Specifications
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA maximum
EOL resistance: 47K Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Temperature Range: 32˚ to 120˚ F (0˚ to 49˚ C)
Humidity: 10 to 93% noncondensing
Dimensions: 1.3″ H x 2.75″ W x 0.5″ D
Wire length: 6″ minimum
Before Installing 3. Install the specified EOL resistor value to terminate the
This information is included as a quick reference instal- initiating loop.
lation guide. Refer to the control panel installation man- 4. Set the address on the module per job drawings.
ual for detailed system information. If the modules will Note: Some panels support extended addressing. In or-
be installed in an existing operational system, inform the der to set the module above address 99 on compatible
operator and local authority that the system will be tempo- systems, carefully remove the stop on the upper rotary
rarily out of service. Disconnect power to the control panel switch with thumb in the direction shown in Figure 1.
before installing the modules. 5. Install the module in the desired mounting location.
NOTICE: This manual should be left with the owner/user Figure 1. Removing rotary switch stop:
of this equipment.
General Description
The FMM-101 monitor module can be installed in a single
gang junction box directly behind the monitored unit. Its
13
14
12 1
15
1 0 9
12
rigid mounting (see Figure 1). The FMM-101 is intended for
AD
3
8 NS
DR
TE
ES
5
6
S
LO
OP
systems. A78-1712-07
(+) TO
Mounting and Wiring (–)
NEXT
DEVICE
NOTE: This module is intended to be wired and mounted
BLACK
RED
3 12 3
VIOLET
2 13 2
1 0 15 14 10
1. Connect the red (+) and black (–) wires to the positive
and negative loop power leads of the signaling line circuit
(SLC). ALL WIRING SHOWN
IS SUPERVISED
2. Connect the violet (+) and yellow (–) wires to a two-
AND POWER LIMITED
wire, normally open initiating loop. 47k EOL
INCLUDED
A78-1937-04
N500-50-00 1 I56-1173-04