TECHNICAL DATA VO0250SWD

GENSET SPECIFICATIONS
Prime Power (PRP) 250 KVA 200 kW
Stand-by (LTP) 275 kVA 220 kW
Power factor (cosphì) 0,8
Voltage 400/230 V
Frequency 50 Hz
ENGINE SPECIFICATIONS
Brand VOLVO PENTA
Type TAD 734 GE
Net engine power prime 213 kW
Net engine power stand-by 238 kW
Aspiration TCA
Cycle diesel 4 stroke
Cooling water
Speed 1500 r.p.m.
Cylinders 6L
Bore x stroke 108 x 130 mm
Displacement 7,15 l

This data sheet is not a contractually binding document, Ausonia S.r.l. reserves the right to modify the data without prior notice, due to the constant updating of the product
Fuel consumption 75% prime power 42 l/h +/- 5%
Oil consumption 0,1% of fuel consumption
Oil sump capacity 29 l
Coolant system capacity (engine & radiator) 32 l
Standard voltage 24 V
Governor type electronic
ALTERNATOR SPECIFICATIONS
Power (PRP) 250 kVA
Overload 10% for 1 hour
Voltage 400/230 V
Frequency 50 Hz
Speed 1500 r.p.m.
Temperature rise H
Insulation class H
Degree of protection IP 23
STANDARD EQUIPMENT
Starting motor and alternator battery charger
Dry air filter with removable element
Radiator mounted on skidbase
Water preheating system
Protection for fan and moving parts
Exhaust gas silencer
Built-in fuel tank 120 l
First filling oil
Skidbase with antivibrating shock-absorbers
Lead type batteries with cables and tray
Lifting devices
4-pole circuit breaker in fixed configuration, manual control
VO0250SWD_50_TECH_DATA_REV.1_eng

Rating according ISO 8528

Prime Power (PRP) Limited-Time Running Power (LTP)


It is defined as being the maximum power which a generating set is capable It is defined as the maximum power available, under the agreed operating
of delivering continuously whilst supplying a variable electrical load when conditions, for which the generating set is capable of delivering for up to 500 h
operated for an unlimited number of hours per year under the agreed of operation per year (of which no more than 300 for continuative use) with the
operating conditions with the maintenance intervals and procedures being maintenance intervals and procedures being carried out as prescribed by the
carried out as prescribed by the manufacturer. The permissible average manufacturers. No overload capability is available.
power output over 24 h of operation shall not exceed 70% of the prime power.
A 10% overload capacity is available for a period of 1 hour within a 12-hour
period of operation.

Ausonia S.r.l. - Via Favara 452/I, 91025 Marsala (TP), Italy - T +39 0923 722311 - F +39 0923 721274 - ausonia@ausonia.net - www.ausonia.net
OUR ENERGY, YOUR POWER

TECHNICAL DATA VO0250SWD

CONTROL PANEL
Genset control with automatic management of load transfer DG/Mains
Controller with thresholds, counters, alarm, status
LCD display with pushbutton access for monitoring electrical and mechanical parameters
Advanced programmable I/O functions
Multilanguages text for measurements setting and messages
Remote communication interface
List of events
Static battery charger
SOUNDPROOFED CANOPY
Highly corrosionproof
Electrogalvanized steel structure with modular components
Antianimal protection grid (air intake)
Exhaust silencer with rain flap
Insulation with material in fire reaction class A1
Doors with yale type key
Emergency stop
Easy connections for cables installation

This data sheet is not a contractually binding document, Ausonia S.r.l. reserves the right to modify the data without prior notice, due to the constant updating of the product
AVAILABLE OPTIONS
Different soundproofing levels for canopied gensets
Solutions for arctic or hot environment
A wide selection of genset controllers and synch panels
Additional alarms (warning / shutdown)
Extended fuel tank capacity
Automatic refuelling kit
Automatic transfer switch panel (ATS)
Residential Silencer (for open set only)
Leak proof tray
Special tools

DIMENSIONS AND WEIGHTS


Open set on skid base LxWxH: mm 2600x1620x1690 Dry: kg 2200
Soundproofed canopy Silent version LxWxH: mm 3600x1620x1950 Dry: kg 2800 VO0250SWD_50_TECH_DATA_REV.1_eng