Current Transformer White Paper 071415
Current Transformer White Paper 071415
Current Transformer White Paper 071415
Ratio
The CT ratio is the ratio of primary current input to secondary current output at full load. For example, a CT with a ratio of 300:5 is
rated for 300 primary amps at full load and will produce 5 amps of secondary current when 300 amps flow through the primary.
If the primary current changes the secondary current output will change proportionally. For example, if 150 amps flow through
the 300 amp rated primary the secondary current output will be 2.5 amps (150:300 = 2.5:5).
Polarity
The polarity of a CT is determined by the direction the coils are wound around the core of the CT (clockwise or counter-
clockwise) and by the way the leads, if any, are brought out of the transformer case.
All current transformers are subtractive polarity and will have the following designations to guide proper installation:
(H1) primary current, line facing direction; (H2) primary current, load facing direction; and (X1) secondary current.
Taking care to observe proper polarity is important when installing and connecting current transformers to power metering and
protective relays.
Relaying Accuracy CTs are not as accurate as Metering Accuracy CTs. They
Metering Accuracy Clasifications
are designed to perform with a reasonable degree of accuracy over a wider
range of current. These CTs are typically used for supplying current to 0.3 B 0.2
protective relays. The wider range of current allows the protective relay to Accuracy CT Maximum
operate at different fault levels. in % Class Burden
in Ohms
The CT Accuracy Class is listed on the label or the nameplate of the CT and
is comprised of three parts: rated ratio accuracy rating, class rating, and Relaying Accuracy CTs
maximum burden (Figure 2). 2.5 C 100
Rated Ratio Accuracy Rating is a number which is the rated ratio expressed Accuracy CT Maximum
in % Class in Volts
as a percent. For example, a CT with an accuracy class of 0.3 is certified by @20 times CT
the manufacturer to be accurate to within 0.3 percent of its rated ratio value Amp Rating
for a primary current of 100 percent of rated ratio.
Figure 2: Examples of Accuracy Classifications for
Metering CTs and Relaying (Protection) CTs.
CT Class Rating is a letter that designates the application for which the CT is rated. Metering CTs are designated with the letter B.
Relaying CTs have several different letter designations:
C: The CT has low leakage flux. (Accuracy can be calculated before manufacturing.)
T: The CT can have significant leakage flux. (Accuracy must be determined by testing at the factory.)
H: The CT accuracy is applicable within the entire range of secondary currents from 5 to 20 times the nominal CT rating.
(Typically wound primary CTs.)
L: The CT accuracy applies at the maximum rated secondary burden at 20 time the rated current. The ratio accuracy can be
up to four times greater than the listed value, depending on connected burden and fault current. (Typically window,
busing, or bar-type CTs.)
The third part of the CT Accuracy Class is the maximum burden allowed for the CT. This is the load that may be imposed on a
transformer secondary without causing an error greater than the stated accuracy classification. For Metering Class CTs burden is
expressed as ohms impedance. For Protection-class CTs burden is express as volt-amperes (VA). Protection-class CT burdens are
displayed as the maximum secondary volts allowable if 20 times the CT rating were to flow through the secondary circuit (100
amperes with a five-ampere nominal CT secondary).
3. Make sure the total burden does not exceed the specified 14 0.56 66.3 105.9 171.8 273.2 434.1 692.2
limits for the CT. 16 0.64 75.7 121.0 196.3 312.2 496.1 791.1
18 0.72 85.2 136.1 220.9 351.2 558.1 890.0
Examples of Burden Calculations:
20 0.80 94.7 151.2 245.4 390.2 620.2 988.9
Metering CT: The ratio of a 0.3B0.1 rated Metering CT is 25 1.00 118.3 189.0 306.7 487.8 775.2 1,236.1
accurate to 0.3 percent if the connected secondary burden 30 1.20 142.0 226.8 368.1 585.4 930.2 1483.3
if impedance does not exceed 0.1 ohms. A 0.6B8 rated 35 1.40 165.7 264.7 429.4 682.9 1,085.3 1,730.5
metering-class CT will operate within 0.6 percent accuracy if 40 1.60 189.3 302.5 490.8 780.5 1,240.3 1,977.8
the secondary burden does not exceed 8.0 ohms. 45 1.80 213.0 340.3 552.1 878.0 1,395.3 2,225.0
50 2.00 236.7 378.1 613.5 975.6 1,550.4 2,472.2
Relaying (Protection) CT: A 2.5C100 Relaying CT is accurate
within 2.5 percent if the secondary burden is less than 1.0 1
See the NK Technologies’ Product Catalog for Allowable Burden. Add any other
resistance such as terminations, etc.
ohm (100 volts/100 amperes). 2
Lead length is the total wire run (out and back). Divide by two to get the lead
distance.
3
Resistance for 5 Amp output CTs.
A current transformer can also be used as an input to a current relay or transmitter, or to reduce the current so that a current
switch or transducer can be utilized. Simply short the secondary of the CT through the sensing window of the sensor. A trip
point between 1 and 5 amps can be established with a current switch. Use a current transducer with a range of 0–5 amps, or if
the CT secondary is looped through the sensor twice, a transducer with a range of 0–10 amps can be used.