Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

CTS MDS 10 23 Rev0 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Ref: CTS-MDS-10-23-Rev0

set-- air cooled


TRANSFORMER RECTIFIER - Tap set

CTS Transformer Rectifiers are custom built to meet the diverse standards and specifications of the
cathodic protection industry across the globe. CTS can provide different types of Transformer Rectifiers
Transformer Rectifiers for Cathodic Protection of: pipelines, tank bottoms, tank internals, buried vessels, offshore structures, concrete reinforcement, Submerge metallic structures

such as tap set, variac, and phase control.

Each type of Transformer Rectifier can be provided with different types of cooling, enclosure etc.

This data sheet covers the specific details for tap set control air cooled units.

Enclosures can be constructed in a variety of materials and finishes. Standard enclosures are constructed
using steel sheet with rating conforming to IP55. Our standard enclosure is coated with a metallic zinc
flame spray, epoxy seal coat, polyurethane top coat in colour RAL 7036 gloss. However, almost any spec-
ification of material, coating or IP rating can be accommodated. Enclosures are fitted with galva-
nized sunshade for outdoor installations, lifting hooks and earth stud. Transformer Rectifiers are suitable
for indoor/outdoor plinth mounting. Smaller units can be post or wall mounted.
 Single phase input: 115, 220,
230, 415, 480 VAC, 50 / 60 Enclosure - Air cooled Transformer Rectifier enclosure comprises of single housing which accommodates
Hz cycles a.c. and d.c. terminals, instruments and breaker.

Operation - Tap set Transformer Rectifiers convert utility supply to the required d.c. output in the
 Three phase input: 208, 380,
following stages:
415, 480 VAC, 50/ 60 Hz
cycles  Voltage is stepped down using multi tap isolation transformer.
 Output current range:
 Transformer taps are selected using rotary switches or link bars.
3A-75A DC
 Rectification is achieved using full wave diode bridge assembly.


Power Supplies & Remote Monitoring


Output voltage range:
12V-100V DC  DC output voltage filtering (smoothing) is achieved with a choke and capacitor.
 Control: Tap switch, link bar Safety/Protection – AC input breaker is provided for over load and short circuit protection. Lightning
arrestor is provided on the input side and surge arrestor is provided on the output side. High speed fuses
 Over load and short circuit are provided on the transformer secondary.
protection: MCB and high
Instrument panel – The front instrument panel houses rotary switches, circuit breaker, d.c. voltmeter
speed HRC secondary fuses
and d.c. ammeter. A voltmeter with reference electrode selector switch can be offered to monitor
 Meters: 2% accuracy analog structure potential.
voltmeters and ammeters. Control– Constant voltage control is obtainable in 16, 24, 36 or 64 steps using rotary switches.
Options include potential
meter, LED and LCD displays Output ripple - Ripple is less than 5% of RMS voltage from 10% to 100% of rated output.

Transformer -Transformers are open dry type built to class F insulation with temperature limited to
 Standard enclosure: 2 mm
class B.
min thick carbon steel
housing. Options include hot Efficiency - Transformer efficiency is around 95%. Total efficiency is variable depending on Transformer
dipped galvanized, stainless Rectifier type and features but is usually greater than 80%.
steel, aluminium, GRP
Zone classification - Transformer Rectifiers can be manufactured to hazardous area classification. SIRA
 IP Rating: conforming to IP55 certification can also be provided.
up to IP65 Remote Monitoring - Remote monitoring can be offered using 4-20mA output from transducers. Digital
monitoring using RS485 network can be offered and requires a master control unit. Alarm signals can be
 Operating ambient:
offered using potential free contacts.
Continuously rated up to
550 C

 Optional Remote monitoring:


4-20mA transducer, RS485
digital via microcontroller,
potential free contacts

enquirieseu@ctsonline.com www.ctsonline.com
Azerbaijan | Bahrain | Georgia | India | Kingdom of Saudi Arabia | Qatar | United Arab Emirates | United Kingdom
Ref: CTS-MDS-10-23-Rev0

TRANSFORMER RECTIFIER - Typical schematic for tap set control

Single phase input

TAP L
SWITCH (+)
TR E
D
CB LA1 COARSE FS
C D1 D2
TAP

DC Output
L1 B
+ +
AC Input

A
MOV1 MOV2 C R V LA2
2
1
- -
3 FINE
L2
4
TAP
-A+
5
GND D3 D4
(-)
SH

Chassis
Ground

Power Supplies & Remote Monitoring


Three phase input

TAP
SWITCH

TR D E

C COURSE
TAP
B

1
2

FINE
CB LA1 3
TAP
4
L1
5
(+)
FS1
E D1 D3 D5
D
AC Input

L2 C COURSE

DC Output
TAP MOV2
MOV1
B

A FS2 +
MOV4 V LA2
L3 2
1
-
FINE
GND 3 MOV3
TAP
4
5
FS3 D2 D4 D6 -A+
Chassis
Ground
(-)
E SH
D

C COURSE
TAP
B

1
2

FINE
3
TAP
4
5

Detailed design and GA drawings will be provided for approval after order is placed

enquirieseu@ctsonline.com www.ctsonline.com
Azerbaijan | Bahrain | Georgia | India | Kingdom of Saudi Arabia | Qatar | United Arab Emirates | United Kingdom

You might also like