Fired Boilers: 2.1 Design Principles
Fired Boilers: 2.1 Design Principles
Fired Boilers: 2.1 Design Principles
20576 1 Confidential
2. FIRED BOILERS
Typical conditions at
outlet evaporator 350 °C
3-10% Wt steam 23.5 Bar
97-90% Wt water
Temp °C
The boiler is supplied with feed water by a boiler feed pump and it passes through the
economiser to the steam drum. The economiser is a tube bundle located in the coolest part of the
boiler’s flue gas side, just upstream of the flue gas stack. In the economiser, the feed water is
heated up to a temperature close to, or even equal to the saturation temperature of the boiler
water, Fig 1. Then the feed water enters the steam drum through a perforated distribution pipe
where it mixes with boiler water rising from the evaporator.
The mixed boiler water leaves the steam drum through the boiler downcomer pipes which feed
into the evaporator riser tubes via bottom headers or a bottom water drum. In the evaporator
tubes, heat is applied and the water partly vaporises on its return journey to the steam drum. The
flow of boiler water through the evaporator, in this case, is achieved by natural circulation.
In some boilers there may be two different evaporator sections equipped with riser tubes. Firstly
there is always a cooled radiant section where the heat from the burner flames is transferred by
radiation.
Secondly, in some cases only, there is an evaporative convection bank, located as a vertical tube
bundle connecting the steam (top) and water (bottom) drums, Fig. 2.
A A Downcomers
Risers
Risers
Burners
Waterdrum
0022-0
From the top of the evaporator, the mixture of water and steam rises into the steam drum. Here,
the steam is separated from the water and dried by means of cyclones or baffle plates and
demisters. Some of the steam generated in the evaporator condenses in the steam drum in order
to heat the incoming feed water up to the saturation temperature of the boiler water.
The dried saturated steam leaves the steam drum through a pipe at the top and flows through the
superheater tube coils where it is heated up to its final process temperature. A constant steam
temperature at varying boiler loads is obtained by use of condensate spray desuperheating. To
reduce the metal temperature of the superheater outlet tubes, the superheater is often divided
into a primary and a secondary section with the desuperheater located in between, Fig. 3.
Superheaters
Condensate injection
TC
Flue gas
Steam Drum
Blowdown
Economizer
Unheated
Section A -A A downcomer
Feed water
Furnace wall
Burners To Stack
In natural circulation, the mixture of water and steam in the evaporator rises because it has a
lower density than the water supplied in the unheated or cooler downcomer tubes. In refinery
boilers, around 3% to 10% by mass of the circulated water is vaporised within the evaporator
tubes. In other words, the circulation ratio (CR), defined as the mass of water and steam
circulating to the mass of steam generated, is between 11 and 34. When the boiler load changes,
the steam generation rate changes and the CR adapts automatically to the prevailing conditions.
The objective of the boiler designer is to ensure that the evaporator tubes are effectively cooled
by nucleate boiling under all operating loads. This requires a well designed system for distribution
of water to each heated tube so that there is adequate cooling and there is no risk of overheating
of tubes due to film boiling, flow segregation, vapour locking, or flow starvation.
As mentioned above, there may be two different types of evaporator sections depending on the
type of boiler, these are the radiant section and the evaporative convection bank.
Radiant Section
The walls of the radiant section are built from vertical riser tubes of 2 to 3 inches diameter. Boiler
water from the steam drum is supplied to the bottom of the riser tubes by the downcomer tubes
that are always cooler than the risers and in some boilers are unheated, Figs. 2, 3, 4.
4 x Corner Burners
Fireball
In the radiant section, a number of (normally) horizontal firing burners are located in one of the
vertical walls, Fig. 2. In the corner- or tangentially-fired boiler, fuel burners are mounted in the four
corners of the radiant section, Fig. 4. In Group Refineries, boilers burn fuel oil and/or fuel gas and
part of the heat liberated within the radiant section is transferred by radiation to the riser tube
walls.
The non-vertical radiant section roof and floor tubes should have sufficient slope to allow proper
water circulation. Floor tubes are often protected from overheating by a layer of fire bricks.
Convective Evaporator
Figures 2 shows the general arrangements of a bi-drum boiler with horizontal burners. Here the
combustion gases have to turn near the radiant section rear wall opposite the burners and then
flow upwards and around an aerodynamic "nose" before reaching the convective evaporator
bank.
This tube bank is a bundle of convection tubes that are connected at the top to the steam drum
and at the bottom to the water drum. The tube bank consists of a number of steam raising riser
tubes located in front of a vertical partition baffle and a number of downcomer tubes located
behind this baffle. The boiler water enters the downcomer tubes at the top and flows by natural
circulation through the water drum into the risers of both the boiler bank and the radiant section
walls.
A feature of the bi-drum design is that the downcomers are heated. This requires very careful
design in order to guarantee a positive downflow of non-vaporised water through the downcomers
at all boiler loads. There must be a clear-cut separation between the riser tubes with a high heat
load and the downcomer tubes with a lower heat load. Otherwise there would be a transition zone
with tubes that have no cooling flow. Such tubes would be overheated and would very soon fail.
The single-drum boiler, Figs. 3 and 4, uses unheated downcomers located outside of the flue gas
path. These consist of a small number of large diameter pipes which feed boiler water from the
steam drum to the bottom headers of the boiler wall tubes.
In both cases a final separation stage is used consisting of a screen separator. This can be a
bank of closely-spaced corrugated plates that directs the steam through a tortuous path and
forces any remaining water droplets against the plates. Alternatively, the separator can be a
demister pad which collects the water droplets on its matrix of twisted wires. In both types of
separator, the water cannot be picked up again by the low velocity steam and it drains down into
the lower part of the drum.
2.1.4 Superheater
The job of the superheater is to take dry saturated steam from the steam drum and superheat it to
the required temperature. As a consequence, the superheater has the highest process and metal
temperatures in the boiler.
The superheater is located in the transition zone between the radiant section and the convection
bank, Fig. 2. It consists generally of a convection superheater (primary section) at the inlet of the
convection section and a radiant/convection superheater (secondary section) at the radiant
section exit.
The heat transfer film coefficient inside the superheater tubes is rather small, therefore the tube
metal temperature is rather high. There are several techniques used to minimise the maximum
wall temperature, for example by placing evaporative shield tubes in front of the secondary
superheater, Fig. 4 or by employing concurrent flow in the secondary superheater, Fig. 3.
2.1.5 Economiser
The economiser is a convection tube bank located at the end of the flue gas path in the coolest
part of the boiler, Figs 3 and 4. To avoid the risk of acid corrosion from sulphur-bearing fuels, the
economiser water inlet temperature is nearly always controlled at or above 145°C.
In the bi-drum boiler, the economiser has a smaller duty than it does in a boiler with unheated
downcomers. In the latter case the economiser may be specially designed to produce a small
amount of steam (see "steaming eco" in Fig. 1).
(b) All critical parts of the radiant section shall be visible through an adequate number of
observation windows. This is to allow visual checking of combustion conditions both at the
burner throats and the flame extremities and also to verify that there is no flame
impingement on radiant section side wall tubes, rear wall tubes or superheater shield tubes.
(d) Boilers shall be forced draught, i.e. balanced draught boilers with both forced and induced
draught fans are not generally acceptable any more.
(e) The combustion air shall be supplied by a motor-driven forced draught fan complete with a
flow measuring venturi in the air intake stack. Automatic control of the air flow shall be by
variable inlet guide vanes or by electric variable speed motor drive.