Report On Workshop: Submitted by
Report On Workshop: Submitted by
Report On Workshop: Submitted by
SUBMITTED BY
NAME : V.KRISHNAN
2. Standards:-
3.Ferranti Effect:
During light load / No load conditions in Long/ Very Long, HV / EHV line, Vr > Vs due to
shunt capacitance. This is called Ferranti effect. It is more pronounced with increase
frequency. In DC there is no Ferranti effect since there is no Capacitive reactance effect.
Receiving end voltage will be higher than the sending end voltage at no load condition
and low load condition in EHV/HV lines and long transmission lines.
• When the distance between the conductor and ground is low then the shunt
capacitance will be high ( Hill areas )
• Transposition is required in long transmission line to reduce the unbalance in
line parameters
Surge Impedance Loading is a very essential parameter when it comes to the study
of power systems as it is used in the prediction of maximum loading capacity of
transmission lines.
a) Ferranti Effect
Plot kW, kVAR
As per above simulation in Sending end voltage is greater than receiving end
voltage
b) At SIL
Voltage at sending end and receiving end will be
same at SIL. (Here SIL is calculated with R=0 and simulation R = 30 ohm hence the drop in
voltage due to R. Repeat the simulation with very small R value)
In this case surge impedance load is connected to bus 2 as per calculation, Now
voltage at the receiving end is controlled.
𝐿
Zs = √𝐶
𝑍 𝑅+𝑗𝑋
Which is derived from SIL = √𝑌 = √𝐺+𝑗𝐵
Interns of power
So in above simulation 480 MVA static load is connected in bus 2 and the receiving end
voltage is controlled
Identify the right shunt reactor value to reduce the Vr during no load
6. Types of Buses:-
1. Swing bus
2. PV bus ( Voltage control bus )
3. PQ bus ( load bus )
7. Types of Loads:-
Varies types of loads are there, ZIP load is called constant
Impedance load, constant current load, constant power load.
𝑽 𝟐 𝑽
P= P0[𝒂 ( ) + 𝒃 ( ) + 𝒄] where P = Real power, Q= Reactive power ,
𝐕𝟎 𝐕𝟎
𝐕 𝟐 𝐕
Q= Q0[𝐚 (𝐕𝟎) + 𝐛 (𝐕𝟎) + 𝐜] a – impedance, b – current, c – power
8. Simulation:-
Solve a question with combination on all type of loads and simulate to validate.
OLTC is used for changing the tap of the transformer while it is connected
to load.
Modelling of OLTC:-
Simulation:-
• choose the tap ratio to maintain the 11kv voltage within ±5 % tolerance for
the system shown in simulation when the 110 kv grid voltage fluctuates
from -17.5 % to 12.5 % and load changes from 10MW to 38 MW ( lumped
load is 100% constant power load )
Taps has to be designed in a way that for the following maximum and minimum
conditions the 11kv bus voltage fluctuations has to be within ±5 %
Conditions:-
Steps = 1.25
No of steps = 17
a) After providing taps to transformer simulation done for above four conditions
• From simulation results 11kv bus voltage is maintained for ±5% tolerance by
providing taps to transformer as modelled
tap changer:
It is used for providing taps for the transformer when it is not connected to load.
Percentage of the tap can be given in fixed tap row as per shown in the screenshot
Because of change in grid voltage, bus voltage the power of grid may change. To
maintain the power factor capacitor banks has to be connected parallel to the loads.
1. P = I2 R
2. P =√3VIcosɸ
3. Q = I2 X
4. Q = √3VIsinɸ
5. S = I2 Z
6. S = √3VI
7. S= √P 2 + Q2
P
8. cosɸ = S
Example:-
• Find out grid power factor for the given system. What is the capacitor
rating required to boost the grid power factor to 0.95 when the load of 38
MW, 0.8 PF load is connected to bus 2...
Validate the results with manual calculation
b) Reactive power flow from grid and Reactive power compensated by capacitor bank
• Grid PF is found from simulation 𝑐𝑜𝑠ɸ = 0.74
• Pf to be maintained 𝑐𝑜𝑠ɸ(𝑛𝑒𝑤) = 0.95
• Capacitor bank value calculated = 17.14 Mvar
From PF correction formula
• From simulation b) we can find out the reactive power demand of the load 22.8
Mvar is compensated by the capacitor bank (17.14 Mvar) and the reactive power
flow from grid is also reduced from 27.5 to 9.3 Mvar because the required
reactive power to maintain Pf at 0.95 is compensated by capacitor bank.
• Hence power factor correction at grid to 0.95 is done
Contingency Analysis: (Kindly note contingency and configuration are
different)
Example:
6.6/0.433
b) Conditions:
90% - is it Voltage or
Peak Generation
Power?
Normal Generation 100%
Minimum Generation 110%
90% - is it Voltage or
Peak load
Power
Normal load 70%
Minimum load 20%
c) Cases:
Procedure and screenshot for applying the conditions and cases in Etap:-
• In configuration manager cases can be created and In each case CBs also can be
close and open
c) Study case:
New study case – Generation peak, Load Peak ( Pg, Pd )
d) Edit study case:
a) Loading tab b) Alert tab:-
• Edit study case – loading tab – loading and generation category is assigned as
peak
• Alert tab - For all the equipments Critical, Marginal values can be given in
percentage. If the bus voltage is going beyond the critical or marginal limits alert
will be shown while running simulation.
e) Scenario wizard:
• For each study case new scenario has to be created and renamed as Pg Pd
scenario
• Then for each configuration status of each study case, Output report name has to
be changed then only for corresponding study case and configurations reports
will be generated
• After selecting Scenario , Study case , Configuration we have to Run the
simulation by clicking Run button
f) Study wizard:
o In study wizard all the scenario has to be added by clicking add button
then after adding all the scenarios we have to run the simulation
o In load flow analyzer all the study reports are shown here we can see for
what is the cases simulation has been done.
o Report type: General information, Bus results, Loads, Sources, Branch
results can be viewed in report type tab.
o All those reports can be exported in excel by clicking export.
Simulation reports:-
a) General:
b) Bus:
c) Branch
d)Load
e) Source
ETAP Practice
Modelling in ETAP
a) Simulation Questions 1,2,3
b) Inference from the result by using plot and data options
Effects:-
When a short circuit occurs, the current in the system increases to an abnormally high
value while the system voltage decreases to a low value.
1. The heavy current due to short-circuit causes excessive heating which may result
in fire or explosion. Sometimes short-circuit takes the form of an arc and causes
considerable damage to the system. For example, an arc on a transmission line
not cleared quickly will burn the conductor severely causing it to break, resulting
in a long time interruption of the line.
2. The low voltage created by the fault has a very harmful effect on the service
rendered by the power system. If the voltage remains low for even a few
seconds, the consumer’s motors may be shut down and generators on the power
system may become unstable.
5. For every 10 degree Celsius increase more than equipment insulation rated
temperature its life will be reduced by 50 %
Causes of fault:-
1. Insulation failure
2. Switching over voltage
3. Lightning
4. Overload
5. Equipment damage
6. Tree branches/ Birds
7. Wind / Ice loading
8. Environment / chemical pollution
Types of Faults:-
1. Symmetrical fault
2. Unsymmetrical fault
Symmetrical fault:-
➢ Line to line to line fault ( L-L-L)
➢ Line to line to line to ground fault ( L-L-L-G)
Unsymmetrical fault:-
• If the fault is near to source then the fault current will be high
because of low impedance between fault and source
• If the fault is away from the source then the fault current will be
low because of higher impedance
Example:-
• In this simulation bus 2,3,4 is faulted
• Fault current at bus 2 is higher than the fault current at bus 4
Sequence components:-
1. Z0 = Zs +2 Zm
2. X0 = 3X1
3. X1 = X2
√𝟑 𝐄𝐚𝟏
2. L-L fault current If = 𝒁𝟏+𝒁𝟐
𝟑 𝐄𝐚𝟏
3. L-L-G Fault current If = 𝒁𝟏+𝒁𝟐 𝑰𝑰 (𝒁𝒐+𝟑𝒁𝒏)
𝐄𝐚𝟏
4. Three phase fault current If =
𝒁𝟏+𝒁𝒇
Where
Ea1 – Positive sequence supply voltage
Z0 , Z1 , Z2 , - Zero, positive, Negative sequence Impedance
Zn - Neutral Impedance
Zf - Fault path impedance ( As per IEC 60909 Fault
path impedance is negligible )
1. Equipment Grounding:-
Non conducting metal part is connected to ground. Equipment
grounding is used to protect the equipment and personnel.
2. System Grounding:-
Neutral of the system is connected to ground. It is used to protect
the system. There are various types of system grounding.
1. Solid grounding
2. Resistance grounding
3. Reactance grounding
4. Resonance grounding
5. Ungrounded System
It is source voltage correction factor as per IEC 60909 minimum and maximum
values are given below
C max= 1.1
C min = 1.0
a)C-Max:
b)C-Min:
• Method A – Using the uniform ratio X/R in calculating the peak current
• Method B – Using the X/R ratio at the short circuit location in calculating the
peak current
• As per ANSI C37 standard pre-fault voltage can be fixed as shown in screenshot.
X/R Ratio:-
• It is the ratio of reactance and resistance. For any system reactance will be
greater than the resistance
• If resistance is greater than the reactance then there will be more loss
• So the X/R ratio has to be more than 1
• If the reactance value is very high then reactive drop will be high so the value has
to be optimum.
• As per IEC 62271 for 50 Hz system X/R = 14 (Relate with time constant and
Power factor, IEC 62271)
60 Hz system X/R = 17
Example:-
For the given system three phase and single phase fault current at bus 3has to be
find out.
Grid Parameters:
X/R = 14
KAsc = 40
Transformer Parameters:
Voltage = 33/11 KV
Base MVA = 25
Impedance = 10 %
Z tolerance = ±10
X/R = 20 (typical value taken)
If the fault is at bus 3, all the equipments impedance has to be calculated which is
connected till bus 3
Generator Impedance Per unit value can be calculated from following formulas.
• MVAsc = √𝟑 𝑲𝑽 𝑿 𝑲𝑨𝒔𝒄
𝐙𝐬 𝐚𝐜𝐭𝐮𝐚𝐥
• Zp.u = 𝐙𝐬 𝐛𝐚𝐬𝐞
• X/R = 14 so X= 14 R
• Z= √𝑹𝟐 + 𝑿𝟐
𝐄𝐚𝟏
2. Three phase fault current If = 𝒁𝟏+𝒁𝒇
Display the results at right place (19.05kV & 6.34kV at same bus???)
C) Manual and Simulation results are compared:
𝐕𝐦𝐚𝐱
2. Vrms = √𝟐
𝑽𝒎
3. Isym = Iss = |𝒁|√𝟐 (Initial Symmetrical RMS fault current ) ( Irms)
= 2 √𝟐 Isym
𝐈𝐦𝐚𝐱
6. Ip = Peak current = Irms = √𝟐
8. Idc.rms = √𝟐 X Isym
• The entire fault currents can be obtained from simulation also. Simulation
results given below
Simulation: (Where IEC 61363 is used, Why)
Physical Generator
• During transient period transient reactance will be lower than sub transient
reactance.
• And sub transient reactance will be lower than steady state reactance
• Xd” < Xd’ < Xd
• So that Transient fault current will be higher than the sub transient and steady
state fault current
• If” > If ‘ > If
• Induction machine fault current will decrease to steady state on 2 to 4 cycles
• Synchronous machine fault current will decrease to steady state on 6 to 8 cycles
1. Harmonic Analysis:
Objective:
1. Current Harmonics.
2. Voltage Harmonics.
Current Harmonics:
Voltage harmonics:
Sources Of Harmonics:
• Soft Starter.
• Electronic Ballast.
• Arc Furnace.
• Discharge Lamps
• Rectifier.
Effects of Harmonics:
Individual harmonic distortion is the ratio between the RMS value of the
individual harmonic and the RMS value of the fundamental.
𝐈𝐧
%IHD =
𝐈𝟏
I1
In = n
• As per the IEEE 519 standard, there are limits for voltage and current
harmonics.
Table:
1 Up To 1KV 5 8
Power Factor:
• The displacement power factor is the power factor due to the phase
shift between voltage and current at the fundamental line frequency.
• Displacement power factor = Cos (ɸ)
√∑n
h=1 Ih2
TDD = Load Current
K-Rated Transformer:
Harmonic Sequence:
• Harmonic sequence refers to the phasor rotation of the harmonic voltages and
currents with respect to the fundamental waveform.
• Harmonics are grouped into positive , negative and zero, sequence components.
• Pulse converter is used to reduce the harmonics. The higher the pulse, harmonics
level will be reduced.
• When the pulses are high then the Harmonics will be less
Mitigation of Harmonics:
1. Passive Filter
2. Active Filter
Passive Filter:
Passive or Line harmonic filters are also known as harmonic trap filters
and are used to eliminate or control more dominant lower order harmonics
specifically 5th, 7th, 11th and 13th.
Active Filter:
• Active filters are now relatively common in industrial applications for
both harmonic mitigation and reactive power compensation (i.e.,
electronic power factor correction).
• Shunt-connected active filters (i.e. parallel with the nonlinear load) are
the common configuration of the active filter.
𝐊𝐕 𝟐
Xbank perphase = 𝐌𝐕𝐀𝐫
Xbank = XL - Xc
𝐗𝐜
nXL = ( At resonance condition )
𝐧
XL = Lѡ
Where ѡ = 2ᴨF
𝐗𝐋
L= 𝟐ᴨ𝐅
Xc = n2 XL
𝟏
Xc = 𝐜ѡ
𝟏
C= 𝟐ᴨ𝐟𝐗𝐋
Example:
• In harmonic analysis Loads which are connected to the bus has to inject
harmonics to bus for that Loads-> harmonics tab -> select the source from
library
• That is 6 pulse device so 5th and 7th order harmonics will be injected by load
• Formula for Harmonics order by no of pulse= np±1
• Harmonics of the Bus 2 and Bus 13 are obtained from Harmonic report.
• Hence the harmonic level at bus 13 is reduced by adding the Harmonic filter
as designed.
Bus ID, Tag number, Standard , conductor typle Nominal voltage, Condition , Connection Nominal voltage, Condition , Connection Nominal voltage, Condition , Connection
Primary, secondary voltage, base MVA , % Primary, secondary voltage, base MVA , %
Primary, secondary voltage, base MVA , % impedance,
impedance, class , type, X/R value , Tap setting impedance, class , type, X/R value , Tap setting
2 winding transformer Id, Tag number , Service,Standard class , type, X/R value , Tap setting value , Grounding,
value , Grounding, positive , zero sequence value , Grounding, positive , zero sequence
phase shift
impedance, Impedance tolerance impedance, Impedance tolerance, Harmonics
Bus duct Id, Tag number , Service,Standard Type and material ( cu,al). Type and material ( cu,al). Type and material ( cu,al).
conductor type ( al, cu) , length , ground wire conductor type ( al, cu) , length , ground wire type,
conductor type ( al, cu) , length , ground wire type, R, X type, R, X values per km, configuration type , R, X values per km, configuration type , spacing ,
Transmission Line Id, Tag number , Service
values per km, configuration type , spacing , transposed spacing , transposed ,Postive, negative , zero transposed ,Postive, negative , zero sequence
sequence impedance impedance
voltage, current rating , connection, impedance voltage, current rating , connection, impedance
Reactor current Limiting Id, Tag number , Service voltage, current rating , connection, impedance
,zero sequence , positive sequence impedance ,zero sequence , positive sequence impedance
Mode of operation ( configuration ), Rated voltage Mode of operation ( configuration ), Rated voltage ,
Mode of operation ( configuration ), Rated voltage , X/R
, X/R ratio, power factor , MVA, MW , grounding X/R ratio, power factor , MVA, MW , grounding
Generator Id, Tag number , Service ratio, power factor , MVA, MW , grounding type, Qmin ,
type, zero sequence , negative sequence, type, zero sequence , negative sequence, transient
Qmax
transient reactance Xd" , Xd"/R reactance Xd" , Xd"/R, Harminics library
Rated Kv, Full load current (FLA ), Power factor, Rated Kv, Full load current (FLA ), Power factor, HP ,
Rated Kv, Full load current (FLA ), Power factor, HP , HP , Speed , Slip , No of poles , locked rotor Speed , Slip , No of poles , locked rotor current , PF,
Induction Machine Id, Tag number , Service
Speed , Slip , No of poles , locked rotor current , PF current , PF, Zero sequence , negative sequence Zero sequence , negative sequence impedance ,
impedance , Transient reactence Transient reactence, Harmonics
Rated Kv, Full load current (FLA ), Power factor, Rated Kv, Full load current (FLA ), Power factor, HP ,
Rated Kv, Full load current (FLA ), Power factor, HP , HP , Speed , Slip , No of poles , locked rotor Speed , Slip , No of poles , locked rotor current , PF,
Sytnchronous Machine Id, Tag number , Service
Speed , Slip , No of poles , locked rotor current , PF current , PF, Zero sequence , negative sequence Zero sequence , negative sequence impedance ,
impedance , Transient reactence Transient reactence, Harmonics
Reted Voltage , Power, PF, Constant current , Impedance, Reted Voltage , Power, PF, Constant current ,
Lumped load Id, Tag number , Service
Power load , Impedance, Power load , LRC
Static Load Id, Tag number , Service Reted Voltage , Power, PF Reted Voltage , Power, PF, Harmonics
Id, Tag number , Service,Standard, status, Rated Id, Tag number , Service,Standard, status, Rated
HV Circuit Breaker Id, Tag number , Service,Standard
voltage, rated currert voltage, rated currert , Short circuit current