Busbar
Busbar
Busbar
Handbook
© ABB Group - 1 -
14-Nov-07
Busbar protection
Need for Bus bar protection
n = TURNS RATIO
R = RCT + 2 RL
© ABB Group - 6 -
Z = MAGNETIZING IMPEDANCE
14-Nov-07
Busbar protection
Limitations of High impedance differential
relay
Puts stringent requirements on CTs
Need for dedicated CTs
Identical CT ratios , magnetising impedances
Aux CTs not acceptable
Inability to cope with increasing fault levels
© ABB Group - 7 -
14-Nov-07
Busbar protection
RADSS medium
impedance relay
T MD IR1
n MD
Ud3
dR
D2 D1
US
© ABB Group - 8 -
14-Nov-07
Busbar protection
REB500 - Numerical Busbar ABB Network Partner AG REB 500
Central Unit
Distributed installation
ABB Network Partner AG REB 500 ABB Network Partner AG REB 500 ABB Network Partner AG REB 500 ABB Network Partner AG REB 500
C C C C
E E E E
Central installation C
Cubicle
Cubicle
SCS/SMS
© ABB Group - 10 -
REB004aE
Busbar protection
Advantages of medium/ Low impedance
relays
Free from any need for Identical CT ratios or matched CT s
Other relays can be included in the same CT core
Increasing fault levels have no impact
© ABB Group - 11 -
14-Nov-07
Busbar protection
Gas Density Detectors
3.5 A 5A 5A
Diff. relay
© ABB Group - 18 -
RADSS RADSS
A B
© ABB Group - 19 -
14-Nov-07
RADSS RADSS
A B
© ABB Group - 20 -
# CT DISCONNECTION UNIT
14-Nov-07
Busbar protection
SINGLE BUSBAR SYSTEM WITH AUX. BUS & CT ON LINE SIDE
MAIN BUS
AUX. BUS
© ABB Group - 21 -
RADSS
14-Nov-07
Busbar protection
USE OF DIRECTIONAL RELAY IN BC CIRCUIT FOR AUX. BUS SELECTIVITY
MAIN BUS
DIR.
RELAY
AUX. BUS
RS/2
© ABB Group - 22 -
RS/2 Rd
14-Nov-07
Busbar protection
L1 LX
:3 :4 :3
L1 : 0 LX : 0
AB : 0
:1 :2 :1 :2 :1 :2
A A
B B
:1 :2 :4 :1 :2
DA
© ABB Group - 23 -
DB
14-Nov-07
TYPE AB
Busbar protection
REQUIREMENTS ON THE ISOLATOR AUXILIARY CONTACTS
0% 100%
Main
contact
Aux.
Contact
a
© ABB Group - 24 -
Aux.
Contact
b
14-Nov-07
Busbar protection
DOUBLE BUSBAR SYSTEM WITH TRANSFER BUS
BUS - A
BUS - B
AUX. BUS
© ABB Group - 25 -
14-Nov-07
Busbar protection
APPLICATION OF RADSS TO ABC BUS CONFIGURATION
RADSS - A
L1 L3 L5
BUS - A
BUS - B
L2 L4 L6
© ABB Group - 27 -
RADSS - B
14-Nov-07
CBIP manual on Protection
of Generators, generator Bus bar protection
transformers and 220kV
and 400 kV networks
© ABB Group - 28 -
14-Nov-07
Busbar protection
1.0
1.0 GENERAL
GENERAL
• Bus bar protection is provided for high speed sensitive clearance
of bus bar faults by tripping all the circuit breakers connected to
faulty bus
(i) Bus bar protection must be provided in all new 400kV and 220kV
substations as well as generating station switchyards.
In case of radially fed 220kV substations, having more than one bus
it is desirable to have bus bar protection but is not a must.
© ABB Group - 29 -
14-Nov-07
Busbar protection
2.0
2.0 Special
SpecialComments
Comments
2.1
2.1
• The D.C. supply for bus bar protection shall be from an independent
feeder
2.2
2.2
• Faults lying between C.B and C.T. shall be cleared from one side by
opening of C.B on bus bar protection operation
• 3 Phase trip relays shall be provided for each circuit breaker which
shall also initiate B.F.P. of concerned breaker
2.4
2.4
2.5
2.5
• C.T wire supervision relays should be set with a sensitivity such that
they can detect C.T secondary open circuit even in case of least
loaded feeder
3.2
3.2
current
14-Nov-07
Busbar protection
3.3
3.3
T MD IR1
n MD
Ud3
dR
D2 D1
US
© ABB Group - 45 -
14-Nov-07
Busbar protection
RADSS CHARACTERISTICS APPLYING TO EXTERNAL AND INTERNAL FAULTS RELAY SLOPE S = 0.8
Id1 = SIt3
Slope S= RS / ndRd3 + RS / 2
1 / 1A 1 / 0.675A 1 / 0.325A
RADSS - A
Overall CT ratio 1200/1A
Total maximum incoming current 4000A
© ABB Group - 50 -