1EM GEN 4 Ducted IndoorUnits
1EM GEN 4 Ducted IndoorUnits
1EM GEN 4 Ducted IndoorUnits
For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc.
Table of Contents
Introduction
Low Static Ducted Indoor Units..................................................... 53-72
Mechanical Specifications.................................................................. 54 Acronyms............................................................................................ 129
General Data...................................................................................... 55
Electrical Data.................................................................................... 56
External Dimensions........................................................................... 57
Electrical Wiring Diagrams............................................................ 58-61
Refrigerant Flow Diagrams................................................................. 62
External Static Pressure and Air Flow........................................... 63-64
External Static Pressure Ranges........................................................ 65
Acoustic Data..................................................................................... 66
Capacity Tables............................................................................. 69-72
TABLE OF sYMBOLS
DANGER This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
This symbol indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action should not be completed.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 3
unit nomenclature
ARN U 07 3 TN C 4
Family
ARN = Multi V Indoor Unit
(Refrigerant R410A)
Type
U = DC Inverter Heat Pump
MULTI V Ducted Indoor Unit Engineering Manual
Electrical Ratings
3 = 208–230V/60Hz/1Ph
Model
B3 = Ducted (low static - bottom return) NJ = Vertical/Horizontal Air Handling Unit TN = 4-Way Ceiling Cassette
B4 = Ducted (low static - bottom return) NK = Vertical/Horizontal Air Handling Unit TP = 4-Way Ceiling Cassette
B8 = Ducted (high static) S8 = Wall Mounted/Mirror (large frame) TQ = 4-Way Ceiling Cassette
BG = Ducted (high static) SE = Wall Mounted/Mirror (small frame) TR = 4-Way Ceiling Cassette
BR = Ducted (high static) SB = Standard Wall Mounted VE = Convertible Surface Mounted
CE = Floor Standing (small frame) SC = Standard Wall Mounted VJ = Ceiling Suspended
CF = Floor Standing (large frame) TT = 1-Way Ceiling Cassette
L1 = Ducted (low static) TU = 1-Way Ceiling Cassette
L2 = Ducted (low static) TL = 2-Way Ceiling Cassette
L3 = Ducted (low static) TM = 4-Way Ceiling Cassette
Feature
A = Basic L = Neo Plasma
C = Plasma Filter R = Mirror and Neo Plasma
G = Low Static U = Uncased
Generation
2 = Second
4 = Fourth
A = Second, Revision A
Due to our policy of continuous product innovation, some specifications may change without notification.
4 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Indoor Unit Overview
Wall-Mounted / Ceiling Cassette
Introduction
123 TUC4 12,300 13,600 353/325/290
183 TTC4 Body: 46-1/2 x 17-3/4 x 6-7/8 19,100 21,500 470/427/385 Body: 42
243 TTC4 Panel: 55-15/16 x 19-3/4 x 1-3/8 24,200 24,200 515/470/406 Panel: 13 3/8, 5/8
Ceiling Cassette–Two Way
183 TLC4 19,100 21,500 459/424/353 1/4, 1/2
Body: 32-11/16 x 21-5/8 x 8-7/8 Body: 49
Panel: 41-5/16 x 25-3/16 x 1-5/8 Panel: 11
243 TLC4 24,200 27,300 601/530/459 3/8, 5/8
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 5
Indoor Unit Overview
Ducted
Due to our policy of continuous product innovation, some specifications may change without notification.
6 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Indoor Unit Overview
Surface Mounted / Floor Standing
Ceiling Suspended
183VJA2 19,100 21,500 565/495/424 1/4, 1/2
37-7/16 x 8-11/16 x 25-5/8 55
243VJA2 24,200 27,300 636/565/495 3/8, 5/8
Introduction
093 CEA4 9,600 10,900 335/300/265
42 x 8 x 25 60
123 CEA4 12,300 13,600 371/335/300 1/4, 1/2
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 7
Controllers Overview
Zone Controllers and Communication Cables
PQRCVCL0Q Black
Simple Controller with Allows control of indoor unit on/off, operation mode, fan speed,
164
mode selection and temperature setpoint for up to 16 indoor units.
PQRCVCL0QW White
PQRCHCA0Q Black
Simple Controller Allows control of indoor unit on/off, fan speed, and temperature
164
MULTI V Ducted Indoor Unit Engineering Manual
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
Wired Remote Group Required when grouping multiple indoor units with a single
PZCWRCG3 33
Control Cable Assembly zone controller.
Wired Remote/Group Control Increases the distance between a remote controller and an
PZCWRC1 33
Extension Cable indoor unit or between indoor units in a control group.
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
Due to our policy of continuous product innovation, some specifications may change without notification.
8 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Specialty Application Devices
Introduction
3 Digital Outputs: Max. 2A@30VAC/DC
Third party equipment 4 Analog Outputs: 0 to 10 VDC,
AC
control. Allows system configurable; 0 to 20 mA, configurable
PEXPMB000. Smart IV
I/O Module expansion through --- 4 Universal Inputs individually
ENCXLUS and
Digital and Analog configurable as analog or digital:
ACP IV
inputs and outputs. Analog: Voltage. Current. Thermistor
(NTC, PT, Ni)
Digital for Dry Contact input only
PRARH0 Third party Adds coordinated control of an
Auxiliary Heater Indoor
supplemental heat 0/1 external heater with normal heat
Relay Kit Unit
PRARS0 control pump operations.
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 9
Controllers Overview
Central Controllers
Table 7: Central Controllers (connect to the outdoor unit terminals Internet A, Internet B).
No. of Binary
Devices Systems Devices Comm
Central per Comm per Comm Bus Signals Power,
Name Model No. per Description
Controller Input/ Conn
Controller Bus Bus Ports Output
Monitors / operates indoor units
through a touch screen. Manages
up to 128 devices. Advanced
functions include programmable
schedules, temperature setpoint
range lock, remote controller lock,
PACS4B000. 2 DI / run time limit, manual control and
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
10 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Integration Solutions
Table 8: Summary Data—Integration Solutions (connect to outdoor unit terminals Internet A, Internet B).
Devices Systems No. of Binary
Devices Comm
Integration per Signals
Name Model No. per per Comm Power Description
Solution Controller Comm Bus Input/
Bus
Bus Ports Output
ACP IV
BACnet® PQNFB17C1 256 16 256 4 24 VAC 10/4 Allow integration of LG equipment
Gateway for control and monitoring by open
protocol BACnet® and LonWorks®
building automation and controls
LonWorks®
PLNWKB100 64 16 64 1 24 VAC 2/2 systems.*
Gateway
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
* BACnetTM is a trademark of ASHRAE; LonWorksTM is a trademark of Echlelon Corporation.
Introduction
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 11
Controllers Overview
Options and Features
Nominal Chassis Size (MBh) 5–24 7–24 7–24 18–24 5–18 24–48 7–96 7–24
Air supply outlets 1 1 1 2 4 4 1 1
Airflow direction (left/right) manual auto
Auto airflow direction (up/down) √ √ √ √ √ √
Fan speed (Heating mode) 3 3 4 4 4 4 3 3
MULTI V Ducted Indoor Unit Engineering Manual
Airflow
Washable anti-fungal2 √ √ √ √ √ √ √ √
7-day programmable controller o o o o o o o o
Simple controller w/mode o o o o o o o o
Simple controller w/o mode o o o o o o o o
Wireless controller o o o o o o o4 o4
Condensate lift √ √ √ √ √ √
Ventilation air √ √5 √5 √ √
Casing √ √ √ √ √ √
Others
Standard grille √ √ √ √
Auto elevation grille o
Suction grille
Suction canvas
Aux. heat kit
1
For Heat Recovery systems only. √ = Standard feature
2
Primary washable filters. o = Unit option
3
Secondary plasma filters.
4
Requires 7-day programmable zone controller.
5
Requires ventilation kit PTVK430 or PTVK410+PTVK420 (For TP, TN, TM frames)(Temperature, humidity, and volume limitations apply).
6
Heat Pump systems only.
Due to our policy of continuous product innovation, some specifications may change without notification.
12 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Options and Features
Nominal Chassis Size (MBh) 7–24 12-36 42-53 18–24 9–12 7–24 7–24
Air supply outlets 1 1 1 1 1 1 1
Airflow direction (left/right) manual manual
Auto airflow direction (up/down) √ √
Fan speed (Heating mode) 3 3 3 3 3 3 3
Airflow
Introduction
Auto operation6 √ √ √ √ √ √ √
Auto clean (coil dry)
Child lock √ √ √ √ √ √ √
Dual thermistor control √ √ √ √ √ √ √
Operation
Washable anti-fungal2 √ √ √ √ √
7-day programmable controller o o o o o
Simple controller w/mode o o o o o o o
Simple controller w/o mode o o o o o o o
Wireless controller o4 o o o o o4 o4
Condensate lift √
Ventilation air √
Casing √ √ √
Others
Standard grille
Auto elevation grille
Suction grille o
Suction canvas o
Aux. heat kit √ √
1
For Heat Recovery systems only. √ = Standard feature
2
Primary washable filters. o = Unit option
3
Secondary plasma filters.
4
Requires 7-day programmable zone controller.
5
Requires ventilation kit PTVK430 or PTVK410+PTVK420 (For TP, TN, TM frames)(Temperature, humidity, and volume limitations apply).
6
Heat Pump systems only.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 13
LATS Multi V Piping
Design Software
To ensure that the refrigerant piping design meets LG’s quality standards, a LATS refrigerant piping design must be provided with
every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be
created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.
Design Choices
LATS Multi V software is flexible, offering the HVAC system engineer an easy to use Tree mode.
Tree Mode
Using the Tree mode, the engineer can quickly create a one-line schematic drawing of a Multi V system. Integration of the engineered pipe
system into the building drawings is done at a later date by the draftsperson using standard drafting software tools.
LATS Report
LATS Multi V software generates a report file (.xls format) containing
project design parameters, cooling and heating design day system
component performance, and capacity data. The report calculates
the system combination ratio, calculates the system refrigerant
charge, and provides detailed bill of material information including a
list of Multi V outdoor units, air handlers, control devices, accesso-
ries, refrigerant pipe sizes segregated by building, by system, by pipe
size, and by pipe segments.
Due to our policy of continuous product innovation, some specifications may change without notification.
14 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
HIGH STATIC
Mechanical Specifications on page 16
General Data on page 17
Electrical Data on page 20
External Dimensions on page 21
Electrical Wiring Diagram on page 24
Refrigerant Flow Diagrams on page 30
External Static Pressure and Air Flow on page 32
External Static Pressure Ranges on page 34
Acoustic Data on page 36
Capacity Tables on page 42
Optional Accessories on page 51
DUCTED High Static
Mechanical Specifications
The unit has Sirocco fans made of high strength ABS GP-2200 lers and/or a wall-mounted remote temperature sensor. The unit
polymeric resin. Fans are directly driven and mounted on a common microprocessor is capable of accepting space temperature readings
shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) concurrently or individually from either:
design with permanently lubricated and sealed ball bearings. The 1. Wall-mounted wired controller(s)
fan motor includes thermal, overcurrent and low RPM protection. 2. Factory mounted return air thermistor or the optional wall-
The fan/motor assembly is mounted on vibration attenuating rubber mounted wired remote temperature sensor
grommets. The fan impeller is statically and dynamically balanced. A single indoor unit has the capability of being controlled by up to
The fan speed is controlled using a microprocessor based, direct two local wired controllers. The microprocessor controls space
digital control algorithm that provides a high fan speed in cooling temperature using the value provided by the temperature sensor
thermal ON and low fan speed in cooling thermal OFF, high fan sensing a space temperature that is farthest away from the tem-
speed in heating thermal ON and fan off in heating thermal OFF. The perature set-point. The microprocessor control provides a cooling or
fan speeds can be field adjusted between low, medium, and high heating mode test cycle that operates the unit for 18 minutes without
speeds and DIP switch settings will allow the fan to run constantly regard to the space temperature. If the system is provided with an
during defrost or oil return modes. Each setting can be field adjusted optional wall-mounted local or central controller, displayed diagnostic
from the factory setting (RPM / ESP) to compensate for additional codes are specific, alpha numeric, and provide the service technician
resistance to airflow caused by field connected ductwork or other with a reason for the code displayed.
airflow restricting devices.
Condensate Lift/Pump
Air Filter The indoor unit is provided with a factory installed and wired conden-
Return air is filtered with a removable, washable filter with antifungal sate lift/pump capable of providing a minimum 27.5 inch lift from the
treatment. MERV 13 filter modules with plenums available. bottom exterior surface of the unit casing. The unit drain pan is pro-
vided with a secondary drain port/plug allowing the pan to be drained
Microprocessor Controls for service. The lift pump comes with a safety switch that will shut off
The unit is provided with an integrated microprocessor-based con- indoor unit if condensate rises too high in the drain pan.
troller. The controller is capable of performing functions necessary
to operate the system without the use of a wall-mounted controller. Condensate Drain Pan
A temperature thermistor is factory-mounted in the return air stream. The condensate drain pan is constructed of HIPS (high impact poly-
All unit operation parameters, excluding the unit operating schedule, styrene resin).
are stored in non-volatile memory resident on the unit microproces-
sor. Operating schedules are stored in select models of the optional, Coil
wall-mounted, local, or central controller. The field supplied commu- The indoor unit coil is constructed with grooved design copper tubes
nication cable between the indoor unit(s) and outdoor unit is to be with slit coil fins, two (2) to three (3) rows, nineteen (19) to twen-
a minimum of 18 AWG, 2-conductor, stranded, and shielded cable ty-one (21) fins per inch.
(RS-485), terminated via screw terminals on the control boards.
The microprocessor control provides the following functions: auto Controls Features
addressing, self-diagnostics, auto restart following power restoration, • Auto changeover • Group control
test run, and will operate the indoor unit using one of five operating
modes: (Heat Recovery only) • External static pressure control
1. Auto Changeover (Heat Recovery only) • Auto operation • Hot start
2. Heating • Auto restart • Self diagnostics
3. Cooling • Child lock • Timer (on / off)
4. Dry • Dual thermistor control • Weekly schedule
5. Fan Only • Dual setpoint control • Fan speed control
For Heat Recovery systems the Auto Changeover setting automati- • Filter life and power consump- • Ventilation (outside air)
cally switches control of the indoor unit between cooling and heating tion display
modes based on space temperature conditions.
For Heat Pump systems, heated or cooled air delivery is dependent • Multiple auxiliary heater
upon outdoor unit operating mode. applications
Due to our policy of continuous product innovation, some specifications may change without notification.
16 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
General Data
BG Units
Table 11: Ducted High Static (BG Frame) Indoor Unit General Data.
Model No. ARNU073BGA4 ARNU093BGA4 ARNU123BGA4 ARNU153BGA4 ARNU183BGA4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100
Power Input1 (W) 450 450 450 450 450
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500
Power Input (W) 1
450 450 450 450 450
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
35 / 35 / 34 35 / 35 / 34 36 / 35 / 34 37 / 36 / 33 41 / 39 / 37
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 17
DUCTED HIGH STATIC
General Data
BG Units
Table 12: Ducted High Static (BG Frame) Indoor Unit General Data, continued.
Model No. ARNU243BGA4 ARNU283BGA4 ARNU363BGA4 ARNU423BGA4
Cooling Mode Performance
Capacity (Btu/h) 24,200 28,000 36,200 42,000
Power Input1 (W) 450 450 450 450
Heating Mode Performance
Capacity (Btu/h) 27,300 31,500 40,600 43,800
Power Input (W)1
450 450 450 450
Entering Mixed Air
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
18 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
General Data
BR and B8 Units
Table 13: Ducted High Static (BR and B8 Frames) Indoor Unit General Data.
Model No. ARNU483BRA4 ARNU543BRA4 ARNU763B8A4 ARNU963B8A4
Cooling Mode Performance
Capacity (Btu/h) 48,100 54,000 76,400 95,900
Power Input1 (W) 450 450 800 800
Heating Mode Performance
Capacity (Btu/h) 51,200 61,400 86,000 107,500
Power Input (W) 1
450 450 800 800
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76
Heating Min. (°F DB) 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
45 / 43 / 41 46 / 45 / 43 50 / 48 / 48 52 / 50 / 50
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 19
Ducted High Static
Electrical Data
Table 14: Ducted High Static (BG, BR, and B8 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
BG Units
ARNU073BGA4 3.3 2.65 450 450
ARNU093BGA4 3.3 2.65 450 450
ARNU123BGA4 3.3 2.65 450 450
ARNU153BGA4 3.3 2.65 450 450
ARNU183BGA4 208-230 3.3 15 2.65 60 208-230 1 450 450
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
20 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Dimensions
BG Units
41 4-1/2
Power Supply
8-5/8
Connection
Liquid Pipe
Connection: 3/8 4
48-1/2 1-1/4
2-1/16
15/16 Air Return
2-1/16
6-9/16
1-7/8
5-7/8
8-7/8
1-15/16
ø4
8
2-3/
17-3/4
14
5-9/16
4-13/16
8-5/8
3-7/16
1-15/16
22-1/4 Air Supply
3
1-3/16
10-1/4
3-7/16
Gas Pipe Drain Pipe
32-11/16 Connection: 5/8 Connection: 1
46-9/16 4-1/4
7-5/16
6-1/4
11-3/4
4-7/16
Center of Gravity
17-3/4
Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.
46-9/16
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 21
Ducted High Static
External Dimensions
BR Units
Liquid Pipe
Connection: 3/8
Gas Pipe
Connection: 5/8 3-15/16
MULTI V Ducted Indoor Unit Engineering Manual
50-1/2 3-1/4
4-9/16
2-13/16
48-7/16
1
Air Return
4-13/16
8-3/4
7-3/4
12-1/4
R6
0
3-9/16
23-5/16
/8
2-3
18-3/4
5-11/16
4-13/16
11-7/8
1-1/4
11-9/16
7
15
6-7/8
7
Center of Gravity
Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.
48-7/16
Due to our policy of continuous product innovation, some specifications may change without notification.
22 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Dimensions
B8 Units
Power
Supply
Connection Gas Pipe
4-9/16 Connection
13/16
2-3/4
4-3/4
7/8
18-1/8 63-7/8 6 3-
5-9/1
61-5/8
Liquid Pipe Drain Pipe
2-1/2
Air Return
Connection: 3/8 Connection: 1
2-3/4
2-1/4
3/4
2-3/8
4-7/8
15-11/16
2-5/8
14
44-3/16
12-9/16
11-1/2
18-1/8
8-3/4
6-3/8
Center of Gravity
27-3/8
Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.
61-1/2
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 23
Ducted High Static
Electrical Wiring Diagram
BG Units
Due to our policy of continuous product innovation, some specifications may change without notification.
24 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
BG Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 25
Ducted High Static
Electrical Wiring Diagram
BR Units
Due to our policy of continuous product innovation, some specifications may change without notification.
26 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
BR Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 27
Ducted High Static
Electrical Wiring Diagram
B8 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
28 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
B8 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 29
Ducted High Static
Refrigerant Flow Diagram
BG, BR Units
Cooling
Heat Exchanger EEV Heating
Filter
TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
30 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Refrigerant Flow Diagram
B8 Units
TH3 TH2
Check
Sirocco Fan Valve
Solenoid Valve
Filter
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 31
Ducted High Static
External Static Pressure and Air Flow Tables
BG, BR, B8 Units
Table 25: BG Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.15 0.19 0.23 0.27 0.31 0.35 0.39 0.47 0.55 0.62
70 - - - - - - - - - -
80 285 141 - - - - - - - -
90 498 427 243 145 - - - - - -
100 672 600 547 388 218 148 - - - -
110 780 755 692 619 494 409 233 - - -
120 925 911 847 769 699 632 515 427 - -
130 1,066 1,059 1,006 951 893 826 769 639 515 399
MULTI V Ducted Indoor Unit Engineering Manual
140 1,281 1,271 1,133 1,073 1,024 968 914 762 628 512
143 1,334 1,324 1,197 1,133 1,084 1,017 960 812 709 593
150 1,465 1,447 1,432 1,271 1,218 1,133 1,063 928 791 642
160 1,500 1,497 1,469 1,349 1,274 1,236 1,221 1,098 946 822
Table 26: BR Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.19 0.23 0.31 0.39 0.47 0.55 0.59 0.62 0.66 0.70 0.78
91 1,642 1,543 1,349 1,105 819 494 317 130 - - -
96 1,762 1,628 1,518 1,183 1,098 649 483 317 91 - -
101 1,839 1,772 1,691 1,395 1,320 964 889 628 314 215 -
106 1,815 1,808 1,779 1,568 1,522 1,176 1,133 1,020 741 632 293
111 1,892 1,896 1,868 1,762 1,705 1,433 1,419 1,158 1,112 960 618
116 - - - 1,967 1,794 1,582 1,504 1,416 1,327 1,147 974
121 - - - - 1,843 1,794 1,776 1,613 1,575 1,370 1,137
126 - - - - - - 1,921 1,808 1,779 1,624 1,536
Table 27: B8 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.23 0.35 0.47 0.59 0.71 0.79 0.86 0.90 0.98
60 1,430 - - - - - - - -
65 1,861 - - - - - - - -
70 2,249 1,663 - - - - - - -
75 2,511 2,009 1,578 - - - - - -
80 2,694 2,461 1,949 - - - - - -
85 2,941 2,775 2,380 1,974 - - - - -
91 3,167 3,076 2,786 2,387 1,914 - - - -
95 3,298 3,227 3,040 2,719 2,345 1,787 1,059 - -
100 3,298 3,227 3,118 2,998 2,680 2,454 2,147 1,522 -
105 3,291 3,224 3,118 2,998 2,864 2,733 2,443 2,398 1,811
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
32 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Static Pressure and Air Flow Charts
BG, BR, B8 Units
Figure 10: BG Unit External Static Pressure and Air Flow Chart.
0.65
P
0.55 ESP
Setting
160
ESP
Setting
0.45 150
ESP ESP
Setting Setting
130 140
ESP
0.35 Setting
120
ESP
Setting
110
0.25 ESP
Setting
100
0.15
100 300 500 700 900 1100 1300 1500
Q (CFM)
Figure 11: BR Unit External Static Pressure and Air Flow Chart.
0.25
0.15
100 600 1100 1600
Q (CFM)
Figure 12: B8 Unit External Static Pressure and Air Flow Chart.
1
P
0.9
ESP
Setting
0.8 105
0.7
ESP
Setting
0.6 95
0.5 ESP
Setting
0.4 85
ESP
0.3 Setting
75
0.2
1000 1500 2000 2500 3000
Q (CFM)
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 33
Ducted High Static
External Static Pressure Ranges
BG, BR, B8 Units
High 93 533
Standard Mid 89 0.15 484 0.15 0.31
Low 86 434
High 100 477
High
Mid 96 0.23 427 0.23 0.47
(Factory Set)
Low 93 332
ARNU123BGA4 12.3
High 95 586
Standard Mid 92 0.15 533 0.15 0.31
Low 89 483
High 112 540
High
Mid 100 0.31 219 0.31 0.62
(Factory Set)
Low 95 127
ARNU153BGA4 15.4
High 102 576
Standard Mid 96 0.23 427 0.23 0.39
Low 89 240
High 113 562
High
Mid 110 0.31 494 0.31 0.62
(Factory Set)
Low 100 219
ARNU183BGA4 19.1
High 110 692
Standard Mid 100 0.23 547 0.23 0.39
Low 93 332
High 120 699
High
Mid 113 0.31 562 0.31 0.62
(Factory Set)
Low 100 219
ARNU243BGA4 24.2
High 112 720
Standard Mid 100 0.23 547 0.23 0.39
Low 95 396
High 127 660
High
Mid 120 0.39 516 0.31 0.62
(Factory Set)
Low 113 332
ARNU283BGA4 28.0
High 113 562
Standard Mid 102 0.31 304 0.23 0.39
Low 97 180
High 151 1,084
High
Mid 145 0.39 1,024 0.31 0.55
(Factory Set)
Low 139 894
ARNU363BGA4 36.2
High 138 1,003
Standard Mid 130 0.31 894 0.23 0.39
Low 124 770
High 157 1,218
High
Mid 154 0.39 1,141 0.31 0.47
(Factory Set)
Low 151 1,084
ARNU423BGA4 42.0
High 145 1,130
Standard Mid 138 0.31 1,003 0.31 0.39
Low 134 961
The table above shows the available E.S.P. range.
Due to our policy of continuous product innovation, some specifications may change without notification.
34 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Static Pressure Ranges
BG, BR, B8 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 35
Ducted High Static
Acoustic Data
Sound Pressure Levels
Figure 13: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
DISCHARGE SUCTION • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
DUCT DUCT Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3 ft.
4.9 ft.
6.6 ft. tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.
MULTI V Ducted Indoor Unit Engineering Manual
Table 31: Ducted High Static Indoor Unit Sound Pressure Levels.
Sound Pressure Levels dB(A)
Model
High Fan Speed Medium Fan Speed Low Fan Speed
BG Units
ARNU073BGA4 35 35 34
ARNU093BGA4 35 35 34
ARNU123BGA4 36 35 34
ARNU153BGA4 37 36 33
ARNU183BGA4 41 39 37
ARNU243BGA4 42 39 37
ARNU283BGA4 42 41 40
ARNU363BGA4 44 43 42
ARNU423BGA4 45 44 44
BR Units
ARNU483BRA4 45 43 41
ARNU543BRA4 46 45 43
B8 Units
ARNU763B8A4 50 48 48
ARNU963B8A4 52 50 50
Figure 14: ARNU073BGA4, ARNU093BGA4, and ARNU123BGA4 Sound Pressure Level Diagrams.
ARNU073BGA4 ARNU093BGA4 ARNU123BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
36 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Pressure Levels
Figure 15: ARNU153BGA4, ARNU183BGA4, and ARNU243BGA4 Sound Pressure Level Diagrams.
ARNU153BGA4 ARNU183BGA4 ARNU243BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 37
Ducted High Static
Acoustic Data
Sound Pressure Levels
ARNU483BRA4 ARNU543BRA4
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
38 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Power Levels
Table 32: Ducted High Static Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions.
Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
Model • Sound power level is measured using rated conditions, and tested
High Fan Speed
BG Units in a reverberation room per ISO 3741 standards.
ARNU073BGA4 53 • Sound level will vary depending on a range of factors such as
ARNU093BGA4 54 construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
ARNU123BGA4 55
ARNU153BGA4 56 • Reference acoustic intensity: 0dB = 10E-6μW/m2
ARNU183BGA4 58
ARNU243BGA4 60
ARNU283BGA4 61
ARNU363BGA4 62
ARNU423BGA4 64
BR Units
ARNU483BRA4 62
ARNU543BRA4 65
B8 Units
ARNU763B8A4 70
Figure 19: ARNU073BGA4, ARNU093BGA4, and ARNU123BGA4 Sound Power Level Diagrams.
ARNU073BGA4 ARNU093BGA4 ARNU123BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 39
Ducted High Static
Acoustic Data
Sound Power Levels
Figure 20: ARNU153BGA4, ARNU183BGA4, and ARNU243BGA4 Sound Power Level Diagrams.
ARNU153BGA4 ARNU183BGA4 ARNU243BGA4
MULTI V Ducted Indoor Unit Engineering Manual
Figure 21: ARNU283BGA4, ARNU363BGA4, and ARNU423BGA4 Sound Power Level Diagrams.
ARNU283BGA4 ARNU363BGA4 ARNU423BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
40 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Power Levels
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 41
Ducted High Static
Cooling Capacity Tables
ARNU073BGA4, ARNU093BGA4, ARNU123BGA4
ARNU073BGA4 /
65 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.4 6.1
7.5
70 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.3 6.0
75 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.1 5.9
80 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.7 6.2 8.8 5.9
85 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.3 6.2 8.4 6.0 8.6 5.6
90 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.2 6.1 8.3 5.9 8.4 5.6
95 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.0 6.1 8.2 5.8 8.3 5.5
100 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 7.9 6.0 8.0 5.8 8.2 5.5
105 4.9 4.5 5.7 4.9 6.4 5.3 7.2 5.6 7.3 5.6 7.7 5.6 7.9 5.3
110 4.8 4.4 5.4 4.7 6.0 4.9 6.8 5.3 6.9 5.3 7.3 5.3 7.7 5.2
23 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
25 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
30 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
35 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
40 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
45 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
50 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
55 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
60 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.3 7.9
ARNU093BGA4 /
65 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.1 7.8
9.6
70 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 11.9 7.7
75 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 11.6 7.5
80 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.1 7.9 11.3 7.4
85 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.6 8.0 10.8 7.6 11.0 7.2
90 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.5 7.8 10.6 7.4 10.8 7.1
95 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.3 7.8 10.5 7.4 10.6 7.0
100 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.1 7.7 10.3 7.3 10.5 6.9
105 6.3 5.7 7.3 6.3 8.2 6.7 9.2 7.2 9.4 7.2 9.9 7.1 10.1 6.8
110 6.2 5.6 6.9 5.9 7.7 6.3 8.6 6.7 8.8 6.7 9.4 6.7 9.8 6.6
23 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
25 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
30 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
35 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
40 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
45 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
50 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
55 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
60 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.7 10.2
ARNU123BGA4 /
65 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.5 10.0
12.3
70 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.3 9.8
75 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 14.9 9.6
80 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.2 10.2 14.5 9.6
85 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.6 10.2 13.8 9.7 14.0 9.2
90 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.4 10.1 13.5 9.6 13.8 9.1
95 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.2 10.0 13.4 9.5 13.6 9.0
100 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 12.9 9.8 13.2 9.4 13.4 8.9
105 8.1 7.4 9.3 8.1 10.6 8.7 11.8 9.2 12.0 9.2 12.7 9.1 12.9 8.7
110 7.9 7.1 8.9 7.6 9.8 8.1 11.1 8.7 11.3 8.7 12.0 8.7 12.6 8.4
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
42 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Cooling Capacity Tables
ARNU153BGA4, ARNU183BGA4, ARNU243BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 43
Ducted High Static
Cooling Capacity Tables
ARNU283BGA4, ARNU363BGA4, ARNU423BGA4
ARNU283BGA4 /
65 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 35.3 21.6
28.0
70 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 34.7 21.2
75 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 33.9 20.8
80 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 32.5 21.9 33.0 20.7
85 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.1 22.1 31.4 21.0 31.9 19.9
90 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.5 21.7 30.8 20.6 31.4 19.6
95 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.0 21.5 30.5 20.5 31.1 19.4
100 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 29.4 21.2 30.0 20.3 30.5 19.2
105 18.5 15.9 21.3 17.4 24.1 18.7 26.9 19.9 27.4 19.9 28.8 19.6 29.4 18.8
110 17.9 15.4 20.2 16.5 22.4 17.4 25.2 18.6 25.8 18.7 27.4 18.7 28.6 18.2
23 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
25 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
30 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
35 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
40 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
45 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
50 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
55 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
60 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.3 28.3
ARNU363BGA4 /
65 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 45.6 27.9
36.2
70 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 44.9 27.5
75 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 43.8 26.8
80 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 42.0 28.4 42.7 26.7
85 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.2 28.5 40.5 27.1 41.3 25.7
90 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 39.5 28.0 39.8 26.7 40.5 25.3
95 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.7 27.9 39.5 26.5 40.2 25.1
100 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.0 27.4 38.7 26.3 39.5 24.9
105 23.9 20.6 27.5 22.5 31.1 24.1 34.8 25.7 35.5 25.7 37.3 25.4 38.0 24.3
110 23.2 19.9 26.1 21.3 29.0 22.4 32.6 24.1 33.3 24.1 35.5 24.1 36.9 23.6
23 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
25 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
30 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
35 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
40 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
45 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
50 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
55 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.1
60 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 53.8 32.9
ARNU423BGA4 /
65 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.9 32.4
42.0
70 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.1 31.9
75 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 50.8 31.1
80 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 48.7 32.9 49.6 31.0
85 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 46.6 33.1 47.0 31.4 47.9 29.8
90 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 45.8 32.5 46.2 31.0 47.0 29.3
95 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.9 32.3 45.8 30.8 46.6 29.1
100 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.1 31.8 44.9 30.5 45.8 28.8
105 27.7 23.9 31.9 26.0 36.1 28.0 40.3 29.8 41.2 29.8 43.3 29.4 44.1 28.2
110 26.9 23.1 30.2 24.7 33.6 26.0 37.8 28.0 38.6 28.0 41.2 28.0 42.8 27.4
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
44 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Cooling Capacity Tables
ARNU483BRA4, ARNU543BRA4, ARNU763B8A4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 45
Ducted High Static
Cooling Capacity Tables
ARNU963B8A4
ARNU963B8A4 /
65 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 120.8 69.9
95.9
70 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 118.9 68.8
75 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 116.0 67.2
80 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 111.2 71.1 113.2 67.0
85 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 106.4 71.4 107.4 67.9 109.3 64.4
90 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 104.5 70.2 105.5 66.9 107.4 63.3
95 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 102.6 69.8 104.5 66.5 106.4 62.9
100 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 100.7 68.8 102.6 65.9 104.5 62.3
105 63.3 51.5 72.9 56.3 82.5 60.4 92.1 64.4 94.0 64.4 98.8 63.6 100.7 60.8
110 61.4 50.0 69.0 53.3 76.7 56.2 86.3 60.4 88.2 60.5 94.0 60.5 97.8 59.1
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
46 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Heating Capacity Tables
ARNU073BGA4, ARNU093BGA4, ARNU123BGA4, ARNU153BGA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 47
Ducted High Static
Heating Capacity Tables
ARNU183BGA4, ARNU243BGA4, ARNU283BGA4, ARNU363BGA4
40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.2 24.2 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 24.8
ARNU243BGA4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 24.3
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.8
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.8
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.8
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.8
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.8
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
-4 -4.4 21.1 21.1 21.1 21.1 20.8 20.8 20.8 20.8
0 -0.4 21.7 21.7 21.7 21.7 21.7 21.4 21.4 21.4
5.0 4.5 24.6 24.3 23.9 23.9 23.9 23.9 23.9 23.9
10.0 9.0 25.5 25.5 25.5 25.2 25.2 25.2 25.2 25.2
15.0 14.0 27.1 27.1 27.1 27.1 27.1 27.1 26.8 26.5
20.0 19.0 28.7 28.7 28.7 28.7 28.0 28.0 27.6 27.2
25.0 23.0 29.9 29.9 29.9 29.9 29.9 29.3 29.0 28.7
ARNU283BGA4 /
30.0 28.0 30.6 30.6 30.6 30.6 30.6 29.9 29.0 28.1
28.0
35.0 32.0 31.5 31.5 31.5 31.5 31.2 30.6 29.0 27.5
40.0 36.0 32.8 32.8 32.8 32.8 31.5 30.6 29.0 27.5
45.0 41.0 34.0 34.0 34.0 33.1 31.5 30.6 29.0 27.5
47.0 43.0 35.3 35.0 34.7 33.1 31.5 30.6 29.0 27.5
50.0 46.0 37.9 36.2 34.7 33.1 31.5 30.6 29.0 27.5
55.0 51.0 38.5 36.5 34.7 33.1 31.5 30.6 29.0 27.5
60.0 56.0 38.5 36.5 34.7 33.1 31.5 30.6 29.0 27.5
-4 -4.4 27.2 27.2 27.2 27.2 26.8 26.8 26.8 26.8
0 -0.4 28.0 28.0 28.0 28.0 28.0 27.6 27.6 27.6
5.0 4.5 31.7 31.3 30.9 30.9 30.9 30.9 30.9 30.9
10.0 9.0 32.9 32.9 32.9 32.5 32.5 32.5 32.5 32.5
15.0 14.0 34.9 34.9 34.9 34.9 34.9 34.9 34.5 34.1
20.0 19.0 36.9 36.9 36.9 36.9 36.0 36.0 35.5 35.0
25.0 23.0 38.6 38.6 38.6 38.6 38.6 37.8 37.4 37.0
ARNU363BGA4 /
30.0 28.0 39.4 39.4 39.4 39.4 39.4 38.6 37.4 36.2
36.2
35.0 32.0 40.6 40.6 40.6 40.6 40.2 39.4 37.4 35.4
40.0 36.0 42.2 42.2 42.2 42.2 40.6 39.4 37.4 35.4
45.0 41.0 43.8 43.8 43.8 42.6 40.6 39.4 37.4 35.4
47.0 43.0 45.5 45.1 44.7 42.6 40.6 39.4 37.4 35.4
50.0 46.0 48.8 46.7 44.7 42.6 40.6 39.4 37.4 35.4
55.0 51.0 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.4
60.0 56.0 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.4
TC: Total Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
48 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Heating Capacity Tables
ARNU423BGA4, ARNU483BRA4, ARNU543BRA4, ARNU763B8A4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 49
Ducted High Static
Heating Capacity Tables
ARNU963B8A4
40.0 36.0 111.8 111.8 111.8 111.8 107.5 104.3 98.9 93.8
45.0 41.0 116.1 116.1 116.1 112.9 107.5 104.3 98.9 93.8
47.0 43.0 120.4 119.3 118.3 112.9 107.5 104.3 98.9 93.8
50.0 46.0 129.2 123.6 118.3 112.9 107.5 104.3 98.9 93.8
55.0 51.0 131.5 124.7 118.3 112.9 107.5 104.3 98.9 93.8
60.0 56.0 131.5 124.7 118.3 112.9 107.5 104.3 98.9 93.8
TC: Total Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
50 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Optional Accessories
Table 42: Optional Accessories for Ducted High Static Indoor Units.
Accessory Model Number
ZFBXBG01A (For 7~42MBh Ducted High Static Indoor Units)
High Efficiency Filter Box ZFBXBR01A (For 48-54MBh Ducted High Static Indoor Units)
ZFBXB801A (For 76-96MBh Ducted High Static Indoor Units)
ZPLMV201A (2VL)
Dynamic V8 Low Profile Air Cleaner
ZPLMV402A (4VL)
ZFLT1301A (4-Pack)
Dynamic V8 VL Replacement Filter Pads
ZFLT1302A (24-Pack)
ZGRLRA01A (Louvered)
Return Air Grille
ZGRLRA02A (Egg Crate)
ZPLMV201A (2VL)
Return Air Plenum
ZPLMV402A (4VL)
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 51
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
52 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
LOW STATIC
Mechanical Specifications on page 54
General Data on page 55
Electrical Data on page 56
External Dimensions on page 57
Electrical Wiring Diagram on page 58
Refrigerant Flow Diagrams on page 62
External Static Pressure and Air Flow on page 63
External Static Pressure Ranges on page 65
Acoustic Data on page 66
Capacity Tables on page 69
DUCTED LOW Static
Mechanical Specifications
polymeric resin. Fans are directly driven and mounted on a common lers and/or a wall-mounted remote temperature sensor. The unit
shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) microprocessor is capable of accepting space temperature readings
design with permanently lubricated and sealed ball bearings. The fan concurrently or individually from either:
motor includes thermal, overcurrent and low RPM protection. The 1. Wall-mounted wired controller(s)
fan/motor assembly is mounted on vibration attenuating rubber grom-
mets. The fan impeller is statically and dynamically balanced. The fan 2. Factory mounted return air thermistor or the optional wall-
speed is controlled using a microprocessor based direct digital con- mounted wired remote temperature sensor.
trol algorithm that provides a high fan speed in cooling thermal ON A single indoor unit has the capability of being controlled by up to
and low fan speed in cooling thermal OFF, high fan speed in heating two local wired controllers. The microprocessor controls space tem-
thermal ON and fan off in heating thermal OFF. The fan speeds can perature using the value provided by the temperature sensor sensing
be field adjusted between low, medium, and high speeds and DIP a space temperature that is farthest away from the temperature
switch settings will allow the fan to run constantly during defrost or set-point. The microprocessor control provides a cooling or heating
oil return modes. Each setting can be field adjusted from the factory mode test cycle that operates the unit for 18 minutes without regard
setting (RPM / ESP) to compensate for resistance to airflow caused to the space temperature. If the system is provided with an optional
by field connected ductwork or other airflow restricting devices. wall-mounted or central controller, displayed diagnostic codes are
specific, alpha numeric, and provide the service technician with a
Air Filter reason for the code displayed.
Return air is filtered with a removable, washable filter with anti-fun-
gal treatment. Condensate Lift/Pump
The indoor unit is provided with a factory installed and wired
Microprocessor Controls condensate lift/pump capable of providing a minimum 27.5 inch lift
The unit is provided with an integrated microprocessor-based con- from the bottom exterior surface of the unit casing. The lift pump
troller. The controller is capable of performing functions necessary comes with a safety switch that will shut off indoor unit if condensate
to operate the system without the use of a wall-mounted controller. rises too high in the drain pan.
A temperature thermistor is factory-mounted in the return air stream.
All unit operation parameters, excluding the unit operating schedule, Condensate Drain Pan
are stored in non-volatile memory resident on the unit microproces- The condensate drain pan is constructed of high impact polystyrene
sor. Operating schedules are stored in select models of the optional, resin (HIPS).
wall-mounted, local, or central controller. The field-supplied commu- Coil
nication cable between the indoor unit(s) and outdoor unit is to be
The indoor unit coil is constructed with grooved design copper tubes
a minimum of 18 AWG, 2 conductor, stranded and shielded cable
with slit coil fins, two (2) to three (3) rows, eighteen (18) to
(RS-485), terminated via screw terminals on the control boards.
twenty-one (21) fins per inch.
The microprocessor control provides the following functions: auto
addressing, self-diagnostics, auto restart following power restoration, Controls Features
test run, and will operate the indoor unit using one of five operating • Auto changeover • Group control
modes: (Heat Recovery only) • External static pressure control
1. Auto Changeover (Heat Recovery only) • Auto operation • Hot start
2. Heating • Auto restart • Self diagnostics
3. Cooling • Child lock • Timer (on / off)
4. Dry • Dual thermistor control • Weekly schedule
5. Fan Only • Dual set-point control • Fan speed control
For Heat Recovery systems the Auto Changeover setting automati- • Filter life and power consump- • Ventilation (outside air)
cally switches control of the indoor unit between cooling and heating tion display
modes based on space temperature conditions. • Multiple auxiliary heater
For Heat Pump systems, heated or cooled air delivery is dependent applications
Due to our policy of continuous product innovation, some specifications may change without notification.
54 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW STATIC
General Data
L1, L2, L3 Units
Table 43: Ducted Low Static (L1, L2, L3 Frames) Indoor Unit General Data.
Model No. ARNU073L1G4 ARNU093L1G4 ARNU123L2G4 ARNU153L2G4 ARNU183L2G4 ARNU243L3G4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100 24,000
Power Input1 (W) 40 40 85 85 85 115
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500 27,300
Power Input (W) 1
40 40 85 85 85 115
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
27 / 26 / 23 30 / 26 / 23 31 / 29 / 26 34 / 31 / 29 36 / 34 / 31 39 / 35 / 32
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 55
DUCTED LOW Static
Electrical Data
Table 44: Ducted Low Static (L1, L2, L3 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
L1 Units
ARNU073L1G4 0.5 0.4 40 40
208-230 15 60 208-230 1
ARNU093L1G4 0.5 0.4 40 40
L2 Units
ARNU123L2G4 1.0 0.76 85 85
ARNU153L2G4 208-230 1.0 15 0.76 60 208-230 1 85 85
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
56 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW STATIC
External Dimensions
L1, L2, L3 Units
13/16 D
Air Outlet
5-5/16
L1 : 14-7/16
L2 : 22-1/16
L3 : 29-3/4 C
Air Inlet
13/16
6-1/16
7-1/2
L1 : 2-15/16
L2 : 3-1/16
L3 : 3-3/16
B
A
A B C D
ARNU073L1G4
30-1/2 27-9/16 28-7/8 26
Center of Gravity ARNU093L1G4
ARNU123L2G4
Unit: inches ARNU153L2G4 38-3/8 35-7/16 36-3/4 33-7/8
Note: All measurements ARNU183L2G4
have a tolerance of ±1/4 in. ARNU243L3G4 46-1/4 43-5/16 44-5/8 41-3/4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 57
DUCTED LOW Static
Electrical Wiring Diagram
L1 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
58 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Electrical Wiring Diagram
L1 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 59
DUCTED LOW Static
Electrical Wiring Diagram
L2, L3 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
60 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Electrical Wiring Diagram
L2, L3 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 61
DUCTED LOW Static
Refrigerant Flow Diagram
L1, L2, L3 Units
Cooling
Heat Exchanger EEV Heating
Filter
TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual
Table 49: L1, L2, L3 Unit Refrigerant Pipe Connection Port Diameters.
Model Liquid (inch) Vapor (inch)
L1 Units
ARNU073L1G4
1/4 Flare 1/2 Flare
ARNU093L1G4
L2 Units
ARNU123L2G4
ARNU153L2G4 1/4 Flare 1/2 Flare
ARNU183L2G4
L3 Units
ARNU243L3G4 3/8 Flare 5/8 Flare
Due to our policy of continuous product innovation, some specifications may change without notification.
62 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW Static
External Static Pressure and Air Flow Tables
L1, L2, L3 Units
Table 51: L1 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15 0.19
65 178 - - - - -
70 198 171 - - - -
75 219 192 161 - - -
80 240 214 183 - - -
85 262 236 205 170 - -
90 284 258 227 192 - -
95 308 281 251 215 176 -
100 331 305 274 239 199 -
105 356 329 299 263 224 180
110 - 354 324 288 249 205
115 - - 349 314 274 230
120 - - - 340 300 256
125 - - - 367 327 283
130 - - - - 354 310
Table 52: L2 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 63
Ducted Low Static
External Static Pressure and Air Flow Charts
L1, L2, L3 Units
Figure 28: L1 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)
0.16
ESP
0.14 Setting
120
0.12 ESP
Setting
0.1 110
ESP
0.08 Setting
100
0.06 ESP
Setting
MULTI V Ducted Indoor Unit Engineering Manual
0.04 90
ESP
0.02 Setting
80
0
180.0 230.0 280.0 330.0
Air Flow(cfm)
Figure 29: L2 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)
0.16
0.14
ESP
0.12 Setting
130
0.1 ESP
Setting
0.08 ESP 120
0.06 Setting
ESP 110
0.04 ESP Setting
Setting 100
0.02 90
0
200.0 300.0 400.0 500.0 600.0
Air Flow(cfm)
Figure 30: L3 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)
0.16
0.14
0.12
0.1
0.08 ESP
Setting
0.06 135
ESP
0.04 Setting
ESP ESP ESP ESP 130
0.02 Setting Setting Setting Setting
90 100 110 120
0
350.0 450.0 550.0 650.0 750.0
Air Flow(cfm))
Due to our policy of continuous product innovation, some specifications may change without notification.
64 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW Static
External Static Pressure Ranges
L1, L2, L3 Units
Figure 31: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
DISCHARGE SUCTION • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
DUCT DUCT Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3 ft.
4.9 ft.
6.6 ft. tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.
MULTI V Ducted Indoor Unit Engineering Manual
Figure 32: ARNU073L1G4, ARNU093L1G4, and ARNU123L2G4 Sound Pressure Level Diagrams.
ARNU073L1G4 ARNU093L1G4 ARNU123L2G4
Due to our policy of continuous product innovation, some specifications may change without notification.
66 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Acoustic Data
Sound Pressure Levels / Sound Power Levels
Figure 33: ARNU153L2G4, ARNU183L2G4, and ARNU243L3G4 Sound Pressure Level Diagrams.
ARNU153L2G4 ARNU183L2G4 ARNU243L3G4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 67
Ducted Low Static
Acoustic Data
Sound Power Levels
Figure 34: ARNU073L1G4, ARNU093L1G4, and ARNU123L2G4 Sound Power Level Diagrams.
ARNU073L1G4 ARNU093L1G4 ARNU123L2G4
MULTI V Ducted Indoor Unit Engineering Manual
Figure 35: ARNU153L2G4, ARNU183L2G4, and ARNU243L3G4 Sound Power Level Diagrams.
ARNU153L2G4 ARNU183L2G4 ARNU243L3G4
Due to our policy of continuous product innovation, some specifications may change without notification.
68 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Cooling Capacity Tables
ARNU073L1G4, ARNU093L1G4, ARNU123L2G4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 69
Ducted Low Static
Cooling Capacity Tables
ARNU153L2G4, ARNU183L2G4, ARNU243L3G4
ARNU153L2G4 /
65 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.4 11.7
15.4
70 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.1 11.5
75 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 18.6 11.3
80 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 17.8 11.9 18.2 11.2
85 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.1 12.0 17.3 11.4 17.6 10.8
90 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.8 11.8 16.9 11.2 17.3 10.7
95 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.5 11.7 16.8 11.2 17.1 10.5
100 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.2 11.5 16.5 11.0 16.8 10.5
105 10.1 8.6 11.7 9.4 13.2 10.1 14.8 10.8 15.1 10.8 15.8 10.7 16.2 10.2
110 9.9 8.4 11.1 8.9 12.3 9.4 13.9 10.1 14.2 10.1 15.1 10.1 15.7 9.9
23 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
25 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
30 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
35 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
40 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
45 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
50 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
55 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
60 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.4 14.8
ARNU183L2G4 /
65 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.0 14.5
19.1
70 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 23.7 14.3
75 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 23.1 14.0
80 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.1 14.8 22.5 13.9
85 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.2 14.8 21.4 14.1 21.8 13.4
90 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.9 14.6 21.0 13.9 21.4 13.2
95 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.5 14.5 20.9 13.8 21.2 13.0
100 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.1 14.3 20.5 13.7 20.9 13.0
105 12.6 10.7 14.5 11.7 16.4 12.6 18.3 13.4 18.7 13.4 19.7 13.2 20.1 12.6
110 12.3 10.4 13.8 11.1 15.3 11.7 17.2 12.6 17.6 12.6 18.7 12.6 19.5 12.3
23 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
25 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
30 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
35 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
40 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
45 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
50 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
55 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
60 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 30.7 19.3
ARNU243L3G4 /
65 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 30.2 19.0
24.2
70 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 29.8 18.7
75 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 29.0 18.3
80 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 27.8 19.3 28.3 18.2
85 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.6 19.4 26.9 18.5 27.4 17.4
90 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.2 19.1 26.4 18.2 26.9 17.2
95 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 25.7 19.0 26.2 18.0 26.6 17.0
100 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 25.2 18.7 25.7 17.8 26.2 16.9
105 15.8 13.9 18.2 15.3 20.6 16.4 23.0 17.4 23.5 17.4 24.7 17.2 25.2 16.5
110 15.4 13.5 17.3 14.5 19.2 15.3 21.6 16.4 22.1 16.4 23.5 16.4 24.5 16.0
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
70 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Heating Capacity Tables
ARNU073L1G4, ARNU093L1G4, ARNU123L2G4, ARNU153L2G4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 71
Ducted Low Static
Heating Capacity Tables
ARNU183L2G4, ARNU243L3G4
40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.3 24.3 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 23.9
ARNU243L3G4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 23.9
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.9
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.9
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.9
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.9
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.9
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9
TC: Total Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
72 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
BUILT IN
Mechanical Specifications on page 74
General Data on page 75
Electrical Data on page 76
External Dimensions on page 77
Electrical Wiring Diagram on page 78
Refrigerant Flow Diagrams on page 80
External Static Pressure and Air Flow on page 81
External Static Pressure Ranges on page 83
Acoustic Data on page 84
Capacity Tables on page 87
Optional Accessories on page 91
DUCTED Built In
Mechanical Specifications
design with permanently lubricated and sealed ball bearings. The istor, screw terminals on the microprocessor circuit board accom-
fan motor includes thermal, overcurrent and low RPM protection. modate various models of wall-mounted local controllers and/or a
The fan/motor assembly is mounted on vibration attenuating rubber wall-mounted remote temperature sensor. The unit microprocessor
grommets. The fan impeller is statically and dynamically balanced. is capable of accepting space temperature readings concurrently or
The fan speed is controlled using a microprocessor based direct individually from either:
digital control algorithm that provides a high fan speed in cooling 1. Wall-mounted wired controller(s)
thermal ON and low fan speed in cooling thermal OFF, high fan 2. Factory mounted return air thermistor or the optional
speed in heating thermal ON and fan off in heating thermal OFF. The wall-mounted wired remote temperature sensor
fan speeds can be field adjusted between low, medium, and high A single indoor unit has the capability of being controlled by up to
speeds and DIP switch settings will allow the fan to run constantly two local wired controllers. The microprocessor controls space tem-
during defrost or oil return modes. Each setting can be field adjusted perature using the value provided by the temperature sensor sensing
from the factory setting (RPM / ESP) to compensate for a limited a space temperature that is farthest away from the temperature
amount of additional resistance to airflow caused by field connected set-point. The microprocessor control provides a cooling or heating
ductwork or other airflow restricting devices. mode test cycle that operates the unit for 18 minutes without regard
to the space temperature. If the system is provided with an optional
Ceiling Grille/Duct Kit wall-mounted local or central controller, displayed diagnostic codes
An optional flush-mounted ceiling return air grille and accordion-style are specific, alpha numeric, and provide the service technician with a
canvas duct kit provides a short-ducted return air solution. reason for the code displayed.
Table 63: Ducted Built In (B3, B4 Frames) Indoor Unit General Data.
Model No. ARNU073B3G4 ARNU093B3G4 ARNU123B3G4 ARNU153B3G4 ARNU183B4G4 ARNU243B4G4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100 24,200
Power Input1 (W) 85 85 85 85 115 115
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500 27,300
Power Input (W) 1
85 85 85 85 115 115
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37
Net Unit Weight (lbs.) 46.3 46.3 46.3 46.3 57.3 57.3
Ducted Built In
Shipping Weight (lbs.) 53.3 53.3 53.3 53.3 67.2 67.2
Communication Cable (No. x AWG) 4
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco Sirocco Sirocco
Motor 2 2 2 2 2 2
Housing 3 3 3 3 4 4
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
Standard Mode
Airflow Rate H/M/L (CFM) 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
High Mode (Factory Set)
External Static Pressure (in. wg) 0 0 0 0 0 0
Standard Mode
External Static Pressure (in. wg) 0.08 0.08 0.08 0.08 0.08 0.08
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 3/8 Flare
Vapor Line (in., O.D.) 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 75
DUCTED Built In
Electrical Data
Table 64: Ducted Built In (B3, B4 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
B3 Units
ARNU073B3G4 1.0 0.76 85 85
ARNU093B3G4 1.0 0.76 85 85
208-230 15 60 208-230 1
ARNU123B3G4 1.0 0.76 85 85
ARNU153B3G4 1.0 0.76 85 85
B4 Units
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
76 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Dimensions
B3, B4 Units
7-1/2
2-3/8
2-1/2
Return Air
1 8-1/2
10-7/8
Liquid
15-1/8
22-5/8
24-5/16
15-1/4
Vapor
Drain
Supply Air
B2
Ducted Built In
A1 With Suction Grill
Power Connection
A2 C2
7-7/16
9-13/16
Model A1
ARNU073B3G4
7-1/2
19-11/16 (Max)
ARNU093B3G4
32-5/8
ARNU123B3G4
ARNU153B3G4
C3
Unit: inches
ARNU183B4G4 Note: All measurements
A3 B3 43-5/16
With Suction Grill & Suction Canvas ARNU243B4G4 have a tolerance of ±1/4 in.
Accessory A2 B2 C2 Accessory A3 B3 C3
PBSGB30 35-13/16 14-1/8 2-3/16 PBSC30 32-5/16 10-11/16 1-9/16 to 9-13/16
PBSGB40 46-13/16 14-1/8 2-3/16 PBSC40 43-5/16 10-11/16 1-9/16 to 9-13/16
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 77
DUCTED Built In
Electrical Wiring Diagram
B3, B4 Units
Due to our policy of continuous product innovation, some specifications may change without notification.
78 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Electrical Wiring Diagram
B3, B4 Units
Ducted Built In
CN-PIPE/IN Suction pipe sensor Pipe in thermistor
CN-REMO Wired remote controller Wired remote control connection
CN-ROOM Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 79
DUCTED Built In
Refrigerant Flow Diagram
B3, B4 Units
Cooling
Heat Exchanger EEV Heating
Filter
TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
80 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Static Pressure and Air Flow Tables
B3, B4 Units
Table 69: B3 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15
60 222 107 33 - -
65 234 171 54 - -
70 272 199 77 28 -
75 289 222 99 30 -
80 315 263 175 56 -
85 336 288 209 97 34
90 361 310 240 121 48
95 383 340 287 194 92
100 400 373 319 216 117
105 418 395 353 293 188
110 448 420 367 324 245
115 466 432 408 361 291
Ducted Built In
Table 70: B4 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15
75 365 271 125 - -
80 391 310 166 49 -
85 418 354 246 76 -
90 450 380 292 167 44
95 476 429 351 238 96
100 500 468 371 297 129
105 540 499 435 347 219
110 569 522 477 367 294
115 598 561 512 451 351
120 629 597 535 494 383
125 656 630 570 535 458
130 672 656 612 575 516
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 81
Ducted Built In
External Static Pressure and Air Flow Charts
B3, B4 Units
Figure 39: B3 Unit External Static Pressure and Air Flow Chart.
0.16
0.14
External Stac Pressure(in-wg)
0.12
0.1 ESP
ESP ESP Setting
Setting Setting 110
0.08 ESP 100
Setting 90
80
0.06
ESP
Setting
0.04
MULTI V Ducted Indoor Unit Engineering Manual
70
ESP
0.02 Setting
60
0
30 130 230 330 430
Air Flow(cfm)
Figure 40: B4 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)
0.16
0.14
0.12
0.1
0.08 ESP ESP
0.06 ESP Setting Setting
ESP Setting 120 130
0.04 ESP Setting 110
Setting 100
0.02 90
0
200.0 250.0 300.0 350.0 400.0 450.0 500.0 550.0 600.0
Air Flow(cfm)
Due to our policy of continuous product innovation, some specifications may change without notification.
82 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Static Pressure Ranges
B3, B4 Units
Ducted Built In
High 110 388
High
Mid 105 0.08 353 - 0.15
(Factory Set)
Low 94 283
ARNU153B3G4 15.4
High 96 388
Standard Mid 90 0 353 - 0.15
Low 74 283
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 83
Ducted Built In
Acoustic Data
Sound Pressure Levels
Figure 41: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
• Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
Ceiling Operating Conditions:
• Power source: 220V/60 Hz
4.9ft
6.6ft
• Sound level will vary depending on a range of factors including the construc-
tion (acoustic absorption coefficient) of a particular room in which the unit was
Microphone
installed.
MULTI V Ducted Indoor Unit Engineering Manual
Figure 42: ARNU073B3G4, ARNU093B3G4, and ARNU123B3G4 Sound Pressure Level Diagrams.
ARNU073B3G4 ARNU093B3G4 ARNU123B3G4
Due to our policy of continuous product innovation, some specifications may change without notification.
84 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Acoustic Data
Sound Pressure Levels / Sound Power Levels
Figure 43: ARNU153B3G4, ARNU183B4G4, and ARNU243B4G4 Sound Pressure Level Diagrams.
ARNU153B3G4 ARNU183B4G4 ARNU243B4G4
Ducted Built In
Sound Power Levels
Table 74: Ducted Built In Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions.
Model Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
B3 Units • Sound power level is measured using rated conditions, and tested
ARNU073B3G4 53 in a reverberation room per ISO 3741 standards.
ARNU093B3G4 54 • Sound level will vary depending on a range of factors such as
ARNU123B3G4 55 construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
ARNU153B3G4 60
• Reference acoustic intensity: 0dB = 10E-6μW/m2
B4 Units
ARNU183B4G4 61
ARNU243B4G4 62
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 85
Ducted Built In
Acoustic Data
Sound Power Levels
Figure 44: ARNU073B3G4, ARNU093B3G4, and ARNU123B3G4 Sound Power Level Diagrams.
ARNU073B3G4 ARNU093B3G4 ARNU123B3G4
MULTI V Ducted Indoor Unit Engineering Manual
Figure 45: ARNU153B3G4, ARNU183B4G4, and ARNU243B4G4 Sound Power Level Diagrams.
ARNU153B3G4 ARNU183B4G4 ARNU243B4G4
Due to our policy of continuous product innovation, some specifications may change without notification.
86 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Cooling Capacity Tables
ARNU073B3G4, ARNU093B3G4, ARNU123B3G4
Ducted Built In
25 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
30 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
35 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
40 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
45 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
50 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
55 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.5
60 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.3 7.4
ARNU093B3G4 /
65 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.1 7.3
9.6
70 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.9 7.2
75 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.6 7.0
80 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.1 7.4 11.3 7.0
85 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.7 7.5 10.8 7.1 10.9 6.7
90 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.5 7.3 10.6 7.0 10.8 6.6
95 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.3 7.3 10.5 6.9 10.7 6.6
100 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.1 7.2 10.3 6.9 10.5 6.5
105 6.3 5.4 7.3 5.9 8.3 6.3 9.2 6.7 9.4 6.7 9.9 6.6 10.1 6.3
110 6.1 5.2 6.9 5.6 7.7 5.9 8.6 6.3 8.8 6.3 9.4 6.3 9.8 6.2
23 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
25 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
30 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
35 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
40 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
45 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
50 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
55 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.6
60 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.7 9.5
ARNU123B3G4 /
65 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.5 9.4
12.3
70 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.3 9.2
75 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 14.9 9.0
80 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.3 9.5 14.5 9.0
85 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.7 9.6 13.8 9.1 14.0 8.6
90 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.4 9.4 13.5 8.9 13.8 8.5
95 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.2 9.3 13.4 8.9 13.7 8.4
100 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 12.9 9.2 13.2 8.8 13.4 8.3
105 8.1 6.9 9.3 7.5 10.6 8.1 11.8 8.6 12.1 8.6 12.7 8.5 12.9 8.1
110 7.9 6.7 8.9 7.1 9.8 7.5 11.1 8.1 11.3 8.1 12.1 8.1 12.5 7.9
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 87
Ducted Built In
Cooling Capacity Tables
ARNU153B3G4, ARNU183B4G4, ARNU243B4G4
ARNU153B3G4 /
65 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.4 11.7
15.4
70 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.1 11.5
75 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 18.6 11.3
80 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 17.9 11.9 18.2 11.2
85 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.1 12.0 17.2 11.4 17.6 10.8
90 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.8 11.7 16.9 11.2 17.2 10.6
95 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.5 11.7 16.8 11.1 17.1 10.5
100 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.2 11.5 16.5 11.0 16.8 10.4
105 10.2 8.6 11.7 9.4 13.2 10.1 14.8 10.8 15.1 10.8 15.9 10.7 16.2 10.2
110 9.9 8.4 11.1 8.9 12.3 9.4 13.9 10.1 14.2 10.1 15.1 10.1 15.7 9.9
23 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
25 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
30 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
35 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
40 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
45 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
50 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
55 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
60 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.4 14.3
ARNU183B4G4 /
65 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.1 14.1
19.1
70 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 23.7 13.9
75 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 23.1 13.6
80 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.2 14.4 22.5 13.5
85 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.2 14.4 21.4 13.7 21.8 13.0
90 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.8 14.2 21.0 13.5 21.4 12.8
95 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.4 14.1 20.8 13.4 21.2 12.7
100 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.1 13.9 20.4 13.3 20.8 12.6
105 12.6 10.4 14.5 11.4 16.4 12.2 18.3 13.0 18.7 13.0 19.7 12.8 20.1 12.3
110 12.2 10.1 13.8 10.8 15.3 11.4 17.2 12.2 17.6 12.2 18.7 12.2 19.5 11.9
23 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
25 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
30 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
35 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
40 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
45 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
50 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
55 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
60 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.0 18.2
ARNU243B4G4 /
65 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 30.5 17.9
24.2
70 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 30.0 17.6
75 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 29.3 17.2
80 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.1 18.2 28.6 17.1
85 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 26.9 18.3 27.1 17.4 27.6 16.5
90 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 26.4 18.0 26.6 17.1 27.1 16.2
95 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 25.9 17.9 26.4 17.0 26.9 16.1
100 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 25.4 17.6 25.9 16.9 26.4 15.9
105 16.0 13.2 18.4 14.4 20.8 15.5 23.2 16.5 23.7 16.5 24.9 16.3 25.4 15.6
110 15.5 12.8 17.4 13.6 19.4 14.4 21.8 15.5 22.3 15.5 23.7 15.5 24.7 15.1
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
88 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Heating Capacity Tables
ARNU073B3G4, ARNU093B3G4, ARNU123B3G4, ARNU153B3G4
Ducted Built In
20.0 19.0 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.4
25.0 23.0 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.9
ARNU093B3G4 /
30.0 28.0 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.7
9.6
35.0 32.0 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.5
40.0 36.0 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.5
45.0 41.0 11.8 11.8 11.8 11.4 10.9 10.6 10.0 9.5
47.0 43.0 12.2 12.1 12.0 11.4 10.9 10.6 10.0 9.5
50.0 46.0 13.1 12.5 12.0 11.4 10.9 10.6 10.0 9.5
55.0 51.0 13.3 12.6 12.0 11.4 10.9 10.6 10.0 9.5
60.0 56.0 13.3 12.6 12.0 11.4 10.9 10.6 10.0 9.5
-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.0
0 -0.4 9.4 9.4 9.4 9.4 9.4 9.2 9.2 9.2
5.0 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3
10.0 9.0 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.9
15.0 14.0 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.4
20.0 19.0 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.7
25.0 23.0 12.9 12.9 12.9 12.9 12.9 12.6 12.5 12.4
ARNU123B3G4 /
30.0 28.0 13.2 13.2 13.2 13.2 13.2 12.9 12.5 12.1
12.3
35.0 32.0 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.9
40.0 36.0 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.9
45.0 41.0 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.9
47.0 43.0 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.9
50.0 46.0 16.4 15.6 15.0 14.3 13.6 13.2 12.5 11.9
55.0 51.0 16.6 15.8 15.0 14.3 13.6 13.2 12.5 11.9
60.0 56.0 16.6 15.8 15.0 14.3 13.6 13.2 12.5 11.9
-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3
0 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.6
5.0 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0
10.0 9.0 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.7
15.0 14.0 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.4
20.0 19.0 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.8
25.0 23.0 16.2 16.2 16.2 16.2 16.2 15.9 15.7 15.6
ARNU153B3G4 /
30.0 28.0 16.6 16.6 16.6 16.6 16.6 16.2 15.7 15.2
15.4
35.0 32.0 17.1 17.1 17.1 17.1 16.9 16.6 15.7 14.9
40.0 36.0 17.8 17.8 17.8 17.8 17.1 16.6 15.7 14.9
45.0 41.0 18.5 18.5 18.5 18.0 17.1 16.6 15.7 14.9
47.0 43.0 19.2 19.0 18.8 18.0 17.1 16.6 15.7 14.9
50.0 46.0 20.6 19.7 18.8 18.0 17.1 16.6 15.7 14.9
55.0 51.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
60.0 56.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
TC: Total Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 89
Ducted Built In
Heating Capacity Tables
ARNU183B4G4, ARNU243B4G4
40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.2 24.2 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 24.8
ARNU243B4G4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 24.3
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.8
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.8
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.8
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.8
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.8
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
TC: Total Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
90 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Optional Accessories
Ducted Built In
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 91
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
92 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
VERTICAL /
HORIZONTAL
AIR HANDLER
Mechanical Specifications on page 94
General Data on page 96
Electrical Data on page 98
External Dimensions on page 99
Electrical Wiring Diagram on page 101
Refrigerant Flow Diagrams on page 103
External Static Pressure and Air Flow on page 104
External Static Pressure Ranges on page 105
Heater Capacity Airflow / Static Pressure Drop Factors on page 106
Acoustic Data on page 107
Capacity Tables on page 111
Optional Accessories on page 116
Vertical / Horizontal Air Handler
Mechanical Specifications
and sealed along the edges with a reinforced foil-faced covering to disconnects are to be field provided.
prevent deterioration caused by panel removal. All access panels are
provided with gasket seals to minimize air leakage. The unit case is Electric Heat Module Controls
designed to accept an internal, optional, LG electric strip heater. The The electric heat module is capable of operating at full capacity
unit bears the ETL label. Unit breaker, fuses, and / or disconnect are during system defrost and oil return operations. When the air handler
provided by others. is operating in the Cooling, Dry, or Fan Only modes, the electric
heater operation is locked out and unavailable. When the air handler
Fan Assembly and Control is operating in the Heating mode, the heater is field selectable to
The indoor unit has an integral fan assembly consisting of a operate when the room temperature is 2°F lower than set-point or
galvanized steel housing and a forward-curved fan wheel. The direct manually if provided with a start/stop signal from a third-party outside
drive fan/motor assembly is mounted on rubber grommets isolat- source.
ing the rotating assembly from the fan housing. The fan motor is a
Brushless Digitally-Controlled design (BLDC), having permanently Microprocessor Controls
lubricated and sealed ball bearings. The fan motor includes thermal, The unit is equipped with an integrated microprocessor-based
overcurrent and low RPM protection. The fan/motor assembly is controller capable of performing functions necessary to operate the
mounted on vibration attenuating rubber grommets. The fan impeller system without the use of a wall-mounted controller. A temperature
is statically and dynamically balanced. Fan speed is controlled using thermistor is mounted in the return air stream. All unit operating
a microprocessor-based direct digital control algorithm that provides parameters, excluding the operation schedule, are stored in non-vol-
a minimum of a high fan speed in cooling thermal ON and low fan atile memory resident on the unit microprocessor. Operating sched-
speed in cooling thermal OFF, high fan speed in heating thermal ules are stored in select models of the optional wall-mounted local or
ON and fan off in heating thermal OFF. The fan speeds can be field central controller. The field-supplied communication cable between
adjusted between low, medium, and high speeds and DIP switch the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG,
settings will allow the fan to run constantly during defrost or oil return 2 conductor, stranded, and shielded (RS-485). The microprocessor
modes. Each setting can be field adjusted from the factory setting control provides the following functions: auto addressing, self-
(RPM/ESP). The setting provides delivery of the high speed air diagnostics, auto restart following power restoration, and will operate
volume against an external static pressure of up to 1.0 in-wg. the indoor unit using one of the following five operation modes:
Due to our policy of continuous product innovation, some specifications may change without notification.
94 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Mechanical Specifications
In Heating mode, the microprocessor control does not begin fan Controls Features
operation until coil pipe temperature reaches 76ºF. Significant • Auto changeover (Heat Recovery only)
airflow is generated when pipe temperature reaches 80°F. A field-se- • Auto operation
lectable option maintains fan operation for 30 minutes following
• Auto restart
cooling cycle operations.
• Child lock
• Dual thermistor control
1. Wall-mounted wire controller
• External static pressure control
2. Factory-mounted return air thermistor or the optional wall-
mounted wired remote temperature sensor. • Group control
• Hot start
The microprocessor controls space temperature using the value • Self diagnostics
provided by the temperature sensor sensing a space temperature • Timer (on / off)
that is farthest away from the temperature set-point. A single indoor • Weekly schedule
unit has the capability of being controlled by up to two local wired • Fan speed control
controllers. The microprocessor control provides a cooling or heating
Handling Condensate
The drain pan is designed to work with a gravity building drain sys-
tem. If condensate lifts/pumps are needed, they are to be field-pro-
vided. A secondary drain port plug is provided allowing the pan to be
drained for service. Condensate float safety switch connections are
available on the main control board for connection of a field supplied
float safety switch.
Coil
The indoor unit coil is constructed with grooved design copper tubes
with slit coil fins, 2 to 3 rows, 18 fins per inch.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 95
Vertical / Horizontal Air Handler
General Data
NJ Frames
Table 80: Vertical / Horizontal (NJ Frame) Air Handler Unit General Data.
Model No. ARNU123NJA4 ARNU183NJA4 ARNU243NJA4 ARNU303NJA4 ARNU363NJA4
Cooling Mode Performance
Capacity (Btu/h) 12,000 18,000 24,000 30,000 36,000
Power Input1 (W) 228 228 228 228 228
Heating Mode Performance
Capacity (Btu/h) 13,500 20,000 27,000 34,000 40,000
Power Input (W) 1
228 228 228 228 228
Entering Mixed Air
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
96 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
General Data
NK Frames
Table 81: Vertical / Horizontal (NK Frame) Air Handler Unit General Data.
Model No. ARNU423NKA4 ARNU483NKA4 ARNU543NKA4
Cooling Mode Performance
Capacity (Btu/h) 42,000 48,000 54,000
Power Input1 (W) 366 366 366
Heating Mode Performance
Capacity (Btu/h) 46,000 54,000 60,000
Power Input1 (W) 366 366 366
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76
Heating Min. (°F DB) 59 59 59
Unit Data
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 97
Vertical / Horizontal Air Handler
Electrical Data
Table 82: Vertical / Horizontal (NJ, NK Frames) Air Handler Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
NJ Frames
ARNU123NJA4 1.4 1.12 228 228
ARNU183NJA4 1.4 1.12 228 228
ARNU243NJA4 208-230 1.4 15 1.12 60 208-230 1 228 228
ARNU303NJA4 1.4 1.12 228 228
ARNU363NJA4 1.4 1.12 228 228
MULTI V Ducted Indoor Unit Engineering Manual
NK Frames
ARNU423NKA4 2.3 1.8 260 260
ARNU483NKA4 208-230 2.3 15 1.8 60 208-230 1 330 330
ARNU543NKA4 2.3 1.8 366 366
MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
MOP : Maximum Overcurrent Protection. Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
Due to our policy of continuous product innovation, some specifications may change without notification.
98 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
External Dimensions
NJ Frame
48-11/16
SIDE VIEW
1-5/8 1-9/16 7/8” Wiring
21-1/4 18
1-9/16 1-15/16
2-1/16
18
17
7/8” Wiring
knockouts
2-1/8
21-1/4
TOP VIEW
Vapor pipe
2-9/16
Drain connection
for upflow application
1-1/2
Return Air
14-5/16
opening
4-11/16
1-9/16
9-15/16
BOTTOM VIEW Drain connection
for horizontal
application 13
Unit: inches
Note: All measurements FRONT VIEW
have a tolerance of ±1/4 in.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 99
Vertical / Horizontal Air Handler
External Dimensions
NK Frame
55-3/16
MULTI V Ducted Indoor Unit Engineering Manual
1-9/16 1-15/16
2-1/16
7/8” Wiring
knockouts
25
24
2-3/16
55-13/16
55-3/16
Drain connection
for upflow application
1-1/2
14-1/4
Return Air
opening
1-9/16
4-11/16
Due to our policy of continuous product innovation, some specifications may change without notification.
100 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Electrical Wiring Diagram
NJ, NK Frame
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 101
Vertical / Horizontal Air Handler
Electrical Wiring Diagram
NJ, NK Frame
For Multi V systems with an electric heater, DIP switches 5 and 6 must be set to ON.
• SW 5 ON: Fan operates continuously. During defrost or oil return operation, uninterrupted heating can be attained as a result of continuous
heater and fan operation.
• SW 5 OFF: Fan does not operate continuously. There will be a reduction in heating capacity during defrost or oil return operation.
• SW 6 ON: Automatic heater operation. The heater operates automatically according to heater logic without manual intervention.
• SW 6 OFF: Heater manual operation. Manual operation is required for on/off, but heater operation will follow heater logic.
Due to our policy of continuous product innovation, some specifications may change without notification.
102 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Refrigerant Flow Diagram
NJ, NK Frames
Sirroco Fan
Cooling
Heat Exchanger EEV Heating
Filter
TH3 TH2
TH1 Filter
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 103
Vertical / Horizontal Air Handler
External Static Pressure and Air Flow Charts
NJ, NK Frames
Figure 50: NJ Frame External Static Pressure and Air Flow Chart.
70
60
50
350 550 750 950
CFM
Figure 51: NK Frame External Static Pressure and Air Flow Chart.
120
0.8 (in wg)
0.7 (in wg)
110
0.6 (in wg)
100
0.5 (in wg)
0.4 (in wg)
ESP @ Pressure
90
0.3 (in wg)
0.2 (in wg)
80
0.1 (in wg)
70
60
50
900 1000 1100 1200 1300 1400 1500
CFM
Due to our policy of continuous product innovation, some specifications may change without notification.
104 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
External Static Pressure and Air Flow
NJ, NK Frames
Table 87: NJ Frame External Static Pressure and Air Flow Table.
Model No. / Flow Rate Static Pressure (in. WG)
Capacity (MBh) Mode CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
High 530 **53 58 66 72 82 84 92 *92 *92 *92
ARNU123NJA / 12 Mid 480 **53 56 64 70 79 83 92 *92 *92 *92
Low 380 **53 54 62 69 77 83 92 *92 *92 *92
High 580 **53 60 68 74 84 85 95 *95 *95 *95
ARNU183NJA4 / 18 Mid 530 **53 58 66 72 82 84 92 *92 *92 *92
Low 480 **53 55 64 70 79 83 92 *92 *92 *92
High 710 56 67 74 78 87 94 98 *98 *98 *98
ARNU243NJA4 / 24 Mid 640 53 65 70 75 85 91 96 *96 *96 *96
Low 480 **53 55 64 70 79 84 92 *92 *92 *92
High 880 65 72 80 85 92 98 103 *103 *103 *103
Table 88: NK Frame External Static Pressure and Air Flow Table.
Model No. / Flow Rate Static Pressure (in. WG)
Capacity (MBh) Mode CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
High 1,260 67 75 80 87 90 98 102 110 *115 *115
ARNU423NKA4 / 42 Mid 1,100 61 67 75 80 87 92 100 108 110 115
Low 1,000 56 65 72 77 84 90 98 105 108 115
High 1,400 74 79 84 91 96 102 110 115 *115 *115
ARNU483NKA4 / 48 Mid 1,260 67 75 80 87 90 98 102 110 115 *115
Low 1,000 56 65 72 77 84 90 98 105 108 115
High 1,475 77 82 87 93 98 105 113 115 *115 *115
ARNU543NKA4 / 54 Mid 1,400 74 79 84 91 96 102 110 113 *115 *115
Low 1,260 67 75 80 87 90 98 102 110 115 *115
* Flow rate (CFM) decreases by 3% per 0.1 in. WG. Minimum airflow rates are listed in CFM. Factory Default is high static pressure.
** Fan external static pressure is at minimum value. If the flow rate (CFM) is increased by 400 CFM/ton from 1.5 tons to High static pressure is 0.5 in wg.
2.5 tons of capacity, then ESP value should be increased by 4.
Low static pressure is 0.3 in wg.
If the flow rate (CFM) is increased by 400 CFM/ton from 3.0 tons to
4.5 tons of capacity, then The ESP value should be increased by 5. Vertical Air Handling Units are UL Listed up to 0.5 in wg external
static pressure, including air filter, set coil, and largest kW size
heater, unless otherwise noted.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 105
Vertical / Horizontal Air Handler
Heater Capacity Airflow / Static Pressure Drop Factors
Airflow rates in the table above are listed in CFM. Flow rate (CFM) is decreased by 3% per 0.1 in wg from 0.8 in wg to 1.0 in wg.
Vertical Air Handling Units are UL Listed up to 0.5 in wg external static pressure, including air filter, set
coil, and largest kW size heater, unless otherwise noted.
Do not operate with less than the minimum airflow. If an airflow is Do not operate with less than the minimum airflow. If an airflow is
used below the minimum, there is a risk of fire, which may lead to used below the minimum, there is a risk of damage to the product.
physical injury or death.
Table 90: Electric Heater Static Pressure Drop Factors.
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
5 -0.01
10 -0.02
15 -0.04
20 -0.06
in wg = inch water gauge If the ESP setting value is inappropriate, the provided safety device will turn the heater off according to
If the electric heater has been installed, then the ESP value has to be set. the airflow.
For every increase in static pressure by 0.01 in wg, the ESP value should be increased by 1.
Due to our policy of continuous product innovation, some specifications may change without notification.
106 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Acoustic Data
Sound Pressure Levels
Figure 52: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
Microphone • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3ft
tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.
3.3ft
Figure 53: ARNU123NJA4, ARNU183NJA4, and ARNU243NJA4 Sound Pressure Level Diagrams.
ARNU123NJA4 ARNU183NJA4 ARNU243NJA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 107
Vertical / Horizontal Air Handler
Acoustic Data
Sound Pressure Levels
Figure 54: ARNU303NJA4, ARNU363NJA4, and ARNU423NKA4 Sound Pressure Level Diagrams.
ARNU303NJA4 ARNU363NJA4 ARNU423NKA4
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
108 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Acoustic Data
Sound Power Levels
Figure 56: ARNU123NJA4, ARNU183NJA4, and ARNU243NJA4 Sound Power Level Diagrams.
ARNU123NJA4 ARNU183NJA4 ARNU243NJA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 109
Vertical / Horizontal Air Handler
Acoustic Data
Sound Power Levels
Figure 57: ARNU303NJA4, ARNU363NJA4, and ARNU423NKA4 Sound Power Level Diagrams.
ARNU303NJA4 ARNU363NJA4 ARNU423NKA4
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
110 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU123NJA4, ARNU183NJA4, ARNU243NJA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 111
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU303NJA4, ARNU363NJA4, ARNU423NKA4
ARNU303NJA4 /
65 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 37.8 22.4
30.0
70 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 37.3 22.1
75 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 36.3 21.6
80 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 34.8 22.8 35.4 21.5
85 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.3 22.9 33.6 21.8 34.3 20.6
90 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 32.8 22.6 33.0 21.5 33.6 20.4
95 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 32.1 22.4 32.8 21.3 33.3 20.1
100 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 31.5 22.1 32.1 21.1 32.8 20.0
105 19.8 16.5 22.8 18.1 25.8 19.4 28.8 20.6 29.4 20.6 30.9 20.4 31.5 19.5
110 19.3 16.0 21.6 17.1 24.0 18.1 27.0 19.4 27.6 19.4 29.4 19.4 30.6 18.9
23 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
25 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
30 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
35 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
40 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
45 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
50 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
55 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.6
60 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.1 27.4
ARNU363NJA4 /
65 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 45.4 27.0
36.0
70 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 44.6 26.6
75 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 43.6 26.0
80 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 41.8 27.4 42.5 25.9
85 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.0 27.6 40.3 26.2 41.0 24.8
90 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 39.2 27.1 39.6 25.8 40.3 24.5
95 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 38.5 27.0 39.2 25.7 40.0 24.3
100 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 37.8 26.5 38.5 25.4 39.2 24.1
105 23.8 19.9 27.4 21.7 31.0 23.3 34.6 24.9 35.3 24.9 37.1 24.6 37.8 23.5
110 23.0 19.3 25.9 20.6 28.8 21.7 32.4 23.3 33.1 23.3 35.3 23.4 36.7 22.8
23 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
25 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
30 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
35 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
40 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
45 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
50 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
55 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.2
60 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 53.8 32.0
ARNU42NKA4 /
65 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 52.9 31.5
42.0
70 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 52.1 31.0
75 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 50.8 30.3
80 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 48.7 32.0 49.6 30.2
85 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 46.6 32.2 47.0 30.6 47.9 29.0
90 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 45.8 31.6 46.2 30.1 47.0 28.5
95 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 44.9 31.4 45.8 29.9 46.6 28.3
100 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 44.1 31.0 44.9 29.7 45.8 28.1
105 27.7 23.2 31.9 25.3 36.1 27.2 40.3 29.0 41.2 29.0 43.3 28.6 44.1 27.4
110 26.9 22.5 30.2 24.0 33.6 25.3 37.8 27.2 38.6 27.2 41.2 27.3 42.8 26.6
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Due to our policy of continuous product innovation, some specifications may change without notification.
112 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU483NKA4, ARNU543NKA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 113
Vertical / Horizontal Air Handler
Heating Capacity Tables
ARNU123NJA4, ARNU183NJA4, ARNU243NJA4, ARNU303NJA4
Due to our policy of continuous product innovation, some specifications may change without notification.
114 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Heating Capacity Tables
ARNU363NJA4, ARNU423NKA4, ARNU483NKA4, ARNU543NKA4
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 115
Vertical / Horizontal Air Handler
Optional Accessories
Table 99: Optional Accessories for Vertical / Horizontal Air Handler Units.
Accessory Model Number
5kW Electric Heater ANEH053B1
10kW Electric Heater ANEH103B2
15kW Electric Heater ANEH153B2
20kW Electric Heater ANEH203B2
All accessories are sold separately.
Heater Coil
Terminal Block
Relay
Heater Cable
Due to our policy of continuous product innovation, some specifications may change without notification.
116 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
APPLICATION
GUIDELINES
Selecting the Best Location on page 118
General Mounting - High, Low, and Built In Ducted Units
on page 120
General Mounting - Vertical / Horizontal Air Handling Units
on page 122
General Drain Piping Information on page 124
Wiring Guidelines on page 126
Wired Controller Location on page 128
Acronyms on page 129
Application Guidelines
Selecting the Best Location
Selecting the Best Location Figure 60: Selecting the Best Location / Minimum Clearance Require-
ments (for High Static, Low Static, Built In Ducted Units).
Do’s
• Place the unit where air circulation will not be blocked. Service access
23-5/8 x 23-5/8
• Place the unit where drainage can be obtained easily and to mini-
mize the length of the condensate drain piping. Control box
39-3/8
• Locate the indoor unit in a location where it can be easily connect- 23-5/8 23-5/8
ed to the outdoor unit / heat recovery unit.
Don’ts
• Avoid installing the unit near high-frequency generators.
• Do not install the unit near a doorway.
• The unit should not be installed near a heat or steam source, or Minumim 13/16 for High and Low Static Ducted Units
where considerable amounts of oil, iron powder, or flour are used. Unit: inch
(These materials may generate condensate, cause a reduction in
heat exchanger efficiency, or the drain pump to malfunction. If this Figure 61: Minimum Clearances for Vertical / Horizontal Air Handler Units.
is a potential problem, install a ventilation fan large enough to vent
out these materials.) Minimum 14 inches
The unit should not be installed where sulfuric acid and flammable
or corrosive gases are generated, vented into, or stored. There is
risk of fire, explosion, and physical injury or death. Front
Due to our policy of continuous product innovation, some specifications may change without notification.
118 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
Selecting the Best Location
Figure 63: Service Clearances for High Static Ducted Units. Figure 64: Service Clearances for Low Static and Built In Ducted Units.
Service access
23-5/8 x 23-5/8
Control box
B (Minimum)
A (Minimum)
A
Unit: inch
Application Guidelines
Figure 65: Minimum Clearances for Built In Ducted Units with
Accessories.
Ceiling
Service Space
Minimum 7-5/8
A
With Return Air Grille
Table 101: Service Clearance Dimensions For High Static, Low Static, and
Minimum 7-5/8
Refer to Return Air Grille and Return Air Canvas Installation B8 23-5/8 23-5/8
Manual for detail installation of built in ducted units. Low Static Ducted
Unit: inch L1 31-1/2 31-1/2
L2 31-1/2 39-3/8
L3 31-1/2 47-1/4
Built In Ducted
B3 23-5/8 35-7/16
B4 23-5/8 43-5/16
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 119
Application Guidelines
General Mounting - High, Low, and Built In Ducted Units
C
E
EC
D
G
F
GD
I
H
H Drainage Point I
Table 102: High Static Ducted BG, BR, B8 Frame Suspension Bolt Positions
Dimensions (inches)
Frame
A B C D E F G H I J K L
BG 48-9/16 46-9/16 13-5/8 1-3/4 17-3/4 1-3/16 3-5/8 32-11/16 7-5/16 - - -
BR 50-7/16 48-7/16 18-13/16 2-1/4 23-1/4 1-3/16 4-11/16 39-5/8 11-9/16 - -
B8 63-7/8 61-5/8 22-7/8 11-1/2 27-3/8 55-1/8 18-1/8 44-3/16 66-3/16 15-3/8 17-9/16 5/8
Table 103: Low Static L1, L2, L3 Suspension Bolt Positions. Figure 68: Low Static Ducted Bolt Locations.
Dimension (inches) E
Frame
A B C D E F G H I J G
L1 28-7/8 30-7/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 26 6-1/8 27-9/16
L2 36-3/4 38-5/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 33-7/8 6-1/8 35-7/16
L3 44-5/8 46-3/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 41-3/4 6-1/8 43-5/16 D C
J
A
B
F
I
H Drain
Hole
Due to our policy of continuous product innovation, some specifications may change without notification.
120 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
General Mounting - High, Low, and Built In Ducted Units
Table 104: Built In Ducted Suspension Bolt Positions. Figure 69: Built In Ducted Bolt Locations.
Dimensions (inches) B
Frame A
A B C D E F G H I J
B3 33-7/16 35-7/16 15 22-5/8 3-11/16 7-1/2 7/8 31-5/16 6-7/16 32-3/8
J
B4 44-7/16 46-1/2 15 22-5/8 3-11/16 7-1/2 7/8 41-15/16 6-7/16 43-5/16
D
C
E
G
General Mounting Procedure
F
I
1. Select and mark the areas where the hanging bolts should be placed.
Application Guidelines
2. Drill the holes.
H
3. Install the unit horizontally using a level gauge.
Drainage point
Do not damage power wiring during installation. There is risk of electric shock, Figure 70: Drilling Holes for the Hanging Bolts.
which may result in physical injury or death.
Flat washer for M10 Figure 72: Old Versus New Building Hanging Bolt Installation.
(accessory) Old Building New Building
Nut
(W3/8 or M10)
The following parts are field Included with the indoor unit:
supplied: • Flat washer - M10
• Hanging bolt - W-3/8″ or 1/2″
• Nut - W-3/8″ or M10 1 Set Anchor
• Spring washer - M10 2 Plate Washer
3 Spring Washer
The threaded rod hangers (bolts) and hardware must be secure- 4 Nut
ly tightened to prevent the unit from falling from its installation 5 Hanging Bolts
location. There is a risk of personal injury from falling equip-
ment.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 121
Application Guidelines
General Mounting - Vertical / Horizontal Air Handler Units
Duct Work For Vertical / Horizontal Air Handler Units Figure 75: Attaching Ducts to the Vertical / Horizontal Air Handler Unit.
• Use at least ten (10) M4-25L screws when attaching the supply
duct to the vertical-horizontal air handler unit.
Application Guidelines
Air Conditioning Contractors’ National Association (SMACNA)
Construction Standard.
Table 106: Vertical / Horizontal Air Handler Unit Duct Connection Figure 76: Vertical / Horizontal Air Handler Unit Duct Connection
Dimensions Table. Dimensions Diagram.
Dimensions (inches)
Model No. A B C
D E F G H
Height Width Depth
NJ Frames Front
ARNU123NJA2
48-5/8 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8
ARNU183NJA2
Refrigerant Pipe Right Side
ARNU243NJA2 Connections
Drain
Connections
ARNU303NJA2 48-5/8 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 for Upflow
ARNU363NJA2 Installation
Drain Connections
NK Frames for Horizontal-Left
ARNU423NKA2 Installation
Bottom
Top
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 123
APPLICATION GUIDELINES
General Drain Piping Information
General Drain Piping Information Figure 77: High Static, Low Static, Built In Ducted Indoor Unit Drain
Pump to Drain Piping System.
All ducted indoor units generate water during cooling operation,
therefore, how to properly handle this condensation must be Hanger distance
considered. High Static, Low Static, and Built In Ducted indoor Max. 3.3~4.9 feet
units include factory-installed drain pumps; Vertical / Horizontal Air 11-13/16 inches Hanger Bracket
Handler units have a gravity drain. Depending on the location of the
indoor unit, condensation can be drained directly to the outside of PVC Elbow
1/50~1/100
slope
the building, or a common indoor unit drainage piping system can be Metal PVC Piping
installed. clamp
Vertical / Horizontal Air Handler Unit Drain Information Drain pump Flexible drain hose
MULTI V Ducted Indoor Unit Engineering Manual
• Avoid blocking filter access panel when connecting the condensate Insulation
drain lines.
• An additional external condensate line should run from the unit into Figure 78: Vertical / Horizontal Air Handler Unit Drain Piping System.
the pan. Drain for Upflow Installations Drain for Horizontal-Left Installations
• The entire condensate line should be drained from the external
condensate pan. Horizontal-Left
Drain Access Hole
• Point the drain hose downward for easy drain flow.
• Do not use pipe joint connection or PVC/CPVC for the unit drain Air Filter Cover
Supplementary drain
with proper trap. (Field-
supplied kit can be used.)
Drain Leak Test Figure 82: Properly Insulating the Drainage Piping.
A leak test should be performed 24 hours after the drainage system
has been installed.
Application Guidelines
To prevent condensate from forming on the drain piping, field-
supplied 5/16 inch thick polyethylene insulation should be properly
installed.
Ensure the indoor unit, refrigerant piping, drain piping, and power wiring /
communication cables are properly supported with anchor bolts and clamp Insulation Insulation Properly Fitting Insulation
hangers positioned at 3.3 to 4.9 foot intervals. Not Required Requir ed
Common Indoor Unit Drainage System Figure 83: Example of a Common Indoor Unit Drainage System.
It is usual work practice to connect individual 45° to 60° Angle 45° to 60° angle for protection against overflow
indoor unit drain pipes to one common indoor unit
drainage system.
45° to 60° Angle
The diameter of the common vertical drain pipe
should be as large as necessary. The diameter of 45° to 60° Angle Position the vent
down to prevent
the horizontal pipe should be the same or larger Common horizontal drain pipe debris from entering
1/50
than the vertical drain pipe. To avoid property to 1
/100 the system
damage in the event of the primary drain becom- Slop
e
ing clogged, and to optimize drain system perfor-
mance, it may be prudent to install a secondary
drain line.
27-1/2 in.
(Maximum pump
Common
Design the drain system to plan for winter opera- lift distance
vertical
[depends on indoor
tion (condensate line may freeze up if condensate unit type]). drain pipe
does not properly drain away). Drain all gener-
ated condensate from the external condensate
Include trap
pan to an appropriate area. Install a trap in the at the end.
condensate lines as near to the indoor unit coil as
possible. To prevent overflow, the outlet of each
trap should be positioned below its connection to • It is recommended that a dedicated drain pipe be installed for the air conditioning
the condensate pan. All traps should be primed, system. If the indoor unit drainage system is shared with a rainwater drain, waste
insulated, and leak tested. water, or any other type of building drain system, back flow, leaks, ice may form,
or noxious odors may infiltrate the air conditioning system.
• Install a trap if the drain access to the outside faces an undesirable location (i.e.,
sewer), otherwise, noxious odors may infiltrate the air conditioning system.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 125
Application Guidelines
Wiring Guidelines
• Communication cable must be a minimum of 18 AWG, two-conductor, stranded, shielded, and must comply with the applicable local
and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU-IDU
communication cable at any other point.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system. Add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Any openings where the field wiring enters the cabinet must be completely sealed.
• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk electric shock,
physical injury or death.
• Loose wiring may cause the wires to burnout or the terminal to overheat and catch fire. There is a risk of electric shock, physical
injury or death.
• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk equipment
malfunction or property damage.
• Loose wiring may cause unit malfunction, the wires to burnout or the terminal to overheat and catch fire. There is a risk of equip-
ment malfunction or property damage.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
tems only) wiring match the color and terminal High Voltage
(208/230V)
numbers on the indoor unit.
Due to our policy of continuous product innovation, some specifications may change without notification.
126 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
Wiring Guidelines
Figure 85: Location of Power Wiring / Communications Cable Terminals in the Built In Ducted Indoor Unit.
L(L1) N(L2) YL RD BK
3(A) 4(B)
Lock nut
Figure 86: Location of Power Wiring / Communications Cable Terminals in the Vertical / Horizontal Air Handler Unit.
Application Guidelines
Power Wiring Through
Optional Access Hole
Figure 87: Terminal Block in the High Static (BG, BR, B8 Frame) Ducted Indoor Unit.
Outdoor Unit Terminal Block
Indoor Unit Terminal Block
SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) YL RD BK A B B A - - B A - - - -
Figure 88: Terminal Block in the Low Static (L1, L2, L2 Frame) Ducted Indoor Unit.
Outdoor Unit Terminal Block
Indoor Unit Terminal Block SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) 3(A) 4(B) B A - - B A - - - -
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 127
Application Guidelines
Wiring Guidelines / Wired Controller Placement
Figure 90: Terminal Block in the Vertical / Horizontal Air Handler Units.
Wired Controller Placement Figure 91: Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To
maintain comfort levels in the conditioned space, the wired control-
ler must be installed in a location away from direct sunlight, high
humidity, and where it could be directly exposed to cold air. Control-
ler must be installed four (4) to five (5) feet above the floor where its
LED display can be read easily, in an area with good air circulation, YES
and where it can detect an average room temperature.
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
Due to our policy of continuous product innovation, some specifications may change without notification.
128 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Acronyms
Application Guidelines
DPST Double-Pole Single Throw SMACNA Sheet Metal & Air Conditioning Contractors’ National Association
DX Direct expansion RPM Revolutions per Minute
EEV Electric Expansion valve TC Total Capacity
EPDM Ethylene Propylene Diene M-Class Rubber USD United States Dollar
EMF Electromagnetic Field UL Underwriters Laboratories
ESP External Static Pressure V Voltage
ETL Electric Testing Laboratories VAV Variable Air Volume
GND Ground VRF Variable Refrigerant Flow
H/M/L High/Medium/Low W Watts
HVAC Heating, Ventilating and Air Conditioning WB Wet Bulb
Hz Hertz wg Water Gauge
ID Inside Diameter
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 129
LG Electronics U.S.A., Inc. LG Electronics Commercial Products Support
Commercial Air Conditioning Division 1-888-865-3026 USA
11405 Old Roswell Road Follow the prompts for commercial A/C products. EM-MultiV-Ducted-IndoorUnits-02-15
Alpharetta, Georgia 30009 Supersedes: EM-MultiV-Ducted-IndoorUnits-01-15