Installation Instructions

FLEX I/O Terminal Base Units


When you insert or remove the module while backplane power is on, an
1794-TB2, -TB3, -TB3K, -TB3S, -TB32, -TB32S, -TB3G, WARNING
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
-TB3GK, -TB3GS, -TB3T, -TB3TS, -TBN, -TBNK, -TBNF, before proceeding.
-TBNFK, -TBKD, -TB3SK, -TB3GSK, -TB3TK, -TB3TSK
(Modules with a K in the last position of the catalog number are conformally coated
to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 WARNING If you connect or disconnect wiring while the field-side power is on, an
Environment.) electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State
Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.literature.rockwellautomation.com) describes some important differences between ATTENTION FLEX I/O systems are grounded through the DIN rail to chassis ground. Use
solid state equipment and hard-wired electromechanical devices. Because of this difference, and zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
also because of the wide variety of uses for solid state equipment, all persons responsible for use of other DIN rail materials (for example, aluminum or plastic) that can
applying this equipment must satisfy themselves that each intended application of this equipment is
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
acceptable. (7.8 in.) and use end-anchors appropriately.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential
damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of
the many variables and requirements associated with any particular installation, Rockwell ATTENTION Prevent Electrostatic Discharge
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams. This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, this equipment:
circuits, equipment, or software described in this manual. • Touch a grounded object to discharge potential static.
Reproduction of the contents of this manual, in whole or in part, without written permission of • Wear an approved grounding wriststrap.
Rockwell Automation, Inc. is prohibited. • Do not touch connectors or pins on component boards.
Throughout this manual we use notes to make you aware of safety considerations. • Do not touch circuit components inside the equipment.
Identifies information about practices or circumstances that can cause an • Use a static-safe workstation, if available.
WARNING
explosion in a hazardous environment, which may lead to personal injury or • Store the equipment in appropriate static-safe packaging when not in
death, property damage, or economic loss. use.

IMPORTANT Identifies information that is critical for successful application and


understanding of the product. ATTENTION Do not remove or replace a Terminal Base unit while power is applied.
Interruption of the backplane can result in unintentional operation or machine
ATTENTION Identifies information about practices or circumstances that can lead to motion.
personal injury or death, property damage, or economic loss. Attentions
help you identify a hazard, avoid a hazard, or recognize the consequence

ATTENTION Do not wire more than 1 conductor on any single terminal.


ATTENTION Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial


environment, in overvoltage Category II applications (as defined in IEC
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR 11. Without appropriate precautions, there may be
difficulties with electromagnetic compatibility in residential and other Personnel responsible for the application of safety-related Programmable
environments due to conducted and radiated disturbances. ATTENTION
Electronic Systems (PES) shall be aware of the safety requirements in the
This equipment is supplied as open-type equipment. It must be mounted application of the system and shall be trained in using the system.
within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed
to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure
must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product
safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1, for additional installation
requirements.
• NEMA Standards 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure.

Publication 1794-IN092E-EN-P - November 2009


2 FLEX I/O Terminal Base Units

North American Hazardous Location Approval FLEX I/O Spring-clamp Terminal Base Units
The following terminal bases are Hazardous Location approved: 1794-TBN, Cat. No. 1794-TB3S, -TB3SK, -TB32S, -TB3GS, -TB3GSK, -TB3TS, -TB3TSK
-TBNK, -TB2, -TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, 10
1 4
-TB3GSK, -TB3T, -TB3TK, -TB3TS, -TB3TSK, -TB32S, -TB32.
3
The following information applies when operating Informations sur l’utilisation de cet équipement en 11
this equipment in hazardous locations: environnements dangereux :
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent 5
use in Class I Division 2 Groups A, B, C, D, Hazardous qu’à une utilisation en environnements de Classe I Division 2 2
Locations and nonhazardous locations only. Each product is Groupes A, B, C, D dangereux et non dangereux. Chaque produit 6
supplied with markings on the rating nameplate indicating est livré avec des marquages sur sa plaque d’identification qui
the hazardous location temperature code. When combining indiquent le code de température pour les environnements 7
products within a system, the most adverse temperature dangereux. Lorsque plusieurs produits sont combinés dans un
code (lowest “T” number) may be used to help determine the système, le code de température le plus défavorable (code de 8
overall temperature code of the system. Combinations of température le plus faible) peut être utilisé pour déterminer le
equipment in your system are subject to investigation by the code de température global du système. Les combinaisons 9 12 13 12
local Authority Having Jurisdiction at the time of d’équipements dans le système sont sujettes à inspection par les
installation. autorités locales qualifiées au moment de l’installation.
EXPLOSION HAZARD RISQUE D’EXPLOSION
WARNING
• Do not disconnect equipment
AVERTISSEMENT
• Couper le courant ou s’assurer que
FLEX I/O Terminal Base Units
unless power has been removed l’environnement est classé non Cat. No. 1794-TBN, -TBNK
or the area is known to be dangereux avant de débrancher
nonhazardous. l'équipement. 10
• Do not disconnect connections to • Couper le courant ou s'assurer que 4
this equipment unless power has l’environnement est classé non 1
been removed or the area is dangereux avant de débrancher les 3
known to be nonhazardous. connecteurs. Fixer tous les
Secure any external connections connecteurs externes reliés à cet 11
that mate to this equipment by équipement à l'aide de vis, loquets 6
using screws, sliding latches, coulissants, connecteurs filetés ou
threaded connectors, or other autres moyens fournis avec ce 5
means provided with this product. produit.
• Substitution of components may • La substitution de composants peut 2
impair suitability for Class I, rendre cet équipement inadapté à 8
Division 2. une utilisation en environnement de
• If this product contains batteries, Classe I, Division 2.
they must only be changed in an • S’assurer que l’environnement est
area known to be nonhazardous. classé non dangereux avant de 15
changer les piles. 9

European Hazardous Location Approval FLEX I/O Fused Terminal Base Units
The following adapters are European Zone 2 approved: 1794-TBN, -TBNK, -TB2,
-TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, -TB3GSK, -TB3T, Cat. No. 1794-TBNF, -TBNFK
-TB3TK, -TB3TS, -TB3TSK. 10
4 14
1
3
European Zone 2 Certification (The following applies when the product bears the Ex
or EEx Marking) 11
5
This equipment is intended for use in potentially explosive atmospheres as defined by European
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 2
Requirements relating to the design and construction of Category 3 equipment intended for use
in potentially explosive atmospheres, given in Annex II to this Directive. 6
Compliance with the Essential Health and Safety Requirements has been assured by compliance 6
with EN 60079-15 and EN 60079-0. 14 15 9

WARNING Observe the following additional Zone 2 certification requirements. FLEX I/O Knifeswitch Terminal Base Unit
• This equipment is not resistant to sunlight or other sources of UV Cat.Cat.
NoNo.
1794-TBKD
1794-TBKD
radiation.
• This equipment must be installed in an enclosure providing at least IP54 10 4
protection when applied in Zone 2 environments. 1 3
• This equipment shall be used within its specified ratings defined by
Allen-Bradley. 16
• Provision shall be made to prevent the rated voltage from being 11
exceeded by transient disturbances of more than 40% when applied in 5
Zone 2 environments. 2
• Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided 6, 7
with this product. 6, 7
• Do not disconnect equipment unless power has been removed or the 9
area is known to be nonhazardous.
Description
1 Female flexbus connector
FLEX I/O Cage-clamp Terminal Base Units 2 Terminal base unit
Cat. No. 1794-TB2, -TB3, -TB3K, -TB32, -TB3G, -TB3GK, -TB3T, -TB3TK 3 Male flexbus connector
10
1 4 4 Keyswitch - set to the position required for the installed module
3 5 Mounting holes for panel mounting
11 6, 7, Input/output terminal strips for connecting inputs/output wiring, commons, power
1794-TB2 8 connections, customer power supplies, chassis grounds
5
2 9 Locking tab
6 10 Module locking latch
7 11 Cover plug for male flexbus connector
8 1794-TB3, -TB3K, -TB32, 12 Cold-junction compensation terminals (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK only)
9 -TB3G, -TB3GK, -TB3T, -TB3TK 13 Chassis ground terminations (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK, -TB3G, -TB3GS,
-TB3GSK only)
14 Fuses - eight 5x20 mm (1794-TBNF, -TBNFK only)
15 Terminal strip cover (1794-TBN, -TBNK -TBNF, -TBNFK only)
16 Knife switches (1794-TBKD only)

Publication 1794-IN092E-EN-P - November 2009


FLEX I/O Terminal Base Units 3

Mount the Terminal Base Unit on a DIN Rail

ATTENTION During mounting of all devices, be sure that all debris (such as metal chips or
wire strands) is kept from falling into the module. Debris that falls into the
module could cause damage upon application of power.

1. Remove the cover plug (if used) in the male connector of the unit to which
you are connecting this terminal base unit.
2. Check to make sure the 16 pins in the male connector on the adjacent Gently push the flexbus connector into the side of the side of the adapter to
device are straight and in line so that the mating female connector on this complete the backplane connection.
terminal base unit will mate correctly.
6. Refer to the installation instructions for specific wiring information for the
3. Make certain the female connector (B) is fully retracted.
module you are installing in this terminal base.
4. Position the terminal base unit on the 35 x 7.5 DIN rail (A) (A-B pt no.
7. Repeat the above steps to install the next terminal base.
199-DR1).

ATTENTION Do not force the terminal base into the adjacent base/adapter. Forcing the units
together can bend or break the hook and allow the units to separate and break ATTENTION When using FLEX I/O modules in a high-vibration installation, especially when
communication over the backplane. mounting the DIN rail vertically, use DIN-rail locks (A-B part number
1492-EA35) to prevent accidental separation of the terminal block units.

Wire Connections for the Terminal Base Units


DIN Rail
Wiring Connections
Wiring for the
Connections 1794-TB32,
for the -TB32S
1794-TB32, 1794-TB32S
B A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

C A
Inputs/Outputs
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

B
NC
A Inputs/Outputs NC

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

C
Position the terminal base at a slight angle and hook it over the top of the DIN rail. NC +V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC

+V1 = Terminals 35, 37, 39, 41 (1794-TB32 shown)


+V2 = Terminals 43, 45, 47, 49
COM1 = Terminals 36, 38, 40, 42
COM2 = Terminals 44, 46, 48, 50
NC = No connections (terminals 16, 33, 34, 51)
C
Wiring Connections
Wiring forfor
Connections thethe
1794-TB2, -TB3,
1794-TB2, -TB3K, -TB3S,
1794-TB3, TB3SK
1794-TB3K, 1794-TB3S
Inputs
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

B
-V Commons -V
Common Common
Make sure the hook (C) on the terminal base slides under the edge of the adapter and the 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

flexbus connector is fully retracted. Slide the terminal base over, tight against the adapter. C
Voltage Voltage
5. Rotate the terminal base onto the DIN rail with the top of the rail hooked In +V Terminals 35 to 50 not available on 1794-TB2 Out +V
under the lip on the rear of the terminal base. Use caution to make Voltage
sure that the female flexbus connector does not strike any of -V (Common) = Terminals B-16 and B-33 (1794-TB3 shown)
+V (Voltage In) = Terminals C-34 and C-51
the pins in the mating connector. For daisy-chaining: Supply in - C-34 (+) and B-16 (-)
Supply out - C-51 (+) and B-33 (-)

WiringWiring
Connections for the
Connections 1794-TB3G,
for the -TB3GK,
1794-TB3G, -TB3GS,
1794-TB3GK, -TB3GSK
1794-TB3GS
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
Inputs/Outputs
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

B
Chassis Inputs/Outputs Chassis
Ground Ground
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

C
+V COM NC Chassis Chassis NC +V COM
Ground Ground
24V dc Chassis Grounds for Shields 24V dc
Supply In Supply Out
I/O I/O
Press down on the terminal base to lock it on the DIN rail. If the terminal base does not lock
into place, use a screwdriver or similar device to open the locking tab, press down on the +24V dc = Terminals C-34, C-50 (1794-TB3G shown)
COM = C-35, C-51
base, and release the locking lever to lock the base in place. Chassis Ground = Terminals B-16, B-33, C-38, C-40 through 45, C-47
NC = No connection
For daisy-chaining: Supply in - C-34 (+), C-35 (-)
Supply out - C-50 (+), C-51 (-)

Publication 1794-IN092E-EN-P - November 2009


4 FLEX I/O Terminal Base Units

Wiring Connections for the 1794-TBN, 1794-TBNK, 1794-TBNF, 1794-TBNFK For Spring-clamp Terminal Base Units: 1794-TB3S, -TB3TS, -TB3GS, -TB32S,
Even Numbered I/O Terminals 0 to 14 -TB3SK, -TB3TSK, -TB3GSK
COM
″ Insert a 2.54…3.05 mm (0.10…0.12 in.) wide-bladed screwdriver into the slot and lift up.
COM
16 0 2 4 6 8 10 12 14 33
B
Insert wire, and remove screwdriver.For Cage-clamp Terminal Base Units: 1794-TB2,
-TB3, -TB3K, -TB3T,-TB3TK, -TB3G, -TB3GK, -TB32
34 1 3 5 7 9 11 13 15 51

C
+V +V ″ Tighten screws to 0.8 Nm (7 lb-in).
Odd Numbered I/O Terminals 1 to 15 For Knifeswitch Cage-clamp Terminal Base Unit: 1794-TBKD
+V = Terminals C-34, C-51 (1794-TBN shown) ″ Tighten screws to 0.53 Nm (6 lb-in).
COM (-V) = Terminals B-16, B-33 For NEMA Screw-clamp Terminal Base Units: 1794-TBN, -TBNK, -TBNF,
-TBNFK
Wiring Connections for the 1794-TB3T,
Wiring Connections for the- 1794-TB3T,
TB3TK, -TB3TS, -TB3TSK
-TB3TS ″ Tighten screws to 1.02 Nm (9 lb-in).
Inputs/Outputs
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Install or Change a Fuse in the 1794-TBNF or 1794-TBNFK Terminal Base
A
Channel Channel Channel Channel Channel Channel Channel Channel Unit
+ 0 -- + 1 -- + 2 -- + 3 -- + 4 -- + 5 -- + 6 -- + 7 --
This terminal base unit has fuse holders for 5x20 mm fuses on each of the eight
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
even-numbered I/O terminals (0 through 14 - row B). To install or change a fuse:
B
C C N0 C N1 C N2 C N3 C N4 C N5 C N6 C N7 C
1. Press the fuse holder down toward the terminal strip.
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
Press down to open.
C
+V Supply CJC Chassis Ground CJC +V Supply
In Out
+V) = 24V dc Supply In - Terminals C-34, C-35 (1794-TB3T shown)
-V = 24V dc Common Terminal B-16
+V = Supply Out - Terminals C-50, C-51
-V = Terminal B-33
C = -V dc common

2. Remove the fuse from the fuse holder.


Wiring Connections for Connections
Wiring the 1794-TBKD
for the 1794-TBKD 3. Insert a known good 5x20 mm fuse into the fuse holder.
CH0 CH1 CH2 CH3 CH4 CH5 CH6 CH7

16
CH0 RET CH1 RET CH2 RET CH3 RET CH4 RET CH5
17 18 19 20 21 22 23 24 25 26 27
RET CH6 RET CH7 RET
28 29 30 31 32 33
4. Rotate the fuse holder back to vertical until it snaps into the locked
B
position.
-V Inputs/Outputs -V
Common
The 1794-TBNF and 1794-TBNFK terminal base units are shipped with eight 5x20
Common
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 mm, 1.6 A, 250V AC slow-blow fuses, one for each even-numbered terminal (0
C through 14 on row B). These fuses are suitable for use with the 1794-OA8 AC
Voltage Voltage output module. Refer to the specific installation instructions for fusing
In +V Common Out +V
recommendations for your particular module.
+V (Voltage In) = Terminals C-34, C-51
-V (Common) = Terminals B-16, B-33, C-35 through C-50
For daisy-chaining: Supply in - C-34 (+), B-16 (-) Use the Knifeswitch Terminal Base
Supply out - C-51 (+), B-33 (-) The knifeswitch terminal base has 16 individual mechanical-knifeswitch circuit
breakers (two for each channel). Each switch opens or closes one side (input/output
and return) for a channel.
Typical Wiring Guidelines

Wiring when total current draw through base is less than 10 A.


Modules in this configuration must be all analog or all digital.

1. Place a small-bladed screwdriver into the slot of the knifeswitch of the I/O
point circuit that you wish to break.
2. Rotate downward to open the circuit.
Wiring when total current draw through base is greater than 10 A.
Total current draw through any base must not be greater than 10 A.
This opens the path of an individual circuit.
3. To reestablish the circuit, rotate the knifeswitch back into the terminal base
unit until it snaps into place.
Thermocouple
or Analog Module Digital Module Digital Module Digital Module

24V dc
24V dc

24V dc

Use separate power supplies for analog and digital modules.


Wiring when there is a mix of analog and digital modules.

Terminal base units are rated at 10 A.

Publication 1794-IN092E-EN-P - November 2009


FLEX I/O Terminal Base Units 5

General

North American T4A (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK,
General temp code -TB3S,-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)

Attribute Value T6 (1794-TB2)

Terminal screw 0.56...0.79 Nm (5...7 lb-in) (1794-TB3TK, -TB3G, -TB3GK, -TB2, -TB32, -TB3, IEC temp code T4 (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S,
torque -TB3K, -TB3T) -TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK)
0.3...0.6 Nm (2.6...5.3 lb-in) (1794-TBKD)
1.4 Nm (12 lb-in) (1794-TBN, -TBNF, -TBNFK, -TBNK) T6 (1794-TB2)
Dimensions, 94 x 94 x 69 mm (HxWxD) (3.7 x 3.7 x 2.7 in.)
Supply voltage FLEXBUS: 5V DC, 640 mA approx. (with module installed in terminal base)
range (max) I/O Terminals: 2A max
V/COM Terminals: 125V DC/AC, 50/60Hz, 10A (1794-TB3SK, -TB3TK,-TB2, -TB3, (1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
-TB3K, -TB3S, -TB3TK, -TB3TS) Grounding Guidelines, publication 1770-4.1.
V/COM Terminals: 31.2V DC/AC, 50/60Hz, 10A (1794-TB3GSK, -TB3G, -TB3GS,
-TB3GK, -TB32, -TB32S
V/COM Terminals: 250V DC/AC, 50/60Hz, 10A (1794-TBN, -TBNF, -TBNFK, Environmental
-TBNK)
Attribute Value
1794-TBKD only
FLEXBUS: 5V DC, 640 mA Operating IEC 60068-2-1 (Test Ad, Operating Cold),
Terminal Block: 120V AC, 50/60Hz, 10A temperature IEC 60068-2-2 (Test Bd, Operating Dry Heat),
Disconnecting Switch: 3A, 20mΩ IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F) (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK,
ATTENTION -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3SK, -TB3TS, -TB3TSK,
A disconnecting switch does not shut off the current. Make or break a circuit TB32, -TB32S, -TBN, -TBNK)
only under no-load conditions.
0…55 °C (32…131 °F) (1794-TBKD)
Isolation voltage Capable of 250V (continuous) maximum, Basic Insulation Type, Field Wiring -20…55 °C (-4…131 °F) (1794-TBNF, -TBNFK, -TB2)
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TBN, -TBNF, Non-operating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
-TBNFK, -TBNK) temperature IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
Capable of 125V (continuous) maximum, Basic Insulation Type, Field Wiring IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Terminals to FLEXBUS, or the lesser of the installed module (1794-TB3SK, Shock):
-TB3TK, -TB3TK, -TB3TSK, -TB2, -TB3, -TB3K, -TB3S, -TB3TS) -40…85 °C (-40…185 °F)
Capable of 50V (continuous) maximum, Basic Insulation Type, Field Wiring -20…85 °C (-4…185 °F) (1794-TBKD)
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TB3G,
-TB3GS, -TB3GK, -TB3GSK, -TB32, -TB32S) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
2500V DC/sec, Field Wiring Terminals to FLEXBUS.
220V DC/sec, Field Wiring Terminals to Functional Ground. (1794-TBKD) Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Voltage rating See Working Voltage and Isolation Voltage Ratings for nominal values Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g (Except for 1794-TBKD)
Enclosure type None (open-style)
rating Non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
shock 50 g (Except for 1794-TBKD)

Working Voltage and Isolation Voltage Ratings


Terminal Base 1794- 24V 120V 230V Isolation Voltage Certifications (when product is marked)(1)
TBN, TBNK, TBNF, TBNFK AC/DC AC/DC AC/DC Dependent upon installed
module - refer to individual Attribute Value
TB2, TB3, TB3K, TB3S, TB3SK AC/DC AC/DC
installation instructions for
TB3T, TB3TS, TB3TK, TB3TSK AC/DC AC/DC UL (1794-TB2)
your specific module. UL Listed Industrial Control Equipment. See UL File E65584.
TB3G, TB3GK, TB3GS, TB3GSK AC/DC
c-UL-us (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3TS,
TB32, TB32S AC/DC -TB3SK, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)
TBKD DC AC UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
and Canada. See UL File E194810.

General (1794 -TBKD, -TBNF, -TBNFK )


UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
Attribute Value
CSA (1794-TB2, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK, -TB3SK, -TB3TSK, -TBN,
Wire size 0.34... 3.3 mm² (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F -TBNK, -TB3G, -TB3GK, -TB3GS, -TB3GSK)
) or greater, 1.2 mm (3/64 in.) insulation max. Strip Length: 5-6 mm (0.20...0.24 in.) CSA Certified Process Control Equipment. See CSA File LR54689C.
(1794-TB3SK, -TB3GSK, -TB3TSK, -TB3GK, -TB3GS, -TB32S, -TB3, -TB3K, -TB3S, CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D
Hazardous Locations. See CSA File LR69960C.
-TB3TS, -TBN, -TBNF, -TBNFK, -TBNK)
(1794-TBNF, -TBNFK)
0.34…2.1 mm² (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F CSA Certified Process Control Equipment. See CSA File LR54689C.
) or greater, 1.2 mm (3/64 in.) insulation max (1794-TBKD)
CE European Union 2004/108/EC EMC Directive, compliant with:
0.21... 1.3 mm² (24…16 AWG) stranded copper wire rated at 75 °C (167 °F ) or EN 61326-1; Meas./Control/Lab., Industrial Requirements
greater, 1.2 mm (3/64 in.) insulation max (1794-TB3TK, -TB3G, -TB2, -TB32) EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Wiring Established by installed module EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
category(1) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)

Publication 1794-IN092E-EN-P - November 2009


Certifications (when product is marked)(1)

C-Tick Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Ex (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, TB3TK,
-TB3SK, -TB3TSK, -TBN, -TBNK)
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)

(1794-TB2)
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T6 X)
EN 60079-0; General Requirements (Zone 2)

TÜV (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK,
-TB3SK, -TB3TSK, -TBNF, -TBNFK)
TÜV Certified for Functional Safety:
Capable of SIL 2

(1) See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and
other certification details.

A 94
(3.7)
23
59 35 (0.9)
35 (2.3) (1.4)
(1.4)
Mounting Dimensions
21 (0.83)
mm 50 94
(2.0) (3.7)
(in.) 80
(3.2)
80
87 (3.2)
(3.4)
28
(1.2)

68 94 94
(2.7) (3.7) (3.7) B
Adapter (1794-ASB shown) Terminal Base (1794-TB3S shown) Terminal Base (1794-TB3 shown) C
87 x 68 x 69 94 x 94 x 69 94 x 94 x 69
(3.4 x 2.7 x 2.7) (3.7 x 3.7 x 2.7) (3.7 x 3.7 x 2.7)
Secure DIN rail approximately every 200 mm (7.87 in.).
Measure here for
Maintain at least 25.4 (1.0) air space around your FLEX I/O system installation. vertical mounting
position with
A = Mounting hole dimensions for optional mounting kit. adapter up.
B = DIN rail.
C = Operating temperature 25.4 (1.0) below each module when mounted in any position Measure here for horizontal position.
must not exceed 55 ˚C (131 ˚F).

Publication 1794-IN092E-EN-P - November 2009 6 PN-64237