Relion® Protection and Control

611 series
Operation Manual
Document ID: 1MRS757453
Issued: 2011-11-18
Revision: A
Product version: 1.0

© Copyright 2011 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license


and may be used, copied, or disclosed only in accordance with the terms of such
license.

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantial


property damage.

Only a competent electrician is allowed to carry out the electrical


installation.

National and local electrical safety regulations must always be


followed.

The frame of the IED has to be carefully earthed.

When the plug-in unit has been detached from the case, do not touch the
inside of the case. The IED case internals may contain high voltage
potential and touching these may cause personal injury.

The IED contains components which are sensitive to electrostatic


discharge. Unnecessary touching of electronic components must
therefore be avoided.

Whenever changes are made in the IED, measures should be taken


to avoid inadvertent tripping.
Table of contents

Table of contents

Section 1 Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................9
Related documentation................................................................10
Symbols and conventions.................................................................10
Symbols.......................................................................................10
Document conventions................................................................10
Functions, codes and symbols....................................................11

Section 2 Environmental aspects...................................................15


Sustainable development.................................................................15
Disposing of the IED.........................................................................15

Section 3 611 series overview........................................................17


Overview...........................................................................................17
Local HMI.........................................................................................18
Display.........................................................................................18
LEDs............................................................................................20
Keypad........................................................................................20
Local HMI functionality................................................................22
Protection and alarm indication..............................................22
Parameter management ........................................................24
Front communication..............................................................24
Web HMI...........................................................................................25
Command buttons.......................................................................26
Authorization.....................................................................................27
Communication.................................................................................27
PCM600 tool.....................................................................................28
Connectivity packages.................................................................29
PCM600 and IED connectivity package version..........................29

Section 4 Using the HMI.................................................................31


Using the local HMI..........................................................................31
Logging in....................................................................................31
Logging out..................................................................................32
Turning the display backlight on..................................................32
Selecting local or remote use......................................................33

611 series 1
Operation Manual
Table of contents

Identifying the device...................................................................33


Adjusting the display contrast......................................................34
Changing the local HMI language...............................................34
Changing display symbols...........................................................35
Navigating in the menu................................................................35
Menu structure.......................................................................35
Scrolling the display...............................................................36
Changing the default view......................................................36
Browsing setting values...............................................................36
Editing values..............................................................................37
Editing numerical values........................................................37
Editing string values...............................................................38
Editing enumerated values.....................................................39
Committing settings.....................................................................39
Clearing and acknowledging.......................................................40
Using the local HMI help..............................................................40
Using the Web HMI..........................................................................40
Logging in....................................................................................41
Logging out..................................................................................41
Identifying the device...................................................................41
Navigating in the menu................................................................42
Menu structure.......................................................................43
Showing all parameters...............................................................43
Editing values..............................................................................44
Committing settings.....................................................................46
Clearing and acknowledging.......................................................48
Selecting the programmable LEDs view......................................49
Selecting the event view..............................................................50
Selecting the disturbance record view.........................................52
Uploading disturbance records...............................................53
Triggering the disturbance recorder manually........................54
Deleting disturbance records..................................................55
Selecting phasor diagrams..........................................................56
Selecting fault records.................................................................59
Selecting signal configuration......................................................60
Using the Web HMI help..............................................................65

Section 5 IED operation ................................................................67


Normal operation..............................................................................67
Disturbance identification.................................................................67
Disturbance recording triggering.................................................68
Disturbance record analysis........................................................68
Disturbance reports.....................................................................68
Internal IED errors.......................................................................68

2 611 series
Operation Manual
Table of contents

IED parametrization..........................................................................69
IED settings for IED functionality.................................................69
IED settings for different operating conditions.............................69

Section 6 Operating procedures.....................................................71


Monitoring.........................................................................................71
Indications...................................................................................71
Monitoring indication messages.............................................71
Monitoring an internal IED fault .............................................71
Monitoring condition monitoring data.....................................72
Measured and calculated values.................................................72
Measured values....................................................................72
Using the local HMI for monitoring.........................................73
Recorded data.............................................................................73
Creating disturbance recordings............................................73
Monitoring disturbance recorder data.....................................73
Controlling and reading of disturbance recorder data............74
Monitoring fault records..........................................................74
Monitoring events...................................................................75
Remote monitoring......................................................................75
Monitoring the IED remotely...................................................75
Controlling........................................................................................76
Controlling circuit breaker or contactor........................................76
Resetting IED...................................................................................77
Clearing and acknowledging via the local HMI............................77
Changing the IED functionality.........................................................78
Defining the setting group............................................................78
Activating a setting group.......................................................78
Copying a setting group.........................................................78
Browsing and editing setting group values.............................79
Activating programmable LEDs...................................................80
Setting autoscroll delay...............................................................80

Section 7 Troubleshooting .............................................................81


Fault tracing......................................................................................81
Identifying hardware errors..........................................................81
Identifying runtime errors.............................................................81
Identifying communication errors.................................................81
Checking the communication link operation...........................81
Checking the time synchronization.........................................82
Running the display test..............................................................82
Indication messages.........................................................................82
Internal faults...............................................................................82
Warnings.....................................................................................84

611 series 3
Operation Manual
Table of contents

LED and display messages.........................................................85


Correction procedures......................................................................85
Rebooting the software................................................................85
Restoring factory settings.......................................................85
Setting the password..............................................................86
Identifying IED application problems......................................86

Section 8 Commissioning...............................................................89
Commissioning checklist..................................................................89
Checking the installation...................................................................89
Checking the power supply.........................................................89
Checking of CT circuits................................................................90
Checking VT circuits....................................................................91
Checking binary input and output circuits....................................91
Binary input circuits................................................................91
Binary output circuits..............................................................91
Authorizations...................................................................................91
User authorization.......................................................................91
Using PCM600.................................................................................92
Setting the communication between IEDs and PCM600.............92
Communication options..........................................................93
Setting communication parameters........................................93
Setting IED and communication.......................................................98
Communication settings..............................................................98
Serial communication ports and drivers.................................98
Serial link diagnostics and monitoring..................................100
Defining Ethernet port settings.............................................101
Defining serial port settings..................................................102
Setting communication protocol parameters........................102
Connecting jumper connectors.............................................102
Communication checklist......................................................102
Setting the local HMI.................................................................103
Changing the local HMI language........................................103
Adjusting the display contrast...............................................103
Changing display symbols....................................................104
Changing the default view....................................................104
Setting the system time and time synchronization...............104
Setting IED parameters.............................................................105
Defining setting groups.........................................................105
IED parametrization..............................................................108
Defining disturbance recorder channel settings...................108
Configuring analog inputs.....................................................108
Testing IED operation.....................................................................109
Selecting the test mode.............................................................109

4 611 series
Operation Manual
Table of contents

Testing the digital I/O interface..................................................109


Testing functions.......................................................................110
Selecting the internal fault test..................................................110
ABB Product Data Registration......................................................110

Section 9 Glossary.......................................................................113

611 series 5
Operation Manual
6
1MRS757453 A Section 1
Introduction

Section 1 Introduction

1.1 This manual

The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.

1.2 Intended audience

This manual addresses the operator, who operates the IED on a daily basis.

The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.

611 series 7
Operation Manual
Section 1 1MRS757453 A
Introduction

1.3 Product documentation

1.3.1 Product documentation set

deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual
Service manual

Application manual

Technical manual

Communication protocol
manual

en07000220.vsd

IEC07000220 V1 EN

Figure 1: The intended use of manuals in different lifecycles

The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and other
supported protocols.

The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED.


The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for checking
of external circuitry and energizing the IED, parameter setting and configuration as

8 611 series
Operation Manual
1MRS757453 A Section 1
Introduction

well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.

The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.

The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.

The application manual contains application descriptions and setting guidelines


sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.

The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.

The communication protocol manual describes a communication protocol


supported by the IED. The manual concentrates on vendor-specific implementations.

The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.

Some of the manuals are not available yet.

1.3.2 Document revision history


Document revision/date Product series version History
A/2011-11-18 1.0 First release

Download the latest documents from the ABB Web site


http://www.abb.com/substationautomation.

611 series 9
Operation Manual
Section 1 1MRS757453 A
Introduction

1.3.3 Related documentation


Product series- and product-specific manuals can be downloaded from the ABB
web site http://www.abb.com/substationautomation.

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard


which could result in electrical shock.

The warning icon indicates the presence of a hazard which could


result in personal injury.

The caution icon indicates important information or warning related


to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.

The information icon alerts the reader of important facts and


conditions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to


understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.

1.4.2 Document conventions


A particular convention may not be used in this manual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.

10 611 series
Operation Manual
1MRS757453 A Section 1
Introduction

To navigate between the options, use and .


• HMI menu paths are presented in bold.
Select Main menu/Settings.
• WHMI menu names are presented in bold.
Click Information in the WHMI menu structure.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.

1.4.3 Functions, codes and symbols


All available functions are listed in the table. All of them may not be applicable to
all products.

Table 1: Functions, codes and symbols


Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional
overcurrent protection, low stage, PHLPTOC1 3I> (1) 51P-1 (1)
instance 1
Three-phase non-directional
overcurrent protection, high stage, PHHPTOC1 3I>> (1) 51P-2 (1)
instance 1
Three-phase non-directional
overcurrent protection, high stage, PHHPTOC2 3I>> (2) 51P-2 (2)
instance 2
Three-phase non-directional
overcurrent protection, PHIPTOC1 3I>>> (1) 50P/51P (1)
instantaneous stage, instance 1
Non-directional earth-fault protection,
EFLPTOC1 Io> (1) 51N-1 (1)
low stage, instance 1
Non-directional earth-fault protection,
EFLPTOC2 Io> (2) 51N-1 (2)
low stage, instance 2
Non-directional earth-fault protection,
EFHPTOC1 Io>> (1) 51N-2 (1)
high stage, instance 1
Non-directional earth-fault protection,
EFIPTOC1 Io>>> 50N/51N
instantaneous stage
Directional earth-fault protection, low
DEFLPDEF1 Io> -> (1) 67N-1 (1)
stage, instance 1
Directional earth-fault protection, low
DEFLPDEF2 Io> -> (2) 67N-1 (2)
stage, instance 2
Directional earth-fault protection,
DEFHPDEF1 Io>> -> 67N-2
high stage
Table continues on next page

611 series 11
Operation Manual
Section 1 1MRS757453 A
Introduction

Function IEC 61850 IEC 60617 IEC-ANSI


Transient/intermittent earth-fault
INTRPTEF1 Io> -> IEF 67NIEF
protection
Non-directional (cross-country) earth-
EFHPTOC1 Io>> (1) 51N-2 (1)
fault protection, using calculated Io
Negative-sequence overcurrent
NSPTOC1 I2> (1) 46 (1)
protection, instance 1
Negative-sequence overcurrent
NSPTOC2 I2> (2) 46 (2)
protection, instance 2
Negative-sequence overcurrent
MNSPTOC1 I2>M (1) 46M (1)
protection for motors, instance 1
Negative-sequence overcurrent
MNSPTOC2 I2>M (2) 46M (2)
protection for motors, instance 2
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Residual overvoltage protection,
ROVPTOV1 Uo> (1) 59G (1)
instance 1
Residual overvoltage protection,
ROVPTOV2 Uo> (2) 59G (2)
instance 2
Residual overvoltage protection,
ROVPTOV3 Uo> (3) 59G (3)
instance 3
Three-phase thermal protection for
feeders, cables and distribution T1PTTR1 3Ith>F 49F
transformers
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
Motor start-up supervision STTPMSU1 Is2t n< 49,66,48,51LR
Phase reversal protection PREVPTOC1 I2>> 46R
Thermal overload protection for
MPTTR1 3Ith>M 49M
motors
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
High-impedance differential
HIPDIF1 dHi>(1) 87(1)
protection, instance 1
High-impedance differential
HIPDIF2 dHi>(2) 87(2)
protection, instance 2
High-impedance differential
HIPDIF3 dHi>(3) 87(3)
protection, instance 3
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Switch groups
Input switch group ISWGAPC ISWGAPC ISWGAPC
Output switch group OSWGAPC OSWGAPC OSWGAPC
Selector switch group SELGAPC SELGAPC SELGAPC
Configurable timers
Minimum pulse timer (2 pcs) TPGAPC TP TP
Minimum pulse timer (2 pcs, second
TPSGAPC TPS (1) TPS (1)
resolution), instance 1
Table continues on next page

12 611 series
Operation Manual
1MRS757453 A Section 1
Introduction

Function IEC 61850 IEC 60617 IEC-ANSI


Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Emergergency startup ESMGAPC1 ESTART ESTART
Auto-reclosing DARREC1 O -> I 79
Supervision
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and
MDSOPT1 OPTS OPTM
devices
CT supervision for high-impedance
HZCCRDIF1 MCS 1I(1) MCS 1I(1)
protection scheme, instance 1
CT supervision for high-impedance
HZCCRDIF2 MCS 1I(2) MCS 1I(2)
protection scheme, instance 2
CT supervision for high-impedance
HZCCRDIF3 MCS 1I(3) MCS 1I(3)
protection scheme, instance 3
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement,
CMMXU1 3I 3I
instance 1 1)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement,
RESCMMXU1 Io In
instance 1
Residual voltage measurement RESVMMXU1 Uo Vn

1) In REB611, CMMXU is used for measuring differential phase currents.

611 series 13
Operation Manual
14
1MRS757453 A Section 2
Environmental aspects

Section 2 Environmental aspects

2.1 Sustainable development

Sustainability has been taken into account from the beginning of the product design
including the pro-environmental manufacturing process, long life time, operation
reliability and disposing of the IED.

The choice of materials and the suppliers have been made according to the EU
RoHS directive (2002/95/EC). This directive limits the use of hazardous substances
which are the following:

Table 2: Maximum concentration values by weight per homogeneous material


Substance Proposed maximum concentration
Lead - Pb 0.1%
Mercury - Hg 0.1%
Cadmium - Cd 0.01%
Hexavalent Chromium Cr (VI) 0.1%
Polybrominated biphenyls - PBB 0.1%
Polybrominated diphenyl ethers - PBDE 0.1%

Operational reliability and long life time have been assured with extensive testing
during the design and manufacturing processes. Moreover, long life time is
supported by maintenance and repair services as well as by the availability of spare
parts.

Design and manufacturing have been done under a certified environmental system.
The effectiveness of the environmental system is constantly evaluated by an
external auditing body. We follow environmental rules and regulations
systematically to evaluate their effect on our products and processes.

2.2 Disposing of the IED

Definitions and regulations of hazardous materials are country-specific and change


when the knowledge of materials increases. The materials used in this product are
typical for electric and electronic devices.

All parts used in this product are recyclable. When disposing of an IED or its parts
contact a local waste handler who is authorized and specialized in disposing

611 series 15
Operation Manual
Section 2 1MRS757453 A
Environmental aspects

electronic waste. These handlers can sort the material by using dedicated sorting
processes and dispose of the product according to the local requirements.

Table 3: Materials of the IED parts


IED Parts Material
Case Metallic plates, parts and screws Steel
Plastic parts PC1), LCP2)
Electronics plug in module Various
Plug-in unit Electronics plug in modules Various
Electronics LHMI module Various
Plastic parts PC, PBT3), LCP, PA4)
Metallic parts Aluminium
Package Box Cardboard
Attached material Manuals Paper

1) Polycarbonate
2) Liquid crystal polymer
3) Polybutylene terephthalate
4) Polyamide

16 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

Section 3 611 series overview

3.1 Overview

611 series is a product family of IEDs designed for protection, control,


measurement and supervision of utility substations and industrial switchgear and
equipment. The design of the IEDs has been guided by the IEC 61850 standard for
communication and interoperability of substation automation devices.

The IEDs feature draw-out-type design with a variety of mounting methods,


compact size and ease of use. Depending on the product, optional functionality is
available at the time of order for both software and hardware, for example,
autoreclosure and additional I/Os.

The 611 series IEDs support the IEC 61850 with GOOSE messaging and the
Modbus® communication protocol.

611 series 17
Operation Manual
Section 3 1MRS757453 A
611 series overview

3.2 Local HMI

REF611

Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure

GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN

Figure 2: Example of 611 series LHMI

The LHMI of the IED contains several elements.


• Display
• Buttons
• LED indicators
• Communication port

The LHMI is used for setting, monitoring and controlling.

3.2.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.

18 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

Table 4: Characters and rows on the view


Character size Rows in view Characters on row
Small, mono-spaced (6x12 pixels) 5 rows 20
Large, variable width (13x14 pixels) 4 rows min 8

The display view is divided into four basic areas.

1 2

3 4
GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN

Figure 3: Display layout

1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)

• The header area at the top of the display view shows the current location in the
menu structure.
• The icon area at the upper right corner of the display shows the current action
or user level.
Current action is indicated by the following characters:
• U: Font/Firmware is being updated
• S: Parameters are being stored
• !: Warning and/or indication
Current user level is indicated by the following characters:
• V: Viewer
• O: Operator
• E: Engineer
• A: Administrator
• The content area shows the menu content.
• If the menu contains more rows than the display can show at a time, a scroll
bar is displayed on the right.

611 series 19
Operation Manual
Section 3 1MRS757453 A
611 series overview

The display is updated either cyclically or based on changes in the source data such
as parameters or events.

3.2.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.

There are also 8 programmable LEDs on front of the LHMI. The LEDs can be
configured with the LHMI, WHMI or PCM600.

3.2.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can give open or close commands to
one object in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.

20 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

GUID-A9613A2B-0084-4D1D-A4E3-D04E72A1728E V1 EN

Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port

1 Close
2 Escape
3 Up
4 Enter
5 Uplink LED
6 Communication LED
7 Open
8 Left
9 Down
10 Right
11 Remote/Local
12 Help
13 Communication port

Object control
If the control position of the IED is set to local with the R/L button, the IED can be
controlled using the object control buttons.

Table 5: Object control push-buttons


Name Description
Closing the object.
Close

Opening the object.


Open

611 series 21
Operation Manual
Section 3 1MRS757453 A
611 series overview

Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow
button several times or simply keep it pressed down.

Table 6: Navigation push-buttons


Name Description
• Leaving setting mode without saving the values.
ESC • Cancelling certain actions.
• Adjusting the display contrast in combination with or .
• Changing the language in combination with .
• Inserting a space in combination with when editing a string.
• Clearing indications and LEDs. The first three-second press clears the
indications. The second three-second press clears the programmable
LEDs. Requires appropriate user rights.

• Entering parameter setting mode.


Enter • Confirming a new value of a setting parameter.

• Moving up and down in menus.


Up • Scrolling active digits of a parameter when entering a new setting value.
Down

• Moving left and right in menus.


Left • Changing the active digit of a parameter when entering a new setting value.
• Deleting a character when editing a string by pressing .
Right
• Logging out, when the user is currently logged in. Press for three
seconds in the main menu.

Commands
Table 7: Command push-buttons
Name Description
Changing the control position (remote or local) of the device.
R/L
• When the R LED is lit, remote control is enabled and local control disabled.
• When the L LED is lit, local control is enabled and remote control disabled.
• When none of the LEDs are lit, both control positions are disabled.

Showing context sensitive help messages.


Help

3.2.4 Local HMI functionality

3.2.4.1 Protection and alarm indication

Protection indicators
The protection indicator LEDs are Ready, Start and Trip.

22 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

Table 8: Ready LED


LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred or the IED is in test mode. Internal faults are
accompanied by an indication message.

Table 9: Start LED


LED state Description
Off Normal operation.
On A protection function has started and an indication message is displayed.

• If several protection functions start within a short time, the last start
is indicated on the display.

Flashing A protection function is blocked.

• The blocking indication disappears when the blocking is removed or


when the protection function is reset.

Table 10: Trip LED


LED state Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.

• The trip indication is latching and must be reset via communication.


• If several protection functions trip within a short time, the last trip is
indicated on the display.

Alarm indicators
The 8 matrix programmable LEDs are used for alarm indication.

Table 11: Alarm indications


LED state Description
Off Normal operation. All activation signals are off.
On • Non-latched mode: activation signal is still on.
• Latched mode: activation signal is still on, or it is off but has not
been acknowledged.
• Latched flashing mode: activation signal is still on but has been
acknowledged.

Flashing • Non-latched flashing mode: activation signal is still on.


• Latched flashing mode: activation signal is still on, or it is off but has
not been acknowledged.

611 series 23
Operation Manual
Section 3 1MRS757453 A
611 series overview

3.2.4.2 Parameter management

The LHMI is used to access the IED parameters. Three types of parameters can be
read and written.
• Numerical values
• String values
• Enumerated values

Numerical values are presented either in integer or in decimal format with


minimum and maximum values. Character strings can be edited character by
character. Enumerated values have a predefined set of selectable values.

3.2.4.3 Front communication

The RJ-45 port in the LHMI enables front communication. Two LEDs are located
above the communication port.

• The green uplink LED on the left is lit when the cable is successfully
connected to the port.
• The yellow communication LED on the right flashes when the IED
communicates with the connected device.

1 2

A070816 V2 EN

Figure 5: RJ-45 communication port and indication LEDs

1 Uplink LED
2 Communication LED

When a computer is connected to the IED, the IED's DHCP server for the front
interface assigns an IP address to the computer. The fixed IP address for the front
port is 192.168.0.254.

24 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

3.3 Web HMI

The WHMI enables the user to access the IED via a web browser. The supported
web browser version is Internet Explorer 7.0 or 8.0.

WHMI is disabled by default. To enable the WHMI, select Main


Menu/Configuration/HMI/Web HMI mode via the LHMI.
Reboot the IED for the change to take effect.

WHMI offers several functions.

• Programmable LEDs and event lists


• System supervision
• Parameter settings
• Measurement display
• Disturbance records
• Phasor diagram
• Signal configuration

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V1 EN

Figure 6: Example view of the WHMI

The WHMI can be accessed locally and remotely.

611 series 25
Operation Manual
Section 3 1MRS757453 A
611 series overview

• Locally by connecting your laptop to the IED via the front communication port.
• Remotely over LAN/WAN.

3.3.1 Command buttons


Command buttons can be used to edit parameters and control information via the
WHMI.

Table 12: Command buttons


Name Description
Enabling parameter editing.

Disabling parameter editing.

Writing parameters to the IED.

Refreshing parameter values.

Printing out parameters.

Committing changes to IED's non-


volatile flash memory.

Rejecting changes.

Showing context sensitive help


messages.
Error icon.

Clearing events.

Triggering the disturbance recorder


manually.
Saving values to CSV file format.

Freezing the values so that


updates are not displayed.
Receiving continuous updates to
the monitoring view.
Deleting the disturbance record.

Deleting all disturbance records.

Uploading part one of a


disturbance record.

Uploading part two of a


disturbance record.

26 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

3.4 Authorization

The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.

The default passwords can be changed with Administrator user rights.

User authorization is disabled by default for LHMI and can be


enabled via the LHMI or the WHMI Main Menu/Configuration/
Authorization. WHMI always requires authentication.

Table 13: Predefined user categories


Username User rights
VIEWER Read only access
OPERATOR • Selecting remote or local state with (only locally)
• Changing setting groups
• Controlling
• Clearing indications

ENGINEER • Changing settings


• Clearing event list
• Clearing disturbance records
• Changing system settings such as IP address, serial baud rate
or disturbance recorder settings
• Setting the IED to test mode
• Selecting language

ADMINISTRATOR • All listed above


• Changing password
• Factory default activation

For user authorization for PCM600, see PCM600 documentation.

3.5 Communication

For application specific situations where communication between IEDs and remote
systems are needed, the 611 series IEDs also support IEC 61850 and Modbus®
communication protocols. Operational information and controls are available
through these protocols. Some communication functionality, for example,
horizontal communication between the IEDs, is only enabled by the IEC 61850
communication protocol.

611 series 27
Operation Manual
Section 3 1MRS757453 A
611 series overview

The IEC 61850 communication implementation supports monitoring and control


functionality. Additionally, parameter settings and disturbance and fault records
can be accessed using the IEC 61850 protocol. Disturbance records are available to
any Ethernet-based application in the standard COMTRADE file format. The IED
can send and receive binary signals from other IEDs (so called horizontal
communication) using the IEC 61850-8-1 GOOSE profile, where the highest
performance class with a total transmission time of 3 ms is supported. The IED
meets the GOOSE performance requirements for tripping applications in
distribution substations, as defined by the IEC 61850 standard. The IED can
simultaneously report events to five different clients on the station bus.

The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.

All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100Base-TX) or the fibre-
optic LC connector (100Base-FX). An optional serial interface is available for
RS-485 communication.

Client A
Client B

Network

Network

Managed Ethernet switch Managed Ethernet switch


with RSTP support with RSTP support

REF611 REF611 REM611 REB611


REF611

Overcurrent Overcurrent High-impedance 1 operate


Short circuit
Earth-fault Overcurrent
Earth-fault Combined protection High-impedance 2 operate
Phase unbalance Earth-fault
Phase unbalance Thermal overload High-impedance 3 operate
Thermal overload Phase unbalance
Thermal overload Motor restart inhibit High-impedance start
AR sequence in progress Thermal overload
AR sequence in progress Emergency start enabled Segregated supervision
Disturb.rec.trigged AR sequence in progress
Disturb.rec.trigged Disturb.rec.trigged Disturb.rec.trigged
Trip circuit failure Disturb.rec.trigged
Trip circuit failure Supervision alarm
Trip circuit failure Trip circuit failure
Breaker failure Breaker failure Breaker failure Breaker failure
Breaker failure

REF611 REF611 REF611 REM611 REB611


GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V1 EN

Figure 7: Self-healing Ethernet ring solution

3.6 PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the IED life cycle.

28 611 series
Operation Manual
1MRS757453 A Section 3
611 series overview

• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis

With the individual tool components, you can perform different tasks and functions
and control the whole substation. PCM600 can operate with many different
topologies, depending on the customer needs.

The system settings must be set before a new PCM600 project is


started. For more information, see PCM600 documentation.

3.6.1 Connectivity packages


A connectivity package is a software component that consists of executable code
and data which enables system tools to communicate with an IED. Connectivity
packages are used to create configuration structures in PCM600. The latest
PCM600 and connectivity packages are backward compatible with older IED
versions.

A connectivity package includes all of the data which is used to describe the IED.
For example it contains a list of what parameters exist, which data format is used,
the units, the setting range, the access rights and visibility of the parameter. In
addition it contains code which allows software packages that consume the
connectivity package to properly communicate with the IED. It also allows for
localization of text even when its read from the IED in a standard format such as
COMTRADE.

Update Manager is a tool that helps in defining the right connectivity package
versions for different system products and tools. Update Manager is included with
products that use connectivity packages.

3.6.2 PCM600 and IED connectivity package version


• Protection and Control IED Manager PCM600 Ver. 2.4 or later
• REB611 Connectivity Package Ver. 1.0 or later
• REF611 Connectivity Package Ver. 1.0 or later
• REM611 Connectivity Package Ver. 1.0 or later

Download connectivity packages from the ABB web site http://


www.abb.com/substationautomation

611 series 29
Operation Manual
30
1MRS757453 A Section 4
Using the HMI

Section 4 Using the HMI

4.1 Using the local HMI

You must be logged in and authorized to use the LHMI. Password authorization is
disabled by default and can be enabled via the LHMI or WHMI.

To enable password authorization, select Main menu/


Configuration/Authorization/Local override. Set the parameter
to False.

4.1.1 Logging in

1. Press or or to activate the login procedure.


2. Press or to select the user level.

GUID-7B40EC73-2324-4E9A-9DF7-CC742744EC1B V1 EN

Figure 8: Selecting access level

3. Confirm the selection with .


4. Enter the password when prompted digit by digit.
• Activate the digit to be entered with and .
• Enter the character with and .

GUID-C8BDDF55-EB8B-42AD-8184-3939BF51B4C4 V1 EN

Figure 9: Entering password

5. Press to confirm the login.


• To cancel the procedure, press .

611 series 31
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-39601B65-8E32-49F7-AE8A-C16B71770D69 V1 EN

Figure 10: Error message indicating wrong password

The current user level is shown on the display's upper right corner
in the icon area.

4.1.2 Logging out


The user is automatically logged out 30 seconds after the backlight timeout.

1. Press for three seconds in the main menu.


2. To confirm logout, select Yes and press .

GUID-65BD2160-B3FF-4FD0-8028-C5F0CB67FE54 V1 EN

Figure 11: Logging out

• To cancel logout, press .

4.1.3 Turning the display backlight on


The display backlight is normally off. It turns on during the display test at power up.

• To turn on the backlight manually, press any LHMI push button.


The backlight turns on and the panel is ready for further operations.

If the panel has not been used for a predefined timeout period, the backlight is
switched off. The user is logged out from the current user level 30 seconds after the
display backlight has turned off.

The display returns to the default view and all unconfirmed operations such as
parameter editing and breaker selection are cancelled.

32 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

Change the backlight timeout period in Main menu/Configuration/


HMI/Backlight timeout.

4.1.4 Selecting local or remote use


The control position of the IED can be changed with the R/L button. In local
position primary equipment, such as circuit breakers or disconnectors, can be
controlled via the LHMI. In remote position, control operations are possible only
from a higher level, that is from a control center.

• Press for two seconds.


• When the L LED is lit, local control is enabled and remote control disabled.
• When the R LED is lit, remote control is enabled and local control disabled.
• When neither of the LEDs is lit, both control positions are disabled.

The control position cannot be simultaneously local and remote


but it can be disabled when neither of the positions is active.

To control the IED, log in with the appropriate user rights.

4.1.5 Identifying the device


The IED information includes detailed information about the device, such as
revision and serial number.

The IED information is shown on the display for a few seconds when the device
starts up. The same information is also found in the IED menu.

1. Select Main menu/Information.


2. Select a submenu with and .

611 series 33
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-36916877-1917-4472-AA11-37897C5FD709 V1 EN

Figure 12: Selecting a submenu

3. Enter the submenu with .


4. Browse the information with and .

GUID-2437E75E-0B00-4B47-89D2-FD4E5690BCC6 V1 EN

Figure 13: IED information

4.1.6 Adjusting the display contrast


Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.

• To increase the contrast, press simultaneously and .


• To decrease the contrast, press simultaneously and .

The selected contrast value is stored in the non-volatile memory if you are logged
in and authorized to control the IED. After an auxiliary power failure, the contrast
is restored.

4.1.7 Changing the local HMI language

1. Select Main menu/Language and press .


2. Change the language using or .
3. Press to confirm the selection.
4. Commit the changes.

GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN

Figure 14: Changing the LHMI language

34 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

To change the language using a shortcut, press and


simultaneously anywhere in the menu.

4.1.8 Changing display symbols


Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and
IEC-ANSI.

1. Select Main Menu/Configuration/HMI/FB naming convention and press


.
2. Change the display symbols with or .
3. Press to confirm the selection.

The IED has to be rebooted if the WHMI display symbols are


changed. With the LHMI, the change takes effect immediately.

4.1.9 Navigating in the menu


Navigate the menus and change the display views on the screen with the keypad.

• To move up or down in a menu, press or .


• To move downwards in the menu tree, press .
• To move upwards in the menu tree, press .
• To enter setting mode, press .
• To leave setting mode without saving, press .

4.1.9.1 Menu structure

The Main menu contains main groups which are divided further into more detailed
submenus.

• Control
• Events
• Measurements
• Disturbance records
• Settings
• Configuration
• Monitoring
• Tests
• Information
• Clear
• Language

611 series 35
Operation Manual
Section 4 1MRS757453 A
Using the HMI

4.1.9.2 Scrolling the display

If a menu contains more rows than the display can show at a time, a scroll bar is
displayed on the right.

GUID-3DB7835C-EA13-46C3-AAF5-455C07D454EC V1 EN

Figure 15: Scroll bar on the right

• To scroll the view upwards, press .


• To scroll the view downwards, press .
• To jump from the last row to the first row, press again.
• Press to jump from the first row to the last row.
• To scroll parameter names and values that do not fit the screen, press .
Press once to return to the beginning.

4.1.9.3 Changing the default view

The default view of the display is Measurements unless set otherwise.

1. Select Main menu/Configuration/HMI/Default view and press .


2. Change the default view with or .
3. Press to confirm the selection.

4.1.10 Browsing setting values

1. Select Main menu/Settings/Settings and press .


2. Select the setting group to be viewed with or .

36 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN

Figure 16: Selecting a setting group

3. Press to confirm selection.


4. To browse the settings, scroll the list with and and to select a submenu
press . To move back to the list, press .

GUID-E1C19F9C-079D-479C-BAF0-71E6E2FAF112 V1 EN

Figure 17: Example of submenus in the Settings menu

4.1.11 Editing values


• To edit values, log in with the appropriate user rights.

4.1.11.1 Editing numerical values

1. Select Main menu/Settings and then a setting.


The last digit of the value is active.
• When the symbol in front of the value is ↑, the active value can only be
increased.
• When the symbol is ↓, the active value can only be decreased.
• When the symbol in front of the value is ↕, the active value can either
be increased or decreased.

GUID-91310FC1-E8FB-452E-B9B6-4D65C874278C V1 EN

Figure 18: Last digit is active and it can only be increased

2. Press to increase or to decrease the value of an active digit.


One press increases or decreases the value by a certain step. For integer
values, the change is 1, 10, 100 or 1000 (...) depending on the active digit. For

611 series 37
Operation Manual
Section 4 1MRS757453 A
Using the HMI

decimal values, the change can be fractions 0.1, 0.01, 0.001 (...) depending on
the active digit.

For parameters with defined steps, digits smaller than the step
value cannot be edited.

3. Press or to move the cursor to another digit.


4. To select the minimum or maximum value, select the arrow symbol in front
of the value.
• To set the value to the maximum, press .
• To set the value to the minimum, press .

GUID-604A2ED9-E1A7-4986-8CDD-92E43188CA48 V1 EN

Figure 19: Arrow symbol is active, the value is set to the maximum

After pressing , the previous value can be restored by pressing once,


and vice versa. Another press of or sets the value to the lower or
higher limit. The symbol in front of the value is ↕, when the previous value is
shown.

GUID-F65419AD-767F-488E-9915-4BBEB859D15A V1 EN

Figure 20: Restoring the previous value

4.1.11.2 Editing string values

1. Activate the setting mode and select a setting.


When editing string values, the cursor moves to the first character.
2. Press or to change the value of an active character.
One press changes the value by one step.
3. Press to move the cursor to the right. Press to delete the character on
the left side of the cursor.

38 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

4.1.11.3 Editing enumerated values

1. Activate the setting mode and select a setting.


When editing an enumerated value, the selected value is shown inverted.
2. Press or to change the value of an active enumerated value.
One press changes the enumerated value by one step in the parameter specific
order.

4.1.12 Committing settings


Editable values are stored either in RAM or in non-volatile flash memory. Values
stored in flash memory are in effect also after reboot.

Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-
copy, such as string values, are restored to the original value only after a reboot
even though the edited value is not stored in the flash memory.

1. Press to confirm any changes.


2. Press to move upwards in the menu tree.
3. To save the changes in non-volatile memory, select Yes and press .

GUID-2366EB35-75C9-48AC-8D11-E2B058BCF996 V1 EN

Figure 21: Confirming settings

• To exit without saving changes, select No and press .


• If the parameter has an edit-copy, the original parameter value is
restored.
• If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the
edited value is not stored in non-volatile memory and the reboot
restores the original value.
• To cancel saving settings, select Cancel and press .

After certain parameters are changed, the IED has to be restarted.

611 series 39
Operation Manual
Section 4 1MRS757453 A
Using the HMI

4.1.13 Clearing and acknowledging


The Clear view is used to reset, acknowledge or clear all messages and indications,
including LEDs and latched outputs as well as registers and recordings. Select
Main menu/Clear to activate the clear menu, and select the wanted clearance or
reset function. Events and alarms assigned to programmable LEDs are cleared with
the Clear button as well.

1. Navigate to Clear view.

GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN

Figure 22: Clear view

2. Select the item to be cleared with or .


3. Press , change the value with or and press again.
The item is now cleared.
4. Repeat steps 2 and 3 to clear other items.

Use the button as a shortcut for clearing. The first three-second


press clears the indications. The second three-second press clears
the programmable LEDs.

4.1.14 Using the local HMI help

1. Press to open the help view.


2. Scroll the text with or if the help text exceeds the display area.
3. To close the help, press .

4.2 Using the Web HMI

WHMI is disabled by default. Log in with the proper user rights to use the WHMI.

1. To enable the WHMI, select Main menu/Configuration/HMI/Web HMI


mode via the LHMI.
2. Reboot the IED for the change to take effect.

For more information on the WHMI, see the operation manual.

40 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

4.2.1 Logging in

1. Enter the username with capital letters.


2. Enter the password.
3. Click OK.

A070923 V2 EN

Figure 23: Entering username and password to use the WHMI

4.2.2 Logging out


The user is logged out after session timeout. The timeout can be set in Main menu/
Configuration/HMI/Web HMI timeout.

• To log out manually, click Logout on the menu bar.

4.2.3 Identifying the device


The IED information includes detailed information about the device, for example,
revision and serial number.

1. Click Information in the WHMI menu structure.


2. Click a submenu to see the data.

611 series 41
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-0526D2B8-9C7C-4C29-9E1C-C9DF549B2970 V1 EN

Figure 24: Device information

4.2.4 Navigating in the menu


The menu tree structure on the WHMI is almost identical to the one on the LHMI.
Use the menu bar to access different views.
• The General view shows the IED version and status.
• The Events view contains a list of events produced by the application
configuration.
• The Programmable LEDs view shows the status of programmable LEDs.
• The Phasor diagrams view shows phasor diagrams.
• The Disturbance records view shows the list of disturbance records.
• Logout ends the session.

42 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-C08AA4D5-0F4E-4DC5-9194-8338A19761AC V1 EN

Figure 25: Navigating in the WHMI menus

4.2.4.1 Menu structure

The Main menu contains main groups which are divided further into more detailed
submenus.

• Control
• Events
• Measurements
• Disturbance records
• Settings
• Configuration
• Monitoring
• Tests
• Information
• Clear
• Language
• Parameter list
• WHMI settings

4.2.5 Showing all parameters

1. Click Parameter list in the main menu.

611 series 43
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-93613E3F-4CD3-4578-9F97-424282B1228B V1 EN

Figure 26: Show all parameters

2. Click Print to print out all parameters on paper.


3. Click Save to save all parameters in CSV file format.

4.2.6 Editing values

1. Click the menu in the WHMI tree.


2. Click the submenu to see function blocks.
3. Click a function block to see the setting values.
4. Click Enable Write.

Some parameters, for example the IED test mode, cannot be


set via the WHMI.

44 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-C6FA8F5E-19CC-47AD-A000-8DFF91B3FFE7 V1 EN

Figure 27: Enable writing to edit a value

The selected setting group is shown in the Setting Group drop-down list. The
active setting group is indicated with an asterisk *.
5. Edit the value.
• The minimum, maximum and step values for a parameter are shown in
the Min., Max. and Step columns.
• Setting group values are indicated with .

GUID-35C049F6-D716-451D-9886-CFC607295675 V1 EN

Figure 28: Editing a value

• If the entered value is within the accepted value range, the selection is
highlighted in green. If the value is out of range, the row is highlighted
in red and a warning dialog box is displayed. Write to IED button is
disabled.

611 series 45
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-12C28E34-2871-423A-B9D9-A03FB55362AC V1 EN

Figure 29: Warning indicating that the entered value is incorrect

• If writing values fails, a warning dialog box is displayed.

GUID-E85F77ED-C27F-426B-AAAD-9C6E10994A7C V1 EN

Figure 30: Warning indicating that the values were not written to
the IED

If writing is enabled accidentally, click Disable Write. Disable


Write cannot be selected, when a value has already been written to
the IED. After clicking Write to IED, click either Commit or
Reject.

4.2.7 Committing settings


Editable values are stored either in RAM or in non-volatile flash memory. Values
stored in flash memory are in effect also after reboot.

46 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-
copy, such as string values, are restored to the original value only after a reboot
even though the edited value is not stored in the flash memory.

1. Click Write to IED after editing parameter values to put the values into IED's
database for use.
The values are not stored to the flash memory.
2. Click Commit to write the values to the flash memory.
• Click Reject to cancel saving settings.
• If the parameter has an edit-copy, the original parameter value is
restored.
• If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the
edited value is not stored in non-volatile memory and thus the
reboot restores the original value.

GUID-88F499E6-799A-44D0-869A-1F01E7ED6722 V1 EN

Figure 31: Committing changes

Committing values will take a few seconds.

611 series 47
Operation Manual
Section 4 1MRS757453 A
Using the HMI

If the values are not committed, they are not taken into use and they
are lost after a reboot.

4.2.8 Clearing and acknowledging


Reset, acknowledge or clear all messages and indications, including LEDs and
latched outputs as well as registers and recordings, in the Clear menu.

1. Click the Clear menu.

GUID-BD2CC4E6-6363-4EEA-9402-415901CC74FA V1 EN

Figure 32: Selecting clear menu

2. In the New Value box, click Clear to select the item to be cleared.
3. Click Write to IED.

48 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-3CAE395C-EC4D-409A-99EB-C3434680BB61 V1 EN

Figure 33: Clearing indications and LEDs

4.2.9 Selecting the programmable LEDs view


The programmable LEDs view shows the status of the programmable LEDs. These
are the same LEDs that are located on the upper right side of the LHMI panel.

• Click Programmable LEDs in the menu bar.

611 series 49
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-20C268F8-B2BA-41E1-A17D-5DBAE8CEFA2F V1 EN

Figure 34: Monitoring programmable LEDs

4.2.10 Selecting the event view


The event view contains a list of events produced by the application configuration.
When event page is opened it displays up to 100 latest events at one time. The
event list is updated automatically.

1. Click Events in the menu bar.

50 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-4E351C8C-EE76-46F5-B83B-14230676BCE8 V1 EN

Figure 35: Monitoring events

2. Click Freeze to stop updating the event list.


3. Select a page from the drop-down menu to view older documents.

611 series 51
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-4FD2F9CC-D690-4A68-8E17-E6DE420ADED9 V1 EN

Figure 36: Events view

4. Click Save to save the events in CSV file format.


The CSV file can be opened with a spreadsheet program such as
OpenOffice.org Calc or Microsoft Excel.
5. Click Clear events to clear all events from the IED.

4.2.11 Selecting the disturbance record view


Disturbance records are listed in the disturbance records view.

• Click Disturbance records on the menu bar.

52 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-FD3ED365-053B-4613-B290-2F3F46D04A0D V1 EN

Figure 37: Disturbance record view

4.2.11.1 Uploading disturbance records

1. Click Disturbance records on the menu bar.


2. To upload a disturbance record, click the icons in the CFG and DAT columns
of the record.

611 series 53
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-0280828D-0DFF-4C83-90A0-D8E57E17E51A V1 EN

Figure 38: Uploading a disturbance record

3. Save both the files in the same folder on your computer.


4. Open the disturbance record files with a suitable program.

4.2.11.2 Triggering the disturbance recorder manually

1. Click Disturbance records on the menu bar.


2. Click Manual trigger.

54 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-BD629C96-3A49-47C3-B09B-B2776C9CF467 V1 EN

Figure 39: Manual triggering

4.2.11.3 Deleting disturbance records

1. Click Disturbance records on the menu bar.


2. Delete records.
• Click Delete all to delete all records.
• Select one or more recordings and click Delete to delete selected records.

611 series 55
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-9B5D6FB6-68F0-472F-B23D-6369158D6BD7 V1 EN

Figure 40: Deleting disturbance records

3. Click OK to confirm or Cancel to cancel the deletion.

4.2.12 Selecting phasor diagrams

1. Click Phasor diagrams.

56 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-BC13067A-6C27-4532-9BD8-FD9BA724BFFF V1 EN

Figure 41: Monitoring phasors

2. Toggle the diagram visibility by selecting it from the drop-down menu.

GUID-91F00B72-85EE-4577-B828-7B6E158F4CBF V1 EN

Figure 42: Toggling the diagram visibility

Visible diagrams are indicated with an asterisk *.


3. Change the size of the diagram by changing the zoom value.

611 series 57
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-D1C26F94-FCD1-4A0B-AE94-A3E4DACB8682 V1 EN

Figure 43: Zooming the diagram

4. Click Freeze to stop updating the phasor diagram.


No updates are displayed in the diagram.

GUID-8BA2E56F-8828-4C5E-807C-F1F780F6E0C8 V1 EN

Figure 44: The arrow extends outside the circle if the current value is too
high

58 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

Install an SVG plugin to view the phasor diagrams.

4.2.13 Selecting fault records

• Select from the main menu Monitoring/Recorded data/Fault record to view


a list of all available fault records.
The newest fault record is first on the list. The fault records list is updated
automatically.

GUID-2D4814EC-F4F7-4FF6-9E40-65D8C7F83487 V1 EN

Figure 45: Fault records

611 series 59
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-0E215160-B6E8-4ACB-B91A-DEAC98501FFC V1 EN

Figure 46: Fault record parameters

4.2.14 Selecting signal configuration


The signal configuration view provides an easy tool to manage the application
configuration, simplifying the configuration work.

1. Click Signal configuration on the menu bar to open the overview page.
The switch groups used in the IED are categorized into four logical groups as
Binary Inputs, GOOSE, Internal Signals and Binary outputs and LEDs. Each
of the logical groups is represented by an area enclosed in a rectangle with
general description text.

60 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-3DC3C22C-ED52-4C1C-A9E8-5559DEA5724D V1 EN

Figure 47: Overview

2. Click the corresponding area to view a specific logical group, and then the
switch groups included in the logical group are listed in the Function View
page. Click Overview to go back to the overview page.

GUID-EAB8BB7D-C914-436D-8DDC-643EDF49ED40 V1 EN

Figure 48: Binary Input Configuration

611 series 61
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-B804DF59-FFE6-42FE-8E41-5A2A125DCD46 V1 EN

Figure 49: GOOSE Configuration

GUID-4CF3B8E5-F756-4892-AE71-C4AA5895F075 V1 EN

Figure 50: Internal Signal Configuration

62 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-085A93F1-AD8B-42E4-9362-407C7057EA20 V1 EN

Figure 51: Binary Outputs and LEDs Configuration

3. Click switch group on the Function View page to open the configuration page
of that switch group function (ISWGAPCx, OSWGAPCx or SELGAPCx ).
Click Function View to go back to the logical group page.

611 series 63
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-404D1B47-081B-4C33-9B57-5618379B6683 V1 EN

Figure 52: ISWGAPC Configuration

GUID-4AE3751D-4DF3-474B-B30F-E493650ABC2D V1 EN

Figure 53: OSWGAPC Configuration

64 611 series
Operation Manual
1MRS757453 A Section 4
Using the HMI

GUID-7E979F4A-0CCC-4723-AF77-4D47A4BCFE15 V1 EN

Figure 54: SELGAPC configuration

4. Click Enable Write to edit field values.

For more information on editing field values, see the section


on editing values.

4.2.15 Using the Web HMI help


The context sensitive WHMI help provides information, for example, of a single
parameter.

• Move the mouse over the to display the help dialog box.

611 series 65
Operation Manual
Section 4 1MRS757453 A
Using the HMI

GUID-1769ECA8-EC02-4260-B658-8698D54E89DB V1 EN

Figure 55: Opening the WHMI help

66 611 series
Operation Manual
1MRS757453 A Section 5
IED operation

Section 5 IED operation

5.1 Normal operation

In a normal IED use situation, the basic operation includes monitoring and
checking procedures.
• Monitoring measured values
• Checking object states
• Checking function setting parameters
• Checking events and alarms

All basic operations can be performed via the LHMI, WHMI or with PCM600.

For more information, see PCM600 documentation.

5.2 Disturbance identification

Disturbances and their causes can be identified by indicator LEDs: Ready, Start
and Trip. During normal operation, the Ready LED is steady green.

Table 14: Disturbance indications


LED State Description
Start LED Yellow, steady Protection started
Start LED Yellow, flashing Protection function blocked
Trip LED Red, steady Protection operated
Ready LED Green, flashing Internal fault

Further actions to be taken to identify the disturbance:

• Checking programmable LEDs


• Reading event history
• Checking fault records
• Analyzing disturbance recordings

611 series 67
Operation Manual
Section 5 1MRS757453 A
IED operation

Document the disturbance before clearing the information from the


IED.

Only authorized and skilled personnel should analyze possible


errors and decide on further actions. Otherwise, stored disturbance
data can be lost.

5.2.1 Disturbance recording triggering


Disturbance recordings are normally triggered by IED applications when they
detect fault events. Disturbance recordings can also be triggered manually or
periodically. The manual trigger generates an instant disturbance report. Use this
function to get a snapshot of the monitored signals.

5.2.2 Disturbance record analysis


The IED collects disturbance records of fault events which are set to trigger the
disturbance recorder. Disturbance data is collected and stored for later viewing and
analysis. The disturbance recorder data can be read and analyzed with PCM600.

For more information, see PCM600 documentation.

5.2.3 Disturbance reports


PCM600 can be used for creating reports of disturbance recorder data.

For more information, see PCM600 documentation.

5.2.4 Internal IED errors


The IED self-supervision handles internal run-time fault situations. The main
indication of an internal fault is a flashing green Ready LED.

Internal faults can be divided to hardware errors, run-time errors in the application
or operating system and communication errors. Further actions always depend on
the cause of the error.

68 611 series
Operation Manual
1MRS757453 A Section 5
IED operation

Only authorized and skilled personnel should analyze the errors and
decide on further actions.

The IED records system registrations, IED status data and events.

Document all the recorded data from the IED before resetting the
tripping and IED lockout functions.

5.3 IED parametrization

IED parameters are set via the LHMI, WHMI or PCM600.

Setting parameters need to be calculated according to the electrical network


conditions and the electrical characteristics of the protected equipment. The IED's
settings need to be verified before the IED is connected to a system.

Document all changes to parameter settings.

For more information, see PCM600 documentation.

5.3.1 IED settings for IED functionality


Function settings can be edited one by one by navigating to the individual setting
values, for example via the LHMI. The values in other setting groups should be
known before editing a certain setting value.

After completing the editing of setting group values, the new values are activated.
The user can either commit the edited values or discard them. Setting values can
also be copied from one setting group to another.

5.3.2 IED settings for different operating conditions


IED settings can be designed for various operation conditions by defining different
setting values to different setting groups. The active setting group can be changed
by the IED application or manually via the LHMI, WHMI or PCM600.

611 series 69
Operation Manual
70
1MRS757453 A Section 6
Operating procedures

Section 6 Operating procedures

6.1 Monitoring

6.1.1 Indications
The operation of the IED can be monitored via three different indications on the
LHMI.

• Three indicator LEDs with fixed functionality: Ready, Start and Trip
• 8 programmable LEDs
• A text message on the display.

6.1.1.1 Monitoring indication messages

Indication messages and tripping data are shown in a dialog box.

1. Read the indication message in the dialog box.


The message can indicate the starting or tripping of protection functions or an
internal fault in the device.
2. Press to close the indication message without clearing it or press to
activate the Clear view and to clear messages.

GUID-851D3AA9-F22C-49E9-B964-032A24C94B9F V1 EN

Figure 56: Indication message

6.1.1.2 Monitoring an internal IED fault

The flashing green LED indicates an internal IED fault. Internal IED fault
messages are shown in a dialog box.

611 series 71
Operation Manual
Section 6 1MRS757453 A
Operating procedures

GUID-216C00ED-ACFF-43AA-A2A6-B53C0FDE8D49 V1 EN

Figure 57: Fault indication

1. Select Main menu/Monitoring/IED status/Self-supervision to monitor the


latest fault indication.
2. Press or to scroll the view.

6.1.1.3 Monitoring condition monitoring data

1. Select Main menu/Monitoring/I/O status/Condition monitoring.


2. Press or to scroll the view.
3. Press to enter or to exit a submenu.

With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.

6.1.2 Measured and calculated values


Measurement view in Main Menu/Measurements shows the momentary actual
values for various power system measurements.

All values show the momentary measurement value and some include demand
values calculated from a set period.

6.1.2.1 Measured values

Measured values can be accessed through the LHMI, WHMI or PCM600.

Table 15: Measured values


Indicator Description
IL1-A Current measured on phase L1
IL2-A Current measured on phase L2
IL3-A Current measured on phase L3
Io-A Measured earth-fault current
Uo-kV Measured residual voltage
Ng-Seq-A Negative-phase-sequence current
Ps-Seq-A Positive-phase-sequence current
Zro-Seq-A Zero-phase-sequence current

72 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures

6.1.2.2 Using the local HMI for monitoring

1. Select Main menu/Measurements to monitor measured and calculated values.


The list of IED's basic measurements is shown.
2. Scroll the view with and .

6.1.3 Recorded data


The IED is provided with intelligent and flexible functionality that collects
different kinds of data. The recorded data gives substantial information for post
fault analysis.

• Disturbance records
• Fault records
• Events

6.1.3.1 Creating disturbance recordings

Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.

1. Select Main menu/Disturbance records.


2. Select Trig recording with or .
3. Press , change the value with or and press again.

GUID-01F7D531-894B-4D66-A777-4DE7B301EE43 V1 EN

Figure 58: Changing the value

The disturbance recorder is now triggered.

6.1.3.2 Monitoring disturbance recorder data

Upload individual disturbance recordings from the IED with the PCM600 software
to monitor disturbance recorder data.

1. Select Main menu/Disturbance records.


All the disturbance recorder information is listed.
2. Scroll the view with or .
The following items are listed in the view:

611 series 73
Operation Manual
Section 6 1MRS757453 A
Operating procedures

• Number of recordings currently in the IED memory.


• Remaining amount of recordings that fit into the available recording
memory.
• Recording memory used in percentage.
• If the periodic triggering function is used, the time to trigger which
indicates the remaining time to the next periodic triggering of the
disturbance recorder.

GUID-42054948-9852-436A-AA73-FCD44FAA2E60 V1 EN

Figure 59: Monitoring disturbance recorder via the LHMI

6.1.3.3 Controlling and reading of disturbance recorder data

Disturbance recorder data can be controlled and read with PCM600. It can also be
read via WHMI.

For more information, see PCM600 documentation.

6.1.3.4 Monitoring fault records

Timestamps of the fault records are shown as a list. The first fault record is the newest.

1. Select Main Menu/Monitoring/Recorded data/Fault record.


2. To navigate between the fault records, press and .
3. To enter or exit a submenu, press or .

GUID-DE6008BE-30F6-4FD7-A6C3-E65CDC6FCBE0 V1 EN

Figure 60: Monitoring fault records

74 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures

6.1.3.5 Monitoring events

Event view contains a list of events produced by the application configuration.


Each event takes one view area. The header area shows the currently viewed event
index and the total amount of the events. The most recent event is always first.

1. Select Main Menu/Events.


2. Press to view the first event.
Date, time, device description, object description and event text elements of
the event are shown.
3. Press or to scroll the view.

GUID-6D652E3A-0ECD-4025-9FE2-1535AEA9B1D4 V1 EN

Figure 61: Monitoring events

6.1.4 Remote monitoring


The IED supports comprehensive remote monitoring.

6.1.4.1 Monitoring the IED remotely

Use the PCM600 tool and WHMI to operate the IED remotely.

• Read maintenance record and version log.


• Analyze disturbance record data.
• Create disturbance records.
• Monitor IED values.

For more information, see PCM600 documentation.

611 series 75
Operation Manual
Section 6 1MRS757453 A
Operating procedures

6.2 Controlling

6.2.1 Controlling circuit breaker or contactor


The primary equipment can be controlled via the LHMI with the Open and Close
buttons when the IED is set to local control mode and you are authorized to access
control operations.

1. Press to open or to close the object.


2. Enter the password when prompted.
3. To confirm the operation, select Yes and press .

GUID-6210E7B8-A5E3-4869-B654-18EB78E9D3DF V1 EN

Figure 62: Opening circuit breaker

• To cancel the operation, select No and press .

GUID-00AE25C7-C645-4DCF-AE1E-263A099A4E33 V1 EN

Figure 63: Cancelling operation

The time between selecting the object and giving a control


command is restricted by an adjustable time-out. When an object is
selected, the control command has to be given within this time.

With default configurations it is possible to control a breaker open


even when the breaker is in an intermediate state.

76 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures

6.3 Resetting IED

6.3.1 Clearing and acknowledging via the local HMI


All messages and indications, including LEDs and latched outputs as well as
registers and recordings can be reset, acknowledged or cleared with the Clear
button. Selecting Main menu/Clear activates the Clear menu for selecting the
wanted clearance or reset function. Events and alarms assigned to programmable
LEDs can also be cleared with the Clear menu.

1. Select Main menu/Clear to activate the Clear view.


All the items that can be cleared are shown:
• Indications and LEDs
• Programmable LEDs
• Events
• Metering records
• Disturbance records
• Fault records
• Temperature of three-phase thermal protection for feeders, cables, and
thermal overload protection for motors
• Reset of auto-reclosing and cable fault detection
• Operation time of runtime counter for machines and devices
• Counters for auto-reclosing and motor start-up supervision
• Master trip

GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN

Figure 64: Clear view

2. Select the item to be cleared with or .


3. Press , change the value with or and press again.
The item is now cleared.
4. Repeat the steps to clear other items.

Use the button as a shortcut for clearing. The first three-second


press clears the indications. The second three-second press clears
the programmable LEDs.

611 series 77
Operation Manual
Section 6 1MRS757453 A
Operating procedures

6.4 Changing the IED functionality

6.4.1 Defining the setting group

6.4.1.1 Activating a setting group

IED settings are planned in advance for different operation conditions by


calculating setting values to different setting groups. The active setting group can
be changed by the IED application or manually from the menu.

1. Select Main menu/Settings/Setting group/Active group and press .

GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN

Figure 65: Active setting group

2. Select the setting group with or .


3. Press to confirm the selection or to cancel.

GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN

Figure 66: Selecting the active setting group

4. Commit the settings.

Remember to document the changes you make.

6.4.1.2 Copying a setting group

Setting group 1 can be copied to another group or to all available groups.

1. Select Main menu/Settings/Setting group/Copy group 1 and press .


2. Change the options with or and press to confirm the selection.

78 611 series
Operation Manual
1MRS757453 A Section 6
Operating procedures

GUID-0FD1E855-51B6-4CD5-9120-C73079B6C9CB V1 EN

Figure 67: Copy group 1 into 6

6.4.1.3 Browsing and editing setting group values

1. Select Main menu/Settings/Settings and press .


2. Select the setting group to be viewed with or and press to confirm
the selection.

GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN

Figure 68: Selecting a setting group

3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to
select a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.

GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN

Figure 69: Setting group parameter

6. To select a setting group value, press and to edit the value press .

611 series 79
Operation Manual
Section 6 1MRS757453 A
Operating procedures

GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN

Figure 70: Selecting the setting group value

Only values within the selected setting group can be changed.


7. Press or to change the value and to confirm the selection.

GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN

Figure 71: Editing the setting group value

The active setting group is indicated with an asterisk * .

6.4.2 Activating programmable LEDs

1. Select Main menu/Configuration/Programmable LEDs.


2. Select a programmable LED with or .
3. Press to enter the selection and to change the programmable LED mode.
4. Change the mode with or and press to confirm the selection.

6.4.3 Setting autoscroll delay


Autoscroll delay parameter sets the delay of scrolling down measurements view if
it is set as default view and the user is logged out. Autoscroll is active if the delay
value is not zero.

1. Select Main menu/Configuration/ HMI/Autoscroll delay and press .


2. Select delay time with or .
3. Press to confirm the selection.

GUID-E526F966-6D6C-4BB9-885A-C990CDC19EC1 V1 EN

Figure 72: Autoscroll delay

80 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting

Section 7 Troubleshooting

7.1 Fault tracing

7.1.1 Identifying hardware errors

1. Check the module with an error.


Check the IED supervision events in Main menu/Monitoring/IED status/Self-
supervision for a faulty hardware module.
2. Inspect the IED visually.
• Inspect the IED visually to find any physical error causes.
• If you can find some obvious physical damage, contact ABB for repair
or replacement actions.
3. Check whether the error is external or internal.
• Check that the error is not caused by external origins.
• Remove the wiring from the IED and test the input and output operation
with an external test device.
• If the problem remains, contact ABB for repair or replacement actions.

7.1.2 Identifying runtime errors

1. Check the error origin from the IED's supervision events Main menu/
Monitoring/IED status/Self-supervision.
2. Reboot the IED and recheck the supervision events to see if the fault has
cleared.
3. In case of persistent faults, contact ABB for corrective actions.

7.1.3 Identifying communication errors


Communication errors are normally communication interruptions or
synchronization message errors due to communication link breakdown.

• In case of persistent faults originating from IED's internal faults such as


component breakdown, contact ABB for repair or replacement actions.

7.1.3.1 Checking the communication link operation

• To verify communication, check that both LEDs above the RJ-45


communication port are lit.

611 series 81
Operation Manual
Section 7 1MRS757453 A
Troubleshooting

Table 16: Communication LEDs


LED Communication ok
Uplink Steady green light
Communication Flashing yellow light

7.1.3.2 Checking the time synchronization

• Check the time synchronization via LHMI in Main menu/Monitoring/IED


status/Time synchronization.

7.1.4 Running the display test


A short display test is always run, when auxiliary voltage is connected to the IED.

All the LEDs are tested by turning them on simultaneously. The display shows a
set of patterns so that all the pixels are activated. After the test, the display returns
to normal state.

7.2 Indication messages

7.2.1 Internal faults

Internal fault indications have the highest priority on the LHMI.


None of the other LHMI indications can override the internal fault
indication.

An indication about the fault is shown as a message on the LHMI. The text
Internal Fault with an additional text message, a code, date and time, is
shown to indicate the fault type.

Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in internal fault mode. All other output contacts are released and locked for
the internal fault. The IED continues to perform internal tests during the fault
situation.

The internal fault code indicates the type of internal IED fault. When a fault
appears, record the code so that it can be reported to ABB customer service.

82 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting

GUID-DFF011AA-989D-4D59-B7A0-A282FEAD48D9 V1 EN

Figure 73: Fault indication

Table 17: Internal fault indications and codes


Fault indication Fault code Additional information
Internal Fault 2 An internal system error has occurred.
System error
Internal Fault 7 A file system error has occurred.
File system error
Internal Fault 8 Internal fault test activated manually by
Test the user.
Internal Fault 10 Watchdog reset has occurred too many
SW watchdog error times within an hour.
Internal Fault 43 Faulty Signal Output relay(s) in card
SO-relay(s),X100 located in slot X100.
Internal Fault 45 Faulty Signal Output relay(s) in card
SO-relay(s),X120 located in slot X120.
Internal Fault 46 Faulty Signal Output relay(s) in card
SO-relay(s),X130 located in slot X130.
Internal Fault 53 Faulty Power Output relay(s) in card
PO-relay(s),X100 located in slot X100.
Internal Fault 55 Faulty Power Output relay(s) in card
PO-relay(s),X120 located in slot X120.
Internal Fault 56 Faulty Power Output relay(s) in card
PO-relay(s),X130 located in slot X130.
Internal Fault 62 Card in slot X000 is wrong type.
Conf. error,X000
Internal Fault 63 Card in slot X100 is wrong type or does
Conf. error,X100 not belong to the original composition.
Internal Fault 65 Card in slot X120 is wrong type, is
Conf. error,X120 missing or does not belong to the original
composition.
Internal Fault 66 Card in slot X130 is wrong type, is
Conf.error,X130 missing or does not belong to the original
composition.
Internal Fault 72 Card in slot X000 is faulty.
Card error,X000
Internal Fault 75 Card in slot X120 is faulty.
Card error,X120
Internal Fault 76 Card in slot X130 is faulty.
Card error,X130
Internal Fault 79 LHMI module is faulty. The fault
LHMI module indication may not be seen on the LHMI
during the fault.
Table continues on next page

611 series 83
Operation Manual
Section 7 1MRS757453 A
Troubleshooting

Fault indication Fault code Additional information


Internal Fault 80 Error in the RAM memory on the CPU
RAM error card.
Internal Fault 81 Error in the ROM memory on the CPU
ROM error card.
Internal Fault 82 Error in the EEPROM memory on the
EEPROM error CPU card.
Internal Fault 83 Error in the FPGA on the CPU card.
FPGA error
Internal Fault 84 Error in the RTC on the CPU card.
RTC error

7.2.2 Warnings
Warnings are indicated with the text Warning additionally provided with the
name of the warning, a numeric code and the date and time on the LHMI. The
warning indication message can be manually cleared.

If a warning appears, the name and code should be recorded so that they can be
provided to the ABB customer service.

GUID-9EE0CFE1-0DB1-46B7-96A3-F3A0B6CC8018 V1 EN

Figure 74: Warning

Table 18: Warning indications and codes


Warning indication Warning code Additional information
Warning 10 A watchdog reset has occurred.
Watchdog reset
Warning 11 The auxiliary supply voltage has dropped
Power down det. too low.
Warning 20 Error when building the IEC 61850 data
IEC61850 error model.
Warning 21 Error in the Modbus communication.
Modbus error
Warning 24 Error in the Data set(s).
Dataset error
Warning 26 Error in the GOOSE control block(s).
GOOSE contr. error
Warning 27 Error in the SCL configuration file or the
SCL config error file is missing.
Warning 28 Too many connections in the
Logic error configuration.
Warning 30 Error in the GOOSE connections.
GOOSE input error
Table continues on next page

84 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting

Warning indication Warning code Additional information


Warning 32 Error in the GOOSE message receiving.
GOOSE Rx. error
Warning 40 A new composition has not been
Unack card comp. acknowledged/accepted.
Warning 50 Error in protection communication.
Protection comm.

7.2.3 LED and display messages


Usually when a LED is lit, an indication is shown on the LHMI and event 10 is
generated.

7.3 Correction procedures

7.3.1 Rebooting the software

1. Select Main menu/Configuration/General/Software reset and press .


2. Change the value with or and press .

7.3.1.1 Restoring factory settings

In case of configuration data loss or any other file system error that prevents the
IED from working properly, the whole file system can be restored to the original
factory state. All default settings and configuration files stored in the factory are
restored.

1. Select Main menu/Configuration/General/Factory setting and press .


2. Set the value with or and press .
3. Confirm by selecting Yes with or and press again

The IED restores the factory settings and restarts. Restoring takes 1-3 minutes.
Confirmation of restoring the factory settings is shown on the display a few
seconds, after which the IED restarts.

Avoid unnecessary restoring of factory settings, because all the


parameter settings that are written earlier to the relay will be
overwritten with the default values. During normal use, a sudden
change of the settings can cause a protection function to trip.

611 series 85
Operation Manual
Section 7 1MRS757453 A
Troubleshooting

To restore factory settings from bootloader mode, press ESC +


KEY simultaneously for 5 seconds.

7.3.1.2 Setting the password

If user authorization is off or the user is logged in as an administrator, user


passwords can be set via the LHMI or WHMI or with PCM600.

The password can be set to write mode with engineer or operator


rights but the changes to the password are not saved.

1. Select Main menu/Configuration/Authorization.


2. Select the password to be reset with or .
3. Press , change the password with or and press again.
4. Repeat steps 2 and 3 to set the rest of the passwords.

7.3.1.3 Identifying IED application problems

• Check that the function is on.


• Check the blocking.
• Check the mode.
• Check the measurement value.
• Check the connection to trip and disturbance recorder functions.
• Check the channel settings.

Inspecting the wiring


The physical inspection of wiring connections often reveals the wrong connection
for phase currents or voltages. However, even though the phase current or voltage
connections to IED terminals might be correct, wrong polarity of one or more
measurement transformers can cause problems.

• Check the current or voltage measurements and their phase information from
Main menu/Measurements.
• Check that the phase information and phase shift between phases is correct.
• Correct the wiring if needed.
• Check the actual state of the connected binary inputs from Main menu/
Monitoring/I/O status/Binary input values.
• Test and change the relay state manually in Main menu/Tests/Binary outputs.

Sample data interruptions


Occasionally IEDs can receive corrupted or faulty measurement data during
runtime. In these cases the operation system halts the corresponding application
execution until correct data is received. In case of permanent faults, the

86 611 series
Operation Manual
1MRS757453 A Section 7
Troubleshooting

measurement chain should be checked to remove the origin of the faulty


measurement data.

In case of persistent faults originating from IED's internal faults,


contact ABB for repair or replacement actions.

611 series 87
Operation Manual
88
1MRS757453 A Section 8
Commissioning

Section 8 Commissioning

8.1 Commissioning checklist

Familiarize yourself with the IED and its functionality before you start the
commissioning work.
• Ensure that you have all the needed station drawings such as single line and
wiring diagrams.
• Ensure that your version of the technical manual applies to the IED version
you test.
• Ensure that your setting software and connectivity packages work with the
IED version you test.
• Find out if you need any additional software.
• Ensure that you have the IED settings either on paper or in electronic format.
The settings and logic should be well documented.
• Inspect the settings to ensure that they are correct.
• Ensure that you have the correct cable to connect your PC to the IED's
communication port. The RJ-45 port supports any CAT 5 Ethernet cable but
the recommendation is STP.
• Test your PC's communication port before you go to the site.
• Find out who to contact if you have trouble and make sure you have a means
to contact them.
• Find out who is responsible for the settings.
• Ensure that you have with you the proper test equipment and all needed
connection cables.
• Ensure that the owner of the switchgear familiarizes you with the work site
and any special aspects of it.
• Ensure that you know how to operate in emergency situations. Find out where
the first aid and safety materials and exit routes are.

8.2 Checking the installation

8.2.1 Checking the power supply


Check that the auxiliary supply voltage remains within the permissible input
voltage range under all operating conditions. Check that the polarity is correct
before powering the IED.

611 series 89
Operation Manual
Section 8 1MRS757453 A
Commissioning

8.2.2 Checking of CT circuits


Check that the wiring is in strict accordance with the supplied connection diagram.

Correct possible errors before continuing to test the circuitry.

The CTs must be connected in accordance with the terminal diagram provided with
the IED, both with regards to phases and polarity. The following tests are
recommended for every primary CT or CT core connected to the IED.

• Primary injection test to verify the current ratio of the CT, the correct wiring
up to the protection IED and correct phase sequence connection (that is L1,
L2, L3.)
• Polarity check to prove that the predicted direction of the secondary current
flow is correct for a given direction of the primary current flow. This is an
essential test for the proper operation of the directional function, protection or
measurement in the IED.
• CT secondary loop resistance measurement to confirm that the current
transformer secondary loop DC resistance is within specification and that there
are no high resistance joints in the CT winding or wiring.
• CT excitation test to ensure that the correct core in the CT is connected to the
IED. Normally only a few points along the excitation curve are checked to
ensure that there are no wiring errors in the system, for example, due to a
mistake in connecting the CT's measurement core to the IED.
• CT excitation test to ensure that the CT is of the correct accuracy rating and
that there are no short circuited turns in the CT windings. Manufacturer's
design curves should be available for the CT to compare the actual results.
• Earthing check of the individual CT secondary circuits to verify that each three-
phase set of main CTs is properly connected to the station earth and only at
one electrical point.
• Insulation resistance check.
• Phase identification of CT shall be made.

Both the primary and the secondary sides must be disconnected


from the line and the IED when plotting the excitation characteristics.

If the CT secondary circuit is opened or its earth connection is


missing or removed without the CT primary being de-energized
first, dangerous voltages may be produced. This can be lethal and
cause damage to the insulation. The re-energizing of the CT
primary should be prohibited as long as the CT secondary is open
or unearthed."

90 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning

8.2.3 Checking VT circuits


Check that the wiring is in strict accordance with the supplied connection diagram.

Correct possible errors before continuing to test the circuitry.

Test the circuitry.

• Polarity check
• VT circuit voltage measurement (primary injection test)
• Earthing check
• Phase relationship
• Insulation resistance check

The polarity check verifies the integrity of circuits and the phase relationships. The
polarity must be measured as close to the IED as possible to ensure that most of the
wiring is also checked.

The primary injection test verifies the VT ratio and the wiring all the way from the
primary system to the IED. Injection must be performed for each phase-to-neutral
circuit and each phase-to-phase pair. In each case, voltages in all phases and
neutral are measured.

8.2.4 Checking binary input and output circuits

8.2.4.1 Binary input circuits

Preferably, disconnect the binary input connector from the binary input cards.
Check all connected signals so that both input level and polarity are in accordance
with the IED specifications.

8.2.4.2 Binary output circuits

Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and voltage are in accordance with
the IED specifications.

8.3 Authorizations

8.3.1 User authorization


The user categories have been predefined for LHMI and WHMI, each with
different rights and default passwords.

611 series 91
Operation Manual
Section 8 1MRS757453 A
Commissioning

Passwords are settable. LHMI password must be at least four and WHMI password
at least nine characters. Maximum number of characters is 20 for the WHMI
password and 8 for the LHMI password. Only the following characters are accepted:
• Numbers 0-1
• Letters a-z, A-Z
• Space
• Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~

User authorization is disabled by default and can be enabled via the


LHMI or WHMI Main Menu/Configuration/Authorization.

Table 19: Predefined user categories


Username LHMI WHMI password User rights
password
VIEWER 0001 remote0001 Only allowed to view
OPERATOR 0002 remote0002 Authorized to make operations
ENGINEER 0003 remote0003 Allowed to change IED parameters, but no
operation rights
ADMINISTRATOR 0004 remote0004 Full access

For user authorization for PCM600, see PCM600 documentation.

8.4 Using PCM600

8.4.1 Setting the communication between IEDs and PCM600


The communication between the IED and PCM600 is independent of the used
communication protocol within the substation or to the NCC. It can be seen as a
second channel for communication.

The communication media is always Ethernet and the protocol is TCP/IP.

Each IED has an Ethernet front connector for PCM600 access. Depending on the
station concept and the used station protocol, additional Ethernet interfaces may be
available on the rear side of the IED. All Ethernet interfaces can be used to connect
PCM600.

When an Ethernet based station protocol is used, the PCM600 communication can
use the same Ethernet port and IP address. The IED is able to separate the
information belonging to the PCM600 dialog.

92 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning

To configure the physical connection and the IP addresses:

1. Set up or get the IP addresses of the IEDs.


2. Set up the PC for a direct link or connect the PC or workstation to the network.
3. Configure the IED IP addresses in the PCM600 project for each IED. The
addresses are used for communication by the OPC interface of PCM600.

8.4.1.1 Communication options

Two options are available for the connection of PCM600 to the IED.

• Direct point to point link between PCM600 and the IED


• Indirect link via a station LAN or from remote via a network

Point to point link


The IED is provided with an RJ-45 connector on the LHMI. The connector is
mainly for configuration and setting purposes. Any Ethernet cable can be used but
it is recommended to use the shielded twisted pair cable.

The IED has a DHCP server for the front interface. The DHCP server assigns an IP
address to the computer connected to the front interface. The computer's LAN
interface has to be configured to obtain the IP address automatically.

LAN or WAN network


In TCP/IP networking, a LAN is often but not always implemented as a single IP
subnet. A router connects LANs to a WAN. In IP networking, the router maintains
both a LAN address and a WAN address. Design considerations for computer
networks cover a wide range of topics including layout, capacity planning, and
security. To some extent, the network configuration also depends on user preferences.

8.4.1.2 Setting communication parameters

The IP address and the corresponding mask can be set via the LHMI for the rear
port. The front port uses a fixed IP address 192.168.0.254. The front port also uses
DHCP.

Each Ethernet interface has a factory default IP address when the complete IED is
delivered.

Setting the front communication


To set up a standard PC with Microsoft Windows operating system for front
communication:

611 series 93
Operation Manual
Section 8 1MRS757453 A
Commissioning

1. To open Network Connections, click Start, point to Settings, click Control


Panel, and then double-click Network Connections.
2. Double-click the connection that you want to configure, and then click
Properties.
3. Select the TCP/IP protocol from the list of configured components using this
connection and click Properties.

A071162 V1 EN

Figure 75: Selecting TCP/IP protocol

4. Select Obtain an IP address automatically and Obtain DNS server


address automatically.

94 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning

A071224 V1 EN

Figure 76: Obtaining IP address automatically

5. Close all open windows by clicking OK and start PCM600.

Administrator rights are requested to change the configuration


as described above.

Setting the rear communication


To set up a standard PC with MicroSoft Windows operating system for rear
communication:

1. To open Network Connections, click Start, point to Settings, click Control


Panel, and then double-click Network Connections.
2. Double-click the connection that you want to configure, and then click
Properties.
3. Select the TCP/IP protocol from the list of configured components using this
connection and click Properties.

611 series 95
Operation Manual
Section 8 1MRS757453 A
Commissioning

A071162 V1 EN

Figure 77: Selecting TCP/IP protocol

4. Choose Use the following IP address. Enter an IP address and a subnet


mask. Make sure that the IP address is unique, that is not used by any other
IED on the network.

96 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning

A071164 V1 EN

Figure 78: Setting IP address and subnet mask

5. Close all open windows by clicking OK and start PCM600.

Administrator rights are requested to change the configuration


as described above.

Setting IED's IP address in PCM600


In PCM600 the IED's IP address can be defined via the first window of the wizard
by including a new IED in the project or by entering the IED's IP address in the
Object Properties window.

1. Select the IED to which you want to define the IP address.


2. Open the Object Properties window.
3. Place the cursor in the IP Address row and enter the IP address.

The used method depends on the time at which the IP address is available.
Defining IP address in the Object Properties windows allows changing the IP
address at any time.

611 series 97
Operation Manual
Section 8 1MRS757453 A
Commissioning

8.5 Setting IED and communication

8.5.1 Communication settings


The IED is provided with an RJ-45 connector on the LHMI. The connector is
mainly used for configuration and setting purposes. The fixed IP address for the
front port is 192.168.0.254.

Different communication ports are available via optional communication modules.


Ethernet RJ-45 and optical Ethernet LC are the two rear port Ethernet
communication options. Rear port Ethernet is intended for station bus
communication. Communication protocols used via Ethernet ports are IEC
61850-8-1 and Modbus TCP/IP. The RS-485 twisted pair is used for rear port
communication. Modbus RTU/Modbus ASCII is the protocol available for serial
communication.

For more information, see the communication protocol manuals and


the technical manual.

If the protocol does not operate as expected, check that other serial
protocols are not using the COM port.

8.5.1.1 Serial communication ports and drivers

Depending on the hardware configuration, the IED can be equipped with one or
several UART-based serial communication ports. The communication ports can be
either galvanic (RS-485) or fibre-optic. The IED uses serial ports and drivers as
different types of serial communication protocol links.

Serial ports are called COM1, COM2 and so on, depending on the number of serial
ports in the IED hardware configuration. Each COM port driver has its own setting
parameters found via the LHMI in Configuration/Communication/COMn (n= 1,2,
…).

Since the same IED usually supports a variety of different communication


hardware options, all COM port driver setting parameters are not relevant for every
communication hardware type.

98 611 series
Operation Manual
1MRS757453 A Section 8
Commissioning

Table 20: COM port parameters in different HW options


COM parameter Values Hardware options1)
Fiber mode 0 = No fiber Used in the fiber-optic mode only.
Note that No fiber mode is the same
1 = Fiber light ON/loop as the galvanic mode.
2 = Fiber light OFF/loop
3 = Fiber light ON/star
4 = Fiber light OFF/star
Serial mode 0 = RS485 2wire For galvanic modes. RS-type
depends on the communication card
1 = RS485 4wire used.
Note that this setting parameter is
relevant only if Fiber mode is set to
No Fiber.
Baudrate 1 = 300 All modes
2 = 600
3 = 1200
4 = 2400
5 = 4800
6 = 9600
7 = 19200
8 = 38400
9 = 57600
10 = 115200 [bits/sec]

1) When fiber mode is used, the Serial mode parameter value must be RS485 2wire.

In addition to setting the COM parameter, a communication card


with many hardware options may also require changing the jumpers
on the communication card.

Connection of a serial communication protocol to a specific serial port

The serial communication protocol (instance) settings include a setting parameter


called Serial port n (n = protocol instance number). Setting options for this
parameter are COM1, COM2 and so on. Select the desired serial port for the
protocol instance through this parameter.

All link setting parameters are not found in the COMn settings.
Additional link setting parameters are found in the setting
parameter list of the used serial protocol, since some serial protocol
standards allow changes in link parameters, while other protocol
standards do not.

611 series 99
Operation Manual
Section 8 1MRS757453 A
Commissioning

8.5.1.2 Serial link diagnostics and monitoring

Serial communication diagnostics and monitoring is divided between the serial link
driver and the serial communication protocol. The lower level physical and protocol-
independent aspects of the UART-based serial communication are monitored in the
serial link driver. Diagnostic counters and monitoring values are found via the
LHMI in Monitoring/Communication/COMn (n= 1,2,…).

Depending on the communication protocol, the serial driver software receives


single characters or complete protocol frames, based on the frame start/stop
characters or on timing.

Monitoring data for a COM channel can be divided into basic and detailed
diagnostic counters.

Table 21: Monitoring data for a COM channel


Parameter Range Type Description
Characters 0…2147483646 Basic Number of separate characters received.
received
Frames received 0…2147483646 Basic Number of successfully received complete
frames.
Frames discarded 0…2147483646 Basic Number of frames discarded.
Frames 0…2147483646 Basic Number of frames transmitted.
transmitted
CD Lost 0…2147483646 Detailed Number of carrier-detect signal lost during
receive.
Collision 0…2147483646 Detailed Number of collisions detected.
CTS Timeout 0…2147483646 Detailed Number of clear-to-send signal timeout
errors.
Transmission 0…2147483646 Detailed Number of transmission timeout errors.
timeout
Parity errors 0…2147483646 Detailed Number of character parity errors detected.
Overrun errors 0…2147483646 Detailed Number of character overrun errors
detected.
Framing errors 0…2147483646 Detailed Number of character overrun errors
detected.
Link status 1 1 = Reset counters (by entering 1 the
diagnostic counters are reset)

Whether all diagnostic counters are relevant depends on the communication


hardware and communication protocol.

100 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

Table 22: Basic diagnostic counters


Counter Function
Characters received Counts all incoming non-erroneous characters.
This counter operates regardless of if the serial
driver is set to detect a whole protocol link frame
or just separate characters.
Frames received Counts all protocol specific non-erroneous
frames received. Protocol-specific frames can be
based on timing (for example, Modbus RTU) or
on special start and stop characters (for
example, Modbus ASCII).
Frames discarded Counts all protocol-specific erroneous frames
received. If the driver detects an error while
receiving a frame, the frame is automatically
discarded. This also means that the protocol in
question will never receive a faulty frame from
the driver. When this counter is increased, one of
the detailed error counters is also incremented.
Frames transmitted Counts all protocol-specific frames transmitted
from the COM channel.

Table 23: Detailed error counters


Counter Function
Collision Counts transmission collisions. Used in RS-485
mode by some protocols where transmissions
could collide.
Parity errors Counts parity errors detected in characters.
Overrun errors Counts overrun errors detected in characters.
Framing errors Counts framing errors detected in characters

Table 24: Link status


Parameter Function
Link status Link status in write direction: By writing 1 to the
parameter the diagnostic counters are reset to 0.
Link status in monitoring direction: If the driver is
in use by any communication protocol, the
monitoring value shows 1. In other case, the
value is 0.

8.5.1.3 Defining Ethernet port settings

Change the Ethernet port settings primarily via PCM600. Then


PCM600 is able to export consistent configuration to SYS600.
Ethernet port settings are recommended to be changed only when
the device is stand-alone and properly configured.

611 series 101


Operation Manual
Section 8 1MRS757453 A
Commissioning

1. Select Main menu/Configuration/Communication/Ethernet/Rear port.


2. Define the settings for the Ethernet port.
• IP address
• Subnet mask
• Default gateway of the optional rear port Ethernet connector

8.5.1.4 Defining serial port settings

1. Select Main menu/Configuration/Communication/COM1 or COM2.


2. Define the settings for the serial port.
It is possible to change the general serial communication parameters per port.
Select fibre or galvanic mode with the proper baud rate, parity and delays
depending on the system architecture and the selected physical
communication port.

8.5.1.5 Setting communication protocol parameters

1. Select Main menu/Configuration/Communication/<protocol>.


2. Change the protocol specific settings.
Possible settings to be changed are, for example, the selected communication
port, address and link mode.

8.5.1.6 Connecting jumper connectors

See the technical manual for details on jumper connectors.

8.5.1.7 Communication checklist

1. Check the physical connections.


2. After the settings are changed, allow them to be stored in the non-volatile
memory (S character on the icon area of the LHMI).
3. If the WHMI connection is missing, enable the IED's WHMI setting and
prevent the Web browser from attempting to use a proxy via Internet
Options/Connections/LAN Settings/Advanced/Exceptions (for example
192.168.*.*;).
4. Ping the unit.
Verify that the IED has been correctly configured to accept messages with the
IP address.
5. Use the LHMI to enable the WHMI configuration if a ping response is
received from the unit but the WHMI does not respond.

102 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

5.1. Clear the browser of cached pages.


5.2. Logout and log back in.
6. Install a TCP packet sniffer to see what is happening on the network.
7. Clear the ARP table.
8. See the IED's technical manual to determine if the jumpers on the
communication board are correct.

If this protocol does not operate as expected, check that other serial
protocols are not using the COM port also.

8.5.2 Setting the local HMI

8.5.2.1 Changing the local HMI language

1. Select Main menu/Language and press .


2. Change the language using or .
3. Press to confirm the selection.
4. Commit the changes.

GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN

Figure 79: Changing the LHMI language

To change the language using a shortcut, press and


simultaneously anywhere in the menu.

8.5.2.2 Adjusting the display contrast

Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.

• To increase the contrast, press simultaneously and .


• To decrease the contrast, press simultaneously and .

The selected contrast value is stored in the non-volatile memory if you are logged
in and authorized to control the IED. After an auxiliary power failure, the contrast
is restored.

611 series 103


Operation Manual
Section 8 1MRS757453 A
Commissioning

8.5.2.3 Changing display symbols

Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and
IEC-ANSI.

1. Select Main Menu/Configuration/HMI/FB naming convention and press


.
2. Change the display symbols with or .
3. Press to confirm the selection.

The IED has to be rebooted if the WHMI display symbols are


changed. With the LHMI, the change takes effect immediately.

8.5.2.4 Changing the default view

The default view of the display is Measurements unless set otherwise.

1. Select Main menu/Configuration/HMI/Default view and press .


2. Change the default view with or .
3. Press to confirm the selection.

8.5.2.5 Setting the system time and time synchronization

1. Select Main menu/Configuration/Time/System time.


2. Select the parameter with or .
3. Press , change the value with or and press again.
4. Repeat steps 2 and 3 to set the rest of the system time parameters.
5. Select Main menu/Configuration/Time/Synchronization/Synch source
and press .
6. Select the time synchronization source with or .
7. Press to confirm the selection.

Setting the daylight saving time


The IED can be set to determine the correct date for the DST shift every year. The
UTC time is used to set the DST.

1. Set the DST on day and DST off day parameters to define on which week day
the time shift occurs.
2. Set the DST on date and DST off date parameters to define on which month
and week the time shift occurs.
The DST on/off date must precede the selected DST on/off day and be within
the same week as the DST shift.

104 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

Table 25: Possible date values for DST change on Sunday


Day of the DST shift DST on/off date (dd)
First Sunday of the month 1
Second Sunday of the month 8
Third Sunday of the month 15
Fourth Sunday of the month 22
Last Sunday, if the month has 30 days 24
Last Sunday, if the month has 31 days 25

For example, if the DST is observed from the last Sunday in March to the last
Sunday in October and the time shift occurs at 01:00 UTC, the setting
parameters are:

DST on time: 01:00


DST on date: 25.03
DST on day: Sun
DST off time: 01:00
DST off date: 25.10
DST off day: Sun

Set the DST on day and DST off day to "not in use" to determine the
exact date and time for the DST shift. Repeat the setting yearly, as
the time for the DST shift is not on the same date every year.

To disable the DST, set the DST offset parameter to "0 min".

8.5.3 Setting IED parameters

8.5.3.1 Defining setting groups

Selecting a setting group for editing

1. Select Main Menu/Settings/Edit setting group.


2. Select the setting group to be edited with or .
3. Press to confirm the selection.
4. Edit the settings.

611 series 105


Operation Manual
Section 8 1MRS757453 A
Commissioning

GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN

Figure 80: Selecting a setting group

Browsing and editing setting group values

1. Select Main menu/Settings/Settings and press .


2. Select the setting group to be viewed with or and press to confirm
the selection.

GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN

Figure 81: Selecting a setting group

3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to
select a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.

GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN

Figure 82: Setting group parameter

6. To select a setting group value, press and to edit the value press .

106 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN

Figure 83: Selecting the setting group value

Only values within the selected setting group can be changed.


7. Press or to change the value and to confirm the selection.

GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN

Figure 84: Editing the setting group value

The active setting group is indicated with an asterisk * .

Activating a setting group


IED settings are planned in advance for different operation conditions by
calculating setting values to different setting groups. The active setting group can
be changed by the IED application or manually from the menu.

1. Select Main menu/Settings/Setting group/Active group and press .

GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN

Figure 85: Active setting group

2. Select the setting group with or .


3. Press to confirm the selection or to cancel.

GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN

Figure 86: Selecting the active setting group

4. Commit the settings.

611 series 107


Operation Manual
Section 8 1MRS757453 A
Commissioning

Remember to document the changes you make.

8.5.3.2 IED parametrization

IED parameters are set via the LHMI, WHMI or PCM600.

Setting parameters need to be calculated according to the electrical network


conditions and the electrical characteristics of the protected equipment. The IED's
settings need to be verified before the IED is connected to a system.

Document all changes to parameter settings.

For more information, see PCM600 documentation.

8.5.3.3 Defining disturbance recorder channel settings

1. Select Main Menu/Configuration/Disturbance recorder/Channel settings.


2. Press or to select the wanted channel and parameter.
3. To change channel settings, press .

Each analog channel has an equal set of parameters and correspondingly, each
binary channel has an equal set of parameters.

8.5.3.4 Configuring analog inputs

1. Select Main Menu/Configuration/Analog inputs.


2. Select the analog input to be configured with or .
3. Press , change the value with or and press again.
• For CTs, the secondary current and primary current need to be set to the
correct values.
• For VTs, the secondary voltage and primary voltage need to be set to
the correct values.

108 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

8.6 Testing IED operation

The IED has to be in the test mode before the digital outputs and certain output
signals of protection and other functions can be activated.

8.6.1 Selecting the test mode


The test mode can be activated using the LHMI. The green Ready LED will be
flashing to indicate that the test mode is activated.

The Ready LED also flashes if the IED detects a diagnostic failure.
Check the test mode setting and the IED's IRF alarm contact status
to find the reason for the failure.

The test mode is useful for simulated testing of functions and outputs without
providing current inputs.

1. Select Main menu/Tests/IED test/Test mode and press .

GUID-774C947C-70BA-479D-B795-C9222BD17715 V1 EN

Figure 87: Entering test mode

2. Select the test mode status with or .


3. Press to confirm the selection.

If you do not cancel the test mode, it remains on and the Ready
LED remains flashing.

8.6.2 Testing the digital I/O interface


To activate or deactivate, for example, a digital output:

1. Select Main menu/Tests/Binary outputs/X100 (PSM)/X100-PO1 and press


.
2. Select the value with or .
3. Press to confirm the selection.

611 series 109


Operation Manual
Section 8 1MRS757453 A
Commissioning

8.6.3 Testing functions


Activate or deactivate an output signal for protection or other function to test the
function.

1. Select Main Menu/Tests/Function tests/Current protection/<function


block name> and press .
2. Select the output signal to be activated or deactivated with or and
press .
3. To deactivate all output signals for the function, select Reset with or
and press .

8.6.4 Selecting the internal fault test


The internal fault may be tested by using the LHMI. When enabling the test, the
internal relay fault output contact is activated, the green Ready LED will be
blinking and internal fault test indication is shown on the LHMI. See Technical
Manual for internal relay fault output contact location.

Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words,
protection functions can operate and trip the outputs when the
internal fault is tested.

1. Select Main menu/Tests/IED test/Internal fault test and press .

GUID-C60A750A-B76E-4676-A0AE-05BFF595A5D2 V1 EN

Figure 88: Internal fault test

2. Select the value with or .


3. Press to confirm the selection.

8.7 ABB Product Data Registration

The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.

110 611 series


Operation Manual
1MRS757453 A Section 8
Commissioning

After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other
indications. If PCM600 is not connected to the IED, the indication is seen again
after the IED's reboot.

GUID-4DC42A7C-150D-4B60-A4EC-679581F98F44 V1 EN

Figure 89: LCT indication

The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status.

611 series 111


Operation Manual
112
1MRS757453 A Section 9
Glossary

Section 9 Glossary

ANSI American National Standards Institute


ARP Address Resolution Protocol
CAT 5 A twisted pair cable type designed for high signal integrity
COMTRADE Common format for transient data exchange for power
systems. Defined by the IEEE Standard.
CPU Central processing unit
CSV Comma-separated values
CT Current transformer
DHCP Dynamic Host Configuration Protocol
DNS Domain Name System
DST Daylight-saving time
EEPROM Electrically erasable programmable read-only memory
EMC Electromagnetic compatibility
Ethernet A standard for connecting a family of frame-based
computer networking technologies into a LAN
FB Function block
Firmware System software or hardware that has been written and
stored in a device's memory that controls the device
FPGA Field-programmable gate array
GOOSE Generic Object-Oriented Substation Event
HMI Human-machine interface
HW Hardware
IEC International Electrotechnical Commission
IEC 61850 International standard for substation communication and
modeling
IEC 61850-8-1 A communication protocol based on the IEC 61850
standard series
IED Intelligent electronic device
IP Internet protocol
IP address A set of four numbers between 0 and 255, separated by
periods. Each server connected to the Internet is

611 series 113


Operation Manual
Section 9 1MRS757453 A
Glossary

assigned a unique IP address that specifies the location


for the TCP/IP protocol.
LAN Local area network
LC Connector type for glass fibre cable
LCD Liquid crystal display
LCP Liquid crystal polymer
LCT Life cycle traceability
LED Light-emitting diode
LHMI Local human-machine interface
Modbus A serial communication protocol developed by the
Modicon company in 1979. Originally used for
communication in PLCs and RTU devices.
Modbus ASCII Modbus link mode. Character length 10 bits.
Modbus RTU Modbus link mode. Character length 11 bits.
Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and Ethernet to
carry data between devices
NCC Network control center
OPC Object linking and embedding for process control
PA Polyamide
PBT Polybutylene terephthalate
PC Personal computer; Polycarbonate
PCM600 Protection and Control IED Manager
R/L Remote/Local
RAM Random access memory
RJ-45 Galvanic connector type
RoHS Restriction of the use of certain hazardous substances in
electrical and electronic equipment
ROM Read-only memory
RS-485 Serial link according to EIA standard RS485
RTC Real-time clock
SCL XML-based substation description configuration language
defined by IEC 61850
STP Shielded twisted-pair
SVG Scalable vector graphics
SW Software
TCP/IP Transmission Control Protocol/Internet Protocol

114 611 series


Operation Manual
1MRS757453 A Section 9
Glossary

UTC Coordinated universal time


VT Voltage transformer
WAN Wide area network
WHMI Web human-machine interface

611 series 115


Operation Manual
116
117
Contact us

1MRS757453 A © Copyright 2011 ABB. All rights reserved.