration/deceleration time setting, etc.), overcurrent or other protection may be activated upon power
restoration.
When instantaneous power failure protection is activated, the IPF signal is output. (Refer to page 597 and page
604.)
Check point Find the cause of instantaneous power failure occurrence.
• Remedy the instantaneous power failure.
• Prepare a backup power supply for instantaneous power failure.
Corrective action
• Set the function of automatic restart after instantaneous power failure (Pr.57). (Refer to page 597 and page
604.)
*6 10 ms for IP55 compatible models
Operation panel
E.UVT FR-LU08 indication Under Voltage
indication
Name Undervoltage (Standard models and IP55 compatible models only)
If the power supply voltage of the inverter decreases, the control circuit will not perform normal functions. In
addition, the motor torque will be insufficient and/or heat generation will increase. To prevent this, if the power
supply voltage decreases to about 150 VAC (300 VAC for the 400 V class) or below, this function shuts off the
Description
inverter output.
When a jumper is not connected across P/+ and P1, the undervoltage protective function is activated.
When undervoltage protection is activated, the IPF signal is output. (Refer to page 597 and page 604.)
• Check if a high-capacity motor is driven.
Check point
• Check if the jumper is connected across terminals P/+ and P1.
• Check the devices on the power supply line such as the power supply itself.
Corrective action • Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor.
• If the problem still persists after taking the above measure, contact your sales representative.
Operation panel
E.LUP FR-LU08 indication Upper limit fault detection
indication
Name Upper limit fault detection
The inverter output is shut off when the load exceeds the upper limit fault detection range. This protective
Description
function is not available in the initial setting of Pr.1490 (Pr.1490 = "9999").
• Check if too much load is applied to the equipment.
Check point
• Check that the load characteristics settings are correct.
• Inspect the equipment.
Corrective action
• Set the load characteristics (Pr.1481 to Pr.1487) correctly.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
755
Operation panel
E.LDN FR-LU08 indication Lower limit fault detection
indication
Name Lower limit fault detection
The inverter output is shut off when the load falls below the lower limit fault detection range. This protective
Description
function is not available in the initial setting of Pr.1491 (Pr.1491 = "9999").
• Check if the equipment load is too light.
Check point
• Check that the load characteristics settings are correct.
• Inspect the equipment.
Corrective action
• Set the load characteristics (Pr.1481 to Pr.1487) correctly.
Operation panel
E.BE FR-LU08 indication Br. Cct. Fault
indication
Name Brake transistor alarm detection
• The inverter output is shut off if a fault due to damage of the brake transistor and such occurs in the brake
circuit.
Description
In such a case, the power supply to the inverter must be shut off immediately.
• Appears when an internal circuit fault occurred for separated converter types and IP55 compatible models.
• Reduce the load inertia.
Check point
• Check that the brake duty is proper.
Corrective action Replace the inverter.
Operation panel
E.GF FR-LU08 indication Ground Fault
indication
Name Output side earth (ground) fault overcurrent
The inverter output is shut off if an earth (ground) fault overcurrent flows due to an earth (ground) fault that
Description
occurred on the inverter's output side (load side).
Check point Check for a ground fault in the motor and connection cable.
Corrective action Remedy the earth (ground) fault portion.
Operation panel
E.LF FR-LU08 indication Output phase loss
indication
Name Output phase loss
Description The inverter output is shut off if one of the three phases (U, V, W) on the inverter's output side (load side) is lost.
• Check the wiring. (Check that the motor is normally operating.)
Check point • Check that the capacity of the motor used is not smaller than that of the inverter.
• Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
• Wire the cables properly.
Corrective action • Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power
failure/flying start function (page 604). (PM sensorless vector control)
Operation panel
E.OHT FR-LU08 indication Ext TH relay oper
indication
Name External thermal relay operation
The inverter output is shut off if the external thermal relay provided for motor overheat protection or the internally
mounted thermal relay in the motor, etc. switches ON (contacts open). This function is available when "7" (OH
Description
signal) is set in any of Pr.178 to Pr.189 (Input terminal function selection). This protective function is not
available in the initial status. (OH signal is not assigned.)
• Check for motor overheating.
Check point • Check that the value "7" (OH signal) is set correctly to any of Pr.178 to Pr.189 (Input terminal function
selection).
• Reduce the load and operation duty.
Corrective action
• Even if the relay contacts are reset automatically, the inverter will not restart unless it is reset.
Operation panel
E.OPT FR-LU08 indication Option Fault
4
indication
Name Option fault
• Appears when the AC power supply is connected to terminal R/L1, S/L2, or T/L3 accidentally when a high
power factor converter (FR-HC2) or power regeneration common converter (FR-CV) is connected (when Pr.30 5
Regenerative function selection = "2").
• Appears when torque command by the plug-in option is selected using Pr.804 Torque command source
Description selection and no plug-in option is mounted. This function is available under torque control.
• Appears when either one of a Vector control compatible plug-in option or a control terminal option (FR-A8TP) 6
is not installed during machine end orientation control.
• Appears when the switch for manufacturer setting of the plug-in option is changed.
• Appears when a communication option is connected while Pr.296 Password lock level = "0 or 100".
• Check that the AC power supply is not connected to terminal R/L1, S/L2, or T/L3 when a high power factor 7
converter (FR-HC2) or power regeneration common converter (FR-CV) is connected (when Pr.30 = "2").
• Check that the plug-in option for torque command setting is connected.
Check point
• Check that the Vector control plug-in option and the control terminal option (FR-A8TP) are installed correctly.
Check that the Pr.393 Orientation selection and Pr.862 Encoder option selection settings are correct.
• Check for the password lock with a setting of Pr.296 = "0, 100".
8
• Check the Pr.30 setting and wiring.
• The inverter may be damaged if the AC power supply is connected to terminal R/L1, S/L2, or T/L3 when a high
power factor converter is connected. Contact your sales representative.
• Check for connection of the plug-in option. Check the Pr.804 setting.
9
Corrective action • Install the Vector control plug-in option and the control terminal option (FR-A8TP) correctly. Set Pr.393 and
Pr.862 correctly. (Refer to page 554.)
• Set the switch on the plug-in option, which is for manufacturer setting, back to the initial setting. (Refer to the
Instruction Manual of each option.) 10
• To apply the password lock when installing a communication option, set Pr.296 ≠ "0, 100". (Refer to page 331.)
Operation panel to
E.OP1 to E.OP3 FR-LU08 indication Option1 Fault to Option3 Fault
indication
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
757
Operation panel to
E.16 to E.20 FR-LU08 indication Fault 16 to Fault 20
indication
Operation panel
E.PE FR-LU08 indication Corrupt Memory
indication
Name Parameter storage device fault
Description The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)
Check point Check for too many number of parameter write times.
Contact your sales representative.
Set "1" in Pr.342 Communication EEPROM write selection (write to RAM) for the operation which requires
Corrective action
frequent parameter writing via communication, etc. Note that writing to RAM goes back to the initial status at
power OFF.
Operation panel
E.PUE FR-LU08 indication PU disconnection
indication
Name PU disconnection
• The inverter output is shut off if communication between the inverter and PU is suspended, e.g. the operation
panel or parameter unit is disconnected, when the disconnected PU disconnection function is valid in Pr.75
Reset selection/disconnected PU detection/PU stop selection.
Description • The inverter output is shut off if communication errors occurred consecutively for more than permissible
number of retries when Pr.121 PU communication retry count ≠ "9999" during the RS-485 communication.
• The inverter output is shut off if communication is broken within the period of time set in Pr.122 PU
communication check time interval during the RS-485 communication via the PU connector.
• Check that the operation panel or the parameter unit is connected properly.
Check point
• Check the Pr.75 setting.
Corrective action Fit the operation panel or the parameter unit securely.
Operation panel
E.RET FR-LU08 indication Retry count excess
indication
Name Retry count excess
The inverter output is shut off if the operation cannot be resumed properly within the number of retries set in Pr.67
Description Number of retries at fault occurrence. This function is available when Pr.67 is set. This protective function is
not available in the initial setting (Pr.67 = "0").
Check point Find the cause of the fault occurrence.
Corrective action Eliminate the cause of the fault preceding this fault indication.
Operation panel
E.PE2 FR-LU08 indication PR storage alarm
indication
Name Parameter storage device fault
Description The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)
Check point ――――
Corrective action Contact your sales representative.
Check point
• Check for a short circuit in the PC terminal output. 10
• Check that the 24 V external power supply voltage is correct.
• Repair the short-circuited portion.
• Supply the power at 24 V. (If the power with insufficient voltage is supplied to the 24 V input circuit for a long
Corrective action
time, the inverter internal circuit may heats up. Although it will not damage the inverter, supply power at the
correct voltage .)
Operation panel
E.CDO FR-LU08 indication OC detect level
indication
Name Abnormal output current detection
The inverter output is shut off if the output current exceeds the Pr.150 Output current detection level setting.
Description This functions is available when "1" is set in Pr.167 Output current detection operation selection. When the
initial value (Pr.167 = "0") is set, this protective function is not available.
Check the settings of Pr.150, Pr.151 Output current detection signal delay time, Pr.166 Output current
Check point
detection signal retention time, and Pr.167. (Refer to page 464.)
Operation panel
E.IOH FR-LU08 indication Inrush overheat
indication
Name Inrush current limit circuit fault (Standard models and IP55 compatible models only)
The inverter output is shut off when the resistor of the inrush current limit circuit is overheated. The inrush current
Description
limit circuit is faulty.
• Check that frequent power ON/OFF is not repeated.
• Check if the input side fuse (5A) in the power supply circuit of the inrush current limit circuit contactor (FR-A840-
Check point
03250(110K) or higher) is blown.
• Check that the power supply circuit of inrush current limit circuit contactor is not damaged.
Configure a circuit where frequent power ON/OFF is not repeated.
Corrective action
If the problem still persists after taking the above measure, contact your sales representative.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
759
Operation panel
E.SER FR-LU08 indication VFD Comm error
indication
Name Communication fault (inverter)
The inverter output is shut off when communication error occurs consecutively for the permissible number of
retries or more when Pr.335 RS-485 communication retry count ≠ "9999" during RS-485 communication
Description
through the RS-485 terminals. The inverter output is also shut off if communication is broken for the period of
time set in Pr.336 RS-485 communication check time interval.
Check point Check the RS-485 terminal wiring.
Corrective action Perform wiring of the RS-485 terminals properly.
Operation panel
E.AIE FR-LU08 indication Analog input fault
indication
Name Analog input fault
The inverter output is shut off when a 30 mA or higher current or a 7.5 V or higher voltage is input to terminal 2
Description while the current input is selected by Pr.73 Analog input selection, or to terminal 4 while the current input is
selected by Pr.267 Terminal 4 input selection.
Check point Check the Pr.73, Pr.267, and the voltage/current input switch settings. (Refer to page 473.)
Either give a current less than 30 mA, or set Pr.73, Pr.267, and the voltage/current input switch to the voltage
Corrective action
input and input a voltage.
Operation panel
E.USB FR-LU08 indication USB comm error
indication
Name USB communication fault
The inverter output is shut off when the communication is cut off for the time set in Pr.548 USB communication
Description
check time interval.
Check point • Check that the USB communication cable is connected securely.
• Check the Pr.548 setting.
Corrective action • Connect the USB communication cable securely.
• Increase the Pr.548 setting or set "9999." (Refer to page 666.)
Operation panel
E.SAF FR-LU08 indication safety circuit fault
indication
Name Safety circuit fault
• The inverter output is shut off when a safety circuit fault occurs.
• The inverter output is shut off if the either of the wire between S1 and SIC or S2 and SIC becomes non-
Description conductive while using the safety stop function.
• When the safety stop function is not used, the inverter output is shut off when the shorting wire between
terminals S1 and PC or across S2 and PC is disconnected.
• Check that the safety relay module or the connection has no fault when using the safety stop function.
Check point • Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not using the safety
stop function.
• When using the safety stop function, check that wiring of terminal S1, S2 and SIC is correct and the safety stop
input signal source such as a safety relay module is operating properly. Refer to the Safety Stop Function
Corrective action Instruction Manual for causes and countermeasures. (Contact your sales representative for the manual.)
• When the safety stop function is not used, short across terminals S1 and PC and across S2 and PC with
shorting wires. (Refer to page 80.)
Corrective action
• Set the Pr.374 correctly. 3
• Set Pr.369 (Pr.851) correctly. (Under encoder feedback control or vector control)
Operation panel
indication
E.OSD
Vector
FR-LU08 indication Spd deviation fault 4
Name Speed deviation excess detection
• The inverter output is shut off if the motor speed is increased or decreased under the influence of the load etc.
during Vector control with Pr.285 Overspeed detection frequency set and cannot be controlled in accordance 5
Description with the speed command value.
• If the motor is accelerated against the stop command accidentally, the deceleration check function (Pr.690) is
activated to stop the inverter output.
• Check that the settings of Pr.285 and Pr.853 Speed deviation time are correct. 6
• Check for sudden load change.
Check point
• Check that the setting of Pr.369 (Pr.851) Number of encoder pulses does not differ from the actual number
of encoder pulses.
• Set Pr.285 and Pr.853 correctly. 7
Corrective action • Keep the load stable.
• Set Pr.369 (Pr.851) correctly.
Operation panel
E.ECT FR-LU08 indication Encoder signal loss
8
indication
Name Signal loss detection
Description
The inverter output is shut off when the encoder signal is shut off under orientation control, encoder feedback
control or vector control. This protective function is not available in the initial status. 9
• Check for the encoder signal loss.
• Check that the encoder specifications are correct.
• Check for a loose connector.
Check point • Check that the switch setting of a Vector control compatible option is correct. 10
• Check that the power is supplied to the encoder. Alternatively, check that the power is not supplied to the
encoder later than the inverter.
• Check that the voltage of the power supplied to the encoder is the same as the encoder output voltage.
• Remedy the signal loss.
• Use an encoder that meets the specifications.
• Make connection securely.
• Make a switch setting of a Vector control compatible option correctly. (Refer to page 87.)
• Supply the power to the encoder. Or supply the power to the encoder at the same time when the power is
Corrective action
supplied to the inverter.
If the power is supplied to the encoder after sent to the inverter, check that the encoder signal is properly sent
and set "0 (initial value)" in Pr.376 Encoder signal loss detection enable/disable selection to disable signal
loss detection.
• Make the voltage of the power supplied to the encoder the same as the encoder output voltage.
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
761
to
Operation panel
E.MB1 to 7 FR-LU08 indication E.MB1 Fault to E.MB7 Fault
indication
Operation panel
E.IAH FR-LU08 indication Abnormal Intnl Temp
indication
Name Abnormal internal temperature (Standard models and IP55 compatible models only)
Description The inverter output is shut off when the inverter internal temperature reaches the specified value or higher.
• Check for too high surrounding air temperature.
Check point
• Check if the internal air circulation fan or the cooling fan stops due to a fault.
• Install an inverter suitable for the installation environment. (Refer to the Instruction Manual (Hardware) of the
Corrective action FR-A806.)
• Replace the internal air circulation fan or the cooling fan.
Operation panel
E.LCI FR-LU08 indication 4 mA input fault
indication
Name 4 mA input fault
The inverter output is shut off when the analog input current is 2 mA or less for the time set in Pr.778 4 mA input
Description check filter. This function is available when Pr.573 4 mA input check selection = "2 or 3". (Refer to page 492.)
This protective function is not available in the initial status.
• Check for a break in the wiring for the analog current input.
Check point
• Check that the Pr.778 setting is not too short.
• Check the wiring for the analog current input.
Corrective action
• Set the Pr.778 setting larger.
Operation panel
indication
E.PID FR-LU08 indication PID signal fault 5
Name PID signal fault
The inverter output is shut off if the measured value exceeds the PID upper limit or PID lower limit parameter
Description
setting, or the absolute deviation value exceeds the PID deviation parameter setting during PID control. Set this
function in Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit, and Pr.554 PID signal 6
operation selection. (Refer to page 570.) This protective function is not available in the initial status.
• Check the meter for a failure or break.
Check point
• Check that the parameter settings are correct.
• Check that the meter has no failure or break.
7
Corrective action
• Set the parameters correctly.
Operation panel
to 8
E. 1 to E. 3 FR-LU08 indication Fault 1 to Fault 3
indication
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
763
Others
Indicate the status of the inverter. It is not a fault.
Operation panel
EV FR-LU08 indication —
indication
Name 24 V external power supply operation
Description Blinks when the main circuit power supply is off and the 24 V external power supply is being input.
Check point • Power is supplied from a 24 V external power supply.
• Turning ON the power supply (main circuit) of the inverter clears the indication.
Corrective action • If the indication is still displayed after turning ON of the power supply (main circuit) of the inverter, the power
supply voltage may be low, or the jumper between terminals P/+ and P1 may be disconnected.
Operation panel
RD
indication
Name Backup in progress
The GOT is used for backing up inverter parameters and the data used in the PLC function of inverter. (Refer to
Description
page 668.)
Operation panel
WR
indication
Name Restoration in progress
Description The backup data stored in the GOT is used to restore the data in the inverter. (Refer to page 668.)
NOTE
• If protective functions with indication of "Fault" on the FR-LU08 or FR-PU07 are activated, "ERR" appears in the faults history
of the FR-LU08 or FR-PU07.
• If faults other than the above appear, contact your sales representative.
• If the cause is still unknown after every check, it is recommended to initialize the parameters, set the required parameter values
and check again.
3
10
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
765
Check Refer to
Possible cause Countermeasure
point page
Check the start command source, and input a start signal.
A start signal is not input. PU operation mode: / 373
External operation mode: STF/STR signal
Turn ON only one of the forward and reverse rotation start signals
Both the forward and reverse rotation start
(STF or STR).
signals (STF, STR) are input 68
When the STF and STR signals are turned ON simultaneously in
simultaneously.
the initial setting, a stop command is given.
Frequency command is zero. (The [FWD] or
Check the frequency command source and input a frequency
[REV] LED indicator on the operation panel 373
command.
is blinking.)
The AU signal is not ON when terminal 4 is
used for frequency setting. (The [FWD] or Turn ON the AU signal.
473
[REV] LED indicator on the operation panel Turning ON the AU signal activates terminal 4 input.
is blinking.)
The Output stop (MRS) signal or Inverter Turn the MRS or RES signal OFF.
reset (RES) signal is ON. The inverter starts the operation with a given start command and a
68
(The [FWD] or [REV] LED indicator on the frequency command after turning OFF the MRS or RES signal.
operation panel is blinking.) Before turning OFF, ensure the safety.
The CS signal is OFF while the automatic
restart after instantaneous power failure Turn ON the Selection of automatic restart after instantaneous
function is selected (Pr.57 Restart power failure / flying start (CS) signal.
597
coasting time≠ 9999). (The [FWD] or When the CS signal is assigned to an input terminal, automatic
Input [REV] LED indicator on the operation panel restart operation is enabled when the CS signal is turned ON.
signal is blinking.)
The jumper connector for selecting sink
Check that the control logic switchover jumper connector is
logic or source logic is incorrectly installed.
correctly installed. 72
(The [FWD] or [REV] LED indicator on the
If it is not installed correctly, the input signal is not recognized.
operation panel is blinking.)
The wiring of the encoder is incorrect.
(Under encoder feedback control or vector Check the wiring of the encoder. 90
control)
The voltage/current input switch is not
correctly set for the analog input signal (0 to Set Pr.73 Analog input selection, Pr.267 Terminal 4 input
5 V, 0 to 10 V, or 4 to 20 mA). (The [FWD] selection, and a voltage/current input switch correctly, then input 473
or [REV] LED indicator on the operation an analog signal in accordance with the setting.
panel is blinking.)
The key was pressed. During the External operation mode, check the method of restarting
(The operation panel indication is 321, 749
from a input stop from PU.
" " (PS).)
Refer to the
For the separated converter type, terminals
Instruction
RDA and SE of the converter unit are not
Manual
connected to terminals MRS (X10 signal) Check for secure wiring connections.
(Hardware)
and SD (PC for source logic) of the inverter
of the FR-
respectively.
A802.
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
767
6.6.2 Motor or machine is making abnormal acoustic
noise
Check Refer to
Possible cause Countermeasure
point page
Input
Disturbance due to EMI when the frequency Take countermeasures against EMI. 114
signal
or torque command is given through analog
Parameter Increase the Pr.74 Input filter time constant setting if steady
input terminal 1, 2, or 4. 480
setting operation cannot be performed due to EMI.
In the initial setting, Pr.240 Soft-PWM operation selection is
No carrier frequency noises (metallic enabled to change motor noise to an unoffending complex tone.
339
noises) are generated. Therefore, no carrier frequency noises (metallic noises) are
generated. Set Pr.240 = "0" to disable this function.
The motor noise increases due to activation Reduce the load. Disable the automatic reduction function by
of the carrier frequency automatic reduction setting Pr.260 PWM frequency automatic switchover = "0". (As
339
function when the motor is driven the load remains excessive, overload may cause a protective
overloaded. function E.THT.)
Set Pr.31 to Pr.36, and Pr.552 (frequency jump).
When it is desired to avoid resonance attributable to the natural
Resonance occurs. (output frequency) 408
frequency of a mechanical system, these parameters allow
resonant frequencies to be jumped.
Change the Pr.72 PWM frequency selection setting.
Changing the PWM carrier frequency produces an effect on
339
Parameter Resonance occurs. (carrier frequency) avoiding the resonance frequency of a mechanical system or a
setting motor.
Set a notch filter. 261
Auto tuning is not performed under
Advanced magnetic flux vector control,
Perform offline auto tuning. 509
Real sensorless vector control, or Vector
control.
To stabilize the measured value, change the proportional band
(Pr.129) to a larger value, the integral time (Pr.130) to a slightly
Gain adjustment during PID control is
longer time, and the differential time (Pr.134) to a slightly shorter 570
insufficient.
time.
Check the calibration of set point and measured value.
During speed control, check the setting of Pr.820 Speed control P
The gain is too high under Real sensorless 244
gain 2.
vector control, Vector control, or PM
During torque control, check the setting of Pr.824 Torque control
sensorless vector control. 280
P gain 2.
Adjust machine/equipment so that there is no mechanical
Mechanical looseness —
Others looseness.
Contact the motor manufacturer.
Motor Operating with output phase loss Check the motor wiring. —
Motor
(Dust is accumulated.) Improve the environment.
— 2
Phase to phase insulation of the motor is
Check the insulation of the motor. —
insufficient.
Main The inverter output voltage (U, V, W) are Check the output voltage of the inverter.
Circuit unbalanced. Check the insulation of the motor.
784 3
Parameter The Pr.71 Applied motor setting is
Check the Pr.71 Applied motor setting. 505
setting incorrect.
— Motor current is too large Refer to "6.6.11 Motor current is too large". 772
4
6.6.5 Motor rotates in the opposite direction
Check Refer to
5
Possible cause Countermeasure
point page
Main The phase sequence of output terminals U,
Connect the output side terminals (terminals U, V, and W) correctly. 55
Circuit V and W is incorrect. 6
The start signals (STF and STR signals) are Check the connection. (STF: forward rotation, STR: reverse
68, 502
connected improperly. rotation)
Input The polarity of the frequency command is
signal negative during the polarity reversible
operation set by Pr.73 Analog input
Check the polarity of the frequency command. 473 7
selection.
Input
signal, The torque command is negative during
parameter torque control under Vector control.
Check the torque command value. 270 8
setting
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
769
6.6.7 Acceleration/deceleration is not smooth
Check Refer to
Possible cause Countermeasure
point page
The acceleration/deceleration time is too
Increase the acceleration/deceleration time. 349
short.
The torque boost (Pr.0, Pr.46, Pr.112)
Increase/decrease the Pr.0 Torque boost setting value by 0.5%
setting is not appropriate under V/F control, 672
increments so that stall prevention does not occur.
so the stall prevention function is activated.
Parameter
Under V/F control, set Pr.3 Base frequency, Pr.47 Second V/F
setting The base frequency does not match the 673
(base frequency), and Pr.113 Third V/F (base frequency).
motor characteristics.
Under Vector control, set Pr.84 Rated motor frequency. 215
If the frequency becomes unstable during regeneration avoidance
Regeneration avoidance operation is
operation, decrease the setting of Pr.886 Regeneration 696
performed.
avoidance voltage gain.
Load Reduce the load. —
Set Pr.22 Stall prevention operation level (Torque limit level)
Parameter The stall prevention (torque limit) function is
higher according to the load. (If Pr.22 is set too high, an overcurrent 235, 409
setting activated due to a heavy load.
trip (E.OC[]) is likely to occur.)
Motor Check the capacities of the inverter and the motor. —
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
771
6.6.9 Operation mode is not changed properly
Check Refer to
Possible cause Countermeasure
point page
Input Check that the STF and STR signals are OFF.
The start signal (STF or STR) is ON. 68, 502
signal When either is ON, the operation mode cannot be changed.
When the Pr.79 is set to "0 (initial value)", the operation mode is the
External operation mode at power ON. To switch to the PU
The Pr.79 Operation mode selection operation mode, press the key on the operation panel 370
setting is not appropriate.
(press the key on the parameter unit (FR-PU07)). At other
Parameter settings (1 to 4, 6, 7), the operation mode is limited accordingly.
setting
Check Pr.79 Operation mode selection, Pr.338 Communication
operation command source, Pr.339 Communication speed
Operation mode and a writing device do not command source, Pr.550 NET mode operation command
370, 380
correspond. source selection and Pr.551 PU mode operation command
source selection, and select an operation mode suitable for the
purpose.
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
773
6.6.13 Unable to write parameter setting
Check Refer to
Possible cause Countermeasure
point page
Input Operation is being performed (the STF or Stop the operation. When Pr.77 Parameter write selection = "0
328
signal STR signal is ON). (initial value)", writing is enabled only during a stop.
Choose the PU operation mode. Or, set Pr.77 Parameter write
Parameter setting was attempted in the
selection = "2" to enable parameter writing regardless of the 328, 370
External operation mode.
operation mode.
Parameter write is disabled by the Pr.77
Check the Pr.77 setting. 328
Parameter write selection setting.
The key lock mode is enabled by the
Pr.161 Frequency setting/key lock Check the Pr.161 setting. 324
Parameter
operation selection setting.
setting
Operation mode and a writing device do Check Pr.79, Pr.338, Pr.339, Pr.550 and Pr.551, and select an
370, 380
not correspond. operation mode suitable for the purpose.
Under PM sensorless vector control,
setting "25" in Pr.72 PWM frequency Under PM sensorless vector control, "25" cannot be set in Pr.72. (A
selection was attempted. Or, setting PM sine wave filter (MT-BSL/BSC) cannot be used under PM sensorless 339
sensorless vector control was attempted vector control.)
while Pr.72 = "25".
INSPECTION 5
10
775
7 PRECAUTIONS FOR MAINTENANCE AND
INSPECTION
This chapter explains the precautions for maintenance and inspection of this product.
Always read the instructions before use.
For the precautions for maintenance and inspection of the separated converter type inverter, refer to the FR-A802 (Separated
Converter Type) Instruction Manual (Hardware).
For the precautions for maintenance and inspection of the IP55 compatible model inverter, refer to the FR-A806 (IP55/UL Type
12 specification) Instruction Manual (Hardware).
Check and clean the cooling system: Clean the air filter, etc.
Check the tightening and retighten: The screws and bolts may become loose due to vibration, temperature
changes, etc. Check and tighten them. Tighten them according to the
specified tightening torque. (Refer to page 57.)
Check the conductors and insulating materials for corrosion and damage.
Measure the insulation resistance.
Check and change the cooling fan and relay.
NOTE
• When using the safety stop function, periodic inspection is required to confirm that safety function of the safety system
operates correctly. For more details, refer to the Safety Stop Function Instruction Manual.
Conductors and
• Check conductors for distortion. ○
Contact the
manufacturer. 6
cables • Check cable sheaths for breakage and deterioration Contact the
○
(crack, discoloration, etc.). manufacturer.
Main circuit
Stop the
equipment and
8
Terminal block Check for a damage. ○
contact the
manufacturer.
Smoothing
• Check for liquid leakage. ○
Contact the
manufacturer.
9
aluminum ○ Contact the
• Check for safety valve projection and bulge.
electrolytic manufacturer.
capacitor • Visual check and judge by the life check of the main
circuit capacitor. (Refer to page 779.)
○
10
Check that the operation is normal and no chattering Contact the
Relay/contactor ○
sound is heard. manufacturer.
Contact the
• Check for cracks in the resistor insulator. ○
manufacturer.
Resistor
Contact the
• Check for a break in the cable. ○
manufacturer.
• Check for an output voltage imbalance between Contact the
○
Operation phases while operating the inverter alone. manufacturer.
check • Check that no fault is found in protective and display Contact the
○
circuits in a sequence protective operation test. manufacturer.
Stop the
Control equipment and
• Check for unusual odor and discoloration. ○
Components check
NOTE
• Continuous use of a leaked, deformed, or degraded smoothing aluminum electrolytic capacitor (as shown in the table above)
may lead to a burst, breakage, or fire. Replace such capacitor without delay.
Checking method
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, P/+, and N/- and check the
electric continuity.
NOTE
• Before measurement, check that the smoothing capacitor is discharged.
• At the time of electric discontinuity, the measured value is almost ∞. When there is an instantaneous electric continuity, due
to the smoothing capacitor, the tester may not indicate ∞. At the time of electric continuity, the measured value is several Ω to
several tens of Ω. If all measured values are almost the same, although these values are not constant depending on the
module type and tester type, the modules are without fault.
R/L1 C
U 2
S/L2 V
T/L3 W 3
D4 D5 D6
TR4 TR6 TR2 4
N/−
7.1.5 Cleaning 5
Always run the inverter in a clean status.
When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol. 6
NOTE
• Do not use solvent, such as acetone, benzene, toluene and alcohol, as these will cause the inverter surface paint to peel off.
• The display, etc. of the operation panel (FR-DU08) and parameter unit (FR-PU07) are vulnerable to detergent and alcohol. 7
Therefore, avoid using them for cleaning.
NOTE
• For parts replacement, contact the nearest Mitsubishi FA center.
*1 Initial values differ according to the inverter capacity (Refer to page 344 for details.)
NOTE
• Refer to page 341 to perform the life check of the inverter parts.
AIR FLOW
3
FR-A820-1.5K to 3.7K FR-A820-5.5K to 15K
FR-A840-2.2K, 3.7K FR-A840-5.5K to 15K
8
FR-A820-37K, 45K FR-A820-55K or higher
FR-A840-37K to 55K FR-A840-75K or higher
9
3. Install the fan cover.
2. Insert hooks 1. Insert hooks 2. Insert hooks
until you hear
a click sound.
1. Insert hooks
into holes. until you
hear a click
1. Insert hooks 2. Insert hooks
into holes. until you 10
into holes. sound. hear a click
sound.
NOTE
• Installing the fan in the opposite direction of air flow may shorten the inverter life.
• Ensure that the cables are not caught when the fan is installed.
• Switch OFF the power before starting the fan replacement work. To prevent an electric shock accident, keep the inverter with
its covers on during fans replacement since the inverter circuits are charged with voltage even after power OFF.
Fan *1
Fan block
3)
Fan cover
2)
Fan connection
connector
1)
AIR FLOW
NOTE
• Installing the fan in the opposite direction of air flow may shorten the inverter life.
• Ensure that the cables are not caught when the fan is installed.
• Switch OFF the power before starting the fan replacement work. To prevent an electric shock accident, keep the inverter with
its covers on during fans replacement since the inverter circuits are charged with voltage even after power OFF.
Smoothing capacitors
A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum
electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the
adverse effects of ripple currents, etc. The replacement intervals greatly vary with the surrounding air temperature and
operating conditions. When the inverter is operated in air-conditioned, normal environment conditions, replace the capacitors
about every 10 years.
The appearance criteria for inspection are as follows:
• Case: Check the side and bottom faces for expansion.
• Sealing plate: Check for a remarkable warp and extreme crack.
• Check for an external crack, discoloration, liquid leakage, etc. Judge that the capacitor has reached its life when the
measured capacitance of the capacitor reduced below 80% of the rating.
NOTE
• The inverter diagnoses the main circuit capacitor and control circuit capacitor by itself and can judge their lives. (Refer to page
341.)
9
2. Be careful not to bend the pins of the inverter's control circuit connector, reinstall the control circuit terminal block
and fix it with the mounting screws. 10
Fix it with
the screws
NOTE
• Before starting inverter replacement, switch OFF the power, wait for at least 10 minutes, and then check the voltage with a
tester and such to ensure safety.
NOTE
• When installing meters etc. on the inverter output side
When the inverter-to-motor wiring length is long, especially in the 400 V class, small-capacity models, the meters and CTs may
generate heat due to line-to-line leakage current. Therefore, choose the equipment which has enough allowance for the
current rating.
To measure and display the output voltage and output current of the inverter, it is recommended to use the terminal AM and
FM/CA output functions of the inverter.
Input current
Output current
Inverter
: Electrodynamometer type
V
+ - : Moving-coil type
Instrument
types : Rectifier type
Output voltage Between U and V, V and Rectifier type AC voltmeter*1*4 Difference between the phases is within 1% of the
V2 W, or W and U (moving-iron type cannot
measure.)
maximum output voltage. 5
Output current Moving-iron type AC Difference between the phases is 10% or lower of
U, V and W line currents
I2 ammeter*2*4 the rated inverter current.
Output power
U, V, or W, and Digital power meter (designed for
P2 = W21 + W22
6
between U and V, or V and inverter) or electrodynamic type
P2 2-wattmeter method (or 3-wattmeter method)
W single-phase wattmeter
Calculate in similar manner to the input power factor.
Output power factor 3
7
Pf2 3I [
Ҁ9[ ,
T2 Terminal SD
is a common
Pulse width T1: Adjust with C0
terminal.
(Pr.900).
Pulse cycle T2: Set with Pr.55
(for frequency monitor only).
STF, STR, RH, RM, RL,
Start signal
JOG, RT, AU, STP When open
Select signal
(STOP), CS, RES, 20 to 30 VDC
Reset signal
between MRS(+) and SD ON voltage: 1 V or less
Output stop signal
(for sink logic)
Continuity check*3
Between A1 and C1 Moving-coil type [Normal] [Fault]
Fault signal
Between B1 and C1 (such as tester) A1-C1 No Yes
B1-C1 Yes No
*1 Use an FFT to measure the output voltage accurately. A tester or general measuring instrument cannot measure accurately.
*2 When the carrier frequency exceeds 5 kHz, do not use this instrument since using it may increase eddy current losses produced in metal parts
inside the instrument, leading to burnout. In this case, use an approximate-effective value type.
*3 When the setting of Pr.195 ABC1 terminal function selection is the positive logic
100 100
Example of measuring inverter input power Example of measuring inverter output power
PT
No PT can be used on the output side of the inverter. Use a direct-reading meter. (A PT can be used on the input side of the
inverter.)
0 20 40 60 Hz 0 20 40 60 Hz
7
Example of measuring the inverter input current Example of measuring the inverter output current
8
7.2.4 Use of CT and transducer
A CT may be used both on the inverter's input and output sides. Use the one with the largest possible VA ability because an
error will increase if the frequency gets lower. 9
When using a transducer, use the effective value calculation type which is immune to harmonics.
Effective power
Total power factor of the inverter =
Apparent power
Three-phase input power found by the 3-wattmeter method
=
√3×V (power supply voltage) × I (input current effective value)
NOTE
• Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter
so that the test voltage is not applied to the inverter.
• For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.
Motor
Power R/L1 Inverter U
S/L2 V IM
supply
T/L3 W
500 VDC
megger
10
789
8 SPECIFICATIONS
This chapter explains the specifications of this product.
Always read the instructions before use.
For the separated converter type inverter, refer to "SPECIFICATIONS" in the FR-A802 (Separated Converter Type) Instruction
Manual (Hardware).
For the IP55 compatible model inverter, refer to "SPECIFICATIONS" in the FR-A806 (IP55/UL Type12 specification) Instruction
Manual (Hardware).
200 V class
00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330 03160 03800 04750
Model FR-A820-[]
0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K
90/
SLD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 132
110
Applicable motor LD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110
capacity (kW)*1 ND (initial setting) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
HD 0.2*2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
SLD 1.8 2.9 4 6.4 10 13 19 24 29 35 48 59 71 89 120 145 181
Rated
LD 1.6 2.7 3.7 5.8 8.8 12 17 22 27 32 43 53 65 81 110 132 165
capacity
ND (initial setting) 1.1 1.9 3 4.2 6.7 9.1 13 18 23 29 34 44 55 67 82 110 132
(kVA)*3
HD 0.6 1.1 1.9 3 4.2 6.7 9.1 13 18 23 29 34 44 55 67 82 110
SLD 4.6 7.7 10.5 16.7 25 34 49 63 77 93 125 154 187 233 316 380 475
Rated LD 4.2 7 9.6 15.2 23 31 45 58 70.5 85 114 140 170 212 288 346 432
current (A) ND (initial setting) 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215 288 346
HD 1.5 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215 288
SLD 110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40°C
Output
Overload
LD 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
current
ND (initial setting) 150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
rating*4
HD 200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
Rated voltage*5 Three-phase 200 to 240 V
Brake transistor Built-in FR-BU2 (option)
150% torque, 3% 100% torque, 100% torque, 10% torque,
Regenerative Maximum brake torque*7 20% torque, continuous
ED*6 3% ED*6 2% ED*6 continuous
braking FR-ABR
150% torque,
(when the option is 100% torque, 10% ED 100% torque, 6% ED — — — — — —
10% ED
used)
Rated input
Three-phase 200 to 240 V, 50/60 Hz
AC voltage and frequency
Permissible AC voltage fluctuation 170 to 264 V, 50/60 Hz
Permissible frequency fluctuation ±5%
SLD 5.3 8.9 13.2 19.7 31.3 45.1 62.8 80.6 96.7 115 151 185 221 269 — — —
LD 5 8.3 12.2 18.3 28.5 41.6 58.2 74.8 90.9 106 139 178 207 255 — — —
Without DC
reactor ND
3.9 6.3 10.6 14.1 22.6 33.4 44.2 60.9 80 96.3 113 150 181 216 266 — —
(initial setting)
Rated input HD 2.3 3.9 6.3 10.6 14.1 22.6 33.4 44.2 60.9 80 96.3 113 150 181 216 — —
current (A)*8 SLD 4.6 7.7 10.5 16.7 25 34 49 63 77 93 125 154 187 233 316 380 475
Power supply
LD 4.2 7 9.6 15.2 23 31 45 58 70.5 85 114 140 170 212 288 346 432
With DC
reactor ND
3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215 288 346
(initial setting)
HD 1.5 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215 288
SLD 2 3.4 5 7.5 12 17 24 31 37 44 58 70 84 103 — — —
LD 1.9 3.2 4.7 7 11 16 22 29 35 41 53 68 79 97 — — —
Without DC
reactor ND
1.5 2.4 4 5.4 8.6 13 17 23 30 37 43 57 69 82 101 — —
(initial setting)
Power supply
HD 0.9 1.5 2.4 4 5.4 8.6 13 17 23 30 37 43 57 69 82 — —
capacity
SLD 1.8 2.9 4 6.4 10 13 19 24 29 35 48 59 71 89 120 145 181
(kVA)*9
LD 1.6 2.7 3.7 5.8 8.8 12 17 22 27 32 43 53 65 81 110 132 165
With DC
reactor ND
1.1 1.9 3 4.2 6.7 9.1 13 18 23 29 34 44 55 67 82 110 132
(initial setting)
HD 0.6 1.1 1.9 3 4.2 6.7 9.1 13 18 23 29 34 44 55 67 82 110
Protection rating of structure (IEC 60529)*10 Enclose type (IP20) Open type (IP00)
Cooling system Natural Forced air
790 8. SPECIFICATIONS
8.1 Inverter rating
00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330 03160 03800 04750
Model FR-A820-[]
0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K
Approx. mass (kg) 2.0 2.2 3.3 3.3 3.3 6.7 6.7 8.3 15 15 15 22 42 42 54 74 74 1
*1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
*2 A 0.2 kW motor can be operated under V/F control only.
*3 The rated output capacity is the value with respect to 220 V output voltage.
*4 The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow 2
time for the inverter and motor to return to or below the temperatures under 100% load.
*5 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
√2 .
*6
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
The built-in brake resistor is used.
3
*7 Value for the ND rating
*8 The rated input current is the value at a rated output voltage. The input power impedances (including those of the input reactor and cables) affect
the value.
*9 The power supply capacity is the value at the rated output current. The input power impedances (including those of the input reactor and cables) 4
affect the value.
*10 The protection rating of the FR-DU08 is IP40 (except for the PU connector).
400 V class 5
00023 to 01800
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800
Model FR-A840-[]
0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 6
SLD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75/90
Applicable motor LD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
capacity (kW)*1 ND (initial setting) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
HD 0.2*2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 7
SLD 1.8 2.9 4 6.3 10 13 19 24 29 36 47 59 71 88 137
Rated
LD 1.6 2.7 3.7 5.8 8.8 12 18 22 27 33 43 53 65 81 110
capacity
ND (initial setting) 1.1 1.9 3 4.6 6.9 9.1 13 18 24 29 34 43 54 66 84
(kVA)*3
HD
SLD
0.6
2.3
1.1
3.8
1.9
5.2
3
8.3
4.6
12.6 17
6.9 9.1
25
13
31
18
38
24
47
29
62
34
77
43
93
54
116
66
180
8
Rated LD 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 144
current (A) ND (initial setting) 1.5 2.5 4 6 9 12 17 23 31 38 44 57 71 86 110
HD 0.8 1.5 2.5 4 6 9 12 17 23 31 38 44 57 71 86
9
Output
Rated voltage*5
HD 200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
Three-phase 380 to 500 V
10
Brake transistor Built-in
Regenerative Maximum brake torque*7 100% torque, 2% ED*6 20% torque, continuous
braking FR-ABR
(when the option is used)
100% torque, 10% ED 100% torque, 6% ED —*12
Rated input
AC voltage and frequency Three-phase 380 to 500 V, 50/60 Hz*11
Permissible AC voltage fluctuation 323 to 550 V, 50/60 Hz
Permissible frequency fluctuation ±5%
SLD 3.2 5.4 7.8 10.9 16.4 22.5 31.7 40.3 48.2 58.4 76.8 97.6 115 141 —
LD 3 4.9 7.3 10.1 15.1 22.3 31 38.2 44.9 53.9 75.1 89.7 106 130 —
Without DC
reactor ND
2.3 3.7 6.2 8.3 12.3 17.4 22.5 31 40.3 48.2 56.5 75.1 91 108 134
(initial setting)
Rated input HD 1.4 2.3 3.7 6.2 8.3 12.3 17.4 22.5 31 40.3 48.2 56.5 75.1 91 108
current (A)*8 SLD 2.3 3.8 5.2 8.3 12.6 17 25 31 38 47 62 77 93 116 180
Power supply
8. SPECIFICATIONS
8.1 Inverter rating
791
*1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
*2 A 0.2 kW motor can be operated under V/F control only.
*3 The rated output capacity is the value with respect to 440 V output voltage.
*4 The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow
time for the inverter and motor to return to or below the temperatures under 100% load.
*5 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2 .
*6 The built-in brake resistor is used.
*7 Value for the ND rating
*8 The rated input current is the value at a rated output voltage. The input power impedances (including those of the input reactor and cables) affect
the value.
*9 The power supply capacity is the value at the rated output current. The input power impedances (including those of the input reactor and cables)
affect the value.
*10 FR-DU08: IP40 (except for the PU connector)
*11 For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For details, refer to page 327.)
*12 The braking capability of the inverter can be improved with a commercial brake resistor. For the details, please contact your sales representative.
792 8. SPECIFICATIONS
8.1 Inverter rating
75K to 280K
Model FR-A840-[]
02160 02600 03250 03610 04320 04810 05470 06100 06830 1
75K 90K 110K 132K 160K 185K 220K 250K 280K
SLD 110 132 160 185 220 250 280 315 355
Applicable motor LD 90 110 132 160 185 220 250 280 315
capacity (kW)*1 ND (initial setting) 75 90 110 132 160 185 220 250 280 2
HD 55 75 90 110 132 160 185 220 250
SLD 165 198 248 275 329 367 417 465 521
Rated
LD 137 165 198 248 275 329 367 417 465
capacity
(kVA) *2 ND (initial setting)
HD
110
84
137
110
165
137
198
165
248
198
275
248
329
275
367
329
417
367
3
SLD 216 260 325 361 432 481 547 610 683
Rated LD 180 216 260 325 361 432 481 547 610
current (A) ND (initial setting)
HD
144
110
180
144
216
180
260
216
325
260
361
325
432
361
481
432
547
481
4
Output
— — — — — — — — —
6
(when the option is used)
Rated input
AC voltage and frequency Three-phase 380 to 500 V, 50/60 Hz*9
Permissible AC voltage fluctuation
Permissible frequency fluctuation
323 to 550 V, 50/60 Hz
±5%
7
SLD 216 260 325 361 432 481 547 610 683
Power supply
8. SPECIFICATIONS
8.1 Inverter rating
793
8.2 Motor rating
794 8. SPECIFICATIONS
8.2 Motor rating
400 V class
Motor model: SF-V5RUH[]K
Applicable inverter model
1 2 3 5 7 11 15 18 22 30 37 45 55
1
2.2 2.2 3.7 7.5 11 15 18.5 22 30 37 45 55 75
FR-A840-[]K (ND rating)
Rated output power (kW) 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30*1 37*1 45*1 55
Rated current (A)
Rated torque (N·m)
4.2
9.55
5.8
14.1
8.8
23.6
14.5
35.0
18.5
47.7
27.5
70.0
35.5
95.5
44
118
51
140
67
191
84
235
99
286
132
350
2
Maximum torque at 150% 60 s
14.3 21.1 35.4 52.4 71.6 105 143 176 211 287 353 429 525
(N·m)
Rated speed (r/min) 1500
3
Maximum speed (r/min) 3000*2 2400
Frame No. 90L 100L 112M 132S 132M 160M 160L 180M 180M 200L 200L 200L 225S
-4 2 67.5 105 175 275 400 750 875 1725 1875 3250 3625 3625 6850
Inertia moment J (×10 kg·m )
Noise *5 75 dB or less 80 dB or less 85 dB or less 4
Single-phase 200 V/50 Hz Three-phase 380 to 400 V/50 Hz
Cooling fan Voltage
Single-phase 200 to 230 V/60 Hz Three-phase 400 to 460V/60Hz
(with
thermal 36/55 W 22/28 W 55/71 W 100/156 W 85/130 W
protector)*7*
Input*3 (0.26/0.32 A) (0.11/0.13 A) (0.19/0.19 A) (0.27/0.30 A) (0.23/0.26 A) 5
8 Recommended
0.36 A 0.18 A 0.25 A 0.39 A 0.34 A
thermal setting
Surrounding air temperature and
-10 to +40°C (non-freezing), 90% RH or less (non-condensing)
humidity
Structure (Protection rating) Totally enclosed forced ventilated (Motor: IP44, Cooling fan: IP23S)*4
6
Detector Encoder 2048P/R, A phase, B phase, Z phase, +12 V/24 VDC power supply*6
Equipment Encoder, thermal protector, fan
Insulation class F 7
Vibration rank V10
Approx. mass (kg) 24 33 41 52 62 99 113 138 160 238 255 255 320
*1 80% output in the high-speed range. (The output is reduced at the speed of 2400 r/min or faster.) Contact us separately for details.
*2 The maximum speed of a 3.7 kW motor or less is 3600 r/min. Consult our sales office for use of these motor. 8
*3 Power (current) at 50/60 Hz.
*4 Since a brake motor has a window for gap check, the protection rating of both the cooling fan section and brake section of the motor is IP20. The
letter S in IP23S is an additional code indicating that a cooling fan was checked for water protection while it is stationary.
*5 The value shown is applicable to the motor at high carrier frequency (Pr.72 = 6 and Pr.240 = 0). 9
*6 A separate power supply of 12/24 V is required for the encoder. (When the FR-A8TP is installed on the inverter, the 24 V power supply from the
FR-A8TP is available.)
*7 The cooling fan is equipped with a thermal protector. The cooling fan stops when the coil temperature exceeds the specified value in order to
protect the fan motor. A restrained cooling fan or degraded fan motor insulation could be causes for the rise in coil temperature. The cooling fan
re-starts when the coil temperature drops to normal.
10
*8 The cooling fan voltage and input values are the basic specifications of the cooling fan alone and free air values. The input value becomes slightly
larger when it is rotated by this motor due to an increased workload, but the cooling fan can be used as it is. When preparing a thermal relay at
the user side, use the recommended thermal setting.
Motor torque
The torque characteristics of the SF-V5RU series driven by the inverter are shown in graph form as follows.
8. SPECIFICATIONS
8.2 Motor rating
795
These are the case of the motor driven by the inverter at ND or HD rating. As the overload capacity decreases in the case of
LD or SLD rating, observe the specified range of the inverter.
SF-V5RU (1500 r/min series)
1.5 to 22 (kW) 30 to 55 (kW)
Maximum torque for short time Maximum torque for short time
150 150
Output torque
Output torque
Continuous Continuous
operation torque operation torque Constant power
100 Constant power 100
94 Reduced output
75
63
(%) 50 (%) 60
40
SF-V5RU1 (1000 r/min) speed ratio = 1:2 SF-V5RU3 (1000 r/min) speed ratio = 1:3 SF-V5RU4 (500 r/min) speed ratio = 1:4
1.5 to 37 (kW) 1.5 to 30 (kW) 1.5 to 15 (kW)
Maximum torque for short time Maximum torque for short time Maximum torque for short time
(SF-V5RU[]K1Y) (SF-V5RU[]K3Y) (SF-V5RU[]K4Y)
150 Maximum torque for short time 150 150
(SF-V5RU[]K1) Maximum torque for short time Maximum torque for short time
Constant power (SF-V5RU[]K3) (SF-V5RU[]K4)
120 120 120
Continuous operation Continuous operation
Output torque
Output torque
Output torque
torque torque
100 100 100
Reduced output Continuous
30 kW operation
Constant power torque
(SF-V5RU30K1)
75 Constant power
(%) 60 (%) 63 (%)
54
50 50
45 42
40 37.5
33 30
25
0 0 0
0 1000 2000 0 1000 2400 3000 0 500 2000
Speed (r/min) Speed (r/min) Speed (r/min)
796 8. SPECIFICATIONS
8.2 Motor rating
8.2.2 Vector control dedicated motor SF-THY
Motor specifications
1
Motor model SF-THY
Cooling fan
Voltage
(400 V class cooling fan is available upon order) 5
50 Hz 400 400 400 400 400 750 750
Input (W) 750
60 Hz 750 750 750 750 750 1500 1500
Approx. mass (kg)
Surrounding air temperature and
610 610 660 870 890 920 1170 1630
6
-10 to +40°C (non-freezing), 90% RH or less (non-condensing)
humidity
Structure Totally enclosed forced ventilated
Equipment Encoder, thermal protector*2, fan 7
Insulation class F
Vibration rank V10
Common
Resolution 2048 pulses/rev
specifications
Power supply voltage 12/24 VDC±10%*1
8
Current consumption 90 mA
Dedicated
encoder Output signal form Phase A and Phase B: 90 degrees out of phase, Phase Z: 1 pulse/rev
Output circuit Complementary (constant voltage output matched by emitter follow) 9
"H" level: Power supply voltage 9 V or more (IOH: -20 mA)
Output voltage
"L" level: Power supply voltage 3 V or less (IOL: 20 mA)
*1
*2
The 12/24 V power supply is required for the encoder.
A motor with a thermal protector is available. Contact your sales representative.
10
Motor torque
The torque characteristics of the SF-THY driven by the inverter are shown in graph form as follows.
75 (kW) 90 to 250 (kW)
125
Rated torque Rated torque
100 100
94
83
63
(%) (%)
8. SPECIFICATIONS
8.2 Motor rating
797
8.2.3 IPM motor MM-CF (2000 r/min series)
Motor specifications
Motor model: MM-CF[] 52(C)(B) 102(C)(B) 152(C)(B) 202(C)(B) 352(C)(B) 502(C) 702(C)
SLD 0.4 0.4 0.75 1.5 2.2 3.7 5.5
Applicable inverter model LD 0.4 0.4 0.75 1.5 2.2 3.7 5.5
FR-A820-[]K ND (initial setting) 0.4 0.75 1.5 2.2 3.7 5.5 7.5
HD 0.75*6 1.5*6 2.2*6 3.7*6 5.5*6 7.5*6 11*6
Continuous Rated output power (kW) 0.5 1.0 1.5 2.0 3.5 5.0 7.0
characteristics*1 Rated torque (N·m) 2.39 4.78 7.16 9.55 16.70 23.86 33.41
Rated speed*1(r/min) 2000
Maximum speed (r/min) 3000
Instantaneous permissible speed (r/min) 3450*7
Maximum torque (N·m) 4.78 9.56 14.32 19.09 33.41 47.73 66.82
*5
Inertia moment J 6.6 13.7 20.0 45.5 85.6
120.0 160.0
(×10-4 kg m2) (7.0) (14.9) (21.2) (48.9) (89.0)
Recommended ratio of load inertia moment to
100 times max. 50 times max.
motor shaft inertia moment*2
Rated current (A) 1.81 3.70 5.22 7.70 12.5 20.5 27.0
Insulation class F
Structure (Protection rating) Totally enclosed, naturally air-cooled (IP44*3/IP65*3*4)
Surrounding air temperature and humidity -10 to +40°C (non-freezing), 90% RH or less (non-condensing)
Storage temperature and humidity -20 to +70°C (non-freezing), 90% RH or less (non-condensing)
Indoors (no direct sunlight),
Ambience
free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude Maximum 1000 m
Vibration X: 9.8 m/s2, Y: 24.5 m/s2
Approx. mass*5 (kg) 5.1/7.8 7.2/11 9.3/13 13/20 19/28 27 36
*1 The rated output power or speed is not guaranteed at low supply voltages.
*2 It is the case that the load torque is 20% of the motor rating. The permissible load inertia moment ratio is smaller when the load torque is larger.
Consult us if the load inertia moment ratio exceeds the above value.
*3 This does not apply to the shaft through portion.
*4 The value after the slash is for MM-CF[ ]2C.
*5 The value for MM-CF[ ]2B is indicated in parentheses.
*6 The one-rank higher inverter is designated for high torque in low-speed range.
*7 Set 3150 r/min (210 Hz) or less in Pr.374 Overspeed detection level. The inverter may be damaged by the motor induction voltage if the motor
speed exceeds 3150 r/min (210 Hz).
798 8. SPECIFICATIONS
8.2 Motor rating
Motor torque
Motor capacity Low speed high torque setting enabled (high frequency superposition control) 1
1.5 kW or lower ND rating HD rating
Torque % Torque %
2
Instantaneous (3 s) Instantaneous (3 s)
200 200
Short duration (60 s) Short duration (60 s)
150 150
120 Continuous Continuous
100 100
3
Torque %
Instantaneous (3 s)
Torque %
Instantaneous (3 s)
5
200 200
Short duration (60 s) Short duration (60 s)
150 150
120
100
Continuous
Continuous
6
100
Torque %
9
Instantaneous (3 s)
200
Short duration (60 s)
150
Continuous
10
100
50
8. SPECIFICATIONS
8.2 Motor rating
799
8.3 Common specifications
Soft-PWM control, high carrier frequency PWM control (selectable among V/F control, Advanced
Control method magnetic flux vector control, Real sensorless vector control), Optimum excitation control, Vector
control*1, and PM sensorless vector control
0.2 to 590 Hz (The upper-limit frequency is 400 Hz under Advanced magnetic flux vector control, Real
Output frequency range
sensorless vector control, Vector control*1, and PM sensorless vector control.)
0.015 Hz/60 Hz at 0 to 10 V/12 bits (terminals 2 and 4)
Frequency 0.03 Hz/60 Hz at 0 to 5 V/11 bits or 0 to 20 mA/approx. 11 bits (terminals 2 and 4), at 0 to ±10 V/12
Analog input
setting and bits (terminal 1)
resolution 0.06 Hz/60 Hz at 0 to ±5 V/11 bits (terminal 1)
Digital input 0.01 Hz
Frequency Analog input Within ±0.2% of the maximum output frequency (25 ± 10°C)
accuracy Digital input 0.01% or less of the set output frequency
Voltage/frequency The base frequency can be set from 0 to 590 Hz. The constant-torque/variable-torque pattern or
Control
frequency jump, rotation indication, automatic restart after instantaneous power failure, electronic
bypass sequence, remote setting, Automatic acceleration/deceleration, retry function, carrier
frequency selection, fast-response current limit, forward/reverse rotation prevention, Operation mode
selection, slip compensation, droop control, load torque high-speed frequency control, Speed
Operational function smoothing control, traverse, auto tuning, applied motor selection, gain tuning, RS-485
communication, PID control, PID pre-charge function, dancer control, Cooling fan operation selection,
Stop selection (deceleration stop/coasting), power-failure deceleration stop function, stop-on-contact
control, PLC function, life diagnosis, maintenance timer, current average monitoring, multiple rating,
orientation control*1, speed control, torque control, position control, pre-excitation, torque limit, test
operation, 24 V power supply input for control circuit, safety stop function, anti-sway control, CC-Link
IE Field Network communication*11
Inverter running, Up to frequency, Instantaneous power failure/undervoltage*4, Overload warning,
Output signal
800 8. SPECIFICATIONS
8.3 Common specifications
Pulse train
Max. 2.4 kHz via one terminal (for the indication of inverter output frequency).
output (FM
For type inverter)
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
1
indication Current output
Max. 20 mADC via one terminal (for the indication of inverter output frequency).
on external (CA type
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
Indication
meters inverter)
Voltage output
Max. 10 VDC via one terminal (for the indication of inverter output frequency). 2
The item for monitoring can be changed using Pr.158 FM/CA terminal function selection.
Status Output frequency, output current, output voltage, and frequency setting value are monitored.
Operation monitoring The item for monitoring can be changed using Pr.52 FM/CA terminal function selection.
panel (FR-
Fault
When a protective function is activated, a fault indication is displayed and the output voltage, output 3
DU08) current, output frequency, cumulative energization time, date (year, month, day) and time at the
monitoring
occurrence of the fault are stored. Each fault is recorded and the last 8 records can be displayed.
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during
deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip 4
during constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload
trip (electronic thermal relay function), Motor overload trip (electronic thermal relay function), Heatsink
overheat, Instantaneous power failure*4, Undervoltage*4, Input phase loss*4*5, Stall prevention stop,
Loss of synchronism detection*5, Brake transistor alarm detection*6, Upper limit fault detection, Lower
5
limit fault detection, Output side earth (ground) fault overcurrent, Output short circuit, Output phase
loss, External thermal relay operation*5, PTC thermistor operation*5, Option fault, Communication
Fault option fault, Parameter storage device fault, PU disconnection, Retry count excess*5, CPU fault,
Operation panel power supply short circuit/RS-485 terminals power supply short circuit, 24 VDC
6
power fault, Abnormal output current detection*5, Inrush current limit circuit fault*4, Communication
Protective fault (inverter), Analog input fault, USB communication fault, Safety circuit fault, Overspeed
function occurrence*5, Speed deviation excess detection*1*5, Signal loss detection*1*5, Excessive position 7
fault*1*5, Brake sequence fault*5, Encoder phase fault*1*5, 4 mA input fault*5, Pre-charge fault*5, PID
signal fault*5, Option fault, Opposite rotation deceleration fault*5, Internal circuit fault, Abnormal
internal temperature*7, Magnetic pole position unknown*1
Fan alarm, Stall prevention (overcurrent), Stall prevention (overvoltage), Regenerative brake pre- 8
*5*6 *5
alarm , Electronic thermal relay function pre-alarm, PU stop, Speed limit indication , Parameter
Alarm, copy, Safety stop, Maintenance signal output*5, USB host error, Home position return setting error*5,
Warning, Error Home position return uncompleted*5, Home position return parameter setting error*5, Operation panel
message
9
lock*5, Password locked*5, Parameter write error, Copy operation error, 24 V external power supply
operation, Internal fan alarm*7, Continuous operation during communication fault*5, Load fault
warning
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC60721-3-3 3C2/3S2),
Surrounding air humidity IP55 compatible models)
90% RH or less (non-condensing) (Without circuit board coating)
Storage temperature*8 -20 to +65°C
Ambience Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude/vibration Maximum 1000 m *9, 5.9 m/s2 or less*10 at 10 to 55 Hz (directions of X, Y, Z axes)
*1 Available when a Vector control compatible option is installed.
*2 For PM sensorless vector control, refer to page 823.
*3 For the FR-A820-00340(5.5K) or higher and the FR-A840-00170(5.5K) or higher, the starting torque is initially limited to a level of 150% due to
the torque limitation.
*4 Available for the standard model and the IP55 compatible model.
*5 Not activated in the inverter in the initial state.
*6 Available only for the standard model.
*7 Available only for the IP55 compatible model.
*8 Applicable to conditions for a short time, for example, in transit.
*9 For the installation at an altitude above 1000 m (up to 2500 m), consider a 3% reduction in the rated current per 500 m increase in altitude.
*10 2.9 m/s2 or less for the FR-A840-04320(160K) or higher.
*11 Available only for the FR-A800-GF series.
8. SPECIFICATIONS
8.3 Common specifications
801
8.4 Outline dimension drawings
(7.5)
2-φ6 hole
245
260
*1
7.5
(1.5)
6 5
7.5 95 D1
110 D
Inverter model D D1
FR-A820-00046(0.4K) 110 20
FR-A820-00077(0.75K) 125 35
*1 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth.
(Unit: mm)
802 8. SPECIFICATIONS
8.4 Outline dimension drawings
FR-A820-00105(1.5K), 00167(2.2K), 00250(3.7K)(-GF)
FR-A840-00023(0.4K), 00038(0.75K), 00052(1.5K), 00083(2.2K), 00126(3.7K)(-GF) 1
7.5
2-φ6 hole
*1
2
FAN
245
260
*2
4
(7.5)
(1.5)
6 5
12.5 125 140 6
150
8
45.5
10
8. SPECIFICATIONS
8.4 Outline dimension drawings
803
FR-A820-00340(5.5K), 00490(7.5K), 00630(11K)(-GF)
FR-A840-00170(5.5K), 00250(7.5K), 00310(11K), 00380(15K)(-GF)
(7.5)
2-φ6 hole
FAN
H1
H
*1
2.3
7.5
H2
6
12.5 195
220 D
D1
Inverter model H H1 H2 D D1
FR-A820-00340(5.5K), 00490(7.5K)
260 245 1.5 170 84
FR-A840-00170(5.5K), 00250(7.5K)
FR-A820-00630(11K)
300 285 3 190 101.5
FR-A840-00310(11K), 00380(15K)
*1 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth.
(Unit: mm)
804 8. SPECIFICATIONS
8.4 Outline dimension drawings
FR-A820-00770(15K), 00930(18.5K), 01250(22K)(-GF)
FR-A840-00470(18.5K), 00620(22K)(-GF) 1
2-φ10 hole
(10)
2
FAN
3
*1
380
400
4
2.3
6
10
10
(1.5)
10 230
250 190
8
93.3
*1 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth. 9
(Unit: mm)
10
8. SPECIFICATIONS
8.4 Outline dimension drawings
805
FR-A820-01540(30K)(-GF)
FR-A840-00770(30K)(-GF)
(10)
2-φ10 hole 4-φ20 hole for hanging 17
(15)
520
530
550
3.2 *1
15
10 3.2
10
270 195
325
*1 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth.
(Unit: mm)
806 8. SPECIFICATIONS
8.4 Outline dimension drawings
FR-A820-01870(37K), 02330(45K), 03160(55K), 03800(75K), 04750(90K)(-GF)
FR-A840-00930(37K), 01160(45K), 01800(55K), 02160(75K), 02600(90K), 03250(110K), 03610(132K)(-GF) 1
2-φ12 hole 4-φd hole D1
(18)
(15)
2
FAN
H2
H1
*2
H
5
7
12 3.2
W1
8
10
18
W D
Inverter model W W1 H H1 H2 d D D1 9
FR-A820-01870(37K), 02330(45K)
435 380 550 525 514 25 250 24
FR-A840-00930(37K), 01160(45K), 01800(55K)*1
FR-A820-03160(55K)*1 465 410 700 675 664 25 250 22 10
*1,
FR-A820-03800(75K) 04750(90K)*1 465 400 740 715 704 24 360 22
FR-A840-02160(75K)*1, 02600(90K)*1 465 400 620 595 584 24 300 22
*1 *1 465 400 740 715 704 25 360 22
FR-A840-03250(110K) , 03610(132K)
*1 For the FR-A820-03800(75K) or higher, the FR-A840-02160(75K) or higher, or whenever a 75 kW or higher motor is used, always connect a DC
reactor (FR-HEL), which is available as an option.
*2 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth.
(Unit: mm)
8. SPECIFICATIONS
8.4 Outline dimension drawings
807
FR-A840-04320(160K), 04810(185K)(-GF)
22
(15)
(13)
3-φ12 hole 4-φ16 hole
FAN
*1
1010
984
985
12 3.2
200 200
10
380
13
498
808 8. SPECIFICATIONS
8.4 Outline dimension drawings
FR-A840-05470(220K), 06100(250K), 06830(280K)(-GF)
1
22
(13)
3-φ12 hole
(13)
4-φ16 hole
2
FAN
*1
4
1010
984
984
5
12 3.2 8
13
13
300 300
680 380
9
Always connect a DC reactor (FR-HEL), which is available as an option.
*1 The LED display cover attached to the FR-A800-GF in this position has an additional 2.1 mm depth.
(Unit: mm)
10
Operation panel (FR-DU08)
Air-
72.5
78.5
20
72.5
bleeding
hole
5
22
cable
(FR-ADP option)
3 66 3 16
(Unit: mm)
8. SPECIFICATIONS
8.4 Outline dimension drawings
809
8.4.2 Dedicated motor outline dimension drawings
Dedicated motor (SF-V5RU(H)) outline dimension drawings (standard
horizontal type)
Frame number: 90L Frame number: 100L, 112M, 132S, 132M
A A
KP
I
H
C
A
KG
KG
A
6.5
C
4
φ27
Direction of φ27
Direction of
cooling fan wind F F XB E E cooling fan wind 40
F F XB
Mark for earthing N M Mark for earthing E E
(grounding) N
Earth (ground) terminal (M5) (grounding) M
Earth (ground) terminal (M5) W ML Sliding distance
W Sliding distance
15 4
U
U
T
T
9
12
S
Frame leg viewed from above S
Frame leg viewed
Section AA
Section AA from above
A B U V W G1 G2
810 8. SPECIFICATIONS
8.4 Outline dimension drawings
Frame Number: 160M, 160L, 180M, 180L Frame number: 200L, 225S
1
Connector (for encoder) Connector (for encoder)
MS3102A20-29P MS3102A20-29P
A
L
B
R
110
KL
A
L
B
R
140 D
2
D
KA 90 KA 110
Exhaust
Suction
φ90
Exhaust
With guard
wires
A Suction
With guard
3
I
A
KP
wires
KG
H
C
A
KG
φ56
8
Direction of A
C
50
4
cooling fan wind
11
Mark for earthing XB E E
(grounding) F F Direction of 70
M
N cooling fan wind Mark for earthing F F XB E E
Earth (ground) (grounding)
terminal (M8) N M
Sliding distance
W 4 Earth (ground) Sliding distance
W
5
U
terminal (M12)
T
4
14.5
U
T
18.5
S
Frame leg viewed
Section AA from above S
Frame leg viewed
Section AA from above
Earthing (grounding)
terminal (M8)
Make sure to earth the earth terminal of the flange section
7
as well as the earth terminal in the terminal box.
NOTE
• Install the motor with a frame number 180 or larger on the floor and use it with the shaft horizontal.
• Leave an enough clearance between the fan suction port and wall to ensure adequate cooling. Check that a fan blows air from
the opposite load side to the load side.
0
• The vertical tolerance for the shaft center height is -0.5 .
• The 400 V class motor has "-H" at the end of its model name.
8. SPECIFICATIONS
8.4 Outline dimension drawings
811
Dedicated motor (SF-V5RU(H)) outline dimension drawings (standard
horizontal type with brake)
Frame number: 90L Frame number: 100L, 112M, 132S, 132M
φ22
50 D 1
φ22
Exhaust Main QK
Exhaust Main 40 terminal box
Suction
Suction terminal box
1
1 1 A 2
KP
A
KP
H
A
KG
C
2 φ27
G
A
C
KG
Direction of
G
2 φ27 J
cooling fan wind
Direction of F F XB E E
Mark for earthing Mark for earthing
cooling fan wind (grounding) F F XB 2 E E N M
(grounding)
N M ML
Earth (ground)
Earth (ground) terminal (M5) W
terminal (M5) Sliding distance
W Sliding distance X
U
X
U
T
T
Z
Z
S
S Frame leg viewed
from above Section AA Frame leg viewed
Section AA from above
812 8. SPECIFICATIONS
8.4 Outline dimension drawings
Frame Number: 160M, 160L, 180M, 180L Frame number: 200L, 225S
1
Terminal box for cooling fan Connector (for encoder)
Connector (for encoder) MS3102A20-29P Terminal box for cooling fan
MS3102A20-29P
L L
A
KA
Main
B
R
110
90
KL
D
A
φ22 KA
B
R
140
110
D 2
Suction Exhaust terminal box 1 Main
terminal box
φ22
φ90
Exhaust
Suction
1, 2 A 2 1
KP
2
1, 2 A
KP
KG
H
φ56
C
KG
A
G
A
C
Direction of Mark for earthing
G
J
cooling fan wind (grounding) F F XB E E
Earth (ground) N Direction of Mark for earthing J
4
M (grounding) F F XB
terminal (M8) cooling fan wind E E
N M
W Sliding distance
X Earth (ground) W
U
Sliding distance
U
terminal (M12)
T
T
Z
Z
Frame leg viewed S
Section AA
from above Frame leg viewed
Section AA
from above
NOTE
• Install the motor on the floor and use it with the shaft horizontal.
• Leave an enough clearance between the fan suction port and wall to ensure adequate cooling. Check that a fan blows air from
the opposite load side to the load side.
• The vertical tolerance for the shaft center height is -0.5
0
.
• The 400 V class motor has "-H" at the end of its model name.
• Since a brake power device is a stand-alone, install it inside the enclosure. (This device should be arranged by the customer.
Refer to the FR-A800 catalog.)
8. SPECIFICATIONS
8.4 Outline dimension drawings
813
Dedicated motor (SF-V5RU(H)) outline dimension drawings (flange type)
Frame number: 90L Frame number: 100L, 112M, 132S, 132M
IE
LC
LB
D
B B A
LC
LB
D
A
KD B
Direction of
cooling fan wind
W KD A
Earth (ground) terminal (M5)
U
Direction of
Mark for earthing (grounding)
T
U
S Earth (ground) terminal (M5)
T
Section BB Mark for earthing (grounding)
S
Section BB
For cooling fan (A, B) Make sure to earth the earth terminal of the flange section as well as
For motor (U, V, W)
For thermal protector (G1, G2) the earth terminal in the terminal box.
A B U V W G1 G2
Earthing (grounding)
terminal (M4)
814 8. SPECIFICATIONS
8.4 Outline dimension drawings
Frame Number: 160M, 160L, 180M, 180L Frame number: 200L
IE
LA
IE
B A
LA
A
LC
LB
B
D
LC
LB
B
D
B
KD A KD A
3
Direction of
cooling fan wind Earth (ground) terminal (M12)
Direction of W
Earth (ground) terminal (M8) W Mark for earthing (grounding)
cooling fan wind
U
Mark for earthing (grounding) With guard wires
T
With guard wires
T
S 4
S Section BB
Section BB
For motor (U, V, W) Make sure to earth the earth terminal of the flange section as well as
5
the earth terminal in the terminal box.
Earthing (grounding)
terminal (M8) 6
7
For cooling fan (A, B, C) For thermal protector (G1, G2)
FF350
160L
180M
125
160
318
363
207
230
362
378.5
56
56
330
352
300
350
250j6
300j6
350
400
5
5
20
20
669
690
4
4
18.5
18.5
110
110
110
110
90
90
42k6
48k6
8
9
5
5.5
12
14
M8
M8
M4
M4
M4
M4
9
22 15 11 — 185
— 18 15 5 FF350 180L 225 363 230 416.5 56 352 350 300j6 400 5 20 728 4 18.5 110 110 90 55m6 10 6 16 M8 M4 M4
30 — — 7 270
FF400 200L 406 255 485 90 346 400 350j6 450 5 22 823.5 8 18.5 140 140 110 60m6 11 7 18 M10 M4 M4
37, 45 22, 30 18, 22 — 290
10
NOTE
• The motor with a frame number 180 or larger cannot be installed on the ceiling (with the shaft facing up). For use with the shaft
facing down, the protection rating of the cooling fan is IP20.
• Leave an enough clearance between the fan suction port and wall to ensure adequate cooling. Check that a fan blows air from
the opposite load side to the load side.
• The 400 V class motor has "-H" at the end of its model name.
8. SPECIFICATIONS
8.4 Outline dimension drawings
815
Dedicated motor (SF-V5RU(H)) outline dimension drawings (flange type
with brake)
Frame number: 90L Frame number: 100L, 112M, 132S, 132M
Connector (for encoder) Connector (for encoder) Terminal box for cooling fan
MS3102A20-29P Terminal box for cooling fan MS3102A20-29P
LL
LL
KB LR KB LR
LG LE Q KL
KL Exhaust LG LE
Exhaust Main Q Main 1
terminal box QK
terminal box QK Suction
φ22
Section A LN LZ
φ22
Suction Section
LN LZ AA
AA
KP
1
KP
1 1 2
B LA
D
B A
LC
LB
LC
LB
D
LA B A
B 2
2 A KD
KD
Direction of
Direction of 2 cooling fan wind W
cooling fan wind
W Earth (ground) terminal (M5)
U
Earth (ground) terminal (M5)
Mark for earthing (grounding)
U
T
Mark for earthing (grounding)
T
S
S
Section BB Section BB
B1 B2 U V W G1 G2 A B C
Earthing Earthing
(grounding) (grounding)
terminal (M4) terminal (M4)
816 8. SPECIFICATIONS
8.4 Outline dimension drawings
Frame number: 160M, 160L
φ22
terminal box LN LZ
Exhaust QK 1
Section
AA
Suction
KP
LA
1, 2 A 2
B
LC
LB
D
B
KD A
W
Direction of
U
cooling fan wind
T
Earth (ground) terminal (M8)
Mark for earthing (grounding)
S
Section BB
Main terminal box Terminal box for cooling fan indicates an inserting position of a bolt with hex head holes for
For motor (U, V, W)
For cooling fan (A, B, C)
manual opening.
Make sure to earth the earth terminal of the flange section as well as
Earthing A B C the earth terminal in the terminal box.
U V W
(grounding) Earthing
terminal (M8) (grounding)
terminal (M4)
B1 B2 G1 G2
NOTE
• Install the motor on the wall and use it with the shaft horizontal.
• Leave an enough clearance between the fan suction port and wall to ensure adequate cooling. Check that a fan blows air from
the opposite load side to the load side.
• The 400 V class motor has "-H" at the end of its model name.
• Since a brake power device is a stand-alone, install it inside the enclosure. (This device should be arranged by the customer.
Refer to the FR-A800 catalog.)
817 8. SPECIFICATIONS
8.4 Outline dimension drawings
Dedicated motor (SF-THY) outline dimension drawings (1500 r/min
series)
Frame number: 250MD, 280MD
75 to 160 kW
A R
PF4 Class B screw
B Q
KA
Connector (for encoder)
Terminal box for cooling fan MS3102A20-29P
QK
Suction Exhaust
KG
C
G
Direction of W
cooling fan wind K2 K2 J
U
T
K1 K E E
4-φZ hole
F F XB M
This hole is not used. N
S
A R
PF4 Class B screw
B Q
KA
Connector (for encoder)
Terminal box for cooling fan MS3102A20-29P
QK
Suction Exhaust
H
KG
C-1.0
0
Direction of
W
cooling fan wind
K2 K2 J
U
T
4-φZ hole K1 K E E
F F XB M
This hole is not used.
N S
NOTE
• The vertical tolerance for the shaft center height C is 0
-0.5 for the frame number 250, and 0
-1.0 for the frame number 280 or larger.
818 8. SPECIFICATIONS
8.4 Outline dimension drawings
CHAPTER 9
CHAPTER 9 APPENDIX
4
9.1 For customers replacing the conventional model with this inverter ......................................................................820
9.2 Specification comparison between PM sensorless vector control and induction motor control............................823
6
9.3 Parameters (functions) and instruction codes under different control methods....................................................824
9.4 For customers using HMS network options ..........................................................................................................851
7
10
819
9 APPENDIX
APPENDIX provides the reference information for use of this product.
Refer to APPENDIX as required.
Advanced
magnetic flux 120 Hz 400 Hz
vector control
Real sensorless
120 Hz 400 Hz
vector control
Vector control 120 Hz 400 Hz
PM sensorless
300 Hz 400 Hz
vector control
820 9. APPENDIX
9.1 For customers replacing the conventional model with this inverter
Item FR-A700 FR-A800
FR-DU08 (5-digit LED)
FR-DU07 (4-digit LED)
FR-LU08 (LCD operation panel) 1
PU FR-PU07 (Some functions, such as parameter copy, are
FR-PU07
unavailable.)
The FR-DU07 is not supported.
Plug-in option Dedicated plug-in options (not interchangeable) 2
Communication
Connected to the connector 3 Connected to the connector 1
option
For standard models, installation size is compatible for all capacities. (Replacement between the same capacities
Installation size does not require new mounting holes.) 3
For separated converter types, installation size is not compatible. (New mounting holes are required.)
An optional converter unit (FR-CC2) is required for
Converter Built-in for all capacities
separated converter types.
For the FR-A820-03800(75K) or higher, the FR-A840-
4
02160(75K) or higher, and when a 75 kW or higher
motor is used, select a DC reactor suitable for the
DC reactor The 75K or higher comes with a DC reactor (FR-HEL). applicable motor capacity. (A DC reactor is not
included.) 5
Separated converter types (converter unit FR-CC2) and
IP55 compatible models have a built-in DC reactor.
Brake unit
(75 kW or higher)
FR-BU2, MT-BU5 FR-BU2 6
Installation precautions
• Removal procedure of the front cover is different. (Refer to page 33.)
• Plug-in options of the FR-A700 series are not compatible.
7
• Operation panel (FR-DU07) cannot be used.
Wiring instructions 8
• The spring clamp type terminal block has changed to the screw type. Use of blade terminals is recommended.
9
Instructions for continuous use of the PU07 (parameter unit)
manufactured in September 2015 or earlier
• For the FR-A800 series, many functions (parameters) have been added. When setting these parameters, the parameter 10
names and setting ranges are not displayed.
• Only the parameter with the numbers up to "999" can be read and set. The parameters with the numbers after "999" cannot
be read or set.
• Many protective functions have been added for the FR-A800 series. These functions are available, but all faults are
displayed as "Fault". When the faults history is checked, "ERR" appears. Added faults will not appear on the parameter
unit. (However, MT1 to MT3 are displayed as MT.)
• Parameter copy/verification function are not available.
9. APPENDIX
9.1 For customers replacing the conventional model with this inverter
821
NOTE
• For the installation size and the outline dimensions of the separated converter type, refer to the FR-A802 (Separated Converter
Type) Instruction Manual (Hardware).
822 9. APPENDIX
9.1 For customers replacing the conventional model with this inverter
9.2 Specification comparison between PM sensorless 1
vector control and induction motor control
2
Item PM sensorless vector control (MM-CF) Induction motor control
IPM motor MM-CF series (0.5 to 7.0 kW) (Refer to page 798.)
Applicable motor
IPM motors other than MM-CF (tuning required)*1
Induction motor*1 3
200% (200% for the 1.5 kW or 200% (FR-A820-00250(3.7K) or
High frequency superposition
lower with MM-CF, 150% for the lower and FR-A840-00126(3.7K)
control
2.0 kW or higher) or lower)
150%: (FR-A820-00340(5.5K) or 4
Starting torque higher and FR-A840-00126(3.7K)
Current synchronization or higher)
50% under Real sensorless vector
operation
control and 5
Vector control
High frequency superposition Available (Select the HD rating for
control zero speed 200%.) Available under Real sensorless
Zero speed
Current synchronization
Not available
vector control and vector control
Available under Vector control. 6
operation
6 kHz (Pr.72 = "0 to 9"),
Any value in the range of 0.75
10kHz (Pr.72 = "10 to 13"),
High frequency superposition 14 kHz (Pr.72 = "14 to 15")
kHz to 14.5 kHz
(FR-A820-03160(55K) or lower
7
control (6 kHz in a low-speed range of 10
and FR-A840-01800(55K) or
kHz or higher.
lower)
2 kHz is not selectable.)
Carrier frequency
2kHz (Pr.72 = "0 to 5"), 8
6 kHz (Pr.72 = "6 to 9"),
0.75kHz to 6kHz
Current synchronization 10kHz (Pr.72 = "10 to 13"),
(FR-A820-03800(75K) or higher,
operation 14 kHz (Pr.72 = "14 to 15")
FR-A840-02160(75K) or higher.)
(6 kHz in a low-speed range of 10
kHz or higher.)
9
No startup waiting time.
Automatic restart after
Using the regeneration avoidance function or retry function together Startup waiting time exists.
instantaneous power failure
is recommended.
No startup delay (when online
10
Startup delay Startup delay of about 0.1 s for magnetic pole position detection. auto tuning is not performed at
startup).
Can be driven by the commercial
Driving by the commercial
Cannot be driven by the commercial power supply. power supply. (Other than vector
power supply
control dedicated motor.)
While the motor is coasting,
While the motor is coasting, potential is generated across motor
Operation during coasting potential is not generated across
terminals.
motor terminals.
Available under Real sensorless
Torque control Not available vector control and vector control.
Available under Vector control.
High frequency superposition
Available (sensorless)
control
Position control Available under Vector control.
Current synchronization
Not available
operation
*1 For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (It must be 0.4 kW or higher.)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
NOTE
• Before wiring, make sure that the motor is stopped. Otherwise you may get an electric shock.
• Never connect an IPM motor to the commercial power supply.
• No slippage occurs with an IPM motor because of its characteristic. If an IPM motor, which took over an induction motor, is
driven at the same speed as for the general-purpose motor, the running speed of the IPM motor becomes faster by the amount
of the general-purpose motor's slippage. Adjust the speed command to run the IPM motor at the same speed as the induction
motor, as required.
9. APPENDIX
9.2 Specification comparison between PM sensorless vector control and induction motor control
823
9.3 Parameters (functions) and instruction codes
under different control methods
*1 Instruction codes are used to read and write parameters in accordance with the Mitsubishi inverter protocol of RS-485 communication. (For RS-
485 communication, refer to page 636.)
*2 Function availability under each control method is shown as follows:
○: Available
×: Not available
∆: Available with some restrictions
*3 If function availability differs between using induction motors with an encoder and using PM motors with an encoder, the function availability using
PM motors with an encoder is described in parentheses. Also, a PM motor with an encoder is not available in the torque control mode.
*4 For Parameter copy, Parameter clear, and All parameter clear, ○ indicates the function is available, and × indicates the function is not available.
*5 Communication parameters that are not cleared by parameter clear or all clear (H5A5A or H55AA) via communication. (For RS-485
communication, refer to page 636.)
*6 When a communication option is installed, parameter clear (lock release) during password lock (Pr.297 Password lock/unlock ≠ ”9999”) can be
performed only from the communication option.
*7 Available when the IPM motor MM-CF series is used and the low-speed range high-torque characteristic is enabled (Pr.788 Low speed range
torque characteristic selection = "9999 (initial value)").
*8 Reading and writing via the PU connector are available.
Symbols in the table indicate parameters that operate when the options are connected.
FR-A8AP, FR-A8AL, FR-A8TP, FR-A8APR, FR-A8APS, FR-A8AR, FR-A8AX, FR-A8AY, FR-
A8AZ, FR-A8NC, FR-A8NCE, FR-A8ND, FR-A8NP, FR-A8NF, FR-A8NS
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
0 Torque boost 00 80 0 ○ × × × × × × × × ○ ○ ○
1 Maximum frequency 01 81 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2 Minimum frequency 02 82 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
3 Base frequency 03 83 0 ○ × × × × × × × × ○ ○ ○
4 Multi-speed setting (high speed) 04 84 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
Multi-speed setting (middle
5 05 85 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
speed)
6 Multi-speed setting (low speed) 06 86 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
7 Acceleration time 07 87 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
8 Deceleration time 08 88 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
9 Electronic thermal O/L relay 09 89 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
DC injection brake operation
10 0A 8A 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
frequency
DC injection brake operation
11 0B 8B 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
time
DC injection brake operation
12 0C 8C 0 ○ ○ × × × × × × × ○ ○ ○
voltage
13 Starting frequency 0D 8D 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
14 Load pattern selection 0E 8E 0 ○ × × × × × × × × ○ ○ ○
15 Jog frequency 0F 8F 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Jog acceleration/deceleration
16 10 90 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
time
17 MRS input selection 11 91 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
18 High speed maximum frequency 12 92 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
19 Base frequency voltage 13 93 0 ○ × × × × × × × × ○ ○ ○
Acceleration/deceleration
20 14 94 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
reference frequency
824 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
21
Acceleration/deceleration time
15 95 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
3
increments
Stall prevention operation level
22 16 96 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
(Torque limit level)
Stall prevention operation level 4
23 compensation factor at double 17 97 0 ○ ○ × × × × × × × ○ ○ ○
speed
24 Multi-speed setting (4 speed) 18 98 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
25 Multi-speed setting (5 speed) 19 99 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
5
26 Multi-speed setting (6 speed) 1A 9A 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
27 Multi-speed setting (7 speed) 1B 9B 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
28
Multi-speed input compensation
1C 9C 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○ 6
selection
Acceleration/deceleration
29 1D 9D 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
pattern selection
30 Regenerative function selection 1E 9E 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 7
31 Frequency jump 1A 1F 9F 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
32 Frequency jump 1B 20 A0 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
33
34
Frequency jump 2A
Frequency jump 2B
21
22
A1
A2
0
0
○
○
○
○
○
○
○
○
×
×
○
○
○
○
○
○
×
×
○
○
○
○
○
○
8
35 Frequency jump 3A 23 A3 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
36 Frequency jump 3B 24 A4 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
37 Speed display 25 A5 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 9
41 Up-to-frequency sensitivity 29 A9 0 ○ ○ ○ × × ○ × ○ × ○ ○ ○
42 Output frequency detection 2A AA 0 ○ ○ ○ ∆ ∆ ○ ∆ ○ ∆ ○ ○ ○
Output frequency detection for
43
reverse rotation
2B AB 0 ○ ○ ○ ∆ ∆ ○ ∆ ○ ∆ ○ ○ ○ 10
Second acceleration/
44 2C AC 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
deceleration time
45 Second deceleration time 2D AD 0 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
46 Second torque boost 2E AE 0 ○ × × × × × × × × ○ ○ ○
47 Second V/F (base frequency) 2F AF 0 ○ × × × × × × × × ○ ○ ○
Second stall prevention
48 30 B0 0 ○ ○ × × × × × × × ○ ○ ○
operation level
Second stall prevention
49 31 B1 0 ○ ○ × × × × × × × ○ ○ ○
operation frequency
Second output frequency
50 32 B2 0 ○ ○ ○ ∆ ∆ ○ ∆ ○ ∆ ○ ○ ○
detection
Second electronic thermal O/L
51 33 B3 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
relay
Operation panel main monitor
52 34 B4 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
FM/CA terminal function
54 36 B6 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
55 Frequency monitoring reference 37 B7 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
56 Current monitoring reference 38 B8 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
57 Restart coasting time 39 B9 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
58 Restart cushion time 3A BA 0 ○ ○ × × × × × × × ○ ○ ○
59 Remote function selection 3B BB 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
60 Energy saving control selection 3C BC 0 ○ ○ × × × × × × × ○ ○ ○
○
61 Reference current 3D BD 0 ○ ○ × × ○ × × × ○ ○ ○
(×)
○
62 Reference value at acceleration 3E BE 0 ○ ○ × × ○ × × × ○ ○ ○
(×)
9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
825
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
○
63 Reference value at deceleration 3F BF 0 ○ ○ × × ○ × × × ○ ○ ○
(×)
Starting frequency for elevator
64 40 C0 0 ○ × × × × × × × × ○ ○ ○
mode
65 Retry selection 41 C1 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Stall prevention operation
66 42 C2 0 ○ ○ × × × × × × × ○ ○ ○
reduction starting frequency
Number of retries at fault
67 43 C3 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
occurrence
68 Retry waiting time 44 C4 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
69 Retry count display erase 45 C5 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
70 Special regenerative brake duty 46 C6 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
71 Applied motor 47 C7 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
72 PWM frequency selection 48 C8 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
73 Analog input selection 49 C9 0 ○ ○ ○ ○ × ○ ○ ○ × ○ × ○
74 Input filter time constant 4A CA 0 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Reset selection/disconnected
75 4B CB 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ×
PU detection/PU stop selection
76 Fault code output selection 4C CC 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
77*8 Parameter write selection 4D CD 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Reverse rotation prevention
78 4E CE 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
79*8 Operation mode selection 4F CF 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
80 Motor capacity 50 D0 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
81 Number of motor poles 51 D1 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○
82 Motor excitation current 52 D2 0 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
○
83 Rated motor voltage 53 D3 0 × ○ ○ ○ ○ ○ ○ × ○ ○ ○
(×)
84 Rated motor frequency 54 D4 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
85 Excitation current break point 55 D5 0 × ○ × × × ○ ○ × × ○ × ○
Excitation current low speed
86 56 D6 0 × ○ × × × ○ ○ × × ○ × ○
scaling factor
Speed control gain (Advanced
89 59 D9 0 × ○ × × × × × × × ○ × ○
magnetic flux vector)
90 Motor constant (R1) 5A DA 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
○ ○
91 Motor constant (R2) 5B DB 0 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
Motor constant (L1)/d-axis
92 5C DC 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
inductance (Ld)
Motor constant (L2)/q-axis
93 5D DD 0 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
inductance (Lq)
○ ○
94 Motor constant (X) 5E DE 0 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
○ ○
95 Online auto tuning selection 5F DF 0 × ○ ○ ○ ○ × × ○ ○ ○
(×) (×)
○
96 Auto tuning setting/status 60 E0 0 × ○ ○ ○ ○ ○ ○ × ○ × ○
(×)
100 V/F1 (first frequency) 00 80 1 ○ × × × × × × × × ○ ○ ○
101 V/F1 (first frequency voltage) 01 81 1 ○ × × × × × × × × ○ ○ ○
102 V/F2 (second frequency) 02 82 1 ○ × × × × × × × × ○ ○ ○
103 V/F2 (second frequency voltage) 03 83 1 ○ × × × × × × × × ○ ○ ○
104 V/F3 (third frequency) 04 84 1 ○ × × × × × × × × ○ ○ ○
105 V/F3 (third frequency voltage) 05 85 1 ○ × × × × × × × × ○ ○ ○
826 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
115
Third stall prevention operation
0F 8F 1 ○ ○ × × × × × × × ○ ○ ○
6
frequency
116 Third output frequency detection 10 90 1 ○ ○ ○ ∆ ∆ ○ ∆ ○ ∆ ○ ○ ○
117
PU communication station
number
11 91 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5 7
118 PU communication speed 12 92 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
PU communication stop bit
119 13 93 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
length / data length 8
120 PU communication parity check 14 94 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
121 PU communication retry count 15 95 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
122
PU communication check time
interval
16 96 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5 9
PU communication waiting time
123
setting
17 97 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
124
PU communication CR/LF
selection
18 98 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5 10
Terminal 2 frequency setting
125 19 99 1 ○ ○ ○ ○ × ○ ○ ○ × ○ × ○
gain frequency
Terminal 4 frequency setting
126 1A 9A 1 ○ ○ ○ ○ × ○ ○ ○ × ○ × ○
gain frequency
PID control automatic switchover
127 1B 9B 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
frequency
128 PID action selection 1C 9C 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
129 PID proportional band 1D 9D 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
130 PID integral time 1E 9E 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
131 PID upper limit 1F 9F 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
132 PID lower limit 20 A0 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
133 PID action set point 21 A1 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
134 PID differential time 22 A2 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
Electronic bypass sequence ○
135 23 A3 1 ○ ○ × × ○ × × × ○ ○ ○
selection (×)
○
136 MC switchover interlock time 24 A4 1 ○ ○ × × ○ × × × ○ ○ ○
(×)
○
137 Start waiting time 25 A5 1 ○ ○ × × ○ × × × ○ ○ ○
(×)
○
138 Bypass selection at a fault 26 A6 1 ○ ○ × × ○ × × × ○ ○ ○
(×)
Automatic switchover frequency ○
139 27 A7 1 ○ ○ × × ○ × × × ○ ○ ○
from inverter to bypass operation (×)
Backlash acceleration stopping
140 28 A8 1 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
frequency
Backlash acceleration stopping
141 29 A9 1 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
time
9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
827
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
Backlash deceleration stopping
142 2A AA 1 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
frequency
Backlash deceleration stopping
143 2B AB 1 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
time
144 Speed setting switchover 2C AC 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
145 PU display language selection 2D AD 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ×
Acceleration/deceleration time
147 2F AF 1 ○ ○ ○ ○ ∆ ○ ○ ○ ∆ ○ ○ ○
switching frequency
148 Stall prevention level at 0 V input 30 B0 1 ○ ○ × × × × × × × ○ ○ ○
Stall prevention level at 10 V
149 31 B1 1 ○ ○ × × × × × × × ○ ○ ○
input
150 Output current detection level 32 B2 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Output current detection signal
151 33 B3 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
delay time
152 Zero current detection level 34 B4 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
153 Zero current detection time 35 B5 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Voltage reduction selection
154 36 B6 1 ○ ○ × × × × × × × ○ ○ ○
during stall prevention operation
RT signal function validity
155 37 B7 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
condition selection
Stall prevention operation
156 38 B8 1 ○ ○ ○ × × ○ × ○ × ○ ○ ○
selection
157 OL signal output timer 39 B9 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
158 AM terminal function selection 3A BA 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Automatic switchover frequency
○
159 range from bypass to inverter 3B BB 1 ○ ○ × × ○ × × × ○ ○ ○
(×)
operation
160 User group read selection 00 80 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Frequency setting/key lock
161 01 81 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
operation selection
Automatic restart after
162 instantaneous power failure 02 82 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
selection
163 First cushion time for restart 03 83 2 ○ ○ × × × × × × × ○ ○ ○
164 First cushion voltage for restart 04 84 2 ○ ○ × × × × × × × ○ ○ ○
Stall prevention operation level
165 05 85 2 ○ ○ × × × × × × × ○ ○ ○
for restart
Output current detection signal
166 06 86 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
retention time
Output current detection
167 07 87 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
operation selection
168
Parameter for manufacturer setting. Do not set.
169
170 Watt-hour meter clear 0A 8A 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
171 Operation hour meter clear 0B 8B 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
User group registered display/
172 0C 8C 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
batch clear
173 User group registration 0D 8D 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
174 User group clear 0E 8E 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
178 STF terminal function selection 12 92 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
179 STR terminal function selection 13 93 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
180 RL terminal function selection 14 94 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
181 RM terminal function selection 15 95 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
182 RH terminal function selection 16 96 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
828 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
242
Terminal 1 added compensation
32 B2 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
10
amount (terminal 2)
Terminal 1 added compensation
243 33 B3 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
amount (terminal 4)
244 Cooling fan operation selection 34 B4 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
245 Rated slip 35 B5 2 ○ × × × × × × × × ○ ○ ○
246 Slip compensation time constant 36 B6 2 ○ × × × × × × × × ○ ○ ○
Constant output range slip
247 37 B7 2 ○ × × × × × × × × ○ ○ ○
compensation selection
Self power management ×
248 38 B8 2 ○ ○ × × × × ○ × ○ ○ ○
selection (○)
Earth (ground) fault detection at
249 39 B9 2 ○ ○ × × × × × × × ○ ○ ○
start
250 Stop selection 3A BA 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Output phase loss protection
251 3B BB 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
252 Override bias 3C BC 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
253 Override gain 3D BD 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Main circuit power OFF waiting ×
254 3E BE 2 ○ ○ × × × × ○ × ○ ○ ○
time (○)
255 Life alarm status display 3F BF 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
Inrush current limit circuit life
256 40 C0 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
display
Control circuit capacitor life
257 41 C1 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
display
258 Main circuit capacitor life display 42 C2 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
Main circuit capacitor life
259 43 C3 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
measuring
9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
829
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
PWM frequency automatic
260 44 C4 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
switchover
261 Power failure stop selection 45 C5 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Subtracted frequency at
262 46 C6 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
deceleration start
263 Subtraction starting frequency 47 C7 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
264 Power-failure deceleration time 1 48 C8 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
265 Power-failure deceleration time 2 49 C9 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Power failure deceleration time
266 4A CA 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
switchover frequency
267 Terminal 4 input selection 4B CB 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
268 Monitor decimal digits selection 4C CC 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
269 Parameter for manufacturer setting. Do not set.
Stop-on contact/load torque
270 high- speed frequency control 4E CE 2 ○ ○ ○ × × ○ × × × ○ ○ ○
selection
High-speed setting maximum
271 4F CF 2 ○ ○ ○ × × ○ × × × ○ ○ ○
current
Middle-speed setting minimum
272 50 D0 2 ○ ○ ○ × × ○ × × × ○ ○ ○
current
273 Current averaging range 51 D1 2 ○ ○ ○ × × ○ × × × ○ ○ ○
Current averaging filter time
274 52 D2 2 ○ ○ ○ × × ○ × × × ○ ○ ○
constant
Stop-on contact excitation
275 53 D3 2 × ○ × × × ○ × × × ○ ○ ○
current low-speed scaling factor
PWM carrier frequency at stop-
276 54 D4 2 × ○ × × × ○ × × × ○ ○ ○
on contact
278 Brake opening frequency 56 D6 2 ○ ○ ○ × × ○ × ○ × ○ ○ ○
279 Brake opening current 57 D7 2 ○ ○ ○ × × ○ × ○ × ○ ○ ○
Brake opening current detection
280 58 D8 2 ○ ○ ○ × × ○ × ○ × ○ ○ ○
time
281 Brake operation time at start 59 D9 2 ○ ○ ○ × × ○ × ○ × ○ ○ ○
282 Brake operation frequency 5A DA 2 ○ ○ ○ × × ○ × ○ × ○ ○ ○
283 Brake operation time at stop 5B DB 2 ○ ∆ ○ × × × × ○ × ○ ○ ○
Deceleration detection function
284 5C DC 2 × ∆ ○ × × ○ × ○ × ○ ○ ○
selection
Overspeed detection frequency
285 (Speed deviation excess 5D DD 2 × ∆ ○ × × × × × × ○ ○ ○
detection frequency)
286 Droop gain 5E DE 2 × ○ ○ × × ○ × ○ × ○ ○ ○
287 Droop filter time constant 5F DF 2 × × ○ × × ○ × ○ × ○ ○ ○
Droop function activation
288 60 E0 2 × ○ ○ × × ○ × ○ × ○ ○ ○
selection
289 Inverter output terminal filter 61 E1 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
Monitor negative output
290 62 E2 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
291 Pulse train I/O selection 63 E3 2 ○ ○ ○ ○ × ○ ○ ○ × ○ × ○
Automatic acceleration/ ∆
292 64 E4 2 ∆ ∆ × × ∆ × × × ○ ○ ○
deceleration (×)
Acceleration/deceleration ○
293 65 E5 2 ○ ○ × × ○ × × × ○ ○ ○
separate selection (×)
294 UV avoidance voltage gain 66 E6 2 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Frequency change increment
295 67 E7 2 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
amount setting
830 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
299
Rotation direction detection
selection at restarting
6B EB 2 ○ ○ × × × ○ × × × ○ ○ ○ 4
300 BCD input bias 00 80 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
301 BCD input gain 01 81 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
302 BIN input bias 02 82 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○ 5
303 BIN input gain 03 83 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
Digital/analog input
304 compensation enable/disable
selection
04 84 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
6
Read timing operation
305 05 85 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
selection
306
Analog output signal
selection
06 86 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 7
Setting for zero analog
307 07 87 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
output
308
Setting for maximum analog
08 88 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 8
output
Analog output voltage/current
309 09 89 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
signal switchover
310
Analog meter voltage output
0A 8A 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
9
selection
Setting for zero analog meter
311 0B 8B 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
voltage output
312
Setting for maximum analog
0C 8C 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
10
meter voltage output
313 DO0 output selection 0D 8D 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
314 DO1 output selection 0E 8E 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
315 DO2 output selection 0F 8F 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
316 DO3 output selection 10 90 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
317 DO4 output selection 11 91 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
318 DO5 output selection 12 92 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
319 DO6 output selection 13 93 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
320 RA1 output selection 14 94 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
321 RA2 output selection 15 95 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
322 RA3 output selection 16 96 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
323 AM0 0 V adjustment 17 97 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
324 AM1 0 mA adjustment 18 98 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
Motor temperature feedback ○ ○
326 1A 9A 3 × × ○ × × × × ○ × ○
reference (×) (×)
329 Digital input unit selection 1D 9D 3 ○ ○ ○ ○ × ○ ○ ○ × ○ × ○
RS-485 communication station
331
number
1F 9F 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
831
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
RS-485 communication check
336
time interval
24 A4 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
RS-485 communication waiting
337
time setting
25 A5 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
Communication operation
338
command source
26 A6 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
Communication speed
339
command source
27 A7 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
Communication startup mode
340
selection
28 A8 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
RS-485 communication CR/LF
341
selection
29 A9 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
Communication EEPROM write
342 2A AA 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
343 Communication error count 2B AB 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ × × ×
345 DeviceNet address 2D AD 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
346 DeviceNet baud rate 2E AE 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
Communication reset
349 31 B1 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
selection
Stop position command
350 32 B2 3 ○ ○ ○ × × × × × × ○ ○ ○
selection
Orientation
351 33 B3 3 ○ ○ ○ × × × × × × ○ ○ ○
speed
352 Creep speed 34 B4 3 ○ ○ ○ × × × × × × ○ ○ ○
Creep switchover
353 35 B5 3 ○ ○ ○ × × × × × × ○ ○ ○
position
Position loop switchover
354 36 B6 3 ○ ○ ○ × × × × × × ○ ○ ○
position
DC injection brake start
355 37 B7 3 ○ ○ ○ × × × × × × ○ ○ ○
position
Internal stop position
356 38 B8 3 ○ ○ ○ × × × × × × ○ ○ ○
command
Orientation in-position
357 39 B9 3 ○ ○ ○ × × × × × × ○ ○ ○
zone
Servo torque
358 3A BA 3 ○ ○ ○ × × × × × × ○ ○ ○
selection
Encoder rotation ○ ○
359 3B BB 3 ○ ○ ○ × × × × ○ ○ ○
direction (∆) (∆)
16-bit data
360 3C BC 3 ○ ○ ○ × × × × × × ○ ○ ○
selection
361 Position shift 3D BD 3 ○ ○ ○ × × × × × × ○ ○ ○
Orientation position loop
362 3E BE 3 ○ ○ ○ × × × × × × ○ ○ ○
gain
Completion signal output delay
363 3F BF 3 ○ ○ ○ × × × × × × ○ ○ ○
time
Encoder stop check
364 40 C0 3 ○ ○ ○ × × × × × × ○ ○ ○
time
Orientation
365 41 C1 3 ○ ○ ○ × × × × × × ○ ○ ○
limit
366 Recheck time 42 C2 3 ○ ○ ○ × × × × × × ○ ○ ○
Speed feedback
367 43 C3 3 ○ ○ × × × × × × × ○ ○ ○
range
Feedback
368 44 C4 3 ○ ○ × × × × × × × ○ ○ ○
gain
832 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
369
Number of encoder
45 C5 3 ○ ○
○
○
○
× × × × ○ ○ ○
3
pulses (×) (×)
Encoder position tuning setting/ ×
373 49 C9 3 × × × × × × × × ○ × ○
status (○)
374 Overspeed detection level 4A CA 3 × × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
4
Encoder signal loss detection
376 enable/disable 4C CC 3 × × ○ ○ ○ × × × ○ ○ ○ ○
selection
SSCNET III rotation direction
5
379 4F CF 3 × × ○ ○ ○ × × × × ○ ○*5 ○*5
selection
380 Acceleration S-pattern 1 50 D0 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
381 Deceleration S-pattern 1 51 D1 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○ 6
382 Acceleration S-pattern 2 52 D2 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
383 Deceleration S-pattern 2 53 D3 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
384 Input pulse division scaling factor 54 D4 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
385 Frequency for zero input pulse 55 D5 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○ 7
Frequency for maximum input
386 56 D6 3 ○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○
pulse
393
Orientation
selection
5D DD 3 × × ○ × × × × × × ○ ○ ○ 8
Number of machine side gear
394 5E DE 3 × × ○ × × × × × × ○ ○ ○
teeth
395
Number of motor side gear
teeth
5F DF 3 × × ○ × × × × × × ○ ○ ○ 9
Orientation speed gain (P
396 60 E0 3 × × ○ × × × × × × ○ ○ ○
term)
397
Orientation speed integral
61 E1 3 × × ○ × × × × × × ○ ○ ○
10
time
Orientation speed gain (D
398 62 E2 3 × × ○ × × × × × × ○ ○ ○
term)
Orientation deceleration
399 63 E3 3 × × ○ × × × × × × ○ ○ ○
ratio
High resolution analog input
406 06 86 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
selection
Motor temperature detection
407 07 87 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
filter
408 Motor thermistor selection 08 88 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
413 Encoder pulse division ratio 0D 8D 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
414 PLC function operation selection 0E 8E 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ×
Inverter operation lock mode
415 0F 8F 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
setting
416 Pre-scale function selection 10 90 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
417 Pre-scale setting value 11 91 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Extension output terminal
418 12 92 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
filter
Position command source
419 13 93 4 × × × × ○ × × × ○ ○ ○ ○
selection
Command pulse scaling factor
420 numerator (electronic gear 14 94 4 × × × × ○ × × × ○ ○ ○ ○
numerator)
Command pulse multiplication
421 denominator (electronic gear 15 95 4 × × × × ○ × × × ○ ○ ○ ○
denominator)
422 Position control gain 16 96 4 × × × × ○ × × × ○ ○ ○ ○
9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
833
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
423 Position feed forward gain 17 97 4 × × × × ○ × × × ○ ○ ○ ○
Position command acceleration/
424 18 98 4 × × × × ○ × × × ○ ○ ○ ○
deceleration time constant
Position feed forward command
425 19 99 4 × × × × ○ × × × ○ ○ ○ ○
filter
426 In-position width 1A 9A 4 × × × × ○ × × × ○ ○ ○ ○
427 Excessive level error 1B 9B 4 × × × × ○ × × × ○ ○ ○ ○
428 Command pulse selection 1C 9C 4 × × × × ○ × × × ○ ○ ○ ○
429 Clear signal selection 1D 9D 4 × × × × ○ × × × ○ ○ ○ ○
430 Pulse monitor selection 1E 9E 4 × × × × ○ × × × ○ ○ ○ ○
Pulse train torque command
432 20 A0 4 × × × ○ × × ○ × × ○ ○ ○
bias
Pulse train torque command
433 21 A1 4 × × × ○ × × ○ × × ○ ○ ○
gain
Network number (CC-Link
434 22 A2 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
IE)
435 Station number (CC-Link IE) 23 A3 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○*5 ○*5
446 Model position control gain 2E AE 4 × × × × ○ × × × ○ ○ ○ ○
447 Digital torque command bias 2F AF 4 × × × ○ × × ○ × × ○ ○ ○
448 Digital torque command gain 30 B0 4 × × × ○ × × ○ × × ○ ○ ○
449 SSCNET III input filter setting 31 B1 4 × × ○ ○ ○ × × × ○ ○ ○*5 ○*5
450 Second applied motor 32 B2 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Second motor control method
451 33 B3 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
selection
453 Second motor capacity 35 B5 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
454 Number of second motor poles 36 B6 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○
455 Second motor excitation current 37 B7 4 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
○
456 Rated second motor voltage 38 B8 4 × ○ ○ ○ ○ ○ ○ × ○ ○ ○
(×)
457 Rated second motor frequency 39 B9 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
458 Second motor constant (R1) 3A BA 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
○ ○
459 Second motor constant (R2) 3B BB 4 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
Second motor constant (L1) / d-
460 3C BC 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
axis inductance (Ld)
Second motor constant (L2) / q-
461 3D BD 4 × ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○
axis inductance (Lq)
○ ○
462 Second motor constant (X) 3E BE 4 × ○ ○ ○ ○ × × ○ × ○
(×) (×)
Second motor auto tuning ○
463 3F BF 4 × ○ ○ ○ ○ ○ ○ × ○ × ○
setting/status (×)
Digital position control sudden
464 40 C0 4 × × × × ○ × × × ○ ○ ○ ○
stop deceleration time
465 First target position lower 4 digits 41 C1 4 × × × × ○ × × × ○ ○ ○ ○
466 First target position upper 4 digits 42 C2 4 × × × × ○ × × × ○ ○ ○ ○
Second target position lower 4
467 43 C3 4 × × × × ○ × × × ○ ○ ○ ○
digits
Second target position upper 4
468 44 C4 4 × × × × ○ × × × ○ ○ ○ ○
digits
Third target position lower 4
469 45 C5 4 × × × × ○ × × × ○ ○ ○ ○
digits
Third target position upper 4
470 46 C6 4 × × × × ○ × × × ○ ○ ○ ○
digits
834 9. APPENDIX
9.3 Parameters (functions) and instruction codes under different control methods
Instruction
Control method*2 Parameter
code*1
Vector *3 Sensorless PM 1
Position control*7
Position control
Torque control
Torque control
Speed control
Speed control
Speed control
All clear*4
Extended
Pr. Name
Magnetic flux
Copy*4
Clear*4
Write
V/F
Read
2
471
Fourth target position lower 4
47 C7 4 × × × × ○ × × × ○ ○ ○ ○
3
digits
Fourth target position upper 4
472 48 C8 4 × × × × ○ × × × ○ ○ ○ ○
digits
473 Fifth target position lower 4 digits 49 C9 4 × × × × ○ × × × ○ ○ ○ ○ 4
474 Fifth target position upper 4 digits 4A CA 4 × × × × ○ × × × ○ ○ ○ ○
Sixth target position lower 4
475 4B CB 4 × × × × ○ × × × ○ ○ ○ ○
digits
Sixth target position upper 4
5
476 4C CC 4 × × × × ○ × × × ○ ○ ○ ○
digits
Seventh target position lower 4
477 4D CD 4 × × × × ○ × × × ○ ○ ○ ○
digits 6
Seventh target position upper 4
478 4E CE 4 × × × × ○ × × × ○ ○ ○ ○
digits
Eighth target position lower 4
479 4F CF 4 × × × × ○ × × × ○ ○ ○ ○
digits 7
Eighth target position upper 4
480 50 D0 4 × × × × ○ × × × ○ ○ ○ ○
digits
Ninth target position lower 4
481
digits
51 D1 4 × × × × ○ × × × ○ ○ ○ ○
8
Ninth target position upper 4
482 52 D2 4 × × × × ○ × × × ○ ○ ○ ○
digits
Tenth target position lower 4
483
digits
53 D3 4 × × × × ○ × × × ○ ○ ○ ○
9
Tenth target position upper 4
484 54 D4 4 × × × × ○ × × × ○ ○ ○ ○
digits
Eleventh target position lower 4
485
digits
55 D5 4 × × × × ○ × × × ○ ○ ○ ○ 10
Eleventh target position upper 4
486 56 D6 4 × × × × ○ × × × ○ ○ ○ ○
digits
Twelfth target position lower 4
487 57 D7 4 × × × × ○ × × × ○ ○ ○ ○
digits
Twelfth target position upper 4
488 58 D8 4 × × × × ○ × × × ○ ○ ○ ○
digits
Thirteenth target position lower 4
489 59 D9 4 × × × × ○ × × × ○ ○ ○ ○
digits
Thirteenth target position upper
490 5A DA 4 × × × × ○ × × × ○ ○ ○ ○
4 digits
Fourteenth target position lower
491 5B DB 4 × × × × ○ × × × ○ ○ ○ ○
4 digits
Fourteenth target position upper
492 5C DC 4 × × × × ○ × × × ○ ○ ○ ○
4 digits
Fifteenth target position lower 4
493