Manual
Manual
Manual
INSTRUCTION MANUAL
__________________________________________________________________________
IMPORTANT MESSAGES
Read this manual and follow its intructions. Signal words such as DANGER, WARNING
and CAUTION will be followed by important safety information that must be carefully reviewed.
DANGER
Indicates a situation which will result in death, serious injury, and severe property damage if you
do not follow instructions.
Means that you might be seriously injured or killed if you do not follow instructions. Severe
WARNING
property damage might also occur.
CAUTION Means that you might be injured if you do not follow instructions. Equipment damage might
also occur.
Note: The contents of this manual will not become apart of or modify the warranty policy.
The terms of which are set forth at the end of this manual.
To avoid injury, you must read and follow all safety signs.
Keep the safety signs visible and in good shape. Never remove or cover any safety sign.
DANGER
Only qualified persons are to install, operate, or service this equipment according to all applicable
codes and established safety practices.
SAFETY CODES
Toshiba motor control is designed and built in accordance with the latest applicable provisions of
NEMA and the National Electrical Code. Installations must comply with all applicable state and
local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions
provided in this manual.
HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and
property damage.
• Turn off and lock out Primary and Control Circuit Power before servicing.
Model: ___________________________________
Chapter 1 - Introduction
This chapter is an introduction to the Toshiba JKSSS+ Series reduced voltage solid
state starter for medium voltage AC motors. It describes the basic configuration,
operation and unit features. It is highly recommended that new users read this
section thoroughly to gain a basic understanding of the starter system before
attempting to start up a unit. If you are already familiar with the JKSSS+ Series
starter, you may begin setup procedures immediately by proceeding to Chapter 2 –
Installation.
1.1 Overview
The standard JKSSS+ Series solid state starter is a complete NEMA Class E-2
motor controller designed for the starting, protection and control of AC medium
voltage motors. It contains the motor disconnect switch, motor circuit fuses,
control power transformer, a line isolation contactor, SCR stack assemblies, a
bypass contactor, low voltage controls and motor terminal blocks in that order.
An optional “soft start only” version is also available which is supplied without
the control power transformer, the disconnect switch and line isolation contactor.
(The soft start only model must be used with a customer supplied, mechanically
interlocked line start panel).
1.2 Specifications
JKSSS+ Series - 1
Overload will not reset until thermal capacity available in the motor is enough
Dynamic Reset Capacity for a successful restart. Starter learns and retains this information by
monitoring previous successful starts.
Phase Current Imbalance Imbalance Trip Level: 5 - 30% current between any two phases
Protection Imbalance Trip Delay: 1 -20 seconds
Over Current Protection Trip Level: 100 - 300% of motor FLA
(Electronic Shear Pin) Trip Delay: 1 - 20 seconds
Under Current Trip Level: 10 -90 % of motor FLA
Load Loss Trip Protection
Under Current Trip Delay: 1 - 60 seconds
Coast Down (Back Spin)
Coast Down Time Range: 1 - 60 minutes
Lockout Timer
Range: 1 - 6 successful starts per hour
Starts-per-hour Lockout Timer
Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Type / Rating Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA)
Run Indication Programmable
At Speed Indication Programmable
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Acceleration Adjustments
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 500% (VR or CR)
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Settings Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input
Data includes cause of event, time, date, voltage, power factor and current for
Up to 60 Events
each phase and ground fault current at time of event
JKSSS+ Series - 2
Metering Functions
Motor Load Percent of FLA
Current Data A, B, C Phase Current, Avg Current, Ground Fault (Option)
Thermal Data Remaining thermal register; thermal capacity to start
Avg Start Time, Avg Start Current, Measured Capacity to start, time since last
Start Data
start
RTD Data (Option) Temperature readings from up to 12 RTDs (6 stator RTDs)
Voltage Metering kW, kVAR, PF, kWH
Serial Communications
Protocol Modbus RTU
Signal RS-485, RS-422 or RS232
Network Up to 247 devices per mode
Functionality Full operation, status view, and programming via communications port
Operator Interface
LCD Readout Alpha numeric LCD display
Keypad 8 function keys with tactile feedback
Status Indicators 12 LEDs include Power, Run, Alarm, Trip, Aux Relays
Up to 1000 circuit-feet from chassis (use twisted, shielded wire & power
Remote Mount Capability
source)
Clock and Memory
Operating Memory SRAM loaded from EEPROM at initialization
Factory Default Storage Flash EPROM, field replaceable
Customer Settings and Status Non-volatile EEPROM, no battery backup necessary
Real Time Clock Lithium ion battery for clock memory only
JKSSS+ Series - 3
• Isolation Switch:
An isolation switch is provided in the incoming power section of the starter
assembly. The maximum voltage is 7200V.
Typically the fuses are ANSI class “R” for units rated up to 4800V. The fuses
are sized according to motor locked rotor current and are coordinated with the
solid state overload relay. The fuse and overload coordination is designed to
allow the controller and contactor to clear low and medium level faults. This
prevents exceeding the contactor interrupt ratings. Fuses interrupt high level
faults that exceed the contactor interrupt ratings. Fuse holders include blown
fuse indicators (wired to the isolation contactor circuit) to disconnect all three
phases if any one of the fuses clears (see section 2.7).
JKSSS+ Series - 4
• Contactors: Vacuum contactors are provided for both In-Line Isolation and SCR
Bypass. The contactor voltage ratings are: 7.2kV for 2300 - 6900V units.
• Soft Start Only Option: The JKSSS+ Series is also offered in an optional “Soft
Start Only” package for use in retrofitting behind an existing customer supplied
line start controller. In this configuration, the Disconnect Switch, Fuses and
Line Isolation Vacuum Contactor are NOT included in the JKSSS+ unit, so
proper interlocking of sections containing medium voltage becomes the install-
er’s responsibility.
All retrofit “Soft Start Only” packages must be used with complete line isola-
tion using a contactor or other “air-gap” device. The Optional “Soft Start Only”
includes overload protection in normal operation mode and will sequence the
isolation contactor, so all logic control should be done at the JKSSS+ control
unit. Avoid turning the JKSSS+ on and off using the isolation device.
• Structure: 11 gauge frame with 16 gauge side, back and top sheets. Doors are
12 gauge steel. The enclosure assembly is NEMA / EEMAC type 1 as standard.
Type 12 and 3R are available as an option.
The Main Incoming Power Compartment houses the main disconnect switch,
amain power fuses and input isolation contactor. A viewing window provides
clear indication of the switch position without opening the compartment. Main
Bus Compartment contains the horizontal bus bars (if provided). Top, bottom or
side cable entry can be made with minimum bending.
One or more Starter Power Compartments contain the bypass vacuum con-
tactors, SCR power modules, instrument transformers and all other medium
voltage devices. Adequate room is provided for motor lead connections to be
made with minimum conductor bend.
JKSSS+ Series - 5
Removable conduit entry plates are provided in the bottom of the enclosure to
facilitate drilling and punching of conduit holes without exposing the equip-
ment to contamination from metal debris.
• Power Bus: Optional main horizontal phase bus bars can be configured to
extend the entire length of the starter lineup. Bus bar material is tin-plated or
silver-plated copper. All bus ratings are per UL Standard 347.
• Bracing: Bus bars are braced with non-tracking fire resistant non-hygroscopic
insulation supports and have a minimum fault current rating of 50,000 Amps.
• Connections: All bus connections use 2 bolts minimum, with Belleville spring
washers to ensure tightness. Splice kits for each shipping split are included,
along with specific installation instructions.
• Ground Bus: A continuous ground bus bar with a minimum rating of 400
Amps extends the entire length of the starter near the bottom of each enclo-
sure. A grounding strap connects each vertically adjacent compartment and
also ties the grounding arm of the disconnect switch to the main ground bus
bar (see section 2.11).
The factory default setting applies a Voltage Ramp with Current Limit as this
has been proven the most reliable starting method for the vast majority of
applications. Using this starting method, the Initial Torque setting applies just
enough voltage to the motor to cause the motor shaft to begin to turn. This
voltage is then gradually increased over time (as per the Ramp Time setting)
JKSSS+ Series - 6
until one of three things happen: the motor accelerates to full speed, the Ramp
Time expires or a Current Limit setting is reached.
If the motor accelerates to full speed before the ramp time setting has expired,
an automatic Anti-Oscillation feature will override the remaining ramp time and
full voltage will be applied. This will prevent any surging or pulsation in the mo-
tor torque, which might otherwise occur due to the load not being fully coupled
to the motor when operating at reduced voltage and torque levels.
If the motor has not reached full speed at the end of the ramp time setting,
the current limit setting will proportionally control the maximum output torque.
Feedback sensors in the JKSSS+ Series provide protection from a stall condi-
tion, an overload condition or excessive acceleration time.
When the motor reaches full speed and the current drops to running levels, the
soft starter detects an At-Speed condition and closes the Bypass Contactor.
The Bypass Contactor serves to shunt power around the SCR stack assemblies
to prevent heat buildup in the starter enclosure due to the slight voltage drop
across the SCRs. At this point, the soft starter has the motor operating at full
voltage, just as any other starter would.
· Current Ramp: Uses a closed current feedback PID loop to provide a linear
torque increase up to a Maximum Current level.
· Custom Curve: Gives the user the ability to plot torque and time points on a
graph. The soft starter will then accelerate the motor following these points.
Deceleration: The soft starter provides the user with the option of having
the load coast to a stop or controlling the deceleration by slowly reducing the
voltage to the motor upon initiating a stop command. The Decel feature is the
opposite of DC injection braking in that the motor will actually take longer
to come to a stop than if allowed to coast to a stop. The most common ap-
plication for the Decel feature is pumping applications where a controlled stop
prevents water hammer and mechanical damage to the system.
JKSSS+ Series - 7
Ready Mode: In this mode, control and line power are applied and the starter is
ready for a start command. Protection during this mode includes the monitoring
of current for leakage through multiple shorted SCRs or welded contacts on the
Bypass Contactor. Other protection features in effect are:
· Starter Temperature
· Shorted SCR
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults
Note: The “Programming Mode” can only be entered from the Ready Mode.
During programming, all protection features and start command are disabled.
Start Mode: These additional protection functions are enabled when the soft
starter receives a valid Start command:
Note: Shorted SCR and Shunt Trip protection are no longer in effect once the
soft starter goes into the Start Mode.
Run Mode: The soft starter enters the Run Mode when it reaches full output
voltage and the motor current drops below the FLA setting (motor nameplate
FLA plus service factor) for a predetermined period of time. During the Run Mode
these additional protection features are enabled:
Stop Mode: Once a Stop command has been given, the protection features
change depending on which Stop Mode is selected.
· Decel Mode: Retains all protection features of the Run Mode. At the end of
Decel, the motor will be stopped and the protection features change as
indicated below.
JKSSS+ Series - 8
· Coast-To-Stop Mode: Power is immediately removed from the motor and the
soft starter returns to the Ready Mode.
Additional protection features activated when the stop command is given include:
· Coast-Down / Back Spin Timer
· Starts-per-Hour
· Time Between Starts
· External Input Faults
· Learned Curve Protection: The user sets the soft starter to the “LEARN”
mode and starts the motor under normal starting conditions. The CPU then
samples and records 100 data points during the start curve, analyzes them and
creates a graphical representation in memory. The soft starter is then switched
to Curve Follow protection mode and monitors motor performance against this
curve. This feature is especially useful in initial commissioning tests to record a
base line performance sample (in this case, it is not necessarily used for motor
protection).
Run Mode overload protection is initiated when the starter determines that the
motor is At-Speed. Overload Protection is initiated when the motor RMS current
rises above a “pick-up point” (as determined by the motor nameplate FLA and
service factor). Run mode protection is provided by the CPU monitoring the Dy-
namic Thermal Register. Data for the Dynamic Thermal Register is accumulated
from I2t calculations and cooling rates. A trip occurs when the register reaches
100% as determined by the selected Overload Protection Curve (NEMA Class
5-30 standard curves) and is based on the programmed Locked Rotor Current
indicated on the motor nameplate. The Dynamic Thermal Register is altered, or
“biased”, by the following conditions:
· Current Imbalance: Will bias the register higher to add protection from ad-
ditional motor heating during a current imbalance condition.
· Normal Cooling: Provided when the motor current drops below the pick-up
point or the motor is off line. The cooling rate is lower for motors that are off-line
(such as after a trip) since cooling fans are also inoperative.
JKSSS+ Series - 9
· RTD Input: Will bias the register in either direction based on real-time input of
the motor, bearing and even ambient temperature conditions.
· Dynamic Reset is another feature that adds reliability and consistency to the
performance of the soft starter. If a motor overload condition occurs and the soft
starter trips, it cannot be reset until sufficient cool down time has elapsed. This
cool down time is determined by the thermal state of the motor when it tripped
(i.e. hot motors cool more quickly due to additional convection). The cool down
time is also biased by RTD measurements when used.
· Retentive Memory provides continuous overload protection and real time
reset even if power is lost. Upon restoration of power, the soft starter will
read the Real Time Clock and restore the thermal register to what it should be
given the elapsed time.
Auto Synchronizing of the gate timing pulses match each phase firing angle
to their respective phases. The starter actively tracks minor shifts in the line fre-
quency, avoiding nuisance tripping that may happen with conventional gate firing
systems. This is especially useful on portable or backup generator supplies,
allowing the starter to be used confidently in applications that have unstable
power.
Sustained Pulse firing keeps the firing signal active for 270 electrical degrees,
ensuring that the DC gate pulse causes the SCR to fire even if line noise is
present at a critical moment. This provides the soft starter with superior noise
immunity and protects against misfiring, enhancing the system reliability.
Closed Loop Firing Control is a method of balancing the SCR firing pattern
based on the desired output. The CPU uses feedback signals from both the
output current and voltage providing smooth output and preventing imbalances
during ramping which prevents unnecessary motor heating.
Transformer Isolation of the firing signals prevents interference from line noise
and EMI/RFI signals that may be present. Specially designed 120V 3 phase iso-
lation transformers provide potential measurement, firing board power and gate
power systems while being isolated from the line voltage. High isolation Ring
Transformers are used to step this down to 28Vac for the Sustained Pulse firing
circuit, providing further isolation for the SCR gates.
Fiber Optic Isolation is provided for all signal interfaces between the Medium
Voltage and Low Voltage systems. Even the current signals from CTs are con-
verted to fiber optic signals for maximum isolation and safety.
JKSSS+ Series - 10
1.9 Electronics
The JKSSS+ Series electronics systems are divided into two categories, Low Voltage
and Medium Voltage, based solely on where they are located in the starter structure.
Low Voltage electronics include the Keypad Operator Interface, CPU and Main
Power PC boards are located in an isolated Low Voltage Compartment of the
enclosure.
· Main Power Board: is also referred to as the Firing Board. It contains the
Digital I/O relays and interfaces to the TCB board (see below) for user inter-
face. It also controls the sequencing of the Isolation and Bypass contactors with
the SCR firing. This board generates all firing signals for the SCR stacks and
receives feedback signals from fiber optic transmitters. It converts analog levels
to digital signals for the CPU. These firing pulses are via fiber optic signals to
isolate them from the Medium Voltage environment.
Control Electronics are located in the medium voltage and low voltage sections of
the soft starter. The main line power must be disconnected before these electronics
can be accessed. They include the TCB, Gate Drive and Temp/CT boards.
· TCB (Terminal and Control Board): is the user connection interface board. It
is located in the Low Voltage section in order to satisfy UL termination require-
ments, and does not connect directly to the medium voltage components other
than the contactor coils. This board contains the user terminal blocks, output
relays (duplicated), inputs and control power connections. It also contains ad-
ditional timed relays for interfacing with Power Factor Correction contactors (if
used) and other external devices. Please note Power Factor Capacitor warn-
ings in Section 2.8.
· Gate Drive Boards: located directly on the SCR stacks. These boards com-
municate to the Main Power board via fiber optic cables. They amplify the gate
pulse signals with power from the Ring Transformers to create the Sustained
Pulse Firing of the SCRs. There is one Gate Drive board for each pair of SCRs
in each stack.
· Temp / CT Boards: are attached to the Gate Drive boards on the SCR stacks
and provide the heat sink temperature and current signals back to the Main
Power Board via fiber optic cables.
· MOV Boards: are attached to standoffs mounted on the SCR heat sinks and
are mounted directly below the Gate Drive boards. The MOV boards are used
to protect the gate/cathode section of the SCRs.
· DV/DT Boards: are also attached to standoffs mounted on the SCR heat sinks
and are mounted below the MOV boards. The DV/DT boards are used to re-
duce voltage transients across the stack assemblies.
JKSSS+ Series - 11
Chapter 2 - Installation
For additional information on the equipment, refer to the following additional
instruction manuals:
For fixed type input isolation contactor - “JK Series Medium Voltage Controllers
- Fixed Type”, manual number VF010H03 or “JK Series 720 Ampere Medium
Voltage Controllers”, manual number VF010H02.
For drawout type input isolation contactor - “JK Series Medium Voltage
Controllers”, manual number VF010H01.
The capability of the moving equipment to handle the weight of the controller shipping
section should be confirmed. The equipment should remain secured to the shipping skid
to prevent distortion of the frame during moving and to minimize tipping. Extreme care
should be exercised during any movement and placement operations to prevent dropping
or tipping.
Using a Forklift
A forklift truck may offer a more convenient method of handling the controller. A safety
strap should be used when handling with a forklift. The ends of the forks should not enter
the bottom of an open-bottom enclosure.
Overhead Lifting
When it is necessary to move the equipment between elevations, overhead hoisting may
be required. Lifting angles (for multiple controller sections) are provided on top of the
enclosure for this purpose. Spreaders (Fig. 1) should be used to provide the vertical lift
on single controllers to prevent eye-bolt failure.
JKSSS+ Series - 12
Always keep the controller upright while lifting. Some controller sections may contain
heavy or special equipment that will cause the center of gravity to be off-center. Rigging
lengths should be adjusted to maintain the controller in an upright position. The angle
between the lifting cables and vertical should not be allowed to exceed 45 degrees
(Fig. 2). Ropes or cables should not pass through the holes in lifting angles or eye-
bolts. Slings with safety hooks or shackles of adequate load rating should be used.
2.3 - Location
Storage
If the controller is to be stored for any length of time prior to
installation, the packing should be restored for protection
during that period. Where conditions permit, the packing
should be left intact until the controller is at the final installation
position. If the packing is removed, the top and openings Fig. 1 Use of Spreader Bar - Single Section
of the controller should be covered during the construction
period to protect it against dust and debris.
Indoor Equipment
Controllers designed for indoor installation (NEMA Type 1, 12)
which are not to be installed and energized immediately, should
be stored in a clean, dry space where a uniform temperature
prevents condensation. Preferably, the controller should be
stored in a heated building, with adequate air circulation and
protected from dirt and water. Equipment should be stored
where it is not subject to mechanical damage, especially during
building construction. An indoor controller that is to be stored
outdoors should be securely covered for protection from weather
conditions and dirt. Temporary electrical heating should be
installed to prevent condensation. Approximately 150 watts per
enclosure is usually adequate.
JKSSS+ Series - 13
Routine Inspection
Routine scheduled inspection should be established if storage for an extended period is
anticipated. This is to check for condensation, corrosion, vermin, and adequacy of space
heating. Prior to inspection, the equipment should be carefully examined for evidence of
physical damage, corrosion, or other deterioration.
WARNING Do not install equipment found to have damage or
deterioration that could affect the unit performance.
SERVICE CONDITIONS
Toshiba medium voltage controllers are intended for usual service conditions as defined
by NEMA. The equipment should not be exposed to corrosive or explosive fumes, dusts,
vapors, dripping or standing water, abnormal vibration, shock, tilting, or other abnormal
operation conditions. The temperature of the ambient air surrounding the controller should
be between the limits of 0°C(32°F) and +40°C(104°F). The altitude of the equipment
installed should not exceed 3300 ft (1000m).
NOTE: Temperature or altitude conditions outside of the usual limits may require derating
or other special equipment, such as heating, cooling or ventilation. Contact Toshiba for
further information.
If the location for installation is damp, space heaters may be required. If space heaters
are furnished inside the controller, they should be connected in accordance with the wir-
ing diagram furnished.
JKSSS+ Series - 14
2.4 - Dimensions
2.5 - Mounting
Each shipping section must be leveled and firmly secured to its supporting
foundation. Steel shims may be used for final leveling (Fig. 3), if necessary.
When three or more shipping sections are to be arranged in one continuous
line-up, the center shipping section should normally be the first located.
There is a rating data label on the inside of each medium voltage compartment door.
Verify that the controller ratings properly match the system data by checking the follow-
ing:
1. Verify agreement of full load current, locked rotor current and acceleration time
with motor nameplate.
2. Verify that system voltage, number of phases and frequency matches controller
rating.
3. Verify that available short circuit current of power system is less than rated
short circuit capacity of controller.
Check connections - Although the equipment and devices have been completely tested
at the factory, a final field check should be made that all electrical wiring and bus bar
connections are correct and have not become loose in transportation. Refer to MAINTE-
NANCE Section for electrical joint specification.
All blocks or other temporary braces used for shipment must be removed.
Before closing the enclosure, all metal chips, scrap wire and other debris left over from
installation must be cleaned out.
The integrity of all bus bar supports must be checked for secureness and damage.
Care should be exercised that when covers are installed and doors closed, no wires are
pinched and that all enclosure parts are properly aligned and tightened.
WIRING CHECK
Field wiring should be checked for clearance to live busses where necessary, physically
secured to withstand the effects of fault current.
Each motor should be connected to its intended controller, and phase rotation should be
correct prior to startup.
DEVICE/MECHANISM CHECKS
All devices should be checked for damage. All necessary repairs or replacements should
be made.
WARNING
Do not remove, cover or destroy any safety signs.
The setting of any adjustable current and voltage trip mechanisms should be verified to
the proper values.
NOTE: Damage from faults can be reduced if devices used for short circuit and ground
fault protection are chosen and set to operate at values as close to minimum as feasible,
while allowing normal transients.
All switches, relays and other operating mechanisms should be manually exercised to
make certain that they are properly aligned and operate freely.
Operating mechanisms such as interlocks, key switches, etc. should be checked for func-
tion as intended for protection of personnel and equipment.
Overload relay settings should be checked to be sure they are selected and adjusted to
the proper settings per the load nameplate data.
Power circuit fuses were selected and installed in accordance with the application re-
quirements. Fuses must be completely inserted in their holders. Instruction on removing
and installing the fuses can be found in one of the following manuals: VF010H03 (Fixed
Type) or VF010H01 (Drawout Type).
Electrical Checks
With incoming power isolated and all loads disconnected electrically, the control cir-
cuit and other mechanisms should be exercised to determine that the devices operate
properly. An auxiliary source of control power will be necessary to provide power to the
electrical operators.
The ground fault protection system (if furnished) should be tested in accordance with the
instructions furnished with the device.
An electrical insulation test should be performed to ensure that the controller and asso-
ciated field wiring are free from short circuits and grounds. The preferred method is to
perform a dielectric test at 2.25 times the nominal system voltage plus 2000 volts. This
should be done phase-to-ground, phase-to-phase and phase-to-neutral (if applicable),
with all switches and circuit breakers opened. Disconnect any devices which may have
limited dielectric strength and that are not intended for this test.
The light or buzzer, or both, used to indicate breakdown should be calibrated to indicate
failure with an output current between 1.5 and 2.0 milliamperes per 1000 volts applied.
All devices must be set to their normal or OFF position before energizing incoming power.
JKSSS+ Series - 17
WARNING Do not service this equipment with voltage applied! The unit
can be the source of fatal electric shocks! To avoid shock
hazard, disconnect main power and control power before
working on the unit. Warning labels must be attached to
terminals, enclosure and control panel to meet local codes.
CAUTION
Do not connect the capacitors to the load side (motor side)
of the solid state starter. This will cause di/dt damage to the ! CAUTION
SCRs when they are turned on. SCR DAMAGE
Do not connect (PFC) capacitors to the load side of
the unit.
Do not connect the capacitors to the input side of the unit.
CAUTION Doing so will cause DI/DT damage to the SCRs when
If you cannot avoid using capacitors across the power lines, they energized.
must be located as far upstream as possible of the input line
contactor. In this situation, optional power factor correction (PFC)
caps contactor should be specified. For additional information and
specifications, please contact the factory.
CAUTION
Never interchange the input and output power connections
on the unit. This will cause excessive voltage to the control circuit
logic.
CAUTION
For bus protection, it is strongly recommended to use non-gap
lightning arrestors in areas where lightning is a significant
problem. The arrestors should be mounted on the nearest utility pole.
All access covers, barriers, partitions, etc. that are temporarily removed during installation
must be replaced.
JKSSS+ Series - 18
NOTE: Covers and braces supplied only for protection during shipment should not be
replaced. All debris and tools should be removed from each compartment as cabling is
completed.
JKSSS+ Series - 19
Note: Proper phase sequence must be observed when connecting the input power.
For example, phase A must lead phase B, which in turn must lead phase C by 120°
respectively. If the phase rotation is not correct, a fault light and the LCD display will
indicate the problem. The SCR output will be clamped.
Each section contains a vertical ground bus extending from the main ground bus or ground
pad to each controller compartment.
The following may be used as a general guide with regard to equipment grounding.
Controller used as service equipment for a grounded system or as a main section for a
seperately derived system:
a. The grounding electrode conductor (ground wire) sized in accordance with NEC 250
should be run from the grounding electrode to the controller ground bus or ground
terminal.
b. Unless already done at the factory, a main bonding jumper should be installed from
the incoming grounded connector bus (neutral) to the ground bus or designated
grounding point. If a jumper is not furnished, one having a size in accordance with
NEC 250 should be selected.
c. Steps (a) and (b) should effectively connect together the grounding electrode, the
controller frame, all outgoing equipment grounding conductors and the grounded
neutral bus of the system.
d. No connection should be made to ground on the load side of any neutral disconnecting
line or any sensor used for ground fault protection. No connections should be made
between outgoing grounding connectors and the neutral.
e. Where the controller or system is dual-fed (double-ended) and has ground fault
protection, special precautions are necessary to accomplish proper grounding and
bonding.
JKSSS+ Series - 20
Controller used as service equipment for an ungrounded system or as a main section for a separately derived
system.
a. A grounding electrode conductor (ground wire) sized in accordance with NEC 250 should be run from the
grounding electrode to the controller ground bus or ground terminal.
b. If the system is grounded at any point ahead of the controller, the grounded conductor should be run to the
controller in accordance with NEC 250 and connected to the ground bus or ground terminal.
c. Steps (a) and (b) should effectively connect together the grounding electrode, the controller frame, all outgoing
equipment grounding connectors and any grounded conductor which runs to the controller.
Controller not used as service equipment or as a main section for a separately derived system, and used on either
a grounded or ungrounded system:
a. The controller frame and any ground bus should be grounded by means of equipment grounding conductors
having a size in accordance with NEC 250 and run with the main supply conductors or by bonding to the
raceway enclosing the main supply conductors in accordance with NEC 250.
b. Ground leads should be connected to cable potheads/shields as specified by the manufacturer of these de-
vices.
JKSSS+ Series - 21
WARNING
This section involves C us tomer P rovided
potentially lethal voltage
levels! Use extreme Momentary or Maintained
caution to prevent injury. S tart / S top S witching
Maintained
Do not bypass the electrical or mechanical S TAR T S TOP
interlocks. This will cause severe equipment Fus es Momentary
damage and possible fatal injury. F1: C ontrol Fus es for TB 1 1 - 9
P art #AC G 1A250 VAC or equivalent
F2: C ontactor and relay output fus es
The JKSSS Plus-TCB board provides P art #AC G 4A250 VAC or equivalent
NC
11
Output
NO
E1 E2 E3
connections. It is a 120Vac control board with
E4
10
120 VAC
C
R ed
several auxiliary dry control contacts, built-in
AC
9
LED Neut
Neutral
8
time delay circuits and emergency bypass func- FUS E
7
S tart
LED
isolation and bypass contactor and provides 5
Inter
HE ATSINK
S ourc e
S ourc e
F1 10
NC
9
NO
HE AT S INK
F2 8
FAC TOR Y WIR E D
C
7
G reen DO NOT US E
N
F3
{
LED 6
Line 1
S
120VAC 5
Neutral 2 -12V
TB 2
NC
Start/Stop Control 3 G reen
4 E mergenc y B ypas s
NO
Delayed S tart G reen
Figure 2-1 4
LED LED 3 AUX C ontac ts
C
5 +12V S TAR T
2 E mergenc y B ypas s
F use B lown/
C
Disconnect Open TB 6 1 F ull Voltage S tart
2.10.2 Description of Terminal Connections 6
NO
7
Dual R amp ON OFF 12
J P1
NC
8
Start/Stop Control - Terminal Block 1 (TB1) : S W1 11
NO
9 R emove J P 1 for electronic 10
B ypass S tatus DUA L ADJ
• Positions 1 and 9 are the 120 Vac control power. motor overload protection
Fault
10 during emergency 9
bypass operation NC
• Positions 2-3 and 4-5 are factory jumpers 8
NO
2 TB 3
normally closed, dry, shutdown contacts (See 6
NC
3
Fig. 2-1 above).
C P U (AUX1) F ault
TB 7 B OAR D 5
Lock Out
NO
4
4
• Positions 6-7-8 are for either two wire or three-
C
5
At S peed 3
NC
7
positions 6 and 8 with a N.O. dry, maintained 1
C
F use B lown/
start/stop contact. Three wire control connects Disconnect 1 12
NC
AUX-S
DLY-S
PFC-C
DLY-C
PFC-S
AUX-C
G reen
to 6 with 7 as the stop push-button, and the start Interlock Input 2 LED 11
NO
P.F.C. CA P
PFC
4 9
• Positions 10-11-12 is a dry FORM C contact. T IME D
NC
7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1 OUT 8
5
B ypass Aux C ontact
The contact is an immediate start/stop contact.
NO
6 7
TB 4
{
C
C oil A2 8 5
NO
{
T ime Delay
Main A1 9 G reen 4
C
C oil LED 3
A2 10
NC
DE L AY
2
NO
T IME D 1
OUT
C
JKSSS+ Series - 22
JKSSS+ Series - 23
• Positions 5 and 6 accept dry, normally closed contact from the bypass contac-
tor for an At Speed indication. (Factory wired)
• Positions 7 and 8 are wired to the coil of the bypass contactor and energizes
and de-energizes the contactor. (Factory wired)
• Positions 9 and 10 are wired to the coil of the inline isolation contactor and
energizes and de-energizes the contactor.
Note: All customer contacts are 960VA, 120VAC (Max) rated dry contacts.
LEDs provided on the TCB board (for low voltage testing only):
• -12 VDC power supply
• +12 VDC power supply
• Start = start is initiated to TCB board
• Fault = any fault has occurred
• Fuse Blown = disconnect open or blown fuse has activated
• PFC On = Power Factor Correction Capacitor contacts have energized
• Timed Out = Auxiliary time delay contacts have energized
Jumper Selection
For the following, please refer to Figure 2-6.
Start Delay
This is a selectable delay period between the intiation of the start command and
when the CPU actually receives the start signal. Selecting Jumper X1 or X2 deter- Jumper Selection on TCB Board
mines the method by which this delay (in cycles or seconds) is calculated. See SW3 Figure 2-6
Auxiliary (Start) Delay (from the time the start input is given). Selecting jumper X3 or
X4 determines the method by which this delay is calculated (cycles or seconds). See
SW4 below for instructions on setting delay time.
• X3 = (AUX-C) Auxiliary time delay in cycles
• X4 = (AUX-S) Auxiliary time delay in seconds (Factory setting)
Power Factor Correction (PFC) Capacitor Contactor Delay (From the time the
bypass closes to when contacts change state). Jumper selection determines the
method by which this delay is calculated. See SW5 for instructions.
• X5 = (PFC-C) Time delay in cycles
• X6 = (PFC-S) Time delay in seconds (Factory setting)
Switch Positions
Please refer to Figure 2-7.
• SW1 = ON = Dual Adjustment
OFF = Disabled
• SW2* = Not used - Switches SW3, SW4 and SW5 are 7 position dip switches
that use binary code to count up to 127 seconds/cycles (see “Jumper Selec-
Figure 2-7
tion” above).
Example:
• SW3 = Start Delay; 7 position dip switch uses binary count up to 127 seconds/
Switch settings are cumulative.
cycles (see jumper selection above). Factory setting: 1 second. Setting dip switch positions 1, 2,
• SW4** = Auxiliary (Start) Delay 7 position dip switch uses binary count up to and 3 to “on” = 1+2+4 = 7 seconds
127 seconds/cycles (see jumper selection above). Factory setting: 1 second. total time. Note: This example ap-
• SW5** = PFC time delay; 7 position dip switch uses binary count up to 127 plies to SW3, SW4 & SW5.
seconds/cycles (see jumper selection above). Factory setting: 1 second.
* Note: This switch interacts with the CPU programming when the Decel function is
enabled.
** Note: These times are in addition to SP2 in the CPU setpoints.
JKSSS+ Series - 24
RTD1 RTD2 RTD3 RTD4 RTD5 RTD6 RTD7 RTD8 RTD9 RTD10 RTD11 RTD12
Compensation
Shield
Power
Signal
RTD
Typical RTD
Installation
JKSSS+ Series - 25
REAR
VIEW
(RS485) (RS422)
Board
Ground Test Points
19 1 7 1 7 1 19 1
20 2 J3 20 J6 2
J5 J4
AI
AT
BI
BT
CI
CT
3
GF
1
J1
C2 C1
7
7, A - Phase
B2 B1
4, B - Phase
A2 A1
1, C - Phase
1
J2
1
3
J8
J7 J2
6
1
F1
TB1 TB2
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
TB3
TB1 TB2
Factory use only. Do not reprogram. Refer to Setpoint Page 5 for programming information
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C.
AUX1 AUX2 AUX3 AUX4 AUX5 AUX6 AUX7 AUX8
(TRIP) (ALARM) (RUN) (AT SPEED) Relay Relay Relay Relay
Relay Relay Relay Relay
JKSSS+ Series - 27
1 2
19 20
1 2
19 20
Analog Output #2
Program Enable
UV-P Rotation
Input
Thermostat
Tach Input
Dual Ramp
4 - 20 mA
4 - 20 mA
TCB Fault
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
+ - + - + - + - + - + - + -
+ -
Note: Install program jumper to enable
setpoint programming. Jumper must be
removed after programming or for
prolonged storage to preserve settings.
JKSSS+ Series - 28
3.2 Introduction
It is best to operate the motor at its full load starting condition to achieve the proper time,
torque and ramp settings. Initial settings are set to accommodate most motor conditions.
TRY INITIAL SETTINGS FIRST. See Setpoint 5.1.2 Starter Confiuration (Setpoint Page
2) to make any adjustments.
JKSSS+ Series - 29
Shock Wave is avoided. When the output voltage to the motor is low enough to no longer
be needed, the soft starter will end the Decel cycle and turn itself off.
Another common application for decel control is on material handling conveyors as a
means to prevent sudden stops that may cause products to fall over or to bump into one
another. In overhead crane applications, soft stopping of the Bridge or Trolley can prevent
loads from beginning to over swing on sudden stops.
• When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit. MOTOR STOPPED
Display 1
• The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has READY TO START
energized. IA, IB, IC will display the current setting for Phase A, Phase B,
MOTOR STARTING
and Phase C and the G/F indicates ground fault. (Display 4) Display 2 00 X FLA
• If the motor decelerates, or stops, during the acceleration period, hit the
stop button immediately and open the disconnect line. If the unit does not Display 3 OVERLOAD ALARM
TIME TO TRIP: XXX SECS.
follow this operational sequence, please refer to the Troubleshooting Chapter.
IA: _ _ _ IB: _ _ _
Display 4
It is best to operate the motor at its full load starting condition to achieve the proper IC: _ _ _ G/F: _ _ _
time, torque and ramp settings. Initial settings are set to accommodate most motor
conditions. TRY INITIAL SETTINGS FIRST. See Section 5.1.1 (Setpoint Page 2) to
make any adjustments.
• Initial Voltage
• Soft Start Curve
• Current Limit
• Acceleration Time
If decel is enabled, the following parameters for Deceleration Time, Start Decel Volt-
age (see SP2) and Stop Decel Voltage (see SP2) must also be programmed.
3.6 Emergency Bypass Operation
•
! DANGER
HAZARDOUS OPERATION
Do not operate the Bypass Contactor with medium
voltage power applied to the unit.
Remove input power (using line start section and lock out disconnect).
• Close the emergency bypass contact.
• Re-close the disconnect on line start panel.
• If integral overload protection is not to be used (see JP-1 Motor Protection
Jumper), then bimetallic or solid state overload protection is required
(customer supplied if factory emergency overload protection option has not
been included.)
JKSSS+ Series - 32
Note: The soft start is menu driven and there are three levels of programming. The
programming for two of these levels is password protected. Level two requires a
three digit password and level three requires a four digit password.
RESET Will clear the trip indicator and release the trip relay.
In the edit mode, press the ENTER pushbutton so the Keypad Operator Interface
unit will accept the new programming information.
ENTER When not in the edit mode, the ENTER pushbutton
will toggle through the event indicator list (such as
alarms or trips)
JKSSS+ Series - 33
LEVEL 1
PAGE 2 STARTER
CONFIGURATION
PAGE 4 RELAY
ASSIGNMENT
LEVEL 2
PAGE 5 RELAY
CONFIGURATION
PAGE 7 CUSTOM
ACCELERATION CURVE
PAGE 8 OVERLOAD
CURVE CONFIGURATION
PAGE 9 RTD
CONFIGURATION
LEVEL 3
PAGE 10 SECURITY
SET PASSWORD
PAGE 11
COMMUNICATIONS
PAGE 12 SYSTEM
SETPOINTS
JKSSS+ Series - 34
MENU
ENTER
ENTER
JKSSS+ Series - 35
JKSSS+ Series - 36
SP3.11
Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Overvoltage Trip Level 10% 5-30%, Off
SP3.12
Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec
Undervoltage Alarm Level Off 5-30%, Off
SP3.13
Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Undervoltage Trip Level 15% 5-30%, Off
SP3.14
Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec
Line Frequency Trip Window Disabled 0-6 Hz, Disabled
SP3.15
Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec
P/F Lead P/F Alarm Off 0.1-1.00, Off
SP3.16
P/F Lead Alarm Delay 1.0 sec 1-120 sec
P/F Lead P/F Trip Off .01-1.00, Off
SP3.17
P/F Lead Trip Delay 1.0 sec 1-120 sec
P/F Lag P/F Alarm Off .01-1.00, Off
SP3.18
P/F Lag Alarm Delay 1.0 sec 1-120 sec
P/F Lag P/F Trip Off .01-1.00, Off
SP3.19
P/F Lag Trip Delay 1.0 sec 1-120 sec
Power Demand Period 10 min 1 - 60 min
KW Demand Alarm Pickup Off KW Off, 1-100000
KVA Demand Alarm Pickup Off KVA Off, 1-100000 SP3.20
KVAR Demand Alarm Pickup Off KVAR Off, 1-100000
Amps Demand Alarm Pickup Off Amps Off, 1-100000
JKSSS+ Series - 37
Notes:
Dual Ramp None None None AUX1 to AUX4 are for Factory SP4.1
Thermostat Trip None None Use only. Do not change!
O/L Warning Alarm None None Only AUX 5 - 8 are used in the
Overcurrent Alarm Alarm None None 2nd & 3rd relay assignments.
SCR Fail Shunt Alarm None None None
*Ground Fault Alarm Alarm None None
Under Current Alarm None None None
Motor Running AUX3 None None
I/B Alarm Alarm None None
Stator RTD Alarm None None None
Non-Stator RTD Alarm None None None
RTD Failure Alarm None None None
Self Test Fail Trip None None
Thermal Register Alarm None None
U/V Alarm Alarm None None
O/V Alarm Alarm None None
Power Factor Alarm None None None
KW Demand Alarm None None None
KVA Demand Alarm None None None
KVAR Demand Alarm None None None
Amps Demand Alarm None None None
Timed Output None None None
Run Delay Time None None None
At Speed AUX4 None None
JKSSS+ Series - 38
JKSSS+ Series - 39
Passowrd Protection
JKSSS+ Series - 40
Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
Start Locked Rotor Current 600% FLA 400-800%
Level 3
Page 8
SP8.2
Acceleration Time Limit 30 sec 1-300 sec, Disabled
Number of Starts Per Hour Disabled 1-6, Disabled
Time Between Starts Time 5 min 1-60 Min, Disabled
Area Under Curve Protection Disabled Enabled or Disabled
SP8.3
Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec
Current Over Curve Disabled Disabled, Learn, Enabled
Learned Start Curve Bias 10% 5-40% SP8.4
Time for Sampling 30 sec 1-300 sec
JKSSS+ Series - 41
Use NEMA Temp for RTD Values Disabled Enabled or Disabled SP9.1
JKSSS+ Series - 42
Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.2
Page 11
Level 3
JKSSS+ Series - 43
Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay
Page 12
Level 3
Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp
FACTORY SET;
Enter Date (DDMMYYYY) D=1-31, M=1-12, Y=1970-2069 SP13.1
##/##/####
Page 13
FACTORY SET;
Enter Time (HH:MM) H=00-23, M=0-59
##:##
Model # FACTORY SET;
Display Only, Cannot be changed SP13.2
Firmware REV. # ###### ######
Press Enter to Access Factory
Available to Qualified Factory Personnel SP13.3
Settings
JKSSS+ Series - 44
LEVEL 1
PAGE 2 STARTER
CONFIGURATION
PAGE 4 RELAY
ASSIGNMENT
LEVEL 2
PAGE 5 RELAY
CONFIGURATION
PAGE 7 CUSTOM
ACCELERATION CURVE
PAGE 8 OVERLOAD
CURVE CONFIGURATION
PAGE 9 RTD
CONFIGURATION
LEVEL 3
PAGE 10 SECURITY
SET PASSWORD
PAGE 11
COMMUNICATIONS
PAGE 12 SYSTEM
SETPOINTS
JKSSS+ Series - 45
SP1.2 Service Factor: Sets the pickup point on the overload curve SERVICE FACTOR
: 1.15 X FLA
as defined by the programmed motor full load current. Ex: Range: 1.00 - 1.3
If the motor FLA is 100 and the service factor is 1.15, the Increments of 0.01
overload pickup point will be 115 Amps.
OVERLOAD
SP1.3 Overload Class: Choose the motor protection overload class, CLASS: 10
Range: 5 - 30
range from 5-30. Increments of 5
Ex: Overload Class 10 will trip in 10 seconds at six times
FLA. NEMA
DESIGN: B
Range: A - F
INSULATION
CLASS: B
Range: A - S
LINE VOLTAGE
INPUT: 4160 VOLTS
Range: 100 - 7200
LINE FREQUENCY
HZ: 60
Range: 50 or 60
JKSSS+ Series - 46
MENU
(Hit DOWN ARROW one time)
If If
START RAMP #2 TYPE VOLTAGE CURRENT
: DISABLED selected INITIAL VOLTAGE selected INITIAL CURRENT
these these
#2: 60% #2: 200% FLA
Options: Voltage, Current screens screens
or Off will appear. Range: 0 - 100% will appear. Range: 0 - 300%
Increments of 1 Increments of 1
START DECELERATION
TIMED OUTPUT VOLTAGE: 60%
TIME: OFF
Range: 0 - 100%
Range: 1 - 1000 sec, OFF Increments of 1
Increments of 1
the Voltage Ramp or the Current Ramp. Every SP2.5 Kick Start: Used as an initial energy burst in
load requires some amount of torque to start from applications with high friction loads.
a standstill. It is inefficient to begin ramping the
motor from zero every time, since between zero • Kick Start Voltage: The initial voltage (as a
and the WK2 break-away torque level, no work is percent of full voltage value) that is needed to
being performed. The initial torque level should be start the motor (i.e. Breakaway or Initial Torque).
set to provide enough torque to start rotating the
motor shaft, enabling a soft start and preventing • Kick Start Time: The time the initial torque boost
torque shock damage. Setting this start point too is applied.
high will not damage the starter, but may reduce
or eliminate the soft start effect. SP2.6 Deceleration: Allows the motor to gradually come to
a soft stop.
• Ramp Time #1: Sets the maximum allowable time
for ramping the initial voltage or current (torque) • Start Deceleration Voltage: The first part of
setting to either of the following: the deceleration ramp. The soft starter initially
1) the Current Limit setting when the motor is still drops to this voltage level upon receiving a STOP
accelerating, or command. (Represented as a percent of voltage
2) full output voltage if the Current Limit is set to value.)
maximum.
Increasing the ramp time softens the start process • Stop Deceleration Voltage: The drop-off point of
by gradually increasing the voltage or current. the deceleration ramp. (Percent of voltage value.)
Ideally, the ramp time should be set for the longest
amount of time the application will allow (without • Deceleration Time: Decel ramp time.
stalling the motor). Some applications require
a short ramp time due to the mechanics of the SP2.7 Timed Output: Used with an AUX 5-8 relay. When
system (i.e. centrifugal pumps, because pump enabled, and upon a start command, it waits until
problems can occur due to insufficient torque). the programmed time plus the run delayed time
has expired. The relay energizes and remains so
• Current Limit: Sets the maximum motor current until a stop command is received. It de-energizes
the starter will allow during Ramping. As the motor upon receiving a stop command.
begins to ramp, the Current Limit feature sets a
ceiling at which the current draw is held. Current SP2.8 Run Delay Time: Can be used with an AUX 5-8
Limit remains in effect until the following occurs: relay. The delay timer begins upon receipt of the
1) the motor reaches full speed (detected by the start command. The relay will then drop out when
At-Speed detection circuit) or the time has expired.
2) the Overload Protection trips on Motor Thermal
Overload. SP2.9 At Speed Delay Time: Used with an AUX 4 relay, it
Once the motor reaches full speed, the Current waits until after the motor reaches the end of ramp
Limit feature becomes inactive. and the programmed delay time has expired. The
relay energizes until a stop command has been
In the Voltage Ramp Profile, the voltage output is received.
increased until it reaches the Current Limit. Ramp
time is the maximum amount of time it takes for
the voltage to increase until the Current Limit
setting takes over. With some load conditions, the
Current Limit is reached before the Ramp Time
expires.
The Current Ramp profile varies the output
voltage to provide a linear increase in current up
to the Maximum Current setpoint value. A closed
loop feedback of motor current maintains the
Current Ramp profile.
JKSSS+ Series - 49
OVERCURRENT TRIP
SP3.1 Imbalance Alarm Level: This is an advance warning LEVEL: OFF
OVERCURRENT TRIP
DELAY: 2.0 SEC.
of a phase imbalance problem. The problem may Range: 100 - 300%, OFF Range: 1.0 - 20.0 SEC.
not be a fault in the motor, but merely caused by Increments of 1 Increments of 0.1
• Phase Rotation: There are two possible phase AMPS DEMAND ALARM
PICKUP: OFF AMPS
rotation options: ABC or ACB. This setpoint
Range: OFF, 1 - 100000
monitors the wiring to ensure that the phase Increments of 1
rotation is correct. To view the present phase
rotation, go to Metering Page1, screen number 4.
SP3.10 * Ground Fault Hiset Trip Level: Used to trip the
SP3.8 * Ground Fault Alarm: Typically used to warn of low motor (within milliseconds) upon detecting a high
level ground current leakage. level of ground current leakage. This setpoint is
intended to detect low impedance faults.
• * Ground Fault Alarm Delay: The amount of time
that the ground fault condition must exist before an • *Ground Fault Hiset Trip Delay: The amount
alarm will occur. of time that the ground fault condition must exist
before a trip will occur.
SP3.9 * Ground Fault Loset Trip Level: Typically used
to trip the motor on a low level of ground current SP3.11 Overvoltage Alarm Level: Typically used to
leakage. This setpoint is intended to detect high indicate when the line voltage is too high. This is
impedance faults. an alarm level.
• * Ground Fault Loset Trip Delay: The amount • Overvoltage Alarm Delay: The amount of time
of time that the ground fault condition must exist that the overvoltage condition must exist before a
before a trip will occur. trip will occur.
JKSSS+ Series - 51
SP3.12 Overvoltage Trip Level: Typically used to indicate SP3.18 Power Factor Lag Alarm: Typically used to
that the line voltage is too high and at which point a indicate a lagging power factor.
trip occurs
• Power Factor Lag Alarm Delay: The amount of
• Overvoltage Trip Delay: The amount of time that time that the power factor lagging condition must
the overvoltage condition must exist before a trip exist beyond the window before a trip will occur.
will occur.
SP3.19 Power Factor Lag Trip: The acceptable amount
SP3.13 Undervoltage Alarm Level: Typically used to of power factor lag before a trip is generated.
indicate when the line voltage is too low. This is an
alarm level. • Power Factor Lag Delay: The amount of time
that the power factor lag condition must exist
• Undervoltage Alarm Delay: The amount of time beyond the window before a trip will occur.
that the overvoltage condition must exist before a
trip will occur. SP3.20 Power Demand Period: The soft starter
measures the demand of the motor for several
SP3.14 Undervoltage Trip Level: Typically used to parameters (current, kW, kvar, kVA). The demand
indicate that the line voltage is too low and at which values of motors assists in energy management
point a trip occurs programs where processes may be altered or
scheduled to reduce overall demand. Demand
• Undervoltage Trip Delay: The amount of time that is calculated by a programmed amount of time
the undervoltage condition must exist before a trip where current, kW, kvar and kva samples are
will occur. taken and then averaged and stored to assess
demand.
SP3.15 Line Frequency Trip Window: The acceptable
amount of drift above or below the line frequency
(Hz) before a trip is generated.
JKSSS+ Series - 52
O/V ALARM
G/F HI SET TRIP 1ST: ALARM
1ST: TRIP TCB FAULT
1ST: TRIP
DUAL RAMP
1ST: NONE KW DEMAND ALARM
PHASE LOSS TRIP 1ST: NONE
1ST: TRIP
THERMOSTAT
1ST: TRIP
KVA DEMAND ALARM
ACCEL. TIME TRIP 1ST: NONE
1ST: TRIP ONLY
O/L WARNING
1ST: ALARM
TIMED OUTPUT
UNDER FREQUENCY TRIP GROUND FAULT ALARM 1ST: NONE
1ST: TRIP 1ST: ALARM
JKSSS+ Series - 53
The protection functions are user programmable to an output relay. Factory setting for the trip functions assigned to TRIP
(AUX1) relay and alarm functions to ALARM (AUX2) relay. AUX1 - 4 are Factory Set and should not be changed.
JKSSS+ Series - 55
MENU
(Hit DOWN ARROW five times)
ENABLED
PAGE 6 USER I/O TACHOMETER SCALE MANUAL TACH SCALE
CONFIGURATION SELECTION: DISABLED 4.0 mA: 0 RPM
Options: ENABLED or Range: 0-3600
DISABLED Increments of 5
USER PROGRAMMABLE
EXTERNAL INPUTS
Continued...
JKSSS+ Series - 56
SP6.1 The first screen of setpoint page 6 is TACHOMETER SP6.3 The controller provides two 4-20mA analog outputs.
SCALE SELECTION. When this is set to Each analog output is independent of the
ENABLED, the user will need to input the other and can be assigned to monitor different
tachometer scale of the 4-20mA input range. functions. The available output ranges are RPM,
Hottest Non-Stator (Bearing) RTD, Hottest Stator
• Manual Tach Scale 4.0 mA: The unit is looking RTD, RMS current, % Motor Load, or kW.
for an RPM value to assign to the lowest point on
the scale. This value should represent the motor • Analog Output #1 – Select a function from
at zero speed. the available options to be transmitted from
the 4-20mA output. Note: If selecting RPM,
• Manual Tach Scale 20.0 mA: The unit is looking the Tachometer feedback input signal must be
for an RPM value to assign to the highest point on present in order for the controller to give proper
the scale. This value should represent the motor output. If selecting RTD, the RTD option must
at full speed. be installed and an RTD input signal must be
present for a proper output to be given from the
SP6.2 Tach Accel Trip Mode Select: When enabled, the analog output.
underspeed or overspeed must be selected for the • Analog Output #1 (4 mA): Enter a value that the
Tach Accel Trip. If underspeed is selected, only 4mA level will represent for the selected function;
the Tach Underspeed Trip Point will be used. If typically this value should be 0.
overspeed is selected only the Tach Overspeed • Analog Output #1 (20 mA): Enter a value that
Trip Point will be used. the 20mA level will represent for the selected
function.
• Tach Ramp Time: This is the duration of time
before the tachometer begins to sample. SP6.4 Analog Output #2 – All of the setpoints and setup
screens for Analog Output #2 are the same as
• Tach Underspeed Trip: The minimum value of those for Analog Output #1.
motor RPM which must be achieved before the
Tach Ramp Time sample is taken.
JKSSS+ Series - 57
USER TCB FAULT NAME EXT. INPUT #1 TCB FAULT TCB FAULT
PROGRAMMABLE SELECT: ENABLED TCB FAULT TYPE: NORMALLY OPEN TIME DELAY: 1 SEC.
EXTERNAL Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC
INPUTS Normally Closed Increments of 1
(Continued)
• External Input #1: Factory programmed for TCB • External Input #3: The setup screens and
Trip. setpoints for External Input #3 includes the option
of being configured for Dual Ramp. In Dual Ramp
• External Input #2: If used, this setpoint must be mode, the initial contact setting is the same as the
enabled. START RAMP #1. Upon a change in input contact
state, the controller will switch over to START
• Name Ext. Input #2: The user can assign a RAMP #2 and use that setting for start control
description name to the input to easily identify mode. Note: The start RAMP types should only be
the cause of external trip or alarm. Up to 15 switched while the motor is stopped. In Setpoint
characters including spaces can be used to assign Page 4 Relay Assignments, do not assign any
the name. output relay to this function. The controller will
ship with External input #3 programmed for dual
• External Input #2 Type: The external input can ramp. If it is not needed, disable the dual ramp.
be set as either a normally open or normally
closed contact. • External Input #4: This input screens are for the
thermostat input and can be enabled or disabled.
• External Input #2 Time Delay: Upon a change in Note: It is recommended that this function remain
contact setting, the unit will wait the programmed enabled. If the thermostat indicates an over
amount of time before generating an output. If temperature condition, the controller will trip the
no delay is needed, then input 0 seconds. The motor.
controller will post an event upon seeing a change
in state.
JKSSS+ Series - 58
three different curves in the soft starter. Only one CURVE A RAMP
curve can be active (enabled) at a time. Each of TIME 1: 2 SEC
the three curves allow for eight voltage plotting Range: 1 - 60 SEC
Increments of 1
points, with corresponding ramp times and a
CURVE A VOLTAGE
current limit setting. LEVEL 2: 30%
Note: Each successive voltage level must be Range: 0 - 100%
Increments of 1
programmed to a voltage level equal to or greater
than the previous level. All eight levels of voltages CURVE A RAMP
TIME 2: 2 SEC.
must be programmed and the eighth level has
Range: 1 - 60 SEC
been preset at 100%. Increments of 1
CURVE A VOLTAGE
• If Custom Accel Curve has been set to curve A, LEVEL 3: 37%
B or C on this page, the soft starter will override Range: 0 - 100%
Increments of 1
the Start Control Mode selected in Setpoint Page
2, (even if Start Control Mode in Setpoint Page 2 CURVE A RAMP
has not been set to Custom Accel Curve). TIME 3: 2 SEC.
Note: Setpoint Page 7 has a security level 3 Range: 1 - 60 SEC
Increments of 1
requirement.
CURVE A VOLTAGE
LEVEL 4: 45%
Range: 0 - 100%
Increments of 1
CURVE A RAMP
TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE
LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE A RAMP
TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE
LEVEL 6: 67%
Range: 0 - 100%
Increments of 1
CURVE A RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE
LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
CURVE A RAMP
TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
JKSSS+ Series - 59
CURVE A CURRENT
LIMIT: 350% FLA CURVE B VOLTAGE
LEVEL 8: 100%
Range: 200 - 500%
Increments of 10 Range: 0 - 100%
Increments of 1
CURVE B RAMP
CURVE B VOLTAGE TIME 8: 2 SEC
CUSTOM CURVE B LEVEL 1: 25%
Range: 1 - 60 SEC
Range: 0 - 100% Increments of 1
Increments of 1
CURVE B CURRENT
CURVE B RAMP LIMIT: 350% FLA
TIME 1: 2 SEC.
Range: 200 - 500%
Range: 1 - 60 SEC Increments of 10
Increments of 1
CURVE B VOLTAGE
LEVEL 2: 30% CUSTOM CURVE C CURVE C VOLTAGE
Range: 0 - 100% LEVEL 1: 25%
Increments of 1 Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 2: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 1: 2 SEC.
Increments of 1 Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 3: 37% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 2: 30%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 3: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 2: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 4: 45% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 3: 37%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 4: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC TIME 3: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 5: 55%
CURVE C VOLTAGE
Range: 0 - 100% LEVEL 4: 45%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 5: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC
Increments of 1 TIME 4: 2 SEC.
Range:1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 6: 67%
CURVE C VOLTAGE
Range: 0 - 100%
Increments of 1 LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC CURVE C RAMP
Increments of 1 TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
JKSSS+ Series - 60
CURVE C RAMP
TIME 8: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C CURRENT
LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10
JKSSS+ Series - 61
MENU
(Hit DOWN ARROW seven times)
PAGE 8 OVERLOAD BASIC RUN RUN CURVE LOCKED RUN LOCKED ROTOR
CURVE CONFIGURATION OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range: 1 - 30 SEC, O/L CLASS Range: 400 - 800%
Configures the unit’s start and Increments of 1
motor’s locked rotor current and time. BASIC START START CURVE LOCKED START LOCKED ROTOR
OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range:1 - 30 SEC, O/L CLASS Range: 400 - 800%
SP8.1 Basic Run Overload Curve Increments of 1 Increments of 10
• Run Curve Locked Rotor
Time: Set the locked rotor time ACCELERATION TIME
to the OL Class default chosen LIMIT: 30 SEC
Range:1 - 300 SEC, DISABLED
in Setpoint Page 1 or set the Increments of 1
time in seconds. This is the
time the locked rotor condition NUMBER OF STARTS PER
exists before a trip occurs. HOUR: DISABLED
Range: 1 - 6, DISABLED
• Run Locked Rotor Current: Increments of 1
The current the motor draws
with full voltage on the windings TIME BETWEEN STARTS
TIME: 5 MIN
and no rotor movement (as a Range:1 - 60 MIN, DISABLED
percent of motor FLA). Refer to Increments of 1
the nameplate data or contact
AREA UNDER CURVE MAX I*I*T START
the motor manufacturer. PROTECTION: DISABLED : 368 FLA*FLA*SEC
• Coast Down Timer: If enabled, Range: ENABLED or DISABLED Range:1 - 2500, FLA*Time (Sec)
this prevents the motor from Increments of 1
• Start Curve Locked Rotor Time: The locked SP8.3 Area Under Curve Protection: If enabled, this
rotor time can be set to the OL Class default secondary start protection uses both the basic start
chosen in Setpoint Page 1 or to a specific protection and the area under the curve protection.
time. The overload condition must exist for the • Max I*I*T Start: The maximum I2T allowed during
programmed amount of time before a trip occurs. start. If the I2T to start exceeds this number then the
• Start Locked Rotor Current: The current the soft starter will generate a trip.
motor draws with full voltage on the windings and
no motor movement (as a percent of motor FLA). SP8.4 Current Over Curve: Learns the motor’s starting
Refer to the motor nameplate data or contact the characteristics and protects the motor based upon
motor manufacturer. the learned curve. It is useful when commissioning a
• Acceleration Time Limit: If the motor does not new motor.
enter run mode (reach at speed) within the preset • Learn: The unit reads the motor’s starting
time, the unit trips on acceleration time limit. characteristics. Start the motor and allow it to come
• Number of Starts per hour: If enabled, this to full speed. The start feedback enables the motor
limits the maximum number of starts permitted per protection based on the learned start curve.
hour. This setpoint allows a maximum of 6 starts • Learned Start Curve Basis: The maximum allowed
per hour. Contact motor manufacturer. deviation above or below the start curve before a trip
• Time Between Starts: If enabled, the soft is generated.
starter prevents another start attempt until the • Time for Sampling: The time the soft starter
programmed time has expired. continues to sample the start curve characteristic
during learn the mode.
JKSSS+ Series - 62
MENU
(Hit DOWN ARROW eight times)
Ranges:
* 120 OHM NICKEL (NI)
PAGE 9 RTD USE NEMA TEMP FOR 100 OHM NICKEL (NI)
CONFIGURATION RTD VALUES: DISABLED 10 OHM COPPER (CU)
100 OHM PLATINUM (PT)
Options: ENABLED OR OFF
DISABLED
** OFF or 0 - 240C (32-464F) Example: ### C = ### F
# OF RTD’S USED FOR Increments of 1
STATOR: 4
*** STATOR A1, STATOR A2, STATOR B1, STATOR B2, STATOR C1, STATOR C2,
Range: 0 - 6 FRONT BEARING, BACK BEARING, BEARING BOX, AMBIENT, NONE
Increments of 1
RTD VOTING
: DISABLED
Options: ENABLED or
DISABLED
STATOR PHASE A1 TYPE RTD # 1 DESCRIPTION STATOR PHASE A1 ALARM STATOR PHASE A1 TRIP
: OFF STATOR PHASE A1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
STATOR PHASE A2 TYPE RTD # 2 DESCRIPTION STATOR PHASE A2 ALARM STATOR PHASE A2 TRIP
: OFF STATOR PHASE A2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
STATOR PHASE B1 TYPE RTD # 3 DESCRIPTION STATOR PHASE B1 ALARM STATOR PHASE B1 TRIP
: OFF STATOR PHASE B1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
STATOR PHASE B2 TYPE RTD # 4 DESCRIPTION STATOR PHASE B2 ALARM STATOR PHASE B2 TRIP
: OFF STATOR PHASE B2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
STATOR PHASE C1 TYPE RTD # 5 DESCRIPTION STATOR PHASE C1 ALARM STATOR PHASE C1 TRIP
: OFF STATOR PHASE C1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: *** Range: ***
STATOR PHASE C2 TYPE RTD # 6 DESCRIPTION STATOR PHASE C2 ALARM STATOR PHASE C2 TRIP
: OFF STATOR PHASE C2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
END BEARING TYPE RTD #7 DESCRIPTION END BEARING ALARM END BEARING TRIP
: OFF END BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
SHAFT BEARING TYPE RTD # 8 DESCRIPTION SHAFT BEARING ALARM SHAFT BEARING TRIP
: OFF SHAFT BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **
JKSSS+ Series - 63
SP9.1 Use NEMA Temp for RTD Value: When this setpoint
is enabled, the soft starter will use the NEMA design
insulation class to limit the maximum allowed range
of the alarm and trip level. The maximum allowed
temperature range is 240° C or (464°F).
SP9.3 RTD Voting: When this is enabled, the soft starter will not
post a trip until 2 RTD’s have exceeded the trip level.
This prevents nuisance RTD tripping.
JKSSS+ Series - 64
JKSSS+ Series - 65
JKSSS+ Series - 66
MENU
(Hit DOWN ARROW eleven times)
THERMAL REGISTER
MINIMUM: 15%
Range: 10 - 50%, OFF
Increments of 1
USE CALCULATED K OR
ASSIGN: 7
Range: 1 - 50, ON
SP12.1 Default Display Screen: This setpoint group • Thermal Register Minimum: Sets the value
allows the user to choose the default screen the in the thermal register which represents a
soft starter displays while the motor is running. motor running at the nameplate current (with
Select the metering page number (1-3), then no overheating or negative sequence currents
select the metering screen number. The range present).
varies depending on the selected page. To display • Motor Design Ambient Temperature: Use the
a default screen, program the following two data from the motor manufacturer’s specifications.
setpoints: When RTDs are used, this setpoint will be the
• Metering Data Page#: Range is Page 1 - 3. base point for the RTD biasing of the Thermal
• Metering Data Screen#: If Page 1 is selected Register.
as the default page, then Screens 1- 10 are • Motor Design Run Temperature: Use the data
available. If Page 2, Screens 1-29 are available. from the motor manufacturer’s specifications. This
If Page 3 is selected, then Screens 1-6 are setpoint defines the operating temperature rise of
available. (See Metering Menu, MP.1, for screen the motor at full load amps or 100% load.
number assignment.) • Motor Stator Max Temperature: This represents
the maximum temperature the stator insulation
SP12.2 Alarms: Configures the RTD failure alarm and the will withstand. The user may choose to use
thermal register alarm. the temperature setting of the insulation class
• RTD Failure Alarm: If enabled, and an RTD (selected in Setpoint Page 1) or enter a specific
shorts or open, an alarm occurs. maximum temperature. This value should not
• Thermal Register Alarm: Sets a level in the exceed the stator’s insulation temperature. This
thermal register to generate an alarm when the maximum temperature represents 100% thermal
Thermal Register Capacity Used has exceeded capacity.
this level. • U/B Input to Thermal Register: Always enabled.
• Thermal Alarm Delay: The amount of time that It allows the soft starter to use the line current
the Thermal Register Used must exceed the imbalance information to bias the Thermal
setpoint before an alarm condition will occur. Register.
SP12.3 Thermal Register Setup Information: This • User Calculated K or Assign: When the setpoint
setpoint group will configure the thermal register is set to ON the controller will calculate the k
and indicate to the soft starter which inputs to use constant factor for biasing the thermal register, or
when thermal modeling. the user may choose to assign the k value.
• Cold Stall Time: Enter the time from the motor
manufacturer’s specification sheet or use the time SP12.4 Press Enter to CLR Thermal Register: Allows
defined by the OL Class. This setpoint is used to the level three password user to clear the thermal
define the thermal capacity of the motor. register for emergency restarts.
• Hot Stall Time: Enter the amount of time
specified by the motor manufacturer or use half of
the time defined by the OL Class.
• Stopped Cool Down Time: The time the motor
requires to cool down after it has stopped. Use
only the data provided by the motor manufacturer.
This setpoint is used to configure the cooling rate
of the thermal register.
• Running Cool Down Time: The amount of
time the motor requires for cooling down while
running. Use only the data provided by the motor
manufacturer.
• Relay Measured Cool Rates: When RTDs are
used, the soft starter can be configured to use the
measured cool rates from the RTDs instead of the
programmed settings. This setpoint should only be
enabled when RTDs are present.
JKSSS+ Series - 68
MENU
(Hit DOWN ARROW twelve times)
PAGE 13 CALIBRATION SET DATE AND TIME ENTER DATE (DDMMYYYY) ENTER TIME (hh:mm)
& SERVICE ##/##/## ##:## :##/##/#### :##:##
Range: D = 1 - 31, M = 1-12, Range: H = 00 - 23, M = 0 - 59
Y = 1970 - 2069 Increments of 1
Increments of 1
MODEL #: ######
FIRMWARE REV. #: ######
JKSSS+ Series - 69
JKSSS+ Series - 70
2
I T start curve trips 13
Learned start curve trips 14
Fail shunt trip trips 15
Phase loss trip trips 16
Tach accel trip trips 17
Undervoltage and Overvoltage trips 18
Power Factor trips 19
Phase reversal trips 20
Ext Inp #1 21
Ext Inp #2 22
Ext Inp #3 23
Ext Inp #4 24
Press enter to clear statistics 25
JKSSS+ Series - 71
MENU
METERING PAGE 1
CURRENT METERED DATA
METERING PAGE 2
VOLTAGE & POWER DATA
METERING PAGE 3
RTD VALUES
METERING PAGE 4
STATUS
METERING PAGE 5
EVENT RECORDER
METERING PAGE 6
LAST TRIP
METERING PAGE 7
STATISTICS
JKSSS+ Series - 72
Screen 4: Displays the line frequency and the present MOTOR LOAD % OF FLA
Phase Order. FLA: ### %
Screen 3
I*I*T TO START
Screen 9
I*I*T: #######
LAST START
Screen 10
TIME: ##.# SEC
JKSSS+ Series - 73
Screen 6
Screen 7: Displays Peak On and KVAR demand.
PEAK ON: ##/## ##:##
Note: P/F: N/A Motor stopped kVA: #####
P/F: LG #.## (Lagging)
P/F: LD #.## (Leading) Screen 7
PEAK ON: ##/## ##:##
Screen 8: Displays Peak On and Amps demand. kVAR: #####
Screen 8
Screen 9: Clears Demand Values. PEAK ON: ##/## ##:##
AMPS: #####
Screen 10: Displays the Megawatts used per hour.
Screen 9
Screen 11: Press Enter to clear statistics on MWH values. PRESS ENTER TO CLEAR
DEMAND VALUES
Screen 10
MWH USED
: #####
Screen 11
PRESS ENTER TO CLEAR
MWH VALUES
JKSSS+ Series - 74
MENU
Screen 1
METERING PAGE 3 HOTTEST STATOR
RTD VALUES RTD#: # @ ### C
Screen 19 Screen 20
RTD #9 MAX TEMP SINCE
RTD #9: ### C = ### F CLEAR RTD #9: ### C
Screen 21 Screen 22
RTD #10 MAX TEMP SINCE
RTD #10: ### C = ### F CLEAR RTD #10: ### C
Screen 23 Screen 24
RTD #11 MAX TEMP SINCE
RTD #11: ### C = ### F CLEAR RTD #11: ### C
Screen 25 Screen 26
RTD #12 MAX TEMP SINCE
RTD #12: ### C = ### F CLEAR RTD #12: ### C
Screen 27
PRESS ENTER TO
CLEAR MAX TEMP REGS
Screen 28
MEASURED RUN COOL
TIME: ### MIN
Screen 29
MEASURED STOPPED
COOL TIME: ### MIN
JKSSS+ Series - 75
3. MOTOR RUNNING
Screen 4
AT ###.## x FLA
COAST DOWN TIMER
4. LAST TRIP CAUSE TIME LEFT: #:## MIN
NONE (or trip cause)
Screen 5
5. PROGRAMMING
TIME BETWEEN STARTS
SETPOINTS TIME: #:## MIN
6. MOTOR STATUS
UNKNOWN STATE ### (displays relay state upon error) Screen 6
STARTS PER HOUR TIME
## ## ## ## ## ## ##
Screen 2: Displays the amount of time remaining before
an overload trip will occur.
JKSSS+ Series - 76
MENU
Screen 1 Screen 1a Screen 1b
METERING PAGE 5 :<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
Event Recorder (60 event) 1st :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event
:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
2nd :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event
:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
59th :##/##/## ##:##
Event
IC: ###### G/F: #### Vca: ###### P/F: ####
:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
60th :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event
All events will be viewed from oldest event in buffer to most recent event.
Screen 1b: Displays the Vab, Vbc, Vca and power factor at the
time of trip.
JKSSS+ Series - 77
Screen 5
Screen 6: Displays the hottest non-stator RTD HOTTEST STATOR
temperature at the time of the trip. RTD# # @ ### C
Screen 6
HOTTEST NON-STATOR
RTD# # @ ### C
JKSSS+ Series - 78
MENU
Screen 1
METERING PAGE 7 MWH TOTAL
STATISTICS : ###
Screen 2 Screen 3
Screen 13: Displays the number of I2T start curve trips. Screen 10
Screen 14: Displays the number of learned start curve ACCELERATION TIME
Screen 23
TRIPS: ###
trips. EXT INP #3: ###
Screen 15: Displays the number of fail shunt trips. Screen 11
Screen 16: Displays the number of phase loss trips. START UNDER CURVE
Screen 24
TRIPS: ###
Screen 17: Displays the number of tachometer EXT INP #4: ###
acceleration trips. Screen 12
Screen 18: Displays the number of undervoltage and START OVER CURVE
Screen 25
overvoltage trips. TRIPS: ###
PRESS ENTER TO
Screen 19: Displays the number of power factor trips. CLEAR STATISTICS
Screen 13 LEVEL 2 Password required
Screen 20: Displays the number of phase reversal trips. I*I*T START CURVE
Screen 21: Displays the number of external input #1 trips. TRIPS: ###
Screen 22: Displays the number of external input #2 trips.
Screen 14
Screen 23: Displays the number of external input #3 trips. LEARNED START CURVE
Screen 24: Displays the number of external input #4 trips. TRIPS: ###
Screen 16
PHASE LOSS TRIP
TRIPS: ###
Screen 17
TACH ACCEL TRIP
TRIPS: ###
JKSSS+ Series - 79
Note: If the unit is installed in a contaminated environment and forced air cooling is used, blower
filters must be checked and cleaned regularly to insure proper air flow and cooling of the enclosure.
Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
One of the main Short circuit between the
fuses blows or inputs
Locate and remove short
circuit breaker
opens when the TCB FAULT TRIP Trip AUX1
Remove power and test SCR(s). Refer to
power is applied
Faulty SCRs Section 7.1.1 for the SCR testing
or disconnect is procedure
open
Short circuit or ground fault
Locate and remove short or ground
in motor/cabling
Phase Loss Repair cause of phase loss
Branch circuit protection Verify correct sizing of branch circuit
Short Circuit Trip SHORT CIRCUIT TRIP not correctly sized protection
Trip AUX1
Remove power and replace main circuit
Faulty main circuit board
board.
Remove power and test SCR(s). Refer to
Faulty SCRs Section 7.1.1 for the SCR testing
procedure
Single phase incoming
Correct problem with incoming power
SINGLE PHASE TRIP power
Single Phase Trip (Check LCD display for Trip AUX1
Remove power and test SCR(s). Refer to
possible fault indicators)
Faulty SCRs Section 7.1.1 for the SCR testing
procedure
Thermostat trips EXTERNAL TRIP ON Verify that running current does not
Trip AUX1 Overcurrent on unit
during run THERMOSTAT exceed unit rating
Environment temperature
over 122° F (ambient
Place unit in environment temperature
temperature for chassis
less than 122°F for panel version or less
units) or over 104°F
than 104°F for enclosed version.
(ambient temperature for
enclosed version
JKSSS+ Series - 80
Aux
Proble m CPU LCD Displa y LED Possible Ca use Solutions
Re la y
Los s of 1 or m ore
phas es of power from Check power s ource
Phase Loss PHASE LOSS Trip AUX1
utility or generated power
W arning: This is a s erious fault condition. Ens ure that the fault
condition is cleared on the load before attem pting to res tart the
m otor.
Motor stopped
Check for fault indication Trip AUX1
during run
Load s horted/ grounded/
Rem ove power and repair.
faulted
Faulty m ain circuit board Replace the m ain circuit board
JKSSS+ Series - 81
Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
No control voltage applied Apply control voltage to TB1 pins 1 and 6
to control board on the power board
Voltage L1 L2 L3
Transformer
Ring
Transformer
Temp/ CT
3
1
Board
CT
Fiber Optics 4 3
1
2
CT
4
3
1
CT
4
2
A B C
DV/DT Boards
MOV Boards
Digital
Controller Main Fiber Optics
SCR Assembly
Firing Board
Control Board
Customer Connections T1 T2 T3
JKSSS+ Series - 83
JKSSS+ Series - 84
START STOP
Fuses Momentary
F1: Control Fuses for TB1 1 - 9
Part #ACG1A250VAC or equivalent
F2: Contactor and relay output fuses
Part #ACG4A250VAC or equivalent
F3: TB2 Pin #6
Part #ACG4A250VAC or equivalent
12
NC
Aux Start
11
NO
E1 E2 E3 E4 Output
10
C
Red AC 120 VAC
9
LED Neut
Neutral
8
Start
FUSE
7
T1 Red TB1 6
Stop
LED
5
Inter
FAULT 4
Lock
Optional
3 Interlocks
Inter
Lock
2
1
AC 120 VAC
HEATSINK
Source
Source
F1 10
NC
9
NO
F2 8
C
HEATSINK
7
FACTORY WIRED
N
Green DO NOT USE
LED F3 6
120VAC { Line
Neutral
1
2 -12V
TB2
5 S
NC
3 Green
4 Emergency Bypass
NO
4
5 +12V
2 Emergency Bypass
C
6
7
Dual Ramp ON OFF 12
NC
8 JP1
SW1 11
NO
10 during emergency 9
NC
bypass operation
8
NO
1
Run 7
TCB
C
2 TB3 6
NC
3
Lock Out
4 TB7 4
C
5
At Speed 3
NC
6
2
NO
7
1
C
Fuse Blown/
1 12
Disconnect
NC
AUX-S
DLY-S
PFC-C
DLY-C
PFC-S
AUX-C
Green
Interlock Input 2 LED 11
P.F.C. CAP
NO
3 10
TB8
C
7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1 OUT
5 8
NO
Coil A2 8 5
NO
Time Delay
A1 4
Main
{ 9 Green
C
Coil LED 3
A2 10
NC
DELAY
2
NO
TIMED 1
C
OUT
JKSSS+ Series - 85
JKSSS+ Series - 86
JKSSS+ Series - 87
Temp CT
Board
JKSSS+ Series - 88
JKSSS+ Series - 89
TEMP / CT Board
Gate Drive Board
MOV Board
DV/DT Board
Temp CT
Board
JKSSS+ Series - 90
DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment prior
to working on it.
Tools:
• Phillips screwdriver
• 3/8” 12 point socket set
• 2 9/16” wrenches
• ½” wrench
• AC/DC Multimeter
• JKSSS+ manual (refer to drawings in this section)
Procedure:
1. Verify that no DC or AC voltage is present on any of the power compo-
nents.
2. Disconnect all four wires connected to TB1 positions 1-3 on the tempera-
ture CT board.
3. Disconnect the 4 red transformer wires on each of the gate drive boards.
These would be TB1, positions 3 and 5 for each gate drive board. Typically,
the 2300V unit will have only 4 wires per phase to disconnect, a 4160V unit
will have 8 wires per phase, and a 6000 - 7200V unit will have 12 wires per
phase. (Note: the 7200V/600A unit will also have 24 wires.)
4. Use the 9/16 wrench and carefully unbolt all of the line and load power con-
nections attached to the heat sinks. Note: If the unit is a 6000 - 7200V, re-
move the power strap connecting one side of the stack to the stack directly
below it.
5. Before removing the fiber optic wiring, make a note of the label on the
fiber cable to ensure they are placed exactly in the same socket they were
removed from. Now remove all fiber optic connectors on the stack. Gently
push on the connector tab and pull with a gentle left-to-right motion on the
connector in the direction away from the fiber optic device. Two connectors
will be found per gate drive board and one duplex connector will be found
on the small Temp/CT board on top. Caution: Do not touch the tip of the
connectors or contaminate the connection sockets with any dust or foreign
material.
6. Remove the wires from the Temp/CT board terminal block (3 screws).
7. Use a 9/16” socket with a 6” extension to remove the lower bolt that
routes through the front face of the heat sink and into the isolation standoff
mounted to the white panel. Then carefully hold the heat sink in place with
one hand and remove the top bolt from the heat sink.
8. Ensure the fiber optic connectors and all wires are positioned out of the
way, and then the heat sink can be gently removed from the unit.
JKSSS+ Series - 91
SCR Replacement:
1. Remove white jumper wires on the gate drive board and make a note
of their placement.
2. Remove both 7/16 bolts and the singular 10 - 32 screw at the top of
gate drive board and lift off the board.
3. To remove the MOV board, remove the SCR gate/cathode leads (thin
red and white wires) and the white jumper wires attached to them.
Make a note as to how they were connected. Unbolt the ½” fasteners
as well.
4. At this point, all boards should now be removed from the aluminum
heat sink assembly.
5. Make a note (or drawing) of how each of the SCRs are oriented within
the heat sink. If factory supplied replacement SCRs and heatsinks are
used, the following steps are not required.
6. Loosen and carefully remove the ½” feed-through bolt and two black
springs that hold the assembly together and turn it on its side.
7. Remove the two (2) SCRs in the top layer, making certain to note that
the SCRs are not facing the same direction.
8. Remove the two (2) SCRs in the bottom layer, also making certain to
note that the SCRs are not facing the same direction.
9. Clean the heat sink surface area thoroughly and reapply some thermal
heat sink grease sparingly to the SCRs mating surfaces.
10. Please note that replacement SCRs are in matched sets of four and as
such, please try to keep the matched sets within the same phase.
11. Now, take any two SCRs from a set and place them on the heat sink in
the same direction as the old SCRs were, ensuring that the dimple in
the center of the SCR is properly placed onto the center pin of the heat
sink assembly. Place the next level of heat sink bar on the mounted
SCRs. Note: There is a difference in the heat sink bars. The center bar
has more holes drilled in it for mounting the circuit boards on it.
12. Now replace the other two (2) SCRs by repeating steps 10 and 11.
13. Next, carefully sandwich the SCRs and turn the stack over so the heat
sink bars are vertical and run the center bolt through the springs and
hand tighten the nut on the center bolt assembly.
14. Then make approximately 3 and ½ full revolutions on the nut to create
the appropriate amount of compression force. You can tell if there is
enough compression force applied to the heat sink by the fact that the
force needed to turn the nut will suddenly increase.
15. Finally, reinstall all boards in the same manner in which they were
removed.
16 Refer to drawing PCB for disassembling and reassembling the stack
assembly.
JKSSS+ Series - 92
Reinstallation:
1. Hold the rebuilt or new stack assembly in the vertical position with
the Temp/CT board on top (only the top stack assembly will have this
board in a multi-stack phase) and place the stack on the positioning
studs that protrude from the isolation standoffs.
2. While pressing on the stack to hold it on the positioning studs, place
the feed-through bolt through the heat sink and finger-tighten the top
bolt. Then repeat the process with the bottom feed-through bolt to
ensure the stack is held against the isolation standoffs.
3. After verifying no wires or fibers have been pinched between the stack
assembly and isolation standoffs, tighten the top bolt completely, then
repeat the process for the bottom bolt. Now the stack assembly should
be held firmly in place.
4. Using the 9/16” wrench reinstall the line and load power cables and
tighten.
5. If needed, refer to the appropriate drawing to reconnect red transformer
wires on each gate drive board. As an example, for the 4160V stack,
reattach TB4-1 to X3, TB4-3 to X4, TB1-3 to X2 and TB1-1 to X1. Verify
all X(#) wires are reconnected to their original position on the gate drive
boards. Otherwise the SCRs will misfire.
6. Reconnect thermostat wires on TB1 positions 2 and 3 of the Temp/CT
board.
7. Reconnect the main CT black wire to TB1-1. Then feed the white wire
through the board mounted CT and connect to TB1-1 on the Temp/
CT board. Please note that one each of the thick white wires from the
encapsulated CT must be connected with the Main CTs wiring.
8. Ensure the same fiber optic routing is used as before. If the fiber optic
wiring is positioned close to a heat source, (such as the 25-watt resis-
tors on the gate drive board) melting or distortion of the plastic fiber
may occur. Minimum distance is a ½ inch with a minimum bend radius
of 2 inches. All gate drive boards require 2 single connectors per board
and the Temp/CT connector is a duplex piece with a mating tab that
faces away from the stack. If the tab is broken off, refer to an adjacent
stack’s labels to see how the labels should be positioned when install-
ing a duplex connector with a broken tab. Again, caution should be
taken not to touch the fiber connector end or force it in with the tab
facing down.
JKSSS+ Series - 93
DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment prior
to working on it.
Tools:
• Phillips screwdriver
• Medium voltage fuse pullers if available
• Two control power transformer (Test PT) 500 VA minimum
• 120Vac control power (Test plug)
• Low voltage motor strapped for the proper voltage (typically 5 HP or
less)
• Oscilloscope if available
• Wire jumper
• Test switch (single pole i.e. - light switch)
JKSSS+ Series - 94
9. Verify or wire a 120Vac plug to the TEST plug supplied by the factory.
10. Remove all both power fuses on the medium voltage CPT (single
phase control power transformer), if present..
11. Remove 3 fuses from the medium voltage potential transformer (PT).
12. Verify the 120-volt test switch is in the “NORMAL” position.
13. Connect test power to test plug connector and place the 120-volt test
switch to the “TEST” position.
14. The keypad should be energized with the “Power LED,” Stop LED.
15. Close the temporary Start switch, which is connected to the control
board.
16. The Main Vacuum contactor should close and the keypad should
trip on “Under Voltage” Open temporary TEST switch and reset CPU
fault.
17. Connect the Secondary of the TEST PT to Panel TB1 positions 1 -
phase A, position 3- phase B, and position 5 - phase C on the main
firing board (JKSSS+-MB). It is physically located behind the low
voltage compartment door. (Screw terminal block)
18. Verify all connections are good and then energize the low voltage of
either 480 or 240 volt, three phases.
19. Use the multimeter on the AC scale and verify 3 phase 120Vac
(phase to phase) at TB1 pins 1, 3 and 5 of the main firing board.
20. If all 120Vac 3 phase is present then de-energize low voltage of 480
or 240Vac.
21. Re-energize the low voltage of 480 or 240Vac.
22. Now all test voltages should be present 480 or 240Vac and three
phase 120Vac (TEST PT) and 120Vac single phase for control
power.
23. Close the temporary Start switch and the test motor should spin up
smoothly.
24. Use the Multimeter on the AC scale and check (phase to phase)
voltages on T1, T2 and T3 motor leads. The voltages should be bal-
anced.
25. If the motor doesn’t spin up smoothly the soft starter is malfunction-
ing. Proceed to step 27 for troubleshooting.
26. If the motor starts and runs smoothly then repeat this procedure in
reverse to remove all test connect and reinstall all fuses.
JKSSS+ Series - 95
32. The gate and cathode leads are the white wires on the gate drive
board in the medium voltage cabinet. See drawing below.
33. If waveform is inverted, swap Oscilloscope connections for proper
polarity. Close the temporary Start switch and allow the test motor to
reach full speed.
34. Then verify all gating signals to each SCR (two gating signals on
every gate drive board). See drawing below for correct waveform.
35. Once the bad signal(s) are found; write down the location and call
the factory for further guidance.
Waveform is
the gating signal as
measured with an
ungrounded oscilloscope
at the gate to cathode
of the SCR. The
waveform should be 1.7
to 2msec off time and
approximately 1.5 to
3 Vdc. This signal is only
present at full conduction
or the motor is at speed.
Each SCR gating signal
should be checked
in accordance with the
low voltage test procedure.
JKSSS+ Series - 96
MAINTENANCE PROGRAM
Contact with energized components can cause severe injury, death and
property damage. Turn off and lock-out primary and control circuit power
before servicing.
MAINTENANCE RECORD
Keep a permanent record of all maintenance work. At a minimum, this record should
include information on:
1) Items inspected
2) Reports of any testing
3) Equipment condition
4) Corrective actions or adjustments
5) Date of work
6) Comments
The degree of detail of the record will depend somewhat on the operating
conditions.
SERVICING EQUIPMENT
For your safety, turn off and lock out main and control circuit power before servicing
the starter. Certain minimum safety procedures must be followed:
JKSSS+ Series - 97
DISPOSAL
STORAGE
If the starter is to be stored for any length of time prior to installation, the
following precautions should be taken:
2) Do not subject the equipment to moisture or sun rays. Store in cool, clean,
and dry location.
3) Place a dust cover over the starter packaging to protect against dirt and
moisture.
JKSSS+ Series - 98
Toshiba International Corporation (“Company”) warrants that all equipment and parts described herein will be free from
defects in materials and workmanship. THIS WARRANTY WILL EXPIRE TWENTY-FOUR (24) MONTHS AFTER SUCH
EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED
PURSUANT TO THIS WARRANTY) ARE PLACED IN OPERATION OR THIRTY (30) MONTHS AFTER THE DATE ON
WHICH SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS
FURNISHED PURSUANT TO THIS WARRANTY) ARE SHIPPED TO THE INITIAL PURCHASER, WHICHEVER PERIOD
FIRST EXPIRES. THERE ARE NO OTHER WARRANTIES WHETHER EXPRESS, IMPLIED, STATUTORY OR OTHER-
WISE, INCLUDING THE IMPLIED WARRANTIES OR MERCHANTABILITYAND FITNESS FOR A PARTICULAR PURPOSE.
The Company will, at its option, repair or replace or refund the purchase price paid for such equipment or part
which is defective under the terms of the foregoing warranty, free of charge; provided the purchaser (1) promptly
notifies the Company in writing of such defect, and (2) furnishes the Company satisfactory proof thereof, and (3)
establishes that the equipment or part has been properly installed, maintained and operated within the limits of rated
capacity and normal usage and in accordance with current operating and maintenance instructions , and (4) has
not been altered or modified in any manner without the written consent of the Company, and (5) if requested by the
Company, returns the defective equipment or part to the Company and pays all expenses incurred in connection
with such return. The repaired or replacement equipment or part will be delivered, free of charge, to the purchaser
F.O.B. the Company’s warehouse or, at the Company’s option, F.O.B. a Company authorized service shop, not
loaded on truck or other carrier. The purchaser will pay the costs applicable to the equipment or part following such
delivery, including, without limitation, all handling, transportation assembly, insurance, testing and inspection charges.
THE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL BE THE SOLE AND
EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USERS OF THE EQUIPMENT AND
PARTS FOR BREACH OF THE FOREGOING WARRANTY. THE COMPANY WILL HAVE NO OBLIGATIONS TO
DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE
WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COSTS
INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. THE COMPANY, TOSHIBA
CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTORS HEREBY DISCLAIM ALL OTHER EXPRESS,
STATUTORY AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, ALL EXPRESS, STATUTORY AND
IMPLIED WARRANTIES, SUCH AS MERCHANTIBILITY AND FITNESS FOR A PARTICULAR PURPOSE APPLICABLE TO
ALL REPAIRED OR REPLACED EQUIPMENT AND PARTS FURNISHED PURSUANT TO THE FOREGOING WARRANTY.
The total liability of the Company, Toshiba Corporation and their suppliers and subcontractors for any loss, damage or
claim, whether in contact, tort (including negligence and liability without fault), or otherwise, arising out of, connected
with or resulting from the equipment and parts described herein or the performance or breach of any contract for the
sale or supply of such equipment and parts, or from the design, manufacture, sale delivery, resale, installation, technical
direction or supervision of installation, inspection, testing, repair, replacement, operation, maintenance or use of any such
equipment or part or any service relating thereto furnished by the Company shall not in any event exceed the price
allocable to the equipment, part or service which gives claim, loss or damage. In no event, whether as a breach of
contract or warranty, alleged negligence, liability without fault, or otherwise, shall the Company, Toshiba Corporation or their
suppliers or subcontractors be liable for indirect, incidental, special or consequential damages, including, without limitation,
property damage, loss of profits or revenue, loss of information or data, loss of equipment described herein or any associated
equipment, cost of capital, cost of substitute equipment or parts, facilities or services, down-time costs, labor costs or claims
of customers of the purchaser for such damages, even if Company has been advised of the possibility of such damages.
Purchaser shall provide this Limited Warranty and Limitation of Liability to its customers and users of the equipment and
parts described herein prior to any sale to or use of the equipment and parts by such customer or user. Company does
not authorize anyone to make any representations or warranties other than the express warranties contained herein.
JKSSS+ Series - 99