HPL
HPL
HPL
Domestic
Vapor Compression refrigeration
System
T. Mahaboob Basha1, H.Ranganna2,G. Maruthi Prasad Yadav3
1.PG Student, Mechanical Engineering Dept, St Johns College of Engg & Technology, Yemmiganur-518360,
Kurnool(Dist), AP
2 & 3.Associate Professor, Mechanical Engineering Dept, St Johns College of Engg & Technology, Yemmiganur-
518360,
Kurnool(Dist), AP,
Abstract: The performance of Vapor compressionre frigeration system (VCRS) depends on the
performance of all its components like compressor,condenser, expansion value and evaporator. The
current paper is involved in analysis of the effect of condenser length on the performance of on
VCRS.
Condenser is a heat exchanger where heat transfer takes place between the super heated
refrigerant received from the compressor and the cooling medium of the condenser. The condenser
removes the heat from refrigerant which received in two stages. Heat is received by the refrigerant
in the evaporator and also heat is added by the compressor during compression. The refrigerant is
first cooled to saturation and then condensed to liquid state. In Domestic refrigerator the condenser
coil is used todischarge the heat from the refrigerant after operating the compression to the
atmosphere. In this present work a condenser coil with different lengths are tested.In the present
work condenser with variable length ((9.45m, 9.75m, 10.06m) has been used for this investigation by
keeping the diameter as constant and compared with existing condenser of 9.14m length. The
results shown that 9.75m length condenser coil gives optimum performance than the remaining
which gives higher COP, higher heat rejection, refrigeration effect and lower power consumption..
Vapor Compression Refrigeration system is an improved type of air refrigeration system. The
ability of certain liquids to absorb enormous quantities of heat as they vaporize is the basis of
this system. Compared to melting solids (say ice) to obtain refrigeration effect, vaporizing liquid
refrigerant has more advantages. To mention a few,the refrigerating effect can be started or stopped
at
will, the rate of cooling can be predetermined, the vaporizing temperatures can be governed by
controlling the pressure at which the liquid vaporizes. Moreover, the vapor can be readily
collected and condensed back into liquid state so that same liquid can be re-circulated over and over
again to obtain refrigeration effect. Thus the vapor compression system employs a liquid refrigerant
which evaporates and condenses readily. The System is a closed one since the refrigerant never
leaves the system. The coefficient of performance of a refrigeration system is the ratio of refrigerating
effect to the compression work; therefore the coefficient of performance can be increased by
increasing the refrigerating effect or by decreasingthe compression work.
II.SELECTION OF CONDENSER FOR A VCR SYSTEM
2.1 Condenser
Condenser is that component which is placed next to compressor in a vapor compression
refrigeration system. It is a heat exchanger that affects heat transfer between refrigerant gas, vapor
or super saturated vapor coming from compressor and cooling medium such as air or water. It
removes heat absorbed by refrigerant in the evaporator and the heat of compression added in the
compressor and condenses it back to liquid. The condenser abstracts the latent heat from high
pressure refrigerant at the same pressure and constant temperature. For this purpose the
condenser employs a cooling medium such as air or water.
III.EXPERIMENTAL SETUP
In vapor compression refrigerating system basically there are two heat exchangers. One is to
absorb the heat which is done by evaporator and another is to remove heat absorbed by refrigerant in
the evaporator and the heat of compression added in the compressor and condenses it back to liquid
which is done by condenser. This project focuses on heat rejection in the condenser this is only
possible either by providing a fan or by extending the surfaces. The extended surfaces are called fins.
The rate of heat rejection in the condenser depends upon the number of fins attached to the
condenser. In the present domestic refrigerator copper material fins are used. The performance of the
condenser will also help to increase COP of the system as the sub cooling region incurred at the exit of
the condenser. The
performance of the condenser is also investigated by existing and modification condenser. In general
domestic refrigerators have no fans at the condenser and hence extended surfaces like fins play a very
vital role in the rejection of heat.
International Journal of Science, Engineering and Technology Research (IJSETR)
Volume 4, Issue 2, February 2015
ISSN: 2278 – 7798 All Rights Reserved © 2015 IJSETR 278
In order to know the performance characteristics of the vapor compression refrigerating system the
temperature and pressure gauges are installed at each entry and exit of the component. Experiments
are conducted on condenser having fins. Different types of tools are also used like snips to
cut the fins to required sizes, tube cutter to cut the tubes and tube bender to bend the copper tube to
the
required angle. Finally the domestic refrigerator is fabricated as for the requirement of the project. All
the values of pressures and temperatures are tabulated.
The figure 1 shows the experimental setup of the refrigerator. In order to know the performance
characteristics of the vapor compression refrigeration system the temperature and pressure
gauges are installed at each entry and exit of the components. Experiments are conducted on
condenser with coil spacing of the condenser on a refrigerator of capacity 170liters. All the values of
pressures and temperatures are tabulated.
Domestic refrigerator selected for the project has the following specifications:
Refrigerant used: R-134a
Capacity of The Refrigerator: 170 liters
Compressor capacity: 0.16 H.P.
Condenser Sizes
Diameter - 6.35 mm
Evaporator
Length - 7.62 m
Diameter - 6.4 mm
Capillary
Length - 2.428 m
Diameter - 0.8 mm
Condenser length of existing system is 9.14m and in the present work condenser lengths of 9.45m,
9.75m and 10.06m are tested to analyze its effect on the performance of refrigeration system.
Fig 1 Proposed System with condenser coil lengths of9.14m, 9.45m, 9.75m & 10.06m.
IV.EXPERIMENTAL PROCEDURE
The following procedure is adopted for experimental setup of the vapor compression refrigeration
system
1. The domestic refrigerator is selected, working on
vapor compression refrigeration system.
2. Pressure and temperature gauges are installed at
each entry and exit of the components.
3. Flushing of the system is done by pressurized
nitrogen gas.
4. R 134a refrigerant is charged in to the vapor
compression refrigeration system by the following
process:
The systematic line diagram for charging is shown in the fig 2. it is necessary to remove the air from
the refrigeration unit before charging. First the valve V2 is closed and pressure gauge P2, vacuum
gauge V are fitted as shown in the fig. the valve V5 is also closed and valves V1, V4, V6 and V3 are
opened and the motor is started thus the air from the condenser receiver and evaporator is sucked
through the valve V1 and it is discharged in to atmosphere through the valve V6 after compressing
it in the compressor the vacuum gauge V indicates sufficiently low vacuum when most of the air is
removed in the system. The vacuum reading should be at least 74 to 75 cm of Hg. If the vacuum is
retained per above an hour it may be concluded that the system is free from the air. After removing
the air the compressor is stopped and valves V1 and V6 are closed, the valves V5, V2 and V7 of the
refrigerant cylinder are opened and then the compressor is started whenever the sufficient
quantity of refrigerant is taken in to the system which will be noted in the pressure gauges. The
compressor is stopped. The valves V7 and V5 are closed and valve V1 is opened the refrigerant
cylinder is disconnected from the system the pressure gauge is used to note the pressure during
the charging the system.
Fig.2 charging of refrigeration system
5. Leakage tests are done by using soap solution, In order to further test the condenser and evaporator
pressure and check purging daily for 12 hours and found that there is no leakages which required the
absolutely the present investigation to carry out further experiment.
6. Switch on the refrigerator and observation is required for 1 hour and take the pressure and
temperature readings at each section.
7. The performance of the existing system is investigated, with the help of temperature and pressure
gauge readings.
8. The refrigerant is discharged out and condenser is located at the inlet of the capillary tube.
9. Temperature and pressure gauge readings are taken and the performance is investigated.
10. The readings are tabulated for condenser coil diameter 6.35mm, 7.93mm, and 9.52mm.
11. The following tests are conducted and calculations are shown below.
V.PERFORMANCE CALCULATIONS
The temperature and pressure readings are noted down and from pressure-enthalpy chart for R-134a,
enthalpy values at state points 1,2,3,4 and are tabulated as follows shown in table 1 .
Parameter
Condenser coil length(m) 9.14, 9.45, 9.75, 10.1
Compressor Suction Temperature T1(°C) 32, 34,34, 31
Compressor Discharge Temperature T2(°C) 65, 68, 67, 65
Condensing Temperature T3(°C) 51, 48, 39, 48
Evaporator Temperature T4(°C) -10, -10, -10, -10
Compressor suction pressure P1(bar) 3.2, 3.2, 3.1, 2.7
Compressor discharge pressure P2(bar) 12, 12.1, 12.2, 12.5
Condenser pressure P3 (bar) 12, 11.8, 11.7, 11.2
Evaporator pressure P4(bar) 3.2, 3.2, 3.2, 2.5
Enthalpy,h1(kJ/kg) 425, 428, 427, 427
Enthalpy,h2 (kJ/kg) 459, 462, 461, 464
Enthalpy,h3(kJ/kg) 263, 262, 255, 262
Enthalpy,h4(kJ/kg) 263, 262, 255, 262