433 All
433 All
433 All
R410A
R410A
High
HighPerformance
Performance
Air-Conditioning
Air-Conditioning
2018
2018
VRF
VRF
inverter
inverter
multi-system
multi-system
Air-Conditioners
Air-Conditioners
50Hz
50Hz
18KX01E
18KX01E
EU/EEA
EU/EEA
High Performance
Air-Conditioning
2018
2
Line Up R410A
NEW
model
Heat recovery system
RC-EX3
Simple use with advanced setting Remote control
Contents
Introduction 4~29
Outdoor units 30~75
Micro KXZ, Micro model 30~33
KXZ Lite 34 . 35
Refresh series 70 . 71
EEV-KIT 1 16 . 117
3
R410A
NEW
4
Specific cases of VRF system installation from
Mitsubishi Heavy Industries Thermal Systems
5
R410A
The KXZ product lineup has been extended to offer solutions delivering up to 60 horsepower (60HP) when using a combination
of 3 outdoor units. Furthermore with the addition of the Hi-COP series, installation options have been greatly increased.
Up to 48HP Up to 60HP
KXZXE1 (Hi-COP)
8-36HP
Capacity Range
Capacity 4HP 5HP 6HP 8HP 10HP 12HP 14HP 16HP 17HP 18HP 20HP
Model Code : kW 11.2 14 15.5 22.4 28 33.5 40.0 45.0 47.5 50.0 56.0
BTU / h 38,200 47,800 52,900 76,400 95,500 114,300 136,500 153,500 162,100 170,600 191,100
Capacity 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
Model Code : kW 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0
BTU / h 209,800 228,600 250,800 273,000 290,000 307,100 324,100 341,200 361,700 382,100
Capacity 42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
Model Code : kW 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0
BTU / h 409,400 426,500 443,600 460,600 486,200 494,700 511,800 532,200 552,700 573,200
6
Product Line Up
<Outdoor units>
NEW
11.2kW 14.0kW 15.5kW
4HP 5HP 6HP
FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1
FDC112KXZES1 FDC140KXZES1 FDC155KXZES1
model
Standard model
28.0kW 33.5kW 40.0kW 45.0kW 47.5kW 50.0kW 56.0kW
10HP 12HP 14HP 16HP 17HP 18HP 20HP
FDC280KXZE1 FDC335KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1
FDC280,335 FDC400~560
61.5kW 67.0kW 73.5kW 80.0kW 85.0kW 90.0kW 95.0kW 100.0kW 106.0kW 112.0kW
22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
FDC615KXZE1 FDC670KXZE1 FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
FDC280KXZE1 FDC335KXZE1 FDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1
FDC615,670 FDC335KXZE1 FDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1
FDC735 FDC800~1120
120.0kW 125.0kW 130.5kW 135.0kW 142.5kW 145.0kW 150.0kW 156.0kW 162.0kW 168.0kW
42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1
FDC400KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1
FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1
FDC1200~1680 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1 FDC560KXZE1
Hi-COP model
22.4kW 28.0kW 33.5kW
8HP 10HP 12HP
FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1
7
R410A
<Indoor units> A range of 17 types of exposed or concealed indoor units available in a wide range of capacities (total 93 indoor models).
The best solution of indoor units for all applications is available from our full lineup.
1.5kW 2.2kW 2.8kW 3.6kW
<0.5HP> <0.8HP> <1HP> <1.25HP>
NEW (4~6HP)
model (8~12HP)
KXZ Lite
Standard model KXZE1
Ceiling
2way FDTW FDTW28KXE6F
Cassette
1way FDTS
High FDU
Static Pressure
Low/Middle FDUM FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F
Duct Static Pressure
Connected Low Static
Pressure(thin) FDUT FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E
Floor
With Casing FDFL
Standing
Without Casing FDFU FDFU28KXE6F
OA Processing unit FDU-F • FDU-F series are not connectable to Micro model (4~6HP), KXZ
8
4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW
<1.6HP> <2HP> <2.5HP> <3.2HP> <4HP> <5HP> <6HP> <8HP> <10HP>
FDTC45KXE6F FDTC56KXE6F
FDTS45KXE6F FDTS71KXE6F
FDFW45KXE6F FDFW56KXE6F
FDFL71KXE6F
800 1000
SAF800E7 SAF1000E7
SAF-DX800E6 SAF-DX1000E6
9
R410A
MODEL
4.50
4.30
4.10
3.90
3.70
3.50
224 280 335 400 450 475 500 560 615 670 735 800 850 900 950 1000 1060 1120 1200 1250 1300 1350 1425 1450 1500 1560 1620 1680
MODEL
10~60HP (KXZ)
DC Fan Motor
Double tube
10
Variable Temperature and Capacity Control (KXZ)
34%
designed by Mitsubishi Heavy Industries Thermal Systems.
• A new feature to all our KXZ ranges which provides
up to 34%* energy savings in both cooling and
heating mode.
• VTCC is a function specifically designed to maximise ENERGY SAVINGS*
energy savings in partial load conditions throughout
all seasons.
*34% energy savings are based on comparison with a KXZ standard model with
VTCC vs. a KXZ standard model both under partial load condition.
Normal operation (in the cooling mode) Energy saving operation (in the cooling mode)
Room temperature Room temperature
Check temp erature difference
Compressor
Compressor
VTCC adjusts the target pressure of the refrigerant cycle in the For example, in partial load conditions where you have low cooling
outdoor unit automatically according to the demand of the indoor and heating requirements, VTCC reduces the compressor frequency
units in partial load conditions. and controls the actuators in the outdoor unit.
These smooth adjustments ensure an optimal capacity usage of the Overall with the VTCC functionality you will always have an
indoor units as well as maximised energy savings. Ultimately this additional energy saving of up to 34% (depending on configuration
also increases comfort for the user. and usage of system) in low cooling and heating load requirements.
Multi-discharge port
By optimizing pressure
adjustment in decompression,
the compressor realizes higher
efficiency.
Discharge port
11
R410A
Output
The newly designed high performance CPU
Winding Motor
enables high precision optimization for
compressor speed, which leads to concentrated
winding motor use.
Our product achieves high output and better
energy saving effects and Conventional Distributed
in particular improves seasonal efficiency rating. Winding Motor
Improved Seasonal
Efficiency rating
Compressor Speed
* Applied for KXZE1:10/12/17/18/20HP, KXZXE1:8HP & KXZ Lite:8/10HP
advanced features.
• Smooth operation from low speed to high speed
• Smooth Sine Voltage Wave form are attained
• Energy efficiency is further improved in low speed range
Operation period
DC Fan Motor
Long-chorded 3 propeller fan with serration Employment of DC fan motor has enabled to realize an excellent
Fan blade design adapted from Mitsubishi Heavy Industries efficiency of approximate 60% higher than previous models.
aerospace division - with serrated edges that deliver increased
air volume with less power input. Rotor(Squirrel Cage made of conductor)
Stator (coil) Rotor(made of permanent magnet)
12
Oil level control capability Capacity control (KXZ)
Our proprietary technology of adjusting oil level for combination of Capacity control can be set by peak cut function with RC-EX3
two or three outdoor units has realized leveled operation rate, keeping for better energy saving.
performance of the units and ensuring long life of the system. Five-step capacity control is available. (100-80-60-40-0%)
(kW)
PEAK CUT
AM PM
8 9 10 11 12 13 14 15 16 17 18 19
Oil-equalizing pipe
DC Fan Motor
Compact & High efficiency
DC Fan motor
Compact & High efficiency
Inverter Control
Compact & Vector Inverter Control system
Downsized accumulator
3D-Scroll Compressor(12HP)
Previous Micro
13
R410A
2. Design Flexibility
Indoor unit capacity connection HP Capacity connection
HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34
Numbers 24 29 34 39 41 43 48 53 58 63 69 73 78 80
Standard KXZ
HP 36 38 40 42 44 46 48 50 52 54 56 58 60
Numbers 80 80 80 80 80 80 80 80 80 80 80 80 80
* When connecting 9 units or more, set the total capacity as follows : 5HP : 110% or less, 6HP : 100% or less.
-20 -10 0 10 20 30 40 50
Control Systems
All series offer wide variation of control system and provide the best solution.
14
Long Pipe Length 10~60HP(KXZ)
Piping length has extended max height difference between indoor units up to 18m and enables us to put indoor units on extra three floors.
The furthest indoor unit: 160m or total length: 1000m contributes to system design flexibility.
1,400
Transportation in an
8~12HP (Micro) elevator made for six
persons
H1,675 x W1,080 x D480
850
Easy
transportation
800
1350mm
1350mm
1350mm
Blue Fin
Due to application of blue coated fins for the heat
exchanger of new outdoor unit, corrosion resistance
Blue
Fin
has been improved compared to current models.
15
R410A
56 56
71 56
71
28
28
16
3. Serviceability
Easy Service Check Operation (10~60HP)
Quick and easy access to service parts by separation of Closing of Service valve, crossing connection of refrigerant
compartments. piping and electrical wiring, proper operation of EEV (Electrical
Expansion Valve) can be checked automatically in cooling
operation. This check operation can be done at 0~43ºC outdoor
temperature and 10~32ºC indoor temperature by use of
outdoor unit dip switch. The check should be done in one
refrigerant system. It takes 15~30 minutes and avoids frequent
failure by preventing careless mistakes during installation.
Blower dip switch
compartment
Mechanical
compartment
Monitoring Function
All series includes feature to assist with servicing and trouble shooting.
Various data can be monitored through 3-digit or 6-digit display on the outdoor unit PCB.
Detailed fault diagnosis and operation history memory via Equipped with RS232C
7-segment display. for connection directly to
your PC monitoring and
service tasks made
simple with our service
software (“Mente PC”).
All series
4~6HP 8~60HP
8 . 10HP(KXZ Lite)
Automatically produced test-run report Operation data storage during servicing
6
Indoor unit
Outdoor unit
USB
Superlink Line SL checker KXZ (3 layer) KXZ Lite (2 layer)
monitor interface SL checker
17
R410A
Back-up Operation
In the event that one unit has a failure, the system will keep operating In the event that one compressor has a failure, the unit will keep
with the other good units. operating with the another good compressor.
Combination of two or three outdoor units KXZ : 18 & 20HP
Keeping Compressor
operation failed
Inverter
Unit failed This operation is an emergency measure for a limited time and
a necessary repair should be done as soon as possible.
Improved freedom of piping layout Wire insertion holes for fall prevention External static pressure
Front 4 Rear
1 2 Right
3
Down
current
KXZ Lite External static pressure is
available up to 35 Pa.
135mm
90mm
50mm 90mm
2
4 1
2 1
3
5
2
Located at the same level for easy Attached as a standard for easy Decreasing number of screws from 5 to 2,
transport and transfer. maintenance. installation & service speed is improved.
18
Easy Selection Tool E-solution
E-Solution is a design software tool which includes specification details of the latest KXZ VRF systems. By using E-Solution
this simplifies the process and enables engineers to select the most cost-effective and energy efficient mix of indoor units,
outdoor units, pipework and controls.
Engineers must register and download the E-solution software to ensure they are automatically sent updates as they become
available and this can be done by simply visiting www.mhiae.com/support-downloads/e-solution
Furthermore it is also developed to cater for the design of two and three pipe systems and specifies appropriate models and
sizes. It also generates wiring diagrams and engineering drawings which can be exported to AutoCAD or saved in PDF format.
This flexibility enables engineers to print select design information and comprehensive operation and maintenance manuals for
presentations to clients.
Engineers can also incorporate design information into their own
formats and documents for personalised proposals.
19
R410A
Quiet operation
※It can also prevent user from being directly blown by hot drafts
in heating mode.
20
New Generation FDK
Left Right
FDK71,90KXZE1
Down
20
21
R410A
(in Japan)
Flap
Draft Prevention
Panel Wing
temperature
Draft Prevention Panel provides a comfortable airflow without any draft feeling. Whether cooling or
heating a room, the remote control can be used to instantly suppress any warm or cool drafts. This
accurately assists how air flow is directed out of the indoor unit.
22
Motion sensor User
3 Step Control
New motion sensor (option) detects human activity.
Power Energy saving control is achieved by shift set
Control temperature according to detected amount of activity.
eco
in cooling
26℃
ON
comfort
24℃
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24(hour)
comfort
in heating
22℃
ON
eco
20℃
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24(hour)
+2℃
Low
Cooling
+2℃ +2℃ - -
Power Human Heating
+2℃
Control ※1 activity -2℃
High
Cooling
-2℃ -2℃ - -
Heating
-2℃
Auto Off ※2 ● ● ● ● ●
※1 Set temperature is revised maximum 2℃ at Cooling/Heating mode by detecting heat volume movement.
※2 Absence for 1 hour ⇒ Operation stops ( Stand-by ) More 12 hours absence ⇒ Operation stops completely
23
R410A
Builder Maintenance
New shape of slit is suitable to install the unit with more Flexible positioning is available, which helps adjusting the
flexibility, according to many kinds of suspending bolt direction of panel according to lines or pattern on the
pitch on site. ceiling.
Any rectangular or
Compatible with both square
squared pitch of or rectangular bolt pitch
suspending bolts are
available with this slit.
1 The control box and bell mouth 2 Easy access to impeller New shape of path gives easy wiring work for installation.
can be removed together. and fan motor.
Control box
Bell mouth
It is possible to loose and slide open the cover without When unit is installed
remove of the screws. with hook between
This prevents the cover from falling and damaging to washers, this stopper
stuffs on site. helps to install the unit
safely, without adjusting
washer.
Separate the provisional Washer on
washer securing material. the upper side
e sd own
Slid hang
ver
The co
Loosen Loosen
Slide
24
Builder Maintenance
For smooth
and easy
working
Hook of soft material helps to The direction of the strap hook part has
remove the filter without dust been changed from longitudinal to lateral.
spreading. Furthermore, a barb has been added to
the hook pin to prevent the strap from
coming off.
Easy to hook
but
not easy to loose
Before After
Press the filter tab to the outside
and remove the filter.
3 Drain-up-lift increases up to 850 mm (previous:700mm) 4 New port to check drain water flow
The drain can be lifted up to 850 mm from the ceiling surface. A water supply port has been provided in
the piping lid for easier testing of the drain
water flow.
(The port is usually sealed with a rubber cap.)
700 Up to
mm 850 mm
Flexible hose
5 Re-use of packages during construction work 6 More flexible outlet for ducting
Package material (carton) help to protect the unit from Both φ125 and φ200 (oval shaped) are available.
unexpected welding spatter or coming dust to the new
unit.
φ125 φ125
φ200
φ200
25
R410A
Bright screen
RC-EX1A
RC-EX3
26
New functions
Function Switch
The function switch allows you to select and set two functions that you desire
among the six available functions shown.
These functions can be used by simply pressing the button after they
are set, allowing you to use your preferable functions immediately.
Function switch Function switch
15
min 1 High Power Mode (F1) (F2)
High Power Mode achieve excessive cooling / heating capacity for 15 minutes to quickly adjust the room temperature to a comfortable level.
3 Quiet Mode
Outdoor unit starts to operate quietly by activating this mode. The time of this mode can be set in conjunction with Indoor Silent Timer.
5 Favorite Mode
Operation mode, set temperature, fan speed and air flow direction are automatically adjusted to the programmed favorite setting.
Now
6 Filter Sign
Announces the due time for cleaning the air filter.
【e.g.】 【e.g.】
【operation mode】
Operation mode Operation mode
cooling
Dry
Direction Fan speed Direction Fan speed
F1 Auto F2
Fan
Heating
Set temp Set temp
No.3?
This is No.3!
27
R410A
1
2
i
H!
Backup Control
Control restricted to two indoor units (two groups)
Keep back up all the time! Maintains users' comfort! Energy saving and longer life!
If one of the two indoor units malfunctions When the control system detects either of By operating two indoor units alternately,
and stops its operation, the other starts two units is operating with overload, the their chronological changes are equalized.
backup operation so that users' comfort other unit cover the capacity. (The alternate operation cycle can be
will not be compromised. specified in a range from 10 hours to 990
1 1
hours in increments of 10 hours.)
1
Remote control Remote control
Remote control
2 2
3 3
CNT (New)
External Input External Output 2 Output - Operation
- Heating
CNT (1-6) - Compressor ON (thermo-ON)
CNTA (1-2) 3 Output - Inspection
Input On/Off - Cooling (defrosting)
- Fan operation
Permission/Prohibition
Cooling/Heating 4 Output - Fan operation with Phi or Hi
- Fan operation with Me or Lo
Emergency Stop - Defrosting (oil return in heating operation)
Set temp. shift - Ventilation
Forced thermo-off 5 Output - Heater ON
Newly added IU operation stop - Free cooling
Silent mode
Newly added - IU overload alarm
28
Silent mode control Indoor unit capacity display
The Outdoor unit is controlled with priority on quietness. Capacities of Indoor units connected to the RC-EX3 are
Silent mode control must be set to the F1 or F2 switch. displayed.
User can start/stop the silent mode control with a single
tap of a button.
Timer START
Polish/Japanese/Chinese.
140
“Error”
Function added
1) High power
2) Energy-saving
3) ON/OFF Timer by clock
4) Child lock
5) Silent mode control for Outdoor unit
6) Home leave mode
29
R410A
Outdoor units
Heat pump systems
4, 5, 6HP (11.2kW~15.5kW)
Model No. Nominal Cooling Capacity
Blue
NEW
FDC112KXZEN1 11.2kW (220V)
Fin
FDC140KXZEN1 14.0kW (220V)
FDC155KXZEN1 15.5kW (220V)
FDC112KXZES1 11.2kW (380V)
FDC140KXZES1 14.0kW (380V)
FDC155KXZES1 15.5kW (380V)
Specifications
Item Model FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1 FDC112KXZES1 FDC140KXZES1 FDC155KXZES1
Nominal horse power 4HP 5HP 6HP 4HP 5HP 6HP
Power source 1 Phase 220-240V, 50Hz 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 23 23.3 13.5
Cooling 11.2 14.0 15.5 11.2 14.0 15.5
Nominal capacity kW
Heating 11.2 14.0 15.5 11.2 14.0 15.5
Power Cooling 2.52 3.96 5.20 2.52 3.96 5.20
Electrical characteristics kW
consumption Heating 2.57 3.66 4.28 2.57 3.66 4.28
Exterior dimensions HxWxD mm 845x970x370
Net weight kg 85 87
Sound pressure level Cooling/Heating dB(A) 52/55 53/57 54/57 52/55 53/57 54/57
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 5.0 / 10.44
Liquid line ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line ø15.88(5/8")
Capacity connection % 80~150
Number of connectable indoor units 8 10 * 10 * 8 10 * 10 *
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
30
Refrigerant piping
Outdoor unit (HP) 4 5 6 Branch pipes Header pipe
DIS-22-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G
Dimensions
All measurements in mm.
I II III
L1 Open Open 500
L2 300 5 Open
L4 5 5 5
31
R410A
between 10
indoor units:
From the first Indoor unit 18m 0
* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
Specifications
Item Model FDC224KXE6 FDC280KXE6 FDC335KXE6
Nominal horse power 8HP 10HP 12HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 20 23
Cooling 22.4 28.0 33.5
Nominal capacity kW
Heating 25.0 31.5 37.5
Power Cooling 5.60 8.09 9.82
Electrical characteristics kW
consumption Heating 6.03 8.21 10.12
Exterior dimensions HxWxD mm 1675x1080x480
Net weight kg 221 224
Sound pressure level Cooling/Heating dB(A) 58/58 59/60 61/61
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8") ø25.4(1") [ø22.22(7/8")]
Capacity connection % 50~150
Number of connectable indoor units 22 24 24
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
32
Refrigerant piping
Outdoor unit (HP) 8 10 12 Branch pipes Header pipe
Dimensions
All measurements in mm.
Notes:
I II III
*1 Figure in ( ) shows the value applicable
L1 Open Open 1500(500)*1 when the flex flow adaptor is installed.
*2 Under the setting condition as specified
L2 300 5 Open
in ( ), it is necessary to secure 250 mm
L3 300 300 300 for the dimension L4 when replacing the
51(48)*
33
R410A
Cooling
20
Max height +15.5ºC
Indoor unit difference 10
between
indoor units: 0
From the first Indoor unit 18m Heating
branch to the -10
Specifications
Item Model FDC224KXZPE1 FDC280KXZPE1
Nominal horse power 8HP 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 21 22
Cooling 22.4 28.0
Nominal capacity kW
Heating 22.4 28.0
Power Cooling 5.6 7.87
Electrical characteristics kW
consumption Heating 4.8 6.47
Exterior dimensions HxWxD mm 1505x970x370
Net weight kg 165
Sound pressure level Cooling/Heating dB(A) 59/60 60/63
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 8.9 / 18.583
Liquid line ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8")
Capacity connection % 50~120
Number of connectable indoor units 8 8
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
34
Refrigerant piping
Outdoor unit (HP) 8 10 Branch pipes Header pipe
Dimensions
All measurements in mm.
Notes:
I II III
*1 At the time of the installation at ( )
L1 Open Open 500 dimension,
L2 300 5 Open Secure space of 250mm in lateral
(L4) by unit movement at the time
L3 150 300 150 of the exchange work of the
L4 250 (5)*1 250 (5)*1 250 (5)*1 compressor.
35
R410A
*1 The difference between the longest and the shortest indoor unit piping
-15ºC
-20
from the first branch must be within 40m. (MAX85m)
-20ºC
*2 In case of height difference up to 70m, please contact your dealer.
Height difference up to 90m is possible with High Head series.
Please refer to page66.
Specifications
Item Model FDC280KXZE1 FDC335KXZE1
Nominal horse power 10HP 12HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 21.2
Cooling 28.0 33.5
Nominal capacity kW
Heating 31.5 37.5
Power Cooling 7.24 8.96
Electrical characteristics kW
consumption Heating 7.28 9.04
Exterior dimensions HxWxD mm 1690x1350x720
Net weight kg 272
Sound pressure level Cooling/Heating dB(A) 55/57 61/58
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.0 / 22.968
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø22.22(7/8") ø25.4(1") [ø22.22(7/8")]
Capacity connection % 50~130
Number of connectable indoor units 24 29
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
36
Dimensions
All measurements in mm.
D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) L3 100 100
Installation example
When more than one unit is installed Dimensions 1 2
Wall height
H3
L1 500 Open
L3 L2 10(30) 200
L3 100 300
Wall height
Wall height
L2 L5 L6 L4
H2
H4
L4 10(30) Open
L1 (Unit front side) L5 10(30) 400
Wall height
H1
L6 10(30) 400
H1 1500 Open
H2 No limit No limit
H3 1000 No limit
H4 No limit Open
37
R410A
*1 The difference between the longest and the shortest indoor unit piping -20
-15ºC
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer.
-20ºC
Specifications
Item Model FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1
Nominal horse power 14HP 16HP 17HP 18HP 20HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5 8
Max current A 32 42.4
Cooling 40.0 45.0 47.5 50.0 56.0
Nominal capacity kW
Heating 45.0 50.0 53.0 56.0 63.0
Power Cooling 10.96 13.98 13.98 13.97 16.62
Electrical characteristics kW
consumption Heating 10.69 12.50 13.00 13.49 15.95
Exterior dimensions HxWxD mm 2048x1350x720
Net weight kg 317 370
Sound pressure level Cooling/Heating dB(A) 60/62 61/62 61/61 61/62 64/66
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø25.4(1") [ø28.58(1 1/8")] ø28.58(1 1/8")
Capacity connection % 50~130
Number of connectable indoor units 34 39 41 43 48
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
38
Dimensions
All measurements in mm.
D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) L3 100 100
39
R410A
40
Heat pump combination systems
26, 28, 30, 32, 34, 36, 38, 40HP (73.5kW~112.0kW)
Model No. Nominal Cooling Capacity
FDC735KXZE1 (FDC335+FDC400) 73.5kW Blue
FDC800KXZE1 (FDC400+FDC400) 80.0kW Fin
FDC850KXZE1 (FDC400+FDC450) 85.0kW
FDC900KXZE1 (FDC450+FDC450) 90.0kW
FDC950KXZE1 (FDC475+FDC475) 95.0kW
FDC1000KXZE1 (FDC500+FDC500) 100.0kW
FDC1060KXZE1 (FDC500+FDC560) 106.0kW
FDC1120KXZE1 (FDC560+FDC560) 112.0kW
*1 The difference between the longest and the shortest indoor unit piping -10
Heating
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer. -15ºC
Height difference up to 90m is possible with High Head series. -20
Please refer to page66. -20ºC
Item Model FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
335KXZE1 400KXZE1 400KXZE1 450KXZE1 475KXZE1 500KXZE1 500KXZE1 560KXZE1
Combination (FDC)
400KXZE1 400KXZE1 450KXZE1 450KXZE1 475KXZE1 500KXZE1 560KXZE1 560KXZE1
Nominal horse power 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 10 16
Max current A 53.2 64 84.8
Cooling 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0
Nominal capacity kW
Heating 82.5 90.0 95.0 100.0 106.0 112.0 119.0 126.0
Power Cooling 19.92 21.92 24.94 27.96 27.96 27.94 30.59 33.24
Electrical characteristics kW
consumption Heating 19.73 21.38 23.19 25.00 26.00 26.98 29.44 31.90
Exterior dimensions HxWxD mm 2048x2700x720
Net weight kg 589 634 740
Refrigerant charge R410A kg 11.0+11.5 11.5x2
Liquid line ø15.88(5/8") ø19.05(3/4")
Refrigerant piping size mm(in)
Gas line ø31.75(1 1/4") [ø34.92(1 3/8")] ø38.1(1 1/2") [ø34.92(1 3/8")]
Capacity connection % 50~130
Number of connectable indoor units 63 69 73 78 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
41
R410A
160m -15ºC
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. (MAX85m)
-20ºC
* Height difference
2 In case of height difference up to 70m, please contact your dealer.
up to 90m is possible with High Head series.
Please refer to page66.
42
Heat pump combination systems
50, 52, 54, 56, 58, 60HP (142.5kW~168.0kW)
160m -15ºC
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. (MAX85m)
-20ºC
* Height difference
2 In case of height difference up to 70m, please contact your dealer.
up to 90m is possible with High Head series.
Please refer to page66.
43
R410A
Hi-COP series
8~36HP(22.4kW~100.0kW)
Model No. Nominal Cooling Capacity Model No. Nominal Cooling Capacity
FDC224KXZXE1 22.4kW FDC450KXZXE1 (FDC224+FDC224) 45.0kW
FDC280KXZXE1 28.0kW FDC500KXZXE1 (FDC224+FDC280) 50.0kW
FDC335KXZXE1 33.5kW FDC560KXZXE1 (FDC280+FDC280) 56.0kW
FDC615KXZXE1 (FDC280+FDC335) 61.5kW
FDC670KXZXE1 (FDC335+FDC335) 67.0kW
FDC735KXZXE1 (FDC224+FDC224+FDC280) 73.5kW
FDC800KXZXE1 (FDC224+FDC280+FDC280) 80.0kW
High
Efficiency FDC850KXZXE1 (FDC280+FDC280+FDC280) 85.0kW
FDC900KXZXE1 (FDC280+FDC280+FDC335) 90.0kW
FDC950KXZXE1 (FDC280+FDC335+FDC335) 95.0kW
High
FDC1000KXZXE1 (FDC335+FDC335+FDC335) 100.0kW
Higher
Energy
Economy
Saving
Blue
Blue Fin
Fin
kW capacity connection
22.4~45.0 200%
50.0~100.0 160%
44
Specifications
Item Model FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1
Nominal horse power 8HP 10HP 12HP
Power source 3Phase 380-415V, 50Hz
Starting current A 5
Max current A 21.2 32
Cooling 22.4 28.0 33.5
Nominal capacity kW
Heating 25.0 31.5 37.5
Power Cooling 4.98 6.95 8.68
Electrical characteristics kW
consumption Heating 5.56 6.83 8.39
Exterior dimensions HxWxD mm 1690x1350x720 2048x1350x720
Net weight kg 280 325
Sound pressure level Cooling / Heating dB(A) 56/57 56/56 62/57
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.0 / 22.968 11.5 / 24.012
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8") ø25.4(1")[ø22.22(7/8")]
Capacity connection % 200
Number of connectable indoor units 29 37 44
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
45
R410A
Dimensions
All measurements in mm.
FDC224KXZXE1
D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100
K Refrigerant oil equalization piping connection pipe ø9.52 (Flare) H3 1000 No limit
46
FDC280KXZXE1, 335KXZXE1
B Refrigerant liquid piping connection pipe ø9.52 (Flare) ø12.7 (Flare) L1 500 Open
D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100
47
R410A
48
New features
- Improve energy efficiency
- Expand Line-up up to 60HP
Up to 48HP Up to 60HP
120.0kW 125.0kW 130.0kW 135.0kW 142.5kW 145.0kW 150.0kW 156.0kW 162.0kW 168.0kW
42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
FDC1200KXZRE1 FDC1250KXZRE1 FDC1300KXZRE1 FDC1350KXZRE1 FDC1425KXZRE1 FDC1450KXZRE1 FDC1500KXZRE1 FDC1560KXZRE1 FDC1620KXZRE1 FDC1680KXZRE1
FDC400KXZRE1 FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1
FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1
FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1 FDC560KXZRE1
FDC1200~1680
49
R410A
Cooling 8
7
PFD
6
Cooling
EER/COP
5
50
4 4HP
PFD
Heating 3
2
1
PFD
0
(ex.) Indoor ambient 23.5℃DB/17.5℃
0 Heating
Outdoor ambient 16℃DB/12℃WB
4HP
(Condition) FDC224KXZRE1
PFD
50% Indoor unit in cooling (27℃DB/19℃)
Max COP > 9.0 50% Indoor unit in heating (20℃DB/14.5℃)
Outdoor ambient 16℃DB/12℃WB
High Efficiency
The below graphs highlight the improved efficiencies between the previous models compared to the KXZR standard and Hi-COP models.
Previous model
Comparison of EER in Cooling Mode KXZR
EER KXZR Hi-COP
4.50
4.30
4.10
3.90
3.70
3.50
3.30
3.10
2.90
2.70
2.50
224 280 335 400 450 475 500 560 615 670
MODEL
50
Improved Features
New Heating Solution - Continuous Heating Capacity Control (CHCC) -
New defrosting control achieves more capacity than that of previous model in low ambient temperature condition.
Target pressure is controlled automatically before capacity drops, which makes longer period of heating operation and shorter defrosting time.
(*1) Patent is now under being applied. (*2) This control will be activated in specific condition. Please refer to the technical manual in detail.
In previous model, when high demand for heating and low cooling * The numeric values are provisional.
demand are required at the same time in low ambient temperature Blown air temperature in the cooled room
condition, pressure control is adjusted to keep more heating capacity
Previous model During simultaneous cooling and heating operation
than good enough cooling capacity.
KXZRE1 at an outside temperature of -5°C.
New adopted heat exchanger and pressure control in KXZR series,
has improved its capacity for both good enough heating and cooling
capacity at the same time. (*)
Design Flexibility
Indoor unit capacity connection Connectable indoor units
HP KXZR HP KXZRX • In case that capacity connection is more than 130%, Up to 91 indoor units can be connected to the
additional charge of refrigerant is required on site.
8~16 200% 16 200% largest capacity outdoor unit, with a range of 17
• In case of 8-34HP of the systems, if one or more types of exposed or concealed indoor unit, in
indoor units of FDK, FDFL,FDFU and/or FDFW series
17~34 160% 18~34 160% are connected to the system, the total connecting several capacities, a choice of 91 indoor units is
36~60 130% 36 130% capacity of indoor units should not exceed 130%. available.
-20 -10 0 10 20 30 40 50
51
R410A
Specifications
Item Model FDC224KXZRE1 FDC280KXZRE1 FDC335KXZRE1
Nominal horse power 8HP 10HP 12HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 16.0 20.0 21.2
Cooling 22.4 28.0 33.5
Nominal capacity kW
Heating 22.4 28.0 33.5
Power Cooling 5.15 7.38 9.64
Electrical characteristics kW
consumption Heating 4.62 6.19 8.12
Exterior dimensions HxWxD mm 1690x1350x720
Net weight kg 289
Sound pressure level Cooling/Heating dB(A) 55/57 61/58
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø9.52(3/8”) ø12.7(1/2”)
Refrigerant piping size Suction Gas line mm(in) ø19.05(3/4”) ø22.22(7/8”) ø25.4(1”) [ø22.22(7/8")]
Discharge Gas line ø15.88(5/8”) ø19.05(3/4”)
Capacity connection % 50~200
Number of connectable indoor units 29 37 44
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
52
Dimensions
All measurements in mm.
Installation example
Dimensions 1 2
L1 500 Open
L2 10(30) 10(30)
L3 100 100
L4 10(30) Open
H1 1500 Open
H2 No limit No limit
H3 1000 No limit
H4 No limit Open
53
R410A
Cooling
Max height 20
+15.5ºC
Indoor unit difference
between 10
indoor units:
Indoor unit 18m 0
* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
Specifications
Item Model FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC615KXZRE1 FDC670KXZRE1
Nominal horse power 14HP 16HP 17HP 18HP 20HP 22HP 24HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5 8
Max current A 30.0 32.0 40.4 41.0 41.6 42.0 42.4
Cooling 40.0 45.0 47.5 50.0 56.0 61.5 67.0
Nominal capacity kW
Heating 40.0 45.0 47.5 50.0 56.0 61.5 63.0
Power Cooling 11.55 14.45 14.82 15.19 18.31 21.35 25.51
Electrical characteristics kW
consumption Heating 9.76 11.38 11.58 12.7 14.33 16.15 17.47
Exterior dimensions HxWxD mm 2048x1350x720
Net weight kg 357 410
Sound pressure level Cooling/Heating dB(A) 60/62 61/62 64/65 65/66
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø12.7(1/2”)
Refrigerant piping size Suction Gas line mm(in) ø25.4(1”)[ø28.58(1 1/8”)] ø28.58(1 1/8”)
Discharge Gas line ø22.22(7/8”) ø25.4(1”) [ø22.22(7/8")]
Capacity connection % 50~200 50~160
Number of connectable indoor units 53 60 50 53 59 65 71
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
54
Dimensions
All measurements in mm.
Installation example
Dimensions 1 2
L1 500 Open
L2 10(30) 10(30)
L3 100 100
L4 10(30) Open
H1 1500 Open
H2 No limit No limit
H3 1000 No limit
H4 No limit Open
55
R410A
* The difference between the longest and the shortest indoor unit piping Heating
from the first branch must be within 40m. (MAX85m) -10
-15ºC
-20
-20ºC
56
Heat recovery 3-pipe combination systems
34, 36, 38, 40HP (95.0kW – 112.0kW)
- for simultaneous heating and cooling
Model No. Nominal Cooling Capacity Blue
FDC950KXZRE1 (FDC475+FDC475) 95.0kW Fin
FDC1000KXZRE1 (FDC500+FDC500) 100.0kW
FDC1060KXZRE1 (FDC500+FDC560) 106.0kW
FDC1120KXZRE1 (FDC560+FDC560) 112.0kW
* The difference between the longest and the shortest indoor unit piping Heating
from the first branch must be within 40m. (MAX85m) -10
-15ºC
-20
-20ºC
Specifications
*Exterior dimension : Please refer to page 55.
Item Model FDC950KXZRE1 FDC1000KXZRE1 FDC1060KXZRE1 FDC1120KXZRE1
475KXZRE1 500KXZRE1 500KXZRE1 560KXZRE1
Combination (FDC)
475KXZRE1 500KXZRE1 560KXZRE1 560KXZRE1
Nominal horse power 34HP 36HP 38HP 40HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 16
Max current A 80.8 82.0 82.6 83.2
Cooling 95.0 100.0 106.0 112.0
Nominal capacity kW
Heating 95.0 100.0 106.0 112.0
Power Cooling 29.6 30.4 33.5 36.6
Electrical characteristics consumption kW
Heating 23.2 24.3 26.5 28.7
Exterior dimensions HxWxD mm 2048x2700x720
Net weight kg 820
Refrigerant charge R410A kg 11.5x2
Liquid line ø15.88(5/8”) ø19.05(3/4”)
Refrigerant piping size Suction Gas line mm(in) ø31.75(1 1/4”)[ø34.92(1 3/8”)] ø38.1(1 1/2”)[ø34.92(1 3/8”)]
Discharge Gas line ø28.58(1 1/8”) ø31.75(1 1/4”)[ø28.58(1 1/8”)]
Capacity connection % 50~160 50~130
Number of connectable indoor units 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
57
R410A
* The difference between the longest and the shortest indoor unit piping -20
-20ºC
from the first branch must be within 40m. (MAX85m)
Specifications
*Exterior dimension : Please refer to page 55.
Item Model FDC1200KXZRE1 FDC1250KXZRE1 FDC1300KXZRE1 FDC1350KXZRE1 FDC1425KXZRE1
400KXZRE1 400KXZRE1 400KXZRE1 450KXZRE1 475KXZRE1
Combination (FDC) 400KXZRE1 400KXZRE1 450KXZRE1 450KXZRE1 475KXZRE1
400KXZRE1 450KXZRE1 450KXZRE1 450KXZRE1 475KXZRE1
Nominal horse power 42HP 44HP 46HP 48HP 50HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 15 24
Max current A 90.0 92.0 94.0 96.0 121.2
Cooling 120.0 125.0 130.0 135.0 142.5
Nominal capacity kW
Heating 120.0 125.0 130.0 135.0 142.5
Power Cooling 34.65 37.55 40.45 43.35 44.46
Electrical characteristics consumption kW
Heating 29.28 30.90 32.52 34.14 34.74
Exterior dimensions HxWxD mm 2048x4050x720
Net weight kg 1071 1230
Refrigerant charge R410A kg 11.5x3
Liquid line ø19.05(3/4”)
Refrigerant piping size Suction Gas line mm(in) ø38.1(1 1/2”)[ø34.92(1 3/8”)]
Discharge Gas line ø31.75(1 1/4”)[ø28.58(1 1/8”)]
Capacity connection % 50~130
Number of connectable indoor units 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
58
Heat recovery 3-pipe combination systems
52, 54, 56, 58, 60HP (145.0kW – 168.0kW)
- for simultaneous heating and cooling Blue
Fin
Model No. Nominal Cooling Capacity
FDC1450KXZRE1 (FDC475+FDC475+FDC500) 145.0kW
FDC1500KXZRE1 (FDC500+FDC500+FDC500) 150.0kW
FDC1560KXZRE1 (FDC500+FDC500+FDC560) 156.0kW
FDC1620KXZRE1 (FDC500+FDC560+FD560) 162.0kW
FDC1680KXZRE1 (FDC560+FDC560+FDC560) 168.0kW
* The difference between the longest and the shortest indoor unit piping -20
-20ºC
from the first branch must be within 40m. (MAX85m)
Specifications
*Exterior dimension : Please refer to page 55.
Item Model FDC1450KXZRE1 FDC1500KXZRE1 FDC1560KXZRE1 FDC1620KXZRE1 FDC1680KXZRE1
475KXZRE1 500KXZRE1 500KXZRE1 500KXZRE1 560KXZRE1
Combination (FDC) 475KXZRE1 500KXZRE1 500KXZRE1 560KXZRE1 560KXZRE1
500KXZRE1 500KXZRE1 560KXZRE1 560KXZRE1 560KXZRE1
Nominal horse power 52HP 54HP 56HP 58HP 60HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 24
Max current A 121.8 123.0 123.6 124.2 124.8
Cooling 145.0 150.0 156.0 162.0 168.0
Nominal capacity kW
Heating 145.0 150.0 156.0 162.0 168.0
Power Cooling 44.83 45.57 48.69 51.81 54.93
Electrical characteristics consumption kW
Heating 35.33 36.51 38.67 40.83 42.99
Exterior dimensions HxWxD mm 2048x4050x720
Net weight kg 1230
Refrigerant charge R410A kg 11.5x3
Liquid line ø19.05(3/4”)
Refrigerant piping size Suction Gas line mm(in) ø38.1(1 1/2”)[ø34.92(1 3/8”)]
Discharge Gas line ø31.75(1 1/4”)[ø28.58(1 1/8”)]
Capacity connection % 50~130
Number of connectable indoor units 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
59
R410A
160m -15ºC
-20
* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
-20ºC
60
Heat recovery 3-pipe Hi-COP combination systems
26, 28, 30, 32, 34, 36HP (73.5kW~100.0kW)
- for simultaneous heating and cooling
Model No. Nominal Cooling Capacity
FDC735KXZRXE1 (FDC224+FDC224+FDC280) 73.5kW Blue
FDC800KXZRXE1 (FDC224+FDC280+FDC280) 80.0kW Fin
FDC850KXZRXE1 (FDC280+FDC280+FDC280) 85.0kW
FDC900KXZRXE1 (FDC280+FDC280+FDC335) 90.0kW
FDC950KXZRXE1 (FDC280+FDC335+FDC335) 95.0kW
FDC1000KXZRXE1(FDC335+FDC335+FDC335) 100.0kW
160m -15ºC
-20
* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
-20ºC
61
R410A
Design flexibility Branch control Total downstream capacity *Connectable indoor units
PFD1124-E less than 112 1-5
Groups of indoor units can be connected up to a total
PFD1804-E 112 or more but less than 180 1-8
capacity 44.8kW to a single PFD with branch piping and
all units in that group will operate in the same mode PFD2804-E 180 or more but less than 280 1-10
only (cooling or heating). PFD1124X4-E less than 371(less than 112 per branch) Up to 20
*Refer to Data Book for details
We also have introduced the 4-way PFD control
PFD1124X4-E which can connect up to four indoor
units with individual control - simultaneous cooling or
heating. PFD1124-E PFD1124-E PFD1124X4-E PFD1124-E
90 56 36 56 36 90
28 90
• The remote control setting (as individual indoor unit on-off, temperature • In case of the mode changeover from cooling to heating and from cooling
setting other than cooling/heating mode control) is possible with one to heating, by the use of only the indoor units and PFD box combination,
remote control connected to each indoor unit, while at the same time, the mode changeover sound was reduced. All this made possible without
Center Control (SC-SL1N/2NA/4-AE) can be used together with the turning off the compressor and at the same time without the reduction of
individual remote control. capacity.
• It is necessary to set the central control to use this function.
Please refer to the Installation Manual for details. • The risk of refrigerant leakage was reduced by changing piping connection
at the PFD box to brazing method.
Same mode (Heating or Cooling)
Individual on-off, temperature setting
• By the use of optional PFD box extension cable that has a connector at
ends, makes it possible to further separate the indoor unit and PFD box.
PFD
This will enable the PFD box to be located away from the indoor unit and
Heating help reduce the influence of sound caused by PFD box and refrigerant flow.
Heating
PFD
Heating
Cooling
SC-SL1N/2NA/4-AE
Easy installation central control Power cable 240v AC
New PFD design means the The PFD is connected to the
relay kit
connection of the indoor unit liquid Outdoor discharge gas pipe gas pipe indoor unit by 3 core signal wire PFD Indoor
unit
pipe is made directly to the liquid via a relay kit (supplied) to be unit
62
Dimensions PFD1124-E
All measurements in mm.
PFD1804-E
PFD2804-E
PFD1124X4-E
63
R410A
Features Applicable to
1. High efficiency (EER/COP) 1. High-rise Building 2. Glass-exterior facade Building
• Energy saving Reduction of operation cost! - 50m <FDC> , -100m <FDCH> - Possible to hide KXZW units
- 100m or higher in height <FDCW> and to keep fine sight
2. Compact design
• Easy transportation and installation
• Elevator carrying
3. BMS (Building Management System)
• Can use the same BMS as air-cooled KX
• Available to large-scale and fine control
4. Serviceability & Maintenance
• Service and maintenance of main parts
can be done from the front side only 8, 10, 12HP 16, 18, 20, 22, 24HP 26, 28, 30, 32, 34, 36HP
• Useful service tools (Mente-PC, SL-Checker etc.)
Specifications
Item Model FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE1
- - - 224KXZWE1 224KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1
Combination (FDC)
- - - 224KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1 335KXZWE1
Nominal horse power 8HP 10HP 12HP 16HP 18HP 20HP 22HP 24HP
Power source 3 Phase 380-415V, 50Hz
Cooling 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0
Nominal capacity kW
Heating 25.0 31.5 37.5 50.0 56.0 63.0 69.0 75.0
Cooling 4.23 5.75 8.13 8.49 9.83 11.5 13.7 16.3
Power consumption kW
Heating 4.24 5.10 6.30 8.47 9.27 10.2 11.4 12.6
EER Cooling 5.3 4.9 4.1 5.3 5.1 4.9 4.5 4.1
COP Heating 5.9 6.2 6.0 5.9 6.0 6.2 6.1 6.0
Exterior dimensions HxWxD mm 1100x780x550 (1100x780x550)x2
Sound pressure level dB(A) 48 50 52 50 52 53 54 55
Net weight kg 185 185x2
64
Heat source units on every floor Heat source units in the machine room
- New building projects - - Renovation projects -
Total piping length : 510m Total piping length : 510m
To the Height
first branch: difference
Heat source
max 130m 50m
unit
Dimensions
All measurements in mm.
VIEW A
A
Piping size
Mark Content FDC-KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 Connection method
Dimension
A High/low gas line Refer to piping size 224,280 335 High/low gas line ø19.05 ø22.22 ø25.4 Flange
B - Not to use. C1 142 139 Liquid line ø9.52 ø9.52 ø12.7
Flare
C Liquid line C2 322 316 Oil equalization line ø9.52 ø9.52 ø9.52
Refer to piping size
D Oil equalization line
F Water inlet R1 1/4 Installation
example 1
G Water outlet R1 1/4 Dimension
H Drain outlet Rp 1/2,2places L1 600 or more
J Power source intake ø35 L2 20 or more
K Signal wiring intake ø35 L3 500 or more
L Anchor bolt hole ø18,4places L4 20 or more
L5 300 or more
65
R410A
FDCH335KXE6-K
FDCH400KXE6
FDCH450KXE6 FDCH504~680KXE6
*1 Select the total pipe length depending on the connectable capacity of indoor units.
Outdoor units' capacity A = Max. connectable capacity of indoor units (%)
Connectable
*2 The difference between the longest and shortest indoor unit piping
capacity
400~450 150%
504~960 140% from the first branch must be within 40m.
1010~1360 130%
*3 In case of less than 50m, the High Head models can not be applied.
A%
In case Indoor unit is higher than outdoor unit, the High Head models
can not be applied.
130%
100%
66
Specifications
Item Model FDCH400KXE6 FDCH450KXE6 FDCH504KXE6 FDCH560KXE6 FDCH615KXE6 FDCH680KXE6
Nominal horse power 14HP 16HP 18HP 20HP 22HP 24HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 8
Max current A 47
Cooling kW 40.0 45.0 50.4 56.0 61.5 68.0
Nominal capacity
Heating kW 45.0 50.0 56.5 63.0 69.0 73.0
Cooling kW 11.27 12.97 14.73 16.79 20.37 24.98
Electrical characteristics Power consumption
Heating kW 11.73 13.10 15.12 16.79 18.48 19.08
Exterior dimensions HxWxD mm 1690x1350x720 2048x1350x720
Net weight kg 336 358 377
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Sound pressure level Cooling / Heating dB(A) 59.5 / 59.5 62.5 / 62.5 61.5 / 61.5 63.0 / 63.0 64.5 / 64.5 65.0 / 65.0
Liquid line ø12.7(1/2") ø15.88(5/8")
Refrigerant piping size mm(in)
Gas line ø25.4(1") [ø28.58(1 1/8")] ø28.58(1 1/8") ø28.58(1 1/8")
Capacity connection % 50~150 50~140
Number of connectable indoor units 36 40 36 40 44 49
67
R410A
Dimensions
All measurements in mm.
D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (Bottom) L3 100 100
Wall height
L2 L5 L6 L4
are covered with half-blanks. Please cut off a half-blank with
H2
H4
L3 100 300
nippers in using these ports.
(5) Use a ø88 port for refrigerant pipe connection. L1 (Unit front side) L4 10 Open
(6) Anchor holes marked “L J” (four holes for M10) are for a Wall height
H1 L5 0 400
renewal installation.
(7) The oil-equalising pipe K should be used when outdoor units L6 0 400
are used in combination. (For 14,16HP only) H1 1500 No limit
H2 No limit No limit
H3 1000 No limit
H4 No limit No limit
68
Dimensions
All measurements in mm.
D Power supply entry hole ø50 (right . left . front), long hole 40 x 80(Bottom) L3 100 100
Notes:
(1) The unit must be fixed with anchor bolts.
(2) Leave a 2m or larger space above the unit.
(3) The unit name plate is attached on the lower right corner of
the front panel.
(4) The ports for refrigerant pipe and power cable penetrations
are covered with half-blanks. Please cut off a half-blank with
nippers in using these ports.
(5) Use a ø88 port for refrigerant pipe connection.
(6) Anchor holes marked “L J” (four holes for M10) are for a
renewal installation.
(7) The oil-equalising pipe K should be used when outdoor units
are used in combination.
69
R410A
Refresh series
8, 10HP(22.4kW • 28.0kW)
If replacing a used unit with a new one, these units can reuse existing piping. Blue
Fin
Model No. Nominal Cooling Capacity
FDCR224KXE6 22.4kW
FDCR280KXE6 28.0kW
<Option>
FDCR-KIT-E : Service valve kit
• Applies to a wide range of pipe sizes (R22, R407C, R410A standard size).
• Meets to a short period of renewal installation.
• Savings on replacement expenses such as scrapping waste material or procuring new pipe.
• Possible to replace the existing unit with a new larger capacity unit.
• Possible to replace plural systems with one system.
For example:Existing 5HP x 2units can be replaced with a new 10HP x 1unit.
5HP x 2 10HP x 1
Max height 30
Furthest -20
-20ºC
indoor unit: 160m
Specifications
Item Model FDCR224KXE6 FDCR280KXE6
Nominal horse power 8HP 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 20
Cooling 22.4 28.0
Nominal capacity kW
Heating 25.0 31.5
Power Cooling 5.60 8.09
Electrical characteristics consumption kW
Heating 6.03 8.21
Exterior dimensions HxWxD mm 1675x1080x480
Net weight kg 224
Sound pressure level Cooling/Heating dB(A) 58/58 59/60
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø9.52(3/8")~ø15.88(5/8")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4")~ø25.4(1") ø22.22(7/8")~ø28.58(11/8")
Capacity connection % 50~130
Number of connectable indoor units 13 16
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
70
Advanced refresh function
When the existing unit is operable
The existing pipe can be reused by cooling operation only.
Pipe refresh kit and Service valve kit are not required.
1.Implement cooling operation of all indoor units for more than 30 minutes.
2.Implement pump-down after cooling operation.
3.Recover refrigerant and remove the existing outdoor unit and indoor unit.
and Pipe refresh kit is very easy by use of flexible heat exchanger
Dimensions
All measurements in mm. Service valve kit
71
R410A
Refrigerant piping
Installation of Interconnecting Pipework
KXZ/KX6 equipment is manufactured to the highest standards of quality and reliability. It is imperative the method of installation and the materials used are
also to high standards, to ensure trouble free operation and long term reliability.
The interconnecting pipework must be installed by a competent and trained engineer. Refrigeration quality copper tube must be used, soft copper coils or
half-hard straight lengths. The refrigeration quality tube must be soft drawn seamless high grade copper pipe. The copper tube must be selected taking into
account the higher operating pressures of R410A refrigerant, and that high pressures will occur throughout the system because of the reverse cycle operation.
All pipework material used should be EN12735 European standard.
The supplied branch pipe kits, must be used to make connections to indoor units, and the supplied manifold kits must be used to make connections between
outdoor units (where applicable); it is not permitted to use standard fittings such as elbows, tees etc. The branch pipes shall be installed in accordance with
the manufacturer’s instructions, allowing unrestricted flow of refrigerant, and in accordance with European standard E378.
All brazed joints shall be made with dry nitrogen purge to ensure the prevention of oxidisation to the internal surface of the copper pipes.
The ingress of moisture, dirt and any other contaminants to the interior of the copper pipes, and air conditioning units, must be prevented during the
installation procedure.
After the installation of pipework, prior to the connection of the outdoor units, and sealing of insulation joints, the pipework must be pressure tested for
leakage, using dry nitrogen.
Additional Refrigerant
Additional R410A refrigerant only shall be used, and must be charged by weight only, using electronic scales. The amount of additional refrigerant must be
accurately calculated from the manufacturer’s data, based on the length and diameter of each section of the liquid refrigerant pipework of the system.
Standard (Outdoor unit side branching pipe – Indoor unit side first branching pipe) Branch pipes Header pipe
If the longest distance (measured between the outdoor unit and the farthest indoor unit) is
90m or longer (actual length), please change the main pipe size according to the table below.
Outdoor Main pipe size (normal) Pipe size for an actual length of 90m or longer mm inch
unit Gas pipe Liquid pipe Gas pipe Liquid pipe ø9.52 3/8"
280 ø22.22 × t 1.0 ø9.52 × t 0.8 ø12.7 1/2"
335 ø25.4 (ø22.22) × t 1.0 ø25.4 (ø22.22) × t 1.0 DIS-22-1G/DIS-180-1G HEAD6-180-1G
ø12.7 × t 0.8 ø15.88 5/8"
400 ø25.4 (ø28.58) × t 1.0 ø28.58 × t 1.0 Combination outdoor unit manifold
450 ø19.05 3/4"
475 ø12.7 × t 0.8 ø22.22 7/8"
500 ø31.8 × t 1.1
ø28.58 × t 1.0 (ø28.58 × t 1.0) ø15.88 × t 1.0 ø25.4 1"
560
615
670 mm inch
735 ø28.58 11/8"
800 DIS-371-1G/DIS-540-3 DOS-2A-3
ø31.8 × t 1.1 ø31.8 11/4" DOS-3A-3
850 (ø34.92 × t 1.2) ø15.88 × t 1.0 ø19.05 × t 1.0
900 ø34.92 13/8"
950 ø38.1 11/2"
Horizontally
1000
1060 ø44.5 13/4" Good
Floor
1120 ø50.8 2"
1200 ø38.1 × t 1.35
1250 (ø34.92 × t 1.2)
1300 No Good
ø38.1 × t 1.35
1350 (ø34.92 × t 1.2) ø22.22 × t 1.0
1425 ø19.05 × t 1.0 Vertically
Floor
1450
1500
1560 Floor
No
1620
1680
Please use C1220T-1/2H for ø19.05 or larger pipes. Floor
HEAD8-371-2
72
Combination outdoor unit piping examples:
112 112 90 90 90 140 140 140 112 112 90 90 90 140 140 140
Outdoor unit's branch piping set Indoor unit's first branch piping set
Outdoor unit Branch piping set Total capacity of Header set
Branch piping set
For two units (for 615~1120) DOS-2A-3 indoor units Model Branches
For three units (for 1200~1680) DOS-3A-3 ~179 DIS-22-1G HEAD4-22-1G Max 4 branches
180~370 DIS-180-1G HEAD6-180-1G Max 6 branches
371~539 DIS-371-1G HEAD8-371-2 Max 8 branches
540~ DIS-540-3 HEAD8-540-3 Max 8 branches
1680
Please use C1220T-1/2H for ø19.05 or larger pipes. Pipe sizes applicable to European installations. Floor
No
90 56 36 56 36 90 56 36 56 36 56 36 90 140
28 90 28 90 28 90
73
R410A
Oil equalisation
pipe(1)
Outdoor unit's branch piping set
Outdoor unit branch PFD1124-E PFD1124X4-E PFD2804-E PFD1124-E
piping set (DOS-2A-3-R) Outdoor unit Branch piping set
2 units (for 735~1120) DOS-2A-3-R
3 units (for 1200~1680) DOS-3A-3-R
90 56 36 140 90 90
Indoor unit's first branch piping set
28 90 Total capacity of indoor units Branch piping set
~179 DIS-22-1-RG
180~370 DIS-180-1-RG
371~539 DIS-371-2-RG
540~ DIS-540-2-RG
For Down Stream of PFD box
Total capacity of indoor units Branch piping set
Oil equalisation ~179 DIS-22-1G
pipe(1)
180~370 DIS-180-1G
Outdoor unit branch PFD1124X4-E PFD1124X4-E PFD1124-E PFD1124-E 371~539 DIS-371-1G
piping set (DOS-2A-3-R)
540~ DIS-540-3
56 36 56 56 36 90 90
28 90 28 90
Power wiring
Cables can be laid through the front, right, left or bottom of the outdoor unit casing.
Separate power supplies should be used for the outdoor unit (3Phase) and the indoor units (1Phase).
Only control wiring is connected from outdoor to indoor unit.
Outdoor unit power supply: 3 Phase 4 wiring 380-415V Distributed, separate power supply system
B B
Circuit breaker
for cabling
Indoor unit
Earth leakage breaker
D
R R R R R R Remote control unit
74
Electrical wiring – control wiring
1. The control wiring is 5 Volt DC, (1) When one outdoor unit is used
non-polarised, two wire connection
notated as ‘A1’ and ‘B1’. This ‘AB’ wiring Outdoor signal line A1 B1
Indoor and outdoor signal lines do not have a polarity.
Any of the connections in the following illustration can be made.
connects outdoor unit to indoor unit and terminal block
indoor unit to indoor unit.
A1 A A1 A
2. This wiring must be a 2-core shielded
cable size 0.75mm2 or 1.25mm2. Indoor signal line A B A B A B B1 B B1 B
0.75mm2 1.25mm2 terminal block
~1000m YES YES
1000~1500m YES NO
(2) When plural outdoor units are used
3. We recommend the both ends of the
shield of the cable are connected to Outdoor unit Outdoor unit Outdoor unit Outdoor unit Network connector
ground (earth) at all the indoor units and
outdoor units.
A1·B1 A2·B2 A1·B1 A2·B2 A1·B1 A2·B2 A1·B1 A2·B2
4. When plural outdoor units are used,
.Connect the signal cable between indoor
and outdoor units and the signal cable Indoor unit Indoor unit
between outdoor units belonging to the A A
same refrigerant line to A1 and B1. B B
.Connect the signal line between outdoor
units on different refrigerant lines to A2 Refrigerant pipe
Indoor unit Indoor unit
and B2.
A A
5. For current specification of 2-core (AB) B B
wiring, please consult your dealer. Signal line
The maximum number of indoor units that can be connected in a system is 128 and it is possible to configure
outdoor units and/or indoor units as an outdoor or indoor unit group connected with each other with two wires.
(3) The signal lines can also be connected using the method shown below.
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
75
R410A
Indoor units
Benefits Summary When using RC-EX3 (Remote control), functions with symbol
However, for RC-E5 (Remote control), functions with
are available.
are not available.
Inverter control technology functions at high efficiency with smooth operation from high speed to low speed.
Inverter technology A smooth sine voltage wave is attained.
Since the capacity is controlled automatically based on the outdoor temperature, energy can be saved without
Economy
Set temperature auto return The temperature automatically returns to the previously set temperature.
Automatic operation The air conditioner automatically selects from among heating, cooling operations.
Silent mode
Comfort
The unit can be set to prioritise the period of time it operates at a lower noise level.
When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and the fan to
Draught prevention low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired.
The high power operation adjusts the room temperature quickly to a pleasant level by increasing the operation capacity.
Hi power mode The high power operation continues for 15 minutes at maximum and returns to the normal operation automatically.
Flap control system Motion range (upper and lower limit positions) of the flap at each air outlet can be set at a desired range
individually.
Flap moves up and down continuously. The Up/Down flap swing can be fixed at the preferred operation angle.
Ceiling stain prevention The shape & angled louver redirects the air current away from the ceiling reducing ceiling stains.
Automatic fan speed The micro-computer automatically adjusts the airflow effectively to follow the changes of return air temperature.
Set the time period from start to stop of operation. The selectable range of setting time is from 30 to 240 minutes
Sleep timer
(at 10-minute intervals).
Timer
Capacity control can be set by using peak cut function on RC-EX3 for better energy saving.
Peak-cut timer Five-step capacity control is available.
The function switch allows you to select and set two functions among six available functions.
Function Switch
(Cannot be used when a centralied control remote is connected)
Favorite setting Operation mode, set temperature, fan speed and air flow direction automatically adjust to the programmed favorite setting.
This is operable when connecting duct type indoor units equipped with the external static pressure adjustment function.
Static pressure adjustment It will adjust the airflow accordingly based on the connected duct static pressure.
Convenient
Remote control You can select wired remote controls, wireless remote controls or central remote controls.
Select the language Set the language to be displayed on the remote control.
Air filter Removes airborne dust particles through the air filter to ensure a steady supply of clean air.
Filter sign Announces the due time for cleaning of the air filter.
In the case that the air conditioner malfunctions, an internal microcomputer automatically runs a self-diagnosis.
Self-diagnosis
Others
76
FDT FDTC FDTW FDTS FDTQ FDU FDUM FDUT FDUH FDK FDE FDFW FDFL FDFU FDU-F
(71only)
Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option
procure procure
locally Option Option Option locally
Option
Option
*1 *2
1 : Except 224 • 280 2 : Except 1800 • 2400
* *
77
R410A
FDT
RC-EX3 RC-E5 RCH-E3
Wireless
Model No.
FDT28KXZE1
FDT36KXZE1
FDT45KXZE1
FDT56KXZE1 RCN-T-5AW-E2
FDT71KXZE1
FDT90KXZE1
FDT112KXZE1
FDT140KXZE1
FDT160KXZE1
Draft Prevention Panel prevents cold / hot draft being blown Advanced airflow control technology cultivated through
directly on the user. aircraft development.
It is possible to set Draft Prevention Panel for each air outlet.
Draft prevention
Draft prevention panel working
panel not working Cool
Dry
78
Panel select pattern (Option)
8 patterns of panel are avilable. Installation position of Wireless kit and Motion sensor kit
Flexible hose
Remove corner lid. Remove drain cap cover and check the condition. Clean up the area around
It is necessary to clean-up, firstly remove the rubber the drain pump port.
stopper to drain water out and secondly remove the
drain cap.
79
R410A
Specifications
Item Model FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1 FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1
Nominal cooling capacity kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Nominal heating capacity kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.03-0.03 0.04-0.04 0.08-0.08 0.13-0.13 0.14-0.14
consumption Heating kW 0.02-0.02 0.03-0.03 0.04-0.04 0.08-0.08 0.13-0.13 0.14-0.14
Sound power level dB(A) 49 50 55 62 65 66
Sound pressure level dB(A) Hi:33 Me:30 Lo:28 Hi:33 Me:31 Lo:29 Hi:35 Me:32 Lo:28 Hi:38 Me:36 Lo:31 Hi:39 Me:37 Lo:31 Hi:42 Me:39 Lo:32 Hi:42 Me:39 Lo:33
Exterior dimensions
mm Unit:236x840x840 Panel:35x950x950 Unit:298x840x840 Panel:35x950x950
HxWxD
Net weight kg Unit:20 Standard Panel:5 Unit:21.5 Standard Panel:5 Unit:25 Standard Panel:5
Air flow m3/min Hi:14 Me:12 Lo:10 Hi:15 Me:13 Lo:10 Hi:16 Me:13 Lo:11 Hi:17 Me:14 Lo:12 Hi:25 Me:22 Lo:15 Hi:26 Me:23 Lo:17 Hi:28 Me:25 Lo:18 Hi:29 Me:26 Lo:19
Outside air intake Possible
Panel T-PSA-5AW-E, T-PSAE-5AW-E
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-T-5AW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDT28/36 37dB(A), FDT45/56 38dB(A), FDT71 47dB(A), FDT90/112/140/160 49dB(A). Air flow: FDT28 15m 3/min, FDT36 16m3/min, FDT45 17m3/min, FDT56 20m3/min, FDT71
28m3/min, FDT90 37m3/min,, FDT112/140/160 38m3/min.
80
Dimensions
All measurements in mm.
FDT28KXZE1
36KXZE1
45KXZE1
56KXZE1
71KXZE1
FDT90KXZE1
112KXZE1
140KXZE1
160KXZE1
81
R410A
According to room temperature conditions, four directions of air flow Selection of flap position is
can be controlled by individual flap as preferred. possible. Individual flaps can be Upper
position
Individual flap control is available even after installation. set at different angles.
Movable
range
*The wireless remote control is not applicable to
the Individual flap control system.
Lower
position
Taking OA (Outside Air) into inside Quiet operation (Sound pressure level in the Lo mode.)
OA Spacer TC-OAS-E (option) The industry's lowest sound pressure level:25dB(A) of FDTC15KXE6F was
Joint Duct TC-OAD-E (option) achieved by Optimizing fan speed and distributor size.
Utilizing OA spacer which comes as optional equipment, outside air
can be taken inside. dB(A)
40 dB(A)40 dB(A)40
39
dB
300mm 25 25
dB dB
OA Spacer 20 20 20
Specifications
Item Model FDTC15KXE6F FDTC22KXE6F FDTC28KXE6F FDTC36KXE6F FDTC45KXE6F FDTC56KXE6F
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.3
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.03-0.03 0.05-0.05
consumption Heating kW 0.02-0.02 0.03-0.03 0.05-0.05
Sound power level dB(A) 56 58 60
Sound pressure Cooling Hi:32 Me:28 Lo:25 Hi:35 Me:33 Lo:30 Hi:38 Me:36 Lo:31 Hi:40 Me:37 Lo:31 Hi:45 Me:39 Lo:31
dB(A)
level Heating Hi:32 Me:28 Lo:25 Hi:35 Me:33 Lo:32 Hi:38 Me:36 Lo:34 Hi:40 Me:37 Lo:34 Hi:45 Me:39 Lo:34
Exterior dimensions
mm Unit:248x570x570 Panel:35x700x700
HxWxD
Net weight kg Unit:14 Panel:3.5 Unit:15 Panel:3.5
Cooling Hi:7 Me:5.5 Lo:4.5 Hi:9.5 Me:8.5 Lo:7 Hi:10 Me:9 Lo:7 Hi:11 Me:9 Lo:7 Hi:13 Me:10 Lo:7
Air flow m3/min
Heating Hi:7 Me:5.5 Lo:4.5 Hi:9.5 Me:8.5 Lo:8 Hi:10 Me:9 Lo:8 Hi:11 Me:9 Lo:8 Hi:13 Me:10 Lo:8
Outside air intake Possible with OA Spacer TC-OAS-E & Joint Duct TC-OAD-E
Panel TC-PSA-25W-E
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-TC-24W-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDTC15 34dB(A), FDTC22/28 44dB(A), FDTC36 46dB(A), FDTC45 48dB(A), FDTC56 49dB(A). Air flow: FDTC15 8m 3/min, FDTC22/28 12m3/min, FDTC36 13m3/min, FDTC45
15m3/min, FDTC56 16m3/min.
82
Dimensions
All measurements in mm.
FDTC15KXE6F,
22KXE6F,
28KXE6F
VP25(O.D.32)
Ultra slim design at just 248mm above the ceiling Condensate drain pump included as standard
83
R410A
FDTW FDTW28~71
FDTW90~140
Specifications
Item Model FDTW28KXE6F FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F FDTW90KXE6F FDTW112KXE6F FDTW140KXE6F
Nominal cooling capacity kW 2.8 4.5 5.6 7.1 9.0 11.2 14.0
Nominal heating capacity kW 3.2 5.0 6.3 8.0 10.0 12.5 16.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.09-0.09 0.10-0.10 0.14-0.14 0.19-0.19
consumption Heating kW 0.09-0.09 0.10-0.10 0.14-0.14 0.19-0.19
Sound power level dB(A) 58 65
Sound pressure level dB(A) Hi:38 Me:34 Lo:31 Hi:45 Me:41 Lo:37
Exterior dimensions
mm Unit:325x820x620 Panel:20x1120x680 Unit:325x1535x620 Panel:20x1835x680
HxWxD
Net weight kg Unit:20 Panel:8.5 Unit:21 Panel:8.5 Unit:23 Panel:8.5 Unit:35 Panel:13
Air flow m3/min Hi:12 Me:10 Lo:9 Hi:27 Me:23 Lo:20
Outside air intake Possible
Panel TW-PSA-26W-E TW-PSA-46W-E
Air filter, Q’ty Pocket Plastic net x2 (Washable) Pocket Plastic net x3 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-TW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDTW28/45/56/71 42dB(A), FDTW90/112/140 48dB(A). Air flow: FDTW28/45/56/71 14.5m3/min, FDTW90/112/140 31m3/min.
84
Dimensions
All measurements in mm.
650
102
650
102
85
R410A
FDTS
Wired Wireless
Model No.
FDTS45KXE6F RC-EX3 RC-E5
FDTS71KXE6F
RCH-E3
RCN-TS-E2
Two directions of air flow can be controlled individually by Indoor unit size (W:1,150 x
flap control system. D:565) brings easy installation for
1,200 x 600 ceiling and Panel size 220mm
(1,250 x 650) is suitable for 1,200
x 600 ceiling. Height is the
industry's lowest height level
220mm and weight is 27/28kg
only.
Specifications
Item Model FDTS45KXE6F FDTS71KXE6F
Nominal cooling capacity kW 4.5 7.1
Nominal heating capacity kW 5.0 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.04-0.04 0.09-0.09
consumption Heating kW 0.04-0.04 0.09-0.09
Sound power level dB(A) 60 61
Sound pressure level dB(A) Hi:40 Me:38 Lo:35 Hi:46 Me:41 Lo:36
Exterior dimensions
mm Unit:220x1150x565 Panel:35x1250x650
HxWxD
Net weight kg Unit:27 Panel:5 Unit:28 Panel:5
Air flow m3/min Hi:12 Me:11 Lo:9.5 Hi:15 Me:12 Lo:9.5
Outside air intake Possible
Panel TS-PSA-3AW-E
Air filter, Q’ty Pocket Plastic net x2 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-TS-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDTS45 42dB(A), FDTS71 49dB(A). Air flow: FDTS45 13m3/min, FDTS71 17m3/min.
86
Dimensions
All measurements in mm.
87
R410A
Wireless
RCN-KIT4-E2
Compact design
Fresh air
Holes for opening
tapping screws for ducting
(Knock out)
Max.Drain up
250
295~325
285
63
600 or less
35
210
Optional wide panel shown for solid ceiling Condensate drain pump Ultra slim design at just 250mm above the ceiling
included as standard
Specifications
Item Model FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6F
Panel Name Direct blow panel Duct panel Direct blow panel Duct panel Direct blow panel Duct panel
Panel mode (Option) TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER
Nominal cooling capacity kW 2.2 2.8 3.6
Nominal heating capacity kW 2.5 3.2 4.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.07 0.05-0.07 0.05-0.07
consumption Heating kW 0.05-0.07 0.05-0.07 0.05-0.07
Sound power level dB(A) 60
Sound pressure level dB(A) Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33
Exterior dimensions Unit 250x570x570 250x570x570 250x570x570
HxWxD mm
Panel 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650
Net weight kg Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3
Air flow m3/min Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5
Outside air intake Possible
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDTQ22/38/36 45dB(A). Air flow: FDTQ22/38/36 8m3/min.
88
Dimensions
All measurements in mm.
model a b c d model a b c
89
R410A
FDU
Wired
Model No.
FDU45KXE6F
RC-EX3 RC-E5 RCH-E3
FDU56KXE6F
FDU71KXE6F Wireless
FDU90KXE6F
FDU112KXE6F
FDU140KXE6F
FDU160KXE6F RCN-KIT4-E2
Previous
90
Dimensions
All measurements in mm.
FDU45KXE6F, 56KXE6F
FDU71KXE6F, 90KXE6F
91
R410A
FDU
Wired
Model No.
FDU224KXZE1 RC-EX3 RC-E5 RCH-E3
FDU280KXZE1
Wireless
RCN-KIT4-E2
You can set External Static Pressure (E.S.P.) by Thanks to use of DC fan motor, fan steps increase from
method of manual setting on remote control. two to four and quiet operation is achieved.
Indoor unit will control fan-speed to keep rated air (Sound pressure level 45dB(A) in the Lo mode).
flow volume at each fan speed setting. You can set
required E.S.P. by wired remote
control that calculated with the RC-E5
set air flow rate and pressure E.S.P. button
loss of the duct connected. External Static Pressure (E.S.P.) can Improvement of the serviceability
be set by E.S.P. button.
Fan unit (impeller and motor) can
Pipe
Duct Duct Longer Duct
be pulled out from the right side
FDU
of the unit. Maintenance can be Fan unit
Ceiling
available from the right side or
the bottom side.
Keep the same
air flow volume
(Common for FDUM22~160KXE6F
& FDU45~160KXE6F)
case1 case2
Setting No. No.8 No.9 No.10 No.11 No.12 No.13 No.14 No.15
Specifications
Item Model FDU224KXZE1 FDU280KXZE1
Nominal cooling capacity kW 22.4 28.0
Nominal heating capacity kW 25.0 31.5
Power source 1 Phase 220-240V, 50Hz
Power Cooling 1.16-1.20 1.16-1.20
consumption Heating kW 1.16-1.20 1.16-1.20
Sound pressure level dB(A) Hi:50 Me:47 Lo:45
Exterior dimensions
mm 379x1600x893
HxWxD
Net weight kg 89
Air flow m3/min Hi:72 Me:64 Lo:56
Maximum external static pressure Pa 200
Outside air intake Possible(on return duct)
Air filter Procure locally
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø19.05(3/4") Gas line:ø22.22(7/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static
pressure of indoor unit is 72Pa.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDU224/280 52dB(A). Air flow: FDU224/280 80m3/min.
92
Dimensions
All measurements in mm.
Company : AIRZONE
URL : http://www.airzone.es
All-in-one solution: the whole zoning system in a
plug&play device perfectly adapted to the indoor DX unit Main components
FRESH AIR
AIR INLET
DAMPERS Ø150/Ø200
2 to 8
IP6 BOARD +
COMMUNICATION GATEWAY
WIRING DONE IN FACTORY
Zone Thermostat
93
R410A
Setting No. No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9 No.10 H 280
E.S.P. 10Pa 20Pa 30Pa 40Pa 50Pa 60Pa 70Pa 80Pa 90Pa 100Pa
FDUM22~90KXE6F
Improvement of the serviceability
Fan unit (impeller and motor) can be pulled out Pipe Transparent inspection window
from the right side or the bottom side of the unit. Unit Fan unit
Specifications
Item Model FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6F
Nominal cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Nominal heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.10-0.10 0.20-0.20 0.29-0.29 0.33-0.33 0.45-0.45
consumption Heating kW 0.10-0.10 0.20-0.20 0.29-0.29 0.33-0.33 0.45-0.45
Sound power level dB(A) 60 65
Sound pressure level dB(A) Hi:32 Me:29 Lo:26 Hi:33 Me:29 Lo:25 Hi:38 Me:36 Lo:30 Hi:40 Me:34 Lo:29 Hi:40 Me:35 Lo:30
Exterior dimensions
mm 280 x 750 x 635 280 x 950 x 635 280 x 1370 x 740
HxWxD
Net weight kg 29 34 54
Air flow m3/min Hi:10 Me:9 Lo:8 Hi:19 Me:15 Lo:10 Hi:28 Me:25 Lo:19 Hi:32 Me:26 Lo:20 Hi:35 Me:28 Lo:22
Maximum external
Pa 100
static pressure
Outside air intake Possible
Air filter Filter kit:UM-FL1EF/UM-FL2EF/UM-FL3EF(option)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static
pressure of indoor unit is 35Pa(22/28/36/45/56/71/90), 60Pa(112/140/160).
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDUM22/28/36/45/56 37dB(A), FDUM71/90 38dB(A), FDUM112 44dB(A), FDUM140 45dB(A), FDUM160 47dB(A). Air flow: FDUM22/28/36/45/56 13m3/min, FDUM71/90
24m3/min, FDUM112 36m3/min, FDUM140 39m3/min, FDUM160 48m3/min.
94
Dimensions
All measurements in mm.
FDUM71KXE6F, 90KXE6F
95
R410A
Model No.
FDUT15KXE6F-E
FDUT22KXE6F-E
RC-EX3 RC-E5 RCH-E3
FDUT28KXE6F-E
Wireless
FDUT36KXE6F-E
FDUT45KXE6F-E
FDUT56KXE6F-E
FDUT71KXE6F-E RCN-KIT4-E2
Access to control Access to fan motor Access to fan motor Filter pressure loss : 5 Pa
Previous Model Current Model 2 Filter fixing plate
3 Filter
1 Outlet duct plate
Specifications
Item Model FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-E
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.0 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.06-0.06 0.07-0.07 0.08-0.08 0.08-0.08
consumption Heating kW 0.06-0.06 0.07-0.07 0.08-0.08 0.07-0.07
Sound power level dB(A) 52 57 58 59
Sound pressure level 1 dB(A) Hi:28 Me:26 Lo:22 Hi:28 Me:26 Lo:22 Hi:33 Me:30 Lo:26 Hi:34 Me:32 Lo:28 Hi:35 Me:33 Lo:30 Hi:35 Me:31 Lo:28
Sound pressure level 2 dB(A) Hi:32 Me:29 Lo:25 Hi:32 Me:29 Lo:26 Hi:37 Me:34 Lo:28 Hi:36 Me:33 Lo:27 Hi:38 Me:33 Lo:29 Hi:41 Me:37 Lo:32
Exterior dimensions
mm 200x750x500 200x950x500 220x1150x565
HxWxD
Net weight kg 21 22 25 31
Air flow (Standard) m3/min Hi:6 Me:5 Lo:4 Hi:7.5 Me:6 Lo:5 Hi:8.5 Me:7 Lo:5.5 Hi:11.5 Me:9 Lo:7 Hi:12.5 Me:9 Lo:7.2 Hi:16 Me:13 Lo:9.5
External Static pressure Pa Standard:10, Max:35 Standard:10, Max:50
Outside air intake Possible from return duct
Air filter Filter set:UT-FL1EF/UT-FL2EF/UT-FL3EF(option)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static
pressure of indoor unit is 10Pa.
2. The data of nominal cooling and heating capacity and sound pressure level are measured with 10Pa of external static pressure.
3. The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
4. Sound pressure levels are values when 2m supply duct and 1m return duct are connected.
1 : Mike position is 1.5m below unit, 2 : Mike position is 1m in front and 1m below the air supply duct.
96
Dimensions
All measurements in mm.
FDUT15KXE6F-E, 22KXE6F-E, 28KXE6F-E, 36KXE6F-E
15,22,28
FDUT45KXE6F-E, 56KXE6F-E
FDUT71KXE6F-E
97
R410A
FDUH
RC-EX3 RC-E5 RCH-E3
Model No.
Wireless
FDUH22KXE6F
FDUH28KXE6F Drain up kit (option)
FDUH36KXE6F (600mm)
UH-DU-E
RCN-KIT4-E2
530m
m
Installation Flexibility
Control box and drain piping can be installed on both side of the unit and air intake Wired remote control
to the unit is available from bottom or back side. Our highest technology can satisfy
diverse installation requirements.
Control box
Simple remote control
Considering specialized
usage in hotel rooms,
control buttons are limited
only to minimum required
functions such as ON/OFF,
mode, temperature setting
RCH-E3 and fan speed. It is really
(option) simple and easy to use.
Drain piping
Specifications
Item Model FDUH22KXE6F FDUH28KXE6F FDUH36KXE6F
Nominal cooling capacity kW 2.2 2.8 3.6
Nominal heating capacity kW 2.5 3.2 4.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.07
consumption Heating kW 0.05-0.07
Sound power level dB(A) 60
Sound pressure level dB(A) Hi: 33 Me: 30 Lo: 27
Exterior dimensions HxWxD mm 257x570x530
Net weight kg 22
Air flow m3/min Hi: 7 Me: 6.5 Lo: 6
External static pressure Pa 30
Outside air intake Possible from return duct
Air filter Filter kit:UH-FL1E(option)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
mm(in)
Refrigerant piping size Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDUH22/28/36 39dB(A). Air flow: FDUH22/28/36 8.5m3/min.
98
Dimensions
All measurements in mm.
53
30.8
83.3
32.5
Symbol Content
Model FDUH22KXE6F,28KXE6F FDUH36KXE6F
A Gas piping ø9.52 (3/8") (Flare) ø12.7 (1/2") (Flare)
(Duct dimension)
B Liquid piping ø6.35 (1/4") (Flare)
100
145
C1,C2 Drain piping VP20(I.D.20, O.D.26) Note (2)
D Hole for wiring ø30
32.5
12-ø4 E Suspension bolts (M10)
Holes for 32 150 150 150 32 F Inspection hole (635X890) Note (3)
tapping screws Supply air duct
27.6 494 27.6
(Duct dimension)
66.4
C1
40
95.3
21
66
66
156.8
610
(Suspension bolts pitch)
A 62.1 C2
488
530
B Control box
Note(4) 890
600 100
Unit:mm
21
(D)
Air
68
inlet
12-ø4
549.2 E
Holes for Notes
30
tapping screws ( 1 ) The model name label is attached on the fan case
inside the air return grille.
( 2 ) Prepare the connecting socket (VP20) on site.
160
200
28.3
32 150 150 150 32 ( 4 ) Control box and Drain hose piece are able to be relocated
D 27.5 494.2 27.5 on the reverse side.
574
Bottom plate
(Able to be located on the back side)
View G
Holes for
tapping screws
120
18.2 537.6
198.2
160
Air inlet
70 15
30
View G
(After bottom plate is replaced to back side)
99
R410A
FDK15KXZE1
FDK22KXZE1
RC-EX3 RC-E5 RCH-E3
FDK28KXZE1
FDK15~56
FDK36KXZE1
FDK45KXZE1 Wireless
FDK56KXZE1
FDK71KXZE1
FDK90KXZE1
RCN-K-E2: RCN-K71-E2:
FDK15~56 FDK71,90
FDK71,90
The new FDK series air-conditioners have been stylishly designed FDK models adopt the air flow
with rounded contours that fit beautifully into any of Europe’s diverse design that's proven to
interior settings. The design was created by the Italian industrial minimise resistance in a CFD
design studio Tensa srl, based in Milan, to respond to a broad analysis to achieve uniform air
spectrum of local user needs. (15~56KXZE1) conditioning to the furthest
corners of the room.
Fast Slow
Colors in the figure show the air speed.
Selection of flap position is Lateral Swing flap swings from right to left
possible. A flap can be set at Upper
position automatically
different angles. Up/Down Flap swing
Movable
range
+ Up
Left Right
Specifications Down
Item Model FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1 FDK45KXZE1 FDK56KXZE1 FDK71KXZE1 FDK90KXZE1
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1 9.0
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.3 8.0 10.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.03-0.03 0.04-0.04 0.05-0.05
consumption Heating kW 0.02-0.02 0.03-0.03 0.04-0.04 0.05-0.05
Sound power level dB(A) 54 55 58 Cooling:58 Heating:61 59 61
Sound pressure Cooling Hi:34 Me:31 Lo:28 Hi:36 Me:32 Lo:28 Hi:38 Me:33 Lo:28 Hi:41 Me:36 Lo:33 Hi:41 Me:36 Lo:33 Hi:40 Me:37 Lo:35 Hi:42 Me:39 Lo:35
dB(A)
level Heating Hi:34 Me:31 Lo:28 Hi:36 Me:32 Lo:28 Hi:38 Me:33 Lo:28 Hi:41 Me:36 Lo:33 Hi:42 Me:37 Lo:33 Hi:40 Me:37 Lo:35 Hi:42 Me:39 Lo:35
Exterior dimensions
mm 290 x 870 x 230 339 x 1197 x 262
HxWxD
Net weight kg 11.5 11 11.5 17
100
Dimensions
All measurements in mm.
F 35 60 F 60 35
9
45
45
43
185
190
268
47
47
230 3
13
870
80(Service space)
55 SRK 15, 22, 28 :469 55
D B E A C
SRK 36, 45, 56 :475
528
290
Space for installation and service when viewing from the front
60
FDK71KXZE1, 90KXZE1
101
R410A
Selection of flap Thanks to decreasing the numbers of fan motor from two to one,
position is possible. Upper reduction of weight was achieved.
A flap can be set at position
different angles.
Previous Current
Movable
range FDE71 37 33 4kg less!!
*The wireless remote control is
not applicable to the flap control FDE112 49 43 6kg less!!
Lower
system.
position
FDE140 49 43 6kg less!!
The industry's lowest sound pressure levels were achieved by decreasing air flow volume, decreasing pressure loss with employment of one
fan motor and optimizing casing and distributor shape.
(Comparison of previous model)
dB(A)
50 5dB 8dB
8dB 8dB 5dB less!! 43dB less!!
10dB 39dB less!! less!! less!!
40 39dB 39dB
36dB less!! 37dB 35dB
34dB
31dB 31dB 32dB
30 26dB
20
Specifications
Item Model FDE36KXZE1 FDE45KXZE1 FDE56KXZE1 FDE71KXZE1 FDE112KXZE1 FDE140KXZE1
Nominal cooling capacity kW 3.6 4.5 5.6 7.1 11.2 14.0
Nominal heating capacity kW 4.0 5.0 6.3 8.0 12.5 16.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.05 0.07-0.07 0.10-0.10 0.13-0.13
consumption Heating kW 0.05-0.05 0.07-0.07 0.10-0.10 0.13-0.13
Sound power level dB(A) 60 62 —
Sound pressure level dB(A) Hi:38 Me:31 Lo:26 Hi:38 Me:36 Lo:31 Hi:38 Me:36 Lo:31 Hi:39 Me:37 Lo:32 Hi:42 Me:38 Lo:34 Hi:43 Me:40 Lo:35
Exterior dimensions
mm 210 x 1070 x 690 210 x 1320 x 690 250 x 1620 x 690
HxWxD
Net weight kg 28 33 43
Air flow m3/min Hi:10 Me:7 Lo:5.5 Hi:10 Me:9 Lo:7 Hi:15 Me:13 Lo:10 Hi:25 Me:21 Lo:16.5 Hi:26 Me:23 Lo:17
Outside air intake Not possible
Air filter, Q’ty Pocket Plastic net x2 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-E-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Powerful-Hi can be selected. Sound pressure level: FDE36/45/56 46dB(A), FDE71 47dB(A), FDE112 45dB(A), FDE140 48dB(A). Air flow: FDE36/45/56 13m3/min, FDE71 20m3/min, FDE112 28m3/min, FDE140 32m3/min.
102
Dimensions
All measurements in mm. C1,C2
10
53
290 (Suspension bolts pitch)
135 410 145 Note) The slope of drain piping inside the
24 1022 (Suspension bolts pitch) 24
68 52 unit must take decline of 10mm.
B
A
5
Symbol Content
40
A Gas piping ø12.7 (1/2") (Flare)
31
215
210
173
108
B Liquid piping ø6.35 (1/4") (Flare)
C 1,2 Drain piping VP20 (I.D.20)
53
27
27
40 990 40 15 60 7 D Hole for suspension bolt (M10 or M8)
109
690
20 100 E Back cutout PE cover
1070 195
C1,C2 F Top cutout Plate cover
Air supply 235 Drain hose piece (Accessory, 0.3m) G Hole for drain piping (for left back) (Knock out)
(Installed on site)
271
Space for installation and service Position of top cutout and back cutout
Hole for
0 175 drain piping
12 19 (for left)
20
F
300 or more
100 or more
G
308
C1,C2
53
10
A
5
Symbol Content
40
108
27
27
40 1240 40 15 60 7
109
Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
0
12 19 (for left)
20
F
300 or more
100 or more
G
308
C1,C2
FDE112KXZE1, 140KXZE1
D
53
10
31
108
27
27
40 1540 40 15 60 7
109
Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
0
12 19 (for left)
20
300 or more
100 or more F
G
308
103
R410A
With classy semi flat front panel in chic white, the new Thanks to optimum balance of air outlet direction and
series fit in various kinds of rooms and create relaxing sufficient air flow volume, the sound level has been
atmosphere. Choice of wall hanging, floor standing or minimized. The level of FDFW28KXE6F in the cooling lo
behind gallery installation is available. mode is 30dB(A) only.
Selection of flap Simultaneous lower and upper air outlets or upper outlet
Upper can be selected by air flow direction button. Further
position is possible. position
A flap can be set at control can be arranged by a remote control.
different angles. Movable
range
Specifications
Item Model FDFW28KXE6F FDFW45KXE6F FDFW56KXE6F
Nominal cooling capacity kW 2.8 4.5 5.6
Nominal heating capacity kW 3.2 5.0 6.3
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.02-0.02 0.03-0.03
consumption Heating kW 0.02-0.02 0.02-0.02 0.03-0.03
Sound power level dB(A) 55 57 60
Sound pressure level dB(A) Hi:36 Me:34 Lo:30 Hi:38 Me:36 Lo:33 Hi:44 Me:37 Lo:33
Exterior dimensions
mm 600x860x238
HxWxD
Net weight kg 19 20
Air flow (Standard) m3/min Hi:9 Me:8 Lo:7 Hi:11 Me:9 Lo:8
Air filter, Q’ty Polypropylene net x1 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-FW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
104
Dimensions
All measurements in mm.
105
R410A
FDFL
Floor Standing (without casing) RC-EX3 RC-E5 RCH-E3 RCN-KIT4-E2
FDFU
Model No.
FDFL71KXE6F
FDFU28KXE6F
FDFU45KXE6F
FDFU56KXE6F
FDFU71KXE6F
FDFL FDFU (concealed type)
Specifications
Item Model FDFL71KXE6F FDFU28KXE6F FDFU45KXE6F FDFU56KXE6F FDFU71KXE6F
Nominal cooling capacity kW 7.1 2.8 4.5 5.6 7.1
Nominal heating capacity kW 8.0 3.2 5.0 6.3 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.09-0.10 0.09-0.10
consumption Heating kW 0.09-0.10 0.09-0.10
Sound power level dB(A) 62 58 60
Sound pressure level dB(A) Hi:43 Me:41 Lo:40 Hi:41 Me:38 Lo:36 Hi:43 Me:41 Lo:40
Exterior dimensions
HxWxD mm 630x1481x225 630x1077x225 630x1362x225
Net weight kg 40 25 32
Air flow (Standard) m3/min Hi:18 Me:15 Lo:12 Hi:12 Me:11 Lo:10 Hi:14 Me:12 Lo:10 Hi:18 Me:15 Lo:12
Air filter, Q’ty Polypropylene net x1 (Washable)
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø9.52(3/8") Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø15.88(5/8") Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
106
Dimensions
All measurements in mm.
FDFL
FDFU
model a b c d e
107
R410A
Model No.
FDU650FKXZE1
FDU1100FKXZE1 RC-EX3 RC-E5 RCH-E3
FDU1800FKXZE1
FDU2400FKXZE1 Wireless
RCN-KIT4-E2
Air conditioning and intake of outdoor air are in the same system
Compact design
outdoor air
supply air
outdoor air
supply air
(1) This unit is the specific unit for processing the outdoor air temperature closer to the room temperature. For conditioning the room temperature a
dedicated air-conditioner is required additionally.
(2) This unit monitors the outdoor air temperature and controls thermostat ON/OFF at the setting temperature by the remote controller, which
indicates the outdoor air temperature for controlling thermostat ON/OFF. When thermostat is turned OFF, the operation is changed to the fan mode
so that unprocessed outdoor air will be blown into the room directly. Therefore place the air outlet port or orient the air outlet direction not to blow
air directly to persons in the room, especially in the small room such as a restroom and/or sanitary hot water supplying room.
(3) It is strictly prohibited to monitor the room temperature by switching to the thermistor at remote controller side and/or the optional remote
thermistor. Otherwise dew formation at air outlet port and/or dew dripping may occur during cooling operation due to the lower outdoor air
temperature. Therefore keep the remote controller of this unit in place closer to the administrator so as not to be touched it freely by the end user.
(4) Dehumidifying operation with this unit is prohibited.
(5) When handing over this unit to the end user, make sure to explain sufficiently about the foregoing cautions, the installation place and usage of
remote control for this unit and the location of the air outlet.
108
Connectivity with Outdoor units
FDU-F series are connectable to 8~60HP outdoor units, not connectable to 4~6HP, KXZ Lite.
(Micro)
Outside
Exhaust Air
Air Supply
Direct Expansion
Heat Exchanger
SAF
Outside
Air Supply
Exhaust Air
109
R410A
Specifications
Item Model FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1
Nominal cooling capacity kW 9.0 14.0 22.4 28.0
Nominal heating capacity kW 6.5 10.5 16.0 21.5
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.24-0.25 0.35-0.36 1.16-1.20 1.16-1.20
consumption Heating kW 0.24-0.25 0.35-0.36 1.16-1.20 1.16-1.20
Sound pressure level dB(A) Hi:31 Hi:37 Hi:42 Hi:45
Exterior dimension
mm 280x950x635 280x1370x740 379x1600x893
HxWxD
Net weight kg 34 54 89 89
Air flow (Standard) m3/min Hi:11 Hi:18 Hi:30 Hi:40
External static pressure Pa 200 (at Hi Air flow)
Air filter, Q'ty Procure locally
Remote control(option) wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data mm Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8")
Refrigerating piping size (in) Gas line:ø15.88(5/8") Gas line:ø19.05(3/4") Gas line:ø22.22(7/8")
1. The data are measured at 33ºCDB 28ºCWB (68%RH) during cooling and 0ºCDB-2.9ºCWB (50%RH) during heating (no frost).
2. Temperature range of outdoor air must be 20~40ºCDB (32ºCWB) during cooling and 0~24ºCDB during heating.
3. Sound level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to ambient conditions.
4. The factory E.S.P. setting is set within the range of 10 - 120Pa.lf SW8-4 is turned to “ON”, E.S.P. setting range can be changed to 10 - 200 Pa. (with RC-EX3 and RC-E5 only)
Dimensions
All measurements in mm.
110
FDU1100FKXZE1
Symbol Content
A Gas piping ø15.88 (5/8") (Flare)
B Liquid piping ø9.52 (3/8") (Flare)
C1 Drain piping VP25(O.D.32)
C2 Drain piping(Gravity drainage) V20(O.D.26)
D Hole for wiring
E Suspension bolts M10
F Outside air opening for ducting (Knock out)
G Air outlet opening for ducting (Knock out)
H lnspection hole (450X450)
FDU1800FKXZE1, FDU2400FKXZE1
Content
Symbol
MODEL 1800 2400
A Gas piping ø19.05 (3/4") ø22.22 (7/8")
B Liquid piping ø9.52 (3/8") (Brazing)
C Drain piping(Gravity drainage) VP25(O.D.32)
D Hole for wiring
E Suspension bolts M10
F Inspection hole (450X450)
111
R410A
Pa
140
140 140 140 Previous New
120
120
100
105 105 105
80 90 95 90
Remote control
The following functions are newly available.
・ON/OFF Timer – The hour and minute of timer
SAF250E7 SAF350E7 SAF500E7 SAF800E7 SAF1000E7 on/off can be set.
・Filter Sign – Announces the due time for cleaning
the air filter.
Specifications
Item Model SAF150E7 SAF250E7 SAF350E7 SAF500E7 SAF800E7 SAF1000E7
Power source 1 Phase 220-240V, 50Hz
Exterior dimensions
Height x Width x Depth mm 270x970x467 270x882x599 317x1050x804 317x1090x904 388x1322x884 388x1322x1134
Exterior appearance Galvanized steel sheet
Power input W 92-107 108-123 178-185 204-225 360-378 416-432
Running current A 0.42-0.45 0.49-0.51 0.81-0.77 0.93-0.94 1.64-1.58 1.89-1.80
Enthalpy Cooling 63 63 66 62 65 65
exchange
UHi efficiency Heating 70 70 69 67 71 71
Temperature exchange efficiency 75
Enthalpy Cooling 63 63 66 62 65 65
Capacity
exchange
Hi efficiency Heating % 70 70 69 67 71 71
Temperature exchange efficiency 75
Enthalpy Cooling 66 65 71 64 68 70
exchange
Lo efficiency Heating 73 72 73 69 74 76
Temperature exchange efficiency 77 77 78 76 76 79
Motor & Q'ty W 10 x 2 20 x 2 40 x 2 70 x 2 180 x 2 180 x 2
Air handling equipment Fan type & Q’ty Sirocco fan x 2
UHi 150 250 350 500 800 1000
Air flow Hi m3/h 150 250 350 500 800 1000
Lo 120 190 240 440 630 700
UHi 80 105 140 120 140 105
External static pressure Hi Pa 70 95 60 60 110 80
Lo 25 45 45 35 55 75
Net weight kg 25 29 49 57 71 83
Remote control Included
Supply air
Air filter Protection for element (Washable) PS400
Exhaust air
112
Structure (SAF800E7) Principle of operation (simple ventilation) Principle of operation (heat exchanging)
Heat exchanger element Damper FREE COOLING ENERGY RECOVERY
Exhaust Air outdoor indoor Supply Air Exhaust Air outdoor indoor Supply Air
EA RA
(Exhaust Air) (Room Air)
27 ºC 10 ºC 33 ºC 29 ºC
10 ºC 27 ºC 35 ºC 27 ºC
OA SA
(Outside Air) (Supply Air)
e.g. For cooling
in winter time
Dimensions
All measurements in mm.
RA EA RA
EA (Exhaust Air)
(Exhaust Air) (Room Air) (Room Air)
OA SA
OA SA (Outside Air) (Supply Air)
(Outside Air) (Supply Air)
4-13 x 30
11 1 7 4-13 x 30 11 1 7 oblong hole
oblong hole
Applied duct
Model No. Nominal
diameter
Applied duct
SAF150E7 ø100 Nominal
Model No. diameter
SAF250E7
ø150 SAF800E7
4 8 3 12 SAF350E7 ø250
SAF1000E7
SAF500E7 ø200 4
3
12
Dimension table Unit:mm Dimension table Unit:mm
Model A B C E F G H I J K L M N P Model A B C E F G H I J K L M N P
SAF150E7 467 970 49 525
82 303 82 ø98 ø110 SAF800E7 884 940 428
810 135 159 270 1322 85 1250 19 228 612 194 218 388 ø242 ø258
SAF250E7 599 882 95 655 142 315 142 ø164 SAF1000E7 1134 1190 678
19 ø144
SAF350E7 804 1050 978 860 112 580 112 ø164
70 159 182 317
SAF500E7 904 1090 1018 960 132 640 132 ø194 ø210
113
R410A
RC-E5 RCH-E3
• SAF-DX is a heating or cooling coil incorporating KXZ series controls. It can be used in combination with our SAF series of total heat exchanger.
• Combination of SAF-DX together with other indoor units is possible. The capacity code index of each model is shown below and must be used when
making the system selection. Total capacity code index must be within 100% of outdoor unit capacity code index.
• Remote control option is the same as with other indoor units (see above). Connection to all Superlink controls is also possible.
• Optional condensate lift mechanism is also available (600mm height).
• Return air temp. control or supply air temp. control can be selectable.
RA (Room Air)
OA
(Outside Air)
Total heat SAF-DX
Supply / fresh air temp.
exchanger sensor
Return / fresh air
EA temp.sensor SA (Supply Air)
(Exhaust Air)
Heating or cooling coil
SAF-DX can provide heating or cooling to the fresh air supplied through a 3rd party air handling unit or total heat exchanger such as our SAF series.
Specifications
Item Model SAF-DX250E6 SAF-DX350E6 SAF-DX500E6 SAF-DX800E6 SAF-DX1000E6
Nominal cooling capacity *1 kW 2.0 2.8 3.6 5.6 6.3
Nominal heating capacity *2 kW 1.8 2.2 2.8 4.5 5.6
Capacity code 22 28 36 56 71
Power source 1 Phase 220-240V, 50Hz
Power Cooling 7.2-7.2
consumption Heating W 7.2-7.2
Running Cooling 0.05-0.05
A
current Heating 0.05-0.05
Exterior dimensions
mm 315 x 452 x 422 315 x 537 x 422 315 x 682 x 422 315 x 822 x 422
HxWxD
Net weight kg 12.3 13.6 16.1 18.4
Air flow (Standard) m3/h 250 350 500 800 1000
Internal resistance Pa 38 66
Remote control(option) wired: RC-E5, RCH-E3 wireless: RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
(1) The data are measured at the following conditions.
Item Return/fresh air temperature Outdoor air temperature Standards
Operation DB WB DB WB
Cooling*1 27ºC 19ºC 35ºC 24ºC
ISO-T1
Heating*2 20ºC 7ºC 6ºC
(2) This air-conditioner is manufactured and tested in conformity with ISO-T1 "UNITARY AIR-CONDITIONERS".
114
Dimensions
All measurements in mm.
SAF-DX250E6,350E6 SAF-DX500E6
SAF-DX800E6 SAF-DX1000E6
115
R410A
EEV-KIT KXZ
Outdoor units
DX-AHU
• EEV-KIT is the control kit for operating the locally provided
AHU or FCU with direct expansion heat exchanger coils in
connection with the KXZ / KXE6 system.
(AHU : Air Handling Unit, FCU : Fan Coil Unit)
• EEV-KIT is composed of one EEV-Control ASSY and one
EEV-Set.
EEV-KIT
Features
EEV-Control Assy has 2 types.
Refrigeration system EEV-Control Assy System configuration
EEVKIT6-E-M EEVKIT6-E-C
Single Not Use 1 box-Many boxes • Single refrigeration system EEVKIT6-E-C … Possible with multiple
Multiple 1 box (for master) Many boxes(for slave) • Multiple refrigeration system EEVKIT6-E-M (1) + EEVKIT6-E-C …
Possible with multiple (Max32)
EEV-Set Select from following 3 types according to the coil capacity.
Type EEV6-71-E EEV6-160-E EEV6-280-E • EEVKIT6-E-C is common for both single and multiple refrigeration systems
Capacity 22-71 90-160 224-280
EEV-Set
EEV-Set×2 sets
FAN FAN
116
Multiple refrigerant system
Multiple refrigeration system is an AHU system with
1) Multiple independent refrigerant circuits
2) One master control to control the whole system.
Advantage
• Large systems are possible [max capacity 896kW (Indoor unit : 28kW x 32)]
• External control FAN
Master EEV-KIT
Master EEV-Control box FAN
Slave EEV-KIT #1 Slave EEV-KIT #2 #3 • • • •
Sensor (2pcs)
Slave EEV-Control box Slave EEV-Control box
Heat exchanger temp. Heat exchanger temp.
Return air
temp. sensor
Supply air
Sensor x 3
EEV x 1
Sensor (Thi-R1,R2,R3)
EEV-Set
Sensor x 3
EEV x 1
Sensor (Thi-R1,R2,R3)
EEV-Set
••••
temp. sensor
Thi-A Thi-AF Strainer Strainer Strainer Strainer
Connection to SUPERLINK II
Single refrigeration system
Superlink Adapter
SC-ADNA-E SL4
DX-FCU
Slave1 FDT
Single System A Remote control line
Slave2
KXZ KXZ
DX-FCU
Single System B KXZ
Multiple refrigeration system
Superlink Adapter
SC-ADNA-E SL4
DX-FCU
Master FDT
Remote control line Single System A
Slave1
KXZ KXZ
Slave2 KXZ KXZ
Slave3
Slave4
DX-AHU
Multiple System
117
R410A
Control Systems
<Individual control>
Remote Control line up
indoor unit remote control indoor unit remote control indoor unit remote control indoor unit remote control
RC-EX3 FDT RCN-T-5AW-E2 FDTS RCN-TS-E2 FDE RCN-E-E2
wired all models RC-E5 wireless FDTC RCN-TC-24W-E2 FDK22~56 RCN-K-E2 FDFW RCN-FW-E2
RCH-E3 FDTW RCN-TW-E2 FDK71 RCN-K71-E2 others* RCN-KIT4-E2
*FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F
Dry Heating
Auto
The desired operation mode can You can select the temperature as
be selected by simply tapping desired by tapping button.
this button. Run / Stop
2. Main functions
Function name Description
Energy-saving operation Since the capacity is controlled automatically based on the outdoor temperature, energy can be saved without losing comfort.
Sleep timer Set the time period from start to stop of operation. The selectablerange of setting time is from 30 to 240 minutes (at 10-minuteintervals).
Set temperature auto return The temperature automatically returns to the previously set temperature.
Economy Set ON timer by hour When the set time elapses, the air conditioner starts.
& Set OFF timer by hour When the set time elapses, the air conditioner stops.
Timer Set ON timer by clock The air conditioner starts at the set time.
Set OFF timer by clock The air conditioner stops at the set time.
Weekly timer On or Off timer can be set on a weekly basis.
Peak-cut timer Capacity control can be set by using peak cut function on RC-EX3 for better energy saving. Five-step capacity control is available.
Home leave operation When the unit is not used for a long period of time, the room temperature is maintained at a moderate level, avoiding extremely hot or cool temperatures.
Big LCD & Touch screen panel Large 3.8 inch screen has resulted in improved visibility and operability.
Easy modification of Individual flap control User can visually confirm and set the direction of flaps using the visual display on the remote controller.
Comfort Automatic fan speed *1 The micro-computer automatically adjusts the airflow effectively to follow the changes of return air temperature.
Temp increment setting Temperature increment for the change of the set temp can be changed.
Silent mode Set the period of time to operate the Outdoor unit with prioritizing the quietness.
Function switch The function switch allows user to select and set two functions among seven available functions.
Favorite setting Operation mode, set temperature, fan speed and air flow direction automatically adjust to the programmed favorite setting.
Adjusting Brightness of the background light The brightness of the background light can be adjusted by 10 stages.
LCD contrast setting This function allows user to adjust LCD display contrast.
Convenience High power operation High Power Mode increases the unit operating ability for 15 minutes to quickly adjust the room temperature to a comfortable level.
Back light setting This convenient function allows user to see controls under low light conditions.
Administrator settings This function only allows specific individuals to operate the unit.
Setting temp range Limited range of setting temperature in the heating or the cooling operation can be selected.
External Input/Output Function The external input/output of indoor unit by remote controller can set input/output based on user needs.
Select the language Set the language to be displayed on the remote control.
USB connection (mini-B) This function allows batch input of schedule timer settings and other settings involving a large amount of data.
Error code display This function allows user to check information displayed when abnormal function of the unit occurs.
Operation data display Displays various types of air conditioner operation data in real time.
Service Contact company display Address of the service contact is displayed.
Filter sign Announces the due time for cleaning of the air filter.
Static pressure adjustment Allows user to adjust duct static pressure using the remote control.
Backup Control Allows for rotation control, fault backup control, and capacity backup control.
*1 Cannot be used when a centralized control remote is connected.
118
Wireless remote control (option)
For wireless control simply insert the infra-red receiver kit on a corner of the panel
*The wireless remote control is not applicable to the Individual flap control system.
Changeable range
Upper limit 20~30ºC(effective for heating operation)
Timer operation
Lower limit 18~26ºC(effective for non-heating operation)
119
R410A
Central control
SC-SL4-A,-B
Lonworks gateway
SC-LGWNB
SUPERLINK E BOARD(SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network option.
Blue
SL E board A A Connected to the terminals for
Abnormal
LED3
120
Lighting Fan
3-core + earth cable 3-core cable for 3-core cable for 3-core + earth cable
for connecting indoor connecting indoor connecting indoor for connecting indoor
and outdoor units and outdoor units and outdoor units and outdoor units
RACseries
Wireless
remote
control
121
R410A
<Central Control>
SC-SL4-AE/BE Indoor unit 128 units
Green : in operation
23mm Blue : stop
Red : error
9 inch wide LCD Yellow : communication error
Gray : no groups
122
Block layout function Web function
You can monitor and control up to 128 indoor units (Max.128 groups)
from a PC or tablet PC.
Import of floor layout is possible.
(JPEG) Internet
Explorer
Tablet
PC
Demand level 1 – Any indoor unit set to D1 (Demand level 1)has its temperature set point shifted by +2°C in cooling mode or -2°C in heating
mode and cannot be operated from the local remote controller
Demand level 2 – Any indoor unit set to D1 or D2 switch to fan only mode and cannot be operated from the local remote controller
Demand level 3 – Any indoor unit set to D1 or D2 or D3 switch to fan only mode and cannot be operated from the local remote controller
SC-SL1N-E
Start/stop control of up to 16 indoor units either
individually or collectively.
Simple centralised control.
1. The SC-SL1N-E is connected to the Superlink- network via 2-core, non-polar wires (‘AB’ connection).
2. It will monitor and control the start/stop function of up to 16 units, with the sixteen operation button.
3. The unit or group numbers in operation or in need of service are displayed with an LED.
4. Collective start/stop is also available through the simultaneous on/off button.
5. Up to 12 SC-SL1N-E units can be connected to a Superlink- network (consisting of up to 128 indoor
units).
6. If a power failure occurs, the SC-SL1N-E will resume the operation of the system according to a stored
operation condition, once power is restored.
SC-SL2NA-E
Central control of up to 64 indoor units including weekly timer function as standard.
1. The SC-SL2NA-E is connected to the Superlink- network via 2-core, non-polar wires (‘AB’
connection).
2. It will monitor and control the start/stop function of up to16 units, or 16 groups of units, with the
sixteen operation buttons.
3. It also monitors and controls the following functions for individual units, groups of units or the
complete network: operation mode, set point temperature, return air temperature, louvre position,
error code. Air flow and center lock function.
4. The unit or group numbers in operation or in need of service are displayed with an LCD.
5. Collective start/stop is also available through the simultaneous on/off button.
6. If a power failure occurs, the SC-SL2NA-E will resume the operation of the system according to a
stored operation condition, once power is restored.
7. The SC-SL2NA-E can be connected to an external timer to facilitate timed on/off cycles.
Terminal block
51X 52 52R
1 2 3 4 5 6 7 8 A B
An SC-SL2NA-E performs the start/stop control, monitoring and mode setting of up to 64 units. It
is a high quality air conditioner control system that allows up to 64 indoor units to be freely
grouped into 1 to 16 groups.
It allows not only the start/stop control but also the monitoring, display of operation statuses such
as in operation or in need of service and mode setting such as switching of operation modes of
connected units collectively, by group or individually.
• Outer dimensions: H120 x W215 x D25+35*mm.
35* is the measurement including the part contained in a recess.
Note:Please consult dealer for combination of center controls and Building Management Systems interface units.
124
<Building Management Systems>
SC-WBGW256 (Web gateway+BACnet
BACnet gateway) Production by order
SC-WBGW256 control and monitoring of up to 256 cells (some cells can have two or more indoor units and
total number of indoor units can be up to 256 units) centralised to a network PC using the Superlink- web
gateway. Simple installation is assured with no special software requirements, operation is via Internet
Explorer. A low power embedded CPU and compact flash ROM ensure a large storage capacity with high
reliability (no moving parts such as a PC fan, etc). An IP address filter function combined with three-level user
authentication check also ensures security.
Also, SC-WBGW256 can be used as interface devices that convert Mitsubishi Heavy Industries Superlink-
communication data to BACnet code and are controlled centrally from a building management system.
128 units
128 cells
Internet
Explorer HUB
Internet
Explorer HUB
Network 128 cells
BACnet I/P Protocol.
SC-LGWNB is an interface device that converts Mitsubishi Heavy Industries Superlink- communication data
to LonWorks code. Control and monitoring functions of the a/c system for up to 96 indoor units can be
integrated to a central control point via the building management system network.
SUPERLINK- No. 1 system
48 units
lighting
(FTT-10)
125
INTESIS BMS Interface for
Mitsubishi Heavy Industries Thermal Systems air conditioners
All technical support, including specifying work, compatibility issues, product quality (repair and replacement issues), product liability issues
and the required after sales service (including spare parts supply) will be provided by Intesis as it is an Intesis product.
Product sales and delivery will be conducted by Intesis as well.
For details concerning such matters please directly contact Intesis.
Integration of Mitsubishi Heavy Industries Thermal Systems VRF in your KNX installation by Superlink
MH-AC-KNX-48 TOUCH SCREEN
(Max 48 indoor units / Superlink I & II)
MH-AC-KNX-128
(Max 128 indoor units / Superlink II)
INTEGRATED GATEWAY
Integration of Mitsubishi Heavy Industries Thermal Systems VRF in your Modbus installation by Superlink
MH-AC-MBS-48
(Max 48 indoor units / Superlink I & II)
MH-AC-MBS-128
(Max 128 indoor units / Superlink II) MODBUS
INTEGRATED GATEWAY
126
Integration of Mitsubishi Heavy Industries Thermal Systems PAC in your KNX installation by Remote control line
MH-RC-KNX-1i
Example : Example :
Device as Master Device as Slave
TOUCH SCREEN TOUCH SCREEN
Integration of Mitsubishi Heavy Industries Thermal Systems PAC in your Modbus installation by Remote control line
MH-RC-MBS-1
Example : Example :
Device as Master Device as Slave
MODBUS MODBUS
Integration of Mitsubishi Heavy Industries Thermal systems PAC in your EnOcean installation by Remote control line
MH-RC-ENO-1i/1iC
Example : Example :
Device as Master Device as Slave RC-E5
• Protocol : EnOcean
1i : 868MHz@EU
1iC : 315MHz@USA, ASIA
• Dimension : 100 x 70 x 28 mm
• External Power supply : no need
127
R410A
Employment of
All models use refrigerant R410A characterized by the ozone depletion coefficient being 0.
SEER / SCOP (Outdoor unit) 7.73 / 4.59 7.73 / 4.59 7.21 / 4.55 7.21 / 4.55 6.55 / 4.55 6.03 / 4.54 5.77 / 4.49
SEER / SCOP (Outdoor unit) 7.25 / 4.89 7.38 / 4.85 6.66 / 4.23 6.36 / 4.36 6.84 / 4.31 7.29 / 4.58 6.45 / 4.30
SEER / SCOP (Outdoor unit) 7.58 / 4.86 7.27 / 4.91 7.41 / 4.86 6.27 / 4.06 6.11 / 4.02 7.00 / 4.84 6.34 / 4.22
SEER / SCOP (Outdoor unit) 6.04 / 4.33 6.60 / 4.27 7.01 / 4.54 6.25 / 4.29 5.79 / 4.34 5.78 / 4.66
SEER / SCOP (Outdoor unit) 6.65 / 4.34 6.68 / 4.50 6.55 / 4.55 6.03 / 4.54
R410A refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281. Temperature conditions for calculating SCOP are based on "Average climate".
128
MEMO
129
Before starting use
Heating performance Refrigerant leakage
The heating performance values (kW) described in the catalogue are the The refrigerant (R410A) used for Air conditioner is non-toxic and
values obtained by operating at an outdoor temperature of 7 C and indoor inflammable in its original state.
temperature of 20 C as set forth in the ISO Standards. As the heating However, in consideration of a state where the refrigerant leaks into the
performance decreases the outdoor temperature drops, if the outdoor room, measures against refrigerant leaks must be taken in small rooms
temperature is too low and the heating performance is insufficient, use other where the tolerable level could be exceeded. Take measures by installing
heating appliances as well. ventilation devices, etc.
Safety Precautions
Air-conditioner usage target Installation
The air-conditioner described in this catalogue is a dedicated cooling/heating Always commission the installation to a dealer or specialist. Improper
device for human use. installation will lead to water leakage, electric shocks and fires.
Do not use it for special applications such as the storage of food items, Make sure that the outdoor unit is stable in installation. Fix the unit to
animals or plants, precision devices or valuable art, etc. stable base.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current leaks Usage place
could occur. Do not install in places where combustible gas could leak or where there
are sparks.
Before use Installation in a place where combustible gas could be generated, flow or
Always read the "User’s Manual" thoroughly before starting use. accumulate, or places containing carbon fibers could lead to fires.
Certificate Number : JQA-0709 Certificate Number : 4333-2007-AQ-RGC-RvA Certificate Number : YKA4005636 Certificate number : 02117E10160R0M
18KX01E February 2018 F Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
Edited in Japan