RE 611 Oper 757453 ENa
RE 611 Oper 757453 ENa
RE 611 Oper 757453 ENa
611 series
Operation Manual
Document ID: 1MRS757453
Issued: 2011-11-18
Revision: A
Product version: 1.0
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
When the plug-in unit has been detached from the case, do not touch the
inside of the case. The IED case internals may contain high voltage
potential and touching these may cause personal injury.
Table of contents
Section 1 Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................9
Related documentation................................................................10
Symbols and conventions.................................................................10
Symbols.......................................................................................10
Document conventions................................................................10
Functions, codes and symbols....................................................11
611 series 1
Operation Manual
Table of contents
2 611 series
Operation Manual
Table of contents
IED parametrization..........................................................................69
IED settings for IED functionality.................................................69
IED settings for different operating conditions.............................69
611 series 3
Operation Manual
Table of contents
Section 8 Commissioning...............................................................89
Commissioning checklist..................................................................89
Checking the installation...................................................................89
Checking the power supply.........................................................89
Checking of CT circuits................................................................90
Checking VT circuits....................................................................91
Checking binary input and output circuits....................................91
Binary input circuits................................................................91
Binary output circuits..............................................................91
Authorizations...................................................................................91
User authorization.......................................................................91
Using PCM600.................................................................................92
Setting the communication between IEDs and PCM600.............92
Communication options..........................................................93
Setting communication parameters........................................93
Setting IED and communication.......................................................98
Communication settings..............................................................98
Serial communication ports and drivers.................................98
Serial link diagnostics and monitoring..................................100
Defining Ethernet port settings.............................................101
Defining serial port settings..................................................102
Setting communication protocol parameters........................102
Connecting jumper connectors.............................................102
Communication checklist......................................................102
Setting the local HMI.................................................................103
Changing the local HMI language........................................103
Adjusting the display contrast...............................................103
Changing display symbols....................................................104
Changing the default view....................................................104
Setting the system time and time synchronization...............104
Setting IED parameters.............................................................105
Defining setting groups.........................................................105
IED parametrization..............................................................108
Defining disturbance recorder channel settings...................108
Configuring analog inputs.....................................................108
Testing IED operation.....................................................................109
Selecting the test mode.............................................................109
4 611 series
Operation Manual
Table of contents
Section 9 Glossary.......................................................................113
611 series 5
Operation Manual
6
1MRS757453 A Section 1
Introduction
Section 1 Introduction
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
This manual addresses the operator, who operates the IED on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
611 series 7
Operation Manual
Section 1 1MRS757453 A
Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and other
supported protocols.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
8 611 series
Operation Manual
1MRS757453 A Section 1
Introduction
well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
611 series 9
Operation Manual
Section 1 1MRS757453 A
Introduction
1.4.1 Symbols
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
10 611 series
Operation Manual
1MRS757453 A Section 1
Introduction
611 series 11
Operation Manual
Section 1 1MRS757453 A
Introduction
12 611 series
Operation Manual
1MRS757453 A Section 1
Introduction
611 series 13
Operation Manual
14
1MRS757453 A Section 2
Environmental aspects
Sustainability has been taken into account from the beginning of the product design
including the pro-environmental manufacturing process, long life time, operation
reliability and disposing of the IED.
The choice of materials and the suppliers have been made according to the EU
RoHS directive (2002/95/EC). This directive limits the use of hazardous substances
which are the following:
Operational reliability and long life time have been assured with extensive testing
during the design and manufacturing processes. Moreover, long life time is
supported by maintenance and repair services as well as by the availability of spare
parts.
Design and manufacturing have been done under a certified environmental system.
The effectiveness of the environmental system is constantly evaluated by an
external auditing body. We follow environmental rules and regulations
systematically to evaluate their effect on our products and processes.
All parts used in this product are recyclable. When disposing of an IED or its parts
contact a local waste handler who is authorized and specialized in disposing
611 series 15
Operation Manual
Section 2 1MRS757453 A
Environmental aspects
electronic waste. These handlers can sort the material by using dedicated sorting
processes and dispose of the product according to the local requirements.
1) Polycarbonate
2) Liquid crystal polymer
3) Polybutylene terephthalate
4) Polyamide
16 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
3.1 Overview
The 611 series IEDs support the IEC 61850 with GOOSE messaging and the
Modbus® communication protocol.
611 series 17
Operation Manual
Section 3 1MRS757453 A
611 series overview
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN
3.2.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.
18 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
1 2
3 4
GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
• The header area at the top of the display view shows the current location in the
menu structure.
• The icon area at the upper right corner of the display shows the current action
or user level.
Current action is indicated by the following characters:
• U: Font/Firmware is being updated
• S: Parameters are being stored
• !: Warning and/or indication
Current user level is indicated by the following characters:
• V: Viewer
• O: Operator
• E: Engineer
• A: Administrator
• The content area shows the menu content.
• If the menu contains more rows than the display can show at a time, a scroll
bar is displayed on the right.
611 series 19
Operation Manual
Section 3 1MRS757453 A
611 series overview
The display is updated either cyclically or based on changes in the source data such
as parameters or events.
3.2.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 8 programmable LEDs on front of the LHMI. The LEDs can be
configured with the LHMI, WHMI or PCM600.
3.2.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can give open or close commands to
one object in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
20 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
GUID-A9613A2B-0084-4D1D-A4E3-D04E72A1728E V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
1 Close
2 Escape
3 Up
4 Enter
5 Uplink LED
6 Communication LED
7 Open
8 Left
9 Down
10 Right
11 Remote/Local
12 Help
13 Communication port
Object control
If the control position of the IED is set to local with the R/L button, the IED can be
controlled using the object control buttons.
611 series 21
Operation Manual
Section 3 1MRS757453 A
611 series overview
Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow
button several times or simply keep it pressed down.
Commands
Table 7: Command push-buttons
Name Description
Changing the control position (remote or local) of the device.
R/L
• When the R LED is lit, remote control is enabled and local control disabled.
• When the L LED is lit, local control is enabled and remote control disabled.
• When none of the LEDs are lit, both control positions are disabled.
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
22 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
• If several protection functions start within a short time, the last start
is indicated on the display.
Alarm indicators
The 8 matrix programmable LEDs are used for alarm indication.
611 series 23
Operation Manual
Section 3 1MRS757453 A
611 series overview
The LHMI is used to access the IED parameters. Three types of parameters can be
read and written.
• Numerical values
• String values
• Enumerated values
The RJ-45 port in the LHMI enables front communication. Two LEDs are located
above the communication port.
• The green uplink LED on the left is lit when the cable is successfully
connected to the port.
• The yellow communication LED on the right flashes when the IED
communicates with the connected device.
1 2
A070816 V2 EN
1 Uplink LED
2 Communication LED
When a computer is connected to the IED, the IED's DHCP server for the front
interface assigns an IP address to the computer. The fixed IP address for the front
port is 192.168.0.254.
24 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
The WHMI enables the user to access the IED via a web browser. The supported
web browser version is Internet Explorer 7.0 or 8.0.
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V1 EN
611 series 25
Operation Manual
Section 3 1MRS757453 A
611 series overview
• Locally by connecting your laptop to the IED via the front communication port.
• Remotely over LAN/WAN.
Rejecting changes.
Clearing events.
26 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
3.4 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
3.5 Communication
For application specific situations where communication between IEDs and remote
systems are needed, the 611 series IEDs also support IEC 61850 and Modbus®
communication protocols. Operational information and controls are available
through these protocols. Some communication functionality, for example,
horizontal communication between the IEDs, is only enabled by the IEC 61850
communication protocol.
611 series 27
Operation Manual
Section 3 1MRS757453 A
611 series overview
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100Base-TX) or the fibre-
optic LC connector (100Base-FX). An optional serial interface is available for
RS-485 communication.
Client A
Client B
Network
Network
Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the IED life cycle.
28 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview
• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis
With the individual tool components, you can perform different tasks and functions
and control the whole substation. PCM600 can operate with many different
topologies, depending on the customer needs.
A connectivity package includes all of the data which is used to describe the IED.
For example it contains a list of what parameters exist, which data format is used,
the units, the setting range, the access rights and visibility of the parameter. In
addition it contains code which allows software packages that consume the
connectivity package to properly communicate with the IED. It also allows for
localization of text even when its read from the IED in a standard format such as
COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package
versions for different system products and tools. Update Manager is included with
products that use connectivity packages.
611 series 29
Operation Manual
30
1MRS757453 A Section 4
Using the HMI
You must be logged in and authorized to use the LHMI. Password authorization is
disabled by default and can be enabled via the LHMI or WHMI.
4.1.1 Logging in
GUID-7B40EC73-2324-4E9A-9DF7-CC742744EC1B V1 EN
GUID-C8BDDF55-EB8B-42AD-8184-3939BF51B4C4 V1 EN
611 series 31
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-39601B65-8E32-49F7-AE8A-C16B71770D69 V1 EN
The current user level is shown on the display's upper right corner
in the icon area.
GUID-65BD2160-B3FF-4FD0-8028-C5F0CB67FE54 V1 EN
If the panel has not been used for a predefined timeout period, the backlight is
switched off. The user is logged out from the current user level 30 seconds after the
display backlight has turned off.
The display returns to the default view and all unconfirmed operations such as
parameter editing and breaker selection are cancelled.
32 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
The IED information is shown on the display for a few seconds when the device
starts up. The same information is also found in the IED menu.
611 series 33
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-36916877-1917-4472-AA11-37897C5FD709 V1 EN
GUID-2437E75E-0B00-4B47-89D2-FD4E5690BCC6 V1 EN
The selected contrast value is stored in the non-volatile memory if you are logged
in and authorized to control the IED. After an auxiliary power failure, the contrast
is restored.
GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN
34 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
The Main menu contains main groups which are divided further into more detailed
submenus.
• Control
• Events
• Measurements
• Disturbance records
• Settings
• Configuration
• Monitoring
• Tests
• Information
• Clear
• Language
611 series 35
Operation Manual
Section 4 1MRS757453 A
Using the HMI
If a menu contains more rows than the display can show at a time, a scroll bar is
displayed on the right.
GUID-3DB7835C-EA13-46C3-AAF5-455C07D454EC V1 EN
36 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN
GUID-E1C19F9C-079D-479C-BAF0-71E6E2FAF112 V1 EN
GUID-91310FC1-E8FB-452E-B9B6-4D65C874278C V1 EN
611 series 37
Operation Manual
Section 4 1MRS757453 A
Using the HMI
decimal values, the change can be fractions 0.1, 0.01, 0.001 (...) depending on
the active digit.
For parameters with defined steps, digits smaller than the step
value cannot be edited.
GUID-604A2ED9-E1A7-4986-8CDD-92E43188CA48 V1 EN
Figure 19: Arrow symbol is active, the value is set to the maximum
GUID-F65419AD-767F-488E-9915-4BBEB859D15A V1 EN
38 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-
copy, such as string values, are restored to the original value only after a reboot
even though the edited value is not stored in the flash memory.
GUID-2366EB35-75C9-48AC-8D11-E2B058BCF996 V1 EN
611 series 39
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN
WHMI is disabled by default. Log in with the proper user rights to use the WHMI.
40 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
4.2.1 Logging in
A070923 V2 EN
611 series 41
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-0526D2B8-9C7C-4C29-9E1C-C9DF549B2970 V1 EN
42 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-C08AA4D5-0F4E-4DC5-9194-8338A19761AC V1 EN
The Main menu contains main groups which are divided further into more detailed
submenus.
• Control
• Events
• Measurements
• Disturbance records
• Settings
• Configuration
• Monitoring
• Tests
• Information
• Clear
• Language
• Parameter list
• WHMI settings
611 series 43
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-93613E3F-4CD3-4578-9F97-424282B1228B V1 EN
44 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-C6FA8F5E-19CC-47AD-A000-8DFF91B3FFE7 V1 EN
The selected setting group is shown in the Setting Group drop-down list. The
active setting group is indicated with an asterisk *.
5. Edit the value.
• The minimum, maximum and step values for a parameter are shown in
the Min., Max. and Step columns.
• Setting group values are indicated with .
GUID-35C049F6-D716-451D-9886-CFC607295675 V1 EN
• If the entered value is within the accepted value range, the selection is
highlighted in green. If the value is out of range, the row is highlighted
in red and a warning dialog box is displayed. Write to IED button is
disabled.
611 series 45
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-12C28E34-2871-423A-B9D9-A03FB55362AC V1 EN
GUID-E85F77ED-C27F-426B-AAAD-9C6E10994A7C V1 EN
Figure 30: Warning indicating that the values were not written to
the IED
46 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-
copy, such as string values, are restored to the original value only after a reboot
even though the edited value is not stored in the flash memory.
1. Click Write to IED after editing parameter values to put the values into IED's
database for use.
The values are not stored to the flash memory.
2. Click Commit to write the values to the flash memory.
• Click Reject to cancel saving settings.
• If the parameter has an edit-copy, the original parameter value is
restored.
• If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the
edited value is not stored in non-volatile memory and thus the
reboot restores the original value.
GUID-88F499E6-799A-44D0-869A-1F01E7ED6722 V1 EN
611 series 47
Operation Manual
Section 4 1MRS757453 A
Using the HMI
If the values are not committed, they are not taken into use and they
are lost after a reboot.
GUID-BD2CC4E6-6363-4EEA-9402-415901CC74FA V1 EN
2. In the New Value box, click Clear to select the item to be cleared.
3. Click Write to IED.
48 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-3CAE395C-EC4D-409A-99EB-C3434680BB61 V1 EN
611 series 49
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-20C268F8-B2BA-41E1-A17D-5DBAE8CEFA2F V1 EN
50 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-4E351C8C-EE76-46F5-B83B-14230676BCE8 V1 EN
611 series 51
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-4FD2F9CC-D690-4A68-8E17-E6DE420ADED9 V1 EN
52 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-FD3ED365-053B-4613-B290-2F3F46D04A0D V1 EN
611 series 53
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-0280828D-0DFF-4C83-90A0-D8E57E17E51A V1 EN
54 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-BD629C96-3A49-47C3-B09B-B2776C9CF467 V1 EN
611 series 55
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-9B5D6FB6-68F0-472F-B23D-6369158D6BD7 V1 EN
56 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-BC13067A-6C27-4532-9BD8-FD9BA724BFFF V1 EN
GUID-91F00B72-85EE-4577-B828-7B6E158F4CBF V1 EN
611 series 57
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-D1C26F94-FCD1-4A0B-AE94-A3E4DACB8682 V1 EN
GUID-8BA2E56F-8828-4C5E-807C-F1F780F6E0C8 V1 EN
Figure 44: The arrow extends outside the circle if the current value is too
high
58 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-2D4814EC-F4F7-4FF6-9E40-65D8C7F83487 V1 EN
611 series 59
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-0E215160-B6E8-4ACB-B91A-DEAC98501FFC V1 EN
1. Click Signal configuration on the menu bar to open the overview page.
The switch groups used in the IED are categorized into four logical groups as
Binary Inputs, GOOSE, Internal Signals and Binary outputs and LEDs. Each
of the logical groups is represented by an area enclosed in a rectangle with
general description text.
60 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-3DC3C22C-ED52-4C1C-A9E8-5559DEA5724D V1 EN
2. Click the corresponding area to view a specific logical group, and then the
switch groups included in the logical group are listed in the Function View
page. Click Overview to go back to the overview page.
GUID-EAB8BB7D-C914-436D-8DDC-643EDF49ED40 V1 EN
611 series 61
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-B804DF59-FFE6-42FE-8E41-5A2A125DCD46 V1 EN
GUID-4CF3B8E5-F756-4892-AE71-C4AA5895F075 V1 EN
62 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-085A93F1-AD8B-42E4-9362-407C7057EA20 V1 EN
3. Click switch group on the Function View page to open the configuration page
of that switch group function (ISWGAPCx, OSWGAPCx or SELGAPCx ).
Click Function View to go back to the logical group page.
611 series 63
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-404D1B47-081B-4C33-9B57-5618379B6683 V1 EN
GUID-4AE3751D-4DF3-474B-B30F-E493650ABC2D V1 EN
64 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI
GUID-7E979F4A-0CCC-4723-AF77-4D47A4BCFE15 V1 EN
• Move the mouse over the to display the help dialog box.
611 series 65
Operation Manual
Section 4 1MRS757453 A
Using the HMI
GUID-1769ECA8-EC02-4260-B658-8698D54E89DB V1 EN
66 611 series
Operation Manual
1MRS757453 A Section 5
IED operation
In a normal IED use situation, the basic operation includes monitoring and
checking procedures.
• Monitoring measured values
• Checking object states
• Checking function setting parameters
• Checking events and alarms
All basic operations can be performed via the LHMI, WHMI or with PCM600.
Disturbances and their causes can be identified by indicator LEDs: Ready, Start
and Trip. During normal operation, the Ready LED is steady green.
611 series 67
Operation Manual
Section 5 1MRS757453 A
IED operation
Internal faults can be divided to hardware errors, run-time errors in the application
or operating system and communication errors. Further actions always depend on
the cause of the error.
68 611 series
Operation Manual
1MRS757453 A Section 5
IED operation
Only authorized and skilled personnel should analyze the errors and
decide on further actions.
The IED records system registrations, IED status data and events.
Document all the recorded data from the IED before resetting the
tripping and IED lockout functions.
After completing the editing of setting group values, the new values are activated.
The user can either commit the edited values or discard them. Setting values can
also be copied from one setting group to another.
611 series 69
Operation Manual
70
1MRS757453 A Section 6
Operating procedures
6.1 Monitoring
6.1.1 Indications
The operation of the IED can be monitored via three different indications on the
LHMI.
• Three indicator LEDs with fixed functionality: Ready, Start and Trip
• 8 programmable LEDs
• A text message on the display.
GUID-851D3AA9-F22C-49E9-B964-032A24C94B9F V1 EN
The flashing green LED indicates an internal IED fault. Internal IED fault
messages are shown in a dialog box.
611 series 71
Operation Manual
Section 6 1MRS757453 A
Operating procedures
GUID-216C00ED-ACFF-43AA-A2A6-B53C0FDE8D49 V1 EN
With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.
All values show the momentary measurement value and some include demand
values calculated from a set period.
72 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures
• Disturbance records
• Fault records
• Events
Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.
GUID-01F7D531-894B-4D66-A777-4DE7B301EE43 V1 EN
Upload individual disturbance recordings from the IED with the PCM600 software
to monitor disturbance recorder data.
611 series 73
Operation Manual
Section 6 1MRS757453 A
Operating procedures
GUID-42054948-9852-436A-AA73-FCD44FAA2E60 V1 EN
Disturbance recorder data can be controlled and read with PCM600. It can also be
read via WHMI.
Timestamps of the fault records are shown as a list. The first fault record is the newest.
GUID-DE6008BE-30F6-4FD7-A6C3-E65CDC6FCBE0 V1 EN
74 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures
GUID-6D652E3A-0ECD-4025-9FE2-1535AEA9B1D4 V1 EN
Use the PCM600 tool and WHMI to operate the IED remotely.
611 series 75
Operation Manual
Section 6 1MRS757453 A
Operating procedures
6.2 Controlling
GUID-6210E7B8-A5E3-4869-B654-18EB78E9D3DF V1 EN
GUID-00AE25C7-C645-4DCF-AE1E-263A099A4E33 V1 EN
76 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures
GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN
611 series 77
Operation Manual
Section 6 1MRS757453 A
Operating procedures
GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN
GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN
78 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures
GUID-0FD1E855-51B6-4CD5-9120-C73079B6C9CB V1 EN
GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN
3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to
select a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.
GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN
6. To select a setting group value, press and to edit the value press .
611 series 79
Operation Manual
Section 6 1MRS757453 A
Operating procedures
GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN
GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN
GUID-E526F966-6D6C-4BB9-885A-C990CDC19EC1 V1 EN
80 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting
Section 7 Troubleshooting
1. Check the error origin from the IED's supervision events Main menu/
Monitoring/IED status/Self-supervision.
2. Reboot the IED and recheck the supervision events to see if the fault has
cleared.
3. In case of persistent faults, contact ABB for corrective actions.
611 series 81
Operation Manual
Section 7 1MRS757453 A
Troubleshooting
All the LEDs are tested by turning them on simultaneously. The display shows a
set of patterns so that all the pixels are activated. After the test, the display returns
to normal state.
An indication about the fault is shown as a message on the LHMI. The text
Internal Fault with an additional text message, a code, date and time, is
shown to indicate the fault type.
Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in internal fault mode. All other output contacts are released and locked for
the internal fault. The IED continues to perform internal tests during the fault
situation.
The internal fault code indicates the type of internal IED fault. When a fault
appears, record the code so that it can be reported to ABB customer service.
82 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting
GUID-DFF011AA-989D-4D59-B7A0-A282FEAD48D9 V1 EN
611 series 83
Operation Manual
Section 7 1MRS757453 A
Troubleshooting
7.2.2 Warnings
Warnings are indicated with the text Warning additionally provided with the
name of the warning, a numeric code and the date and time on the LHMI. The
warning indication message can be manually cleared.
If a warning appears, the name and code should be recorded so that they can be
provided to the ABB customer service.
GUID-9EE0CFE1-0DB1-46B7-96A3-F3A0B6CC8018 V1 EN
84 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting
In case of configuration data loss or any other file system error that prevents the
IED from working properly, the whole file system can be restored to the original
factory state. All default settings and configuration files stored in the factory are
restored.
The IED restores the factory settings and restarts. Restoring takes 1-3 minutes.
Confirmation of restoring the factory settings is shown on the display a few
seconds, after which the IED restarts.
611 series 85
Operation Manual
Section 7 1MRS757453 A
Troubleshooting
• Check the current or voltage measurements and their phase information from
Main menu/Measurements.
• Check that the phase information and phase shift between phases is correct.
• Correct the wiring if needed.
• Check the actual state of the connected binary inputs from Main menu/
Monitoring/I/O status/Binary input values.
• Test and change the relay state manually in Main menu/Tests/Binary outputs.
86 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting
611 series 87
Operation Manual
88
1MRS757453 A Section 8
Commissioning
Section 8 Commissioning
Familiarize yourself with the IED and its functionality before you start the
commissioning work.
• Ensure that you have all the needed station drawings such as single line and
wiring diagrams.
• Ensure that your version of the technical manual applies to the IED version
you test.
• Ensure that your setting software and connectivity packages work with the
IED version you test.
• Find out if you need any additional software.
• Ensure that you have the IED settings either on paper or in electronic format.
The settings and logic should be well documented.
• Inspect the settings to ensure that they are correct.
• Ensure that you have the correct cable to connect your PC to the IED's
communication port. The RJ-45 port supports any CAT 5 Ethernet cable but
the recommendation is STP.
• Test your PC's communication port before you go to the site.
• Find out who to contact if you have trouble and make sure you have a means
to contact them.
• Find out who is responsible for the settings.
• Ensure that you have with you the proper test equipment and all needed
connection cables.
• Ensure that the owner of the switchgear familiarizes you with the work site
and any special aspects of it.
• Ensure that you know how to operate in emergency situations. Find out where
the first aid and safety materials and exit routes are.
611 series 89
Operation Manual
Section 8 1MRS757453 A
Commissioning
The CTs must be connected in accordance with the terminal diagram provided with
the IED, both with regards to phases and polarity. The following tests are
recommended for every primary CT or CT core connected to the IED.
• Primary injection test to verify the current ratio of the CT, the correct wiring
up to the protection IED and correct phase sequence connection (that is L1,
L2, L3.)
• Polarity check to prove that the predicted direction of the secondary current
flow is correct for a given direction of the primary current flow. This is an
essential test for the proper operation of the directional function, protection or
measurement in the IED.
• CT secondary loop resistance measurement to confirm that the current
transformer secondary loop DC resistance is within specification and that there
are no high resistance joints in the CT winding or wiring.
• CT excitation test to ensure that the correct core in the CT is connected to the
IED. Normally only a few points along the excitation curve are checked to
ensure that there are no wiring errors in the system, for example, due to a
mistake in connecting the CT's measurement core to the IED.
• CT excitation test to ensure that the CT is of the correct accuracy rating and
that there are no short circuited turns in the CT windings. Manufacturer's
design curves should be available for the CT to compare the actual results.
• Earthing check of the individual CT secondary circuits to verify that each three-
phase set of main CTs is properly connected to the station earth and only at
one electrical point.
• Insulation resistance check.
• Phase identification of CT shall be made.
90 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning
• Polarity check
• VT circuit voltage measurement (primary injection test)
• Earthing check
• Phase relationship
• Insulation resistance check
The polarity check verifies the integrity of circuits and the phase relationships. The
polarity must be measured as close to the IED as possible to ensure that most of the
wiring is also checked.
The primary injection test verifies the VT ratio and the wiring all the way from the
primary system to the IED. Injection must be performed for each phase-to-neutral
circuit and each phase-to-phase pair. In each case, voltages in all phases and
neutral are measured.
Preferably, disconnect the binary input connector from the binary input cards.
Check all connected signals so that both input level and polarity are in accordance
with the IED specifications.
Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and voltage are in accordance with
the IED specifications.
8.3 Authorizations
611 series 91
Operation Manual
Section 8 1MRS757453 A
Commissioning
Passwords are settable. LHMI password must be at least four and WHMI password
at least nine characters. Maximum number of characters is 20 for the WHMI
password and 8 for the LHMI password. Only the following characters are accepted:
• Numbers 0-1
• Letters a-z, A-Z
• Space
• Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~
Each IED has an Ethernet front connector for PCM600 access. Depending on the
station concept and the used station protocol, additional Ethernet interfaces may be
available on the rear side of the IED. All Ethernet interfaces can be used to connect
PCM600.
When an Ethernet based station protocol is used, the PCM600 communication can
use the same Ethernet port and IP address. The IED is able to separate the
information belonging to the PCM600 dialog.
92 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning
Two options are available for the connection of PCM600 to the IED.
The IED has a DHCP server for the front interface. The DHCP server assigns an IP
address to the computer connected to the front interface. The computer's LAN
interface has to be configured to obtain the IP address automatically.
The IP address and the corresponding mask can be set via the LHMI for the rear
port. The front port uses a fixed IP address 192.168.0.254. The front port also uses
DHCP.
Each Ethernet interface has a factory default IP address when the complete IED is
delivered.
611 series 93
Operation Manual
Section 8 1MRS757453 A
Commissioning
A071162 V1 EN
94 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning
A071224 V1 EN
611 series 95
Operation Manual
Section 8 1MRS757453 A
Commissioning
A071162 V1 EN
96 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning
A071164 V1 EN
The used method depends on the time at which the IP address is available.
Defining IP address in the Object Properties windows allows changing the IP
address at any time.
611 series 97
Operation Manual
Section 8 1MRS757453 A
Commissioning
If the protocol does not operate as expected, check that other serial
protocols are not using the COM port.
Depending on the hardware configuration, the IED can be equipped with one or
several UART-based serial communication ports. The communication ports can be
either galvanic (RS-485) or fibre-optic. The IED uses serial ports and drivers as
different types of serial communication protocol links.
Serial ports are called COM1, COM2 and so on, depending on the number of serial
ports in the IED hardware configuration. Each COM port driver has its own setting
parameters found via the LHMI in Configuration/Communication/COMn (n= 1,2,
…).
98 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning
1) When fiber mode is used, the Serial mode parameter value must be RS485 2wire.
All link setting parameters are not found in the COMn settings.
Additional link setting parameters are found in the setting
parameter list of the used serial protocol, since some serial protocol
standards allow changes in link parameters, while other protocol
standards do not.
611 series 99
Operation Manual
Section 8 1MRS757453 A
Commissioning
Serial communication diagnostics and monitoring is divided between the serial link
driver and the serial communication protocol. The lower level physical and protocol-
independent aspects of the UART-based serial communication are monitored in the
serial link driver. Diagnostic counters and monitoring values are found via the
LHMI in Monitoring/Communication/COMn (n= 1,2,…).
Monitoring data for a COM channel can be divided into basic and detailed
diagnostic counters.
If this protocol does not operate as expected, check that other serial
protocols are not using the COM port also.
GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN
Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.
The selected contrast value is stored in the non-volatile memory if you are logged
in and authorized to control the IED. After an auxiliary power failure, the contrast
is restored.
Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and
IEC-ANSI.
1. Set the DST on day and DST off day parameters to define on which week day
the time shift occurs.
2. Set the DST on date and DST off date parameters to define on which month
and week the time shift occurs.
The DST on/off date must precede the selected DST on/off day and be within
the same week as the DST shift.
For example, if the DST is observed from the last Sunday in March to the last
Sunday in October and the time shift occurs at 01:00 UTC, the setting
parameters are:
Set the DST on day and DST off day to "not in use" to determine the
exact date and time for the DST shift. Repeat the setting yearly, as
the time for the DST shift is not on the same date every year.
To disable the DST, set the DST offset parameter to "0 min".
GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN
GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN
3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to
select a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.
GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN
6. To select a setting group value, press and to edit the value press .
GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN
GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN
GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN
GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN
Each analog channel has an equal set of parameters and correspondingly, each
binary channel has an equal set of parameters.
The IED has to be in the test mode before the digital outputs and certain output
signals of protection and other functions can be activated.
The Ready LED also flashes if the IED detects a diagnostic failure.
Check the test mode setting and the IED's IRF alarm contact status
to find the reason for the failure.
The test mode is useful for simulated testing of functions and outputs without
providing current inputs.
GUID-774C947C-70BA-479D-B795-C9222BD17715 V1 EN
If you do not cancel the test mode, it remains on and the Ready
LED remains flashing.
Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words,
protection functions can operate and trip the outputs when the
internal fault is tested.
GUID-C60A750A-B76E-4676-A0AE-05BFF595A5D2 V1 EN
The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.
After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other
indications. If PCM600 is not connected to the IED, the indication is seen again
after the IED's reboot.
GUID-4DC42A7C-150D-4B60-A4EC-679581F98F44 V1 EN
The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status.
Section 9 Glossary
www.abb.com/substationautomation