C Pid3 009
C Pid3 009
C Pid3 009
0
Function Block Library ILS_CEM
Function Description Edition 09/13
Danger
! indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
! indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
! with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.
Attention
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used.
A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation
of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this
documentation qualified persons are defined as persons who are authorized to commission, ground and label devices,
systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes
could violate the rights of the owner.
Siemens AG
Automation and Drives Siemens AG 2005
Postfach 4848, 90327 Nuremberg, Germany Technical data subject to change.
Siemens Aktiengesellschaft
Reference Manual Objects PID with 3 Parameter sets C_PID3
Description of C_PID3 4
Type/Number 4
Calling OBs 4
Function 4
Input interfaces 6
Process values 7
Interfaces to OS 8
Variable details 9
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
PID with 3 Parameter sets C_PID3 Reference Manual Objects
Description of C_PID3
Type/Number
Module name: C_PID3
Module no.: FB1018
Calling OBs
C_PID3 must be called in a Time-OB e.g. OB35.
Function
The C_PID3 calls inside the standard controller FB61 CTRL_PID. The improved block C_PID3
can handle 3 several sets of controller settings for (GAIN, TI, TD). With 3 binary inputs one can
enable one set of controller settings (1-3).
The presetting is parameter set 1. If there are more than one set are enabled, the set with the
lower number is active. If there are no set enabled then the parameter set 1 is active.
At the diagnosis faceplate the active parameter set is marked with a green frame. Look at the
following picture.
Recommendation:
If there is no need for a controller with 3 several settings use the standard controller
FB61 CTRL_PID because the FB1018 needs more performance.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
Reference Manual Objects PID with 3 Parameter sets C_PID3
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
PID with 3 Parameter sets C_PID3 Reference Manual Objects
Input interfaces
The additional parameters are described only.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
Reference Manual Objects PID with 3 Parameter sets C_PID3
Process values
The process values can be set during engineering and they can be changed online from the
OS. To permit the modification of the process values from the faceplates, they must not be
connected in the CFC.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
PID with 3 Parameter sets C_PID3 Reference Manual Objects
Interfaces to OS
STATUS Statusword to OS
Format DWORD
Interface to OS
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_PID3_009.doc
Reference Manual Objects PID with 3 Parameter sets C_PID3
Variable details
Internal structure of the Visualization status:
STA_B30 8
STA_B31 9
STA_B32 10
STA_B33 11
STA_B34 12
STA_B35 13
STA_B36 14
STA_B37 15
STA_B10 24
STA_B11 25
STA_B12 26
STA_B13 27
STA_B14 28
STA_B15 29
STA_B16 30
STA_B17 31