Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 106

Document: VF010H05

INSTRUCTION MANUAL
__________________________________________________________________________

INSTALLATION - OPERATION - MAINTENANCE

JKSSS Plus Series

Medium Voltage Solid State Starters

Firmware Rev 6.96


Issued: 9/09
Manufactured in the USA

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
SAFETY

IMPORTANT MESSAGES

Read this manual and follow its intructions. Signal words such as DANGER, WARNING
and CAUTION will be followed by important safety information that must be carefully reviewed.

DANGER
Indicates a situation which will result in death, serious injury, and severe property damage if you
do not follow instructions.

Means that you might be seriously injured or killed if you do not follow instructions. Severe
WARNING
property damage might also occur.

CAUTION Means that you might be injured if you do not follow instructions. Equipment damage might
also occur.

NOTE Give you helpful information.

Note: The contents of this manual will not become apart of or modify the warranty policy.
The terms of which are set forth at the end of this manual.

READ SAFETY SIGNS

To avoid injury, you must read and follow all safety signs.

Keep the safety signs visible and in good shape. Never remove or cover any safety sign.

DANGER

QUALIFIED OPERATORS ONLY

Only qualified persons are to install, operate, or service this equipment according to all applicable
codes and established safety practices.

A qualified person must:

1) Carefully read the entire instruction manual.


2) Be skilled in the installation, construction or operation of the equipment and aware of
the hazards involved.
3) Be trained and authorized to safely energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, flash clothing, etc. in accordance with estab-
lished practices.
6) Be trained in rendering first aid.

Downloaded from www.Manualslib.com manuals search engine


SAFETY

SAFETY CODES

Toshiba motor control is designed and built in accordance with the latest applicable provisions of
NEMA and the National Electrical Code. Installations must comply with all applicable state and
local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions
provided in this manual.

HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and
property damage.

• Turn off and lock out Primary and Control Circuit Power before servicing.

• Keep all panels and covers securely in place.

• Never Defeat, Modify, or Bypass any Safety Interlocks.

• Qualified Operators only.


Never attempt to install, operate, maintain or dispose of this equipment until
WARNING
you have first read and understood all of the relevant product warnings and
user directions that are contained in this Instruction Manual.

Use only Toshiba-authorized replacement parts.



This equipment is designed and built in accordance with applicable safety
standards in effect on the date of manufacture. Unauthorized modifications
can result in voiding the warranty, severe injury, death and property
damage. Do not make any modifications to this equipment without
the written approval of Toshiba.

For assistance, address correspondence to:

Toshiba International Corporation


Field Service Department
13131 West Little York Road
Houston, Texas 77041 USA

or call: (713) 466-0277 Fax: (713) 466-8773
(800) 231-1412
(800) 527-1204 (Canada)

Please complete the following information for your records and retain with this manual:

Model: ___________________________________

Serial Number: _____________________________

Date of Installation: _________________________

Inspected by: ______________________________

Reference Number: _________________________

© TOSHIBA INTERNATIONAL CORPORATION, 2009

Downloaded from www.Manualslib.com manuals search engine


JKSSS+
JKSSS+Series
Series 2.3 - 4.2KV1
Chapter 1: Introduction .....................................................................................................
1.1 Overview
Medium Voltage Solid
1.2 Specifications
State Soft Starters 1.3 Design Features
2.3 - 4.2KV 1.4 Structure and Power Bus
1.5 Theory of Operation
1.6 General Protection
Installation &
1.7 Thermal Overload Protection
Operation Manual 1.8 Firing Circuit
1.9 Electronics

Chapter 2: Installation ..................................................................................................... 12


2.1 Receiving and Unpacking
2.2 Initial Unit Inspection
2.3 Location
2.4 Dimensions
2.5 Mounting
2.6 Additional Equipment
2.7 Before Applying Power
2.8 Warnings
2.9 Medium Voltage Power Connections
2.10 Control Connections and JKSSS+-TCB
2.11 Reference Section

Chapter 3: Start-Up ........................................................................................................ 29


3.1 Preliminary Start-up Check List
3.2 Introduction
3.3 Acceleration Adjustments
3.4 Deceleration Adjustments
3.5 Sequence of Normal Operation
3.6 Emergency Bypass Operation

Chapter 4: Programming ................................................................................................ 33


4.1 Keypad/Operator Interface
4.2 Menu Navigation

Chapter 5: Setpoint and Programming........................................................................... 36


5 .1 Setpoints Page List
5.2 Setpoint Menu
SP.1 Basic Configuration .................................................................................................46
SP.2 Starter Configuration ...............................................................................................47
SP.3 Phase & Ground Settings .......................................................................................50
SP.4 Relay Assignment ...................................................................................................53
SP.5 Relay Configuration ...............................................................................................55
SP.6 I/O Configuration ....................................................................................................56
SP.7 Custom Acceleration Curve ...................................................................................59
SP.8 Overload Curve Configuration ...............................................................................62
SP.9 RTD Configuration .................................................................................................63
SP.10 Set Password ........................................................................................................65
SP.11 Communications ...................................................................................................66
SP.12 System Setpoints ..................................................................................................67
SP.13 Calibration & Service ............................................................................................69

Chapter 6: Metering Pages .............................................................................................. 70


6 .1 Metering Page List

Chapter 7: Maintenance and Troubleshooting/Disposal/Storage ............................... 80


7.1 Failure Analysis
7.2 Typical Block Diagram
7.3 Overload Curve Definition
7.4 Typical Wiring Diagram for TCB Board
7.5 Typical Internal Wiring Diagram
7.6 Spare Parts List
7.7 Instructions for Stack Replacement
7.8 Instructions for Low Voltage Test
7.9 Maintenance Program/Servicing Equipment/Disposal/Storage

Warranty and Limitations of Liability ............................................................................. 99

JKSSS+ Series - 105

Downloaded from www.Manualslib.com manuals search engine


Reference Chart

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Chapter 1 - Introduction
This chapter is an introduction to the Toshiba JKSSS+ Series reduced voltage solid
state starter for medium voltage AC motors. It describes the basic configuration,
operation and unit features. It is highly recommended that new users read this
section thoroughly to gain a basic understanding of the starter system before
attempting to start up a unit. If you are already familiar with the JKSSS+ Series
starter, you may begin setup procedures immediately by proceeding to Chapter 2 –
Installation.

1.1 Overview
The standard JKSSS+ Series solid state starter is a complete NEMA Class E-2
motor controller designed for the starting, protection and control of AC medium
voltage motors. It contains the motor disconnect switch, motor circuit fuses,
control power transformer, a line isolation contactor, SCR stack assemblies, a
bypass contactor, low voltage controls and motor terminal blocks in that order.
An optional “soft start only” version is also available which is supplied without
the control power transformer, the disconnect switch and line isolation contactor.
(The soft start only model must be used with a customer supplied, mechanically
interlocked line start panel).

1.2 Specifications

JKSSS+ Series - 1

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
1.2 Specifications (continued)

Advanced Motor Protection

Two Stage Electronic Starting: Programmable for Class 5 through 30


Overload Curves Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Overload Reset Manual (default) or automatic
Overload circuit retains thermal condition of the motor regardless of control
Retentive Thermal Memory
power status. Unit uses real time clock to adjust for off time.

Overload will not reset until thermal capacity available in the motor is enough
Dynamic Reset Capacity for a successful restart. Starter learns and retains this information by
monitoring previous successful starts.
Phase Current Imbalance Imbalance Trip Level: 5 - 30% current between any two phases
Protection Imbalance Trip Delay: 1 -20 seconds
Over Current Protection Trip Level: 100 - 300% of motor FLA
(Electronic Shear Pin) Trip Delay: 1 - 20 seconds
Under Current Trip Level: 10 -90 % of motor FLA
Load Loss Trip Protection
Under Current Trip Delay: 1 - 60 seconds
Coast Down (Back Spin)
Coast Down Time Range: 1 - 60 minutes
Lockout Timer
Range: 1 - 6 successful starts per hour
Starts-per-hour Lockout Timer
Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Type / Rating Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA)
Run Indication Programmable
At Speed Indication Programmable
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Acceleration Adjustments
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 500% (VR or CR)
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Settings Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input

Begin Decel Level: 0 - 100% of line voltage


Deceleration Adjustments Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds

Jog Settings Voltage Jog: 5 - 75%


Kick Voltage: 10 - 100%
Kick Start Settings
Kick Time: 0.1 - 2 seconds
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload,
Fault Display
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Lockout Display Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
Event History

Data includes cause of event, time, date, voltage, power factor and current for
Up to 60 Events
each phase and ground fault current at time of event
JKSSS+ Series - 2

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

1.2 Specifications (continued)

Metering Functions
Motor Load Percent of FLA
Current Data A, B, C Phase Current, Avg Current, Ground Fault (Option)
Thermal Data Remaining thermal register; thermal capacity to start
Avg Start Time, Avg Start Current, Measured Capacity to start, time since last
Start Data
start
RTD Data (Option) Temperature readings from up to 12 RTDs (6 stator RTDs)
Voltage Metering kW, kVAR, PF, kWH
Serial Communications
Protocol Modbus RTU
Signal RS-485, RS-422 or RS232
Network Up to 247 devices per mode
Functionality Full operation, status view, and programming via communications port
Operator Interface
LCD Readout Alpha numeric LCD display
Keypad 8 function keys with tactile feedback
Status Indicators 12 LEDs include Power, Run, Alarm, Trip, Aux Relays
Up to 1000 circuit-feet from chassis (use twisted, shielded wire & power
Remote Mount Capability
source)
Clock and Memory
Operating Memory SRAM loaded from EEPROM at initialization
Factory Default Storage Flash EPROM, field replaceable
Customer Settings and Status Non-volatile EEPROM, no battery backup necessary
Real Time Clock Lithium ion battery for clock memory only

JKSSS+ Series - 3

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

1.3 Design Features


The standard JKSSS+ configuration is a complete NEMA Class E-2 motor
controller which includes the following features:

• Isolation Switch:
An isolation switch is provided in the incoming power section of the starter
assembly. The maximum voltage is 7200V.

Power is switched on and off to the controller by a fixed-mounted, externally-


operated, three-pole isolation switch. When the switch is in the opened
position, incoming power is isolated from the controller compartment interior by
an automatic shutter. For additional safety, the load terminals of the switch are
automatically grounded when the switch is opened. This allows any stored
energy in the controller load circuit to be discharged by closing the contactor
using test power.
A viewing window in the Main Incoming Power Compartment allows visual
inspection of the disconnect blade status with the medium voltage door closed.
The external operating handle for the isolation switch is designed to accept up
to three external padlocks in the OFF position.

For additional information on the isolation switch, see instruction manual


VF010H01, VF010H02 or VF010H03.

• Power Fuses: As a NEMA Class E2 controller, current limiting primary power


fuses are provided for each incoming phase.

Typically the fuses are ANSI class “R” for units rated up to 4800V. The fuses
are sized according to motor locked rotor current and are coordinated with the
solid state overload relay. The fuse and overload coordination is designed to
allow the controller and contactor to clear low and medium level faults. This
prevents exceeding the contactor interrupt ratings. Fuses interrupt high level
faults that exceed the contactor interrupt ratings. Fuse holders include blown
fuse indicators (wired to the isolation contactor circuit) to disconnect all three
phases if any one of the fuses clears (see section 2.7).

• SCR Power Modules: For each phase, the SCRs are


matched devices arranged in inverse parallel pairs and in
series strings as indicated in the chart to facilitate sufficient
PIV ratings for the applied voltage.

• RC Snubber Networks: Provide Transient Voltage Protec-


tion for SCR Power Modules in each phase to reduce dv/dt
damage.

• Firing Circuit: The SCRs are gated (turned on) using a


Sustained Pulse Firing Circuit. This circuitry is amplified and
isolated from the control voltage by means of fiber optics for
current and ring transformers.

Unit PIV Ratings

JKSSS+ Series - 4

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

• Contactors: Vacuum contactors are provided for both In-Line Isolation and SCR
Bypass. The contactor voltage ratings are: 7.2kV for 2300 - 6900V units.

A sequencing feature controls the contactors. Under normal operating conditions


this ensures that both contactors make and break under no-load conditions to
maximize contactor life. Vacuum contactors are rated for the maximum starting
requirement of the unit design. The Bypass Contactor is rated to be capable
of emergency start. For further information on the vacuum contactor, see the
instruction manual on the vacuum contactor supplied with the equipment, and
also either VF010H01 (400A Drawout Type) or VF010H03 (Fixed Type).

• Soft Start Only Option: The JKSSS+ Series is also offered in an optional “Soft
Start Only” package for use in retrofitting behind an existing customer supplied
line start controller. In this configuration, the Disconnect Switch, Fuses and
Line Isolation Vacuum Contactor are NOT included in the JKSSS+ unit, so
proper interlocking of sections containing medium voltage becomes the install-
er’s responsibility.

All retrofit “Soft Start Only” packages must be used with complete line isola-
tion using a contactor or other “air-gap” device. The Optional “Soft Start Only”
includes overload protection in normal operation mode and will sequence the
isolation contactor, so all logic control should be done at the JKSSS+ control
unit. Avoid turning the JKSSS+ on and off using the isolation device.

1.4 Structure and Power Bus


The JKSSS+ Series is a heavy duty design. Special consideration has been given
to the enclosure and unit design to ensure that it is suitable for most applications and
environments.

• Structure: 11 gauge frame with 16 gauge side, back and top sheets. Doors are
12 gauge steel. The enclosure assembly is NEMA / EEMAC type 1 as standard.
Type 12 and 3R are available as an option.

• Sections: In a typical arrangement, each enclosure is divided vertically into


three major compartments, each with a separate door. In the JK400, the upper-
most and lowermost compartments contain medium voltage controller compo-
nents (>600V) while the middle compartment contains low voltage components
(<600V). Other variations of this basic arrangement are possible.

The Main Incoming Power Compartment houses the main disconnect switch,
amain power fuses and input isolation contactor. A viewing window provides
clear indication of the switch position without opening the compartment. Main
Bus Compartment contains the horizontal bus bars (if provided). Top, bottom or
side cable entry can be made with minimum bending.
One or more Starter Power Compartments contain the bypass vacuum con-
tactors, SCR power modules, instrument transformers and all other medium
voltage devices. Adequate room is provided for motor lead connections to be
made with minimum conductor bend.

A Low Voltage Control Compartment houses the digital microprocessor


controller and LCD keypad operator interface, along with any other low voltage
devices. This allows the operator to make adjustments without exposure to the
line voltages.

JKSSS+ Series - 5

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Removable conduit entry plates are provided in the bottom of the enclosure to
facilitate drilling and punching of conduit holes without exposing the equip-
ment to contamination from metal debris.

• Enclosure Finish: The enclosure is suitable for use in noncorrosive environ-


ments. The paint is ANSI 61 gray polyurethane powder over a zinc phosphate
pretreatment with a minimum thickness of 2 mil. 11 gauge steel is used in all
enclosures. All NEMA 1 & 12 units have bottom entrance plates.

• Lifting Provisions: Eyes or angles capable of supporting the maximum


weight of each shipping split are provided on the top of the enclosure.

• Power Bus: Optional main horizontal phase bus bars can be configured to
extend the entire length of the starter lineup. Bus bar material is tin-plated or
silver-plated copper. All bus ratings are per UL Standard 347.

• Bracing: Bus bars are braced with non-tracking fire resistant non-hygroscopic
insulation supports and have a minimum fault current rating of 50,000 Amps.

• Connections: All bus connections use 2 bolts minimum, with Belleville spring
washers to ensure tightness. Splice kits for each shipping split are included,
along with specific installation instructions.

• Ground Bus: A continuous ground bus bar with a minimum rating of 400
Amps extends the entire length of the starter near the bottom of each enclo-
sure. A grounding strap connects each vertically adjacent compartment and
also ties the grounding arm of the disconnect switch to the main ground bus
bar (see section 2.11).

• Seismic Qualifications: The entire starter assembly, when properly installed,


withstands vertical and horizontal accelerations typical of seismic Zones 1
through 4 as defined in the UBC. The assembly will not overturn or show
significant lateral movement, but cannot be expected to continue operating
during, or after, a seismic event.

1.5 Theory of Operation


The power of the JKSSS+ Series is in the CPU, a microprocessor based
protection and control system for the motor and starter assembly. The CPU
uses Phase Angle Firing of the SCRs to apply a reduced voltage to the motor,
and then slowly and gently increases torque through control of the voltage and
current until the motor accelerates to full speed. This starting method lowers
the starting current of the motor, reducing electrical stresses on the power
system and motor. It also reduces peak starting torque stresses on both the
motor and load mechanical components, promoting longer service life and
less downtime.

Acceleration: The JKSSS+ Series comes standard with several methods of


accelerating the motor so that it can be programmed to match almost any
industrial AC motor application.

The factory default setting applies a Voltage Ramp with Current Limit as this
has been proven the most reliable starting method for the vast majority of
applications. Using this starting method, the Initial Torque setting applies just
enough voltage to the motor to cause the motor shaft to begin to turn. This
voltage is then gradually increased over time (as per the Ramp Time setting)

JKSSS+ Series - 6

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

until one of three things happen: the motor accelerates to full speed, the Ramp
Time expires or a Current Limit setting is reached.

If the motor accelerates to full speed before the ramp time setting has expired,
an automatic Anti-Oscillation feature will override the remaining ramp time and
full voltage will be applied. This will prevent any surging or pulsation in the mo-
tor torque, which might otherwise occur due to the load not being fully coupled
to the motor when operating at reduced voltage and torque levels.

If the motor has not reached full speed at the end of the ramp time setting,
the current limit setting will proportionally control the maximum output torque.
Feedback sensors in the JKSSS+ Series provide protection from a stall condi-
tion, an overload condition or excessive acceleration time.

The Current Limit feature is provided to accommodate installations where there


is limited power available (for example, on-site generator power or utility lines
with limited capacity). The torque is increased until the motor current reaches
the preset Current Limit point and it is then held at that level. Current Limit
overrides the ramp time setting so if the motor has not accelerated to full speed
under the Current Limit setting, the current remains limited for as long as it
takes the motor to accelerate to full speed.

When the motor reaches full speed and the current drops to running levels, the
soft starter detects an At-Speed condition and closes the Bypass Contactor.
The Bypass Contactor serves to shunt power around the SCR stack assemblies
to prevent heat buildup in the starter enclosure due to the slight voltage drop
across the SCRs. At this point, the soft starter has the motor operating at full
voltage, just as any other starter would.

Other starting methods available in the soft starter are:

· Current Ramp: Uses a closed current feedback PID loop to provide a linear
torque increase up to a Maximum Current level.

· Constant Current: Current is immediately increased to the Current Limit


point and held there until the motor reaches full speed.

· Custom Curve: Gives the user the ability to plot torque and time points on a
graph. The soft starter will then accelerate the motor following these points.

· Tachometer Feedback Ramp: Uses a closed loop speed follower method


monitoring a tachometer input signal from the motor or load shaft.

Deceleration: The soft starter provides the user with the option of having
the load coast to a stop or controlling the deceleration by slowly reducing the
voltage to the motor upon initiating a stop command. The Decel feature is the
opposite of DC injection braking in that the motor will actually take longer
to come to a stop than if allowed to coast to a stop. The most common ap-
plication for the Decel feature is pumping applications where a controlled stop
prevents water hammer and mechanical damage to the system.

JKSSS+ Series - 7

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

1.6 General Protection


The soft starter is provided with a built-in motor protection relay that can be
programmed for primary protection of the motor/load system. Operation of the soft
starter can be divided into 4 modes; Ready, Start, Run and Stop.

Ready Mode: In this mode, control and line power are applied and the starter is
ready for a start command. Protection during this mode includes the monitoring
of current for leakage through multiple shorted SCRs or welded contacts on the
Bypass Contactor. Other protection features in effect are:

· Starter Temperature
· Shorted SCR
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults

Note: The “Programming Mode” can only be entered from the Ready Mode.
During programming, all protection features and start command are disabled.

Start Mode: These additional protection functions are enabled when the soft
starter receives a valid Start command:

· Phase Reversal (if enabled)


· Start Curve
· Acceleration Timer
· Phase Imbalance
· Short Circuit / Load Pre-check (Toe-in-the-Water)
· Ground Fault (Optional)
· External Input Faults
· Accumulated Starting FLA Units (I2t Protection)
· Overload Protection
· Thermal Capacity

Note: Shorted SCR and Shunt Trip protection are no longer in effect once the
soft starter goes into the Start Mode.

Run Mode: The soft starter enters the Run Mode when it reaches full output
voltage and the motor current drops below the FLA setting (motor nameplate
FLA plus service factor) for a predetermined period of time. During the Run Mode
these additional protection features are enabled:

· Running Overload Curve


· Phase Loss
· Under Current / Load Loss
· Over Current / Electronic Shear Pin (Jam protection)
· External Input Faults

Stop Mode: Once a Stop command has been given, the protection features
change depending on which Stop Mode is selected.

· Decel Mode: Retains all protection features of the Run Mode. At the end of
Decel, the motor will be stopped and the protection features change as
indicated below.

JKSSS+ Series - 8

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

· Coast-To-Stop Mode: Power is immediately removed from the motor and the
soft starter returns to the Ready Mode.

Additional protection features activated when the stop command is given include:
· Coast-Down / Back Spin Timer
· Starts-per-Hour
· Time Between Starts
· External Input Faults

1.7 Thermal Overload Protection


The JKSSS+ Series plays an important role in the protection of your motor in that it
monitors the motor for excessive thermal conditions due to starting, running or even
ambient conditions. The soft starter has a Dynamic Thermal Register system in the
CPU that provides a mathematical representation of the thermal state of the motor.
This thermal state information is kept in memory and is monitored for excesses in
both value and rate of change. Input is derived from current imbalances and RTD
measurements making it dynamic to all processes involving the motor. The starter
monitors these conditions separately during Start and Run modes to provide proper
thermal overload protection at all times.

Start Mode overload protection is selectable using one of three methods:

· Basic Protection: I2t data is accumulated and plotted based on an Overload


Curve selected in programming. This is programmed per NEMA Class 5-30
standard curves and is based on the Locked Rotor Current (from the motor
nameplate) as programmed into the soft starter.

· Measured Start Capacity: The user enters a measured amount of thermal


capacity from a pre-selected successful start as a setpoint to the Thermal Reg-
ister for the soft starter to follow.

· Learned Curve Protection: The user sets the soft starter to the “LEARN”
mode and starts the motor under normal starting conditions. The CPU then
samples and records 100 data points during the start curve, analyzes them and
creates a graphical representation in memory. The soft starter is then switched
to Curve Follow protection mode and monitors motor performance against this
curve. This feature is especially useful in initial commissioning tests to record a
base line performance sample (in this case, it is not necessarily used for motor
protection).

Run Mode overload protection is initiated when the starter determines that the
motor is At-Speed. Overload Protection is initiated when the motor RMS current
rises above a “pick-up point” (as determined by the motor nameplate FLA and
service factor). Run mode protection is provided by the CPU monitoring the Dy-
namic Thermal Register. Data for the Dynamic Thermal Register is accumulated
from I2t calculations and cooling rates. A trip occurs when the register reaches
100% as determined by the selected Overload Protection Curve (NEMA Class
5-30 standard curves) and is based on the programmed Locked Rotor Current
indicated on the motor nameplate. The Dynamic Thermal Register is altered, or
“biased”, by the following conditions:

· Current Imbalance: Will bias the register higher to add protection from ad-
ditional motor heating during a current imbalance condition.

· Normal Cooling: Provided when the motor current drops below the pick-up
point or the motor is off line. The cooling rate is lower for motors that are off-line
(such as after a trip) since cooling fans are also inoperative.

JKSSS+ Series - 9

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

· RTD Input: Will bias the register in either direction based on real-time input of
the motor, bearing and even ambient temperature conditions.

· Dynamic Reset is another feature that adds reliability and consistency to the
performance of the soft starter. If a motor overload condition occurs and the soft
starter trips, it cannot be reset until sufficient cool down time has elapsed. This
cool down time is determined by the thermal state of the motor when it tripped
(i.e. hot motors cool more quickly due to additional convection). The cool down
time is also biased by RTD measurements when used.

· Retentive Memory provides continuous overload protection and real time
reset even if power is lost. Upon restoration of power, the soft starter will
read the Real Time Clock and restore the thermal register to what it should be
given the elapsed time.

· Learned Reset Capacity is a feature that is unique to the JKSSS+ Series. By


sampling the amount of thermal capacity used in the previous three successful
starts, the soft starter will not allow a reset until a sufficient amount of thermal
capacity has been regained in the motor. This prevents nuisance tripping and
insures that unsuccessful start attempts (which would otherwise use up the
starts-per-hour capacity of the motor) are not counted.

1.8 Firing Circuit


The SCR gate firing circuit is critical to performance and stability of the system.
The firing circuit includes several unique features which enhance the ruggedness,
noise immunity and flexibility for maximized performance. In most applications, this
performance is attained without the need for reactors or field installed devices. These
features include:

Auto Synchronizing of the gate timing pulses match each phase firing angle
to their respective phases. The starter actively tracks minor shifts in the line fre-
quency, avoiding nuisance tripping that may happen with conventional gate firing
systems. This is especially useful on portable or backup generator supplies,
allowing the starter to be used confidently in applications that have unstable
power.

Sustained Pulse firing keeps the firing signal active for 270 electrical degrees,
ensuring that the DC gate pulse causes the SCR to fire even if line noise is
present at a critical moment. This provides the soft starter with superior noise
immunity and protects against misfiring, enhancing the system reliability.

Closed Loop Firing Control is a method of balancing the SCR firing pattern
based on the desired output. The CPU uses feedback signals from both the
output current and voltage providing smooth output and preventing imbalances
during ramping which prevents unnecessary motor heating.

Transformer Isolation of the firing signals prevents interference from line noise
and EMI/RFI signals that may be present. Specially designed 120V 3 phase iso-
lation transformers provide potential measurement, firing board power and gate
power systems while being isolated from the line voltage. High isolation Ring
Transformers are used to step this down to 28Vac for the Sustained Pulse firing
circuit, providing further isolation for the SCR gates.

Fiber Optic Isolation is provided for all signal interfaces between the Medium
Voltage and Low Voltage systems. Even the current signals from CTs are con-
verted to fiber optic signals for maximum isolation and safety.

JKSSS+ Series - 10

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

1.9 Electronics
The JKSSS+ Series electronics systems are divided into two categories, Low Voltage
and Medium Voltage, based solely on where they are located in the starter structure.

Low Voltage electronics include the Keypad Operator Interface, CPU and Main
Power PC boards are located in an isolated Low Voltage Compartment of the
enclosure.

· Keypad Operator Interface: a 2 line x 20 character LCD display with backlight-


ing for low ambient conditions. The display reads out in truncated English and
can show multiple data points in each screen. Also included are 12 LED indica-
tors, which include Power, Run, Alarm, Trip and the status of the 8 Aux. Relays.
It communicates to the CPU via a serial link and, if necessary, can be remotely
mounted up to 1000’ from the soft starter.

· CPU Board: where the microprocessor and communications coprocessor


reside. It is attached to the main power board, and communicates to it and
the Keypad Operator Interface via serial links. The CPU determines operating
functions, stores user programming and acts upon feedback signals for faults,
metering and historical data. This board also contains the flash EPROM and
SRAM memory, as well as the Analog I/O and terminations. Keypad Operator Interface

· Main Power Board: is also referred to as the Firing Board. It contains the
Digital I/O relays and interfaces to the TCB board (see below) for user inter-
face. It also controls the sequencing of the Isolation and Bypass contactors with
the SCR firing. This board generates all firing signals for the SCR stacks and
receives feedback signals from fiber optic transmitters. It converts analog levels
to digital signals for the CPU. These firing pulses are via fiber optic signals to
isolate them from the Medium Voltage environment.

Control Electronics are located in the medium voltage and low voltage sections of
the soft starter. The main line power must be disconnected before these electronics
can be accessed. They include the TCB, Gate Drive and Temp/CT boards.

· TCB (Terminal and Control Board): is the user connection interface board. It
is located in the Low Voltage section in order to satisfy UL termination require-
ments, and does not connect directly to the medium voltage components other
than the contactor coils. This board contains the user terminal blocks, output
relays (duplicated), inputs and control power connections. It also contains ad-
ditional timed relays for interfacing with Power Factor Correction contactors (if
used) and other external devices. Please note Power Factor Capacitor warn-
ings in Section 2.8.

· Gate Drive Boards: located directly on the SCR stacks. These boards com-
municate to the Main Power board via fiber optic cables. They amplify the gate
pulse signals with power from the Ring Transformers to create the Sustained
Pulse Firing of the SCRs. There is one Gate Drive board for each pair of SCRs
in each stack.

· Temp / CT Boards: are attached to the Gate Drive boards on the SCR stacks
and provide the heat sink temperature and current signals back to the Main
Power Board via fiber optic cables.

· MOV Boards: are attached to standoffs mounted on the SCR heat sinks and
are mounted directly below the Gate Drive boards. The MOV boards are used
to protect the gate/cathode section of the SCRs.

· DV/DT Boards: are also attached to standoffs mounted on the SCR heat sinks
and are mounted below the MOV boards. The DV/DT boards are used to re-
duce voltage transients across the stack assemblies.
JKSSS+ Series - 11

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Chapter 2 - Installation
For additional information on the equipment, refer to the following additional
instruction manuals:
For fixed type input isolation contactor - “JK Series Medium Voltage Controllers
- Fixed Type”, manual number VF010H03 or “JK Series 720 Ampere Medium
Voltage Controllers”, manual number VF010H02.
For drawout type input isolation contactor - “JK Series Medium Voltage
Controllers”, manual number VF010H01.

2.1 - Receiving, Handling/Moving and Unpacking


Upon receipt of the equipment, do the following:
• All JKSSS+ Series units are shipped in the vertical (upright) position and should be
handled accordingly when received. If the controller is not upright upon receipt, notify
the carrier of possible damage. Upright the unit as soon as possible. Immediately
notify the nearest Toshiba representative.
• Carefully unpack the unit and make an immediate inspection for any damage which
might have occurred during shipment. If damage is found, it should be noted with the
carrier prior to accepting the shipment, if possible. Report any damage immediately
and file a claim with the freight carrier within 15 days of receipt.
• Carefully unpack the equipment sufficiently to check for concealed damage and
to verify that the starter description on your unit matches your purchase order.
The starter information is located on stickers in the medium voltage, incoming
compartment.
• Keep the equipment upright. If is located on stickers in the medium voltage, incoming
compartment.

WARNING Do not install or energize equipment that has been damaged.

CAUTION Do not lay the equipment on its side or upside down.

Handling and Moving


Medium voltage motor controllers should be handled with care, to avoid damage to
components and to the frame or its finish.

The capability of the moving equipment to handle the weight of the controller shipping
section should be confirmed. The equipment should remain secured to the shipping skid
to prevent distortion of the frame during moving and to minimize tipping. Extreme care
should be exercised during any movement and placement operations to prevent dropping
or tipping.

Do not place any part of your body beneath equipment


WARNING
being lifted. Improperly secured equipment
can fall or tip over quickly and without notice.

Using a Forklift
A forklift truck may offer a more convenient method of handling the controller. A safety
strap should be used when handling with a forklift. The ends of the forks should not enter
the bottom of an open-bottom enclosure.

Overhead Lifting
When it is necessary to move the equipment between elevations, overhead hoisting may
be required. Lifting angles (for multiple controller sections) are provided on top of the
enclosure for this purpose. Spreaders (Fig. 1) should be used to provide the vertical lift
on single controllers to prevent eye-bolt failure.
JKSSS+ Series - 12

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Always keep the controller upright while lifting. Some controller sections may contain
heavy or special equipment that will cause the center of gravity to be off-center. Rigging
lengths should be adjusted to maintain the controller in an upright position. The angle
between the lifting cables and vertical should not be allowed to exceed 45 degrees
(Fig. 2). Ropes or cables should not pass through the holes in lifting angles or eye-
bolts. Slings with safety hooks or shackles of adequate load rating should be used.

2.2 - Initial Inspection


• Make a complete visual check of the unit for damage which
may have occurred during shipping and handling. Do not
attempt to continue installation or start up the unit if it is
damaged.
• Check for loose mechanical assemblies or broken wires
which may have occurred during transportation or handling.
Loose electrical connections will increase resistance and
cause the unit to function improperly.
• Prior to beginning the installation, verify that the motor and
JKSSS unit are rated for the proper amperage and voltage.

2.3 - Location
Storage
If the controller is to be stored for any length of time prior to
installation, the packing should be restored for protection
during that period. Where conditions permit, the packing
should be left intact until the controller is at the final installation
position. If the packing is removed, the top and openings Fig. 1 Use of Spreader Bar - Single Section
of the controller should be covered during the construction
period to protect it against dust and debris.

Indoor Equipment
Controllers designed for indoor installation (NEMA Type 1, 12)
which are not to be installed and energized immediately, should
be stored in a clean, dry space where a uniform temperature
prevents condensation. Preferably, the controller should be
stored in a heated building, with adequate air circulation and
protected from dirt and water. Equipment should be stored
where it is not subject to mechanical damage, especially during
building construction. An indoor controller that is to be stored
outdoors should be securely covered for protection from weather
conditions and dirt. Temporary electrical heating should be
installed to prevent condensation. Approximately 150 watts per
enclosure is usually adequate.

NOTE: All loose packing or flammable materials should be


removed before energizing space heaters.
Fig. 2 Lifting Multiple Sections
Outdoor Equipment
An unenergized controller designed for outdoor installation (NEMA Type 3R, EPIC
building, etc.) should be kept dry internally by installing electrical heating or by energiz-
ing self-heaters, if provided. All openings, either used or unused should be covered or
sealed to prevent the entry of rain, vermin, insects, etc.

JKSSS+ Series - 13

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Routine Inspection
Routine scheduled inspection should be established if storage for an extended period is
anticipated. This is to check for condensation, corrosion, vermin, and adequacy of space
heating. Prior to inspection, the equipment should be carefully examined for evidence of
physical damage, corrosion, or other deterioration.


WARNING Do not install equipment found to have damage or
deterioration that could affect the unit performance.

Overhead should be checked for plumbing condensation, sprinklers or similar possible


sources of trouble. A clearance of 1/2 inch should be provided between a wall and the rear
of the controller for indoor equipment, when rear access is not required. If rear access is
required in either environment, a minimum of 30 inches should be provided. A minimum
of 48 inches working space should be allowed in front of the controller. This minimum
should be increased if necessary to accommodate movement around open enclosure
doors to comply with applicable codes.

SERVICE CONDITIONS

Toshiba medium voltage controllers are intended for usual service conditions as defined
by NEMA. The equipment should not be exposed to corrosive or explosive fumes, dusts,
vapors, dripping or standing water, abnormal vibration, shock, tilting, or other abnormal
operation conditions. The temperature of the ambient air surrounding the controller should
be between the limits of 0°C(32°F) and +40°C(104°F). The altitude of the equipment
installed should not exceed 3300 ft (1000m).

NOTE: Temperature or altitude conditions outside of the usual limits may require derating
or other special equipment, such as heating, cooling or ventilation. Contact Toshiba for
further information.

If the location for installation is damp, space heaters may be required. If space heaters
are furnished inside the controller, they should be connected in accordance with the wir-
ing diagram furnished.

Do not install this equipment in areas where unusual service


WARNING
conditions exist, unless the equipment has been specially
designed for the particular environment.

Installation Site Preparation


It is recommended that site preparation be completed before the controller is unpacked,
so that possible problems such as headroom, conduit location, cable tray locations, ven-
tilation, etc. can be solved, assuring a proper installation in compliance with the building
plans and codes. The floor on which the controller will be placed must be level so that the
enclosure is not distorted when bolted in place. Ensure the equipment adequately clears
any underground raceways or cables.

JKSSS+ Series - 14

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.4 - Dimensions

Note: Dimensions are for reference only and subject to change.


Contact factory for exact dimensions.

2.5 - Mounting
Each shipping section must be leveled and firmly secured to its supporting
foundation. Steel shims may be used for final leveling (Fig. 3), if necessary.
When three or more shipping sections are to be arranged in one continuous
line-up, the center shipping section should normally be the first located.

Follow the equipment outline drawings to determine the location of the


mounting bolt holes and any conduit locations.

Sill channels may or may not be furnished, depending on order specifica-


tions. Refer to outline drawings furnished for location
of sill channels, if furnished.

Various methods may be used to anchor the enclosure to the foundation,


including expandable inserts or “J” bolts embedded
in concrete. The recommended size for anchor bolts is 1/2" (Fig. 4). Fig. 3 Leveling Using Shims

Heavy Equipment. Enclosure must be securely


anchored to prevent tipping over.

2.6 - Additional Cabinet Entries


If conduit entry locations are required in areas other than the
removable plates, cover the electrical assemblies to prevent
metal filings from becoming lodged in areas which may cause
a reduction in the high voltage clearances or a short circuit.
After the work is completed, thoroughly clean the area and
reinspect the unit for foreign material.

2.7 - Pre-energization Check


AFTER INSTALLATION, BUT BEFORE ENERGIZING THE CONTROLLER
for the first time, follow the procedure below to
verify that the equipment is properly installed and functional. Fig. 4 Securely Anchor the Controller
JKSSS+ Series - 15

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

There is a rating data label on the inside of each medium voltage compartment door.
Verify that the controller ratings properly match the system data by checking the follow-
ing:

1. Verify agreement of full load current, locked rotor current and acceleration time
with motor nameplate.

2. Verify that system voltage, number of phases and frequency matches controller
rating.

3. Verify that available short circuit current of power system is less than rated
short circuit capacity of controller.

Check connections - Although the equipment and devices have been completely tested
at the factory, a final field check should be made that all electrical wiring and bus bar
connections are correct and have not become loose in transportation. Refer to MAINTE-
NANCE Section for electrical joint specification.

All blocks or other temporary braces used for shipment must be removed.

Before closing the enclosure, all metal chips, scrap wire and other debris left over from
installation must be cleaned out.

If there is an appreciable accumulation of dust or dirt, the enclosure should be cleaned


by using a brush, vacuum cleaner or clean, lint free brush.

The integrity of all bus bar supports must be checked for secureness and damage.

Care should be exercised that when covers are installed and doors closed, no wires are
pinched and that all enclosure parts are properly aligned and tightened.

A supply of spare parts, fuses, etc. should be established.

Instruction manuals and diagrams should be collected and filed.

WIRING CHECK

Field wiring should be checked for clearance to live busses where necessary, physically
secured to withstand the effects of fault current.

All grounding connections should be checked.

Each motor should be connected to its intended controller, and phase rotation should be
correct prior to startup.

Changes made to circuit diagrams during installation should be recorded.

DEVICE/MECHANISM CHECKS

All devices should be checked for damage. All necessary repairs or replacements should
be made.

Do not energize damaged equipment that has not been repaired


WARNING and verified.
JKSSS+ Series - 16

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Ensure that safety signs are not covered or obscured by paint.

WARNING
Do not remove, cover or destroy any safety signs.

The setting of any adjustable current and voltage trip mechanisms should be verified to
the proper values.

NOTE: Damage from faults can be reduced if devices used for short circuit and ground
fault protection are chosen and set to operate at values as close to minimum as feasible,
while allowing normal transients.

All switches, relays and other operating mechanisms should be manually exercised to
make certain that they are properly aligned and operate freely.

Operating mechanisms such as interlocks, key switches, etc. should be checked for func-
tion as intended for protection of personnel and equipment.

Overload relay settings should be checked to be sure they are selected and adjusted to
the proper settings per the load nameplate data.

Power circuit fuses were selected and installed in accordance with the application re-
quirements. Fuses must be completely inserted in their holders. Instruction on removing
and installing the fuses can be found in one of the following manuals: VF010H03 (Fixed
Type) or VF010H01 (Drawout Type).

Electrical Checks

With incoming power isolated and all loads disconnected electrically, the control cir-
cuit and other mechanisms should be exercised to determine that the devices operate
properly. An auxiliary source of control power will be necessary to provide power to the
electrical operators.

Electrical shock hazard. Do not touch energized components


WARNING
during a test using auxiliary power.

The ground fault protection system (if furnished) should be tested in accordance with the
instructions furnished with the device.

An electrical insulation test should be performed to ensure that the controller and asso-
ciated field wiring are free from short circuits and grounds. The preferred method is to
perform a dielectric test at 2.25 times the nominal system voltage plus 2000 volts. This
should be done phase-to-ground, phase-to-phase and phase-to-neutral (if applicable),
with all switches and circuit breakers opened. Disconnect any devices which may have
limited dielectric strength and that are not intended for this test.

The light or buzzer, or both, used to indicate breakdown should be calibrated to indicate
failure with an output current between 1.5 and 2.0 milliamperes per 1000 volts applied.

Hazardous voltages are present during dielectric testing


WARNING
which can result in serious injury or death. High potential
tests should be performed only by qualified personnel.
Refer to safety instructions provided with the test equipment.

All devices must be set to their normal or OFF position before energizing incoming power.

JKSSS+ Series - 17

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.8 - Warnings & Cautions

WARNING This section involves working with potentially lethal voltage


levels! Use extreme caution to prevent injury. Pressing “Stop”
push button does not remove AC mains potential.

WARNING Do not service this equipment with voltage applied! The unit
can be the source of fatal electric shocks! To avoid shock
hazard, disconnect main power and control power before
working on the unit. Warning labels must be attached to
terminals, enclosure and control panel to meet local codes.

CAUTION
Do not connect the capacitors to the load side (motor side)
of the solid state starter. This will cause di/dt damage to the ! CAUTION
SCRs when they are turned on. SCR DAMAGE
Do not connect (PFC) capacitors to the load side of
the unit.
Do not connect the capacitors to the input side of the unit.
CAUTION Doing so will cause DI/DT damage to the SCRs when
If you cannot avoid using capacitors across the power lines, they energized.
must be located as far upstream as possible of the input line
contactor. In this situation, optional power factor correction (PFC)
caps contactor should be specified. For additional information and
specifications, please contact the factory.

CAUTION
Never interchange the input and output power connections
on the unit. This will cause excessive voltage to the control circuit
logic.

CAUTION
For bus protection, it is strongly recommended to use non-gap
lightning arrestors in areas where lightning is a significant
problem. The arrestors should be mounted on the nearest utility pole.

2.9 - Medium Voltage Power Connections


Use a properly calibrated torque wrench to tighten all MV connections Torque at Full
Bolt
according to the chart. Engagement
Size
(ft - lbs)
Connections 1/4 - 20 6
Cable and wire bundles that enter the controller enclosure should be routed to 3/16 - 18 12
avoid interference with moving parts. Minimum bending radius for the type of 3/8 - 16 18
cable used should be observed. 7/16 - 14 30
1/2 - 13 45
Power cables should be braced and/or laced to withstand short circuit forces 9/16 - 12 68
wherever such cables are unsupported. Power cables should be adequately sized 5/8 - 11 90
to carry the motor full load current in accordance with NEC requirements, and 3/4 - 10 150
have an adequate voltage rating. Cables should be dressed and terminated as 7/8 - 9 240
appropriate to the voltage class and cable manufacturer’s recommendations.
1.0 - 8 245
Torque Specs for MV Power
Main power bus (when provided) and horizontal ground bus are supplied with links Connections
to join shipping sections together. These should be installed in accordance with Fig.
5 through Fig. 7.

All access covers, barriers, partitions, etc. that are temporarily removed during installation
must be replaced.

JKSSS+ Series - 18

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

NOTE: Covers and braces supplied only for protection during shipment should not be
replaced. All debris and tools should be removed from each compartment as cabling is
completed.

Fig. 5 Main Bus Splice Connections - 1200A Main Bus

Fig. 6 Main Bus Splice Connections - 2000A Main Bus

JKSSS+ Series - 19

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.9.1 - Incoming Line


On the Standard JKSSS, incoming power cable connections should be made at the
points shown on the wiring diagram furnished with the equipment.

Note: Proper phase sequence must be observed when connecting the input power.
For example, phase A must lead phase B, which in turn must lead phase C by 120°
respectively. If the phase rotation is not correct, a fault light and the LCD display will
indicate the problem. The SCR output will be clamped.

2.9.2- Load Connections


The load cables should be routed through the wireways furnished within the enclosure.
Load cable termination arrangements, refer to the drawings furnished with the equip-
ment.

2.9.3- Ground Connections


The controller line-up must be grounded in accordance with the requirements of the Na-
tional Electrical Code. Proper equipment grounding must be established before making
any incoming power connection. If a main ground bus is furnished, make the ground con-
nection to this bus. If there is no ground bus, the sections which are shipped separately
should be connected in such a way as to ensure a continuous grounding path.

Each section contains a vertical ground bus extending from the main ground bus or ground
pad to each controller compartment.

Special attention should be paid to protection for operating personnel, to protection of


equipment itself, (i.e. such as ground fault relays, if used) and protection of sensitive
transducers or control devices that are electronic in nature.

The following may be used as a general guide with regard to equipment grounding.

Controller used as service equipment for a grounded system or as a main section for a
seperately derived system:

a. The grounding electrode conductor (ground wire) sized in accordance with NEC 250
should be run from the grounding electrode to the controller ground bus or ground
terminal.

b. Unless already done at the factory, a main bonding jumper should be installed from
the incoming grounded connector bus (neutral) to the ground bus or designated
grounding point. If a jumper is not furnished, one having a size in accordance with
NEC 250 should be selected.

c. Steps (a) and (b) should effectively connect together the grounding electrode, the
controller frame, all outgoing equipment grounding conductors and the grounded
neutral bus of the system.

d. No connection should be made to ground on the load side of any neutral disconnecting
line or any sensor used for ground fault protection. No connections should be made
between outgoing grounding connectors and the neutral.

e. Where the controller or system is dual-fed (double-ended) and has ground fault
protection, special precautions are necessary to accomplish proper grounding and
bonding.

JKSSS+ Series - 20

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Controller used as service equipment for an ungrounded system or as a main section for a separately derived
system.

a. A grounding electrode conductor (ground wire) sized in accordance with NEC 250 should be run from the
grounding electrode to the controller ground bus or ground terminal.

b. If the system is grounded at any point ahead of the controller, the grounded conductor should be run to the
controller in accordance with NEC 250 and connected to the ground bus or ground terminal.

c. Steps (a) and (b) should effectively connect together the grounding electrode, the controller frame, all outgoing
equipment grounding connectors and any grounded conductor which runs to the controller.

Controller not used as service equipment or as a main section for a separately derived system, and used on either
a grounded or ungrounded system:

a. The controller frame and any ground bus should be grounded by means of equipment grounding conductors
having a size in accordance with NEC 250 and run with the main supply conductors or by bonding to the
raceway enclosing the main supply conductors in accordance with NEC 250.

b. Ground leads should be connected to cable potheads/shields as specified by the manufacturer of these de-
vices.

Fig. 7 Ground Bus Splice

JKSSS+ Series - 21

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.10 Control Connections - TCB (Terminal and Control Board)

WARNING
This section involves C us tomer P rovided
potentially lethal voltage
levels! Use extreme Momentary or Maintained
caution to prevent injury. S tart / S top S witching
Maintained

Do not bypass the electrical or mechanical S TAR T S TOP
interlocks. This will cause severe equipment Fus es Momentary
damage and possible fatal injury. F1: C ontrol Fus es for TB 1 1 - 9
P art #AC G 1A250 VAC or equivalent
F2: C ontactor and relay output fus es

2.10.1 JKSSS Plus-TCB Board


P art #AC G 4A250 VAC or equivalent
F3: TB 2 P in #6

The JKSSS Plus-TCB board provides P art #AC G 4A250 VAC or equivalent

interconnections between the main power and 12


CPU boards and the customer’s control logic Aux S tart

NC
11
Output

NO
E1 E2 E3
connections. It is a 120Vac control board with
E4
10
120 VAC

C
R ed
several auxiliary dry control contacts, built-in
AC
9
LED Neut
Neutral
8
time delay circuits and emergency bypass func- FUS E
7
S tart

tions. It also controls the sequence of the inline T1 R ed TB 1 6


S top

LED
isolation and bypass contactor and provides 5
Inter

provisions for shutdown interlocks. (see section FAULT 4


Loc k
Optional
Interloc ks
2.10.2) 3
Inter
Loc k
2
1
AC 120 VAC

HE ATSINK
S ourc e
S ourc e
F1 10

NC
9

NO
HE AT S INK
F2 8
FAC TOR Y WIR E D

C
7
G reen DO NOT US E

N
F3
{
LED 6
Line 1

S
120VAC 5
Neutral 2 -12V
TB 2

NC
Start/Stop Control 3 G reen
4 E mergenc y B ypas s

NO
Delayed S tart G reen
Figure 2-1 4
LED LED 3 AUX C ontac ts

C
5 +12V S TAR T
2 E mergenc y B ypas s
F use B lown/

C
Disconnect Open TB 6 1 F ull Voltage S tart
2.10.2 Description of Terminal Connections 6

NO
7
Dual R amp ON OFF 12
J P1

NC
8
Start/Stop Control - Terminal Block 1 (TB1) : S W1 11

NO
9 R emove J P 1 for electronic 10
B ypass S tatus DUA L ADJ
• Positions 1 and 9 are the 120 Vac control power. motor overload protection

Fault
10 during emergency 9
bypass operation NC
• Positions 2-3 and 4-5 are factory jumpers 8
NO

installed and can be removed for customer’s


1
R un 7
TC B
C

2 TB 3
normally closed, dry, shutdown contacts (See 6
NC

3
Fig. 2-1 above).
C P U (AUX1) F ault
TB 7 B OAR D 5
Lock Out
NO

4
4
• Positions 6-7-8 are for either two wire or three-
C

5
At S peed 3
NC

wire start/stop logic. Two wire is connected to 6


2
NO

7
positions 6 and 8 with a N.O. dry, maintained 1
C

F use B lown/
start/stop contact. Three wire control connects Disconnect 1 12
NC
AUX-S
DLY-S
PFC-C
DLY-C
PFC-S

AUX-C

G reen
to 6 with 7 as the stop push-button, and the start Interlock Input 2 LED 11
NO

P.F.C. CA P

push-button is connected to 7 and 8. E xternal Overload


3
TB 8 10
C

PFC
4 9
• Positions 10-11-12 is a dry FORM C contact. T IME D
NC

7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1 OUT 8
5
B ypass Aux C ontact
The contact is an immediate start/stop contact.
NO

6 7
TB 4
{
C

B ypass A1 7 PFC AUX S TAR T 6


NC

C oil A2 8 5
NO

{
T ime Delay

Main A1 9 G reen 4
C

C oil LED 3
A2 10
NC

DE L AY
2
NO

T IME D 1
OUT
C

TCB (Terminal and Control Board)


Figure 2-2
(See page 85 for larger version)

JKSSS+ Series - 22

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Emergency Bypass Control - Terminal Block 2 (TB2): TB2
• Positions 1 and 2 are for an emergency bypass contact. If a dry contact
closes position 1 and 2, this causes the CPU to be shut off
so there is no display. Then when a start is initiated, it pulls in the inline
isolation contactor which starts the motor across the line. #1 #2 #3 #4 #5
NO O C NO NC
#6 #7
S N
#8 #9 #10
C NO NC
See section 3.6 for more details. EMER BYP
SWITCH
INTER
LOCK
CUST. POWER DELAYED
OUTPUT START
• Positions 3-4-5 are a FORM C contact. This is a dry contact that is Emergency Bypass Control
initiated by the emergency contact being closed. It provides indication Figure 2-3
of the emergency bypass mode.
• Positions 6 and 7 is a customer connection for control power. Position CAUTION
6 is the 120 Vac supply at (400 VA) and position 7 is the return.
OVERLOAD PROTECTION LOSS
• Positions 8-9-10 are a FORM C contact. The dry contact is a delayed start/
stop contact. The amount of delay is determined by X1, X2 and SW3. See When operating the unit in Emergency Bypass Mode,
there is no electronic overload protection.
“Switch Positions” and “Jumper Selection” on the next page. Note: Additional
Time Delay to SP2 of the CPU programming. External overload protection must be provided for
continued safe operation.
• JP1 - Motor Protection Jumper. Removing jumper JP1 on the TCB Board will
allow the soft starter CPU to continue providing electronic motor protection while operating in the Emer-
gency Bypass Mode. If necessary to disable the CPU system during operation in Emergency Bypass, be
sure JP1 is placed over both pins and an external means of overload protection is used.

Fault - Terminal Block 3 (TB3): TB3


• Positions 1-2-3 and 4-5-6 are sets of FORM C contacts. These are dry
contacts that operate when a blown fuse indication is given or discon-
nect is open.
#1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12
• Positions 7-8-9 and 10-11-12 are sets of FORM C contacts. These are C NO NC C NO NC C NO NC C NO NC

fault contacts that change state if any fault condition occurs.


Lockout/Fault Contacts
Figure 2-4
Optional Relay - Terminal 4 (TB4):
• Positions 1-2-3 and 4-5-6 are sets of FORM C contacts. These are aux-
iliary time delay contacts that will change state (after a delay) when the
Start contact is initiated. X3, X4 and SW4 determine the amount of delay.
(Switch Position and Jumper Selection on following page)
• Positions 7-8-9 and 10-11-12 are sets of FORM C contacts. These are
power factor correction capacitor (PFC) contacts to pull in an isolation con-
tactor for the capacitors (if required by the application). These will change
state when the At Speed contact is initiated. X5, X6 and SW5 determine the
amount of delay. See “Switch Positions” and “Jumper Selection” on Time
Delay/PFC Cap Contacts
the following page. Note: This delay is in addition to SP2 of the CPU programming. Figure 2-5

Terminal Block 6 (TB6):


• Positions 1 and 2 are 120 VAC power supply to the Main and CPU circuit boards.
• Positions 3 and 4 are the start input connections to the Main and CPU circuit boards.
• Positions 5 and 6 are the fuse blown input connections to the Main and CPU circuit boards.
• Positions 7 and 8 are the Dual Ramp input connections to the Main and CPU circuit boards.
• Positions 9 and 10 are the Bypass Status input connections to the Main and CPU circuit boards.

Terminal Block 7 (TB7):


• Positions 1 and 2 are the Run contacts (AUX 3) from the Main and CPU circuit boards to the TCB board.
This signal is used to hold the Main Contactor closed during deceleration.
• Positions 3 and 4 are the Main and CPU circuit board output connections to the TCB that signal the AUX1
Fault Status.
• Positions 5 and 6 are the At Speed contacts (AUX 4) from the Main and CPU circuit boards that signal the
Bypass Contactor to close.
• Position 7 has no connection..

Terminal Block 8 (TB8):


• Positions 1 and 2 accept dry, normally closed contacts from blown fuse indicators and/or disconnect inter-
lock contact.
• Positions 3 and 4 accept dry, normally closed contacts from an external overload protection device (re-
quired if emergency bypass is used).

JKSSS+ Series - 23

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

• Positions 5 and 6 accept dry, normally closed contact from the bypass contac-
tor for an At Speed indication. (Factory wired)
• Positions 7 and 8 are wired to the coil of the bypass contactor and energizes
and de-energizes the contactor. (Factory wired)
• Positions 9 and 10 are wired to the coil of the inline isolation contactor and
energizes and de-energizes the contactor.
Note: All customer contacts are 960VA, 120VAC (Max) rated dry contacts.

LEDs provided on the TCB board (for low voltage testing only):
• -12 VDC power supply
• +12 VDC power supply
• Start = start is initiated to TCB board
• Fault = any fault has occurred
• Fuse Blown = disconnect open or blown fuse has activated
• PFC On = Power Factor Correction Capacitor contacts have energized
• Timed Out = Auxiliary time delay contacts have energized

Jumper Selection
For the following, please refer to Figure 2-6.

Start Delay
This is a selectable delay period between the intiation of the start command and
when the CPU actually receives the start signal. Selecting Jumper X1 or X2 deter- Jumper Selection on TCB Board
mines the method by which this delay (in cycles or seconds) is calculated. See SW3 Figure 2-6

below for instructions on setting the actual delay time.


• X1 = (DLY-C) Start time delay in cycles
• X2 = (DLY-S) Start time delay in seconds (Factory setting)

Auxiliary (Start) Delay (from the time the start input is given). Selecting jumper X3 or
X4 determines the method by which this delay is calculated (cycles or seconds). See
SW4 below for instructions on setting delay time.
• X3 = (AUX-C) Auxiliary time delay in cycles
• X4 = (AUX-S) Auxiliary time delay in seconds (Factory setting)

Power Factor Correction (PFC) Capacitor Contactor Delay (From the time the
bypass closes to when contacts change state). Jumper selection determines the
method by which this delay is calculated. See SW5 for instructions.
• X5 = (PFC-C) Time delay in cycles
• X6 = (PFC-S) Time delay in seconds (Factory setting)

Switch Positions
Please refer to Figure 2-7.
• SW1 = ON = Dual Adjustment
OFF = Disabled
• SW2* = Not used - Switches SW3, SW4 and SW5 are 7 position dip switches
that use binary code to count up to 127 seconds/cycles (see “Jumper Selec-
Figure 2-7
tion” above).
Example:
• SW3 = Start Delay; 7 position dip switch uses binary count up to 127 seconds/
Switch settings are cumulative.
cycles (see jumper selection above). Factory setting: 1 second. Setting dip switch positions 1, 2,
• SW4** = Auxiliary (Start) Delay 7 position dip switch uses binary count up to and 3 to “on” = 1+2+4 = 7 seconds
127 seconds/cycles (see jumper selection above). Factory setting: 1 second. total time. Note: This example ap-
• SW5** = PFC time delay; 7 position dip switch uses binary count up to 127 plies to SW3, SW4 & SW5.
seconds/cycles (see jumper selection above). Factory setting: 1 second.
* Note: This switch interacts with the CPU programming when the Decel function is
enabled.
** Note: These times are in addition to SP2 in the CPU setpoints.

JKSSS+ Series - 24

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.11 Reference Section

2.11a RTD Board

RTD1 RTD2 RTD3 RTD4 RTD5 RTD6 RTD7 RTD8 RTD9 RTD10 RTD11 RTD12
Compensation
Shield
Power
Signal

RTD
Typical RTD
Installation

JKSSS+ Series - 25

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.11b Communications Board

REAR
VIEW

(RS485) (RS422)

Note: Remove for last unit in modbus string

2.11c Communications Board Connections

RS485 Connections RS422 Connections


(Customer Connections) (Factory Only)
JKSSS+ Series - 26

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.11d Power Board

Board
Ground Test Points
19 1 7 1 7 1 19 1

20 2 J3 20 J6 2
J5 J4

AI

AT

BI

BT

CI

CT

3
GF

1
J1

C2 C1

7
7, A - Phase
B2 B1

4, B - Phase
A2 A1

1, C - Phase

1
J2
1
3

J8
J7 J2

6
1
F1

TB1 TB2
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
TB3

2.11e Power Board Connections

TB1 TB2
Factory use only. Do not reprogram. Refer to Setpoint Page 5 for programming information

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C.
AUX1 AUX2 AUX3 AUX4 AUX5 AUX6 AUX7 AUX8
(TRIP) (ALARM) (RUN) (AT SPEED) Relay Relay Relay Relay
Relay Relay Relay Relay

(Max Relay Contact Rating is 240 VAC, 4A, 960VA)

JKSSS+ Series - 27

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

2.11f CPU Board Connections

1 2

19 20

1 2

19 20

Contact factory for remote


reset connections Factory wired. Do not change
Analog Output #1

Analog Output #2

Program Enable

UV-P Rotation
Input

Thermostat
Tach Input

Dual Ramp
4 - 20 mA

4 - 20 mA

TCB Fault

TB1 TB2 TB3

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

+ - + - + - + - + - + - + -
+ -
Note: Install program jumper to enable
setpoint programming. Jumper must be
removed after programming or for
prolonged storage to preserve settings.

JKSSS+ Series - 28

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Chapter 3 - Start-up
The JKSSS+ unit deals with potentially lethal voltage
WARNING
levels. You must be certain that personnel are
thoroughly trained in the applicable safety
precautions before proceeding with this section!

3.1 Preliminary Start-Up Check List


Please make the following checks before applying power to the unit:
• Qualified personnel have hi-potted the line and load wiring before connecting to the soft
start. (Typically 1.5 x Rated Voltage)
• Verify that all wiring is completed and all connections are tightened.
• Check the motor nameplate and confirm the unit is programmed with the correct motor
FLA.
Note: It is necessary to connect the line power to L1, L2 and L3, or the “Phase
Rotation Protection” will be activated.
• Verify control logic via 120V test switcher (available on standard JKSSS+ NEMA Class
E2 Starters only). A separate 120Vac test receptacle can be supplied to the control logic
without powering up the medium voltage section for control logic testing. It also allows
isolation of the 120Vac from back-feeding the control power transformer.
• Connect control supply (Optional “Soft Start Only” Package only). The “On” and “Stop”
LEDs will light up.
• Review all parameters and readjust as required. See Chapter 5 - Programming for de-
tailed instructions. Try factory settings first.
• Verify that the interlocks for the system are installed and working properly.
• Verify that the feed transformer is correctly sized for the motor(s).
• Check for any loose mechanical parts or metal debris in the enclosure.
• Check the motor strapping and connections.
• Verify that the unit is properly grounded.
• Remove tie straps from Blown Fuse Indicator.
• Connect line voltage to line terminals.

3.2 Introduction
It is best to operate the motor at its full load starting condition to achieve the proper time,
torque and ramp settings. Initial settings are set to accommodate most motor conditions.
TRY INITIAL SETTINGS FIRST. See Setpoint 5.1.2 Starter Confiuration (Setpoint Page
2) to make any adjustments.

3.3 Acceleration Adjustments


The unit is set at the factory with typical starting characteristics that perform well in most
applications. When the system is ready to start, try the initial unit settings. If the motor
does not come up to speed, increase the current limit setting. If the motor does not start
to turn as soon as desired, raise the starting voltage adjustment. Adjustment description
and procedures are described as follows. See Setpoint 5.1.2 Starter Configuration (Set-
point Page 2) for additional Accel settings.

3.3.1 Starting Voltage


Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
Starting voltage adjustment changes the initial starting voltage level to the motor.

3.3.2 Ramp Time


Factory Setting = 10 sec.
Range = 0 - 120 sec.
Ramp time adjustment changes the amount of time it takes to reach the current limit
point or full voltage if the current limit point was not reached.
Note: Refer to your motor manual for the maximum number of starts per hour allowed by
the manufacturer and do not exceed the recommended number.

JKSSS+ Series - 29

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

3.3.3 Current Limit


Factory Setting = 350% of unit FLA
Range = 200% - 500% of unit FLA
The current limit adjustment is factory set for 350% of the unit’s rating.
The range of adjustment is 200% to 500%. The main function of cur-
rent limit is to cap the peak current. It may also be used to extend the
ramping time if required. The interaction between the voltage ramp
and the current limit will allow the soft start to ramp the motor until the
maximum current is reached and the current limit will hold the current
at that level. The current limit must be set high enough to allow the
motor to reach full speed. The factory setting of 350% is a good start-
ing point. Do not set the current limit too low on variable starting
loads. This could cause the motor to stall and eventually cause
the overload protection to trip.
Note: If the motor does stall, refer to the motor manufacturer’s motor data
for the proper cooling time.

3.4 Deceleration Adjustments (Pump Control)


Decel extends the stopping time on loads that would otherwise stop too
quickly if allowed to coast to stop. Decel control provides smooth deceler-
ation until the load comes to a stop. Three adjustments optimize the deceleration
curve to meet the most demanding requirements. The unit is shipped from the
factory with the decel feature disabled.

Deceleration Applications
The unit is shipped from the factory with the decel feature disabled.
Apply power and adjust the soft start before enabling or modifying the
deceleration adjustments. Both acceleration and deceleration adjust-
ments should be made under normal load conditions.

The deceleration feature provides a slow decrease in the output voltage,


accomplishing a gentle decrease in motor torque during the stopping
mode. This is the OPPOSITE OF BRAKING in that it will take longer to
come to a stop than if the starter were just turned off. The primary use
of this function is to reduce the sudden changes in pressure that are
associated with “Water Hammer” and slamming of check valves with
centrifugal pumps. Decel control in pump applications is often referred to
as Pump Control.

In a pump system, liquid is being pushed uphill. The force exerted by


gravity on the column of liquid as it goes up hill is called the “Head
Pressure” in the system. The pump is sized to provide enough Output
Pressure to overcome the Head Pressure and move the fluid up the
pipe. When the pump is turned off, the Output Pressure rapidly drops
to zero and the Head Pressure takes over to send the fluid back down
the hill. A “Check Valve” is used somewhere in the system to prevent
this (if necessary) by only allowing the liquid to flow in one direction. The
kinetic energy in that moving fluid is suddenly trapped when the valve
slams closed. Since fluids can’t compress, that energy is transformed
into a “Shock Wave” that travels through the piping system looking for
an outlet in which it dissipates. The sound of that shock wave is referred
to as “Water Hammer”. The energy in that shock wave can be extremely
damaging to pipes, fittings, flanges, seals and mounting systems.
By using the Soft Stop/Deceleration feature of the soft starter, the pump
output torque is gradually and gently reduced, which slowly reduces the
pressure in the pipe. When the Output Pressure is just slightly lower than
the Head Pressure, the flow slowly reverses and closes the Check Valve.
By this time there is very little energy left in the moving fluid and the
JKSSS+ Series - 30

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Shock Wave is avoided. When the output voltage to the motor is low enough to no longer
be needed, the soft starter will end the Decel cycle and turn itself off.
Another common application for decel control is on material handling conveyors as a
means to prevent sudden stops that may cause products to fall over or to bump into one
another. In overhead crane applications, soft stopping of the Bridge or Trolley can prevent
loads from beginning to over swing on sudden stops.

3.4.1 Start Deceleration Voltage


Factory Setting = 60% of line voltage
Range = 0% - 100% of line voltage
The step down voltage adjustment eliminates the dead band in the deceleration mode
that is experienced while the voltage drops to a level where the motor deceleration is
responsive to decreased voltage. This feature allows for an instantaneous drop in volt-
age when deceleration is initiated.

3.4.2 Stop Deceleration Voltage


Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
The stop voltage level setpoint is where the deceleration voltage drops to zero.

3.4.3 Deceleration Time


Factory Setting = 5 sec.
Range = 0 - 60 sec.
The deceleration ramp time adjusts the time it takes to reach the stop voltage level set
point. The unit should be restarted and stopped to verify that the desired deceleration
time has been achieved.

Do not exceed the motor manufacturer’s recommended


WARNING
number of starts per hour. When calculating the
number of starts per hour, a decel curve should be
counted as a start curve. For example: recommended
number of starts per hour = 6, allowable starts with
decel cycle per hour = 3.

3.5 Sequence of Normal Operation


• Apply control power and check that the “Power” LED comes on. (Display 1)
• Apply three phase power to the unit. The motor should run only when the
start command is applied.
• Apply the start command. (Display 2). The RUN LED will be lit. (Display 3)
The AUX3 LED will be lit. If the motor does not enter run mode in the
set time (Acceleration time limit, see SP8.2), a trip will occur.
JKSSS+ Series - 31

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

• When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit. MOTOR STOPPED
Display 1
• The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has READY TO START

energized. IA, IB, IC will display the current setting for Phase A, Phase B,
MOTOR STARTING
and Phase C and the G/F indicates ground fault. (Display 4) Display 2 00 X FLA
• If the motor decelerates, or stops, during the acceleration period, hit the
stop button immediately and open the disconnect line. If the unit does not Display 3 OVERLOAD ALARM
TIME TO TRIP: XXX SECS.
follow this operational sequence, please refer to the Troubleshooting Chapter.
IA: _ _ _ IB: _ _ _
Display 4
It is best to operate the motor at its full load starting condition to achieve the proper IC: _ _ _ G/F: _ _ _
time, torque and ramp settings. Initial settings are set to accommodate most motor
conditions. TRY INITIAL SETTINGS FIRST. See Section 5.1.1 (Setpoint Page 2) to
make any adjustments.
• Initial Voltage
• Soft Start Curve
• Current Limit
• Acceleration Time

If decel is enabled, the following parameters for Deceleration Time, Start Decel Volt-
age (see SP2) and Stop Decel Voltage (see SP2) must also be programmed.

3.6 Emergency Bypass Operation


! DANGER
HAZARDOUS OPERATION
Do not operate the Bypass Contactor with medium
voltage power applied to the unit.

Failure to follow this instruction will cause the motor


to start unexpectedly.

Remove input power (using line start section and lock out disconnect).
• Close the emergency bypass contact.
• Re-close the disconnect on line start panel.
• If integral overload protection is not to be used (see JP-1 Motor Protection
Jumper), then bimetallic or solid state overload protection is required
(customer supplied if factory emergency overload protection option has not
been included.)

In the emergency bypass mode, there is no


overload protection unless a separate
WARNING (optional or customer supplied) thermal or solid
state overload relay is installed, or JP-1 (Motor
Protection Jumper) is removed from the TCB Board.

The line start panel is operable as a normal across-the-line starter. When


power is applied, the bypass contactor is energized, tying the input terminals
directly to its output terminals. When the “ON/OFF” contact is closed, the
main contactor is energized and the motor line starts. When the “ON/OFF”
contact is opened, the motor is disconnected from the line via the main in-line
vacuum contactor.

JKSSS+ Series - 32

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Chapter 4 - User Interface & Menu Navigation


This chapter explains the keypad operator interface, the LCD descriptions and the
programming features

4.1 Keypad/Operator Interface


The user keypad/ keypad operator interface consists of:
• 2 row by 20 characters Liquid Crystal Display (LCD)
• 12 LEDs
• 8 pushbuttons

Note: The soft start is menu driven and there are three levels of programming. The
programming for two of these levels is password protected. Level two requires a
three digit password and level three requires a four digit password.

Toggle between the menu selection for metering and


MENU
setpoint pages.

RESET Will clear the trip indicator and release the trip relay.

In the edit mode, press the ENTER pushbutton so the Keypad Operator Interface
unit will accept the new programming information.
ENTER When not in the edit mode, the ENTER pushbutton
will toggle through the event indicator list (such as
alarms or trips)

Provides general help information about a specific


HELP
setpoint or action.
Will scroll up through the setpoint and metering menu
page. It will scroll to the top of the setpoint page or a
Button UP ARROW section. In edit mode it will increase a setpoint in an
incremental step or toggle through the available
options in the setpoint.

In the main menu the RIGHT ARROW button provides


access to the setpoint page. For setpoint pages with
RIGHT ARROW multiple columns, the RIGHT ARROW will scroll the
setpoint page to the right. When in edit mode it will
shift one character to the right.

Will scroll down through the setpoint pages and down


through the setpoints. In edit mode, it will decrement
DOWN ARROW
through values and toggle available options in the
setpoint.
Will move to the left through setpoint pages with
multiple columns. When in edit mode it will become
LEFT ARROW
the backspace key and will shift one character to the
left.
Power Indicates control power is present
Run Indicates unit/motor is running
Lights in conjunction with AUX 2 to indicate event or
Alarm
LED warn of possible critical condition.
Lights in conjunction with AUX 1 to indicate a critical
Trip
condition has occurred.
AUX 1-8 Auxilary relays
Note: The directional arrow buttons are sensitive. In edit mode, if the buttons
are held for a long period, the scrolling speed will increase.

JKSSS+ Series - 33

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

4.2 Menu Navigation


Notes:
1. The MENU keys allow you to toggle the screens between the Setpoint Menu and
MENU the Metering Menu. Simply use the arrow keys to get to the different screens
(1) within each menu.
Example: To access Setpoint Page 3: PHASE & GROUND SETTINGS, press the
MENU key once and the DOWN ARROW two times.
PAGE 1 BASIC 2. Levels 1, 2 and 3 indicate password protection levels for these setpoint pages.
CONFIGURATION

LEVEL 1
PAGE 2 STARTER
CONFIGURATION

PAGE 3 PHASE &


GROUND SETTINGS

PAGE 4 RELAY
ASSIGNMENT

LEVEL 2

PAGE 5 RELAY
CONFIGURATION

PAGE 6 USER I/O


CONFIGURATION

PAGE 7 CUSTOM
ACCELERATION CURVE

PAGE 8 OVERLOAD
CURVE CONFIGURATION

PAGE 9 RTD
CONFIGURATION

LEVEL 3
PAGE 10 SECURITY
SET PASSWORD

PAGE 11
COMMUNICATIONS

PAGE 12 SYSTEM
SETPOINTS

FACTORY PAGE 13 CALIBRATION


LEVEL & SERVICE

JKSSS+ Series - 34

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

4.2.1 Password Access


Screens in Level 1 of the setpoint menu can be changed without password
access because they list basic motor information. Screens in Levels 2 and
3 require passwords because they provide more in-depth protection and
control of the unit. The password in Levels 2 and 3 can be changed by the
user.

NOTE: Setpoints can only be changed when the motor is in Stop/


Ready Mode! The soft starter will not allow a start if it is still
in the Edit Mode. When the unit is in the Edit Mode, an
asterisk is in the top right corner of the display.

4.2.2 Changing Setpoints


Example 1: Changing Motor FLA
A. Press MENU button to display Setpoint Page 1, Basic Configuration
B. Press the RIGHT ARROW you will view the screen Motor Full Load
Amps.
C. Press the ENTER button for edit mode. Note the asterisk (*) in the top
right corner of the LCD screen that indicates Edit Mode.
D. To change the value, select the UP ARROW or DOWN ARROW.
E. To accept the new value, press the ENTER button. The unit will accept
the changes and will leave the edit mode. Note the * is no longer in the
top right corner of the LCD Display.

MENU

PAGE 1 BASIC MOTOR FULL LOAD AMPS


CONFIGURATION : 140 AMPS

ENTER

MOTOR FULL LOAD AMP*


2x : 142 AMPS

ENTER

MOTOR FULL LOAD AMP


: 142 AMPS

JKSSS+ Series - 35

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Chapter 5 - Setpoint Programming
The JKSSS+ Series has thirteen programmable setpoint pages which define the
motor data, ramp curves, protection, I/O configuration and communications. In Section
5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages
are illustrated and defined for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not start
when it is in programming mode.

5.1 Setpoints Page List


These charts list the Setpoint Page, the programmable functions and the section.

5.1.1 Basic Configuration (Setpoint Page1)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
50 - 100% of Unit Max Current Rating
Motor Full Load Amps (FLA) Model dependent SP1.1
No Passowrd Required

(Model and Service Factor dependent)


Basic Configuration

Service Factor 1.15 1.00 – 1.3 SP1.2


Level 1
Page 1

Overload Class 10 O/L Class 5-30 SP1.3


NEMA Design B A-F SP1.4
Insulation Class B A, B, C, E, F, H, K, N, S SP1.5
Line Voltage Model dependent 1000 to 7200V SP1.6
Line Frequency 60 50 or 60 HZ SP1.7

5.1.2 Starter Configuration (Setpoint Page 2)


Setpoint Security Factory Setting
Description Range Section
Page Level Default

Jog, Start Ramp 1, Start Ramp 2, Custom


SP2.1
Start Control Mode Start Ramp 1 Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp
Jog Voltage 50% 5-75%, Off SP2.2
Start Ramp #1 Type Voltage Current, Voltage
Initial Voltage #1 20% 0-100%
Ramp Time #1 10 sec 0-120 sec
Current Limit #1 350% FLA 200-500 % SP2.3
Initial Current #1 200% FLA 0-300%
Ramp Time #1 10 sec 0-120 sec
Maximum Current #1 350% FLA 200-500 %
Start Ramp #2 Type Disabled Current, Voltage, Disabled
No Passowrd Required
Starter Configuration

Initial Voltage #2 60% 0-100 %


Ramp Time #2 10 sec 0-120 sec
Level 1
Page 2

Current Limit #2 350 % FLA 200-500 % SP2.4


Initial Current #2 200% FLA 0-600 %
Ramp Time #2 10 sec 0-120 sec
Maximum Current #2 350% FLA 200-500 %
Kick Start Type Disabled Voltage or Disabled
Kick Start Voltage 65% 10-100 % SP2.5
Kick Start Time 0.50 sec 0.10-2.00
Deceleration Disabled Enabled or Disabled
Start Deceleration Voltage 60% 0-100 %
SP2.6
Stop Deceleration Voltage 30% 0-59 %
Deceleration Time 5 sec 1-60 sec
Timed Output Time Off 1-1000 sec, Off SP2.7
Run Delay Time 1 Sec 1-30 sec, Off SP2.8
At Speed Delay Time 1 Sec 1-30 sec, Off SP2.9

JKSSS+ Series - 36

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.3 Phase and Ground Settings (Setpoint Page 3)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Imbalance Alarm Level 15% FLA 5-30 %, Off
SP3.1
Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec
Imbalance Trip Level 20% 5-30 %, Off
SP3.2
Imbalance Trip Delay 2.0 sec 1.0-20.0 sec
Undercurrent Alarm Level Off 10-90 %, Off
SP3.3
Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec
Overcurrent Alarm Level Off 100-300 %, Off
SP3.4
Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec
Overcurrent Trip Level Off 100-300 %, Off
SP3.5
Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec
Phase Loss Trip Enabled Enabled or Disabled
SP3.6
Phase Loss Trip Delay 0.1 sec 0-20.0 sec
Phase Rotation Detection ABC ABC, ACB or Disabled
SP3.7
Phase Rotation Trip Delay 1.0 sec 1.0 - 20.0 sec
*Ground Fault Alarm Level Off 5-90 %, Off
SP3.8
*Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec
*Ground Fault Loset Trip Level Off 5-90 %, Off
SP3.9
*Ground Fault Loset Trip Delay 0.5 sec 0.1-20 sec
Phase and Ground Settings

*Ground Fault Hiset Trip Level Off 5-90 %, Off


SP3.10
Password Protection

*Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec


Overvoltage Alarm Level Off 5 -30%, Off
Level 2
Page 3

SP3.11
Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Overvoltage Trip Level 10% 5-30%, Off
SP3.12
Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec
Undervoltage Alarm Level Off 5-30%, Off
SP3.13
Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Undervoltage Trip Level 15% 5-30%, Off
SP3.14
Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec
Line Frequency Trip Window Disabled 0-6 Hz, Disabled
SP3.15
Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec
P/F Lead P/F Alarm Off 0.1-1.00, Off
SP3.16
P/F Lead Alarm Delay 1.0 sec 1-120 sec
P/F Lead P/F Trip Off .01-1.00, Off
SP3.17
P/F Lead Trip Delay 1.0 sec 1-120 sec
P/F Lag P/F Alarm Off .01-1.00, Off
SP3.18
P/F Lag Alarm Delay 1.0 sec 1-120 sec
P/F Lag P/F Trip Off .01-1.00, Off
SP3.19
P/F Lag Trip Delay 1.0 sec 1-120 sec
Power Demand Period 10 min 1 - 60 min
KW Demand Alarm Pickup Off KW Off, 1-100000
KVA Demand Alarm Pickup Off KVA Off, 1-100000 SP3.20
KVAR Demand Alarm Pickup Off KVAR Off, 1-100000
Amps Demand Alarm Pickup Off Amps Off, 1-100000

* Ground fault option must be installed.

JKSSS+ Series - 37

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.4 Relay Assignments (Setpoint Page 4)


Setpoint Security Factory Setting
Description Range Section
Page Level 1st 2nd 3rd
O/L Trip Trip Only None None
I/B Trip Trip None None
S/C Trip Trip Only None None
Overcurrent Trip Trip None None
Stator RTD Trip None None None
Non Stator RTD Trip None None None
*G/F Hi Set Trip Trip None None
*G/F Lo Set Trip Trip None None
Phase Loss Trip Trip None None
Accel. Time Trip Trip Only None None
Start Curve Trip Trip Only None None
Over Frequency Trip None None None
Under Frequency Trip Trip None None
I*I*T Start Curve Trip None None
Learned Start Curve Trip None None
Phase Reversal Trip None None
Overvoltage Trip Trip None None
Undervoltage Trip Trip None None None
Power Factor Trip None None None Trip(AUX1)
Tach Accel Trip None None None Alarm(AUX2)
Inhibits Trip Trip None None AUX3
Shunt Trip None None None AUX4
AUX5-8
Bypass Discrepancy None None None
Password Protection
Relay Assignments

Only Available in 8 Relay


TCB Fault Trip None None System
External Input #2 None None None
Level 2
Page 4

Notes:
Dual Ramp None None None AUX1 to AUX4 are for Factory SP4.1
Thermostat Trip None None Use only. Do not change!
O/L Warning Alarm None None Only AUX 5 - 8 are used in the
Overcurrent Alarm Alarm None None 2nd & 3rd relay assignments.
SCR Fail Shunt Alarm None None None
*Ground Fault Alarm Alarm None None
Under Current Alarm None None None
Motor Running AUX3 None None
I/B Alarm Alarm None None
Stator RTD Alarm None None None
Non-Stator RTD Alarm None None None
RTD Failure Alarm None None None
Self Test Fail Trip None None
Thermal Register Alarm None None
U/V Alarm Alarm None None
O/V Alarm Alarm None None
Power Factor Alarm None None None
KW Demand Alarm None None None
KVA Demand Alarm None None None
KVAR Demand Alarm None None None
Amps Demand Alarm None None None
Timed Output None None None
Run Delay Time None None None
At Speed AUX4 None None

JKSSS+ Series - 38

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.5 Relay Configuration (Setpoint Page 5)

JKSSS+ Series - 39

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.6 User I/O Configuration (Setpoint Page 6)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Tachometer Scale Selection Disabled Enabled or Disabled
Manual Tach Scale 4.0 mA: 0 RPM 0 - 3600 SP6.1
Manual Tach Scale 20.0 mA: 2000 RPM 0 - 3600
Tach Accel Trip Mode Select Disabled Underspeed, Overspeed or Disabled
Tach Ramp Time 20 sec 1 - 120
Tach Underspeed Trip PT 1650 RPM 0-3600 SP6.2
Tach Overspeed Trip PT 1850 RPM 0 - 3600
Tach Accel Trip Delay 1 sec 1 - 60
Off, RPM 0-3600, Hottest Non-Stator RTD
0-200°C, Hottest Stator RTD
Analog Output #1 RMS Current
0 - 200°C, RMS Current 0 - 7500 A, %
Motor Load 0 - 600% Kw SP6.3

Analog Output #1 4mA: 0 0-65535


Analog Output #1 20mA: 250 0-65535
Analog Output #2 % Motor Load Same As Analog Input #1
User I/O Configuration

Passowrd Protection

Analog Output #2 4mA: 0 0-65535 SP6.4


Analog Output #2 20mA: 1000 0-65535
Lavel 2
Page 6

User Programmable External


Inputs
TCB Fault Enabled Enabled or Disabled
Name Ext. Input #1 TCB Fault User Defined, up to 15 Characters
TCB Fault Type NO Normally Open or Closed
TCB Fault Time Delay 1 sec 0-60 sec
External Input #2 Disabled Enabled or Disabled
Name Ext. Input #2 User Defined, up to 15 Characters
External Input #2 Type NO Normally Open or Closed
SP6.5
External Input #2 Time Delay 0 sec 0-60 sec
Dual Ramp Dual Ramp Enabled or Disabled or Dual Ramp
Name Ext. Input #3 Dual Ramp User Defined, up to 15 Characters
Dual Ramp Type NO Normally Open or Closed
Dual Ramp Time Delay 0 sec 0-60 sec
Thermostat Enabled Enabled or Disabled
Name Ext. Input #4 Thermostat User Defined, up to 15 Characters
Thermostat Type NC Normally Open or Closed
Thermostat Time Delay 1 sec 0-60 sec

JKSSS+ Series - 40

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.7 Custom Acceleration Curve (Setpoint Page 7)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Custom Accel Curve Disabled Disabled, Curve A, B, or C
Custom Curve A
Curve A Voltage Level 1 25% 0-100%
Curve A Ramp Time 1 2 sec 1-60 sec
Curve A Voltage Level 2 30% 0-100%
Curve A Ramp Time 2 2 sec 1-60 sec
Curve A Voltage Level 3 37% 0-100%
Curve A Ramp Time 3 2 sec 1-60 sec
Custom Acceleration Curve

Curve A Voltage Level 4 45% 0-100%


Password Protection

Curve A Ramp Time 4 2 sec 1-60 sec


Curve A Voltage Level 5 55% 0-100%
Level 3
Page 7

Curve A Ramp Time 5 2 sec 1-60 sec SP7.1


Curve A Voltage Level 6 67% 0-100%
Curve A Ramp Time 6 2 sec 1-60 sec
Curve A Voltage Level 7 82% 0-100%
Curve A Ramp Time 7 2 sec 1-60 sec
Curve A Voltage Level 8 100% 0-100%
Curve A Ramp Time 8 2 sec 1-60 sec
Curve A Current Limit 350% FLA 200-500%
Same Programmable Data Points and Ranges
Custom Curve B
as Custom Curve A

Same Programmable Data Points and Ranges


Custom Curve C
as Custom Curve A

5.1.8 Overload Curve Configuration (Setpoint Page 8)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Basic Run Overload Curve
Run Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
SP8.1
Run Locked Rotor Current 600% FLA 400-800%
Coast Down Timer Disabled 1-60 Min, Disabled
Overload Curve Configuration

Basic Start Overload Curve


Password Protection

Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
Start Locked Rotor Current 600% FLA 400-800%
Level 3
Page 8

SP8.2
Acceleration Time Limit 30 sec 1-300 sec, Disabled
Number of Starts Per Hour Disabled 1-6, Disabled
Time Between Starts Time 5 min 1-60 Min, Disabled
Area Under Curve Protection Disabled Enabled or Disabled
SP8.3
Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec
Current Over Curve Disabled Disabled, Learn, Enabled
Learned Start Curve Bias 10% 5-40% SP8.4
Time for Sampling 30 sec 1-300 sec

JKSSS+ Series - 41

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.9 RTD Configuration (Setpoint Page 9)


Setpoint Security Factory Setting
Description Range Section
Page Level Default

Use NEMA Temp for RTD Values Disabled Enabled or Disabled SP9.1

# of RTD Used for Stator 4 0-6 SP9.2


RTD Voting Disabled Enabled or Disabled SP9.3
120 OHM NI, 100 OHM NI, 100 OHM PT, 10
Stator Phase A1 Type Off
OHM CU
RTD #1 Description Stator A1 User defined, Up to 15 Characters
Stator Phase A1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase A1 Trip Level Off 0-240C (32-464F), Off
Stator Phase A2 Type Off Same as Stator Phase A1
RTD #2 Description Stator A2 User defined, Up to 15 Characters
Stator Phase A2 Alarm Off 0-240C (32-464F), Off
Stator Phase A2 Trip Level Off 0-240C (32-464F), Off
Stator Phase B1 Type Off Same as Stator Phase A1
RTD #3 Description Stator B1 User defined, Up to 15 Characters
Stator Phase B1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase B1 Trip Level Off 0-240C (32-464F), Off
Stator Phase B2 Type Off Same as Stator Phase A1
Password Protection
RTD Configuration

RTD #4 Description Stator B2 User defined, Up to 15 Characters


Stator Phase B2 Alarm Level Off 0-240C (32-464F), Off
Level 3
Page 9

Stator Phase B2 Trip Level Off 0-240C (32-464F), Off


Stator Phase C1 Type Off Same as Stator Phase A1
RTD #5 Description Stator C1 User defined, Up to 15 Characters SP9.4
Stator Phase C1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase C1 Trip Level Off 0-240C (32-464F), Off
Stator Phase C2 Type Off Same as Stator Phase A1
RTD #6 Description Stator C2 User defined, Up to 15 Characters
Stator Phase C2 Alarm Level Off 0-240C (32-464F), Off
Stator Phase C2 Trip Level Off 0-240C (32-464F), Off
End Bearing Type Off Same as Stator A1
RTD #7 Description End Bearing User defined, Up to 15 Characters
End Bearing Alarm Level Off 0-240C (32-464F), Off
End Bearing Trip Level Off 0-240C (32-464F), Off
Shaft Bearing Type Off Same as Stator Phase A1
RTD #8 Description Shaft Bearing User defined, Up to 15 Characters
Shaft Bearing Alarm Level Off 0-240C (32-464F), Off
Shaft Bearing Trip Level Off 0-240C (32-464F), Off
RTD #9 Type Off Same as Stator Phase A1
RTD #9 Description User defined User defined, Up to 15 Characters
RTD #9 Alarm Level Off 0-240C (32-464F), Off
RTD #9 Trip Level Off 0-240C (32-464F), Off

JKSSS+ Series - 42

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.9 RTD Configuration Page 9 Cont’d


Setpoint Security Factory Setting
Description Range Section
Page Level Default
RTD #10 Type Off Same as Stator Phase A1
RTD #10 Description User defined User defined, Up to 15 Characters
RTD #10 Alarm Level Off 0-240C (32-464F), Off
RTD #10 Trip Level Off 0-240C (32-464F), Off
Password Protection
RTD Configuration

RTD #11 Type Off Same as Stator Phase A1


Level 3
Page 9

RTD #11 Description User defined User defined, Up to 15 Characters


SP9.4
RTD #11 Alarm Level Off 0-240C (32-464F), Off
RTD #11 Trip Level Off 0-240C (32-464F), Off
RTD #12 Type Off Same as Stator Phase A1
RTD #12 Description User defined User defined, Up to 15 Characters
RTD #12 Alarm Level Off 0-240C (32-464F), Off
RTD #12 Trip Level Off 0-240C (32-464F), Off

5.1.10 Security Set Password Page 10


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Level
Page

Set Level 2 Password 100 000 – 999 Three Digits SP10.1


10

Set Level 3 Password 1000 0000 – 9999 Four Digits SP10.2

5.1.11 Communications Page 11


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Set Front Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.1
Password Protection
Communiications

Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.2
Page 11

Level 3

Modbus Address Number 247 1 – 247 SP11.3


Set Access Code 1 1 – 999 SP11.4
Set Link Baud Rate 38.4 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.5
Remote Start/Stop Disabled Enabled or Disabled SP11.6

JKSSS+ Series - 43

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.1.12 System (Setpoint Page 12)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Default Display Screen
Metering Data Page # 1 Enter Metering Page (1-4)
Enter Metering Screen
Page 1(1-10) SP12.1
Metering Data Screen # 1 Page 2 (1-11)
Page 3 (1 - 29)
Page 4 (1 - 6)
Alarms
RTD Failure Alarm Disabled Enabled or Disabled
SP12.2
Thermal Register Alarm 90% Off, 40-95%
Thermal Alarm Delay 10 sec 1-20 sec
Password Protection

Thermal Register Setup Info


System Setpoints

Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay
Page 12

Level 3

Hot Stall Time ½ O/L Class ½ O/L Class, 4-40 sec


Stopped Cool Down Time 30 Min 10-300 Min
Runing Cool Down Time 15 Min 10-300 Min
Relay Measured Cool Rates Disabled Enabled or Disabled
Thermal Register Minimum 15% 10-50% SP12.3
Motor Design Ambient Temp 40C 10-90C

Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp

Motor Stator Max Temp INS CLS INS CLS, 10-240 C


I/B Input to Thermal Register Enabled Enabled or Disabled
Use Calculated K or Assign 7 1-50, On

Press Enter to Clr Thermal Register SP12.4

5.1.13 Calibration and Service (Setpoint Page 13)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Set Date and Time FACTORY SET;
(DDMMYY:HHMM) ##/##/## ##:##
FACTORY USE ONLY
Calibration & Service

FACTORY SET;
Enter Date (DDMMYYYY) D=1-31, M=1-12, Y=1970-2069 SP13.1
##/##/####
Page 13

FACTORY SET;
Enter Time (HH:MM) H=00-23, M=0-59
##:##
Model # FACTORY SET;
Display Only, Cannot be changed SP13.2
Firmware REV. # ###### ######
Press Enter to Access Factory
Available to Qualified Factory Personnel SP13.3
Settings

JKSSS+ Series - 44

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

5.2 Setpoint Menu


Note:
MENU 1. Push MENU key to toggle the screens between Setpoint Menu and Metering
Menu.
(1) 2. Follow the arrow keys to get to different screens.
Example: For Page 3 PHASE & GROUND SETTINGS, press the MENU key and
PAGE 1 BASIC the DOWN ARROW two times.
CONFIGURATION

LEVEL 1
PAGE 2 STARTER
CONFIGURATION

PAGE 3 PHASE &


GROUND SETTINGS

PAGE 4 RELAY
ASSIGNMENT

LEVEL 2

PAGE 5 RELAY
CONFIGURATION

PAGE 6 USER I/O


CONFIGURATION

PAGE 7 CUSTOM
ACCELERATION CURVE

PAGE 8 OVERLOAD
CURVE CONFIGURATION

PAGE 9 RTD
CONFIGURATION

LEVEL 3
PAGE 10 SECURITY
SET PASSWORD

PAGE 11
COMMUNICATIONS

PAGE 12 SYSTEM
SETPOINTS

FACTORY PAGE 13 CALIBRATION


LEVEL & SERVICE

JKSSS+ Series - 45

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.1 Basic Configuration (Setpoint Page 1)


In Setpoint Page 1, the starter is looking for the following basic MENU
nameplate data of the motor.
PAGE 1 BASIC MOTOR FULL LOAD AMPS
SP1.1 Motor Full Load Amps: Allows the user to enter the motor’s CONFIGURATION : 200 AMPS
FLA rating. Range of adjustment is 50 - 100% (less Range: 50 - 100% of Unit
programmed service factor). MAX CURRENT AMPS
Increments of 1

SP1.2 Service Factor: Sets the pickup point on the overload curve SERVICE FACTOR
: 1.15 X FLA
as defined by the programmed motor full load current. Ex: Range: 1.00 - 1.3
If the motor FLA is 100 and the service factor is 1.15, the Increments of 0.01
overload pickup point will be 115 Amps.
OVERLOAD
SP1.3 Overload Class: Choose the motor protection overload class, CLASS: 10
Range: 5 - 30
range from 5-30. Increments of 5
Ex: Overload Class 10 will trip in 10 seconds at six times
FLA. NEMA
DESIGN: B
Range: A - F

INSULATION
CLASS: B
Range: A - S

LINE VOLTAGE
INPUT: 4160 VOLTS
Range: 100 - 7200

LINE FREQUENCY
HZ: 60
Range: 50 or 60

SP1.4 NEMA design: The motor design maximum allowed slip


(Select from Class A through F).

SP1.5 Insulation Class: The motor insulation temperature class


(Select A, B, C, E, F, H, K, N or S).

SP1.6 Line Voltage Input: Applied Voltage

SP1.7 Line Frequency: The user may choose either 50 Hz or 60


Hz.

JKSSS+ Series - 46

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.2 Starter Configuration (Setpoint Page 2)

MENU
(Hit DOWN ARROW one time)

PAGE 2 STARTER START CONTROL MODE


CONFIGURATION : START RAMP 1
JOG, START RAMP 1,
START RAMP 2, DUAL
RAMP, CUSTOM ACCEL
CURVE,START DISABLED
If If
VOLTAGE CURRENT
JOG VOLTAGE selected selected
: 50% these these
screens screens
Range: 5 - 75% or Off will appear. will appear.
Increments 5

START RAMP #1 TYPE INITIAL VOLTAGE INITIAL CURRENT


: VOLTAGE #1: 20% #1: 200% FLA
Options:Voltage, Current Range: 0 - 100% Range: 0 - 300%
or Off Increments of 1 Increments of 1

RAMP TIME RAMP TIME


#1: 10 SEC. #1: 10 SEC.
Range: 0 - 120 SEC. Range: 0 - 120 SEC
Increments of 1 Increments of 1

CURRENT LIMIT MAXIMUM CURRENT


#1: 350% FLA #1: 350% FLA
Range: 200 - 500% Range: 200-500%
Increments of 10 Increments of 10

If If
START RAMP #2 TYPE VOLTAGE CURRENT
: DISABLED selected INITIAL VOLTAGE selected INITIAL CURRENT
these these
#2: 60% #2: 200% FLA
Options: Voltage, Current screens screens
or Off will appear. Range: 0 - 100% will appear. Range: 0 - 300%
Increments of 1 Increments of 1

RAMP TIME RAMP TIME


#2: 10 SEC. #2: 10 SEC.
Range: 0 - 120 SEC. Range: 0 - 120 SEC
Increments of 1 Increments of 1

CURRENT LIMIT MAXIMUM CURRENT


#2: 350% FLA #2: 350% FLA
Range: 200 - 500% Range: 200-500%
Increments of 10 Increments of 10

KICK START KICK START VOLTAGE


TYPE: DISABLED : 65%
Range: Voltage or Disabled Range: 10 - 100%
Increments of 5

DECELERATION KICK START TIME


: DISABLED : 0.50 SEC.
Range: Enabled or Disabled Range: 0.10 - 2.00
Increments of 0.10

START DECELERATION
TIMED OUTPUT VOLTAGE: 60%
TIME: OFF
Range: 0 - 100%
Range: 1 - 1000 sec, OFF Increments of 1
Increments of 1

RUN DELAY STOP DECELERATION


TIME: 1 SEC. VOLTAGE: 30%
Range: 0 - 30 sec, OFF Range: 0 - 59%
Increments of 1 Increments of 1

AT SPEED DELAY DECELERATION


TIME: 1 SEC. TIME: 5 SEC.
Range: 0 - 30 sec, OFF Range: 1 - 60
Increments of 1 Increments of 1
JKSSS+ Series - 47

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.2 Starter Configuration (Setpoint Page 2)


Provides multiple choices for starting ramps that can be • Voltage Ramping with Current Limit is the most
selected for particular loads and applications. used curve and is similar to voltage ramping.
However, it adds an adjustable maximum current
SP2.1 Start Control Mode: Start Ramp 1, Jog, Start output. Voltage is increased gradually until the
Disabled, Tach Ramp, Custom Accel Curve, Dual setting of the Maximum Current Limit setpoint
Ramp, Start Ramp 2. is reached. The voltage is held at this level until
the motor accelerates to full speed. This may be
• Dual Ramp: The dual ramp mode works in necessary in applications where the electrical
conjunction with External Input #3. This allows power is limited. Typical applications include
the user to switch between the two start ramps portable or emergency generator supplies, utility
without having to reconfigure the start mode. (For power near the end of a transmission line and
details on configuring External Input #3 for DUAL utility starting power demand restrictions. Note:
RAMP see Setpoint Page 6.) Using Current Limit will override the Ramp Time
setting if necessary, so use this feature when
• Custom Accel Curve: Allows the user to acceleration time is not critical. To achieve Voltage
custom design the acceleration start curve to the Ramping with Current Limit, select VOLTAGE for
application. (See setpoint page 7 for configuration the START RAMP #1 setpoint and set CURRENT
setup.) Note: If Custom Accel Curve has not LIMIT #1 setpoint to a desired lower setting, as
been enabled in setpoint page 7, the soft starter determined by your application requirements.
will ignore the start control mode and read this
setpoint as disabled. Start Ramp 1 Type: Current
Current Ramping (Closed Loop Torque Ramping)
• Tach Ramp: See setpoint page 6 for configuration is used for smooth linear acceleration of output
setup of tachometer input. torque. This ramp is only used on some conveyor
systems (long haul or down hill). Output voltage
SP2.2 Jog Voltage: The voltage level necessary to cause is constantly updated to provide the linear
the motor to slowly rotate. current ramp, and therefore the available torque
is maximized at any given speed. This is for
SP2.3 Start Ramp 1 Type: The ramp type can be setup for applications where rapid changes in torque may
either Voltage or Current. If Voltage is selected, result in load damage or equipment changes.
initial voltage, ramp time and current limit are Typical applications include overland conveyors
adjustable. If Current is selected, initial current, if belt stretching occurs; fans and mixers if blade
ramp time and maximum current are adjustable. warping is a problem; and material handling
Start Ramp 1 Type: Voltage systems if stacked products fall over or break.
• Voltage Ramping is the most reliable starting This feature can be used with or without the
method, because the starter will eventually Maximum Current Limit setting. To achieve
reach an output Current Ramping select CURRENT for START
voltage high enough to RAMP #1 TYPE setpoint and the MAXIMUM
draw full current and CURRENT #1 setpoint to the desired level.
develop full torque.
This method is useful Current Limit Only: (Current Step) start uses the
for applications where Current Limit feature exclusively. This method of
the load conditions starting eliminates the soft start voltage/current
change frequently and ramp and instead, maximizes the effective
where different levels application of motor torque within the limits of the
of torque are required. motor. In this mode, setpoint RAMP TIME #1 is
Typical applications set to zero (0), so the output current jumps to the
include material handling current limit setting immediately. Typically used
conveyors, positive in with a limited power supply, when starting a
displacement pumps and drum mixers. difficult load such as a centrifuge or deep well
Voltage is increased from a starting point (Initial pump, when the motor capacity is barely adequate
Torque) to full voltage over an adjustable period of (stall condition or overloading occurs) or if other
time (Ramp Time). To achieve Voltage Ramping, starting modes fail. Since ramp times are set to
select VOLTAGE for the START RAMP #1 TYPE zero (0). START RAMP #1 TYPE is set to either
setpoint and set CURRENT LIMIT #1 setpoint VOLTAGE or CURRENT.
to 500% (the maximum setting). Since this is
essentially Locked Rotor Current on most motors, • Initial Torque (Initial Voltage #1 or Initial
there is little or no Current Limit effect on the Current #1): Sets the initial start point of either
Ramp profile.
JKSSS+ Series - 48

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

the Voltage Ramp or the Current Ramp. Every SP2.5 Kick Start: Used as an initial energy burst in
load requires some amount of torque to start from applications with high friction loads.
a standstill. It is inefficient to begin ramping the
motor from zero every time, since between zero • Kick Start Voltage: The initial voltage (as a
and the WK2 break-away torque level, no work is percent of full voltage value) that is needed to
being performed. The initial torque level should be start the motor (i.e. Breakaway or Initial Torque).
set to provide enough torque to start rotating the
motor shaft, enabling a soft start and preventing • Kick Start Time: The time the initial torque boost
torque shock damage. Setting this start point too is applied.
high will not damage the starter, but may reduce
or eliminate the soft start effect. SP2.6 Deceleration: Allows the motor to gradually come to
a soft stop.
• Ramp Time #1: Sets the maximum allowable time
for ramping the initial voltage or current (torque) • Start Deceleration Voltage: The first part of
setting to either of the following: the deceleration ramp. The soft starter initially
1) the Current Limit setting when the motor is still drops to this voltage level upon receiving a STOP
accelerating, or command. (Represented as a percent of voltage
2) full output voltage if the Current Limit is set to value.)
maximum.
Increasing the ramp time softens the start process • Stop Deceleration Voltage: The drop-off point of
by gradually increasing the voltage or current. the deceleration ramp. (Percent of voltage value.)
Ideally, the ramp time should be set for the longest
amount of time the application will allow (without • Deceleration Time: Decel ramp time.
stalling the motor). Some applications require
a short ramp time due to the mechanics of the SP2.7 Timed Output: Used with an AUX 5-8 relay. When
system (i.e. centrifugal pumps, because pump enabled, and upon a start command, it waits until
problems can occur due to insufficient torque). the programmed time plus the run delayed time
has expired. The relay energizes and remains so
• Current Limit: Sets the maximum motor current until a stop command is received. It de-energizes
the starter will allow during Ramping. As the motor upon receiving a stop command.
begins to ramp, the Current Limit feature sets a
ceiling at which the current draw is held. Current SP2.8 Run Delay Time: Can be used with an AUX 5-8
Limit remains in effect until the following occurs: relay. The delay timer begins upon receipt of the
1) the motor reaches full speed (detected by the start command. The relay will then drop out when
At-Speed detection circuit) or the time has expired.
2) the Overload Protection trips on Motor Thermal
Overload. SP2.9 At Speed Delay Time: Used with an AUX 4 relay, it
Once the motor reaches full speed, the Current waits until after the motor reaches the end of ramp
Limit feature becomes inactive. and the programmed delay time has expired. The
relay energizes until a stop command has been
In the Voltage Ramp Profile, the voltage output is received.
increased until it reaches the Current Limit. Ramp
time is the maximum amount of time it takes for
the voltage to increase until the Current Limit
setting takes over. With some load conditions, the
Current Limit is reached before the Ramp Time
expires.

The Current Ramp profile varies the output
voltage to provide a linear increase in current up
to the Maximum Current setpoint value. A closed
loop feedback of motor current maintains the
Current Ramp profile.

SP2.4 Start Ramp 2: The same options and screen setups


as Start Ramp 1. Note: CUSTOM ACCEL CURVE
overrides the voltage or current start in Ramps 1
and 2 when selected to be the start control mode.

JKSSS+ Series - 49

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.3 Phase & Ground Settings


(Setpoint Page 3) MENU
(Security Level: 2) (Hit DOWN ARROW two times)

PAGE 3 PHASE & IMBALANCE ALARM IMBALANCE ALARM


GROUND SETTINGS LEVEL: 15% FLA DELAY: 1.5 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1

IMBALANCE TRIP IMBALANCE TRIP


LEVEL: 20%FLA DELAY: 2.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1

UNDERCURRENT ALARM UNDERCURRENT ALARM


Note: Proper phase sequence must be observed when LEVEL: OFF DELAY: 2.0 SEC.
connecting the input power. For example, phase A Range: 10 - 90%, OFF
Increments of 1
Range: 1.0 - 60.0 SEC.
Increments of 0.1
must lead phase B, which in turn must lead phase
C by 120° respectively. If the phase rotation is OVERCURRENT ALARM OVERCURRENT ALARM
LEVEL: OFF DELAY: 2.0 SEC.
not correct, a fault light and the LCD display will Range: 100 - 300%, OFF Range: 1.0 - 20.0 SEC., OFF
indicate the problem. Increments of 1 Increments of 0.1

OVERCURRENT TRIP
SP3.1 Imbalance Alarm Level: This is an advance warning LEVEL: OFF
OVERCURRENT TRIP
DELAY: 2.0 SEC.
of a phase imbalance problem. The problem may Range: 100 - 300%, OFF Range: 1.0 - 20.0 SEC.
not be a fault in the motor, but merely caused by Increments of 1 Increments of 0.1

imbalanced voltages. PHASE LOSS TRIP PHASE LOSS TRIP


: ENABLED DELAY: 0.1 SEC.
• Imbalance Alarm Delay: The amount of time the Options: Enabled or Disabled Range: 0 - 20.0 SEC.
Increments of 0.1
imbalance condition must exist before an alarm
occurs. PHASE ROTATION PHASE ROTATION TRIP
DETECTION: ABC DELAY: 1.0 SEC
SP3.2 Imbalance Trip Level: This will trip the motor on Options: ABC, ACB or Range: 1.0 - 20.0 SEC.
excessive phase imbalance. The trip level should Disabled

be programmed to a higher value than the alarm


level. * GROUND FAULT ALARM
LEVEL: OFF
GROUND FAULT ALARM
DELAY: 0.1 SEC.
Range: 5 - 90%, OFF Range: 0.1 - 20.0 SEC.
• Imbalance Trip Delay: The amount of time the Increments of 1 Increments of 0.1
imbalance condition must exist before a trip will
* GROUND FAULT LOSET GROUND FAULT LOSET
occur. TRIP LEVEL: OFF TRIP DELAY: 0.5 SEC
Range: 5 - 90%, OFF Range: 0.1 - 20.0 SEC.
Increments of 1 Increments of 0.1
SP3.3 Undercurrent Alarm Level: Typically used to warn
of possible load loss, a coupling breaking or other GROUND FAULT HISET GROUND FAULT HISET
mechanical problems. * TRIP LEVEL: OFF TRIP DELAY: 0.008 SEC.
Range: 5 - 90%, OFF Range: 0.008 - 0.250 SEC.
Increments of 1 Increments of 0.002
• Undercurrent Alarm Delay: The amount of time
the undercurrent condition must exist before an OVERVOLTAGE ALARM OVERVOLTAGE ALARM
alarm will occur. LEVEL: OFF DELAY: 1.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1
SP3.4 Overcurrent Alarm Level: Typically used to indicate
OVERVOLTAGE TRIP OVERVOLTAGE TRIP
when the motor is overloaded. This feature can be LEVEL: 10% DELAY: 2.0 SEC.
used to either stop the feed to the equipment or Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1
warn operators of an overload condition.
UNDERVOLTAGE ALARM UNDERVOLTAGE ALARM
LEVEL: OFF
• Overcurrent Alarm Delay: The amount of time the DELAY: 1.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
overcurrent condition must exist before an alarm Increments of 1 Increments of 0.1
will occur. UNDERVOLTAGE TRIP UNDERVOLTAGE TRIP
LEVEL: 15% DELAY: 2.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1

LINE FREQUENCY TRIP LINE FREQUENCY TRIP


WINDOW: DISABLED DELAY: 1.0 SEC.
Range: 0 - 6, Disabled Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1
JKSSS+ Series - 50

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.3 Phase & Ground Settings (Setpoint Page 3)


MENU
(Hit DOWN ARROW two times)

PAGE 3 PHASE & POWER FACTOR LEAD P/F LEAD ALARM


GROUND SETTINGS P/F ALARM: OFF DELAY: 1 SEC.
Range: .01 - 1.00, OFF Range: 1 - 120 SEC
Increments of .01 Increments of 1

POWER FACTOR LEAD P/F LEAD TRIP


SP3.5 Overcurrent Trip Level: Typically used to indicate P/F TRIP: OFF DELAY: 1.0 SEC.
the motor is severely overloaded and at which Range: .01 - 1.00, OFF
Increments of .01
Range: 1 - 120 SEC.
Increments of 1
point a trip occurs.
POWER FACTOR LAG P/F LAG ALARM
P/F ALARM: OFF DELAY: 1.0 SEC.
• Overcurrent Trip Delay: The amount of time the Range: .01 - 1.00, OFF Range: 1 - 120 SEC.
overcurrent condition must exist before a trip will Increments of .01 Increments of 1
occur. POWER FACTOR LAG P/F LAG TRIP
P/F TRIP: OFF DELAY: 1.0 SEC.
SP3.6 Phase Loss Range: .01 - 1.00, OFF Range: 1 - 120 SEC.
Increments of .01 Increments of 1
Trip: When
enabled, the POWER DEMAND
soft starter will PERIOD: 10 MINUTES
Range: 1 - 60 Minutes
trip the motor Increments of 1
off-line upon a
loss of KW DEMAND ALARM
PICKUP: OFF KW
phase power. Range: OFF, 1 - 100000
Increments of 1
• Phase Loss Trip Delay: The amount of time the KVA DEMAND ALARM
phase loss condition must exist before a trip will PICKUP: OFF KVA
occur. Range: OFF, 1 - 100000
Increments of 1

SP3.7 Phase Rotation Detection: The soft starter is


KVAR DEMAND ALARM
continuously monitoring the phase rotation. Upon PICKUP: OFF KVAR
a start command, a trip will occur if it detects a Range: OFF, 1 - 100000
change in the phase rotation. Increments of 1

• Phase Rotation: There are two possible phase AMPS DEMAND ALARM
PICKUP: OFF AMPS
rotation options: ABC or ACB. This setpoint
Range: OFF, 1 - 100000
monitors the wiring to ensure that the phase Increments of 1
rotation is correct. To view the present phase
rotation, go to Metering Page1, screen number 4.
SP3.10 * Ground Fault Hiset Trip Level: Used to trip the
SP3.8 * Ground Fault Alarm: Typically used to warn of low motor (within milliseconds) upon detecting a high
level ground current leakage. level of ground current leakage. This setpoint is
intended to detect low impedance faults.
• * Ground Fault Alarm Delay: The amount of time
that the ground fault condition must exist before an • *Ground Fault Hiset Trip Delay: The amount
alarm will occur. of time that the ground fault condition must exist
before a trip will occur.
SP3.9 * Ground Fault Loset Trip Level: Typically used
to trip the motor on a low level of ground current SP3.11 Overvoltage Alarm Level: Typically used to
leakage. This setpoint is intended to detect high indicate when the line voltage is too high. This is
impedance faults. an alarm level.

• * Ground Fault Loset Trip Delay: The amount • Overvoltage Alarm Delay: The amount of time
of time that the ground fault condition must exist that the overvoltage condition must exist before a
before a trip will occur. trip will occur.

*Ground Fault Option must be installed

JKSSS+ Series - 51

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP3.12 Overvoltage Trip Level: Typically used to indicate SP3.18 Power Factor Lag Alarm: Typically used to
that the line voltage is too high and at which point a indicate a lagging power factor.
trip occurs
• Power Factor Lag Alarm Delay: The amount of
• Overvoltage Trip Delay: The amount of time that time that the power factor lagging condition must
the overvoltage condition must exist before a trip exist beyond the window before a trip will occur.
will occur.
SP3.19 Power Factor Lag Trip: The acceptable amount
SP3.13 Undervoltage Alarm Level: Typically used to of power factor lag before a trip is generated.
indicate when the line voltage is too low. This is an
alarm level. • Power Factor Lag Delay: The amount of time
that the power factor lag condition must exist
• Undervoltage Alarm Delay: The amount of time beyond the window before a trip will occur.
that the overvoltage condition must exist before a
trip will occur. SP3.20 Power Demand Period: The soft starter
measures the demand of the motor for several
SP3.14 Undervoltage Trip Level: Typically used to parameters (current, kW, kvar, kVA). The demand
indicate that the line voltage is too low and at which values of motors assists in energy management
point a trip occurs programs where processes may be altered or
scheduled to reduce overall demand. Demand
• Undervoltage Trip Delay: The amount of time that is calculated by a programmed amount of time
the undervoltage condition must exist before a trip where current, kW, kvar and kva samples are
will occur. taken and then averaged and stored to assess
demand.
SP3.15 Line Frequency Trip Window: The acceptable
amount of drift above or below the line frequency
(Hz) before a trip is generated.

• Line Frequency Trip Delay: The amount of time


that the frequency drift condition must exist beyond
the window before a trip will occur.

SP3.16 Power Factor Lead Alarm: Typically used to


indicate a leading power factor.

• Power Factor Lead Alarm Delay: The amount of


time that the power factor lead condition must exist
beyond the window before a trip will occur.

SP3.17 Power Factor Lead Trip: The acceptable amount


of power factor lead before a trip is generated.

• Power Factor Lead Delay: The amount of time


that the power factor lead condition must exist
beyond the window before a trip will occur.

JKSSS+ Series - 52

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.4 Relay Assignment (Setpoint Page 4)
PHASE REVERSAL I/B ALARM
MENU 1ST: TRIP 1ST: ALARM

(Hit DOWN ARROW three times)

OVERVOLTAGE TRIP STATOR RTD ALARM


PAGE 4 RELAY O/L TRIP 1ST: TRIP 1ST: NONE
ASSIGNMENT 1ST: TRIP ONLY
Range: TRIP (AUX1),
ALARM (AUX2), AUX3,
AUX4 UNDERVOLTAGE TRIP
1ST: TRIP NON-STATOR RTD ALARM
1ST: NONE
I/B TRIP
1ST: TRIP
POWER FACTOR TRIP
1ST: NONE RTD FAILURE ALARM
1ST: NONE
S/C TRIP
1ST: TRIP ONLY
TACH ACCEL TRIP
1ST: NONE SELF-TEST FAIL
1ST: TRIP
OVERCURRENT TRIP
1ST: TRIP
INHIBITS TRIP
1ST: TRIP
THERMAL REGISTER
STATOR RTD TRIP 1ST: ALARM
1ST: NONE
SHUNT TRIP
1ST: NONE
U/V ALARM
NON-STATOR RTD TRIP 1ST: ALARM
1ST: NONE
BYPASS DISCREPANCY
1ST: NONE

O/V ALARM
G/F HI SET TRIP 1ST: ALARM
1ST: TRIP TCB FAULT
1ST: TRIP

EXTERNAL INPUT #2 POWER FACTOR ALARM


G/F LO SET TRIP 1ST: NONE
1ST: NONE
1ST: TRIP

DUAL RAMP
1ST: NONE KW DEMAND ALARM
PHASE LOSS TRIP 1ST: NONE
1ST: TRIP

THERMOSTAT
1ST: TRIP
KVA DEMAND ALARM
ACCEL. TIME TRIP 1ST: NONE
1ST: TRIP ONLY
O/L WARNING
1ST: ALARM

KVAR DEMAND ALARM


START CURVE TRIP
1ST: NONE
1ST: TRIP ONLY
OVERCURRENT ALARM
1ST: ALARM

AMPS DEMAND ALARM


OVER FREQUENCY TRIP 1ST: NONE
1ST: NONE SCR FAIL SHUNT ALARM
1ST: NONE

TIMED OUTPUT
UNDER FREQUENCY TRIP GROUND FAULT ALARM 1ST: NONE
1ST: TRIP 1ST: ALARM

UNDERCURRENT ALARM RUN DELAY TIME


I*I*T START CURVE 1ST: NONE 1ST: NONE
1ST: TRIP

LEARNED START CURVE MOTOR RUNNING AT SPEED


1ST: TRIP 1ST: AUX3 1ST: AUX4

JKSSS+ Series - 53

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.4 Relay Assignment (Setpoint Page 4)


(Security Level: 2)

The protection functions are user programmable to an output relay. Factory setting for the trip functions assigned to TRIP
(AUX1) relay and alarm functions to ALARM (AUX2) relay. AUX1 - 4 are Factory Set and should not be changed.

SP4.1 The following is a list of the user programmable functions.


FUNCTIONS RELAY ASSIGNMENTS
1st 2nd 3rd
OVERLOAD TRIP TRIP ONLY NONE NONE
IMBALANCE TRIP TRIP (AUX1) NONE NONE
SHORT CIRCUIT TRIP TRIP ONLY NONE NONE
OVERCURRENT TRIP TRIP (AUX1) NONE NONE
STATOR RTD TRIP NONE NONE NONE
NON-STATOR RTD TRIP NONE NONE NONE
GROUND FAULT HI SET TRIP* TRIP (AUX1) NONE NONE
GROUND FAULT LO SET TRIP* TRIP (AUX1) NONE NONE
PHASE LOSS TRIP TRIP (AUX1) NONE NONE
ACCEL TIME TRIP TRIP ONLY NONE NONE
START CURVE TRIP TRIP ONLY NONE NONE
OVER FREQUENCY TRIP NONE NONE NONE
UNDER FREQUENCY TRIP TRIP (AUX1) NONE NONE
I*I*T START CURVE TRIP (AUX1) NONE NONE
LEARNED START CURVE TRIP (AUX1) NONE NONE
PHASE REVERSAL TRIP (AUX1) NONE NONE
OVERVOLTAGE TRIP TRIP (AUX1) NONE NONE
UNDERVOLTAGE TRIP TRIP (AUX1) NONE NONE
POWER FACTOR TRIP NONE NONE NONE
TACH ACCEL TRIP NONE NONE NONE
INHIBITS TRIP TRIP (AUX1) NONE NONE
SHNT TRIP NONE NONE NONE
BYPASS DISCREPANCY NONE NONE NONE
TCB FAULT TRIP (AUX1) NONE NONE
EXTERNAL INPUT 2 NONE NONE NONE
DUAL RAMP NONE NONE NONE
THERMOSTAT TRIP (AUX1) NONE NONE
OVERLOAD WARNING ALARM (AUX2) NONE NONE
OVERCURRENT ALARM ALARM (AUX2) NONE NONE
SCR FAIL SHUNT ALARM ALARM (AUX2) NONE NONE
GROUND FAULT ALARM* ALARM (AUX2) NONE NONE
UNDERCURRENT ALARM NONE NONE NONE
MOTOR RUNNING AUX3 NONE NONE
IMBALANCE ALARM ALARM (AUX2) NONE NONE
STATOR RTD ALARM NONE NONE NONE
NON-STATOR RTD ALARM NONE NONE NONE
RTD FAILURE ALARM NONE NONE NONE
SELF TEST FAIL TRIP (AUX1) NONE NONE
THERMAL REGISTER ALARM (AUX2) NONE NONE
U/V ALARM ALARM (AUX2) NONE NONE
O/V ALARM ALARM (AUX2) NONE NONE
POWER FACTOR ALARM NONE NONE NONE
KW DEMAND ALARM NONE NONE NONE
KVA DEMAND ALARM NONE NONE NONE
KVAR DEMAND ALARM NONE NONE NONE
AMPS DEMAND ALARM NONE NONE NONE
TIMED OUTPUT NONE NONE NONE
RUN DELAY TIME NONE NONE NONE
AT SPEED AUX4 NONE NONE
*Ground fault option must be installed.
JKSSS+ Series - 54

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.5 Relay Configuration (Setpoint Page 5)


(Security Level: 2)
MENU
In Setpoint Page 5 the user (Hit DOWN ARROW four times)
can configure the four output
relays as either fail-safe or
PAGE 5 RELAY TRIP (AUX1) RELAY TRIP (AUX1) RELAY
non fail-safe and latching or CONFIGURATION FAIL-SAFE: NO LATCHED: YES
non-latching. Options: Yes or No

SP5.1 When a relay has been configured


ALARM (AUX2) RELAY ALARM (AUX2) RELAY
as fail-safe and power is applied, FAIL-SAFE: NO LATCHED: NO
the relay will be energized. The
relay will then de-energize when
an event occurs or if the power AUX 3 RELAY AUX3 RELAY
fails. Note: The relays in the FAIL-SAFE: NO LATCHED: NO
soft starter will not prevent a start
sequence unless they are wired in
as interlocks. If power is lost, the AUX4 RELAY AUX4 RELAY
motor power is also lost. Do not FAIL-SAFE: NO LATCHED: NO
change the programming for AUX
1-4. These are for factory use only.
AUX 5-8 are user defined outputs. AUX5 RELAY AUX5 RELAY
FAIL-SAFE: NO LATCHED: NO

SP5.2 A relay configured as non-latching


will reset itself when the cause of
the trip event is not continuous. AUX6 RELAY AUX6 RELAY
The TRIP (AUX1) relay should FAIL-SAFE: NO LATCHED: NO
always be programmed for latching,
because this trip should require a
visual inspection of the motor and
AUX7 RELAY AUX7 RELAY
starter before issuing a manual FAIL-SAFE: NO LATCHED: NO
reset to release the relay after a trip
has been stored.

AUX8 RELAY AUX8 RELAY


FAIL-SAFE: NO LATCHED: NO

JKSSS+ Series - 55

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)

MENU
(Hit DOWN ARROW five times)

ENABLED
PAGE 6 USER I/O TACHOMETER SCALE MANUAL TACH SCALE
CONFIGURATION SELECTION: DISABLED 4.0 mA: 0 RPM
Options: ENABLED or Range: 0-3600
DISABLED Increments of 5

MANUAL TACH SCALE


20.0 mA: 2000 RPM
Range: 0-3600
Increments of 5
TACH ACCEL TRIP MODE
SELECT: DISABLED
TACH RAMP TIME
: 20 SEC
Range: 1 - 120 SEC.,
Disabled
Increments of 1

TACH UNDERSPEED TRIP


PT: 1650 RPM
Range: 0 - 3600
Increments of 5

TACH OVERSPEED TRIP


PT: 1850 RPM
Range: 0 - 3600
Increments of 5

TACH ACCEL TRIP


DELAY: 1 SEC
Options: UNDERSPEED,
OVERSPEED or DISABLED Range: 1 - 60
Increments of 1

ANALOG OUTPUT #1 ANALOG OUTPUT #1 ANALOG OUTPUT #1


:RMS CURRENT 4ma: 0 20mA: 250
Range: Range: 0-65535 Range: 0-65535
Analog Output Range Increments of 1 Increments of 1
RPM 0 - 3600
Hottest Bearing 0 - 200°C
Hottest Stator RTD 0 - 200°C
RMS Current 0 - 6500A
% Motor Load 0 - 1000%
KW 0-30000 KW
OFF
Increments of 1

ANALOG OUTPUT #2 ANALOG OUTPUT #2 ANALOG OUTPUT #2


:% MOTOR LOAD 4mA: 0 20mA: 1000
Range: See Analog Output #1 Range: 0-65535 Range: 0-65535
Increments of 1 Increments of 1 Increments of 1

USER PROGRAMMABLE
EXTERNAL INPUTS

Continued...

JKSSS+ Series - 56

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)
The controller can be configured to accept a tachometer
feedback signal through the 4-20mA input.

SP6.1 The first screen of setpoint page 6 is TACHOMETER SP6.3 The controller provides two 4-20mA analog outputs.
SCALE SELECTION. When this is set to Each analog output is independent of the
ENABLED, the user will need to input the other and can be assigned to monitor different
tachometer scale of the 4-20mA input range. functions. The available output ranges are RPM,
Hottest Non-Stator (Bearing) RTD, Hottest Stator
• Manual Tach Scale 4.0 mA: The unit is looking RTD, RMS current, % Motor Load, or kW.
for an RPM value to assign to the lowest point on
the scale. This value should represent the motor • Analog Output #1 – Select a function from
at zero speed. the available options to be transmitted from
the 4-20mA output. Note: If selecting RPM,
• Manual Tach Scale 20.0 mA: The unit is looking the Tachometer feedback input signal must be
for an RPM value to assign to the highest point on present in order for the controller to give proper
the scale. This value should represent the motor output. If selecting RTD, the RTD option must
at full speed. be installed and an RTD input signal must be
present for a proper output to be given from the
SP6.2 Tach Accel Trip Mode Select: When enabled, the analog output.
underspeed or overspeed must be selected for the • Analog Output #1 (4 mA): Enter a value that the
Tach Accel Trip. If underspeed is selected, only 4mA level will represent for the selected function;
the Tach Underspeed Trip Point will be used. If typically this value should be 0.
overspeed is selected only the Tach Overspeed • Analog Output #1 (20 mA): Enter a value that
Trip Point will be used. the 20mA level will represent for the selected
function.
• Tach Ramp Time: This is the duration of time
before the tachometer begins to sample. SP6.4 Analog Output #2 – All of the setpoints and setup
screens for Analog Output #2 are the same as
• Tach Underspeed Trip: The minimum value of those for Analog Output #1.
motor RPM which must be achieved before the
Tach Ramp Time sample is taken.

• Tach Overspeed Trip: The maximum motor RPM


allowed when the Tach Ramp Time sample is
taken.

• Tach Accel Trip Delay: The duration of time that


the Tach Accel trip condition must persist before a
trip is generated.

JKSSS+ Series - 57

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)

USER TCB FAULT NAME EXT. INPUT #1 TCB FAULT TCB FAULT
PROGRAMMABLE SELECT: ENABLED TCB FAULT TYPE: NORMALLY OPEN TIME DELAY: 1 SEC.
EXTERNAL Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC
INPUTS Normally Closed Increments of 1
(Continued)

EXTERNAL INPUT #2 NAME EXT INPUT #2 EXTERNAL INPUT #2 EXTERNAL INPUT #2


SELECT: DISABLED TYPE: NORMALLY OPEN TIME DELAY: 0 SEC.
Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC.
Normally Closed Increments of 1

DUAL RAMP NAME EXT INPUT #3 DUAL RAMP DUAL RAMP


SELECT: DUAL RAMP SECOND RAMP TYPE: NORMALLY OPEN TIME DELAY: 0 SEC.
Options: Enabled, Disabled or See text for directions Options: Normally Open or Range: 0 - 60 SEC
Dual Ramp Normally Closed Increments of 1

THERMOSTAT NAME EXT INPUT #4 THERMOSTAT THERMOSTAT


SELECT: ENABLED THERMOSTAT TYPE: NORMALLY CLOSED TIME DELAY: 1 SEC.
Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC.
Normally Closed Increments of 1

SP6.5 User Programmable External Inputs: The


controller provides up to 4 digital external inputs
which are individually programmable. A description
name can be assigned to each individual input for
easy identification.

• External Input #1: Factory programmed for TCB • External Input #3: The setup screens and
Trip. setpoints for External Input #3 includes the option
of being configured for Dual Ramp. In Dual Ramp
• External Input #2: If used, this setpoint must be mode, the initial contact setting is the same as the
enabled. START RAMP #1. Upon a change in input contact
state, the controller will switch over to START
• Name Ext. Input #2: The user can assign a RAMP #2 and use that setting for start control
description name to the input to easily identify mode. Note: The start RAMP types should only be
the cause of external trip or alarm. Up to 15 switched while the motor is stopped. In Setpoint
characters including spaces can be used to assign Page 4 Relay Assignments, do not assign any
the name. output relay to this function. The controller will
ship with External input #3 programmed for dual
• External Input #2 Type: The external input can ramp. If it is not needed, disable the dual ramp.
be set as either a normally open or normally
closed contact. • External Input #4: This input screens are for the
thermostat input and can be enabled or disabled.
• External Input #2 Time Delay: Upon a change in Note: It is recommended that this function remain
contact setting, the unit will wait the programmed enabled. If the thermostat indicates an over
amount of time before generating an output. If temperature condition, the controller will trip the
no delay is needed, then input 0 seconds. The motor.
controller will post an event upon seeing a change
in state.

JKSSS+ Series - 58

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)
MENU
(Hit DOWN ARROW six times)

PAGE 7 CUSTOM CUSTOM ACCEL CURVE


ACCELERATION CURVE : DISABLED
Range: DISABLED,
CURVE A, B or C
CURVE A VOLTAGE
SP7.1 Setpoint Page 7 allows the user to custom design CUSTOM CURVE A LEVEL 1: 25%
the acceleration curve (start curve) to the specific Range: 0 - 100%
application. The user can custom design up to Increments of 1

three different curves in the soft starter. Only one CURVE A RAMP
curve can be active (enabled) at a time. Each of TIME 1: 2 SEC

the three curves allow for eight voltage plotting Range: 1 - 60 SEC
Increments of 1
points, with corresponding ramp times and a
CURVE A VOLTAGE
current limit setting. LEVEL 2: 30%
Note: Each successive voltage level must be Range: 0 - 100%
Increments of 1
programmed to a voltage level equal to or greater
than the previous level. All eight levels of voltages CURVE A RAMP
TIME 2: 2 SEC.
must be programmed and the eighth level has
Range: 1 - 60 SEC
been preset at 100%. Increments of 1

CURVE A VOLTAGE
• If Custom Accel Curve has been set to curve A, LEVEL 3: 37%
B or C on this page, the soft starter will override Range: 0 - 100%
Increments of 1
the Start Control Mode selected in Setpoint Page
2, (even if Start Control Mode in Setpoint Page 2 CURVE A RAMP
has not been set to Custom Accel Curve). TIME 3: 2 SEC.
Note: Setpoint Page 7 has a security level 3 Range: 1 - 60 SEC
Increments of 1
requirement.
CURVE A VOLTAGE
LEVEL 4: 45%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 5: 55%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 6: 67%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 7: 82%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

JKSSS+ Series - 59

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)

CURVE A VOLTAGE CURVE B VOLTAGE


CUSTOM CURVE A LEVEL 8: 100% CUSTOM CURVE B LEVEL 7: 82%
Range: 0 - 100% Range: 0 - 100%
Increments of 1 Increments of 1

CURVE A RAMP CURVE B RAMP


TIME 8: 2 SEC TIME 7: 2 SEC.
Range: 1 - 60 SEC Range: 1 - 60 SEC
Increments of 1 Increments of 1

CURVE A CURRENT
LIMIT: 350% FLA CURVE B VOLTAGE
LEVEL 8: 100%
Range: 200 - 500%
Increments of 10 Range: 0 - 100%
Increments of 1

CURVE B RAMP
CURVE B VOLTAGE TIME 8: 2 SEC
CUSTOM CURVE B LEVEL 1: 25%
Range: 1 - 60 SEC
Range: 0 - 100% Increments of 1
Increments of 1
CURVE B CURRENT
CURVE B RAMP LIMIT: 350% FLA
TIME 1: 2 SEC.
Range: 200 - 500%
Range: 1 - 60 SEC Increments of 10
Increments of 1

CURVE B VOLTAGE
LEVEL 2: 30% CUSTOM CURVE C CURVE C VOLTAGE
Range: 0 - 100% LEVEL 1: 25%
Increments of 1 Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 2: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 1: 2 SEC.
Increments of 1 Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 3: 37% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 2: 30%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 3: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 2: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 4: 45% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 3: 37%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 4: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC TIME 3: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 5: 55%
CURVE C VOLTAGE
Range: 0 - 100% LEVEL 4: 45%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 5: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC
Increments of 1 TIME 4: 2 SEC.
Range:1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 6: 67%
CURVE C VOLTAGE
Range: 0 - 100%
Increments of 1 LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC CURVE C RAMP
Increments of 1 TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
JKSSS+ Series - 60

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)

SP7.1 Setpoint Page 7 allows the user to custom design


the acceleration curve (start curve) to the specific
application. The user can custom design up to
CURVE C VOLTAGE
three different curves in the soft starter. Only one CUSTOM CURVE C
LEVEL 6: 67%
curve can be active (enabled) at a time. Each of Range: 0 - 100%
Increments of 1
the three curves has eight voltage levels, with
corresponding ramp times and a current limit
setting. CURVE C RAMP
TIME 6: 2 SEC.
Note: Each successive voltage level must be Range: 1 - 60 SEC
programmed to a voltage level equal to or greater Increments of 1
than the previous level. All eight levels of voltages
must be programmed and the eighth level has CURVE C VOLTAGE
been preset at 100%. LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
• If Custom Accel Curve has been set to curve A, B
or C on this page, the soft starter will override the CURVE C RAMP
Start Control Mode selected in Setpoint Page 2, TIME 7: 2 SEC.
(even if Start Control Mode in Setpoint Page 2 has Range: 1 - 60 SEC
Increments of 1
not been set to Custom Accel Curve).
Note: Setpoint Page 7 has a security level 3 CURVE C VOLTAGE
requirement. LEVEL 8: 100%
Range: 0 - 100%
Increments of 1

CURVE C RAMP
TIME 8: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE C CURRENT
LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10

JKSSS+ Series - 61

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.8 Overload Curve Configuration (Setpoint Page 8)
(Security Level: 3)

MENU
(Hit DOWN ARROW seven times)

PAGE 8 OVERLOAD BASIC RUN RUN CURVE LOCKED RUN LOCKED ROTOR
CURVE CONFIGURATION OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range: 1 - 30 SEC, O/L CLASS Range: 400 - 800%
Configures the unit’s start and Increments of 1

run protection mode. The unit has COAST DOWN TIMER


independent start and run curve TIME: DISABLED
protection and the settings can be Range:1 - 60 MIN, DISABLED
based on the OL Class or set by the Increments of 1

motor’s locked rotor current and time. BASIC START START CURVE LOCKED START LOCKED ROTOR
OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range:1 - 30 SEC, O/L CLASS Range: 400 - 800%
SP8.1 Basic Run Overload Curve Increments of 1 Increments of 10
• Run Curve Locked Rotor
Time: Set the locked rotor time ACCELERATION TIME
to the OL Class default chosen LIMIT: 30 SEC
Range:1 - 300 SEC, DISABLED
in Setpoint Page 1 or set the Increments of 1
time in seconds. This is the
time the locked rotor condition NUMBER OF STARTS PER
exists before a trip occurs. HOUR: DISABLED
Range: 1 - 6, DISABLED
• Run Locked Rotor Current: Increments of 1
The current the motor draws
with full voltage on the windings TIME BETWEEN STARTS
TIME: 5 MIN
and no rotor movement (as a Range:1 - 60 MIN, DISABLED
percent of motor FLA). Refer to Increments of 1
the nameplate data or contact
AREA UNDER CURVE MAX I*I*T START
the motor manufacturer. PROTECTION: DISABLED : 368 FLA*FLA*SEC
• Coast Down Timer: If enabled, Range: ENABLED or DISABLED Range:1 - 2500, FLA*Time (Sec)
this prevents the motor from Increments of 1

restarting for the programmed


amount of time, after a stop CURRENT OVER
CURVE: DISABLED
LEARNED START CURVE
BIAS: 10%
TIME FOR SAMPLING
: 30 SEC
command is given. Options: DISABLED, LEARN Range: 5 - 40% Range: 1 - 300 SEC
SP8.2 Basic Start Overload Curve or ENABLED Increments of 1 Increments of 1

• Start Curve Locked Rotor Time: The locked SP8.3 Area Under Curve Protection: If enabled, this
rotor time can be set to the OL Class default secondary start protection uses both the basic start
chosen in Setpoint Page 1 or to a specific protection and the area under the curve protection.
time. The overload condition must exist for the • Max I*I*T Start: The maximum I2T allowed during
programmed amount of time before a trip occurs. start. If the I2T to start exceeds this number then the
• Start Locked Rotor Current: The current the soft starter will generate a trip.
motor draws with full voltage on the windings and
no motor movement (as a percent of motor FLA). SP8.4 Current Over Curve: Learns the motor’s starting
Refer to the motor nameplate data or contact the characteristics and protects the motor based upon
motor manufacturer. the learned curve. It is useful when commissioning a
• Acceleration Time Limit: If the motor does not new motor.
enter run mode (reach at speed) within the preset • Learn: The unit reads the motor’s starting
time, the unit trips on acceleration time limit. characteristics. Start the motor and allow it to come
• Number of Starts per hour: If enabled, this to full speed. The start feedback enables the motor
limits the maximum number of starts permitted per protection based on the learned start curve.
hour. This setpoint allows a maximum of 6 starts • Learned Start Curve Basis: The maximum allowed
per hour. Contact motor manufacturer. deviation above or below the start curve before a trip
• Time Between Starts: If enabled, the soft is generated.
starter prevents another start attempt until the • Time for Sampling: The time the soft starter
programmed time has expired. continues to sample the start curve characteristic
during learn the mode.

JKSSS+ Series - 62

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.9 RTD Optional Configuration (Setpoint Page 9)


(Security Level: 3)

MENU
(Hit DOWN ARROW eight times)
Ranges:
* 120 OHM NICKEL (NI)
PAGE 9 RTD USE NEMA TEMP FOR 100 OHM NICKEL (NI)
CONFIGURATION RTD VALUES: DISABLED 10 OHM COPPER (CU)
100 OHM PLATINUM (PT)
Options: ENABLED OR OFF
DISABLED
** OFF or 0 - 240C (32-464F) Example: ### C = ### F
# OF RTD’S USED FOR Increments of 1
STATOR: 4
*** STATOR A1, STATOR A2, STATOR B1, STATOR B2, STATOR C1, STATOR C2,
Range: 0 - 6 FRONT BEARING, BACK BEARING, BEARING BOX, AMBIENT, NONE
Increments of 1

RTD VOTING
: DISABLED
Options: ENABLED or
DISABLED

STATOR PHASE A1 TYPE RTD # 1 DESCRIPTION STATOR PHASE A1 ALARM STATOR PHASE A1 TRIP
: OFF STATOR PHASE A1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE A2 TYPE RTD # 2 DESCRIPTION STATOR PHASE A2 ALARM STATOR PHASE A2 TRIP
: OFF STATOR PHASE A2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE B1 TYPE RTD # 3 DESCRIPTION STATOR PHASE B1 ALARM STATOR PHASE B1 TRIP
: OFF STATOR PHASE B1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE B2 TYPE RTD # 4 DESCRIPTION STATOR PHASE B2 ALARM STATOR PHASE B2 TRIP
: OFF STATOR PHASE B2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE C1 TYPE RTD # 5 DESCRIPTION STATOR PHASE C1 ALARM STATOR PHASE C1 TRIP
: OFF STATOR PHASE C1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: *** Range: ***

STATOR PHASE C2 TYPE RTD # 6 DESCRIPTION STATOR PHASE C2 ALARM STATOR PHASE C2 TRIP
: OFF STATOR PHASE C2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

END BEARING TYPE RTD #7 DESCRIPTION END BEARING ALARM END BEARING TRIP
: OFF END BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

SHAFT BEARING TYPE RTD # 8 DESCRIPTION SHAFT BEARING ALARM SHAFT BEARING TRIP
: OFF SHAFT BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 9 TYPE RTD # 9 DESCRIPTION RTD # 9 ALARM RTD # 9 TRIP


: OFF RTD # 9 LEVEL: OFF LEVEL: OFF
Range:* Range: *** Range: ** Range: **

RTD # 10 TYPE RTD # 10 DESCRIPTION RTD # 10 ALARM RTD # 10 TRIP


: OFF RTD # 10 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 11 TYPE RTD # 11 DESCRIPTION RTD # 11 ALARM RTD # 11 TRIP


: OFF RTD #11 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 12 TYPE RTD # 12 DESCRIPTION RTD # 12 ALARM RTD # 12 TRIP


: OFF RTD # 12 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

JKSSS+ Series - 63

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.9 RTD Configuration (Setpoint Page 9)


(Security Level: 3)

The soft starter comes with an RTD card that provides 12


programmable RTDs which are individually programmable
for type. The available types are 100 ohm platinum, 100 ohm
nickel, 120 ohm nickel and 10 ohm copper. Each RTD can
be identified with a description name of up to 15 characters
(including spacing). Also, each individual RTD has it own alarm
and trip level.

SP9.1 Use NEMA Temp for RTD Value: When this setpoint
is enabled, the soft starter will use the NEMA design
insulation class to limit the maximum allowed range
of the alarm and trip level. The maximum allowed
temperature range is 240° C or (464°F).

SP9.2 # Of RTD’S Used for Stator: Up to six RTDs can be


assigned to monitor the stator of the motor.

SP9.3 RTD Voting: When this is enabled, the soft starter will not
post a trip until 2 RTD’s have exceeded the trip level.
This prevents nuisance RTD tripping.

SP9.4 All 12 RTDs are configured in the following manner. The


first column is the RTD type, the second column is the
RTD description, the third column is the alarm level,
and the fourth column is the trip level.
The first six RTDs have been pre-programmed with
a description name for the STATOR, with two RTDs
per phase. RTDs #1 & #2 have been named STATOR
PHASE A1 and A2 respectively. RTDs #3 & 4 are
named STATOR PHASE B1 and B2, RTDs #5 & 6
are named STATOR PHASE C1 and C2. If other
description names are required, press the right arrow
button from the RTD Type screen to go the RTD
description screen. If no alarm or trip level is required
these setpoints can be turned off.

JKSSS+ Series - 64

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.10 Set Password (Setpoint Page 10)


(Security Level: 3) MENU
(Hit DOWN ARROW nine times)
The soft starter has three levels of user programmable
setpoint screens. Level one setpoints do not require a PAGE 10 SECURITY SET LEVEL 2
password because the data contained in level one is basic SET PASSWORD PASSWORD: 100
nameplate data and starter control. Level two setpoint Range: 000 - 999
screens require a three-digit password to configure the
protection schemes. Level three setpoint screens require SET LEVEL 3
a four-digit password to access the full range of protection PASSWORD: 1000

and starter schemes. Range: 0000 - 9999

SP10.1 Set Level 2 Password: This level uses a 3-digit


password. The default level 2 password is 100.

SP10.2 Set Level 3 Password: Level three uses a 4-digit


password. The default level 3 password is 1000.

JKSSS+ Series - 65

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.11 Communications (Setpoint Page 11)


(Security Level: 3)
MENU
SP11.1 Set Front Baud Rate: Configures the RS232 (Hit DOWN ARROW ten times)
communications baud rate.
PAGE 11 SET FRONT BAUD
SP11.2 Set Modbus Baud Rate: Configures the COMMUNICATIONS RATE: 9.6 KB/SEC
Modbus communications baud rate. Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC

SP11.3 Modbus Address Number: Assigns a Modbus SET MODBUS BAUD


address to the soft starter relay. RATE: 9.6 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
SP11.4 Set Access Code: Assigns an access code to
the Modbus addressing. This is typically not MODBUS ADDRESS
NUMBER: 247
used.
Range: 1 - 247
Increments of 1
SP11.5 Set Link Baud Rate: Configures the RS422
SET ACCESS CODE
communications baud rate between the keypad CODE: 1
operator and the CPU board. (For applications Range: 1 - 999
with remote keypad only.) Increments of 1

SET LINK BAUD


SP11.6 Remote Start/Stop: Allows the RS485 Modbus RATE: 38.4 KB/SEC
communications to start and stop the motor. Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
Contact factory for details.
REMOTE START/STOP:
DISABLED
Option: Enabled or Disabled

JKSSS+ Series - 66

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
SP.12 System Setpoints (Setpoint Page 12)
(Security Level: 3)

MENU
(Hit DOWN ARROW eleven times)

PAGE 12 SYSTEM DEFAULT DISPLAY METERING DATA METERING DATA


SETPOINTS SCREEN PAGE #: 1 SCREEN #: 1
Enter Metering Page (1 - 4) Enter Metering
Number for display Screen Number for display

ALARMS RTD FAILURE ALARM


ALARM: DISABLED
Enabled or Disabled

THERMAL REGISTER THERMAL ALARM


ALARM: 90% DELAY: 10 SEC.
Range: Off, 40 - 95% Range: 1 - 20 SEC.
Increments of 1 Increments of 1

COLD STALL TIME


THERMAL REGISTER : O/L CLASS
SETUP INFORMATION
Range: O/L CLASS,
4 - 40 SEC
Increments of 1
HOT STALL TIME
: 1/2 O/L CLASS
Range: 1/2 O/L CLASS,
4 - 40 SEC
Increments of 1
STOPPED COOL DOWN
TIME: 30 MIN
Range: 10 - 300 MIN
Increments of 1

RUNNING COOL DOWN


TIME: 15 MIN
Range: 10 - 300 MIN
Increments of 1

RELAY MEASURED COOL


RATES: DISABLED
Range: ENABLED or
DISABLED

THERMAL REGISTER
MINIMUM: 15%
Range: 10 - 50%, OFF
Increments of 1

MOTOR DESIGN AMBIENT


TEMPERATURE: 40 C
Range: 10 - 90 C
Increments of 1

MOTOR DESIGN RUN


TEMPERATURE: 80% MAX
Range: 50 - 100% of Motor
Stator Max Temp.
Increments of 1%

MOTOR STATOR MAX


TEMPERATURE: INS CLS
Range: Insulation Class
10 - 240 C
Increments of 1

I/B INPUT TO THERMAL


REGISTER: ENABLED
Options: ENABLED or
DISABLED

USE CALCULATED K OR
ASSIGN: 7
Range: 1 - 50, ON

PRESS ENTER TO CLR


THERMAL REGISTER
JKSSS+ Series - 67

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.12 System Setpoints (Setpoint Page 12)


(Security Level: 3)

SP12.1 Default Display Screen: This setpoint group • Thermal Register Minimum: Sets the value
allows the user to choose the default screen the in the thermal register which represents a
soft starter displays while the motor is running. motor running at the nameplate current (with
Select the metering page number (1-3), then no overheating or negative sequence currents
select the metering screen number. The range present).
varies depending on the selected page. To display • Motor Design Ambient Temperature: Use the
a default screen, program the following two data from the motor manufacturer’s specifications.
setpoints: When RTDs are used, this setpoint will be the
• Metering Data Page#: Range is Page 1 - 3. base point for the RTD biasing of the Thermal
• Metering Data Screen#: If Page 1 is selected Register.
as the default page, then Screens 1- 10 are • Motor Design Run Temperature: Use the data
available. If Page 2, Screens 1-29 are available. from the motor manufacturer’s specifications. This
If Page 3 is selected, then Screens 1-6 are setpoint defines the operating temperature rise of
available. (See Metering Menu, MP.1, for screen the motor at full load amps or 100% load.
number assignment.) • Motor Stator Max Temperature: This represents
the maximum temperature the stator insulation
SP12.2 Alarms: Configures the RTD failure alarm and the will withstand. The user may choose to use
thermal register alarm. the temperature setting of the insulation class
• RTD Failure Alarm: If enabled, and an RTD (selected in Setpoint Page 1) or enter a specific
shorts or open, an alarm occurs. maximum temperature. This value should not
• Thermal Register Alarm: Sets a level in the exceed the stator’s insulation temperature. This
thermal register to generate an alarm when the maximum temperature represents 100% thermal
Thermal Register Capacity Used has exceeded capacity.
this level. • U/B Input to Thermal Register: Always enabled.
• Thermal Alarm Delay: The amount of time that It allows the soft starter to use the line current
the Thermal Register Used must exceed the imbalance information to bias the Thermal
setpoint before an alarm condition will occur. Register.
SP12.3 Thermal Register Setup Information: This • User Calculated K or Assign: When the setpoint
setpoint group will configure the thermal register is set to ON the controller will calculate the k
and indicate to the soft starter which inputs to use constant factor for biasing the thermal register, or
when thermal modeling. the user may choose to assign the k value.
• Cold Stall Time: Enter the time from the motor
manufacturer’s specification sheet or use the time SP12.4 Press Enter to CLR Thermal Register: Allows
defined by the OL Class. This setpoint is used to the level three password user to clear the thermal
define the thermal capacity of the motor. register for emergency restarts.
• Hot Stall Time: Enter the amount of time
specified by the motor manufacturer or use half of
the time defined by the OL Class.
• Stopped Cool Down Time: The time the motor
requires to cool down after it has stopped. Use
only the data provided by the motor manufacturer.
This setpoint is used to configure the cooling rate
of the thermal register.
• Running Cool Down Time: The amount of
time the motor requires for cooling down while
running. Use only the data provided by the motor
manufacturer.
• Relay Measured Cool Rates: When RTDs are
used, the soft starter can be configured to use the
measured cool rates from the RTDs instead of the
programmed settings. This setpoint should only be
enabled when RTDs are present.

JKSSS+ Series - 68

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SP.13 Calibration & Service (Setpoint Page 13)


(Security Level: Factory Use Only)

MENU
(Hit DOWN ARROW twelve times)

PAGE 13 CALIBRATION SET DATE AND TIME ENTER DATE (DDMMYYYY) ENTER TIME (hh:mm)
& SERVICE ##/##/## ##:## :##/##/#### :##:##
Range: D = 1 - 31, M = 1-12, Range: H = 00 - 23, M = 0 - 59
Y = 1970 - 2069 Increments of 1
Increments of 1
MODEL #: ######
FIRMWARE REV. #: ######

PRESS ENTER TO ACCESS


FACTORY SETTINGS

SP.13 Calibration & Service (Setpoint Page 13)


Certain screens are displayed for user information only, such
as: Current date and time, Model number and Firmware
revision number. Setpoint changes in this page will only be
accessible to factory personnel.
SP13.1 Set Date and Time: Displays the date and time.
• Enter Date (DDMMYYYY): Allows the factory
personnel to program the date for the soft starter in
the format shown.
• Enter Time (hh:mm): Allows the factory personnel to
program the time for the soft starter.

SP13.2 Model & Firmware #: Displays the model number


and firmware revision in the soft starter.

SP13.3 Press Enter to Access Factory Settings: Available


to qualified personnel.

JKSSS+ Series - 69

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Chapter 6 - Metering Pages
The soft starter offers performance metering which gives the user the ability to view
information about the motor and the JKSSS+ unit.
6.1 Metering Page List
The following charts list each Metering Page and the functions within that page. The
applicable section of the manual is also referenced.

6.1.1 Metering Menu & Data (Metering Page 1)


Metering
Description of Display Screen
Page
Phase A, B, C and Ground Fault (Option) 1
Average current of the % of imbalance and the motor's RPM 2
Metering Menu & Data

Motor load as a percentage of motor FLA 3


Line frequency and present phase sequence 4
Page 1

Percentage of remaining Thermal Register 5


Thermal capacity required to start the motor 6
Average time required to start 7
Average current during start 8
2
Measured I T required to start the motor 9
Amount of time required to start the motor during the last successful start 10

6.1.2 Metering (Metering Page 2)


Metering
Description of Display Screen
Page
Phase A, B, C currents and Power Factor 1
Phase A, B, C currents and Ground Fault (Option) 2
Displays kW and kVA 3
Displays kVAR and Power Factor 4
Displays Peak ON and kW Demand 5
Metering
Page 2

Displays Peak ON and kVA Demand 6


Displays Peak ON and kVAR Demand 7
Displays Peak ON and Amps Demand 8
Clears Demand values 9
Displays Megawatt hours used 10
Press enter to clear statistics on MWH values 11

6.1.3 RTD Values (Metering Page 3)


Metering
Description of Display Screen
Page
Hottest stator RTD (#1 - 6) 1
Hottest non-stator RTD (#7 - 12) 2
Temperature of start phase A1 in °C and °F 3
RTD Values
Page 3

Maximum temperature for RTD #1 4


Same as Screens 3 - 4 for RTDs #2 - 12 5 - 26
Clear the maximum temperature register (Level 3 password required) 27
Measured running thermal stabilization time of motor (in minutes) 28
Measured stopped cooling time (to ambient) of motor (in minutes) 29

JKSSS+ Series - 70

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
6.1.4 Status (Metering Page 4)
Metering
Description of Display Screen
Page
Current status 1
Page 4 Amount of time remaining before an overload trip occurs 2
Status Amount of time remaining from a thermal inhibit signal 3
Coast down time remaining 4
Amount of time remaining before a start command can be given 5
Excessive number of starts per hour 6
6.1.5 Event Recorder (Metering Page 5)
Metering
Description of Display Screen
Page
Recorder

Displays the event with date and time (Up to 60 events) 1


Page 5
Event

Displays Phase A, B, C current values, Ground Fault (Option) at time of trip 1A


Displays Vab, Vbc, Vca and Power Factor at time of trip 1B

6.1.6 Last Trip (Metering Page 6)

6.1.7 Statistics (Metering Page 7)


Metering
Description of Display Screen
Page
Total megawatt hours 1
Accumulated total running hours 2
Clear the total running hour count 3
Total number of trips 4
Number of start and run overload trips since the last statistical data
5
clearing
Number of frequency trips and imbalance trips 6
Overcurrent trips 7
Stator and non-stator RTD trips 8
Ground fault hiset and loset trips 9
Acceleration time trips 10
Start under curve trips 11
Start over curve trips 12
Statistics
Page 7

2
I T start curve trips 13
Learned start curve trips 14
Fail shunt trip trips 15
Phase loss trip trips 16
Tach accel trip trips 17
Undervoltage and Overvoltage trips 18
Power Factor trips 19
Phase reversal trips 20
Ext Inp #1 21
Ext Inp #2 22
Ext Inp #3 23
Ext Inp #4 24
Press enter to clear statistics 25
JKSSS+ Series - 71

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
6.2 Metering Menu
Push MENU key to toggle the screens between Setpoint Menu and Metering Menu
and follow the arrow keys to get to different screens.

MENU

METERING PAGE 1
CURRENT METERED DATA

METERING PAGE 2
VOLTAGE & POWER DATA

METERING PAGE 3
RTD VALUES

METERING PAGE 4
STATUS

METERING PAGE 5
EVENT RECORDER

METERING PAGE 6
LAST TRIP

METERING PAGE 7
STATISTICS

JKSSS+ Series - 72

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
MP.1 Metering Data (Metering Page 1)

Displays the basic current metering data: MENU


Screen 1: Phase A, B, C and ground fault (option)
current.
METERING PAGE 1 IA: ###### IB: ######
Screen 1
Screen 2: Displays the average current, percent of CURRENT METERED DATA IC: ###### G/F: #####
imbalance and the motor’s RPM (available
with tachometer input)
I (AVG): ####
Screen 2
Screen 3: Displays the motor load in percent of motor I/B: ## % RPM: ####
FLA.

Screen 4: Displays the line frequency and the present MOTOR LOAD % OF FLA
Phase Order. FLA: ### %
Screen 3

Screen 5: Displays the percent of the remaining thermal


register. In order for the motor to successfully
LINE FREQUENCY:: ##.##
start, the percentage must be greater than Screen 4
PHASE ORDER: ###
the thermal capacity required for a successful
start.

Screen 6: Displays the thermal capacity required to THERMAL REGISTER


Screen 5
successfully start the motor. REMAINING: ### %

Screen 7: Displays the average time required to start.


THERMAL CAPACITY
Screen 6
Screen 8: Displays the average current during start. TO START: ### %

Screen 9: Displays the measured I2T required to start


the motor. AVERAGE START TIME
Screen 7
TIME: ##.# SECS
Screen 10: Displays the amount of time required to start
the motor during the last successful start.
AVG START CURENT
Screen 8
: ###### AMPS

I*I*T TO START
Screen 9
I*I*T: #######

LAST START
Screen 10
TIME: ##.# SEC

JKSSS+ Series - 73

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MP.2 Metering (Metering Page 2)


MENU
Displays the statistical voltage metering informa-
tion.
Screen 1
METERING PAGE 2 Vab: ### Vbc: ###
Screen 1: Displays Phase A, B, C and Power Factor. VOLTAGE & POWER DATA Vca: ### P/F: ## #.##
Note: P/F: N/A Motor stopped
P/F: LG #.## (Lagging) Screen 2
P/F: LD #.## (Leading) IA: ##### IB: #####
IC: ##### G/F:###.#

Screen 2: Displays Phase A, B, C and Ground Fault Screen 3


Current. kW: #####
kVA: #####
Screen 3: Displays KW and KVA.
Screen 4
kVAR: #####
Screen 4: Displays KVAR and Power Factor.
P/F: ## #.##

Screen 5: Displays Peak On and KW demand. Screen 5


PEAK ON: ##/## ##:##
Screen 6: Displays Peak On and KVA demand. kW: #####

Screen 6
Screen 7: Displays Peak On and KVAR demand.
PEAK ON: ##/## ##:##
Note: P/F: N/A Motor stopped kVA: #####
P/F: LG #.## (Lagging)
P/F: LD #.## (Leading) Screen 7
PEAK ON: ##/## ##:##
Screen 8: Displays Peak On and Amps demand. kVAR: #####

Screen 8
Screen 9: Clears Demand Values. PEAK ON: ##/## ##:##
AMPS: #####
Screen 10: Displays the Megawatts used per hour.
Screen 9
Screen 11: Press Enter to clear statistics on MWH values. PRESS ENTER TO CLEAR
DEMAND VALUES

Screen 10
MWH USED
: #####

Screen 11
PRESS ENTER TO CLEAR
MWH VALUES

JKSSS+ Series - 74

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MENU
Screen 1
METERING PAGE 3 HOTTEST STATOR
RTD VALUES RTD#: # @ ### C

MP.3 RTD Values (Metering Page 3) Screen 2


Displays the RTD information. HOTTEST NON-STATOR
RTD#: # @ ### C

Screen 1: Displays the hottest stator RTD (#1 - 6


Screen 3 Screen 4
depending upon number of RTDs used for
STATOR PHASE A1 MAX TEMP SINCE
stator). RTD #1: ### C = ### F CLEAR RTD #1: ### C

Screen 2: Displays the hottest non-stator RTD (#7-12 if Screen 5 Screen 6


#1-6 is used for stator). STATOR PHASE A2 MAX TEMP SINCE
RTD #2: ### C = ### F CLEAR RTD #2: ### C

Screen 3: Displays the temperature of stator phase A1 Screen 7 Screen 8


in °C and °F. STATOR PHASE B1 MAX TEMP SINCE
RTD #3: ### C = ### F CLEAR RTD #3: ### C
Screen 4: Displays the maximum temperature for
Screen 10
RTD #1 since the last command to clear the Screen 9
STATOR PHASE B2
thermal register. RTD #4: ### C = ### F
MAX TEMP SINCE
CLEAR RTD #4: ### C

Screen 5 - 26: Same as Screens 3 - 4 for RTDs #2-12. Screen 11 Screen 12


STATOR PHASE C1 MAX TEMP SINCE
Screen 27: Allows the user to clear the maximum RTD #5: ### C = ### F CLEAR RTD #5: ### C

temperature register upon entering the


Screen 13 Screen 14
setpoint level 3 password. STATOR PHASE C2 MAX TEMP SINCE
RTD #6: ### C = ### F CLEAR RTD #6: ### C
Screen 28: Displays the measured run cool time in
minutes. Screen 15 Screen 16
END BEARING MAX TEMP SINCE
RTD #7: ### C = ### F CLEAR RTD #7: ### C
Screen 29: Displays the measured stopped cool time in
minutes. Screen 17 Screen 18
SHAFT BEARING MAX TEMP SINCE
RTD #8: ### C = ### F CLEAR RTD #8: ### C

Screen 19 Screen 20
RTD #9 MAX TEMP SINCE
RTD #9: ### C = ### F CLEAR RTD #9: ### C

Screen 21 Screen 22
RTD #10 MAX TEMP SINCE
RTD #10: ### C = ### F CLEAR RTD #10: ### C

Screen 23 Screen 24
RTD #11 MAX TEMP SINCE
RTD #11: ### C = ### F CLEAR RTD #11: ### C

Screen 25 Screen 26
RTD #12 MAX TEMP SINCE
RTD #12: ### C = ### F CLEAR RTD #12: ### C

Screen 27
PRESS ENTER TO
CLEAR MAX TEMP REGS

Screen 28
MEASURED RUN COOL
TIME: ### MIN

Screen 29
MEASURED STOPPED
COOL TIME: ### MIN
JKSSS+ Series - 75

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MP.4 Status (Metering Page 4)


MENU
Displays the present status of the soft start.

Screen 1 (See note at left)
Screen 1: Displays the present state of the unit as METERING PAGE 4
(CURRENT STATUS)
follows: STATUS

Screen 1 Note: Screen 2


CURRENT STATUS Screens include: O/L TRIP LEFT TO
TRIP: ###### SEC
1. MOTOR STOPPED
READy TO START
Screen 3
2. MOTOR STARTING THERM INH TIME LEFT
MULT. OF FLA : #### MIN

3. MOTOR RUNNING
Screen 4
AT ###.## x FLA
COAST DOWN TIMER
4. LAST TRIP CAUSE TIME LEFT: #:## MIN
NONE (or trip cause)
Screen 5
5. PROGRAMMING
TIME BETWEEN STARTS
SETPOINTS TIME: #:## MIN
6. MOTOR STATUS
UNKNOWN STATE ### (displays relay state upon error) Screen 6
STARTS PER HOUR TIME
## ## ## ## ## ## ##
Screen 2: Displays the amount of time remaining before
an overload trip will occur.

Screen 3: Displays the amount of time remaining from


a thermal inhibit. The inhibit time comes from
the amount of thermal register remaining
versus the amount of thermal capacity
required to start.

Screen 4: Displays the coast down time remaining


(Backspin time). The time remaining depends
upon the user setting in Setpoint Page 8,
Coast Down Time.

Screen 5: Displays the amount of time remaining before


a start command can be given.

Screen 6: If the number of starts per hour has exceeded


the setting.

JKSSS+ Series - 76

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MP.5 Event Recorder - 60 Events (Metering Page 5)

MENU
Screen 1 Screen 1a Screen 1b
METERING PAGE 5 :<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
Event Recorder (60 event) 1st :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
2nd :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
59th :##/##/## ##:##
Event
IC: ###### G/F: #### Vca: ###### P/F: ####

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
60th :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

All events will be viewed from oldest event in buffer to most recent event.

The events are listed from oldest to most recent.


Screen 1: Displays the event (i.e. Imbalance Trip) with the
date and time it occurred.

Screen 1a: Displays the current of Phase A, B, C and the


ground fault at the time of the trip.

Screen 1b: Displays the Vab, Vbc, Vca and power factor at the
time of trip.

JKSSS+ Series - 77

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MP.6 Last Trip (Metering Page 6)


MENU
Displays the information regarding the last trip.
Screen 1
Screen 1: Displays the cause of the last trip.
METERING PAGE 6 (cause of trip)
LAST TRIP (value at time of trip)
Screen 2: Displays the measured phase current at the
time of the trip. Screen 2
Ia: #### Ib: ####
Screen 3: Displays the Vab, Vbc, Vca and power factor Ic: #### G/F: ####.#

at the time of trip.


Screen 3
Vab: ###### Vbc: ######
Screen 4: Displays the imbalance percentage, the Vca: ###### P/F: ######
frequency and the kW at the time of the trip.
Screen 4
Screen 5: Displays the hottest stator RTD temperature I/B: ## % Hz: ##.#
at time of the trip. KW: ########

Screen 5
Screen 6: Displays the hottest non-stator RTD HOTTEST STATOR
temperature at the time of the trip. RTD# # @ ### C

Screen 6
HOTTEST NON-STATOR
RTD# # @ ### C

JKSSS+ Series - 78

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

MENU
Screen 1
METERING PAGE 7 MWH TOTAL
STATISTICS : ###

Screen 2 Screen 3

MP.7 Statistics (Metering Page 7) RUNNING HOURS TOTAL PRESS ENTER TO


TIME: ## ## HOURS CLEAR RUN HOURS
Displays the statistical trip information.
Screen 1: Displays the total of megawatt hours. Screen 4
Screen 2: Displays the accumulated total running hours. TOTAL TRIPS: ###
S/C TRIPS: ###
Screen 3: Clears the total running hour count.
Screen 4: Displays the total number of trips since the Screen 5 Screen 18
last clearing the statistical data and the total START O/L TRIPS: ### U/V TRIPS: ###
number of short circuit trips. RUN O/L TRIPS: ### O/V TRIPS: ###

Screen 5: Displays the numbers of start overload and Screen 6 Screen 19


run overload trips since the last clearing of the FREQUENCY TRIPS: ###
POWER FACTOR
statistical data. I/B TRIPS: ### TRIPS: ###
Screen 6: Displays the number of frequency trips and
Screen 7
Imbalance trips. OVERCURRENT Screen 20
Screen 7: Displays the number of overcurrent trips. TRIPS: ### PHASE REVERSAL
TRIPS: ###
Screen 8: Displays the number of Stator and non-Stator
Screen 8
RTD Trips.
STATOR TRIPS: ### Screen 21
Screen 9: Displays the number of Ground Fault Hi and NON-STATOR TRIPS: ### EXT INP #1: ###
Lo Set trips.
Screen 10: Displays the number of acceleration time trips. Screen 9
G/F HISET TRIPS: ###
Screen 11: Displays the number of start under curve trips. G/F LOSET TRIPS: ###
Screen 22
Screen 12: Displays the number start over curve trips. EXT INP #2: ###

Screen 13: Displays the number of I2T start curve trips. Screen 10
Screen 14: Displays the number of learned start curve ACCELERATION TIME
Screen 23
TRIPS: ###
trips. EXT INP #3: ###
Screen 15: Displays the number of fail shunt trips. Screen 11
Screen 16: Displays the number of phase loss trips. START UNDER CURVE
Screen 24
TRIPS: ###
Screen 17: Displays the number of tachometer EXT INP #4: ###
acceleration trips. Screen 12
Screen 18: Displays the number of undervoltage and START OVER CURVE
Screen 25
overvoltage trips. TRIPS: ###
PRESS ENTER TO
Screen 19: Displays the number of power factor trips. CLEAR STATISTICS
Screen 13 LEVEL 2 Password required
Screen 20: Displays the number of phase reversal trips. I*I*T START CURVE
Screen 21: Displays the number of external input #1 trips. TRIPS: ###
Screen 22: Displays the number of external input #2 trips.
Screen 14
Screen 23: Displays the number of external input #3 trips. LEARNED START CURVE
Screen 24: Displays the number of external input #4 trips. TRIPS: ###

Screen 25: Requires a Security Level 2 password to clear


Screen 15
the statistics.
FAIL SHUNT TRIP
TRIPS: ###

Screen 16
PHASE LOSS TRIP
TRIPS: ###

Screen 17
TACH ACCEL TRIP
TRIPS: ###

JKSSS+ Series - 79

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Chapter 7 - Maintenance and Troubleshooting
The soft starter is designed to be a maintenance-free product. However, as with all electronic equipment, the
unit should be checked periodically for dirt, moisture or industrial contaminants. These can cause high voltage
arc-over, carbon tracking or prevent proper cooling of the SCR heat sinks. All bolts should be checked annu-
ally for proper tightness using an accurate torque wrench. According to the manufacturer’s manual, check the
contactor for air gap spacing of the vacuum bottles.

Note: If the unit is installed in a contaminated environment and forced air cooling is used, blower
filters must be checked and cleaned regularly to insure proper air flow and cooling of the enclosure.

7.1 - Failure Analysis


When a fault occurs, the LCD will display the fault error and the listed LED and AUX Relay will be lit.
Please clear all faults before attempting to restart the unit. Note: If the problem persists after the
required programming changes have been made, and all corrective action has been taken, please
contact the factory for assistance.

Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
One of the main Short circuit between the
fuses blows or inputs
Locate and remove short
circuit breaker
opens when the TCB FAULT TRIP Trip AUX1
Remove power and test SCR(s). Refer to
power is applied
Faulty SCRs Section 7.1.1 for the SCR testing
or disconnect is procedure
open
Short circuit or ground fault
Locate and remove short or ground
in motor/cabling
Phase Loss Repair cause of phase loss
Branch circuit protection Verify correct sizing of branch circuit
Short Circuit Trip SHORT CIRCUIT TRIP not correctly sized protection
Trip AUX1
Remove power and replace main circuit
Faulty main circuit board
board.
Remove power and test SCR(s). Refer to
Faulty SCRs Section 7.1.1 for the SCR testing
procedure
Single phase incoming
Correct problem with incoming power
SINGLE PHASE TRIP power
Single Phase Trip (Check LCD display for Trip AUX1
Remove power and test SCR(s). Refer to
possible fault indicators)
Faulty SCRs Section 7.1.1 for the SCR testing
procedure

If fans have power, remove power and


Fan(s) not functioning
replace fan(s). If fans do not have power,
(If supplied)
find cause of power loss and repair.

Remove power and clean heatsink with


Heatsink coated with dirt high pressure air (80 - 100 psi max clean
and dry air)

Thermostat trips EXTERNAL TRIP ON Verify that running current does not
Trip AUX1 Overcurrent on unit
during run THERMOSTAT exceed unit rating

Environment temperature
over 122° F (ambient
Place unit in environment temperature
temperature for chassis
less than 122°F for panel version or less
units) or over 104°F
than 104°F for enclosed version.
(ambient temperature for
enclosed version

Bypass failed to close Check bypass contactor and wiring

JKSSS+ Series - 80

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Aux
Proble m CPU LCD Displa y LED Possible Ca use Solutions
Re la y
Los s of 1 or m ore
phas es of power from Check power s ource
Phase Loss PHASE LOSS Trip AUX1
utility or generated power

Blown power fus es Check for s hort circuits


Check m otor nam eplate vers us
Im proper program m ing
program m ed param eters
Overload OVERLOAD TRIP Trip AUX1
Pos s ible load dam age or
Check m otor currents
jam m ed load

Im proper s etting for


Verify current lim it s etting
m otor load condition
Stall prevention ACCEL TIME TRIP Trip AUX1
Dam aged load Check for load failure

Im proper program m ing Check s etpoint s ettings


Wrong pos ition of
Check dis connect or open breaker
dis connected breaker
Under Voltage
UNDER VOLTAGE TRIP Trip AUX1 Main contactor failed to
Trip Check internal connections
clos e

Reduce current lim it s etting, s aturation


Trans form er too s m all
or s agging power s upply trans form er

Under Current Im proper program m ing Check s etpoint s ettings


UNDER CURRENT TRIP Trip AUX1
Trip
Unloaded m otor Check load

Failed CPU or Main Firing


Contact factory
Self-test Failure SELF-TEST FAILURE Trip AUX1 Board
Vibration Check internal wiring connections
Troubles hoot and repair generator
Contact utilities com pany
Line Frequency OVER OR UNDER Generator Power
Trip AUX1 Main board failure
Trip FREQUENCY TRIP Problem or grid change
Three phas e power rem oved from
Main Board
Im proper program m ing Check program s etpoints

Any wire going to ground


GROUND FAULT Check with m egger or Hi-pot m otor
Any Ground (I.e. s tator ground, m otor
HI-SET OR LO-SET Trip AUX1 leads and m otor
Fault Trip ground, s oft s tart ground)

High vibration or loos e


Check internal connections
connections

W arning: This is a s erious fault condition. Ens ure that the fault
condition is cleared on the load before attem pting to res tart the
m otor.
Motor stopped
Check for fault indication Trip AUX1
during run
Load s horted/ grounded/
Rem ove power and repair.
faulted
Faulty m ain circuit board Replace the m ain circuit board

Control circuit Rem ove power, locate and rem ove


Short in control circuit
fuses b low after this s hort
None None None
control power is
Apply the correct voltage to the control
applied. Wrong control voltage
circuit

JKSSS+ Series - 81

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
No control voltage applied Apply control voltage to TB1 pins 1 and 6
to control board on the power board

Control power transformer Remove power and replace the power


failure or CPT fuse failure transformer or the CPT fuse

Start circuit wired Remove power and correct the start


incorrectly circuit wiring

Any fault indication No start command Apply the start command


Motor will not start Trip AUX1
message No 3 phase line voltage Apply 3 phase line voltage to the unit

Remove power and test SCR(s). Refer to


Shorted SCR in starter Section 7.1.1 for the SCR testing
procedure

Remove power and repair the control


Faulty control logic
logic.

Failure of main circuit


Replace the main circuit board
board

Check the motor and the motor


Faulty motor
connections

Remove power and perform the SCR


Motor vibrates/ Faulty SCRs
Trip AUX1 device checks
Motor growls
while starting or IMBALANCE TRIP Remove power and test SCR(s). Refer to
extremely IMBALANCE ALARM Faulty gate/cathode on
Section 7.1.1 for the SCR testing
unbalanced motor SCRs
procedure
currents run mode
Faulty main circuit board Replace the main circuit board
Faulty motor/wiring Troubleshoot and repair/replace wiring
Alarm AUX2
Faulty main circuit board Replace the main circuit board

7.1.1 - SCR Testing Procedure


Perform the SCR Heat Sink Ohm test on each Stack Assembly.

Test To Perform Ohm Meter Reading Test Result


From Position A to Greater than 10K Ohm Pass
Position B Less than 10K Ohm Fail
C From Position B to Greater than 10K Ohm Pass
Position C Less than 10K Ohm Fail
Pass (Typical 8 to 20
Gate (G) to Cathode 8 to 100 Ohms
Ohms)
(K) for each SCR
B Less than 10 or greater than 100 Ohms Fail
Note: Allow 15 minutes after shutdown for DV/DT network to discharge DC
A voltage.
Gate Drive
Board

K = Cathode = Red Wire


G = Gate = White Wire
JKSSS+ Series - 82

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.2 - Typical Block Diagram

Voltage L1 L2 L3
Transformer

Ring
Transformer

Temp/ CT
3

1
Board
CT
Fiber Optics 4 3

1
2
CT
4
3

1
CT
4

2
A B C

Gate Drive Boards


CPU

DV/DT Boards
MOV Boards
Digital
Controller Main Fiber Optics
SCR Assembly
Firing Board

Control Board
Customer Connections T1 T2 T3

JKSSS+ Series - 83

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.3 - Overload Curve Definition

JKSSS+ Series - 84

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
Customer Provided

7.4 - TCB Diagram Momentary or Maintained


Start / Stop Switching
Maintained

START STOP
Fuses Momentary
F1: Control Fuses for TB1 1 - 9
Part #ACG1A250VAC or equivalent
F2: Contactor and relay output fuses
Part #ACG4A250VAC or equivalent
F3: TB2 Pin #6
Part #ACG4A250VAC or equivalent

12

NC
Aux Start
11

NO
E1 E2 E3 E4 Output
10

C
Red AC 120 VAC
9
LED Neut
Neutral
8
Start
FUSE
7
T1 Red TB1 6
Stop

LED
5
Inter
FAULT 4
Lock
Optional
3 Interlocks
Inter
Lock
2
1
AC 120 VAC
HEATSINK

Source
Source
F1 10

NC
9

NO
F2 8

C
HEATSINK
7
FACTORY WIRED

N
Green DO NOT USE
LED F3 6
120VAC { Line
Neutral
1
2 -12V
TB2
5 S
NC

3 Green
4 Emergency Bypass
NO

Delayed Start Green


LED LED 3 AUX Contacts
C

4
5 +12V
2 Emergency Bypass
C

Fuse Blown/ START


Disconnect Open TB6 1 Full Voltage Start
NO

6
7
Dual Ramp ON OFF 12
NC

8 JP1
SW1 11
NO

9 Remove JP1 for electronic 10


Bypass Status DUAL ADJ
Fault

motor overload protection


C

10 during emergency 9
NC

bypass operation
8
NO

1
Run 7
TCB
C

2 TB3 6
NC

3
Lock Out

CPU (AUX1) Fault


BOARD 5
NO

4 TB7 4
C

5
At Speed 3
NC

6
2
NO

7
1
C

Fuse Blown/
1 12
Disconnect
NC
AUX-S
DLY-S
PFC-C
DLY-C
PFC-S

AUX-C

Green
Interlock Input 2 LED 11
P.F.C. CAP
NO

3 10
TB8
C

External Overload PFC


4 TIMED 9
NC

7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1 OUT
5 8
NO

Bypass Aux Contact


6 7
C

PFC AUX START TB4


Bypass
{ A1 7 6
NC

Coil A2 8 5
NO

Time Delay

A1 4
Main
{ 9 Green
C

Coil LED 3
A2 10
NC

DELAY
2
NO

TIMED 1
C

OUT

JKSSS+ Series - 85

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.5 - Typical Wiring Diagram

JKSSS+ Series - 86

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

JKSSS+ Series - 87

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV
7.6 - Spare Parts List

Unit Voltage Quantity


Description Part Number
and Amp Rating Req./Unit
Current
Contact Factory Specify model number 3
Transformer
MVC3-STK23200 2300V, 200A 3
MVC3-STK23400 2300V, 400A 3
MVC3-STK23600 2300V, 600A 3
Heatsink
MVC3-STK41200 3300/4160V, 200A 3
Assembly with
MVC3-STK41400 3300/4160V, 400A 3
Boards
MVC3-STK41600 3300/4160V, 600A 3
(1 Phase)*
MVC3-STK72200 6000 - 7200V, 200A 3
MVC3-STK72400 6000 - 7200V, 400A 3
MVC3-STK72600 6000 - 7200V, 600A 3
25-0200-6500-23 2300V, 200A 3
25-0400-6500-23 2300V, 400A 3
25-0600-3500-23 2300V, 600A 3
SCR(s) Clamped 25-0200-6500-41 3300/4160V, 200A 3
in Heat Sink 25-0400-6500-41 3300/4160V, 400A 3
Alone 25-0600-3500-41 3300/4160V, 600A 3
25-0200-6500-72 6000 - 7200V, 200A 3
25-0400-6500-72 6000 - 7200V, 400A 3
25-0600-3500-72 6000 - 7200V, 600A 3
10-0090 2300V, 200A & 400A 3
10-0090 2300V, 600A 6
Gate Drive 10-0090 3300/4160V, 200A & 400A 6
Transfomer 10-0090 3300/4160V, 600A 12
10-0090 6000 - 7200V, 200A & 400A 9
10-0090 6000 - 7200V, 600A 9
Temperature &
MVC3-Temp/CT-PS All models 3
Current Board

PCB Mounting Order

DVDT MOV Gate Drive


Board Board Board

Temp CT
Board

JKSSS+ Series - 88

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

JKSSS+ Series - 89

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.7 - Instructions for Stack Replacement


For Reference Only

TEMP / CT Board
Gate Drive Board
MOV Board

DV/DT Board

PCB Mounting Order

DVDT MOV Gate Drive


Board Board Board

Temp CT
Board

JKSSS+ Series - 90

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.7 - Instructions for Stack Replacement

DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment prior
to working on it.

Failure to follow this instruction will result in death


or serious injury.

Note: All power sources must be removed and a waiting period of at


least 15 minutes must be observed before initiating any repairs to
the unit(s) because DC voltage may still be present immediately after
turning off power to the unit.
Note: It is good practice to disassemble and reassemble one stack at a
time so you can have an assembled and wired stack in the unit as a
reference.
Note: Toshiba recommends that the order include the SCR with the heat-
sink assembly at a minimum. Only an experienced technician should
attempt to replace the SCRs.

Tools:
• Phillips screwdriver
• 3/8” 12 point socket set
• 2 9/16” wrenches
• ½” wrench
• AC/DC Multimeter
• JKSSS+ manual (refer to drawings in this section)

Procedure:
1. Verify that no DC or AC voltage is present on any of the power compo-
nents.
2. Disconnect all four wires connected to TB1 positions 1-3 on the tempera-
ture CT board.
3. Disconnect the 4 red transformer wires on each of the gate drive boards.
These would be TB1, positions 3 and 5 for each gate drive board. Typically,
the 2300V unit will have only 4 wires per phase to disconnect, a 4160V unit
will have 8 wires per phase, and a 6000 - 7200V unit will have 12 wires per
phase. (Note: the 7200V/600A unit will also have 24 wires.)
4. Use the 9/16 wrench and carefully unbolt all of the line and load power con-
nections attached to the heat sinks. Note: If the unit is a 6000 - 7200V, re-
move the power strap connecting one side of the stack to the stack directly
below it.
5. Before removing the fiber optic wiring, make a note of the label on the
fiber cable to ensure they are placed exactly in the same socket they were
removed from. Now remove all fiber optic connectors on the stack. Gently
push on the connector tab and pull with a gentle left-to-right motion on the
connector in the direction away from the fiber optic device. Two connectors
will be found per gate drive board and one duplex connector will be found
on the small Temp/CT board on top. Caution: Do not touch the tip of the
connectors or contaminate the connection sockets with any dust or foreign
material.
6. Remove the wires from the Temp/CT board terminal block (3 screws).
7. Use a 9/16” socket with a 6” extension to remove the lower bolt that
routes through the front face of the heat sink and into the isolation standoff
mounted to the white panel. Then carefully hold the heat sink in place with
one hand and remove the top bolt from the heat sink.
8. Ensure the fiber optic connectors and all wires are positioned out of the
way, and then the heat sink can be gently removed from the unit.
JKSSS+ Series - 91

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

SCR Replacement:

FAILURE TO PERFORM THIS PROCEDURE


CORRECTLY WILL DAMAGE THE SCR AND
WILL NOT BE COVERED UNDER WARRANTY.

1. Remove white jumper wires on the gate drive board and make a note
of their placement.
2. Remove both 7/16 bolts and the singular 10 - 32 screw at the top of
gate drive board and lift off the board.
3. To remove the MOV board, remove the SCR gate/cathode leads (thin
red and white wires) and the white jumper wires attached to them.
Make a note as to how they were connected. Unbolt the ½” fasteners
as well.
4. At this point, all boards should now be removed from the aluminum
heat sink assembly.
5. Make a note (or drawing) of how each of the SCRs are oriented within
the heat sink. If factory supplied replacement SCRs and heatsinks are
used, the following steps are not required.
6. Loosen and carefully remove the ½” feed-through bolt and two black
springs that hold the assembly together and turn it on its side.
7. Remove the two (2) SCRs in the top layer, making certain to note that
the SCRs are not facing the same direction.
8. Remove the two (2) SCRs in the bottom layer, also making certain to
note that the SCRs are not facing the same direction.
9. Clean the heat sink surface area thoroughly and reapply some thermal
heat sink grease sparingly to the SCRs mating surfaces.
10. Please note that replacement SCRs are in matched sets of four and as
such, please try to keep the matched sets within the same phase.
11. Now, take any two SCRs from a set and place them on the heat sink in
the same direction as the old SCRs were, ensuring that the dimple in
the center of the SCR is properly placed onto the center pin of the heat
sink assembly. Place the next level of heat sink bar on the mounted
SCRs. Note: There is a difference in the heat sink bars. The center bar
has more holes drilled in it for mounting the circuit boards on it.
12. Now replace the other two (2) SCRs by repeating steps 10 and 11.
13. Next, carefully sandwich the SCRs and turn the stack over so the heat
sink bars are vertical and run the center bolt through the springs and
hand tighten the nut on the center bolt assembly.
14. Then make approximately 3 and ½ full revolutions on the nut to create
the appropriate amount of compression force. You can tell if there is
enough compression force applied to the heat sink by the fact that the
force needed to turn the nut will suddenly increase.
15. Finally, reinstall all boards in the same manner in which they were
removed.
16 Refer to drawing PCB for disassembling and reassembling the stack
assembly.

JKSSS+ Series - 92

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

Reinstallation:

1. Hold the rebuilt or new stack assembly in the vertical position with
the Temp/CT board on top (only the top stack assembly will have this
board in a multi-stack phase) and place the stack on the positioning
studs that protrude from the isolation standoffs.
2. While pressing on the stack to hold it on the positioning studs, place
the feed-through bolt through the heat sink and finger-tighten the top
bolt. Then repeat the process with the bottom feed-through bolt to
ensure the stack is held against the isolation standoffs.
3. After verifying no wires or fibers have been pinched between the stack
assembly and isolation standoffs, tighten the top bolt completely, then
repeat the process for the bottom bolt. Now the stack assembly should
be held firmly in place.
4. Using the 9/16” wrench reinstall the line and load power cables and
tighten.
5. If needed, refer to the appropriate drawing to reconnect red transformer
wires on each gate drive board. As an example, for the 4160V stack,
reattach TB4-1 to X3, TB4-3 to X4, TB1-3 to X2 and TB1-1 to X1. Verify
all X(#) wires are reconnected to their original position on the gate drive
boards. Otherwise the SCRs will misfire.
6. Reconnect thermostat wires on TB1 positions 2 and 3 of the Temp/CT
board.
7. Reconnect the main CT black wire to TB1-1. Then feed the white wire
through the board mounted CT and connect to TB1-1 on the Temp/
CT board. Please note that one each of the thick white wires from the
encapsulated CT must be connected with the Main CTs wiring.
8. Ensure the same fiber optic routing is used as before. If the fiber optic
wiring is positioned close to a heat source, (such as the 25-watt resis-
tors on the gate drive board) melting or distortion of the plastic fiber
may occur. Minimum distance is a ½ inch with a minimum bend radius
of 2 inches. All gate drive boards require 2 single connectors per board
and the Temp/CT connector is a duplex piece with a mating tab that
faces away from the stack. If the tab is broken off, refer to an adjacent
stack’s labels to see how the labels should be positioned when install-
ing a duplex connector with a broken tab. Again, caution should be
taken not to touch the fiber connector end or force it in with the tab
facing down.

JKSSS+ Series - 93

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.8 - Instructions for Low Voltage Test

DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment prior
to working on it.

Failure to follow this instruction will result in death


or serious injury.

Tools:
• Phillips screwdriver
• Medium voltage fuse pullers if available
• Two control power transformer (Test PT) 500 VA minimum
• 120Vac control power (Test plug)
• Low voltage motor strapped for the proper voltage (typically 5 HP or
less)
• Oscilloscope if available
• Wire jumper
• Test switch (single pole i.e. - light switch)

480 or 240 VAC 3 Phase Supply

DANGER Construct an open delta low


voltage source for powering
A B C
Ensure proper
HAZARDOUS VOLTAGE the MVC for low voltage testing phase sequence
Remove all medium voltage fuses to prevent back-
(Minimum of 500VA each) H2 H1 H1 H2
feeding transformers.
PTs
Failure to follow this instruction will result in death X1
or serious injury. X1
X2 X2
A B C
• Manual (reference drawing above) Low Voltage Panel
TB1 Terminal 1 TB1 Terminal 3 TB1 Terminal 5
Procedure: 120 VAC 3 Phase Output
1. Verify that no DC or AC voltage Connect to MVC3-MB (Main Firing Board)
is present on any of the power Caution: Remove the three phase transformer PT fuses and CPT fuses
components. on panel to prevent backfeed to the Medium Voltage
2. Verify setup of control power
transformers for the proper
voltage. If using 480Vac or 240Vac 3 phase verify transformers are
strapped for that voltage. See above drawing. Configure as an open
delta for 3 phase as shown in drawing.
3. Verify medium voltage disconnect is open and pull medium voltage
fuses including PT and CPT fuses.
4. Connect 3 phase power 480 or 240Vac to the down stream side of
the fuses. Do not connect to disconnect side of fuses. Depending on
the small test motor used will depend on what size cable or current
that is required. Also, connect the Primaries of the TEST PT in the
proper phase sequence of A-B-C.
5. Disconnect medium voltage motor.
6. Connect low voltage motor. (Typically 5 HP or less)
7. Connect a wire jumper between TB8 pins 1 and 2 on the TCB (con-
trol board) to bypass fuse blown and open disconnect fault. The
TCB is located in the low voltage compartment.
8. Install a switch on TB1 pins 1 and 8 on the TCB (control board) to
bypass all interlocks (TEST Switch).

JKSSS+ Series - 94

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

9. Verify or wire a 120Vac plug to the TEST plug supplied by the factory.
10. Remove all both power fuses on the medium voltage CPT (single
phase control power transformer), if present..
11. Remove 3 fuses from the medium voltage potential transformer (PT).
12. Verify the 120-volt test switch is in the “NORMAL” position.
13. Connect test power to test plug connector and place the 120-volt test
switch to the “TEST” position.
14. The keypad should be energized with the “Power LED,” Stop LED.
15. Close the temporary Start switch, which is connected to the control
board.
16. The Main Vacuum contactor should close and the keypad should
trip on “Under Voltage” Open temporary TEST switch and reset CPU
fault.
17. Connect the Secondary of the TEST PT to Panel TB1 positions 1 -
phase A, position 3- phase B, and position 5 - phase C on the main
firing board (JKSSS+-MB). It is physically located behind the low
voltage compartment door. (Screw terminal block)
18. Verify all connections are good and then energize the low voltage of
either 480 or 240 volt, three phases.
19. Use the multimeter on the AC scale and verify 3 phase 120Vac
(phase to phase) at TB1 pins 1, 3 and 5 of the main firing board.
20. If all 120Vac 3 phase is present then de-energize low voltage of 480
or 240Vac.
21. Re-energize the low voltage of 480 or 240Vac.
22. Now all test voltages should be present 480 or 240Vac and three
phase 120Vac (TEST PT) and 120Vac single phase for control
power.
23. Close the temporary Start switch and the test motor should spin up
smoothly.
24. Use the Multimeter on the AC scale and check (phase to phase)
voltages on T1, T2 and T3 motor leads. The voltages should be bal-
anced.
25. If the motor doesn’t spin up smoothly the soft starter is malfunction-
ing. Proceed to step 27 for troubleshooting.
26. If the motor starts and runs smoothly then repeat this procedure in
reverse to remove all test connect and reinstall all fuses.

Low Voltage Troubleshooting:


Tools: Ungrounded Oscilloscope
27. Open test switch and stop motor.
28. Change Setpoint Page 5 AUX4 is set at non-fail safe. Change it to fail
safe.
29. Observe bypass contactor closes immediately.
30. Place the Oscilloscope on the 2msec time scale and 1 Volt per
division.
31. Connect the Oscilloscope probe to the Gate and Cathode of the
SCRs.

JKSSS+ Series - 95

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

32. The gate and cathode leads are the white wires on the gate drive
board in the medium voltage cabinet. See drawing below.
33. If waveform is inverted, swap Oscilloscope connections for proper
polarity. Close the temporary Start switch and allow the test motor to
reach full speed.
34. Then verify all gating signals to each SCR (two gating signals on
every gate drive board). See drawing below for correct waveform.
35. Once the bad signal(s) are found; write down the location and call
the factory for further guidance.

Waveform is
the gating signal as
measured with an
ungrounded oscilloscope
at the gate to cathode
of the SCR. The
waveform should be 1.7
to 2msec off time and
approximately 1.5 to
3 Vdc. This signal is only
present at full conduction
or the motor is at speed.
Each SCR gating signal
should be checked
in accordance with the
low voltage test procedure.

JKSSS+ Series - 96

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

7.9 - Maintenance Program/Servicing Equipment/Disposal/Storage

MAINTENANCE PROGRAM

In order to ensure continued reliable and safe operation of the equipment, a


program of periodic maintenance must be established. Operating and environmental
conditions will usually dictate the frequency of inspection required. NFPA Publication
70B “Electrical Equipment Maintenance” may be used as a guide for setting up the
maintenance program.

Contact with energized components can cause severe injury, death and
property damage. Turn off and lock-out primary and control circuit power
before servicing.

Improper maintenance can cause severe injury, death and property


damage. Only qualified and authorized persons are to install, operate or
service this equipment.

Grease is conductive. Do not allow grease or any other substances to


contaminate insulating materials. Contaminated insulators can allow a
short-circuit or ground fault to occur.

NOTE: Refer to the SAFETY section of this manual for important


information.

MAINTENANCE RECORD

Keep a permanent record of all maintenance work. At a minimum, this record should
include information on:

1) Items inspected
2) Reports of any testing
3) Equipment condition
4) Corrective actions or adjustments
5) Date of work
6) Comments

The degree of detail of the record will depend somewhat on the operating
conditions.

SERVICING EQUIPMENT

For your safety, turn off and lock out main and control circuit power before servicing
the starter. Certain minimum safety procedures must be followed:

1) Only qualified personnel should attempt this service.

2) Never perform service on or next to exposed components energized with line


voltage.

Failure to adhere to these safety procedures can result in severe injury,


death and property damage.

JKSSS+ Series - 97

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

DISPOSAL

Contact your state environmental agency for details on disposal of electrical


components and packaging in your particular area.

STORAGE

If the starter is to be stored for any length of time prior to installation, the
following precautions should be taken:

1) The original packing should be restored, if possible.

2) Do not subject the equipment to moisture or sun rays. Store in cool, clean,
and dry location.

3) Place a dust cover over the starter packaging to protect against dirt and
moisture.

4) Store in an upright position.

INSPECTION DURING STORAGE

Routine scheduled inspection is necessary if storage is for an extended


period. The unit should be checked for condensation, moisture, corrosion,
and vermin.

Prior to installation, the starter should be carefully examined for evidence of


physical damage, corrosion, or other deterioration.

The MAINTENANCE section of this manual describes various types of


inspections recommended for this starter during the operation period.

JKSSS+ Series - 98

Downloaded from www.Manualslib.com manuals search engine


JKSSS+ Series 2.3 - 4.2KV

WARRANTY AND LIMITATION OF LIABILITY

Toshiba International Corporation (“Company”) warrants that all equipment and parts described herein will be free from
defects in materials and workmanship. THIS WARRANTY WILL EXPIRE TWENTY-FOUR (24) MONTHS AFTER SUCH
EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED
PURSUANT TO THIS WARRANTY) ARE PLACED IN OPERATION OR THIRTY (30) MONTHS AFTER THE DATE ON
WHICH SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS
FURNISHED PURSUANT TO THIS WARRANTY) ARE SHIPPED TO THE INITIAL PURCHASER, WHICHEVER PERIOD
FIRST EXPIRES. THERE ARE NO OTHER WARRANTIES WHETHER EXPRESS, IMPLIED, STATUTORY OR OTHER-
WISE, INCLUDING THE IMPLIED WARRANTIES OR MERCHANTABILITYAND FITNESS FOR A PARTICULAR PURPOSE.

The Company will, at its option, repair or replace or refund the purchase price paid for such equipment or part
which is defective under the terms of the foregoing warranty, free of charge; provided the purchaser (1) promptly
notifies the Company in writing of such defect, and (2) furnishes the Company satisfactory proof thereof, and (3)
establishes that the equipment or part has been properly installed, maintained and operated within the limits of rated
capacity and normal usage and in accordance with current operating and maintenance instructions , and (4) has
not been altered or modified in any manner without the written consent of the Company, and (5) if requested by the
Company, returns the defective equipment or part to the Company and pays all expenses incurred in connection
with such return. The repaired or replacement equipment or part will be delivered, free of charge, to the purchaser
F.O.B. the Company’s warehouse or, at the Company’s option, F.O.B. a Company authorized service shop, not
loaded on truck or other carrier. The purchaser will pay the costs applicable to the equipment or part following such
delivery, including, without limitation, all handling, transportation assembly, insurance, testing and inspection charges.

THE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL BE THE SOLE AND
EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USERS OF THE EQUIPMENT AND
PARTS FOR BREACH OF THE FOREGOING WARRANTY. THE COMPANY WILL HAVE NO OBLIGATIONS TO
DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE
WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COSTS
INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. THE COMPANY, TOSHIBA
CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTORS HEREBY DISCLAIM ALL OTHER EXPRESS,
STATUTORY AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, ALL EXPRESS, STATUTORY AND
IMPLIED WARRANTIES, SUCH AS MERCHANTIBILITY AND FITNESS FOR A PARTICULAR PURPOSE APPLICABLE TO
ALL REPAIRED OR REPLACED EQUIPMENT AND PARTS FURNISHED PURSUANT TO THE FOREGOING WARRANTY.

The total liability of the Company, Toshiba Corporation and their suppliers and subcontractors for any loss, damage or
claim, whether in contact, tort (including negligence and liability without fault), or otherwise, arising out of, connected
with or resulting from the equipment and parts described herein or the performance or breach of any contract for the
sale or supply of such equipment and parts, or from the design, manufacture, sale delivery, resale, installation, technical
direction or supervision of installation, inspection, testing, repair, replacement, operation, maintenance or use of any such
equipment or part or any service relating thereto furnished by the Company shall not in any event exceed the price
allocable to the equipment, part or service which gives claim, loss or damage. In no event, whether as a breach of
contract or warranty, alleged negligence, liability without fault, or otherwise, shall the Company, Toshiba Corporation or their
suppliers or subcontractors be liable for indirect, incidental, special or consequential damages, including, without limitation,
property damage, loss of profits or revenue, loss of information or data, loss of equipment described herein or any associated
equipment, cost of capital, cost of substitute equipment or parts, facilities or services, down-time costs, labor costs or claims
of customers of the purchaser for such damages, even if Company has been advised of the possibility of such damages.

Purchaser shall provide this Limited Warranty and Limitation of Liability to its customers and users of the equipment and
parts described herein prior to any sale to or use of the equipment and parts by such customer or user. Company does
not authorize anyone to make any representations or warranties other than the express warranties contained herein.

JKSSS+ Series - 99

Downloaded from www.Manualslib.com manuals search engine


TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 West Little York Rd., Houston, Texas 77041
Tel 713-466-0277 Fax 713-466-8773
US 800-231-1412 Can 800-872-2192
Mex 95-800-527-1204
World Wide Web http://www.toshiba.com/ind

Downloaded from www.Manualslib.com manuals search engine

You might also like