Issue Date:
Service April 09, 2015
Global Lit Num: CPGK - S - 00000207 - 0
Revision: 0
Background/Description:
It has come to our attention that there have been several incidents of engine failures when
a VTA28-G5 engine is being operated at 60Hz whilst configured for operation at 50Hz and
vice versa.
Corrective Actions:
This Product Support Bulletin details the parts that need to be changed/replaced to carry
out the 50Hz to 60Hz conversion or vice-versa.
When carrying out this conversion, observe all applicable Health and Safety guidelines.
Health and Safety information can be found in the documentation specific to the generator
set.
Warranty Statement:
This PSB does not include any authorized warrantable work.
Contact:
Dealers:
Contact you Cummins Distributor
Distributors:
Your local Service Manager
DFSE-Counterpart
The EMEA Technical Support line +44(0) 1843 255873
An Authorised Cummins Distributor must complete the conversion to prevent voiding the warranty.
Please note: Unauthorised modification of a Cummins engine / generator set may void factory
warranty (see Warranty Manual A040W374) and could lead to product and property damage,
personal liability, as well as significant health and safety risks. Please refer to Bulletin ‘CPGF-S-
00000196-0’ for further information on Product Modification Authorisation.
Prior to Conversion
Before the engine is reconfigured, EBU approval must be requested. To request approval, the Engine
Modification Form must be filled out in accordance to the desired changes to the engine. The Engine
Modification Form can be found on QSOL in the ‘Warranty Documents’ listed in the ‘Related
Information’ section, which can be found under the ‘Warranty’ tab. The completed form must be
sent to emea.customerassistance@cummins.com
Once approval is received from EBU, an appropriate TSR has to be raised by the party carrying out
the conversion. The TSR has to be raised and escalated to the Factory. It must contain the following
information:
Once the Factory has received the TSR, any additional requirements will be communicated to the
Distributor. These requirements may include feature codes, software/calibration updates etc.
Additionally, the Distributor has to order a new Generator Data Plate detailing the new operating
frequency. To order a new Data Plate, please contact cpgk.customer.quality@cummins.com. Please
note, a new Generator Data Plate is not required in case of a G Drive application.
Conversion Steps
Parts required for VTA28 G5 to operate at 1500 RPM (50 Hz Output):
All damper mounting cap screws must be checked for damage or permanent elongation and
changed if required. If in doubt, please proceed to replace these bolts. Please see Figure 1 and Figure
2 for appropriate bolt Part Numbers.
Conversion Steps:
2. Damper
Install Viscous Damper DA5073 (for 50Hz operating frequency, see Figure 1) or Rubber
Damper DA5014 (for 60Hz operating frequency, see Figure 2).
3. Air Cleaner
Install the AC5115 Heavy Duty Air Cleaner.
Ref. No. Part No. Part Description Qty Ref. No. Part No. Part Description Qty
2 3015585 Screw, Twelve Point Cap 6 2 3015585 Screw, Twelve Point Cap 6
4 169195 Screw, Hexagon Head Cap 6 4 213364 Screw, Hexagon Head Cap 6
6 3077985 Damper, Vibration 1 5 213351 Damper, Vibration 1